Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:31:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2276.71 | 456.97 | 456.97 |
Net Site Energy | 2276.71 | 456.97 | 456.97 |
Total Source Energy | 6983.63 | 1401.72 | 1401.72 |
Net Source Energy | 6983.63 | 1401.72 | 1401.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 983.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 118.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2167.88 | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 983.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 118.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 983.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 118.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.08 | 21.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 435.13 | 21.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.08 | 21.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 435.13 | 21.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2167.875 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2167.875 | 100.00 |
Total On-Site and Utility Electric Sources | 2167.875 | 100.00 |
Total Electricity End Uses | 2167.875 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 738.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2355.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:20 | 03-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15278.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9347.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 182110.45 | 9347.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 98231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15278.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9347.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 949.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 156.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 374.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6865.66 | 117.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 624.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1378.04 | 23.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 624.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1378.04 | 23.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.90 | 0.258183 | 0.270000 | 0.783757 | 0.688488 | 0.500000 | 0.001476 |
CORE_MID VAV BOX COMPONENT | 2.15 | 0.348250 | 0.349000 | 0.751069 | 0.928667 | 0.500000 | 0.001094 |
CORE_TOP VAV BOX COMPONENT | 2.29 | 0.327408 | 0.342000 | 0.782857 | 0.873088 | 0.500000 | 0.001164 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.753303 | 0.209732 | 0.219000 | 0.164973 | 0.559285 | 0.500000 | 0.001817 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.669038 | 0.149501 | 0.200000 | 0.133808 | 0.398669 | 0.500000 | 0.002548 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.734052 | 0.215232 | 0.225000 | 0.165162 | 0.573953 | 0.500000 | 0.001770 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.774362 | 0.129158 | 0.200000 | 0.154872 | 0.344422 | 0.500000 | 0.002950 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.646574 | 0.244352 | 0.255000 | 0.164876 | 0.651605 | 0.500000 | 0.001559 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.605875 | 0.165087 | 0.200000 | 0.121175 | 0.440231 | 0.500000 | 0.002308 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.628820 | 0.251251 | 0.262000 | 0.164751 | 0.670003 | 0.500000 | 0.001516 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.652301 | 0.153327 | 0.200000 | 0.130460 | 0.408872 | 0.500000 | 0.002485 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.657329 | 0.240354 | 0.241000 | 0.158416 | 0.640944 | 0.500000 | 0.001585 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.644436 | 0.155208 | 0.200000 | 0.128887 | 0.413889 | 0.500000 | 0.002455 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.640058 | 0.246840 | 0.247000 | 0.158094 | 0.658239 | 0.500000 | 0.001544 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.703011 | 0.142267 | 0.200000 | 0.140602 | 0.379379 | 0.500000 | 0.002678 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26164.25 |
CORE_MID VAV BOX REHEAT COIL | 25072.99 |
CORE_TOP VAV BOX REHEAT COIL | 26134.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 5507.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4466.91 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 5513.61 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5170.12 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5504.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4045.19 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5499.89 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4355.16 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5288.43 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4302.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5277.68 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4693.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.72 | 1.37 | 5.44 | 1.37 | 5.02 | 5.02 | 0.300000 | 0.271869 | 5.02 |
PACU_VAV_MID | 2.40 | 1.34 | 4.80 | 1.34 | 4.33 | 4.33 | 0.300000 | 0.308731 | 4.33 |
PACU_VAV_TOP | 2.61 | 1.40 | 5.22 | 1.40 | 5.02 | 5.02 | 0.300000 | 0.279290 | 5.02 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.02 |
PACU_VAV_MID_OA_CONTROLLER | 4.33 |
PACU_VAV_TOP_OA_CONTROLLER | 5.02 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.02 | 124680.14 | 0.701083 | 1.67 | 41555.89 | 0.701083 |
PACU_VAV_MID COOLING COIL | 4.33 | 107545.53 | 0.701083 | 1.44 | 35844.93 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 5.02 | 124626.39 | 0.701083 | 1.67 | 41537.98 | 0.701083 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 23318.22 |
PACU_VAV_MID HEATING COIL | 20113.63 |
PACU_VAV_TOP HEATING COIL | 23308.17 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.02 |
PACU_VAV_MID FAN | 4.33 |
PACU_VAV_TOP FAN | 5.02 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5151E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5504E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5650E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5946E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8809E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9014E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5694E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5839E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7301E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4151E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9015E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3591E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0132E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8570E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8227E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0568E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5144E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5480E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5642E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5920E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8801E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8991E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5692E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5837E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4422E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9838E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0539E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7301E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0085E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5052E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3172E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5628E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3363E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3480E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0516E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0602E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8640E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8671E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9989E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0039E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4102E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4402E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0796E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1031E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7720E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7851E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5692E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5837E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1729E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1842E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7295E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3048E-003 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4477E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1282E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8227E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0568E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4106E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4408E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0800E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1039E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7725E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7867E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5694E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5839E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6562E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0762E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3007E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8363E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2424E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6059E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3172E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5628E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4829E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5023E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2232E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2412E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0190E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0301E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9990E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0040E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.2017E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1440E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3542E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0976E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5016E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4995E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2209E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5024E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3378E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9246E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9688E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6822E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9475E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4696E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2554E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5255E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5150E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5940E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0404E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2929E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.7450E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.3584E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2209E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5024E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5459E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0131E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2087E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7837E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1751E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5660E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2554E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5255E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.2013E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1437E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3537E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0973E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5011E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4992E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2206E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5023E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3377E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9245E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9687E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6821E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9473E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4695E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2551E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5253E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5150E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5939E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0404E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2928E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.7448E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.3576E-003 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2206E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5023E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5458E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0129E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2086E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7836E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1749E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5658E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2551E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5253E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40266.47739 | 40266.47739 | 2.90280 | 2.90280 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 29886.54182 | 29886.54182 | 2.15206 | 2.15206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 1396.48619 | 1396.48619 | 5.93723E-002 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31490.49293 | 31490.49293 | 2.28906 | 2.28906 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 4707.06859 | 4707.06859 | 0.19785 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10362.04557 | 10362.04557 | 0.75330 | 0.75330 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 1580.44798 | 1580.44798 | 6.63616E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9202.93458 | 9202.93458 | 0.66904 | 0.66904 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 1026.55418 | 1026.55418 | 4.31083E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10097.22605 | 10097.22605 | 0.73405 | 0.73405 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 1630.17647 | 1630.17647 | 6.84161E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10651.75148 | 10651.75148 | 0.77436 | 0.77436 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 1026.51861 | 1026.51861 | 4.31068E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8894.40855 | 8894.40855 | 0.64657 | 0.64657 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 198.08374 | 198.08374 | 8.46434E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8334.56537 | 8334.56537 | 0.60587 | 0.60587 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 140.77245 | 140.77245 | 6.01366E-003 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8650.17425 | 8650.17425 | 0.62882 | 0.62882 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 233.15483 | 233.15483 | 9.95758E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8973.22959 | 8973.22959 | 0.65230 | 0.65230 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 140.76908 | 140.76908 | 6.01351E-003 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9042.02715 | 9042.02715 | 0.65733 | 0.65733 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 878.57028 | 878.57028 | 3.71348E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8864.69774 | 8864.69774 | 0.64444 | 0.64444 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 580.63043 | 580.63043 | 2.45398E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8804.44234 | 8804.44234 | 0.64006 | 0.64006 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 921.48998 | 921.48998 | 3.89291E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9670.45213 | 9670.45213 | 0.70301 | 0.70301 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 580.61819 | 580.61819 | 2.45393E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 83983.78 | 5.02087 | 5.02087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | PACU_VAV_MID | Cooling | Sensible | 74478.84 | 4.33086 | 4.33086 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | PACU_VAV_TOP | Cooling | Sensible | 83838.74 | 5.01870 | 5.01870 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.90280 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25818 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78376 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68849 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47570E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26164.24690 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15206 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34825 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75107 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92867 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09404E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25072.99393 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28906 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32741 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78286 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87309 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16369E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26134.19366 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75330 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20973 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16497 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55928 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81661E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5507.32424 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66904 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14950 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13381 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39867 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54848E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4466.91048 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73405 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21523 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16516 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57395 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77018E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5513.60844 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77436 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12916 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15487 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34442 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94987E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5170.11750 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64657 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24435 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16488 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65161 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55923E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5504.08422 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60587 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16509 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12117 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44023 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30788E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4045.19425 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62882 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25125 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16475 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51641E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5499.89434 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65230 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15333 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13046 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40887 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48489E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4355.16347 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65733 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24035 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15842 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64094 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58516E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5288.42766 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64444 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15521 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12889 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41389 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45477E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4302.65563 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64006 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24684 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15809 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65824 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54351E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5277.67771 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70301 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14227 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14060 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37938 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67806E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4693.73602 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71819 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36502 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.43637 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36502 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02087 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.02087 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27187 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.39845 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33707 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.79689 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33707 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.33086 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.33086 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.30873 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60991 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40167 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.21981 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40167 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01870 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.01870 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.27929 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.02087 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.33086 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.01870 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02087 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.02087 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 124680.13736 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67346 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41555.88978 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 23318.22258 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.02087 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.33086 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.33086 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107545.53391 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.44348 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35844.92645 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 20113.63438 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.33086 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01870 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.01870 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 124626.39351 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67273 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41537.97696 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 23308.17117 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.01870 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 124476.50 | 424731.46 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.8044 | 4.5949 | 3.0921 | 1.3328 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 107369.89 | 366361.26 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.0067 | 3.9634 | 2.6672 | 1.1496 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 124422.85 | 424548.38 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.8019 | 4.5929 | 3.0908 | 1.3322 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3816432409 | 0.3334141647 | Pass | Pass | 0.1896526999 | 0.4004428956 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1332582822E-002 | 7.8845832381E-002 | Pass | Pass | 0.1599962305 | 0.3438766946 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.3639225325E-002 | 5.7656825330E-002 | Pass | Pass | 0.1596319638 | 0.3615320443 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6777474309E-002 | 6.1645435956E-002 | Pass | Pass | 0.2123900204 | 0.4789393829 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2037387073 | 0.2654525109 | Pass | Pass | 0.1498272842 | 0.3559738409 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2039379167 | 0.2772103461 | Pass | Pass | 0.1551896188 | 0.3611773696 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2036590727 | 0.2911075427 | Pass | Pass | 0.1557995711 | 0.3611871766 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2490165899 | 0.3508670931 | Pass | Pass | 0.1569601411 | 0.3619710474 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2266316665 | 0.3260496542 | Pass | Pass | 0.1622583051 | 0.3707696788 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2699970423 | 0.3827935323 | Pass | Pass | 0.1562519097 | 0.3605980246 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3371495301 | 0.3027767765 | Pass | Pass | 0.1782891505 | 0.3819709937 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3802543772 | 0.3496007210 | Pass | Pass | 0.1870011499 | 0.3979586790 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3410694996 | 0.3207902080 | Pass | Pass | 0.1970139419 | 0.4162309112 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3975522061 | 0.3649439817 | Pass | Pass | 0.1785555256 | 0.3820131277 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1966517789 | 0.2685637825 | Pass | Pass | 0.1499101423 | 0.3557594676 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2421549923 | 0.3359163223 | Pass | Pass | 0.1615810409 | 0.3772873411 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2055591804 | 0.2978344898 | Pass | Pass | 0.1710179107 | 0.4015710230 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2531245936 | 0.3484758994 | Pass | Pass | 0.1509961896 | 0.3562397778 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3160.26 | -182.0 | 0.00 | -2067.4 | 4870.03 | 5780.86 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.34 | 0.0000 | Y | 8.58 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 5.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.21 | 0.0000 | Y | 5.40 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.29 | 0.0000 | Y | 8.56 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.45 | 0.0000 | Y | 5.46 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.17 | 0.0000 | Y | 8.52 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.16 | 0.0000 | Y | 5.39 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.34 | 0.0000 | Y | 8.58 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 5.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.21 | 0.0000 | Y | 5.40 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 299.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.93 | 41.93 | 4.44 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.83 | 62.88 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.83 | 45.49 | 40.26 | |
Exterior Lighting Total | 5686.19 | 49.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 124680.14 | 87411.15 | 37268.99 | 0.70 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107545.53 | 75398.37 | 32147.16 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 124626.39 | 87373.47 | 37252.92 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 124476.5 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_MID COOLING COIL | 107369.9 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 124422.8 | 2.97 | 10.14 | N/A | N/A | 11.65 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26164.25 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25072.99 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26134.19 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5507.32 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4466.91 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5513.61 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5170.12 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5504.08 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4045.19 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5499.89 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4355.16 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5288.43 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4302.66 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5277.68 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4693.74 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 23318.22 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 20113.63 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 23308.17 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.02 | 10990.74 | 2189.01 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.33 | 9480.30 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.02 | 10986.00 | 2189.01 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 124476.50 | 2.97 | 10.14 | 11.65 | 5.8044 | 3.34 | 11.39 | 4.5949 | 3.52 | 12.03 | 3.0921 | 3.64 | 12.43 | 1.3328 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107369.89 | 2.97 | 10.14 | 11.65 | 5.0067 | 3.34 | 11.39 | 3.9634 | 3.52 | 12.03 | 2.6672 | 3.64 | 12.43 | 1.1496 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 124422.85 | 2.97 | 10.14 | 11.65 | 5.8019 | 3.34 | 11.39 | 4.5929 | 3.52 | 12.03 | 3.0908 | 3.64 | 12.43 | 1.3322 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40266.48 | 40266.48 | 40.94 | 2.903 | 2.903 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_MID | 29886.54 | 29886.54 | 30.39 | 2.152 | 2.152 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_TOP | 31490.49 | 31490.49 | 32.02 | 2.289 | 2.289 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 35.20 | 0.01716 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10362.05 | 10362.05 | 49.98 | 0.753 | 0.753 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 24.00 | 0.00906 | 35.03 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9202.93 | 9202.93 | 70.11 | 0.669 | 0.669 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 24.00 | 24.00 | 0.00891 | 31.73 | 0.01715 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10097.23 | 10097.23 | 48.70 | 0.734 | 0.734 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00907 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10651.75 | 10651.75 | 81.15 | 0.774 | 0.774 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00886 | 34.58 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8894.41 | 8894.41 | 42.90 | 0.647 | 0.647 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00898 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8334.57 | 8334.57 | 63.50 | 0.606 | 0.606 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 24.00 | 24.00 | 0.00883 | 31.73 | 0.01715 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8650.17 | 8650.17 | 41.72 | 0.629 | 0.629 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 24.00 | 24.00 | 0.00899 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8973.23 | 8973.23 | 68.37 | 0.652 | 0.652 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00881 | 34.35 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9042.03 | 9042.03 | 43.61 | 0.657 | 0.657 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00908 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8864.70 | 8864.70 | 67.53 | 0.644 | 0.644 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00889 | 31.25 | 0.01715 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8804.44 | 8804.44 | 42.46 | 0.640 | 0.640 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00909 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9670.45 | 9670.45 | 73.68 | 0.703 | 0.703 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00885 | 34.58 | 0.01716 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 21.96 | 0.01480 | 20.10 | 0.01480 | 0.425 | 0.00 | |
CORE_MID | 1396.49 | 1396.49 | 1.42 | 0.059 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
CORE_TOP | 4707.07 | 4707.07 | 4.79 | 0.198 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 1580.45 | 1580.45 | 7.62 | 0.066 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01140 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 1026.55 | 1026.55 | 7.82 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01146 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 1630.18 | 1630.18 | 7.86 | 0.068 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01136 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 1026.52 | 1026.52 | 7.82 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01146 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 198.08 | 198.08 | 0.96 | 0.008 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01276 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 140.77 | 140.77 | 1.07 | 0.006 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01270 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 233.15 | 233.15 | 1.12 | 0.010 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01254 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 140.77 | 140.77 | 1.07 | 0.006 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01270 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 878.57 | 878.57 | 4.24 | 0.037 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01178 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 580.63 | 580.63 | 4.42 | 0.025 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01183 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 921.49 | 921.49 | 4.44 | 0.039 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01172 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 580.62 | 580.62 | 4.42 | 0.025 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01183 | 20.10 | 0.01480 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.02 | 5.02 | 0.00 | 0.00 | 5.0209 | 1.3650 | 5.0209 | 0.2719 | 0.3000 |
PACU_VAV_MID | 4.33 | 4.33 | 0.00 | 0.00 | 4.3309 | 1.3371 | 4.3309 | 0.3087 | 0.3000 |
PACU_VAV_TOP | 5.02 | 5.02 | 0.00 | 0.00 | 5.0187 | 1.4017 | 5.0187 | 0.2793 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26164.247 | 26164.247 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 26164.25 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25072.994 | 25072.994 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25072.99 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800185 | 51.7046 | 1396.49 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26134.194 | 26134.194 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26134.19 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 4707.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 5507.324 | 5507.324 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5507.32 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01140029 | 73.2574 | 1580.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4466.910 | 4466.910 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4466.91 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01145713 | 73.6154 | 1026.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 5513.608 | 5513.608 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5513.61 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01135643 | 72.9803 | 1630.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5170.118 | 5170.118 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5170.12 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01145720 | 73.6159 | 1026.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5504.084 | 5504.084 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5504.08 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01275976 | 81.8280 | 198.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4045.194 | 4045.194 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4045.19 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01269776 | 81.4382 | 140.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5499.894 | 5499.894 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5499.89 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01254382 | 80.4704 | 233.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4355.163 | 4355.163 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4355.16 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01269781 | 81.4385 | 140.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5288.428 | 5288.428 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5288.43 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01178035 | 75.6593 | 878.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4302.656 | 4302.656 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4302.66 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01182556 | 75.9438 | 580.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5277.678 | 5277.678 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5277.68 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01171828 | 75.2678 | 921.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4693.736 | 4693.736 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4693.74 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01182562 | 75.9442 | 580.62 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 124680.137 | 87411.152 | 5.020869 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 127466.82 | 91687.75 | 5.020869 | 26.67 | 19.20 | 0.01085514 | 11.03 | 11.03 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 23.8040 | 24.00 | 0.00887803 | 47.7443 | 68856.83 | 0.00 | 128561.96 | 88934.87 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 23318.223 | 23318.223 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 23318.22 | 23318.22 | 1.506261 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 79.3468 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 107545.534 | 75398.369 | 4.330859 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 111322.62 | 77058.33 | 4.330859 | 27.08 | 19.64 | 0.01125501 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 27.5966 | 24.00 | 0.00899200 | 48.3493 | 59326.95 | 0.00 | 110893.88 | 76712.68 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 20113.634 | 20113.634 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 20113.63 | 20113.63 | 1.299258 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 91.9887 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 124626.394 | 87373.473 | 5.018705 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 127615.11 | 91154.44 | 5.018705 | 26.65 | 19.24 | 0.01091091 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 23.8143 | 24.00 | 0.00895057 | 48.1300 | 68833.74 | 0.00 | 128506.54 | 88896.53 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 23308.171 | 23308.171 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 23308.17 | 23308.17 | 1.505611 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 79.3810 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26164.247 | 26164.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 26164.25 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26164.25 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25072.994 | 25072.994 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25072.99 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25072.99 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.85 | 0.00800185 | 21.00 | 0.00800185 | 51.7046 | 1396.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26134.194 | 26134.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26134.19 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26134.19 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.70 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 4707.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5507.324 | 5507.324 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5507.32 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5507.32 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01140029 | 21.00 | 0.01140029 | 73.2574 | 1580.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4466.910 | 4466.910 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4466.91 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4466.91 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01145713 | 21.00 | 0.01145713 | 73.6154 | 1026.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5513.608 | 5513.608 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5513.61 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5513.61 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01135643 | 21.00 | 0.01135643 | 72.9803 | 1630.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5170.118 | 5170.118 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5170.12 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5170.12 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01145720 | 21.00 | 0.01145720 | 73.6159 | 1026.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5504.084 | 5504.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5504.08 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5504.08 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.95 | 0.01275976 | 21.00 | 0.01275976 | 81.8280 | 198.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4045.194 | 4045.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4045.19 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4045.19 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.94 | 0.01269776 | 21.00 | 0.01269776 | 81.4382 | 140.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5499.894 | 5499.894 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5499.89 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5499.89 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.94 | 0.01254382 | 21.00 | 0.01254382 | 80.4704 | 233.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4355.163 | 4355.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4355.16 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4355.16 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.94 | 0.01269781 | 21.00 | 0.01269781 | 81.4385 | 140.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5288.428 | 5288.428 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5288.43 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5288.43 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.75 | 0.01178035 | 21.00 | 0.01178035 | 75.6593 | 878.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4302.656 | 4302.656 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4302.66 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4302.66 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.74 | 0.01182556 | 21.00 | 0.01182556 | 75.9438 | 580.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5277.678 | 5277.678 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5277.68 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5277.68 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.74 | 0.01171828 | 21.00 | 0.01171828 | 75.2678 | 921.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4693.736 | 4693.736 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4693.74 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4693.74 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.74 | 0.01182562 | 21.00 | 0.01182562 | 75.9442 | 580.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 124680.137 | 87411.152 | 5.020869 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99503 | 1025.0192 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.020869 | 6.04309289 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 127466.82 | 91687.75 | 1.0224 | 6.04309289 | 5.020869 | 26.67 | 19.20 | 0.01085514 | 54488.5 | 11.03 | 11.03 | 0.00850000 | 32511.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10990.738 | 116476.08 | 35.20 | 0.01715815 | 25.83 | 1.19517000 | 23.8040 | 24.00 | 0.00887803 | 24.00 | 0.00887803 | 47.7443 | 68856.83 | 0.00 | 128561.96 | 88934.87 | 5.80443640 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23318.223 | 23318.223 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.020869 | 6.04309289 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 23318.22 | 23318.22 | 1.0000 | 1.81292787 | 1.506261 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23318.22 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 79.3468 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107545.534 | 75398.369 | 4.330859 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.94761 | 1025.7625 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.330859 | 5.21259974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 111322.62 | 77058.33 | 1.0351 | 5.21259974 | 4.330859 | 27.08 | 19.64 | 0.01125501 | 55924.6 | 11.03 | 11.03 | 0.00850000 | 32512.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9480.297 | 101842.33 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 27.5966 | 24.00 | 0.00899200 | 24.00 | 0.00899200 | 48.3493 | 59326.95 | 0.00 | 110893.88 | 76712.68 | 5.00674145 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20113.634 | 20113.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.330859 | 5.21259974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 20113.63 | 20113.63 | 1.0000 | 1.56377992 | 1.299258 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20113.63 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 91.9887 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 124626.394 | 87373.473 | 5.018705 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99116 | 1025.1228 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.018705 | 6.04048799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 127615.11 | 91154.44 | 1.0240 | 6.04048799 | 5.018705 | 26.65 | 19.24 | 0.01091091 | 54610.5 | 11.03 | 11.03 | 0.00850000 | 32511.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10986.000 | 116629.11 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 23.8143 | 24.00 | 0.00895057 | 24.00 | 0.00895057 | 48.1300 | 68833.74 | 0.00 | 128506.54 | 88896.53 | 5.80193438 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23308.171 | 23308.171 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.018705 | 6.04048799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 23308.17 | 23308.17 | 1.0000 | 1.81214640 | 1.505611 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23308.17 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 79.3810 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5941.50 | 0.00 | 0.00 |
CORE_MID | 5380.33 | 3.00 | 0.00 |
CORE_TOP | 5205.83 | 21.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 5757.33 | 659.67 | 638.33 |
PERIMETER_TOP_ZN_2 | 5711.50 | 755.50 | 738.17 |
PERIMETER_TOP_ZN_1 | 5847.17 | 762.17 | 760.00 |
PERIMETER_TOP_ZN_4 | 5397.50 | 707.50 | 581.00 |
PERIMETER_BOT_ZN_3 | 5932.67 | 253.83 | 253.83 |
PERIMETER_BOT_ZN_2 | 5940.33 | 448.17 | 448.17 |
PERIMETER_BOT_ZN_1 | 5941.33 | 1903.67 | 1903.67 |
PERIMETER_BOT_ZN_4 | 5931.17 | 366.00 | 366.00 |
PERIMETER_MID_ZN_3 | 5890.00 | 458.50 | 457.00 |
PERIMETER_MID_ZN_2 | 4904.17 | 573.50 | 572.67 |
PERIMETER_MID_ZN_1 | 5924.00 | 607.50 | 607.50 |
PERIMETER_MID_ZN_4 | 5676.00 | 491.83 | 478.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5942.50 | 2448.00 | 2355.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 43.67 | 0.00 | 40.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 80.67 | 0.00 | 79.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 74.83 | 0.00 | 72.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 61.50 | 0.00 | 51.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 12.33 | 0.00 | 11.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 52.17 | 0.00 | 51.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 618.33 | 0.00 | 617.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 47.00 | 0.00 | 40.17 |
PERIMETER_MID_ZN_3 | 0.00 | 18.17 | 0.00 | 16.67 |
PERIMETER_MID_ZN_2 | 0.00 | 53.67 | 0.00 | 53.67 |
PERIMETER_MID_ZN_1 | 0.00 | 67.17 | 0.00 | 67.17 |
PERIMETER_MID_ZN_4 | 0.00 | 46.83 | 0.00 | 40.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 752.67 | 0.00 | 738.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.466 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.444 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.442 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.627 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.776 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.683 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.785 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.539 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.657 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.678 | 1.244 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.656 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.634 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.736 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.690 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.784 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7716284.82 | 0.00 | 7716284.82 | 0.00 | 7716284.82 | 13393058.27 | 7926.06 | 363.35 | 470.59 | 308.92 |
CORE_MID | 7221759.25 | 0.00 | 7221759.25 | 0.00 | 7221759.25 | 13393058.27 | 8734.53 | 5.38 | 20.09 | 213.48 |
CORE_TOP | 7197569.58 | 0.00 | 7197569.58 | 0.00 | 7197569.58 | 13393058.27 | 8745.70 | 3.61 | 10.69 | 223.61 |
PERIMETER_TOP_ZN_3 | 2123122.49 | 0.00 | 2123122.49 | 330276.95 | 2453399.44 | 2823374.22 | 4812.00 | 52.44 | 3895.55 | 223.61 |
PERIMETER_TOP_ZN_2 | 1664473.16 | 0.00 | 1664473.16 | 220183.31 | 1884656.47 | 1787429.43 | 3437.62 | 1.48 | 5320.90 | 223.61 |
PERIMETER_TOP_ZN_1 | 2307821.26 | 0.00 | 2307821.26 | 330276.95 | 2638098.21 | 2823374.22 | 4586.92 | 38.43 | 4134.66 | 223.61 |
PERIMETER_TOP_ZN_4 | 1695791.11 | 0.00 | 1695791.11 | 220183.31 | 1915974.42 | 1787312.18 | 3462.58 | 15.32 | 5282.10 | 223.61 |
PERIMETER_BOT_ZN_3 | 1862892.79 | 0.00 | 1862892.79 | 175608.30 | 2038501.09 | 2823374.22 | 5777.46 | 302.14 | 2680.40 | 308.92 |
PERIMETER_BOT_ZN_2 | 1434389.31 | 0.00 | 1434389.31 | 117071.50 | 1551460.81 | 1787429.43 | 3473.27 | 49.43 | 5237.30 | 308.92 |
PERIMETER_BOT_ZN_1 | 2309054.21 | 0.00 | 2309054.21 | 4121307.75 | 6430361.96 | 2823374.22 | 4476.94 | 60.85 | 4222.21 | 308.92 |
PERIMETER_BOT_ZN_4 | 1438905.50 | 0.00 | 1438905.50 | 117071.50 | 1555977.00 | 1787312.18 | 3804.00 | 105.96 | 4850.05 | 308.92 |
PERIMETER_MID_ZN_3 | 2142202.24 | 0.00 | 2142202.24 | 274931.61 | 2417133.85 | 2823374.22 | 4668.99 | 54.98 | 4036.03 | 213.48 |
PERIMETER_MID_ZN_2 | 1654273.08 | 0.00 | 1654273.08 | 183286.64 | 1837559.72 | 1787429.43 | 3452.96 | 2.66 | 5304.38 | 1122.48 |
PERIMETER_MID_ZN_1 | 2327378.63 | 0.00 | 2327378.63 | 274931.61 | 2602310.24 | 2823374.22 | 4478.46 | 28.17 | 4253.38 | 213.48 |
PERIMETER_MID_ZN_4 | 1686655.43 | 0.00 | 1686655.43 | 183286.64 | 1869942.07 | 1787312.18 | 3492.53 | 12.96 | 5254.51 | 213.48 |
Total Facility | 44782572.85 | 0.00 | 44782572.85 | 6548416.08 | 51330988.93 | 67843644.98 | 8760.00 | 928.40 | 5558.75 | 1281.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3385 | 0.0000 | 0.3385 | 0.0000 | 0.3385 | 0.4247 | 5162.35 | 323.57 | 457.08 |
CORE_MID | 0.3226 | 0.0000 | 0.3226 | 0.0000 | 0.3226 | 0.4247 | 5922.59 | 5.25 | 15.16 |
CORE_TOP | 0.3209 | 0.0000 | 0.3209 | 0.0000 | 0.3209 | 0.4247 | 5931.86 | 3.43 | 7.71 |
PERIMETER_TOP_ZN_3 | 0.0959 | 0.0000 | 0.0959 | 0.0084 | 0.1043 | 0.0895 | 2007.60 | 51.92 | 3883.48 |
PERIMETER_TOP_ZN_2 | 0.0751 | 0.0000 | 0.0751 | 0.0056 | 0.0807 | 0.0567 | 842.30 | 1.03 | 5099.66 |
PERIMETER_TOP_ZN_1 | 0.1045 | 0.0000 | 0.1045 | 0.0084 | 0.1129 | 0.0895 | 1780.83 | 37.74 | 4124.43 |
PERIMETER_TOP_ZN_4 | 0.0761 | 0.0000 | 0.0761 | 0.0056 | 0.0817 | 0.0567 | 868.61 | 15.11 | 5059.28 |
PERIMETER_BOT_ZN_3 | 0.0825 | 0.0000 | 0.0825 | 0.0044 | 0.0869 | 0.0895 | 2970.69 | 297.52 | 2674.79 |
PERIMETER_BOT_ZN_2 | 0.0637 | 0.0000 | 0.0637 | 0.0030 | 0.0667 | 0.0567 | 957.52 | 48.21 | 4937.27 |
PERIMETER_BOT_ZN_1 | 0.1033 | 0.0000 | 0.1033 | 0.1889 | 0.2922 | 0.0895 | 1670.03 | 58.81 | 4214.16 |
PERIMETER_BOT_ZN_4 | 0.0635 | 0.0000 | 0.0635 | 0.0030 | 0.0665 | 0.0567 | 1291.38 | 105.58 | 4546.05 |
PERIMETER_MID_ZN_3 | 0.0969 | 0.0000 | 0.0969 | 0.0070 | 0.1039 | 0.0895 | 1861.07 | 54.44 | 4027.49 |
PERIMETER_MID_ZN_2 | 0.0713 | 0.0000 | 0.0713 | 0.0049 | 0.0763 | 0.0567 | 845.60 | 1.51 | 4186.89 |
PERIMETER_MID_ZN_1 | 0.1056 | 0.0000 | 0.1056 | 0.0070 | 0.1126 | 0.0895 | 1669.34 | 27.87 | 4245.79 |
PERIMETER_MID_ZN_4 | 0.0760 | 0.0000 | 0.0760 | 0.0046 | 0.0806 | 0.0567 | 887.49 | 12.76 | 5042.75 |
Total Facility | 1.9966 | 0.0000 | 1.9966 | 0.2507 | 2.2472 | 2.1513 | 5943.00 | 883.74 | 5186.15 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21384157.76 | 0.00 | 21384157.76 | 22614548.33 | 3345.06 | 0.00 | 5414.94 | 308.92 |
PACU_VAV_MID | 21776367.34 | 0.00 | 21776367.34 | 22614548.33 | 3443.58 | 0.00 | 5316.42 | 213.48 |
PACU_VAV_TOP | 21713363.30 | 0.00 | 21713363.30 | 22614548.33 | 3429.81 | 0.00 | 5330.19 | 223.61 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9439 | 0.0000 | 0.9439 | 0.7171 | 836.99 | 0.00 | 5106.01 |
PACU_VAV_MID | 0.9791 | 0.0000 | 0.9791 | 0.7171 | 840.07 | 0.00 | 5102.93 |
PACU_VAV_TOP | 0.9743 | 0.0000 | 0.9743 | 0.7171 | 836.42 | 0.00 | 5106.58 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5414.94 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5316.42 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5330.19 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0986 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1405 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1340 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2218 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
Electricity:Building | 1005.13 | 12266.72 | 18-JUN-17:20 | 73343.20 | 18-DEC-17:00 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1005.13 | 12266.72 | 18-JUN-17:20 | 73343.20 | 18-DEC-17:00 |
InteriorLights:Electricity | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 32.91 | 422.10 | 28-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.87 | 271.65 | 29-MAY-17:10 | 1768.58 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.87 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.81 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 32.89 | 422.10 | 07-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.56 | 36.00 | 01-JAN-09:00 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.56 | 36.00 | 01-JAN-09:00 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 271.65 | 29-MAY-17:10 | 1768.58 | 04-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:20 | 860.01 | 04-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:20 | 860.01 | 04-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.86 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.52 | 36.00 | 01-JAN-07:50 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.52 | 36.00 | 01-JAN-07:50 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.80 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.39 | 22.79 | 01-JAN-09:30 | 750.02 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.39 | 22.79 | 01-JAN-09:30 | 750.02 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 32.91 | 422.10 | 28-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.87 | 271.65 | 29-MAY-17:10 | 1768.58 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.87 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.81 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1113.09 | 168.34 | 01-JAN-00:10 | 114350.11 | 13-JUN-15:20 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 846.73 | 18-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 846.73 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
ElectricityPurchased:Plant | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
Cogeneration:ElectricityPurchased | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
General:Cogeneration:ElectricityPurchased | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
ElectricityNet:Plant | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
Cogeneration:ElectricityNet | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
General:Cogeneration:ElectricityNet | 2167.88 | 12440.18 | 04-JUL-17:40 | 182110.45 | 13-JUN-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 118.30 | 0.00 | 01-JAN-00:10 | 15642.86 | 12-JUN-15:20 |
General:Fans:Electricity | 118.30 | 0.00 | 01-JAN-00:10 | 15642.86 | 12-JUN-15:20 |
ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 983.03 | 0.00 | 01-JAN-00:10 | 98231.63 | 13-JUN-15:20 |
General:Cooling:Electricity | 983.03 | 0.00 | 01-JAN-00:10 | 98231.63 | 13-JUN-15:20 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-14:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-14:50 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-14:50 |
WIRED_LTG_ELECTRICITY | 8.42 | 0.00 | 01-JAN-00:10 | 878.71 | 18-DEC-17:10 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 108.83 | 1886.44 | 01-JAN-00:10 | 9347.50 | 03-JAN-12:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 108.83 | 1886.44 | 01-JAN-00:10 | 9347.50 | 03-JAN-12:10 |
WaterSystems:NaturalGas | 108.83 | 1886.44 | 01-JAN-00:10 | 9347.50 | 03-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 108.83 | 1886.44 | 01-JAN-00:10 | 9347.50 | 03-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5925.87 | 0.00 | 01-JAN-00:10 | 507888.16 | 13-JUN-15:30 |
EnergyTransfer:Building | 2007.11 | 0.00 | 01-JAN-00:10 | 174216.11 | 12-JUN-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 347.03 | 0.00 | 01-JAN-00:10 | 28885.87 | 02-JAN-09:00 |
Heating:EnergyTransfer | 0.49 | 0.00 | 01-JAN-00:10 | 2134.44 | 02-AUG-04:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.49 | 0.00 | 01-JAN-00:10 | 2134.44 | 02-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2006.61 | 0.00 | 01-JAN-00:10 | 174216.11 | 12-JUN-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 347.03 | 0.00 | 01-JAN-00:10 | 28885.87 | 02-JAN-09:00 |
General:Cooling:EnergyTransfer | 2006.61 | 0.00 | 01-JAN-00:10 | 174216.11 | 12-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 347.03 | 0.00 | 01-JAN-00:10 | 28885.87 | 02-JAN-09:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.44 | 0.00 | 01-JAN-00:10 | 11049.79 | 05-MAY-13:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.17 | 0.00 | 01-JAN-00:10 | 1403.61 | 23-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.17 | 0.00 | 01-JAN-00:10 | 1403.61 | 23-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.27 | 0.00 | 01-JAN-00:10 | 11049.79 | 05-MAY-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.27 | 0.00 | 01-JAN-00:10 | 11049.79 | 05-MAY-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.75 | 0.00 | 01-JAN-00:10 | 5467.23 | 21-FEB-16:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.11 | 0.00 | 01-JAN-00:10 | 600.91 | 02-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.11 | 0.00 | 01-JAN-00:10 | 600.91 | 02-AUG-04:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.64 | 0.00 | 01-JAN-00:10 | 5467.23 | 21-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.64 | 0.00 | 01-JAN-00:10 | 5467.23 | 21-FEB-16:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.16 | 0.00 | 01-JAN-00:10 | 5764.77 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.21 | 0.00 | 01-JAN-00:10 | 984.35 | 02-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.21 | 0.00 | 01-JAN-00:10 | 984.35 | 02-AUG-04:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 58.95 | 0.00 | 01-JAN-00:10 | 5764.77 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 58.95 | 0.00 | 01-JAN-00:10 | 5764.77 | 12-JUN-16:00 |
EnergyTransfer:Zone:CORE_MID | 257.84 | 0.00 | 01-JAN-00:10 | 20564.52 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 257.84 | 0.00 | 01-JAN-00:10 | 20564.52 | 02-JAN-08:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 257.84 | 0.00 | 01-JAN-00:10 | 20564.52 | 02-JAN-08:40 |
EnergyTransfer:Zone:CORE_TOP | 273.23 | 0.00 | 01-JAN-00:10 | 21983.32 | 21-FEB-14:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 273.23 | 0.00 | 01-JAN-00:10 | 21983.32 | 21-FEB-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 273.23 | 0.00 | 01-JAN-00:10 | 21983.32 | 21-FEB-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 85.28 | 0.00 | 01-JAN-00:10 | 9564.79 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 85.28 | 0.00 | 01-JAN-00:10 | 9564.79 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 85.28 | 0.00 | 01-JAN-00:10 | 9564.79 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.25 | 0.00 | 01-JAN-00:10 | 7616.29 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.25 | 0.00 | 01-JAN-00:10 | 7616.29 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.25 | 0.00 | 01-JAN-00:10 | 7616.29 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.54 | 0.00 | 01-JAN-00:10 | 10603.43 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.54 | 0.00 | 01-JAN-00:10 | 10603.43 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.54 | 0.00 | 01-JAN-00:10 | 10603.43 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.51 | 0.00 | 01-JAN-00:10 | 8343.21 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.51 | 0.00 | 01-JAN-00:10 | 8343.21 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.51 | 0.00 | 01-JAN-00:10 | 8343.21 | 11-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.38 | 0.00 | 01-JAN-00:10 | 8946.73 | 12-JUN-15:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.38 | 0.00 | 01-JAN-00:10 | 8946.73 | 12-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.38 | 0.00 | 01-JAN-00:10 | 8946.73 | 12-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.20 | 0.00 | 01-JAN-00:10 | 7027.93 | 20-MAR-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.20 | 0.00 | 01-JAN-00:10 | 7027.93 | 20-MAR-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.20 | 0.00 | 01-JAN-00:10 | 7027.93 | 20-MAR-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.56 | 0.00 | 01-JAN-00:10 | 11745.51 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.56 | 0.00 | 01-JAN-00:10 | 11745.51 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.56 | 0.00 | 01-JAN-00:10 | 11745.51 | 05-MAY-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.39 | 0.00 | 01-JAN-00:10 | 7372.16 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.39 | 0.00 | 01-JAN-00:10 | 7372.16 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.39 | 0.00 | 01-JAN-00:10 | 7372.16 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.39 | 0.00 | 01-JAN-00:10 | 8748.25 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.39 | 0.00 | 01-JAN-00:10 | 8748.25 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.39 | 0.00 | 01-JAN-00:10 | 8748.25 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.71 | 0.00 | 01-JAN-00:10 | 7235.11 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.71 | 0.00 | 01-JAN-00:10 | 7235.11 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.71 | 0.00 | 01-JAN-00:10 | 7235.11 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.22 | 0.00 | 01-JAN-00:10 | 9458.49 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.22 | 0.00 | 01-JAN-00:10 | 9458.49 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.22 | 0.00 | 01-JAN-00:10 | 9458.49 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.24 | 0.00 | 01-JAN-00:10 | 7719.58 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.24 | 0.00 | 01-JAN-00:10 | 7719.58 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.24 | 0.00 | 01-JAN-00:10 | 7719.58 | 18-APR-15:30 |
PlantLoopHeatingDemand:Facility | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
EnergyTransfer:HVAC | 3887.00 | 0.00 | 01-JAN-00:10 | 332892.50 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3887.00 | 0.00 | 01-JAN-00:10 | 332892.50 | 15-JUN-10:00 |
EnergyTransfer:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3781.38 | 04-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -347.029 | 0.000 | 0.000 | 32.682 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 6.251 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -257.841 | 0.000 | 0.000 | 32.743 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 37.745 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -273.230 | 0.000 | 0.000 | 32.763 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 53.113 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -85.272 | 0.000 | 0.000 | 6.890 | 8.581 | 24.333 | 37.780 | 0.000 | 1.014 | 10.450 | 0.000 | -3.612 | 0.000 | -0.164 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -66.248 | 0.000 | 0.000 | 4.361 | 5.468 | 15.404 | 37.598 | 0.000 | 0.674 | 5.167 | 0.000 | -2.311 | 0.000 | -0.113 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -93.538 | 0.000 | 0.000 | 6.884 | 8.537 | 24.332 | 48.498 | 0.000 | 1.003 | 8.056 | 0.000 | -3.596 | 0.000 | -0.177 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -66.504 | 0.000 | 0.000 | 4.374 | 5.404 | 15.403 | 37.739 | 0.000 | 0.678 | 5.521 | 0.000 | -2.499 | 0.000 | -0.117 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -85.379 | 0.000 | 0.000 | 6.886 | 8.561 | 24.333 | 37.944 | 0.000 | 0.559 | 11.110 | 0.000 | -3.918 | 0.000 | -0.096 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -66.194 | 0.000 | 0.000 | 4.356 | 5.456 | 15.404 | 37.680 | 0.000 | 0.360 | 5.674 | 0.000 | -2.665 | 0.000 | -0.071 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -111.552 | 0.000 | 0.000 | 6.776 | 8.523 | 24.332 | 48.294 | 0.000 | 21.647 | 6.538 | 0.000 | -4.136 | 0.000 | -0.423 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -65.384 | 0.000 | 0.000 | 4.358 | 5.393 | 15.403 | 37.759 | 0.000 | 0.356 | 5.092 | 0.000 | -2.902 | 0.000 | -0.074 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -80.385 | 0.000 | 0.000 | 6.887 | 8.581 | 24.333 | 38.090 | 0.000 | 0.862 | 5.500 | 0.000 | -3.724 | 0.000 | -0.143 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -61.710 | 0.000 | 0.000 | 3.215 | 5.467 | 15.404 | 37.825 | 0.000 | 0.571 | 1.708 | 0.000 | -2.382 | 0.000 | -0.098 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -88.213 | 0.000 | 0.000 | 6.877 | 8.537 | 24.332 | 48.812 | 0.000 | 0.850 | 2.664 | 0.000 | -3.705 | 0.000 | -0.154 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -62.240 | 0.000 | 0.000 | 4.366 | 5.404 | 15.403 | 37.914 | 0.000 | 0.566 | 1.291 | 0.000 | -2.601 | 0.000 | -0.103 | -0.000 |
TOPFLOOR_PLENUM | 0.173 | -85.264 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.249 | 84.031 | 0.000 | 0.000 | 0.000 | -0.189 | 0.000 |
MIDFLOOR_PLENUM | 0.113 | -51.639 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.297 | 50.444 | 0.000 | 0.000 | 0.000 | -0.216 | 0.000 |
FIRSTFLOOR_PLENUM | 0.205 | -58.949 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.001 | 57.920 | 0.000 | 0.000 | 0.000 | -0.177 | -0.000 |
Total Facility | 0.492 | -195.853 | 0.000 | -1810.719 | 0.000 | 0.000 | 164.419 | 299.699 | 705.434 | 485.933 | 0.000 | 32.688 | 358.276 | 0.000 | -38.053 | 0.000 | -2.315 | -0.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -46627.64 | 0.00 | 0.00 | 287.13 | 211.73 | 4989.51 | 0.00 | 0.00 | 0.00 | 41139.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -35483.65 | 0.00 | 0.00 | 294.09 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 31951.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -37813.68 | 0.00 | 0.00 | 299.84 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 34276.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-13:22 | 0.00 | 0.00 | 0.00 | -13698.61 | 0.00 | 0.00 | 24.19 | 36.00 | 478.42 | 4770.75 | 0.00 | 312.19 | 8077.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:52 | 0.00 | 0.00 | 0.00 | -12136.64 | 0.00 | 0.00 | 14.99 | 22.79 | 302.86 | 4352.31 | 0.00 | 187.63 | 7256.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 08-JAN-16:02 | 0.00 | 0.00 | 0.00 | -13348.85 | 0.00 | 0.00 | 24.49 | 36.00 | 478.41 | 3798.80 | 0.00 | 88.02 | 8923.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 19-MAR-15:32 | 0.00 | 0.00 | 0.00 | -13783.51 | 0.00 | 0.00 | 12.34 | 22.79 | 302.86 | 6477.87 | 0.00 | 343.93 | 6623.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUN-13:52 | 0.00 | 0.00 | 0.00 | -11494.48 | 0.00 | 0.00 | 26.05 | 36.00 | 478.42 | 4813.27 | 0.00 | 172.77 | 5967.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 11-JUN-09:52 | 0.00 | 0.00 | 0.00 | -10817.66 | 0.00 | 0.00 | 15.98 | 22.79 | 302.86 | 4429.64 | 0.00 | 107.35 | 5939.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-MAY-12:00 | 0.00 | 0.00 | 0.00 | -11744.73 | 0.00 | 0.00 | 288.83 | 647.98 | 1275.77 | 3341.70 | 0.00 | 10925.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4735.19 |
PERIMETER_BOT_ZN_4 | 10-SEP-15:12 | 0.00 | 0.00 | 0.00 | -11774.11 | 0.00 | 0.00 | 15.44 | 22.79 | 302.86 | 5853.33 | 0.00 | 64.21 | 5515.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-12:53 | 0.00 | 0.00 | 0.00 | -11524.37 | 0.00 | 0.00 | 25.97 | 36.00 | 478.42 | 4738.74 | 0.00 | 252.96 | 5992.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 11-JUN-09:52 | 0.00 | 0.00 | 0.00 | -11561.33 | 0.00 | 0.00 | 15.51 | 22.79 | 302.86 | 4390.04 | 0.00 | 162.82 | 6667.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-12:32 | 0.00 | 0.00 | 0.00 | -11899.37 | 0.00 | 0.00 | 24.86 | 36.00 | 478.41 | 7619.14 | 0.00 | 32.84 | 3708.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-15:12 | 0.00 | 0.00 | 0.00 | -12650.47 | 0.00 | 0.00 | 14.84 | 22.79 | 302.86 | 5798.20 | 0.00 | 92.30 | 6419.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 05-MAY-13:40 | 0.00 | -11049.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.72 | 10872.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 21-FEB-16:10 | 0.00 | -5467.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.36 | 5352.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:10 | 0.00 | -5942.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 5921.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JUL-04:02 | 0.00 | 8228.89 | 0.00 | -210033.84 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 191003.74 | 0.00 | -4418.72 | 0.00 | -186.55 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 06-FEB-06:02 | 5253.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5253.12 |
MIDFLOOR_PLENUM | 10-MAY-04:02 | 2487.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2514.72 |
FIRSTFLOOR_PLENUM | 02-AUG-04:03 | 3936.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4015.08 |
Total Facility | 06-FEB-06:02 | -192133.80 | 202230.69 | 0.00 | -202230.69 | 0.00 | 0.00 | 1508.44 | 1072.56 | 17291.51 | 0.00 | 0.00 | 0.00 | 177560.50 | 0.00 | -4904.31 | 0.00 | -394.90 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4364 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0209 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.7969 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3309 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2198 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7182 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3650 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3984 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3371 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6099 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4017 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9028 | 2.9028 | 0.7838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1521 | 2.1521 | 0.7511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2891 | 2.2891 | 0.7829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7533 | 0.7533 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6690 | 0.6690 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7341 | 0.7341 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7744 | 0.7744 | 0.1549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6466 | 0.6466 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6059 | 0.6059 | 0.1212 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6288 | 0.6288 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6523 | 0.6523 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6573 | 0.6573 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6444 | 0.6444 | 0.1289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6401 | 0.6401 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7030 | 0.7030 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4364 | 5.0209 | 5.4364 | 1.3650 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.7969 | 4.3309 | 4.7969 | 1.3371 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2198 | 5.0187 | 5.2198 | 1.4017 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4514 | 1.4514 | 0.7838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0760 | 1.0760 | 0.7511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1445 | 1.1445 | 0.7829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3767 | 0.3767 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3345 | 0.3345 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3670 | 0.3670 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3872 | 0.3872 | 0.1549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3233 | 0.3233 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3029 | 0.3029 | 0.1212 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3144 | 0.3144 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3262 | 0.3262 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3287 | 0.3287 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3222 | 0.3222 | 0.1289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3200 | 0.3200 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3515 | 0.3515 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7182 | 1.3650 | 1.3650 | 1.3650 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3984 | 1.3371 | 1.3371 | 1.3371 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6099 | 1.4017 | 1.4017 | 1.4017 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4982.19 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 738.17 |
Number of hours not met | 738.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 983.03 | 98231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 299.70 | 31270.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.51 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 846.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 118.30 | 15642.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 108.83 | 9347.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 2167.88 |
Natural Gas | 0.00 | 108.83 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2276.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.15 |
Space Heating | 0.00 |
Space Cooling | 197.31 |
Fans (All) | 23.74 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 435.13 |
Subtotal | 435.13 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 21.84 |
Miscellaneous (All) | 21.84 |
Subtotal | 21.84 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.16 |
Space Heating | 0.00 |
Space Cooling | 43.18 |
Fans (All) | 5.20 |
Service Water Heating | 4.78 |
Receptacle Equipment | 30.98 |
Miscellaneous | 2.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8045.50 | 714.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8695.67 | 64.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7854.33 | 905.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7722.83 | 1037.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7697.00 | 1063.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7577.67 | 1182.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8239.67 | 520.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7832.83 | 927.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7889.67 | 870.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7537.33 | 1222.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7999.00 | 761.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7832.50 | 927.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7825.67 | 934.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7607.17 | 1152.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8131.83 | 628.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
Min | 7537.33 | 25.00 | 0.00 | 0.00 | 0.00 |
Max | 8735.00 | 1222.67 | 0.00 | 0.00 | 0.00 |
Average | 8034.31 | 725.69 | 0.00 | 0.00 | 0.00 |
Sum | 144617.67 | 13062.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128181.33 | 122.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128293.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128294.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24677.50 | 231.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128294.33 | 231.50 | 0.00 | 0.00 | 0.00 |
Average | 34122.55 | 20.79 | 0.00 | 0.00 | 0.00 |
Sum | 614205.83 | 374.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6944.00 | 1816.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8494.33 | 265.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8502.17 | 257.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 4969.50 | 3790.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5028.00 | 3732.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 4890.67 | 3869.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5132.83 | 3627.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 5384.00 | 3376.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5205.17 | 3554.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 3404.00 | 5356.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5240.50 | 3519.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 4963.50 | 3796.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5031.00 | 3729.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 4871.83 | 3888.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5075.67 | 3684.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 5396.83 | 3363.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5559.00 | 3201.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 5903.33 | 2856.67 | 0.00 | 0.00 | 0.00 |
Min | 3404.00 | 257.83 | 0.00 | 0.00 | 0.00 |
Max | 8502.17 | 5356.00 | 0.00 | 0.00 | 0.00 |
Average | 5555.35 | 3204.65 | 0.00 | 0.00 | 0.00 |
Sum | 99996.33 | 57683.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127679.67 | 624.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128262.33 | 41.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128269.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24753.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24750.00 | 159.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24852.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16068.33 | 8840.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24768.17 | 140.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24765.17 | 143.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128269.00 | 8840.67 | 0.00 | 0.00 | 0.00 |
Average | 33576.75 | 566.58 | 0.00 | 0.00 | 0.00 |
Sum | 604381.50 | 10198.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290804E+11 | 44067.71 | 03-JAN-05:02 | 24.93 | 22.82 | 0.199419E+10 | 2606.54 | 02-JAN-14:30 | 24.93 | 22.82 |
February | 0.265417E+11 | 46630.56 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180807E+10 | 2606.54 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.307665E+11 | 43876.83 | 07-MAR-05:03 | 24.00 | 22.62 | 0.215842E+10 | 2606.54 | 03-MAR-10:20 | 24.00 | 22.62 |
April | 0.286344E+11 | 43364.16 | 08-APR-04:02 | 26.33 | 24.54 | 0.191596E+10 | 2606.55 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.304843E+11 | 43651.21 | 25-MAY-04:03 | 25.50 | 25.27 | 0.207548E+10 | 2606.54 | 01-MAY-13:20 | 25.50 | 25.27 |
June | 0.303348E+11 | 43500.24 | 01-JUN-04:03 | 24.17 | 24.06 | 0.206948E+10 | 2606.55 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.285347E+11 | 43745.10 | 18-JUL-04:23 | 24.00 | 23.32 | 0.192313E+10 | 2606.54 | 03-JUL-13:30 | 24.00 | 23.32 |
August | 0.302396E+11 | 44216.35 | 22-AUG-04:03 | 24.08 | 23.67 | 0.215912E+10 | 2606.55 | 03-AUG-13:00 | 24.08 | 23.67 |
September | 0.279904E+11 | 45498.14 | 19-SEP-05:03 | 24.00 | 24.00 | 0.191620E+10 | 2606.54 | 14-SEP-13:30 | 24.00 | 24.00 |
October | 0.285184E+11 | 44064.48 | 24-OCT-04:03 | 24.08 | 24.04 | 0.199347E+10 | 2606.54 | 30-OCT-13:30 | 24.25 | 24.19 |
November | 0.281382E+11 | 43874.81 | 07-NOV-05:03 | 24.00 | 23.42 | 0.197434E+10 | 2606.54 | 08-NOV-14:30 | 30.00 | 25.66 |
December | 0.277658E+11 | 41216.61 | 30-DEC-06:03 | 24.07 | 24.03 | 0.192387E+10 | 2606.54 | 04-DEC-14:30 | 24.07 | 24.03 |
Annual Sum or Average | 0.347029E+12 | 0.239117E+11 | ||||||||
Minimum of Months | 0.265417E+11 | 41216.61 | 23.95 | 22.59 | 0.180807E+10 | 2606.54 | 23.53 | 20.42 | ||
Maximum of Months | 0.307665E+11 | 46630.56 | 26.33 | 25.27 | 0.215912E+10 | 2606.55 | 36.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.687141E+10 | 9907.77 | 04-JAN-14:10 | 33.83 | 23.50 | 0.00 | 0.00 | 01-JAN-00:10 | 33.83 | 23.50 |
February | 0.685285E+10 | 10956.35 | 21-FEB-14:40 | 34.33 | 21.86 | 0.00 | 0.00 | 01-FEB-00:10 | 34.33 | 21.86 |
March | 0.828052E+10 | 11002.91 | 21-MAR-14:00 | 36.00 | 23.97 | 0.00 | 0.00 | 01-MAR-00:10 | 36.00 | 23.97 |
April | 0.795271E+10 | 10249.27 | 11-APR-14:30 | 34.85 | 26.00 | 0.00 | 0.00 | 01-APR-00:10 | 34.85 | 26.00 |
May | 0.797904E+10 | 11049.79 | 05-MAY-13:40 | 36.13 | 27.07 | 0.00 | 0.00 | 01-MAY-00:10 | 36.13 | 27.07 |
June | 0.836069E+10 | 10853.84 | 16-JUN-14:00 | 36.00 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 27.59 |
July | 0.679628E+10 | 9444.41 | 14-JUL-14:30 | 32.25 | 24.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.25 | 24.82 |
August | 0.688903E+10 | 9998.51 | 14-AUG-13:50 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.661891E+10 | 10001.21 | 06-SEP-14:00 | 34.00 | 26.51 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 26.51 |
October | 0.606799E+10 | 9539.70 | 04-OCT-13:50 | 32.88 | 26.26 | 0.00 | 0.00 | 01-OCT-00:10 | 32.88 | 26.26 |
November | 0.627171E+10 | 9437.52 | 22-NOV-13:02 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.632483E+10 | 9731.13 | 26-DEC-13:02 | 32.00 | 23.12 | 0.00 | 0.00 | 01-DEC-00:10 | 32.00 | 23.12 |
Annual Sum or Average | 0.852660E+11 | 0.00 | ||||||||
Minimum of Months | 0.606799E+10 | 9437.52 | 31.50 | 21.86 | 0.00 | 0.00 | 31.50 | 21.86 | ||
Maximum of Months | 0.836069E+10 | 11049.79 | 36.13 | 27.67 | 0.00 | 0.00 | 36.13 | 27.67 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425699E+10 | 5088.89 | 02-JAN-07:03 | 23.85 | 23.26 | 0.00 | 0.00 | 01-JAN-00:10 | 23.85 | 23.26 |
February | 0.408108E+10 | 5467.23 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.476584E+10 | 5231.24 | 20-MAR-15:20 | 34.77 | 24.85 | 0.00 | 0.00 | 01-MAR-00:10 | 34.77 | 24.85 |
April | 0.453211E+10 | 4842.35 | 17-APR-15:40 | 32.90 | 26.39 | 0.00 | 0.00 | 01-APR-00:10 | 32.90 | 26.39 |
May | 0.481776E+10 | 5247.39 | 30-MAY-12:02 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.500141E+10 | 5423.55 | 12-JUN-16:00 | 35.40 | 27.71 | 0.00 | 0.00 | 01-JUN-00:10 | 35.40 | 27.71 |
July | 0.416890E+10 | 4575.37 | 17-JUL-14:10 | 31.67 | 26.15 | 0.00 | 0.00 | 01-JUL-00:10 | 31.67 | 26.15 |
August | 0.425823E+10 | 4775.94 | 14-AUG-14:30 | 32.50 | 27.94 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 27.94 |
September | 0.400890E+10 | 4837.01 | 05-SEP-14:10 | 32.17 | 27.21 | 0.00 | 0.00 | 01-SEP-00:10 | 32.17 | 27.21 |
October | 0.393309E+10 | 4862.71 | 10-OCT-14:30 | 30.50 | 26.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.50 | 26.20 |
November | 0.397236E+10 | 5029.07 | 13-NOV-13:02 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.384394E+10 | 5063.91 | 26-DEC-16:00 | 30.20 | 22.54 | 0.00 | 0.00 | 01-DEC-00:10 | 30.20 | 22.54 |
Annual Sum or Average | 0.516406E+11 | 0.00 | ||||||||
Minimum of Months | 0.384394E+10 | 4575.37 | 23.85 | 22.54 | 0.00 | 0.00 | 23.85 | 22.54 | ||
Maximum of Months | 0.500141E+10 | 5467.23 | 35.40 | 27.94 | 0.00 | 0.00 | 35.40 | 27.94 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489046E+10 | 5491.94 | 02-JAN-13:10 | 30.25 | 24.20 | 0.00 | 0.00 | 01-JAN-00:10 | 30.25 | 24.20 |
February | 0.460913E+10 | 5655.47 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.534001E+10 | 5444.09 | 20-MAR-16:00 | 34.30 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.30 | 24.91 |
April | 0.504788E+10 | 5230.85 | 17-APR-15:50 | 32.75 | 26.32 | 0.00 | 0.00 | 01-APR-00:10 | 32.75 | 26.32 |
May | 0.539314E+10 | 5942.89 | 30-MAY-12:10 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.562608E+10 | 5851.58 | 12-JUN-12:08 | 34.05 | 27.94 | 0.00 | 0.00 | 01-JUN-00:10 | 34.05 | 27.94 |
July | 0.481150E+10 | 5213.39 | 17-JUL-12:30 | 31.40 | 25.74 | 0.00 | 0.00 | 01-JUL-00:10 | 31.40 | 25.74 |
August | 0.496181E+10 | 5418.67 | 14-AUG-12:08 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.460155E+10 | 5496.07 | 05-SEP-12:10 | 33.02 | 26.93 | 0.00 | 0.00 | 01-SEP-00:10 | 33.02 | 26.93 |
October | 0.453918E+10 | 5363.16 | 10-OCT-15:10 | 29.17 | 26.02 | 0.00 | 0.00 | 01-OCT-00:10 | 29.17 | 26.02 |
November | 0.461883E+10 | 5567.86 | 13-NOV-13:10 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.451114E+10 | 5396.06 | 26-DEC-07:03 | 23.17 | 21.69 | 0.00 | 0.00 | 01-DEC-00:10 | 23.17 | 21.69 |
Annual Sum or Average | 0.589507E+11 | 0.00 | ||||||||
Minimum of Months | 0.451114E+10 | 5213.39 | 23.17 | 21.69 | 0.00 | 0.00 | 23.17 | 21.69 | ||
Maximum of Months | 0.562608E+10 | 5942.89 | 34.30 | 27.94 | 0.00 | 0.00 | 34.30 | 27.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213610E+11 | 32868.08 | 10-JAN-05:02 | 23.95 | 22.91 | 0.198873E+10 | 2606.56 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.197357E+11 | 35485.20 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180381E+10 | 2606.53 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.229789E+11 | 32465.86 | 22-MAR-04:02 | 25.08 | 22.89 | 0.215397E+10 | 2606.54 | 03-MAR-10:09 | 25.08 | 22.89 |
April | 0.216609E+11 | 32254.29 | 05-APR-04:02 | 26.08 | 23.61 | 0.191208E+10 | 2606.54 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.229960E+11 | 32729.51 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207164E+10 | 2606.54 | 01-MAY-13:09 | 24.17 | 24.17 |
June | 0.228060E+11 | 32238.21 | 20-JUN-04:02 | 24.08 | 23.67 | 0.206606E+10 | 2606.54 | 16-JUN-13:00 | 24.08 | 23.67 |
July | 0.213189E+11 | 32578.55 | 25-JUL-04:02 | 25.08 | 24.00 | 0.191775E+10 | 2606.53 | 10-JUL-13:09 | 25.08 | 24.00 |
August | 0.222243E+11 | 32330.72 | 16-AUG-04:02 | 24.92 | 24.29 | 0.215337E+10 | 2606.54 | 03-AUG-13:00 | 24.92 | 24.29 |
September | 0.207613E+11 | 31987.62 | 14-SEP-04:02 | 25.50 | 24.23 | 0.191096E+10 | 2606.53 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.210854E+11 | 32417.21 | 17-OCT-04:02 | 25.00 | 24.24 | 0.198728E+10 | 2606.54 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.205867E+11 | 32965.47 | 21-NOV-05:02 | 24.08 | 22.25 | 0.196901E+10 | 2606.54 | 08-NOV-14:09 | 24.08 | 22.25 |
December | 0.203262E+11 | 31029.99 | 04-DEC-06:12 | 23.00 | 23.00 | 0.191678E+10 | 2606.55 | 21-DEC-10:09 | 26.17 | 20.56 |
Annual Sum or Average | 0.257841E+12 | 0.238514E+11 | ||||||||
Minimum of Months | 0.197357E+11 | 31029.99 | 23.00 | 22.25 | 0.180381E+10 | 2606.53 | 20.83 | 18.11 | ||
Maximum of Months | 0.229960E+11 | 35485.20 | 26.08 | 24.29 | 0.215397E+10 | 2606.56 | 33.50 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222165E+11 | 34971.71 | 09-JAN-05:02 | 23.92 | 23.24 | 0.198521E+10 | 2606.63 | 24-JAN-10:39 | 25.13 | 19.53 |
February | 0.208007E+11 | 37815.31 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180145E+10 | 2606.55 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.245528E+11 | 34791.76 | 06-MAR-05:02 | 24.00 | 21.84 | 0.215276E+10 | 2606.54 | 03-MAR-10:09 | 24.00 | 21.84 |
April | 0.235460E+11 | 34990.58 | 10-APR-04:02 | 25.17 | 23.75 | 0.191227E+10 | 2606.54 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.247234E+11 | 34711.43 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207145E+10 | 2606.54 | 25-MAY-13:09 | 31.17 | 27.76 |
June | 0.245842E+11 | 34901.92 | 26-JUN-04:02 | 24.00 | 23.59 | 0.206612E+10 | 2606.54 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.226316E+11 | 34834.06 | 17-JUL-04:02 | 24.42 | 23.35 | 0.191661E+10 | 2606.53 | 10-JUL-13:09 | 24.42 | 23.35 |
August | 0.234605E+11 | 34717.20 | 21-AUG-04:02 | 24.17 | 23.75 | 0.215146E+10 | 2606.54 | 17-AUG-13:00 | 24.17 | 23.75 |
September | 0.220534E+11 | 34554.75 | 14-SEP-04:02 | 25.50 | 24.23 | 0.190995E+10 | 2606.54 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.219998E+11 | 35202.38 | 02-OCT-04:02 | 24.00 | 23.36 | 0.198534E+10 | 2606.55 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.215464E+11 | 34995.50 | 13-NOV-05:02 | 25.00 | 24.24 | 0.196620E+10 | 2606.55 | 16-NOV-14:09 | 29.85 | 25.47 |
December | 0.211152E+11 | 33352.50 | 09-DEC-06:03 | 24.15 | 23.94 | 0.191178E+10 | 2606.61 | 21-DEC-10:09 | 26.17 | 20.56 |
Annual Sum or Average | 0.273231E+12 | 0.238306E+11 | ||||||||
Minimum of Months | 0.208007E+11 | 33352.50 | 23.92 | 21.84 | 0.180145E+10 | 2606.53 | 24.00 | 19.53 | ||
Maximum of Months | 0.247234E+11 | 37815.31 | 25.50 | 24.24 | 0.215276E+10 | 2606.63 | 34.17 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.628158E+10 | 9058.43 | 08-JAN-16:02 | 31.42 | 23.26 | 0.419311E+09 | 549.49 | 24-JAN-10:39 | 25.13 | 19.53 |
February | 0.609904E+10 | 11536.37 | 26-FEB-17:02 | 29.83 | 22.66 | 0.380886E+09 | 549.48 | 15-FEB-14:00 | 29.83 | 22.66 |
March | 0.749438E+10 | 12762.39 | 19-MAR-16:52 | 32.00 | 24.03 | 0.455037E+09 | 549.47 | 03-MAR-10:09 | 32.00 | 24.03 |
April | 0.749817E+10 | 12617.08 | 30-APR-12:53 | 33.70 | 26.84 | 0.404602E+09 | 549.47 | 20-APR-13:00 | 33.70 | 26.84 |
May | 0.859701E+10 | 13013.80 | 28-MAY-12:02 | 33.17 | 27.16 | 0.438357E+09 | 549.47 | 09-MAY-13:00 | 33.17 | 27.16 |
June | 0.924364E+10 | 13695.46 | 18-JUN-13:22 | 35.20 | 27.23 | 0.437057E+09 | 549.48 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.761670E+10 | 12963.75 | 04-JUL-17:42 | 27.67 | 24.91 | 0.406019E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.744173E+10 | 12826.36 | 13-AUG-12:53 | 34.00 | 28.60 | 0.455099E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.667205E+10 | 12642.53 | 04-SEP-12:53 | 32.50 | 27.43 | 0.404150E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.631497E+10 | 11783.87 | 09-OCT-13:32 | 29.20 | 26.08 | 0.420049E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.614114E+10 | 9507.84 | 05-NOV-14:32 | 30.67 | 24.44 | 0.415774E+09 | 549.47 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.587507E+10 | 6756.75 | 26-DEC-14:10 | 31.17 | 22.67 | 0.404023E+09 | 549.48 | 21-DEC-10:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.852755E+11 | 0.504036E+10 | ||||||||
Minimum of Months | 0.587507E+10 | 6756.75 | 27.67 | 22.66 | 0.380886E+09 | 549.47 | 25.00 | 19.53 | ||
Maximum of Months | 0.924364E+10 | 13695.46 | 35.20 | 28.60 | 0.455099E+09 | 549.49 | 34.00 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515131E+10 | 9923.41 | 16-JAN-11:02 | 29.63 | 21.29 | 0.265944E+09 | 347.88 | 24-JAN-10:39 | 25.13 | 19.53 |
February | 0.512734E+10 | 11395.48 | 20-FEB-08:53 | 28.00 | 23.69 | 0.241484E+09 | 347.86 | 15-FEB-14:00 | 28.00 | 23.69 |
March | 0.635158E+10 | 12107.81 | 26-MAR-10:42 | 32.97 | 25.11 | 0.288230E+09 | 347.86 | 03-MAR-10:20 | 32.97 | 25.11 |
April | 0.622439E+10 | 11666.31 | 23-APR-09:13 | 28.07 | 23.90 | 0.256263E+09 | 347.86 | 20-APR-13:00 | 28.07 | 23.90 |
May | 0.618613E+10 | 11625.59 | 07-MAY-08:62 | 31.17 | 27.28 | 0.277334E+09 | 347.86 | 30-MAY-09:00 | 33.40 | 27.88 |
June | 0.631496E+10 | 12133.96 | 11-JUN-09:52 | 33.10 | 28.50 | 0.276497E+09 | 347.86 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.530643E+10 | 11184.35 | 30-JUL-10:02 | 29.67 | 24.39 | 0.256755E+09 | 347.86 | 11-JUL-13:00 | 29.67 | 24.39 |
August | 0.569839E+10 | 11704.17 | 13-AUG-08:53 | 31.00 | 27.87 | 0.287980E+09 | 347.86 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.529239E+10 | 11703.88 | 10-SEP-09:23 | 30.30 | 26.10 | 0.255876E+09 | 347.86 | 14-SEP-09:09 | 30.13 | 26.40 |
October | 0.498746E+10 | 11638.09 | 08-OCT-09:23 | 30.00 | 26.31 | 0.265873E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.484573E+10 | 9703.67 | 05-NOV-11:13 | 30.67 | 23.05 | 0.263344E+09 | 347.86 | 17-NOV-10:20 | 28.93 | 25.06 |
December | 0.476449E+10 | 10249.44 | 31-DEC-10:53 | 31.00 | 25.04 | 0.256335E+09 | 347.87 | 21-DEC-10:09 | 31.00 | 25.04 |
Annual Sum or Average | 0.662506E+11 | 0.319192E+10 | ||||||||
Minimum of Months | 0.476449E+10 | 9703.67 | 28.00 | 21.29 | 0.241484E+09 | 347.86 | 25.13 | 19.53 | ||
Maximum of Months | 0.635158E+10 | 12133.96 | 33.10 | 28.50 | 0.288230E+09 | 347.88 | 33.40 | 28.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.909855E+10 | 13349.53 | 08-JAN-16:02 | 31.42 | 23.26 | 0.421596E+09 | 573.23 | 04-JAN-14:09 | 31.42 | 23.26 |
February | 0.821151E+10 | 13145.96 | 26-FEB-12:23 | 33.25 | 24.69 | 0.381954E+09 | 568.81 | 21-FEB-14:20 | 33.25 | 24.69 |
March | 0.855897E+10 | 12829.19 | 26-MAR-12:43 | 34.42 | 25.47 | 0.455332E+09 | 549.47 | 02-MAR-14:00 | 34.42 | 25.47 |
April | 0.738382E+10 | 12298.37 | 16-APR-13:13 | 33.63 | 26.91 | 0.404547E+09 | 549.47 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.778261E+10 | 12275.62 | 07-MAY-14:42 | 34.00 | 27.16 | 0.438039E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 26.97 |
June | 0.770740E+10 | 12747.44 | 18-JUN-13:22 | 35.20 | 27.23 | 0.436688E+09 | 549.47 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.676775E+10 | 12131.67 | 30-JUL-14:43 | 31.33 | 25.41 | 0.405592E+09 | 549.47 | 11-JUL-13:00 | 31.33 | 25.41 |
August | 0.704348E+10 | 12273.25 | 13-AUG-12:53 | 34.00 | 28.60 | 0.454901E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.696446E+10 | 12475.50 | 04-SEP-12:53 | 32.50 | 27.43 | 0.404231E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.736130E+10 | 13108.24 | 29-OCT-11:43 | 31.50 | 26.00 | 0.420513E+09 | 549.48 | 13-OCT-13:09 | 31.50 | 26.00 |
November | 0.805130E+10 | 13184.52 | 23-NOV-11:43 | 30.88 | 24.99 | 0.416658E+09 | 549.48 | 22-NOV-14:00 | 30.88 | 24.99 |
December | 0.861048E+10 | 13224.73 | 25-DEC-11:23 | 29.00 | 24.27 | 0.406930E+09 | 575.81 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.935416E+11 | 0.504698E+10 | ||||||||
Minimum of Months | 0.676775E+10 | 12131.67 | 29.00 | 23.26 | 0.381954E+09 | 549.47 | 29.00 | 22.67 | ||
Maximum of Months | 0.909855E+10 | 13349.53 | 35.20 | 28.60 | 0.455332E+09 | 575.81 | 34.50 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527049E+10 | 13731.02 | 29-JAN-16:42 | 31.22 | 23.22 | 0.264190E+09 | 347.84 | 24-JAN-10:00 | 31.22 | 23.22 |
February | 0.519133E+10 | 13548.54 | 26-FEB-17:02 | 29.83 | 22.66 | 0.240186E+09 | 347.84 | 15-FEB-14:00 | 29.83 | 22.66 |
March | 0.642509E+10 | 13785.46 | 19-MAR-15:32 | 34.80 | 24.95 | 0.287291E+09 | 347.84 | 03-MAR-10:09 | 34.80 | 24.95 |
April | 0.620685E+10 | 13653.45 | 02-APR-15:42 | 33.75 | 27.23 | 0.255608E+09 | 347.84 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.614578E+10 | 13209.69 | 14-MAY-15:42 | 34.83 | 27.45 | 0.276604E+09 | 347.83 | 30-MAY-09:09 | 31.40 | 27.36 |
June | 0.622377E+10 | 13477.59 | 11-JUN-15:52 | 34.50 | 28.11 | 0.275920E+09 | 347.84 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.531074E+10 | 13737.77 | 04-JUL-17:42 | 27.67 | 24.91 | 0.255682E+09 | 347.83 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.562229E+10 | 13260.47 | 27-AUG-16:12 | 32.67 | 25.94 | 0.286994E+09 | 347.83 | 25-AUG-13:00 | 32.67 | 25.94 |
September | 0.525521E+10 | 13352.80 | 04-SEP-16:12 | 32.67 | 26.80 | 0.254911E+09 | 347.84 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.502856E+10 | 12015.30 | 15-OCT-17:03 | 28.42 | 25.82 | 0.264634E+09 | 347.84 | 13-OCT-13:00 | 28.42 | 25.82 |
November | 0.493067E+10 | 11797.93 | 19-NOV-17:03 | 29.42 | 25.42 | 0.262165E+09 | 347.84 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.489633E+10 | 11947.51 | 03-DEC-16:42 | 28.67 | 22.76 | 0.254234E+09 | 347.84 | 08-DEC-14:00 | 33.00 | 23.65 |
Annual Sum or Average | 0.665071E+11 | 0.317842E+10 | ||||||||
Minimum of Months | 0.489633E+10 | 11797.93 | 27.67 | 22.66 | 0.240186E+09 | 347.83 | 25.00 | 22.66 | ||
Maximum of Months | 0.642509E+10 | 13785.46 | 34.83 | 28.11 | 0.287291E+09 | 347.84 | 34.80 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.630877E+10 | 7512.82 | 02-JAN-07:03 | 23.85 | 23.26 | 0.420035E+09 | 549.48 | 09-JAN-14:00 | 31.00 | 24.49 |
February | 0.601803E+10 | 8713.13 | 21-FEB-05:02 | 25.00 | 21.63 | 0.381213E+09 | 549.48 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.721257E+10 | 8721.71 | 20-MAR-04:02 | 27.08 | 23.58 | 0.455113E+09 | 549.47 | 03-MAR-10:09 | 27.08 | 23.58 |
April | 0.720971E+10 | 8944.94 | 11-APR-04:02 | 27.00 | 25.07 | 0.404433E+09 | 549.47 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.849614E+10 | 11047.81 | 07-MAY-14:31 | 34.00 | 27.03 | 0.438488E+09 | 549.47 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.921030E+10 | 11493.23 | 11-JUN-13:52 | 35.00 | 28.16 | 0.437252E+09 | 549.87 | 12-JUN-13:00 | 34.00 | 27.86 |
July | 0.783774E+10 | 11028.54 | 04-JUL-17:42 | 27.67 | 24.91 | 0.406324E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.765831E+10 | 9014.15 | 29-AUG-04:02 | 25.33 | 24.59 | 0.455487E+09 | 549.47 | 25-AUG-13:00 | 25.33 | 24.59 |
September | 0.682002E+10 | 9036.20 | 18-SEP-04:02 | 25.42 | 25.21 | 0.404373E+09 | 549.47 | 07-SEP-13:00 | 25.42 | 25.21 |
October | 0.640539E+10 | 8930.27 | 02-OCT-04:02 | 24.00 | 23.36 | 0.420429E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.624365E+10 | 8423.10 | 24-NOV-05:02 | 24.42 | 21.44 | 0.416188E+09 | 549.47 | 08-NOV-14:00 | 24.42 | 21.44 |
December | 0.596117E+10 | 6969.86 | 26-DEC-07:03 | 23.17 | 21.69 | 0.405227E+09 | 549.47 | 04-DEC-14:00 | 23.17 | 21.69 |
Annual Sum or Average | 0.853818E+11 | 0.504456E+10 | ||||||||
Minimum of Months | 0.596117E+10 | 6969.86 | 23.17 | 21.44 | 0.381213E+09 | 549.47 | 21.92 | 19.78 | ||
Maximum of Months | 0.921030E+10 | 11493.23 | 35.00 | 28.16 | 0.455487E+09 | 549.87 | 34.00 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.518896E+10 | 7818.93 | 16-JAN-11:23 | 29.90 | 21.44 | 0.266389E+09 | 347.86 | 31-JAN-10:09 | 24.17 | 21.37 |
February | 0.510695E+10 | 10482.71 | 20-FEB-09:13 | 28.47 | 23.42 | 0.241796E+09 | 347.86 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.619398E+10 | 10805.18 | 26-MAR-10:42 | 32.97 | 25.11 | 0.288534E+09 | 347.86 | 03-MAR-10:30 | 32.97 | 25.11 |
April | 0.602954E+10 | 10704.34 | 09-APR-09:23 | 31.45 | 26.05 | 0.256410E+09 | 347.86 | 24-APR-09:30 | 30.65 | 25.59 |
May | 0.609477E+10 | 10484.52 | 07-MAY-09:52 | 33.20 | 27.88 | 0.277676E+09 | 347.86 | 30-MAY-09:30 | 32.20 | 27.59 |
June | 0.625789E+10 | 10816.43 | 11-JUN-09:52 | 33.10 | 28.50 | 0.276751E+09 | 347.86 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.539034E+10 | 9237.97 | 30-JUL-10:32 | 30.17 | 24.41 | 0.257191E+09 | 347.86 | 17-JUL-13:00 | 30.17 | 24.41 |
August | 0.581382E+10 | 10372.66 | 27-AUG-08:53 | 31.00 | 28.65 | 0.288485E+09 | 347.86 | 28-AUG-09:30 | 30.95 | 26.94 |
September | 0.537568E+10 | 10627.39 | 04-SEP-09:53 | 30.20 | 27.28 | 0.256307E+09 | 347.86 | 14-SEP-09:30 | 30.40 | 26.60 |
October | 0.501117E+10 | 10400.42 | 08-OCT-09:43 | 30.33 | 26.40 | 0.266420E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.490186E+10 | 7979.77 | 23-NOV-09:32 | 28.77 | 23.95 | 0.263853E+09 | 347.86 | 06-NOV-10:30 | 28.77 | 23.95 |
December | 0.483125E+10 | 8252.83 | 31-DEC-10:53 | 31.00 | 25.04 | 0.257047E+09 | 347.86 | 29-DEC-10:30 | 31.00 | 25.04 |
Annual Sum or Average | 0.661962E+11 | 0.319686E+10 | ||||||||
Minimum of Months | 0.483125E+10 | 7818.93 | 28.47 | 21.44 | 0.241796E+09 | 347.86 | 23.53 | 20.42 | ||
Maximum of Months | 0.625789E+10 | 10816.43 | 33.20 | 28.65 | 0.288534E+09 | 347.86 | 32.97 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102119E+11 | 11599.00 | 29-JAN-13:52 | 32.00 | 23.45 | 0.438106E+09 | 732.67 | 04-JAN-13:09 | 32.00 | 23.45 |
February | 0.924269E+10 | 11430.36 | 21-FEB-13:00 | 34.10 | 22.08 | 0.398646E+09 | 725.86 | 21-FEB-13:09 | 34.25 | 22.07 |
March | 0.101962E+11 | 11312.39 | 21-MAR-12:00 | 35.00 | 23.21 | 0.466434E+09 | 715.42 | 21-MAR-12:09 | 35.23 | 23.19 |
April | 0.901087E+10 | 10808.69 | 18-APR-12:00 | 34.00 | 26.52 | 0.410455E+09 | 673.94 | 18-APR-12:09 | 34.03 | 26.51 |
May | 0.964724E+10 | 11745.51 | 05-MAY-12:00 | 37.00 | 25.95 | 0.445232E+09 | 744.57 | 05-MAY-12:09 | 36.90 | 26.19 |
June | 0.968567E+10 | 11194.14 | 16-JUN-12:00 | 35.00 | 28.16 | 0.444035E+09 | 699.65 | 16-JUN-12:09 | 35.17 | 28.24 |
July | 0.823399E+10 | 10312.14 | 26-JUL-17:00 | 33.00 | 26.23 | 0.409093E+09 | 622.89 | 27-JUL-12:09 | 31.48 | 25.75 |
August | 0.895822E+10 | 10817.76 | 15-AUG-12:00 | 33.70 | 27.96 | 0.459840E+09 | 672.13 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.854803E+10 | 10653.12 | 05-SEP-12:00 | 33.00 | 26.98 | 0.408835E+09 | 661.96 | 05-SEP-12:09 | 33.02 | 26.93 |
October | 0.874427E+10 | 11158.02 | 29-OCT-11:43 | 31.50 | 26.00 | 0.425677E+09 | 661.85 | 04-OCT-12:09 | 31.50 | 26.00 |
November | 0.941542E+10 | 11193.52 | 23-NOV-11:32 | 30.77 | 24.95 | 0.426852E+09 | 666.56 | 22-NOV-13:09 | 30.77 | 24.95 |
December | 0.966290E+10 | 11622.87 | 25-DEC-12:32 | 30.00 | 24.38 | 0.421168E+09 | 703.11 | 26-DEC-13:09 | 32.00 | 23.12 |
Annual Sum or Average | 0.111557E+12 | 0.515437E+10 | ||||||||
Minimum of Months | 0.823399E+10 | 10312.14 | 30.00 | 22.08 | 0.398646E+09 | 622.89 | 30.77 | 22.07 | ||
Maximum of Months | 0.102119E+11 | 11745.51 | 37.00 | 28.16 | 0.466434E+09 | 744.57 | 36.90 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.518051E+10 | 11523.90 | 29-JAN-17:12 | 30.67 | 23.11 | 0.266152E+09 | 347.84 | 09-JAN-14:00 | 30.67 | 23.11 |
February | 0.505848E+10 | 11637.14 | 20-FEB-16:32 | 31.03 | 23.92 | 0.241541E+09 | 347.84 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.618007E+10 | 11500.42 | 05-MAR-16:42 | 28.37 | 23.27 | 0.288403E+09 | 347.84 | 03-MAR-10:09 | 28.37 | 23.27 |
April | 0.593742E+10 | 11507.24 | 02-APR-16:22 | 32.75 | 27.02 | 0.256252E+09 | 347.84 | 24-APR-09:30 | 30.65 | 25.59 |
May | 0.598518E+10 | 11298.11 | 07-MAY-15:51 | 33.20 | 28.05 | 0.277485E+09 | 347.84 | 30-MAY-09:09 | 31.40 | 27.36 |
June | 0.613335E+10 | 11345.91 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276638E+09 | 347.84 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.531633E+10 | 11595.68 | 04-JUL-17:42 | 27.67 | 24.91 | 0.257068E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.567322E+10 | 10825.26 | 27-AUG-16:12 | 32.67 | 25.94 | 0.288379E+09 | 347.84 | 25-AUG-13:00 | 32.67 | 25.94 |
September | 0.526206E+10 | 11773.04 | 10-SEP-15:12 | 30.67 | 26.54 | 0.256104E+09 | 347.84 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.496066E+10 | 10661.93 | 08-OCT-15:02 | 31.22 | 25.87 | 0.266244E+09 | 347.84 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.487580E+10 | 9605.23 | 19-NOV-17:03 | 29.42 | 25.42 | 0.263598E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.482275E+10 | 11592.36 | 25-DEC-16:32 | 29.67 | 23.46 | 0.256715E+09 | 347.84 | 08-DEC-14:00 | 29.67 | 23.46 |
Annual Sum or Average | 0.653858E+11 | 0.319458E+10 | ||||||||
Minimum of Months | 0.482275E+10 | 9605.23 | 27.67 | 23.11 | 0.241541E+09 | 347.84 | 21.92 | 19.78 | ||
Maximum of Months | 0.618007E+10 | 11773.04 | 33.50 | 28.05 | 0.288403E+09 | 347.84 | 32.67 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602089E+10 | 9099.89 | 02-JAN-06:12 | 23.37 | 23.04 | 0.419876E+09 | 549.48 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.577659E+10 | 9339.98 | 27-FEB-05:02 | 24.00 | 22.49 | 0.381194E+09 | 549.48 | 15-FEB-14:00 | 24.00 | 22.49 |
March | 0.700950E+10 | 10465.93 | 19-MAR-16:52 | 32.00 | 24.03 | 0.455153E+09 | 549.47 | 03-MAR-10:09 | 32.00 | 24.03 |
April | 0.692566E+10 | 8930.41 | 18-APR-04:02 | 26.92 | 25.08 | 0.404520E+09 | 549.47 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.801244E+10 | 11259.71 | 28-MAY-12:02 | 33.17 | 27.16 | 0.438401E+09 | 549.47 | 09-MAY-13:00 | 33.17 | 27.16 |
June | 0.861161E+10 | 11522.41 | 18-JUN-12:53 | 34.40 | 27.45 | 0.437072E+09 | 549.47 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.716866E+10 | 11207.82 | 04-JUL-17:42 | 27.67 | 24.91 | 0.406105E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.704313E+10 | 10467.91 | 13-AUG-12:53 | 34.00 | 28.60 | 0.455270E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.628033E+10 | 10749.43 | 10-SEP-15:12 | 30.67 | 26.54 | 0.404237E+09 | 549.47 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.603292E+10 | 8952.56 | 10-OCT-04:02 | 24.00 | 23.63 | 0.420300E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.586949E+10 | 9304.02 | 20-NOV-05:02 | 24.00 | 22.62 | 0.416083E+09 | 549.47 | 24-NOV-14:00 | 29.00 | 22.42 |
December | 0.563713E+10 | 7333.63 | 26-DEC-07:03 | 23.17 | 21.69 | 0.404848E+09 | 549.47 | 04-DEC-14:00 | 23.17 | 21.69 |
Annual Sum or Average | 0.803884E+11 | 0.504306E+10 | ||||||||
Minimum of Months | 0.563713E+10 | 7333.63 | 23.17 | 21.69 | 0.381194E+09 | 549.47 | 20.83 | 18.11 | ||
Maximum of Months | 0.861161E+10 | 11522.41 | 34.40 | 28.60 | 0.455270E+09 | 549.48 | 33.50 | 27.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487186E+10 | 8314.76 | 16-JAN-11:23 | 29.90 | 21.44 | 0.197012E+09 | 338.72 | 23-JAN-08:20 | 22.27 | 18.63 |
February | 0.480590E+10 | 11210.83 | 20-FEB-09:13 | 28.47 | 23.42 | 0.178834E+09 | 338.73 | 24-FEB-08:20 | 23.67 | 18.66 |
March | 0.589182E+10 | 11512.55 | 26-MAR-10:42 | 32.97 | 25.11 | 0.212903E+09 | 338.72 | 21-MAR-12:20 | 32.97 | 25.11 |
April | 0.571345E+10 | 11191.67 | 23-APR-09:13 | 28.07 | 23.90 | 0.189690E+09 | 338.72 | 13-APR-12:20 | 28.07 | 23.90 |
May | 0.570048E+10 | 11155.79 | 07-MAY-08:62 | 31.17 | 27.28 | 0.205165E+09 | 338.72 | 01-MAY-12:20 | 31.17 | 27.28 |
June | 0.581808E+10 | 11559.27 | 11-JUN-09:52 | 33.10 | 28.50 | 0.204275E+09 | 338.72 | 23-JUN-12:20 | 33.33 | 26.58 |
July | 0.492699E+10 | 10164.95 | 30-JUL-10:02 | 29.67 | 24.39 | 0.190254E+09 | 338.71 | 14-JUL-12:20 | 29.67 | 24.39 |
August | 0.531682E+10 | 11199.12 | 13-AUG-08:53 | 31.00 | 27.87 | 0.212710E+09 | 338.72 | 15-AUG-12:20 | 32.93 | 27.75 |
September | 0.491537E+10 | 11152.81 | 03-SEP-08:53 | 30.00 | 26.93 | 0.189388E+09 | 338.72 | 12-SEP-12:20 | 32.73 | 26.56 |
October | 0.468722E+10 | 11123.60 | 08-OCT-09:13 | 29.83 | 26.26 | 0.196953E+09 | 338.72 | 13-OCT-12:20 | 31.97 | 26.42 |
November | 0.455586E+10 | 9071.50 | 23-NOV-09:32 | 28.77 | 23.95 | 0.195088E+09 | 338.72 | 08-NOV-13:20 | 28.77 | 23.95 |
December | 0.450862E+10 | 9187.47 | 31-DEC-10:53 | 31.00 | 25.04 | 0.190021E+09 | 338.72 | 21-DEC-08:20 | 31.00 | 25.04 |
Annual Sum or Average | 0.617125E+11 | 0.236229E+10 | ||||||||
Minimum of Months | 0.450862E+10 | 8314.76 | 28.07 | 21.44 | 0.178834E+09 | 338.71 | 22.27 | 18.63 | ||
Maximum of Months | 0.589182E+10 | 11559.27 | 33.10 | 28.50 | 0.212903E+09 | 338.73 | 33.33 | 27.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867588E+10 | 11865.83 | 29-JAN-13:12 | 31.00 | 23.14 | 0.423690E+09 | 585.36 | 04-JAN-14:09 | 31.00 | 23.14 |
February | 0.776957E+10 | 11474.60 | 20-FEB-11:13 | 30.83 | 23.81 | 0.383045E+09 | 580.75 | 21-FEB-14:09 | 34.83 | 21.98 |
March | 0.800828E+10 | 11074.29 | 26-MAR-12:43 | 34.42 | 25.47 | 0.455465E+09 | 549.47 | 06-MAR-14:00 | 34.42 | 25.47 |
April | 0.682007E+10 | 8765.58 | 18-APR-04:02 | 26.92 | 25.08 | 0.404469E+09 | 549.47 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.724873E+10 | 8491.61 | 07-MAY-14:42 | 34.00 | 27.16 | 0.438074E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 26.97 |
June | 0.717222E+10 | 10366.06 | 11-JUN-13:52 | 35.00 | 28.16 | 0.436661E+09 | 549.47 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.636609E+10 | 9179.01 | 17-JUL-04:02 | 24.42 | 23.35 | 0.405734E+09 | 549.47 | 11-JUL-13:00 | 24.42 | 23.35 |
August | 0.666697E+10 | 8955.34 | 28-AUG-04:02 | 25.33 | 24.05 | 0.455116E+09 | 549.47 | 25-AUG-13:00 | 25.33 | 24.05 |
September | 0.655173E+10 | 10723.13 | 10-SEP-15:12 | 30.67 | 26.54 | 0.404332E+09 | 549.47 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.701680E+10 | 11400.76 | 29-OCT-11:43 | 31.50 | 26.00 | 0.420751E+09 | 549.47 | 13-OCT-13:09 | 31.50 | 26.00 |
November | 0.768908E+10 | 11426.71 | 23-NOV-11:32 | 30.77 | 24.95 | 0.417084E+09 | 557.01 | 20-NOV-14:09 | 30.77 | 24.95 |
December | 0.823063E+10 | 11899.26 | 03-DEC-12:32 | 31.33 | 25.50 | 0.409265E+09 | 589.68 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.882161E+11 | 0.505369E+10 | ||||||||
Minimum of Months | 0.636609E+10 | 8491.61 | 24.42 | 23.14 | 0.383045E+09 | 549.47 | 24.42 | 21.98 | ||
Maximum of Months | 0.867588E+10 | 11899.26 | 35.00 | 28.16 | 0.455465E+09 | 589.68 | 34.83 | 28.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498721E+10 | 12416.67 | 29-JAN-16:32 | 31.43 | 23.24 | 0.265318E+09 | 347.84 | 24-JAN-10:09 | 31.43 | 23.24 |
February | 0.487823E+10 | 12457.63 | 20-FEB-16:32 | 31.03 | 23.92 | 0.240944E+09 | 347.84 | 15-FEB-14:00 | 31.03 | 23.92 |
March | 0.599246E+10 | 12401.54 | 05-MAR-16:42 | 28.37 | 23.27 | 0.287884E+09 | 347.84 | 03-MAR-10:09 | 28.37 | 23.27 |
April | 0.572214E+10 | 12420.90 | 23-APR-15:52 | 33.20 | 24.64 | 0.255937E+09 | 347.83 | 20-APR-13:00 | 33.20 | 24.64 |
May | 0.570363E+10 | 11972.18 | 14-MAY-15:42 | 34.83 | 27.45 | 0.277002E+09 | 347.83 | 30-MAY-09:09 | 31.40 | 27.36 |
June | 0.578404E+10 | 12139.57 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276229E+09 | 347.84 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.495186E+10 | 12398.87 | 04-JUL-17:42 | 27.67 | 24.91 | 0.256338E+09 | 347.83 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.528764E+10 | 12039.69 | 27-AUG-16:12 | 32.67 | 25.94 | 0.287667E+09 | 347.83 | 25-AUG-13:00 | 32.67 | 25.94 |
September | 0.491077E+10 | 12648.08 | 10-SEP-15:12 | 30.67 | 26.54 | 0.255452E+09 | 347.84 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.474392E+10 | 10549.98 | 15-OCT-17:03 | 28.42 | 25.82 | 0.265448E+09 | 347.83 | 13-OCT-13:00 | 28.42 | 25.82 |
November | 0.465002E+10 | 10176.26 | 19-NOV-17:03 | 29.42 | 25.42 | 0.262924E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.463077E+10 | 12465.68 | 25-DEC-16:32 | 29.67 | 23.46 | 0.255659E+09 | 347.84 | 08-DEC-14:00 | 29.67 | 23.46 |
Annual Sum or Average | 0.622427E+11 | 0.318680E+10 | ||||||||
Minimum of Months | 0.463077E+10 | 10176.26 | 27.67 | 23.24 | 0.240944E+09 | 347.83 | 25.00 | 23.24 | ||
Maximum of Months | 0.599246E+10 | 12648.08 | 34.83 | 27.84 | 0.287884E+09 | 347.84 | 33.20 | 28.03 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16610140.19 | 3708.89 | 09-JAN-05:02 | 23.92 |
February | 15935145.99 | 5253.85 | 06-FEB-06:02 | 23.95 |
March | 15349695.83 | 4069.90 | 20-MAR-04:02 | 27.08 |
April | 14533443.83 | 3765.30 | 10-APR-04:02 | 25.17 |
May | 12735352.20 | 3476.69 | 15-MAY-04:02 | 26.33 |
June | 12273311.76 | 3931.85 | 12-JUN-04:02 | 26.33 |
July | 14348425.42 | 4149.20 | 17-JUL-04:02 | 24.42 |
August | 13660188.70 | 3999.85 | 28-AUG-04:02 | 25.33 |
September | 13876377.59 | 3980.74 | 25-SEP-04:02 | 26.00 |
October | 13170255.33 | 4047.86 | 02-OCT-04:02 | 24.00 |
November | 13253114.77 | 4264.92 | 13-NOV-05:02 | 25.00 |
December | 17743408.30 | 2806.28 | 09-DEC-06:03 | 24.15 |
Annual Sum or Average | 0.173489E+09 | |||
Minimum of Months | 12273311.76 | 2806.28 | 23.92 | |
Maximum of Months | 17743408.30 | 5253.85 | 27.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9528359.04 | 1744.53 | 09-JAN-05:02 | 23.92 |
February | 7728327.61 | 1805.17 | 06-FEB-06:02 | 23.95 |
March | 10646381.06 | 2129.72 | 28-MAR-04:02 | 27.25 |
April | 10107761.95 | 2231.03 | 12-APR-04:02 | 27.08 |
May | 10395250.44 | 2487.40 | 10-MAY-04:02 | 28.33 |
June | 9261639.77 | 2288.11 | 06-JUN-04:02 | 26.83 |
July | 8669428.14 | 2086.30 | 24-JUL-04:02 | 25.67 |
August | 9060762.05 | 2403.63 | 02-AUG-04:03 | 29.25 |
September | 9061211.13 | 2286.07 | 18-SEP-04:02 | 25.42 |
October | 8971397.20 | 2077.14 | 26-OCT-05:03 | 25.00 |
November | 9971204.71 | 2124.54 | 24-NOV-05:02 | 24.42 |
December | 9810438.27 | 1782.49 | 17-DEC-10:10 | 26.33 |
Annual Sum or Average | 0.113212E+09 | |||
Minimum of Months | 7728327.61 | 1744.53 | 23.92 | |
Maximum of Months | 10646381.06 | 2487.40 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16754073.24 | 3378.34 | 03-JAN-05:02 | 24.93 |
February | 13332715.10 | 3213.13 | 16-FEB-05:03 | 25.00 |
March | 18088459.45 | 3574.93 | 30-MAR-04:02 | 26.83 |
April | 16893544.12 | 3667.89 | 06-APR-04:02 | 26.58 |
May | 18416031.38 | 3817.63 | 10-MAY-04:02 | 28.33 |
June | 17110813.10 | 3764.47 | 06-JUN-04:02 | 26.83 |
July | 17958358.87 | 3614.75 | 06-JUL-04:02 | 25.17 |
August | 18301542.79 | 3937.40 | 02-AUG-04:03 | 29.25 |
September | 18058562.41 | 3836.44 | 28-SEP-04:02 | 25.67 |
October | 18310493.22 | 3534.11 | 03-OCT-04:02 | 25.58 |
November | 18161640.03 | 3414.61 | 14-NOV-05:03 | 26.00 |
December | 14093109.27 | 2522.39 | 09-DEC-05:03 | 24.00 |
Annual Sum or Average | 0.205479E+09 | |||
Minimum of Months | 13332715.10 | 2522.39 | 24.00 | |
Maximum of Months | 18416031.38 | 3937.40 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745435E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.664175E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.768129E+09 | 947.97 | 01-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668725E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.722885E+09 | 774.31 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710918E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.669309E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.750374E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.683661E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.720365E+09 | 947.97 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.744246E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.733009E+09 | 1184.79 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.858123E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664175E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.768129E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471708E+09 | 750.07 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.422222E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487889E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426731E+09 | 450.21 | 10-APR-15:09 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462926E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.456809E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430246E+09 | 450.21 | 03-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479176E+09 | 450.21 | 02-AUG-15:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434906E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.456963E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474037E+09 | 860.01 | 09-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.463911E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546752E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.422222E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487889E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.722044E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.653291E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764067E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674123E+09 | 774.31 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.733917E+09 | 774.31 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.724664E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.683493E+09 | 774.31 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.759327E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683987E+09 | 774.31 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.710827E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721991E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705762E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853749E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.653291E+09 | 754.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.764067E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.459784E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413758E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483358E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425849E+09 | 600.10 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462272E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455503E+09 | 600.10 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430661E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479672E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434267E+09 | 600.10 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.453453E+09 | 600.10 | 10-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.456759E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.448746E+09 | 750.02 | 18-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.540408E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413758E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.483358E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743012E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.662790E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.766349E+09 | 947.97 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.667687E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.721492E+09 | 711.15 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710017E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.668253E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.749245E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682420E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.718402E+09 | 774.31 | 11-OCT-15:50 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.741482E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.730186E+09 | 1184.79 | 04-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.856133E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.662790E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.766349E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470634E+09 | 750.07 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421275E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.486937E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426128E+09 | 450.21 | 10-APR-15:20 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462193E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455921E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429139E+09 | 450.21 | 03-JUL-15:50 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478372E+09 | 450.21 | 02-AUG-15:39 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434119E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.455732E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.472649E+09 | 750.07 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.462671E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545577E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.421275E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.486937E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721308E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.652756E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763082E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.672602E+09 | 711.15 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.731955E+09 | 774.31 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723028E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.681915E+09 | 774.31 | 07-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.757290E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682575E+09 | 711.15 | 07-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.709572E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721755E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705146E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.852298E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.652756E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.763082E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.458899E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413338E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.482180E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425106E+09 | 490.17 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.461286E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.454390E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429789E+09 | 600.10 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478690E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433335E+09 | 490.17 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.452128E+09 | 600.10 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.455932E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.447837E+09 | 750.02 | 18-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.539291E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413338E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.482180E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745435E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.664175E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.768127E+09 | 947.97 | 01-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668725E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.722847E+09 | 774.31 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710918E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.669309E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.750374E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.683661E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.720353E+09 | 947.97 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.744246E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.733009E+09 | 1184.79 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.858118E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664175E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.768127E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471708E+09 | 750.07 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.422198E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487889E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426731E+09 | 450.21 | 10-APR-15:09 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462926E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.456809E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430246E+09 | 450.21 | 03-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479176E+09 | 450.21 | 02-AUG-15:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434906E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.456963E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474037E+09 | 860.01 | 09-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.463911E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546750E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.422198E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487889E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.722044E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.653291E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764067E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674123E+09 | 774.31 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.733911E+09 | 774.31 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.724664E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.683493E+09 | 774.31 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.759327E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683987E+09 | 774.31 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.710827E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721991E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705762E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853749E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.653291E+09 | 754.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.764067E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.459784E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413758E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483358E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425849E+09 | 600.10 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462272E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455503E+09 | 600.10 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430653E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479672E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434267E+09 | 600.10 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.453429E+09 | 600.10 | 10-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.456759E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.448746E+09 | 750.02 | 18-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.540405E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413758E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.483358E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.745435E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52110020.82 | 32620483.33 |
February | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73300864.90 | 8055947.88 |
March | 0.107774E+10 | 0.768129E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125732E+09 | 12094605.55 |
April | 0.956342E+09 | 0.668725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125588E+09 | 2194637.60 |
May | 0.103597E+10 | 0.722885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136451E+09 | 6664796.92 |
June | 0.103308E+10 | 0.710918E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121220E+09 | 8441344.24 |
July | 0.959235E+09 | 0.669309E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75582459.71 | 7139934.30 |
August | 0.107774E+10 | 0.750374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92160062.19 | 12802145.80 |
September | 0.956342E+09 | 0.683661E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69067465.59 | 7870600.98 |
October | 0.994195E+09 | 0.720365E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56293235.50 | 14584755.20 |
November | 0.984487E+09 | 0.744246E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44562377.60 | 17426945.51 |
December | 0.959235E+09 | 0.733009E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42260977.60 | 34141712.84 |
Annual Sum or Average | 0.119305E+11 | 0.858123E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101433E+10 | 0.164038E+09 |
Minimum of Months | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42260977.60 | 2194637.60 |
Maximum of Months | 0.107774E+10 | 0.768129E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136451E+09 | 34141712.84 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.471708E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34217672.66 | 22739641.80 |
February | 0.571020E+09 | 0.422222E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47676412.61 | 6077738.59 |
March | 0.682301E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81689782.99 | 8862503.54 |
April | 0.605444E+09 | 0.426731E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82746933.78 | 1666604.61 |
May | 0.655854E+09 | 0.462926E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92532310.31 | 4244765.94 |
June | 0.654023E+09 | 0.456809E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83312390.47 | 5227310.59 |
July | 0.607275E+09 | 0.430246E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51933678.50 | 4350033.77 |
August | 0.682301E+09 | 0.479176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61494680.61 | 8482043.70 |
September | 0.605444E+09 | 0.434906E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45002235.50 | 5436007.16 |
October | 0.629407E+09 | 0.456963E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36839495.53 | 9945247.71 |
November | 0.623262E+09 | 0.474037E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28726818.95 | 12026090.81 |
December | 0.607275E+09 | 0.463911E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27347292.90 | 23521588.65 |
Annual Sum or Average | 0.755301E+10 | 0.546752E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673520E+09 | 0.112580E+09 |
Minimum of Months | 0.571020E+09 | 0.422222E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27347292.90 | 1666604.61 |
Maximum of Months | 0.682301E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92532310.31 | 23521588.65 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.722044E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46914445.37 | 37171457.79 |
February | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68767737.50 | 9842314.66 |
March | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122054E+09 | 13476045.36 |
April | 0.956342E+09 | 0.674123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126355E+09 | 2151573.78 |
May | 0.103597E+10 | 0.733917E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139850E+09 | 6340728.96 |
June | 0.103308E+10 | 0.724664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126265E+09 | 7651971.22 |
July | 0.959235E+09 | 0.683493E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78926719.51 | 6366387.20 |
August | 0.107774E+10 | 0.759327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94272202.08 | 12232789.44 |
September | 0.956342E+09 | 0.683987E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68319523.06 | 8056018.31 |
October | 0.994195E+09 | 0.710827E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53139795.83 | 15957431.62 |
November | 0.984487E+09 | 0.721991E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40647059.46 | 19569045.26 |
December | 0.959235E+09 | 0.705762E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37213596.85 | 38066605.41 |
Annual Sum or Average | 0.119305E+11 | 0.853749E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100272E+10 | 0.176882E+09 |
Minimum of Months | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37213596.85 | 2151573.78 |
Maximum of Months | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139850E+09 | 38066605.41 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.459784E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34268655.25 | 23037686.03 |
February | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48564680.88 | 6200680.28 |
March | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81734577.72 | 10135222.47 |
April | 0.605404E+09 | 0.425849E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81651423.66 | 1748821.24 |
May | 0.655811E+09 | 0.462272E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92594795.21 | 4482183.45 |
June | 0.653980E+09 | 0.455503E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82490509.77 | 5606225.67 |
July | 0.607235E+09 | 0.430661E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52699230.25 | 4690420.84 |
August | 0.682256E+09 | 0.479672E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62340018.29 | 9255682.98 |
September | 0.605404E+09 | 0.434267E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45916371.52 | 5785908.01 |
October | 0.629366E+09 | 0.453453E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38019235.14 | 10404314.33 |
November | 0.623221E+09 | 0.456759E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30060002.49 | 12063525.83 |
December | 0.607235E+09 | 0.448746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28011532.01 | 23498239.35 |
Annual Sum or Average | 0.755252E+10 | 0.540408E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678351E+09 | 0.116909E+09 |
Minimum of Months | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28011532.01 | 1748821.24 |
Maximum of Months | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92594795.21 | 23498239.35 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.743012E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28915107.37 | 18078028.98 |
February | 0.901968E+09 | 0.662790E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40554069.51 | 4668102.62 |
March | 0.107774E+10 | 0.766349E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70349169.67 | 6713012.96 |
April | 0.956342E+09 | 0.667687E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69931638.58 | 1200539.26 |
May | 0.103597E+10 | 0.721492E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74265817.41 | 4063780.47 |
June | 0.103308E+10 | 0.710017E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65563524.98 | 4860070.86 |
July | 0.959235E+09 | 0.668253E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41613702.45 | 4416065.77 |
August | 0.107774E+10 | 0.749245E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50091167.38 | 8413314.00 |
September | 0.956342E+09 | 0.682420E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38285145.61 | 4605138.64 |
October | 0.994195E+09 | 0.718402E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31503948.94 | 8058484.01 |
November | 0.984487E+09 | 0.741482E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24706509.53 | 10318099.55 |
December | 0.959235E+09 | 0.730186E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23623387.78 | 20489101.95 |
Annual Sum or Average | 0.119305E+11 | 0.856133E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559403E+09 | 95883739.07 |
Minimum of Months | 0.901968E+09 | 0.662790E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23623387.78 | 1200539.26 |
Maximum of Months | 0.107774E+10 | 0.766349E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74265817.41 | 20489101.95 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.470634E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18303576.86 | 13307761.08 |
February | 0.571020E+09 | 0.421275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25519406.13 | 3986819.21 |
March | 0.682301E+09 | 0.486937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43611098.33 | 5812184.21 |
April | 0.605444E+09 | 0.426128E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44057362.50 | 1054132.37 |
May | 0.655854E+09 | 0.462193E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49220054.30 | 2737533.97 |
June | 0.654023E+09 | 0.455921E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44602563.18 | 3142035.03 |
July | 0.607275E+09 | 0.429139E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28111706.05 | 2894362.46 |
August | 0.682301E+09 | 0.478372E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32660765.69 | 6000728.83 |
September | 0.605444E+09 | 0.434119E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24166081.75 | 3525431.42 |
October | 0.629407E+09 | 0.455732E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19825933.12 | 6049367.41 |
November | 0.623262E+09 | 0.472649E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15464492.18 | 7614201.59 |
December | 0.607275E+09 | 0.462671E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14742380.75 | 14628724.62 |
Annual Sum or Average | 0.755301E+10 | 0.545577E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360285E+09 | 70753282.20 |
Minimum of Months | 0.571020E+09 | 0.421275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14742380.75 | 1054132.37 |
Maximum of Months | 0.682301E+09 | 0.486937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49220054.30 | 14628724.62 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.721308E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150672E+10 | 0.129233E+09 |
February | 0.901968E+09 | 0.652756E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157867E+10 | 71194847.10 |
March | 0.107774E+10 | 0.763082E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228843E+10 | 13725709.39 |
April | 0.956342E+09 | 0.672602E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222903E+10 | 1458643.81 |
May | 0.103597E+10 | 0.731955E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234562E+10 | 5118212.14 |
June | 0.103308E+10 | 0.723028E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242947E+10 | 8573389.80 |
July | 0.959235E+09 | 0.681915E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148523E+10 | 6453561.88 |
August | 0.107774E+10 | 0.757290E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195421E+10 | 10156922.12 |
September | 0.956342E+09 | 0.682575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163975E+10 | 7449505.18 |
October | 0.994195E+09 | 0.709572E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145413E+10 | 21211952.73 |
November | 0.984487E+09 | 0.721755E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148085E+10 | 30303996.64 |
December | 0.959235E+09 | 0.705146E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125506E+10 | 0.117966E+09 |
Annual Sum or Average | 0.119305E+11 | 0.852298E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216472E+11 | 0.422846E+09 |
Minimum of Months | 0.901968E+09 | 0.652756E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125506E+10 | 1458643.81 |
Maximum of Months | 0.107774E+10 | 0.763082E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242947E+10 | 0.129233E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.458899E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17938575.07 | 13645981.37 |
February | 0.570983E+09 | 0.413338E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25408551.75 | 4197779.41 |
March | 0.682256E+09 | 0.482180E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42948725.07 | 6676133.43 |
April | 0.605404E+09 | 0.425106E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42780376.80 | 1163477.08 |
May | 0.655811E+09 | 0.461286E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48678457.60 | 2935408.76 |
June | 0.653980E+09 | 0.454390E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43548122.61 | 3348460.11 |
July | 0.607235E+09 | 0.429789E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27862241.09 | 3129084.04 |
August | 0.682256E+09 | 0.478690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32343716.97 | 6451268.88 |
September | 0.605404E+09 | 0.433335E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24179006.18 | 3732038.32 |
October | 0.629366E+09 | 0.452128E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19854625.91 | 6377117.14 |
November | 0.623221E+09 | 0.455932E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15631323.85 | 7735088.54 |
December | 0.607235E+09 | 0.447837E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14589821.05 | 14845502.24 |
Annual Sum or Average | 0.755252E+10 | 0.539291E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355764E+09 | 74237339.32 |
Minimum of Months | 0.570983E+09 | 0.413338E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14589821.05 | 1163477.08 |
Maximum of Months | 0.682256E+09 | 0.482180E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48678457.60 | 14845502.24 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.745435E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44260466.10 | 28664567.44 |
February | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61819890.27 | 7361902.74 |
March | 0.107774E+10 | 0.768127E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107176E+09 | 10491052.26 |
April | 0.956342E+09 | 0.668725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106799E+09 | 1884505.31 |
May | 0.103597E+10 | 0.722847E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115277E+09 | 5655120.28 |
June | 0.103308E+10 | 0.710918E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102569E+09 | 7000059.85 |
July | 0.959235E+09 | 0.669309E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64461758.05 | 6050918.86 |
August | 0.107774E+10 | 0.750374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77927434.09 | 11186073.28 |
September | 0.956342E+09 | 0.683661E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59257840.43 | 6490366.60 |
October | 0.994195E+09 | 0.720353E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48389122.68 | 12251179.79 |
November | 0.984487E+09 | 0.744246E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37773165.08 | 15724503.75 |
December | 0.959235E+09 | 0.733009E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35940383.40 | 30697292.55 |
Annual Sum or Average | 0.119305E+11 | 0.858118E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861651E+09 | 0.143458E+09 |
Minimum of Months | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35940383.40 | 1884505.31 |
Maximum of Months | 0.107774E+10 | 0.768127E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115277E+09 | 30697292.55 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.471708E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28973741.41 | 19859005.99 |
February | 0.421807E+09 | 0.422198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40135636.60 | 5533646.01 |
March | 0.502994E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69170113.05 | 7597217.97 |
April | 0.447140E+09 | 0.426731E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69957396.01 | 1436785.22 |
May | 0.484071E+09 | 0.462926E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78135236.00 | 3603688.38 |
June | 0.482240E+09 | 0.456809E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70707367.04 | 4339549.53 |
July | 0.448971E+09 | 0.430246E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44513137.85 | 3685681.81 |
August | 0.502994E+09 | 0.479176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51887629.21 | 7407408.11 |
September | 0.447140E+09 | 0.434906E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38435055.66 | 4495705.25 |
October | 0.465148E+09 | 0.456963E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31508121.34 | 8367726.06 |
November | 0.460569E+09 | 0.474037E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24346132.85 | 10815207.06 |
December | 0.448971E+09 | 0.463911E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23218661.44 | 21003066.72 |
Annual Sum or Average | 0.557719E+10 | 0.546750E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570988E+09 | 98144688.11 |
Minimum of Months | 0.421807E+09 | 0.422198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23218661.44 | 1436785.22 |
Maximum of Months | 0.502994E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78135236.00 | 21003066.72 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.722044E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39239606.77 | 32537447.14 |
February | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57414676.12 | 8974553.82 |
March | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103215E+09 | 11631101.36 |
April | 0.956342E+09 | 0.674123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107490E+09 | 1847855.98 |
May | 0.103597E+10 | 0.733911E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118608E+09 | 5395439.91 |
June | 0.103308E+10 | 0.724664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107596E+09 | 6330133.40 |
July | 0.959235E+09 | 0.683493E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67988384.62 | 5350187.55 |
August | 0.107774E+10 | 0.759327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79850272.35 | 10749532.68 |
September | 0.956342E+09 | 0.683987E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58408753.64 | 6643752.19 |
October | 0.994195E+09 | 0.710827E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44965927.84 | 13414342.06 |
November | 0.984487E+09 | 0.721991E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34032565.26 | 17541919.00 |
December | 0.959235E+09 | 0.705762E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31123350.07 | 33956801.71 |
Annual Sum or Average | 0.119305E+11 | 0.853749E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849933E+09 | 0.154373E+09 |
Minimum of Months | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31123350.07 | 1847855.98 |
Maximum of Months | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118608E+09 | 33956801.71 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.459784E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28384499.25 | 20415921.13 |
February | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40095319.20 | 5765092.82 |
March | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68238825.61 | 8717747.73 |
April | 0.605404E+09 | 0.425849E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68071689.21 | 1550678.12 |
May | 0.655811E+09 | 0.462272E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77286265.23 | 3841134.79 |
June | 0.653980E+09 | 0.455503E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69303617.09 | 4726451.57 |
July | 0.607235E+09 | 0.430653E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44363107.24 | 4058858.24 |
August | 0.682256E+09 | 0.479672E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51732487.69 | 8108543.71 |
September | 0.605404E+09 | 0.434267E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38541984.55 | 4844005.10 |
October | 0.629366E+09 | 0.453429E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31797167.76 | 8867819.94 |
November | 0.623221E+09 | 0.456759E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24827557.99 | 11026740.16 |
December | 0.607235E+09 | 0.448746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23084361.42 | 21229215.46 |
Annual Sum or Average | 0.755252E+10 | 0.540405E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565727E+09 | 0.103152E+09 |
Minimum of Months | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23084361.42 | 1550678.12 |
Maximum of Months | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77286265.23 | 21229215.46 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44942642.15 | 38420397.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68448925.03 | 8779435.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122603E+09 | 12589024.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129929E+09 | 1862350.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142002E+09 | 6447310.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127264E+09 | 7640290.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78251288.82 | 6056215.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90475598.36 | 12047768.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67897616.32 | 7101214.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53299283.78 | 14472848.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39600606.26 | 19741985.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36508636.23 | 42128922.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100122E+10 | 0.177288E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36508636.23 | 1862350.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142002E+09 | 42128922.04 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59102696.06 | 47903890.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89224243.51 | 10495031.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158299E+09 | 15308067.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167085E+09 | 2251850.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182184E+09 | 7873162.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163114E+09 | 9680455.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101921E+09 | 7448132.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118171E+09 | 13574473.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88192592.91 | 8383731.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69641889.36 | 17743056.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52043677.60 | 23547984.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48245019.08 | 51369705.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129722E+10 | 0.215580E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48245019.08 | 2251850.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182184E+09 | 51369705.62 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55056410.58 | 41805416.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85779664.86 | 6601375.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158256E+09 | 10548482.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167614E+09 | 1510156.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185374E+09 | 6934891.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161800E+09 | 10297929.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88474214.51 | 7794447.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115909E+09 | 11846916.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81088372.65 | 9429440.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60768345.02 | 17977129.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47514736.59 | 20608876.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41747624.58 | 43761057.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124938E+10 | 0.189116E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41747624.58 | 1510156.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185374E+09 | 43761057.96 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 206.22 | 15-JAN-13:00 | 423.50 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 351.28 | 19-FEB-14:53 | 50.65 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 628.58 | 19-MAR-16:00 | 90.33 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.19 | 30-APR-15:36 | 34.50 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.77 | 07-MAY-14:46 | 181.16 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.56 | 18-JUN-14:18 | 209.01 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.51 | 04-JUL-13:50 | 100.65 | 02-JUL-13:50 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.35 | 06-AUG-13:00 | 194.15 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.52 | 10-SEP-14:55 | 104.55 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.26 | 29-OCT-13:10 | 89.12 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.72 | 11-NOV-16:00 | 92.87 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.07 | 31-DEC-13:00 | 170.26 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 157.07 | 34.50 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 628.58 | 423.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.55 | 15-JAN-13:00 | 281.61 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 235.95 | 19-FEB-14:53 | 54.86 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 426.21 | 19-MAR-15:35 | 60.78 | 05-MAR-07:27 |
April | 827.22 | 03-APR-09:09 | 450.21 | 10-APR-15:09 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.11 | 30-APR-15:40 | 35.26 | 23-APR-07:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.20 | 07-MAY-14:46 | 120.49 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.24 | 18-JUN-14:45 | 136.75 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 03-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.87 | 04-JUL-13:50 | 58.12 | 02-JUL-13:50 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 02-AUG-15:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.49 | 06-AUG-13:00 | 137.39 | 20-AUG-11:00 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.89 | 10-SEP-14:48 | 68.11 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 | 29-OCT-13:10 | 59.13 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.97 | 11-NOV-16:00 | 66.72 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.99 | 31-DEC-13:00 | 113.10 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 106.99 | 35.26 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.21 | 281.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.25 | 15-JAN-13:15 | 438.25 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.33 | 19-FEB-14:53 | 58.97 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 628.57 | 19-MAR-16:00 | 92.03 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.69 | 30-APR-15:36 | 34.01 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.28 | 07-MAY-14:46 | 179.08 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.86 | 18-JUN-14:06 | 202.36 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.45 | 04-JUL-13:50 | 75.01 | 02-JUL-13:50 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.53 | 06-AUG-13:00 | 192.44 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.29 | 10-SEP-14:46 | 105.89 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.39 | 29-OCT-13:05 | 91.02 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.85 | 11-NOV-15:50 | 100.14 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.35 | 31-DEC-12:56 | 173.98 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 754.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 141.35 | 34.01 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 628.57 | 438.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.27 | 15-JAN-13:00 | 282.06 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 228.89 | 19-FEB-14:53 | 35.72 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.04 | 19-MAR-16:00 | 60.65 | 03-MAR-05:40 |
April | 827.17 | 03-APR-09:09 | 600.10 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.56 | 30-APR-15:34 | 24.85 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.20 | 21-MAY-12:00 | 120.21 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.21 | 18-JUN-14:06 | 139.88 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.13 | 04-JUL-13:50 | 57.17 | 02-JUL-13:50 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.36 | 06-AUG-13:00 | 128.60 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.77 | 10-SEP-14:55 | 68.39 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 10-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.48 | 29-OCT-13:10 | 61.18 | 29-OCT-17:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.21 | 11-NOV-15:50 | 61.91 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 | 31-DEC-10:00 | 113.65 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 | 24.85 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 419.04 | 282.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.13 | 15-JAN-13:10 | 276.68 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.58 | 20-FEB-16:00 | 30.58 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 360.25 | 19-MAR-16:00 | 53.93 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.63 | 30-APR-15:40 | 21.80 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.48 | 07-MAY-14:55 | 107.66 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.35 | 18-JUN-14:06 | 118.26 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.71 | 04-JUL-13:50 | 38.58 | 02-JUL-14:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.61 | 06-AUG-13:00 | 110.18 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.11 | 10-SEP-15:00 | 69.64 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-15:50 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.19 | 29-OCT-13:10 | 50.64 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.13 | 11-NOV-16:00 | 54.48 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 04-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.40 | 24-DEC-15:00 | 103.38 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.40 | 21.80 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 360.25 | 276.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 | 15-JAN-13:10 | 192.63 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.73 | 20-FEB-16:00 | 31.26 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 226.88 | 19-MAR-15:37 | 38.09 | 14-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 450.21 | 10-APR-15:20 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.23 | 30-APR-15:40 | 19.46 | 23-APR-07:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.41 | 07-MAY-14:36 | 73.50 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.74 | 18-JUN-14:47 | 78.04 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 03-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.11 | 04-JUL-14:30 | 25.17 | 02-JUL-13:20 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 02-AUG-15:39 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.79 | 06-AUG-13:00 | 77.84 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.50 | 10-SEP-14:55 | 48.47 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.71 | 29-OCT-13:10 | 34.02 | 23-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.52 | 11-NOV-16:00 | 38.87 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 | 24-DEC-15:00 | 69.89 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 | 19.46 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 226.88 | 192.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9447.35 | 04-JAN-12:02 | 5290.95 | 23-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9161.58 | 24-FEB-17:03 | 3324.29 | 02-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11354.38 | 21-MAR-11:02 | 916.57 | 15-MAR-06:05 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11751.34 | 11-APR-16:02 | 201.03 | 14-APR-16:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13803.27 | 05-MAY-11:01 | 188.03 | 17-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12452.91 | 12-JUN-16:02 | 758.14 | 21-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 07-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9791.06 | 20-JUL-16:03 | 428.62 | 13-JUL-05:03 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11017.25 | 15-AUG-11:02 | 412.07 | 21-AUG-11:10 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9487.11 | 13-SEP-16:03 | 1248.40 | 15-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9131.75 | 04-OCT-11:02 | 1246.48 | 30-OCT-17:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8747.95 | 10-NOV-12:02 | 2421.20 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7831.00 | 08-DEC-12:02 | 5523.84 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7831.00 | 188.03 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13803.27 | 5523.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 15-JAN-13:10 | 193.32 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.18 | 20-FEB-15:54 | 23.18 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.24 | 19-MAR-16:00 | 37.98 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 490.17 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 | 30-APR-15:34 | 16.64 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.28 | 21-MAY-12:00 | 73.93 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.46 | 18-JUN-14:06 | 79.91 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.32 | 04-JUL-13:50 | 25.05 | 19-JUL-21:20 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.35 | 06-AUG-13:00 | 73.75 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 490.17 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.31 | 10-SEP-14:55 | 49.55 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.41 | 29-OCT-13:10 | 34.24 | 23-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.05 | 11-NOV-15:40 | 37.23 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 31-DEC-13:00 | 70.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 16.64 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 224.24 | 193.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.50 | 15-JAN-13:00 | 396.89 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 305.78 | 20-FEB-16:00 | 46.61 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 528.65 | 19-MAR-16:00 | 81.15 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.11 | 30-APR-15:38 | 31.92 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.33 | 07-MAY-14:46 | 153.25 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.24 | 18-JUN-14:15 | 170.96 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.12 | 04-JUL-13:50 | 64.50 | 02-JUL-14:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.75 | 06-AUG-13:00 | 166.51 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.40 | 10-SEP-15:00 | 94.89 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.80 | 29-OCT-13:10 | 76.19 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.14 | 11-NOV-16:00 | 81.85 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.19 | 24-DEC-15:00 | 153.05 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 141.19 | 31.92 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 528.65 | 396.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.51 | 15-JAN-13:00 | 263.70 | 07-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.15 | 20-FEB-16:00 | 48.64 | 19-FEB-07:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 353.27 | 19-MAR-15:37 | 54.00 | 03-MAR-05:30 |
April | 805.43 | 03-APR-07:10 | 450.21 | 10-APR-15:09 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.20 | 30-APR-15:40 | 31.10 | 23-APR-07:10 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.25 | 07-MAY-14:48 | 102.02 | 08-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.14 | 18-JUN-14:18 | 111.78 | 20-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 03-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.29 | 04-JUL-14:00 | 37.43 | 02-JUL-13:20 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 02-AUG-15:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.39 | 06-AUG-13:00 | 117.68 | 20-AUG-10:50 |
September | 805.43 | 01-SEP-07:10 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.61 | 10-SEP-15:00 | 61.56 | 15-SEP-22:00 |
October | 805.43 | 02-OCT-07:10 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.41 | 29-OCT-13:10 | 50.29 | 23-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.63 | 11-NOV-16:00 | 57.18 | 26-NOV-10:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 24-DEC-15:00 | 101.58 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 31.10 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 353.27 | 263.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 | 15-JAN-12:58 | 409.17 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 283.16 | 20-FEB-15:56 | 53.52 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 524.98 | 19-MAR-16:00 | 82.14 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.56 | 30-APR-15:40 | 31.49 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.37 | 07-MAY-14:46 | 151.42 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.55 | 18-JUN-14:18 | 165.45 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.28 | 04-JUL-14:00 | 43.99 | 02-JUL-13:20 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.68 | 06-AUG-13:00 | 165.03 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.04 | 10-SEP-14:55 | 95.99 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.65 | 29-OCT-13:05 | 76.62 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.98 | 11-NOV-15:40 | 85.81 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 | 31-DEC-12:56 | 156.08 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 754.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 | 31.49 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 524.98 | 409.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.48 | 15-JAN-13:00 | 265.03 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.95 | 20-FEB-15:54 | 32.81 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.94 | 19-MAR-16:00 | 54.85 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 600.10 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.09 | 30-APR-15:34 | 22.93 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.00 | 21-MAY-12:00 | 102.76 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.96 | 18-JUN-14:15 | 114.90 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.98 | 04-JUL-13:50 | 34.97 | 02-JUL-14:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.93 | 06-AUG-13:00 | 110.40 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.20 | 10-SEP-14:55 | 62.85 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 10-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.10 | 29-OCT-13:10 | 50.49 | 23-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 | 11-NOV-15:38 | 54.61 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.98 | 31-DEC-13:00 | 102.21 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 95.98 | 22.93 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 349.94 | 265.03 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.25 | 15-JAN-12:53 | 592.02 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.73 | 19-FEB-14:53 | 69.15 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.73 | 19-MAR-16:00 | 107.65 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.17 | 30-APR-16:00 | 40.99 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.19 | 07-MAY-15:00 | 181.28 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.82 | 18-JUN-14:20 | 178.40 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.16 | 04-JUL-14:00 | 60.69 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.67 | 06-AUG-13:00 | 177.71 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.84 | 10-SEP-15:00 | 123.85 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.64 | 29-OCT-12:52 | 99.23 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.81 | 11-NOV-16:00 | 111.89 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 24-DEC-15:00 | 216.07 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 40.99 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.73 | 592.02 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.15 | 15-JAN-13:00 | 713.82 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.96 | 19-FEB-14:53 | 87.60 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.15 | 19-MAR-16:00 | 132.07 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.91 | 23-APR-15:00 | 49.49 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.56 | 07-MAY-15:00 | 233.30 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.00 | 18-JUN-14:02 | 224.29 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.27 | 04-JUL-14:00 | 74.81 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.18 | 06-AUG-13:00 | 212.76 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.68 | 10-SEP-15:00 | 147.33 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.62 | 29-OCT-12:52 | 123.89 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.62 | 11-NOV-16:00 | 139.51 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.59 | 24-DEC-15:00 | 268.15 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.59 | 49.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.15 | 713.82 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.45 | 15-JAN-13:00 | 566.34 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.57 | 19-FEB-15:00 | 72.76 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.92 | 19-MAR-16:00 | 119.08 | 03-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.21 | 09-APR-14:53 | 34.23 | 13-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.19 | 21-MAY-12:00 | 219.96 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.16 | 18-JUN-14:10 | 269.78 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.46 | 04-JUL-14:00 | 192.48 | 02-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.32 | 06-AUG-13:00 | 266.46 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.00 | 10-SEP-15:00 | 170.54 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.84 | 29-OCT-12:52 | 141.87 | 29-OCT-17:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.99 | 11-NOV-16:00 | 136.89 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 31-DEC-10:00 | 243.43 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 34.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.92 | 566.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 44067.71 | 03-JAN-05:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46630.56 | 06-FEB-06:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43876.83 | 07-MAR-05:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43364.16 | 08-APR-04:02 | 0.00 | 1058.67 | 18975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43651.21 | 25-MAY-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43500.24 | 01-JUN-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43745.10 | 18-JUL-04:23 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44216.35 | 22-AUG-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45498.14 | 19-SEP-05:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44064.48 | 24-OCT-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43874.81 | 07-NOV-05:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41216.61 | 30-DEC-06:03 | 2541.06 | 846.94 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 41216.61 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46630.56 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9907.77 | 04-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 | 0.00 |
February | 10956.35 | 21-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.19 | 0.00 |
March | 11002.91 | 21-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.15 | 0.00 |
April | 10249.27 | 11-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 | 0.00 |
May | 11049.79 | 05-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.72 | 0.00 |
June | 10853.84 | 16-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 | 0.00 |
July | 9444.41 | 14-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 0.00 |
August | 9998.51 | 14-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.01 | 0.00 |
September | 10001.21 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.64 | 0.00 |
October | 9539.70 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.58 | 0.00 |
November | 9437.52 | 22-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 0.00 |
December | 9731.13 | 26-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9437.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 0.00 | |
Maximum of Months | 11049.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.72 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5088.89 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
February | 5467.23 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.36 | 0.00 |
March | 5231.24 | 20-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.72 | 0.00 |
April | 4842.35 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 | 0.00 |
May | 5247.39 | 30-MAY-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
June | 5423.55 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.51 | 0.00 |
July | 4575.37 | 17-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 | 0.00 |
August | 4775.94 | 14-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 0.00 |
September | 4837.01 | 05-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 0.00 |
October | 4862.71 | 10-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.85 | 0.00 |
November | 5029.07 | 13-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 0.00 |
December | 5063.91 | 26-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4575.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5467.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.72 | 1.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5491.94 | 02-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 0.00 |
February | 5655.47 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.19 | 0.00 |
March | 5444.09 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.99 | 0.00 |
April | 5230.85 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.05 | 0.00 |
May | 5942.89 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 0.00 |
June | 5851.58 | 12-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 | 0.00 |
July | 5213.39 | 17-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 0.00 |
August | 5418.67 | 14-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.19 | 0.00 |
September | 5496.07 | 05-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 0.00 |
October | 5363.16 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | 0.00 |
November | 5567.86 | 13-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 0.00 |
December | 5396.06 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5213.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5942.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.99 | 12.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32868.08 | 10-JAN-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35485.20 | 06-FEB-06:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32465.86 | 22-MAR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32254.29 | 05-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32729.51 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32238.21 | 20-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32578.55 | 25-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32330.72 | 16-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31987.62 | 14-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32417.21 | 17-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32965.47 | 21-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31029.99 | 04-DEC-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 31029.99 | 0.00 | 1058.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35485.20 | 3811.58 | 2863.91 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34971.71 | 09-JAN-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37815.31 | 06-FEB-06:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34791.76 | 06-MAR-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34990.58 | 10-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34711.43 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34901.92 | 26-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34834.06 | 17-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34717.20 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34554.75 | 14-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35202.38 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34995.50 | 13-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33352.50 | 09-DEC-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33352.50 | 0.00 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37815.31 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9058.43 | 08-JAN-16:02 | 334.80 | 197.54 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 119.29 | 0.00 |
February | 11536.37 | 26-FEB-17:02 | 334.80 | 263.32 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 82.30 | 0.00 |
March | 12762.39 | 19-MAR-16:52 | 334.80 | 215.08 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 345.38 | 0.00 |
April | 12617.08 | 30-APR-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 119.94 | 0.00 |
May | 13013.80 | 28-MAY-12:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 105.20 | 0.00 |
June | 13695.46 | 18-JUN-13:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 312.19 | 0.00 |
July | 12963.75 | 04-JUL-17:42 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 0.00 |
August | 12826.36 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 183.02 | 0.00 |
September | 12642.53 | 04-SEP-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 149.31 | 0.00 |
October | 11783.87 | 09-OCT-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 118.66 | 0.00 |
November | 9507.84 | 05-NOV-14:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 63.45 | 0.00 |
December | 6756.75 | 26-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6756.75 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 | |
Maximum of Months | 13695.46 | 1306.65 | 647.98 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 345.38 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9923.41 | 16-JAN-11:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 | 0.00 |
February | 11395.48 | 20-FEB-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 0.00 |
March | 12107.81 | 26-MAR-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 147.83 | 0.00 |
April | 11666.31 | 23-APR-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
May | 11625.59 | 07-MAY-08:62 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 0.00 |
June | 12133.96 | 11-JUN-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 187.63 | 0.00 |
July | 11184.35 | 30-JUL-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 | 0.00 |
August | 11704.17 | 13-AUG-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 0.00 |
September | 11703.88 | 10-SEP-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 48.14 | 0.00 |
October | 11638.09 | 08-OCT-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 31.09 | 0.00 |
November | 9703.67 | 05-NOV-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 86.93 | 0.00 |
December | 10249.44 | 31-DEC-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 49.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9703.67 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 0.00 | |
Maximum of Months | 12133.96 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 187.63 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13349.53 | 08-JAN-16:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 | 0.00 |
February | 13145.96 | 26-FEB-12:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 78.14 | 0.00 |
March | 12829.19 | 26-MAR-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 224.49 | 0.00 |
April | 12298.37 | 16-APR-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 177.89 | 0.00 |
May | 12275.62 | 07-MAY-14:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 431.51 | 0.00 |
June | 12747.44 | 18-JUN-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 341.98 | 0.00 |
July | 12131.67 | 30-JUL-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 220.19 | 0.00 |
August | 12273.25 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 189.72 | 0.00 |
September | 12475.50 | 04-SEP-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 144.66 | 0.00 |
October | 13108.24 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 245.05 | 0.00 |
November | 13184.52 | 23-NOV-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 90.26 | 0.00 |
December | 13224.73 | 25-DEC-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12131.67 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 | |
Maximum of Months | 13349.53 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 431.51 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13731.02 | 29-JAN-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 0.00 |
February | 13548.54 | 26-FEB-17:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 0.00 |
March | 13785.46 | 19-MAR-15:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 343.93 | 0.00 |
April | 13653.45 | 02-APR-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 173.83 | 0.00 |
May | 13209.69 | 14-MAY-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 | 0.00 |
June | 13477.59 | 11-JUN-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 166.04 | 0.00 |
July | 13737.77 | 04-JUL-17:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | 0.00 |
August | 13260.47 | 27-AUG-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 0.00 |
September | 13352.80 | 04-SEP-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 130.76 | 0.00 |
October | 12015.30 | 15-OCT-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 0.00 |
November | 11797.93 | 19-NOV-17:03 | 169.55 | 100.04 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 0.00 |
December | 11947.51 | 03-DEC-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11797.93 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | 0.00 | |
Maximum of Months | 13785.46 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 343.93 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7512.82 | 02-JAN-07:03 | 803.52 | 947.98 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
February | 8713.13 | 21-FEB-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8721.71 | 20-MAR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 0.00 |
April | 8944.94 | 11-APR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 0.00 |
May | 11047.81 | 07-MAY-14:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 219.85 | 0.00 |
June | 11493.23 | 11-JUN-13:52 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 172.77 | 0.00 |
July | 11028.54 | 04-JUL-17:42 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 0.00 |
August | 9014.15 | 29-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
September | 9036.20 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
October | 8930.27 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
November | 8423.10 | 24-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
December | 6969.86 | 26-DEC-07:03 | 1071.35 | 1032.43 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6969.86 | 0.00 | 179.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11493.23 | 1071.35 | 1032.43 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 219.85 | 6.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7818.93 | 16-JAN-11:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 0.00 |
February | 10482.71 | 20-FEB-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 | 0.00 |
March | 10805.18 | 26-MAR-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 85.23 | 0.00 |
April | 10704.34 | 09-APR-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 0.00 |
May | 10484.52 | 07-MAY-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.49 | 0.00 |
June | 10816.43 | 11-JUN-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
July | 9237.97 | 30-JUL-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 0.00 |
August | 10372.66 | 27-AUG-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 | 0.00 |
September | 10627.39 | 04-SEP-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 0.00 |
October | 10400.42 | 08-OCT-09:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 | 0.00 |
November | 7979.77 | 23-NOV-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 0.00 |
December | 8252.83 | 31-DEC-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7818.93 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 0.00 | |
Maximum of Months | 10816.43 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11599.00 | 29-JAN-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 | 0.00 |
February | 11430.36 | 21-FEB-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7937.66 | 0.00 |
March | 11312.39 | 21-MAR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9177.14 | 0.00 |
April | 10808.69 | 18-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8905.57 | 0.00 |
May | 11745.51 | 05-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10925.65 | 0.00 |
June | 11194.14 | 16-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9517.65 | 0.00 |
July | 10312.14 | 26-JUL-17:00 | 401.76 | 395.08 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8478.36 | 0.00 |
August | 10817.76 | 15-AUG-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8562.46 | 0.00 |
September | 10653.12 | 05-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7986.16 | 0.00 |
October | 11158.02 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 140.10 | 0.00 |
November | 11193.52 | 23-NOV-11:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 49.35 | 0.00 |
December | 11622.87 | 25-DEC-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10312.14 | 267.84 | 143.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 0.00 | |
Maximum of Months | 11745.51 | 687.71 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10925.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11523.90 | 29-JAN-17:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 | 0.00 |
February | 11637.14 | 20-FEB-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 59.53 | 0.00 |
March | 11500.42 | 05-MAR-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 |
April | 11507.24 | 02-APR-16:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 91.65 | 0.00 |
May | 11298.11 | 07-MAY-15:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 0.00 |
June | 11345.91 | 11-JUN-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 | 0.00 |
July | 11595.68 | 04-JUL-17:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
August | 10825.26 | 27-AUG-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 0.00 |
September | 11773.04 | 10-SEP-15:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 64.21 | 0.00 |
October | 10661.93 | 08-OCT-15:02 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 0.00 |
November | 9605.23 | 19-NOV-17:03 | 169.55 | 100.04 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.04 | 0.00 |
December | 11592.36 | 25-DEC-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9605.23 | 0.00 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 | |
Maximum of Months | 11773.04 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9099.89 | 02-JAN-06:12 | 535.68 | 603.74 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9339.98 | 27-FEB-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 |
March | 10465.93 | 19-MAR-16:52 | 334.80 | 215.08 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 309.70 | 0.00 |
April | 8930.41 | 18-APR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 26.27 | 0.00 |
May | 11259.71 | 28-MAY-12:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 0.00 |
June | 11522.41 | 18-JUN-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 252.96 | 0.00 |
July | 11207.82 | 04-JUL-17:42 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 0.00 |
August | 10467.91 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 159.56 | 0.00 |
September | 10749.43 | 10-SEP-15:12 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 204.21 | 0.00 |
October | 8952.56 | 10-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
November | 9304.02 | 20-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 |
December | 7333.63 | 26-DEC-07:03 | 1071.35 | 1263.98 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7333.63 | 0.00 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11522.41 | 1071.35 | 1263.98 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 309.70 | 23.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8314.76 | 16-JAN-11:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.74 | 0.00 |
February | 11210.83 | 20-FEB-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 |
March | 11512.55 | 26-MAR-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 129.25 | 0.00 |
April | 11191.67 | 23-APR-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 0.00 |
May | 11155.79 | 07-MAY-08:62 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 45.62 | 0.00 |
June | 11559.27 | 11-JUN-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 | 0.00 |
July | 10164.95 | 30-JUL-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 | 0.00 |
August | 11199.12 | 13-AUG-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 0.00 |
September | 11152.81 | 03-SEP-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 | 0.00 |
October | 11123.60 | 08-OCT-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
November | 9071.50 | 23-NOV-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 0.00 |
December | 9187.47 | 31-DEC-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8314.76 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 | |
Maximum of Months | 11559.27 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11865.83 | 29-JAN-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 | 0.00 |
February | 11474.60 | 20-FEB-11:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 | 0.00 |
March | 11074.29 | 26-MAR-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 194.63 | 0.00 |
April | 8765.58 | 18-APR-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 | 0.00 |
May | 8491.61 | 07-MAY-14:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 362.80 | 0.00 |
June | 10366.06 | 11-JUN-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 288.85 | 0.00 |
July | 9179.01 | 17-JUL-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
August | 8955.34 | 28-AUG-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 10723.13 | 10-SEP-15:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 191.47 | 0.00 |
October | 11400.76 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 210.53 | 0.00 |
November | 11426.71 | 23-NOV-11:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 74.93 | 0.00 |
December | 11899.26 | 03-DEC-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8491.61 | 0.00 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11899.26 | 401.76 | 223.18 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 362.80 | 11.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12416.67 | 29-JAN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 59.87 | 0.00 |
February | 12457.63 | 20-FEB-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 0.00 |
March | 12401.54 | 05-MAR-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
April | 12420.90 | 23-APR-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 0.00 |
May | 11972.18 | 14-MAY-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 0.00 |
June | 12139.57 | 11-JUN-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 | 0.00 |
July | 12398.87 | 04-JUL-17:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
August | 12039.69 | 27-AUG-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 122.68 | 0.00 |
September | 12648.08 | 10-SEP-15:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 92.30 | 0.00 |
October | 10549.98 | 15-OCT-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 0.00 |
November | 10176.26 | 19-NOV-17:03 | 169.55 | 100.04 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 | 0.00 |
December | 12465.68 | 25-DEC-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10176.26 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 | |
Maximum of Months | 12648.08 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.170849E+12 | 154668.41 | 04-JAN-13:00 | 0.932095E+10 | 9347.50 | 03-JAN-12:09 |
February | 0.159696E+12 | 162654.82 | 13-FEB-14:00 | 0.842291E+10 | 9343.39 | 10-FEB-12:09 |
March | 0.189853E+12 | 165785.90 | 20-MAR-15:09 | 0.950575E+10 | 9330.65 | 06-MAR-12:09 |
April | 0.184707E+12 | 166111.07 | 11-APR-15:00 | 0.888127E+10 | 9309.18 | 03-APR-11:20 |
May | 0.201954E+12 | 177386.63 | 04-MAY-12:00 | 0.923148E+10 | 9287.66 | 02-MAY-11:09 |
June | 0.202146E+12 | 182110.45 | 13-JUN-15:20 | 0.896979E+10 | 9262.20 | 15-JUN-11:09 |
July | 0.173661E+12 | 157475.84 | 17-JUL-12:00 | 0.895345E+10 | 9255.95 | 27-JUL-11:09 |
August | 0.193426E+12 | 166618.75 | 14-AUG-12:00 | 0.930101E+10 | 9269.09 | 29-AUG-11:09 |
September | 0.177442E+12 | 163159.97 | 05-SEP-12:00 | 0.882559E+10 | 9287.99 | 25-SEP-11:09 |
October | 0.176979E+12 | 159613.77 | 16-OCT-15:09 | 0.918932E+10 | 9311.95 | 30-OCT-11:20 |
November | 0.171324E+12 | 159651.12 | 13-NOV-13:00 | 0.901167E+10 | 9331.31 | 29-NOV-12:09 |
December | 0.165839E+12 | 153745.20 | 12-DEC-13:00 | 0.921699E+10 | 9347.06 | 29-DEC-12:09 |
Annual Sum or Average | 0.216788E+13 | 0.108830E+12 | ||||
Minimum of Months | 0.159696E+12 | 153745.20 | 0.842291E+10 | 9255.95 | ||
Maximum of Months | 0.202146E+12 | 182110.45 | 0.950575E+10 | 9347.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.251855E+11 | 0.456186E+10 | 0.593559E+11 | 0.988560E+09 | 0.986011E+10 | 12379742.02 | 0.00 | 0.708845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227813E+11 | 0.400802E+10 | 0.537310E+11 | 0.894642E+09 | 0.946562E+10 | 11196021.66 | 0.00 | 0.688041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269479E+11 | 0.419680E+10 | 0.617796E+11 | 0.103563E+10 | 0.109590E+11 | 12675672.10 | 0.00 | 0.849213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239031E+11 | 0.388710E+10 | 0.572952E+11 | 0.952004E+09 | 0.101669E+11 | 11960507.72 | 0.00 | 0.884903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.258590E+11 | 0.388975E+10 | 0.605677E+11 | 0.101198E+10 | 0.108659E+11 | 12527707.06 | 0.00 | 0.997472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256834E+11 | 0.371634E+10 | 0.594895E+11 | 0.996280E+09 | 0.115042E+11 | 12231776.97 | 0.00 | 0.100744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.240310E+11 | 0.390630E+10 | 0.583622E+11 | 0.967564E+09 | 0.936284E+10 | 12256437.81 | 0.00 | 0.770183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.268429E+11 | 0.397154E+10 | 0.617796E+11 | 0.103558E+10 | 0.986469E+10 | 12675672.10 | 0.00 | 0.899192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240268E+11 | 0.400992E+10 | 0.572729E+11 | 0.951840E+09 | 0.905389E+10 | 11960507.72 | 0.00 | 0.821147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250130E+11 | 0.434010E+10 | 0.593671E+11 | 0.988559E+09 | 0.894041E+10 | 12379742.02 | 0.00 | 0.783174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249811E+11 | 0.440359E+10 | 0.580818E+11 | 0.970411E+09 | 0.923192E+10 | 12059151.09 | 0.00 | 0.736431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244435E+11 | 0.461491E+10 | 0.583511E+11 | 0.967740E+09 | 0.902441E+10 | 12256437.81 | 0.00 | 0.684255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299699E+12 | 0.495062E+11 | 0.705434E+12 | 0.117608E+11 | 0.118300E+12 | 0.146559E+09 | 0.00 | 0.983029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227813E+11 | 0.371634E+10 | 0.537310E+11 | 0.894642E+09 | 0.894041E+10 | 11196021.66 | 0.00 | 0.684255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269479E+11 | 0.461491E+10 | 0.617796E+11 | 0.103563E+10 | 0.115042E+11 | 12675672.10 | 0.00 | 0.100744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.932095E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.842291E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.950575E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.888127E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.923148E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.896979E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.895345E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.930101E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.882559E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.918932E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.901167E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.921699E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.108830E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.842291E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.950575E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29780.74 | 02-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 843.87 | 02-JAN-16:00 | 13382.49 | 17-JAN-15:09 | 6.85 | 01-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 27340.31 | 07-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 841.47 | 08-FEB-08:20 | 15155.79 | 21-FEB-15:09 | 6.85 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 27649.77 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 842.35 | 28-MAR-07:19 | 14705.99 | 20-MAR-15:09 | 6.85 | 19-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 26646.21 | 21-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 842.35 | 21-APR-07:19 | 13437.38 | 17-APR-15:20 | 6.85 | 02-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 27025.62 | 17-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 842.86 | 17-MAY-07:19 | 14782.83 | 05-MAY-15:20 | 6.85 | 01-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 26709.37 | 20-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 842.43 | 20-JUN-07:19 | 15642.86 | 12-JUN-15:20 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 26819.30 | 11-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 842.58 | 11-JUL-07:19 | 12627.00 | 17-JUL-12:00 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 26819.30 | 02-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 842.58 | 02-AUG-07:19 | 12978.68 | 14-AUG-14:30 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 26646.21 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 842.35 | 21-SEP-07:19 | 12992.45 | 05-SEP-12:00 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 27476.12 | 30-OCT-15:00 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 842.99 | 23-OCT-07:19 | 13180.05 | 10-OCT-14:20 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 31040.88 | 09-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 845.72 | 09-NOV-16:00 | 13392.55 | 13-NOV-13:30 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 31270.78 | 18-DEC-16:00 | 5686.19 | 01-DEC-17:30 | 45864.70 | 01-DEC-08:09 | 846.73 | 18-DEC-16:00 | 13668.65 | 26-DEC-14:00 | 6.85 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26646.21 | 5686.19 | 45864.70 | 841.47 | 12627.00 | 6.85 | 0.00 | |||||||
Maximum of Months | 31270.78 | 5686.19 | 45864.70 | 846.73 | 15642.86 | 6.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 73062.12 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81919.87 | 13-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82479.88 | 20-MAR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84325.80 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95409.07 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98231.63 | 13-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75918.93 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85054.86 | 22-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81435.83 | 06-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79573.51 | 16-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77387.65 | 13-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72942.53 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 72942.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 154668.41 | 04-JAN-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 12830.50 | 6.85 | 0.00 | 72907.99 | 0.00 |
February | 162654.82 | 13-FEB-14:00 | 25681.07 | 40588.47 | 0.00 | 839.16 | 13619.39 | 6.85 | 0.00 | 81919.87 | 0.00 |
March | 165785.90 | 20-MAR-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 14705.99 | 6.85 | 0.00 | 82479.88 | 0.00 |
April | 166111.07 | 11-APR-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13185.23 | 6.85 | 0.00 | 84325.80 | 0.00 |
May | 177386.63 | 04-MAY-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 13047.64 | 6.85 | 0.00 | 95409.07 | 0.00 |
June | 182110.45 | 13-JUN-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 15278.78 | 6.85 | 0.00 | 98231.63 | 0.00 |
July | 157475.84 | 17-JUL-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 12627.00 | 6.85 | 0.00 | 75918.93 | 0.00 |
August | 166618.75 | 14-AUG-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 12736.79 | 6.85 | 0.00 | 84952.05 | 0.00 |
September | 163159.97 | 05-SEP-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 12992.45 | 6.85 | 0.00 | 81237.60 | 0.00 |
October | 159613.77 | 16-OCT-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 12592.19 | 6.85 | 0.00 | 78421.54 | 0.00 |
November | 159651.12 | 13-NOV-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 13333.56 | 6.85 | 0.00 | 77387.65 | 0.00 |
December | 153745.20 | 12-DEC-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 11872.75 | 6.85 | 0.00 | 72942.53 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 153745.20 | 25681.07 | 40588.47 | 0.00 | 839.16 | 11872.75 | 6.85 | 0.00 | 72907.99 | 0.00 | |
Maximum of Months | 182110.45 | 25681.07 | 42402.18 | 0.00 | 839.81 | 15278.78 | 6.85 | 0.00 | 98231.63 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9347.50 | 03-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 9343.39 | 10-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9330.65 | 06-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9309.18 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9287.66 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9262.20 | 15-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9255.95 | 27-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9269.09 | 29-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9287.99 | 25-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9311.95 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9331.31 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9347.06 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9255.95 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9347.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.46 | 2.50 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.54 | 3.67 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.53 | 4.67 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.76 | 7.00 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.83 | 7.33 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.52 | 6.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.59 | 3.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.43 | 3.17 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 1.83 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.67 | 27.62 | 40.00 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.83 | 7.33 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.49 | 1.50 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.59 | 8.17 | 27.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.87 | 8.67 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.84 | 10.83 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.93 | 9.17 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.81 | 8.17 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.51 | 6.50 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.82 | 5.17 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.75 | 8.00 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.65 | 5.83 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.46 | 4.17 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.52 | 2.83 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 80.67 | 27.74 | 79.00 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.50 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.93 | 10.83 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.00 | 9.17 | 28.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.85 | 8.67 | 27.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.77 | 6.00 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 4.50 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 4.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.59 | 3.83 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.40 | 3.00 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.50 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.52 | 4.33 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.67 | 7.50 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.79 | 8.33 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.01 | 9.83 | 28.01 |
Annual Sum or Average | 0.00 | 0.00 | 74.83 | 27.75 | 72.33 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.40 | 2.50 | 27.40 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.01 | 9.83 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.04 | 5.17 | 28.04 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.00 | 4.83 | 28.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.20 | 5.00 | 28.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.18 | 4.67 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.11 | 4.33 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.14 | 4.50 | 28.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.79 | 3.50 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.02 | 3.00 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.96 | 3.67 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 3.83 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.76 | 3.50 | 27.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.97 | 5.00 | 27.97 |
Annual Sum or Average | 0.00 | 0.00 | 61.50 | 28.02 | 51.00 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.76 | 3.00 | 27.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.20 | 5.17 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.52 | 4.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.60 | 5.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 27.55 | 11.00 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.60 | 5.00 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 1.17 | 27.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.83 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.61 | 6.50 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.59 | 8.33 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.66 | 9.17 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.61 | 6.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 1.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 4.17 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.56 | 5.83 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.46 | 3.50 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.33 | 1.33 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 1.17 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 52.17 | 27.57 | 51.83 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.33 | 1.17 | 27.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.66 | 9.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 98.33 | 25.42 | 98.17 | 25.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 90.83 | 25.47 | 90.67 | 25.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 25.61 | 55.33 | 25.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 25.59 | 38.33 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 | 25.59 | 41.50 | 25.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 25.72 | 40.00 | 25.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 25.16 | 28.67 | 25.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 25.42 | 29.67 | 25.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 25.38 | 28.67 | 25.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 25.42 | 33.50 | 25.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 25.52 | 53.50 | 25.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 25.52 | 79.50 | 25.51 |
Annual Sum or Average | 0.00 | 0.00 | 618.33 | 25.49 | 617.50 | 25.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 25.16 | 28.67 | 25.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 98.33 | 25.72 | 98.17 | 25.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.73 | 4.50 | 27.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.82 | 3.50 | 27.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.89 | 4.17 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.89 | 4.17 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.85 | 4.00 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.83 | 4.00 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.67 | 2.17 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.78 | 2.50 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.89 | 2.50 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.53 | 2.67 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.62 | 1.67 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 4.33 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 47.00 | 27.79 | 40.17 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.53 | 1.67 | 27.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.89 | 4.50 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.57 | 5.50 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.64 | 6.33 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 1.83 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 1.17 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.17 | 27.55 | 16.67 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.64 | 6.33 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 1.00 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.50 | 4.33 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.76 | 6.50 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.68 | 8.83 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.75 | 8.67 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.69 | 6.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.64 | 4.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.59 | 5.50 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.52 | 3.83 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 1.83 | 27.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.67 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 53.67 | 27.64 | 53.67 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.76 | 8.83 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.42 | 16.17 | 26.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.25 | 9.50 | 27.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.56 | 5.17 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 2.17 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.67 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.54 | 5.00 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.67 | 7.17 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 26.25 | 19.17 | 26.25 |
Annual Sum or Average | 0.00 | 0.00 | 67.17 | 26.86 | 67.17 | 26.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.67 | 19.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.88 | 4.50 | 27.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.88 | 3.83 | 27.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.04 | 4.17 | 28.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.03 | 4.17 | 28.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 3.67 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.99 | 4.00 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.86 | 1.83 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.87 | 2.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.99 | 2.50 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.67 | 2.50 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.72 | 2.00 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.74 | 4.83 | 27.74 |
Annual Sum or Average | 0.00 | 0.00 | 46.83 | 27.92 | 40.50 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.67 | 1.83 | 27.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.08 | 4.83 | 28.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.41 | 0.00 | 24.41 |
February | 0.00 | 0.00 | 453.83 | 24.37 | 0.00 | 24.37 |
March | 0.00 | 0.00 | 514.00 | 24.31 | 0.00 | 24.31 |
April | 0.00 | 0.00 | 485.00 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 508.00 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 513.50 | 24.35 | 0.00 | 24.35 |
September | 0.00 | 0.00 | 484.67 | 24.34 | 0.00 | 24.34 |
October | 0.00 | 0.00 | 502.00 | 24.40 | 0.00 | 24.40 |
November | 0.00 | 0.00 | 489.00 | 24.41 | 0.00 | 24.41 |
December | 0.00 | 0.00 | 496.50 | 24.39 | 0.00 | 24.39 |
Annual Sum or Average | 0.00 | 5941.50 | 24.36 | 0.00 | 24.36 | |
Minimum of Months | 0.00 | 0.00 | 453.83 | 24.31 | 0.00 | 24.31 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.41 | 0.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 456.00 | 24.30 | 0.00 | 24.30 |
February | 0.00 | 0.00 | 419.17 | 24.26 | 0.00 | 24.26 |
March | 0.00 | 0.00 | 472.83 | 24.23 | 0.00 | 24.23 |
April | 0.00 | 0.00 | 448.67 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 475.83 | 24.26 | 0.00 | 24.26 |
June | 0.00 | 0.00 | 470.83 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 449.17 | 24.28 | 0.00 | 24.28 |
August | 1.00 | 23.22 | 454.17 | 24.26 | 0.00 | 24.26 |
September | 1.17 | 23.19 | 426.67 | 24.25 | 0.00 | 24.25 |
October | 0.00 | 0.00 | 438.83 | 24.30 | 0.00 | 24.30 |
November | 0.00 | 0.00 | 444.67 | 24.30 | 0.00 | 24.30 |
December | 0.83 | 23.26 | 423.50 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 3.00 | 23.22 | 5380.33 | 24.27 | 0.00 | 24.27 |
Minimum of Months | 0.00 | 0.00 | 419.17 | 24.23 | 0.00 | 24.23 |
Maximum of Months | 1.17 | 23.26 | 475.83 | 24.30 | 0.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 23.34 | 418.00 | 24.31 | 0.00 | 24.31 |
February | 0.00 | 0.00 | 389.17 | 24.29 | 0.00 | 24.29 |
March | 1.50 | 23.34 | 462.67 | 24.25 | 0.00 | 24.25 |
April | 0.00 | 0.00 | 463.33 | 24.27 | 0.00 | 24.27 |
May | 0.00 | 0.00 | 478.33 | 24.29 | 0.00 | 24.29 |
June | 0.00 | 0.00 | 473.83 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 440.33 | 24.31 | 0.00 | 24.31 |
August | 2.17 | 23.19 | 441.50 | 24.26 | 0.00 | 24.26 |
September | 2.67 | 23.14 | 427.33 | 24.26 | 0.00 | 24.26 |
October | 0.83 | 23.25 | 417.67 | 24.33 | 0.00 | 24.33 |
November | 0.67 | 23.29 | 410.00 | 24.32 | 0.00 | 24.32 |
December | 10.00 | 23.27 | 383.67 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 21.83 | 23.26 | 5205.83 | 24.29 | 0.00 | 24.29 |
Minimum of Months | 0.00 | 0.00 | 383.67 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 10.00 | 23.34 | 478.33 | 24.33 | 0.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.17 | 24.91 | 468.83 | 24.44 | 27.67 | 24.49 |
February | 35.00 | 25.96 | 433.67 | 24.54 | 35.00 | 24.64 |
March | 49.17 | 25.68 | 506.17 | 24.49 | 49.17 | 24.58 |
April | 60.50 | 25.86 | 485.00 | 24.63 | 60.50 | 24.75 |
May | 77.67 | 26.14 | 504.50 | 24.73 | 77.67 | 24.90 |
June | 71.83 | 26.23 | 494.67 | 24.71 | 71.83 | 24.88 |
July | 65.17 | 26.36 | 492.33 | 24.75 | 65.17 | 24.92 |
August | 67.50 | 25.65 | 507.67 | 24.53 | 67.50 | 24.65 |
September | 51.00 | 25.78 | 476.67 | 24.56 | 51.00 | 24.66 |
October | 63.50 | 25.95 | 480.67 | 24.64 | 63.50 | 24.78 |
November | 38.67 | 25.73 | 467.67 | 24.53 | 38.17 | 24.61 |
December | 43.50 | 24.70 | 439.50 | 24.42 | 31.17 | 24.48 |
Annual Sum or Average | 659.67 | 25.82 | 5757.33 | 24.58 | 638.33 | 24.70 |
Minimum of Months | 35.00 | 24.70 | 433.67 | 24.42 | 27.67 | 24.48 |
Maximum of Months | 77.67 | 26.36 | 507.67 | 24.75 | 77.67 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.17 | 26.13 | 475.33 | 24.61 | 41.83 | 24.73 |
February | 55.33 | 26.46 | 439.67 | 24.72 | 55.33 | 24.89 |
March | 58.83 | 26.25 | 504.50 | 24.61 | 58.67 | 24.77 |
April | 69.83 | 26.36 | 483.33 | 24.76 | 69.83 | 24.94 |
May | 75.00 | 26.27 | 496.50 | 24.74 | 74.17 | 24.92 |
June | 67.83 | 26.27 | 492.33 | 24.68 | 67.67 | 24.86 |
July | 64.83 | 26.39 | 476.50 | 24.74 | 64.83 | 24.92 |
August | 65.33 | 25.92 | 496.00 | 24.57 | 65.17 | 24.71 |
September | 64.00 | 26.26 | 466.17 | 24.70 | 63.33 | 24.87 |
October | 74.83 | 26.08 | 470.67 | 24.72 | 70.83 | 24.90 |
November | 57.33 | 26.09 | 460.17 | 24.67 | 54.00 | 24.82 |
December | 59.17 | 25.91 | 450.33 | 24.63 | 52.50 | 24.79 |
Annual Sum or Average | 755.50 | 26.20 | 5711.50 | 24.68 | 738.17 | 24.84 |
Minimum of Months | 43.17 | 25.91 | 439.67 | 24.57 | 41.83 | 24.71 |
Maximum of Months | 75.00 | 26.46 | 504.50 | 24.76 | 74.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.83 | 26.44 | 492.50 | 24.78 | 66.00 | 24.96 |
February | 55.33 | 26.47 | 451.17 | 24.73 | 55.33 | 24.90 |
March | 56.33 | 25.94 | 510.33 | 24.56 | 56.33 | 24.68 |
April | 59.17 | 25.81 | 485.00 | 24.61 | 59.17 | 24.73 |
May | 71.33 | 25.92 | 503.17 | 24.65 | 71.33 | 24.79 |
June | 68.00 | 25.94 | 494.33 | 24.62 | 68.00 | 24.76 |
July | 51.50 | 26.15 | 483.83 | 24.65 | 51.50 | 24.78 |
August | 67.17 | 25.52 | 506.17 | 24.49 | 67.17 | 24.60 |
September | 54.17 | 25.87 | 477.33 | 24.58 | 54.17 | 24.70 |
October | 74.17 | 26.23 | 487.17 | 24.75 | 74.17 | 24.92 |
November | 66.67 | 26.41 | 479.50 | 24.77 | 66.67 | 24.95 |
December | 71.50 | 26.43 | 476.67 | 24.79 | 70.17 | 24.99 |
Annual Sum or Average | 762.17 | 26.10 | 5847.17 | 24.66 | 760.00 | 24.81 |
Minimum of Months | 51.50 | 25.52 | 451.17 | 24.49 | 51.50 | 24.60 |
Maximum of Months | 74.17 | 26.47 | 510.33 | 24.79 | 74.17 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.33 | 24.94 | 433.50 | 24.50 | 42.50 | 24.62 |
February | 46.50 | 25.46 | 404.33 | 24.54 | 35.83 | 24.66 |
March | 48.50 | 25.74 | 482.00 | 24.51 | 44.50 | 24.62 |
April | 53.17 | 26.09 | 474.67 | 24.62 | 53.17 | 24.75 |
May | 64.00 | 25.90 | 485.17 | 24.62 | 60.50 | 24.76 |
June | 60.17 | 26.08 | 481.00 | 24.61 | 59.33 | 24.76 |
July | 50.50 | 25.85 | 449.50 | 24.62 | 44.50 | 24.75 |
August | 62.67 | 25.49 | 471.33 | 24.49 | 57.33 | 24.61 |
September | 48.17 | 25.70 | 446.00 | 24.54 | 44.50 | 24.65 |
October | 69.50 | 25.31 | 438.00 | 24.59 | 53.00 | 24.72 |
November | 56.67 | 25.24 | 424.50 | 24.53 | 42.33 | 24.65 |
December | 82.33 | 24.49 | 407.50 | 24.43 | 43.50 | 24.55 |
Annual Sum or Average | 707.50 | 25.47 | 5397.50 | 24.55 | 581.00 | 24.68 |
Minimum of Months | 46.50 | 24.49 | 404.33 | 24.43 | 35.83 | 24.55 |
Maximum of Months | 82.33 | 26.09 | 485.17 | 24.62 | 60.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 25.67 | 498.33 | 24.41 | 6.67 | 24.42 |
February | 5.33 | 25.68 | 454.00 | 24.42 | 5.33 | 24.44 |
March | 13.17 | 25.61 | 513.67 | 24.38 | 13.17 | 24.41 |
April | 17.50 | 25.86 | 485.00 | 24.50 | 17.50 | 24.54 |
May | 45.67 | 26.35 | 508.00 | 24.67 | 45.67 | 24.80 |
June | 46.50 | 26.47 | 496.00 | 24.68 | 46.50 | 24.82 |
July | 23.67 | 26.66 | 497.00 | 24.65 | 23.67 | 24.74 |
August | 35.00 | 26.01 | 514.00 | 24.52 | 35.00 | 24.61 |
September | 14.00 | 26.06 | 485.00 | 24.48 | 14.00 | 24.52 |
October | 20.67 | 26.07 | 502.00 | 24.52 | 20.67 | 24.58 |
November | 13.33 | 26.00 | 489.00 | 24.47 | 13.33 | 24.51 |
December | 12.33 | 25.65 | 490.67 | 24.41 | 12.33 | 24.44 |
Annual Sum or Average | 253.83 | 26.16 | 5932.67 | 24.51 | 253.83 | 24.58 |
Minimum of Months | 5.33 | 25.61 | 454.00 | 24.38 | 5.33 | 24.41 |
Maximum of Months | 46.50 | 26.66 | 514.00 | 24.68 | 46.50 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 26.69 | 502.00 | 24.57 | 14.67 | 24.63 |
February | 27.00 | 26.76 | 454.00 | 24.66 | 27.00 | 24.77 |
March | 39.67 | 26.67 | 514.00 | 24.62 | 39.67 | 24.76 |
April | 50.50 | 26.67 | 485.00 | 24.75 | 50.50 | 24.92 |
May | 55.50 | 26.58 | 508.00 | 24.74 | 55.50 | 24.91 |
June | 45.00 | 26.52 | 496.00 | 24.67 | 45.00 | 24.81 |
July | 32.00 | 26.71 | 497.00 | 24.68 | 32.00 | 24.80 |
August | 46.33 | 26.40 | 514.00 | 24.61 | 46.33 | 24.75 |
September | 44.33 | 26.66 | 485.00 | 24.70 | 44.33 | 24.85 |
October | 44.17 | 26.57 | 501.83 | 24.70 | 44.17 | 24.84 |
November | 26.17 | 26.60 | 488.83 | 24.64 | 26.17 | 24.73 |
December | 22.83 | 26.61 | 494.67 | 24.59 | 22.83 | 24.68 |
Annual Sum or Average | 448.17 | 26.60 | 5940.33 | 24.66 | 448.17 | 24.79 |
Minimum of Months | 14.67 | 26.40 | 454.00 | 24.57 | 14.67 | 24.63 |
Maximum of Months | 55.50 | 26.76 | 514.00 | 24.75 | 55.50 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.33 | 25.66 | 501.33 | 25.00 | 115.33 | 25.11 |
February | 100.50 | 25.66 | 454.00 | 25.00 | 100.50 | 25.10 |
March | 127.17 | 25.12 | 514.00 | 24.72 | 127.17 | 24.78 |
April | 139.00 | 24.77 | 485.00 | 24.62 | 139.00 | 24.65 |
May | 212.00 | 24.62 | 508.00 | 24.61 | 212.00 | 24.61 |
June | 202.50 | 24.66 | 496.00 | 24.61 | 202.50 | 24.62 |
July | 124.83 | 24.50 | 497.00 | 24.55 | 124.83 | 24.54 |
August | 238.67 | 24.46 | 514.00 | 24.48 | 238.67 | 24.47 |
September | 170.50 | 24.53 | 485.00 | 24.54 | 170.50 | 24.54 |
October | 188.33 | 24.85 | 502.00 | 24.70 | 188.33 | 24.73 |
November | 155.17 | 25.23 | 489.00 | 24.87 | 155.17 | 24.94 |
December | 129.67 | 25.56 | 496.00 | 24.96 | 129.67 | 25.07 |
Annual Sum or Average | 1903.67 | 24.89 | 5941.33 | 24.71 | 1903.67 | 24.75 |
Minimum of Months | 100.50 | 24.46 | 454.00 | 24.48 | 100.50 | 24.47 |
Maximum of Months | 238.67 | 25.66 | 514.00 | 25.00 | 238.67 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.83 | 26.57 | 498.33 | 24.57 | 24.83 | 24.66 |
February | 21.17 | 26.65 | 454.00 | 24.58 | 21.17 | 24.67 |
March | 29.17 | 26.54 | 514.00 | 24.55 | 29.17 | 24.65 |
April | 35.00 | 26.54 | 485.00 | 24.66 | 35.00 | 24.77 |
May | 39.50 | 26.43 | 507.83 | 24.64 | 39.50 | 24.76 |
June | 38.33 | 26.45 | 496.00 | 24.63 | 38.33 | 24.75 |
July | 23.67 | 26.64 | 497.00 | 24.62 | 23.67 | 24.71 |
August | 38.50 | 26.27 | 514.00 | 24.57 | 38.50 | 24.68 |
September | 26.17 | 26.54 | 485.00 | 24.58 | 26.17 | 24.68 |
October | 35.17 | 26.46 | 501.00 | 24.63 | 35.17 | 24.74 |
November | 23.83 | 26.50 | 488.33 | 24.58 | 23.83 | 24.66 |
December | 30.67 | 26.44 | 490.67 | 24.57 | 30.67 | 24.67 |
Annual Sum or Average | 366.00 | 26.49 | 5931.17 | 24.60 | 366.00 | 24.70 |
Minimum of Months | 21.17 | 26.27 | 454.00 | 24.55 | 21.17 | 24.65 |
Maximum of Months | 39.50 | 26.65 | 514.00 | 24.66 | 39.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.33 | 25.50 | 491.50 | 24.43 | 19.33 | 24.47 |
February | 16.83 | 25.69 | 453.17 | 24.46 | 16.83 | 24.50 |
March | 29.67 | 25.47 | 513.17 | 24.42 | 29.67 | 24.48 |
April | 39.33 | 25.64 | 485.00 | 24.54 | 39.33 | 24.62 |
May | 69.83 | 26.13 | 506.67 | 24.70 | 69.83 | 24.86 |
June | 62.67 | 26.23 | 495.50 | 24.68 | 62.67 | 24.84 |
July | 46.83 | 26.38 | 497.00 | 24.68 | 46.83 | 24.82 |
August | 59.00 | 25.69 | 512.17 | 24.52 | 59.00 | 24.63 |
September | 30.33 | 25.66 | 482.83 | 24.49 | 30.33 | 24.55 |
October | 38.67 | 25.85 | 495.50 | 24.55 | 38.67 | 24.64 |
November | 23.17 | 25.77 | 482.33 | 24.49 | 23.17 | 24.54 |
December | 22.83 | 25.17 | 475.17 | 24.41 | 21.33 | 24.44 |
Annual Sum or Average | 458.50 | 25.86 | 5890.00 | 24.53 | 457.00 | 24.62 |
Minimum of Months | 16.83 | 25.17 | 453.17 | 24.41 | 16.83 | 24.44 |
Maximum of Months | 69.83 | 26.38 | 513.17 | 24.70 | 69.83 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 26.29 | 418.33 | 24.64 | 26.17 | 24.73 |
February | 38.33 | 26.56 | 381.17 | 24.76 | 38.33 | 24.91 |
March | 48.83 | 26.33 | 429.00 | 24.68 | 48.83 | 24.84 |
April | 58.67 | 26.37 | 409.50 | 24.83 | 58.67 | 25.00 |
May | 67.67 | 26.33 | 424.00 | 24.83 | 67.67 | 25.01 |
June | 56.83 | 26.27 | 415.67 | 24.75 | 56.83 | 24.91 |
July | 43.33 | 26.44 | 411.67 | 24.76 | 43.33 | 24.91 |
August | 56.83 | 26.02 | 422.33 | 24.65 | 56.83 | 24.80 |
September | 51.50 | 26.38 | 398.00 | 24.77 | 51.50 | 24.93 |
October | 54.17 | 26.33 | 404.50 | 24.79 | 54.17 | 24.95 |
November | 36.67 | 26.31 | 396.83 | 24.73 | 36.50 | 24.85 |
December | 34.50 | 26.24 | 393.17 | 24.68 | 33.83 | 24.80 |
Annual Sum or Average | 573.50 | 26.32 | 4904.17 | 24.74 | 572.67 | 24.89 |
Minimum of Months | 26.17 | 26.02 | 381.17 | 24.64 | 26.17 | 24.73 |
Maximum of Months | 67.67 | 26.56 | 429.00 | 24.83 | 67.67 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.17 | 26.61 | 501.17 | 24.80 | 59.17 | 24.97 |
February | 48.50 | 26.58 | 454.00 | 24.74 | 48.50 | 24.90 |
March | 45.83 | 26.04 | 513.50 | 24.54 | 45.83 | 24.66 |
April | 38.50 | 25.58 | 485.00 | 24.53 | 38.50 | 24.60 |
May | 57.00 | 25.82 | 506.33 | 24.59 | 57.00 | 24.70 |
June | 51.00 | 25.81 | 495.17 | 24.55 | 51.00 | 24.66 |
July | 27.17 | 25.99 | 496.33 | 24.54 | 27.17 | 24.61 |
August | 54.67 | 25.50 | 511.50 | 24.47 | 54.67 | 24.56 |
September | 37.00 | 25.83 | 483.50 | 24.53 | 37.00 | 24.61 |
October | 65.00 | 26.31 | 497.83 | 24.73 | 65.00 | 24.89 |
November | 59.33 | 26.56 | 486.67 | 24.78 | 59.33 | 24.95 |
December | 64.33 | 26.58 | 493.00 | 24.81 | 64.33 | 25.00 |
Annual Sum or Average | 607.50 | 26.14 | 5924.00 | 24.63 | 607.50 | 24.76 |
Minimum of Months | 27.17 | 25.50 | 454.00 | 24.47 | 27.17 | 24.56 |
Maximum of Months | 65.00 | 26.61 | 513.50 | 24.81 | 65.00 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.17 | 25.89 | 470.50 | 24.54 | 35.67 | 24.65 |
February | 28.67 | 26.32 | 434.00 | 24.54 | 28.67 | 24.65 |
March | 37.17 | 26.12 | 504.50 | 24.50 | 37.17 | 24.60 |
April | 43.67 | 26.09 | 483.33 | 24.59 | 43.67 | 24.71 |
May | 52.33 | 26.03 | 496.50 | 24.60 | 51.83 | 24.72 |
June | 50.00 | 26.09 | 493.17 | 24.57 | 50.00 | 24.70 |
July | 32.17 | 26.29 | 471.83 | 24.58 | 32.17 | 24.68 |
August | 50.50 | 25.78 | 494.00 | 24.50 | 50.50 | 24.60 |
September | 33.00 | 26.04 | 463.50 | 24.52 | 33.00 | 24.61 |
October | 43.83 | 26.09 | 463.17 | 24.60 | 42.83 | 24.72 |
November | 36.00 | 26.10 | 457.50 | 24.56 | 35.50 | 24.66 |
December | 44.33 | 25.62 | 444.00 | 24.52 | 37.67 | 24.63 |
Annual Sum or Average | 491.83 | 26.02 | 5676.00 | 24.55 | 478.67 | 24.66 |
Minimum of Months | 28.67 | 25.62 | 434.00 | 24.50 | 28.67 | 24.60 |
Maximum of Months | 52.33 | 26.32 | 504.50 | 24.60 | 51.83 | 24.72 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40886 | 46.93596 | 0.56649 | 11.97826 |
February | 454.00000 | 24.36555 | 47.22268 | 0.56028 | 11.79220 |
March | 514.00000 | 24.31318 | 47.44655 | 0.54938 | 11.51680 |
April | 485.00000 | 24.33225 | 47.54178 | 0.55245 | 11.59857 |
May | 508.00000 | 24.34108 | 47.47895 | -0.2924 | 7.19247 |
June | 496.00000 | 24.33653 | 47.42095 | -0.2893 | 7.16363 |
July | 497.00000 | 24.37666 | 47.38206 | -0.2866 | 7.18441 |
August | 514.00000 | 24.34912 | 47.61604 | -0.2942 | 7.28262 |
September | 485.00000 | 24.33905 | 47.69612 | -0.2971 | 7.24519 |
October | 502.00000 | 24.39733 | 47.50258 | 0.56351 | 11.91140 |
November | 489.00000 | 24.41194 | 47.32660 | 0.56778 | 12.01267 |
December | 497.00000 | 24.38599 | 47.21480 | 0.55957 | 11.78742 |
Annual Sum or Average | 5943.00000 | 24.36300 | 47.39984 | 0.20156 | 9.87019 |
Minimum of Months | 454.00000 | 24.31318 | 46.93596 | -0.2971 | 7.16363 |
Maximum of Months | 514.00000 | 24.41194 | 47.69612 | 0.56778 | 12.01267 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24648 | 48.27456 | 0.52036 | 10.87980 |
February | 454.00000 | 24.21952 | 48.37464 | 0.51733 | 10.76957 |
March | 514.00000 | 24.18274 | 48.57985 | 0.51034 | 10.60552 |
April | 485.00000 | 24.19752 | 48.51176 | 0.51354 | 10.68546 |
May | 508.00000 | 24.22422 | 48.43390 | -0.3443 | 7.81381 |
June | 496.00000 | 24.22601 | 48.37069 | -0.3403 | 7.74568 |
July | 497.00000 | 24.21644 | 48.52486 | -0.3526 | 7.99213 |
August | 514.00000 | 24.18795 | 48.78369 | -0.3625 | 8.11659 |
September | 485.00000 | 24.18060 | 48.79650 | -0.3631 | 8.10424 |
October | 502.00000 | 24.22250 | 48.64451 | 0.51406 | 10.74063 |
November | 489.00000 | 24.24485 | 48.52370 | 0.51939 | 10.84039 |
December | 497.00000 | 24.19112 | 48.52114 | 0.50471 | 10.50813 |
Annual Sum or Average | 5943.00000 | 24.21156 | 48.52954 | 0.14959 | 9.55509 |
Minimum of Months | 454.00000 | 24.18060 | 48.27456 | -0.3631 | 7.74568 |
Maximum of Months | 514.00000 | 24.24648 | 48.79650 | 0.52036 | 10.87980 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21034 | 47.90715 | 0.51652 | 10.80659 |
February | 454.00000 | 24.20185 | 48.01204 | 0.52018 | 10.84758 |
March | 514.00000 | 24.19688 | 48.28977 | 0.52368 | 10.91286 |
April | 485.00000 | 24.23990 | 48.33306 | 0.53608 | 11.19726 |
May | 508.00000 | 24.25235 | 48.32278 | -0.3185 | 7.51788 |
June | 496.00000 | 24.25629 | 48.26491 | -0.3124 | 7.42575 |
July | 497.00000 | 24.23566 | 48.36820 | -0.3336 | 7.73911 |
August | 514.00000 | 24.17826 | 48.77664 | -0.3528 | 7.97755 |
September | 485.00000 | 24.19376 | 48.72129 | -0.3441 | 7.86665 |
October | 502.00000 | 24.21772 | 48.65274 | 0.52063 | 10.91074 |
November | 489.00000 | 24.20890 | 48.48503 | 0.51848 | 10.83229 |
December | 497.00000 | 24.13363 | 48.35036 | 0.49634 | 10.35691 |
Annual Sum or Average | 5943.00000 | 24.21045 | 48.37619 | 0.16077 | 9.51969 |
Minimum of Months | 454.00000 | 24.13363 | 47.90715 | -0.3528 | 7.42575 |
Maximum of Months | 514.00000 | 24.25629 | 48.77664 | 0.53608 | 11.19726 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.34863 | 50.72482 | 0.58771 | 12.75455 |
February | 454.00000 | 24.39146 | 50.42445 | 0.60651 | 13.29406 |
March | 514.00000 | 24.36193 | 51.46695 | 0.61619 | 13.49353 |
April | 485.00000 | 24.47537 | 51.69148 | 0.65597 | 14.70535 |
May | 508.00000 | 24.50726 | 51.86076 | -0.1312 | 6.97603 |
June | 496.00000 | 24.49154 | 51.39738 | -0.1127 | 6.84188 |
July | 497.00000 | 24.52592 | 50.58227 | -0.1545 | 7.02149 |
August | 514.00000 | 24.36902 | 53.25994 | -0.2051 | 7.00261 |
September | 485.00000 | 24.41299 | 51.95378 | -0.2067 | 7.03004 |
October | 502.00000 | 24.43085 | 52.24626 | 0.61894 | 13.79267 |
November | 489.00000 | 24.39456 | 51.49410 | 0.60464 | 13.26234 |
December | 497.00000 | 24.29552 | 51.30929 | 0.57162 | 12.39974 |
Annual Sum or Average | 5943.00000 | 24.41701 | 51.54650 | 0.28448 | 10.68718 |
Minimum of Months | 454.00000 | 24.29552 | 50.42445 | -0.2067 | 6.84188 |
Maximum of Months | 514.00000 | 24.52592 | 53.25994 | 0.65597 | 14.70535 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42615 | 49.95225 | 0.63990 | 14.27649 |
February | 454.00000 | 24.47141 | 49.60094 | 0.66553 | 15.11055 |
March | 514.00000 | 24.40667 | 50.56785 | 0.66969 | 15.19523 |
April | 485.00000 | 24.52221 | 50.80430 | 0.70709 | 16.41370 |
May | 508.00000 | 24.48698 | 51.51055 | -0.1128 | 7.13875 |
June | 496.00000 | 24.45892 | 51.29088 | -0.1098 | 6.85189 |
July | 497.00000 | 24.48016 | 50.57717 | -0.1520 | 7.06636 |
August | 514.00000 | 24.35748 | 52.75571 | -0.1719 | 7.06742 |
September | 485.00000 | 24.44622 | 51.28938 | -0.1515 | 7.21498 |
October | 502.00000 | 24.43876 | 51.68445 | 0.64837 | 14.79571 |
November | 489.00000 | 24.43046 | 50.88886 | 0.64106 | 14.43428 |
December | 497.00000 | 24.37780 | 50.49870 | 0.62164 | 13.93627 |
Annual Sum or Average | 5943.00000 | 24.44129 | 50.96604 | 0.32128 | 11.58994 |
Minimum of Months | 454.00000 | 24.35748 | 49.60094 | -0.1719 | 6.85189 |
Maximum of Months | 514.00000 | 24.52221 | 52.75571 | 0.70709 | 16.41370 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.53766 | 49.41113 | 0.68607 | 15.81428 |
February | 454.00000 | 24.50994 | 49.44457 | 0.67866 | 15.52446 |
March | 514.00000 | 24.40307 | 51.01271 | 0.64545 | 14.38714 |
April | 485.00000 | 24.46558 | 51.77565 | 0.65137 | 14.56314 |
May | 508.00000 | 24.45878 | 52.32739 | -0.1692 | 6.93835 |
June | 496.00000 | 24.43441 | 52.17029 | -0.1736 | 6.89146 |
July | 497.00000 | 24.46764 | 51.06071 | -0.1979 | 7.10880 |
August | 514.00000 | 24.34280 | 53.52829 | -0.2245 | 7.06512 |
September | 485.00000 | 24.42670 | 51.81169 | -0.1938 | 7.00294 |
October | 502.00000 | 24.49757 | 51.64219 | 0.65420 | 14.91631 |
November | 489.00000 | 24.52415 | 50.44271 | 0.67207 | 15.39621 |
December | 497.00000 | 24.51230 | 49.81692 | 0.67540 | 15.61727 |
Annual Sum or Average | 5943.00000 | 24.46428 | 51.22194 | 0.30508 | 11.73268 |
Minimum of Months | 454.00000 | 24.34280 | 49.41113 | -0.2245 | 6.89146 |
Maximum of Months | 514.00000 | 24.53766 | 53.52829 | 0.68607 | 15.81428 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.27408 | 50.34237 | 0.60753 | 13.61186 |
February | 454.00000 | 24.31561 | 50.03503 | 0.63007 | 14.16521 |
March | 514.00000 | 24.32386 | 50.85813 | 0.65079 | 14.70317 |
April | 485.00000 | 24.43163 | 51.12928 | 0.68346 | 15.67178 |
May | 508.00000 | 24.39626 | 51.75526 | -0.1470 | 7.17256 |
June | 496.00000 | 24.39373 | 51.56841 | -0.1373 | 7.03873 |
July | 497.00000 | 24.37609 | 50.83326 | -0.1875 | 7.33389 |
August | 514.00000 | 24.27449 | 53.00704 | -0.2037 | 7.36354 |
September | 485.00000 | 24.32421 | 51.62688 | -0.1946 | 7.33674 |
October | 502.00000 | 24.31954 | 51.92612 | 0.62079 | 14.03175 |
November | 489.00000 | 24.29018 | 51.20286 | 0.61047 | 13.63154 |
December | 497.00000 | 24.19502 | 50.96054 | 0.58305 | 13.05165 |
Annual Sum or Average | 5943.00000 | 24.32606 | 51.28343 | 0.28973 | 11.23033 |
Minimum of Months | 454.00000 | 24.19502 | 50.03503 | -0.2037 | 7.03873 |
Maximum of Months | 514.00000 | 24.43163 | 53.00704 | 0.68346 | 15.67178 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38475 | 49.17788 | 0.58362 | 12.42952 |
February | 454.00000 | 24.40764 | 49.19724 | 0.59735 | 12.83910 |
March | 514.00000 | 24.35215 | 49.95160 | 0.59513 | 12.74729 |
April | 485.00000 | 24.44607 | 50.00826 | 0.62802 | 13.71534 |
May | 508.00000 | 24.51766 | 49.79794 | -0.1480 | 6.64771 |
June | 496.00000 | 24.51209 | 49.42400 | -0.1239 | 6.52024 |
July | 497.00000 | 24.55674 | 48.85834 | -0.1521 | 6.60258 |
August | 514.00000 | 24.41537 | 50.82975 | -0.2022 | 6.74912 |
September | 485.00000 | 24.43221 | 49.88684 | -0.2141 | 6.72262 |
October | 502.00000 | 24.45390 | 50.20409 | 0.60985 | 13.28736 |
November | 489.00000 | 24.43069 | 49.71980 | 0.60077 | 12.95244 |
December | 497.00000 | 24.36954 | 49.66060 | 0.57875 | 12.32114 |
Annual Sum or Average | 5943.00000 | 24.43992 | 49.73323 | 0.27633 | 10.26793 |
Minimum of Months | 454.00000 | 24.35215 | 48.85834 | -0.2141 | 6.52024 |
Maximum of Months | 514.00000 | 24.55674 | 50.82975 | 0.62802 | 13.71534 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50741 | 48.53448 | 0.64789 | 14.29286 |
February | 454.00000 | 24.53565 | 48.46657 | 0.66985 | 15.02807 |
March | 514.00000 | 24.46025 | 49.14118 | 0.66592 | 14.90219 |
April | 485.00000 | 24.55249 | 49.24192 | 0.69495 | 15.86213 |
May | 508.00000 | 24.54054 | 49.60799 | -0.1146 | 6.72619 |
June | 496.00000 | 24.50154 | 49.45933 | -0.1136 | 6.48289 |
July | 497.00000 | 24.55050 | 48.93227 | -0.1383 | 6.56289 |
August | 514.00000 | 24.45210 | 50.49705 | -0.1529 | 6.63790 |
September | 485.00000 | 24.52296 | 49.36012 | -0.1398 | 6.70405 |
October | 502.00000 | 24.53060 | 49.75074 | 0.65557 | 14.71499 |
November | 489.00000 | 24.52985 | 49.21795 | 0.65254 | 14.53081 |
December | 497.00000 | 24.49758 | 49.00455 | 0.64061 | 14.16585 |
Annual Sum or Average | 5943.00000 | 24.51458 | 49.27712 | 0.32737 | 11.34798 |
Minimum of Months | 454.00000 | 24.45210 | 48.46657 | -0.1529 | 6.48289 |
Maximum of Months | 514.00000 | 24.55249 | 50.49705 | 0.69495 | 15.86213 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.85066 | 53.05781 | 0.78245 | 18.67846 |
February | 454.00000 | 24.84769 | 53.18343 | 0.77762 | 18.50800 |
March | 514.00000 | 24.61786 | 55.88336 | 0.71935 | 16.45630 |
April | 485.00000 | 24.58261 | 58.22541 | 0.71188 | 16.17270 |
May | 508.00000 | 24.60692 | 61.19723 | -0.0707 | 6.15047 |
June | 496.00000 | 24.59301 | 61.18791 | -0.0702 | 6.16695 |
July | 497.00000 | 24.56018 | 57.79274 | -0.1201 | 6.12216 |
August | 514.00000 | 24.48249 | 63.00035 | -0.1119 | 6.14805 |
September | 485.00000 | 24.54953 | 59.99404 | -0.0987 | 6.10572 |
October | 502.00000 | 24.63799 | 59.69664 | 0.74287 | 17.26296 |
November | 489.00000 | 24.75517 | 56.91474 | 0.77135 | 18.25165 |
December | 497.00000 | 24.80334 | 53.67591 | 0.77195 | 18.39515 |
Annual Sum or Average | 5943.00000 | 24.65560 | 57.85955 | 0.39690 | 12.81546 |
Minimum of Months | 454.00000 | 24.48249 | 53.05781 | -0.1201 | 6.10572 |
Maximum of Months | 514.00000 | 24.85066 | 63.00035 | 0.78245 | 18.67846 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46529 | 48.70569 | 0.63699 | 14.03237 |
February | 454.00000 | 24.48057 | 48.69208 | 0.65437 | 14.54411 |
March | 514.00000 | 24.43844 | 49.29651 | 0.65955 | 14.69299 |
April | 485.00000 | 24.51969 | 49.45662 | 0.68372 | 15.46938 |
May | 508.00000 | 24.50463 | 49.78607 | -0.1322 | 6.62865 |
June | 496.00000 | 24.48492 | 49.64143 | -0.1257 | 6.53503 |
July | 497.00000 | 24.52822 | 49.05106 | -0.1499 | 6.58872 |
August | 514.00000 | 24.43860 | 50.65565 | -0.1641 | 6.67335 |
September | 485.00000 | 24.47707 | 49.57357 | -0.1609 | 6.62589 |
October | 502.00000 | 24.50015 | 49.87256 | 0.64645 | 14.41427 |
November | 489.00000 | 24.48363 | 49.38054 | 0.64053 | 14.15629 |
December | 497.00000 | 24.44209 | 49.21769 | 0.62704 | 13.78465 |
Annual Sum or Average | 5943.00000 | 24.48001 | 49.45275 | 0.31473 | 11.14563 |
Minimum of Months | 454.00000 | 24.43844 | 48.69208 | -0.1641 | 6.53503 |
Maximum of Months | 514.00000 | 24.52822 | 50.65565 | 0.68372 | 15.46938 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.37496 | 50.54490 | 0.58542 | 12.57165 |
February | 454.00000 | 24.40894 | 50.32923 | 0.60010 | 13.00686 |
March | 514.00000 | 24.35907 | 51.20131 | 0.60121 | 12.99570 |
April | 485.00000 | 24.45352 | 51.39433 | 0.63411 | 13.99076 |
May | 508.00000 | 24.50501 | 51.44718 | -0.1540 | 6.89781 |
June | 496.00000 | 24.48802 | 51.00321 | -0.1377 | 6.77072 |
July | 497.00000 | 24.52562 | 50.30386 | -0.1724 | 6.89754 |
August | 514.00000 | 24.38061 | 52.68134 | -0.2189 | 6.98791 |
September | 485.00000 | 24.40888 | 51.51867 | -0.2267 | 6.96249 |
October | 502.00000 | 24.43916 | 51.73776 | 0.60927 | 13.39476 |
November | 489.00000 | 24.41814 | 51.13452 | 0.59995 | 13.03750 |
December | 497.00000 | 24.33957 | 51.03956 | 0.57383 | 12.29068 |
Annual Sum or Average | 5943.00000 | 24.42502 | 51.20462 | 0.27135 | 10.45741 |
Minimum of Months | 454.00000 | 24.33957 | 50.30386 | -0.2267 | 6.77072 |
Maximum of Months | 514.00000 | 24.52562 | 52.68134 | 0.63411 | 13.99076 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.52156 | 49.88625 | 0.63979 | 14.25695 |
February | 385.00000 | 24.57023 | 49.57702 | 0.66342 | 15.05114 |
March | 433.00000 | 24.48975 | 50.51988 | 0.65892 | 14.91600 |
April | 410.00000 | 24.60699 | 50.73774 | 0.69428 | 16.07632 |
May | 430.00000 | 24.57645 | 51.35133 | -0.1257 | 7.25309 |
June | 418.00000 | 24.53596 | 51.18954 | -0.1290 | 6.96096 |
July | 422.00000 | 24.56183 | 50.41295 | -0.1629 | 7.08573 |
August | 433.00000 | 24.44383 | 52.59111 | -0.1818 | 7.22471 |
September | 410.00000 | 24.53091 | 51.00608 | -0.1637 | 7.27891 |
October | 427.00000 | 24.53133 | 51.39632 | 0.64519 | 14.69091 |
November | 417.00000 | 24.53085 | 50.67239 | 0.64147 | 14.44456 |
December | 422.00000 | 24.47992 | 50.37229 | 0.62506 | 13.96863 |
Annual Sum or Average | 5034.00000 | 24.53095 | 50.82179 | 0.31443 | 11.57227 |
Minimum of Months | 385.00000 | 24.44383 | 49.57702 | -0.1818 | 6.96096 |
Maximum of Months | 433.00000 | 24.60699 | 52.59111 | 0.69428 | 16.07632 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58758 | 49.16737 | 0.68643 | 15.72667 |
February | 454.00000 | 24.54256 | 49.29606 | 0.67369 | 15.28559 |
March | 514.00000 | 24.40941 | 50.72923 | 0.63167 | 13.92338 |
April | 485.00000 | 24.44381 | 51.48005 | 0.62974 | 13.85796 |
May | 508.00000 | 24.45008 | 51.92633 | -0.1929 | 6.88833 |
June | 496.00000 | 24.42049 | 51.78243 | -0.2000 | 6.85840 |
July | 497.00000 | 24.46144 | 50.78338 | -0.2165 | 6.98615 |
August | 514.00000 | 24.35516 | 52.94860 | -0.2376 | 7.05713 |
September | 485.00000 | 24.42624 | 51.37482 | -0.2131 | 6.92291 |
October | 502.00000 | 24.51587 | 51.13033 | 0.64587 | 14.56721 |
November | 489.00000 | 24.55453 | 50.05887 | 0.66725 | 15.17639 |
December | 497.00000 | 24.57563 | 49.48990 | 0.67923 | 15.59221 |
Annual Sum or Average | 5943.00000 | 24.47771 | 50.86356 | 0.29250 | 11.53519 |
Minimum of Months | 454.00000 | 24.35516 | 49.16737 | -0.2376 | 6.85840 |
Maximum of Months | 514.00000 | 24.58758 | 52.94860 | 0.68643 | 15.72667 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36165 | 50.14905 | 0.61664 | 13.64204 |
February | 454.00000 | 24.38626 | 49.92575 | 0.63358 | 14.06974 |
March | 514.00000 | 24.36453 | 50.61320 | 0.64409 | 14.35665 |
April | 485.00000 | 24.45266 | 50.85432 | 0.67021 | 15.15011 |
May | 508.00000 | 24.42633 | 51.39723 | -0.1599 | 6.95425 |
June | 496.00000 | 24.41487 | 51.20713 | -0.1541 | 6.84210 |
July | 497.00000 | 24.41732 | 50.55270 | -0.1934 | 7.02748 |
August | 514.00000 | 24.33103 | 52.46940 | -0.2047 | 7.12400 |
September | 485.00000 | 24.36910 | 51.19168 | -0.2015 | 7.07187 |
October | 502.00000 | 24.38522 | 51.42641 | 0.62239 | 13.88404 |
November | 489.00000 | 24.37355 | 50.83005 | 0.61716 | 13.64357 |
December | 497.00000 | 24.30415 | 50.67317 | 0.59747 | 13.15993 |
Annual Sum or Average | 5943.00000 | 24.38195 | 50.95198 | 0.28736 | 11.04758 |
Minimum of Months | 454.00000 | 24.30415 | 49.92575 | -0.2047 | 6.84210 |
Maximum of Months | 514.00000 | 24.45266 | 52.46940 | 0.67021 | 15.15011 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100642E+12 | 0.256231E+11 | 445.97 | 0.688042E+11 | 0.318374E+11 | 0.00 | 1.00 | 01-JAN-00:12 | 0.00 | 01-JAN-00:10 | 139313.83 | 09-JAN-05:02 | 81719.86 | 09-JAN-05:02 | 57593.96 | 09-JAN-05:02 | 31802.85 | 09-JAN-05:02 | 0.00 |
February | 0.951833E+11 | 0.245977E+11 | 409.08 | 0.651314E+11 | 0.300519E+11 | 0.00 | 1.00 | 01-FEB-06:13 | 0.00 | 01-FEB-00:10 | 139040.55 | 06-FEB-06:02 | 86334.50 | 21-FEB-05:02 | 60140.17 | 06-FEB-06:03 | 31775.32 | 06-FEB-06:02 | 0.00 |
March | 0.116099E+12 | 0.303249E+11 | 476.32 | 0.772301E+11 | 0.388693E+11 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 139356.46 | 13-MAR-04:02 | 87345.38 | 20-MAR-04:02 | 58553.91 | 29-MAR-04:02 | 33393.85 | 28-MAR-04:02 | 0.00 |
April | 0.120990E+12 | 0.313899E+11 | 456.63 | 0.735157E+11 | 0.474743E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 140252.95 | 01-APR-04:02 | 86630.57 | 03-APR-04:02 | 66138.83 | 01-APR-04:02 | 33339.80 | 12-APR-04:02 | 0.00 |
May | 0.138284E+12 | 0.355601E+11 | 480.53 | 0.782237E+11 | 0.600604E+11 | 0.00 | 1.00 | 01-MAY-00:38 | 0.00 | 01-MAY-00:05 | 145307.71 | 22-MAY-04:02 | 86631.58 | 15-MAY-04:02 | 81000.44 | 22-MAY-04:04 | 34213.28 | 06-MAY-04:02 | 0.00 |
June | 0.139456E+12 | 0.360177E+11 | 467.33 | 0.794589E+11 | 0.599970E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 145152.95 | 10-JUN-04:02 | 85856.50 | 12-JUN-04:02 | 73604.92 | 10-JUN-04:02 | 34336.10 | 15-JUN-12:13 | 0.00 |
July | 0.111077E+12 | 0.277828E+11 | 454.06 | 0.683610E+11 | 0.427160E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 133399.45 | 10-JUL-04:02 | 86259.05 | 24-JUL-04:02 | 48944.05 | 21-JUL-04:02 | 31345.34 | 10-JUL-04:02 | 0.00 |
August | 0.130662E+12 | 0.325997E+11 | 469.48 | 0.726968E+11 | 0.579649E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 146413.09 | 21-AUG-04:02 | 86477.39 | 14-AUG-04:02 | 81307.33 | 21-AUG-04:02 | 34501.59 | 02-AUG-04:03 | 0.00 |
September | 0.118761E+12 | 0.296536E+11 | 447.14 | 0.673423E+11 | 0.514183E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 139664.25 | 25-SEP-04:02 | 86096.02 | 11-SEP-04:02 | 57958.88 | 25-SEP-04:02 | 32815.07 | 25-SEP-04:02 | 0.00 |
October | 0.114745E+12 | 0.282914E+11 | 444.58 | 0.657916E+11 | 0.489529E+11 | 0.00 | 1.00 | 01-OCT-06:22 | 0.00 | 01-OCT-00:10 | 142304.67 | 30-OCT-04:02 | 86206.59 | 16-OCT-04:02 | 64870.21 | 30-OCT-04:02 | 32581.72 | 30-OCT-04:02 | 0.00 |
November | 0.107434E+12 | 0.267389E+11 | 430.49 | 0.657073E+11 | 0.417262E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 123863.74 | 13-NOV-07:03 | 86153.45 | 13-NOV-07:03 | 45826.73 | 10-NOV-13:02 | 29651.80 | 13-NOV-07:03 | 0.00 |
December | 0.984483E+11 | 0.247039E+11 | 433.32 | 0.647654E+11 | 0.336829E+11 | 0.00 | 1.00 | 01-DEC-06:13 | 0.00 | 01-DEC-00:10 | 117577.54 | 11-DEC-07:03 | 82267.87 | 26-DEC-07:03 | 43915.21 | 30-DEC-05:03 | 27304.68 | 11-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.139178E+13 | 0.353284E+12 | 5414.94 | 0.847028E+12 | 0.544752E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.951833E+11 | 0.245977E+11 | 409.08 | 0.647654E+11 | 0.300519E+11 | 0.00 | 1.00 | 0.00 | 117577.54 | 81719.86 | 43915.21 | 27304.68 | 0.00 | ||||||
Maximum of Months | 0.139456E+12 | 0.360177E+11 | 480.53 | 0.794589E+11 | 0.600604E+11 | 0.00 | 1.00 | 0.00 | 146413.09 | 87345.38 | 81307.33 | 34501.59 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.869587E+11 | 0.220237E+11 | 437.15 | 0.577345E+11 | 0.292242E+11 | 0.00 | 1.00 | 01-JAN-06:30 | 0.00 | 01-JAN-00:10 | 122064.53 | 09-JAN-05:02 | 70026.76 | 02-JAN-06:12 | 56505.01 | 09-JAN-05:02 | 27703.23 | 09-JAN-05:02 | 0.00 |
February | 0.833501E+11 | 0.214176E+11 | 402.92 | 0.552751E+11 | 0.280750E+11 | 0.00 | 1.00 | 01-FEB-06:13 | 0.00 | 01-FEB-00:10 | 121854.06 | 06-FEB-06:02 | 74781.30 | 21-FEB-05:02 | 57177.89 | 06-FEB-06:03 | 27686.34 | 06-FEB-06:02 | 0.00 |
March | 0.101822E+12 | 0.264062E+11 | 470.60 | 0.655085E+11 | 0.363135E+11 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 122300.13 | 13-MAR-04:02 | 70214.55 | 20-MAR-04:02 | 57465.18 | 25-MAR-05:03 | 28980.50 | 28-MAR-04:02 | 0.00 |
April | 0.107306E+12 | 0.275744E+11 | 448.00 | 0.625268E+11 | 0.447794E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 122737.80 | 06-APR-04:02 | 71437.43 | 18-APR-04:02 | 58362.87 | 06-APR-04:02 | 28939.62 | 12-APR-04:02 | 0.00 |
May | 0.122319E+12 | 0.311763E+11 | 471.84 | 0.660339E+11 | 0.562848E+11 | 0.00 | 1.00 | 01-MAY-00:32 | 0.00 | 01-MAY-00:05 | 125521.91 | 24-MAY-04:02 | 71332.26 | 01-MAY-04:02 | 75236.70 | 22-MAY-04:04 | 29609.81 | 10-MAY-04:02 | 0.00 |
June | 0.122935E+12 | 0.314338E+11 | 458.45 | 0.667365E+11 | 0.561985E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 125338.29 | 10-JUN-05:03 | 70847.39 | 19-JUN-04:02 | 69183.22 | 10-JUN-04:02 | 33038.23 | 11-JUN-13:52 | 0.00 |
July | 0.964424E+11 | 0.239236E+11 | 445.42 | 0.564873E+11 | 0.399552E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 120216.49 | 10-JUL-04:02 | 73829.30 | 05-JUL-04:02 | 49112.23 | 10-JUL-04:02 | 28063.81 | 24-JUL-04:02 | 0.00 |
August | 0.113340E+12 | 0.280068E+11 | 459.53 | 0.594746E+11 | 0.538659E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 126337.75 | 21-AUG-05:03 | 73846.70 | 28-AUG-04:02 | 75729.45 | 21-AUG-04:02 | 29897.94 | 02-AUG-04:03 | 0.00 |
September | 0.103357E+12 | 0.255751E+11 | 435.52 | 0.555721E+11 | 0.477850E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 122755.68 | 25-SEP-04:02 | 74858.51 | 05-SEP-04:02 | 57145.75 | 02-SEP-05:03 | 28538.61 | 25-SEP-04:02 | 0.00 |
October | 0.100201E+12 | 0.245012E+11 | 438.70 | 0.545722E+11 | 0.456285E+11 | 0.00 | 1.00 | 01-OCT-06:26 | 0.00 | 01-OCT-00:10 | 125038.11 | 30-OCT-04:02 | 72147.58 | 16-OCT-04:02 | 62184.20 | 30-OCT-04:02 | 28338.17 | 30-OCT-04:02 | 0.00 |
November | 0.926523E+11 | 0.229032E+11 | 421.14 | 0.542995E+11 | 0.383528E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 121741.86 | 13-NOV-05:02 | 72538.85 | 20-NOV-05:02 | 52527.63 | 13-NOV-05:02 | 28049.75 | 13-NOV-05:02 | 0.00 |
December | 0.852963E+11 | 0.212887E+11 | 427.15 | 0.539889E+11 | 0.313074E+11 | 0.00 | 1.00 | 01-DEC-07:30 | 0.00 | 01-DEC-00:10 | 105244.60 | 30-DEC-06:03 | 68871.27 | 26-DEC-07:03 | 45880.61 | 30-DEC-06:03 | 24089.59 | 30-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.121598E+13 | 0.306231E+12 | 5316.42 | 0.708210E+12 | 0.507770E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.833501E+11 | 0.212887E+11 | 402.92 | 0.539889E+11 | 0.280750E+11 | 0.00 | 1.00 | 0.00 | 105244.60 | 68871.27 | 45880.61 | 24089.59 | 0.00 | ||||||
Maximum of Months | 0.122935E+12 | 0.314338E+11 | 471.84 | 0.667365E+11 | 0.562848E+11 | 0.00 | 1.00 | 0.00 | 126337.75 | 74858.51 | 75729.45 | 33038.23 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.911986E+11 | 0.232377E+11 | 435.33 | 0.616998E+11 | 0.294988E+11 | 0.00 | 1.00 | 01-JAN-07:55 | 0.00 | 01-JAN-00:10 | 122704.10 | 09-JAN-05:02 | 70811.44 | 05-JAN-15:00 | 60215.61 | 09-JAN-05:02 | 27835.28 | 09-JAN-05:02 | 0.00 |
February | 0.881668E+11 | 0.227887E+11 | 402.82 | 0.597585E+11 | 0.284084E+11 | 0.00 | 1.00 | 01-FEB-08:50 | 0.00 | 01-FEB-00:10 | 140527.96 | 06-FEB-06:02 | 77799.12 | 26-FEB-15:02 | 64300.70 | 06-FEB-06:02 | 31990.02 | 06-FEB-06:02 | 0.00 |
March | 0.108181E+12 | 0.281902E+11 | 469.66 | 0.715662E+11 | 0.366146E+11 | 0.00 | 1.00 | 01-MAR-05:42 | 0.00 | 01-MAR-00:10 | 141991.55 | 13-MAR-04:02 | 85911.99 | 19-MAR-14:52 | 68969.75 | 28-MAR-04:02 | 33405.02 | 28-MAR-04:02 | 0.00 |
April | 0.114486E+12 | 0.295259E+11 | 452.60 | 0.690286E+11 | 0.454576E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 142516.56 | 12-APR-04:02 | 83699.54 | 02-APR-15:02 | 68934.38 | 12-APR-04:02 | 34958.51 | 02-APR-15:02 | 0.00 |
May | 0.129001E+12 | 0.330108E+11 | 475.02 | 0.720743E+11 | 0.569268E+11 | 0.00 | 1.00 | 01-MAY-00:32 | 0.00 | 01-MAY-00:05 | 145677.94 | 13-MAY-05:03 | 81958.60 | 07-MAY-14:42 | 89734.61 | 22-MAY-04:04 | 34891.24 | 07-MAY-15:22 | 0.00 |
June | 0.129689E+12 | 0.332923E+11 | 460.85 | 0.730264E+11 | 0.566625E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 145245.07 | 10-JUN-05:03 | 86209.43 | 18-JUN-13:22 | 82844.59 | 10-JUN-04:02 | 38285.51 | 11-JUN-13:52 | 0.00 |
July | 0.101645E+12 | 0.253118E+11 | 448.50 | 0.612043E+11 | 0.404404E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 136825.78 | 10-JUL-04:02 | 81632.59 | 31-JUL-04:02 | 56964.32 | 10-JUL-04:02 | 31971.94 | 10-JUL-04:02 | 0.00 |
August | 0.118269E+12 | 0.293127E+11 | 459.26 | 0.640731E+11 | 0.541964E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 145245.07 | 12-AUG-05:03 | 79779.20 | 28-AUG-04:02 | 79812.15 | 21-AUG-04:02 | 36605.89 | 13-AUG-12:53 | 0.00 |
September | 0.108291E+12 | 0.268860E+11 | 435.95 | 0.602179E+11 | 0.480732E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 142289.89 | 25-SEP-04:02 | 85286.39 | 05-SEP-04:02 | 68254.49 | 25-SEP-04:02 | 33074.72 | 25-SEP-04:02 | 0.00 |
October | 0.104082E+12 | 0.255248E+11 | 438.78 | 0.581595E+11 | 0.459221E+11 | 0.00 | 1.00 | 01-OCT-06:22 | 0.00 | 01-OCT-00:10 | 145416.45 | 30-OCT-04:02 | 81387.73 | 16-OCT-04:02 | 74977.56 | 30-OCT-04:02 | 32886.52 | 30-OCT-04:02 | 0.00 |
November | 0.967738E+11 | 0.240010E+11 | 422.50 | 0.580817E+11 | 0.386921E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 132464.19 | 13-NOV-05:02 | 71210.05 | 13-NOV-05:02 | 61254.13 | 13-NOV-05:02 | 30566.44 | 13-NOV-05:02 | 0.00 |
December | 0.894581E+11 | 0.224329E+11 | 428.93 | 0.576752E+11 | 0.317829E+11 | 0.00 | 1.00 | 01-DEC-08:65 | 0.00 | 01-DEC-00:10 | 102248.03 | 30-DEC-06:03 | 69822.63 | 26-DEC-15:00 | 47216.84 | 30-DEC-06:03 | 24798.50 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.127924E+13 | 0.323515E+12 | 5330.19 | 0.766565E+12 | 0.512676E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.881668E+11 | 0.224329E+11 | 402.82 | 0.576752E+11 | 0.284084E+11 | 0.00 | 1.00 | 0.00 | 102248.03 | 69822.63 | 47216.84 | 24798.50 | 0.00 | ||||||
Maximum of Months | 0.129689E+12 | 0.332923E+11 | 475.02 | 0.730264E+11 | 0.569268E+11 | 0.00 | 1.00 | 0.00 | 145677.94 | 86209.43 | 89734.61 | 38285.51 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.11 | 0.00 | 402.11 | 912.89 | 202.08 | 0.00 | 0.00 | 0.00 |
February | 428.94 | 0.00 | 428.94 | 1021.73 | 155.06 | 0.00 | 0.00 | 0.00 |
March | 440.23 | 0.00 | 440.23 | 1111.85 | 103.38 | 0.00 | 0.00 | 0.00 |
April | 479.08 | 6.79 | 472.29 | 1246.58 | 45.94 | 0.00 | 0.00 | 0.00 |
May | 614.13 | 65.42 | 548.70 | 1590.13 | 55.86 | 0.00 | 0.00 | 0.00 |
June | 750.18 | 151.61 | 598.57 | 1888.34 | 64.27 | 0.00 | 0.00 | 0.00 |
July | 645.08 | 67.62 | 577.47 | 1483.53 | 112.12 | 0.00 | 0.00 | 0.00 |
August | 531.11 | 22.65 | 508.47 | 1242.15 | 83.73 | 0.00 | 0.00 | 0.00 |
September | 452.18 | 0.22 | 451.97 | 1090.97 | 85.04 | 0.00 | 0.00 | 0.00 |
October | 435.70 | 0.00 | 435.70 | 972.86 | 111.35 | 0.00 | 0.00 | 0.00 |
November | 412.27 | 0.00 | 412.27 | 929.63 | 135.50 | 0.00 | 0.00 | 0.00 |
December | 390.65 | 0.00 | 390.65 | 879.80 | 219.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 498.77 | 26.26 | 472.51 | 1197.98 | 114.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.65 | 0.00 | 390.65 | 879.80 | 45.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.18 | 151.61 | 598.57 | 1888.34 | 219.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.92 | 174.22 | 342.71 | 1079.29 | 127.80 | 0.00 | 0.00 | 0.00 |
February | 586.19 | 214.93 | 371.26 | 1252.13 | 96.47 | 0.00 | 0.00 | 0.00 |
March | 639.06 | 250.25 | 388.81 | 1398.94 | 62.83 | 0.00 | 0.00 | 0.00 |
April | 645.87 | 246.75 | 399.12 | 1452.25 | 28.46 | 0.00 | 0.00 | 0.00 |
May | 555.18 | 168.05 | 387.13 | 1301.38 | 35.69 | 0.00 | 0.00 | 0.00 |
June | 591.31 | 194.75 | 396.57 | 1366.85 | 40.11 | 0.00 | 0.00 | 0.00 |
July | 505.06 | 113.15 | 391.92 | 1098.50 | 71.58 | 0.00 | 0.00 | 0.00 |
August | 555.83 | 163.39 | 392.44 | 1191.63 | 54.58 | 0.00 | 0.00 | 0.00 |
September | 521.99 | 142.25 | 379.75 | 1148.82 | 56.78 | 0.00 | 0.00 | 0.00 |
October | 489.22 | 125.16 | 364.06 | 1024.66 | 74.01 | 0.00 | 0.00 | 0.00 |
November | 473.47 | 130.84 | 342.63 | 996.95 | 89.56 | 0.00 | 0.00 | 0.00 |
December | 484.52 | 155.49 | 329.03 | 1007.55 | 141.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.61 | 172.87 | 373.74 | 1192.23 | 73.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.47 | 113.15 | 329.03 | 996.95 | 28.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 645.87 | 250.25 | 399.12 | 1452.25 | 141.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1064.65 | 444.18 | 620.46 | 2244.30 | 206.57 | 0.00 | 0.00 | 0.00 |
February | 904.04 | 294.75 | 609.29 | 2052.21 | 153.98 | 0.00 | 0.00 | 0.00 |
March | 616.96 | 82.86 | 534.10 | 1550.80 | 98.23 | 0.00 | 0.00 | 0.00 |
April | 459.97 | 0.21 | 459.77 | 1213.49 | 40.98 | 0.00 | 0.00 | 0.00 |
May | 460.29 | 0.00 | 460.29 | 1245.82 | 51.17 | 0.00 | 0.00 | 0.00 |
June | 458.63 | 0.00 | 458.63 | 1236.61 | 56.58 | 0.00 | 0.00 | 0.00 |
July | 472.46 | 0.00 | 472.46 | 1102.97 | 105.81 | 0.00 | 0.00 | 0.00 |
August | 459.94 | 0.71 | 459.23 | 1083.24 | 77.11 | 0.00 | 0.00 | 0.00 |
September | 509.19 | 16.63 | 492.56 | 1221.56 | 85.25 | 0.00 | 0.00 | 0.00 |
October | 666.17 | 106.21 | 559.95 | 1466.61 | 117.68 | 0.00 | 0.00 | 0.00 |
November | 866.24 | 264.28 | 601.96 | 1856.06 | 145.12 | 0.00 | 0.00 | 0.00 |
December | 1064.10 | 452.73 | 611.37 | 2210.22 | 229.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 665.96 | 138.01 | 527.95 | 1537.85 | 114.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.63 | 0.00 | 458.63 | 1083.24 | 40.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1064.65 | 452.73 | 620.46 | 2244.30 | 229.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.76 | 184.17 | 339.59 | 1109.94 | 141.53 | 0.00 | 0.00 | 0.00 |
February | 575.23 | 203.56 | 371.67 | 1245.78 | 108.24 | 0.00 | 0.00 | 0.00 |
March | 644.79 | 254.68 | 390.11 | 1420.72 | 77.26 | 0.00 | 0.00 | 0.00 |
April | 647.98 | 248.19 | 399.80 | 1448.89 | 34.98 | 0.00 | 0.00 | 0.00 |
May | 551.36 | 163.34 | 388.02 | 1286.95 | 35.90 | 0.00 | 0.00 | 0.00 |
June | 597.47 | 205.93 | 391.54 | 1371.27 | 41.02 | 0.00 | 0.00 | 0.00 |
July | 509.37 | 120.12 | 389.25 | 1107.63 | 73.49 | 0.00 | 0.00 | 0.00 |
August | 553.79 | 164.00 | 389.79 | 1182.34 | 55.62 | 0.00 | 0.00 | 0.00 |
September | 518.71 | 143.87 | 374.84 | 1138.67 | 59.38 | 0.00 | 0.00 | 0.00 |
October | 487.17 | 125.58 | 361.59 | 1022.07 | 77.42 | 0.00 | 0.00 | 0.00 |
November | 475.09 | 129.57 | 345.52 | 1006.30 | 93.77 | 0.00 | 0.00 | 0.00 |
December | 486.21 | 159.05 | 327.16 | 1030.42 | 152.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 547.22 | 174.87 | 372.35 | 1196.71 | 79.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.09 | 120.12 | 327.16 | 1006.30 | 34.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.98 | 254.68 | 399.80 | 1448.89 | 152.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.03 | 0.00 | 134.03 | 305.46 | 70.99 | 0.00 | 0.00 | 0.00 |
February | 142.97 | 0.00 | 142.97 | 342.51 | 55.07 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 373.25 | 36.06 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.42 | 419.09 | 15.82 | 0.00 | 0.00 | 0.00 |
May | 204.70 | 21.81 | 182.89 | 532.71 | 20.73 | 0.00 | 0.00 | 0.00 |
June | 250.05 | 50.53 | 199.51 | 631.60 | 23.95 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.48 | 496.72 | 41.72 | 0.00 | 0.00 | 0.00 |
August | 177.03 | 7.55 | 169.48 | 414.16 | 32.24 | 0.00 | 0.00 | 0.00 |
September | 150.72 | 0.07 | 150.65 | 364.93 | 31.12 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 325.99 | 40.07 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 311.13 | 49.45 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 293.40 | 79.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 401.06 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 293.40 | 15.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.05 | 50.53 | 199.51 | 631.60 | 79.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.04 | 0.00 | 134.04 | 305.48 | 71.00 | 0.00 | 0.00 | 0.00 |
February | 142.98 | 0.00 | 142.98 | 342.52 | 55.08 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 373.27 | 36.07 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.43 | 419.11 | 15.82 | 0.00 | 0.00 | 0.00 |
May | 204.71 | 21.81 | 182.90 | 532.74 | 20.73 | 0.00 | 0.00 | 0.00 |
June | 250.06 | 50.53 | 199.52 | 631.63 | 23.95 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.49 | 496.74 | 41.73 | 0.00 | 0.00 | 0.00 |
August | 177.04 | 7.55 | 169.49 | 414.18 | 32.24 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 0.07 | 150.65 | 364.95 | 31.12 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 326.01 | 40.08 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 311.15 | 49.45 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 293.42 | 79.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 401.08 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 293.42 | 15.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.06 | 50.53 | 199.52 | 631.63 | 79.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.04 | 0.00 | 134.04 | 305.48 | 71.00 | 0.00 | 0.00 | 0.00 |
February | 142.98 | 0.00 | 142.98 | 342.52 | 55.08 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 373.27 | 36.07 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.43 | 419.11 | 15.82 | 0.00 | 0.00 | 0.00 |
May | 204.71 | 21.81 | 182.90 | 532.74 | 20.73 | 0.00 | 0.00 | 0.00 |
June | 250.06 | 50.53 | 199.52 | 631.63 | 23.95 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.49 | 496.74 | 41.73 | 0.00 | 0.00 | 0.00 |
August | 177.04 | 7.55 | 169.49 | 414.18 | 32.24 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 0.07 | 150.65 | 364.95 | 31.12 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 326.01 | 40.08 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 311.15 | 49.45 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 293.42 | 79.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 401.08 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 293.42 | 15.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.06 | 50.53 | 199.52 | 631.63 | 79.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 497.26 | 167.59 | 329.67 | 1040.25 | 135.53 | 0.00 | 0.00 | 0.00 |
February | 563.89 | 206.75 | 357.14 | 1207.69 | 106.04 | 0.00 | 0.00 | 0.00 |
March | 614.74 | 240.73 | 374.01 | 1351.72 | 71.55 | 0.00 | 0.00 | 0.00 |
April | 621.29 | 237.36 | 383.93 | 1401.77 | 33.27 | 0.00 | 0.00 | 0.00 |
May | 534.05 | 161.66 | 372.40 | 1253.84 | 40.41 | 0.00 | 0.00 | 0.00 |
June | 568.81 | 187.34 | 381.48 | 1317.61 | 44.79 | 0.00 | 0.00 | 0.00 |
July | 485.85 | 108.84 | 377.00 | 1059.11 | 79.40 | 0.00 | 0.00 | 0.00 |
August | 534.68 | 157.17 | 377.51 | 1146.16 | 64.77 | 0.00 | 0.00 | 0.00 |
September | 502.13 | 136.83 | 365.30 | 1106.60 | 64.77 | 0.00 | 0.00 | 0.00 |
October | 470.61 | 120.40 | 350.21 | 988.64 | 82.17 | 0.00 | 0.00 | 0.00 |
November | 455.46 | 125.86 | 329.59 | 961.23 | 99.47 | 0.00 | 0.00 | 0.00 |
December | 466.09 | 149.57 | 316.51 | 969.88 | 153.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 525.81 | 166.29 | 359.52 | 1149.39 | 81.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.46 | 108.84 | 316.51 | 961.23 | 33.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.29 | 240.73 | 383.93 | 1401.77 | 153.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.66 | 6.63 | 13.03 | 41.13 | 5.36 | 0.00 | 0.00 | 0.00 |
February | 22.30 | 8.17 | 14.12 | 47.75 | 4.19 | 0.00 | 0.00 | 0.00 |
March | 24.31 | 9.52 | 14.79 | 53.45 | 2.83 | 0.00 | 0.00 | 0.00 |
April | 24.57 | 9.38 | 15.18 | 55.42 | 1.32 | 0.00 | 0.00 | 0.00 |
May | 21.12 | 6.39 | 14.72 | 49.58 | 1.60 | 0.00 | 0.00 | 0.00 |
June | 22.49 | 7.41 | 15.08 | 52.10 | 1.77 | 0.00 | 0.00 | 0.00 |
July | 19.21 | 4.30 | 14.91 | 41.88 | 3.14 | 0.00 | 0.00 | 0.00 |
August | 21.14 | 6.21 | 14.93 | 45.32 | 2.56 | 0.00 | 0.00 | 0.00 |
September | 19.85 | 5.41 | 14.44 | 43.75 | 2.56 | 0.00 | 0.00 | 0.00 |
October | 18.61 | 4.76 | 13.85 | 39.09 | 3.25 | 0.00 | 0.00 | 0.00 |
November | 18.01 | 4.98 | 13.03 | 38.01 | 3.93 | 0.00 | 0.00 | 0.00 |
December | 18.43 | 5.91 | 12.51 | 38.35 | 6.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.79 | 6.57 | 14.22 | 45.45 | 3.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.01 | 4.30 | 12.51 | 38.01 | 1.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.57 | 9.52 | 15.18 | 55.42 | 6.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.88 | 148.06 | 206.82 | 744.12 | 78.90 | 0.00 | 0.00 | 0.00 |
February | 301.34 | 98.25 | 203.10 | 679.44 | 60.68 | 0.00 | 0.00 | 0.00 |
March | 205.65 | 27.62 | 178.03 | 514.66 | 37.92 | 0.00 | 0.00 | 0.00 |
April | 153.32 | 0.07 | 153.25 | 403.60 | 15.14 | 0.00 | 0.00 | 0.00 |
May | 153.43 | 0.00 | 153.43 | 413.59 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 152.88 | 0.00 | 152.88 | 409.33 | 20.72 | 0.00 | 0.00 | 0.00 |
July | 157.48 | 0.00 | 157.48 | 367.62 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 153.31 | 0.24 | 153.08 | 358.44 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 169.73 | 5.54 | 164.18 | 406.28 | 32.22 | 0.00 | 0.00 | 0.00 |
October | 222.05 | 35.40 | 186.65 | 488.75 | 44.62 | 0.00 | 0.00 | 0.00 |
November | 288.74 | 88.09 | 200.65 | 616.23 | 56.78 | 0.00 | 0.00 | 0.00 |
December | 354.69 | 150.91 | 203.79 | 733.34 | 88.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.98 | 46.00 | 175.98 | 510.47 | 43.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 0.00 | 152.88 | 358.44 | 15.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.88 | 150.91 | 206.82 | 744.12 | 88.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.88 | 148.06 | 206.82 | 744.12 | 78.90 | 0.00 | 0.00 | 0.00 |
February | 301.34 | 98.25 | 203.10 | 679.44 | 60.68 | 0.00 | 0.00 | 0.00 |
March | 205.65 | 27.62 | 178.03 | 514.66 | 37.92 | 0.00 | 0.00 | 0.00 |
April | 153.32 | 0.07 | 153.25 | 403.60 | 15.14 | 0.00 | 0.00 | 0.00 |
May | 153.43 | 0.00 | 153.43 | 413.59 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 152.88 | 0.00 | 152.88 | 409.33 | 20.72 | 0.00 | 0.00 | 0.00 |
July | 157.48 | 0.00 | 157.48 | 367.62 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 153.31 | 0.24 | 153.08 | 358.44 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 169.73 | 5.54 | 164.18 | 406.28 | 32.22 | 0.00 | 0.00 | 0.00 |
October | 222.05 | 35.40 | 186.65 | 488.75 | 44.62 | 0.00 | 0.00 | 0.00 |
November | 288.74 | 88.09 | 200.65 | 616.23 | 56.78 | 0.00 | 0.00 | 0.00 |
December | 354.69 | 150.91 | 203.79 | 733.34 | 88.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.98 | 46.00 | 175.98 | 510.47 | 43.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 0.00 | 152.88 | 358.44 | 15.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.88 | 150.91 | 206.82 | 744.12 | 88.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.85 | 148.05 | 206.81 | 744.07 | 78.89 | 0.00 | 0.00 | 0.00 |
February | 301.32 | 98.24 | 203.08 | 679.39 | 60.67 | 0.00 | 0.00 | 0.00 |
March | 205.64 | 27.62 | 178.02 | 514.63 | 37.92 | 0.00 | 0.00 | 0.00 |
April | 153.31 | 0.07 | 153.24 | 403.57 | 15.14 | 0.00 | 0.00 | 0.00 |
May | 153.42 | 0.00 | 153.42 | 413.56 | 19.20 | 0.00 | 0.00 | 0.00 |
June | 152.87 | 0.00 | 152.87 | 409.30 | 20.72 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 0.00 | 157.47 | 367.60 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 153.30 | 0.24 | 153.07 | 358.41 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 169.72 | 5.54 | 164.17 | 406.26 | 32.22 | 0.00 | 0.00 | 0.00 |
October | 222.04 | 35.40 | 186.64 | 488.71 | 44.62 | 0.00 | 0.00 | 0.00 |
November | 288.72 | 88.08 | 200.64 | 616.19 | 56.77 | 0.00 | 0.00 | 0.00 |
December | 354.67 | 150.90 | 203.77 | 733.30 | 88.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.97 | 46.00 | 175.97 | 510.44 | 43.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.87 | 0.00 | 152.87 | 358.41 | 15.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.85 | 150.90 | 206.81 | 744.07 | 88.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 503.83 | 177.16 | 326.67 | 1067.73 | 150.42 | 0.00 | 0.00 | 0.00 |
February | 553.35 | 195.82 | 357.53 | 1200.06 | 119.13 | 0.00 | 0.00 | 0.00 |
March | 620.26 | 244.99 | 375.27 | 1370.56 | 85.93 | 0.00 | 0.00 | 0.00 |
April | 623.33 | 238.74 | 384.59 | 1396.87 | 40.59 | 0.00 | 0.00 | 0.00 |
May | 530.38 | 157.13 | 373.26 | 1238.33 | 41.98 | 0.00 | 0.00 | 0.00 |
June | 574.74 | 198.10 | 376.64 | 1320.27 | 47.11 | 0.00 | 0.00 | 0.00 |
July | 489.99 | 115.55 | 374.44 | 1066.63 | 83.22 | 0.00 | 0.00 | 0.00 |
August | 532.72 | 157.76 | 374.96 | 1135.75 | 67.56 | 0.00 | 0.00 | 0.00 |
September | 498.97 | 138.39 | 360.58 | 1095.38 | 68.07 | 0.00 | 0.00 | 0.00 |
October | 468.63 | 120.80 | 347.83 | 983.48 | 86.88 | 0.00 | 0.00 | 0.00 |
November | 457.01 | 124.64 | 332.37 | 967.35 | 104.85 | 0.00 | 0.00 | 0.00 |
December | 467.71 | 153.00 | 314.72 | 989.13 | 166.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 526.40 | 168.21 | 358.18 | 1151.77 | 88.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.01 | 115.55 | 314.72 | 967.35 | 40.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.33 | 244.99 | 384.59 | 1396.87 | 166.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.92 | 7.00 | 12.92 | 42.22 | 5.95 | 0.00 | 0.00 | 0.00 |
February | 21.88 | 7.74 | 14.14 | 47.45 | 4.71 | 0.00 | 0.00 | 0.00 |
March | 24.52 | 9.69 | 14.84 | 54.19 | 3.40 | 0.00 | 0.00 | 0.00 |
April | 24.65 | 9.44 | 15.21 | 55.23 | 1.60 | 0.00 | 0.00 | 0.00 |
May | 20.97 | 6.21 | 14.76 | 48.96 | 1.66 | 0.00 | 0.00 | 0.00 |
June | 22.72 | 7.83 | 14.89 | 52.20 | 1.86 | 0.00 | 0.00 | 0.00 |
July | 19.37 | 4.57 | 14.81 | 42.17 | 3.29 | 0.00 | 0.00 | 0.00 |
August | 21.06 | 6.24 | 14.83 | 44.91 | 2.67 | 0.00 | 0.00 | 0.00 |
September | 19.73 | 5.47 | 14.26 | 43.31 | 2.69 | 0.00 | 0.00 | 0.00 |
October | 18.53 | 4.78 | 13.75 | 38.89 | 3.44 | 0.00 | 0.00 | 0.00 |
November | 18.07 | 4.93 | 13.14 | 38.25 | 4.15 | 0.00 | 0.00 | 0.00 |
December | 18.49 | 6.05 | 12.44 | 39.11 | 6.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.81 | 6.65 | 14.16 | 45.54 | 3.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.07 | 4.57 | 12.44 | 38.25 | 1.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.65 | 9.69 | 15.21 | 55.23 | 6.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.11 | 0.00 | 402.11 | 919.01 | 210.13 | 0.00 | 0.00 | 0.00 |
February | 428.94 | 0.00 | 428.94 | 1029.91 | 161.96 | 0.00 | 0.00 | 0.00 |
March | 440.23 | 0.00 | 440.23 | 1122.49 | 105.79 | 0.00 | 0.00 | 0.00 |
April | 479.08 | 6.79 | 472.29 | 1260.76 | 45.99 | 0.00 | 0.00 | 0.00 |
May | 614.13 | 65.42 | 548.70 | 1603.70 | 56.35 | 0.00 | 0.00 | 0.00 |
June | 750.18 | 151.61 | 598.57 | 1902.41 | 63.79 | 0.00 | 0.00 | 0.00 |
July | 645.08 | 67.62 | 577.47 | 1495.78 | 113.52 | 0.00 | 0.00 | 0.00 |
August | 531.11 | 22.65 | 508.47 | 1250.73 | 86.31 | 0.00 | 0.00 | 0.00 |
September | 452.18 | 0.22 | 451.97 | 1102.00 | 85.80 | 0.00 | 0.00 | 0.00 |
October | 435.70 | 0.00 | 435.70 | 981.13 | 113.89 | 0.00 | 0.00 | 0.00 |
November | 412.27 | 0.00 | 412.27 | 936.35 | 142.65 | 0.00 | 0.00 | 0.00 |
December | 390.65 | 0.00 | 390.65 | 884.29 | 230.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 498.77 | 26.26 | 472.51 | 1207.82 | 118.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.65 | 0.00 | 390.65 | 884.29 | 45.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.18 | 151.61 | 598.57 | 1902.41 | 230.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.92 | 174.22 | 342.71 | 1084.22 | 132.53 | 0.00 | 0.00 | 0.00 |
February | 586.19 | 214.93 | 371.26 | 1258.62 | 100.94 | 0.00 | 0.00 | 0.00 |
March | 639.06 | 250.25 | 388.81 | 1407.58 | 64.78 | 0.00 | 0.00 | 0.00 |
April | 645.87 | 246.75 | 399.12 | 1462.47 | 28.77 | 0.00 | 0.00 | 0.00 |
May | 555.18 | 168.05 | 387.13 | 1310.61 | 36.09 | 0.00 | 0.00 | 0.00 |
June | 591.31 | 194.75 | 396.57 | 1376.45 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 505.06 | 113.15 | 391.92 | 1106.57 | 72.58 | 0.00 | 0.00 | 0.00 |
August | 555.83 | 163.39 | 392.44 | 1197.74 | 56.28 | 0.00 | 0.00 | 0.00 |
September | 521.99 | 142.25 | 379.75 | 1156.60 | 57.24 | 0.00 | 0.00 | 0.00 |
October | 489.22 | 125.16 | 364.06 | 1030.86 | 75.58 | 0.00 | 0.00 | 0.00 |
November | 473.47 | 130.84 | 342.63 | 1002.21 | 94.03 | 0.00 | 0.00 | 0.00 |
December | 484.52 | 155.49 | 329.03 | 1011.42 | 147.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.61 | 172.87 | 373.74 | 1199.43 | 75.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.47 | 113.15 | 329.03 | 1002.21 | 28.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 645.87 | 250.25 | 399.12 | 1462.47 | 147.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1064.65 | 444.18 | 620.46 | 2250.47 | 213.58 | 0.00 | 0.00 | 0.00 |
February | 904.04 | 294.75 | 609.29 | 2061.05 | 160.66 | 0.00 | 0.00 | 0.00 |
March | 616.96 | 82.86 | 534.10 | 1562.18 | 101.19 | 0.00 | 0.00 | 0.00 |
April | 459.97 | 0.21 | 459.77 | 1227.27 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 460.29 | 0.00 | 460.29 | 1258.90 | 52.00 | 0.00 | 0.00 | 0.00 |
June | 458.63 | 0.00 | 458.63 | 1249.81 | 56.49 | 0.00 | 0.00 | 0.00 |
July | 472.46 | 0.00 | 472.46 | 1114.55 | 107.54 | 0.00 | 0.00 | 0.00 |
August | 459.94 | 0.71 | 459.23 | 1091.45 | 80.16 | 0.00 | 0.00 | 0.00 |
September | 509.19 | 16.63 | 492.56 | 1232.95 | 86.11 | 0.00 | 0.00 | 0.00 |
October | 666.17 | 106.21 | 559.95 | 1475.85 | 120.11 | 0.00 | 0.00 | 0.00 |
November | 866.24 | 264.28 | 601.96 | 1864.03 | 151.58 | 0.00 | 0.00 | 0.00 |
December | 1064.10 | 452.73 | 611.37 | 2214.93 | 238.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 665.96 | 138.01 | 527.95 | 1547.81 | 117.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.63 | 0.00 | 458.63 | 1091.45 | 41.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1064.65 | 452.73 | 620.46 | 2250.47 | 238.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.76 | 184.17 | 339.59 | 1113.05 | 147.78 | 0.00 | 0.00 | 0.00 |
February | 575.23 | 203.56 | 371.67 | 1250.73 | 113.90 | 0.00 | 0.00 | 0.00 |
March | 644.79 | 254.68 | 390.11 | 1427.49 | 79.52 | 0.00 | 0.00 | 0.00 |
April | 647.98 | 248.19 | 399.80 | 1457.08 | 35.56 | 0.00 | 0.00 | 0.00 |
May | 551.36 | 163.34 | 388.02 | 1294.47 | 36.90 | 0.00 | 0.00 | 0.00 |
June | 597.47 | 205.93 | 391.54 | 1379.61 | 41.49 | 0.00 | 0.00 | 0.00 |
July | 509.37 | 120.12 | 389.25 | 1114.47 | 75.59 | 0.00 | 0.00 | 0.00 |
August | 553.79 | 164.00 | 389.79 | 1187.28 | 58.37 | 0.00 | 0.00 | 0.00 |
September | 518.71 | 143.87 | 374.84 | 1145.05 | 60.58 | 0.00 | 0.00 | 0.00 |
October | 487.17 | 125.58 | 361.59 | 1026.41 | 79.95 | 0.00 | 0.00 | 0.00 |
November | 475.09 | 129.57 | 345.52 | 1009.61 | 99.54 | 0.00 | 0.00 | 0.00 |
December | 486.21 | 159.05 | 327.16 | 1032.37 | 160.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 547.22 | 174.87 | 372.35 | 1202.25 | 82.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.09 | 120.12 | 327.16 | 1009.61 | 35.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.98 | 254.68 | 399.80 | 1457.08 | 160.74 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.244507E+10 | 0.541242E+09 |
February | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.247178E+10 | 0.375113E+09 |
March | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.297799E+10 | 0.276905E+09 |
April | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.323112E+10 | 0.119086E+09 |
May | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.425899E+10 | 0.149626E+09 |
June | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.489459E+10 | 0.166588E+09 |
July | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.397349E+10 | 0.300300E+09 |
August | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.332696E+10 | 0.224260E+09 |
September | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.282779E+10 | 0.220431E+09 |
October | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.260571E+10 | 0.298244E+09 |
November | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.240961E+10 | 0.351226E+09 |
December | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.235645E+10 | 0.588830E+09 |
Annual Sum or Average | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.377796E+11 | 0.361185E+10 |
Minimum of Months | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.235645E+10 | 0.119086E+09 |
Maximum of Months | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.489459E+10 | 0.588830E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.289076E+10 | 0.342289E+09 |
February | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.302915E+10 | 0.233385E+09 |
March | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.374691E+10 | 0.168278E+09 |
April | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.376422E+10 | 73767691.66 |
May | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.348562E+10 | 95583833.29 |
June | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.354287E+10 | 0.103953E+09 |
July | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.294221E+10 | 0.191728E+09 |
August | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.319167E+10 | 0.146198E+09 |
September | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.297775E+10 | 0.147170E+09 |
October | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.274445E+10 | 0.198223E+09 |
November | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.258409E+10 | 0.232135E+09 |
December | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.269862E+10 | 0.378314E+09 |
Annual Sum or Average | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.375983E+11 | 0.231103E+10 |
Minimum of Months | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.258409E+10 | 73767691.66 |
Maximum of Months | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.376422E+10 | 0.378314E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.601114E+10 | 0.553264E+09 |
February | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.496471E+10 | 0.372497E+09 |
March | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.415367E+10 | 0.263097E+09 |
April | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.314536E+10 | 0.106214E+09 |
May | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.333680E+10 | 0.137046E+09 |
June | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.320529E+10 | 0.146656E+09 |
July | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.295420E+10 | 0.283407E+09 |
August | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.290136E+10 | 0.206535E+09 |
September | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.316629E+10 | 0.220958E+09 |
October | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.392818E+10 | 0.315182E+09 |
November | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.481091E+10 | 0.376158E+09 |
December | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.591986E+10 | 0.614828E+09 |
Annual Sum or Average | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.484978E+11 | 0.359584E+10 |
Minimum of Months | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.290136E+10 | 0.106214E+09 |
Maximum of Months | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.601114E+10 | 0.614828E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.297288E+10 | 0.379076E+09 |
February | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.301380E+10 | 0.261858E+09 |
March | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.380525E+10 | 0.206922E+09 |
April | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.375552E+10 | 90672754.38 |
May | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.344697E+10 | 96157373.88 |
June | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.355433E+10 | 0.106334E+09 |
July | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.296668E+10 | 0.196840E+09 |
August | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.316678E+10 | 0.148984E+09 |
September | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.295143E+10 | 0.153911E+09 |
October | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.273752E+10 | 0.207358E+09 |
November | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.260832E+10 | 0.243041E+09 |
December | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.275988E+10 | 0.408035E+09 |
Annual Sum or Average | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.377394E+11 | 0.249919E+10 |
Minimum of Months | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.260832E+10 | 90672754.38 |
Maximum of Months | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.380525E+10 | 0.408035E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358988E+09 | 0.00 | 0.358988E+09 | 0.818152E+09 | 0.190151E+09 |
February | 0.345883E+09 | 0.00 | 0.345883E+09 | 0.828590E+09 | 0.133237E+09 |
March | 0.393016E+09 | 0.00 | 0.393016E+09 | 0.999702E+09 | 96595780.57 |
April | 0.413908E+09 | 5865858.05 | 0.408043E+09 | 0.108628E+10 | 40992972.61 |
May | 0.548267E+09 | 58406913.62 | 0.489860E+09 | 0.142682E+10 | 55517562.42 |
June | 0.648123E+09 | 0.130981E+09 | 0.517143E+09 | 0.163712E+10 | 62081736.38 |
July | 0.575902E+09 | 60364849.74 | 0.515537E+09 | 0.133042E+10 | 0.111753E+09 |
August | 0.474155E+09 | 20218349.67 | 0.453937E+09 | 0.110930E+10 | 86342969.70 |
September | 0.390669E+09 | 187073.42 | 0.390482E+09 | 0.945903E+09 | 80652035.28 |
October | 0.388972E+09 | 0.00 | 0.388972E+09 | 0.873142E+09 | 0.107334E+09 |
November | 0.356181E+09 | 0.00 | 0.356181E+09 | 0.806457E+09 | 0.128177E+09 |
December | 0.348752E+09 | 0.00 | 0.348752E+09 | 0.785853E+09 | 0.213296E+09 |
Annual Sum or Average | 0.524282E+10 | 0.276024E+09 | 0.496679E+10 | 0.126477E+11 | 0.130613E+10 |
Minimum of Months | 0.345883E+09 | 0.00 | 0.345883E+09 | 0.785853E+09 | 40992972.61 |
Maximum of Months | 0.648123E+09 | 0.130981E+09 | 0.517143E+09 | 0.163712E+10 | 0.213296E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359002E+09 | 0.00 | 0.359002E+09 | 0.818191E+09 | 0.190159E+09 |
February | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.828631E+09 | 0.133242E+09 |
March | 0.393032E+09 | 0.00 | 0.393032E+09 | 0.999753E+09 | 96598386.02 |
April | 0.413925E+09 | 5866015.72 | 0.408059E+09 | 0.108634E+10 | 40993314.53 |
May | 0.548287E+09 | 58408483.62 | 0.489878E+09 | 0.142688E+10 | 55519396.20 |
June | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163718E+10 | 62083928.01 |
July | 0.575922E+09 | 60366472.37 | 0.515556E+09 | 0.133047E+10 | 0.111757E+09 |
August | 0.474173E+09 | 20218893.15 | 0.453954E+09 | 0.110935E+10 | 86345971.73 |
September | 0.390684E+09 | 187078.45 | 0.390497E+09 | 0.945947E+09 | 80655021.78 |
October | 0.388987E+09 | 0.00 | 0.388987E+09 | 0.873181E+09 | 0.107338E+09 |
November | 0.356194E+09 | 0.00 | 0.356194E+09 | 0.806493E+09 | 0.128182E+09 |
December | 0.348766E+09 | 0.00 | 0.348766E+09 | 0.785889E+09 | 0.213306E+09 |
Annual Sum or Average | 0.524302E+10 | 0.276031E+09 | 0.496699E+10 | 0.126483E+11 | 0.130618E+10 |
Minimum of Months | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.785889E+09 | 40993314.53 |
Maximum of Months | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163718E+10 | 0.213306E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359002E+09 | 0.00 | 0.359002E+09 | 0.818191E+09 | 0.190159E+09 |
February | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.828631E+09 | 0.133242E+09 |
March | 0.393032E+09 | 0.00 | 0.393032E+09 | 0.999753E+09 | 96598386.02 |
April | 0.413925E+09 | 5866015.72 | 0.408059E+09 | 0.108634E+10 | 40993314.53 |
May | 0.548287E+09 | 58408483.62 | 0.489878E+09 | 0.142688E+10 | 55519396.20 |
June | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163718E+10 | 62083928.01 |
July | 0.575922E+09 | 60366472.37 | 0.515556E+09 | 0.133047E+10 | 0.111757E+09 |
August | 0.474173E+09 | 20218893.15 | 0.453954E+09 | 0.110935E+10 | 86345971.73 |
September | 0.390684E+09 | 187078.45 | 0.390497E+09 | 0.945947E+09 | 80655021.78 |
October | 0.388987E+09 | 0.00 | 0.388987E+09 | 0.873181E+09 | 0.107338E+09 |
November | 0.356194E+09 | 0.00 | 0.356194E+09 | 0.806493E+09 | 0.128182E+09 |
December | 0.348766E+09 | 0.00 | 0.348766E+09 | 0.785889E+09 | 0.213306E+09 |
Annual Sum or Average | 0.524302E+10 | 0.276031E+09 | 0.496699E+10 | 0.126483E+11 | 0.130618E+10 |
Minimum of Months | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.785889E+09 | 40993314.53 |
Maximum of Months | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163718E+10 | 0.213306E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133185E+10 | 0.448870E+09 | 0.882980E+09 | 0.278620E+10 | 0.362999E+09 |
February | 0.136415E+10 | 0.500163E+09 | 0.863989E+09 | 0.292165E+10 | 0.256527E+09 |
March | 0.164653E+10 | 0.644769E+09 | 0.100176E+10 | 0.362044E+10 | 0.191638E+09 |
April | 0.161039E+10 | 0.615233E+09 | 0.995154E+09 | 0.363338E+10 | 86235702.49 |
May | 0.143041E+10 | 0.432981E+09 | 0.997431E+09 | 0.335829E+10 | 0.108222E+09 |
June | 0.147437E+10 | 0.485576E+09 | 0.988790E+09 | 0.341523E+10 | 0.116104E+09 |
July | 0.130129E+10 | 0.291519E+09 | 0.100977E+10 | 0.283672E+10 | 0.212676E+09 |
August | 0.143209E+10 | 0.420973E+09 | 0.101112E+10 | 0.306987E+10 | 0.173486E+09 |
September | 0.130153E+10 | 0.354670E+09 | 0.946857E+09 | 0.286831E+10 | 0.167887E+09 |
October | 0.126048E+10 | 0.322474E+09 | 0.938006E+09 | 0.264799E+10 | 0.220089E+09 |
November | 0.118054E+10 | 0.326236E+09 | 0.854304E+09 | 0.249150E+10 | 0.257833E+09 |
December | 0.124836E+10 | 0.400610E+09 | 0.847753E+09 | 0.259772E+10 | 0.410216E+09 |
Annual Sum or Average | 0.165820E+11 | 0.524407E+10 | 0.113379E+11 | 0.362473E+11 | 0.256391E+10 |
Minimum of Months | 0.118054E+10 | 0.291519E+09 | 0.847753E+09 | 0.249150E+10 | 86235702.49 |
Maximum of Months | 0.164653E+10 | 0.644769E+09 | 0.101112E+10 | 0.363338E+10 | 0.410216E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52660145.69 | 17747905.58 | 34912240.10 | 0.110164E+09 | 14352657.50 |
February | 53937353.26 | 19776011.67 | 34161341.59 | 0.115519E+09 | 10142863.92 |
March | 65102162.17 | 25493581.81 | 39608580.36 | 0.143149E+09 | 7577183.23 |
April | 63673235.12 | 24325746.10 | 39347489.02 | 0.143661E+09 | 3409682.04 |
May | 56557228.11 | 17119695.80 | 39437532.32 | 0.132784E+09 | 4279000.53 |
June | 58295072.81 | 19199225.68 | 39095847.13 | 0.135035E+09 | 4590634.32 |
July | 51451763.28 | 11526410.80 | 39925352.48 | 0.112161E+09 | 8409007.79 |
August | 56623620.63 | 16644873.82 | 39978746.81 | 0.121380E+09 | 6859462.13 |
September | 51461181.99 | 14023326.63 | 37437855.36 | 0.113410E+09 | 6638118.43 |
October | 49838260.44 | 12750344.95 | 37087915.50 | 0.104699E+09 | 8702123.86 |
November | 46677498.68 | 12899084.95 | 33778413.73 | 98511535.76 | 10194482.70 |
December | 49359125.00 | 15839742.50 | 33519382.50 | 0.102711E+09 | 16219573.94 |
Annual Sum or Average | 0.655637E+09 | 0.207346E+09 | 0.448291E+09 | 0.143319E+10 | 0.101375E+09 |
Minimum of Months | 46677498.68 | 11526410.80 | 33519382.50 | 98511535.76 | 3409682.04 |
Maximum of Months | 65102162.17 | 25493581.81 | 39978746.81 | 0.143661E+09 | 16219573.94 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950500E+09 | 0.396558E+09 | 0.553943E+09 | 0.199305E+10 | 0.211325E+09 |
February | 0.729011E+09 | 0.237684E+09 | 0.491328E+09 | 0.164369E+10 | 0.146785E+09 |
March | 0.550815E+09 | 73974117.02 | 0.476841E+09 | 0.137847E+10 | 0.101567E+09 |
April | 0.397414E+09 | 178399.50 | 0.397235E+09 | 0.104612E+10 | 39234058.45 |
May | 0.410940E+09 | 0.00 | 0.410940E+09 | 0.110775E+10 | 51420212.79 |
June | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.106098E+10 | 53711925.70 |
July | 0.421806E+09 | 0.00 | 0.421806E+09 | 0.984635E+09 | 0.105389E+09 |
August | 0.410632E+09 | 634632.62 | 0.409997E+09 | 0.960035E+09 | 81821196.92 |
September | 0.439934E+09 | 14368407.66 | 0.425565E+09 | 0.105309E+10 | 83516470.83 |
October | 0.594745E+09 | 94826739.91 | 0.499918E+09 | 0.130906E+10 | 0.119519E+09 |
November | 0.748416E+09 | 0.228330E+09 | 0.520085E+09 | 0.159728E+10 | 0.147170E+09 |
December | 0.950014E+09 | 0.404190E+09 | 0.545824E+09 | 0.196418E+10 | 0.237233E+09 |
Annual Sum or Average | 0.700048E+10 | 0.145074E+10 | 0.554974E+10 | 0.160983E+11 | 0.137869E+10 |
Minimum of Months | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.960035E+09 | 39234058.45 |
Maximum of Months | 0.950500E+09 | 0.404190E+09 | 0.553943E+09 | 0.199305E+10 | 0.237233E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950500E+09 | 0.396558E+09 | 0.553943E+09 | 0.199305E+10 | 0.211325E+09 |
February | 0.729011E+09 | 0.237684E+09 | 0.491328E+09 | 0.164369E+10 | 0.146785E+09 |
March | 0.550815E+09 | 73974117.02 | 0.476841E+09 | 0.137847E+10 | 0.101567E+09 |
April | 0.397414E+09 | 178399.50 | 0.397235E+09 | 0.104612E+10 | 39234058.45 |
May | 0.410940E+09 | 0.00 | 0.410940E+09 | 0.110775E+10 | 51420212.79 |
June | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.106098E+10 | 53711925.70 |
July | 0.421806E+09 | 0.00 | 0.421806E+09 | 0.984635E+09 | 0.105389E+09 |
August | 0.410632E+09 | 634632.62 | 0.409997E+09 | 0.960035E+09 | 81821196.92 |
September | 0.439934E+09 | 14368407.66 | 0.425565E+09 | 0.105309E+10 | 83516470.83 |
October | 0.594745E+09 | 94826739.91 | 0.499918E+09 | 0.130906E+10 | 0.119519E+09 |
November | 0.748416E+09 | 0.228330E+09 | 0.520085E+09 | 0.159728E+10 | 0.147170E+09 |
December | 0.950014E+09 | 0.404190E+09 | 0.545824E+09 | 0.196418E+10 | 0.237233E+09 |
Annual Sum or Average | 0.700048E+10 | 0.145074E+10 | 0.554974E+10 | 0.160983E+11 | 0.137869E+10 |
Minimum of Months | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.960035E+09 | 39234058.45 |
Maximum of Months | 0.950500E+09 | 0.404190E+09 | 0.553943E+09 | 0.199305E+10 | 0.237233E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950440E+09 | 0.396533E+09 | 0.553908E+09 | 0.199293E+10 | 0.211311E+09 |
February | 0.728965E+09 | 0.237669E+09 | 0.491297E+09 | 0.164359E+10 | 0.146776E+09 |
March | 0.550780E+09 | 73969442.28 | 0.476811E+09 | 0.137838E+10 | 0.101560E+09 |
April | 0.397389E+09 | 178388.23 | 0.397210E+09 | 0.104606E+10 | 39231579.08 |
May | 0.410914E+09 | 0.00 | 0.410914E+09 | 0.110768E+10 | 51416963.32 |
June | 0.396228E+09 | 0.00 | 0.396228E+09 | 0.106091E+10 | 53708531.41 |
July | 0.421779E+09 | 0.00 | 0.421779E+09 | 0.984572E+09 | 0.105382E+09 |
August | 0.410606E+09 | 634592.51 | 0.409971E+09 | 0.959974E+09 | 81816026.29 |
September | 0.439906E+09 | 14367499.66 | 0.425538E+09 | 0.105302E+10 | 83511193.06 |
October | 0.594708E+09 | 94820747.40 | 0.499887E+09 | 0.130897E+10 | 0.119512E+09 |
November | 0.748368E+09 | 0.228316E+09 | 0.520052E+09 | 0.159718E+10 | 0.147160E+09 |
December | 0.949954E+09 | 0.404165E+09 | 0.545789E+09 | 0.196406E+10 | 0.237219E+09 |
Annual Sum or Average | 0.700004E+10 | 0.145065E+10 | 0.554939E+10 | 0.160973E+11 | 0.137860E+10 |
Minimum of Months | 0.396228E+09 | 0.00 | 0.396228E+09 | 0.959974E+09 | 39231579.08 |
Maximum of Months | 0.950440E+09 | 0.404165E+09 | 0.553908E+09 | 0.199293E+10 | 0.237219E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134945E+10 | 0.474509E+09 | 0.874943E+09 | 0.285982E+10 | 0.402892E+09 |
February | 0.133866E+10 | 0.473718E+09 | 0.864941E+09 | 0.290319E+10 | 0.288208E+09 |
March | 0.166131E+10 | 0.656182E+09 | 0.100513E+10 | 0.367091E+10 | 0.230167E+09 |
April | 0.161567E+10 | 0.618822E+09 | 0.996846E+09 | 0.362068E+10 | 0.105213E+09 |
May | 0.142058E+10 | 0.420851E+09 | 0.999730E+09 | 0.331675E+10 | 0.112447E+09 |
June | 0.148972E+10 | 0.513469E+09 | 0.976250E+09 | 0.342215E+10 | 0.122097E+09 |
July | 0.131240E+10 | 0.309492E+09 | 0.100291E+10 | 0.285685E+10 | 0.222891E+09 |
August | 0.142684E+10 | 0.422547E+09 | 0.100429E+10 | 0.304198E+10 | 0.180962E+09 |
September | 0.129333E+10 | 0.358712E+09 | 0.934621E+09 | 0.283922E+10 | 0.176433E+09 |
October | 0.125518E+10 | 0.323558E+09 | 0.931626E+09 | 0.263415E+10 | 0.232712E+09 |
November | 0.118457E+10 | 0.323068E+09 | 0.861504E+09 | 0.250738E+10 | 0.271778E+09 |
December | 0.125273E+10 | 0.409788E+09 | 0.842939E+09 | 0.264929E+10 | 0.445851E+09 |
Annual Sum or Average | 0.166004E+11 | 0.530472E+10 | 0.112957E+11 | 0.363224E+11 | 0.279165E+10 |
Minimum of Months | 0.118457E+10 | 0.309492E+09 | 0.842939E+09 | 0.250738E+10 | 0.105213E+09 |
Maximum of Months | 0.166131E+10 | 0.656182E+09 | 0.100513E+10 | 0.367091E+10 | 0.445851E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53355979.96 | 18761608.46 | 34594371.51 | 0.113074E+09 | 15929969.51 |
February | 52929233.04 | 18730341.46 | 34198891.58 | 0.114789E+09 | 11395475.46 |
March | 65686454.75 | 25944774.78 | 39741679.96 | 0.145144E+09 | 9100565.04 |
April | 63881894.26 | 24467603.31 | 39414290.95 | 0.143158E+09 | 4160026.76 |
May | 56168334.98 | 16640018.50 | 39528316.48 | 0.131141E+09 | 4446031.61 |
June | 58902015.65 | 20302051.45 | 38599964.20 | 0.135308E+09 | 4827585.26 |
July | 51890886.15 | 12237012.32 | 39653873.84 | 0.112957E+09 | 8812900.36 |
August | 56415770.54 | 16707089.12 | 39708681.43 | 0.120277E+09 | 7155065.09 |
September | 51137097.82 | 14183118.72 | 36953979.10 | 0.112260E+09 | 6975991.69 |
October | 49628696.88 | 12793148.88 | 36835548.01 | 0.104152E+09 | 9201215.75 |
November | 46836773.01 | 12773757.78 | 34063015.23 | 99139305.57 | 10745849.83 |
December | 49531592.49 | 16202610.85 | 33328981.64 | 0.104750E+09 | 17628534.50 |
Annual Sum or Average | 0.656365E+09 | 0.209743E+09 | 0.446622E+09 | 0.143615E+10 | 0.110379E+09 |
Minimum of Months | 46836773.01 | 12237012.32 | 33328981.64 | 99139305.57 | 4160026.76 |
Maximum of Months | 65686454.75 | 25944774.78 | 39741679.96 | 0.145144E+09 | 17628534.50 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.246148E+10 | 0.562810E+09 |
February | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.249155E+10 | 0.391809E+09 |
March | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.300649E+10 | 0.283360E+09 |
April | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.326789E+10 | 0.119202E+09 |
May | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.429535E+10 | 0.150921E+09 |
June | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.493104E+10 | 0.165350E+09 |
July | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.400629E+10 | 0.304065E+09 |
August | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.334995E+10 | 0.231178E+09 |
September | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.285639E+10 | 0.222388E+09 |
October | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.262787E+10 | 0.305039E+09 |
November | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.242702E+10 | 0.369742E+09 |
December | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.236848E+10 | 0.618431E+09 |
Annual Sum or Average | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.380898E+11 | 0.372430E+10 |
Minimum of Months | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.236848E+10 | 0.119202E+09 |
Maximum of Months | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.493104E+10 | 0.618431E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.290396E+10 | 0.354969E+09 |
February | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.304485E+10 | 0.244190E+09 |
March | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.377006E+10 | 0.173509E+09 |
April | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.379072E+10 | 74570186.52 |
May | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.351033E+10 | 96659352.78 |
June | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.356776E+10 | 0.103216E+09 |
July | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.296383E+10 | 0.194406E+09 |
August | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.320804E+10 | 0.150750E+09 |
September | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.299791E+10 | 0.148372E+09 |
October | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.276105E+10 | 0.202439E+09 |
November | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.259773E+10 | 0.243716E+09 |
December | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.270899E+10 | 0.395535E+09 |
Annual Sum or Average | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.378252E+11 | 0.238233E+10 |
Minimum of Months | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.259773E+10 | 74570186.52 |
Maximum of Months | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.379072E+10 | 0.395535E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.602766E+10 | 0.572066E+09 |
February | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.498609E+10 | 0.388658E+09 |
March | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.418414E+10 | 0.271028E+09 |
April | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.318109E+10 | 0.107310E+09 |
May | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.337184E+10 | 0.139264E+09 |
June | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.323950E+10 | 0.146428E+09 |
July | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.298522E+10 | 0.288022E+09 |
August | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.292333E+10 | 0.214696E+09 |
September | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.319580E+10 | 0.223187E+09 |
October | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.395291E+10 | 0.321693E+09 |
November | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.483155E+10 | 0.392886E+09 |
December | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.593248E+10 | 0.639979E+09 |
Annual Sum or Average | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.488116E+11 | 0.370522E+10 |
Minimum of Months | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.292333E+10 | 0.107310E+09 |
Maximum of Months | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.602766E+10 | 0.639979E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.298118E+10 | 0.395806E+09 |
February | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.302576E+10 | 0.275554E+09 |
March | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.382338E+10 | 0.212990E+09 |
April | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.377674E+10 | 92173344.03 |
May | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.346711E+10 | 98833933.40 |
June | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.357595E+10 | 0.107554E+09 |
July | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.298500E+10 | 0.202472E+09 |
August | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.318000E+10 | 0.156328E+09 |
September | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.296796E+10 | 0.157015E+09 |
October | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.274913E+10 | 0.214127E+09 |
November | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.261690E+10 | 0.258016E+09 |
December | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.276511E+10 | 0.430539E+09 |
Annual Sum or Average | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.379142E+11 | 0.260141E+10 |
Minimum of Months | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.261690E+10 | 92173344.03 |
Maximum of Months | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.382338E+10 | 0.430539E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 912.89 | 202.08 | 402.11 | 0.00 | 402.11 | 0.00 | 0.00 |
February | 1021.73 | 155.06 | 428.94 | 0.00 | 428.94 | 0.00 | 0.00 |
March | 1111.85 | 103.38 | 440.23 | 0.00 | 440.23 | 0.00 | 0.00 |
April | 1246.58 | 45.94 | 479.08 | 6.79 | 472.29 | 0.00 | 0.00 |
May | 1590.13 | 55.86 | 614.13 | 65.42 | 548.70 | 0.00 | 0.00 |
June | 1888.34 | 64.27 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
July | 1483.53 | 112.12 | 645.08 | 67.62 | 577.47 | 0.00 | 0.00 |
August | 1242.15 | 83.73 | 531.11 | 22.65 | 508.47 | 0.00 | 0.00 |
September | 1090.97 | 85.04 | 452.18 | 0.22 | 451.97 | 0.00 | 0.00 |
October | 972.86 | 111.35 | 435.70 | 0.00 | 435.70 | 0.00 | 0.00 |
November | 929.63 | 135.50 | 412.27 | 0.00 | 412.27 | 0.00 | 0.00 |
December | 879.80 | 219.84 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Annual Sum or Average | 1197.98 | 114.53 | 498.77 | 26.26 | 472.51 | 0.00 | 0.00 |
Minimum of Months | 879.80 | 45.94 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Maximum of Months | 1888.34 | 219.84 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1079.29 | 127.80 | 516.92 | 174.22 | 342.71 | 0.00 | 0.00 |
February | 1252.13 | 96.47 | 586.19 | 214.93 | 371.26 | 0.00 | 0.00 |
March | 1398.94 | 62.83 | 639.06 | 250.25 | 388.81 | 0.00 | 0.00 |
April | 1452.25 | 28.46 | 645.87 | 246.75 | 399.12 | 0.00 | 0.00 |
May | 1301.38 | 35.69 | 555.18 | 168.05 | 387.13 | 0.00 | 0.00 |
June | 1366.85 | 40.11 | 591.31 | 194.75 | 396.57 | 0.00 | 0.00 |
July | 1098.50 | 71.58 | 505.06 | 113.15 | 391.92 | 0.00 | 0.00 |
August | 1191.63 | 54.58 | 555.83 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1148.82 | 56.78 | 521.99 | 142.25 | 379.75 | 0.00 | 0.00 |
October | 1024.66 | 74.01 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 996.95 | 89.56 | 473.47 | 130.84 | 342.63 | 0.00 | 0.00 |
December | 1007.55 | 141.25 | 484.52 | 155.49 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1192.23 | 73.28 | 546.61 | 172.87 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 996.95 | 28.46 | 473.47 | 113.15 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1452.25 | 141.25 | 645.87 | 250.25 | 399.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2244.30 | 206.57 | 1064.65 | 444.18 | 620.46 | 0.00 | 0.00 |
February | 2052.21 | 153.98 | 904.04 | 294.75 | 609.29 | 0.00 | 0.00 |
March | 1550.80 | 98.23 | 616.96 | 82.86 | 534.10 | 0.00 | 0.00 |
April | 1213.49 | 40.98 | 459.97 | 0.21 | 459.77 | 0.00 | 0.00 |
May | 1245.82 | 51.17 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
June | 1236.61 | 56.58 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
July | 1102.97 | 105.81 | 472.46 | 0.00 | 472.46 | 0.00 | 0.00 |
August | 1083.24 | 77.11 | 459.94 | 0.71 | 459.23 | 0.00 | 0.00 |
September | 1221.56 | 85.25 | 509.19 | 16.63 | 492.56 | 0.00 | 0.00 |
October | 1466.61 | 117.68 | 666.17 | 106.21 | 559.95 | 0.00 | 0.00 |
November | 1856.06 | 145.12 | 866.24 | 264.28 | 601.96 | 0.00 | 0.00 |
December | 2210.22 | 229.55 | 1064.10 | 452.73 | 611.37 | 0.00 | 0.00 |
Annual Sum or Average | 1537.85 | 114.02 | 665.96 | 138.01 | 527.95 | 0.00 | 0.00 |
Minimum of Months | 1083.24 | 40.98 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
Maximum of Months | 2244.30 | 229.55 | 1064.65 | 452.73 | 620.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1109.94 | 141.53 | 523.76 | 184.17 | 339.59 | 0.00 | 0.00 |
February | 1245.78 | 108.24 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1420.72 | 77.26 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1448.89 | 34.98 | 647.98 | 248.19 | 399.80 | 0.00 | 0.00 |
May | 1286.95 | 35.90 | 551.36 | 163.34 | 388.02 | 0.00 | 0.00 |
June | 1371.27 | 41.02 | 597.47 | 205.93 | 391.54 | 0.00 | 0.00 |
July | 1107.63 | 73.49 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1182.34 | 55.62 | 553.79 | 164.00 | 389.79 | 0.00 | 0.00 |
September | 1138.67 | 59.38 | 518.71 | 143.87 | 374.84 | 0.00 | 0.00 |
October | 1022.07 | 77.42 | 487.17 | 125.58 | 361.59 | 0.00 | 0.00 |
November | 1006.30 | 93.77 | 475.09 | 129.57 | 345.52 | 0.00 | 0.00 |
December | 1030.42 | 152.34 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1196.71 | 79.25 | 547.22 | 174.87 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1006.30 | 34.98 | 475.09 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1448.89 | 152.34 | 647.98 | 254.68 | 399.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 916.42 | 212.99 | 402.10 | 0.00 | 402.10 | 0.00 | 0.00 |
February | 1027.55 | 165.23 | 428.93 | 0.00 | 428.93 | 0.00 | 0.00 |
March | 1119.78 | 108.20 | 440.22 | 0.00 | 440.22 | 0.00 | 0.00 |
April | 1257.31 | 47.45 | 479.07 | 6.79 | 472.28 | 0.00 | 0.00 |
May | 1598.18 | 62.19 | 614.11 | 65.42 | 548.69 | 0.00 | 0.00 |
June | 1894.86 | 71.86 | 750.16 | 151.60 | 598.56 | 0.00 | 0.00 |
July | 1490.21 | 125.17 | 645.07 | 67.61 | 577.45 | 0.00 | 0.00 |
August | 1242.53 | 96.71 | 531.10 | 22.65 | 508.45 | 0.00 | 0.00 |
September | 1094.83 | 93.35 | 452.17 | 0.22 | 451.96 | 0.00 | 0.00 |
October | 978.01 | 120.22 | 435.69 | 0.00 | 435.69 | 0.00 | 0.00 |
November | 933.43 | 148.36 | 412.26 | 0.00 | 412.26 | 0.00 | 0.00 |
December | 880.24 | 238.91 | 390.64 | 0.00 | 390.64 | 0.00 | 0.00 |
Annual Sum or Average | 1203.21 | 124.25 | 498.76 | 26.26 | 472.50 | 0.00 | 0.00 |
Minimum of Months | 880.24 | 47.45 | 390.64 | 0.00 | 390.64 | 0.00 | 0.00 |
Maximum of Months | 1894.86 | 238.91 | 750.16 | 151.60 | 598.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1081.38 | 140.89 | 516.92 | 174.22 | 342.70 | 0.00 | 0.00 |
February | 1255.44 | 110.23 | 586.18 | 214.92 | 371.26 | 0.00 | 0.00 |
March | 1405.16 | 74.38 | 639.05 | 250.25 | 388.80 | 0.00 | 0.00 |
April | 1457.19 | 34.59 | 645.86 | 246.74 | 399.11 | 0.00 | 0.00 |
May | 1303.42 | 42.00 | 555.17 | 168.05 | 387.12 | 0.00 | 0.00 |
June | 1369.70 | 46.56 | 591.30 | 194.74 | 396.56 | 0.00 | 0.00 |
July | 1100.99 | 82.54 | 505.06 | 113.14 | 391.91 | 0.00 | 0.00 |
August | 1191.48 | 67.33 | 555.82 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1150.35 | 67.33 | 521.99 | 142.24 | 379.74 | 0.00 | 0.00 |
October | 1027.73 | 85.42 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 999.23 | 103.41 | 473.46 | 130.84 | 342.62 | 0.00 | 0.00 |
December | 1008.23 | 159.21 | 484.51 | 155.48 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1194.84 | 84.52 | 546.60 | 172.86 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 999.23 | 34.59 | 473.46 | 113.14 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1457.19 | 159.21 | 645.86 | 250.25 | 399.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2232.32 | 236.69 | 1064.61 | 444.16 | 620.44 | 0.00 | 0.00 |
February | 2038.26 | 182.02 | 904.01 | 294.74 | 609.27 | 0.00 | 0.00 |
March | 1543.95 | 113.76 | 616.94 | 82.85 | 534.09 | 0.00 | 0.00 |
April | 1210.77 | 45.41 | 459.96 | 0.21 | 459.75 | 0.00 | 0.00 |
May | 1240.73 | 57.59 | 460.27 | 0.00 | 460.27 | 0.00 | 0.00 |
June | 1227.96 | 62.17 | 458.62 | 0.00 | 458.62 | 0.00 | 0.00 |
July | 1102.84 | 118.04 | 472.44 | 0.00 | 472.44 | 0.00 | 0.00 |
August | 1075.29 | 91.64 | 459.93 | 0.71 | 459.22 | 0.00 | 0.00 |
September | 1218.82 | 96.66 | 509.17 | 16.63 | 492.54 | 0.00 | 0.00 |
October | 1466.21 | 133.87 | 666.14 | 106.21 | 559.93 | 0.00 | 0.00 |
November | 1848.66 | 170.33 | 866.20 | 264.27 | 601.94 | 0.00 | 0.00 |
December | 2199.98 | 265.71 | 1064.06 | 452.71 | 611.35 | 0.00 | 0.00 |
Annual Sum or Average | 1531.39 | 131.15 | 665.94 | 138.01 | 527.93 | 0.00 | 0.00 |
Minimum of Months | 1075.29 | 45.41 | 458.62 | 0.00 | 458.62 | 0.00 | 0.00 |
Maximum of Months | 2232.32 | 265.71 | 1064.61 | 452.71 | 620.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1109.95 | 156.37 | 523.75 | 184.17 | 339.58 | 0.00 | 0.00 |
February | 1247.51 | 123.84 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1424.75 | 89.33 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1452.10 | 42.20 | 647.97 | 248.18 | 399.79 | 0.00 | 0.00 |
May | 1287.30 | 43.64 | 551.35 | 163.34 | 388.01 | 0.00 | 0.00 |
June | 1372.47 | 48.97 | 597.46 | 205.93 | 391.53 | 0.00 | 0.00 |
July | 1108.80 | 86.51 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1180.65 | 70.23 | 553.78 | 164.00 | 389.78 | 0.00 | 0.00 |
September | 1138.69 | 70.76 | 518.70 | 143.86 | 374.84 | 0.00 | 0.00 |
October | 1022.37 | 90.32 | 487.16 | 125.58 | 361.58 | 0.00 | 0.00 |
November | 1005.60 | 109.00 | 475.08 | 129.57 | 345.51 | 0.00 | 0.00 |
December | 1028.24 | 173.04 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1197.31 | 92.02 | 547.21 | 174.86 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1005.60 | 42.20 | 475.08 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1452.10 | 173.04 | 647.97 | 254.68 | 399.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 919.01 | 210.13 | 402.11 | 0.00 | 402.11 | 0.00 | 0.00 |
February | 1029.91 | 161.96 | 428.94 | 0.00 | 428.94 | 0.00 | 0.00 |
March | 1122.49 | 105.79 | 440.23 | 0.00 | 440.23 | 0.00 | 0.00 |
April | 1260.76 | 45.99 | 479.08 | 6.79 | 472.29 | 0.00 | 0.00 |
May | 1603.70 | 56.35 | 614.13 | 65.42 | 548.70 | 0.00 | 0.00 |
June | 1902.41 | 63.79 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
July | 1495.78 | 113.52 | 645.08 | 67.62 | 577.47 | 0.00 | 0.00 |
August | 1250.73 | 86.31 | 531.11 | 22.65 | 508.47 | 0.00 | 0.00 |
September | 1102.00 | 85.80 | 452.18 | 0.22 | 451.97 | 0.00 | 0.00 |
October | 981.13 | 113.89 | 435.70 | 0.00 | 435.70 | 0.00 | 0.00 |
November | 936.35 | 142.65 | 412.27 | 0.00 | 412.27 | 0.00 | 0.00 |
December | 884.29 | 230.90 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Annual Sum or Average | 1207.82 | 118.10 | 498.77 | 26.26 | 472.51 | 0.00 | 0.00 |
Minimum of Months | 884.29 | 45.99 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Maximum of Months | 1902.41 | 230.90 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1084.22 | 132.53 | 516.92 | 174.22 | 342.71 | 0.00 | 0.00 |
February | 1258.62 | 100.94 | 586.19 | 214.93 | 371.26 | 0.00 | 0.00 |
March | 1407.58 | 64.78 | 639.06 | 250.25 | 388.81 | 0.00 | 0.00 |
April | 1462.47 | 28.77 | 645.87 | 246.75 | 399.12 | 0.00 | 0.00 |
May | 1310.61 | 36.09 | 555.18 | 168.05 | 387.13 | 0.00 | 0.00 |
June | 1376.45 | 39.82 | 591.31 | 194.75 | 396.57 | 0.00 | 0.00 |
July | 1106.57 | 72.58 | 505.06 | 113.15 | 391.92 | 0.00 | 0.00 |
August | 1197.74 | 56.28 | 555.83 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1156.60 | 57.24 | 521.99 | 142.25 | 379.75 | 0.00 | 0.00 |
October | 1030.86 | 75.58 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 1002.21 | 94.03 | 473.47 | 130.84 | 342.63 | 0.00 | 0.00 |
December | 1011.42 | 147.68 | 484.52 | 155.49 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1199.43 | 75.54 | 546.61 | 172.87 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 1002.21 | 28.77 | 473.47 | 113.15 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1462.47 | 147.68 | 645.87 | 250.25 | 399.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2250.47 | 213.58 | 1064.65 | 444.18 | 620.46 | 0.00 | 0.00 |
February | 2061.05 | 160.66 | 904.04 | 294.75 | 609.29 | 0.00 | 0.00 |
March | 1562.18 | 101.19 | 616.96 | 82.86 | 534.10 | 0.00 | 0.00 |
April | 1227.27 | 41.40 | 459.97 | 0.21 | 459.77 | 0.00 | 0.00 |
May | 1258.90 | 52.00 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
June | 1249.81 | 56.49 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
July | 1114.55 | 107.54 | 472.46 | 0.00 | 472.46 | 0.00 | 0.00 |
August | 1091.45 | 80.16 | 459.94 | 0.71 | 459.23 | 0.00 | 0.00 |
September | 1232.95 | 86.11 | 509.19 | 16.63 | 492.56 | 0.00 | 0.00 |
October | 1475.85 | 120.11 | 666.17 | 106.21 | 559.95 | 0.00 | 0.00 |
November | 1864.03 | 151.58 | 866.24 | 264.28 | 601.96 | 0.00 | 0.00 |
December | 2214.93 | 238.94 | 1064.10 | 452.73 | 611.37 | 0.00 | 0.00 |
Annual Sum or Average | 1547.81 | 117.49 | 665.96 | 138.01 | 527.95 | 0.00 | 0.00 |
Minimum of Months | 1091.45 | 41.40 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
Maximum of Months | 2250.47 | 238.94 | 1064.65 | 452.73 | 620.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1113.05 | 147.78 | 523.76 | 184.17 | 339.59 | 0.00 | 0.00 |
February | 1250.73 | 113.90 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1427.49 | 79.52 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1457.08 | 35.56 | 647.98 | 248.19 | 399.80 | 0.00 | 0.00 |
May | 1294.47 | 36.90 | 551.36 | 163.34 | 388.02 | 0.00 | 0.00 |
June | 1379.61 | 41.49 | 597.47 | 205.93 | 391.54 | 0.00 | 0.00 |
July | 1114.47 | 75.59 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1187.28 | 58.37 | 553.79 | 164.00 | 389.79 | 0.00 | 0.00 |
September | 1145.05 | 60.58 | 518.71 | 143.87 | 374.84 | 0.00 | 0.00 |
October | 1026.41 | 79.95 | 487.17 | 125.58 | 361.59 | 0.00 | 0.00 |
November | 1009.61 | 99.54 | 475.09 | 129.57 | 345.52 | 0.00 | 0.00 |
December | 1032.37 | 160.74 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1202.25 | 82.49 | 547.22 | 174.87 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1009.61 | 35.56 | 475.09 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1457.08 | 160.74 | 647.98 | 254.68 | 399.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244507E+10 | 0.541242E+09 | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.00 | 0.00 |
February | 0.247178E+10 | 0.375113E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
March | 0.297799E+10 | 0.276905E+09 | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.00 | 0.00 |
April | 0.323112E+10 | 0.119086E+09 | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.00 | 0.00 |
May | 0.425899E+10 | 0.149626E+09 | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.00 | 0.00 |
June | 0.489459E+10 | 0.166588E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
July | 0.397349E+10 | 0.300300E+09 | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.00 | 0.00 |
August | 0.332696E+10 | 0.224260E+09 | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.00 | 0.00 |
September | 0.282779E+10 | 0.220431E+09 | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.00 | 0.00 |
October | 0.260571E+10 | 0.298244E+09 | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.00 | 0.00 |
November | 0.240961E+10 | 0.351226E+09 | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.00 | 0.00 |
December | 0.235645E+10 | 0.588830E+09 | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377796E+11 | 0.361185E+10 | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235645E+10 | 0.119086E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.489459E+10 | 0.588830E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289076E+10 | 0.342289E+09 | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.00 | 0.00 |
February | 0.302915E+10 | 0.233385E+09 | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.00 | 0.00 |
March | 0.374691E+10 | 0.168278E+09 | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.00 | 0.00 |
April | 0.376422E+10 | 73767691.66 | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.00 | 0.00 |
May | 0.348562E+10 | 95583833.29 | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.00 | 0.00 |
June | 0.354287E+10 | 0.103953E+09 | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.00 | 0.00 |
July | 0.294221E+10 | 0.191728E+09 | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.00 | 0.00 |
August | 0.319167E+10 | 0.146198E+09 | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.00 | 0.00 |
September | 0.297775E+10 | 0.147170E+09 | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.00 | 0.00 |
October | 0.274445E+10 | 0.198223E+09 | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.00 | 0.00 |
November | 0.258409E+10 | 0.232135E+09 | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.00 | 0.00 |
December | 0.269862E+10 | 0.378314E+09 | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375983E+11 | 0.231103E+10 | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258409E+10 | 73767691.66 | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376422E+10 | 0.378314E+09 | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601114E+10 | 0.553264E+09 | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.00 | 0.00 |
February | 0.496471E+10 | 0.372497E+09 | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.00 | 0.00 |
March | 0.415367E+10 | 0.263097E+09 | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.00 | 0.00 |
April | 0.314536E+10 | 0.106214E+09 | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.00 | 0.00 |
May | 0.333680E+10 | 0.137046E+09 | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.00 | 0.00 |
June | 0.320529E+10 | 0.146656E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
July | 0.295420E+10 | 0.283407E+09 | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.00 | 0.00 |
August | 0.290136E+10 | 0.206535E+09 | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.00 | 0.00 |
September | 0.316629E+10 | 0.220958E+09 | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.00 | 0.00 |
October | 0.392818E+10 | 0.315182E+09 | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.00 | 0.00 |
November | 0.481091E+10 | 0.376158E+09 | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.00 | 0.00 |
December | 0.591986E+10 | 0.614828E+09 | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.484978E+11 | 0.359584E+10 | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290136E+10 | 0.106214E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.601114E+10 | 0.614828E+09 | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297288E+10 | 0.379076E+09 | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.00 | 0.00 |
February | 0.301380E+10 | 0.261858E+09 | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.00 | 0.00 |
March | 0.380525E+10 | 0.206922E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
April | 0.375552E+10 | 90672754.38 | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.00 | 0.00 |
May | 0.344697E+10 | 96157373.88 | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.00 | 0.00 |
June | 0.355433E+10 | 0.106334E+09 | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.00 | 0.00 |
July | 0.296668E+10 | 0.196840E+09 | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.00 | 0.00 |
August | 0.316678E+10 | 0.148984E+09 | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.00 | 0.00 |
September | 0.295143E+10 | 0.153911E+09 | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.00 | 0.00 |
October | 0.273752E+10 | 0.207358E+09 | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.00 | 0.00 |
November | 0.260832E+10 | 0.243041E+09 | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.00 | 0.00 |
December | 0.275988E+10 | 0.408035E+09 | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377394E+11 | 0.249919E+10 | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260832E+10 | 90672754.38 | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380525E+10 | 0.408035E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245453E+10 | 0.570469E+09 | 0.107699E+10 | 0.00 | 0.107699E+10 | 0.00 | 0.00 |
February | 0.248585E+10 | 0.399721E+09 | 0.103768E+10 | 0.00 | 0.103768E+10 | 0.00 | 0.00 |
March | 0.299921E+10 | 0.289793E+09 | 0.117908E+10 | 0.00 | 0.117908E+10 | 0.00 | 0.00 |
April | 0.325896E+10 | 0.122980E+09 | 0.124176E+10 | 17597889.49 | 0.122416E+10 | 0.00 | 0.00 |
May | 0.428058E+10 | 0.166556E+09 | 0.164484E+10 | 0.175224E+09 | 0.146962E+10 | 0.00 | 0.00 |
June | 0.491148E+10 | 0.186250E+09 | 0.194442E+10 | 0.392949E+09 | 0.155147E+10 | 0.00 | 0.00 |
July | 0.399137E+10 | 0.335267E+09 | 0.172775E+10 | 0.181098E+09 | 0.154665E+10 | 0.00 | 0.00 |
August | 0.332799E+10 | 0.259035E+09 | 0.142250E+10 | 60656135.97 | 0.136185E+10 | 0.00 | 0.00 |
September | 0.283780E+10 | 0.241962E+09 | 0.117204E+10 | 561230.32 | 0.117148E+10 | 0.00 | 0.00 |
October | 0.261950E+10 | 0.322011E+09 | 0.116695E+10 | 0.00 | 0.116695E+10 | 0.00 | 0.00 |
November | 0.241944E+10 | 0.384541E+09 | 0.106857E+10 | 0.00 | 0.106857E+10 | 0.00 | 0.00 |
December | 0.235763E+10 | 0.639908E+09 | 0.104628E+10 | 0.00 | 0.104628E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.379443E+11 | 0.391849E+10 | 0.157289E+11 | 0.828086E+09 | 0.149008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235763E+10 | 0.122980E+09 | 0.103768E+10 | 0.00 | 0.103768E+10 | 0.00 | 0.00 |
Maximum of Months | 0.491148E+10 | 0.639908E+09 | 0.194442E+10 | 0.392949E+09 | 0.155147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289636E+10 | 0.377352E+09 | 0.138451E+10 | 0.466618E+09 | 0.917892E+09 | 0.00 | 0.00 |
February | 0.303717E+10 | 0.266670E+09 | 0.141809E+10 | 0.519939E+09 | 0.898150E+09 | 0.00 | 0.00 |
March | 0.376358E+10 | 0.199215E+09 | 0.171163E+10 | 0.670262E+09 | 0.104137E+10 | 0.00 | 0.00 |
April | 0.377704E+10 | 89645384.52 | 0.167406E+10 | 0.639558E+09 | 0.103450E+10 | 0.00 | 0.00 |
May | 0.349107E+10 | 0.112501E+09 | 0.148697E+10 | 0.450101E+09 | 0.103687E+10 | 0.00 | 0.00 |
June | 0.355027E+10 | 0.120694E+09 | 0.153266E+10 | 0.504775E+09 | 0.102789E+10 | 0.00 | 0.00 |
July | 0.294888E+10 | 0.221085E+09 | 0.135274E+10 | 0.303046E+09 | 0.104969E+10 | 0.00 | 0.00 |
August | 0.319125E+10 | 0.180345E+09 | 0.148872E+10 | 0.437617E+09 | 0.105110E+10 | 0.00 | 0.00 |
September | 0.298172E+10 | 0.174526E+09 | 0.135299E+10 | 0.368693E+09 | 0.984294E+09 | 0.00 | 0.00 |
October | 0.275268E+10 | 0.228791E+09 | 0.131032E+10 | 0.335225E+09 | 0.975094E+09 | 0.00 | 0.00 |
November | 0.259001E+10 | 0.268027E+09 | 0.122722E+10 | 0.339135E+09 | 0.888082E+09 | 0.00 | 0.00 |
December | 0.270043E+10 | 0.426436E+09 | 0.129772E+10 | 0.416449E+09 | 0.881272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376805E+11 | 0.266529E+10 | 0.172376E+11 | 0.545142E+10 | 0.117862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259001E+10 | 89645384.52 | 0.122722E+10 | 0.303046E+09 | 0.881272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.377704E+10 | 0.426436E+09 | 0.171163E+10 | 0.670262E+09 | 0.105110E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597903E+10 | 0.633961E+09 | 0.285144E+10 | 0.118965E+10 | 0.166179E+10 | 0.00 | 0.00 |
February | 0.493097E+10 | 0.440347E+09 | 0.218699E+10 | 0.713036E+09 | 0.147395E+10 | 0.00 | 0.00 |
March | 0.413531E+10 | 0.304694E+09 | 0.165241E+10 | 0.221918E+09 | 0.143049E+10 | 0.00 | 0.00 |
April | 0.313831E+10 | 0.117700E+09 | 0.119222E+10 | 535187.22 | 0.119168E+10 | 0.00 | 0.00 |
May | 0.332318E+10 | 0.154257E+09 | 0.123280E+10 | 0.00 | 0.123280E+10 | 0.00 | 0.00 |
June | 0.318288E+10 | 0.161132E+09 | 0.118873E+10 | 0.00 | 0.118873E+10 | 0.00 | 0.00 |
July | 0.295384E+10 | 0.316160E+09 | 0.126539E+10 | 0.00 | 0.126539E+10 | 0.00 | 0.00 |
August | 0.288004E+10 | 0.245458E+09 | 0.123187E+10 | 1903857.75 | 0.122997E+10 | 0.00 | 0.00 |
September | 0.315919E+10 | 0.250544E+09 | 0.131977E+10 | 43104314.98 | 0.127667E+10 | 0.00 | 0.00 |
October | 0.392708E+10 | 0.358550E+09 | 0.178420E+10 | 0.284474E+09 | 0.149972E+10 | 0.00 | 0.00 |
November | 0.479173E+10 | 0.441500E+09 | 0.224520E+10 | 0.684977E+09 | 0.156022E+10 | 0.00 | 0.00 |
December | 0.589242E+10 | 0.711686E+09 | 0.284998E+10 | 0.121255E+10 | 0.163744E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.482940E+11 | 0.413599E+10 | 0.210010E+11 | 0.435214E+10 | 0.166489E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288004E+10 | 0.117700E+09 | 0.118873E+10 | 0.00 | 0.118873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.597903E+10 | 0.711686E+09 | 0.285144E+10 | 0.121255E+10 | 0.166179E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297289E+10 | 0.418822E+09 | 0.140281E+10 | 0.493271E+09 | 0.909537E+09 | 0.00 | 0.00 |
February | 0.301798E+10 | 0.299604E+09 | 0.139159E+10 | 0.492449E+09 | 0.899139E+09 | 0.00 | 0.00 |
March | 0.381605E+10 | 0.239267E+09 | 0.172699E+10 | 0.682127E+09 | 0.104487E+10 | 0.00 | 0.00 |
April | 0.376384E+10 | 0.109373E+09 | 0.167955E+10 | 0.643290E+09 | 0.103626E+10 | 0.00 | 0.00 |
May | 0.344789E+10 | 0.116893E+09 | 0.147675E+10 | 0.437491E+09 | 0.103926E+10 | 0.00 | 0.00 |
June | 0.355745E+10 | 0.126924E+09 | 0.154862E+10 | 0.533771E+09 | 0.101485E+10 | 0.00 | 0.00 |
July | 0.296981E+10 | 0.231704E+09 | 0.136429E+10 | 0.321729E+09 | 0.104256E+10 | 0.00 | 0.00 |
August | 0.316226E+10 | 0.188117E+09 | 0.148325E+10 | 0.439254E+09 | 0.104400E+10 | 0.00 | 0.00 |
September | 0.295148E+10 | 0.183409E+09 | 0.134447E+10 | 0.372896E+09 | 0.971575E+09 | 0.00 | 0.00 |
October | 0.273831E+10 | 0.241913E+09 | 0.130481E+10 | 0.336351E+09 | 0.968461E+09 | 0.00 | 0.00 |
November | 0.260652E+10 | 0.282524E+09 | 0.123141E+10 | 0.335841E+09 | 0.895567E+09 | 0.00 | 0.00 |
December | 0.275404E+10 | 0.463480E+09 | 0.130226E+10 | 0.425991E+09 | 0.876268E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377585E+11 | 0.290203E+10 | 0.172568E+11 | 0.551446E+10 | 0.117423E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260652E+10 | 0.109373E+09 | 0.123141E+10 | 0.321729E+09 | 0.876268E+09 | 0.00 | 0.00 |
Maximum of Months | 0.381605E+10 | 0.463480E+09 | 0.172699E+10 | 0.682127E+09 | 0.104487E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246148E+10 | 0.562810E+09 | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.00 | 0.00 |
February | 0.249155E+10 | 0.391809E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
March | 0.300649E+10 | 0.283360E+09 | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.00 | 0.00 |
April | 0.326789E+10 | 0.119202E+09 | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.00 | 0.00 |
May | 0.429535E+10 | 0.150921E+09 | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.00 | 0.00 |
June | 0.493104E+10 | 0.165350E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
July | 0.400629E+10 | 0.304065E+09 | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.00 | 0.00 |
August | 0.334995E+10 | 0.231178E+09 | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.00 | 0.00 |
September | 0.285639E+10 | 0.222388E+09 | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.00 | 0.00 |
October | 0.262787E+10 | 0.305039E+09 | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.00 | 0.00 |
November | 0.242702E+10 | 0.369742E+09 | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.00 | 0.00 |
December | 0.236848E+10 | 0.618431E+09 | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.380898E+11 | 0.372430E+10 | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236848E+10 | 0.119202E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.493104E+10 | 0.618431E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290396E+10 | 0.354969E+09 | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.00 | 0.00 |
February | 0.304485E+10 | 0.244190E+09 | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.00 | 0.00 |
March | 0.377006E+10 | 0.173509E+09 | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.00 | 0.00 |
April | 0.379072E+10 | 74570186.52 | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.00 | 0.00 |
May | 0.351033E+10 | 96659352.78 | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.00 | 0.00 |
June | 0.356776E+10 | 0.103216E+09 | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.00 | 0.00 |
July | 0.296383E+10 | 0.194406E+09 | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.00 | 0.00 |
August | 0.320804E+10 | 0.150750E+09 | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.00 | 0.00 |
September | 0.299791E+10 | 0.148372E+09 | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.00 | 0.00 |
October | 0.276105E+10 | 0.202439E+09 | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.00 | 0.00 |
November | 0.259773E+10 | 0.243716E+09 | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.00 | 0.00 |
December | 0.270899E+10 | 0.395535E+09 | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378252E+11 | 0.238233E+10 | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259773E+10 | 74570186.52 | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.379072E+10 | 0.395535E+09 | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.602766E+10 | 0.572066E+09 | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.00 | 0.00 |
February | 0.498609E+10 | 0.388658E+09 | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.00 | 0.00 |
March | 0.418414E+10 | 0.271028E+09 | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.00 | 0.00 |
April | 0.318109E+10 | 0.107310E+09 | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.00 | 0.00 |
May | 0.337184E+10 | 0.139264E+09 | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.00 | 0.00 |
June | 0.323950E+10 | 0.146428E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
July | 0.298522E+10 | 0.288022E+09 | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.00 | 0.00 |
August | 0.292333E+10 | 0.214696E+09 | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.00 | 0.00 |
September | 0.319580E+10 | 0.223187E+09 | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.00 | 0.00 |
October | 0.395291E+10 | 0.321693E+09 | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.00 | 0.00 |
November | 0.483155E+10 | 0.392886E+09 | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.00 | 0.00 |
December | 0.593248E+10 | 0.639979E+09 | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.488116E+11 | 0.370522E+10 | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292333E+10 | 0.107310E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.602766E+10 | 0.639979E+09 | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298118E+10 | 0.395806E+09 | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.00 | 0.00 |
February | 0.302576E+10 | 0.275554E+09 | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.00 | 0.00 |
March | 0.382338E+10 | 0.212990E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
April | 0.377674E+10 | 92173344.03 | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.00 | 0.00 |
May | 0.346711E+10 | 98833933.40 | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.00 | 0.00 |
June | 0.357595E+10 | 0.107554E+09 | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.00 | 0.00 |
July | 0.298500E+10 | 0.202472E+09 | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.00 | 0.00 |
August | 0.318000E+10 | 0.156328E+09 | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.00 | 0.00 |
September | 0.296796E+10 | 0.157015E+09 | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.00 | 0.00 |
October | 0.274913E+10 | 0.214127E+09 | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.00 | 0.00 |
November | 0.261690E+10 | 0.258016E+09 | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.00 | 0.00 |
December | 0.276511E+10 | 0.430539E+09 | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.379142E+11 | 0.260141E+10 | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261690E+10 | 92173344.03 | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.382338E+10 | 0.430539E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.345016E+10 | -0.276324E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686918530.0 | 58.98 | 0.00 | 0.00 |
February | 0.311633E+10 | -0.249542E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -620918903.9 | 58.97 | 0.00 | 0.00 |
March | 0.359718E+10 | -0.290729E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689895849.9 | 58.98 | 0.00 | 0.00 |
April | 0.322678E+10 | -0.255955E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667235029.1 | 58.98 | 0.00 | 0.00 |
May | 0.337544E+10 | -0.268559E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689849041.4 | 58.98 | 0.00 | 0.00 |
June | 0.329573E+10 | -0.262840E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667326298.0 | 58.98 | 0.00 | 0.00 |
July | 0.315128E+10 | -0.246323E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688044295.2 | 58.98 | 0.00 | 0.00 |
August | 0.343311E+10 | -0.274363E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689485493.7 | 58.98 | 0.00 | 0.00 |
September | 0.317955E+10 | -0.251270E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666854398.8 | 58.98 | 0.00 | 0.00 |
October | 0.334070E+10 | -0.265342E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687277060.6 | 58.98 | 0.00 | 0.00 |
November | 0.333064E+10 | -0.266589E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664747766.5 | 58.98 | 0.00 | 0.00 |
December | 0.336362E+10 | -0.267668E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686945558.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.398605E+11 | -0.317550E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.810550E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.311633E+10 | -0.290729E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -689895849.9 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.359718E+10 | -0.246323E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -620918903.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:49 | 2217.28 | 25.16 | 147.67 | 323.00 | 1094.02 | 24.85 | 305.00 | 311.67 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1749.25 | 19.02 | 0.00 | 294.00 | 924.98 | 21.20 | 199.67 | 273.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1322.03 | 18.81 | 0.00 | 326.67 | 736.93 | 20.92 | 161.67 | 299.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 1084.11 | 18.46 | 0.00 | 323.50 | 616.08 | 20.60 | 68.50 | 287.00 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 927.95 | 17.37 | 0.00 | 330.00 | 516.69 | 19.47 | 0.00 | 282.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 906.21 | 17.54 | 0.00 | 323.00 | 521.19 | 19.71 | 0.00 | 277.33 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 877.96 | 16.93 | 0.00 | 326.17 | 477.26 | 18.99 | 0.00 | 275.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1038.11 | 17.88 | 0.00 | 327.67 | 568.58 | 19.97 | 35.67 | 286.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1173.42 | 17.74 | 0.00 | 314.00 | 617.96 | 19.78 | 85.33 | 275.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 1520.05 | 19.18 | 15.00 | 324.17 | 773.59 | 20.75 | 145.00 | 286.17 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:10 | 1921.19 | 23.57 | 114.83 | 313.00 | 941.98 | 21.73 | 232.67 | 281.83 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2226.60 | 25.19 | 148.67 | 319.83 | 1093.99 | 24.79 | 301.00 | 304.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1397.59 | 19.67 | 426.17 | 3845.00 | 732.81 | 21.02 | 1534.50 | 3440.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 877.96 | 16.93 | 0.00 | 294.00 | 477.26 | 18.99 | 0.00 | 273.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2226.60 | 25.19 | 148.67 | 330.00 | 1094.02 | 24.85 | 305.00 | 311.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1863.63 | 21.59 | 108.50 | 308.50 | 978.07 | 22.52 | 77.50 | 273.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2067.88 | 21.71 | 99.00 | 286.33 | 1089.39 | 22.63 | 71.17 | 258.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2346.86 | 21.75 | 112.17 | 321.83 | 974.57 | 21.26 | 52.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1935.09 | 19.98 | 84.17 | 328.33 | 1014.79 | 21.23 | 54.33 | 297.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1658.82 | 19.20 | 87.33 | 337.83 | 868.05 | 21.39 | 67.33 | 299.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1779.87 | 19.62 | 84.50 | 334.17 | 937.53 | 21.67 | 63.33 | 301.17 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:19 | 1480.12 | 18.89 | 86.67 | 336.17 | 760.80 | 20.89 | 64.17 | 293.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1688.00 | 19.55 | 86.00 | 336.50 | 874.58 | 20.78 | 55.00 | 298.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1593.46 | 18.96 | 83.67 | 313.83 | 815.86 | 20.14 | 54.50 | 274.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-06:10 | 1591.38 | 19.52 | 86.17 | 316.00 | 812.26 | 20.66 | 55.17 | 276.17 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1604.95 | 20.16 | 84.50 | 298.50 | 806.11 | 21.03 | 51.33 | 260.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1811.85 | 21.67 | 112.50 | 302.00 | 830.99 | 21.41 | 56.00 | 268.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1781.29 | 20.19 | 1115.17 | 3820.00 | 894.92 | 21.29 | 722.00 | 3394.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1480.12 | 18.89 | 83.67 | 286.33 | 760.80 | 20.14 | 51.33 | 258.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2346.86 | 21.75 | 112.50 | 337.83 | 1089.39 | 22.63 | 77.50 | 301.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-08:00 | 740.54 | 16.51 | 0.00 | 298.33 | 437.33 | 18.68 | 0.00 | 241.83 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-07:00 | 815.14 | 17.04 | 0.00 | 280.17 | 483.22 | 19.19 | 0.00 | 240.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 931.08 | 17.97 | 0.00 | 323.33 | 551.22 | 20.09 | 1.33 | 289.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1138.35 | 18.94 | 0.00 | 333.17 | 644.93 | 21.04 | 118.50 | 303.00 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1322.52 | 18.75 | 3.83 | 349.33 | 694.59 | 20.81 | 140.67 | 317.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1584.26 | 23.13 | 112.83 | 348.50 | 808.81 | 22.66 | 224.50 | 323.83 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1370.66 | 22.65 | 116.00 | 351.50 | 688.00 | 22.83 | 168.83 | 319.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:19 | 1227.61 | 18.66 | 0.00 | 342.83 | 658.49 | 20.75 | 122.67 | 308.33 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 996.49 | 17.46 | 0.00 | 314.83 | 539.39 | 19.48 | 42.00 | 273.83 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 880.76 | 17.24 | 0.00 | 311.50 | 483.80 | 19.28 | 0.00 | 260.67 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:49 | 788.33 | 16.86 | 0.00 | 288.50 | 444.15 | 18.94 | 0.00 | 235.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:40 | 721.09 | 16.27 | 0.00 | 291.17 | 420.66 | 18.43 | 0.00 | 233.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1052.55 | 18.52 | 232.67 | 3833.17 | 575.26 | 20.23 | 818.50 | 3347.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 721.09 | 16.27 | 0.00 | 280.17 | 420.66 | 18.43 | 0.00 | 233.50 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1584.26 | 23.13 | 116.00 | 351.50 | 808.81 | 22.83 | 224.50 | 323.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:30 | 1924.04 | 21.74 | 109.33 | 308.00 | 1007.36 | 22.60 | 77.50 | 275.17 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:20 | 2156.36 | 21.67 | 102.33 | 283.33 | 907.40 | 21.05 | 46.67 | 255.17 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:39 | 2393.35 | 21.49 | 112.67 | 331.33 | 992.19 | 20.94 | 51.17 | 298.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 2332.07 | 15.23 | 0.00 | 327.67 | 980.92 | 18.58 | 0.00 | 296.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1836.13 | 14.97 | 0.00 | 337.17 | 825.53 | 18.08 | 0.00 | 298.17 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1731.03 | 15.41 | 0.00 | 332.67 | 906.27 | 18.64 | 0.00 | 299.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1480.25 | 14.77 | 0.00 | 335.50 | 755.01 | 17.79 | 0.00 | 291.33 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1696.43 | 15.56 | 8.50 | 334.50 | 857.08 | 18.27 | 0.00 | 296.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:40 | 1748.23 | 18.76 | 87.00 | 311.50 | 793.60 | 18.02 | 7.67 | 275.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:20 | 1660.58 | 20.65 | 101.83 | 315.33 | 856.24 | 21.86 | 72.67 | 278.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:20 | 1640.54 | 19.93 | 85.00 | 299.83 | 850.09 | 22.00 | 66.00 | 264.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1703.56 | 20.04 | 90.00 | 305.17 | 902.69 | 22.07 | 71.83 | 270.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1854.60 | 18.26 | 696.67 | 3822.00 | 885.00 | 19.93 | 393.50 | 3398.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1480.25 | 14.77 | 0.00 | 283.33 | 755.01 | 17.79 | 0.00 | 255.17 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2393.35 | 21.74 | 112.67 | 337.17 | 1007.36 | 22.60 | 77.50 | 299.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 2126.19 | 22.71 | 147.50 | 322.33 | 1030.52 | 22.65 | 88.50 | 309.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1673.13 | 15.15 | 0.00 | 293.67 | 873.20 | 18.74 | 0.00 | 271.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1268.78 | 15.34 | 0.00 | 326.17 | 703.72 | 18.80 | 0.00 | 298.00 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1043.38 | 15.08 | 0.00 | 320.00 | 592.45 | 18.54 | 0.00 | 283.33 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 894.23 | 13.71 | 0.00 | 327.00 | 496.98 | 17.11 | 0.00 | 277.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 872.70 | 14.03 | 0.00 | 320.17 | 501.98 | 17.51 | 0.00 | 273.17 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 846.99 | 13.10 | 0.00 | 324.17 | 458.88 | 16.50 | 0.00 | 269.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 999.83 | 14.27 | 0.00 | 325.67 | 545.90 | 17.66 | 0.00 | 280.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1129.14 | 14.00 | 0.00 | 310.67 | 590.85 | 17.34 | 0.00 | 273.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:10 | 1459.27 | 15.43 | 15.00 | 322.67 | 735.49 | 18.35 | 4.50 | 281.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 1842.05 | 20.86 | 114.33 | 312.00 | 895.20 | 20.39 | 39.83 | 282.17 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2134.53 | 22.76 | 148.50 | 318.67 | 1029.85 | 22.54 | 87.50 | 302.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1342.19 | 16.29 | 425.33 | 3823.17 | 697.67 | 18.79 | 220.33 | 3402.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 846.99 | 13.10 | 0.00 | 293.67 | 458.88 | 16.50 | 0.00 | 269.50 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2134.53 | 22.76 | 148.50 | 327.00 | 1030.52 | 22.65 | 88.50 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1807.10 | 21.14 | 108.50 | 307.17 | 938.85 | 22.32 | 77.50 | 270.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-06:40 | 2014.93 | 21.26 | 99.00 | 285.50 | 1045.26 | 22.44 | 71.17 | 256.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2283.42 | 21.30 | 112.17 | 320.50 | 928.50 | 21.08 | 52.17 | 291.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1864.66 | 19.52 | 84.17 | 325.67 | 968.12 | 21.06 | 54.33 | 294.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1619.36 | 18.75 | 87.33 | 336.00 | 829.57 | 21.24 | 67.33 | 295.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1728.28 | 19.17 | 84.50 | 331.50 | 896.45 | 21.50 | 63.00 | 296.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:30 | 1439.62 | 18.44 | 86.67 | 333.00 | 721.35 | 19.99 | 56.33 | 288.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-05:00 | 1639.44 | 19.10 | 86.00 | 334.17 | 834.77 | 20.62 | 55.00 | 295.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1533.95 | 18.51 | 83.67 | 312.50 | 778.71 | 19.96 | 54.50 | 271.67 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-06:10 | 1548.23 | 19.04 | 86.17 | 313.83 | 775.91 | 20.45 | 55.17 | 272.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-06:40 | 1554.72 | 19.68 | 84.50 | 295.50 | 770.24 | 20.81 | 51.33 | 256.50 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-06:40 | 1760.10 | 21.22 | 112.50 | 300.00 | 794.26 | 21.19 | 56.00 | 265.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1729.07 | 19.73 | 1115.17 | 3795.33 | 854.85 | 21.04 | 713.83 | 3354.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1439.62 | 18.44 | 83.67 | 285.50 | 721.35 | 19.96 | 51.33 | 256.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2283.42 | 21.30 | 112.50 | 336.00 | 1045.26 | 22.44 | 77.50 | 296.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-09:09 | 713.59 | 13.04 | 0.00 | 295.17 | 422.31 | 16.52 | 0.00 | 235.00 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-08:09 | 785.59 | 13.66 | 0.00 | 277.67 | 466.75 | 17.13 | 0.00 | 235.50 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:20 | 896.76 | 14.69 | 0.00 | 320.00 | 532.01 | 18.14 | 0.00 | 286.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1095.30 | 15.53 | 0.00 | 330.67 | 619.82 | 19.03 | 0.00 | 299.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1271.76 | 14.92 | 3.83 | 347.17 | 662.92 | 18.30 | 1.17 | 314.00 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1522.57 | 20.47 | 112.17 | 347.67 | 769.29 | 20.36 | 33.17 | 319.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1319.34 | 19.90 | 115.67 | 350.17 | 655.38 | 20.56 | 59.17 | 315.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1180.95 | 14.95 | 0.00 | 340.50 | 630.11 | 18.40 | 0.00 | 304.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 960.21 | 13.80 | 0.00 | 313.00 | 517.84 | 17.13 | 0.00 | 270.50 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 849.42 | 13.52 | 0.00 | 309.83 | 465.41 | 16.90 | 0.00 | 256.00 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:00 | 760.35 | 13.19 | 0.00 | 286.00 | 428.05 | 16.61 | 0.00 | 229.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:49 | 694.91 | 12.71 | 0.00 | 289.00 | 405.97 | 16.17 | 0.00 | 228.00 |
Annual Sum or Average | 4292.33 | 0.53 | 1013.32 | 15.10 | 231.67 | 3806.83 | 551.75 | 17.98 | 93.50 | 3293.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 694.91 | 12.71 | 0.00 | 277.67 | 405.97 | 16.17 | 0.00 | 228.00 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1522.57 | 20.47 | 115.67 | 350.17 | 769.29 | 20.56 | 59.17 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1868.00 | 21.35 | 109.33 | 305.83 | 967.72 | 22.48 | 77.67 | 271.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:30 | 2102.21 | 21.27 | 102.33 | 282.00 | 864.92 | 20.92 | 46.67 | 252.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:50 | 2336.50 | 21.07 | 112.67 | 329.00 | 945.86 | 20.79 | 51.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 2253.95 | 14.67 | 0.00 | 325.83 | 935.14 | 18.37 | 0.00 | 294.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1796.97 | 14.40 | 0.00 | 335.50 | 787.76 | 17.85 | 0.00 | 294.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1683.94 | 14.83 | 0.00 | 330.83 | 865.34 | 18.41 | 0.00 | 295.50 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1440.92 | 14.19 | 0.00 | 333.83 | 721.16 | 17.55 | 0.00 | 289.67 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1644.99 | 15.01 | 8.50 | 332.33 | 818.14 | 18.05 | 0.00 | 291.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:49 | 1689.05 | 18.11 | 85.00 | 310.67 | 756.99 | 17.82 | 7.67 | 271.00 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-08:30 | 1601.22 | 18.93 | 87.50 | 312.67 | 819.97 | 21.73 | 72.67 | 275.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1588.65 | 19.49 | 85.00 | 298.17 | 813.81 | 21.88 | 66.00 | 260.50 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1646.43 | 19.38 | 87.33 | 303.67 | 864.59 | 21.95 | 71.83 | 267.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1800.63 | 17.63 | 677.67 | 3800.33 | 845.62 | 19.76 | 393.67 | 3356.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1440.92 | 14.19 | 0.00 | 282.00 | 721.16 | 17.55 | 0.00 | 252.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2336.50 | 21.35 | 112.67 | 335.50 | 967.72 | 22.48 | 77.67 | 295.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 2126.07 | 22.71 | 147.50 | 322.33 | 1030.43 | 22.65 | 88.50 | 309.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1673.02 | 15.15 | 0.00 | 293.67 | 873.13 | 18.74 | 0.00 | 271.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1268.71 | 15.35 | 0.00 | 326.17 | 703.67 | 18.80 | 0.00 | 298.00 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1043.33 | 15.08 | 0.00 | 320.00 | 592.40 | 18.54 | 0.00 | 283.33 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 894.18 | 13.71 | 0.00 | 327.00 | 496.94 | 17.11 | 0.00 | 277.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 872.66 | 14.03 | 0.00 | 320.17 | 501.95 | 17.51 | 0.00 | 273.17 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 846.94 | 13.10 | 0.00 | 324.17 | 458.84 | 16.50 | 0.00 | 269.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 999.77 | 14.28 | 0.00 | 325.67 | 545.86 | 17.67 | 0.00 | 280.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1129.06 | 14.01 | 0.00 | 310.67 | 590.80 | 17.34 | 0.00 | 273.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:10 | 1459.16 | 15.43 | 15.00 | 322.67 | 735.42 | 18.35 | 4.50 | 281.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 1841.93 | 20.86 | 114.33 | 312.00 | 895.11 | 20.39 | 39.83 | 282.17 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2134.41 | 22.76 | 148.50 | 318.67 | 1029.76 | 22.54 | 87.50 | 302.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1342.11 | 16.29 | 425.33 | 3823.17 | 697.61 | 18.80 | 220.33 | 3402.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 846.94 | 13.10 | 0.00 | 293.67 | 458.84 | 16.50 | 0.00 | 269.50 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2134.41 | 22.76 | 148.50 | 327.00 | 1030.43 | 22.65 | 88.50 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1807.04 | 21.14 | 108.50 | 307.17 | 938.79 | 22.32 | 77.50 | 270.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-06:40 | 2014.87 | 21.27 | 99.00 | 285.50 | 1045.20 | 22.44 | 71.17 | 256.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2283.37 | 21.30 | 112.17 | 320.50 | 928.44 | 21.08 | 52.17 | 291.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1864.60 | 19.52 | 84.17 | 325.67 | 968.05 | 21.06 | 54.33 | 294.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1619.29 | 18.75 | 87.33 | 336.00 | 829.51 | 21.24 | 67.33 | 295.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1728.21 | 19.17 | 84.50 | 331.50 | 896.39 | 21.50 | 63.00 | 296.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:30 | 1439.53 | 18.44 | 86.67 | 333.00 | 721.29 | 19.99 | 56.33 | 288.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-05:00 | 1639.36 | 19.10 | 86.00 | 334.17 | 834.71 | 20.62 | 55.00 | 295.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1533.87 | 18.51 | 83.67 | 312.50 | 778.65 | 19.96 | 54.50 | 271.67 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-06:10 | 1548.16 | 19.04 | 86.17 | 313.83 | 775.85 | 20.45 | 55.17 | 272.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-06:40 | 1554.65 | 19.68 | 84.50 | 295.50 | 770.18 | 20.81 | 51.33 | 256.50 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-06:40 | 1760.04 | 21.22 | 112.50 | 300.00 | 794.20 | 21.19 | 56.00 | 265.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1729.00 | 19.73 | 1115.17 | 3795.33 | 854.79 | 21.04 | 713.83 | 3354.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1439.53 | 18.44 | 83.67 | 285.50 | 721.29 | 19.96 | 51.33 | 256.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2283.37 | 21.30 | 112.50 | 336.00 | 1045.20 | 22.44 | 77.50 | 296.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-09:09 | 713.57 | 13.04 | 0.00 | 295.17 | 422.28 | 16.52 | 0.00 | 235.00 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-08:09 | 785.56 | 13.67 | 0.00 | 277.67 | 466.71 | 17.13 | 0.00 | 235.50 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:20 | 896.73 | 14.70 | 0.00 | 320.00 | 531.97 | 18.14 | 0.00 | 286.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1095.25 | 15.53 | 0.00 | 330.67 | 619.77 | 19.03 | 0.00 | 299.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1271.67 | 14.92 | 3.83 | 347.17 | 662.87 | 18.30 | 1.17 | 313.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1522.48 | 20.47 | 112.17 | 347.67 | 769.23 | 20.36 | 33.17 | 319.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1319.25 | 19.90 | 115.67 | 350.17 | 655.32 | 20.56 | 59.17 | 315.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1180.88 | 14.95 | 0.00 | 340.50 | 630.06 | 18.40 | 0.00 | 304.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 960.15 | 13.80 | 0.00 | 313.00 | 517.80 | 17.13 | 0.00 | 270.50 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 849.37 | 13.52 | 0.00 | 309.83 | 465.38 | 16.90 | 0.00 | 256.00 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:00 | 760.31 | 13.19 | 0.00 | 286.00 | 428.02 | 16.61 | 0.00 | 229.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:49 | 694.88 | 12.72 | 0.00 | 289.00 | 405.94 | 16.17 | 0.00 | 228.00 |
Annual Sum or Average | 4292.33 | 0.53 | 1013.26 | 15.11 | 231.67 | 3806.83 | 551.71 | 17.98 | 93.50 | 3293.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 694.88 | 12.72 | 0.00 | 277.67 | 405.94 | 16.17 | 0.00 | 228.00 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1522.48 | 20.47 | 115.67 | 350.17 | 769.23 | 20.56 | 59.17 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1867.94 | 21.35 | 109.33 | 305.83 | 967.66 | 22.48 | 77.67 | 271.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:30 | 2102.15 | 21.27 | 102.33 | 282.00 | 864.86 | 20.92 | 46.67 | 252.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:50 | 2336.44 | 21.07 | 112.67 | 329.00 | 945.80 | 20.79 | 51.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 2253.89 | 14.67 | 0.00 | 325.83 | 935.08 | 18.38 | 0.00 | 294.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1796.89 | 14.40 | 0.00 | 335.50 | 787.70 | 17.85 | 0.00 | 294.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1683.87 | 14.84 | 0.00 | 330.83 | 865.28 | 18.41 | 0.00 | 295.50 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1440.84 | 14.19 | 0.00 | 333.83 | 721.11 | 17.55 | 0.00 | 289.67 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1644.91 | 15.01 | 8.50 | 332.33 | 818.08 | 18.05 | 0.00 | 291.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:49 | 1688.98 | 18.11 | 85.00 | 310.67 | 756.93 | 17.82 | 7.67 | 271.00 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-08:30 | 1601.14 | 18.93 | 87.50 | 312.67 | 819.91 | 21.73 | 72.67 | 274.83 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1588.58 | 19.49 | 85.00 | 298.17 | 813.75 | 21.88 | 66.00 | 260.50 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1646.38 | 19.38 | 87.33 | 303.67 | 864.53 | 21.95 | 71.83 | 267.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1800.56 | 17.63 | 677.67 | 3800.33 | 845.56 | 19.76 | 393.67 | 3356.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1440.84 | 14.19 | 0.00 | 282.00 | 721.11 | 17.55 | 0.00 | 252.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2336.44 | 21.35 | 112.67 | 335.50 | 967.66 | 22.48 | 77.67 | 295.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100642E+12 | 0.688042E+11 | 139313.83 | 09-JAN-05:02 | 81719.86 | 0.00 |
February | 0.00 | 0.00 | 0.951833E+11 | 0.651314E+11 | 139040.55 | 06-FEB-06:02 | 83760.81 | 0.00 |
March | 0.00 | 0.00 | 0.116099E+12 | 0.772301E+11 | 139356.46 | 13-MAR-04:02 | 82295.84 | 0.00 |
April | 0.00 | 0.00 | 0.120990E+12 | 0.735157E+11 | 140252.95 | 01-APR-04:02 | 74114.12 | 0.00 |
May | 0.00 | 0.00 | 0.138284E+12 | 0.782237E+11 | 145307.71 | 22-MAY-04:02 | 68588.13 | 0.00 |
June | 0.00 | 0.00 | 0.139456E+12 | 0.794589E+11 | 145152.95 | 10-JUN-04:02 | 71548.03 | 0.00 |
July | 0.00 | 0.00 | 0.111077E+12 | 0.683610E+11 | 133399.45 | 10-JUL-04:02 | 85731.80 | 0.00 |
August | 0.00 | 0.00 | 0.130662E+12 | 0.726968E+11 | 146413.09 | 21-AUG-04:02 | 65105.76 | 0.00 |
September | 0.00 | 0.00 | 0.118761E+12 | 0.673423E+11 | 139664.25 | 25-SEP-04:02 | 81705.37 | 0.00 |
October | 0.00 | 0.00 | 0.114745E+12 | 0.657916E+11 | 142304.67 | 30-OCT-04:02 | 77434.46 | 0.00 |
November | 0.00 | 0.00 | 0.107434E+12 | 0.657073E+11 | 123863.74 | 13-NOV-07:03 | 86153.45 | 0.00 |
December | 0.00 | 0.00 | 0.984483E+11 | 0.647654E+11 | 117577.54 | 11-DEC-07:03 | 75294.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139178E+13 | 0.847028E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.951833E+11 | 0.647654E+11 | 117577.54 | 65105.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139456E+12 | 0.794589E+11 | 146413.09 | 86153.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.869587E+11 | 0.577345E+11 | 122064.53 | 09-JAN-05:02 | 65559.52 | 0.00 |
February | 0.00 | 0.00 | 0.833501E+11 | 0.552751E+11 | 121854.06 | 06-FEB-06:02 | 68055.21 | 0.00 |
March | 0.00 | 0.00 | 0.101822E+12 | 0.655085E+11 | 122300.13 | 13-MAR-04:02 | 67565.33 | 0.00 |
April | 0.00 | 0.00 | 0.107306E+12 | 0.625268E+11 | 122737.80 | 06-APR-04:02 | 64374.94 | 0.00 |
May | 0.00 | 0.00 | 0.122319E+12 | 0.660339E+11 | 125521.91 | 24-MAY-04:02 | 60547.89 | 0.00 |
June | 0.00 | 0.00 | 0.122935E+12 | 0.667365E+11 | 125338.29 | 10-JUN-05:03 | 57655.17 | 0.00 |
July | 0.00 | 0.00 | 0.964424E+11 | 0.564873E+11 | 120216.49 | 10-JUL-04:02 | 71104.27 | 0.00 |
August | 0.00 | 0.00 | 0.113340E+12 | 0.594746E+11 | 126337.75 | 21-AUG-05:03 | 55006.27 | 0.00 |
September | 0.00 | 0.00 | 0.103357E+12 | 0.555721E+11 | 122755.68 | 25-SEP-04:02 | 66475.74 | 0.00 |
October | 0.00 | 0.00 | 0.100201E+12 | 0.545722E+11 | 125038.11 | 30-OCT-04:02 | 62853.92 | 0.00 |
November | 0.00 | 0.00 | 0.926523E+11 | 0.542995E+11 | 121741.86 | 13-NOV-05:02 | 69214.22 | 0.00 |
December | 0.00 | 0.00 | 0.852963E+11 | 0.539889E+11 | 105244.60 | 30-DEC-06:03 | 59363.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121598E+13 | 0.708210E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.833501E+11 | 0.539889E+11 | 105244.60 | 55006.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122935E+12 | 0.667365E+11 | 126337.75 | 71104.27 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.911986E+11 | 0.616998E+11 | 122704.10 | 09-JAN-05:02 | 62488.49 | 0.00 |
February | 0.00 | 0.00 | 0.881668E+11 | 0.597585E+11 | 140527.96 | 06-FEB-06:02 | 76227.26 | 0.00 |
March | 0.00 | 0.00 | 0.108181E+12 | 0.715662E+11 | 141991.55 | 13-MAR-04:02 | 76004.39 | 0.00 |
April | 0.00 | 0.00 | 0.114486E+12 | 0.690286E+11 | 142516.56 | 12-APR-04:02 | 73582.18 | 0.00 |
May | 0.00 | 0.00 | 0.129001E+12 | 0.720743E+11 | 145677.94 | 13-MAY-05:03 | 66406.51 | 0.00 |
June | 0.00 | 0.00 | 0.129689E+12 | 0.730264E+11 | 145245.07 | 10-JUN-05:03 | 64189.12 | 0.00 |
July | 0.00 | 0.00 | 0.101645E+12 | 0.612043E+11 | 136825.78 | 10-JUL-04:02 | 79861.46 | 0.00 |
August | 0.00 | 0.00 | 0.118269E+12 | 0.640731E+11 | 145245.07 | 12-AUG-05:03 | 66753.80 | 0.00 |
September | 0.00 | 0.00 | 0.108291E+12 | 0.602179E+11 | 142289.89 | 25-SEP-04:02 | 74035.40 | 0.00 |
October | 0.00 | 0.00 | 0.104082E+12 | 0.581595E+11 | 145416.45 | 30-OCT-04:02 | 70438.89 | 0.00 |
November | 0.00 | 0.00 | 0.967738E+11 | 0.580817E+11 | 132464.19 | 13-NOV-05:02 | 71210.05 | 0.00 |
December | 0.00 | 0.00 | 0.894581E+11 | 0.576752E+11 | 102248.03 | 30-DEC-06:03 | 55031.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127924E+13 | 0.766565E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.881668E+11 | 0.576752E+11 | 102248.03 | 55031.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129689E+12 | 0.730264E+11 | 145677.94 | 79861.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1186.19 | 4024.36 | 05-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1185.50 | 4010.01 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1243.77 | 3965.45 | 02-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1141.74 | 3893.03 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1158.92 | 3819.37 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1171.93 | 3734.92 | 05-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1072.93 | 3708.51 | 24-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1182.53 | 3753.10 | 28-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1124.20 | 3825.23 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1145.42 | 3902.21 | 27-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1183.97 | 3964.43 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1152.54 | 4006.50 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1162.36 | ||||
Minimum of Months | 0.00 | 0.00 | 1072.93 | 3708.51 | ||
Maximum of Months | 0.00 | 0.00 | 1243.77 | 4024.36 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.383836E+10 | 0.43 | 10861.76 | 30-JAN-07:03 | 1.77 |
February | 0.363734E+10 | 0.44 | 10986.34 | 06-FEB-06:02 | 1.78 |
March | 0.423506E+10 | 0.47 | 10986.34 | 06-MAR-05:02 | 1.78 |
April | 0.393086E+10 | 0.46 | 10986.34 | 03-APR-04:02 | 1.78 |
May | 0.425256E+10 | 0.47 | 10986.34 | 02-MAY-04:02 | 1.78 |
June | 0.452657E+10 | 0.49 | 10986.34 | 05-JUN-04:02 | 1.78 |
July | 0.374703E+10 | 0.43 | 10986.34 | 03-JUL-04:02 | 1.78 |
August | 0.398378E+10 | 0.45 | 10986.34 | 02-AUG-04:03 | 1.78 |
September | 0.360608E+10 | 0.43 | 10986.34 | 06-SEP-04:02 | 1.78 |
October | 0.356743E+10 | 0.42 | 10986.34 | 02-OCT-04:02 | 1.78 |
November | 0.366435E+10 | 0.43 | 10986.34 | 06-NOV-07:03 | 1.78 |
December | 0.355094E+10 | 0.41 | 10986.34 | 04-DEC-07:03 | 1.78 |
Annual Sum or Average | 0.465404E+11 | 0.44 | |||
Minimum of Months | 0.355094E+10 | 0.41 | 10861.76 | 1.77 | |
Maximum of Months | 0.452657E+10 | 0.49 | 10986.34 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305455E+10 | 0.41 | 8371.51 | 02-JAN-06:12 | 1.64 |
February | 0.293438E+10 | 0.42 | 9476.51 | 06-FEB-06:02 | 1.78 |
March | 0.334590E+10 | 0.44 | 9476.51 | 13-MAR-04:02 | 1.78 |
April | 0.308187E+10 | 0.43 | 9476.51 | 03-APR-04:02 | 1.78 |
May | 0.329506E+10 | 0.44 | 9476.51 | 01-MAY-04:02 | 1.78 |
June | 0.347792E+10 | 0.46 | 9476.51 | 05-JUN-04:02 | 1.78 |
July | 0.282089E+10 | 0.40 | 9476.51 | 05-JUL-04:02 | 1.78 |
August | 0.295550E+10 | 0.41 | 9476.51 | 02-AUG-05:03 | 1.78 |
September | 0.272208E+10 | 0.40 | 9476.51 | 05-SEP-04:02 | 1.78 |
October | 0.272172E+10 | 0.39 | 9476.51 | 16-OCT-04:02 | 1.78 |
November | 0.282720E+10 | 0.40 | 9476.51 | 13-NOV-05:02 | 1.78 |
December | 0.278017E+10 | 0.39 | 8893.21 | 26-DEC-07:03 | 1.71 |
Annual Sum or Average | 0.360172E+11 | 0.41 | |||
Minimum of Months | 0.272172E+10 | 0.39 | 8371.51 | 1.64 | |
Maximum of Months | 0.347792E+10 | 0.46 | 9476.51 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.296721E+10 | 0.38 | 6261.63 | 02-JAN-06:12 | 1.25 |
February | 0.289390E+10 | 0.40 | 10981.61 | 06-FEB-06:02 | 1.78 |
March | 0.337804E+10 | 0.42 | 10981.61 | 20-MAR-04:02 | 1.78 |
April | 0.315419E+10 | 0.41 | 10981.61 | 03-APR-04:02 | 1.78 |
May | 0.331827E+10 | 0.42 | 10981.61 | 01-MAY-04:02 | 1.78 |
June | 0.349969E+10 | 0.43 | 10981.61 | 12-JUN-04:02 | 1.78 |
July | 0.279492E+10 | 0.38 | 10098.97 | 31-JUL-04:02 | 1.69 |
August | 0.292542E+10 | 0.39 | 10981.61 | 14-AUG-04:02 | 1.78 |
September | 0.272572E+10 | 0.38 | 10981.61 | 05-SEP-04:02 | 1.78 |
October | 0.265126E+10 | 0.36 | 10199.47 | 30-OCT-04:02 | 1.69 |
November | 0.274037E+10 | 0.37 | 7411.32 | 13-NOV-05:02 | 1.39 |
December | 0.269330E+10 | 0.36 | 6376.52 | 26-DEC-07:03 | 1.26 |
Annual Sum or Average | 0.357423E+11 | 0.39 | |||
Minimum of Months | 0.265126E+10 | 0.36 | 6261.63 | 1.25 | |
Maximum of Months | 0.349969E+10 | 0.43 | 10981.61 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.20 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.20 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.06 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.83 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.24 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.72 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.96 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.93 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.22 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.06 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.85 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.86 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.06 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.99 | 56.99 | 1186.19 | 4024.36 | 05-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.39 | 57.39 | 1185.50 | 4010.01 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.20 | 58.20 | 1243.77 | 3965.45 | 02-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.02 | 57.02 | 1141.74 | 3893.03 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.41 | 57.41 | 1158.92 | 3819.37 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.90 | 57.90 | 1171.93 | 3734.92 | 05-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.15 | 58.15 | 1072.93 | 3708.51 | 24-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.10 | 58.10 | 1182.53 | 3753.10 | 28-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.40 | 57.40 | 1124.20 | 3825.23 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.60 | 57.60 | 1145.42 | 3902.21 | 27-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.05 | 58.05 | 1183.97 | 3964.43 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.05 | 57.05 | 1152.54 | 4006.50 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1162.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.99 | 56.99 | 1072.93 | 3708.51 | ||
Maximum of Months | 0.00 | 0.00 | 58.20 | 58.20 | 1243.77 | 4024.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.294615E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.282351E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.345599E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.353208E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.398126E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.405443E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.315299E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.365834E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.332596E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.318588E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.304033E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.282548E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.399824E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.282351E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.405443E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.250782E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.243520E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.297521E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.306563E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.344714E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349117E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267445E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309623E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.282972E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.272229E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.257304E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.240688E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342248E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.240688E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349117E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.262049E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.256826E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.315682E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.326801E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.363291E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.367920E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.281067E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.322381E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.296118E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.281761E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267414E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.251262E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359257E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.251262E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.367920E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.383836E+10 | 0.100642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363734E+10 | 0.951833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423506E+10 | 0.116099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393086E+10 | 0.120990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425256E+10 | 0.138284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.452657E+10 | 0.139456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.374703E+10 | 0.111077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.398378E+10 | 0.130662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360608E+10 | 0.118761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356743E+10 | 0.114745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366435E+10 | 0.107434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355094E+10 | 0.984483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465404E+11 | 0.139178E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355094E+10 | 0.951833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.452657E+10 | 0.139456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.305455E+10 | 0.869587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293438E+10 | 0.833501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334590E+10 | 0.101822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308187E+10 | 0.107306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329506E+10 | 0.122319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.347792E+10 | 0.122935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282089E+10 | 0.964424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295550E+10 | 0.113340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272208E+10 | 0.103357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272172E+10 | 0.100201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282720E+10 | 0.926523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278017E+10 | 0.852963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360172E+11 | 0.121598E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272172E+10 | 0.833501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347792E+10 | 0.122935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.296721E+10 | 0.911986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289390E+10 | 0.881668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337804E+10 | 0.108181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315419E+10 | 0.114486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331827E+10 | 0.129001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.349969E+10 | 0.129689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279492E+10 | 0.101645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292542E+10 | 0.118269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272572E+10 | 0.108291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265126E+10 | 0.104082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274037E+10 | 0.967738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269330E+10 | 0.894581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357423E+11 | 0.127924E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265126E+10 | 0.881668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.349969E+10 | 0.129689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.383836E+10 | 0.00 | 0.00 | 0.00 | 0.256231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363734E+10 | 0.00 | 0.00 | 0.00 | 0.245977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423506E+10 | 0.00 | 0.00 | 0.00 | 0.303249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393086E+10 | 0.00 | 0.00 | 0.00 | 0.313899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425256E+10 | 0.00 | 0.00 | 0.00 | 0.355601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.452657E+10 | 0.00 | 0.00 | 0.00 | 0.360177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.374703E+10 | 0.00 | 0.00 | 0.00 | 0.277828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.398378E+10 | 0.00 | 0.00 | 0.00 | 0.325997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360608E+10 | 0.00 | 0.00 | 0.00 | 0.296536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356743E+10 | 0.00 | 0.00 | 0.00 | 0.282914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366435E+10 | 0.00 | 0.00 | 0.00 | 0.267389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355094E+10 | 0.00 | 0.00 | 0.00 | 0.247039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465404E+11 | 0.00 | 0.00 | 0.00 | 0.353284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355094E+10 | 0.00 | 0.00 | 0.00 | 0.245977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.452657E+10 | 0.00 | 0.00 | 0.00 | 0.360177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.305455E+10 | 0.00 | 0.00 | 0.00 | 0.220237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293438E+10 | 0.00 | 0.00 | 0.00 | 0.214176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334590E+10 | 0.00 | 0.00 | 0.00 | 0.264062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308187E+10 | 0.00 | 0.00 | 0.00 | 0.275744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329506E+10 | 0.00 | 0.00 | 0.00 | 0.311763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.314338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282089E+10 | 0.00 | 0.00 | 0.00 | 0.239236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295550E+10 | 0.00 | 0.00 | 0.00 | 0.280068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272208E+10 | 0.00 | 0.00 | 0.00 | 0.255751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272172E+10 | 0.00 | 0.00 | 0.00 | 0.245012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282720E+10 | 0.00 | 0.00 | 0.00 | 0.229032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278017E+10 | 0.00 | 0.00 | 0.00 | 0.212887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360172E+11 | 0.00 | 0.00 | 0.00 | 0.306231E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272172E+10 | 0.00 | 0.00 | 0.00 | 0.212887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.314338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.296721E+10 | 0.00 | 0.00 | 0.00 | 0.232377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289390E+10 | 0.00 | 0.00 | 0.00 | 0.227887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337804E+10 | 0.00 | 0.00 | 0.00 | 0.281902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315419E+10 | 0.00 | 0.00 | 0.00 | 0.295259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331827E+10 | 0.00 | 0.00 | 0.00 | 0.330108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.349969E+10 | 0.00 | 0.00 | 0.00 | 0.332923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279492E+10 | 0.00 | 0.00 | 0.00 | 0.253118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292542E+10 | 0.00 | 0.00 | 0.00 | 0.293127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272572E+10 | 0.00 | 0.00 | 0.00 | 0.268860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265126E+10 | 0.00 | 0.00 | 0.00 | 0.255248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274037E+10 | 0.00 | 0.00 | 0.00 | 0.240010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269330E+10 | 0.00 | 0.00 | 0.00 | 0.224329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357423E+11 | 0.00 | 0.00 | 0.00 | 0.323515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265126E+10 | 0.00 | 0.00 | 0.00 | 0.224329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.349969E+10 | 0.00 | 0.00 | 0.00 | 0.332923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 923499.92 | 0.119046E+11 | 0.00 | 69956.92 | 0.203991E+10 | 0.00 | 1598375.09 | 0.00 | 0.33 |
February | 0.00 | 0.114098E+11 | 0.00 | 0.00 | 0.222842E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.152670E+11 | 0.00 | 0.00 | 0.232857E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.179917E+11 | 0.00 | 0.00 | 0.400599E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.221559E+11 | 0.00 | 0.00 | 0.488038E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.223379E+11 | 0.00 | 0.00 | 0.397844E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.156707E+11 | 0.00 | 0.00 | 0.341264E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.222536E+11 | 0.00 | 0.00 | 0.313375E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.193193E+11 | 0.00 | 0.00 | 0.397231E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.186166E+11 | 0.00 | 0.00 | 0.329413E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.156599E+11 | 0.00 | 0.00 | 0.276648E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.124546E+11 | 0.00 | 0.00 | 0.243583E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 923499.92 | 0.205042E+12 | 0.00 | 69956.92 | 0.384769E+11 | 0.00 | 1598375.09 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.114098E+11 | 0.00 | 0.00 | 0.203991E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 923499.92 | 0.223379E+11 | 0.00 | 69956.92 | 0.488038E+10 | 0.00 | 1598375.09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2852576.40 | 0.109939E+11 | 0.00 | 41966.97 | 0.189799E+10 | 0.00 | 2033283.94 | 0.00 | 0.30 |
February | 0.00 | 0.106297E+11 | 0.00 | 0.00 | 0.217398E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.140773E+11 | 0.00 | 0.00 | 0.249694E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.168774E+11 | 0.00 | 0.00 | 0.405746E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.210234E+11 | 0.00 | 0.00 | 0.483901E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.212348E+11 | 0.00 | 0.00 | 0.401903E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.148080E+11 | 0.00 | 0.00 | 0.344440E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.210176E+11 | 0.00 | 0.00 | 0.327990E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.182006E+11 | 0.00 | 0.00 | 0.396838E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.173824E+11 | 0.00 | 0.00 | 0.343955E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.146392E+11 | 0.00 | 0.00 | 0.266865E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 157938.94 | 0.115824E+11 | 0.00 | 8862.55 | 0.231251E+10 | 0.00 | 18636.29 | 0.00 | 0.30 |
Annual Sum or Average | 3010515.34 | 0.192467E+12 | 0.00 | 50829.52 | 0.385978E+11 | 0.00 | 2051920.22 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.106297E+11 | 0.00 | 0.00 | 0.189799E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 2852576.40 | 0.212348E+11 | 0.00 | 41966.97 | 0.483901E+10 | 0.00 | 2033283.94 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2278616.58 | 0.106409E+11 | 0.00 | 0.00 | 0.190085E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
February | 0.00 | 0.102829E+11 | 0.00 | 0.00 | 0.221213E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.136071E+11 | 0.00 | 0.00 | 0.241796E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.163546E+11 | 0.00 | 0.00 | 0.415316E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.204507E+11 | 0.00 | 0.00 | 0.494866E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.206227E+11 | 0.00 | 0.00 | 0.410969E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.142930E+11 | 0.00 | 0.00 | 0.356875E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.203781E+11 | 0.00 | 0.00 | 0.339806E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.177332E+11 | 0.00 | 0.00 | 0.392184E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.168612E+11 | 0.00 | 0.00 | 0.350793E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.141654E+11 | 0.00 | 0.00 | 0.283380E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.110371E+11 | 0.00 | 0.00 | 0.261002E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 2278616.58 | 0.186427E+12 | 0.00 | 0.00 | 0.395828E+11 | 0.00 | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.102829E+11 | 0.00 | 0.00 | 0.190085E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 2278616.58 | 0.206227E+11 | 0.00 | 0.00 | 0.494866E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 480178.59 | 0.305777E+10 | 0.00 | 0.00 | 0.399028E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.318163E+10 | 0.00 | 0.00 | 0.380966E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
March | 0.00 | 0.437455E+10 | 0.00 | 0.00 | 0.383574E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.570315E+10 | 0.00 | 0.00 | 0.633751E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.786184E+10 | 0.00 | 0.00 | 0.624582E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.857904E+10 | 0.00 | 0.00 | 0.439490E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.530489E+10 | 0.00 | 0.00 | 0.482360E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.682884E+10 | 0.00 | 0.00 | 0.528501E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.573510E+10 | 0.00 | 0.00 | 0.635429E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.510784E+10 | 0.00 | 0.00 | 0.563894E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.416748E+10 | 0.00 | 0.00 | 0.511460E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.314146E+10 | 0.00 | 0.00 | 0.536933E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 480178.59 | 0.630436E+11 | 0.00 | 0.00 | 0.611997E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.305777E+10 | 0.00 | 0.00 | 0.380966E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 480178.59 | 0.857904E+10 | 0.00 | 0.00 | 0.635429E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 389465.86 | 0.255358E+10 | 0.00 | 0.00 | 0.256232E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.00 | 0.272232E+10 | 0.00 | 0.00 | 0.209197E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.374872E+10 | 0.00 | 0.00 | 0.265154E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.480950E+10 | 0.00 | 0.00 | 0.443489E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.562582E+10 | 0.00 | 0.00 | 0.532623E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.579516E+10 | 0.00 | 0.00 | 0.420584E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.363736E+10 | 0.00 | 0.00 | 0.431754E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.524462E+10 | 0.00 | 0.00 | 0.411622E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.463562E+10 | 0.00 | 0.00 | 0.437232E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.406609E+10 | 0.00 | 0.00 | 0.436050E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.333438E+10 | 0.00 | 0.00 | 0.344139E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.262861E+10 | 0.00 | 0.00 | 0.332434E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 389465.86 | 0.488018E+11 | 0.00 | 0.00 | 0.452051E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.255358E+10 | 0.00 | 0.00 | 0.209197E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 389465.86 | 0.579516E+10 | 0.00 | 0.00 | 0.532623E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 480726.51 | 0.461610E+10 | 0.00 | 0.00 | 0.212868E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
February | 0.00 | 0.443319E+10 | 0.00 | 0.00 | 0.242983E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.504682E+10 | 0.00 | 0.00 | 0.332875E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.00 | 0.558100E+10 | 0.00 | 0.00 | 0.654438E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.696005E+10 | 0.00 | 0.00 | 0.752547E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.695489E+10 | 0.00 | 0.00 | 0.603274E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.457476E+10 | 0.00 | 0.00 | 0.596232E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.640364E+10 | 0.00 | 0.00 | 0.559148E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.602085E+10 | 0.00 | 0.00 | 0.615423E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.609988E+10 | 0.00 | 0.00 | 0.462167E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.565611E+10 | 0.00 | 0.00 | 0.323240E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.488969E+10 | 0.00 | 0.00 | 0.274815E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 480726.51 | 0.672370E+11 | 0.00 | 0.00 | 0.563001E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.443319E+10 | 0.00 | 0.00 | 0.212868E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 480726.51 | 0.696005E+10 | 0.00 | 0.00 | 0.752547E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 450777.84 | 0.254062E+10 | 0.00 | 0.00 | 0.364253E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
February | 0.00 | 0.267931E+10 | 0.00 | 0.00 | 0.390461E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.376421E+10 | 0.00 | 0.00 | 0.365769E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.470995E+10 | 0.00 | 0.00 | 0.588459E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.540709E+10 | 0.00 | 0.00 | 0.767613E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.556366E+10 | 0.00 | 0.00 | 0.598601E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.350503E+10 | 0.00 | 0.00 | 0.633638E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.505714E+10 | 0.00 | 0.00 | 0.583946E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.445726E+10 | 0.00 | 0.00 | 0.639999E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.389487E+10 | 0.00 | 0.00 | 0.721202E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.326715E+10 | 0.00 | 0.00 | 0.567012E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.255168E+10 | 0.00 | 0.00 | 0.545218E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 450777.84 | 0.473980E+11 | 0.00 | 0.00 | 0.676617E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.254062E+10 | 0.00 | 0.00 | 0.364253E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 450777.84 | 0.556366E+10 | 0.00 | 0.00 | 0.767613E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 522722.25 | 0.257305E+10 | 0.00 | 0.00 | 0.484781E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.260305E+10 | 0.00 | 0.00 | 0.519294E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.359073E+10 | 0.00 | 0.00 | 0.549882E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.469720E+10 | 0.00 | 0.00 | 0.829087E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.664081E+10 | 0.00 | 0.00 | 0.773186E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.740699E+10 | 0.00 | 0.00 | 0.497416E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.461562E+10 | 0.00 | 0.00 | 0.576200E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.584851E+10 | 0.00 | 0.00 | 0.610236E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.484023E+10 | 0.00 | 0.00 | 0.852575E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.418174E+10 | 0.00 | 0.00 | 0.766139E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.344333E+10 | 0.00 | 0.00 | 0.646296E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.268434E+10 | 0.00 | 0.00 | 0.572289E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 522722.25 | 0.531256E+11 | 0.00 | 0.00 | 0.767738E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.257305E+10 | 0.00 | 0.00 | 0.484781E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 522722.25 | 0.740699E+10 | 0.00 | 0.00 | 0.852575E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 303656.25 | 0.214040E+10 | 0.00 | 3072.35 | 0.309885E+09 | 0.00 | 77443.04 | 0.00 | 0.44 |
February | 0.00 | 0.231392E+10 | 0.00 | 0.00 | 0.241810E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.323513E+10 | 0.00 | 0.00 | 0.254643E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.414085E+10 | 0.00 | 0.00 | 0.409793E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.481949E+10 | 0.00 | 0.00 | 0.509657E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.495511E+10 | 0.00 | 0.00 | 0.421148E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.315120E+10 | 0.00 | 0.00 | 0.420613E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.450251E+10 | 0.00 | 0.00 | 0.369774E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.402658E+10 | 0.00 | 0.00 | 0.426707E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.342454E+10 | 0.00 | 0.00 | 0.419389E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.278993E+10 | 0.00 | 0.00 | 0.362575E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
December | 0.00 | 0.224354E+10 | 0.00 | 0.00 | 0.332831E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 303656.25 | 0.417432E+11 | 0.00 | 3072.35 | 0.447883E+10 | 0.00 | 77443.04 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.214040E+10 | 0.00 | 0.00 | 0.241810E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 303656.25 | 0.495511E+10 | 0.00 | 3072.35 | 0.509657E+09 | 0.00 | 77443.04 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 417450.08 | 0.439749E+10 | 0.00 | 508.06 | 0.256145E+09 | 0.00 | 104366.20 | 0.00 | 0.51 |
February | 0.00 | 0.424034E+10 | 0.00 | 0.00 | 0.259165E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.00 | 0.515522E+10 | 0.00 | 0.00 | 0.376492E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.573511E+10 | 0.00 | 0.00 | 0.787765E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.712859E+10 | 0.00 | 0.00 | 0.920372E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.718002E+10 | 0.00 | 0.00 | 0.769672E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.455878E+10 | 0.00 | 0.00 | 0.726709E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.658478E+10 | 0.00 | 0.00 | 0.662853E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.605329E+10 | 0.00 | 0.00 | 0.765726E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.597633E+10 | 0.00 | 0.00 | 0.504337E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.553381E+10 | 0.00 | 0.00 | 0.321832E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.466438E+10 | 0.00 | 0.00 | 0.282237E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 417450.08 | 0.672081E+11 | 0.00 | 508.06 | 0.663330E+10 | 0.00 | 104366.20 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.424034E+10 | 0.00 | 0.00 | 0.256145E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 417450.08 | 0.718002E+10 | 0.00 | 508.06 | 0.920372E+09 | 0.00 | 104366.20 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 362999.48 | 0.217043E+10 | 0.00 | 98.43 | 0.323878E+09 | 0.00 | 50511.47 | 0.00 | 0.44 |
February | 0.00 | 0.231138E+10 | 0.00 | 0.00 | 0.320722E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.327984E+10 | 0.00 | 0.00 | 0.296107E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.409367E+10 | 0.00 | 0.00 | 0.487498E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.468501E+10 | 0.00 | 0.00 | 0.618565E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.487505E+10 | 0.00 | 0.00 | 0.472387E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.309400E+10 | 0.00 | 0.00 | 0.491787E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.440505E+10 | 0.00 | 0.00 | 0.427982E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.388308E+10 | 0.00 | 0.00 | 0.546764E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.337207E+10 | 0.00 | 0.00 | 0.495972E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.277269E+10 | 0.00 | 0.00 | 0.442381E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.224879E+10 | 0.00 | 0.00 | 0.377674E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 362999.48 | 0.411911E+11 | 0.00 | 98.43 | 0.530172E+10 | 0.00 | 50511.47 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.217043E+10 | 0.00 | 0.00 | 0.296107E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 362999.48 | 0.487505E+10 | 0.00 | 98.43 | 0.618565E+09 | 0.00 | 50511.47 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1031227.46 | 0.318554E+10 | 0.00 | 154.56 | 0.406937E+09 | 0.00 | 4695.81 | 0.00 | 0.39 |
February | 0.00 | 0.324716E+10 | 0.00 | 0.00 | 0.441521E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.451197E+10 | 0.00 | 0.00 | 0.452515E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.00 | 0.583234E+10 | 0.00 | 0.00 | 0.689370E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.806581E+10 | 0.00 | 0.00 | 0.664002E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.887149E+10 | 0.00 | 0.00 | 0.443416E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.542974E+10 | 0.00 | 0.00 | 0.530758E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.701305E+10 | 0.00 | 0.00 | 0.556983E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.581514E+10 | 0.00 | 0.00 | 0.741174E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.514059E+10 | 0.00 | 0.00 | 0.681327E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.425335E+10 | 0.00 | 0.00 | 0.556772E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
December | 39112.77 | 0.327714E+10 | 0.00 | 0.00 | 0.503997E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 1070340.23 | 0.646433E+11 | 0.00 | 154.56 | 0.666877E+10 | 0.00 | 4695.81 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.318554E+10 | 0.00 | 0.00 | 0.406937E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 1031227.46 | 0.887149E+10 | 0.00 | 154.56 | 0.741174E+09 | 0.00 | 4695.81 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 776072.10 | 0.255709E+10 | 0.00 | 5329.45 | 0.296646E+09 | 0.00 | 64116.65 | 0.00 | 0.50 |
February | 0.00 | 0.272592E+10 | 0.00 | 0.00 | 0.247133E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.383722E+10 | 0.00 | 0.00 | 0.283821E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.490024E+10 | 0.00 | 0.00 | 0.441058E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.571464E+10 | 0.00 | 0.00 | 0.528983E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.587201E+10 | 0.00 | 0.00 | 0.443030E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.365523E+10 | 0.00 | 0.00 | 0.462419E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.529211E+10 | 0.00 | 0.00 | 0.421194E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.466690E+10 | 0.00 | 0.00 | 0.471480E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.408238E+10 | 0.00 | 0.00 | 0.455744E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.335460E+10 | 0.00 | 0.00 | 0.349915E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 31822.08 | 0.264349E+10 | 0.00 | 0.00 | 0.340896E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 807894.19 | 0.493018E+11 | 0.00 | 5329.45 | 0.474232E+10 | 0.00 | 64116.65 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.255709E+10 | 0.00 | 0.00 | 0.247133E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 776072.10 | 0.587201E+10 | 0.00 | 5329.45 | 0.528983E+09 | 0.00 | 64116.65 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1029131.25 | 0.479415E+10 | 0.00 | 6852.17 | 0.221574E+09 | 0.00 | 2222.12 | 0.00 | 0.54 |
February | 0.00 | 0.461973E+10 | 0.00 | 0.00 | 0.236453E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.527616E+10 | 0.00 | 0.00 | 0.353809E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.571153E+10 | 0.00 | 0.00 | 0.708901E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.711200E+10 | 0.00 | 0.00 | 0.807300E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.711783E+10 | 0.00 | 0.00 | 0.672097E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.465655E+10 | 0.00 | 0.00 | 0.658918E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.655315E+10 | 0.00 | 0.00 | 0.608656E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.615370E+10 | 0.00 | 0.00 | 0.679455E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.626802E+10 | 0.00 | 0.00 | 0.472583E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.587664E+10 | 0.00 | 0.00 | 0.291265E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 39033.27 | 0.507363E+10 | 0.00 | 0.00 | 0.253793E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 1068164.51 | 0.692131E+11 | 0.00 | 6852.17 | 0.596481E+10 | 0.00 | 2222.12 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.461973E+10 | 0.00 | 0.00 | 0.221574E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 1029131.25 | 0.711783E+10 | 0.00 | 6852.17 | 0.807300E+09 | 0.00 | 2222.12 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 919569.31 | 0.265950E+10 | 0.00 | 0.00 | 0.311244E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.00 | 0.280867E+10 | 0.00 | 0.00 | 0.339109E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.396712E+10 | 0.00 | 0.00 | 0.338499E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.489084E+10 | 0.00 | 0.00 | 0.557302E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.563031E+10 | 0.00 | 0.00 | 0.682699E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.579249E+10 | 0.00 | 0.00 | 0.554007E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.364010E+10 | 0.00 | 0.00 | 0.566716E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.527547E+10 | 0.00 | 0.00 | 0.482162E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.459417E+10 | 0.00 | 0.00 | 0.599417E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.409610E+10 | 0.00 | 0.00 | 0.567678E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.341900E+10 | 0.00 | 0.00 | 0.445752E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 34714.48 | 0.271450E+10 | 0.00 | 0.00 | 0.402296E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 954283.80 | 0.494883E+11 | 0.00 | 0.00 | 0.584688E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.265950E+10 | 0.00 | 0.00 | 0.311244E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 919569.31 | 0.579249E+10 | 0.00 | 0.00 | 0.682699E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234531E+12 | -0.969897E+10 | 0.00 | -0.116737E+12 | 0.349683E+12 |
February | 0.228561E+12 | -0.996142E+10 | 0.00 | -0.117228E+12 | 0.335504E+12 |
March | 0.292588E+12 | -0.161043E+11 | 0.00 | -0.145674E+12 | 0.411023E+12 |
April | 0.288354E+12 | -0.178010E+11 | 0.00 | -0.188035E+12 | 0.431273E+12 |
May | 0.289784E+12 | -0.222100E+11 | 0.00 | -0.229785E+12 | 0.489351E+12 |
June | 0.300457E+12 | -0.216429E+11 | 0.00 | -0.223539E+12 | 0.492824E+12 |
July | 0.250268E+12 | -0.132490E+11 | 0.00 | -0.167025E+12 | 0.386182E+12 |
August | 0.310972E+12 | -0.199798E+11 | 0.00 | -0.207171E+12 | 0.452191E+12 |
September | 0.246061E+12 | -0.154022E+11 | 0.00 | -0.197593E+12 | 0.412523E+12 |
October | 0.271803E+12 | -0.146761E+11 | 0.00 | -0.186978E+12 | 0.397344E+12 |
November | 0.225335E+12 | -0.120371E+11 | 0.00 | -0.157905E+12 | 0.370503E+12 |
December | 0.221547E+12 | -0.926476E+10 | 0.00 | -0.129713E+12 | 0.341628E+12 |
Annual Sum or Average | 0.316026E+13 | -0.182028E+12 | 0.00 | -0.206738E+13 | 0.487003E+13 |
Minimum of Months | 0.221547E+12 | -0.222100E+11 | 0.00 | -0.229785E+12 | 0.335504E+12 |
Maximum of Months | 0.310972E+12 | -0.926476E+10 | 0.00 | -0.116737E+12 | 0.492824E+12 |