Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:31:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1981.51 | 397.72 | 397.72 |
Net Site Energy | 1981.51 | 397.72 | 397.72 |
Total Source Energy | 6039.65 | 1212.25 | 1212.25 |
Net Source Energy | 6039.65 | 1212.25 | 1212.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 2.09 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 701.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1868.31 | 113.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 2.09 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 701.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 113.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 2.09 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 701.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 96.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 113.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 160.61 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 375.00 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 160.61 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 375.00 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1868.309 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1868.309 | 100.00 |
Total On-Site and Utility Electric Sources | 1868.309 | 100.00 |
Total Electricity End Uses | 1868.309 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 18.33 |
Time Setpoint Not Met During Occupied Cooling | 454.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1538.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-15:30 | 04-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 24-JAN-12:09 |
Heating | 0.00 | 1505.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82384.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14195.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8595.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 165180.87 | 10100.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 1505.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 82384.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14195.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8595.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 6.63 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2222.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 951.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 304.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5916.94 | 122.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 446.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1187.62 | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 446.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1187.62 | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.91 | 0.257834 | 0.268000 | 0.779003 | 0.687558 | 0.500000 | 0.001478 |
CORE_MID VAV BOX COMPONENT | 2.16 | 0.347324 | 0.348000 | 0.750914 | 0.926197 | 0.500000 | 0.001097 |
CORE_TOP VAV BOX COMPONENT | 2.33 | 0.321315 | 0.336000 | 0.783707 | 0.856840 | 0.500000 | 0.001186 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.740964 | 0.213224 | 0.223000 | 0.165235 | 0.568599 | 0.500000 | 0.001787 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.705785 | 0.141717 | 0.200000 | 0.141157 | 0.377912 | 0.500000 | 0.002688 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.758722 | 0.208234 | 0.218000 | 0.165401 | 0.555291 | 0.500000 | 0.001830 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.800874 | 0.124883 | 0.200000 | 0.160175 | 0.333020 | 0.500000 | 0.003051 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.626058 | 0.252359 | 0.263000 | 0.164653 | 0.672959 | 0.500000 | 0.001510 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.625699 | 0.159856 | 0.200000 | 0.125140 | 0.426283 | 0.500000 | 0.002383 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.635782 | 0.248500 | 0.259000 | 0.164668 | 0.662666 | 0.500000 | 0.001533 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.662221 | 0.151030 | 0.200000 | 0.132444 | 0.402747 | 0.500000 | 0.002523 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.645564 | 0.244734 | 0.245000 | 0.158163 | 0.652625 | 0.500000 | 0.001557 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.678051 | 0.147514 | 0.200000 | 0.135610 | 0.393370 | 0.500000 | 0.002583 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.656976 | 0.240483 | 0.241000 | 0.158331 | 0.641288 | 0.500000 | 0.001584 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.725789 | 0.137802 | 0.200000 | 0.145158 | 0.367472 | 0.500000 | 0.002765 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25987.05 |
CORE_MID VAV BOX REHEAT COIL | 25049.99 |
CORE_TOP VAV BOX REHEAT COIL | 26143.95 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 10464.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 6845.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 10444.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 6852.70 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6627.58 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4386.12 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6593.83 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4418.25 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8238.12 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5426.21 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8199.62 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5445.41 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.73 | 1.37 | 5.46 | 1.37 | 4.97 | 4.97 | 0.300000 | 0.274659 | 4.97 |
PACU_VAV_MID | 2.43 | 1.35 | 4.86 | 1.35 | 4.32 | 4.32 | 0.300000 | 0.312381 | 4.32 |
PACU_VAV_TOP | 2.67 | 1.42 | 5.34 | 1.85 | 5.07 | 5.07 | 0.300000 | 0.364389 | 5.07 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.97 |
PACU_VAV_MID_OA_CONTROLLER | 4.32 |
PACU_VAV_TOP_OA_CONTROLLER | 5.07 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.97 | 120877.38 | 0.708388 | 1.66 | 40288.43 | 0.708388 |
PACU_VAV_MID COOLING COIL | 4.32 | 107171.85 | 0.701083 | 1.44 | 35720.38 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 5.07 | 122316.77 | 0.710196 | 1.69 | 40768.18 | 0.710196 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 3024.98 |
PACU_VAV_MID HEATING COIL | 4976.38 |
PACU_VAV_TOP HEATING COIL | 2697.30 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.97 |
PACU_VAV_MID FAN | 4.32 |
PACU_VAV_TOP FAN | 5.07 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2430E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2816E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5513E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5832E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0952E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1195E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8128E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7132E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5844E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8594E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1994E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7391E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2446E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2915E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5531E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5940E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0971E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1281E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8421E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7183E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5486E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4909E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6288E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2786E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4032E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4180E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1752E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1859E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9731E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9772E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8262E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8624E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4028E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4318E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0970E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1175E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5772E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4440E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0150E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1155E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8150E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.6976E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8257E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8616E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4019E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4296E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0954E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1115E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8750E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2864E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3980E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9772E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6527E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8452E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7706E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7988E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4152E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4427E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3641E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3800E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.2824E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.7035E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1001 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.8981E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.7833E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.5721E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6921E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6309E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4166E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4135E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5245E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2155E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9695E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9207E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3682E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5318E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1628E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1500E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7533E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2188E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2999E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9237E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5760E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8012E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.2819E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.7030E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1001 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.8976E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.7826E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5717E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6920E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6307E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4164E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4133E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5242E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2153E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9696E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9206E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3683E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5317E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1626E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1499E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7533E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2187E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2999E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9236E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5757E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8010E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40291.99188 | 40291.99188 | 2.90673 | 2.90673 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3119.67653 | 3119.67653 | 0.13232 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29944.51602 | 29944.51602 | 2.15780 | 2.15780 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 9479.56452 | 9479.56452 | 0.39975 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32064.79216 | 32064.79216 | 2.33246 | 2.33246 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 17615.66882 | 17615.66882 | 0.74733 | 0.74733 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10184.94065 | 10184.94065 | 0.74096 | 0.74096 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8015.67311 | 8015.67311 | 0.31369 | 0.31369 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9701.40254 | 9701.40254 | 0.70579 | 0.70579 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5238.87381 | 5238.87381 | 0.20521 | 0.20521 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10429.02536 | 10429.02536 | 0.75872 | 0.75872 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8000.46723 | 8000.46723 | 0.31308 | 0.31308 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11008.48878 | 11008.48878 | 0.80087 | 0.80087 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5244.00446 | 5244.00446 | 0.20542 | 0.20542 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8605.99257 | 8605.99257 | 0.62606 | 0.62606 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 4672.71493 | 4672.71493 | 0.19867 | 0.19867 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8601.10342 | 8601.10342 | 0.62570 | 0.62570 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3091.36526 | 3091.36526 | 0.13148 | 0.13148 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8739.66494 | 8739.66494 | 0.63578 | 0.63578 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 4649.10647 | 4649.10647 | 0.19766 | 0.19766 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9103.15259 | 9103.15259 | 0.66222 | 0.66222 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.03867 | 1.71650E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3106.91260 | 3106.91260 | 0.13215 | 0.13215 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8873.77371 | 8873.77371 | 0.64556 | 0.64556 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5800.61690 | 5800.61690 | 0.24695 | 0.24695 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9320.37560 | 9320.37560 | 0.67805 | 0.67805 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3819.95777 | 3819.95777 | 0.16266 | 0.16266 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9030.64400 | 9030.64400 | 0.65698 | 0.65698 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5773.65278 | 5773.65278 | 0.24580 | 0.24580 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9976.58349 | 9976.58349 | 0.72579 | 0.72579 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3833.40256 | 3833.40256 | 0.16323 | 0.16323 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 80123.90 | 4.97310 | 4.97310 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 5374.65 | 1.08465 | 1.08465 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70969.42 | 4.31581 | 4.31581 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 5904.33 | 1.24333 | 1.24333 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 81312.91 | 5.06864 | 5.06864 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 5921.26 | 1.84696 | 1.84696 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.90673 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25783 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68756 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47769E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25987.05293 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15780 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34732 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75091 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92620 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09696E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25049.99306 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33246 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32132 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78371 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85684 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18575E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26143.94792 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74096 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21322 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16523 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56860 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78685E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10464.49772 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70579 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14172 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14116 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37791 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68846E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6845.72060 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75872 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20823 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21800 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16540 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55529 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82967E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10444.01449 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80087 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12488 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16017 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33302 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05086E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6852.70244 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62606 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25236 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16465 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67296 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50975E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6627.57935 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62570 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15986 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12514 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42628 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38340E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4386.11539 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63578 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24850 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16467 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66267 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53320E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6593.82691 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66222 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15103 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13244 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40275 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52268E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4418.25054 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64556 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24473 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15816 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65262 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55679E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8238.12481 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67805 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14751 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13561 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39337 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58281E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5426.20814 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65698 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24048 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15833 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64129 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58431E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8199.62041 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72579 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13780 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14516 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36747 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76483E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5445.40717 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72824 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36591 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.45649 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36591 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.97310 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.97310 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27466 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.43209 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34818 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.86418 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34818 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.31581 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.31581 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31238 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.66940 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41567 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.33881 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.84696 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06864 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.06864 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.36439 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.97310 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.31581 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.06864 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.97310 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.97310 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120877.38433 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70839 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65753 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40288.43220 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70839 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 3024.97722 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.97310 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.31581 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.31581 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107171.85315 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.43846 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35720.37865 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 4976.37823 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.31581 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06864 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06864 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 122316.76812 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71020 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68938 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40768.17882 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71020 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 2697.30397 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.06864 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 120598.48 | 411499.10 | 11.61 | 2.96 | 3.33 | 3.51 | 3.63 | 10.11 | 11.35 | 11.98 | 12.40 | 5.7451 | 4.5619 | 3.0694 | 1.3102 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 106996.81 | 365088.29 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 4.9858 | 3.9467 | 2.6559 | 1.1452 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 122006.45 | 416303.30 | 11.59 | 2.96 | 3.32 | 3.51 | 3.63 | 10.11 | 11.34 | 11.96 | 12.39 | 5.8555 | 4.6468 | 3.1233 | 1.3340 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2139032029 | 0.2683741017 | Pass | Pass | 0.2383558073 | 0.4241316482 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8137054775E-002 | 0.1095565844 | Pass | Pass | 0.3085341085 | 1.1700064680 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0634708792E-002 | 5.2686049048E-002 | Pass | Pass | 0.4328900829 | 2.6923440558 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1243588215E-002 | 5.4243560235E-002 | Pass | Pass | 0.4278856508 | 2.0629089785 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1578197377 | 0.2306284671 | Pass | Pass | 0.2029008290 | 0.4005155226 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1447434245 | 0.2351702392 | Pass | Pass | 0.1895467342 | 0.3901444895 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1498497197 | 0.2197466555 | Pass | Pass | 0.1880157363 | 0.3892018434 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2515844661 | 0.3519999203 | Pass | Pass | 0.1900811942 | 0.3907335591 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2656839693 | 0.4323869517 | Pass | Pass | 0.2229073733 | 0.4464377338 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2171948209 | 0.3152215489 | Pass | Pass | 0.1885996397 | 0.3884012391 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1912605215 | 0.2428652607 | Pass | Pass | 0.2371050761 | 0.4229157991 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2904960608 | 0.3682208781 | Pass | Pass | 0.2401293357 | 0.4236147286 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3092839458 | 0.4451331206 | Pass | Pass | 0.2821877111 | 0.4796939084 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2411431059 | 0.3117296401 | Pass | Pass | 0.2377092670 | 0.4221830364 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1553377571 | 0.2304465830 | Pass | Pass | 0.2028328017 | 0.3993635020 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2508409298 | 0.3668242413 | Pass | Pass | 0.2053094133 | 0.3981367300 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2639258786 | 0.4358450815 | Pass | Pass | 0.2347914489 | 0.4434069880 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2187887967 | 0.3304013004 | Pass | Pass | 0.2040101145 | 0.3986699074 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2948.41 | -104.8 | 0.00 | -1044.8 | 3540.49 | 5339.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.71 | 0.0000 | Y | 8.71 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.24 | 0.0000 | Y | 8.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 8.68 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.47 | 0.0000 | Y | 5.46 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.19 | 0.0000 | Y | 8.53 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.45 | 0.0000 | Y | 5.46 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.71 | 0.0000 | Y | 8.71 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.24 | 0.0000 | Y | 8.55 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.82 | 41.82 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.82 | 62.82 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.82 | 46.78 | 41.40 | |
Exterior Lighting Total | 5686.19 | 50.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120877.38 | 85628.12 | 35249.26 | 0.71 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107171.85 | 75136.39 | 32035.47 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 122316.77 | 86868.83 | 35447.94 | 0.71 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 120598.5 | 2.96 | 10.11 | N/A | N/A | 11.61 | |
PACU_VAV_MID COOLING COIL | 106996.8 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 122006.5 | 2.96 | 10.11 | N/A | N/A | 11.59 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25987.05 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25049.99 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26143.95 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10464.50 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6845.72 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10444.01 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6852.70 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6627.58 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4386.12 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6593.83 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4418.25 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8238.12 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5426.21 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8199.62 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5445.41 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 3024.98 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 4976.38 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 2697.30 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.97 | 10886.17 | 2189.01 | 1.00 | 1.13 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.32 | 9447.36 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.07 | 11023.73 | 2174.89 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120598.48 | 2.96 | 10.11 | 11.61 | 5.7451 | 3.33 | 11.35 | 4.5619 | 3.51 | 11.98 | 3.0694 | 3.63 | 12.40 | 1.3102 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106996.81 | 2.97 | 10.14 | 11.65 | 4.9858 | 3.34 | 11.39 | 3.9467 | 3.52 | 12.03 | 2.6559 | 3.64 | 12.43 | 1.1452 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 122006.45 | 2.96 | 10.11 | 11.59 | 5.8555 | 3.32 | 11.34 | 4.6468 | 3.51 | 11.96 | 3.1233 | 3.63 | 12.39 | 1.3340 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40291.99 | 40291.99 | 40.97 | 2.907 | 2.907 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_MID | 29944.52 | 29944.52 | 30.45 | 2.158 | 2.158 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_TOP | 32064.79 | 32064.79 | 32.60 | 2.332 | 2.332 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00887 | 33.13 | 0.01717 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10184.94 | 10184.94 | 49.12 | 0.741 | 0.741 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00910 | 32.26 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9701.40 | 9701.40 | 73.91 | 0.706 | 0.706 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00892 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10429.03 | 10429.03 | 50.30 | 0.759 | 0.759 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00908 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11008.49 | 11008.49 | 83.87 | 0.801 | 0.801 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00887 | 32.26 | 0.01717 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8605.99 | 8605.99 | 41.51 | 0.626 | 0.626 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00902 | 31.93 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8601.10 | 8601.10 | 65.53 | 0.626 | 0.626 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00884 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8739.66 | 8739.66 | 42.15 | 0.636 | 0.636 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00901 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9103.15 | 9103.15 | 69.36 | 0.662 | 0.662 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00882 | 32.04 | 0.01717 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8873.77 | 8873.77 | 42.80 | 0.646 | 0.646 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00912 | 31.82 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9320.38 | 9320.38 | 71.01 | 0.678 | 0.678 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00889 | 30.46 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9030.64 | 9030.64 | 43.56 | 0.657 | 0.657 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00911 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9976.58 | 9976.58 | 76.01 | 0.726 | 0.726 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00886 | 32.26 | 0.01717 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3119.68 | 3119.68 | 3.17 | 0.132 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_MID | 9479.56 | 9479.56 | 9.64 | 0.400 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_TOP | 17615.67 | 17615.67 | 17.91 | 0.747 | 0.747 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8015.67 | 8015.67 | 38.66 | 0.314 | 0.314 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00772 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5238.87 | 5238.87 | 39.91 | 0.205 | 0.205 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00773 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8000.47 | 8000.47 | 38.59 | 0.313 | 0.313 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00772 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5244.00 | 5244.00 | 39.95 | 0.205 | 0.205 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00773 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 4672.71 | 4672.71 | 22.54 | 0.199 | 0.199 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3091.37 | 3091.37 | 23.55 | 0.131 | 0.131 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 4649.11 | 4649.11 | 22.42 | 0.198 | 0.198 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3106.91 | 3106.91 | 23.67 | 0.132 | 0.132 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5800.62 | 5800.62 | 27.98 | 0.247 | 0.247 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3819.96 | 3819.96 | 29.10 | 0.163 | 0.163 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5773.65 | 5773.65 | 27.85 | 0.246 | 0.246 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3833.40 | 3833.40 | 29.21 | 0.163 | 0.163 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 8.70 | 0.00699 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.97 | 4.97 | 1.08 | 1.08 | 4.9731 | 1.3659 | 4.9731 | 0.2747 | 0.3000 |
PACU_VAV_MID | 4.32 | 4.32 | 1.24 | 1.24 | 4.3158 | 1.3482 | 4.3158 | 0.3124 | 0.3000 |
PACU_VAV_TOP | 5.07 | 5.07 | 1.85 | 1.85 | 5.0686 | 1.8470 | 5.0686 | 0.3644 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25987.053 | 25987.053 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25987.05 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00799978 | 51.6546 | 3119.68 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25049.993 | 25049.993 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25049.99 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 9479.56 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26143.948 | 26143.948 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26143.95 | 24930.37 | 0.747328 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 17615.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 10464.498 | 10464.498 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10464.50 | 10464.50 | 0.313690 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00772473 | 50.8421 | 8015.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 6845.721 | 6845.721 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6845.72 | 6845.72 | 0.205211 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00772999 | 50.8770 | 5238.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 10444.014 | 10444.014 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10444.01 | 10444.01 | 0.313076 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00772403 | 50.8375 | 8000.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 6852.702 | 6852.702 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6852.70 | 6852.70 | 0.205421 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00773045 | 50.8800 | 5244.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6627.579 | 6627.579 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6627.58 | 6627.58 | 0.198672 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00781539 | 50.4802 | 4672.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4386.115 | 4386.115 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4386.12 | 4386.12 | 0.131481 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00781949 | 50.5064 | 3091.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6593.827 | 6593.827 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6593.83 | 6593.83 | 0.197661 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00781420 | 50.4726 | 4649.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4418.251 | 4418.251 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4418.25 | 4408.34 | 0.132147 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782067 | 50.5139 | 3106.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8238.125 | 8238.125 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8238.12 | 8238.12 | 0.246951 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782446 | 50.5383 | 5800.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5426.208 | 5426.208 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5426.21 | 5426.21 | 0.162659 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782868 | 50.5651 | 3819.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8199.620 | 8199.620 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8199.62 | 8199.62 | 0.245797 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782338 | 50.5313 | 5773.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5445.407 | 5445.407 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5445.41 | 5445.41 | 0.163235 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782947 | 50.5702 | 3833.40 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 120877.384 | 85628.123 | 4.973099 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 124911.37 | 88682.11 | 4.973099 | 26.23 | 19.08 | 0.01089496 | 11.02 | 11.02 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 24.0327 | 24.00 | 0.00889211 | 47.7850 | 67882.26 | 0.00 | 124640.81 | 87055.83 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 3024.977 | 3024.977 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3024.98 | 3024.98 | 1.491930 | 11.12 | 9.99 | 0.00717101 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 80.1090 | 21.00 | 0.00784745 | 50.6845 | 18639.78 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 107171.853 | 75136.388 | 4.315811 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 112052.05 | 76414.44 | 4.315811 | 26.46 | 19.45 | 0.01127811 | 11.03 | 11.03 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 27.6928 | 24.00 | 0.00900958 | 48.4082 | 59075.01 | 0.00 | 110508.57 | 76423.89 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 4976.378 | 4976.378 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4976.38 | 4976.38 | 1.294743 | 9.62 | 9.20 | 0.00706032 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 92.3094 | 21.00 | 0.00786186 | 50.7765 | 26713.17 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 122316.768 | 86868.831 | 5.068641 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 126546.22 | 89561.27 | 5.068641 | 26.09 | 19.04 | 0.01089902 | 11.04 | 11.04 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 23.5797 | 24.00 | 0.00896172 | 48.1550 | 69580.85 | 0.00 | 126125.01 | 88290.24 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 2697.304 | 2697.304 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2697.30 | 2697.30 | 1.520592 | 11.33 | 10.11 | 0.00719261 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 78.5990 | 21.00 | 0.00792624 | 51.1863 | 27845.82 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25987.053 | 25987.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25987.05 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25987.05 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.82 | 0.00799978 | 21.00 | 0.00799978 | 51.6546 | 3119.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25049.993 | 25049.993 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25049.99 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25049.99 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 9479.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26143.948 | 26143.948 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26143.95 | 24930.37 | 1.0000 | 0.89884023 | 0.747328 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26143.95 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 17615.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10464.498 | 10464.498 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10464.50 | 10464.50 | 1.0000 | 0.37728725 | 0.313690 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10464.50 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.48 | 0.00772473 | 20.70 | 0.00772473 | 50.8421 | 8015.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6845.721 | 6845.721 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6845.72 | 6845.72 | 1.0000 | 0.24681577 | 0.205211 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6845.72 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.48 | 0.00772999 | 20.70 | 0.00772999 | 50.8770 | 5238.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10444.014 | 10444.014 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10444.01 | 10444.01 | 1.0000 | 0.37654874 | 0.313076 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10444.01 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.48 | 0.00772403 | 20.70 | 0.00772403 | 50.8375 | 8000.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6852.702 | 6852.702 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6852.70 | 6852.70 | 1.0000 | 0.24706749 | 0.205421 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6852.70 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.48 | 0.00773045 | 20.70 | 0.00773045 | 50.8800 | 5244.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6627.579 | 6627.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6627.58 | 6627.58 | 1.0000 | 0.23895090 | 0.198672 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6627.58 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00781539 | 21.00 | 0.00781539 | 50.4802 | 4672.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4386.115 | 4386.115 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4386.12 | 4386.12 | 1.0000 | 0.15813711 | 0.131481 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4386.12 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00781949 | 21.00 | 0.00781949 | 50.5064 | 3091.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6593.827 | 6593.827 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6593.83 | 6593.83 | 1.0000 | 0.23773399 | 0.197661 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6593.83 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00781420 | 21.00 | 0.00781420 | 50.4726 | 4649.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4418.251 | 4418.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4418.25 | 4408.34 | 1.0000 | 0.15893841 | 0.132147 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4418.25 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00782067 | 21.00 | 0.00782067 | 50.5139 | 3106.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8238.125 | 8238.125 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8238.12 | 8238.12 | 1.0000 | 0.29701754 | 0.246951 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8238.12 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00782446 | 21.00 | 0.00782446 | 50.5383 | 5800.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5426.208 | 5426.208 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5426.21 | 5426.21 | 1.0000 | 0.19563664 | 0.162659 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5426.21 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00782868 | 21.00 | 0.00782868 | 50.5651 | 3819.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8199.620 | 8199.620 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8199.62 | 8199.62 | 1.0000 | 0.29562931 | 0.245797 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8199.62 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00782338 | 21.00 | 0.00782338 | 50.5313 | 5773.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5445.407 | 5445.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5445.41 | 5445.41 | 1.0000 | 0.19632884 | 0.163235 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5445.41 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00782947 | 21.00 | 0.00782947 | 50.5702 | 3833.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120877.384 | 85628.123 | 4.973099 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0932 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.973099 | 5.98133991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 124911.37 | 88682.11 | 1.0334 | 5.98133991 | 4.973099 | 26.23 | 19.08 | 0.01089496 | 54131.2 | 11.02 | 11.02 | 0.00850000 | 32510.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10886.169 | 114025.20 | 33.20 | 0.01716721 | 25.32 | 1.19517000 | 24.0327 | 24.00 | 0.00889211 | 24.00 | 0.00889211 | 47.7850 | 67882.26 | 0.00 | 124640.81 | 87055.83 | 5.74512220 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.82 | 11.81 | 0.00861966 | 33627.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3024.977 | 3024.977 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.973099 | 5.98133991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3024.98 | 3024.98 | 1.0000 | 1.79440197 | 1.491930 | 11.12 | 9.99 | 0.00717101 | 29258.7 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3024.98 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 80.1090 | 20.88 | 0.00788851 | 21.00 | 0.00784745 | 50.6845 | 18639.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107171.853 | 75136.388 | 4.315811 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.97984 | 1025.8054 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.315811 | 5.19079336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 112052.05 | 76414.44 | 1.0455 | 5.19079336 | 4.315811 | 26.46 | 19.45 | 0.01127811 | 55352.8 | 11.03 | 11.03 | 0.00850000 | 32511.3 | -999.0 | -999.00 | -999.00 | -999.00 | 9447.357 | 102604.70 | 32.87 | 0.01716657 | 25.24 | 1.19517000 | 27.6928 | 24.00 | 0.00900958 | 24.00 | 0.00900958 | 48.4082 | 59075.01 | 0.00 | 110508.57 | 76423.89 | 4.98579626 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.62 | 0.00850428 | 33157.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4976.378 | 4976.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.315811 | 5.19079336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4976.38 | 4976.38 | 1.0000 | 1.55723801 | 1.294743 | 9.62 | 9.20 | 0.00706032 | 27450.1 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4976.38 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 92.3094 | 20.66 | 0.00787009 | 21.00 | 0.00786186 | 50.7765 | 26713.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 122316.768 | 86868.831 | 5.068641 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1007 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.068641 | 6.09625233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 126546.22 | 89561.27 | 1.0346 | 6.09625233 | 5.068641 | 26.09 | 19.04 | 0.01089902 | 54004.4 | 11.04 | 11.04 | 0.00850000 | 32521.8 | -999.0 | -999.00 | -999.00 | -999.00 | 11023.729 | 115522.50 | 32.87 | 0.01716657 | 25.24 | 1.19517000 | 23.5797 | 24.00 | 0.00896172 | 24.00 | 0.00896172 | 48.1550 | 69580.85 | 0.00 | 126125.01 | 88290.24 | 5.85549645 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.90 | 11.88 | 0.00865129 | 33782.8 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 2697.304 | 2697.304 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.068641 | 6.09625233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2697.30 | 2697.30 | 1.0000 | 1.82887570 | 1.520592 | 11.33 | 10.11 | 0.00719261 | 29526.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2697.30 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 78.5990 | 21.00 | 0.00792624 | 21.00 | 0.00792624 | 51.1863 | 27845.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5209.33 | 65.83 | 0.00 |
CORE_MID | 4067.83 | 689.67 | 0.00 |
CORE_TOP | 3810.50 | 1174.50 | 0.33 |
PERIMETER_TOP_ZN_3 | 4265.67 | 1706.33 | 501.67 |
PERIMETER_TOP_ZN_2 | 4392.33 | 1600.83 | 554.33 |
PERIMETER_TOP_ZN_1 | 4744.33 | 1358.67 | 622.83 |
PERIMETER_TOP_ZN_4 | 4101.67 | 1800.00 | 488.83 |
PERIMETER_BOT_ZN_3 | 4505.83 | 1134.50 | 221.33 |
PERIMETER_BOT_ZN_2 | 4862.17 | 922.50 | 368.17 |
PERIMETER_BOT_ZN_1 | 5195.50 | 1547.50 | 1166.67 |
PERIMETER_BOT_ZN_4 | 4770.50 | 1006.33 | 318.67 |
PERIMETER_MID_ZN_3 | 4469.17 | 1330.33 | 355.67 |
PERIMETER_MID_ZN_2 | 3742.67 | 1250.17 | 457.17 |
PERIMETER_MID_ZN_1 | 4970.17 | 1010.67 | 504.33 |
PERIMETER_MID_ZN_4 | 4387.83 | 1400.50 | 405.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5492.83 | 2937.00 | 1538.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 19.00 | 0.00 | 16.83 |
PERIMETER_TOP_ZN_2 | 0.00 | 48.33 | 0.00 | 47.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 67.83 | 0.00 | 65.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 40.17 | 0.00 | 30.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 28.00 | 0.00 | 28.00 |
PERIMETER_BOT_ZN_1 | 18.33 | 353.17 | 18.33 | 352.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 27.33 | 0.00 | 21.17 |
PERIMETER_MID_ZN_3 | 0.00 | 2.00 | 0.00 | 1.83 |
PERIMETER_MID_ZN_2 | 0.00 | 36.17 | 0.00 | 36.17 |
PERIMETER_MID_ZN_1 | 0.00 | 93.67 | 0.00 | 93.50 |
PERIMETER_MID_ZN_4 | 0.00 | 30.83 | 0.00 | 24.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 18.33 | 468.00 | 18.33 | 454.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.500 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.443 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.439 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.545 | 0.087 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.750 | 0.092 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.688 | 0.087 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.769 | 0.092 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.469 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.634 | 0.049 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.644 | 1.278 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.627 | 0.049 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.551 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.711 | 0.081 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.700 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.762 | 0.076 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.05 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8138334.21 | 0.00 | 8138334.21 | 0.00 | 8138334.21 | 13393058.27 | 6447.53 | 548.33 | 1764.14 | 186.39 |
CORE_MID | 7174220.52 | 0.00 | 7174220.52 | 0.00 | 7174220.52 | 13393058.27 | 8542.43 | 95.78 | 121.78 | 140.74 |
CORE_TOP | 7110666.91 | 0.00 | 7110666.91 | 0.00 | 7110666.91 | 13393058.27 | 8697.95 | 21.96 | 40.09 | 145.58 |
PERIMETER_TOP_ZN_3 | 1850807.85 | 0.00 | 1850807.85 | 538833.39 | 2389641.24 | 2823374.22 | 6052.60 | 71.35 | 2636.05 | 145.58 |
PERIMETER_TOP_ZN_2 | 1610566.60 | 0.00 | 1610566.60 | 359220.10 | 1969786.70 | 1787429.43 | 3622.06 | 4.49 | 5133.45 | 145.58 |
PERIMETER_TOP_ZN_1 | 2321322.42 | 0.00 | 2321322.42 | 538833.39 | 2860155.81 | 2823374.22 | 5249.34 | 36.51 | 3474.15 | 145.58 |
PERIMETER_TOP_ZN_4 | 1659351.76 | 0.00 | 1659351.76 | 359220.10 | 2018571.86 | 1787312.18 | 3657.97 | 17.23 | 5084.79 | 145.58 |
PERIMETER_BOT_ZN_3 | 1610926.91 | 0.00 | 1610926.91 | 286497.20 | 1897424.11 | 2823374.22 | 6577.74 | 942.98 | 1239.29 | 186.39 |
PERIMETER_BOT_ZN_2 | 1371746.41 | 0.00 | 1371746.41 | 190996.98 | 1562743.40 | 1787429.43 | 3886.90 | 104.14 | 4768.96 | 186.39 |
PERIMETER_BOT_ZN_1 | 2183585.84 | 0.00 | 2183585.84 | 4346331.72 | 6529917.56 | 2823374.22 | 4479.67 | 846.92 | 3433.42 | 186.39 |
PERIMETER_BOT_ZN_4 | 1361778.69 | 0.00 | 1361778.69 | 190996.98 | 1552775.68 | 1787312.18 | 4329.79 | 157.78 | 4272.43 | 186.39 |
PERIMETER_MID_ZN_3 | 1865674.47 | 0.00 | 1865674.47 | 448539.25 | 2314213.73 | 2823374.22 | 5940.77 | 105.67 | 2713.56 | 140.74 |
PERIMETER_MID_ZN_2 | 1610627.78 | 0.00 | 1610627.78 | 299024.37 | 1909652.15 | 1787429.43 | 3642.16 | 11.65 | 5106.20 | 1049.74 |
PERIMETER_MID_ZN_1 | 2360647.47 | 0.00 | 2360647.47 | 448539.25 | 2809186.73 | 2823374.22 | 5032.93 | 92.36 | 3634.71 | 140.74 |
PERIMETER_MID_ZN_4 | 1638118.81 | 0.00 | 1638118.81 | 299024.37 | 1937143.18 | 1787312.18 | 3731.77 | 32.39 | 4995.84 | 140.74 |
Total Facility | 43868376.66 | 0.00 | 43868376.66 | 8306057.11 | 52174433.77 | 67843644.98 | 8760.00 | 1644.23 | 5326.98 | 1145.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3670 | 0.0000 | 0.3670 | 0.0000 | 0.3670 | 0.4247 | 3667.22 | 521.22 | 1754.56 |
CORE_MID | 0.3254 | 0.0000 | 0.3254 | 0.0000 | 0.3254 | 0.4247 | 5728.35 | 95.62 | 119.03 |
CORE_TOP | 0.3223 | 0.0000 | 0.3223 | 0.0000 | 0.3223 | 0.4247 | 5882.45 | 21.78 | 38.77 |
PERIMETER_TOP_ZN_3 | 0.0843 | 0.0000 | 0.0843 | 0.0135 | 0.0978 | 0.0895 | 3240.74 | 71.03 | 2631.23 |
PERIMETER_TOP_ZN_2 | 0.0735 | 0.0000 | 0.0735 | 0.0090 | 0.0824 | 0.0567 | 949.77 | 4.39 | 4988.85 |
PERIMETER_TOP_ZN_1 | 0.1063 | 0.0000 | 0.1063 | 0.0135 | 0.1198 | 0.0895 | 2438.93 | 36.36 | 3467.71 |
PERIMETER_TOP_ZN_4 | 0.0754 | 0.0000 | 0.0754 | 0.0090 | 0.0844 | 0.0567 | 986.42 | 17.20 | 4939.38 |
PERIMETER_BOT_ZN_3 | 0.0725 | 0.0000 | 0.0725 | 0.0072 | 0.0797 | 0.0895 | 3889.63 | 814.51 | 1238.86 |
PERIMETER_BOT_ZN_2 | 0.0620 | 0.0000 | 0.0620 | 0.0048 | 0.0668 | 0.0567 | 1251.93 | 103.06 | 4588.02 |
PERIMETER_BOT_ZN_1 | 0.0993 | 0.0000 | 0.0993 | 0.1969 | 0.2962 | 0.0895 | 1798.62 | 716.97 | 3427.41 |
PERIMETER_BOT_ZN_4 | 0.0613 | 0.0000 | 0.0613 | 0.0048 | 0.0661 | 0.0567 | 1696.92 | 157.66 | 4088.42 |
PERIMETER_MID_ZN_3 | 0.0851 | 0.0000 | 0.0851 | 0.0112 | 0.0963 | 0.0895 | 3127.26 | 105.53 | 2710.20 |
PERIMETER_MID_ZN_2 | 0.0696 | 0.0000 | 0.0696 | 0.0079 | 0.0775 | 0.0567 | 949.81 | 7.37 | 4076.82 |
PERIMETER_MID_ZN_1 | 0.1082 | 0.0000 | 0.1082 | 0.0112 | 0.1195 | 0.0895 | 2221.01 | 92.24 | 3629.75 |
PERIMETER_MID_ZN_4 | 0.0746 | 0.0000 | 0.0746 | 0.0075 | 0.0821 | 0.0567 | 1055.13 | 32.28 | 4855.59 |
Total Facility | 1.9869 | 0.0000 | 1.9869 | 0.2963 | 2.2832 | 2.1513 | 5943.00 | 1511.84 | 5090.71 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21216129.66 | 0.00 | 21216129.66 | 22614548.33 | 3567.28 | 0.00 | 5192.72 | 186.39 |
PACU_VAV_MID | 21191399.86 | 0.00 | 21191399.86 | 22614548.33 | 3612.98 | 0.00 | 5147.02 | 140.74 |
PACU_VAV_TOP | 21051687.50 | 0.00 | 21051687.50 | 22614548.33 | 3611.04 | 0.00 | 5148.96 | 145.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9578 | 0.0000 | 0.9578 | 0.7171 | 936.67 | 0.00 | 5006.33 |
PACU_VAV_MID | 0.9647 | 0.0000 | 0.9647 | 0.7171 | 936.72 | 0.00 | 5006.28 |
PACU_VAV_TOP | 0.9573 | 0.0000 | 0.9573 | 0.7171 | 939.62 | 0.00 | 5003.38 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5192.72 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5147.02 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5148.96 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1371 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1453 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1372 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2218 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
Electricity:Building | 1005.73 | 12229.26 | 09-JUL-17:20 | 78507.21 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1005.73 | 12229.26 | 09-JUL-17:20 | 78507.21 | 27-SEP-07:10 |
InteriorLights:Electricity | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.04 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.88 | 267.21 | 04-JUL-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.88 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.87 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.01 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-09:50 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-09:50 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 267.21 | 29-MAY-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.86 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.86 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:50 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:50 | 859.95 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.04 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.88 | 267.21 | 04-JUL-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.88 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.87 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 811.80 | 168.34 | 01-JAN-00:10 | 97420.54 | 28-JUL-15:30 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 27-SEP-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 27-SEP-07:20 |
ElectricityPurchased:Facility | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
ElectricityPurchased:Plant | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
Cogeneration:ElectricityPurchased | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
General:Cogeneration:ElectricityPurchased | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
ElectricityNet:Plant | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
Cogeneration:ElectricityNet | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
General:Cogeneration:ElectricityNet | 1868.31 | 12404.62 | 29-MAY-17:20 | 165180.87 | 28-JUL-15:30 |
Heating:Electricity | 2.09 | 0.00 | 01-JAN-00:10 | 43312.35 | 04-FEB-07:10 |
General:Heating:Electricity | 2.09 | 0.00 | 01-JAN-00:10 | 43312.35 | 04-FEB-07:10 |
Fans:Electricity | 96.04 | 0.00 | 01-JAN-00:10 | 14235.27 | 31-JUL-14:30 |
General:Fans:Electricity | 96.04 | 0.00 | 01-JAN-00:10 | 14235.27 | 31-JUL-14:30 |
ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 701.90 | 0.00 | 01-JAN-00:10 | 82384.97 | 28-JUL-15:30 |
General:Cooling:Electricity | 701.90 | 0.00 | 01-JAN-00:10 | 82384.97 | 28-JUL-15:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-FEB-17:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-FEB-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-FEB-17:10 |
WIRED_LTG_ELECTRICITY | 8.44 | 0.00 | 01-JAN-00:10 | 917.25 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 113.20 | 1886.44 | 15-DEC-08:10 | 10100.98 | 04-FEB-07:20 |
NaturalGas:HVAC | 0.01 | 0.00 | 01-JAN-00:10 | 2416.80 | 04-FEB-06:10 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 2416.80 | 04-FEB-06:10 |
General:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 2416.80 | 04-FEB-06:10 |
NaturalGas:Plant | 113.19 | 1886.44 | 15-DEC-08:10 | 9539.37 | 03-FEB-12:10 |
WaterSystems:NaturalGas | 113.19 | 1886.44 | 15-DEC-08:10 | 9539.37 | 03-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 113.19 | 1886.44 | 15-DEC-08:10 | 9539.37 | 03-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4611.02 | 0.00 | 01-JAN-00:10 | 457566.46 | 31-JUL-14:00 |
EnergyTransfer:Building | 1735.06 | 0.00 | 01-JAN-00:10 | 168364.51 | 31-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 321.19 | 0.00 | 01-JAN-00:10 | 27946.65 | 05-SEP-08:00 |
Heating:EnergyTransfer | 2.25 | 0.00 | 01-JAN-00:10 | 28476.84 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.25 | 0.00 | 01-JAN-00:10 | 28476.84 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1732.80 | 0.00 | 01-JAN-00:10 | 168364.51 | 31-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 321.19 | 0.00 | 01-JAN-00:10 | 27946.65 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1732.80 | 0.00 | 01-JAN-00:10 | 168364.51 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 321.19 | 0.00 | 01-JAN-00:10 | 27946.65 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.89 | 0.00 | 01-JAN-00:10 | 11672.66 | 28-JUL-15:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.22 | 0.00 | 01-JAN-00:10 | 4443.48 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.22 | 0.00 | 01-JAN-00:10 | 4443.48 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.67 | 0.00 | 01-JAN-00:10 | 11672.66 | 28-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.67 | 0.00 | 01-JAN-00:10 | 11672.66 | 28-JUL-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.44 | 0.00 | 01-JAN-00:10 | 5012.31 | 31-JUL-14:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.16 | 0.00 | 01-JAN-00:10 | 1625.82 | 05-FEB-13:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.16 | 0.00 | 01-JAN-00:10 | 1625.82 | 05-FEB-13:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.29 | 0.00 | 01-JAN-00:10 | 5012.31 | 31-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.29 | 0.00 | 01-JAN-00:10 | 5012.31 | 31-JUL-14:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.25 | 0.00 | 01-JAN-00:10 | 5440.41 | 31-JUL-15:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1487.16 | 05-FEB-13:00 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1487.16 | 05-FEB-13:00 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.06 | 0.00 | 01-JAN-00:10 | 5440.41 | 31-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.06 | 0.00 | 01-JAN-00:10 | 5440.41 | 31-JUL-15:10 |
EnergyTransfer:Zone:CORE_MID | 232.79 | 0.00 | 01-JAN-00:10 | 19208.46 | 02-OCT-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 232.79 | 0.00 | 01-JAN-00:10 | 19208.46 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 232.79 | 0.00 | 01-JAN-00:10 | 19208.46 | 02-OCT-08:00 |
EnergyTransfer:Zone:CORE_TOP | 241.47 | 0.00 | 01-JAN-00:10 | 21839.81 | 31-JUL-14:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 3930.05 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 3930.05 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 241.46 | 0.00 | 01-JAN-00:10 | 21839.81 | 31-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 241.46 | 0.00 | 01-JAN-00:10 | 21839.81 | 31-JUL-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.11 | 0.00 | 01-JAN-00:10 | 7991.14 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3945.18 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3945.18 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.03 | 0.00 | 01-JAN-00:10 | 7991.14 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.03 | 0.00 | 01-JAN-00:10 | 7991.14 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.16 | 0.00 | 01-JAN-00:10 | 8049.38 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2424.78 | 04-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2424.78 | 04-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.12 | 0.00 | 01-JAN-00:10 | 8049.38 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.12 | 0.00 | 01-JAN-00:10 | 8049.38 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.78 | 0.00 | 01-JAN-00:10 | 11256.99 | 07-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3367.49 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3367.49 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.74 | 0.00 | 01-JAN-00:10 | 11256.99 | 07-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.74 | 0.00 | 01-JAN-00:10 | 11256.99 | 07-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.23 | 0.00 | 01-JAN-00:10 | 8703.69 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2527.02 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2527.02 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.17 | 0.00 | 01-JAN-00:10 | 8703.69 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.17 | 0.00 | 01-JAN-00:10 | 8703.69 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.11 | 0.00 | 01-JAN-00:10 | 7179.03 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 985.08 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 985.08 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.11 | 0.00 | 01-JAN-00:10 | 7179.03 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.11 | 0.00 | 01-JAN-00:10 | 7179.03 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.60 | 0.00 | 01-JAN-00:10 | 7163.33 | 25-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 584.88 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 584.88 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.60 | 0.00 | 01-JAN-00:10 | 7163.33 | 25-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.60 | 0.00 | 01-JAN-00:10 | 7163.33 | 25-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.83 | 0.00 | 01-JAN-00:10 | 10930.68 | 27-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.43 | 0.00 | 01-JAN-00:10 | 4844.12 | 16-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.43 | 0.00 | 01-JAN-00:10 | 4844.12 | 16-MAR-07:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.40 | 0.00 | 01-JAN-00:10 | 10930.68 | 27-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.40 | 0.00 | 01-JAN-00:10 | 10930.68 | 27-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 53.98 | 0.00 | 01-JAN-00:10 | 7167.47 | 01-SEP-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 662.50 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 662.50 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 53.98 | 0.00 | 01-JAN-00:10 | 7167.47 | 01-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 53.98 | 0.00 | 01-JAN-00:10 | 7167.47 | 01-SEP-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.18 | 0.00 | 01-JAN-00:10 | 7231.74 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2000.28 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2000.28 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.18 | 0.00 | 01-JAN-00:10 | 7231.74 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.18 | 0.00 | 01-JAN-00:10 | 7231.74 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.31 | 0.00 | 01-JAN-00:10 | 7492.16 | 12-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 973.79 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 973.79 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.31 | 0.00 | 01-JAN-00:10 | 7492.16 | 12-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.31 | 0.00 | 01-JAN-00:10 | 7492.16 | 12-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.61 | 0.00 | 01-JAN-00:10 | 10099.06 | 04-DEC-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1557.12 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1557.12 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.61 | 0.00 | 01-JAN-00:10 | 10099.06 | 04-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.61 | 0.00 | 01-JAN-00:10 | 10099.06 | 04-DEC-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.12 | 0.00 | 01-JAN-00:10 | 8074.96 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1314.62 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1314.62 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.11 | 0.00 | 01-JAN-00:10 | 8074.96 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.11 | 0.00 | 01-JAN-00:10 | 8074.96 | 17-MAY-16:00 |
PlantLoopHeatingDemand:Facility | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
EnergyTransfer:HVAC | 2840.69 | 0.00 | 01-JAN-00:10 | 288763.29 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 2.10 | 0.00 | 01-JAN-00:10 | 44419.56 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2838.59 | 0.00 | 01-JAN-00:10 | 288763.29 | 21-AUG-16:00 |
EnergyTransfer:Plant | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
WaterSystems:EnergyTransfer | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 35.28 | 0.00 | 01-JAN-00:10 | 4408.08 | 20-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -321.193 | 0.000 | 0.000 | 32.687 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -19.590 |
CORE_MID | 0.000 | 0.000 | 0.000 | -232.786 | 0.000 | 0.000 | 32.870 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 12.562 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.002 | -241.463 | 0.000 | 0.000 | 33.112 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 20.994 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.084 | -66.025 | 0.000 | 0.000 | 7.017 | 8.707 | 24.333 | 27.618 | 0.000 | 0.760 | 8.401 | 0.000 | -9.783 | 0.000 | -1.112 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.044 | -57.117 | 0.000 | 0.000 | 4.411 | 5.472 | 15.404 | 36.678 | 0.000 | 0.498 | 1.601 | 0.000 | -6.215 | 0.000 | -0.776 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.044 | -84.735 | 0.000 | 0.000 | 6.940 | 8.546 | 24.332 | 56.946 | 0.000 | 0.714 | 0.000 | 0.000 | -9.963 | 0.000 | -1.282 | -1.543 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.061 | -57.167 | 0.000 | 0.000 | 4.477 | 5.471 | 15.403 | 35.707 | 0.000 | 0.507 | 3.063 | 0.000 | -6.739 | 0.000 | -0.784 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -64.104 | 0.000 | 0.000 | 6.960 | 8.677 | 24.333 | 27.794 | 0.000 | 0.429 | 7.375 | 0.000 | -10.787 | 0.000 | -0.677 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -55.598 | 0.000 | 0.000 | 4.377 | 5.460 | 15.404 | 36.795 | 0.000 | 0.266 | 0.954 | 0.000 | -7.166 | 0.000 | -0.492 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.431 | -91.393 | 0.000 | 0.000 | 6.879 | 8.530 | 24.332 | 57.170 | 0.000 | 11.762 | 0.001 | 0.000 | -11.393 | 0.000 | -5.787 | -0.531 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -53.979 | 0.000 | 0.000 | 4.401 | 5.456 | 15.403 | 35.725 | 0.000 | 0.263 | 0.994 | 0.000 | -7.763 | 0.000 | -0.501 | -0.001 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.006 | -63.173 | 0.000 | 0.000 | 6.970 | 8.707 | 24.333 | 27.721 | 0.000 | 0.647 | 6.369 | 0.000 | -10.551 | 0.000 | -1.029 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.005 | -54.305 | 0.000 | 0.000 | 3.247 | 5.472 | 15.404 | 36.786 | 0.000 | 0.422 | 0.328 | 0.000 | -6.650 | 0.000 | -0.709 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.002 | -81.603 | 0.000 | 0.000 | 6.903 | 8.546 | 24.332 | 57.113 | 0.000 | 0.604 | 0.001 | 0.000 | -10.640 | 0.000 | -1.163 | -4.096 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.006 | -54.109 | 0.000 | 0.000 | 4.435 | 5.471 | 15.403 | 35.752 | 0.000 | 0.419 | 0.610 | 0.000 | -7.263 | 0.000 | -0.724 | -0.000 |
TOPFLOOR_PLENUM | 1.219 | -68.671 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.800 | 68.346 | 0.000 | 0.000 | 0.000 | -1.694 | -0.000 |
MIDFLOOR_PLENUM | 0.157 | -39.286 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.919 | 40.053 | 0.000 | 0.000 | 0.000 | -1.842 | -0.000 |
FIRSTFLOOR_PLENUM | 0.190 | -46.063 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.699 | 46.727 | 0.000 | 0.000 | 0.000 | -1.553 | -0.000 |
Total Facility | 1.566 | -154.021 | 0.687 | -1578.749 | 0.000 | 0.000 | 165.688 | 300.299 | 705.434 | 471.806 | 0.000 | 19.709 | 218.384 | 0.000 | -104.914 | 0.000 | -20.124 | -25.763 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | -46539.11 | 0.00 | 0.00 | 295.34 | 211.73 | 4989.51 | 0.00 | 0.00 | 0.00 | 41042.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-04:04 | 0.00 | 0.00 | 0.00 | -35930.88 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 33277.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:02 | 0.00 | 0.00 | 0.00 | -36383.17 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 33729.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-16:02 | 0.00 | 0.00 | 0.00 | -12820.82 | 0.00 | 0.00 | 26.69 | 36.00 | 478.42 | 2872.37 | 0.00 | 191.97 | 9215.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:12 | 0.00 | 0.00 | 0.00 | -12936.23 | 0.00 | 0.00 | 14.89 | 22.79 | 302.86 | 6860.17 | 0.00 | 50.14 | 5685.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-13:12 | 0.00 | 0.00 | 0.00 | -14208.94 | 0.00 | 0.00 | 23.95 | 36.00 | 478.41 | 9129.14 | 0.00 | 0.00 | 4580.21 | 0.00 | -0.00 | 0.00 | -38.77 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:02 | 0.00 | 0.00 | 0.00 | -14620.67 | 0.00 | 0.00 | 14.03 | 22.79 | 302.86 | 6600.57 | 0.00 | 98.98 | 7581.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 26-JUN-04:02 | 0.00 | 0.00 | 0.00 | -8690.27 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 8555.79 | 0.00 | -424.86 | 0.00 | -0.10 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-10:02 | 0.00 | 0.00 | 0.00 | -11565.55 | 0.00 | 0.00 | 15.36 | 22.79 | 302.86 | 6176.76 | 0.00 | 33.01 | 5014.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -12144.66 | 0.00 | 0.00 | 24.04 | 36.00 | 478.41 | 11301.88 | 0.00 | 57.34 | 246.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 20-FEB-17:22 | 0.00 | 0.00 | 0.00 | -11801.18 | 0.00 | 0.00 | 15.65 | 22.79 | 302.86 | 6239.13 | 0.00 | 0.00 | 5243.14 | 0.00 | -0.00 | 0.00 | -22.39 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-16:02 | 0.00 | 0.00 | 0.00 | -10548.41 | 0.00 | 0.00 | 27.48 | 36.00 | 478.42 | 2994.81 | 0.00 | 387.76 | 6623.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -12792.91 | 0.00 | 0.00 | 14.45 | 22.79 | 302.86 | 7589.31 | 0.00 | 34.63 | 4828.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -12759.87 | 0.00 | 0.00 | 23.02 | 36.00 | 478.41 | 11169.56 | 0.00 | 74.80 | 978.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 12-MAR-16:52 | 0.00 | 0.00 | 0.00 | -12973.55 | 0.00 | 0.00 | 15.40 | 22.79 | 302.86 | 7593.57 | 0.00 | 0.00 | 5135.57 | 0.00 | -0.00 | 0.00 | -96.63 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:30 | 0.00 | -11672.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 | 11596.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 31-JUL-14:40 | 0.00 | -5012.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 | 4920.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:10 | 0.00 | -5659.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 5591.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-04:02 | 0.00 | 7694.95 | 0.00 | -207856.18 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 189129.25 | 0.00 | -4321.80 | 0.00 | -52.70 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-FEB-07:03 | 0.00 | 0.00 | 15720.30 | 0.00 | 0.00 | 0.00 | 448.46 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19910.66 |
PERIMETER_TOP_ZN_3 | 04-FEB-06:12 | 0.00 | 0.00 | 7777.14 | 0.00 | 0.00 | 0.00 | 104.02 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2623.38 | 0.00 | -201.31 | -5845.30 |
PERIMETER_TOP_ZN_2 | 17-MAR-06:03 | 0.00 | 0.00 | 4776.62 | 0.00 | 0.00 | 0.00 | 122.35 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1031.60 | 0.00 | -54.50 | -4503.35 |
PERIMETER_TOP_ZN_1 | 04-FEB-06:12 | 0.00 | 0.00 | 7554.36 | 0.00 | 0.00 | 0.00 | 102.85 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2609.86 | 0.00 | -205.76 | -5630.42 |
PERIMETER_TOP_ZN_4 | 24-FEB-07:03 | 0.00 | 0.00 | 4787.75 | 0.00 | 0.00 | 0.00 | 122.36 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1203.30 | 0.00 | -5.10 | -4392.18 |
PERIMETER_BOT_ZN_3 | 04-FEB-07:03 | 0.00 | 0.00 | 3940.33 | 0.00 | 0.00 | 0.00 | 94.71 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2845.16 | 0.00 | -121.07 | -1857.63 |
PERIMETER_BOT_ZN_2 | 04-FEB-07:03 | 0.00 | 0.00 | 2339.53 | 0.00 | 0.00 | 0.00 | 60.14 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -296.89 | 0.00 | -80.70 | -2521.45 |
PERIMETER_BOT_ZN_1 | 16-MAR-07:00 | 0.00 | 0.00 | 4843.89 | 0.00 | 0.00 | 0.00 | 214.25 | 315.99 | 637.88 | 0.00 | 0.00 | 0.00 | 10110.77 | 0.00 | -1896.91 | 0.00 | -14225.87 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-FEB-07:03 | 0.00 | 0.00 | 2650.01 | 0.00 | 0.00 | 0.00 | 60.13 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1906.16 | 0.00 | -80.69 | -1222.63 |
PERIMETER_MID_ZN_3 | 25-JAN-07:02 | 0.00 | 0.00 | 5384.61 | 0.00 | 0.00 | 0.00 | 190.74 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2263.73 | 0.00 | -104.06 | -4298.27 |
PERIMETER_MID_ZN_2 | 21-DEC-07:03 | 0.00 | 0.00 | 3708.58 | 0.00 | 0.00 | 0.00 | 121.44 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -701.93 | 0.00 | -21.33 | -3797.24 |
PERIMETER_MID_ZN_1 | 04-FEB-07:03 | 0.00 | 0.00 | 5105.51 | 0.00 | 0.00 | 0.00 | 96.65 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2170.06 | 0.00 | -185.42 | -3635.50 |
PERIMETER_MID_ZN_4 | 26-JAN-07:03 | 0.00 | 0.00 | 3763.98 | 0.00 | 0.00 | 0.00 | 121.56 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1355.74 | 0.00 | -22.10 | -3198.16 |
TOPFLOOR_PLENUM | 23-OCT-05:02 | 5786.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.11 | -5777.24 |
MIDFLOOR_PLENUM | 05-FEB-15:13 | 2772.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -171.47 | -2600.71 |
FIRSTFLOOR_PLENUM | 29-SEP-04:02 | 3796.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15.50 | -3780.56 |
Total Facility | 04-FEB-07:03 | -17674.47 | 18951.58 | 63457.53 | -18951.58 | 0.00 | 0.00 | 2180.42 | 3626.85 | 17966.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20879.88 | 0.00 | -2661.71 | -46014.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4565 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9731 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.8642 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3158 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.3388 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0686 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7282 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3659 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4321 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3482 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6694 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4157 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9067 | 2.9067 | 0.7790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1578 | 2.1578 | 0.7509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3325 | 2.3325 | 0.7837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7410 | 0.7410 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7058 | 0.7058 | 0.1412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7587 | 0.7587 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8009 | 0.8009 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6261 | 0.6261 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6257 | 0.6257 | 0.1251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6358 | 0.6358 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6622 | 0.6622 | 0.1324 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6456 | 0.6456 | 0.1582 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6781 | 0.6781 | 0.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6570 | 0.6570 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7258 | 0.7258 | 0.1452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4565 | 4.9731 | 5.4565 | 1.3659 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.8642 | 4.3158 | 4.8642 | 1.3482 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.3388 | 5.0686 | 5.3388 | 1.4157 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4534 | 1.4534 | 0.7790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0789 | 1.0789 | 0.7509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1662 | 1.1662 | 0.7837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3705 | 0.3705 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3529 | 0.3529 | 0.1412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3794 | 0.3794 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4004 | 0.4004 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3130 | 0.3130 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3128 | 0.3128 | 0.1251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3179 | 0.3179 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3311 | 0.3311 | 0.1324 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3228 | 0.3228 | 0.1582 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3390 | 0.3390 | 0.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3285 | 0.3285 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3629 | 0.3629 | 0.1452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7282 | 1.3659 | 1.3659 | 1.3659 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4321 | 1.3482 | 1.3482 | 1.3482 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6694 | 1.4157 | 1.4157 | 1.4157 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 18.33 |
Number of hours cooling loads not met | 454.50 |
Number of hours not met | 472.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 2.09 | 43312.35 | 0.01 | 2416.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 701.90 | 82384.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.30 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.63 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.04 | 14235.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 113.19 | 9539.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1868.31 |
Natural Gas | 0.00 | 113.20 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1981.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.27 |
Space Heating | 0.42 |
Space Cooling | 140.88 |
Fans (All) | 19.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 375.00 |
Subtotal | 375.00 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 22.72 |
Miscellaneous (All) | 22.72 |
Subtotal | 22.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.16 |
Space Heating | 0.11 |
Space Cooling | 35.42 |
Fans (All) | 4.85 |
Service Water Heating | 5.71 |
Receptacle Equipment | 35.60 |
Miscellaneous | 3.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8402.00 | 358.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8720.50 | 39.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8345.50 | 414.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8217.83 | 542.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8149.17 | 610.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8105.50 | 654.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8615.50 | 144.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8295.67 | 464.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8240.67 | 519.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8111.67 | 648.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8401.83 | 358.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8256.83 | 503.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8195.83 | 564.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8092.83 | 667.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8262.83 | 497.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
Min | 8092.83 | 2.17 | 0.00 | 0.00 | 0.00 |
Max | 8757.83 | 667.17 | 0.00 | 0.00 | 0.00 |
Average | 8369.19 | 390.81 | 0.00 | 0.00 | 0.00 |
Sum | 150645.33 | 7034.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128216.00 | 88.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24895.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.00 | 88.00 | 0.00 | 0.00 | 0.00 |
Average | 34137.10 | 6.23 | 0.00 | 0.00 | 0.00 |
Sum | 614467.83 | 112.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7727.00 | 1033.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8586.00 | 174.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8623.50 | 136.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6056.17 | 2703.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6094.50 | 2665.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5923.00 | 2837.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6089.50 | 2670.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6371.00 | 2389.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6205.17 | 2554.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5158.17 | 3601.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6163.50 | 2596.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6004.83 | 2755.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6043.17 | 2716.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5859.50 | 2900.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5995.67 | 2764.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6061.83 | 2698.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6502.17 | 2257.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6713.33 | 2046.67 | 0.00 | 0.00 | 0.00 |
Min | 5158.17 | 136.50 | 0.00 | 0.00 | 0.00 |
Max | 8623.50 | 3601.83 | 0.00 | 0.00 | 0.00 |
Average | 6454.33 | 2305.67 | 0.00 | 0.00 | 0.00 |
Sum | 116178.00 | 41502.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127904.17 | 399.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128246.33 | 57.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128274.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24801.00 | 108.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24798.17 | 110.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24863.50 | 45.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20267.33 | 4641.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24803.17 | 105.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24800.83 | 108.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128274.00 | 4641.67 | 0.00 | 0.00 | 0.00 |
Average | 33831.80 | 311.54 | 0.00 | 0.00 | 0.00 |
Sum | 608972.33 | 5607.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237157E+11 | 39221.08 | 02-JAN-07:03 | 19.08 | 19.01 | 0.199097E+10 | 2606.73 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.218145E+11 | 36171.24 | 11-FEB-06:03 | 23.90 | 22.27 | 0.180605E+10 | 2606.69 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.261273E+11 | 33850.63 | 27-MAR-05:13 | 20.40 | 20.06 | 0.215847E+10 | 2606.66 | 01-MAR-10:09 | 20.40 | 20.06 |
April | 0.255853E+11 | 42085.40 | 13-APR-05:02 | 24.40 | 22.09 | 0.191689E+10 | 2606.66 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.288126E+11 | 46538.37 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207642E+10 | 2606.54 | 30-MAY-13:20 | 26.33 | 24.24 |
June | 0.291650E+11 | 44451.33 | 20-JUN-04:02 | 24.90 | 23.73 | 0.206954E+10 | 2606.54 | 05-JUN-13:30 | 24.90 | 23.73 |
July | 0.288558E+11 | 44391.41 | 06-JUL-04:03 | 23.90 | 22.27 | 0.192272E+10 | 2606.54 | 14-JUL-13:30 | 28.90 | 25.45 |
August | 0.305435E+11 | 43802.80 | 30-AUG-04:03 | 25.50 | 23.18 | 0.215891E+10 | 2606.55 | 07-AUG-13:30 | 25.50 | 23.18 |
September | 0.284163E+11 | 44002.67 | 07-SEP-04:03 | 24.40 | 22.81 | 0.191659E+10 | 2606.54 | 11-SEP-13:30 | 29.20 | 24.70 |
October | 0.286695E+11 | 46486.25 | 23-OCT-05:03 | 23.72 | 21.83 | 0.199434E+10 | 2606.55 | 10-OCT-13:20 | 23.72 | 21.83 |
November | 0.259815E+11 | 43439.45 | 20-NOV-05:03 | 24.40 | 20.52 | 0.197515E+10 | 2606.70 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.235056E+11 | 36515.71 | 11-DEC-06:13 | 22.20 | 21.45 | 0.192072E+10 | 2606.64 | 15-DEC-14:09 | 19.08 | 14.19 |
Annual Sum or Average | 0.321193E+12 | 0.239068E+11 | ||||||||
Minimum of Months | 0.218145E+11 | 33850.63 | 19.08 | 19.01 | 0.180605E+10 | 2606.54 | 19.08 | 14.19 | ||
Maximum of Months | 0.305435E+11 | 46538.37 | 25.50 | 23.73 | 0.215891E+10 | 2606.73 | 29.20 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276669E+10 | 8045.50 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.341290E+10 | 8000.31 | 22-FEB-15:30 | 27.80 | 14.62 | 0.00 | 0.00 | 01-FEB-00:10 | 27.80 | 14.62 |
March | 0.457697E+10 | 9221.17 | 27-MAR-15:00 | 27.80 | 22.40 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 22.40 |
April | 0.583534E+10 | 10136.21 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.739575E+10 | 11258.54 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.772396E+10 | 10535.43 | 09-JUN-13:40 | 30.93 | 24.93 | 0.00 | 0.00 | 01-JUN-00:10 | 30.93 | 24.93 |
July | 0.848625E+10 | 11672.66 | 28-JUL-15:30 | 35.00 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.05 |
August | 0.776410E+10 | 11155.04 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.720685E+10 | 10887.15 | 18-SEP-13:50 | 31.10 | 24.96 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 24.96 |
October | 0.611985E+10 | 10560.24 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.439129E+10 | 8614.83 | 10-NOV-14:30 | 28.90 | 24.27 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.27 |
December | 0.299270E+10 | 7484.49 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.686727E+11 | 0.00 | ||||||||
Minimum of Months | 0.276669E+10 | 7484.49 | 27.40 | 14.62 | 0.00 | 0.00 | 27.40 | 14.62 | ||
Maximum of Months | 0.848625E+10 | 11672.66 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165783E+10 | 3883.46 | 02-JAN-16:30 | 25.30 | 20.50 | 0.00 | 0.00 | 01-JAN-00:10 | 25.30 | 20.50 |
February | 0.183730E+10 | 3276.69 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.250230E+10 | 3940.59 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.308981E+10 | 4181.53 | 17-APR-15:40 | 31.87 | 20.12 | 0.00 | 0.00 | 01-APR-00:10 | 31.87 | 20.12 |
May | 0.403947E+10 | 4631.05 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.437413E+10 | 4420.85 | 26-JUN-12:02 | 30.68 | 25.17 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 25.17 |
July | 0.456938E+10 | 5012.31 | 31-JUL-14:40 | 31.50 | 24.76 | 0.00 | 0.00 | 01-JUL-00:10 | 31.50 | 24.76 |
August | 0.451319E+10 | 4776.84 | 21-AUG-16:00 | 32.20 | 26.46 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 26.46 |
September | 0.421093E+10 | 4830.04 | 18-SEP-15:30 | 31.70 | 25.48 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 25.48 |
October | 0.388665E+10 | 4611.47 | 02-OCT-15:10 | 30.92 | 25.05 | 0.00 | 0.00 | 01-OCT-00:10 | 30.92 | 25.05 |
November | 0.276124E+10 | 4181.40 | 06-NOV-16:20 | 27.80 | 20.13 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.13 |
December | 0.184485E+10 | 3462.55 | 11-DEC-15:30 | 24.45 | 17.75 | 0.00 | 0.00 | 01-DEC-00:10 | 24.45 | 17.75 |
Annual Sum or Average | 0.392871E+11 | 0.00 | ||||||||
Minimum of Months | 0.165783E+10 | 3276.69 | 24.45 | 14.07 | 0.00 | 0.00 | 24.45 | 14.07 | ||
Maximum of Months | 0.456938E+10 | 5012.31 | 34.15 | 26.46 | 0.00 | 0.00 | 34.15 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232489E+10 | 4606.63 | 02-JAN-16:10 | 25.50 | 20.58 | 0.00 | 0.00 | 01-JAN-00:10 | 25.50 | 20.58 |
February | 0.238723E+10 | 3985.60 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.307987E+10 | 4389.71 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.350539E+10 | 4560.12 | 17-APR-15:50 | 31.78 | 20.21 | 0.00 | 0.00 | 01-APR-00:10 | 31.78 | 20.21 |
May | 0.450142E+10 | 5384.27 | 22-MAY-12:08 | 33.48 | 23.09 | 0.00 | 0.00 | 01-MAY-00:10 | 33.48 | 23.09 |
June | 0.481871E+10 | 4911.52 | 26-JUN-12:10 | 30.68 | 25.17 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 25.17 |
July | 0.501268E+10 | 5659.63 | 31-JUL-12:10 | 32.93 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 25.13 |
August | 0.511681E+10 | 5172.99 | 07-AUG-12:10 | 30.92 | 24.97 | 0.00 | 0.00 | 01-AUG-00:10 | 30.92 | 24.97 |
September | 0.477467E+10 | 5239.71 | 11-SEP-12:10 | 31.52 | 24.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.52 | 24.53 |
October | 0.456916E+10 | 5084.82 | 10-OCT-12:10 | 28.38 | 23.66 | 0.00 | 0.00 | 01-OCT-00:10 | 28.38 | 23.66 |
November | 0.352052E+10 | 4717.91 | 06-NOV-16:10 | 27.80 | 20.07 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.07 |
December | 0.245305E+10 | 4058.29 | 11-DEC-16:10 | 23.72 | 17.48 | 0.00 | 0.00 | 01-DEC-00:10 | 23.72 | 17.48 |
Annual Sum or Average | 0.460644E+11 | 0.00 | ||||||||
Minimum of Months | 0.232489E+10 | 3985.60 | 23.72 | 14.07 | 0.00 | 0.00 | 23.72 | 14.07 | ||
Maximum of Months | 0.511681E+10 | 5659.63 | 33.48 | 25.17 | 0.00 | 0.00 | 33.48 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159983E+11 | 23920.38 | 14-JAN-06:03 | 23.62 | 21.60 | 0.195267E+10 | 2606.65 | 12-JAN-10:09 | 23.62 | 21.60 |
February | 0.151502E+11 | 22510.69 | 11-FEB-06:03 | 23.90 | 22.27 | 0.177846E+10 | 2606.67 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.184050E+11 | 20521.56 | 27-MAR-05:13 | 20.40 | 20.06 | 0.213456E+10 | 2606.64 | 01-MAR-10:09 | 20.40 | 20.06 |
April | 0.188361E+11 | 31241.13 | 12-APR-05:03 | 24.50 | 22.52 | 0.190576E+10 | 2606.65 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.213675E+11 | 34938.38 | 08-MAY-05:03 | 23.90 | 19.12 | 0.206987E+10 | 2606.54 | 30-MAY-13:09 | 25.97 | 24.15 |
June | 0.218941E+11 | 32536.16 | 20-JUN-04:02 | 24.90 | 23.73 | 0.206539E+10 | 2606.54 | 05-JUN-13:09 | 24.90 | 23.73 |
July | 0.220147E+11 | 32798.39 | 25-JUL-04:02 | 25.60 | 24.04 | 0.191861E+10 | 2606.54 | 31-JUL-13:09 | 31.47 | 25.13 |
August | 0.226924E+11 | 32275.61 | 08-AUG-04:02 | 26.10 | 23.70 | 0.215427E+10 | 2606.54 | 07-AUG-13:30 | 26.10 | 23.70 |
September | 0.211904E+11 | 32761.69 | 20-SEP-04:02 | 24.40 | 23.23 | 0.191183E+10 | 2606.54 | 11-SEP-13:09 | 24.40 | 23.23 |
October | 0.209520E+11 | 35931.58 | 02-OCT-04:04 | 26.70 | 25.03 | 0.198772E+10 | 2606.57 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.181361E+11 | 31576.75 | 03-NOV-05:03 | 24.40 | 22.49 | 0.196261E+10 | 2606.64 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.161490E+11 | 30920.42 | 09-DEC-06:03 | 24.90 | 22.63 | 0.188254E+10 | 2606.62 | 04-DEC-10:30 | 24.90 | 22.63 |
Annual Sum or Average | 0.232786E+12 | 0.237243E+11 | ||||||||
Minimum of Months | 0.151502E+11 | 20521.56 | 20.40 | 19.12 | 0.177846E+10 | 2606.54 | 19.68 | 13.91 | ||
Maximum of Months | 0.226924E+11 | 35931.58 | 26.70 | 25.03 | 0.215427E+10 | 2606.67 | 31.47 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154472E+11 | 19168.02 | 02-JAN-15:00 | 28.90 | 23.37 | 0.188447E+10 | 2606.60 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.149818E+11 | 17557.05 | 21-FEB-16:00 | 26.10 | 14.02 | 0.174142E+10 | 2606.60 | 16-FEB-10:09 | 26.10 | 14.02 |
March | 0.186774E+11 | 19630.62 | 27-MAR-15:40 | 27.40 | 22.26 | 0.209825E+10 | 2606.64 | 02-MAR-14:09 | 27.40 | 22.26 |
April | 0.196894E+11 | 34077.99 | 13-APR-05:02 | 24.40 | 22.09 | 0.189719E+10 | 2606.66 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.228937E+11 | 35508.00 | 23-MAY-04:02 | 24.90 | 21.94 | 0.206771E+10 | 2606.55 | 08-MAY-09:09 | 24.90 | 21.94 |
June | 0.236901E+11 | 36383.60 | 19-JUN-04:02 | 24.40 | 22.82 | 0.206513E+10 | 2606.54 | 05-JUN-13:09 | 24.40 | 22.82 |
July | 0.240025E+11 | 35902.46 | 24-JUL-04:02 | 24.32 | 23.63 | 0.191863E+10 | 2606.54 | 25-JUL-13:09 | 32.30 | 25.97 |
August | 0.242361E+11 | 35176.09 | 07-AUG-04:02 | 25.68 | 24.34 | 0.215269E+10 | 2606.54 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.224982E+11 | 35232.47 | 25-SEP-04:02 | 24.40 | 22.60 | 0.191016E+10 | 2606.54 | 11-SEP-13:00 | 24.40 | 22.60 |
October | 0.214403E+11 | 35834.51 | 10-OCT-04:02 | 24.32 | 22.47 | 0.198249E+10 | 2606.64 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.181149E+11 | 34034.58 | 20-NOV-06:03 | 24.40 | 20.29 | 0.194181E+10 | 2606.62 | 02-NOV-09:09 | 24.40 | 20.29 |
December | 0.157916E+11 | 20423.57 | 09-DEC-06:03 | 24.90 | 22.63 | 0.182178E+10 | 2606.63 | 05-DEC-10:20 | 24.90 | 22.63 |
Annual Sum or Average | 0.241463E+12 | 0.234817E+11 | ||||||||
Minimum of Months | 0.149818E+11 | 17557.05 | 24.32 | 14.02 | 0.174142E+10 | 2606.54 | 24.40 | 14.02 | ||
Maximum of Months | 0.242361E+11 | 36383.60 | 28.90 | 24.34 | 0.215269E+10 | 2606.66 | 32.30 | 25.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317702E+10 | 5137.76 | 02-JAN-15:00 | 28.90 | 23.37 | 0.383298E+09 | 549.49 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.338787E+10 | 5254.44 | 17-FEB-14:10 | 26.70 | 21.67 | 0.360881E+09 | 549.49 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.439302E+10 | 5786.08 | 27-MAR-15:00 | 27.80 | 22.40 | 0.432966E+09 | 549.49 | 02-MAR-14:09 | 27.80 | 22.40 |
April | 0.518630E+10 | 8501.99 | 16-APR-16:42 | 31.02 | 22.09 | 0.399312E+09 | 549.49 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.689269E+10 | 12465.03 | 29-MAY-16:02 | 33.03 | 24.50 | 0.437288E+09 | 549.47 | 01-MAY-13:00 | 33.03 | 24.50 |
June | 0.759074E+10 | 12365.35 | 25-JUN-15:43 | 29.08 | 24.13 | 0.436641E+09 | 549.47 | 21-JUN-13:00 | 29.08 | 24.13 |
July | 0.778841E+10 | 12820.01 | 09-JUL-16:02 | 30.92 | 25.00 | 0.406062E+09 | 549.47 | 06-JUL-13:00 | 30.92 | 25.00 |
August | 0.741752E+10 | 12538.05 | 20-AUG-12:53 | 32.20 | 25.55 | 0.455106E+09 | 549.47 | 07-AUG-13:00 | 32.20 | 25.55 |
September | 0.667531E+10 | 11830.56 | 04-SEP-13:23 | 30.00 | 24.33 | 0.403780E+09 | 549.47 | 05-SEP-13:09 | 25.73 | 23.35 |
October | 0.573393E+10 | 8902.45 | 30-OCT-04:02 | 26.28 | 24.93 | 0.418605E+09 | 549.49 | 18-OCT-09:39 | 26.28 | 24.93 |
November | 0.442435E+10 | 6064.71 | 30-NOV-06:03 | 25.60 | 24.37 | 0.406768E+09 | 549.48 | 14-NOV-14:20 | 25.60 | 24.37 |
December | 0.336069E+10 | 5048.93 | 08-DEC-14:10 | 27.70 | 22.74 | 0.372511E+09 | 549.48 | 01-DEC-10:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.660278E+11 | 0.491322E+10 | ||||||||
Minimum of Months | 0.317702E+10 | 5048.93 | 25.60 | 21.67 | 0.360881E+09 | 549.47 | 25.00 | 16.72 | ||
Maximum of Months | 0.778841E+10 | 12820.01 | 33.03 | 25.55 | 0.455106E+09 | 549.49 | 33.03 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288680E+10 | 9835.35 | 01-JAN-10:32 | 26.13 | 21.45 | 0.253255E+09 | 347.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.314648E+10 | 5019.30 | 28-FEB-10:10 | 24.40 | 16.25 | 0.233469E+09 | 347.88 | 23-FEB-10:39 | 24.40 | 16.25 |
March | 0.417815E+10 | 6665.52 | 27-MAR-10:30 | 25.85 | 21.67 | 0.282650E+09 | 347.87 | 02-MAR-14:09 | 25.85 | 21.67 |
April | 0.494917E+10 | 12166.63 | 09-APR-09:02 | 24.27 | 18.85 | 0.253725E+09 | 347.88 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.586622E+10 | 11424.71 | 14-MAY-10:23 | 29.15 | 23.76 | 0.276612E+09 | 347.86 | 31-MAY-09:39 | 30.53 | 23.99 |
June | 0.614564E+10 | 12935.01 | 11-JUN-09:12 | 30.20 | 24.17 | 0.276336E+09 | 347.86 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.637960E+10 | 12391.88 | 23-JUL-09:52 | 30.00 | 24.68 | 0.257111E+09 | 347.86 | 25-JUL-09:00 | 32.80 | 25.50 |
August | 0.612108E+10 | 12198.99 | 06-AUG-10:43 | 30.82 | 24.91 | 0.287903E+09 | 347.86 | 08-AUG-09:39 | 31.50 | 24.58 |
September | 0.566795E+10 | 11243.09 | 10-SEP-10:22 | 30.30 | 24.60 | 0.255577E+09 | 347.86 | 14-SEP-09:39 | 29.27 | 25.00 |
October | 0.507791E+10 | 9283.42 | 09-OCT-11:43 | 28.95 | 24.01 | 0.265020E+09 | 347.87 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.381719E+10 | 5854.21 | 07-NOV-09:50 | 25.32 | 21.18 | 0.259851E+09 | 347.87 | 02-NOV-09:09 | 25.32 | 21.18 |
December | 0.288320E+10 | 4901.97 | 08-DEC-10:30 | 26.65 | 22.70 | 0.240052E+09 | 347.88 | 04-DEC-10:00 | 26.65 | 22.70 |
Annual Sum or Average | 0.571194E+11 | 0.314156E+10 | ||||||||
Minimum of Months | 0.288320E+10 | 4901.97 | 24.27 | 16.25 | 0.233469E+09 | 347.86 | 21.70 | 15.05 | ||
Maximum of Months | 0.637960E+10 | 12935.01 | 30.82 | 24.91 | 0.287903E+09 | 347.88 | 32.80 | 25.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614321E+10 | 14210.13 | 01-JAN-13:12 | 26.83 | 21.65 | 0.407673E+09 | 595.09 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.589355E+10 | 13694.42 | 19-FEB-13:32 | 26.83 | 21.86 | 0.372725E+09 | 575.98 | 21-FEB-14:30 | 25.85 | 14.25 |
March | 0.646492E+10 | 13530.00 | 26-MAR-13:43 | 27.70 | 22.37 | 0.442799E+09 | 550.15 | 01-MAR-14:30 | 27.70 | 22.37 |
April | 0.613127E+10 | 12929.43 | 16-APR-12:02 | 30.78 | 21.05 | 0.399966E+09 | 549.49 | 19-APR-13:00 | 23.90 | 15.56 |
May | 0.688156E+10 | 12715.15 | 29-MAY-16:02 | 33.03 | 24.50 | 0.436999E+09 | 549.47 | 01-MAY-13:00 | 33.03 | 24.50 |
June | 0.724501E+10 | 11428.72 | 25-JUN-15:43 | 29.08 | 24.13 | 0.436395E+09 | 549.47 | 21-JUN-13:00 | 29.08 | 24.13 |
July | 0.760878E+10 | 13045.91 | 09-JUL-16:02 | 30.92 | 25.00 | 0.405864E+09 | 549.47 | 06-JUL-13:00 | 30.92 | 25.00 |
August | 0.797159E+10 | 13264.79 | 20-AUG-12:53 | 32.20 | 25.55 | 0.455166E+09 | 549.47 | 07-AUG-13:00 | 32.20 | 25.55 |
September | 0.820744E+10 | 13329.85 | 24-SEP-13:02 | 31.10 | 23.93 | 0.404235E+09 | 555.77 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.853363E+10 | 13744.68 | 29-OCT-12:42 | 30.10 | 25.68 | 0.420941E+09 | 572.36 | 25-OCT-13:20 | 30.10 | 25.68 |
November | 0.735085E+10 | 13605.26 | 23-NOV-14:23 | 27.20 | 24.01 | 0.414927E+09 | 594.96 | 07-NOV-14:09 | 27.20 | 24.01 |
December | 0.630585E+10 | 13743.39 | 03-DEC-13:42 | 24.32 | 18.38 | 0.393027E+09 | 595.22 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.847376E+11 | 0.499072E+10 | ||||||||
Minimum of Months | 0.589355E+10 | 11428.72 | 24.32 | 18.38 | 0.372725E+09 | 549.47 | 23.90 | 14.25 | ||
Maximum of Months | 0.853363E+10 | 14210.13 | 33.03 | 25.68 | 0.455166E+09 | 595.22 | 33.03 | 25.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307062E+10 | 5675.79 | 03-JAN-15:40 | 26.70 | 20.74 | 0.237476E+09 | 347.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.330545E+10 | 14242.87 | 20-FEB-17:22 | 25.85 | 17.65 | 0.223553E+09 | 347.85 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.439284E+10 | 14336.48 | 12-MAR-17:02 | 24.13 | 18.70 | 0.269646E+09 | 347.85 | 02-MAR-14:09 | 24.13 | 18.70 |
April | 0.497985E+10 | 13829.71 | 09-APR-16:22 | 26.95 | 18.54 | 0.249572E+09 | 347.84 | 19-APR-13:00 | 23.90 | 15.56 |
May | 0.581966E+10 | 14071.22 | 29-MAY-16:42 | 31.97 | 24.40 | 0.275069E+09 | 347.83 | 23-MAY-13:00 | 31.97 | 24.40 |
June | 0.575864E+10 | 13405.49 | 10-JUN-17:05 | 30.60 | 24.10 | 0.275248E+09 | 347.84 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.616216E+10 | 14619.55 | 09-JUL-16:02 | 30.92 | 25.00 | 0.256085E+09 | 347.83 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.610560E+10 | 13857.29 | 20-AUG-16:12 | 30.60 | 24.86 | 0.287039E+09 | 347.83 | 08-AUG-09:00 | 30.60 | 24.86 |
September | 0.540300E+10 | 14036.29 | 10-SEP-15:42 | 31.10 | 25.01 | 0.254039E+09 | 347.83 | 07-SEP-13:00 | 31.10 | 25.01 |
October | 0.498803E+10 | 14166.10 | 15-OCT-15:52 | 28.90 | 20.73 | 0.262794E+09 | 347.85 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.392989E+10 | 8188.77 | 19-NOV-15:43 | 26.70 | 20.63 | 0.253516E+09 | 347.84 | 14-NOV-14:00 | 26.70 | 20.63 |
December | 0.325369E+10 | 8401.68 | 10-DEC-15:22 | 28.60 | 22.59 | 0.231550E+09 | 347.84 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.571694E+11 | 0.307559E+10 | ||||||||
Minimum of Months | 0.307062E+10 | 5675.79 | 24.13 | 17.65 | 0.223553E+09 | 347.83 | 21.70 | 13.99 | ||
Maximum of Months | 0.616216E+10 | 14619.55 | 31.97 | 25.01 | 0.287039E+09 | 347.85 | 31.97 | 25.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344914E+10 | 4677.49 | 02-JAN-15:00 | 28.90 | 23.37 | 0.399332E+09 | 549.48 | 20-JAN-14:00 | 19.40 | 12.60 |
February | 0.336909E+10 | 4594.27 | 17-FEB-13:40 | 26.70 | 21.06 | 0.369368E+09 | 549.48 | 28-FEB-10:00 | 24.40 | 16.11 |
March | 0.408650E+10 | 4775.44 | 06-MAR-14:10 | 24.90 | 22.15 | 0.439144E+09 | 549.48 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.458022E+10 | 5780.26 | 17-APR-15:20 | 32.03 | 19.94 | 0.401162E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.622452E+10 | 8375.18 | 24-MAY-05:02 | 23.98 | 22.69 | 0.437374E+09 | 549.47 | 22-MAY-13:00 | 23.98 | 22.69 |
June | 0.692442E+10 | 8693.76 | 26-JUN-04:02 | 25.60 | 24.44 | 0.436381E+09 | 549.47 | 21-JUN-13:00 | 25.60 | 24.44 |
July | 0.728094E+10 | 8508.75 | 17-JUL-04:02 | 26.02 | 23.69 | 0.405859E+09 | 549.47 | 03-JUL-13:09 | 26.02 | 23.69 |
August | 0.726153E+10 | 8560.44 | 07-AUG-04:02 | 25.68 | 24.34 | 0.455348E+09 | 549.47 | 07-AUG-13:30 | 28.60 | 24.70 |
September | 0.666135E+10 | 8441.86 | 25-SEP-04:02 | 24.40 | 22.60 | 0.404269E+09 | 549.47 | 05-SEP-13:09 | 24.40 | 22.60 |
October | 0.595675E+10 | 7999.80 | 26-OCT-05:02 | 23.80 | 22.28 | 0.420082E+09 | 549.47 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.466082E+10 | 5439.88 | 03-NOV-13:50 | 29.40 | 24.41 | 0.413128E+09 | 549.48 | 14-NOV-10:09 | 22.30 | 16.07 |
December | 0.365098E+10 | 4817.55 | 01-DEC-14:10 | 26.10 | 19.79 | 0.389170E+09 | 549.49 | 04-DEC-10:09 | 21.88 | 17.23 |
Annual Sum or Average | 0.641063E+11 | 0.497062E+10 | ||||||||
Minimum of Months | 0.336909E+10 | 4594.27 | 23.80 | 19.79 | 0.369368E+09 | 549.47 | 19.40 | 12.60 | ||
Maximum of Months | 0.728094E+10 | 8693.76 | 32.03 | 24.44 | 0.455348E+09 | 549.50 | 28.60 | 24.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307627E+10 | 9240.14 | 01-JAN-10:02 | 25.28 | 21.21 | 0.261701E+09 | 347.89 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.310866E+10 | 4795.91 | 28-FEB-10:10 | 24.40 | 16.25 | 0.238103E+09 | 347.88 | 23-FEB-10:09 | 24.40 | 16.25 |
March | 0.393759E+10 | 5891.76 | 27-MAR-10:30 | 25.85 | 21.67 | 0.285647E+09 | 347.88 | 01-MAR-10:09 | 25.85 | 21.67 |
April | 0.450442E+10 | 10906.65 | 09-APR-10:12 | 26.30 | 18.69 | 0.255136E+09 | 347.88 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.538850E+10 | 8106.09 | 14-MAY-10:23 | 29.15 | 23.76 | 0.277077E+09 | 347.86 | 31-MAY-09:39 | 30.53 | 23.99 |
June | 0.568156E+10 | 11151.53 | 11-JUN-09:12 | 30.20 | 24.17 | 0.276481E+09 | 347.86 | 14-JUN-09:39 | 28.53 | 23.70 |
July | 0.601671E+10 | 11565.53 | 04-JUL-10:02 | 30.78 | 24.92 | 0.257330E+09 | 347.86 | 25-JUL-09:30 | 31.40 | 25.40 |
August | 0.600630E+10 | 10142.34 | 06-AUG-10:43 | 30.82 | 24.91 | 0.288459E+09 | 347.86 | 08-AUG-09:39 | 31.50 | 24.58 |
September | 0.566366E+10 | 11133.52 | 10-SEP-09:32 | 29.43 | 24.83 | 0.256259E+09 | 347.86 | 14-SEP-09:39 | 29.27 | 25.00 |
October | 0.522330E+10 | 11059.84 | 09-OCT-10:12 | 30.33 | 23.87 | 0.266295E+09 | 347.86 | 11-OCT-09:30 | 28.85 | 24.46 |
November | 0.398048E+10 | 5558.09 | 07-NOV-09:30 | 24.75 | 21.38 | 0.262657E+09 | 347.88 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.301233E+10 | 4690.70 | 08-DEC-10:30 | 26.65 | 22.70 | 0.250602E+09 | 347.87 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.555998E+11 | 0.317575E+10 | ||||||||
Minimum of Months | 0.301233E+10 | 4690.70 | 24.40 | 16.25 | 0.238103E+09 | 347.86 | 19.08 | 13.91 | ||
Maximum of Months | 0.601671E+10 | 11565.53 | 30.82 | 24.92 | 0.288459E+09 | 347.89 | 31.50 | 25.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602567E+10 | 11951.56 | 01-JAN-13:22 | 26.65 | 21.70 | 0.412826E+09 | 629.72 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.594261E+10 | 11337.26 | 26-FEB-14:13 | 25.60 | 16.51 | 0.376959E+09 | 595.82 | 22-FEB-13:09 | 25.60 | 16.51 |
March | 0.604227E+10 | 11138.31 | 26-MAR-13:53 | 27.80 | 22.40 | 0.442136E+09 | 558.10 | 13-MAR-12:09 | 27.80 | 22.40 |
April | 0.605706E+10 | 9978.83 | 17-APR-16:10 | 31.60 | 20.14 | 0.401544E+09 | 601.75 | 13-APR-12:09 | 31.60 | 20.14 |
May | 0.750812E+10 | 10722.04 | 22-MAY-12:00 | 33.30 | 23.06 | 0.439544E+09 | 664.36 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.805452E+10 | 9921.80 | 09-JUN-12:00 | 31.10 | 24.24 | 0.438849E+09 | 606.80 | 09-JUN-12:09 | 31.02 | 24.35 |
July | 0.868754E+10 | 10930.68 | 27-JUL-16:50 | 34.50 | 24.87 | 0.410415E+09 | 673.46 | 31-JUL-12:09 | 32.93 | 25.13 |
August | 0.952953E+10 | 10940.39 | 20-AUG-12:53 | 32.20 | 25.55 | 0.461172E+09 | 669.65 | 23-AUG-12:09 | 33.40 | 24.17 |
September | 0.936536E+10 | 11482.48 | 10-SEP-13:32 | 31.10 | 24.95 | 0.413290E+09 | 657.15 | 11-SEP-12:09 | 31.52 | 24.53 |
October | 0.974292E+10 | 12142.17 | 29-OCT-12:32 | 30.20 | 25.52 | 0.433264E+09 | 667.76 | 03-OCT-12:09 | 30.20 | 25.52 |
November | 0.817908E+10 | 11785.04 | 19-NOV-14:12 | 26.70 | 21.06 | 0.423507E+09 | 635.69 | 08-NOV-13:09 | 26.70 | 21.06 |
December | 0.626178E+10 | 11436.05 | 03-DEC-11:23 | 22.75 | 18.38 | 0.398218E+09 | 618.49 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.913965E+11 | 0.505173E+10 | ||||||||
Minimum of Months | 0.594261E+10 | 9921.80 | 22.75 | 16.51 | 0.376959E+09 | 558.10 | 25.60 | 16.51 | ||
Maximum of Months | 0.974292E+10 | 12142.17 | 34.50 | 25.55 | 0.461172E+09 | 673.46 | 33.48 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301117E+10 | 5060.14 | 02-JAN-16:30 | 25.30 | 20.50 | 0.253836E+09 | 347.84 | 20-JAN-14:00 | 19.40 | 12.60 |
February | 0.307810E+10 | 11798.51 | 20-FEB-17:22 | 25.85 | 17.65 | 0.234328E+09 | 347.85 | 21-FEB-10:09 | 19.78 | 16.20 |
March | 0.395086E+10 | 8706.34 | 12-MAR-17:22 | 23.60 | 18.78 | 0.279662E+09 | 347.84 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.441140E+10 | 10746.34 | 02-APR-16:52 | 25.60 | 18.06 | 0.254531E+09 | 347.85 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.524625E+10 | 11600.68 | 29-MAY-16:42 | 31.97 | 24.40 | 0.276881E+09 | 347.84 | 23-MAY-13:00 | 31.97 | 24.40 |
June | 0.518726E+10 | 10112.85 | 10-JUN-17:05 | 30.60 | 24.10 | 0.276194E+09 | 347.84 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.569656E+10 | 11612.30 | 04-JUL-16:01 | 31.42 | 25.15 | 0.257045E+09 | 347.84 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.591605E+10 | 11499.36 | 20-AUG-16:12 | 30.60 | 24.86 | 0.288398E+09 | 347.84 | 08-AUG-09:00 | 30.60 | 24.86 |
September | 0.528106E+10 | 11754.31 | 10-SEP-15:31 | 31.10 | 25.07 | 0.256070E+09 | 347.84 | 07-SEP-13:00 | 31.10 | 25.07 |
October | 0.503362E+10 | 11743.23 | 09-OCT-16:52 | 28.90 | 23.69 | 0.266155E+09 | 347.84 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.392009E+10 | 6515.01 | 07-NOV-16:30 | 28.05 | 22.28 | 0.261409E+09 | 347.84 | 14-NOV-10:00 | 22.80 | 16.11 |
December | 0.324860E+10 | 6052.68 | 06-DEC-16:30 | 25.85 | 22.11 | 0.246649E+09 | 347.84 | 04-DEC-10:09 | 25.85 | 22.11 |
Annual Sum or Average | 0.539810E+11 | 0.315116E+10 | ||||||||
Minimum of Months | 0.301117E+10 | 5060.14 | 23.60 | 17.65 | 0.234328E+09 | 347.84 | 19.40 | 12.60 | ||
Maximum of Months | 0.591605E+10 | 11798.51 | 31.97 | 25.15 | 0.288398E+09 | 347.85 | 31.97 | 25.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328970E+10 | 4859.61 | 02-JAN-15:00 | 28.90 | 23.37 | 0.395699E+09 | 549.48 | 10-JAN-14:39 | 22.20 | 16.44 |
February | 0.339264E+10 | 4864.91 | 17-FEB-13:40 | 26.70 | 21.06 | 0.368387E+09 | 549.49 | 23-FEB-10:00 | 24.40 | 18.34 |
March | 0.429418E+10 | 5230.48 | 28-MAR-13:30 | 27.20 | 20.57 | 0.440128E+09 | 549.48 | 02-MAR-14:09 | 27.20 | 20.57 |
April | 0.491494E+10 | 6359.92 | 17-APR-15:00 | 32.20 | 19.76 | 0.401639E+09 | 549.49 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.643970E+10 | 10550.47 | 29-MAY-16:02 | 33.03 | 24.50 | 0.437612E+09 | 549.47 | 22-MAY-13:00 | 33.03 | 24.50 |
June | 0.705387E+10 | 9000.95 | 12-JUN-04:02 | 25.60 | 24.44 | 0.436622E+09 | 549.47 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.718213E+10 | 9039.26 | 17-JUL-04:02 | 26.02 | 23.69 | 0.406039E+09 | 549.47 | 03-JUL-13:09 | 26.02 | 23.69 |
August | 0.695875E+10 | 9065.11 | 20-AUG-12:53 | 32.20 | 25.55 | 0.455313E+09 | 549.47 | 08-AUG-09:00 | 32.20 | 25.55 |
September | 0.627465E+10 | 8824.10 | 09-SEP-05:03 | 27.80 | 24.20 | 0.404132E+09 | 549.47 | 05-SEP-13:09 | 27.80 | 24.20 |
October | 0.556421E+10 | 8131.07 | 10-OCT-04:02 | 24.32 | 22.47 | 0.419654E+09 | 549.48 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.438337E+10 | 6832.73 | 30-NOV-06:03 | 25.60 | 24.37 | 0.411172E+09 | 549.48 | 14-NOV-14:09 | 25.60 | 24.37 |
December | 0.342766E+10 | 4713.11 | 07-DEC-14:30 | 26.95 | 22.97 | 0.383866E+09 | 549.49 | 04-DEC-10:09 | 26.95 | 22.97 |
Annual Sum or Average | 0.631758E+11 | 0.496026E+10 | ||||||||
Minimum of Months | 0.328970E+10 | 4713.11 | 24.32 | 19.76 | 0.368387E+09 | 549.47 | 22.20 | 16.44 | ||
Maximum of Months | 0.718213E+10 | 10550.47 | 33.03 | 25.55 | 0.455313E+09 | 549.49 | 33.03 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296578E+10 | 11172.39 | 01-JAN-10:13 | 25.57 | 21.29 | 0.189038E+09 | 338.74 | 27-JAN-11:20 | 22.07 | 15.40 |
February | 0.312127E+10 | 5412.68 | 28-FEB-09:50 | 24.22 | 16.33 | 0.173561E+09 | 338.72 | 27-FEB-11:09 | 24.22 | 16.33 |
March | 0.407602E+10 | 6462.01 | 27-MAR-10:20 | 25.57 | 21.63 | 0.208990E+09 | 338.73 | 17-MAR-10:30 | 25.57 | 21.63 |
April | 0.467724E+10 | 12090.38 | 09-APR-09:32 | 25.37 | 18.85 | 0.187919E+09 | 338.72 | 20-APR-10:20 | 24.97 | 18.53 |
May | 0.545673E+10 | 10932.39 | 07-MAY-08:32 | 26.33 | 21.77 | 0.204590E+09 | 338.72 | 09-MAY-07:19 | 25.77 | 20.66 |
June | 0.567180E+10 | 12344.68 | 11-JUN-09:12 | 30.20 | 24.17 | 0.204135E+09 | 338.71 | 12-JUN-12:20 | 30.40 | 24.57 |
July | 0.586589E+10 | 12791.07 | 23-JUL-09:02 | 30.50 | 25.12 | 0.190583E+09 | 338.72 | 07-JUL-12:20 | 30.50 | 25.12 |
August | 0.569370E+10 | 11269.72 | 06-AUG-10:02 | 29.68 | 24.70 | 0.212695E+09 | 338.72 | 08-AUG-12:20 | 32.23 | 25.08 |
September | 0.528450E+10 | 12237.69 | 10-SEP-09:32 | 29.43 | 24.83 | 0.189236E+09 | 338.71 | 27-SEP-12:20 | 30.93 | 23.96 |
October | 0.486240E+10 | 12095.10 | 09-OCT-08:52 | 28.30 | 24.27 | 0.196438E+09 | 338.72 | 17-OCT-07:19 | 24.07 | 18.67 |
November | 0.372353E+10 | 6087.12 | 07-NOV-09:30 | 24.75 | 21.38 | 0.192909E+09 | 338.73 | 13-NOV-11:20 | 21.83 | 15.41 |
December | 0.290845E+10 | 4865.24 | 08-DEC-10:00 | 26.10 | 22.56 | 0.179951E+09 | 338.72 | 06-DEC-08:20 | 26.10 | 22.56 |
Annual Sum or Average | 0.543073E+11 | 0.233004E+10 | ||||||||
Minimum of Months | 0.290845E+10 | 4865.24 | 24.22 | 16.33 | 0.173561E+09 | 338.71 | 21.83 | 15.40 | ||
Maximum of Months | 0.586589E+10 | 12791.07 | 30.50 | 25.12 | 0.212695E+09 | 338.74 | 32.23 | 25.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631148E+10 | 11908.32 | 15-JAN-11:53 | 25.00 | 17.06 | 0.415420E+09 | 618.63 | 02-JAN-14:39 | 25.00 | 17.06 |
February | 0.588308E+10 | 12628.28 | 20-FEB-13:52 | 26.10 | 17.76 | 0.378147E+09 | 597.07 | 21-FEB-14:20 | 25.77 | 14.45 |
March | 0.634756E+10 | 11243.98 | 12-MAR-14:13 | 24.80 | 18.16 | 0.448037E+09 | 569.86 | 01-MAR-14:30 | 24.80 | 18.16 |
April | 0.581577E+10 | 9559.90 | 16-APR-12:02 | 30.78 | 21.05 | 0.402203E+09 | 549.49 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.642398E+10 | 10193.05 | 29-MAY-16:02 | 33.03 | 24.50 | 0.437481E+09 | 549.47 | 01-MAY-13:00 | 33.03 | 24.50 |
June | 0.672533E+10 | 9105.38 | 12-JUN-04:02 | 25.60 | 24.44 | 0.436439E+09 | 549.47 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.700973E+10 | 10190.09 | 30-JUL-16:12 | 29.80 | 25.10 | 0.405896E+09 | 549.47 | 03-JUL-13:09 | 29.80 | 25.10 |
August | 0.748368E+10 | 11331.08 | 20-AUG-12:53 | 32.20 | 25.55 | 0.455408E+09 | 549.47 | 07-AUG-13:30 | 32.20 | 25.55 |
September | 0.771740E+10 | 11843.79 | 10-SEP-13:32 | 31.10 | 24.95 | 0.404753E+09 | 567.40 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.824061E+10 | 12755.81 | 29-OCT-12:32 | 30.20 | 25.52 | 0.423587E+09 | 587.83 | 25-OCT-13:20 | 30.20 | 25.52 |
November | 0.723555E+10 | 12323.27 | 19-NOV-12:12 | 26.70 | 21.28 | 0.419582E+09 | 616.11 | 07-NOV-14:09 | 26.70 | 21.28 |
December | 0.641107E+10 | 11960.97 | 03-DEC-11:23 | 22.75 | 18.38 | 0.400103E+09 | 618.81 | 04-DEC-14:30 | 25.85 | 18.01 |
Annual Sum or Average | 0.816052E+11 | 0.502705E+10 | ||||||||
Minimum of Months | 0.581577E+10 | 9105.38 | 22.75 | 17.06 | 0.378147E+09 | 549.47 | 24.40 | 14.45 | ||
Maximum of Months | 0.824061E+10 | 12755.81 | 33.03 | 25.55 | 0.455408E+09 | 618.81 | 33.03 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307906E+10 | 5497.00 | 03-JAN-15:30 | 26.70 | 20.80 | 0.246088E+09 | 347.84 | 27-JAN-14:00 | 22.80 | 16.55 |
February | 0.322189E+10 | 12916.58 | 20-FEB-17:12 | 26.13 | 17.73 | 0.229659E+09 | 347.84 | 27-FEB-14:50 | 26.10 | 16.66 |
March | 0.422432E+10 | 12972.10 | 12-MAR-16:52 | 24.40 | 18.65 | 0.275461E+09 | 347.84 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.466206E+10 | 12799.20 | 09-APR-16:11 | 27.03 | 18.57 | 0.252759E+09 | 347.84 | 20-APR-09:50 | 24.40 | 17.95 |
May | 0.541291E+10 | 12694.00 | 29-MAY-16:42 | 31.97 | 24.40 | 0.276223E+09 | 347.83 | 23-MAY-13:00 | 31.97 | 24.40 |
June | 0.531998E+10 | 12029.28 | 10-JUN-17:05 | 30.60 | 24.10 | 0.275852E+09 | 347.84 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.565902E+10 | 12731.30 | 04-JUL-16:01 | 31.42 | 25.15 | 0.256612E+09 | 347.83 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.570637E+10 | 12560.35 | 20-AUG-16:12 | 30.60 | 24.86 | 0.287755E+09 | 347.84 | 08-AUG-09:00 | 30.60 | 24.86 |
September | 0.502777E+10 | 12960.01 | 10-SEP-15:31 | 31.10 | 25.07 | 0.255214E+09 | 347.83 | 07-SEP-13:00 | 31.10 | 25.07 |
October | 0.476843E+10 | 12810.66 | 15-OCT-15:42 | 28.98 | 20.79 | 0.264778E+09 | 347.84 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.379997E+10 | 7296.32 | 19-NOV-14:52 | 26.70 | 20.63 | 0.257930E+09 | 347.84 | 14-NOV-14:00 | 26.70 | 20.63 |
December | 0.322950E+10 | 7385.31 | 10-DEC-15:22 | 28.60 | 22.59 | 0.239224E+09 | 347.85 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.541113E+11 | 0.311756E+10 | ||||||||
Minimum of Months | 0.307906E+10 | 5497.00 | 24.40 | 17.73 | 0.229659E+09 | 347.83 | 21.70 | 13.99 | ||
Maximum of Months | 0.570637E+10 | 12972.10 | 31.97 | 25.15 | 0.287755E+09 | 347.85 | 31.97 | 25.07 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317820E+09 | 4311.28 | 25-JAN-06:03 | 9.40 |
February | 0.204319E+09 | 4674.18 | 04-FEB-07:03 | 5.28 |
March | 0.214472E+09 | 4607.76 | 16-MAR-05:03 | 6.70 |
April | 41049200.63 | 3427.52 | 19-APR-05:03 | 15.10 |
May | 17876944.18 | 4710.80 | 30-MAY-04:02 | 25.40 |
June | 17475715.45 | 4824.65 | 06-JUN-05:02 | 23.98 |
July | 21169537.19 | 5263.76 | 05-JUL-04:02 | 25.60 |
August | 16534104.58 | 4490.74 | 31-AUG-05:03 | 25.60 |
September | 16715343.28 | 4261.07 | 08-SEP-05:03 | 24.40 |
October | 21420380.07 | 5787.83 | 23-OCT-05:02 | 23.72 |
November | 74916574.89 | 4339.06 | 27-NOV-06:02 | 10.00 |
December | 0.255423E+09 | 4444.74 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 0.121919E+10 | |||
Minimum of Months | 16534104.58 | 3427.52 | 5.28 | |
Maximum of Months | 0.317820E+09 | 5787.83 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28881322.55 | 2583.21 | 29-JAN-10:43 | 26.02 |
February | 19701340.12 | 2772.12 | 05-FEB-15:13 | 21.10 |
March | 7442830.37 | 2099.30 | 05-MAR-11:02 | 26.97 |
April | 7448990.53 | 1839.34 | 12-APR-05:03 | 24.50 |
May | 8853932.43 | 1957.12 | 24-MAY-05:02 | 23.98 |
June | 8164315.88 | 2423.17 | 08-JUN-04:02 | 28.80 |
July | 10277126.11 | 1943.02 | 14-JUL-04:02 | 26.78 |
August | 10127406.65 | 2323.49 | 18-AUG-04:02 | 27.70 |
September | 10344762.18 | 2360.02 | 22-SEP-04:02 | 27.80 |
October | 10897968.97 | 2187.05 | 30-OCT-04:02 | 26.28 |
November | 10531057.31 | 2248.02 | 30-NOV-06:03 | 25.60 |
December | 24205921.51 | 2382.10 | 31-DEC-12:43 | 23.40 |
Annual Sum or Average | 0.156877E+09 | |||
Minimum of Months | 7442830.37 | 1839.34 | 21.10 | |
Maximum of Months | 28881322.55 | 2772.12 | 28.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18420652.45 | 2306.30 | 22-JAN-16:13 | 20.20 |
February | 17854973.68 | 2496.36 | 05-FEB-12:53 | 21.10 |
March | 10106544.46 | 1990.03 | 05-MAR-11:08 | 26.97 |
April | 10110842.45 | 2798.36 | 13-APR-04:03 | 24.40 |
May | 16624568.68 | 3258.00 | 24-MAY-05:02 | 23.98 |
June | 15040037.44 | 3449.62 | 08-JUN-04:02 | 28.80 |
July | 15427944.92 | 3369.89 | 12-JUL-04:02 | 26.93 |
August | 17643140.92 | 3669.04 | 18-AUG-04:02 | 27.70 |
September | 18223681.00 | 3796.51 | 29-SEP-04:02 | 24.90 |
October | 17740617.51 | 3743.70 | 04-OCT-04:02 | 26.10 |
November | 15981690.90 | 3507.11 | 20-NOV-05:03 | 24.40 |
December | 16674218.89 | 2409.52 | 09-DEC-05:03 | 25.00 |
Annual Sum or Average | 0.189849E+09 | |||
Minimum of Months | 10106544.46 | 1990.03 | 20.20 | |
Maximum of Months | 18420652.45 | 3796.51 | 28.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 122023.26 | 813.49 | 26-JAN-07:03 | 10.68 |
February | 2358032.82 | 15720.22 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 8236.43 | 54.91 | 21-DEC-07:03 | 11.88 |
Annual Sum or Average | 2488292.51 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 2358032.82 | 15720.22 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20460802.90 | 7259.15 | 09-JAN-07:03 | 12.38 |
February | 28182360.34 | 7777.16 | 04-FEB-06:12 | 5.40 |
March | 12167218.99 | 7034.93 | 16-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 2490396.62 | 7308.09 | 13-NOV-07:03 | 12.30 |
December | 20936391.76 | 7024.90 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 84237170.61 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 28182360.34 | 7777.16 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10744665.55 | 4756.59 | 24-JAN-07:03 | 11.78 |
February | 10827684.80 | 4696.82 | 03-FEB-07:03 | 10.60 |
March | 7161447.23 | 4776.61 | 17-MAR-06:03 | 13.30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 1027822.58 | 4391.56 | 27-NOV-07:02 | 10.37 |
December | 13818547.30 | 4759.50 | 14-DEC-07:02 | 15.78 |
Annual Sum or Average | 43580167.47 | |||
Minimum of Months | 0.00 | 0.00 | 10.37 | |
Maximum of Months | 13818547.30 | 4776.61 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8722303.36 | 7058.59 | 23-JAN-07:03 | 13.58 |
February | 15043910.68 | 7554.38 | 04-FEB-06:12 | 5.40 |
March | 7648971.84 | 7121.87 | 21-MAR-06:03 | 10.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 1307463.19 | 5304.87 | 27-NOV-07:02 | 10.37 |
December | 11602900.93 | 6921.88 | 21-DEC-07:03 | 11.88 |
Annual Sum or Average | 44325550.00 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 15043910.68 | 7554.38 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15101468.89 | 4774.14 | 31-JAN-07:03 | 12.20 |
February | 20012714.99 | 4787.74 | 24-FEB-07:03 | 11.88 |
March | 8439780.68 | 4781.46 | 17-MAR-06:03 | 13.30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 1581808.36 | 4687.90 | 13-NOV-07:03 | 12.30 |
December | 16212580.32 | 4720.07 | 20-DEC-07:03 | 11.60 |
Annual Sum or Average | 61348353.24 | |||
Minimum of Months | 0.00 | 0.00 | 11.60 | |
Maximum of Months | 20012714.99 | 4787.74 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 591048.95 | 3940.33 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 591048.95 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 591048.95 | 3940.33 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 350929.26 | 2339.53 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 350929.26 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 350929.26 | 2339.53 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146645E+09 | 4569.74 | 27-JAN-08:00 | 13.30 |
February | 47790019.08 | 4570.38 | 22-FEB-07:40 | 12.43 |
March | 0.110138E+09 | 4844.12 | 16-MAR-07:00 | 6.70 |
April | 5970366.37 | 3243.32 | 19-APR-06:08 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 28067532.90 | 4517.71 | 13-NOV-07:40 | 12.60 |
December | 92244106.44 | 4487.93 | 13-DEC-07:50 | 13.62 |
Annual Sum or Average | 0.430855E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 0.146645E+09 | 4844.12 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 397500.15 | 2650.00 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 397500.15 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 397500.15 | 2650.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1233263.38 | 5384.59 | 25-JAN-07:02 | 9.50 |
February | 2938408.60 | 5214.51 | 04-FEB-07:03 | 5.28 |
March | 659337.92 | 5128.28 | 16-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 1418939.63 | 5246.32 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 6249949.53 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 2938408.60 | 5384.59 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1314275.89 | 3667.86 | 26-JAN-07:03 | 10.68 |
February | 798992.24 | 3241.99 | 04-FEB-07:03 | 5.28 |
March | 664575.36 | 2639.25 | 16-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 1868438.81 | 3708.56 | 21-DEC-07:03 | 11.88 |
Annual Sum or Average | 4646282.30 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1868438.81 | 3708.56 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 242202.30 | 1716.70 | 25-JAN-07:02 | 9.50 |
February | 1121235.58 | 5105.51 | 04-FEB-07:03 | 5.28 |
March | 404648.33 | 4046.48 | 16-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 283399.01 | 2833.99 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 2051485.21 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1121235.58 | 5105.51 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1201939.42 | 3763.96 | 26-JAN-07:03 | 10.68 |
February | 2164393.55 | 3136.25 | 04-FEB-07:03 | 5.28 |
March | 570164.61 | 2828.71 | 16-MAR-06:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 2114908.11 | 3749.63 | 16-DEC-07:03 | 11.88 |
Annual Sum or Average | 6051405.68 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 2164393.55 | 3763.96 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793023E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.681835E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.776649E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.672729E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708952E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.704881E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655155E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745007E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687532E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740619E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.764013E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.776232E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.870663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655155E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.793023E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.487511E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425800E+09 | 710.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483899E+09 | 600.14 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426437E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453041E+09 | 490.21 | 25-MAY-14:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452173E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418835E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472121E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434720E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.459707E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.476065E+09 | 750.07 | 08-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.482134E+09 | 860.01 | 06-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547244E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418835E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487511E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737989E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655566E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762327E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674910E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719906E+09 | 947.97 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723123E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.665687E+09 | 947.97 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749790E+09 | 1184.79 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683712E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.717248E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.725903E+09 | 1184.79 | 24-NOV-08:09 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.729878E+09 | 1358.45 | 15-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854604E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655566E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.762327E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481145E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421539E+09 | 710.03 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490128E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426526E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455062E+09 | 600.10 | 02-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455793E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421174E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477233E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436805E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465581E+09 | 859.95 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468962E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.470620E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547057E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421174E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490128E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788286E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.679013E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773356E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.671588E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708201E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.703852E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.653792E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.743512E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.685989E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.737598E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.759869E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771837E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.867689E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.653792E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788286E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485864E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424707E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.482701E+09 | 490.21 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425698E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452243E+09 | 490.21 | 25-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.451462E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418204E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471369E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433870E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458742E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474879E+09 | 750.07 | 10-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.480611E+09 | 860.01 | 15-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546035E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418204E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485864E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737091E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.654318E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.760886E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.673952E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.717827E+09 | 774.31 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.720925E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663955E+09 | 774.31 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.748291E+09 | 947.97 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682889E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716290E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.724621E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.728697E+09 | 1358.45 | 15-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.852974E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.654318E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.760886E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479580E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.420137E+09 | 600.10 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488998E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425597E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.454186E+09 | 600.10 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.454579E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420250E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.476178E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435581E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464282E+09 | 750.02 | 18-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.467251E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.469078E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545570E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420137E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.488998E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793023E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.681835E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.776649E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.672717E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708952E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.704881E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655155E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745007E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687532E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740619E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.764013E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.776232E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.870661E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655155E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.793023E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.487511E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425800E+09 | 710.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483891E+09 | 600.14 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426437E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453041E+09 | 490.21 | 25-MAY-14:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452173E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418835E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472121E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434720E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.459707E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.476065E+09 | 750.07 | 08-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.482134E+09 | 860.01 | 06-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547243E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418835E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487511E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737989E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655566E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762321E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674897E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719906E+09 | 947.97 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723111E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.665687E+09 | 947.97 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749777E+09 | 1184.79 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683712E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.717248E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.725903E+09 | 1184.79 | 24-NOV-08:09 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.729878E+09 | 1358.45 | 15-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854599E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655566E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.762321E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481145E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421539E+09 | 710.03 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490128E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426526E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455062E+09 | 600.10 | 02-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455793E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421172E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477233E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436805E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465581E+09 | 859.95 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468962E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.470620E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547057E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421172E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490128E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.793023E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10853971.51 | 0.170069E+09 |
February | 0.901968E+09 | 0.681835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17494805.63 | 0.226053E+09 |
March | 0.107774E+10 | 0.776649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18572009.85 | 0.207539E+09 |
April | 0.956342E+09 | 0.672729E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40821818.04 | 92853912.83 |
May | 0.103597E+10 | 0.708952E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93912927.96 | 39033752.47 |
June | 0.103308E+10 | 0.704881E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110234E+09 | 12624128.76 |
July | 0.959235E+09 | 0.655155E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104286E+09 | 11847532.23 |
August | 0.107774E+10 | 0.745007E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121877E+09 | 6605271.37 |
September | 0.956342E+09 | 0.687532E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114761E+09 | 11674178.56 |
October | 0.994195E+09 | 0.740619E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76720538.46 | 24366219.97 |
November | 0.984487E+09 | 0.764013E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36399839.46 | 0.140666E+09 |
December | 0.959235E+09 | 0.776232E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14371705.87 | 0.169146E+09 |
Annual Sum or Average | 0.119305E+11 | 0.870663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760306E+09 | 0.111248E+10 |
Minimum of Months | 0.901968E+09 | 0.655155E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10853971.51 | 6605271.37 |
Maximum of Months | 0.107774E+10 | 0.793023E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121877E+09 | 0.226053E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.487511E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5472119.97 | 0.120730E+09 |
February | 0.571020E+09 | 0.425800E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10806843.88 | 0.158197E+09 |
March | 0.682301E+09 | 0.483899E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11985740.27 | 0.144705E+09 |
April | 0.605444E+09 | 0.426437E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24439774.18 | 64650967.29 |
May | 0.655854E+09 | 0.453041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62706860.88 | 26413145.76 |
June | 0.654023E+09 | 0.452173E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73997723.39 | 8498211.41 |
July | 0.607275E+09 | 0.418835E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69079801.82 | 8045877.07 |
August | 0.682301E+09 | 0.472121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80654498.65 | 4396829.06 |
September | 0.605444E+09 | 0.434720E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75245286.49 | 7964150.26 |
October | 0.629407E+09 | 0.459707E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49782970.92 | 16764116.39 |
November | 0.623262E+09 | 0.476065E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24097501.94 | 0.100113E+09 |
December | 0.607275E+09 | 0.482134E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9250424.09 | 0.115265E+09 |
Annual Sum or Average | 0.755301E+10 | 0.547244E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497520E+09 | 0.775743E+09 |
Minimum of Months | 0.571020E+09 | 0.418835E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5472119.97 | 4396829.06 |
Maximum of Months | 0.682301E+09 | 0.487511E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80654498.65 | 0.158197E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737989E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5675732.80 | 0.206004E+09 |
February | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12091074.82 | 0.264604E+09 |
March | 0.107774E+10 | 0.762327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15531788.34 | 0.229169E+09 |
April | 0.956342E+09 | 0.674910E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35330391.37 | 97799815.97 |
May | 0.103597E+10 | 0.719906E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94788066.93 | 38850196.26 |
June | 0.103308E+10 | 0.723123E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112227E+09 | 12221339.51 |
July | 0.959235E+09 | 0.665687E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105880E+09 | 11466365.34 |
August | 0.107774E+10 | 0.749790E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120641E+09 | 6706342.01 |
September | 0.956342E+09 | 0.683712E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109017E+09 | 12634279.86 |
October | 0.994195E+09 | 0.717248E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65622843.50 | 29687615.63 |
November | 0.984487E+09 | 0.725903E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28628553.01 | 0.171713E+09 |
December | 0.959235E+09 | 0.729878E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8084450.03 | 0.200863E+09 |
Annual Sum or Average | 0.119305E+11 | 0.854604E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713517E+09 | 0.128172E+10 |
Minimum of Months | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5675732.80 | 6706342.01 |
Maximum of Months | 0.107774E+10 | 0.762327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120641E+09 | 0.264604E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481145E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7803880.91 | 0.115863E+09 |
February | 0.570983E+09 | 0.421539E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11358866.36 | 0.158131E+09 |
March | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13558372.40 | 0.148304E+09 |
April | 0.605404E+09 | 0.426526E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26646952.83 | 70886301.92 |
May | 0.655811E+09 | 0.455062E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63686232.27 | 29253790.23 |
June | 0.653980E+09 | 0.455793E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73999757.32 | 8572265.21 |
July | 0.607235E+09 | 0.421174E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70202528.10 | 8436855.14 |
August | 0.682256E+09 | 0.477233E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80044115.57 | 4635834.11 |
September | 0.605404E+09 | 0.436805E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75247803.00 | 8288161.15 |
October | 0.629366E+09 | 0.465581E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50283005.18 | 18305857.64 |
November | 0.623221E+09 | 0.468962E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25011818.80 | 96843383.68 |
December | 0.607235E+09 | 0.470620E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9605385.03 | 0.116561E+09 |
Annual Sum or Average | 0.755252E+10 | 0.547057E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507449E+09 | 0.784082E+09 |
Minimum of Months | 0.570983E+09 | 0.421174E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7803880.91 | 4635834.11 |
Maximum of Months | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80044115.57 | 0.158131E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.788286E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5589954.57 | 0.107319E+09 |
February | 0.901968E+09 | 0.679013E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9649774.55 | 0.140807E+09 |
March | 0.107774E+10 | 0.773356E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10846371.09 | 0.120640E+09 |
April | 0.956342E+09 | 0.671588E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24557887.27 | 51412563.09 |
May | 0.103597E+10 | 0.708201E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53644025.90 | 19757849.33 |
June | 0.103308E+10 | 0.703852E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62610758.50 | 5779703.99 |
July | 0.959235E+09 | 0.653792E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59345146.10 | 6048460.29 |
August | 0.107774E+10 | 0.743512E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67816138.38 | 3681278.93 |
September | 0.956342E+09 | 0.685989E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64522920.06 | 6990984.49 |
October | 0.994195E+09 | 0.737598E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43065480.76 | 15108210.29 |
November | 0.984487E+09 | 0.759869E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19803700.70 | 90983727.44 |
December | 0.959235E+09 | 0.771837E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7636126.61 | 0.108418E+09 |
Annual Sum or Average | 0.119305E+11 | 0.867689E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429088E+09 | 0.676946E+09 |
Minimum of Months | 0.901968E+09 | 0.653792E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5589954.57 | 3681278.93 |
Maximum of Months | 0.107774E+10 | 0.788286E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67816138.38 | 0.140807E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.485864E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2629925.49 | 77552372.32 |
February | 0.571020E+09 | 0.424707E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5661948.52 | 0.101315E+09 |
March | 0.682301E+09 | 0.482701E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6329994.38 | 88665815.56 |
April | 0.605444E+09 | 0.425698E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13398269.76 | 38936797.27 |
May | 0.655854E+09 | 0.452243E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33984268.64 | 15243532.36 |
June | 0.654023E+09 | 0.451462E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40018819.23 | 4422343.75 |
July | 0.607275E+09 | 0.418204E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37389957.16 | 4802692.95 |
August | 0.682301E+09 | 0.471369E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42970150.00 | 2761223.56 |
September | 0.605444E+09 | 0.433870E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40217876.60 | 5287042.11 |
October | 0.629407E+09 | 0.458742E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26422925.24 | 11672897.97 |
November | 0.623262E+09 | 0.474879E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12285771.15 | 65724373.35 |
December | 0.607275E+09 | 0.480611E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4531464.82 | 75502067.33 |
Annual Sum or Average | 0.755301E+10 | 0.546035E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265841E+09 | 0.491886E+09 |
Minimum of Months | 0.571020E+09 | 0.418204E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2629925.49 | 2761223.56 |
Maximum of Months | 0.682301E+09 | 0.485864E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42970150.00 | 0.101315E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737091E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105546E+09 | 0.159650E+10 |
February | 0.901968E+09 | 0.654318E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233029E+09 | 0.785207E+09 |
March | 0.107774E+10 | 0.760886E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283350E+09 | 0.105078E+10 |
April | 0.956342E+09 | 0.673952E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676951E+09 | 0.259947E+09 |
May | 0.103597E+10 | 0.717827E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147910E+10 | 47210783.96 |
June | 0.103308E+10 | 0.720925E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169117E+10 | 8763900.82 |
July | 0.959235E+09 | 0.663955E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188320E+10 | 12064384.17 |
August | 0.107774E+10 | 0.748291E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202115E+10 | 19417031.00 |
September | 0.956342E+09 | 0.682889E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147139E+10 | 25329372.52 |
October | 0.994195E+09 | 0.716290E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115400E+10 | 79160043.90 |
November | 0.984487E+09 | 0.724621E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630900E+09 | 0.469340E+09 |
December | 0.959235E+09 | 0.728697E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132354E+09 | 0.143283E+10 |
Annual Sum or Average | 0.119305E+11 | 0.852974E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117621E+11 | 0.578655E+10 |
Minimum of Months | 0.901968E+09 | 0.654318E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105546E+09 | 8763900.82 |
Maximum of Months | 0.107774E+10 | 0.760886E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202115E+10 | 0.159650E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.479580E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3274107.09 | 75320487.29 |
February | 0.570983E+09 | 0.420137E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5102867.75 | 0.102020E+09 |
March | 0.682256E+09 | 0.488998E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6421929.81 | 92040383.48 |
April | 0.605404E+09 | 0.425597E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13589784.22 | 42605193.05 |
May | 0.655811E+09 | 0.454186E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33557051.48 | 17066328.76 |
June | 0.653980E+09 | 0.454579E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39702768.31 | 4448328.70 |
July | 0.607235E+09 | 0.420250E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37418113.74 | 4972692.60 |
August | 0.682256E+09 | 0.476178E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41929522.56 | 2934770.89 |
September | 0.605404E+09 | 0.435581E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39511145.59 | 5434963.77 |
October | 0.629366E+09 | 0.464282E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25971958.49 | 12582097.26 |
November | 0.623221E+09 | 0.467251E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12281961.54 | 64673088.44 |
December | 0.607235E+09 | 0.469078E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4359586.65 | 77258706.03 |
Annual Sum or Average | 0.755252E+10 | 0.545570E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263121E+09 | 0.501357E+09 |
Minimum of Months | 0.570983E+09 | 0.420137E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3274107.09 | 2934770.89 |
Maximum of Months | 0.682256E+09 | 0.488998E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41929522.56 | 0.102020E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.793023E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8561645.53 | 0.158961E+09 |
February | 0.901968E+09 | 0.681835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14503925.21 | 0.211265E+09 |
March | 0.107774E+10 | 0.776649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15716251.66 | 0.190794E+09 |
April | 0.956342E+09 | 0.672717E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35993055.18 | 83717172.49 |
May | 0.103597E+10 | 0.708952E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79853934.47 | 34289160.39 |
June | 0.103308E+10 | 0.704881E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94159722.99 | 10407860.52 |
July | 0.959235E+09 | 0.655155E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89509825.61 | 9927590.33 |
August | 0.107774E+10 | 0.745007E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103670E+09 | 5596346.20 |
September | 0.956342E+09 | 0.687532E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98247145.62 | 10447964.59 |
October | 0.994195E+09 | 0.740619E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64886682.93 | 22678517.20 |
November | 0.984487E+09 | 0.764013E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30259448.09 | 0.131896E+09 |
December | 0.959235E+09 | 0.776232E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11905052.60 | 0.158628E+09 |
Annual Sum or Average | 0.119305E+11 | 0.870661E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647267E+09 | 0.102861E+10 |
Minimum of Months | 0.901968E+09 | 0.655155E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8561645.53 | 5596346.20 |
Maximum of Months | 0.107774E+10 | 0.793023E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103670E+09 | 0.211265E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.487511E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4518403.07 | 0.110961E+09 |
February | 0.421807E+09 | 0.425800E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9151486.68 | 0.146164E+09 |
March | 0.502994E+09 | 0.483891E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10165575.50 | 0.131238E+09 |
April | 0.447140E+09 | 0.426437E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21502366.30 | 57788309.82 |
May | 0.484071E+09 | 0.453041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53209145.58 | 23228652.05 |
June | 0.482240E+09 | 0.452173E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62854965.88 | 7057978.78 |
July | 0.448971E+09 | 0.418835E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58858397.38 | 6825722.26 |
August | 0.502994E+09 | 0.472121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68283061.11 | 3746611.30 |
September | 0.447140E+09 | 0.434720E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63959963.18 | 7122183.93 |
October | 0.465148E+09 | 0.459707E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42127363.27 | 15421192.76 |
November | 0.460569E+09 | 0.476065E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20111984.17 | 92501144.35 |
December | 0.448971E+09 | 0.482134E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7731099.40 | 0.106930E+09 |
Annual Sum or Average | 0.557719E+10 | 0.547243E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422474E+09 | 0.708985E+09 |
Minimum of Months | 0.421807E+09 | 0.418835E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4518403.07 | 3746611.30 |
Maximum of Months | 0.502994E+09 | 0.487511E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68283061.11 | 0.146164E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737989E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4491926.31 | 0.187379E+09 |
February | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9919310.49 | 0.242175E+09 |
March | 0.107774E+10 | 0.762321E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13035927.57 | 0.207942E+09 |
April | 0.956342E+09 | 0.674897E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30701714.45 | 87480814.05 |
May | 0.103597E+10 | 0.719906E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80422014.03 | 34109489.77 |
June | 0.103308E+10 | 0.723111E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95939404.17 | 10051983.58 |
July | 0.959235E+09 | 0.665687E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90879987.69 | 9606307.83 |
August | 0.107774E+10 | 0.749777E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102218E+09 | 5689144.92 |
September | 0.956342E+09 | 0.683712E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92173566.67 | 11280846.98 |
October | 0.994195E+09 | 0.717248E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54529950.05 | 27107895.06 |
November | 0.984487E+09 | 0.725903E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23416024.94 | 0.156831E+09 |
December | 0.959235E+09 | 0.729878E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6544254.94 | 0.183375E+09 |
Annual Sum or Average | 0.119305E+11 | 0.854599E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604272E+09 | 0.116303E+10 |
Minimum of Months | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4491926.31 | 5689144.92 |
Maximum of Months | 0.107774E+10 | 0.762321E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102218E+09 | 0.242175E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481145E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5744811.89 | 0.108039E+09 |
February | 0.570983E+09 | 0.421539E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8466153.71 | 0.146974E+09 |
March | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10537500.56 | 0.135887E+09 |
April | 0.605404E+09 | 0.426526E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21868569.90 | 63848757.61 |
May | 0.655811E+09 | 0.455062E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52826919.50 | 26074037.56 |
June | 0.653980E+09 | 0.455793E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62024255.19 | 7244350.91 |
July | 0.607235E+09 | 0.421172E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58985001.09 | 7298735.06 |
August | 0.682256E+09 | 0.477233E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66764282.47 | 3999548.15 |
September | 0.605404E+09 | 0.436805E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62760228.12 | 7504890.27 |
October | 0.629366E+09 | 0.465581E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41186563.55 | 16907380.50 |
November | 0.623221E+09 | 0.468962E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20013520.28 | 90657766.55 |
December | 0.607235E+09 | 0.470620E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7420742.97 | 0.109086E+09 |
Annual Sum or Average | 0.755252E+10 | 0.547057E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418599E+09 | 0.723521E+09 |
Minimum of Months | 0.570983E+09 | 0.421172E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5744811.89 | 3999548.15 |
Maximum of Months | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66764282.47 | 0.146974E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4898614.69 | 0.249591E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9033546.52 | 0.328378E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11580152.10 | 0.288539E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31492672.89 | 0.121187E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86223301.59 | 41723253.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112646E+09 | 10782703.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106054E+09 | 10959111.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122678E+09 | 7141937.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113548E+09 | 13971538.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65780414.06 | 31419830.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26004925.97 | 0.203148E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8864952.40 | 0.245835E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698804E+09 | 0.155268E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4898614.69 | 7141937.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122678E+09 | 0.328378E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8864813.54 | 0.293806E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13556599.11 | 0.387015E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16820790.06 | 0.346683E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42461392.60 | 0.146338E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111420E+09 | 50939133.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144614E+09 | 14245583.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135713E+09 | 14362262.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159105E+09 | 8829891.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147133E+09 | 16893903.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87506533.69 | 37145488.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37517723.31 | 0.239348E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13821606.75 | 0.286660E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918534E+09 | 0.184227E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8864813.54 | 8829891.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159105E+09 | 0.387015E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4389732.89 | 0.273108E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341378.68 | 0.353037E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6165892.82 | 0.322734E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22150690.02 | 0.139510E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97119587.95 | 43423066.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137656E+09 | 15603913.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119781E+09 | 14267215.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153433E+09 | 9207775.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133781E+09 | 12125172.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80228346.23 | 24924412.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34290889.79 | 0.218825E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6993828.32 | 0.267608E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800332E+09 | 0.169437E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341378.68 | 9207775.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153433E+09 | 0.353037E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.14 | 15-JAN-14:00 | 492.99 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.24 | 20-FEB-14:50 | 832.30 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 | 05-MAR-13:55 | 845.73 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.18 | 15-APR-17:02 | 285.56 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 493.75 | 29-MAY-16:05 | 188.69 | 07-MAY-19:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.43 | 17-JUN-17:23 | 210.55 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.07 | 30-JUL-15:38 | 172.77 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.73 | 13-AUG-12:40 | 241.26 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 17-SEP-14:00 | 103.94 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.11 | 29-OCT-11:50 | 177.43 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.26 | 19-NOV-11:10 | 826.23 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.79 | 10-DEC-14:52 | 769.21 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 148.24 | 103.94 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 493.75 | 845.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 15-JAN-14:40 | 361.29 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 710.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 | 19-FEB-15:40 | 552.13 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 | 05-MAR-13:53 | 569.49 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.40 | 15-APR-17:02 | 190.98 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 25-MAY-14:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.94 | 29-MAY-16:07 | 138.13 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.28 | 17-JUN-17:23 | 137.10 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.58 | 30-JUL-15:40 | 122.60 | 02-JUL-16:00 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.16 | 20-AUG-12:18 | 161.68 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.41 | 17-SEP-14:00 | 71.44 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.82 | 29-OCT-14:10 | 119.20 | 01-OCT-07:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 08-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.02 | 22-NOV-22:03 | 660.52 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.70 | 10-DEC-14:52 | 512.29 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 | 71.44 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 348.94 | 660.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.54 | 29-JAN-13:10 | 522.45 | 08-JAN-10:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 | 02-FEB-14:00 | 855.62 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.33 | 05-MAR-13:53 | 878.38 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.62 | 15-APR-17:02 | 290.44 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.66 | 29-MAY-16:05 | 189.39 | 07-MAY-19:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.54 | 17-JUN-17:23 | 211.34 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.77 | 30-JUL-15:38 | 171.51 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.69 | 20-AUG-12:18 | 243.53 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.23 | 17-SEP-16:37 | 111.46 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.66 | 29-OCT-14:06 | 184.52 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 24-NOV-08:09 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.85 | 22-NOV-22:03 | 945.32 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.52 | 10-DEC-14:46 | 797.92 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 80.54 | 111.46 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 499.66 | 945.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 | 15-JAN-12:00 | 331.85 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 710.03 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.63 | 19-FEB-13:05 | 555.81 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.55 | 05-MAR-13:53 | 579.69 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.71 | 16-APR-13:00 | 201.36 | 30-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.44 | 29-MAY-15:24 | 147.38 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.78 | 11-JUN-12:00 | 143.70 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.24 | 30-JUL-15:38 | 111.48 | 02-JUL-16:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.29 | 13-AUG-12:40 | 168.24 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.04 | 17-SEP-13:58 | 78.80 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.83 | 29-OCT-12:10 | 122.37 | 01-OCT-07:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.98 | 19-NOV-11:10 | 547.49 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.98 | 10-DEC-13:32 | 512.29 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.63 | 78.80 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 314.44 | 579.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.60 | 15-JAN-14:00 | 300.00 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.65 | 20-FEB-14:50 | 533.52 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.35 | 05-MAR-14:00 | 513.70 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.05 | 15-APR-17:02 | 165.28 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.91 | 29-MAY-16:10 | 107.50 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.74 | 17-JUN-17:40 | 100.35 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.11 | 30-JUL-15:50 | 76.40 | 04-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.85 | 13-AUG-13:00 | 129.80 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.30 | 17-SEP-14:00 | 59.08 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.03 | 29-OCT-14:00 | 106.85 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 | 23-NOV-12:00 | 519.11 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 | 10-DEC-14:30 | 494.50 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 87.65 | 59.08 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 272.91 | 533.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 15-JAN-14:40 | 210.22 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.41 | 19-FEB-15:40 | 357.72 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 490.21 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.41 | 05-MAR-14:00 | 353.82 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 | 15-APR-17:02 | 115.27 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 25-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.87 | 29-MAY-16:10 | 73.97 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.73 | 17-JUN-17:37 | 68.51 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.04 | 30-JUL-15:40 | 61.11 | 02-JUL-15:25 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 | 13-AUG-13:00 | 90.95 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 17-SEP-14:00 | 43.25 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.52 | 29-OCT-14:00 | 75.28 | 16-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 10-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 | 23-NOV-12:00 | 394.54 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 15-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.16 | 10-DEC-14:30 | 333.62 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 43.25 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 188.87 | 394.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.12 | 23-JAN-17:10 | 14510.55 | 25-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4248.49 | 02-FEB-13:00 | 13210.06 | 03-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6101.07 | 13-MAR-16:03 | 17146.08 | 16-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8640.89 | 17-APR-16:03 | 7422.74 | 19-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9899.01 | 22-MAY-16:02 | 2645.28 | 01-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8167.26 | 09-JUN-16:03 | 876.90 | 13-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12424.92 | 27-JUL-16:02 | 1478.32 | 14-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10024.80 | 08-AUG-11:02 | 2131.01 | 28-AUG-12:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8866.75 | 08-SEP-16:03 | 2079.01 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7546.56 | 03-OCT-11:02 | 2556.31 | 31-OCT-06:05 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4715.64 | 03-NOV-16:05 | 14198.66 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3450.66 | 08-DEC-12:05 | 16636.66 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.12 | 876.90 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12424.92 | 17146.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 15-JAN-12:40 | 209.40 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 600.10 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 19-FEB-13:05 | 359.66 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.41 | 05-MAR-14:00 | 361.14 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.30 | 16-APR-13:00 | 119.13 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.62 | 29-MAY-16:03 | 74.83 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 11-JUN-12:00 | 72.54 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.78 | 30-JUL-15:40 | 55.25 | 02-JUL-15:25 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.64 | 13-AUG-13:00 | 96.10 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 | 10-SEP-13:00 | 47.44 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 | 29-OCT-12:00 | 80.51 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.05 | 23-NOV-12:00 | 350.19 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 | 10-DEC-13:50 | 335.65 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 47.44 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 170.62 | 361.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 | 15-JAN-14:00 | 447.79 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.23 | 20-FEB-15:00 | 779.24 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.79 | 26-MAR-14:50 | 771.80 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.93 | 15-APR-17:02 | 254.54 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.86 | 29-MAY-16:05 | 165.88 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.51 | 17-JUN-17:23 | 167.70 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.87 | 30-JUL-15:40 | 125.93 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.70 | 13-AUG-12:40 | 200.74 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.03 | 17-SEP-14:00 | 87.86 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.70 | 29-OCT-14:00 | 159.03 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.03 | 19-NOV-11:40 | 757.87 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.13 | 10-DEC-14:52 | 719.97 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 123.23 | 87.86 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 419.86 | 779.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 | 15-JAN-14:40 | 328.37 | 08-JAN-10:00 |
February | 805.43 | 01-FEB-08:09 | 710.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 19-FEB-15:40 | 516.08 | 04-FEB-05:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.11 | 05-MAR-14:20 | 517.65 | 16-MAR-02:00 |
April | 805.43 | 03-APR-07:10 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.36 | 15-APR-17:02 | 169.94 | 18-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 25-MAY-14:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.36 | 29-MAY-16:10 | 110.16 | 07-MAY-19:00 |
June | 805.43 | 01-JUN-07:10 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.21 | 17-JUN-17:23 | 109.68 | 18-JUN-20:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.89 | 30-JUL-15:40 | 95.41 | 02-JUL-15:25 |
August | 805.43 | 01-AUG-07:10 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 | 13-AUG-13:00 | 134.90 | 14-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | 17-SEP-14:00 | 60.33 | 19-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.23 | 29-OCT-14:00 | 105.47 | 16-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 750.07 | 08-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.36 | 22-NOV-22:03 | 595.73 | 11-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 06-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.97 | 10-DEC-14:52 | 478.00 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 | 60.33 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 292.36 | 595.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.19 | 29-JAN-12:50 | 477.73 | 08-JAN-10:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 02-FEB-14:00 | 798.41 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.48 | 05-MAR-14:00 | 797.39 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.51 | 15-APR-17:02 | 258.57 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.44 | 29-MAY-16:05 | 165.62 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.34 | 17-JUN-17:23 | 168.11 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.18 | 30-JUL-15:40 | 124.86 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.28 | 13-AUG-12:40 | 203.00 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.96 | 17-SEP-16:37 | 94.10 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.27 | 29-OCT-13:57 | 172.24 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 24-NOV-08:09 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 | 22-NOV-22:03 | 857.03 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.58 | 10-DEC-14:46 | 739.71 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 74.19 | 94.10 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 420.44 | 857.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.89 | 15-JAN-12:40 | 301.16 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 710.03 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 19-FEB-13:05 | 519.43 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 05-MAR-11:53 | 527.17 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.77 | 16-APR-13:00 | 177.82 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.42 | 29-MAY-15:24 | 119.24 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 11-JUN-12:00 | 115.75 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.46 | 30-JUL-15:40 | 85.24 | 02-JUL-15:25 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.42 | 13-AUG-12:40 | 141.44 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.16 | 17-SEP-13:00 | 66.57 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.45 | 29-OCT-12:00 | 111.46 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.66 | 19-NOV-11:40 | 502.62 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.42 | 10-DEC-13:32 | 478.26 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 66.57 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 260.42 | 527.17 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.68 | 29-JAN-12:00 | 663.08 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 02-FEB-14:00 | 1192.05 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.99 | 05-MAR-14:00 | 1157.48 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.22 | 15-APR-17:02 | 367.78 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.08 | 29-MAY-15:51 | 213.93 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.88 | 25-JUN-14:00 | 186.66 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.80 | 30-JUL-15:50 | 151.45 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.44 | 13-AUG-12:55 | 241.15 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.23 | 17-SEP-14:00 | 95.71 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 | 29-OCT-13:42 | 228.14 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.53 | 04-NOV-17:03 | 1093.44 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.52 | 10-DEC-14:50 | 1095.78 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 95.71 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.08 | 1192.05 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.48 | 29-JAN-12:50 | 797.41 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.71 | 19-FEB-14:00 | 1458.40 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.64 | 05-MAR-13:43 | 1441.29 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.96 | 15-APR-17:02 | 464.64 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.48 | 29-MAY-15:51 | 258.82 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.17 | 25-JUN-14:00 | 248.57 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.63 | 30-JUL-15:50 | 198.34 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.99 | 13-AUG-12:55 | 308.81 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.45 | 17-SEP-14:00 | 120.14 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.57 | 29-OCT-13:42 | 284.67 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.20 | 04-NOV-17:03 | 1348.47 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.26 | 10-DEC-15:00 | 1336.79 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.71 | 120.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.48 | 1458.40 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.16 | 29-JAN-12:00 | 740.77 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.45 | 02-FEB-14:00 | 1224.02 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.69 | 05-MAR-14:00 | 1254.86 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.65 | 15-APR-17:02 | 400.07 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.18 | 29-MAY-15:51 | 311.30 | 07-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.97 | 16-JUN-21:03 | 308.10 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.56 | 29-JUL-18:00 | 303.70 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.99 | 13-AUG-12:40 | 341.21 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.62 | 21-SEP-21:03 | 194.76 | 03-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.83 | 29-OCT-08:55 | 262.31 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.37 | 22-NOV-22:03 | 1248.54 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 10-DEC-09:53 | 1120.02 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.45 | 194.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.18 | 1254.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 39221.08 | 02-JAN-07:03 | 5082.11 | 8592.08 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36171.24 | 11-FEB-06:03 | 2541.06 | 846.94 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33850.63 | 27-MAR-05:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42085.40 | 13-APR-05:02 | 3176.32 | 1058.67 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46538.37 | 08-MAY-05:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44451.33 | 20-JUN-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44391.41 | 06-JUL-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43802.80 | 30-AUG-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44002.67 | 07-SEP-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46486.25 | 23-OCT-05:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43439.45 | 20-NOV-05:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36515.71 | 11-DEC-06:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33850.63 | 0.00 | 846.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46538.37 | 5082.11 | 8592.08 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8045.50 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
February | 8000.31 | 22-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 0.00 |
March | 9221.17 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | 0.00 |
April | 10136.21 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 | 0.00 |
May | 11258.54 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.86 | 0.00 |
June | 10535.43 | 09-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.01 | 0.00 |
July | 11672.66 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 | 0.00 |
August | 11155.04 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.71 | 0.00 |
September | 10887.15 | 18-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.50 | 0.00 |
October | 10560.24 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.06 | 0.00 |
November | 8614.83 | 10-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 | 0.00 |
December | 7484.49 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7484.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 0.00 | |
Maximum of Months | 11672.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3883.46 | 02-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
February | 3276.69 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 0.00 |
March | 3940.59 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.26 | 0.00 |
April | 4181.53 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.57 | 0.00 |
May | 4631.05 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.02 | 0.00 |
June | 4420.85 | 26-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.14 | 0.00 |
July | 5012.31 | 31-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 | 0.00 |
August | 4776.84 | 21-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 | 0.00 |
September | 4830.04 | 18-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.41 | 0.00 |
October | 4611.47 | 02-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.44 | 0.00 |
November | 4181.40 | 06-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 |
December | 3462.55 | 11-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3276.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5012.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.02 | 13.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4606.63 | 02-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
February | 3985.60 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 0.00 |
March | 4389.71 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 0.00 |
April | 4560.12 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 | 0.00 |
May | 5384.27 | 22-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 | 0.00 |
June | 4911.52 | 26-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 | 0.00 |
July | 5659.63 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 |
August | 5172.99 | 07-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 0.00 |
September | 5239.71 | 11-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 0.00 |
October | 5084.82 | 10-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 0.00 |
November | 4717.91 | 06-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
December | 4058.29 | 11-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3985.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5659.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 | 21.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23920.38 | 14-JAN-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22510.69 | 11-FEB-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20521.56 | 27-MAR-05:13 | 1905.79 | 2147.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31241.13 | 12-APR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34938.38 | 08-MAY-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32536.16 | 20-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32798.39 | 25-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32275.61 | 08-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32761.69 | 20-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35931.58 | 02-OCT-04:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31576.75 | 03-NOV-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30920.42 | 09-DEC-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20521.56 | 0.00 | 846.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35931.58 | 3811.58 | 2147.94 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19168.02 | 02-JAN-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17557.05 | 21-FEB-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19630.62 | 27-MAR-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34077.99 | 13-APR-05:02 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35508.00 | 23-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36383.60 | 19-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35902.46 | 24-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35176.09 | 07-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35232.47 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35834.51 | 10-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34034.58 | 20-NOV-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20423.57 | 09-DEC-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17557.05 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36383.60 | 6198.29 | 6443.98 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5137.76 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 45.08 | 0.00 |
February | 5254.44 | 17-FEB-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 0.00 |
March | 5786.08 | 27-MAR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
April | 8501.99 | 16-APR-16:42 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 114.25 | 0.00 |
May | 12465.03 | 29-MAY-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 452.26 | 0.00 |
June | 12365.35 | 25-JUN-15:43 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 0.00 |
July | 12820.01 | 09-JUL-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 191.97 | 0.00 |
August | 12538.05 | 20-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 265.26 | 0.00 |
September | 11830.56 | 04-SEP-13:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 | 0.00 |
October | 8902.45 | 30-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
November | 6064.71 | 30-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 |
December | 5048.93 | 08-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5048.93 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 | |
Maximum of Months | 12820.01 | 1306.65 | 647.98 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 452.26 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9835.35 | 01-JAN-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
February | 5019.30 | 28-FEB-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
March | 6665.52 | 27-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
April | 12166.63 | 09-APR-09:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 |
May | 11424.71 | 14-MAY-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 | 0.00 |
June | 12935.01 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 0.00 |
July | 12391.88 | 23-JUL-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 0.00 |
August | 12198.99 | 06-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 0.00 |
September | 11243.09 | 10-SEP-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 89.62 | 0.00 |
October | 9283.42 | 09-OCT-11:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 54.97 | 0.00 |
November | 5854.21 | 07-NOV-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
December | 4901.97 | 08-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4901.97 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12935.01 | 827.22 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 89.62 | 38.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14210.13 | 01-JAN-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 |
February | 13694.42 | 19-FEB-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
March | 13530.00 | 26-MAR-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 0.00 |
April | 12929.43 | 16-APR-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 136.58 | 0.00 |
May | 12715.15 | 29-MAY-16:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 456.09 | 0.00 |
June | 11428.72 | 25-JUN-15:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12.30 | 0.00 |
July | 13045.91 | 09-JUL-16:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 196.77 | 0.00 |
August | 13264.79 | 20-AUG-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 241.53 | 0.00 |
September | 13329.85 | 24-SEP-13:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 181.47 | 0.00 |
October | 13744.68 | 29-OCT-12:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 149.81 | 0.00 |
November | 13605.26 | 23-NOV-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 |
December | 13743.39 | 03-DEC-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11428.72 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14210.13 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 456.09 | 78.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5675.79 | 03-JAN-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 0.00 |
February | 14242.87 | 20-FEB-17:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 |
March | 14336.48 | 12-MAR-17:02 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.16 |
April | 13829.71 | 09-APR-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 14071.22 | 29-MAY-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 237.94 | 0.00 |
June | 13405.49 | 10-JUN-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 | 0.00 |
July | 14619.55 | 09-JUL-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 98.98 | 0.00 |
August | 13857.29 | 20-AUG-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 97.21 | 0.00 |
September | 14036.29 | 10-SEP-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 | 0.00 |
October | 14166.10 | 15-OCT-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 48.28 | 0.00 |
November | 8188.77 | 19-NOV-15:43 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
December | 8401.68 | 10-DEC-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 73.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5675.79 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14619.55 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 237.94 | 126.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4677.49 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 | 0.00 |
February | 4594.27 | 17-FEB-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.52 | 0.00 |
March | 4775.44 | 06-MAR-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
April | 5780.26 | 17-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 0.00 |
May | 8375.18 | 24-MAY-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
June | 8693.76 | 26-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
July | 8508.75 | 17-JUL-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
August | 8560.44 | 07-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8441.86 | 25-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 |
October | 7999.80 | 26-OCT-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
November | 5439.88 | 03-NOV-13:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | 0.00 |
December | 4817.55 | 01-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4594.27 | 0.00 | 223.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8693.76 | 1306.65 | 647.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 23.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9240.14 | 01-JAN-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 |
February | 4795.91 | 28-FEB-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
March | 5891.76 | 27-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
April | 10906.65 | 09-APR-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
May | 8106.09 | 14-MAY-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 0.00 |
June | 11151.53 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 0.00 |
July | 11565.53 | 04-JUL-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 0.00 |
August | 10142.34 | 06-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 |
September | 11133.52 | 10-SEP-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 | 0.00 |
October | 11059.84 | 09-OCT-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 0.00 |
November | 5558.09 | 07-NOV-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 0.00 |
December | 4690.70 | 08-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4690.70 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11565.53 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 13.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11951.56 | 01-JAN-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 |
February | 11337.26 | 26-FEB-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
March | 11138.31 | 26-MAR-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 |
April | 9978.83 | 17-APR-16:10 | 1607.03 | 1439.95 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7357.01 | 0.00 |
May | 10722.04 | 22-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8343.36 | 0.00 |
June | 9921.80 | 09-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7020.73 | 0.00 |
July | 10930.68 | 27-JUL-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9455.10 | 0.00 |
August | 10940.39 | 20-AUG-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 142.44 | 0.00 |
September | 11482.48 | 10-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.75 | 0.00 |
October | 12142.17 | 29-OCT-12:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 57.34 | 0.00 |
November | 11785.04 | 19-NOV-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 |
December | 11436.05 | 03-DEC-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9921.80 | 267.84 | 143.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12142.17 | 1607.03 | 1439.95 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9455.10 | 77.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5060.14 | 02-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 0.00 |
February | 11798.51 | 20-FEB-17:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
March | 8706.34 | 12-MAR-17:22 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 |
April | 10746.34 | 02-APR-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
May | 11600.68 | 29-MAY-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 140.76 | 0.00 |
June | 10112.85 | 10-JUN-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 41.04 | 0.00 |
July | 11612.30 | 04-JUL-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 0.00 |
August | 11499.36 | 20-AUG-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | 0.00 |
September | 11754.31 | 10-SEP-15:31 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 0.00 |
October | 11743.23 | 09-OCT-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 0.00 |
November | 6515.01 | 07-NOV-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
December | 6052.68 | 06-DEC-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5060.14 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11798.51 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 140.76 | 61.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4859.61 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 | 0.00 |
February | 4864.91 | 17-FEB-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 | 0.00 |
March | 5230.48 | 28-MAR-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 0.00 |
April | 6359.92 | 17-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.69 | 0.00 |
May | 10550.47 | 29-MAY-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 387.76 | 0.00 |
June | 9000.95 | 12-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
July | 9039.26 | 17-JUL-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
August | 9065.11 | 20-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 231.37 | 0.00 |
September | 8824.10 | 09-SEP-05:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 0.00 |
October | 8131.07 | 10-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
November | 6832.73 | 30-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
December | 4713.11 | 07-DEC-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4713.11 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10550.47 | 1306.65 | 647.98 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 387.76 | 3.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11172.39 | 01-JAN-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
February | 5412.68 | 28-FEB-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
March | 6462.01 | 27-MAR-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 0.00 |
April | 12090.38 | 09-APR-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.13 |
May | 10932.39 | 07-MAY-08:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
June | 12344.68 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 0.00 |
July | 12791.07 | 23-JUL-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 34.63 | 0.00 |
August | 11269.72 | 06-AUG-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | 0.00 |
September | 12237.69 | 10-SEP-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 0.00 |
October | 12095.10 | 09-OCT-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 |
November | 6087.12 | 07-NOV-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
December | 4865.24 | 08-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4865.24 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12791.07 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 32.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11908.32 | 15-JAN-11:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.39 |
February | 12628.28 | 20-FEB-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.10 |
March | 11243.98 | 12-MAR-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.55 |
April | 9559.90 | 16-APR-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 0.00 |
May | 10193.05 | 29-MAY-16:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 387.92 | 0.00 |
June | 9105.38 | 12-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
July | 10190.09 | 30-JUL-16:12 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 194.45 | 0.00 |
August | 11331.08 | 20-AUG-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 213.04 | 0.00 |
September | 11843.79 | 10-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 138.90 | 0.00 |
October | 12755.81 | 29-OCT-12:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 | 0.00 |
November | 12323.27 | 19-NOV-12:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 |
December | 11960.97 | 03-DEC-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9105.38 | 0.00 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12755.81 | 401.76 | 223.18 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 387.92 | 184.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5497.00 | 03-JAN-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
February | 12916.58 | 20-FEB-17:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 |
March | 12972.10 | 12-MAR-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.63 |
April | 12799.20 | 09-APR-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 |
May | 12694.00 | 29-MAY-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 204.99 | 0.00 |
June | 12029.28 | 10-JUN-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 | 0.00 |
July | 12731.30 | 04-JUL-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 101.47 | 0.00 |
August | 12560.35 | 20-AUG-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 85.57 | 0.00 |
September | 12960.01 | 10-SEP-15:31 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 100.60 | 0.00 |
October | 12810.66 | 15-OCT-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 0.00 |
November | 7296.32 | 19-NOV-14:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
December | 7385.31 | 10-DEC-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 62.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5497.00 | 211.94 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12972.10 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 204.99 | 96.63 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.130483E+12 | 141944.82 | 02-JAN-13:00 | 0.990952E+10 | 9537.37 | 25-JAN-12:09 |
February | 0.122258E+12 | 126674.41 | 17-FEB-13:00 | 0.894990E+10 | 10100.98 | 04-FEB-07:19 |
March | 0.143662E+12 | 136841.25 | 27-MAR-15:20 | 0.100399E+11 | 9500.89 | 01-MAR-12:39 |
April | 0.142962E+12 | 145404.84 | 14-APR-15:09 | 0.926493E+10 | 9440.67 | 03-APR-11:30 |
May | 0.168080E+12 | 156115.83 | 22-MAY-12:00 | 0.952030E+10 | 9382.15 | 01-MAY-11:30 |
June | 0.176145E+12 | 151054.20 | 08-JUN-15:00 | 0.915993E+10 | 9329.17 | 05-JUN-11:20 |
July | 0.179421E+12 | 165180.87 | 28-JUL-15:30 | 0.909654E+10 | 9301.73 | 14-JUL-11:09 |
August | 0.187089E+12 | 160283.65 | 21-AUG-15:00 | 0.947719E+10 | 9328.63 | 31-AUG-11:20 |
September | 0.171832E+12 | 157465.49 | 18-SEP-15:30 | 0.905388E+10 | 9374.71 | 27-SEP-11:09 |
October | 0.166894E+12 | 154353.13 | 02-OCT-15:09 | 0.952640E+10 | 9435.42 | 30-OCT-11:09 |
November | 0.147796E+12 | 141826.48 | 10-NOV-13:00 | 0.945917E+10 | 9494.86 | 30-NOV-12:09 |
December | 0.131688E+12 | 135073.11 | 08-DEC-16:10 | 0.974664E+10 | 9524.46 | 28-DEC-12:09 |
Annual Sum or Average | 0.186831E+13 | 0.113204E+12 | ||||
Minimum of Months | 0.122258E+12 | 126674.41 | 0.894990E+10 | 9301.73 | ||
Maximum of Months | 0.187089E+12 | 165180.87 | 0.100399E+11 | 10100.98 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.254839E+11 | 0.512820E+10 | 0.593559E+11 | 0.988825E+09 | 0.546697E+10 | 12379742.02 | 0.595955E+09 | 0.334505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228719E+11 | 0.428778E+10 | 0.537310E+11 | 0.894721E+09 | 0.545679E+10 | 11196021.66 | 0.428642E+09 | 0.345755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269744E+11 | 0.434999E+10 | 0.617796E+11 | 0.103571E+10 | 0.671675E+10 | 12675672.10 | 0.391938E+09 | 0.424008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239187E+11 | 0.383914E+10 | 0.572952E+11 | 0.952025E+09 | 0.722250E+10 | 11960507.72 | 11651581.37 | 0.497111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257245E+11 | 0.362394E+10 | 0.605677E+11 | 0.101191E+10 | 0.915266E+10 | 12527707.06 | 0.00 | 0.679870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256470E+11 | 0.337880E+10 | 0.594895E+11 | 0.996307E+09 | 0.966716E+10 | 12231776.97 | 0.00 | 0.769535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238724E+11 | 0.355877E+10 | 0.583622E+11 | 0.967491E+09 | 0.101436E+11 | 12256437.81 | 0.00 | 0.825041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267699E+11 | 0.384121E+10 | 0.617796E+11 | 0.103556E+10 | 0.104656E+11 | 12675672.10 | 0.00 | 0.831846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240446E+11 | 0.402405E+10 | 0.572729E+11 | 0.951886E+09 | 0.960858E+10 | 11960507.72 | 0.00 | 0.759177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251372E+11 | 0.455503E+10 | 0.593671E+11 | 0.988689E+09 | 0.921812E+10 | 12379742.02 | 0.00 | 0.676154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250917E+11 | 0.482873E+10 | 0.580818E+11 | 0.970493E+09 | 0.725741E+10 | 12059151.09 | 80028984.52 | 0.514740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247627E+11 | 0.521691E+10 | 0.583511E+11 | 0.968010E+09 | 0.566682E+10 | 12256437.81 | 0.585119E+09 | 0.361251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300299E+12 | 0.506325E+11 | 0.705434E+12 | 0.117616E+11 | 0.960430E+11 | 0.146559E+09 | 0.209333E+10 | 0.701899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228719E+11 | 0.337880E+10 | 0.537310E+11 | 0.894721E+09 | 0.545679E+10 | 11196021.66 | 0.00 | 0.334505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269744E+11 | 0.521691E+10 | 0.617796E+11 | 0.103571E+10 | 0.104656E+11 | 12675672.10 | 0.595955E+09 | 0.831846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.990952E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 10680076.14 | 0.00 | 0.893922E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.100399E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.926493E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.952030E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.915993E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.909654E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.947719E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.905388E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.952640E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.945917E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.974664E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10680076.14 | 0.00 | 0.113194E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.893922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 10680076.14 | 0.00 | 0.100399E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30940.97 | 04-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 846.73 | 04-JAN-16:00 | 10894.54 | 02-JAN-14:00 | 6.85 | 01-JAN-06:10 | 29884.65 | 25-JAN-07:10 |
February | 28370.68 | 08-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 843.32 | 07-FEB-08:20 | 9887.07 | 21-FEB-16:10 | 6.85 | 03-FEB-17:10 | 43312.35 | 04-FEB-07:10 |
March | 28901.49 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 845.37 | 15-MAR-07:19 | 11504.32 | 27-MAR-15:30 | 6.85 | 15-MAR-11:09 | 29714.14 | 16-MAR-06:10 |
April | 29070.25 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 845.59 | 12-APR-07:19 | 11732.51 | 17-APR-15:20 | 6.85 | 01-APR-05:10 | 4149.28 | 19-APR-06:19 |
May | 27476.09 | 25-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 843.46 | 25-MAY-07:19 | 13354.57 | 22-MAY-12:00 | 6.85 | 29-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 31270.76 | 15-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 848.55 | 15-JUN-07:19 | 12277.04 | 29-JUN-15:30 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 27476.09 | 05-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 843.46 | 05-JUL-07:19 | 14235.27 | 31-JUL-14:30 | 6.85 | 27-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 29543.89 | 28-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 846.23 | 28-AUG-07:19 | 13436.11 | 31-AUG-15:20 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 32642.50 | 27-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 850.39 | 27-SEP-07:19 | 13551.06 | 18-SEP-13:39 | 6.85 | 10-SEP-15:39 | 0.00 | 01-SEP-00:10 |
October | 31160.83 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 848.40 | 31-OCT-07:19 | 13252.32 | 02-OCT-15:09 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 30711.07 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 847.27 | 24-NOV-08:20 | 11562.85 | 06-NOV-15:30 | 6.85 | 01-NOV-05:10 | 14375.88 | 27-NOV-07:10 |
December | 32642.50 | 15-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 849.01 | 15-DEC-16:49 | 9934.07 | 08-DEC-16:10 | 6.85 | 01-DEC-06:10 | 28578.35 | 15-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 27476.09 | 5686.19 | 45864.70 | 843.32 | 9887.07 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 45864.70 | 850.39 | 14235.27 | 6.85 | 43312.35 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 62555.00 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48904.40 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 56787.11 | 27-MAR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65813.64 | 14-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73831.34 | 22-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70823.85 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82384.97 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78476.22 | 21-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75388.68 | 18-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74244.86 | 02-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63228.75 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55425.25 | 08-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 48904.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82384.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 141944.82 | 02-JAN-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 10459.91 | 6.85 | 0.00 | 62555.00 | 0.00 |
February | 126674.41 | 17-FEB-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 8840.09 | 6.85 | 0.00 | 48904.40 | 0.00 |
March | 136841.25 | 27-MAR-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 11488.95 | 6.85 | 0.00 | 56752.27 | 0.00 |
April | 145404.84 | 14-APR-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 11148.53 | 6.85 | 0.00 | 65656.27 | 0.00 |
May | 156115.83 | 22-MAY-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 13354.57 | 6.85 | 0.00 | 73831.34 | 0.00 |
June | 151054.20 | 08-JUN-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 11630.32 | 6.85 | 0.00 | 70823.85 | 0.00 |
July | 165180.87 | 28-JUL-15:30 | 25681.07 | 42072.41 | 0.00 | 839.70 | 14195.87 | 6.85 | 0.00 | 82384.97 | 0.00 |
August | 160283.65 | 21-AUG-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13207.39 | 6.85 | 0.00 | 78476.22 | 0.00 |
September | 157465.49 | 18-SEP-15:30 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13476.78 | 6.85 | 0.00 | 75388.68 | 0.00 |
October | 154353.13 | 02-OCT-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13252.32 | 6.85 | 0.00 | 72500.78 | 0.00 |
November | 141826.48 | 10-NOV-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 10817.54 | 6.85 | 0.00 | 62079.03 | 0.00 |
December | 135073.11 | 08-DEC-16:10 | 27150.80 | 42072.41 | 0.00 | 840.11 | 9934.07 | 6.85 | 0.00 | 55068.87 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 126674.41 | 25681.07 | 42072.41 | 0.00 | 839.70 | 8840.09 | 6.85 | 0.00 | 48904.40 | 0.00 | |
Maximum of Months | 165180.87 | 27150.80 | 42402.18 | 0.00 | 840.11 | 14195.87 | 6.85 | 0.00 | 82384.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9537.37 | 25-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 2416.80 | 04-FEB-06:10 | 0.00 | 9539.37 | 03-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9500.89 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9440.67 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9382.15 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9329.17 | 05-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9301.73 | 14-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9328.63 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9374.71 | 27-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9435.42 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9494.86 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9524.46 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9301.73 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2416.80 | 0.00 | 9539.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 1.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.33 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.50 | 6.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.52 | 2.83 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.41 | 3.83 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 27.49 | 16.83 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.55 | 6.17 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.49 | 0.33 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.33 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.62 | 5.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.76 | 6.83 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.94 | 13.17 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.74 | 6.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.78 | 8.17 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.79 | 1.83 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.33 | 27.80 | 47.00 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.94 | 13.17 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.68 | 7.33 | 26.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.95 | 4.17 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.51 | 2.50 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.55 | 2.00 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.42 | 2.17 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.55 | 6.00 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.65 | 4.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.86 | 7.00 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.97 | 8.50 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.23 | 12.17 | 26.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.98 | 7.83 | 26.98 |
Annual Sum or Average | 0.00 | 0.00 | 67.83 | 27.27 | 65.33 | 27.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.23 | 1.67 | 26.23 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.97 | 12.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.99 | 1.67 | 28.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.91 | 1.00 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.01 | 3.67 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.97 | 3.00 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.90 | 2.50 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.01 | 5.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.06 | 3.33 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.07 | 4.00 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.92 | 3.83 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 27.98 | 30.00 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.07 | 5.50 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.69 | 1.50 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 3.33 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.76 | 8.83 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.53 | 4.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.55 | 6.00 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.62 | 1.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.00 | 27.63 | 28.00 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.76 | 8.83 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 19.85 | 4.67 | 19.85 | 12.33 | 23.45 | 12.33 | 24.44 |
February | 2.00 | 19.88 | 2.00 | 19.88 | 13.83 | 24.30 | 13.83 | 24.86 |
March | 5.83 | 19.33 | 5.83 | 19.33 | 1.33 | 19.95 | 1.33 | 20.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.94 | 6.00 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.03 | 19.67 | 25.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 24.93 | 28.00 | 24.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 25.39 | 35.17 | 25.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 25.35 | 39.17 | 25.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 25.45 | 53.83 | 25.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | 25.36 | 76.17 | 25.36 |
November | 0.50 | 20.27 | 0.50 | 20.27 | 50.50 | 25.17 | 50.50 | 25.22 |
December | 5.33 | 19.65 | 5.33 | 19.65 | 16.67 | 23.44 | 16.67 | 24.36 |
Annual Sum or Average | 18.33 | 19.64 | 18.33 | 19.64 | 353.17 | 24.83 | 352.67 | 25.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 19.95 | 1.33 | 20.46 |
Maximum of Months | 5.83 | 20.27 | 5.83 | 20.27 | 76.50 | 25.45 | 76.17 | 25.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 1.17 | 27.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.69 | 0.33 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 2.33 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.72 | 1.83 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.65 | 1.33 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.74 | 4.17 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.76 | 2.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.80 | 3.33 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.68 | 3.33 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 27.33 | 27.73 | 21.17 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 4.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 0.83 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 27.39 | 1.83 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 0.83 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 3.83 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.50 | 4.33 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.72 | 4.50 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.86 | 10.17 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 4.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.65 | 5.67 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.85 | 1.50 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.17 | 27.71 | 36.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.86 | 10.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.00 | 12.50 | 26.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.02 | 10.00 | 26.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.83 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 1.00 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.72 | 6.17 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 26.34 | 16.00 | 26.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 25.46 | 28.00 | 25.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.95 | 14.50 | 25.95 |
Annual Sum or Average | 0.00 | 0.00 | 93.67 | 26.11 | 93.50 | 26.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.72 | 28.00 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.98 | 1.50 | 27.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.72 | 0.83 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.91 | 2.83 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.88 | 2.33 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.82 | 1.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.90 | 4.50 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 2.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.94 | 3.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.83 | 3.33 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
Annual Sum or Average | 0.00 | 0.00 | 30.83 | 27.88 | 24.33 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.98 | 4.50 | 27.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.00 | 23.76 | 296.50 | 24.50 | 0.00 | 24.50 |
February | 20.83 | 23.59 | 301.00 | 24.42 | 0.00 | 24.42 |
March | 7.67 | 23.85 | 368.83 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 446.17 | 24.39 | 0.00 | 24.39 |
May | 0.00 | 0.00 | 505.67 | 24.37 | 0.00 | 24.37 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 513.17 | 24.34 | 0.00 | 24.34 |
September | 0.00 | 0.00 | 485.00 | 24.35 | 0.00 | 24.35 |
October | 0.00 | 0.00 | 502.00 | 24.43 | 0.00 | 24.43 |
November | 0.00 | 0.00 | 465.00 | 24.47 | 0.00 | 24.47 |
December | 18.33 | 23.63 | 333.00 | 24.46 | 0.00 | 24.46 |
Annual Sum or Average | 65.83 | 23.68 | 5209.33 | 24.40 | 0.00 | 24.40 |
Minimum of Months | 0.00 | 0.00 | 296.50 | 24.34 | 0.00 | 24.34 |
Maximum of Months | 20.83 | 23.85 | 513.17 | 24.50 | 0.00 | 24.50 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 205.33 | 23.23 | 146.67 | 23.69 | 0.00 | 23.69 |
February | 135.17 | 23.11 | 178.33 | 23.83 | 0.00 | 23.83 |
March | 121.67 | 23.28 | 248.33 | 23.97 | 0.00 | 23.97 |
April | 21.17 | 23.32 | 307.50 | 24.26 | 0.00 | 24.26 |
May | 3.67 | 23.23 | 435.50 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 459.00 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 461.33 | 24.27 | 0.00 | 24.27 |
August | 2.33 | 23.20 | 472.00 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 436.83 | 24.26 | 0.00 | 24.26 |
October | 1.17 | 23.22 | 430.17 | 24.34 | 0.00 | 24.34 |
November | 33.50 | 23.29 | 337.50 | 24.28 | 0.00 | 24.28 |
December | 165.67 | 23.13 | 154.67 | 23.71 | 0.00 | 23.71 |
Annual Sum or Average | 689.67 | 23.20 | 4067.83 | 24.14 | 0.00 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 146.67 | 23.69 | 0.00 | 23.69 |
Maximum of Months | 205.33 | 23.32 | 472.00 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.50 | 22.88 | 93.67 | 23.17 | 0.00 | 23.17 |
February | 211.17 | 22.81 | 146.17 | 23.40 | 0.33 | 23.40 |
March | 179.67 | 23.00 | 215.33 | 23.68 | 0.00 | 23.68 |
April | 65.83 | 23.22 | 293.67 | 24.08 | 0.00 | 24.08 |
May | 7.17 | 23.29 | 429.17 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 467.67 | 24.27 | 0.00 | 24.27 |
July | 0.17 | 23.30 | 473.50 | 24.30 | 0.00 | 24.30 |
August | 6.00 | 22.96 | 467.50 | 24.25 | 0.00 | 24.25 |
September | 0.67 | 23.29 | 435.83 | 24.27 | 0.00 | 24.27 |
October | 15.33 | 23.19 | 392.17 | 24.31 | 0.00 | 24.31 |
November | 94.67 | 23.10 | 275.00 | 24.00 | 0.00 | 24.00 |
December | 270.33 | 22.78 | 120.83 | 23.22 | 0.00 | 23.22 |
Annual Sum or Average | 1174.50 | 22.91 | 3810.50 | 23.96 | 0.33 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 93.67 | 23.17 | 0.00 | 23.17 |
Maximum of Months | 323.50 | 23.30 | 473.50 | 24.31 | 0.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.67 | 22.39 | 110.83 | 22.73 | 19.33 | 22.70 |
February | 241.33 | 22.57 | 174.17 | 23.11 | 28.50 | 23.08 |
March | 223.17 | 22.77 | 258.33 | 23.51 | 31.33 | 23.54 |
April | 93.17 | 23.67 | 346.33 | 24.17 | 25.00 | 24.22 |
May | 59.50 | 25.51 | 491.83 | 24.52 | 57.17 | 24.62 |
June | 48.50 | 25.87 | 495.33 | 24.56 | 48.50 | 24.67 |
July | 56.17 | 26.23 | 492.83 | 24.71 | 56.17 | 24.85 |
August | 52.17 | 25.89 | 498.17 | 24.55 | 52.17 | 24.67 |
September | 51.17 | 25.71 | 468.33 | 24.56 | 49.83 | 24.67 |
October | 67.83 | 24.89 | 442.67 | 24.49 | 50.33 | 24.58 |
November | 144.17 | 23.34 | 312.33 | 23.95 | 36.83 | 24.01 |
December | 315.50 | 22.48 | 174.50 | 23.01 | 46.50 | 23.04 |
Annual Sum or Average | 1706.33 | 23.27 | 4265.67 | 24.03 | 501.67 | 24.11 |
Minimum of Months | 48.50 | 22.39 | 110.83 | 22.73 | 19.33 | 22.70 |
Maximum of Months | 353.67 | 26.23 | 498.17 | 24.71 | 57.17 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.17 | 22.42 | 156.67 | 23.06 | 18.00 | 23.08 |
February | 203.50 | 22.64 | 213.17 | 23.37 | 23.17 | 23.36 |
March | 176.50 | 22.95 | 294.67 | 23.74 | 29.00 | 23.78 |
April | 108.17 | 24.13 | 365.00 | 24.36 | 41.17 | 24.49 |
May | 67.00 | 25.77 | 476.00 | 24.59 | 62.50 | 24.73 |
June | 54.83 | 26.23 | 492.00 | 24.62 | 54.83 | 24.76 |
July | 72.50 | 26.58 | 489.67 | 24.83 | 72.17 | 25.03 |
August | 64.83 | 25.69 | 490.83 | 24.57 | 53.17 | 24.72 |
September | 67.33 | 26.02 | 459.17 | 24.68 | 62.17 | 24.85 |
October | 86.50 | 25.20 | 433.33 | 24.60 | 62.83 | 24.76 |
November | 120.50 | 23.40 | 327.67 | 24.04 | 32.50 | 24.11 |
December | 298.00 | 22.46 | 194.17 | 23.11 | 42.83 | 23.16 |
Annual Sum or Average | 1600.83 | 23.60 | 4392.33 | 24.18 | 554.33 | 24.30 |
Minimum of Months | 54.83 | 22.42 | 156.67 | 23.06 | 18.00 | 23.08 |
Maximum of Months | 298.00 | 26.58 | 492.00 | 24.83 | 72.17 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.17 | 23.03 | 249.83 | 23.79 | 34.83 | 23.91 |
February | 165.67 | 23.26 | 252.50 | 23.92 | 38.33 | 24.01 |
March | 165.17 | 23.25 | 310.83 | 23.92 | 39.83 | 24.00 |
April | 97.67 | 24.10 | 359.00 | 24.33 | 36.67 | 24.43 |
May | 63.83 | 25.35 | 485.83 | 24.51 | 57.67 | 24.61 |
June | 45.67 | 25.74 | 491.67 | 24.52 | 45.67 | 24.61 |
July | 54.67 | 26.16 | 490.83 | 24.68 | 54.67 | 24.81 |
August | 52.83 | 25.96 | 498.50 | 24.57 | 52.83 | 24.69 |
September | 63.00 | 26.08 | 471.17 | 24.68 | 62.17 | 24.83 |
October | 88.17 | 25.94 | 467.00 | 24.78 | 79.50 | 24.97 |
November | 112.17 | 24.42 | 392.83 | 24.49 | 55.33 | 24.64 |
December | 225.67 | 23.28 | 274.33 | 23.91 | 65.33 | 24.07 |
Annual Sum or Average | 1358.67 | 24.09 | 4744.33 | 24.36 | 622.83 | 24.49 |
Minimum of Months | 45.67 | 23.03 | 249.83 | 23.79 | 34.83 | 23.91 |
Maximum of Months | 225.67 | 26.16 | 498.50 | 24.78 | 79.50 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 335.67 | 22.11 | 135.00 | 22.64 | 17.83 | 22.61 |
February | 253.17 | 22.49 | 177.83 | 23.13 | 33.33 | 23.15 |
March | 217.33 | 22.65 | 269.83 | 23.52 | 34.17 | 23.57 |
April | 132.83 | 23.71 | 332.17 | 24.21 | 39.67 | 24.34 |
May | 69.83 | 24.90 | 445.67 | 24.49 | 50.17 | 24.59 |
June | 44.83 | 25.65 | 469.83 | 24.50 | 41.00 | 24.60 |
July | 52.33 | 25.99 | 471.50 | 24.64 | 47.00 | 24.78 |
August | 55.67 | 25.24 | 477.17 | 24.49 | 42.83 | 24.60 |
September | 64.83 | 25.18 | 436.67 | 24.53 | 47.00 | 24.66 |
October | 96.83 | 24.53 | 410.00 | 24.47 | 54.33 | 24.61 |
November | 165.33 | 23.05 | 294.17 | 23.84 | 35.33 | 23.91 |
December | 311.33 | 22.30 | 181.83 | 22.97 | 46.17 | 23.03 |
Annual Sum or Average | 1800.00 | 23.11 | 4101.67 | 23.98 | 488.83 | 24.08 |
Minimum of Months | 44.83 | 22.11 | 135.00 | 22.64 | 17.83 | 22.61 |
Maximum of Months | 335.67 | 25.99 | 477.17 | 24.64 | 54.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.33 | 22.91 | 138.50 | 23.34 | 1.33 | 23.34 |
February | 198.17 | 23.04 | 186.50 | 23.60 | 13.67 | 23.65 |
March | 204.67 | 23.13 | 252.50 | 23.74 | 26.50 | 23.80 |
April | 53.83 | 24.08 | 351.67 | 24.24 | 18.83 | 24.29 |
May | 26.17 | 25.68 | 502.00 | 24.43 | 26.17 | 24.49 |
June | 18.00 | 26.01 | 496.00 | 24.44 | 18.00 | 24.49 |
July | 11.50 | 26.14 | 497.00 | 24.52 | 11.50 | 24.56 |
August | 20.17 | 25.90 | 514.00 | 24.45 | 20.17 | 24.50 |
September | 12.67 | 25.79 | 485.00 | 24.45 | 12.67 | 24.49 |
October | 26.33 | 25.87 | 491.33 | 24.49 | 26.33 | 24.56 |
November | 58.00 | 24.08 | 387.17 | 24.27 | 22.33 | 24.32 |
December | 235.67 | 23.09 | 204.17 | 23.64 | 23.83 | 23.70 |
Annual Sum or Average | 1134.50 | 23.42 | 4505.83 | 24.17 | 221.33 | 24.22 |
Minimum of Months | 11.50 | 22.91 | 138.50 | 23.34 | 1.33 | 23.34 |
Maximum of Months | 269.33 | 26.14 | 514.00 | 24.52 | 26.50 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.00 | 23.09 | 227.83 | 23.83 | 5.67 | 23.87 |
February | 122.17 | 23.27 | 253.50 | 23.96 | 13.67 | 24.00 |
March | 111.00 | 23.57 | 324.00 | 24.12 | 27.00 | 24.19 |
April | 43.67 | 25.19 | 405.17 | 24.49 | 28.50 | 24.60 |
May | 36.00 | 26.29 | 498.50 | 24.56 | 36.00 | 24.67 |
June | 35.67 | 26.56 | 496.00 | 24.59 | 35.67 | 24.72 |
July | 56.33 | 26.76 | 497.00 | 24.81 | 56.33 | 24.99 |
August | 39.00 | 26.57 | 514.00 | 24.60 | 39.00 | 24.73 |
September | 40.67 | 26.63 | 485.00 | 24.68 | 40.67 | 24.82 |
October | 38.50 | 26.46 | 499.00 | 24.65 | 38.50 | 24.77 |
November | 40.83 | 24.69 | 427.17 | 24.40 | 22.00 | 24.47 |
December | 191.67 | 23.18 | 235.00 | 23.85 | 25.17 | 23.93 |
Annual Sum or Average | 922.50 | 24.29 | 4862.17 | 24.42 | 368.17 | 24.53 |
Minimum of Months | 35.67 | 23.09 | 227.83 | 23.83 | 5.67 | 23.87 |
Maximum of Months | 191.67 | 26.76 | 514.00 | 24.81 | 56.33 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 138.67 | 23.43 | 335.00 | 24.22 | 41.50 | 24.31 |
February | 106.50 | 23.64 | 327.17 | 24.29 | 43.67 | 24.39 |
March | 155.67 | 23.31 | 350.50 | 23.99 | 64.33 | 24.03 |
April | 72.33 | 24.08 | 394.83 | 24.31 | 49.83 | 24.34 |
May | 112.50 | 24.50 | 502.67 | 24.42 | 112.50 | 24.43 |
June | 142.00 | 24.48 | 496.00 | 24.43 | 142.00 | 24.44 |
July | 118.17 | 24.67 | 497.00 | 24.59 | 118.17 | 24.60 |
August | 147.17 | 24.80 | 514.00 | 24.60 | 147.17 | 24.63 |
September | 138.17 | 25.09 | 485.00 | 24.77 | 138.17 | 24.83 |
October | 138.50 | 25.54 | 501.17 | 24.95 | 138.50 | 25.06 |
November | 114.50 | 24.94 | 459.67 | 24.72 | 105.33 | 24.80 |
December | 163.33 | 23.87 | 332.50 | 24.36 | 65.50 | 24.52 |
Annual Sum or Average | 1547.50 | 24.36 | 5195.50 | 24.50 | 1166.67 | 24.56 |
Minimum of Months | 72.33 | 23.31 | 327.17 | 23.99 | 41.50 | 24.03 |
Maximum of Months | 163.33 | 25.54 | 514.00 | 24.95 | 147.17 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 215.50 | 22.88 | 190.83 | 23.54 | 2.33 | 23.54 |
February | 154.33 | 23.17 | 232.83 | 23.88 | 18.17 | 23.96 |
March | 139.50 | 23.32 | 317.17 | 24.03 | 28.50 | 24.10 |
April | 47.67 | 25.10 | 403.00 | 24.48 | 30.50 | 24.59 |
May | 33.33 | 26.22 | 490.17 | 24.55 | 33.33 | 24.65 |
June | 26.00 | 26.35 | 493.33 | 24.50 | 26.00 | 24.59 |
July | 30.83 | 26.61 | 494.83 | 24.65 | 30.83 | 24.76 |
August | 31.00 | 26.42 | 514.00 | 24.56 | 31.00 | 24.66 |
September | 28.17 | 26.55 | 482.83 | 24.60 | 28.17 | 24.70 |
October | 40.00 | 26.39 | 493.00 | 24.65 | 39.67 | 24.77 |
November | 54.33 | 24.21 | 408.67 | 24.35 | 23.33 | 24.41 |
December | 205.67 | 23.15 | 249.83 | 23.84 | 26.83 | 23.91 |
Annual Sum or Average | 1006.33 | 23.88 | 4770.50 | 24.34 | 318.67 | 24.43 |
Minimum of Months | 26.00 | 22.88 | 190.83 | 23.54 | 2.33 | 23.54 |
Maximum of Months | 215.50 | 26.61 | 514.00 | 24.65 | 39.67 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.00 | 22.76 | 125.17 | 23.17 | 7.50 | 23.18 |
February | 201.00 | 22.89 | 191.83 | 23.47 | 20.67 | 23.49 |
March | 185.50 | 23.09 | 277.33 | 23.78 | 26.67 | 23.83 |
April | 54.67 | 24.15 | 377.00 | 24.27 | 22.33 | 24.32 |
May | 44.67 | 25.63 | 503.17 | 24.50 | 44.67 | 24.58 |
June | 31.00 | 25.80 | 496.00 | 24.50 | 31.00 | 24.57 |
July | 29.83 | 26.17 | 496.00 | 24.61 | 29.83 | 24.69 |
August | 38.67 | 25.73 | 510.83 | 24.49 | 38.67 | 24.57 |
September | 28.00 | 25.61 | 482.17 | 24.48 | 28.00 | 24.54 |
October | 41.50 | 25.53 | 469.00 | 24.51 | 38.67 | 24.60 |
November | 99.67 | 23.78 | 352.83 | 24.16 | 32.00 | 24.23 |
December | 271.83 | 22.87 | 187.83 | 23.42 | 35.67 | 23.49 |
Annual Sum or Average | 1330.33 | 23.46 | 4469.17 | 24.15 | 355.67 | 24.22 |
Minimum of Months | 28.00 | 22.76 | 125.17 | 23.17 | 7.50 | 23.18 |
Maximum of Months | 304.00 | 26.17 | 510.83 | 24.61 | 44.67 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 231.17 | 22.71 | 133.33 | 23.36 | 11.50 | 23.41 |
February | 165.33 | 22.92 | 176.00 | 23.63 | 17.50 | 23.67 |
March | 143.00 | 23.21 | 241.17 | 23.93 | 26.50 | 24.00 |
April | 79.83 | 24.55 | 309.50 | 24.52 | 37.17 | 24.67 |
May | 52.00 | 26.08 | 406.33 | 24.68 | 51.83 | 24.83 |
June | 43.83 | 26.36 | 415.83 | 24.69 | 43.83 | 24.83 |
July | 63.00 | 26.69 | 417.67 | 24.93 | 63.00 | 25.13 |
August | 45.17 | 26.26 | 418.00 | 24.67 | 45.17 | 24.81 |
September | 50.33 | 26.38 | 394.33 | 24.76 | 50.33 | 24.93 |
October | 54.17 | 25.85 | 377.50 | 24.73 | 48.50 | 24.88 |
November | 82.83 | 23.84 | 290.83 | 24.28 | 27.83 | 24.37 |
December | 239.50 | 22.79 | 162.17 | 23.43 | 34.00 | 23.54 |
Annual Sum or Average | 1250.17 | 23.88 | 3742.67 | 24.35 | 457.17 | 24.48 |
Minimum of Months | 43.83 | 22.71 | 133.33 | 23.36 | 11.50 | 23.41 |
Maximum of Months | 239.50 | 26.69 | 418.00 | 24.93 | 63.00 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.67 | 23.43 | 276.50 | 24.15 | 27.17 | 24.27 |
February | 119.00 | 23.68 | 281.17 | 24.23 | 33.00 | 24.36 |
March | 119.17 | 23.55 | 330.83 | 24.13 | 32.00 | 24.21 |
April | 52.50 | 24.57 | 387.67 | 24.40 | 27.67 | 24.48 |
May | 45.67 | 25.61 | 498.50 | 24.50 | 45.67 | 24.58 |
June | 29.67 | 25.65 | 496.00 | 24.46 | 29.67 | 24.52 |
July | 29.17 | 26.09 | 496.00 | 24.58 | 29.17 | 24.66 |
August | 45.83 | 25.92 | 512.00 | 24.53 | 45.83 | 24.64 |
September | 51.50 | 26.25 | 483.33 | 24.66 | 51.50 | 24.80 |
October | 73.83 | 26.41 | 488.33 | 24.83 | 72.83 | 25.02 |
November | 81.83 | 25.13 | 422.33 | 24.66 | 52.67 | 24.81 |
December | 194.83 | 23.75 | 297.50 | 24.25 | 57.17 | 24.43 |
Annual Sum or Average | 1010.67 | 24.45 | 4970.17 | 24.46 | 504.33 | 24.58 |
Minimum of Months | 29.17 | 23.43 | 276.50 | 24.13 | 27.17 | 24.21 |
Maximum of Months | 194.83 | 26.41 | 512.00 | 24.83 | 72.83 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.50 | 22.50 | 153.17 | 23.11 | 7.50 | 23.11 |
February | 201.67 | 22.80 | 198.33 | 23.53 | 24.83 | 23.60 |
March | 174.83 | 22.99 | 295.67 | 23.81 | 29.00 | 23.88 |
April | 89.67 | 24.28 | 365.33 | 24.38 | 36.83 | 24.50 |
May | 49.17 | 25.63 | 470.83 | 24.53 | 44.50 | 24.64 |
June | 32.67 | 26.03 | 484.17 | 24.49 | 32.67 | 24.58 |
July | 38.83 | 26.40 | 489.00 | 24.62 | 38.67 | 24.74 |
August | 37.33 | 25.97 | 493.67 | 24.51 | 37.33 | 24.61 |
September | 39.83 | 26.04 | 456.83 | 24.56 | 38.33 | 24.68 |
October | 63.17 | 25.41 | 445.50 | 24.59 | 49.50 | 24.72 |
November | 114.83 | 23.48 | 334.67 | 24.12 | 29.83 | 24.19 |
December | 270.00 | 22.71 | 200.67 | 23.40 | 36.83 | 23.49 |
Annual Sum or Average | 1400.50 | 23.46 | 4387.83 | 24.17 | 405.83 | 24.27 |
Minimum of Months | 32.67 | 22.50 | 153.17 | 23.11 | 7.50 | 23.11 |
Maximum of Months | 288.50 | 26.40 | 493.67 | 24.62 | 49.50 | 24.74 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32350 | 40.86303 | 0.46749 | 9.86703 |
February | 454.00000 | 24.32543 | 41.77357 | 0.47714 | 10.13752 |
March | 514.00000 | 24.32867 | 42.51753 | 0.49096 | 10.34875 |
April | 485.00000 | 24.35477 | 45.66164 | 0.52756 | 11.04642 |
May | 508.00000 | 24.36972 | 47.62612 | -0.2921 | 7.22753 |
June | 496.00000 | 24.34166 | 48.05141 | -0.2916 | 7.21769 |
July | 497.00000 | 24.36187 | 47.86902 | -0.2867 | 7.14762 |
August | 514.00000 | 24.33699 | 48.03026 | -0.2914 | 7.19778 |
September | 485.00000 | 24.35153 | 47.80569 | -0.2894 | 7.19034 |
October | 502.00000 | 24.42579 | 47.26413 | 0.56787 | 12.03534 |
November | 489.00000 | 24.44470 | 46.22311 | 0.55381 | 11.72023 |
December | 497.00000 | 24.31845 | 42.61697 | 0.48002 | 10.10953 |
Annual Sum or Average | 5943.00000 | 24.35697 | 45.54610 | 0.17303 | 9.25807 |
Minimum of Months | 454.00000 | 24.31845 | 40.86303 | -0.2921 | 7.14762 |
Maximum of Months | 514.00000 | 24.44470 | 48.05141 | 0.56787 | 12.03534 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77218 | 42.85413 | 0.32746 | 7.74841 |
February | 454.00000 | 23.83817 | 43.73069 | 0.35519 | 8.31032 |
March | 514.00000 | 23.94618 | 44.23575 | 0.39280 | 8.66616 |
April | 485.00000 | 24.08540 | 47.23070 | 0.45879 | 9.61705 |
May | 508.00000 | 24.19128 | 48.87083 | -0.3637 | 8.13595 |
June | 496.00000 | 24.20882 | 49.02503 | -0.3495 | 7.90648 |
July | 497.00000 | 24.22582 | 48.79360 | -0.3436 | 7.82244 |
August | 514.00000 | 24.19724 | 49.05739 | -0.3530 | 7.94362 |
September | 485.00000 | 24.20561 | 48.84370 | -0.3522 | 7.96075 |
October | 502.00000 | 24.24896 | 48.34731 | 0.51638 | 10.83432 |
November | 489.00000 | 24.14812 | 47.62779 | 0.47131 | 9.93013 |
December | 497.00000 | 23.77440 | 44.57134 | 0.34254 | 7.98967 |
Annual Sum or Average | 5943.00000 | 24.07156 | 46.94948 | 0.08899 | 8.57028 |
Minimum of Months | 454.00000 | 23.77218 | 42.85413 | -0.3637 | 7.74841 |
Maximum of Months | 514.00000 | 24.24896 | 49.05739 | 0.51638 | 10.83432 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.29925 | 42.90796 | 0.20873 | 6.93123 |
February | 454.00000 | 23.50744 | 43.54297 | 0.27348 | 7.77888 |
March | 514.00000 | 23.71903 | 43.92663 | 0.33803 | 8.21685 |
April | 485.00000 | 24.01057 | 46.62444 | 0.44400 | 9.41402 |
May | 508.00000 | 24.18598 | 48.50515 | -0.3506 | 7.95790 |
June | 496.00000 | 24.23974 | 48.84440 | -0.3214 | 7.52936 |
July | 497.00000 | 24.27550 | 48.56973 | -0.3071 | 7.37203 |
August | 514.00000 | 24.20160 | 48.98626 | -0.3357 | 7.74905 |
September | 485.00000 | 24.21313 | 48.75824 | -0.3357 | 7.74554 |
October | 502.00000 | 24.18342 | 48.24636 | 0.50529 | 10.62511 |
November | 489.00000 | 23.93834 | 47.54601 | 0.42010 | 9.16764 |
December | 497.00000 | 23.35189 | 44.68115 | 0.23788 | 7.25884 |
Annual Sum or Average | 5943.00000 | 23.92974 | 46.77922 | 0.06223 | 8.14495 |
Minimum of Months | 454.00000 | 23.29925 | 42.90796 | -0.3506 | 6.93123 |
Maximum of Months | 514.00000 | 24.27550 | 48.98626 | 0.50529 | 10.62511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.87760 | 47.11940 | 0.11979 | 7.43422 |
February | 454.00000 | 23.24488 | 47.60864 | 0.23164 | 8.38933 |
March | 514.00000 | 23.52397 | 48.42067 | 0.31927 | 9.17368 |
April | 485.00000 | 24.05987 | 50.02916 | 0.48858 | 10.67197 |
May | 508.00000 | 24.37559 | 52.64296 | -0.2180 | 7.12341 |
June | 496.00000 | 24.42890 | 52.09662 | -0.1783 | 6.75054 |
July | 497.00000 | 24.52578 | 51.13257 | -0.1449 | 6.80272 |
August | 514.00000 | 24.38487 | 52.36144 | -0.2064 | 7.03689 |
September | 485.00000 | 24.40245 | 52.06911 | -0.2125 | 7.10224 |
October | 502.00000 | 24.32005 | 52.79275 | 0.58095 | 12.81996 |
November | 489.00000 | 23.86814 | 51.93942 | 0.43479 | 10.20332 |
December | 497.00000 | 23.05134 | 50.21780 | 0.18996 | 8.09603 |
Annual Sum or Average | 5943.00000 | 23.92607 | 50.72218 | 0.11521 | 8.46208 |
Minimum of Months | 454.00000 | 22.87760 | 47.11940 | -0.2180 | 6.75054 |
Maximum of Months | 514.00000 | 24.52578 | 52.79275 | 0.58095 | 12.81996 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17251 | 45.69474 | 0.21723 | 8.50198 |
February | 454.00000 | 23.43547 | 46.43250 | 0.31141 | 9.15335 |
March | 514.00000 | 23.71335 | 47.11984 | 0.40565 | 10.23744 |
April | 485.00000 | 24.13079 | 48.97063 | 0.55600 | 12.67738 |
May | 508.00000 | 24.36141 | 51.94914 | -0.1633 | 7.10511 |
June | 496.00000 | 24.43029 | 51.52212 | -0.1253 | 6.75624 |
July | 497.00000 | 24.55816 | 50.38158 | -0.0766 | 7.20731 |
August | 514.00000 | 24.37481 | 51.74991 | -0.1548 | 7.10408 |
September | 485.00000 | 24.42609 | 51.19558 | -0.1446 | 7.20990 |
October | 502.00000 | 24.32590 | 51.90278 | 0.62362 | 14.19757 |
November | 489.00000 | 23.91926 | 51.05100 | 0.47838 | 11.07821 |
December | 497.00000 | 23.10965 | 49.34971 | 0.22804 | 8.75313 |
Annual Sum or Average | 5943.00000 | 23.99996 | 49.79800 | 0.17770 | 9.15695 |
Minimum of Months | 454.00000 | 23.10965 | 45.69474 | -0.1633 | 6.75624 |
Maximum of Months | 514.00000 | 24.55816 | 51.94914 | 0.62362 | 14.19757 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67976 | 43.87501 | 0.36368 | 10.72156 |
February | 454.00000 | 23.81894 | 45.24129 | 0.41847 | 11.18013 |
March | 514.00000 | 23.83846 | 46.85888 | 0.43199 | 10.87366 |
April | 485.00000 | 24.14958 | 49.45869 | 0.52824 | 11.76551 |
May | 508.00000 | 24.36018 | 52.73996 | -0.2239 | 7.23118 |
June | 496.00000 | 24.39893 | 52.36137 | -0.1983 | 6.84808 |
July | 497.00000 | 24.49911 | 51.31125 | -0.1591 | 6.86957 |
August | 514.00000 | 24.39581 | 52.17568 | -0.1882 | 6.99354 |
September | 485.00000 | 24.46923 | 51.37368 | -0.1468 | 7.10554 |
October | 502.00000 | 24.49308 | 51.33648 | 0.67445 | 15.72026 |
November | 489.00000 | 24.26104 | 49.70403 | 0.58303 | 13.77124 |
December | 497.00000 | 23.72917 | 47.08997 | 0.40454 | 11.62245 |
Annual Sum or Average | 5943.00000 | 24.17618 | 49.48965 | 0.20468 | 10.04216 |
Minimum of Months | 454.00000 | 23.67976 | 43.87501 | -0.2239 | 6.84808 |
Maximum of Months | 514.00000 | 24.49911 | 52.73996 | 0.67445 | 15.72026 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76985 | 46.35899 | 0.12791 | 7.91207 |
February | 454.00000 | 23.17718 | 46.85280 | 0.25493 | 9.29804 |
March | 514.00000 | 23.47968 | 47.48236 | 0.35570 | 10.23742 |
April | 485.00000 | 23.99036 | 49.39164 | 0.52280 | 12.14358 |
May | 508.00000 | 24.27298 | 52.22388 | -0.1958 | 7.55620 |
June | 496.00000 | 24.32948 | 51.98878 | -0.1767 | 7.05785 |
July | 497.00000 | 24.43334 | 50.92990 | -0.1301 | 7.14887 |
August | 514.00000 | 24.31715 | 51.93371 | -0.1756 | 7.23476 |
September | 485.00000 | 24.31304 | 51.65974 | -0.1952 | 7.60383 |
October | 502.00000 | 24.22135 | 52.20712 | 0.59605 | 13.57398 |
November | 489.00000 | 23.72786 | 51.42922 | 0.43631 | 10.67215 |
December | 497.00000 | 22.96563 | 49.26282 | 0.20448 | 8.86919 |
Annual Sum or Average | 5943.00000 | 23.83730 | 50.16355 | 0.13357 | 9.10052 |
Minimum of Months | 454.00000 | 22.76985 | 46.35899 | -0.1958 | 7.05785 |
Maximum of Months | 514.00000 | 24.43334 | 52.22388 | 0.59605 | 13.57398 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42560 | 45.90866 | 0.25525 | 7.40789 |
February | 454.00000 | 23.59469 | 46.81622 | 0.31192 | 8.25955 |
March | 514.00000 | 23.68704 | 48.14063 | 0.34899 | 8.76279 |
April | 485.00000 | 24.09866 | 49.65449 | 0.47907 | 10.13223 |
May | 508.00000 | 24.35684 | 51.37936 | -0.2588 | 7.09599 |
June | 496.00000 | 24.38335 | 50.90136 | -0.2258 | 6.74739 |
July | 497.00000 | 24.48311 | 49.87520 | -0.1882 | 6.54595 |
August | 514.00000 | 24.39261 | 50.70240 | -0.2225 | 6.76789 |
September | 485.00000 | 24.41776 | 50.25568 | -0.2229 | 6.75641 |
October | 502.00000 | 24.40589 | 50.83570 | 0.59065 | 12.77502 |
November | 489.00000 | 24.16313 | 50.26484 | 0.50161 | 10.78382 |
December | 497.00000 | 23.61460 | 48.41978 | 0.32549 | 8.36838 |
Annual Sum or Average | 5943.00000 | 24.08793 | 49.44672 | 0.13891 | 8.36153 |
Minimum of Months | 454.00000 | 23.42560 | 45.90866 | -0.2588 | 6.54595 |
Maximum of Months | 514.00000 | 24.48311 | 51.37936 | 0.59065 | 12.77502 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.82136 | 44.47284 | 0.37613 | 9.14031 |
February | 454.00000 | 23.90320 | 45.55323 | 0.41783 | 9.67350 |
March | 514.00000 | 23.99961 | 46.64695 | 0.46359 | 10.48586 |
April | 485.00000 | 24.29524 | 48.40285 | 0.57492 | 12.58669 |
May | 508.00000 | 24.42171 | 50.68659 | -0.1778 | 6.73393 |
June | 496.00000 | 24.45110 | 50.33651 | -0.1501 | 6.55090 |
July | 497.00000 | 24.59292 | 49.15585 | -0.0947 | 6.71895 |
August | 514.00000 | 24.45372 | 50.13353 | -0.1467 | 6.57358 |
September | 485.00000 | 24.51671 | 49.48925 | -0.1288 | 6.59139 |
October | 502.00000 | 24.50471 | 50.01436 | 0.65613 | 14.72033 |
November | 489.00000 | 24.28428 | 49.48908 | 0.56237 | 12.20615 |
December | 497.00000 | 23.77470 | 47.66973 | 0.38585 | 9.42882 |
Annual Sum or Average | 5943.00000 | 24.25345 | 48.52343 | 0.22584 | 9.27210 |
Minimum of Months | 454.00000 | 23.77470 | 44.47284 | -0.1778 | 6.55090 |
Maximum of Months | 514.00000 | 24.59292 | 50.68659 | 0.65613 | 14.72033 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08860 | 45.21671 | 0.50075 | 12.10054 |
February | 454.00000 | 24.13599 | 47.09984 | 0.51993 | 12.20958 |
March | 514.00000 | 23.92961 | 49.56704 | 0.47607 | 11.39745 |
April | 485.00000 | 24.20384 | 52.85862 | 0.55096 | 11.91254 |
May | 508.00000 | 24.39552 | 57.63966 | -0.2059 | 6.58885 |
June | 496.00000 | 24.41804 | 59.60901 | -0.1690 | 6.19665 |
July | 497.00000 | 24.56951 | 57.53249 | -0.1181 | 6.11416 |
August | 514.00000 | 24.53890 | 58.68919 | -0.1065 | 6.16138 |
September | 485.00000 | 24.67632 | 56.61203 | -0.0478 | 6.30806 |
October | 502.00000 | 24.78998 | 54.99823 | 0.77562 | 18.53349 |
November | 489.00000 | 24.59132 | 53.17078 | 0.70197 | 16.39210 |
December | 497.00000 | 24.11458 | 48.20707 | 0.53277 | 12.97524 |
Annual Sum or Average | 5943.00000 | 24.37151 | 53.47943 | 0.28130 | 10.55149 |
Minimum of Months | 454.00000 | 23.92961 | 45.21671 | -0.2059 | 6.11416 |
Maximum of Months | 514.00000 | 24.78998 | 59.60901 | 0.77562 | 18.53349 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58794 | 45.00765 | 0.31910 | 8.24837 |
February | 454.00000 | 23.79991 | 45.78677 | 0.39162 | 9.65056 |
March | 514.00000 | 23.92661 | 46.81399 | 0.44550 | 10.44123 |
April | 485.00000 | 24.27342 | 48.58110 | 0.56619 | 12.37344 |
May | 508.00000 | 24.40917 | 50.83217 | -0.1886 | 6.85864 |
June | 496.00000 | 24.39991 | 50.75672 | -0.1891 | 6.69599 |
July | 497.00000 | 24.52867 | 49.57241 | -0.1306 | 6.53934 |
August | 514.00000 | 24.44752 | 50.23852 | -0.1527 | 6.55457 |
September | 485.00000 | 24.48210 | 49.81549 | -0.1581 | 6.69372 |
October | 502.00000 | 24.49100 | 50.17816 | 0.64699 | 14.47414 |
November | 489.00000 | 24.23051 | 49.66796 | 0.54725 | 11.92249 |
December | 497.00000 | 23.75831 | 47.45010 | 0.38815 | 9.60493 |
Annual Sum or Average | 5943.00000 | 24.19671 | 48.74368 | 0.20481 | 9.15879 |
Minimum of Months | 454.00000 | 23.58794 | 45.00765 | -0.1891 | 6.53934 |
Maximum of Months | 514.00000 | 24.52867 | 50.83217 | 0.64699 | 14.47414 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.26896 | 46.76182 | 0.21855 | 7.39320 |
February | 454.00000 | 23.52288 | 47.47327 | 0.29989 | 8.40138 |
March | 514.00000 | 23.72854 | 48.37337 | 0.36691 | 9.21330 |
April | 485.00000 | 24.14675 | 50.14080 | 0.50305 | 10.70280 |
May | 508.00000 | 24.39227 | 52.39321 | -0.2314 | 7.06518 |
June | 496.00000 | 24.41574 | 51.75495 | -0.2042 | 6.77701 |
July | 497.00000 | 24.50996 | 50.85873 | -0.1744 | 6.70724 |
August | 514.00000 | 24.38922 | 51.96809 | -0.2238 | 6.96194 |
September | 485.00000 | 24.40837 | 51.64081 | -0.2283 | 6.97528 |
October | 502.00000 | 24.37806 | 52.35635 | 0.58662 | 12.82339 |
November | 489.00000 | 24.05138 | 51.55205 | 0.47634 | 10.52122 |
December | 497.00000 | 23.40262 | 49.76440 | 0.27678 | 8.16737 |
Annual Sum or Average | 5943.00000 | 24.05437 | 50.43827 | 0.13666 | 8.47029 |
Minimum of Months | 454.00000 | 23.26896 | 46.76182 | -0.2314 | 6.70724 |
Maximum of Months | 514.00000 | 24.50996 | 52.39321 | 0.58662 | 12.82339 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.40359 | 45.29113 | 0.27074 | 8.53550 |
February | 385.00000 | 23.61737 | 46.29600 | 0.34620 | 9.12815 |
March | 433.00000 | 23.82492 | 47.38088 | 0.42090 | 10.22864 |
April | 410.00000 | 24.23796 | 49.10283 | 0.55776 | 12.58973 |
May | 430.00000 | 24.45059 | 51.98156 | -0.1758 | 7.22917 |
June | 418.00000 | 24.50445 | 51.38670 | -0.1462 | 6.93334 |
July | 422.00000 | 24.65381 | 50.16036 | -0.0950 | 7.31427 |
August | 433.00000 | 24.46247 | 51.55591 | -0.1682 | 7.14064 |
September | 410.00000 | 24.51628 | 50.97143 | -0.1572 | 7.25269 |
October | 427.00000 | 24.44215 | 51.76962 | 0.62798 | 14.28610 |
November | 417.00000 | 24.08238 | 50.81208 | 0.50446 | 11.35525 |
December | 422.00000 | 23.35381 | 49.15161 | 0.28424 | 8.82667 |
Annual Sum or Average | 5034.00000 | 24.13164 | 49.67600 | 0.18756 | 9.23098 |
Minimum of Months | 385.00000 | 23.35381 | 45.29113 | -0.1758 | 6.93334 |
Maximum of Months | 433.00000 | 24.65381 | 51.98156 | 0.62798 | 14.28610 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98858 | 43.63365 | 0.44403 | 11.17057 |
February | 454.00000 | 24.05827 | 45.12466 | 0.47717 | 11.50291 |
March | 514.00000 | 24.01207 | 46.79064 | 0.47186 | 10.98976 |
April | 485.00000 | 24.23986 | 49.53385 | 0.54234 | 11.76499 |
May | 508.00000 | 24.38232 | 52.47284 | -0.2356 | 7.13143 |
June | 496.00000 | 24.38698 | 52.00927 | -0.2235 | 6.87692 |
July | 497.00000 | 24.48545 | 51.02564 | -0.1877 | 6.76982 |
August | 514.00000 | 24.40496 | 51.76529 | -0.2047 | 6.89972 |
September | 485.00000 | 24.48923 | 50.90615 | -0.1602 | 6.91911 |
October | 502.00000 | 24.56864 | 50.82754 | 0.68189 | 15.78875 |
November | 489.00000 | 24.43031 | 49.33810 | 0.62007 | 14.29703 |
December | 497.00000 | 24.00665 | 46.72353 | 0.47476 | 12.02005 |
Annual Sum or Average | 5943.00000 | 24.28863 | 49.20709 | 0.22209 | 10.15925 |
Minimum of Months | 454.00000 | 23.98858 | 43.63365 | -0.2356 | 6.76982 |
Maximum of Months | 514.00000 | 24.56864 | 52.47284 | 0.68189 | 15.78875 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.18834 | 46.09474 | 0.23135 | 7.90332 |
February | 454.00000 | 23.50386 | 46.76764 | 0.33204 | 9.38471 |
March | 514.00000 | 23.72706 | 47.47346 | 0.41091 | 10.36136 |
April | 485.00000 | 24.14824 | 49.47985 | 0.55030 | 12.29695 |
May | 508.00000 | 24.34486 | 51.97316 | -0.1946 | 7.17970 |
June | 496.00000 | 24.36094 | 51.65222 | -0.1902 | 6.88672 |
July | 497.00000 | 24.46451 | 50.63482 | -0.1469 | 6.85014 |
August | 514.00000 | 24.36347 | 51.53901 | -0.1821 | 6.94574 |
September | 485.00000 | 24.37588 | 51.22975 | -0.1960 | 7.18499 |
October | 502.00000 | 24.34301 | 51.77638 | 0.61379 | 13.77729 |
November | 489.00000 | 23.97342 | 51.07027 | 0.48960 | 11.10452 |
December | 497.00000 | 23.34360 | 48.91370 | 0.29591 | 9.00163 |
Annual Sum or Average | 5943.00000 | 24.01448 | 49.90261 | 0.16570 | 9.06284 |
Minimum of Months | 454.00000 | 23.18834 | 46.09474 | -0.1960 | 6.85014 |
Maximum of Months | 514.00000 | 24.46451 | 51.97316 | 0.61379 | 13.77729 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.513338E+11 | 0.124273E+11 | 413.06 | 0.378340E+11 | 0.134998E+11 | 0.00 | 1.00 | 01-JAN-09:23 | 0.00 | 01-JAN-00:10 | 87472.93 | 02-JAN-14:00 | 59848.60 | 02-JAN-14:00 | 30606.78 | 14-JAN-06:03 | 22180.37 | 02-JAN-14:00 | 0.00 |
February | 0.521984E+11 | 0.125774E+11 | 373.86 | 0.389345E+11 | 0.132639E+11 | 0.00 | 1.00 | 01-FEB-11:10 | 0.00 | 01-FEB-00:10 | 85357.45 | 11-FEB-06:03 | 53830.83 | 21-FEB-16:50 | 40004.84 | 13-FEB-06:13 | 19516.48 | 11-FEB-06:03 | 0.00 |
March | 0.630967E+11 | 0.151607E+11 | 432.07 | 0.460747E+11 | 0.170220E+11 | 0.00 | 1.00 | 01-MAR-13:30 | 0.00 | 01-MAR-00:10 | 78573.23 | 13-MAR-12:05 | 57549.26 | 27-MAR-15:30 | 38076.03 | 14-MAR-05:13 | 19398.77 | 13-MAR-12:05 | 0.00 |
April | 0.715982E+11 | 0.174621E+11 | 419.83 | 0.515662E+11 | 0.200320E+11 | 0.00 | 1.00 | 01-APR-05:13 | 0.00 | 01-APR-00:10 | 100718.35 | 13-APR-05:02 | 62834.25 | 17-APR-15:20 | 44937.31 | 13-APR-04:03 | 23200.77 | 13-APR-05:02 | 0.00 |
May | 0.960794E+11 | 0.239129E+11 | 450.49 | 0.645571E+11 | 0.315224E+11 | 0.00 | 1.00 | 01-MAY-05:13 | 0.00 | 01-MAY-00:10 | 134741.53 | 30-MAY-04:02 | 82260.92 | 30-MAY-04:02 | 54599.54 | 27-MAY-05:03 | 31449.42 | 30-MAY-04:02 | 0.00 |
June | 0.108264E+12 | 0.269959E+11 | 453.47 | 0.681796E+11 | 0.400844E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 140794.97 | 19-JUN-04:02 | 84460.14 | 12-JUN-04:02 | 70158.38 | 19-JUN-04:02 | 33172.57 | 08-JUN-04:02 | 0.00 |
July | 0.113512E+12 | 0.289479E+11 | 462.23 | 0.716668E+11 | 0.418447E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 136196.35 | 03-JUL-04:02 | 85337.24 | 05-JUL-04:02 | 56912.66 | 03-JUL-04:02 | 31696.31 | 31-JUL-04:02 | 0.00 |
August | 0.117990E+12 | 0.298141E+11 | 472.23 | 0.741665E+11 | 0.438235E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 134911.36 | 18-AUG-04:02 | 84848.38 | 28-AUG-04:02 | 54541.62 | 18-AUG-04:02 | 32810.27 | 01-AUG-04:02 | 0.00 |
September | 0.108459E+12 | 0.271662E+11 | 452.70 | 0.686240E+11 | 0.398353E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 136310.99 | 23-SEP-04:02 | 86652.27 | 18-SEP-04:02 | 58428.91 | 23-SEP-04:02 | 32794.62 | 23-SEP-04:02 | 0.00 |
October | 0.996603E+11 | 0.246273E+11 | 446.26 | 0.659649E+11 | 0.336954E+11 | 0.00 | 1.00 | 01-OCT-09:53 | 0.00 | 01-OCT-00:10 | 137445.07 | 02-OCT-04:02 | 84284.52 | 10-OCT-04:02 | 61535.46 | 03-OCT-04:02 | 32345.77 | 02-OCT-04:02 | 0.00 |
November | 0.787053E+11 | 0.189805E+11 | 407.03 | 0.530676E+11 | 0.256377E+11 | 0.00 | 1.00 | 01-NOV-05:13 | 0.00 | 01-NOV-00:10 | 128133.04 | 30-NOV-06:03 | 72175.04 | 04-NOV-05:03 | 58832.42 | 30-NOV-06:03 | 29871.21 | 30-NOV-06:03 | 0.00 |
December | 0.550377E+11 | 0.132603E+11 | 409.50 | 0.391684E+11 | 0.158693E+11 | 0.00 | 1.00 | 01-DEC-06:13 | 0.00 | 01-DEC-00:10 | 96281.23 | 11-DEC-06:13 | 55363.03 | 08-DEC-16:10 | 43801.77 | 11-DEC-06:13 | 21976.57 | 11-DEC-06:13 | 0.00 |
Annual Sum or Average | 0.101593E+13 | 0.251333E+12 | 5192.72 | 0.679804E+12 | 0.336130E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.513338E+11 | 0.124273E+11 | 373.86 | 0.378340E+11 | 0.132639E+11 | 0.00 | 1.00 | 0.00 | 78573.23 | 53830.83 | 30606.78 | 19398.77 | 0.00 | ||||||
Maximum of Months | 0.117990E+12 | 0.298141E+11 | 472.23 | 0.741665E+11 | 0.438235E+11 | 0.00 | 1.00 | 0.00 | 140794.97 | 86652.27 | 70158.38 | 33172.57 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424156E+11 | 0.103209E+11 | 408.93 | 0.299159E+11 | 0.124997E+11 | 0.00 | 1.00 | 01-JAN-09:33 | 0.00 | 01-JAN-00:10 | 77181.09 | 02-JAN-14:00 | 52154.80 | 02-JAN-15:00 | 35360.30 | 14-JAN-06:03 | 19481.97 | 02-JAN-14:00 | 0.00 |
February | 0.443676E+11 | 0.107121E+11 | 373.72 | 0.319711E+11 | 0.123966E+11 | 0.00 | 1.00 | 01-FEB-13:20 | 0.00 | 01-FEB-00:10 | 66790.09 | 11-FEB-06:03 | 46667.89 | 21-FEB-16:20 | 35216.99 | 11-FEB-06:03 | 15159.59 | 17-FEB-14:00 | 0.00 |
March | 0.548940E+11 | 0.131878E+11 | 434.25 | 0.387986E+11 | 0.160954E+11 | 0.00 | 1.00 | 01-MAR-14:40 | 0.00 | 01-MAR-00:10 | 71203.13 | 27-MAR-15:00 | 51735.26 | 27-MAR-15:20 | 31621.61 | 05-MAR-11:02 | 17734.90 | 27-MAR-15:00 | 0.00 |
April | 0.637111E+11 | 0.154988E+11 | 422.22 | 0.447875E+11 | 0.189236E+11 | 0.00 | 1.00 | 01-APR-12:50 | 0.00 | 01-APR-00:10 | 103047.00 | 12-APR-05:03 | 57911.11 | 12-APR-05:03 | 45135.89 | 12-APR-05:03 | 23721.77 | 12-APR-05:03 | 0.00 |
May | 0.857180E+11 | 0.212202E+11 | 448.14 | 0.556796E+11 | 0.300384E+11 | 0.00 | 1.00 | 01-MAY-05:13 | 0.00 | 01-MAY-00:10 | 121702.54 | 30-MAY-04:02 | 71100.70 | 15-MAY-04:02 | 63443.69 | 27-MAY-05:03 | 28146.49 | 30-MAY-04:02 | 0.00 |
June | 0.974323E+11 | 0.241313E+11 | 450.98 | 0.590347E+11 | 0.383975E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 125786.90 | 19-JUN-04:02 | 73855.25 | 12-JUN-04:02 | 66205.05 | 19-JUN-04:02 | 29548.86 | 08-JUN-04:02 | 0.00 |
July | 0.102022E+12 | 0.258126E+11 | 457.19 | 0.620440E+11 | 0.399785E+11 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 122596.66 | 03-JUL-04:02 | 74137.46 | 05-JUL-04:02 | 56156.93 | 03-JUL-04:02 | 28356.34 | 31-JUL-04:02 | 0.00 |
August | 0.103323E+12 | 0.259104E+11 | 465.27 | 0.622483E+11 | 0.410749E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 121547.42 | 18-AUG-04:02 | 74079.82 | 21-AUG-04:02 | 54624.23 | 11-AUG-04:02 | 29234.29 | 01-AUG-04:02 | 0.00 |
September | 0.950460E+11 | 0.236544E+11 | 443.70 | 0.576565E+11 | 0.373894E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 123176.95 | 23-SEP-04:02 | 76216.44 | 11-SEP-04:02 | 59085.03 | 23-SEP-04:02 | 29234.73 | 23-SEP-04:02 | 0.00 |
October | 0.855359E+11 | 0.210645E+11 | 435.68 | 0.545254E+11 | 0.310104E+11 | 0.00 | 1.00 | 01-OCT-10:23 | 0.00 | 01-OCT-00:10 | 125018.68 | 02-OCT-04:02 | 71003.94 | 10-OCT-04:02 | 70996.60 | 02-OCT-04:04 | 28911.92 | 02-OCT-04:02 | 0.00 |
November | 0.661647E+11 | 0.159344E+11 | 400.78 | 0.425638E+11 | 0.236009E+11 | 0.00 | 1.00 | 01-NOV-08:30 | 0.00 | 01-NOV-00:10 | 124045.37 | 30-NOV-06:03 | 61001.71 | 04-NOV-05:03 | 65078.47 | 30-NOV-06:03 | 28445.18 | 30-NOV-06:03 | 0.00 |
December | 0.463289E+11 | 0.111957E+11 | 406.17 | 0.313958E+11 | 0.149331E+11 | 0.00 | 1.00 | 01-DEC-09:20 | 0.00 | 01-DEC-00:10 | 99233.41 | 09-DEC-06:03 | 53362.57 | 09-DEC-06:03 | 45870.84 | 09-DEC-06:03 | 22926.04 | 09-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.886959E+12 | 0.218643E+12 | 5147.02 | 0.570621E+12 | 0.316338E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.424156E+11 | 0.103209E+11 | 373.72 | 0.299159E+11 | 0.123966E+11 | 0.00 | 1.00 | 0.00 | 66790.09 | 46667.89 | 31621.61 | 15159.59 | 0.00 | ||||||
Maximum of Months | 0.103323E+12 | 0.259104E+11 | 465.27 | 0.622483E+11 | 0.410749E+11 | 0.00 | 1.00 | 0.00 | 125786.90 | 76216.44 | 70996.60 | 29548.86 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.434652E+11 | 0.107023E+11 | 406.68 | 0.302877E+11 | 0.131775E+11 | 0.00 | 1.00 | 01-JAN-09:53 | 0.00 | 01-JAN-00:10 | 82937.49 | 02-JAN-14:00 | 58861.22 | 02-JAN-15:00 | 26598.99 | 02-JAN-14:00 | 20906.40 | 02-JAN-14:10 | 0.00 |
February | 0.463114E+11 | 0.112860E+11 | 370.22 | 0.333040E+11 | 0.130075E+11 | 0.00 | 1.00 | 02-FEB-09:50 | 0.00 | 01-FEB-00:10 | 68320.94 | 17-FEB-14:10 | 53655.15 | 22-FEB-16:00 | 25789.48 | 19-FEB-11:40 | 16597.99 | 17-FEB-14:10 | 0.00 |
March | 0.580723E+11 | 0.140522E+11 | 435.68 | 0.412029E+11 | 0.168694E+11 | 0.00 | 1.00 | 01-MAR-14:40 | 0.00 | 01-MAR-00:10 | 79891.64 | 27-MAR-15:00 | 60461.31 | 27-MAR-15:20 | 34471.69 | 05-MAR-11:02 | 19869.90 | 27-MAR-15:00 | 0.00 |
April | 0.683848E+11 | 0.167502E+11 | 422.44 | 0.487556E+11 | 0.196292E+11 | 0.00 | 1.00 | 01-APR-13:10 | 0.00 | 01-APR-00:10 | 122420.29 | 13-APR-05:02 | 68639.32 | 16-APR-16:42 | 59691.77 | 13-APR-05:02 | 27982.11 | 13-APR-05:02 | 0.00 |
May | 0.919005E+11 | 0.228539E+11 | 448.78 | 0.613183E+11 | 0.305822E+11 | 0.00 | 1.00 | 01-MAY-08:20 | 0.00 | 01-MAY-00:10 | 138317.07 | 30-MAY-04:02 | 81312.71 | 29-MAY-16:02 | 63776.01 | 27-MAY-05:03 | 32059.97 | 30-MAY-04:02 | 0.00 |
June | 0.103947E+12 | 0.258264E+11 | 453.14 | 0.651674E+11 | 0.387798E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 138632.19 | 08-JUN-04:02 | 83548.40 | 12-JUN-04:02 | 76571.57 | 19-JUN-04:02 | 33762.65 | 08-JUN-04:02 | 0.00 |
July | 0.109262E+12 | 0.277435E+11 | 460.28 | 0.689623E+11 | 0.403001E+11 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 139747.99 | 03-JUL-04:02 | 83526.89 | 10-JUL-04:02 | 67951.64 | 03-JUL-04:02 | 32244.77 | 31-JUL-04:02 | 0.00 |
August | 0.109124E+12 | 0.274601E+11 | 465.37 | 0.678450E+11 | 0.412787E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 139384.17 | 18-AUG-04:02 | 84225.66 | 21-AUG-04:02 | 65018.45 | 18-AUG-04:02 | 33381.79 | 01-AUG-04:02 | 0.00 |
September | 0.100479E+12 | 0.250971E+11 | 445.88 | 0.626913E+11 | 0.377877E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 141301.06 | 19-SEP-04:02 | 86840.16 | 11-SEP-04:02 | 68247.82 | 23-SEP-04:02 | 33363.81 | 22-SEP-04:02 | 0.00 |
October | 0.886371E+11 | 0.219236E+11 | 432.93 | 0.574204E+11 | 0.312167E+11 | 0.00 | 1.00 | 01-OCT-10:23 | 0.00 | 01-OCT-00:10 | 142685.61 | 02-OCT-04:02 | 70244.73 | 30-OCT-04:02 | 77034.73 | 02-OCT-04:02 | 32997.59 | 02-OCT-04:02 | 0.00 |
November | 0.682930E+11 | 0.165590E+11 | 399.36 | 0.441651E+11 | 0.241279E+11 | 0.00 | 1.00 | 01-NOV-09:40 | 0.00 | 01-NOV-00:10 | 127494.33 | 30-NOV-06:03 | 60217.94 | 10-NOV-14:30 | 70176.37 | 30-NOV-06:03 | 29086.49 | 30-NOV-06:03 | 0.00 |
December | 0.478179E+11 | 0.116692E+11 | 406.21 | 0.321842E+11 | 0.156337E+11 | 0.00 | 1.00 | 01-DEC-11:30 | 0.00 | 01-DEC-00:10 | 77257.21 | 08-DEC-15:50 | 54753.14 | 08-DEC-15:30 | 34359.29 | 09-DEC-06:03 | 18908.75 | 08-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.935695E+12 | 0.231924E+12 | 5146.98 | 0.613304E+12 | 0.322390E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.434652E+11 | 0.107023E+11 | 370.22 | 0.302877E+11 | 0.130075E+11 | 0.00 | 1.00 | 0.00 | 68320.94 | 53655.15 | 25789.48 | 16597.99 | 0.00 | ||||||
Maximum of Months | 0.109262E+12 | 0.277435E+11 | 465.37 | 0.689623E+11 | 0.412787E+11 | 0.00 | 1.00 | 0.00 | 142685.61 | 86840.16 | 77034.73 | 33762.65 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.04 | 0.00 | 331.04 | 361.12 | 684.55 | 0.00 | 0.00 | 0.00 |
February | 391.84 | 0.00 | 391.84 | 530.52 | 567.22 | 0.00 | 0.00 | 0.00 |
March | 467.29 | 0.00 | 467.29 | 621.39 | 479.78 | 0.00 | 0.00 | 0.00 |
April | 523.62 | 2.35 | 521.27 | 855.76 | 317.23 | 0.00 | 0.00 | 0.00 |
May | 597.95 | 26.75 | 571.20 | 1177.16 | 169.60 | 0.00 | 0.00 | 0.00 |
June | 638.74 | 45.99 | 592.75 | 1354.32 | 78.86 | 0.00 | 0.00 | 0.00 |
July | 646.38 | 31.67 | 614.71 | 1438.18 | 115.04 | 0.00 | 0.00 | 0.00 |
August | 572.06 | 5.26 | 566.80 | 1210.74 | 76.53 | 0.00 | 0.00 | 0.00 |
September | 507.48 | 0.04 | 507.44 | 1117.27 | 123.51 | 0.00 | 0.00 | 0.00 |
October | 425.15 | 0.00 | 425.15 | 826.16 | 193.46 | 0.00 | 0.00 | 0.00 |
November | 369.67 | 0.00 | 369.67 | 591.98 | 354.02 | 0.00 | 0.00 | 0.00 |
December | 327.44 | 0.00 | 327.44 | 404.41 | 575.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.68 | 9.39 | 474.30 | 875.75 | 310.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.44 | 0.00 | 327.44 | 361.12 | 76.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 646.38 | 45.99 | 614.71 | 1438.18 | 684.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 531.39 | 254.57 | 276.82 | 746.46 | 429.53 | 0.00 | 0.00 | 0.00 |
February | 613.58 | 284.03 | 329.55 | 928.38 | 355.65 | 0.00 | 0.00 | 0.00 |
March | 749.14 | 354.16 | 394.98 | 1125.25 | 296.67 | 0.00 | 0.00 | 0.00 |
April | 813.00 | 362.76 | 450.24 | 1361.78 | 210.32 | 0.00 | 0.00 | 0.00 |
May | 769.13 | 306.29 | 462.85 | 1411.38 | 108.00 | 0.00 | 0.00 | 0.00 |
June | 759.15 | 291.58 | 467.56 | 1465.98 | 51.10 | 0.00 | 0.00 | 0.00 |
July | 780.03 | 281.30 | 498.74 | 1559.66 | 76.87 | 0.00 | 0.00 | 0.00 |
August | 713.27 | 238.50 | 474.77 | 1386.04 | 49.26 | 0.00 | 0.00 | 0.00 |
September | 687.64 | 248.58 | 439.05 | 1355.46 | 82.00 | 0.00 | 0.00 | 0.00 |
October | 632.94 | 272.58 | 360.36 | 1157.64 | 126.42 | 0.00 | 0.00 | 0.00 |
November | 513.72 | 204.84 | 308.88 | 847.82 | 221.96 | 0.00 | 0.00 | 0.00 |
December | 414.97 | 146.51 | 268.47 | 600.36 | 365.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.94 | 270.29 | 394.65 | 1163.06 | 197.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.97 | 146.51 | 268.47 | 600.36 | 49.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.00 | 362.76 | 498.74 | 1559.66 | 429.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1555.86 | 1010.81 | 545.05 | 2393.57 | 679.92 | 0.00 | 0.00 | 0.00 |
February | 1407.50 | 814.41 | 593.09 | 2286.14 | 572.83 | 0.00 | 0.00 | 0.00 |
March | 1080.64 | 456.89 | 623.76 | 1771.05 | 480.36 | 0.00 | 0.00 | 0.00 |
April | 734.82 | 128.86 | 605.96 | 1324.82 | 330.64 | 0.00 | 0.00 | 0.00 |
May | 588.84 | 12.74 | 576.10 | 1163.46 | 165.17 | 0.00 | 0.00 | 0.00 |
June | 561.40 | 1.06 | 560.35 | 1196.91 | 79.69 | 0.00 | 0.00 | 0.00 |
July | 601.11 | 5.57 | 595.54 | 1345.34 | 114.45 | 0.00 | 0.00 | 0.00 |
August | 682.24 | 57.57 | 624.67 | 1451.76 | 77.40 | 0.00 | 0.00 | 0.00 |
September | 873.36 | 214.02 | 659.34 | 1846.31 | 130.40 | 0.00 | 0.00 | 0.00 |
October | 1201.05 | 563.49 | 637.55 | 2250.15 | 215.06 | 0.00 | 0.00 | 0.00 |
November | 1366.53 | 762.67 | 603.85 | 2307.64 | 367.94 | 0.00 | 0.00 | 0.00 |
December | 1499.41 | 945.74 | 553.67 | 2360.79 | 590.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1010.90 | 412.71 | 598.19 | 1805.76 | 315.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.40 | 1.06 | 545.05 | 1163.46 | 77.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1555.86 | 1010.81 | 659.34 | 2393.57 | 679.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 477.37 | 205.80 | 271.57 | 687.62 | 452.61 | 0.00 | 0.00 | 0.00 |
February | 596.94 | 270.15 | 326.79 | 944.49 | 386.40 | 0.00 | 0.00 | 0.00 |
March | 743.37 | 339.46 | 403.91 | 1165.81 | 331.16 | 0.00 | 0.00 | 0.00 |
April | 818.23 | 378.87 | 439.36 | 1395.97 | 230.32 | 0.00 | 0.00 | 0.00 |
May | 745.92 | 287.15 | 458.78 | 1391.64 | 124.00 | 0.00 | 0.00 | 0.00 |
June | 632.03 | 177.29 | 454.74 | 1255.11 | 57.55 | 0.00 | 0.00 | 0.00 |
July | 706.35 | 218.52 | 487.82 | 1440.68 | 82.42 | 0.00 | 0.00 | 0.00 |
August | 704.74 | 229.67 | 475.07 | 1375.62 | 57.47 | 0.00 | 0.00 | 0.00 |
September | 601.18 | 177.27 | 423.91 | 1211.48 | 85.52 | 0.00 | 0.00 | 0.00 |
October | 598.06 | 233.14 | 364.92 | 1110.87 | 139.90 | 0.00 | 0.00 | 0.00 |
November | 493.34 | 180.96 | 312.38 | 840.50 | 242.33 | 0.00 | 0.00 | 0.00 |
December | 494.22 | 220.96 | 273.26 | 754.76 | 383.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.60 | 243.21 | 391.39 | 1132.26 | 213.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 477.37 | 177.27 | 271.57 | 687.62 | 57.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.23 | 378.87 | 487.82 | 1440.68 | 452.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.34 | 0.00 | 110.34 | 114.97 | 259.44 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 174.87 | 210.06 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 211.11 | 170.57 | 0.00 | 0.00 | 0.00 |
April | 174.53 | 0.78 | 173.75 | 292.14 | 108.46 | 0.00 | 0.00 | 0.00 |
May | 199.31 | 8.92 | 190.39 | 399.84 | 56.37 | 0.00 | 0.00 | 0.00 |
June | 212.90 | 15.33 | 197.57 | 459.79 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 215.45 | 10.56 | 204.89 | 486.21 | 38.38 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.92 | 405.64 | 27.70 | 0.00 | 0.00 | 0.00 |
September | 169.15 | 0.01 | 169.14 | 375.10 | 45.11 | 0.00 | 0.00 | 0.00 |
October | 141.71 | 0.00 | 141.71 | 275.71 | 72.47 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 194.15 | 137.49 | 0.00 | 0.00 | 0.00 |
December | 109.14 | 0.00 | 109.14 | 128.98 | 221.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.22 | 3.13 | 158.09 | 293.78 | 114.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.14 | 0.00 | 109.14 | 114.97 | 25.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.45 | 15.33 | 204.89 | 486.21 | 259.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.35 | 0.00 | 110.35 | 114.97 | 259.45 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 174.88 | 210.07 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 211.12 | 170.58 | 0.00 | 0.00 | 0.00 |
April | 174.54 | 0.78 | 173.76 | 292.16 | 108.47 | 0.00 | 0.00 | 0.00 |
May | 199.32 | 8.92 | 190.40 | 399.86 | 56.37 | 0.00 | 0.00 | 0.00 |
June | 212.91 | 15.33 | 197.58 | 459.82 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 215.46 | 10.56 | 204.90 | 486.23 | 38.38 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.93 | 405.66 | 27.70 | 0.00 | 0.00 | 0.00 |
September | 169.16 | 0.01 | 169.15 | 375.12 | 45.11 | 0.00 | 0.00 | 0.00 |
October | 141.72 | 0.00 | 141.72 | 275.73 | 72.47 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 194.16 | 137.49 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 0.00 | 109.15 | 128.98 | 221.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 3.13 | 158.10 | 293.79 | 114.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.15 | 0.00 | 109.15 | 114.97 | 25.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.46 | 15.33 | 204.90 | 486.23 | 259.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.35 | 0.00 | 110.35 | 114.97 | 259.45 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 174.88 | 210.07 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 211.12 | 170.58 | 0.00 | 0.00 | 0.00 |
April | 174.54 | 0.78 | 173.76 | 292.16 | 108.47 | 0.00 | 0.00 | 0.00 |
May | 199.32 | 8.92 | 190.40 | 399.86 | 56.37 | 0.00 | 0.00 | 0.00 |
June | 212.91 | 15.33 | 197.58 | 459.82 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 215.46 | 10.56 | 204.90 | 486.23 | 38.38 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.93 | 405.66 | 27.70 | 0.00 | 0.00 | 0.00 |
September | 169.16 | 0.01 | 169.15 | 375.12 | 45.11 | 0.00 | 0.00 | 0.00 |
October | 141.72 | 0.00 | 141.72 | 275.73 | 72.47 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 194.16 | 137.49 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 0.00 | 109.15 | 128.98 | 221.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 3.13 | 158.10 | 293.79 | 114.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.15 | 0.00 | 109.15 | 114.97 | 25.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.46 | 15.33 | 204.90 | 486.23 | 259.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 511.17 | 244.88 | 266.29 | 704.64 | 483.02 | 0.00 | 0.00 | 0.00 |
February | 590.24 | 273.22 | 317.02 | 889.33 | 393.06 | 0.00 | 0.00 | 0.00 |
March | 720.63 | 340.68 | 379.95 | 1092.06 | 318.73 | 0.00 | 0.00 | 0.00 |
April | 782.07 | 348.95 | 433.11 | 1326.67 | 221.76 | 0.00 | 0.00 | 0.00 |
May | 739.87 | 294.63 | 445.24 | 1374.82 | 112.23 | 0.00 | 0.00 | 0.00 |
June | 730.26 | 280.49 | 449.77 | 1424.65 | 52.01 | 0.00 | 0.00 | 0.00 |
July | 750.35 | 270.59 | 479.76 | 1512.61 | 81.18 | 0.00 | 0.00 | 0.00 |
August | 686.13 | 229.43 | 456.70 | 1336.27 | 57.71 | 0.00 | 0.00 | 0.00 |
September | 661.47 | 239.12 | 422.35 | 1307.59 | 92.24 | 0.00 | 0.00 | 0.00 |
October | 608.86 | 262.21 | 346.65 | 1115.61 | 147.00 | 0.00 | 0.00 | 0.00 |
November | 494.17 | 197.04 | 297.13 | 809.32 | 257.18 | 0.00 | 0.00 | 0.00 |
December | 399.18 | 140.93 | 258.25 | 564.76 | 415.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.64 | 260.01 | 379.63 | 1122.39 | 218.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 399.18 | 140.93 | 258.25 | 564.76 | 52.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 782.07 | 348.95 | 479.76 | 1512.61 | 483.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.21 | 9.68 | 10.53 | 27.86 | 19.10 | 0.00 | 0.00 | 0.00 |
February | 23.34 | 10.80 | 12.53 | 35.16 | 15.54 | 0.00 | 0.00 | 0.00 |
March | 28.49 | 13.47 | 15.02 | 43.18 | 12.60 | 0.00 | 0.00 | 0.00 |
April | 30.92 | 13.80 | 17.12 | 52.46 | 8.77 | 0.00 | 0.00 | 0.00 |
May | 29.25 | 11.65 | 17.60 | 54.36 | 4.44 | 0.00 | 0.00 | 0.00 |
June | 28.87 | 11.09 | 17.78 | 56.33 | 2.06 | 0.00 | 0.00 | 0.00 |
July | 29.67 | 10.70 | 18.97 | 59.81 | 3.21 | 0.00 | 0.00 | 0.00 |
August | 27.13 | 9.07 | 18.06 | 52.83 | 2.28 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 9.45 | 16.70 | 51.70 | 3.65 | 0.00 | 0.00 | 0.00 |
October | 24.07 | 10.37 | 13.71 | 44.11 | 5.81 | 0.00 | 0.00 | 0.00 |
November | 19.54 | 7.79 | 11.75 | 32.00 | 10.17 | 0.00 | 0.00 | 0.00 |
December | 15.78 | 5.57 | 10.21 | 22.33 | 16.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.29 | 10.28 | 15.01 | 44.38 | 8.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.78 | 5.57 | 10.21 | 22.33 | 2.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.92 | 13.80 | 18.97 | 59.81 | 19.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.61 | 336.93 | 181.68 | 796.63 | 266.90 | 0.00 | 0.00 | 0.00 |
February | 469.16 | 271.47 | 197.69 | 764.31 | 220.51 | 0.00 | 0.00 | 0.00 |
March | 360.21 | 152.29 | 207.92 | 598.44 | 176.03 | 0.00 | 0.00 | 0.00 |
April | 244.94 | 42.95 | 201.98 | 449.61 | 115.78 | 0.00 | 0.00 | 0.00 |
May | 196.28 | 4.25 | 192.03 | 394.16 | 55.82 | 0.00 | 0.00 | 0.00 |
June | 187.13 | 0.35 | 186.78 | 405.06 | 25.50 | 0.00 | 0.00 | 0.00 |
July | 200.37 | 1.86 | 198.51 | 452.42 | 38.68 | 0.00 | 0.00 | 0.00 |
August | 227.41 | 19.19 | 208.22 | 482.94 | 29.60 | 0.00 | 0.00 | 0.00 |
September | 291.12 | 71.34 | 219.78 | 614.07 | 50.49 | 0.00 | 0.00 | 0.00 |
October | 400.34 | 187.83 | 212.52 | 748.48 | 87.97 | 0.00 | 0.00 | 0.00 |
November | 455.50 | 254.22 | 201.28 | 767.93 | 149.55 | 0.00 | 0.00 | 0.00 |
December | 499.80 | 315.24 | 184.55 | 787.11 | 233.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.96 | 137.57 | 199.39 | 604.29 | 120.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.13 | 0.35 | 181.68 | 394.16 | 25.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.61 | 336.93 | 219.78 | 796.63 | 266.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.61 | 336.93 | 181.68 | 796.63 | 266.90 | 0.00 | 0.00 | 0.00 |
February | 469.16 | 271.47 | 197.69 | 764.31 | 220.51 | 0.00 | 0.00 | 0.00 |
March | 360.21 | 152.29 | 207.92 | 598.44 | 176.03 | 0.00 | 0.00 | 0.00 |
April | 244.94 | 42.95 | 201.98 | 449.61 | 115.78 | 0.00 | 0.00 | 0.00 |
May | 196.28 | 4.25 | 192.03 | 394.16 | 55.82 | 0.00 | 0.00 | 0.00 |
June | 187.13 | 0.35 | 186.78 | 405.06 | 25.50 | 0.00 | 0.00 | 0.00 |
July | 200.37 | 1.86 | 198.51 | 452.42 | 38.68 | 0.00 | 0.00 | 0.00 |
August | 227.41 | 19.19 | 208.22 | 482.94 | 29.60 | 0.00 | 0.00 | 0.00 |
September | 291.12 | 71.34 | 219.78 | 614.07 | 50.49 | 0.00 | 0.00 | 0.00 |
October | 400.34 | 187.83 | 212.52 | 748.48 | 87.97 | 0.00 | 0.00 | 0.00 |
November | 455.50 | 254.22 | 201.28 | 767.93 | 149.55 | 0.00 | 0.00 | 0.00 |
December | 499.80 | 315.24 | 184.55 | 787.11 | 233.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.96 | 137.57 | 199.39 | 604.29 | 120.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.13 | 0.35 | 181.68 | 394.16 | 25.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.61 | 336.93 | 219.78 | 796.63 | 266.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.58 | 336.91 | 181.67 | 796.58 | 266.88 | 0.00 | 0.00 | 0.00 |
February | 469.13 | 271.45 | 197.68 | 764.27 | 220.50 | 0.00 | 0.00 | 0.00 |
March | 360.19 | 152.28 | 207.90 | 598.41 | 176.02 | 0.00 | 0.00 | 0.00 |
April | 244.92 | 42.95 | 201.97 | 449.58 | 115.77 | 0.00 | 0.00 | 0.00 |
May | 196.27 | 4.25 | 192.02 | 394.13 | 55.82 | 0.00 | 0.00 | 0.00 |
June | 187.12 | 0.35 | 186.77 | 405.03 | 25.49 | 0.00 | 0.00 | 0.00 |
July | 200.36 | 1.86 | 198.50 | 452.39 | 38.68 | 0.00 | 0.00 | 0.00 |
August | 227.40 | 19.19 | 208.21 | 482.91 | 29.60 | 0.00 | 0.00 | 0.00 |
September | 291.10 | 71.33 | 219.76 | 614.03 | 50.49 | 0.00 | 0.00 | 0.00 |
October | 400.32 | 187.82 | 212.50 | 748.43 | 87.97 | 0.00 | 0.00 | 0.00 |
November | 455.47 | 254.20 | 201.27 | 767.88 | 149.54 | 0.00 | 0.00 | 0.00 |
December | 499.76 | 315.22 | 184.54 | 787.07 | 233.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.94 | 137.56 | 199.38 | 604.25 | 120.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.12 | 0.35 | 181.67 | 394.13 | 25.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.58 | 336.91 | 219.76 | 796.58 | 266.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.21 | 197.97 | 261.24 | 648.31 | 510.05 | 0.00 | 0.00 | 0.00 |
February | 574.22 | 259.87 | 314.36 | 902.44 | 426.87 | 0.00 | 0.00 | 0.00 |
March | 715.08 | 326.54 | 388.54 | 1126.64 | 356.39 | 0.00 | 0.00 | 0.00 |
April | 787.10 | 364.45 | 422.65 | 1352.59 | 241.96 | 0.00 | 0.00 | 0.00 |
May | 717.54 | 276.22 | 441.32 | 1350.72 | 128.33 | 0.00 | 0.00 | 0.00 |
June | 607.98 | 170.54 | 437.44 | 1218.45 | 57.32 | 0.00 | 0.00 | 0.00 |
July | 679.47 | 210.21 | 469.27 | 1394.61 | 86.75 | 0.00 | 0.00 | 0.00 |
August | 677.93 | 220.93 | 456.99 | 1324.31 | 66.50 | 0.00 | 0.00 | 0.00 |
September | 578.31 | 170.52 | 407.78 | 1166.33 | 96.90 | 0.00 | 0.00 | 0.00 |
October | 575.31 | 224.27 | 351.04 | 1067.09 | 160.74 | 0.00 | 0.00 | 0.00 |
November | 474.57 | 174.07 | 300.50 | 800.34 | 280.80 | 0.00 | 0.00 | 0.00 |
December | 475.42 | 212.56 | 262.86 | 712.85 | 438.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.45 | 233.96 | 376.50 | 1089.75 | 236.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 459.21 | 170.52 | 261.24 | 648.31 | 57.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.10 | 364.45 | 469.27 | 1394.61 | 510.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.16 | 7.83 | 10.33 | 25.63 | 20.17 | 0.00 | 0.00 | 0.00 |
February | 22.70 | 10.27 | 12.43 | 35.68 | 16.88 | 0.00 | 0.00 | 0.00 |
March | 28.27 | 12.91 | 15.36 | 44.55 | 14.09 | 0.00 | 0.00 | 0.00 |
April | 31.12 | 14.41 | 16.71 | 53.48 | 9.57 | 0.00 | 0.00 | 0.00 |
May | 28.37 | 10.92 | 17.45 | 53.41 | 5.07 | 0.00 | 0.00 | 0.00 |
June | 24.04 | 6.74 | 17.30 | 48.18 | 2.27 | 0.00 | 0.00 | 0.00 |
July | 26.87 | 8.31 | 18.55 | 55.14 | 3.43 | 0.00 | 0.00 | 0.00 |
August | 26.80 | 8.74 | 18.07 | 52.36 | 2.63 | 0.00 | 0.00 | 0.00 |
September | 22.87 | 6.74 | 16.12 | 46.12 | 3.83 | 0.00 | 0.00 | 0.00 |
October | 22.75 | 8.87 | 13.88 | 42.19 | 6.36 | 0.00 | 0.00 | 0.00 |
November | 18.76 | 6.88 | 11.88 | 31.64 | 11.10 | 0.00 | 0.00 | 0.00 |
December | 18.80 | 8.40 | 10.39 | 28.19 | 17.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.14 | 9.25 | 14.89 | 43.09 | 9.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.16 | 6.74 | 10.33 | 25.63 | 2.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.12 | 14.41 | 18.55 | 55.14 | 20.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.04 | 0.00 | 331.04 | 347.11 | 752.05 | 0.00 | 0.00 | 0.00 |
February | 391.84 | 0.00 | 391.84 | 521.69 | 617.83 | 0.00 | 0.00 | 0.00 |
March | 467.29 | 0.00 | 467.29 | 619.29 | 517.11 | 0.00 | 0.00 | 0.00 |
April | 523.62 | 2.35 | 521.27 | 862.28 | 334.25 | 0.00 | 0.00 | 0.00 |
May | 597.95 | 26.75 | 571.20 | 1188.73 | 174.78 | 0.00 | 0.00 | 0.00 |
June | 638.74 | 45.99 | 592.75 | 1370.10 | 79.52 | 0.00 | 0.00 | 0.00 |
July | 646.38 | 31.67 | 614.71 | 1455.43 | 115.89 | 0.00 | 0.00 | 0.00 |
August | 572.06 | 5.26 | 566.80 | 1221.65 | 78.99 | 0.00 | 0.00 | 0.00 |
September | 507.48 | 0.04 | 507.44 | 1130.22 | 129.09 | 0.00 | 0.00 | 0.00 |
October | 425.15 | 0.00 | 425.15 | 831.26 | 207.07 | 0.00 | 0.00 | 0.00 |
November | 369.67 | 0.00 | 369.67 | 587.59 | 389.31 | 0.00 | 0.00 | 0.00 |
December | 327.44 | 0.00 | 327.44 | 392.59 | 633.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.68 | 9.39 | 474.30 | 879.04 | 334.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.44 | 0.00 | 327.44 | 347.11 | 78.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 646.38 | 45.99 | 614.71 | 1455.43 | 752.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 531.39 | 254.57 | 276.82 | 736.32 | 466.06 | 0.00 | 0.00 | 0.00 |
February | 613.58 | 284.03 | 329.55 | 922.95 | 383.74 | 0.00 | 0.00 | 0.00 |
March | 749.14 | 354.16 | 394.98 | 1126.04 | 316.66 | 0.00 | 0.00 | 0.00 |
April | 813.00 | 362.76 | 450.24 | 1368.93 | 220.54 | 0.00 | 0.00 | 0.00 |
May | 769.13 | 306.29 | 462.85 | 1421.41 | 111.71 | 0.00 | 0.00 | 0.00 |
June | 759.15 | 291.58 | 467.56 | 1477.72 | 51.65 | 0.00 | 0.00 | 0.00 |
July | 780.03 | 281.30 | 498.74 | 1572.27 | 77.76 | 0.00 | 0.00 | 0.00 |
August | 713.27 | 238.50 | 474.77 | 1394.67 | 50.89 | 0.00 | 0.00 | 0.00 |
September | 687.64 | 248.58 | 439.05 | 1365.40 | 85.38 | 0.00 | 0.00 | 0.00 |
October | 632.94 | 272.58 | 360.36 | 1162.78 | 134.53 | 0.00 | 0.00 | 0.00 |
November | 513.72 | 204.84 | 308.88 | 845.43 | 241.87 | 0.00 | 0.00 | 0.00 |
December | 414.97 | 146.51 | 268.47 | 592.86 | 398.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.94 | 270.29 | 394.65 | 1166.48 | 210.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.97 | 146.51 | 268.47 | 592.86 | 50.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.00 | 362.76 | 498.74 | 1572.27 | 466.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1555.86 | 1010.81 | 545.05 | 2382.02 | 736.09 | 0.00 | 0.00 | 0.00 |
February | 1407.50 | 814.41 | 593.09 | 2280.69 | 616.65 | 0.00 | 0.00 | 0.00 |
March | 1080.64 | 456.89 | 623.76 | 1772.64 | 513.62 | 0.00 | 0.00 | 0.00 |
April | 734.82 | 128.86 | 605.96 | 1333.48 | 347.68 | 0.00 | 0.00 | 0.00 |
May | 588.84 | 12.74 | 576.10 | 1175.70 | 171.47 | 0.00 | 0.00 | 0.00 |
June | 561.40 | 1.06 | 560.35 | 1212.32 | 80.67 | 0.00 | 0.00 | 0.00 |
July | 601.11 | 5.57 | 595.54 | 1362.62 | 115.50 | 0.00 | 0.00 | 0.00 |
August | 682.24 | 57.57 | 624.67 | 1463.57 | 79.99 | 0.00 | 0.00 | 0.00 |
September | 873.36 | 214.02 | 659.34 | 1860.84 | 135.92 | 0.00 | 0.00 | 0.00 |
October | 1201.05 | 563.49 | 637.55 | 2257.57 | 227.52 | 0.00 | 0.00 | 0.00 |
November | 1366.53 | 762.67 | 603.85 | 2305.26 | 397.77 | 0.00 | 0.00 | 0.00 |
December | 1499.41 | 945.74 | 553.67 | 2354.08 | 640.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1010.90 | 412.71 | 598.19 | 1811.04 | 337.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.40 | 1.06 | 545.05 | 1175.70 | 79.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1555.86 | 1010.81 | 659.34 | 2382.02 | 736.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 477.37 | 205.80 | 271.57 | 678.04 | 496.75 | 0.00 | 0.00 | 0.00 |
February | 596.94 | 270.15 | 326.79 | 938.43 | 419.78 | 0.00 | 0.00 | 0.00 |
March | 743.37 | 339.46 | 403.91 | 1164.76 | 355.99 | 0.00 | 0.00 | 0.00 |
April | 818.23 | 378.87 | 439.36 | 1399.65 | 242.82 | 0.00 | 0.00 | 0.00 |
May | 745.92 | 287.15 | 458.78 | 1398.71 | 128.75 | 0.00 | 0.00 | 0.00 |
June | 632.03 | 177.29 | 454.74 | 1263.75 | 58.65 | 0.00 | 0.00 | 0.00 |
July | 706.35 | 218.52 | 487.82 | 1450.76 | 84.20 | 0.00 | 0.00 | 0.00 |
August | 704.74 | 229.67 | 475.07 | 1381.94 | 59.64 | 0.00 | 0.00 | 0.00 |
September | 601.18 | 177.27 | 423.91 | 1218.45 | 90.14 | 0.00 | 0.00 | 0.00 |
October | 598.06 | 233.14 | 364.92 | 1113.34 | 149.75 | 0.00 | 0.00 | 0.00 |
November | 493.34 | 180.96 | 312.38 | 836.68 | 266.23 | 0.00 | 0.00 | 0.00 |
December | 494.22 | 220.96 | 273.26 | 746.75 | 421.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.60 | 243.21 | 391.39 | 1133.69 | 230.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 477.37 | 177.27 | 271.57 | 678.04 | 58.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.23 | 378.87 | 487.82 | 1450.76 | 496.75 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.967235E+09 | 0.183351E+10 |
February | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.128343E+10 | 0.137223E+10 |
March | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.166433E+10 | 0.128504E+10 |
April | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.221814E+10 | 0.822257E+09 |
May | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.315290E+10 | 0.454254E+09 |
June | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.351041E+10 | 0.204412E+09 |
July | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.385203E+10 | 0.308127E+09 |
August | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.324285E+10 | 0.204987E+09 |
September | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.289596E+10 | 0.320136E+09 |
October | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.221278E+10 | 0.518175E+09 |
November | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.153441E+10 | 0.917631E+09 |
December | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.108318E+10 | 0.154202E+10 |
Annual Sum or Average | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.276177E+11 | 0.978278E+10 |
Minimum of Months | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.967235E+09 | 0.204412E+09 |
Maximum of Months | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.385203E+10 | 0.183351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.199933E+10 | 0.115046E+10 |
February | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.224595E+10 | 0.860383E+09 |
March | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.301387E+10 | 0.794600E+09 |
April | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.352975E+10 | 0.545140E+09 |
May | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.378025E+10 | 0.289260E+09 |
June | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.379983E+10 | 0.132441E+09 |
July | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.417738E+10 | 0.205892E+09 |
August | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.371236E+10 | 0.131944E+09 |
September | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.351335E+10 | 0.212555E+09 |
October | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.310063E+10 | 0.338595E+09 |
November | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.219756E+10 | 0.575328E+09 |
December | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.160801E+10 | 0.978642E+09 |
Annual Sum or Average | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.366783E+11 | 0.621524E+10 |
Minimum of Months | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.160801E+10 | 0.131944E+09 |
Maximum of Months | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.417738E+10 | 0.115046E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.641093E+10 | 0.182110E+10 |
February | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.553062E+10 | 0.138580E+10 |
March | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.474359E+10 | 0.128659E+10 |
April | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.343393E+10 | 0.857012E+09 |
May | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.311622E+10 | 0.442395E+09 |
June | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.310238E+10 | 0.206549E+09 |
July | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.360335E+10 | 0.306553E+09 |
August | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.388840E+10 | 0.207317E+09 |
September | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.478563E+10 | 0.338009E+09 |
October | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.602681E+10 | 0.576024E+09 |
November | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.598141E+10 | 0.953698E+09 |
December | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.632315E+10 | 0.158214E+10 |
Annual Sum or Average | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.569464E+11 | 0.996319E+10 |
Minimum of Months | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.310238E+10 | 0.206549E+09 |
Maximum of Months | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.641093E+10 | 0.182110E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.184173E+10 | 0.121228E+10 |
February | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.228491E+10 | 0.934770E+09 |
March | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.312250E+10 | 0.886966E+09 |
April | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.361835E+10 | 0.596978E+09 |
May | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.372737E+10 | 0.332134E+09 |
June | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.325326E+10 | 0.149167E+09 |
July | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.385873E+10 | 0.220743E+09 |
August | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.368446E+10 | 0.153930E+09 |
September | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.314015E+10 | 0.221668E+09 |
October | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.297535E+10 | 0.374707E+09 |
November | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.217858E+10 | 0.628119E+09 |
December | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.202154E+10 | 0.102788E+10 |
Annual Sum or Average | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.357069E+11 | 0.673934E+10 |
Minimum of Months | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.184173E+10 | 0.149167E+09 |
Maximum of Months | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.385873E+10 | 0.121228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295537E+09 | 0.00 | 0.295537E+09 | 0.307923E+09 | 0.694880E+09 |
February | 0.315962E+09 | 0.00 | 0.315962E+09 | 0.423052E+09 | 0.508177E+09 |
March | 0.417179E+09 | 0.00 | 0.417179E+09 | 0.565434E+09 | 0.456848E+09 |
April | 0.452389E+09 | 2032181.97 | 0.450357E+09 | 0.757233E+09 | 0.281138E+09 |
May | 0.533826E+09 | 23879252.18 | 0.509946E+09 | 0.107094E+10 | 0.150975E+09 |
June | 0.551845E+09 | 39734524.34 | 0.512111E+09 | 0.119179E+10 | 65286311.36 |
July | 0.577063E+09 | 28277226.60 | 0.548786E+09 | 0.130227E+10 | 0.102791E+09 |
August | 0.510709E+09 | 4697120.92 | 0.506012E+09 | 0.108646E+10 | 74195339.00 |
September | 0.438446E+09 | 34685.18 | 0.438412E+09 | 0.972268E+09 | 0.116923E+09 |
October | 0.379554E+09 | 0.00 | 0.379554E+09 | 0.738471E+09 | 0.194104E+09 |
November | 0.319379E+09 | 0.00 | 0.319379E+09 | 0.503235E+09 | 0.356365E+09 |
December | 0.292323E+09 | 0.00 | 0.292323E+09 | 0.345458E+09 | 0.593991E+09 |
Annual Sum or Average | 0.508421E+10 | 98654991.19 | 0.498556E+10 | 0.926453E+10 | 0.359567E+10 |
Minimum of Months | 0.292323E+09 | 0.00 | 0.292323E+09 | 0.307923E+09 | 65286311.36 |
Maximum of Months | 0.577063E+09 | 39734524.34 | 0.548786E+09 | 0.130227E+10 | 0.694880E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295549E+09 | 0.00 | 0.295549E+09 | 0.307935E+09 | 0.694918E+09 |
February | 0.315975E+09 | 0.00 | 0.315975E+09 | 0.423070E+09 | 0.508204E+09 |
March | 0.417196E+09 | 0.00 | 0.417196E+09 | 0.565458E+09 | 0.456872E+09 |
April | 0.452408E+09 | 2032236.59 | 0.450376E+09 | 0.757268E+09 | 0.281151E+09 |
May | 0.533847E+09 | 23879894.06 | 0.509967E+09 | 0.107099E+10 | 0.150981E+09 |
June | 0.551867E+09 | 39735592.41 | 0.512131E+09 | 0.119184E+10 | 65287996.05 |
July | 0.577086E+09 | 28277986.70 | 0.548808E+09 | 0.130233E+10 | 0.102794E+09 |
August | 0.510729E+09 | 4697247.18 | 0.506032E+09 | 0.108651E+10 | 74197056.48 |
September | 0.438464E+09 | 34686.11 | 0.438429E+09 | 0.972315E+09 | 0.116928E+09 |
October | 0.379570E+09 | 0.00 | 0.379570E+09 | 0.738507E+09 | 0.194111E+09 |
November | 0.319391E+09 | 0.00 | 0.319391E+09 | 0.503257E+09 | 0.356382E+09 |
December | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.345471E+09 | 0.594025E+09 |
Annual Sum or Average | 0.508442E+10 | 98657643.07 | 0.498576E+10 | 0.926495E+10 | 0.359585E+10 |
Minimum of Months | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.307935E+09 | 65287996.05 |
Maximum of Months | 0.577086E+09 | 39735592.41 | 0.548808E+09 | 0.130233E+10 | 0.694918E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295549E+09 | 0.00 | 0.295549E+09 | 0.307935E+09 | 0.694918E+09 |
February | 0.315975E+09 | 0.00 | 0.315975E+09 | 0.423070E+09 | 0.508204E+09 |
March | 0.417196E+09 | 0.00 | 0.417196E+09 | 0.565458E+09 | 0.456872E+09 |
April | 0.452408E+09 | 2032236.59 | 0.450376E+09 | 0.757268E+09 | 0.281151E+09 |
May | 0.533847E+09 | 23879894.06 | 0.509967E+09 | 0.107099E+10 | 0.150981E+09 |
June | 0.551867E+09 | 39735592.41 | 0.512131E+09 | 0.119184E+10 | 65287996.05 |
July | 0.577086E+09 | 28277986.70 | 0.548808E+09 | 0.130233E+10 | 0.102794E+09 |
August | 0.510729E+09 | 4697247.18 | 0.506032E+09 | 0.108651E+10 | 74197056.48 |
September | 0.438464E+09 | 34686.11 | 0.438429E+09 | 0.972315E+09 | 0.116928E+09 |
October | 0.379570E+09 | 0.00 | 0.379570E+09 | 0.738507E+09 | 0.194111E+09 |
November | 0.319391E+09 | 0.00 | 0.319391E+09 | 0.503257E+09 | 0.356382E+09 |
December | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.345471E+09 | 0.594025E+09 |
Annual Sum or Average | 0.508442E+10 | 98657643.07 | 0.498576E+10 | 0.926495E+10 | 0.359585E+10 |
Minimum of Months | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.307935E+09 | 65287996.05 |
Maximum of Months | 0.577086E+09 | 39735592.41 | 0.548808E+09 | 0.130233E+10 | 0.694918E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136912E+10 | 0.655893E+09 | 0.713232E+09 | 0.188730E+10 | 0.129371E+10 |
February | 0.142790E+10 | 0.660974E+09 | 0.766923E+09 | 0.215146E+10 | 0.950882E+09 |
March | 0.193014E+10 | 0.912484E+09 | 0.101766E+10 | 0.292497E+10 | 0.853675E+09 |
April | 0.202712E+10 | 0.904489E+09 | 0.112263E+10 | 0.343874E+10 | 0.574791E+09 |
May | 0.198166E+10 | 0.789141E+09 | 0.119252E+10 | 0.368233E+10 | 0.300607E+09 |
June | 0.189284E+10 | 0.727023E+09 | 0.116582E+10 | 0.369270E+10 | 0.134818E+09 |
July | 0.200974E+10 | 0.724751E+09 | 0.128499E+10 | 0.405139E+10 | 0.217425E+09 |
August | 0.183773E+10 | 0.614496E+09 | 0.122324E+10 | 0.357906E+10 | 0.154578E+09 |
September | 0.171454E+10 | 0.619811E+09 | 0.109473E+10 | 0.338928E+10 | 0.239095E+09 |
October | 0.163077E+10 | 0.702307E+09 | 0.928464E+09 | 0.298806E+10 | 0.393718E+09 |
November | 0.128089E+10 | 0.510738E+09 | 0.770151E+09 | 0.209776E+10 | 0.666611E+09 |
December | 0.106917E+10 | 0.377467E+09 | 0.691702E+09 | 0.151265E+10 | 0.111368E+10 |
Annual Sum or Average | 0.201716E+11 | 0.819957E+10 | 0.119721E+11 | 0.353957E+11 | 0.689359E+10 |
Minimum of Months | 0.106917E+10 | 0.377467E+09 | 0.691702E+09 | 0.151265E+10 | 0.134818E+09 |
Maximum of Months | 0.202712E+10 | 0.912484E+09 | 0.128499E+10 | 0.405139E+10 | 0.129371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54133955.09 | 25933416.62 | 28200538.47 | 74622336.59 | 51152252.76 |
February | 56457771.57 | 26134308.99 | 30323462.58 | 85066711.22 | 37597026.66 |
March | 76316054.86 | 36078813.09 | 40237241.78 | 0.115651E+09 | 33753537.61 |
April | 80150581.35 | 35762678.23 | 44387903.11 | 0.135964E+09 | 22726738.23 |
May | 78353173.20 | 31201924.47 | 47151248.73 | 0.145596E+09 | 11885720.40 |
June | 74841127.61 | 28745843.77 | 46095283.84 | 0.146006E+09 | 5330563.48 |
July | 79463329.13 | 28655995.03 | 50807334.10 | 0.160188E+09 | 8596801.45 |
August | 72662332.41 | 24296632.89 | 48365699.52 | 0.141513E+09 | 6111856.83 |
September | 67791450.18 | 24506775.11 | 43284675.07 | 0.134009E+09 | 9453617.43 |
October | 64479227.84 | 27768589.34 | 36710638.49 | 0.118145E+09 | 15567264.49 |
November | 50645196.43 | 20194127.79 | 30451068.64 | 82943479.10 | 26357201.61 |
December | 42273992.56 | 14924701.77 | 27349290.79 | 59809002.81 | 44033782.11 |
Annual Sum or Average | 0.797568E+09 | 0.324204E+09 | 0.473364E+09 | 0.139951E+10 | 0.272566E+09 |
Minimum of Months | 42273992.56 | 14924701.77 | 27349290.79 | 59809002.81 | 5330563.48 |
Maximum of Months | 80150581.35 | 36078813.09 | 50807334.10 | 0.160188E+09 | 51152252.76 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138905E+10 | 0.902429E+09 | 0.486617E+09 | 0.213369E+10 | 0.714860E+09 |
February | 0.113499E+10 | 0.656729E+09 | 0.478262E+09 | 0.184903E+10 | 0.533458E+09 |
March | 0.964783E+09 | 0.407900E+09 | 0.556883E+09 | 0.160287E+10 | 0.471477E+09 |
April | 0.634876E+09 | 0.111331E+09 | 0.523544E+09 | 0.116540E+10 | 0.300092E+09 |
May | 0.525710E+09 | 11373457.81 | 0.514336E+09 | 0.105571E+10 | 0.149515E+09 |
June | 0.485050E+09 | 915359.33 | 0.484135E+09 | 0.104991E+10 | 66086073.37 |
July | 0.536669E+09 | 4974389.47 | 0.531695E+09 | 0.121177E+10 | 0.103614E+09 |
August | 0.609101E+09 | 51398714.70 | 0.557702E+09 | 0.129351E+10 | 79292573.69 |
September | 0.754575E+09 | 0.184909E+09 | 0.569666E+09 | 0.159167E+10 | 0.130875E+09 |
October | 0.107228E+10 | 0.503078E+09 | 0.569201E+09 | 0.200473E+10 | 0.235622E+09 |
November | 0.118066E+10 | 0.658936E+09 | 0.521723E+09 | 0.199047E+10 | 0.387625E+09 |
December | 0.133865E+10 | 0.844344E+09 | 0.494308E+09 | 0.210821E+10 | 0.625217E+09 |
Annual Sum or Average | 0.106264E+11 | 0.433832E+10 | 0.628807E+10 | 0.190570E+11 | 0.379773E+10 |
Minimum of Months | 0.485050E+09 | 915359.33 | 0.478262E+09 | 0.104991E+10 | 66086073.37 |
Maximum of Months | 0.138905E+10 | 0.902429E+09 | 0.569666E+09 | 0.213369E+10 | 0.714860E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138905E+10 | 0.902429E+09 | 0.486617E+09 | 0.213369E+10 | 0.714860E+09 |
February | 0.113499E+10 | 0.656729E+09 | 0.478262E+09 | 0.184903E+10 | 0.533458E+09 |
March | 0.964783E+09 | 0.407900E+09 | 0.556883E+09 | 0.160287E+10 | 0.471477E+09 |
April | 0.634876E+09 | 0.111331E+09 | 0.523544E+09 | 0.116540E+10 | 0.300092E+09 |
May | 0.525710E+09 | 11373457.81 | 0.514336E+09 | 0.105571E+10 | 0.149515E+09 |
June | 0.485050E+09 | 915359.33 | 0.484135E+09 | 0.104991E+10 | 66086073.37 |
July | 0.536669E+09 | 4974389.47 | 0.531695E+09 | 0.121177E+10 | 0.103614E+09 |
August | 0.609101E+09 | 51398714.70 | 0.557702E+09 | 0.129351E+10 | 79292573.69 |
September | 0.754575E+09 | 0.184909E+09 | 0.569666E+09 | 0.159167E+10 | 0.130875E+09 |
October | 0.107228E+10 | 0.503078E+09 | 0.569201E+09 | 0.200473E+10 | 0.235622E+09 |
November | 0.118066E+10 | 0.658936E+09 | 0.521723E+09 | 0.199047E+10 | 0.387625E+09 |
December | 0.133865E+10 | 0.844344E+09 | 0.494308E+09 | 0.210821E+10 | 0.625217E+09 |
Annual Sum or Average | 0.106264E+11 | 0.433832E+10 | 0.628807E+10 | 0.190570E+11 | 0.379773E+10 |
Minimum of Months | 0.485050E+09 | 915359.33 | 0.478262E+09 | 0.104991E+10 | 66086073.37 |
Maximum of Months | 0.138905E+10 | 0.902429E+09 | 0.569666E+09 | 0.213369E+10 | 0.714860E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138896E+10 | 0.902372E+09 | 0.486586E+09 | 0.213355E+10 | 0.714814E+09 |
February | 0.113492E+10 | 0.656688E+09 | 0.478232E+09 | 0.184891E+10 | 0.533425E+09 |
March | 0.964722E+09 | 0.407874E+09 | 0.556848E+09 | 0.160277E+10 | 0.471447E+09 |
April | 0.634835E+09 | 0.111324E+09 | 0.523511E+09 | 0.116532E+10 | 0.300073E+09 |
May | 0.525677E+09 | 11372739.07 | 0.514304E+09 | 0.105564E+10 | 0.149506E+09 |
June | 0.485020E+09 | 915301.49 | 0.484104E+09 | 0.104984E+10 | 66081897.10 |
July | 0.536635E+09 | 4974075.11 | 0.531661E+09 | 0.121169E+10 | 0.103607E+09 |
August | 0.609062E+09 | 51395466.59 | 0.557667E+09 | 0.129343E+10 | 79287562.85 |
September | 0.754527E+09 | 0.184897E+09 | 0.569630E+09 | 0.159157E+10 | 0.130867E+09 |
October | 0.107221E+10 | 0.503046E+09 | 0.569165E+09 | 0.200461E+10 | 0.235607E+09 |
November | 0.118059E+10 | 0.658895E+09 | 0.521690E+09 | 0.199034E+10 | 0.387600E+09 |
December | 0.133857E+10 | 0.844290E+09 | 0.494277E+09 | 0.210808E+10 | 0.625178E+09 |
Annual Sum or Average | 0.106257E+11 | 0.433804E+10 | 0.628767E+10 | 0.190558E+11 | 0.379749E+10 |
Minimum of Months | 0.485020E+09 | 915301.49 | 0.478232E+09 | 0.104984E+10 | 66081897.10 |
Maximum of Months | 0.138896E+10 | 0.902372E+09 | 0.569630E+09 | 0.213355E+10 | 0.714814E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122994E+10 | 0.530241E+09 | 0.699694E+09 | 0.173643E+10 | 0.136611E+10 |
February | 0.138916E+10 | 0.628673E+09 | 0.760489E+09 | 0.218317E+10 | 0.103268E+10 |
March | 0.191528E+10 | 0.874615E+09 | 0.104067E+10 | 0.301758E+10 | 0.954544E+09 |
April | 0.204016E+10 | 0.944659E+09 | 0.109550E+10 | 0.350593E+10 | 0.627158E+09 |
May | 0.192187E+10 | 0.739827E+09 | 0.118204E+10 | 0.361777E+10 | 0.343715E+09 |
June | 0.157588E+10 | 0.442048E+09 | 0.113384E+10 | 0.315821E+10 | 0.148575E+09 |
July | 0.181990E+10 | 0.563018E+09 | 0.125688E+10 | 0.373532E+10 | 0.232349E+09 |
August | 0.181576E+10 | 0.591751E+09 | 0.122401E+10 | 0.354703E+10 | 0.178126E+09 |
September | 0.149897E+10 | 0.441998E+09 | 0.105698E+10 | 0.302313E+10 | 0.251165E+09 |
October | 0.154091E+10 | 0.600692E+09 | 0.940217E+09 | 0.285808E+10 | 0.430539E+09 |
November | 0.123009E+10 | 0.451201E+09 | 0.778885E+09 | 0.207447E+10 | 0.727829E+09 |
December | 0.127336E+10 | 0.569309E+09 | 0.704053E+09 | 0.190929E+10 | 0.117497E+10 |
Annual Sum or Average | 0.192513E+11 | 0.737803E+10 | 0.118733E+11 | 0.343664E+11 | 0.746775E+10 |
Minimum of Months | 0.122994E+10 | 0.441998E+09 | 0.699694E+09 | 0.173643E+10 | 0.148575E+09 |
Maximum of Months | 0.204016E+10 | 0.944659E+09 | 0.125688E+10 | 0.373532E+10 | 0.136611E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48630392.51 | 20965170.66 | 27665221.86 | 68656531.94 | 54014526.35 |
February | 54926052.04 | 24857081.76 | 30068970.27 | 86320383.48 | 40831049.52 |
March | 75728298.02 | 34581375.50 | 41146922.52 | 0.119312E+09 | 37741777.60 |
April | 80665992.58 | 37350830.63 | 43315161.95 | 0.138621E+09 | 24797247.93 |
May | 75988789.82 | 29252006.13 | 46736783.68 | 0.143043E+09 | 13590135.75 |
June | 62308871.72 | 17478117.54 | 44830754.17 | 0.124873E+09 | 5874487.34 |
July | 71956974.33 | 22261134.66 | 49695839.68 | 0.147691E+09 | 9186827.69 |
August | 71793305.40 | 23397217.82 | 48396087.58 | 0.140246E+09 | 7042932.61 |
September | 59267944.34 | 17476161.56 | 41791782.78 | 0.119531E+09 | 9930830.75 |
October | 60925982.45 | 23750735.43 | 37175247.02 | 0.113006E+09 | 17023099.56 |
November | 48636348.25 | 17840022.59 | 30796325.67 | 82022562.04 | 28777654.61 |
December | 50347468.56 | 22509892.26 | 27837576.31 | 75491361.65 | 46457245.94 |
Annual Sum or Average | 0.761176E+09 | 0.291720E+09 | 0.469457E+09 | 0.135881E+10 | 0.295268E+09 |
Minimum of Months | 48630392.51 | 17476161.56 | 27665221.86 | 68656531.94 | 5874487.34 |
Maximum of Months | 80665992.58 | 37350830.63 | 49695839.68 | 0.147691E+09 | 54014526.35 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.929688E+09 | 0.201429E+10 |
February | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.126208E+10 | 0.149466E+10 |
March | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.165869E+10 | 0.138502E+10 |
April | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.223503E+10 | 0.866387E+09 |
May | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.318389E+10 | 0.468141E+09 |
June | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.355131E+10 | 0.206107E+09 |
July | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.389823E+10 | 0.310401E+09 |
August | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.327206E+10 | 0.211566E+09 |
September | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.292953E+10 | 0.334595E+09 |
October | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.222644E+10 | 0.554608E+09 |
November | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.152304E+10 | 0.100909E+10 |
December | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.105151E+10 | 0.169630E+10 |
Annual Sum or Average | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.277215E+11 | 0.105512E+11 |
Minimum of Months | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.929688E+09 | 0.206107E+09 |
Maximum of Months | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.389823E+10 | 0.201429E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.197217E+10 | 0.124829E+10 |
February | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.223281E+10 | 0.928349E+09 |
March | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.301600E+10 | 0.848132E+09 |
April | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.354826E+10 | 0.571638E+09 |
May | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.380710E+10 | 0.299215E+09 |
June | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.383024E+10 | 0.133888E+09 |
July | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.421118E+10 | 0.208285E+09 |
August | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.373548E+10 | 0.136296E+09 |
September | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.353912E+10 | 0.221300E+09 |
October | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.311439E+10 | 0.360320E+09 |
November | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.219134E+10 | 0.626938E+09 |
December | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.158792E+10 | 0.106726E+10 |
Annual Sum or Average | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.367860E+11 | 0.664992E+10 |
Minimum of Months | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.158792E+10 | 0.133888E+09 |
Maximum of Months | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.421118E+10 | 0.124829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.638000E+10 | 0.197155E+10 |
February | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.551744E+10 | 0.149179E+10 |
March | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.474784E+10 | 0.137569E+10 |
April | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.345638E+10 | 0.901186E+09 |
May | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.314899E+10 | 0.459276E+09 |
June | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.314233E+10 | 0.209109E+09 |
July | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.364964E+10 | 0.309355E+09 |
August | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.392003E+10 | 0.214239E+09 |
September | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.482329E+10 | 0.352303E+09 |
October | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.604667E+10 | 0.609400E+09 |
November | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.597525E+10 | 0.103101E+10 |
December | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.630516E+10 | 0.171469E+10 |
Annual Sum or Average | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.571130E+11 | 0.106396E+11 |
Minimum of Months | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.314233E+10 | 0.209109E+09 |
Maximum of Months | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.638000E+10 | 0.197155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.181607E+10 | 0.133049E+10 |
February | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.227024E+10 | 0.101554E+10 |
March | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.311970E+10 | 0.953490E+09 |
April | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.362789E+10 | 0.629398E+09 |
May | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.374631E+10 | 0.344846E+09 |
June | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.327563E+10 | 0.152029E+09 |
July | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.388572E+10 | 0.225516E+09 |
August | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.370139E+10 | 0.159730E+09 |
September | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.315822E+10 | 0.233637E+09 |
October | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.298198E+10 | 0.401080E+09 |
November | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.216868E+10 | 0.690061E+09 |
December | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.200010E+10 | 0.112766E+10 |
Annual Sum or Average | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.357520E+11 | 0.726347E+10 |
Minimum of Months | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.181607E+10 | 0.152029E+09 |
Maximum of Months | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.388572E+10 | 0.133049E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 361.12 | 684.55 | 331.04 | 0.00 | 331.04 | 0.00 | 0.00 |
February | 530.52 | 567.22 | 391.84 | 0.00 | 391.84 | 0.00 | 0.00 |
March | 621.39 | 479.78 | 467.29 | 0.00 | 467.29 | 0.00 | 0.00 |
April | 855.76 | 317.23 | 523.62 | 2.35 | 521.27 | 0.00 | 0.00 |
May | 1177.16 | 169.60 | 597.95 | 26.75 | 571.20 | 0.00 | 0.00 |
June | 1354.32 | 78.86 | 638.74 | 45.99 | 592.75 | 0.00 | 0.00 |
July | 1438.18 | 115.04 | 646.38 | 31.67 | 614.71 | 0.00 | 0.00 |
August | 1210.74 | 76.53 | 572.06 | 5.26 | 566.80 | 0.00 | 0.00 |
September | 1117.27 | 123.51 | 507.48 | 0.04 | 507.44 | 0.00 | 0.00 |
October | 826.16 | 193.46 | 425.15 | 0.00 | 425.15 | 0.00 | 0.00 |
November | 591.98 | 354.02 | 369.67 | 0.00 | 369.67 | 0.00 | 0.00 |
December | 404.41 | 575.73 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Annual Sum or Average | 875.75 | 310.21 | 483.68 | 9.39 | 474.30 | 0.00 | 0.00 |
Minimum of Months | 361.12 | 76.53 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Maximum of Months | 1438.18 | 684.55 | 646.38 | 45.99 | 614.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 746.46 | 429.53 | 531.39 | 254.57 | 276.82 | 0.00 | 0.00 |
February | 928.38 | 355.65 | 613.58 | 284.03 | 329.55 | 0.00 | 0.00 |
March | 1125.25 | 296.67 | 749.14 | 354.16 | 394.98 | 0.00 | 0.00 |
April | 1361.78 | 210.32 | 813.00 | 362.76 | 450.24 | 0.00 | 0.00 |
May | 1411.38 | 108.00 | 769.13 | 306.29 | 462.85 | 0.00 | 0.00 |
June | 1465.98 | 51.10 | 759.15 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1559.66 | 76.87 | 780.03 | 281.30 | 498.74 | 0.00 | 0.00 |
August | 1386.04 | 49.26 | 713.27 | 238.50 | 474.77 | 0.00 | 0.00 |
September | 1355.46 | 82.00 | 687.64 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1157.64 | 126.42 | 632.94 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 847.82 | 221.96 | 513.72 | 204.84 | 308.88 | 0.00 | 0.00 |
December | 600.36 | 365.38 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Annual Sum or Average | 1163.06 | 197.08 | 664.94 | 270.29 | 394.65 | 0.00 | 0.00 |
Minimum of Months | 600.36 | 49.26 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Maximum of Months | 1559.66 | 429.53 | 813.00 | 362.76 | 498.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2393.57 | 679.92 | 1555.86 | 1010.81 | 545.05 | 0.00 | 0.00 |
February | 2286.14 | 572.83 | 1407.50 | 814.41 | 593.09 | 0.00 | 0.00 |
March | 1771.05 | 480.36 | 1080.64 | 456.89 | 623.76 | 0.00 | 0.00 |
April | 1324.82 | 330.64 | 734.82 | 128.86 | 605.96 | 0.00 | 0.00 |
May | 1163.46 | 165.17 | 588.84 | 12.74 | 576.10 | 0.00 | 0.00 |
June | 1196.91 | 79.69 | 561.40 | 1.06 | 560.35 | 0.00 | 0.00 |
July | 1345.34 | 114.45 | 601.11 | 5.57 | 595.54 | 0.00 | 0.00 |
August | 1451.76 | 77.40 | 682.24 | 57.57 | 624.67 | 0.00 | 0.00 |
September | 1846.31 | 130.40 | 873.36 | 214.02 | 659.34 | 0.00 | 0.00 |
October | 2250.15 | 215.06 | 1201.05 | 563.49 | 637.55 | 0.00 | 0.00 |
November | 2307.64 | 367.94 | 1366.53 | 762.67 | 603.85 | 0.00 | 0.00 |
December | 2360.79 | 590.70 | 1499.41 | 945.74 | 553.67 | 0.00 | 0.00 |
Annual Sum or Average | 1805.76 | 315.93 | 1010.90 | 412.71 | 598.19 | 0.00 | 0.00 |
Minimum of Months | 1163.46 | 77.40 | 561.40 | 1.06 | 545.05 | 0.00 | 0.00 |
Maximum of Months | 2393.57 | 679.92 | 1555.86 | 1010.81 | 659.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 687.62 | 452.61 | 477.37 | 205.80 | 271.57 | 0.00 | 0.00 |
February | 944.49 | 386.40 | 596.94 | 270.15 | 326.79 | 0.00 | 0.00 |
March | 1165.81 | 331.16 | 743.37 | 339.46 | 403.91 | 0.00 | 0.00 |
April | 1395.97 | 230.32 | 818.23 | 378.87 | 439.36 | 0.00 | 0.00 |
May | 1391.64 | 124.00 | 745.92 | 287.15 | 458.78 | 0.00 | 0.00 |
June | 1255.11 | 57.55 | 632.03 | 177.29 | 454.74 | 0.00 | 0.00 |
July | 1440.68 | 82.42 | 706.35 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1375.62 | 57.47 | 704.74 | 229.67 | 475.07 | 0.00 | 0.00 |
September | 1211.48 | 85.52 | 601.18 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1110.87 | 139.90 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 840.50 | 242.33 | 493.34 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 754.76 | 383.77 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1132.26 | 213.70 | 634.60 | 243.21 | 391.39 | 0.00 | 0.00 |
Minimum of Months | 687.62 | 57.47 | 477.37 | 177.27 | 271.57 | 0.00 | 0.00 |
Maximum of Months | 1440.68 | 452.61 | 818.23 | 378.87 | 487.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 344.90 | 778.34 | 331.03 | 0.00 | 331.03 | 0.00 | 0.00 |
February | 524.63 | 630.20 | 391.83 | 0.00 | 391.83 | 0.00 | 0.00 |
March | 633.34 | 511.72 | 467.28 | 0.00 | 467.28 | 0.00 | 0.00 |
April | 876.45 | 325.40 | 523.61 | 2.35 | 521.26 | 0.00 | 0.00 |
May | 1199.57 | 169.11 | 597.94 | 26.75 | 571.19 | 0.00 | 0.00 |
June | 1379.42 | 75.56 | 638.73 | 45.99 | 592.74 | 0.00 | 0.00 |
July | 1458.68 | 115.14 | 646.37 | 31.67 | 614.70 | 0.00 | 0.00 |
August | 1216.95 | 83.11 | 572.05 | 5.26 | 566.78 | 0.00 | 0.00 |
September | 1125.35 | 135.33 | 507.47 | 0.04 | 507.43 | 0.00 | 0.00 |
October | 827.17 | 217.42 | 425.14 | 0.00 | 425.14 | 0.00 | 0.00 |
November | 582.46 | 412.47 | 369.66 | 0.00 | 369.66 | 0.00 | 0.00 |
December | 386.95 | 665.34 | 327.43 | 0.00 | 327.43 | 0.00 | 0.00 |
Annual Sum or Average | 881.36 | 342.07 | 483.67 | 9.39 | 474.29 | 0.00 | 0.00 |
Minimum of Months | 344.90 | 75.56 | 327.43 | 0.00 | 327.43 | 0.00 | 0.00 |
Maximum of Months | 1458.68 | 778.34 | 646.37 | 45.99 | 614.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 732.50 | 502.12 | 531.38 | 254.56 | 276.82 | 0.00 | 0.00 |
February | 924.49 | 408.60 | 613.57 | 284.02 | 329.55 | 0.00 | 0.00 |
March | 1135.24 | 331.33 | 749.13 | 354.15 | 394.97 | 0.00 | 0.00 |
April | 1379.13 | 230.52 | 812.99 | 362.75 | 450.24 | 0.00 | 0.00 |
May | 1429.18 | 116.67 | 769.12 | 306.28 | 462.84 | 0.00 | 0.00 |
June | 1480.98 | 54.07 | 759.14 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1572.42 | 84.39 | 780.02 | 281.29 | 498.73 | 0.00 | 0.00 |
August | 1389.10 | 59.99 | 713.26 | 238.50 | 474.76 | 0.00 | 0.00 |
September | 1359.29 | 95.89 | 687.63 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1159.72 | 152.81 | 632.93 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 841.32 | 267.35 | 513.71 | 204.83 | 308.87 | 0.00 | 0.00 |
December | 587.09 | 432.24 | 414.97 | 146.50 | 268.46 | 0.00 | 0.00 |
Annual Sum or Average | 1166.77 | 227.24 | 664.93 | 270.29 | 394.64 | 0.00 | 0.00 |
Minimum of Months | 587.09 | 54.07 | 414.97 | 146.50 | 268.46 | 0.00 | 0.00 |
Maximum of Months | 1572.42 | 502.12 | 812.99 | 362.75 | 498.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2389.83 | 800.68 | 1555.80 | 1010.76 | 545.03 | 0.00 | 0.00 |
February | 2292.89 | 661.52 | 1407.45 | 814.38 | 593.07 | 0.00 | 0.00 |
March | 1795.29 | 528.08 | 1080.60 | 456.87 | 623.74 | 0.00 | 0.00 |
April | 1348.81 | 347.32 | 734.79 | 128.85 | 605.94 | 0.00 | 0.00 |
May | 1182.44 | 167.46 | 588.82 | 12.74 | 576.08 | 0.00 | 0.00 |
June | 1215.14 | 76.49 | 561.39 | 1.06 | 560.33 | 0.00 | 0.00 |
July | 1357.24 | 116.05 | 601.10 | 5.57 | 595.52 | 0.00 | 0.00 |
August | 1448.79 | 88.81 | 682.22 | 57.57 | 624.65 | 0.00 | 0.00 |
September | 1842.17 | 151.47 | 873.33 | 214.01 | 659.32 | 0.00 | 0.00 |
October | 2245.40 | 263.91 | 1201.00 | 563.47 | 637.53 | 0.00 | 0.00 |
November | 2303.74 | 448.63 | 1366.48 | 762.64 | 603.83 | 0.00 | 0.00 |
December | 2361.29 | 700.27 | 1499.35 | 945.71 | 553.65 | 0.00 | 0.00 |
Annual Sum or Average | 1812.84 | 361.27 | 1010.86 | 412.69 | 598.17 | 0.00 | 0.00 |
Minimum of Months | 1182.44 | 76.49 | 561.39 | 1.06 | 545.03 | 0.00 | 0.00 |
Maximum of Months | 2389.83 | 800.68 | 1555.80 | 1010.76 | 659.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 673.94 | 530.21 | 477.36 | 205.80 | 271.56 | 0.00 | 0.00 |
February | 938.12 | 443.74 | 596.93 | 270.14 | 326.78 | 0.00 | 0.00 |
March | 1171.18 | 370.48 | 743.36 | 339.46 | 403.90 | 0.00 | 0.00 |
April | 1406.08 | 251.53 | 818.22 | 378.86 | 439.36 | 0.00 | 0.00 |
May | 1404.13 | 133.40 | 745.91 | 287.14 | 458.77 | 0.00 | 0.00 |
June | 1266.62 | 59.59 | 632.02 | 177.29 | 454.73 | 0.00 | 0.00 |
July | 1449.75 | 90.18 | 706.34 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1376.67 | 69.13 | 704.73 | 229.67 | 475.06 | 0.00 | 0.00 |
September | 1212.44 | 100.73 | 601.17 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1109.28 | 167.10 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 831.98 | 291.90 | 493.33 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 741.03 | 456.03 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1132.84 | 246.16 | 634.59 | 243.21 | 391.38 | 0.00 | 0.00 |
Minimum of Months | 673.94 | 59.59 | 477.36 | 177.27 | 271.56 | 0.00 | 0.00 |
Maximum of Months | 1449.75 | 530.21 | 818.22 | 378.86 | 487.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.11 | 752.05 | 331.04 | 0.00 | 331.04 | 0.00 | 0.00 |
February | 521.69 | 617.83 | 391.84 | 0.00 | 391.84 | 0.00 | 0.00 |
March | 619.29 | 517.11 | 467.29 | 0.00 | 467.29 | 0.00 | 0.00 |
April | 862.28 | 334.25 | 523.62 | 2.35 | 521.27 | 0.00 | 0.00 |
May | 1188.73 | 174.78 | 597.95 | 26.75 | 571.20 | 0.00 | 0.00 |
June | 1370.10 | 79.52 | 638.74 | 45.99 | 592.75 | 0.00 | 0.00 |
July | 1455.43 | 115.89 | 646.38 | 31.67 | 614.71 | 0.00 | 0.00 |
August | 1221.65 | 78.99 | 572.06 | 5.26 | 566.80 | 0.00 | 0.00 |
September | 1130.22 | 129.09 | 507.48 | 0.04 | 507.44 | 0.00 | 0.00 |
October | 831.26 | 207.07 | 425.15 | 0.00 | 425.15 | 0.00 | 0.00 |
November | 587.59 | 389.31 | 369.67 | 0.00 | 369.67 | 0.00 | 0.00 |
December | 392.59 | 633.32 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Annual Sum or Average | 879.04 | 334.58 | 483.68 | 9.39 | 474.30 | 0.00 | 0.00 |
Minimum of Months | 347.11 | 78.99 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Maximum of Months | 1455.43 | 752.05 | 646.38 | 45.99 | 614.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 736.32 | 466.06 | 531.39 | 254.57 | 276.82 | 0.00 | 0.00 |
February | 922.95 | 383.74 | 613.58 | 284.03 | 329.55 | 0.00 | 0.00 |
March | 1126.04 | 316.66 | 749.14 | 354.16 | 394.98 | 0.00 | 0.00 |
April | 1368.93 | 220.54 | 813.00 | 362.76 | 450.24 | 0.00 | 0.00 |
May | 1421.41 | 111.71 | 769.13 | 306.29 | 462.85 | 0.00 | 0.00 |
June | 1477.72 | 51.65 | 759.15 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1572.27 | 77.76 | 780.03 | 281.30 | 498.74 | 0.00 | 0.00 |
August | 1394.67 | 50.89 | 713.27 | 238.50 | 474.77 | 0.00 | 0.00 |
September | 1365.40 | 85.38 | 687.64 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1162.78 | 134.53 | 632.94 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 845.43 | 241.87 | 513.72 | 204.84 | 308.88 | 0.00 | 0.00 |
December | 592.86 | 398.47 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Annual Sum or Average | 1166.48 | 210.87 | 664.94 | 270.29 | 394.65 | 0.00 | 0.00 |
Minimum of Months | 592.86 | 50.89 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Maximum of Months | 1572.27 | 466.06 | 813.00 | 362.76 | 498.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2382.02 | 736.09 | 1555.86 | 1010.81 | 545.05 | 0.00 | 0.00 |
February | 2280.69 | 616.65 | 1407.50 | 814.41 | 593.09 | 0.00 | 0.00 |
March | 1772.64 | 513.62 | 1080.64 | 456.89 | 623.76 | 0.00 | 0.00 |
April | 1333.48 | 347.68 | 734.82 | 128.86 | 605.96 | 0.00 | 0.00 |
May | 1175.70 | 171.47 | 588.84 | 12.74 | 576.10 | 0.00 | 0.00 |
June | 1212.32 | 80.67 | 561.40 | 1.06 | 560.35 | 0.00 | 0.00 |
July | 1362.62 | 115.50 | 601.11 | 5.57 | 595.54 | 0.00 | 0.00 |
August | 1463.57 | 79.99 | 682.24 | 57.57 | 624.67 | 0.00 | 0.00 |
September | 1860.84 | 135.92 | 873.36 | 214.02 | 659.34 | 0.00 | 0.00 |
October | 2257.57 | 227.52 | 1201.05 | 563.49 | 637.55 | 0.00 | 0.00 |
November | 2305.26 | 397.77 | 1366.53 | 762.67 | 603.85 | 0.00 | 0.00 |
December | 2354.08 | 640.19 | 1499.41 | 945.74 | 553.67 | 0.00 | 0.00 |
Annual Sum or Average | 1811.04 | 337.38 | 1010.90 | 412.71 | 598.19 | 0.00 | 0.00 |
Minimum of Months | 1175.70 | 79.99 | 561.40 | 1.06 | 545.05 | 0.00 | 0.00 |
Maximum of Months | 2382.02 | 736.09 | 1555.86 | 1010.81 | 659.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 678.04 | 496.75 | 477.37 | 205.80 | 271.57 | 0.00 | 0.00 |
February | 938.43 | 419.78 | 596.94 | 270.15 | 326.79 | 0.00 | 0.00 |
March | 1164.76 | 355.99 | 743.37 | 339.46 | 403.91 | 0.00 | 0.00 |
April | 1399.65 | 242.82 | 818.23 | 378.87 | 439.36 | 0.00 | 0.00 |
May | 1398.71 | 128.75 | 745.92 | 287.15 | 458.78 | 0.00 | 0.00 |
June | 1263.75 | 58.65 | 632.03 | 177.29 | 454.74 | 0.00 | 0.00 |
July | 1450.76 | 84.20 | 706.35 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1381.94 | 59.64 | 704.74 | 229.67 | 475.07 | 0.00 | 0.00 |
September | 1218.45 | 90.14 | 601.18 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1113.34 | 149.75 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 836.68 | 266.23 | 493.34 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 746.75 | 421.02 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1133.69 | 230.32 | 634.60 | 243.21 | 391.39 | 0.00 | 0.00 |
Minimum of Months | 678.04 | 58.65 | 477.37 | 177.27 | 271.57 | 0.00 | 0.00 |
Maximum of Months | 1450.76 | 496.75 | 818.23 | 378.87 | 487.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.967235E+09 | 0.183351E+10 | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.00 | 0.00 |
February | 0.128343E+10 | 0.137223E+10 | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.00 | 0.00 |
March | 0.166433E+10 | 0.128504E+10 | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.00 | 0.00 |
April | 0.221814E+10 | 0.822257E+09 | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.00 | 0.00 |
May | 0.315290E+10 | 0.454254E+09 | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.00 | 0.00 |
June | 0.351041E+10 | 0.204412E+09 | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.00 | 0.00 |
July | 0.385203E+10 | 0.308127E+09 | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.00 | 0.00 |
August | 0.324285E+10 | 0.204987E+09 | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.00 | 0.00 |
September | 0.289596E+10 | 0.320136E+09 | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.00 | 0.00 |
October | 0.221278E+10 | 0.518175E+09 | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.00 | 0.00 |
November | 0.153441E+10 | 0.917631E+09 | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.00 | 0.00 |
December | 0.108318E+10 | 0.154202E+10 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276177E+11 | 0.978278E+10 | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.967235E+09 | 0.204412E+09 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385203E+10 | 0.183351E+10 | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199933E+10 | 0.115046E+10 | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.00 | 0.00 |
February | 0.224595E+10 | 0.860383E+09 | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.00 | 0.00 |
March | 0.301387E+10 | 0.794600E+09 | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.00 | 0.00 |
April | 0.352975E+10 | 0.545140E+09 | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.00 | 0.00 |
May | 0.378025E+10 | 0.289260E+09 | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.00 | 0.00 |
June | 0.379983E+10 | 0.132441E+09 | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.00 | 0.00 |
July | 0.417738E+10 | 0.205892E+09 | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.00 | 0.00 |
August | 0.371236E+10 | 0.131944E+09 | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.00 | 0.00 |
September | 0.351335E+10 | 0.212555E+09 | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.00 | 0.00 |
October | 0.310063E+10 | 0.338595E+09 | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.00 | 0.00 |
November | 0.219756E+10 | 0.575328E+09 | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.00 | 0.00 |
December | 0.160801E+10 | 0.978642E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366783E+11 | 0.621524E+10 | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160801E+10 | 0.131944E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417738E+10 | 0.115046E+10 | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.641093E+10 | 0.182110E+10 | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.00 | 0.00 |
February | 0.553062E+10 | 0.138580E+10 | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.00 | 0.00 |
March | 0.474359E+10 | 0.128659E+10 | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.00 | 0.00 |
April | 0.343393E+10 | 0.857012E+09 | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.00 | 0.00 |
May | 0.311622E+10 | 0.442395E+09 | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.00 | 0.00 |
June | 0.310238E+10 | 0.206549E+09 | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.00 | 0.00 |
July | 0.360335E+10 | 0.306553E+09 | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.00 | 0.00 |
August | 0.388840E+10 | 0.207317E+09 | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.00 | 0.00 |
September | 0.478563E+10 | 0.338009E+09 | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.00 | 0.00 |
October | 0.602681E+10 | 0.576024E+09 | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.00 | 0.00 |
November | 0.598141E+10 | 0.953698E+09 | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.00 | 0.00 |
December | 0.632315E+10 | 0.158214E+10 | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.569464E+11 | 0.996319E+10 | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310238E+10 | 0.206549E+09 | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641093E+10 | 0.182110E+10 | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184173E+10 | 0.121228E+10 | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.00 | 0.00 |
February | 0.228491E+10 | 0.934770E+09 | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.00 | 0.00 |
March | 0.312250E+10 | 0.886966E+09 | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.00 | 0.00 |
April | 0.361835E+10 | 0.596978E+09 | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.00 | 0.00 |
May | 0.372737E+10 | 0.332134E+09 | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.00 | 0.00 |
June | 0.325326E+10 | 0.149167E+09 | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.00 | 0.00 |
July | 0.385873E+10 | 0.220743E+09 | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.00 | 0.00 |
August | 0.368446E+10 | 0.153930E+09 | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.00 | 0.00 |
September | 0.314015E+10 | 0.221668E+09 | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.00 | 0.00 |
October | 0.297535E+10 | 0.374707E+09 | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.00 | 0.00 |
November | 0.217858E+10 | 0.628119E+09 | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.00 | 0.00 |
December | 0.202154E+10 | 0.102788E+10 | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357069E+11 | 0.673934E+10 | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184173E+10 | 0.149167E+09 | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385873E+10 | 0.121228E+10 | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.923793E+09 | 0.208472E+10 | 0.886634E+09 | 0.00 | 0.886634E+09 | 0.00 | 0.00 |
February | 0.126919E+10 | 0.152459E+10 | 0.947911E+09 | 0.00 | 0.947911E+09 | 0.00 | 0.00 |
March | 0.169635E+10 | 0.137059E+10 | 0.125157E+10 | 0.00 | 0.125157E+10 | 0.00 | 0.00 |
April | 0.227177E+10 | 0.843441E+09 | 0.135720E+10 | 6096655.15 | 0.135111E+10 | 0.00 | 0.00 |
May | 0.321292E+10 | 0.452937E+09 | 0.160152E+10 | 71639040.31 | 0.152988E+10 | 0.00 | 0.00 |
June | 0.357547E+10 | 0.195862E+09 | 0.165558E+10 | 0.119206E+09 | 0.153637E+10 | 0.00 | 0.00 |
July | 0.390692E+10 | 0.308379E+09 | 0.173124E+10 | 84833200.01 | 0.164640E+10 | 0.00 | 0.00 |
August | 0.325947E+10 | 0.222589E+09 | 0.153217E+10 | 14091615.29 | 0.151808E+10 | 0.00 | 0.00 |
September | 0.291690E+10 | 0.350778E+09 | 0.131537E+10 | 104057.40 | 0.131527E+10 | 0.00 | 0.00 |
October | 0.221548E+10 | 0.582325E+09 | 0.113869E+10 | 0.00 | 0.113869E+10 | 0.00 | 0.00 |
November | 0.150975E+10 | 0.106913E+10 | 0.958161E+09 | 0.00 | 0.958161E+09 | 0.00 | 0.00 |
December | 0.103640E+10 | 0.178204E+10 | 0.876992E+09 | 0.00 | 0.876992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277944E+11 | 0.107874E+11 | 0.152530E+11 | 0.295970E+09 | 0.149571E+11 | 0.00 | 0.00 |
Minimum of Months | 0.923793E+09 | 0.195862E+09 | 0.876992E+09 | 0.00 | 0.876992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390692E+10 | 0.208472E+10 | 0.173124E+10 | 0.119206E+09 | 0.164640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196193E+10 | 0.134487E+10 | 0.142326E+10 | 0.681826E+09 | 0.741432E+09 | 0.00 | 0.00 |
February | 0.223652E+10 | 0.988479E+09 | 0.148436E+10 | 0.687108E+09 | 0.797247E+09 | 0.00 | 0.00 |
March | 0.304062E+10 | 0.887428E+09 | 0.200646E+10 | 0.948563E+09 | 0.105789E+10 | 0.00 | 0.00 |
April | 0.357470E+10 | 0.597518E+09 | 0.210727E+10 | 0.940252E+09 | 0.116702E+10 | 0.00 | 0.00 |
May | 0.382792E+10 | 0.312492E+09 | 0.206002E+10 | 0.820343E+09 | 0.123967E+10 | 0.00 | 0.00 |
June | 0.383871E+10 | 0.140148E+09 | 0.196768E+10 | 0.755769E+09 | 0.121191E+10 | 0.00 | 0.00 |
July | 0.421158E+10 | 0.226022E+09 | 0.208920E+10 | 0.753407E+09 | 0.133580E+10 | 0.00 | 0.00 |
August | 0.372057E+10 | 0.160689E+09 | 0.191040E+10 | 0.638793E+09 | 0.127160E+10 | 0.00 | 0.00 |
September | 0.352329E+10 | 0.248549E+09 | 0.178233E+10 | 0.644318E+09 | 0.113802E+10 | 0.00 | 0.00 |
October | 0.310620E+10 | 0.409285E+09 | 0.169525E+10 | 0.730076E+09 | 0.965175E+09 | 0.00 | 0.00 |
November | 0.218070E+10 | 0.692968E+09 | 0.133153E+10 | 0.530932E+09 | 0.800602E+09 | 0.00 | 0.00 |
December | 0.157246E+10 | 0.115771E+10 | 0.111144E+10 | 0.392392E+09 | 0.719052E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367952E+11 | 0.716616E+10 | 0.209692E+11 | 0.852378E+10 | 0.124454E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157246E+10 | 0.140148E+09 | 0.111144E+10 | 0.392392E+09 | 0.719052E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421158E+10 | 0.134487E+10 | 0.210727E+10 | 0.948563E+09 | 0.133580E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640093E+10 | 0.214453E+10 | 0.416705E+10 | 0.270723E+10 | 0.145982E+10 | 0.00 | 0.00 |
February | 0.554697E+10 | 0.160034E+10 | 0.340490E+10 | 0.197015E+10 | 0.143476E+10 | 0.00 | 0.00 |
March | 0.480851E+10 | 0.141440E+10 | 0.289429E+10 | 0.122367E+10 | 0.167061E+10 | 0.00 | 0.00 |
April | 0.349611E+10 | 0.900256E+09 | 0.190459E+10 | 0.333987E+09 | 0.157060E+10 | 0.00 | 0.00 |
May | 0.316706E+10 | 0.448536E+09 | 0.157710E+10 | 34119654.69 | 0.154298E+10 | 0.00 | 0.00 |
June | 0.314965E+10 | 0.198254E+09 | 0.145512E+10 | 2746020.15 | 0.145237E+10 | 0.00 | 0.00 |
July | 0.363524E+10 | 0.310835E+09 | 0.160997E+10 | 14922854.05 | 0.159505E+10 | 0.00 | 0.00 |
August | 0.388044E+10 | 0.237873E+09 | 0.182726E+10 | 0.154193E+09 | 0.167307E+10 | 0.00 | 0.00 |
September | 0.477491E+10 | 0.392618E+09 | 0.226368E+10 | 0.554715E+09 | 0.170896E+10 | 0.00 | 0.00 |
October | 0.601408E+10 | 0.706850E+09 | 0.321677E+10 | 0.150920E+10 | 0.170757E+10 | 0.00 | 0.00 |
November | 0.597129E+10 | 0.116285E+10 | 0.354191E+10 | 0.197677E+10 | 0.156514E+10 | 0.00 | 0.00 |
December | 0.632449E+10 | 0.187561E+10 | 0.401587E+10 | 0.253298E+10 | 0.148289E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.571697E+11 | 0.113930E+11 | 0.318785E+11 | 0.130147E+11 | 0.188638E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314965E+10 | 0.198254E+09 | 0.145512E+10 | 2746020.15 | 0.143476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.640093E+10 | 0.214453E+10 | 0.416705E+10 | 0.270723E+10 | 0.170896E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180508E+10 | 0.142012E+10 | 0.127857E+10 | 0.551206E+09 | 0.727360E+09 | 0.00 | 0.00 |
February | 0.226949E+10 | 0.107351E+10 | 0.144409E+10 | 0.653530E+09 | 0.790558E+09 | 0.00 | 0.00 |
March | 0.313689E+10 | 0.992286E+09 | 0.199101E+10 | 0.909196E+09 | 0.108181E+10 | 0.00 | 0.00 |
April | 0.364455E+10 | 0.651956E+09 | 0.212083E+10 | 0.982009E+09 | 0.113882E+10 | 0.00 | 0.00 |
May | 0.376082E+10 | 0.357305E+09 | 0.199786E+10 | 0.769079E+09 | 0.122878E+10 | 0.00 | 0.00 |
June | 0.328308E+10 | 0.154449E+09 | 0.163819E+10 | 0.459526E+09 | 0.117867E+10 | 0.00 | 0.00 |
July | 0.388301E+10 | 0.241535E+09 | 0.189186E+10 | 0.585279E+09 | 0.130658E+10 | 0.00 | 0.00 |
August | 0.368728E+10 | 0.185169E+09 | 0.188755E+10 | 0.615148E+09 | 0.127240E+10 | 0.00 | 0.00 |
September | 0.314266E+10 | 0.261096E+09 | 0.155824E+10 | 0.459475E+09 | 0.109877E+10 | 0.00 | 0.00 |
October | 0.297109E+10 | 0.447562E+09 | 0.160183E+10 | 0.624443E+09 | 0.977392E+09 | 0.00 | 0.00 |
November | 0.215650E+10 | 0.756606E+09 | 0.127872E+10 | 0.469041E+09 | 0.809681E+09 | 0.00 | 0.00 |
December | 0.198478E+10 | 0.122143E+10 | 0.132371E+10 | 0.591819E+09 | 0.731891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357252E+11 | 0.776302E+10 | 0.200125E+11 | 0.766975E+10 | 0.123427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180508E+10 | 0.154449E+09 | 0.127857E+10 | 0.459475E+09 | 0.727360E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388301E+10 | 0.142012E+10 | 0.212083E+10 | 0.982009E+09 | 0.130658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929688E+09 | 0.201429E+10 | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.00 | 0.00 |
February | 0.126208E+10 | 0.149466E+10 | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.00 | 0.00 |
March | 0.165869E+10 | 0.138502E+10 | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.00 | 0.00 |
April | 0.223503E+10 | 0.866387E+09 | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.00 | 0.00 |
May | 0.318389E+10 | 0.468141E+09 | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.00 | 0.00 |
June | 0.355131E+10 | 0.206107E+09 | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.00 | 0.00 |
July | 0.389823E+10 | 0.310401E+09 | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.00 | 0.00 |
August | 0.327206E+10 | 0.211566E+09 | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.00 | 0.00 |
September | 0.292953E+10 | 0.334595E+09 | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.00 | 0.00 |
October | 0.222644E+10 | 0.554608E+09 | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.00 | 0.00 |
November | 0.152304E+10 | 0.100909E+10 | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.00 | 0.00 |
December | 0.105151E+10 | 0.169630E+10 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277215E+11 | 0.105512E+11 | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.929688E+09 | 0.206107E+09 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389823E+10 | 0.201429E+10 | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197217E+10 | 0.124829E+10 | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.00 | 0.00 |
February | 0.223281E+10 | 0.928349E+09 | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.00 | 0.00 |
March | 0.301600E+10 | 0.848132E+09 | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.00 | 0.00 |
April | 0.354826E+10 | 0.571638E+09 | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.00 | 0.00 |
May | 0.380710E+10 | 0.299215E+09 | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.00 | 0.00 |
June | 0.383024E+10 | 0.133888E+09 | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.00 | 0.00 |
July | 0.421118E+10 | 0.208285E+09 | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.00 | 0.00 |
August | 0.373548E+10 | 0.136296E+09 | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.00 | 0.00 |
September | 0.353912E+10 | 0.221300E+09 | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.00 | 0.00 |
October | 0.311439E+10 | 0.360320E+09 | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.00 | 0.00 |
November | 0.219134E+10 | 0.626938E+09 | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.00 | 0.00 |
December | 0.158792E+10 | 0.106726E+10 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367860E+11 | 0.664992E+10 | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158792E+10 | 0.133888E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421118E+10 | 0.124829E+10 | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.638000E+10 | 0.197155E+10 | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.00 | 0.00 |
February | 0.551744E+10 | 0.149179E+10 | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.00 | 0.00 |
March | 0.474784E+10 | 0.137569E+10 | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.00 | 0.00 |
April | 0.345638E+10 | 0.901186E+09 | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.00 | 0.00 |
May | 0.314899E+10 | 0.459276E+09 | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.00 | 0.00 |
June | 0.314233E+10 | 0.209109E+09 | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.00 | 0.00 |
July | 0.364964E+10 | 0.309355E+09 | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.00 | 0.00 |
August | 0.392003E+10 | 0.214239E+09 | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.00 | 0.00 |
September | 0.482329E+10 | 0.352303E+09 | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.00 | 0.00 |
October | 0.604667E+10 | 0.609400E+09 | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.00 | 0.00 |
November | 0.597525E+10 | 0.103101E+10 | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.00 | 0.00 |
December | 0.630516E+10 | 0.171469E+10 | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.571130E+11 | 0.106396E+11 | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314233E+10 | 0.209109E+09 | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.00 | 0.00 |
Maximum of Months | 0.638000E+10 | 0.197155E+10 | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181607E+10 | 0.133049E+10 | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.00 | 0.00 |
February | 0.227024E+10 | 0.101554E+10 | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.00 | 0.00 |
March | 0.311970E+10 | 0.953490E+09 | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.00 | 0.00 |
April | 0.362789E+10 | 0.629398E+09 | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.00 | 0.00 |
May | 0.374631E+10 | 0.344846E+09 | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.00 | 0.00 |
June | 0.327563E+10 | 0.152029E+09 | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.00 | 0.00 |
July | 0.388572E+10 | 0.225516E+09 | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.00 | 0.00 |
August | 0.370139E+10 | 0.159730E+09 | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.00 | 0.00 |
September | 0.315822E+10 | 0.233637E+09 | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.00 | 0.00 |
October | 0.298198E+10 | 0.401080E+09 | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.00 | 0.00 |
November | 0.216868E+10 | 0.690061E+09 | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.00 | 0.00 |
December | 0.200010E+10 | 0.112766E+10 | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357520E+11 | 0.726347E+10 | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181607E+10 | 0.152029E+09 | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388572E+10 | 0.133049E+10 | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.392488E+10 | -0.323420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690686073.6 | 58.98 | 0.00 | 0.00 |
February | 0.353510E+10 | -0.291125E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -623849465.5 | 58.98 | 0.00 | 0.00 |
March | 0.402947E+10 | -0.333911E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690354972.4 | 58.98 | 0.00 | 0.00 |
April | 0.353274E+10 | -0.286601E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666736455.8 | 58.97 | 0.00 | 0.00 |
May | 0.360975E+10 | -0.292129E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688451909.3 | 58.98 | 0.00 | 0.00 |
June | 0.345183E+10 | -0.278488E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666950300.4 | 58.98 | 0.00 | 0.00 |
July | 0.326590E+10 | -0.257721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688695526.8 | 58.98 | 0.00 | 0.00 |
August | 0.357410E+10 | -0.288467E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689428671.7 | 58.98 | 0.00 | 0.00 |
September | 0.336343E+10 | -0.269670E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666730631.7 | 58.98 | 0.00 | 0.00 |
October | 0.361610E+10 | -0.292889E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687208741.5 | 58.98 | 0.00 | 0.00 |
November | 0.368983E+10 | -0.302521E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664623153.6 | 58.98 | 0.00 | 0.00 |
December | 0.379219E+10 | -0.310166E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690524261.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.433853E+11 | -0.352711E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.811424E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.326590E+10 | -0.333911E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -690686073.6 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.402947E+10 | -0.257721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -623849465.5 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7151.19 | 35.94 | 274.83 | 293.50 | 1417.94 | 24.98 | 194.17 | 277.33 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2646.16 | 25.13 | 135.83 | 278.50 | 1100.78 | 20.55 | 130.83 | 252.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:49 | 1621.16 | 18.77 | 5.67 | 328.83 | 902.02 | 20.65 | 158.17 | 294.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 1253.19 | 18.20 | 0.00 | 327.00 | 715.48 | 20.31 | 99.67 | 293.50 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1071.61 | 17.72 | 0.00 | 348.17 | 602.52 | 19.84 | 59.00 | 300.00 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:19 | 1011.85 | 17.06 | 0.00 | 326.00 | 563.45 | 19.20 | 53.50 | 276.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:10 | 1134.46 | 17.92 | 0.00 | 355.33 | 633.12 | 20.07 | 94.83 | 306.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1351.48 | 18.39 | 0.00 | 343.83 | 740.72 | 20.52 | 150.33 | 305.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1630.69 | 18.59 | 0.00 | 316.50 | 872.10 | 20.74 | 187.67 | 281.17 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:09 | 2174.77 | 20.41 | 31.67 | 315.67 | 1086.95 | 21.55 | 201.17 | 289.17 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 4070.67 | 31.18 | 247.67 | 292.83 | 1225.96 | 24.34 | 235.67 | 274.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6793.53 | 36.23 | 278.67 | 280.00 | 1644.99 | 26.34 | 211.50 | 262.50 |
Annual Sum or Average | 4111.50 | 0.52 | 2458.42 | 22.28 | 974.33 | 3806.17 | 924.04 | 21.38 | 1776.50 | 3412.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1011.85 | 17.06 | 0.00 | 278.50 | 563.45 | 19.20 | 53.50 | 252.50 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7151.19 | 36.23 | 278.67 | 355.33 | 1644.99 | 26.34 | 235.67 | 306.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2252.64 | 22.67 | 102.67 | 269.00 | 1193.06 | 23.11 | 76.83 | 229.33 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:49 | 2354.86 | 21.78 | 101.33 | 260.83 | 894.26 | 20.87 | 45.67 | 227.67 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2186.11 | 19.76 | 86.00 | 322.83 | 1185.73 | 21.90 | 68.00 | 289.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2604.39 | 20.76 | 99.83 | 325.33 | 1394.15 | 21.81 | 70.67 | 291.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2385.00 | 20.10 | 103.83 | 358.50 | 1018.82 | 20.77 | 57.83 | 312.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2311.80 | 20.27 | 111.33 | 342.50 | 996.87 | 21.05 | 65.00 | 300.50 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2293.07 | 20.64 | 115.67 | 363.00 | 995.49 | 20.54 | 54.33 | 320.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:40 | 2263.76 | 20.90 | 97.17 | 346.83 | 1027.88 | 20.86 | 47.33 | 309.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 2219.18 | 21.52 | 104.17 | 312.00 | 1155.90 | 22.44 | 74.83 | 272.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2193.78 | 21.63 | 94.50 | 303.67 | 1167.88 | 22.57 | 70.33 | 269.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1745.20 | 20.53 | 84.83 | 273.50 | 900.62 | 22.08 | 64.50 | 234.00 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1892.19 | 21.39 | 87.17 | 255.83 | 780.89 | 20.76 | 46.50 | 213.67 |
Annual Sum or Average | 4111.50 | 0.53 | 2236.83 | 20.93 | 1188.50 | 3733.83 | 1063.50 | 21.53 | 741.83 | 3269.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1745.20 | 19.76 | 84.83 | 255.83 | 780.89 | 20.54 | 45.67 | 213.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2604.39 | 22.67 | 115.67 | 363.00 | 1394.15 | 23.11 | 76.83 | 320.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-09:50 | 560.12 | 15.01 | 0.00 | 249.83 | 357.07 | 17.46 | 0.00 | 160.33 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:20 | 638.85 | 15.87 | 0.00 | 251.83 | 396.17 | 18.15 | 0.00 | 185.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 765.07 | 17.08 | 0.00 | 315.17 | 464.90 | 19.25 | 0.00 | 260.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 914.83 | 17.98 | 0.00 | 332.00 | 547.77 | 20.04 | 32.17 | 297.83 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:49 | 1091.72 | 19.39 | 27.00 | 368.33 | 607.92 | 20.48 | 103.83 | 331.50 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:19 | 1164.20 | 20.82 | 66.50 | 358.00 | 640.26 | 21.67 | 143.17 | 318.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1220.56 | 19.66 | 26.17 | 375.50 | 674.24 | 21.78 | 175.33 | 340.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1097.72 | 18.40 | 0.00 | 351.67 | 624.89 | 20.51 | 97.83 | 316.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 921.79 | 17.58 | 0.00 | 314.67 | 530.64 | 19.68 | 12.50 | 267.33 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 732.26 | 16.70 | 0.00 | 295.67 | 449.48 | 18.93 | 0.00 | 232.17 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 645.17 | 16.03 | 0.00 | 258.83 | 388.42 | 18.30 | 0.00 | 184.67 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:09 | 612.07 | 15.74 | 0.00 | 245.00 | 378.35 | 18.13 | 0.00 | 168.33 |
Annual Sum or Average | 4111.50 | 0.53 | 887.00 | 17.70 | 119.67 | 3716.50 | 516.26 | 19.67 | 564.83 | 3063.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 560.12 | 15.01 | 0.00 | 245.00 | 357.07 | 17.46 | 0.00 | 160.33 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 1220.56 | 20.82 | 66.50 | 375.50 | 674.24 | 21.78 | 175.33 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:50 | 1938.72 | 21.54 | 91.50 | 271.17 | 1059.82 | 22.35 | 67.00 | 226.67 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1782.17 | 19.65 | 71.50 | 267.67 | 912.09 | 20.56 | 46.83 | 230.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2145.63 | 19.71 | 86.17 | 320.50 | 1133.72 | 21.90 | 69.17 | 288.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:00 | 2375.41 | 19.43 | 80.67 | 335.33 | 1282.00 | 20.69 | 51.83 | 301.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2141.38 | 14.62 | 0.00 | 351.83 | 1116.00 | 17.89 | 0.00 | 312.50 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:49 | 1791.32 | 14.32 | 0.00 | 334.83 | 812.03 | 17.53 | 0.33 | 291.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 2030.04 | 15.28 | 3.67 | 359.33 | 916.13 | 18.32 | 0.00 | 320.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2189.30 | 18.16 | 56.83 | 343.50 | 1139.24 | 18.71 | 5.50 | 306.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1803.26 | 19.55 | 80.83 | 315.50 | 941.52 | 20.75 | 52.00 | 279.50 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2175.28 | 21.87 | 103.00 | 301.00 | 1155.35 | 22.95 | 79.00 | 266.33 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:20 | 1697.27 | 20.12 | 83.00 | 274.00 | 898.01 | 22.26 | 69.17 | 237.83 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 1943.13 | 21.66 | 84.67 | 266.50 | 1051.90 | 23.52 | 75.50 | 232.00 |
Annual Sum or Average | 4111.50 | 0.52 | 2007.72 | 18.57 | 741.83 | 3741.17 | 1033.78 | 20.44 | 516.33 | 3294.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1697.27 | 14.32 | 0.00 | 266.50 | 812.03 | 17.53 | 0.00 | 226.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2375.41 | 21.87 | 103.00 | 359.33 | 1282.00 | 23.52 | 79.00 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7020.72 | 35.64 | 274.83 | 292.67 | 1317.60 | 22.54 | 81.67 | 274.67 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2541.44 | 22.74 | 135.00 | 278.17 | 1022.11 | 17.68 | 0.00 | 250.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1545.24 | 15.07 | 5.67 | 326.67 | 847.82 | 18.28 | 1.00 | 290.67 |
April | 357.50 | 0.53 | 0.48 | 01-APR-07:49 | 1202.47 | 14.72 | 0.00 | 325.50 | 683.34 | 18.17 | 0.00 | 289.33 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:30 | 1032.28 | 14.13 | 0.00 | 345.83 | 579.43 | 17.56 | 0.00 | 293.17 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:30 | 975.20 | 13.38 | 0.00 | 323.50 | 541.95 | 16.83 | 0.00 | 271.50 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1092.36 | 14.27 | 0.00 | 353.00 | 608.35 | 17.73 | 0.00 | 301.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1298.51 | 14.82 | 0.00 | 343.17 | 708.03 | 18.23 | 0.00 | 301.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1561.24 | 14.77 | 0.00 | 316.00 | 826.32 | 18.21 | 1.17 | 278.33 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:20 | 2078.71 | 16.85 | 31.67 | 315.50 | 1017.72 | 19.04 | 9.17 | 286.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3959.97 | 30.14 | 245.50 | 291.17 | 1144.16 | 21.87 | 71.50 | 272.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6658.42 | 36.01 | 278.50 | 278.67 | 1543.00 | 23.98 | 92.67 | 260.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2383.42 | 19.40 | 971.17 | 3789.83 | 871.60 | 18.98 | 257.17 | 3369.33 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 975.20 | 13.38 | 0.00 | 278.17 | 541.95 | 16.83 | 0.00 | 250.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7020.72 | 36.01 | 278.50 | 353.00 | 1543.00 | 23.98 | 92.67 | 301.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2198.19 | 22.22 | 102.67 | 267.17 | 1150.36 | 22.91 | 74.17 | 224.50 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 2299.04 | 21.32 | 101.00 | 259.67 | 851.39 | 20.66 | 45.67 | 224.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2126.95 | 19.26 | 86.00 | 321.00 | 1134.60 | 21.71 | 68.00 | 285.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2523.65 | 20.30 | 99.83 | 323.33 | 1341.32 | 21.64 | 70.67 | 289.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 2322.83 | 19.65 | 103.67 | 355.83 | 959.80 | 19.99 | 50.33 | 307.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2259.76 | 19.83 | 111.33 | 340.83 | 951.25 | 20.89 | 65.00 | 297.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2234.68 | 20.20 | 115.67 | 361.67 | 948.29 | 20.38 | 54.33 | 315.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2191.18 | 20.46 | 97.17 | 345.67 | 980.88 | 20.69 | 47.33 | 305.00 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-06:49 | 2155.19 | 20.90 | 102.33 | 310.83 | 1109.13 | 22.26 | 74.83 | 269.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2088.23 | 19.81 | 81.33 | 302.33 | 1118.52 | 22.25 | 66.83 | 267.00 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1693.08 | 20.04 | 84.67 | 272.00 | 843.77 | 21.05 | 54.00 | 228.67 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1846.41 | 20.90 | 87.17 | 253.83 | 746.05 | 20.52 | 37.33 | 208.83 |
Annual Sum or Average | 4111.50 | 0.53 | 2173.09 | 20.35 | 1172.83 | 3714.17 | 1015.13 | 21.21 | 708.50 | 3223.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1693.08 | 19.26 | 81.33 | 253.83 | 746.05 | 19.99 | 37.33 | 208.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2523.65 | 22.22 | 115.67 | 361.67 | 1341.32 | 22.91 | 74.83 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-09:00 | 539.83 | 11.49 | 0.00 | 246.50 | 346.48 | 15.20 | 0.00 | 153.17 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:30 | 616.37 | 12.37 | 0.00 | 249.17 | 384.23 | 15.95 | 0.00 | 177.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 738.28 | 13.72 | 0.00 | 311.50 | 450.43 | 17.24 | 0.00 | 255.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 882.43 | 14.66 | 0.00 | 331.17 | 529.97 | 18.13 | 0.00 | 292.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1052.27 | 16.02 | 26.83 | 365.83 | 591.00 | 19.27 | 26.00 | 332.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1121.14 | 17.73 | 65.00 | 355.67 | 614.19 | 19.42 | 33.50 | 314.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1171.53 | 14.92 | 0.00 | 372.33 | 647.26 | 19.59 | 26.17 | 337.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1057.19 | 14.93 | 0.00 | 349.50 | 601.48 | 18.38 | 0.00 | 311.83 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-07:19 | 888.45 | 14.07 | 0.00 | 313.67 | 511.71 | 17.48 | 0.00 | 261.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 705.27 | 13.38 | 0.00 | 293.50 | 434.87 | 16.89 | 0.00 | 225.67 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 621.65 | 12.39 | 0.00 | 255.17 | 375.58 | 15.99 | 0.00 | 175.83 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:20 | 589.39 | 12.13 | 0.00 | 240.67 | 366.19 | 15.82 | 0.00 | 160.17 |
Annual Sum or Average | 4111.50 | 0.53 | 854.37 | 14.16 | 91.83 | 3684.67 | 498.54 | 17.60 | 85.67 | 2997.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 539.83 | 11.49 | 0.00 | 240.67 | 346.48 | 15.20 | 0.00 | 153.17 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 1171.53 | 17.73 | 65.00 | 372.33 | 647.26 | 19.59 | 33.50 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1890.39 | 21.14 | 91.50 | 270.00 | 1022.18 | 22.24 | 66.67 | 221.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1726.90 | 19.23 | 71.17 | 264.17 | 870.70 | 20.44 | 47.00 | 227.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2086.75 | 19.26 | 86.00 | 318.17 | 1083.18 | 21.76 | 69.17 | 286.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:00 | 2240.06 | 18.96 | 80.67 | 332.33 | 1228.50 | 20.52 | 51.83 | 299.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2077.18 | 14.06 | 0.00 | 349.67 | 1071.20 | 17.69 | 0.00 | 308.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:00 | 1744.62 | 13.76 | 0.00 | 333.50 | 775.06 | 17.31 | 0.00 | 287.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1973.01 | 14.72 | 3.67 | 357.50 | 874.08 | 18.11 | 0.00 | 317.50 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2116.11 | 17.68 | 56.83 | 342.00 | 1091.82 | 18.53 | 5.50 | 303.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1752.36 | 19.11 | 80.83 | 313.83 | 900.93 | 20.61 | 52.00 | 275.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2117.17 | 21.47 | 103.00 | 299.50 | 1111.13 | 22.83 | 78.83 | 263.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1647.46 | 19.69 | 83.00 | 272.00 | 860.68 | 22.15 | 68.50 | 232.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:20 | 1884.13 | 20.98 | 82.00 | 263.67 | 1008.55 | 23.43 | 73.50 | 229.00 |
Annual Sum or Average | 4111.50 | 0.53 | 1944.23 | 18.08 | 738.67 | 3716.33 | 990.33 | 20.28 | 513.00 | 3252.00 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1647.46 | 13.76 | 0.00 | 263.67 | 775.06 | 17.31 | 0.00 | 221.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2240.06 | 21.47 | 103.00 | 357.50 | 1228.50 | 23.43 | 78.83 | 317.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7020.65 | 35.64 | 274.83 | 292.67 | 1317.52 | 22.54 | 81.67 | 274.67 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2541.35 | 22.74 | 135.00 | 278.17 | 1022.04 | 17.68 | 0.00 | 250.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1545.15 | 15.08 | 5.67 | 326.50 | 847.76 | 18.28 | 1.00 | 290.67 |
April | 357.50 | 0.53 | 0.48 | 01-APR-07:49 | 1202.40 | 14.72 | 0.00 | 325.50 | 683.29 | 18.17 | 0.00 | 289.17 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:30 | 1032.22 | 14.13 | 0.00 | 345.83 | 579.39 | 17.56 | 0.00 | 293.17 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:30 | 975.15 | 13.38 | 0.00 | 323.50 | 541.91 | 16.83 | 0.00 | 271.50 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1092.30 | 14.27 | 0.00 | 353.00 | 608.31 | 17.73 | 0.00 | 301.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1298.43 | 14.82 | 0.00 | 343.17 | 707.98 | 18.23 | 0.00 | 301.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1561.14 | 14.77 | 0.00 | 316.00 | 826.25 | 18.21 | 1.17 | 278.33 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:20 | 2078.60 | 16.86 | 31.67 | 315.50 | 1017.64 | 19.04 | 9.17 | 286.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3959.87 | 30.14 | 245.50 | 291.17 | 1144.07 | 21.87 | 71.50 | 272.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6658.35 | 36.01 | 278.50 | 278.67 | 1542.90 | 23.98 | 92.67 | 260.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2383.35 | 19.40 | 971.17 | 3789.67 | 871.54 | 18.98 | 257.17 | 3369.17 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 975.15 | 13.38 | 0.00 | 278.17 | 541.91 | 16.83 | 0.00 | 250.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7020.65 | 36.01 | 278.50 | 353.00 | 1542.90 | 23.98 | 92.67 | 301.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2198.16 | 22.22 | 102.67 | 267.17 | 1150.32 | 22.91 | 74.17 | 224.50 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 2299.00 | 21.32 | 101.00 | 259.67 | 851.34 | 20.66 | 45.67 | 224.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2126.91 | 19.26 | 86.00 | 321.00 | 1134.55 | 21.71 | 68.00 | 285.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2523.60 | 20.30 | 99.83 | 323.33 | 1341.26 | 21.64 | 70.67 | 289.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 2322.77 | 19.65 | 103.67 | 355.83 | 959.74 | 19.99 | 50.33 | 307.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2259.69 | 19.83 | 111.33 | 340.83 | 951.19 | 20.90 | 65.00 | 297.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2234.60 | 20.20 | 115.67 | 361.67 | 948.22 | 20.38 | 54.33 | 315.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2191.11 | 20.46 | 97.17 | 345.67 | 980.81 | 20.70 | 47.33 | 305.00 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-06:49 | 2155.12 | 20.91 | 102.33 | 310.83 | 1109.06 | 22.26 | 74.83 | 269.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2088.19 | 19.81 | 81.33 | 302.33 | 1118.46 | 22.25 | 66.83 | 267.00 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1693.04 | 20.04 | 84.67 | 272.00 | 843.72 | 21.05 | 54.00 | 228.67 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1846.37 | 20.90 | 87.17 | 253.83 | 746.00 | 20.52 | 37.33 | 208.83 |
Annual Sum or Average | 4111.50 | 0.53 | 2173.04 | 20.35 | 1172.83 | 3714.17 | 1015.07 | 21.21 | 708.50 | 3223.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1693.04 | 19.26 | 81.33 | 253.83 | 746.00 | 19.99 | 37.33 | 208.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2523.60 | 22.22 | 115.67 | 361.67 | 1341.26 | 22.91 | 74.83 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-09:00 | 539.82 | 11.50 | 0.00 | 246.50 | 346.46 | 15.20 | 0.00 | 153.17 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:30 | 616.36 | 12.37 | 0.00 | 249.17 | 384.20 | 15.96 | 0.00 | 177.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 738.25 | 13.73 | 0.00 | 311.50 | 450.40 | 17.24 | 0.00 | 255.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 882.39 | 14.67 | 0.00 | 331.17 | 529.93 | 18.14 | 0.00 | 292.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1052.22 | 16.02 | 26.83 | 365.83 | 590.96 | 19.27 | 26.00 | 332.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1121.08 | 17.73 | 65.00 | 355.67 | 614.14 | 19.42 | 33.50 | 314.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1171.47 | 14.92 | 0.00 | 372.33 | 647.21 | 19.59 | 26.17 | 337.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1057.15 | 14.93 | 0.00 | 349.50 | 601.44 | 18.38 | 0.00 | 311.83 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-07:19 | 888.41 | 14.07 | 0.00 | 313.67 | 511.67 | 17.48 | 0.00 | 261.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 705.25 | 13.38 | 0.00 | 293.50 | 434.85 | 16.89 | 0.00 | 225.67 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 621.64 | 12.40 | 0.00 | 255.17 | 375.55 | 15.99 | 0.00 | 175.83 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:20 | 589.38 | 12.14 | 0.00 | 240.67 | 366.17 | 15.82 | 0.00 | 160.17 |
Annual Sum or Average | 4111.50 | 0.53 | 854.34 | 14.16 | 91.83 | 3684.67 | 498.51 | 17.60 | 85.67 | 2997.00 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 539.82 | 11.50 | 0.00 | 240.67 | 346.46 | 15.20 | 0.00 | 153.17 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 1171.47 | 17.73 | 65.00 | 372.33 | 647.21 | 19.59 | 33.50 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1890.36 | 21.14 | 91.50 | 270.00 | 1022.14 | 22.24 | 66.67 | 221.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1726.87 | 19.23 | 71.17 | 264.17 | 870.65 | 20.44 | 47.00 | 227.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2086.71 | 19.26 | 86.00 | 318.17 | 1083.13 | 21.76 | 69.17 | 286.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:00 | 2240.01 | 18.97 | 80.67 | 332.33 | 1228.45 | 20.52 | 51.83 | 299.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2077.12 | 14.06 | 0.00 | 349.67 | 1071.14 | 17.69 | 0.00 | 308.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:00 | 1744.55 | 13.76 | 0.00 | 333.50 | 775.01 | 17.31 | 0.00 | 287.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1972.94 | 14.72 | 3.67 | 357.50 | 874.02 | 18.12 | 0.00 | 317.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2116.04 | 17.68 | 56.83 | 342.00 | 1091.75 | 18.53 | 5.50 | 303.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1752.29 | 19.11 | 80.83 | 313.83 | 900.87 | 20.61 | 52.00 | 275.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2117.13 | 21.47 | 103.00 | 299.50 | 1111.07 | 22.83 | 78.83 | 263.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1647.42 | 19.69 | 83.00 | 272.00 | 860.63 | 22.15 | 68.50 | 232.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:20 | 1884.11 | 20.98 | 82.00 | 263.67 | 1008.50 | 23.43 | 73.67 | 229.00 |
Annual Sum or Average | 4111.50 | 0.53 | 1944.18 | 18.09 | 738.67 | 3716.33 | 990.28 | 20.28 | 513.17 | 3251.83 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1647.42 | 13.76 | 0.00 | 263.67 | 775.01 | 17.31 | 0.00 | 221.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2240.01 | 21.47 | 103.00 | 357.50 | 1228.45 | 23.43 | 78.83 | 317.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249276E+09 | 6593.83 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88079493.00 | 6593.83 | 03-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188244E+09 | 6593.83 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11651581.37 | 4886.56 | 19-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45274828.83 | 6593.83 | 13-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165016E+09 | 6593.83 | 12-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.747541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249276E+09 | 6593.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 607097.27 | 3584.39 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 607097.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 607097.27 | 3584.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4972.73 | 41.44 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5077073.07 | 5634.76 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 846018.22 | 1509.52 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5928064.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5077073.07 | 5634.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4461335.18 | 3967.40 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4461335.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4461335.18 | 3967.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 875825.79 | 3287.23 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7066457.29 | 8199.62 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2963497.34 | 5776.52 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2987388.02 | 4404.03 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13893168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7066457.29 | 8199.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3989495.39 | 5426.21 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7534349.28 | 5426.21 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4345819.37 | 5426.21 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13457252.16 | 5426.21 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29326916.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13457252.16 | 5426.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7915846.72 | 8238.12 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18899272.26 | 8238.12 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5115912.35 | 8238.12 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10558046.29 | 8238.12 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42489077.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18899272.26 | 8238.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12918643.50 | 5445.41 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22413625.06 | 5445.41 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8170740.06 | 5445.41 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 59229.93 | 279.90 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19588228.82 | 5445.41 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63150467.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22413625.06 | 5445.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9345045.81 | 8603.80 | 26-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24345974.02 | 23460.41 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11135925.33 | 7862.85 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44826945.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24345974.02 | 23460.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36496937.56 | 10444.01 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38222189.01 | 10444.01 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35389035.87 | 10444.01 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2988545.28 | 7576.07 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53613336.96 | 10444.01 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53613336.96 | 10444.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54302592.86 | 6845.72 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35790607.57 | 6845.72 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27925890.28 | 6845.72 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4019179.65 | 6845.72 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81552866.73 | 6845.72 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81552866.73 | 6845.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 98560841.44 | 10464.50 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84078957.44 | 10464.50 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52186911.13 | 10464.50 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12141197.33 | 10464.50 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101687E+09 | 10464.50 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101687E+09 | 10464.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122269E+09 | 6852.70 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92065283.72 | 6852.70 | 03-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66750614.27 | 6852.70 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15546003.49 | 6852.70 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125523E+09 | 6852.70 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.422154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125523E+09 | 6852.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8544060.91 | 2095.19 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8544060.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8544060.91 | 2095.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.513338E+11 | 0.378340E+11 | 87472.93 | 02-JAN-14:00 | 59848.60 | 0.00 |
February | 0.00 | 0.00 | 0.521984E+11 | 0.389345E+11 | 85357.45 | 11-FEB-06:03 | 46475.30 | 0.00 |
March | 0.00 | 0.00 | 0.630967E+11 | 0.460747E+11 | 78573.23 | 13-MAR-12:05 | 49982.81 | 0.00 |
April | 0.00 | 0.00 | 0.715982E+11 | 0.515662E+11 | 100718.35 | 13-APR-05:02 | 57837.41 | 0.00 |
May | 0.00 | 0.00 | 0.960794E+11 | 0.645571E+11 | 134741.53 | 30-MAY-04:02 | 82260.92 | 0.00 |
June | 0.00 | 0.00 | 0.108264E+12 | 0.681796E+11 | 140794.97 | 19-JUN-04:02 | 70636.58 | 0.00 |
July | 0.00 | 0.00 | 0.113512E+12 | 0.716668E+11 | 136196.35 | 03-JUL-04:02 | 79283.69 | 0.00 |
August | 0.00 | 0.00 | 0.117990E+12 | 0.741665E+11 | 134911.36 | 18-AUG-04:02 | 80369.74 | 0.00 |
September | 0.00 | 0.00 | 0.108459E+12 | 0.686240E+11 | 136310.99 | 23-SEP-04:02 | 77882.08 | 0.00 |
October | 0.00 | 0.00 | 0.996603E+11 | 0.659649E+11 | 137445.07 | 02-OCT-04:02 | 77220.48 | 0.00 |
November | 0.00 | 0.00 | 0.787053E+11 | 0.530676E+11 | 128133.04 | 30-NOV-06:03 | 69300.62 | 0.00 |
December | 0.00 | 0.00 | 0.550377E+11 | 0.391684E+11 | 96281.23 | 11-DEC-06:13 | 52479.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101593E+13 | 0.679804E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.513338E+11 | 0.378340E+11 | 78573.23 | 46475.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117990E+12 | 0.741665E+11 | 140794.97 | 82260.92 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424156E+11 | 0.299159E+11 | 77181.09 | 02-JAN-14:00 | 50785.39 | 0.00 |
February | 0.00 | 0.00 | 0.443676E+11 | 0.319711E+11 | 66790.09 | 11-FEB-06:03 | 31573.10 | 0.00 |
March | 0.00 | 0.00 | 0.548940E+11 | 0.387986E+11 | 71203.13 | 27-MAR-15:00 | 51686.18 | 0.00 |
April | 0.00 | 0.00 | 0.637111E+11 | 0.447875E+11 | 103047.00 | 12-APR-05:03 | 57911.11 | 0.00 |
May | 0.00 | 0.00 | 0.857180E+11 | 0.556796E+11 | 121702.54 | 30-MAY-04:02 | 68445.79 | 0.00 |
June | 0.00 | 0.00 | 0.974323E+11 | 0.590347E+11 | 125786.90 | 19-JUN-04:02 | 59581.85 | 0.00 |
July | 0.00 | 0.00 | 0.102022E+12 | 0.620440E+11 | 122596.66 | 03-JUL-04:02 | 66439.73 | 0.00 |
August | 0.00 | 0.00 | 0.103323E+12 | 0.622483E+11 | 121547.42 | 18-AUG-04:02 | 67389.30 | 0.00 |
September | 0.00 | 0.00 | 0.950460E+11 | 0.576565E+11 | 123176.95 | 23-SEP-04:02 | 64091.92 | 0.00 |
October | 0.00 | 0.00 | 0.855359E+11 | 0.545254E+11 | 125018.68 | 02-OCT-04:02 | 59221.63 | 0.00 |
November | 0.00 | 0.00 | 0.661647E+11 | 0.425638E+11 | 124045.37 | 30-NOV-06:03 | 58966.90 | 0.00 |
December | 0.00 | 0.00 | 0.463289E+11 | 0.313958E+11 | 99233.41 | 09-DEC-06:03 | 53362.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.886959E+12 | 0.570621E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.424156E+11 | 0.299159E+11 | 66790.09 | 31573.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103323E+12 | 0.622483E+11 | 125786.90 | 68445.79 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.434652E+11 | 0.302877E+11 | 82937.49 | 02-JAN-14:00 | 56338.50 | 0.00 |
February | 0.00 | 0.00 | 0.463114E+11 | 0.333040E+11 | 68320.94 | 17-FEB-14:10 | 50418.02 | 0.00 |
March | 0.00 | 0.00 | 0.580723E+11 | 0.412029E+11 | 79891.64 | 27-MAR-15:00 | 60450.56 | 0.00 |
April | 0.00 | 0.00 | 0.683848E+11 | 0.487556E+11 | 122420.29 | 13-APR-05:02 | 62728.52 | 0.00 |
May | 0.00 | 0.00 | 0.919005E+11 | 0.613183E+11 | 138317.07 | 30-MAY-04:02 | 76249.20 | 0.00 |
June | 0.00 | 0.00 | 0.103947E+12 | 0.651674E+11 | 138632.19 | 08-JUN-04:02 | 77356.95 | 0.00 |
July | 0.00 | 0.00 | 0.109262E+12 | 0.689623E+11 | 139747.99 | 03-JUL-04:02 | 71796.36 | 0.00 |
August | 0.00 | 0.00 | 0.109124E+12 | 0.678450E+11 | 139384.17 | 18-AUG-04:02 | 74365.72 | 0.00 |
September | 0.00 | 0.00 | 0.100479E+12 | 0.626913E+11 | 141301.06 | 19-SEP-04:02 | 74615.30 | 0.00 |
October | 0.00 | 0.00 | 0.886371E+11 | 0.574204E+11 | 142685.61 | 02-OCT-04:02 | 65650.88 | 0.00 |
November | 0.00 | 0.00 | 0.682930E+11 | 0.441651E+11 | 127494.33 | 30-NOV-06:03 | 57317.96 | 0.00 |
December | 0.00 | 0.00 | 0.478179E+11 | 0.321842E+11 | 77257.21 | 08-DEC-15:50 | 54456.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.935695E+12 | 0.613304E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.434652E+11 | 0.302877E+11 | 68320.94 | 50418.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109262E+12 | 0.689623E+11 | 142685.61 | 77356.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1361.19 | 4647.96 | 25-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1357.88 | 4648.65 | 03-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1404.58 | 4523.43 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1259.19 | 4335.59 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1246.85 | 4156.45 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1232.47 | 3973.78 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1115.50 | 3876.30 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1235.11 | 3961.70 | 30-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1194.78 | 4113.94 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1247.92 | 4319.30 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1322.55 | 4495.29 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1310.97 | 4617.19 | 28-DEC-12:07 |
Annual Sum or Average | 0.00 | 1273.63 | ||||
Minimum of Months | 0.00 | 0.00 | 1115.50 | 3876.30 | ||
Maximum of Months | 0.00 | 0.00 | 1404.58 | 4648.65 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217273E+10 | 0.33 | 4287.21 | 02-JAN-07:03 | 1.00 |
February | 0.213165E+10 | 0.34 | 3729.12 | 21-FEB-17:00 | 0.92 |
March | 0.255887E+10 | 0.36 | 4032.54 | 27-MAR-15:30 | 0.96 |
April | 0.269957E+10 | 0.37 | 4769.35 | 13-APR-05:02 | 1.06 |
May | 0.347420E+10 | 0.42 | 10881.81 | 08-MAY-05:02 | 1.78 |
June | 0.366479E+10 | 0.44 | 10881.81 | 06-JUN-05:02 | 1.78 |
July | 0.386709E+10 | 0.44 | 10881.81 | 03-JUL-04:02 | 1.78 |
August | 0.412604E+10 | 0.46 | 10881.81 | 01-AUG-04:02 | 1.78 |
September | 0.376715E+10 | 0.45 | 10881.81 | 09-SEP-04:02 | 1.78 |
October | 0.368048E+10 | 0.42 | 10881.81 | 02-OCT-04:02 | 1.78 |
November | 0.295869E+10 | 0.38 | 7951.68 | 04-NOV-05:03 | 1.46 |
December | 0.223437E+10 | 0.33 | 4108.60 | 11-DEC-06:13 | 0.97 |
Annual Sum or Average | 0.373356E+11 | 0.39 | |||
Minimum of Months | 0.213165E+10 | 0.33 | 3729.12 | 0.92 | |
Maximum of Months | 0.412604E+10 | 0.46 | 10881.81 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169294E+10 | 0.31 | 3531.27 | 02-JAN-15:10 | 0.97 |
February | 0.170148E+10 | 0.32 | 3203.86 | 21-FEB-16:30 | 0.92 |
March | 0.211493E+10 | 0.35 | 3709.75 | 27-MAR-15:30 | 1.00 |
April | 0.227122E+10 | 0.36 | 5882.00 | 12-APR-05:03 | 1.32 |
May | 0.283870E+10 | 0.40 | 9443.58 | 08-MAY-05:02 | 1.78 |
June | 0.299858E+10 | 0.43 | 9443.58 | 05-JUN-04:02 | 1.78 |
July | 0.311919E+10 | 0.42 | 9443.58 | 01-JUL-05:02 | 1.78 |
August | 0.319021E+10 | 0.43 | 9443.58 | 01-AUG-04:02 | 1.78 |
September | 0.295294E+10 | 0.42 | 9443.58 | 18-SEP-04:02 | 1.78 |
October | 0.285700E+10 | 0.40 | 9443.58 | 02-OCT-04:02 | 1.77 |
November | 0.222516E+10 | 0.35 | 7220.82 | 30-NOV-06:03 | 1.50 |
December | 0.175974E+10 | 0.31 | 4850.85 | 09-DEC-06:03 | 1.17 |
Annual Sum or Average | 0.297221E+11 | 0.37 | |||
Minimum of Months | 0.169294E+10 | 0.31 | 3203.86 | 0.92 | |
Maximum of Months | 0.319021E+10 | 0.43 | 9443.58 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160130E+10 | 0.29 | 3379.26 | 02-JAN-15:00 | 0.86 |
February | 0.162365E+10 | 0.30 | 3065.75 | 21-FEB-16:10 | 0.81 |
March | 0.204295E+10 | 0.33 | 3763.58 | 27-MAR-15:20 | 0.91 |
April | 0.225170E+10 | 0.34 | 5904.99 | 13-APR-05:02 | 1.20 |
May | 0.283976E+10 | 0.37 | 10138.19 | 30-MAY-04:02 | 1.68 |
June | 0.300379E+10 | 0.40 | 10580.36 | 08-JUN-04:02 | 1.72 |
July | 0.315736E+10 | 0.40 | 10508.52 | 10-JUL-04:02 | 1.72 |
August | 0.314940E+10 | 0.40 | 11019.32 | 21-AUG-04:02 | 1.77 |
September | 0.288849E+10 | 0.39 | 11019.32 | 18-SEP-04:02 | 1.77 |
October | 0.268064E+10 | 0.36 | 10291.75 | 02-OCT-04:02 | 1.69 |
November | 0.207355E+10 | 0.32 | 4821.06 | 04-NOV-05:03 | 1.06 |
December | 0.167270E+10 | 0.29 | 3154.55 | 08-DEC-15:30 | 0.82 |
Annual Sum or Average | 0.289853E+11 | 0.35 | |||
Minimum of Months | 0.160130E+10 | 0.29 | 3065.75 | 0.81 | |
Maximum of Months | 0.315736E+10 | 0.40 | 11019.32 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.35 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.35 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.28 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.63 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.41 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.71 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:02 | 2.06 | 2.06 | 57.38 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.01 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.44 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.33 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.07 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.49 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.71 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.63 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.01 | 58.01 | 1361.19 | 4647.96 | 25-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.67 | 57.67 | 1357.88 | 4648.65 | 03-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.55 | 57.55 | 1404.58 | 4523.43 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.88 | 57.88 | 1259.19 | 4335.59 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.84 | 57.84 | 1246.85 | 4156.45 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.90 | 56.90 | 1232.47 | 3973.78 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.57 | 57.57 | 1115.50 | 3876.30 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.14 | 58.14 | 1235.11 | 3961.70 | 30-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.21 | 58.21 | 1194.78 | 4113.94 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.86 | 56.86 | 1247.92 | 4319.30 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.31 | 57.31 | 1322.55 | 4495.29 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.76 | 57.76 | 1310.97 | 4617.19 | 28-DEC-12:07 |
Annual Sum or Average | 0.00 | 1273.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.86 | 56.86 | 1115.50 | 3876.30 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 1404.58 | 4648.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148493E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148073E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179087E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.201734E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.273871E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.306607E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.328150E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.339402E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.309333E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.283078E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.219845E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156597E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.289427E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148073E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.339402E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120396E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124695E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153233E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177700E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.240589E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.271298E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289318E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291006E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266073E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.239215E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.181597E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.130020E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.248514E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120396E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291006E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.126246E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131842E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.162774E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.190019E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.256937E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.288302E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.309009E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.306095E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.279855E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.246042E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.186673E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.137154E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.262095E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.126246E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.309009E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.217273E+10 | 0.513338E+11 | 0.249281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213165E+10 | 0.521984E+11 | 98224998.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255887E+10 | 0.630967E+11 | 0.189090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269957E+10 | 0.715982E+11 | 11651581.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347420E+10 | 0.960794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.366479E+10 | 0.108264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386709E+10 | 0.113512E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.412604E+10 | 0.117990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.376715E+10 | 0.108459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368048E+10 | 0.996603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295869E+10 | 0.787053E+11 | 45274828.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223437E+10 | 0.550377E+11 | 0.165016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373356E+11 | 0.101593E+13 | 0.758538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213165E+10 | 0.513338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412604E+10 | 0.117990E+12 | 0.249281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169294E+10 | 0.424156E+11 | 25699811.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170148E+10 | 0.443676E+11 | 55913703.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211493E+10 | 0.548940E+11 | 20595969.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227122E+10 | 0.637111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283870E+10 | 0.857180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299858E+10 | 0.974323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311919E+10 | 0.102022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319021E+10 | 0.103323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295294E+10 | 0.950460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285700E+10 | 0.855359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222516E+10 | 0.661647E+11 | 59229.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175974E+10 | 0.463289E+11 | 46590915.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297221E+11 | 0.886959E+12 | 0.148860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169294E+10 | 0.424156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319021E+10 | 0.103323E+12 | 55913703.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160130E+10 | 0.434652E+11 | 0.320975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162365E+10 | 0.463114E+11 | 0.283047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204295E+10 | 0.580723E+11 | 0.182252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225170E+10 | 0.683848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283976E+10 | 0.919005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300379E+10 | 0.103947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.315736E+10 | 0.109262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314940E+10 | 0.109124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288849E+10 | 0.100479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268064E+10 | 0.886371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207355E+10 | 0.682930E+11 | 34694925.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167270E+10 | 0.478179E+11 | 0.373512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289853E+11 | 0.935695E+12 | 0.119448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160130E+10 | 0.434652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315736E+10 | 0.109262E+12 | 0.373512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.217273E+10 | 0.00 | 0.00 | 0.00 | 0.124273E+11 | 0.249281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213165E+10 | 0.00 | 0.00 | 0.00 | 0.125774E+11 | 98224998.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255887E+10 | 0.00 | 0.00 | 0.00 | 0.151607E+11 | 0.189090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269957E+10 | 0.00 | 0.00 | 0.00 | 0.174621E+11 | 11651581.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347420E+10 | 0.00 | 0.00 | 0.00 | 0.239129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.366479E+10 | 0.00 | 0.00 | 0.00 | 0.269959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386709E+10 | 0.00 | 0.00 | 0.00 | 0.289479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.412604E+10 | 0.00 | 0.00 | 0.00 | 0.298141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.376715E+10 | 0.00 | 0.00 | 0.00 | 0.271662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368048E+10 | 0.00 | 0.00 | 0.00 | 0.246273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295869E+10 | 0.00 | 0.00 | 0.00 | 0.189805E+11 | 45274828.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223437E+10 | 0.00 | 0.00 | 0.00 | 0.132603E+11 | 0.165016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373356E+11 | 0.00 | 0.00 | 0.00 | 0.251333E+12 | 0.758538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213165E+10 | 0.00 | 0.00 | 0.00 | 0.124273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.412604E+10 | 0.00 | 0.00 | 0.00 | 0.298141E+11 | 0.249281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169294E+10 | 0.00 | 0.00 | 0.00 | 0.103209E+11 | 25699811.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170148E+10 | 0.00 | 0.00 | 0.00 | 0.107121E+11 | 55913703.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211493E+10 | 0.00 | 0.00 | 0.00 | 0.131878E+11 | 20595969.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227122E+10 | 0.00 | 0.00 | 0.00 | 0.154988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283870E+10 | 0.00 | 0.00 | 0.00 | 0.212202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299858E+10 | 0.00 | 0.00 | 0.00 | 0.241313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311919E+10 | 0.00 | 0.00 | 0.00 | 0.258126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319021E+10 | 0.00 | 0.00 | 0.00 | 0.259104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295294E+10 | 0.00 | 0.00 | 0.00 | 0.236544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285700E+10 | 0.00 | 0.00 | 0.00 | 0.210645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222516E+10 | 0.00 | 0.00 | 0.00 | 0.159344E+11 | 59229.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175974E+10 | 0.00 | 0.00 | 0.00 | 0.111957E+11 | 46590915.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297221E+11 | 0.00 | 0.00 | 0.00 | 0.218643E+12 | 0.148860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169294E+10 | 0.00 | 0.00 | 0.00 | 0.103209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319021E+10 | 0.00 | 0.00 | 0.00 | 0.259104E+11 | 55913703.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.160130E+10 | 0.00 | 0.00 | 0.00 | 0.107023E+11 | 0.320975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162365E+10 | 0.00 | 0.00 | 0.00 | 0.112860E+11 | 0.274503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204295E+10 | 0.00 | 0.00 | 0.00 | 0.140522E+11 | 0.182252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225170E+10 | 0.00 | 0.00 | 0.00 | 0.167502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283976E+10 | 0.00 | 0.00 | 0.00 | 0.228539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300379E+10 | 0.00 | 0.00 | 0.00 | 0.258264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.315736E+10 | 0.00 | 0.00 | 0.00 | 0.277435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314940E+10 | 0.00 | 0.00 | 0.00 | 0.274601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288849E+10 | 0.00 | 0.00 | 0.00 | 0.250971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268064E+10 | 0.00 | 0.00 | 0.00 | 0.219236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207355E+10 | 0.00 | 0.00 | 0.00 | 0.165590E+11 | 34694925.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167270E+10 | 0.00 | 0.00 | 0.00 | 0.116692E+11 | 0.373512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289853E+11 | 0.00 | 0.00 | 0.00 | 0.231924E+12 | 0.118594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160130E+10 | 0.00 | 0.00 | 0.00 | 0.107023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315736E+10 | 0.00 | 0.00 | 0.00 | 0.277435E+11 | 0.373512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302773E+09 | 0.317040E+10 | 0.00 | 19920561.82 | 0.395312E+09 | 0.00 | 0.260965E+10 | 0.00 | 0.37 |
February | 0.175953E+09 | 0.365499E+10 | 0.00 | 12981558.15 | 0.351876E+09 | 0.00 | 0.132125E+10 | 0.00 | 0.36 |
March | 0.159459E+09 | 0.492326E+10 | 0.00 | 16095044.92 | 0.493221E+09 | 0.00 | 0.203069E+10 | 0.00 | 0.38 |
April | 23427027.40 | 0.658806E+10 | 0.00 | 4259845.66 | 0.103446E+10 | 0.00 | 0.343906E+09 | 0.00 | 0.36 |
May | 38075.38 | 0.116170E+11 | 0.00 | 2010.25 | 0.177199E+10 | 0.00 | 43286.62 | 0.00 | 0.34 |
June | 0.00 | 0.155197E+11 | 0.00 | 0.00 | 0.217254E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.156304E+11 | 0.00 | 0.00 | 0.352182E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.168431E+11 | 0.00 | 0.00 | 0.247938E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.144110E+11 | 0.00 | 0.00 | 0.303955E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.117604E+11 | 0.00 | 0.00 | 0.224247E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 0.135394E+09 | 0.874999E+10 | 0.00 | 4640954.58 | 0.885227E+09 | 0.00 | 0.279741E+09 | 0.00 | 0.34 |
December | 0.159682E+09 | 0.363875E+10 | 0.00 | 18219728.07 | 0.853939E+09 | 0.00 | 0.231632E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.956725E+09 | 0.116507E+12 | 0.00 | 76119703.44 | 0.192418E+11 | 0.00 | 0.890159E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.317040E+10 | 0.00 | 0.00 | 0.351876E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.302773E+09 | 0.168431E+11 | 0.00 | 19920561.82 | 0.352182E+10 | 0.00 | 0.260965E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106695E+10 | 0.212871E+10 | 0.00 | 5048126.68 | 0.102476E+10 | 0.00 | 0.104964E+10 | 0.00 | 0.30 |
February | 0.567968E+09 | 0.253065E+10 | 0.00 | 4933185.07 | 0.976778E+09 | 0.00 | 0.618182E+09 | 0.00 | 0.30 |
March | 0.634282E+09 | 0.370052E+10 | 0.00 | 5142354.89 | 0.106192E+10 | 0.00 | 0.986672E+09 | 0.00 | 0.31 |
April | 39268938.33 | 0.536052E+10 | 0.00 | 2371067.77 | 0.137101E+10 | 0.00 | 0.243935E+09 | 0.00 | 0.31 |
May | 11362.26 | 0.103125E+11 | 0.00 | 23782.40 | 0.195123E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.141064E+11 | 0.00 | 0.00 | 0.252933E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.145570E+11 | 0.00 | 0.00 | 0.364709E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.154875E+11 | 0.00 | 0.00 | 0.282467E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.133423E+11 | 0.00 | 0.00 | 0.304754E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 36901.88 | 0.106213E+11 | 0.00 | 40772.10 | 0.222089E+10 | 0.00 | 41066.88 | 0.00 | 0.31 |
November | 0.204661E+09 | 0.758799E+10 | 0.00 | 1266184.08 | 0.119026E+10 | 0.00 | 82015340.78 | 0.00 | 0.30 |
December | 0.705725E+09 | 0.246336E+10 | 0.00 | 6006924.65 | 0.164575E+10 | 0.00 | 0.108203E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.321890E+10 | 0.102199E+12 | 0.00 | 24832397.62 | 0.234912E+11 | 0.00 | 0.406252E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.212871E+10 | 0.00 | 0.00 | 0.976778E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.106695E+10 | 0.154875E+11 | 0.00 | 6006924.65 | 0.364709E+10 | 0.00 | 0.108203E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116179E+10 | 0.147905E+10 | 0.00 | 2640548.55 | 0.180808E+10 | 270182.09 | 0.624622E+09 | 0.00 | 0.30 |
February | 0.593293E+09 | 0.202254E+10 | 0.00 | 3440199.88 | 0.149223E+10 | 855540.44 | 0.398142E+09 | 0.00 | 0.29 |
March | 0.802386E+09 | 0.328022E+10 | 0.00 | 3672607.81 | 0.145498E+10 | 0.00 | 0.653467E+09 | 0.00 | 0.31 |
April | 44658766.01 | 0.483046E+10 | 0.00 | 2063161.33 | 0.167460E+10 | 0.00 | 0.201088E+09 | 0.00 | 0.31 |
May | 0.00 | 0.977700E+10 | 0.00 | 0.00 | 0.206331E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.135690E+11 | 0.00 | 0.00 | 0.256515E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.139613E+11 | 0.00 | 0.00 | 0.363876E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.148679E+11 | 0.00 | 0.00 | 0.290571E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.128328E+11 | 0.00 | 0.00 | 0.311018E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 628965.71 | 0.991256E+10 | 0.00 | 39542.90 | 0.258274E+10 | 0.00 | 163093.56 | 0.00 | 0.30 |
November | 0.190204E+09 | 0.673737E+10 | 0.00 | 666896.09 | 0.197141E+10 | 0.00 | 39785737.53 | 0.00 | 0.29 |
December | 0.888284E+09 | 0.190880E+10 | 0.00 | 3171425.31 | 0.225916E+10 | 114678.16 | 0.553772E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.368125E+10 | 0.951789E+11 | 0.00 | 15694381.87 | 0.275263E+11 | 1240400.69 | 0.247104E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.147905E+10 | 0.00 | 0.00 | 0.145498E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.116179E+10 | 0.148679E+11 | 0.00 | 3672607.81 | 0.363876E+10 | 855540.44 | 0.653467E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316460E+09 | 0.361526E+09 | 9243.65 | 228261.02 | 0.366857E+09 | 11584816.77 | 43630379.32 | 100.70 | 0.30 |
February | 0.132689E+09 | 0.561318E+09 | 58657.09 | 670124.95 | 0.273630E+09 | 19366255.67 | 60316554.44 | 3726.66 | 0.32 |
March | 0.217365E+09 | 0.870027E+09 | 0.00 | 567902.36 | 0.287544E+09 | 12977884.69 | 73720917.74 | 0.00 | 0.34 |
April | 11417432.55 | 0.137593E+10 | 0.00 | 454338.55 | 0.308458E+09 | 0.00 | 43855937.78 | 0.00 | 0.37 |
May | 0.00 | 0.312374E+10 | 0.00 | 0.00 | 0.328942E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.465387E+10 | 0.00 | 0.00 | 0.405903E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.501032E+10 | 0.00 | 0.00 | 0.541856E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.485551E+10 | 0.00 | 0.00 | 0.430308E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.404542E+10 | 0.00 | 0.00 | 0.536966E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 132609.75 | 0.273418E+10 | 0.00 | 3239.80 | 0.506891E+09 | 0.00 | 15444.17 | 0.00 | 0.37 |
November | 39281558.36 | 0.177660E+10 | 0.00 | 155364.45 | 0.355819E+09 | 1528901.08 | 8640513.91 | 0.00 | 0.33 |
December | 0.235286E+09 | 0.509655E+09 | 221580.99 | 307550.52 | 0.440759E+09 | 15455341.06 | 48965526.08 | 5595.28 | 0.30 |
Annual Sum or Average | 0.952631E+09 | 0.298781E+11 | 289481.73 | 2386781.65 | 0.478393E+10 | 60913199.26 | 0.279145E+09 | 9422.64 | 0.38 |
Minimum of Months | 0.00 | 0.361526E+09 | 0.00 | 0.00 | 0.273630E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.316460E+09 | 0.501032E+10 | 221580.99 | 670124.95 | 0.541856E+09 | 19366255.67 | 73720917.74 | 5595.28 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184365E+09 | 0.382943E+09 | 47908.96 | 642156.71 | 0.263987E+09 | 5847498.43 | 0.132659E+09 | 360.75 | 0.42 |
February | 0.113894E+09 | 0.529245E+09 | 50591.00 | 842251.37 | 0.223883E+09 | 9043618.32 | 67881804.25 | 2702.22 | 0.46 |
March | 91557603.40 | 0.841393E+09 | 0.00 | 1235191.34 | 0.227995E+09 | 8194807.53 | 0.201259E+09 | 0.00 | 0.51 |
April | 8473622.76 | 0.138495E+10 | 0.00 | 518054.29 | 0.244273E+09 | 0.00 | 47920349.54 | 0.00 | 0.56 |
May | 0.00 | 0.266058E+10 | 0.00 | 0.00 | 0.269750E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.378267E+10 | 0.00 | 0.00 | 0.324456E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.413384E+10 | 0.00 | 0.00 | 0.423997E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.395829E+10 | 0.00 | 0.00 | 0.423167E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.348816E+10 | 0.00 | 0.00 | 0.418782E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 113285.92 | 0.247673E+10 | 0.00 | 2081.32 | 0.405554E+09 | 0.00 | 10181.94 | 0.00 | 0.51 |
November | 32751888.22 | 0.151252E+10 | 0.00 | 172372.12 | 0.310958E+09 | 292979.27 | 8637321.05 | 0.00 | 0.45 |
December | 0.172069E+09 | 0.440995E+09 | 262695.45 | 354120.76 | 0.390342E+09 | 11944853.63 | 71221117.39 | 8365.70 | 0.41 |
Annual Sum or Average | 0.603225E+09 | 0.255923E+11 | 361195.41 | 3766227.91 | 0.392714E+10 | 35323757.18 | 0.529589E+09 | 11428.67 | 0.52 |
Minimum of Months | 0.00 | 0.382943E+09 | 0.00 | 0.00 | 0.223883E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.184365E+09 | 0.413384E+10 | 262695.45 | 1235191.34 | 0.423997E+09 | 11944853.63 | 0.201259E+09 | 8365.70 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152658E+09 | 0.947385E+09 | 0.00 | 3977823.01 | 0.195029E+09 | 4022447.36 | 0.518294E+09 | 0.00 | 0.50 |
February | 87306847.16 | 0.106682E+10 | 0.00 | 2711640.14 | 0.165876E+09 | 12245328.60 | 0.249211E+09 | 0.00 | 0.49 |
March | 0.132454E+09 | 0.130154E+10 | 0.00 | 2496363.23 | 0.196463E+09 | 6901222.61 | 0.311152E+09 | 0.00 | 0.47 |
April | 11085025.14 | 0.166606E+10 | 0.00 | 631043.54 | 0.279097E+09 | 0.00 | 58363256.09 | 0.00 | 0.42 |
May | 0.00 | 0.307758E+10 | 0.00 | 0.00 | 0.344304E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.437501E+10 | 0.00 | 0.00 | 0.434497E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.482780E+10 | 0.00 | 0.00 | 0.573417E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.518891E+10 | 0.00 | 0.00 | 0.415302E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.510610E+10 | 0.00 | 0.00 | 0.430556E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 132743.25 | 0.427812E+10 | 0.00 | 3942.89 | 0.304481E+09 | 0.00 | 18647.71 | 0.00 | 0.52 |
November | 23999260.15 | 0.301093E+10 | 0.00 | 795209.64 | 0.193560E+09 | 327960.18 | 42785108.24 | 0.00 | 0.50 |
December | 0.125024E+09 | 0.131076E+10 | 67925.97 | 2906195.97 | 0.230861E+09 | 8106829.29 | 0.396788E+09 | 436.61 | 0.50 |
Annual Sum or Average | 0.532660E+09 | 0.361570E+11 | 67925.97 | 13522218.42 | 0.376344E+10 | 31603788.03 | 0.157661E+10 | 436.61 | 0.48 |
Minimum of Months | 0.00 | 0.947385E+09 | 0.00 | 0.00 | 0.165876E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.152658E+09 | 0.518891E+10 | 67925.97 | 3977823.01 | 0.573417E+09 | 12245328.60 | 0.518294E+09 | 436.61 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255786E+09 | 0.295981E+09 | 191485.42 | 698211.64 | 0.388849E+09 | 12360407.89 | 0.125054E+09 | 1727.43 | 0.47 |
February | 0.112581E+09 | 0.458271E+09 | 102396.51 | 961756.22 | 0.320961E+09 | 19525171.03 | 97966860.42 | 4197.93 | 0.49 |
March | 0.178095E+09 | 0.783204E+09 | 0.00 | 1282300.51 | 0.302821E+09 | 12688485.28 | 0.158278E+09 | 0.00 | 0.55 |
April | 13151655.27 | 0.130049E+10 | 0.00 | 475646.79 | 0.329951E+09 | 0.00 | 50314325.79 | 0.00 | 0.57 |
May | 0.00 | 0.254044E+10 | 0.00 | 0.00 | 0.394465E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.342902E+10 | 0.00 | 0.00 | 0.476966E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.384678E+10 | 0.00 | 0.00 | 0.593209E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.387372E+10 | 0.00 | 0.00 | 0.548347E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.317445E+10 | 0.00 | 0.00 | 0.595911E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 128548.66 | 0.225838E+10 | 0.00 | 2245.79 | 0.575713E+09 | 0.00 | 11669.66 | 0.00 | 0.51 |
November | 35797796.96 | 0.141765E+10 | 0.00 | 167834.58 | 0.463264E+09 | 1725645.31 | 12656789.57 | 0.00 | 0.47 |
December | 0.200898E+09 | 0.458740E+09 | 225134.49 | 569467.61 | 0.456169E+09 | 15336400.02 | 87795322.00 | 9888.55 | 0.47 |
Annual Sum or Average | 0.796438E+09 | 0.238371E+11 | 519016.42 | 4157463.14 | 0.544662E+10 | 61636109.53 | 0.532076E+09 | 15813.91 | 0.54 |
Minimum of Months | 0.00 | 0.295981E+09 | 0.00 | 0.00 | 0.302821E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.255786E+09 | 0.387372E+10 | 225134.49 | 1282300.51 | 0.595911E+09 | 19525171.03 | 0.158278E+09 | 9888.55 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.368407E+09 | 0.408573E+09 | 0.00 | 406924.30 | 0.204976E+09 | 0.00 | 68499369.13 | 0.00 | 0.28 |
February | 0.176062E+09 | 0.531115E+09 | 0.00 | 657748.57 | 0.170599E+09 | 326291.84 | 61375143.33 | 0.00 | 0.28 |
March | 0.255147E+09 | 0.743256E+09 | 0.00 | 439337.44 | 0.215430E+09 | 0.00 | 60180800.25 | 0.00 | 0.29 |
April | 12719882.93 | 0.116939E+10 | 0.00 | 398823.34 | 0.274173E+09 | 0.00 | 41955106.86 | 0.00 | 0.31 |
May | 17621.89 | 0.250204E+10 | 0.00 | 0.00 | 0.414509E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.368647E+10 | 0.00 | 0.00 | 0.546769E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.404284E+10 | 0.00 | 0.00 | 0.779138E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.405136E+10 | 0.00 | 0.00 | 0.557974E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.341438E+10 | 0.00 | 0.00 | 0.686780E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.241099E+10 | 0.00 | 0.00 | 0.544305E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 52167443.40 | 0.162454E+10 | 0.00 | 352169.63 | 0.233741E+09 | 0.00 | 15236132.49 | 0.00 | 0.29 |
December | 0.269267E+09 | 0.547817E+09 | 0.00 | 609370.50 | 0.295935E+09 | 0.00 | 94347091.12 | 0.00 | 0.28 |
Annual Sum or Average | 0.113379E+10 | 0.251328E+11 | 0.00 | 2864373.79 | 0.492433E+10 | 326291.84 | 0.341594E+09 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.408573E+09 | 0.00 | 0.00 | 0.170599E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.368407E+09 | 0.405136E+10 | 0.00 | 657748.57 | 0.779138E+09 | 326291.84 | 94347091.12 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178509E+09 | 0.419928E+09 | 0.00 | 1288677.50 | 0.102074E+09 | 0.00 | 0.185158E+09 | 0.00 | 0.38 |
February | 98529939.13 | 0.507036E+09 | 0.00 | 1258627.09 | 94699629.86 | 239751.62 | 0.106795E+09 | 0.00 | 0.39 |
March | 89935614.47 | 0.774104E+09 | 0.00 | 1552724.63 | 96600004.73 | 0.00 | 0.213793E+09 | 0.00 | 0.43 |
April | 7456686.22 | 0.121621E+10 | 0.00 | 552681.47 | 0.155672E+09 | 0.00 | 50757344.73 | 0.00 | 0.46 |
May | 13393.00 | 0.221405E+10 | 0.00 | 0.00 | 0.254866E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.314596E+10 | 0.00 | 0.00 | 0.303680E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.354571E+10 | 0.00 | 0.00 | 0.402909E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.346155E+10 | 0.00 | 0.00 | 0.317927E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.305220E+10 | 0.00 | 0.00 | 0.391345E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.217733E+10 | 0.00 | 0.00 | 0.361653E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 33299924.83 | 0.135402E+10 | 0.00 | 463694.21 | 0.169282E+09 | 0.00 | 22910311.07 | 0.00 | 0.39 |
December | 0.148238E+09 | 0.474681E+09 | 0.00 | 881844.38 | 0.216147E+09 | 0.00 | 0.139426E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.555983E+09 | 0.223428E+11 | 0.00 | 5998249.28 | 0.286686E+10 | 239751.62 | 0.718840E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.419928E+09 | 0.00 | 0.00 | 94699629.86 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.178509E+09 | 0.354571E+10 | 0.00 | 1552724.63 | 0.402909E+09 | 239751.62 | 0.213793E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194162E+09 | 0.935626E+09 | 10578.79 | 3249697.70 | 85348878.59 | 61128358.16 | 0.379321E+09 | 437.20 | 0.45 |
February | 0.121320E+09 | 0.102674E+10 | 25446.24 | 3046580.50 | 87310478.94 | 26223994.42 | 0.196986E+09 | 73.78 | 0.45 |
March | 0.185171E+09 | 0.124179E+10 | 0.00 | 1634061.20 | 0.136266E+09 | 61796348.74 | 0.149629E+09 | 0.00 | 0.41 |
April | 15077335.44 | 0.160922E+10 | 0.00 | 431176.47 | 0.264461E+09 | 1711006.89 | 42331171.13 | 0.00 | 0.38 |
May | 17623.42 | 0.294031E+10 | 0.00 | 0.00 | 0.429208E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.420294E+10 | 0.00 | 0.00 | 0.539115E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.473704E+10 | 0.00 | 0.00 | 0.759076E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.530865E+10 | 0.00 | 0.00 | 0.452967E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.502062E+10 | 0.00 | 0.00 | 0.479054E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.426125E+10 | 0.00 | 0.00 | 0.287259E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 26467708.69 | 0.290189E+10 | 0.00 | 1260428.05 | 0.150234E+09 | 13090671.77 | 54137341.10 | 0.00 | 0.48 |
December | 0.157968E+09 | 0.129659E+10 | 855386.82 | 2151564.65 | 0.133857E+09 | 48580853.21 | 0.303847E+09 | 6842.22 | 0.44 |
Annual Sum or Average | 0.700185E+09 | 0.354827E+11 | 891411.85 | 11773508.57 | 0.380416E+10 | 0.212531E+09 | 0.112625E+10 | 7353.20 | 0.45 |
Minimum of Months | 0.00 | 0.935626E+09 | 0.00 | 0.00 | 85348878.59 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.194162E+09 | 0.530865E+10 | 855386.82 | 3249697.70 | 0.759076E+09 | 61796348.74 | 0.379321E+09 | 6842.22 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241745E+09 | 0.365106E+09 | 0.00 | 938764.95 | 0.140303E+09 | 0.00 | 0.144834E+09 | 0.00 | 0.38 |
February | 0.123976E+09 | 0.492345E+09 | 0.00 | 1099605.19 | 0.107186E+09 | 253745.63 | 90431054.72 | 0.00 | 0.39 |
March | 0.166789E+09 | 0.757064E+09 | 0.00 | 1200457.33 | 0.118964E+09 | 0.00 | 0.131055E+09 | 0.00 | 0.44 |
April | 9285762.71 | 0.123385E+10 | 0.00 | 475471.42 | 0.152701E+09 | 0.00 | 46624193.43 | 0.00 | 0.46 |
May | 14174.73 | 0.219226E+10 | 0.00 | 0.00 | 0.271244E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.282520E+10 | 0.00 | 0.00 | 0.394234E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.331996E+10 | 0.00 | 0.00 | 0.490008E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.344562E+10 | 0.00 | 0.00 | 0.342698E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.285129E+10 | 0.00 | 0.00 | 0.427352E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.211175E+10 | 0.00 | 0.00 | 0.354174E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 40700819.50 | 0.135322E+10 | 0.00 | 352883.75 | 0.174815E+09 | 0.00 | 16350754.55 | 0.00 | 0.39 |
December | 0.181587E+09 | 0.516719E+09 | 0.00 | 892311.35 | 0.215816E+09 | 0.00 | 0.132568E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.764098E+09 | 0.214644E+11 | 0.00 | 4959493.99 | 0.318950E+10 | 253745.63 | 0.561862E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.365106E+09 | 0.00 | 0.00 | 0.107186E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.241745E+09 | 0.344562E+10 | 0.00 | 1200457.33 | 0.490008E+09 | 253745.63 | 0.144834E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.373347E+09 | 0.471545E+09 | 0.00 | 295386.14 | 0.226843E+09 | 1059955.40 | 58409830.45 | 0.00 | 0.30 |
February | 0.177288E+09 | 0.645052E+09 | 0.00 | 716444.77 | 0.192839E+09 | 7485589.77 | 62806078.39 | 0.00 | 0.32 |
March | 0.259524E+09 | 0.990267E+09 | 0.00 | 529708.19 | 0.185287E+09 | 810859.36 | 69994539.37 | 0.00 | 0.34 |
April | 16450067.46 | 0.150593E+10 | 0.00 | 435066.17 | 0.255054E+09 | 0.00 | 44658371.41 | 0.00 | 0.37 |
May | 3054.62 | 0.327936E+10 | 0.00 | 4415.51 | 0.342707E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.484475E+10 | 0.00 | 0.00 | 0.436739E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.515858E+10 | 0.00 | 0.00 | 0.659292E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.504326E+10 | 0.00 | 0.00 | 0.469681E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.418193E+10 | 0.00 | 0.00 | 0.570184E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 7772.56 | 0.290836E+10 | 0.00 | 3334.28 | 0.451345E+09 | 0.00 | 5000.68 | 0.00 | 0.37 |
November | 51226793.63 | 0.192947E+10 | 0.00 | 194975.64 | 0.237814E+09 | 0.00 | 9484408.46 | 0.00 | 0.33 |
December | 0.291808E+09 | 0.613354E+09 | 0.00 | 444054.49 | 0.326954E+09 | 790486.00 | 68915786.38 | 0.00 | 0.30 |
Annual Sum or Average | 0.116965E+10 | 0.315719E+11 | 0.00 | 2623385.19 | 0.435474E+10 | 10146890.54 | 0.314274E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.471545E+09 | 0.00 | 0.00 | 0.185287E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.373347E+09 | 0.515858E+10 | 0.00 | 716444.77 | 0.659292E+09 | 7485589.77 | 69994539.37 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216907E+09 | 0.414653E+09 | 0.00 | 836592.07 | 0.196272E+09 | 907188.64 | 0.172959E+09 | 0.00 | 0.42 |
February | 0.143609E+09 | 0.558832E+09 | 0.00 | 1011810.94 | 0.177613E+09 | 1225940.02 | 82704253.31 | 0.00 | 0.46 |
March | 0.114417E+09 | 0.901192E+09 | 0.00 | 1370714.60 | 0.154137E+09 | 1306573.18 | 0.237368E+09 | 0.00 | 0.51 |
April | 12420711.20 | 0.146032E+10 | 0.00 | 503941.01 | 0.200107E+09 | 0.00 | 51126130.40 | 0.00 | 0.55 |
May | 2619.05 | 0.276887E+10 | 0.00 | 3421.79 | 0.261522E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.390561E+10 | 0.00 | 0.00 | 0.331113E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.428460E+10 | 0.00 | 0.00 | 0.448666E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.414042E+10 | 0.00 | 0.00 | 0.370592E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.357540E+10 | 0.00 | 0.00 | 0.416006E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 6664.24 | 0.254510E+10 | 0.00 | 1745.57 | 0.376369E+09 | 0.00 | 5400.88 | 0.00 | 0.51 |
November | 38462447.71 | 0.158241E+10 | 0.00 | 253621.37 | 0.218770E+09 | 0.00 | 15228471.11 | 0.00 | 0.45 |
December | 0.213057E+09 | 0.493509E+09 | 0.00 | 468678.76 | 0.317774E+09 | 1388950.50 | 97568413.61 | 0.00 | 0.41 |
Annual Sum or Average | 0.738882E+09 | 0.266309E+11 | 0.00 | 4450526.12 | 0.346894E+10 | 4828652.34 | 0.656960E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.414653E+09 | 0.00 | 0.00 | 0.154137E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.216907E+09 | 0.428460E+10 | 0.00 | 1370714.60 | 0.448666E+09 | 1388950.50 | 0.237368E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187985E+09 | 0.105293E+10 | 0.00 | 4236254.38 | 92823510.39 | 281397.11 | 0.580991E+09 | 0.00 | 0.52 |
February | 0.123707E+09 | 0.119173E+10 | 0.00 | 3038902.17 | 95743559.28 | 2228863.37 | 0.255402E+09 | 0.00 | 0.50 |
March | 0.157033E+09 | 0.143938E+10 | 0.00 | 2550132.48 | 0.127244E+09 | 162489.89 | 0.317702E+09 | 0.00 | 0.48 |
April | 15793701.81 | 0.183594E+10 | 0.00 | 593832.72 | 0.228180E+09 | 0.00 | 58471465.18 | 0.00 | 0.43 |
May | 3057.87 | 0.325418E+10 | 0.00 | 4493.56 | 0.343745E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.455678E+10 | 0.00 | 0.00 | 0.465898E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.499565E+10 | 0.00 | 0.00 | 0.670549E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.543319E+10 | 0.00 | 0.00 | 0.437328E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.535337E+10 | 0.00 | 0.00 | 0.429939E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 7780.82 | 0.453075E+10 | 0.00 | 4480.14 | 0.265744E+09 | 0.00 | 5218.69 | 0.00 | 0.53 |
November | 30137845.64 | 0.315951E+10 | 0.00 | 975760.71 | 0.126045E+09 | 0.00 | 52022269.37 | 0.00 | 0.51 |
December | 0.156415E+09 | 0.141182E+10 | 0.00 | 3269152.76 | 0.172346E+09 | 136852.90 | 0.477222E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.671082E+09 | 0.382152E+11 | 0.00 | 14673008.94 | 0.345559E+10 | 2809603.28 | 0.174182E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.105293E+10 | 0.00 | 0.00 | 92823510.39 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.187985E+09 | 0.543319E+10 | 0.00 | 4236254.38 | 0.670549E+09 | 2228863.37 | 0.580991E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299905E+09 | 0.365175E+09 | 0.00 | 773848.36 | 0.258468E+09 | 1470293.74 | 0.133281E+09 | 0.00 | 0.45 |
February | 0.145564E+09 | 0.555202E+09 | 0.00 | 1005888.43 | 0.197395E+09 | 7005082.16 | 98581496.14 | 0.00 | 0.48 |
March | 0.209849E+09 | 0.885605E+09 | 0.00 | 1219844.52 | 0.197691E+09 | 888537.37 | 0.144360E+09 | 0.00 | 0.54 |
April | 15385657.72 | 0.147419E+10 | 0.00 | 451497.30 | 0.222488E+09 | 0.00 | 50884819.07 | 0.00 | 0.56 |
May | 2803.44 | 0.277293E+10 | 0.00 | 3095.92 | 0.303267E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.363633E+10 | 0.00 | 0.00 | 0.423207E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.410084E+10 | 0.00 | 0.00 | 0.544170E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.417082E+10 | 0.00 | 0.00 | 0.429476E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.338359E+10 | 0.00 | 0.00 | 0.481364E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 7133.43 | 0.245835E+10 | 0.00 | 2203.42 | 0.423369E+09 | 0.00 | 5446.17 | 0.00 | 0.51 |
November | 44844832.27 | 0.158214E+10 | 0.00 | 211593.44 | 0.266387E+09 | 0.00 | 13447152.24 | 0.00 | 0.46 |
December | 0.248609E+09 | 0.542746E+09 | 0.00 | 685126.79 | 0.331400E+09 | 1625094.31 | 0.100469E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.964168E+09 | 0.259279E+11 | 0.00 | 4353098.20 | 0.407868E+10 | 10989007.57 | 0.541028E+09 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.365175E+09 | 0.00 | 0.00 | 0.197395E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.299905E+09 | 0.417082E+10 | 0.00 | 1219844.52 | 0.544170E+09 | 7005082.16 | 0.144360E+09 | 0.00 | 0.60 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:31:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.198520E+12 | 0.480761E+09 | 0.00 | -0.629826E+10 | 0.170665E+12 |
February | 0.210266E+12 | -797062162.1 | 0.00 | -0.137739E+11 | 0.177455E+12 |
March | 0.282821E+12 | -0.257734E+10 | 0.00 | -0.257820E+11 | 0.218464E+12 |
April | 0.300030E+12 | -0.594630E+10 | 0.00 | -0.548791E+11 | 0.253405E+12 |
May | 0.284485E+12 | -0.137719E+11 | 0.00 | -0.106918E+12 | 0.341685E+12 |
June | 0.254646E+12 | -0.154660E+11 | 0.00 | -0.147583E+12 | 0.386597E+12 |
July | 0.278089E+12 | -0.149898E+11 | 0.00 | -0.163016E+12 | 0.407300E+12 |
August | 0.302234E+12 | -0.167849E+11 | 0.00 | -0.163789E+12 | 0.413621E+12 |
September | 0.232705E+12 | -0.148025E+11 | 0.00 | -0.147509E+12 | 0.379902E+12 |
October | 0.234584E+12 | -0.124402E+11 | 0.00 | -0.119233E+12 | 0.341449E+12 |
November | 0.177848E+12 | -0.635182E+10 | 0.00 | -0.699105E+11 | 0.264637E+12 |
December | 0.192179E+12 | -0.133986E+10 | 0.00 | -0.261156E+11 | 0.185310E+12 |
Annual Sum or Average | 0.294841E+13 | -0.104787E+12 | 0.00 | -0.104481E+13 | 0.354049E+13 |
Minimum of Months | 0.177848E+12 | -0.167849E+11 | 0.00 | -0.163789E+12 | 0.170665E+12 |
Maximum of Months | 0.302234E+12 | 0.480761E+09 | 0.00 | -0.629826E+10 | 0.413621E+12 |