Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:31:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1940.32 | 389.45 | 389.45 |
Net Site Energy | 1940.32 | 389.45 | 389.45 |
Total Source Energy | 5375.93 | 1079.03 | 1079.03 |
Net Source Energy | 5375.93 | 1079.03 | 1079.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 270.42 | 233.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 138.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 135.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1571.11 | 369.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 270.42 | 233.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 138.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 91.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 135.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 270.42 | 233.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 138.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 91.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 135.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 100.61 | 74.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 315.35 | 74.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 100.61 | 74.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 315.35 | 74.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1571.109 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1571.109 | 100.00 |
Total On-Site and Utility Electric Sources | 1571.109 | 100.00 |
Total Electricity End Uses | 1571.109 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 368.67 |
Time Setpoint Not Met During Occupied Cooling | 60.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2746.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:20 |
Heating | 204819.20 | 106591.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 244.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7275.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8928.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 250011.58 | 115520.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 204819.20 | 106591.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 244.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7275.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8928.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 856.42 | 253.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 439.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 954.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 291.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 146.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4975.70 | 400.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 171.90 | 50.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 998.70 | 80.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 171.90 | 50.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 998.70 | 80.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.03 | 0.247394 | 0.260000 | 0.787642 | 0.659718 | 0.500000 | 0.001540 |
CORE_MID VAV BOX COMPONENT | 2.25 | 0.332612 | 0.339000 | 0.763848 | 0.886966 | 0.500000 | 0.001145 |
CORE_TOP VAV BOX COMPONENT | 2.32 | 0.322665 | 0.341000 | 0.792042 | 0.860439 | 0.500000 | 0.001181 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.715478 | 0.220820 | 0.233000 | 0.166706 | 0.588853 | 0.500000 | 0.001725 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.827361 | 0.120893 | 0.200000 | 0.165472 | 0.322380 | 0.500000 | 0.003152 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.153588 | 0.200000 | 0.205735 | 0.409568 | 0.500000 | 0.002481 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.903723 | 0.110670 | 0.200000 | 0.180745 | 0.300000 | 0.500000 | 0.003443 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.566931 | 0.278679 | 0.293000 | 0.166111 | 0.743144 | 0.500000 | 0.001367 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.681054 | 0.146863 | 0.200000 | 0.136211 | 0.391635 | 0.500000 | 0.002594 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.827983 | 0.190815 | 0.201000 | 0.166425 | 0.508840 | 0.500000 | 0.001997 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.710659 | 0.140736 | 0.200000 | 0.142132 | 0.375296 | 0.500000 | 0.002707 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.630210 | 0.250697 | 0.256000 | 0.161334 | 0.668525 | 0.500000 | 0.001520 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.812706 | 0.123072 | 0.200000 | 0.162541 | 0.328193 | 0.500000 | 0.003096 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.941817 | 0.167752 | 0.200000 | 0.188363 | 0.447339 | 0.500000 | 0.002271 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.840184 | 0.119040 | 0.200000 | 0.168037 | 0.317439 | 0.500000 | 0.003201 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25645.77 |
CORE_MID VAV BOX REHEAT COIL | 24871.02 |
CORE_TOP VAV BOX REHEAT COIL | 42381.15 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20863.89 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13546.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20849.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13660.81 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15723.63 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10281.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15723.61 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10381.27 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16498.70 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10760.92 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16481.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10864.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.91 | 1.40 | 5.82 | 2.03 | 5.15 | 5.15 | 0.300000 | 0.392906 | 5.15 |
PACU_VAV_MID | 2.74 | 1.44 | 5.48 | 2.44 | 4.61 | 4.61 | 0.300000 | 0.528966 | 4.61 |
PACU_VAV_TOP | 2.90 | 1.51 | 5.80 | 3.42 | 5.26 | 5.26 | 0.300000 | 0.650347 | 5.26 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.15 |
PACU_VAV_MID_OA_CONTROLLER | 4.61 |
PACU_VAV_TOP_OA_CONTROLLER | 5.26 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.15 | 105994.56 | 0.764942 | 1.72 | 35327.99 | 0.764942 |
PACU_VAV_MID COOLING COIL | 4.61 | 97698.68 | 0.754144 | 1.54 | 32562.97 | 0.754144 |
PACU_VAV_TOP COOLING COIL | 5.26 | 108209.08 | 0.764623 | 1.75 | 36066.09 | 0.764623 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 38480.06 |
PACU_VAV_MID HEATING COIL | 39897.11 |
PACU_VAV_TOP HEATING COIL | 39679.82 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.15 |
PACU_VAV_MID FAN | 4.61 |
PACU_VAV_TOP FAN | 5.26 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8022 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.032 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.013 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.034 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7350 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29755900E-12 | 0.81313074E-15 | -0.93602003E-13 | 0.14510957E-15 |
43 | 6 | 0.28367368E-07 | 0.22496401E-09 | 0.65009128E-08 | -0.13359594E-12 |
44 | 5 | -0.18856357E-03 | 0.19286971E-05 | -0.97009749E-04 | 0.64274374E-08 |
45 | 4 | 0.29034011 | 0.94012602E-03 | 0.99033658E-01 | -0.33316087E-04 |
46 | 3 | -7.2305496 | 0.29163423E-01 | -2.3282961 | 0.28833673E-01 |
47 | 2 | 40.753148 | 0.10379063 | 15.221555 | -0.33202618 |
48 | 1 | -80.455373 | 0.46876469E-01 | -29.102648 | 1.0766925 |
49 | 0 | 46.824339 | 0.94379271E-03 | 16.292168 | |
50 | 7 | -0.29905644E-12 | 0.21441847E-14 | -0.94350753E-13 | 0.15229914E-15 |
51 | 6 | 0.28527035E-07 | 0.22156944E-09 | 0.65361533E-08 | -0.13441220E-12 |
52 | 5 | -0.18937502E-03 | 0.18976302E-05 | -0.97416439E-04 | 0.64617957E-08 |
53 | 4 | 0.29129073 | 0.92413897E-03 | 0.99375489E-01 | -0.33450099E-04 |
54 | 3 | -7.2493786 | 0.28644335E-01 | -2.3338831 | 0.28925940E-01 |
55 | 2 | 40.815249 | 0.10187053 | 15.244478 | -0.33271782 |
56 | 1 | -80.502964 | 0.45980673E-01 | -29.123201 | 1.0777067 |
57 | 0 | 46.824339 | 0.92519179E-03 | 16.291675 | |
58 | 7 | -0.27570686E-12 | 0.13707328E-14 | -0.80264236E-13 | 0.78378346E-16 |
59 | 6 | 0.25615968E-07 | 0.28022365E-09 | 0.58936169E-08 | -0.11887149E-12 |
60 | 5 | -0.17446821E-03 | 0.24481169E-05 | -0.89927666E-04 | 0.58344893E-08 |
61 | 4 | 0.27366067 | 0.12133616E-02 | 0.93044102E-01 | -0.30982017E-04 |
62 | 3 | -6.8997845 | 0.38197916E-01 | -2.2301787 | 0.27213971E-01 |
63 | 2 | 39.661773 | 0.13771433 | 14.818013 | -0.31987377 |
64 | 1 | -79.618511 | 0.62899977E-01 | -28.740542 | 1.0588596 |
65 | 0 | 46.824345 | 0.12804488E-02 | 16.301062 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2280E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2344E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3605E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3660E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2600E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3050E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3739E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3982E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1704 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0078E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1940 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1022 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9965E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8328E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8130E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2281E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2358E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3607E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3675E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2620E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3148E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3736E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3979E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8817E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5551E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5462E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2759E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5339E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7896E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6742E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6741E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0206E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0469E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7332E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7523E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2823E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2891E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1047E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1131E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6737E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7318E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9075E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9545E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3952E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4303E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3736E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3979E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4687E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5588E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4473E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9526E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1720E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3390E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8328E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8130E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6734E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7323E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9067E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9529E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3934E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4234E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3739E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3982E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5869E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9261E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9216E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4835E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4936E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3000E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6742E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6742E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1962E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2694E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6935E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7737E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6487E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6788E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1049E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1133E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1711 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1091 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1919 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1233 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1261 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3347E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5097E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5717E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6218E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4056E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3093E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1393E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3549E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6828E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5687E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6108E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0903E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3334E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0000E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6189E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7247E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9486E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5097E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5717E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3688E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8051E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7378E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3831E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3456E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2142E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5688E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6108E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1711 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1091 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1919 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1232 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1261 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3339E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5092E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5714E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6217E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4053E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3092E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1390E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3544E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6824E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5682E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6105E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0905E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3333E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0001E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6187E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7244E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9484E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5092E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5714E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3688E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8049E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7377E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3829E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3452E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2139E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5683E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6105E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40983.29400 | 40983.29400 | 3.02939 | 3.02939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9064.80839 | 9064.80839 | 0.39921 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30516.41505 | 30516.41505 | 2.25324 | 2.25324 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17508.80112 | 17508.80112 | 0.76121 | 0.76121 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31165.67553 | 31165.67553 | 2.32271 | 2.32271 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 29828.25846 | 29828.25846 | 1.30163 | 1.30163 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9599.39816 | 9599.39816 | 0.71548 | 0.71548 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14645.88390 | 14645.88390 | 0.64078 | 0.64078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11100.57942 | 11100.57942 | 0.82736 | 0.82736 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9508.83455 | 9508.83455 | 0.41604 | 0.41604 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13801.55212 | 13801.55212 | 1.02867 | 1.02867 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14635.65351 | 14635.65351 | 0.64033 | 0.64033 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12125.14953 | 12125.14953 | 0.90372 | 0.90372 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9588.90902 | 9588.90902 | 0.41956 | 0.41956 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7606.66852 | 7606.66852 | 0.56693 | 0.56693 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11043.74452 | 11043.74452 | 0.48291 | 0.48291 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9137.96245 | 9137.96245 | 0.68105 | 0.68105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7220.51266 | 7220.51266 | 0.31576 | 0.31576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11109.34068 | 11109.34068 | 0.82798 | 0.82798 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11043.72795 | 11043.72795 | 0.48291 | 0.48291 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9535.20723 | 9535.20723 | 0.71066 | 0.71066 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7290.64875 | 7290.64875 | 0.31883 | 0.31883 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8455.49431 | 8455.49431 | 0.63021 | 0.63021 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11587.59667 | 11587.59667 | 0.50671 | 0.50671 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10904.13194 | 10904.13194 | 0.81271 | 0.81271 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7557.21760 | 7557.21760 | 0.33049 | 0.33049 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12636.37878 | 12636.37878 | 0.94182 | 0.94182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11575.62710 | 11575.62710 | 0.50619 | 0.50619 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11272.80705 | 11272.80705 | 0.84018 | 0.84018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7629.79549 | 7629.79549 | 0.33368 | 0.33368 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76967.25 | 5.15416 | 5.15416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40468.16 | 2.02510 | 2.02510 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69705.55 | 4.60953 | 4.60953 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40873.05 | 2.43828 | 2.43828 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 78164.25 | 5.25618 | 5.25618 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40874.73 | 3.41834 | 3.41834 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.02939 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24739 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78764 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65972 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54005E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25645.76635 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25324 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33261 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76385 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88697 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14548E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24871.02310 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32271 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32266 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79204 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86044 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18079E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 42381.15247 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71548 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22082 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16671 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58885 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72539E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20863.88523 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82736 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12089 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16547 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32238 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15156E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13546.48984 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02867 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15359 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20573 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40957 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48067E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20849.28174 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90372 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11067 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18074 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44266E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13660.80540 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56693 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27868 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16611 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74314 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36716E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15723.63433 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68105 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14686 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13621 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39164 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59425E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10281.13062 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82798 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19082 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16642 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50884 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99670E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15723.61067 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71066 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14074 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14213 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37530 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70720E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10381.27245 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63021 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25070 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16133 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66852 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51976E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16498.69760 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81271 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12307 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16254 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32819 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09574E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10760.92487 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94182 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16775 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18836 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44734 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27121E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16481.60992 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84018 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11904 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16804 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31744 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20061E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10864.54588 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.90801 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39852 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.81602 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.02510 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.15416 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.15416 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.39291 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.73908 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44412 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.47816 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.43828 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60953 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60953 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.52897 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89897 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51070 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.79794 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.41834 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.25618 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.25618 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.65035 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.15416 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.60953 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.25618 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.15416 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.15416 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105994.55982 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76494 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.71788 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35327.98679 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76494 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 38480.06438 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.15416 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60953 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.60953 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97698.67603 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75414 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53636 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32562.96872 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75414 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 39897.11419 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.60953 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.25618 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.25618 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108209.07739 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76462 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.75188 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36066.08550 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76462 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39679.82021 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.25618 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 105136.48 | 358740.57 | 11.32 | 2.90 | 3.24 | 3.41 | 3.58 | 9.89 | 11.06 | 11.64 | 12.21 | 5.8117 | 4.6385 | 3.1226 | 1.2665 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 97016.97 | 331035.65 | 11.38 | 2.91 | 3.26 | 3.43 | 3.59 | 9.93 | 11.12 | 11.71 | 12.26 | 5.1975 | 4.1465 | 2.7923 | 1.1418 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 107337.46 | 366250.62 | 11.32 | 2.90 | 3.24 | 3.41 | 3.58 | 9.89 | 11.06 | 11.65 | 12.21 | 5.9267 | 4.7300 | 3.1850 | 1.2914 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0836601397E-002 | 2.9453508831E-002 | Pass | Pass | 0.4999780680 | 0.4958052686 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1437154508 | 9.4632830831E-002 | Pass | Pass | 0.4965501446 | 0.4740823622 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7678833223E-002 | 3.9636498997E-002 | Pass | Pass | 0.5008316425 | 0.4626323849 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.5237801584E-002 | 4.1332373355E-002 | Pass | Pass | 0.4943378783 | 0.4607968512 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 9.3648649630E-003 | 8.3763292684E-003 | Pass | Pass | 0.5207505307 | 0.5062942248 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.2883296367E-002 | 7.8540888923E-002 | Pass | Pass | 19.7978082262 | 45.0375525415 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3895381017 | 0.3884339750 | Pass | Pass | 32.3891803498 | 147.2381499343 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4052360068 | 0.4003784258 | Pass | Pass | 23.0825394887 | 76.5929257876 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3736832446 | 0.3775932874 | Pass | Pass | 22.4909816286 | 69.4314767204 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4070295563 | 0.4042651170 | Pass | Pass | 33.7500645194 | 190.8135452156 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2806659116 | 0.2658140792 | Pass | Pass | 17.0055641625 | 41.2683053080 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2885794964 | 0.2748342902 | Pass | Pass | 14.3372652725 | 34.8224290503 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2500460918 | 0.2468041971 | Pass | Pass | 16.2345087548 | 38.4910617863 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2891698797 | 0.2769548437 | Pass | Pass | 14.4822495555 | 34.7832505535 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2927279810 | 0.2817088737 | Pass | Pass | 41.0767215555 | 171.6213274798 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2983685972 | 0.2893282226 | Pass | Pass | 14.3513223172 | 42.6538450218 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2663798207 | 0.2679487932 | Pass | Pass | 22.0583924717 | 78.5237256219 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3001751168 | 0.2924211911 | Pass | Pass | 11.9351526073 | 39.2738555488 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3522.29 | 184.44 | 0.00 | 1798.01 | 752.95 | 6257.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.38 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.38 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.38 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 195.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 5.54 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 8.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.01 | 0.0000 | Y | 8.81 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 5.52 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 8.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.76 | 0.0000 | Y | 5.52 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 5.54 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 8.66 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 5.54 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.41 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.04 | 42.04 | 4.45 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.67 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.67 | 47.45 | 41.99 | |
Exterior Lighting Total | 5686.19 | 51.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105994.56 | 81079.70 | 24914.86 | 0.76 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97698.68 | 73678.89 | 24019.78 | 0.75 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108209.08 | 82739.14 | 25469.94 | 0.76 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 105136.5 | 2.90 | 9.89 | N/A | N/A | 11.32 | |
PACU_VAV_MID COOLING COIL | 97017.0 | 2.91 | 9.93 | N/A | N/A | 11.38 | |
PACU_VAV_TOP COOLING COIL | 107337.5 | 2.90 | 9.89 | N/A | N/A | 11.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25645.77 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24871.02 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 42381.15 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20863.89 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13546.49 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20849.28 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13660.81 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15723.63 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10281.13 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15723.61 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10381.27 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16498.70 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10760.92 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16481.61 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10864.55 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 38480.06 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 39897.11 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39679.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.15 | 11846.65 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.61 | 10663.63 | 2313.39 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.26 | 12081.12 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105136.48 | 2.90 | 9.89 | 11.32 | 5.8117 | 3.24 | 11.06 | 4.6385 | 3.41 | 11.64 | 3.1226 | 3.58 | 12.21 | 1.2665 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97016.97 | 2.91 | 9.93 | 11.38 | 5.1975 | 3.26 | 11.12 | 4.1465 | 3.43 | 11.71 | 2.7923 | 3.59 | 12.26 | 1.1418 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107337.46 | 2.90 | 9.89 | 11.32 | 5.9267 | 3.24 | 11.06 | 4.7300 | 3.41 | 11.65 | 3.1850 | 3.58 | 12.21 | 1.2914 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40983.29 | 40983.29 | 41.67 | 3.029 | 3.029 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 30516.42 | 30516.42 | 31.03 | 2.253 | 2.253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 31165.68 | 31165.68 | 31.69 | 2.323 | 2.323 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00888 | 30.21 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9599.40 | 9599.40 | 46.30 | 0.715 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00901 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11100.58 | 11100.58 | 84.57 | 0.827 | 0.827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00880 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13801.55 | 13801.55 | 66.57 | 1.029 | 1.029 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00886 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12125.15 | 12125.15 | 92.38 | 0.904 | 0.904 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7606.67 | 7606.67 | 36.69 | 0.567 | 0.567 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00900 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9137.96 | 9137.96 | 69.62 | 0.681 | 0.681 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00877 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11109.34 | 11109.34 | 53.58 | 0.828 | 0.828 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00885 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9535.21 | 9535.21 | 72.65 | 0.711 | 0.711 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00876 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8455.49 | 8455.49 | 40.78 | 0.630 | 0.630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00903 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10904.13 | 10904.13 | 83.07 | 0.813 | 0.813 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00878 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12636.38 | 12636.38 | 60.95 | 0.942 | 0.942 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00886 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11272.81 | 11272.81 | 85.89 | 0.840 | 0.840 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9064.81 | 9064.81 | 9.22 | 0.399 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 17508.80 | 17508.80 | 17.80 | 0.761 | 0.761 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 29828.26 | 29828.26 | 30.33 | 1.302 | 1.302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14645.88 | 14645.88 | 70.64 | 0.641 | 0.641 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9508.83 | 9508.83 | 72.44 | 0.416 | 0.416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14635.65 | 14635.65 | 70.59 | 0.640 | 0.640 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9588.91 | 9588.91 | 73.06 | 0.420 | 0.420 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11043.74 | 11043.74 | 53.26 | 0.483 | 0.483 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7220.51 | 7220.51 | 55.01 | 0.316 | 0.316 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11043.73 | 11043.73 | 53.26 | 0.483 | 0.483 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7290.65 | 7290.65 | 55.55 | 0.319 | 0.319 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11587.60 | 11587.60 | 55.89 | 0.507 | 0.507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7557.22 | 7557.22 | 57.57 | 0.330 | 0.330 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11575.63 | 11575.63 | 55.83 | 0.506 | 0.506 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7629.80 | 7629.80 | 58.13 | 0.334 | 0.334 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.15 | 5.15 | 2.03 | 2.03 | 5.1542 | 2.0251 | 5.1542 | 0.3929 | 0.3000 |
PACU_VAV_MID | 4.61 | 4.61 | 2.44 | 2.44 | 4.6095 | 2.4383 | 4.6095 | 0.5290 | 0.3000 |
PACU_VAV_TOP | 5.26 | 5.26 | 3.42 | 3.42 | 5.2562 | 3.4183 | 5.2562 | 0.6503 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25645.766 | 25645.766 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 25645.77 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 9064.81 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24871.023 | 24871.023 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24871.02 | 24785.19 | 0.761212 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 17508.80 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 42381.152 | 42381.152 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 42381.15 | 42381.15 | 1.301625 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 29828.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20863.885 | 20863.885 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20863.89 | 20863.89 | 0.640779 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753444 | 47.5273 | 14645.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13546.490 | 13546.490 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13546.49 | 13546.49 | 0.416045 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00752301 | 47.4564 | 9508.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20849.282 | 20849.282 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20849.28 | 20849.28 | 0.640331 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753413 | 47.5254 | 14635.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13660.805 | 13660.805 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13660.81 | 13660.81 | 0.419556 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00752680 | 47.4800 | 9588.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15723.634 | 15723.634 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15723.63 | 15723.63 | 0.482910 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765201 | 48.2569 | 11043.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10281.131 | 10281.131 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10281.13 | 10281.13 | 0.315758 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764834 | 48.2342 | 7220.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15723.611 | 15723.611 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15723.61 | 15723.61 | 0.482909 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765201 | 48.2569 | 11043.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10381.272 | 10381.272 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10381.27 | 10381.27 | 0.318833 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765232 | 48.2590 | 7290.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16498.698 | 16498.698 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16498.70 | 16498.70 | 0.506714 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750438 | 47.3391 | 11587.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10760.925 | 10760.925 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10760.92 | 10760.92 | 0.330493 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749582 | 47.2860 | 7557.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16481.610 | 16481.610 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16481.61 | 16481.61 | 0.506189 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750385 | 47.3358 | 11575.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10864.546 | 10864.546 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10864.55 | 10864.55 | 0.333676 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750073 | 47.3166 | 7629.80 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 105994.560 | 81079.696 | 5.154165 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 108285.73 | 86925.90 | 5.154165 | 25.46 | 17.79 | 0.00990200 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 23.1884 | 24.00 | 0.00885589 | 46.4526 | 69152.41 | 0.00 | 109294.62 | 81305.12 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 38480.064 | 38480.064 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38480.06 | 38480.06 | 1.546249 | -8.30 | -8.30 | 0.00241661 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 77.2948 | 19.60 | 0.00726690 | 49.9978 | 22647.93 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97698.676 | 73678.895 | 4.609532 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100232.35 | 78623.98 | 4.609532 | 25.63 | 17.99 | 0.01008705 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.9282 | 24.00 | 0.00893716 | 46.8735 | 61776.34 | 0.00 | 100740.45 | 73939.03 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 39897.114 | 39897.114 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39897.11 | 39897.11 | 1.382860 | -11.66 | -11.66 | 0.00178545 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 86.4274 | 17.60 | 0.00689055 | 53.7754 | 21747.96 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108209.077 | 82739.141 | 5.256175 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 110562.66 | 88489.73 | 5.256175 | 25.43 | 17.79 | 0.00992068 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.7384 | 24.00 | 0.00890352 | 46.6997 | 70367.80 | 0.00 | 111578.08 | 82967.16 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39679.820 | 39679.820 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39679.82 | 39679.82 | 1.576853 | -8.53 | -8.53 | 0.00245696 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 75.7947 | 17.38 | 0.00707078 | 55.9392 | 28522.92 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25645.766 | 25645.766 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 25645.77 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25645.77 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.02 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 9064.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24871.023 | 24871.023 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24871.02 | 24785.19 | 1.0000 | 0.89360567 | 0.761212 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24871.02 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 17508.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 42381.152 | 42381.152 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 42381.15 | 42381.15 | 1.0000 | 1.52801106 | 1.301625 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42381.15 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 29828.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20863.885 | 20863.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20863.89 | 20863.89 | 1.0000 | 0.75222701 | 0.640779 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20863.89 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753444 | 21.00 | 0.00753444 | 47.5273 | 14645.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13546.490 | 13546.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13546.49 | 13546.49 | 1.0000 | 0.48840546 | 0.416045 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13546.49 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752301 | 21.00 | 0.00752301 | 47.4564 | 9508.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20849.282 | 20849.282 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20849.28 | 20849.28 | 1.0000 | 0.75170049 | 0.640331 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20849.28 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753413 | 21.00 | 0.00753413 | 47.5254 | 14635.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13660.805 | 13660.805 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13660.81 | 13660.81 | 1.0000 | 0.49252700 | 0.419556 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13660.81 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752680 | 21.00 | 0.00752680 | 47.4800 | 9588.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15723.634 | 15723.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15723.63 | 15723.63 | 1.0000 | 0.56690028 | 0.482910 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15723.63 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765201 | 21.00 | 0.00765201 | 48.2569 | 11043.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10281.131 | 10281.131 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10281.13 | 10281.13 | 1.0000 | 0.37067612 | 0.315758 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10281.13 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764834 | 21.00 | 0.00764834 | 48.2342 | 7220.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15723.611 | 15723.611 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15723.61 | 15723.61 | 1.0000 | 0.56689943 | 0.482909 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15723.61 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765201 | 21.00 | 0.00765201 | 48.2569 | 11043.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10381.272 | 10381.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10381.27 | 10381.27 | 1.0000 | 0.37428664 | 0.318833 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.27 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765232 | 21.00 | 0.00765232 | 48.2590 | 7290.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16498.698 | 16498.698 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16498.70 | 16498.70 | 1.0000 | 0.59484443 | 0.506714 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16498.70 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750438 | 21.00 | 0.00750438 | 47.3391 | 11587.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10760.925 | 10760.925 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10760.92 | 10760.92 | 1.0000 | 0.38797464 | 0.330493 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10760.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749582 | 21.00 | 0.00749582 | 47.2860 | 7557.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16481.610 | 16481.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16481.61 | 16481.61 | 1.0000 | 0.59422835 | 0.506189 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16481.61 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750385 | 21.00 | 0.00750385 | 47.3358 | 11575.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10864.546 | 10864.546 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10864.55 | 10864.55 | 1.0000 | 0.39171059 | 0.333676 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10864.55 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750073 | 21.00 | 0.00750073 | 47.3166 | 7629.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105994.560 | 81079.696 | 5.154165 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2473 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.154165 | 6.05060455 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 108285.73 | 86925.90 | 1.0216 | 6.05060455 | 5.154165 | 25.46 | 17.79 | 0.00990200 | 50816.0 | 10.89 | 10.89 | 0.00850000 | 32369.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11846.650 | 96439.08 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 23.1884 | 24.00 | 0.00885589 | 24.00 | 0.00885589 | 46.4526 | 69152.41 | 0.00 | 109294.62 | 81305.12 | 5.81165141 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.96 | 0.00929638 | 36516.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38480.064 | 38480.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.154165 | 6.05060455 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38480.06 | 38480.06 | 1.0000 | 1.81518136 | 1.546249 | -8.30 | -8.30 | 0.00241661 | -2330.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38480.06 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 77.2948 | 18.95 | 0.00749753 | 19.60 | 0.00726690 | 49.9978 | 22647.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97698.676 | 73678.895 | 4.609532 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5913 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.609532 | 5.41124653 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 100232.35 | 78623.98 | 1.0259 | 5.41124653 | 4.609532 | 25.63 | 17.99 | 0.01008705 | 51466.0 | 10.87 | 10.87 | 0.00850000 | 32357.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10663.630 | 89568.72 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 25.9282 | 24.00 | 0.00893716 | 24.00 | 0.00893716 | 46.8735 | 61776.34 | 0.00 | 100740.45 | 73939.03 | 5.19754320 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.75 | 12.73 | 0.00916289 | 35940.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39897.114 | 39897.114 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.609532 | 5.41124653 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39897.11 | 39897.11 | 1.0000 | 1.62337396 | 1.382860 | -11.66 | -11.66 | 0.00178545 | -7287.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39897.11 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 86.4274 | 17.90 | 0.00727040 | 17.60 | 0.00689055 | 53.7754 | 21747.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108209.077 | 82739.141 | 5.256175 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2820 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.256175 | 6.17035738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 110562.66 | 88489.73 | 1.0218 | 6.17035738 | 5.256175 | 25.43 | 17.79 | 0.00992068 | 50837.5 | 10.89 | 10.89 | 0.00850000 | 32369.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12081.117 | 98481.54 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 22.7384 | 24.00 | 0.00890352 | 24.00 | 0.00890352 | 46.6997 | 70367.80 | 0.00 | 111578.08 | 82967.16 | 5.92667491 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.97 | 12.95 | 0.00929191 | 36496.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39679.820 | 39679.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.256175 | 6.17035738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39679.82 | 39679.82 | 1.0000 | 1.85110721 | 1.576853 | -8.53 | -8.53 | 0.00245696 | -2467.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39679.82 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 75.7947 | 15.79 | 0.00725685 | 17.38 | 0.00707078 | 55.9392 | 28522.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.15 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.61 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.26 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2050.67 | 2918.67 | 122.50 |
CORE_MID | 2432.50 | 3652.50 | 978.50 |
CORE_TOP | 2955.17 | 3947.17 | 1653.17 |
PERIMETER_TOP_ZN_3 | 3647.67 | 4226.33 | 2442.67 |
PERIMETER_TOP_ZN_2 | 3799.67 | 4003.67 | 2318.33 |
PERIMETER_TOP_ZN_1 | 3512.83 | 3939.67 | 2056.33 |
PERIMETER_TOP_ZN_4 | 3708.67 | 4236.67 | 2369.83 |
PERIMETER_BOT_ZN_3 | 3313.00 | 4286.33 | 2158.83 |
PERIMETER_BOT_ZN_2 | 3554.83 | 3861.50 | 1976.17 |
PERIMETER_BOT_ZN_1 | 3304.67 | 4109.00 | 1941.17 |
PERIMETER_BOT_ZN_4 | 3505.00 | 3980.00 | 2015.00 |
PERIMETER_MID_ZN_3 | 3402.00 | 4025.17 | 2089.17 |
PERIMETER_MID_ZN_2 | 3033.33 | 3364.17 | 1788.67 |
PERIMETER_MID_ZN_1 | 3261.83 | 3658.33 | 1660.00 |
PERIMETER_MID_ZN_4 | 3513.50 | 4020.67 | 2031.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4849.17 | 4767.00 | 2746.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.50 | 0.00 | 0.50 | 0.00 |
CORE_MID | 3.17 | 0.00 | 2.83 | 0.00 |
CORE_TOP | 6.50 | 0.00 | 3.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 143.50 | 2.00 | 59.50 | 1.67 |
PERIMETER_TOP_ZN_2 | 101.33 | 13.67 | 17.67 | 13.50 |
PERIMETER_TOP_ZN_1 | 81.33 | 16.83 | 13.83 | 16.33 |
PERIMETER_TOP_ZN_4 | 101.83 | 22.17 | 21.33 | 13.17 |
PERIMETER_BOT_ZN_3 | 38.50 | 0.00 | 24.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14.17 | 4.00 | 0.50 | 4.00 |
PERIMETER_BOT_ZN_1 | 336.67 | 7.00 | 328.33 | 7.00 |
PERIMETER_BOT_ZN_4 | 14.50 | 13.17 | 0.83 | 6.67 |
PERIMETER_MID_ZN_3 | 51.17 | 0.00 | 18.67 | 0.00 |
PERIMETER_MID_ZN_2 | 33.33 | 13.33 | 1.17 | 13.33 |
PERIMETER_MID_ZN_1 | 26.00 | 15.00 | 1.33 | 15.00 |
PERIMETER_MID_ZN_4 | 34.00 | 20.50 | 1.83 | 11.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 480.83 | 76.17 | 368.67 | 60.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.957 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.695 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.698 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.784 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.282 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.121 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.307 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.687 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.063 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.887 | 0.878 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.037 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.763 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.161 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.077 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.237 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15139400.95 | 0.00 | 15139400.95 | 0.00 | 15139400.95 | 13393058.27 | 5793.23 | 113.78 | 2852.99 | 129.12 |
CORE_MID | 11067598.08 | 0.00 | 11067598.08 | 0.00 | 11067598.08 | 13393058.27 | 6416.99 | 22.29 | 2320.72 | 177.61 |
CORE_TOP | 11117835.06 | 0.00 | 11117835.06 | 0.00 | 11117835.06 | 13393058.27 | 6358.44 | 20.83 | 2380.72 | 94.07 |
PERIMETER_TOP_ZN_3 | 2631005.01 | 0.00 | 2631005.01 | 750436.27 | 3381441.28 | 2823374.22 | 5754.95 | 36.48 | 2968.56 | 94.07 |
PERIMETER_TOP_ZN_2 | 2722246.69 | 0.00 | 2722246.69 | 500287.84 | 3222534.54 | 1787429.43 | 4084.47 | 0.68 | 4674.84 | 94.07 |
PERIMETER_TOP_ZN_1 | 3752546.50 | 0.00 | 3752546.50 | 750436.27 | 4502982.77 | 2823374.22 | 4104.70 | 1.86 | 4653.44 | 94.07 |
PERIMETER_TOP_ZN_4 | 2786520.53 | 0.00 | 2786520.53 | 500287.84 | 3286808.37 | 1787312.18 | 4083.01 | 3.96 | 4673.03 | 94.07 |
PERIMETER_BOT_ZN_3 | 2307801.33 | 0.00 | 2307801.33 | 399002.08 | 2706803.41 | 2823374.22 | 6055.72 | 112.04 | 2592.24 | 129.12 |
PERIMETER_BOT_ZN_2 | 2253828.03 | 0.00 | 2253828.03 | 265999.79 | 2519827.82 | 1787429.43 | 4141.24 | 14.20 | 4604.57 | 129.12 |
PERIMETER_BOT_ZN_1 | 2975232.35 | 0.00 | 2975232.35 | 3134132.70 | 6109365.05 | 2823374.22 | 5285.73 | 163.76 | 3310.51 | 129.12 |
PERIMETER_BOT_ZN_4 | 2204728.64 | 0.00 | 2204728.64 | 265999.79 | 2470728.43 | 1787312.18 | 4175.18 | 10.11 | 4574.70 | 129.12 |
PERIMETER_MID_ZN_3 | 2558080.15 | 0.00 | 2558080.15 | 624679.86 | 3182760.01 | 2823374.22 | 5938.32 | 29.95 | 2791.73 | 177.58 |
PERIMETER_MID_ZN_2 | 2673346.41 | 0.00 | 2673346.41 | 416450.74 | 3089797.15 | 1787429.43 | 4081.09 | 2.37 | 4676.54 | 1086.58 |
PERIMETER_MID_ZN_1 | 3601917.75 | 0.00 | 3601917.75 | 624679.86 | 4226597.61 | 2823374.22 | 4111.43 | 3.19 | 4645.39 | 177.58 |
PERIMETER_MID_ZN_4 | 2635317.33 | 0.00 | 2635317.33 | 416450.74 | 3051768.07 | 1787312.18 | 4078.71 | 5.16 | 4676.12 | 177.58 |
Total Facility | 70427404.83 | 0.00 | 70427404.83 | 8648843.76 | 79076248.59 | 67843644.98 | 6560.74 | 326.30 | 4758.18 | 1171.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.4247 | 3009.52 | 113.78 | 2819.70 |
CORE_MID | 0.5112 | 0.0000 | 0.5112 | 0.0000 | 0.5112 | 0.4247 | 3637.09 | 22.29 | 2283.62 |
CORE_TOP | 0.5133 | 0.0000 | 0.5133 | 0.0000 | 0.5133 | 0.4247 | 3587.97 | 20.83 | 2334.19 |
PERIMETER_TOP_ZN_3 | 0.1216 | 0.0000 | 0.1216 | 0.0178 | 0.1394 | 0.0895 | 2984.48 | 36.48 | 2922.04 |
PERIMETER_TOP_ZN_2 | 0.1259 | 0.0000 | 0.1259 | 0.0119 | 0.1378 | 0.0567 | 1314.00 | 0.68 | 4628.32 |
PERIMETER_TOP_ZN_1 | 0.1737 | 0.0000 | 0.1737 | 0.0178 | 0.1915 | 0.0895 | 1334.22 | 1.86 | 4606.92 |
PERIMETER_TOP_ZN_4 | 0.1283 | 0.0000 | 0.1283 | 0.0119 | 0.1402 | 0.0567 | 1312.54 | 3.96 | 4626.50 |
PERIMETER_BOT_ZN_3 | 0.1067 | 0.0000 | 0.1067 | 0.0095 | 0.1161 | 0.0895 | 3272.01 | 112.04 | 2558.95 |
PERIMETER_BOT_ZN_2 | 0.1044 | 0.0000 | 0.1044 | 0.0063 | 0.1107 | 0.0567 | 1357.57 | 14.18 | 4571.26 |
PERIMETER_BOT_ZN_1 | 0.1378 | 0.0000 | 0.1378 | 0.1373 | 0.2752 | 0.0895 | 2502.02 | 163.76 | 3277.22 |
PERIMETER_BOT_ZN_4 | 0.1018 | 0.0000 | 0.1018 | 0.0063 | 0.1081 | 0.0567 | 1391.56 | 10.09 | 4541.35 |
PERIMETER_MID_ZN_3 | 0.1183 | 0.0000 | 0.1183 | 0.0148 | 0.1331 | 0.0895 | 3158.42 | 29.95 | 2754.64 |
PERIMETER_MID_ZN_2 | 0.1140 | 0.0000 | 0.1140 | 0.0105 | 0.1245 | 0.0567 | 1301.54 | 2.37 | 3730.09 |
PERIMETER_MID_ZN_1 | 0.1668 | 0.0000 | 0.1668 | 0.0148 | 0.1817 | 0.0895 | 1331.52 | 3.19 | 4608.29 |
PERIMETER_MID_ZN_4 | 0.1215 | 0.0000 | 0.1215 | 0.0099 | 0.1314 | 0.0567 | 1299.18 | 5.11 | 4638.71 |
Total Facility | 3.2473 | 0.0000 | 3.2473 | 0.2687 | 3.5160 | 2.1513 | 3764.42 | 326.20 | 4699.92 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 34288492.28 | 0.00 | 34288492.28 | 22614548.33 | 4106.68 | 4.34 | 4648.97 | 129.12 |
PACU_VAV_MID | 31057251.34 | 0.00 | 31057251.34 | 22614548.33 | 4086.46 | 2.54 | 4671.00 | 177.54 |
PACU_VAV_TOP | 31710310.37 | 0.00 | 31710310.37 | 22614548.33 | 4084.45 | 0.59 | 4674.96 | 93.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5884 | 0.0000 | 1.5884 | 0.7171 | 1322.97 | 4.34 | 4615.68 |
PACU_VAV_MID | 1.4353 | 0.0000 | 1.4353 | 0.7171 | 1306.56 | 2.54 | 4633.91 |
PACU_VAV_TOP | 1.4647 | 0.0000 | 1.4647 | 0.7171 | 1313.98 | 0.59 | 4628.43 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.33 | 2878.73 | 0.00 | 0.00 | 0.00 | 1986.21 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2742.06 | 0.00 | 0.00 | 0.00 | 2217.32 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.17 | 2726.49 | 0.00 | 0.00 | 0.00 | 2161.81 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6688 | 0.0000 | 0.0000 | 0.0000 | 1.0577 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.4003 | 0.0000 | 0.0000 | 0.0000 | 1.0715 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.4301 | 0.0000 | 0.0000 | 0.0000 | 1.0680 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
Electricity:Building | 1006.85 | 12229.26 | 16-APR-17:20 | 78507.21 | 11-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1006.85 | 12229.26 | 16-APR-17:20 | 78507.21 | 11-JAN-08:10 |
InteriorLights:Electricity | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.17 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.94 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.99 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.14 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-11:20 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-11:20 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.93 | 267.21 | 09-APR-17:10 | 1768.58 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.52 | 22.79 | 01-JAN-09:20 | 860.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.52 | 22.79 | 01-JAN-09:20 | 860.01 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.97 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.92 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.17 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.94 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.99 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 512.86 | 168.59 | 16-APR-17:30 | 212636.74 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 11-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 11-JAN-08:20 |
ElectricityPurchased:Facility | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
ElectricityNet:Plant | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1571.11 | 12397.85 | 30-APR-17:30 | 250011.58 | 02-JAN-07:10 |
Heating:Electricity | 270.42 | 0.00 | 01-JAN-00:40 | 205141.51 | 02-JAN-06:20 |
General:Heating:Electricity | 270.42 | 0.00 | 01-JAN-00:40 | 205141.51 | 02-JAN-06:20 |
Fans:Electricity | 91.89 | 0.00 | 01-JAN-00:40 | 28989.26 | 17-JUL-12:10 |
General:Fans:Electricity | 91.89 | 0.00 | 01-JAN-00:40 | 28989.26 | 17-JUL-12:10 |
ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 138.79 | 0.00 | 01-JAN-00:10 | 78738.48 | 15-AUG-14:30 |
General:Cooling:Electricity | 138.79 | 0.00 | 01-JAN-00:10 | 78738.48 | 15-AUG-14:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
WIRED_LTG_ELECTRICITY | 8.47 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 369.21 | 1886.44 | 09-JAN-05:10 | 115520.39 | 07-FEB-07:30 |
NaturalGas:HVAC | 233.92 | 0.00 | 01-JAN-00:40 | 108110.08 | 07-FEB-07:20 |
Heating:NaturalGas | 233.92 | 0.00 | 01-JAN-00:40 | 108110.08 | 07-FEB-07:20 |
General:Heating:NaturalGas | 233.92 | 0.00 | 01-JAN-00:40 | 108110.08 | 07-FEB-07:20 |
NaturalGas:Plant | 135.29 | 1886.44 | 03-JAN-08:20 | 11188.10 | 06-FEB-12:40 |
WaterSystems:NaturalGas | 135.29 | 1886.44 | 03-JAN-08:20 | 11188.10 | 06-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 135.29 | 1886.44 | 03-JAN-08:20 | 11188.10 | 06-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2172.67 | 0.00 | 01-JAN-00:40 | 489807.18 | 15-AUG-14:30 |
EnergyTransfer:Building | 1094.85 | 0.00 | 01-JAN-00:40 | 199685.28 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 209.10 | 0.00 | 01-JAN-00:40 | 27048.89 | 17-JUL-08:00 |
Heating:EnergyTransfer | 226.32 | 0.00 | 01-JAN-00:40 | 199685.28 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 20128.34 | 02-JAN-06:30 |
General:Heating:EnergyTransfer | 226.32 | 0.00 | 01-JAN-00:40 | 199685.28 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 20128.34 | 02-JAN-06:30 |
Cooling:EnergyTransfer | 868.54 | 0.00 | 01-JAN-00:40 | 160896.81 | 09-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 208.76 | 0.00 | 01-JAN-00:40 | 27048.89 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer | 868.54 | 0.00 | 01-JAN-00:40 | 160896.81 | 09-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 208.76 | 0.00 | 01-JAN-00:40 | 27048.89 | 17-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.24 | 0.00 | 01-JAN-00:40 | 16506.27 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.59 | 0.00 | 01-JAN-00:40 | 16506.27 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.59 | 0.00 | 01-JAN-00:40 | 16506.27 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.65 | 0.00 | 01-JAN-00:10 | 10343.11 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.65 | 0.00 | 01-JAN-00:10 | 10343.11 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.10 | 0.00 | 01-JAN-00:40 | 9714.60 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.27 | 0.00 | 01-JAN-00:40 | 9714.60 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.27 | 0.00 | 01-JAN-00:40 | 9714.60 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.83 | 0.00 | 01-JAN-00:10 | 5295.81 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.83 | 0.00 | 01-JAN-00:10 | 5295.81 | 17-JUL-12:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.70 | 0.00 | 01-JAN-00:40 | 8533.08 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.47 | 0.00 | 01-JAN-00:40 | 8533.08 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.47 | 0.00 | 01-JAN-00:40 | 8533.08 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.23 | 0.00 | 01-JAN-00:10 | 5713.65 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.23 | 0.00 | 01-JAN-00:10 | 5713.65 | 17-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 139.11 | 0.00 | 01-JAN-00:40 | 21045.98 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.60 | 0.00 | 01-JAN-00:20 | 21045.98 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.60 | 0.00 | 01-JAN-00:20 | 21045.98 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 136.50 | 0.00 | 01-JAN-00:40 | 19260.78 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 136.50 | 0.00 | 01-JAN-00:40 | 19260.78 | 17-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 136.61 | 0.00 | 01-JAN-00:40 | 29388.69 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.57 | 0.00 | 01-JAN-00:40 | 29388.69 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.57 | 0.00 | 01-JAN-00:40 | 29388.69 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 125.04 | 0.00 | 01-JAN-00:20 | 20964.05 | 27-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 125.04 | 0.00 | 01-JAN-00:20 | 20964.05 | 27-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.46 | 0.00 | 01-JAN-00:40 | 10527.92 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.44 | 0.00 | 01-JAN-00:40 | 10527.92 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.44 | 0.00 | 01-JAN-00:40 | 10527.92 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.02 | 0.00 | 01-JAN-00:10 | 7095.93 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.02 | 0.00 | 01-JAN-00:10 | 7095.93 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.67 | 0.00 | 01-JAN-00:40 | 9770.90 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.00 | 0.00 | 01-JAN-00:40 | 9770.90 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.00 | 0.00 | 01-JAN-00:40 | 9770.90 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.67 | 0.00 | 01-JAN-00:20 | 8809.88 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.67 | 0.00 | 01-JAN-00:20 | 8809.88 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.18 | 0.00 | 01-JAN-00:40 | 13987.49 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.54 | 0.00 | 01-JAN-00:40 | 13987.49 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.54 | 0.00 | 01-JAN-00:40 | 13987.49 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.64 | 0.00 | 01-JAN-00:20 | 12463.27 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.64 | 0.00 | 01-JAN-00:20 | 12463.27 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.88 | 0.00 | 01-JAN-00:40 | 9949.25 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.01 | 0.00 | 01-JAN-00:40 | 9949.25 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.01 | 0.00 | 01-JAN-00:40 | 9949.25 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.88 | 0.00 | 01-JAN-00:20 | 9205.07 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.88 | 0.00 | 01-JAN-00:20 | 9205.07 | 18-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.04 | 0.00 | 01-JAN-00:40 | 7862.60 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.63 | 0.00 | 01-JAN-00:40 | 7862.60 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.63 | 0.00 | 01-JAN-00:40 | 7862.60 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.41 | 0.00 | 01-JAN-00:20 | 5552.23 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.41 | 0.00 | 01-JAN-00:20 | 5552.23 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.65 | 0.00 | 01-JAN-00:40 | 7348.57 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 0.00 | 01-JAN-00:40 | 7348.57 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 0.00 | 01-JAN-00:40 | 7348.57 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.87 | 0.00 | 01-JAN-00:20 | 7016.31 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.87 | 0.00 | 01-JAN-00:20 | 7016.31 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.72 | 0.00 | 01-JAN-00:40 | 14395.19 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.03 | 0.00 | 01-JAN-00:40 | 14395.19 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.03 | 0.00 | 01-JAN-00:40 | 14395.19 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.69 | 0.00 | 01-JAN-00:20 | 11502.97 | 10-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.69 | 0.00 | 01-JAN-00:20 | 11502.97 | 10-AUG-11:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.78 | 0.00 | 01-JAN-00:40 | 7384.72 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.39 | 0.00 | 01-JAN-00:40 | 7384.72 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.39 | 0.00 | 01-JAN-00:40 | 7384.72 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.39 | 0.00 | 01-JAN-00:20 | 7328.75 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.39 | 0.00 | 01-JAN-00:20 | 7328.75 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.80 | 0.00 | 01-JAN-00:40 | 8893.02 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.38 | 0.00 | 01-JAN-00:40 | 8893.02 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.38 | 0.00 | 01-JAN-00:40 | 8893.02 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.43 | 0.00 | 01-JAN-00:20 | 6455.83 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.43 | 0.00 | 01-JAN-00:20 | 6455.83 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.79 | 0.00 | 01-JAN-00:40 | 8767.86 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.24 | 0.00 | 01-JAN-00:40 | 7651.90 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.24 | 0.00 | 01-JAN-00:40 | 7651.90 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.55 | 0.00 | 01-JAN-00:20 | 8767.86 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.55 | 0.00 | 01-JAN-00:20 | 8767.86 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.72 | 0.00 | 01-JAN-00:40 | 12105.53 | 21-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.39 | 0.00 | 01-JAN-00:40 | 10966.46 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.39 | 0.00 | 01-JAN-00:40 | 10966.46 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.33 | 0.00 | 01-JAN-00:20 | 12105.53 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.33 | 0.00 | 01-JAN-00:20 | 12105.53 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 35.29 | 0.00 | 01-JAN-00:40 | 8794.65 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.65 | 0.00 | 01-JAN-00:40 | 7656.83 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.65 | 0.00 | 01-JAN-00:40 | 7656.83 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.65 | 0.00 | 01-JAN-00:20 | 8794.65 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.65 | 0.00 | 01-JAN-00:20 | 8794.65 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
EnergyTransfer:HVAC | 1024.93 | 0.00 | 01-JAN-00:40 | 345818.44 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 457.56 | 0.00 | 01-JAN-00:40 | 267769.12 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 567.38 | 0.00 | 01-JAN-00:10 | 345818.44 | 15-AUG-14:30 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6714.58 | 13-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.343 | -208.755 | 0.000 | 0.000 | 33.309 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -132.992 |
CORE_MID | 0.000 | 0.000 | 2.604 | -136.502 | 0.000 | 0.000 | 34.862 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -88.318 |
CORE_TOP | 0.000 | 0.000 | 11.574 | -125.041 | 0.000 | 0.000 | 35.535 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -109.422 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 22.439 | -25.023 | 0.000 | 0.000 | 7.644 | 8.836 | 24.333 | 16.797 | 0.000 | 0.063 | 0.001 | 0.000 | -35.018 | 0.000 | -11.583 | -8.488 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 13.000 | -26.671 | 0.000 | 0.000 | 4.805 | 5.537 | 15.404 | 31.014 | 0.000 | 0.041 | 0.000 | 0.000 | -21.990 | 0.000 | -7.788 | -13.351 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 16.541 | -40.637 | 0.000 | 0.000 | 7.511 | 8.661 | 24.332 | 57.610 | 0.000 | 0.059 | 0.001 | 0.000 | -33.042 | 0.000 | -11.929 | -29.106 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 14.006 | -26.877 | 0.000 | 0.000 | 4.861 | 5.535 | 15.403 | 31.206 | 0.000 | 0.042 | 0.000 | 0.000 | -22.841 | 0.000 | -7.823 | -13.512 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 12.632 | -22.410 | 0.000 | 0.000 | 7.624 | 8.807 | 24.333 | 17.129 | 0.000 | 0.041 | 0.000 | 0.000 | -36.205 | 0.000 | -6.453 | -5.498 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.776 | -23.870 | 0.000 | 0.000 | 4.767 | 5.524 | 15.404 | 31.154 | 0.000 | 0.023 | 0.000 | 0.000 | -23.081 | 0.000 | -4.395 | -12.303 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 28.027 | -29.692 | 0.000 | 0.000 | 7.662 | 8.641 | 24.332 | 58.368 | 0.000 | 0.791 | 0.000 | 0.000 | -34.535 | 0.000 | -45.018 | -18.576 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.391 | -23.391 | 0.000 | 0.000 | 4.807 | 5.521 | 15.403 | 31.416 | 0.000 | 0.023 | 0.000 | 0.000 | -23.964 | 0.000 | -4.412 | -12.795 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 12.376 | -26.427 | 0.000 | 0.000 | 7.569 | 8.835 | 24.333 | 16.550 | 0.000 | 0.055 | 3.553 | 0.000 | -36.758 | 0.000 | -10.085 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 7.242 | -27.548 | 0.000 | 0.000 | 3.531 | 5.537 | 15.404 | 30.821 | 0.000 | 0.036 | 0.001 | 0.000 | -23.036 | 0.000 | -6.767 | -5.220 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.389 | -42.329 | 0.000 | 0.000 | 7.419 | 8.661 | 24.332 | 57.291 | 0.000 | 0.050 | 0.000 | 0.000 | -34.745 | 0.000 | -10.413 | -18.655 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 7.646 | -27.646 | 0.000 | 0.000 | 4.810 | 5.535 | 15.403 | 31.048 | 0.000 | 0.036 | 0.001 | 0.000 | -23.970 | 0.000 | -6.806 | -6.056 |
TOPFLOOR_PLENUM | 30.590 | -24.651 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.049 | 11.714 | 0.000 | 0.000 | 0.000 | -17.702 | -0.005 |
MIDFLOOR_PLENUM | 14.268 | -13.827 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.075 | 16.788 | 0.000 | 0.000 | 0.000 | -17.305 | -0.000 |
FIRSTFLOOR_PLENUM | 10.472 | -17.232 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.057 | 20.790 | 0.000 | 0.000 | 0.000 | -14.087 | -0.000 |
Total Facility | 55.331 | -55.710 | 170.986 | -812.821 | 0.000 | 0.000 | 176.718 | 301.415 | 705.434 | 410.403 | 0.000 | 1.444 | 52.849 | 0.000 | -349.186 | 0.000 | -182.566 | -474.298 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -43322.33 | 0.00 | 0.00 | 322.34 | 715.98 | 4989.51 | 0.00 | 0.00 | 0.00 | 37294.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -32329.73 | 0.00 | 0.00 | 332.37 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 28255.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -30314.55 | 0.00 | 0.00 | 701.76 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 24438.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:32 | 0.00 | 0.00 | 0.00 | -11642.52 | 0.00 | 0.00 | 27.57 | 36.00 | 478.42 | 4182.91 | 0.00 | 58.69 | 6858.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:22 | 0.00 | 0.00 | 0.00 | -14261.87 | 0.00 | 0.00 | 15.34 | 22.79 | 302.86 | 9295.20 | 0.00 | 0.00 | 4812.65 | 0.00 | -0.00 | 0.00 | -186.96 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -18133.20 | 0.00 | 0.00 | 24.10 | 36.00 | 478.41 | 13282.66 | 0.00 | 0.00 | 4757.67 | 0.00 | -0.00 | 0.00 | -445.64 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -16979.08 | 0.00 | 0.00 | 13.03 | 22.79 | 302.86 | 10774.27 | 0.00 | 0.00 | 5992.54 | 0.00 | -0.00 | 0.00 | -126.40 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | -5552.31 | 0.00 | 0.00 | 757.17 | 647.98 | 1435.25 | 4388.09 | 0.00 | 46.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1722.98 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:53 | 0.00 | 0.00 | 0.00 | -11490.89 | 0.00 | 0.00 | 16.22 | 22.79 | 302.86 | 8665.55 | 0.00 | 36.42 | 2447.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:43 | 0.00 | 0.00 | 0.00 | -13989.66 | 0.00 | 0.00 | 26.42 | 36.00 | 478.41 | 9701.90 | 0.00 | 0.00 | 3961.10 | 0.00 | -0.00 | 0.00 | -214.17 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-17:22 | 0.00 | 0.00 | 0.00 | -12207.07 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 8379.99 | 0.00 | 0.00 | 3698.54 | 0.00 | -0.00 | 0.00 | -138.67 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:31 | 0.00 | 0.00 | 0.00 | -8119.86 | 0.00 | 0.00 | 29.86 | 36.00 | 478.42 | 2180.28 | 0.00 | 52.66 | 5342.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-08:22 | 0.00 | 0.00 | 0.00 | -13969.75 | 0.00 | 0.00 | 15.55 | 22.79 | 302.86 | 10049.25 | 0.00 | 0.00 | 3628.87 | 0.00 | -0.00 | 0.00 | -49.56 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:32 | 0.00 | 0.00 | 0.00 | -16530.93 | 0.00 | 0.00 | 24.76 | 36.00 | 478.41 | 11549.26 | 0.00 | 0.00 | 4550.32 | 0.00 | -0.00 | 0.00 | -107.81 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:31 | 0.00 | 0.00 | 0.00 | -15173.68 | 0.00 | 0.00 | 13.59 | 22.79 | 302.86 | 9654.87 | 0.00 | 0.00 | 5202.62 | 0.00 | -0.00 | 0.00 | -23.04 | 0.00 |
TOPFLOOR_PLENUM | 27-JUN-15:15 | 0.00 | -11052.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11055.00 | 0.00 | -0.00 | 0.00 | -2.05 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5295.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.96 | 5247.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5712.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 5673.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-06:03 | 0.00 | -8539.28 | 0.00 | -155825.81 | 0.00 | 0.00 | 3549.77 | 9021.99 | 21098.80 | 3083.38 | 0.00 | 0.00 | 130694.76 | 0.00 | 0.00 | 0.00 | -3083.61 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 23286.66 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27904.04 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24496.32 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27150.11 |
CORE_TOP | 26-DEC-05:01 | 0.00 | 0.00 | 33330.13 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35983.92 |
PERIMETER_TOP_ZN_3 | 13-FEB-05:11 | 0.00 | 0.00 | 11400.63 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2761.50 | 0.00 | -2906.70 | -6291.86 |
PERIMETER_TOP_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 13036.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1836.76 | 0.00 | -1964.09 | -9589.57 |
PERIMETER_TOP_ZN_1 | 13-FEB-05:11 | 0.00 | 0.00 | 16267.53 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2871.61 | 0.00 | -2933.37 | -11021.99 |
PERIMETER_TOP_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 14212.42 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1908.04 | 0.00 | -1968.53 | -10690.00 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:11 | 0.00 | 0.00 | 8454.72 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2932.84 | 0.00 | -1662.57 | -4418.76 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 10069.99 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1951.36 | 0.00 | -1118.39 | -7354.38 |
PERIMETER_BOT_ZN_1 | 07-FEB-08:00 | 0.00 | 0.00 | 14394.80 | 0.00 | 0.00 | 0.00 | 252.44 | 216.00 | 637.88 | 0.00 | 0.00 | 0.00 | 9704.99 | 0.00 | -699.25 | 0.00 | -24506.87 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 10529.78 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2018.48 | 0.00 | -1115.97 | -7749.47 |
PERIMETER_MID_ZN_3 | 05-FEB-22:22 | 0.00 | 0.00 | 9553.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3416.69 | 0.00 | -2158.41 | -4408.78 |
PERIMETER_MID_ZN_2 | 05-FEB-22:22 | 0.00 | 0.00 | 11197.24 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2283.04 | 0.00 | -1465.51 | -7721.37 |
PERIMETER_MID_ZN_1 | 05-FEB-22:22 | 0.00 | 0.00 | 13958.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3574.65 | 0.00 | -2203.83 | -8610.67 |
PERIMETER_MID_ZN_4 | 05-FEB-22:22 | 0.00 | 0.00 | 11329.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2350.06 | 0.00 | -1464.06 | -7787.88 |
TOPFLOOR_PLENUM | 11-DEC-06:12 | 17353.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -278.56 | -17074.47 |
MIDFLOOR_PLENUM | 02-JAN-07:02 | 10405.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -270.69 | -10134.79 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -211.45 | -9380.26 |
Total Facility | 02-JAN-05:01 | 12518.92 | 0.00 | 212107.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19096.47 | 0.00 | -8545.82 | -212391.03 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.8160 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1542 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4782 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6095 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7979 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2562 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9080 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7391 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4441 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8990 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5107 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0294 | 3.0294 | 0.7876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2532 | 2.2532 | 0.7638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3227 | 2.3227 | 0.7920 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7155 | 0.7155 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8274 | 0.8274 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0287 | 1.0287 | 0.2057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9037 | 0.9037 | 0.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5669 | 0.5669 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6811 | 0.6811 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8280 | 0.8280 | 0.1664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7107 | 0.7107 | 0.1421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6302 | 0.6302 | 0.1613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8127 | 0.8127 | 0.1625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9418 | 0.9418 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8402 | 0.8402 | 0.1680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.8160 | 5.1542 | 5.8160 | 1.3985 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4782 | 4.6095 | 5.4782 | 1.4441 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7979 | 5.2562 | 5.7979 | 1.5107 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5147 | 1.5147 | 0.7876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1266 | 1.1266 | 0.7638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1614 | 1.1614 | 0.7920 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3577 | 0.3577 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4137 | 0.4137 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5143 | 0.5143 | 0.2057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4519 | 0.4519 | 0.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2835 | 0.2835 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3405 | 0.3405 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4140 | 0.4140 | 0.1664 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3553 | 0.3553 | 0.1421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3151 | 0.3151 | 0.1613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4064 | 0.4064 | 0.1625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4709 | 0.4709 | 0.1884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4201 | 0.4201 | 0.1680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9080 | 1.3985 | 1.3985 | 1.3985 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7391 | 1.4441 | 1.4441 | 1.4441 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8990 | 1.5107 | 1.5107 | 1.5107 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 368.67 |
Number of hours cooling loads not met | 60.00 |
Number of hours not met | 428.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 270.42 | 205141.51 | 233.92 | 108110.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 138.79 | 78738.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.42 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.25 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 91.89 | 28989.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 135.29 | 11188.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1571.11 |
Natural Gas | 0.00 | 369.21 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1940.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.50 |
Space Heating | 54.28 |
Space Cooling | 27.86 |
Fans (All) | 18.44 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 315.35 |
Subtotal | 315.35 |
Natural Gas [MJ/m2] | |
Space Heating | 46.95 |
Service Water Heating | 27.15 |
Miscellaneous (All) | 74.11 |
Subtotal | 74.11 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.53 |
Space Heating | 25.99 |
Space Cooling | 7.15 |
Fans (All) | 4.74 |
Service Water Heating | 6.97 |
Receptacle Equipment | 36.36 |
Miscellaneous | 3.26 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8696.67 | 63.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8669.50 | 90.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8664.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 95.67 | 0.00 | 0.00 | 0.00 |
Average | 8718.43 | 41.57 | 0.00 | 0.00 | 0.00 |
Sum | 156931.67 | 748.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128295.67 | 8.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 8.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.85 | 0.48 | 0.00 | 0.00 | 0.00 |
Sum | 614571.33 | 8.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8239.83 | 520.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8377.17 | 382.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8468.33 | 291.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8332.33 | 427.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8328.33 | 431.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8309.50 | 450.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8299.67 | 460.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8385.17 | 374.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8315.33 | 444.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8230.67 | 529.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8267.67 | 492.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8292.83 | 467.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8293.83 | 466.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8276.33 | 483.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8258.17 | 501.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8028.67 | 731.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8286.33 | 473.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8281.50 | 478.50 | 0.00 | 0.00 | 0.00 |
Min | 8028.67 | 291.67 | 0.00 | 0.00 | 0.00 |
Max | 8468.33 | 731.33 | 0.00 | 0.00 | 0.00 |
Average | 8292.87 | 467.13 | 0.00 | 0.00 | 0.00 |
Sum | 149271.67 | 8408.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128025.17 | 278.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128130.67 | 173.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128167.67 | 136.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24882.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14015.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24897.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14013.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24898.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24492.00 | 417.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24888.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24894.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128167.67 | 417.00 | 0.00 | 0.00 | 0.00 |
Average | 34082.68 | 60.66 | 0.00 | 0.00 | 0.00 |
Sum | 613488.17 | 1091.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.891511E+10 | 9468.55 | 20-JAN-17:00 | -1.1 | -3.7 | 0.177034E+10 | 2606.60 | 13-JAN-14:09 | -1.1 | -3.7 |
February | 0.875471E+10 | 9882.35 | 17-FEB-17:00 | 1.10 | 0.20 | 0.163641E+10 | 2606.58 | 17-FEB-14:20 | 1.10 | 0.20 |
March | 0.132730E+11 | 18090.88 | 17-MAR-08:00 | 9.40 | 9.07 | 0.210694E+10 | 2608.67 | 31-MAR-09:30 | 6.95 | 6.53 |
April | 0.146575E+11 | 18560.47 | 21-APR-07:03 | 3.95 | 2.35 | 0.189901E+10 | 2606.79 | 14-APR-13:09 | 3.95 | 2.35 |
May | 0.205100E+11 | 24483.15 | 24-MAY-06:03 | 18.03 | 15.62 | 0.207506E+10 | 2606.68 | 05-MAY-13:09 | 18.03 | 15.62 |
June | 0.254508E+11 | 42105.42 | 19-JUN-05:12 | 16.70 | 15.97 | 0.207060E+10 | 2606.81 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.262457E+11 | 43314.76 | 05-JUL-05:12 | 19.23 | 16.66 | 0.192566E+10 | 2606.69 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.278973E+11 | 43180.47 | 21-AUG-05:12 | 14.40 | 13.12 | 0.216144E+10 | 2610.59 | 14-AUG-09:00 | 14.40 | 13.12 |
September | 0.231322E+11 | 41842.17 | 18-SEP-06:01 | 10.28 | 9.20 | 0.191804E+10 | 2606.78 | 12-SEP-13:09 | 10.28 | 9.20 |
October | 0.172103E+11 | 22303.56 | 13-OCT-06:02 | 10.00 | 9.62 | 0.198549E+10 | 2607.65 | 30-OCT-09:50 | 8.15 | 5.08 |
November | 0.129443E+11 | 17710.22 | 07-NOV-08:06 | 2.20 | 0.89 | 0.194677E+10 | 2608.88 | 08-NOV-14:00 | 5.60 | 5.31 |
December | 0.976466E+10 | 14231.02 | 01-DEC-08:15 | 11.83 | 10.29 | 0.178916E+10 | 2606.62 | 01-DEC-10:09 | 14.50 | 11.95 |
Annual Sum or Average | 0.208756E+12 | 0.232849E+11 | ||||||||
Minimum of Months | 0.875471E+10 | 9468.55 | -1.1 | -3.7 | 0.163641E+10 | 2606.58 | -1.1 | -3.7 | ||
Maximum of Months | 0.278973E+11 | 43314.76 | 19.23 | 16.66 | 0.216144E+10 | 2610.59 | 20.60 | 15.62 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 280089.64 | 275.02 | 22-FEB-17:20 | 12.07 | 5.77 | 0.00 | 0.00 | 01-FEB-00:10 | 12.07 | 5.77 |
March | 0.345002E+09 | 5347.05 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.977676E+09 | 4484.30 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.263546E+10 | 7038.66 | 31-MAY-14:30 | 21.70 | 14.07 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.07 |
June | 0.514676E+10 | 11052.29 | 27-JUN-15:15 | 25.77 | 22.70 | 0.00 | 0.00 | 01-JUN-00:10 | 25.77 | 22.70 |
July | 0.639128E+10 | 10343.11 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.561274E+10 | 10254.23 | 09-AUG-14:40 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.286770E+10 | 8077.32 | 21-SEP-15:20 | 26.10 | 16.82 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.82 |
October | 0.615546E+09 | 4186.34 | 11-OCT-15:00 | 22.20 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.61 |
November | 58702190.61 | 999.48 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 61221.40 | 57.48 | 16-DEC-14:30 | 5.30 | 2.77 | 0.00 | 0.00 | 01-DEC-00:10 | 5.30 | 2.77 |
Annual Sum or Average | 0.246512E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.639128E+10 | 11052.29 | 31.15 | 22.70 | 0.00 | 0.00 | 31.15 | 22.70 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5766749.99 | 2692.79 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 6110506.97 | 2472.55 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.147686E+09 | 2183.08 | 07-MAR-05:01 | -13.3 | -13.9 | 0.00 | 0.00 | 01-MAR-00:10 | -13.3 | -13.9 |
April | 0.306257E+09 | 1385.34 | 14-APR-06:03 | 2.80 | 1.46 | 0.00 | 0.00 | 01-APR-00:10 | 2.80 | 1.46 |
May | 0.108852E+10 | 2268.52 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.282189E+10 | 4351.88 | 12-JUN-15:30 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
July | 0.377337E+10 | 5295.81 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.348260E+10 | 4563.51 | 14-AUG-15:50 | 27.80 | 21.19 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.19 |
September | 0.175396E+10 | 3218.63 | 18-SEP-13:00 | 18.90 | 12.42 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.42 |
October | 0.375237E+09 | 1675.30 | 24-OCT-06:03 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 59383985.77 | 1383.37 | 18-NOV-06:01 | 1.02 | -0.8 | 0.00 | 0.00 | 01-NOV-00:10 | 1.02 | -0.8 |
December | 6246089.35 | 2410.86 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.138270E+11 | 0.00 | ||||||||
Minimum of Months | 5766749.99 | 1383.37 | -13.3 | -13.9 | 0.00 | 0.00 | -13.3 | -13.9 | ||
Maximum of Months | 0.377337E+10 | 5295.81 | 29.15 | 21.19 | 0.00 | 0.00 | 29.15 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9811419.64 | 2100.85 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 13462963.86 | 1807.47 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.220562E+09 | 2866.26 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.497920E+09 | 2194.50 | 21-APR-06:03 | 2.88 | 1.68 | 0.00 | 0.00 | 01-APR-00:10 | 2.88 | 1.68 |
May | 0.156452E+10 | 2560.08 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.328074E+10 | 4546.48 | 12-JUN-12:10 | 29.40 | 20.05 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 20.05 |
July | 0.420631E+10 | 5713.65 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.418473E+10 | 4944.43 | 09-AUG-15:50 | 29.40 | 18.45 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.45 |
September | 0.251158E+10 | 4238.94 | 18-SEP-12:10 | 18.40 | 12.35 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 12.35 |
October | 0.627076E+09 | 2012.87 | 13-OCT-06:06 | 10.00 | 9.62 | 0.00 | 0.00 | 01-OCT-00:10 | 10.00 | 9.62 |
November | 0.109424E+09 | 1695.28 | 17-NOV-07:03 | 5.50 | 2.77 | 0.00 | 0.00 | 01-NOV-00:10 | 5.50 | 2.77 |
December | 6267580.94 | 1770.70 | 15-DEC-06:11 | 2.20 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | 1.70 |
Annual Sum or Average | 0.172324E+11 | 0.00 | ||||||||
Minimum of Months | 6267580.94 | 1695.28 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.420631E+10 | 5713.65 | 29.40 | 21.00 | 0.00 | 0.00 | 29.40 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501073E+10 | 6248.54 | 12-JAN-16:50 | -6.6 | -8.3 | 0.152051E+10 | 2200.74 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.491731E+10 | 6373.75 | 17-FEB-17:00 | 1.10 | 0.20 | 0.139449E+10 | 2251.20 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.887643E+10 | 12041.52 | 16-MAR-16:00 | 15.60 | 13.95 | 0.185659E+10 | 2606.61 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.940796E+10 | 11178.54 | 21-APR-16:00 | 13.30 | 8.77 | 0.177631E+10 | 2606.62 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.135036E+11 | 14515.55 | 31-MAY-16:00 | 22.20 | 14.47 | 0.204857E+10 | 2606.65 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.177710E+11 | 31272.32 | 19-JUN-05:12 | 16.70 | 15.97 | 0.206376E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.190132E+11 | 32327.32 | 05-JUL-05:12 | 19.23 | 16.66 | 0.192124E+10 | 2606.66 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.193509E+11 | 30198.06 | 07-AUG-06:03 | 20.68 | 18.73 | 0.215662E+10 | 2606.82 | 02-AUG-13:09 | 20.68 | 18.73 |
September | 0.149462E+11 | 30025.93 | 18-SEP-06:01 | 10.28 | 9.20 | 0.190538E+10 | 2606.76 | 12-SEP-13:09 | 10.28 | 9.20 |
October | 0.101459E+11 | 12723.50 | 12-OCT-16:00 | 18.30 | 14.87 | 0.188247E+10 | 2606.61 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.789426E+10 | 8117.87 | 01-NOV-16:00 | 9.40 | 6.91 | 0.171263E+10 | 2598.90 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.566465E+10 | 6679.24 | 01-DEC-17:00 | 7.20 | 4.89 | 0.149307E+10 | 2327.33 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.136502E+12 | 0.217316E+11 | ||||||||
Minimum of Months | 0.491731E+10 | 6248.54 | -6.6 | -8.3 | 0.139449E+10 | 2200.74 | 0.60 | -3.3 | ||
Maximum of Months | 0.193509E+11 | 32327.32 | 22.20 | 18.73 | 0.215662E+10 | 2606.82 | 22.20 | 18.73 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316795E+10 | 5904.09 | 12-JAN-16:40 | -6.5 | -8.3 | 0.147028E+10 | 2078.59 | 06-JAN-14:00 | -6.5 | -8.3 |
February | 0.342179E+10 | 6168.69 | 28-FEB-17:00 | -0.6 | -3.0 | 0.134798E+10 | 2138.11 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.742481E+10 | 12174.60 | 16-MAR-16:00 | 15.60 | 13.95 | 0.176639E+10 | 2606.61 | 15-MAR-13:30 | 15.60 | 13.95 |
April | 0.866252E+10 | 11899.34 | 21-APR-16:00 | 13.30 | 8.77 | 0.168536E+10 | 2606.62 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.130214E+11 | 16045.83 | 31-MAY-16:00 | 22.20 | 14.47 | 0.200964E+10 | 2606.65 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.179185E+11 | 27263.03 | 27-JUN-15:05 | 25.68 | 22.74 | 0.205536E+10 | 2640.85 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.195068E+11 | 25902.43 | 20-JUL-05:03 | 23.90 | 21.99 | 0.191853E+10 | 2606.66 | 12-JUL-09:00 | 23.90 | 21.99 |
August | 0.192106E+11 | 30318.96 | 07-AUG-06:03 | 20.68 | 18.73 | 0.215022E+10 | 2606.83 | 02-AUG-13:09 | 20.68 | 18.73 |
September | 0.139343E+11 | 17146.30 | 18-SEP-13:30 | 18.35 | 12.57 | 0.188057E+10 | 2606.75 | 12-SEP-13:09 | 18.35 | 12.57 |
October | 0.902161E+10 | 12349.09 | 12-OCT-16:00 | 18.30 | 14.87 | 0.176746E+10 | 2606.60 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.621147E+10 | 7464.08 | 01-NOV-16:00 | 9.40 | 6.91 | 0.158214E+10 | 2465.38 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.353902E+10 | 6331.43 | 01-DEC-16:50 | 7.20 | 4.98 | 0.142483E+10 | 2200.44 | 01-DEC-14:00 | 7.20 | 4.98 |
Annual Sum or Average | 0.125041E+12 | 0.210588E+11 | ||||||||
Minimum of Months | 0.316795E+10 | 5904.09 | -6.5 | -8.3 | 0.134798E+10 | 2078.59 | -6.5 | -8.3 | ||
Maximum of Months | 0.195068E+11 | 30318.96 | 25.68 | 22.74 | 0.215022E+10 | 2640.85 | 25.85 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13938996.08 | 1003.47 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304389E+09 | 406.69 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 20987085.46 | 1010.68 | 18-FEB-17:03 | 0.82 | -0.6 | 0.275977E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.712468E+09 | 3667.56 | 15-MAR-14:50 | 25.68 | 16.21 | 0.350002E+09 | 549.50 | 15-MAR-13:30 | 25.68 | 16.21 |
April | 0.129336E+10 | 2418.44 | 21-APR-15:20 | 14.43 | 8.49 | 0.328674E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.271671E+10 | 4731.40 | 23-MAY-14:40 | 23.90 | 13.32 | 0.409928E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.474393E+10 | 8463.60 | 27-JUN-15:05 | 25.68 | 22.74 | 0.431232E+09 | 567.04 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.562578E+10 | 11647.59 | 16-JUL-13:32 | 27.93 | 21.28 | 0.404597E+09 | 549.51 | 24-JUL-13:30 | 25.85 | 17.85 |
August | 0.512426E+10 | 7261.68 | 06-AUG-14:02 | 26.97 | 18.51 | 0.450880E+09 | 549.54 | 02-AUG-13:09 | 26.97 | 18.51 |
September | 0.299773E+10 | 4785.80 | 15-SEP-14:00 | 25.60 | 21.03 | 0.385141E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.133421E+10 | 2446.42 | 12-OCT-15:30 | 18.30 | 15.05 | 0.344377E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.400544E+09 | 1410.47 | 16-NOV-16:50 | 18.12 | 13.51 | 0.307728E+09 | 478.51 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 39218752.87 | 1100.02 | 01-DEC-13:20 | 12.03 | 10.45 | 0.293410E+09 | 406.69 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.250231E+11 | 0.428633E+10 | ||||||||
Minimum of Months | 13938996.08 | 1003.47 | 0.82 | -0.6 | 0.275977E+09 | 406.69 | -9.4 | -11.0 | ||
Maximum of Months | 0.562578E+10 | 11647.59 | 27.93 | 22.74 | 0.450880E+09 | 567.04 | 26.97 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15331541.05 | 984.42 | 14-JAN-17:03 | 3.22 | 2.72 | 0.192962E+09 | 257.46 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 0.107813E+09 | 1312.84 | 28-FEB-10:00 | -3.9 | -5.5 | 0.175643E+09 | 294.71 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.928457E+09 | 2836.92 | 15-MAR-14:00 | 26.10 | 16.06 | 0.226834E+09 | 347.88 | 15-MAR-13:30 | 26.10 | 16.06 |
April | 0.169118E+10 | 5185.76 | 24-APR-09:10 | 6.28 | 2.92 | 0.220852E+09 | 347.88 | 21-APR-13:00 | 6.28 | 2.92 |
May | 0.323895E+10 | 7494.13 | 31-MAY-08:50 | 17.70 | 13.18 | 0.263845E+09 | 347.88 | 26-MAY-09:00 | 17.70 | 13.18 |
June | 0.484883E+10 | 14262.38 | 11-JUN-09:22 | 23.85 | 16.50 | 0.273646E+09 | 348.30 | 12-JUN-09:50 | 27.62 | 19.41 |
July | 0.553082E+10 | 14045.88 | 04-JUL-09:02 | 21.28 | 17.22 | 0.256342E+09 | 348.26 | 03-JUL-09:39 | 21.28 | 17.22 |
August | 0.509637E+10 | 8227.47 | 17-AUG-09:20 | 23.53 | 16.11 | 0.285676E+09 | 347.92 | 04-AUG-09:09 | 23.53 | 16.11 |
September | 0.330863E+10 | 8735.02 | 04-SEP-10:02 | 17.98 | 13.30 | 0.245857E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.144300E+10 | 3987.79 | 11-OCT-09:30 | 15.85 | 11.81 | 0.224617E+09 | 347.87 | 10-OCT-09:00 | 15.85 | 11.81 |
November | 0.427690E+09 | 1486.16 | 03-NOV-09:20 | 4.47 | 2.22 | 0.196095E+09 | 320.81 | 03-NOV-09:30 | 4.75 | 2.42 |
December | 34124066.52 | 992.49 | 16-DEC-17:03 | 3.30 | 1.70 | 0.186112E+09 | 257.47 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.266712E+11 | 0.274848E+10 | ||||||||
Minimum of Months | 15331541.05 | 984.42 | -3.9 | -5.5 | 0.175643E+09 | 257.46 | -9.4 | -11.0 | ||
Maximum of Months | 0.553082E+10 | 14262.38 | 26.10 | 17.22 | 0.285676E+09 | 348.30 | 27.62 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412644E+09 | 3559.38 | 12-JAN-13:40 | -6.5 | -9.0 | 0.316195E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.544660E+09 | 6047.62 | 28-FEB-13:50 | 0.00 | -3.0 | 0.290559E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.200447E+10 | 10089.06 | 15-MAR-13:30 | 25.55 | 15.84 | 0.382322E+09 | 549.53 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.254833E+10 | 8068.73 | 21-APR-13:10 | 15.40 | 7.97 | 0.348198E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.421487E+10 | 8097.00 | 26-MAY-13:30 | 20.85 | 13.56 | 0.410297E+09 | 549.51 | 10-MAY-13:00 | 20.85 | 13.56 |
June | 0.598021E+10 | 11598.38 | 11-JUN-14:02 | 25.68 | 18.32 | 0.428589E+09 | 562.18 | 27-JUN-15:09 | 25.68 | 22.74 |
July | 0.711803E+10 | 17152.40 | 30-JUL-14:02 | 25.40 | 19.72 | 0.403485E+09 | 549.61 | 31-JUL-13:39 | 25.37 | 19.17 |
August | 0.742039E+10 | 17257.85 | 13-AUG-12:32 | 29.63 | 22.57 | 0.450062E+09 | 550.10 | 03-AUG-13:00 | 29.63 | 22.57 |
September | 0.579503E+10 | 18132.71 | 10-SEP-13:42 | 17.20 | 10.65 | 0.389108E+09 | 550.13 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.311186E+10 | 11969.81 | 11-OCT-12:30 | 21.95 | 13.79 | 0.371996E+09 | 549.51 | 30-OCT-13:00 | 15.00 | 8.94 |
November | 0.117262E+10 | 7455.37 | 03-NOV-12:40 | 8.53 | 4.68 | 0.329415E+09 | 549.50 | 01-NOV-13:00 | 8.53 | 4.68 |
December | 0.314798E+09 | 3761.09 | 16-DEC-13:30 | 5.60 | 3.03 | 0.299410E+09 | 549.48 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.406379E+11 | 0.441964E+10 | ||||||||
Minimum of Months | 0.314798E+09 | 3559.38 | -6.5 | -9.0 | 0.290559E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.742039E+10 | 18132.71 | 29.63 | 22.57 | 0.450062E+09 | 562.18 | 29.63 | 22.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48208376.01 | 1230.36 | 06-JAN-15:40 | -2.2 | -4.8 | 0.193017E+09 | 259.90 | 06-JAN-15:50 | -2.2 | -4.8 |
February | 0.117405E+09 | 1767.27 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176280E+09 | 333.46 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.939436E+09 | 3689.84 | 15-MAR-14:20 | 25.93 | 16.12 | 0.224078E+09 | 347.85 | 15-MAR-13:30 | 25.93 | 16.12 |
April | 0.167170E+10 | 6299.65 | 24-APR-16:00 | 13.30 | 7.63 | 0.207317E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.331786E+10 | 12452.13 | 27-MAY-17:05 | 20.32 | 11.21 | 0.250808E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.503253E+10 | 16979.07 | 11-JUN-16:41 | 25.60 | 17.82 | 0.268654E+09 | 367.47 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.541094E+10 | 16062.54 | 02-JUL-17:12 | 24.63 | 16.88 | 0.254117E+09 | 347.86 | 24-JUL-13:30 | 25.85 | 17.85 |
August | 0.509344E+10 | 13757.15 | 06-AUG-16:42 | 27.80 | 19.02 | 0.281886E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 19.02 |
September | 0.325622E+10 | 15422.88 | 04-SEP-16:42 | 18.30 | 12.93 | 0.237487E+09 | 347.86 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.148408E+10 | 6009.42 | 11-OCT-16:00 | 21.70 | 14.52 | 0.215397E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.450358E+09 | 1743.45 | 03-NOV-15:30 | 9.45 | 5.21 | 0.195985E+09 | 329.22 | 03-NOV-15:39 | 9.27 | 5.12 |
December | 55728206.83 | 1249.74 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186110E+09 | 262.29 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.268779E+11 | 0.269114E+10 | ||||||||
Minimum of Months | 48208376.01 | 1230.36 | -2.2 | -4.8 | 0.176280E+09 | 259.90 | -2.2 | -4.8 | ||
Maximum of Months | 0.541094E+10 | 16979.07 | 27.80 | 19.02 | 0.281886E+09 | 367.47 | 27.80 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16233484.78 | 1009.29 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305118E+09 | 406.69 | 02-JAN-14:30 | 3.22 | 2.72 |
February | 18148334.63 | 1010.35 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276980E+09 | 406.70 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.590032E+09 | 1630.02 | 15-MAR-15:30 | 25.30 | 16.10 | 0.344962E+09 | 532.91 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.117410E+10 | 1498.00 | 21-APR-15:40 | 13.87 | 8.65 | 0.318616E+09 | 503.48 | 07-APR-13:00 | 13.87 | 8.65 |
May | 0.210838E+10 | 2791.44 | 23-MAY-14:40 | 23.90 | 13.32 | 0.398767E+09 | 549.49 | 10-MAY-13:39 | 23.90 | 13.32 |
June | 0.361931E+10 | 4818.10 | 27-JUN-13:30 | 28.90 | 23.32 | 0.431472E+09 | 549.52 | 22-JUN-13:09 | 28.90 | 23.32 |
July | 0.456740E+10 | 5552.23 | 21-JUL-13:30 | 31.15 | 21.91 | 0.404369E+09 | 549.50 | 12-JUL-09:00 | 31.15 | 21.91 |
August | 0.453377E+10 | 5433.35 | 14-AUG-12:30 | 26.40 | 21.20 | 0.452969E+09 | 551.93 | 14-AUG-09:00 | 26.40 | 21.20 |
September | 0.294805E+10 | 4120.45 | 15-SEP-14:00 | 25.60 | 21.03 | 0.394774E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.178643E+10 | 2199.08 | 05-OCT-14:40 | 18.90 | 12.59 | 0.364439E+09 | 549.48 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.951689E+09 | 1420.58 | 16-NOV-16:40 | 17.93 | 13.54 | 0.318090E+09 | 486.46 | 01-NOV-13:39 | 17.93 | 13.54 |
December | 96764671.93 | 1212.68 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295499E+09 | 430.76 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.224103E+11 | 0.430606E+10 | ||||||||
Minimum of Months | 16233484.78 | 1009.29 | 0.82 | -0.6 | 0.276980E+09 | 406.69 | 0.82 | -0.6 | ||
Maximum of Months | 0.456740E+10 | 5552.23 | 31.15 | 23.32 | 0.452969E+09 | 551.93 | 31.15 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18328334.18 | 884.91 | 14-JAN-07:05 | 3.30 | 2.57 | 0.193570E+09 | 257.48 | 02-JAN-14:09 | 3.30 | 2.57 |
February | 86047169.38 | 980.16 | 28-FEB-09:45 | -4.5 | -6.0 | 0.176025E+09 | 276.33 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.770786E+09 | 1501.59 | 15-MAR-14:00 | 26.10 | 16.06 | 0.225365E+09 | 347.87 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.138455E+10 | 3714.80 | 24-APR-09:20 | 6.47 | 3.13 | 0.221864E+09 | 347.88 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.238161E+10 | 4983.08 | 31-MAY-09:10 | 17.88 | 13.30 | 0.264623E+09 | 347.88 | 26-MAY-09:00 | 17.88 | 13.30 |
June | 0.396248E+10 | 10660.27 | 11-JUN-10:02 | 24.50 | 16.94 | 0.274889E+09 | 347.89 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.477281E+10 | 11491.89 | 16-JUL-09:53 | 28.90 | 22.64 | 0.256753E+09 | 347.89 | 12-JUL-09:00 | 28.90 | 22.64 |
August | 0.468644E+10 | 6750.45 | 10-AUG-10:00 | 27.80 | 20.31 | 0.287419E+09 | 348.40 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.322094E+10 | 7176.61 | 04-SEP-10:02 | 17.98 | 13.30 | 0.251875E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.167170E+10 | 3564.05 | 11-OCT-09:30 | 15.85 | 11.81 | 0.242166E+09 | 347.88 | 10-OCT-09:09 | 15.85 | 11.81 |
November | 0.839225E+09 | 1346.22 | 03-NOV-08:50 | 3.72 | 1.73 | 0.204503E+09 | 344.21 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 75260717.22 | 950.66 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187119E+09 | 265.06 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.238702E+11 | 0.278617E+10 | ||||||||
Minimum of Months | 18328334.18 | 884.91 | -4.5 | -6.0 | 0.176025E+09 | 257.48 | -3.6 | -5.3 | ||
Maximum of Months | 0.477281E+10 | 11491.89 | 28.90 | 22.64 | 0.287419E+09 | 348.40 | 28.90 | 22.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81307796.99 | 1253.87 | 21-JAN-12:30 | -0.6 | -3.1 | 0.289774E+09 | 430.28 | 12-JAN-14:00 | -0.6 | -3.1 |
February | 0.104505E+09 | 1475.86 | 18-FEB-14:40 | 2.80 | 0.63 | 0.263772E+09 | 467.12 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.885113E+09 | 6198.16 | 15-MAR-13:30 | 25.55 | 15.84 | 0.349426E+09 | 549.50 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.126254E+10 | 3771.71 | 24-APR-14:00 | 12.80 | 6.89 | 0.326329E+09 | 549.51 | 21-APR-13:00 | 12.80 | 6.89 |
May | 0.227295E+10 | 5021.06 | 26-MAY-12:10 | 20.00 | 13.08 | 0.391327E+09 | 549.51 | 05-MAY-13:09 | 20.00 | 13.08 |
June | 0.413158E+10 | 11004.54 | 27-JUN-12:00 | 30.00 | 22.87 | 0.422468E+09 | 549.53 | 22-JUN-13:09 | 30.00 | 22.87 |
July | 0.598254E+10 | 11405.32 | 21-JUL-12:00 | 30.00 | 21.57 | 0.402384E+09 | 549.90 | 21-JUL-13:00 | 31.70 | 21.73 |
August | 0.656603E+10 | 13704.52 | 13-AUG-12:32 | 29.63 | 22.57 | 0.449370E+09 | 551.07 | 10-AUG-12:09 | 29.63 | 22.57 |
September | 0.490871E+10 | 13990.03 | 04-SEP-14:43 | 18.72 | 13.10 | 0.392662E+09 | 549.85 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.245881E+10 | 10050.14 | 11-OCT-12:30 | 21.95 | 13.79 | 0.372789E+09 | 549.75 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.910586E+09 | 4243.49 | 01-NOV-12:20 | 11.30 | 6.51 | 0.325058E+09 | 549.50 | 01-NOV-13:00 | 10.60 | 6.85 |
December | 0.127993E+09 | 1995.71 | 16-DEC-13:30 | 5.60 | 3.03 | 0.282776E+09 | 453.21 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.296927E+11 | 0.426813E+10 | ||||||||
Minimum of Months | 81307796.99 | 1253.87 | -0.6 | -3.1 | 0.263772E+09 | 430.28 | -0.6 | -3.1 | ||
Maximum of Months | 0.656603E+10 | 13990.03 | 30.00 | 22.87 | 0.449370E+09 | 551.07 | 31.70 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41973693.33 | 1017.07 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193580E+09 | 268.25 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 83241014.33 | 1275.83 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176321E+09 | 312.61 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.744243E+09 | 1767.03 | 15-MAR-14:20 | 25.93 | 16.12 | 0.221835E+09 | 347.82 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.131131E+10 | 3794.37 | 24-APR-17:30 | 11.70 | 7.64 | 0.209642E+09 | 347.82 | 21-APR-13:00 | 11.70 | 7.64 |
May | 0.234968E+10 | 6500.60 | 27-MAY-17:07 | 20.32 | 11.21 | 0.255149E+09 | 347.84 | 23-MAY-13:09 | 20.32 | 11.21 |
June | 0.407298E+10 | 11939.39 | 11-JUN-17:51 | 25.00 | 17.50 | 0.273494E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.457163E+10 | 11986.40 | 02-JUL-18:02 | 23.72 | 16.60 | 0.256355E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.460519E+10 | 12182.13 | 27-AUG-16:32 | 22.57 | 18.97 | 0.286997E+09 | 348.40 | 14-AUG-09:00 | 22.57 | 18.97 |
September | 0.301272E+10 | 12207.68 | 04-SEP-17:22 | 17.50 | 12.46 | 0.250196E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.168041E+10 | 4975.11 | 11-OCT-16:00 | 21.70 | 14.52 | 0.232121E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.826881E+09 | 1412.16 | 03-NOV-15:50 | 9.08 | 5.02 | 0.202432E+09 | 336.68 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 91392094.52 | 1047.47 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187119E+09 | 272.98 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.233917E+11 | 0.274524E+10 | ||||||||
Minimum of Months | 41973693.33 | 1017.07 | -6.2 | -8.3 | 0.176321E+09 | 268.25 | -6.3 | -8.3 | ||
Maximum of Months | 0.460519E+10 | 12207.68 | 25.93 | 18.97 | 0.286997E+09 | 348.40 | 25.93 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30312184.10 | 986.16 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305163E+09 | 406.68 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 58101557.97 | 988.94 | 18-FEB-17:03 | 0.82 | -0.6 | 0.277005E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.932703E+09 | 3238.00 | 15-MAR-14:40 | 25.77 | 16.18 | 0.356439E+09 | 549.49 | 15-MAR-13:00 | 25.77 | 16.18 |
April | 0.154986E+10 | 2297.82 | 21-APR-15:20 | 14.43 | 8.49 | 0.341525E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.280660E+10 | 4491.65 | 23-MAY-14:40 | 23.90 | 13.32 | 0.421070E+09 | 549.50 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.470583E+10 | 6079.22 | 12-JUN-15:00 | 30.00 | 19.98 | 0.434082E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.547807E+10 | 7621.73 | 16-JUL-13:32 | 27.93 | 21.28 | 0.405196E+09 | 549.55 | 21-JUL-13:30 | 31.15 | 21.91 |
August | 0.510826E+10 | 8120.04 | 06-AUG-16:31 | 27.80 | 18.98 | 0.453399E+09 | 549.54 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.316354E+10 | 4556.05 | 15-SEP-14:00 | 25.60 | 21.03 | 0.394586E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.170533E+10 | 2581.28 | 12-OCT-15:20 | 18.30 | 15.11 | 0.362067E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.792913E+09 | 1442.46 | 16-NOV-16:50 | 18.12 | 13.51 | 0.316372E+09 | 497.51 | 01-NOV-13:50 | 18.12 | 13.51 |
December | 95879918.58 | 1168.30 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294885E+09 | 427.53 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.264274E+11 | 0.436179E+10 | ||||||||
Minimum of Months | 30312184.10 | 986.16 | 0.82 | -0.6 | 0.277005E+09 | 406.68 | -7.0 | -8.8 | ||
Maximum of Months | 0.547807E+10 | 8120.04 | 30.00 | 21.28 | 0.453399E+09 | 549.55 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40810314.46 | 1097.61 | 18-JAN-07:04 | 2.80 | 1.63 | 0.142256E+09 | 250.68 | 02-JAN-09:50 | 2.80 | 1.63 |
February | 0.147147E+09 | 1412.25 | 28-FEB-09:50 | -4.5 | -6.0 | 0.129759E+09 | 305.75 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.110254E+10 | 2793.56 | 14-MAR-10:30 | 20.80 | 17.14 | 0.169380E+09 | 338.72 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.195090E+10 | 6038.91 | 24-APR-08:40 | 5.73 | 2.63 | 0.165436E+09 | 338.73 | 21-APR-14:09 | 5.73 | 2.63 |
May | 0.331604E+10 | 7730.71 | 31-MAY-08:40 | 17.60 | 13.16 | 0.196561E+09 | 339.18 | 08-MAY-07:49 | 17.60 | 13.16 |
June | 0.473590E+10 | 11565.78 | 11-JUN-08:13 | 22.23 | 15.06 | 0.202460E+09 | 338.85 | 30-JUN-08:00 | 20.00 | 14.70 |
July | 0.532604E+10 | 13972.58 | 09-JUL-08:22 | 20.85 | 17.57 | 0.190065E+09 | 341.09 | 17-JUL-07:19 | 23.50 | 20.94 |
August | 0.499549E+10 | 13967.73 | 06-AUG-09:12 | 24.47 | 17.45 | 0.211345E+09 | 339.22 | 15-AUG-14:39 | 24.23 | 21.18 |
September | 0.340769E+10 | 7221.00 | 04-SEP-08:53 | 16.70 | 13.10 | 0.183436E+09 | 338.74 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.174639E+10 | 4663.59 | 11-OCT-09:00 | 15.00 | 11.35 | 0.170724E+09 | 338.73 | 03-OCT-10:09 | 15.00 | 11.35 |
November | 0.708491E+09 | 1625.87 | 03-NOV-09:00 | 3.90 | 1.83 | 0.147188E+09 | 336.07 | 03-NOV-08:00 | 3.90 | 1.83 |
December | 70810673.46 | 1114.98 | 15-DEC-07:04 | 2.20 | 1.62 | 0.137376E+09 | 254.59 | 01-DEC-13:39 | 2.20 | 1.62 |
Annual Sum or Average | 0.275482E+11 | 0.204598E+10 | ||||||||
Minimum of Months | 40810314.46 | 1097.61 | -4.5 | -6.0 | 0.129759E+09 | 250.68 | -3.9 | -5.5 | ||
Maximum of Months | 0.532604E+10 | 13972.58 | 24.47 | 17.57 | 0.211345E+09 | 341.09 | 25.93 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540080E+09 | 4599.33 | 12-JAN-13:30 | -6.7 | -9.2 | 0.320959E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.696619E+09 | 6323.44 | 28-FEB-13:40 | 0.00 | -2.9 | 0.295325E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.233457E+10 | 9592.34 | 15-MAR-13:30 | 25.55 | 15.84 | 0.393180E+09 | 549.65 | 15-MAR-13:39 | 25.73 | 15.91 |
April | 0.283035E+10 | 7982.28 | 24-APR-13:10 | 11.38 | 6.04 | 0.360915E+09 | 550.09 | 05-APR-13:50 | 11.38 | 6.04 |
May | 0.426228E+10 | 7611.38 | 26-MAY-13:30 | 20.85 | 13.56 | 0.421341E+09 | 549.51 | 05-MAY-13:09 | 20.85 | 13.56 |
June | 0.583836E+10 | 9181.90 | 12-JUN-13:10 | 29.60 | 19.81 | 0.432736E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.686080E+10 | 16535.22 | 30-JUL-12:32 | 25.60 | 19.52 | 0.405057E+09 | 550.09 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.730468E+10 | 15859.57 | 06-AUG-14:32 | 27.77 | 18.96 | 0.453430E+09 | 550.07 | 03-AUG-13:00 | 27.77 | 18.96 |
September | 0.594015E+10 | 16097.58 | 04-SEP-12:53 | 19.40 | 13.13 | 0.396931E+09 | 550.30 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.358718E+10 | 12070.12 | 11-OCT-12:30 | 21.95 | 13.79 | 0.387762E+09 | 549.89 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.166157E+10 | 8398.06 | 03-NOV-12:25 | 8.35 | 4.56 | 0.340976E+09 | 549.50 | 01-NOV-13:00 | 8.35 | 4.56 |
December | 0.473267E+09 | 4359.48 | 16-DEC-13:30 | 5.60 | 3.03 | 0.302941E+09 | 549.48 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.423299E+11 | 0.451155E+10 | ||||||||
Minimum of Months | 0.473267E+09 | 4359.48 | -6.7 | -9.2 | 0.295325E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.730468E+10 | 16535.22 | 29.60 | 19.81 | 0.453430E+09 | 550.30 | 27.77 | 19.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80696802.59 | 1253.06 | 12-JAN-16:00 | -6.1 | -8.3 | 0.193571E+09 | 275.51 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.161708E+09 | 1812.06 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176960E+09 | 338.65 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.111240E+10 | 3400.44 | 15-MAR-14:20 | 25.93 | 16.12 | 0.228329E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.188643E+10 | 6246.25 | 24-APR-16:00 | 13.30 | 7.63 | 0.214043E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.332368E+10 | 11608.63 | 27-MAY-17:05 | 20.32 | 11.21 | 0.259377E+09 | 347.85 | 05-MAY-13:09 | 20.32 | 11.21 |
June | 0.490379E+10 | 14041.71 | 11-JUN-16:52 | 25.60 | 17.82 | 0.272284E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.521434E+10 | 14881.79 | 30-JUL-17:12 | 24.40 | 19.95 | 0.255729E+09 | 347.86 | 03-JUL-13:39 | 24.40 | 19.95 |
August | 0.499007E+10 | 15174.22 | 06-AUG-16:31 | 27.80 | 18.98 | 0.285316E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.329319E+10 | 11005.85 | 10-SEP-17:12 | 16.10 | 10.54 | 0.245379E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.180837E+10 | 5949.03 | 11-OCT-16:00 | 21.70 | 14.52 | 0.224654E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.761690E+09 | 1918.99 | 03-NOV-14:50 | 9.90 | 5.39 | 0.199913E+09 | 343.03 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 0.110475E+09 | 1252.02 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186741E+09 | 274.98 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.276468E+11 | 0.274230E+10 | ||||||||
Minimum of Months | 80696802.59 | 1252.02 | -6.1 | -8.3 | 0.176960E+09 | 274.98 | -6.2 | -8.3 | ||
Maximum of Months | 0.521434E+10 | 15174.22 | 27.80 | 19.95 | 0.285316E+09 | 347.88 | 27.80 | 19.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319374E+09 | 23286.71 | 02-JAN-05:01 | -0.7 |
February | 16009975.28 | 19969.30 | 08-FEB-07:01 | -10.0 |
March | 367273.21 | 6121.22 | 06-MAR-07:01 | -10.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 7057763.22 | 17524.59 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.342809E+09 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.319374E+09 | 23286.71 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766322E+10 | 15756.73 | 24-JAN-06:12 | -12.0 |
February | 0.670078E+10 | 16745.04 | 06-FEB-06:13 | -13.9 |
March | 0.322640E+10 | 15688.54 | 06-MAR-06:13 | -11.1 |
April | 0.125353E+10 | 11863.90 | 17-APR-05:13 | -4.1 |
May | 0.421251E+09 | 4210.58 | 08-MAY-05:03 | 3.40 |
June | 0.146372E+09 | 3890.25 | 14-JUN-05:03 | 6.78 |
July | 77380145.50 | 3439.23 | 04-JUL-06:27 | 16.95 |
August | 0.119236E+09 | 3230.56 | 03-AUG-05:03 | 11.10 |
September | 0.329115E+09 | 4292.97 | 04-SEP-08:62 | 13.45 |
October | 0.113913E+10 | 9530.63 | 30-OCT-06:02 | -0.4 |
November | 0.252864E+10 | 11671.23 | 24-NOV-06:13 | -3.7 |
December | 0.698516E+10 | 17353.03 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.305902E+11 | |||
Minimum of Months | 77380145.50 | 3230.56 | -18.2 | |
Maximum of Months | 0.766322E+10 | 17353.03 | 16.95 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361445E+10 | 10405.46 | 02-JAN-07:02 | -1.1 |
February | 0.313027E+10 | 9354.36 | 06-FEB-07:03 | -14.1 |
March | 0.160066E+10 | 6934.18 | 06-MAR-07:11 | -10.5 |
April | 0.703282E+09 | 3875.36 | 17-APR-06:03 | -4.2 |
May | 0.111361E+09 | 2981.92 | 14-MAY-11:43 | 21.83 |
June | 18720188.17 | 2856.13 | 11-JUN-14:53 | 26.10 |
July | 22416682.50 | 2564.15 | 04-JUL-08:42 | 21.10 |
August | 16564581.58 | 3651.55 | 13-AUG-15:12 | 29.80 |
September | 34679169.60 | 4007.26 | 04-SEP-14:53 | 18.90 |
October | 0.655579E+09 | 3910.64 | 09-OCT-12:13 | 11.87 |
November | 0.125442E+10 | 4075.10 | 24-NOV-07:02 | -3.2 |
December | 0.310582E+10 | 9626.48 | 26-DEC-07:03 | -12.3 |
Annual Sum or Average | 0.142682E+11 | |||
Minimum of Months | 16564581.58 | 2564.15 | -14.1 | |
Maximum of Months | 0.361445E+10 | 10405.46 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285935E+10 | 9591.70 | 02-JAN-07:01 | -1.1 |
February | 0.238427E+10 | 5600.38 | 06-FEB-07:01 | -14.1 |
March | 0.117558E+10 | 4435.67 | 06-MAR-08:15 | -9.0 |
April | 0.393068E+09 | 3416.95 | 05-APR-07:09 | 1.97 |
May | 21605764.22 | 2303.93 | 01-MAY-07:06 | 6.05 |
June | 14844107.51 | 1938.13 | 04-JUN-14:33 | 20.20 |
July | 17856746.23 | 2985.04 | 20-JUL-04:03 | 24.82 |
August | 15806526.64 | 2204.43 | 13-AUG-15:12 | 29.80 |
September | 20508706.67 | 2994.38 | 04-SEP-16:02 | 18.30 |
October | 0.288311E+09 | 3783.93 | 17-OCT-07:05 | -2.4 |
November | 0.929947E+09 | 3381.81 | 07-NOV-08:06 | 2.20 |
December | 0.235076E+10 | 5752.01 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.104719E+11 | |||
Minimum of Months | 14844107.51 | 1938.13 | -14.1 | |
Maximum of Months | 0.285935E+10 | 9591.70 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112144E+10 | 24496.35 | 02-JAN-05:01 | -0.7 |
February | 0.758731E+09 | 22332.04 | 06-FEB-05:01 | -14.8 |
March | 0.102718E+09 | 20989.25 | 06-MAR-06:01 | -11.1 |
April | 13077498.94 | 19125.64 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 1849947.73 | 18499.48 | 30-OCT-06:02 | -0.4 |
November | 29172910.80 | 19575.27 | 24-NOV-06:01 | -3.8 |
December | 0.576532E+09 | 22595.37 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.260352E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.112144E+10 | 24496.35 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375325E+10 | 33088.53 | 09-JAN-05:11 | -9.4 |
February | 0.314722E+10 | 33250.38 | 06-FEB-05:01 | -14.8 |
March | 0.946461E+09 | 32157.66 | 06-MAR-05:11 | -11.1 |
April | 0.170517E+09 | 30012.39 | 17-APR-05:01 | -4.0 |
May | 298769.42 | 1991.80 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.118740E+09 | 29542.91 | 30-OCT-05:01 | -0.1 |
November | 0.488365E+09 | 30633.92 | 24-NOV-05:01 | -3.0 |
December | 0.294884E+10 | 33330.35 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.115737E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.375325E+10 | 33330.35 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650556E+10 | 11027.02 | 09-JAN-01:52 | -8.3 |
February | 0.566162E+10 | 11400.77 | 13-FEB-05:11 | -9.1 |
March | 0.234415E+10 | 10748.99 | 06-MAR-04:33 | -11.1 |
April | 0.468916E+09 | 10228.97 | 17-APR-04:01 | -3.4 |
May | 8943814.70 | 8160.59 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 5422434.12 | 8150.06 | 30-SEP-06:03 | 7.30 |
October | 0.350873E+09 | 10035.97 | 30-OCT-04:01 | -0.5 |
November | 0.134703E+10 | 10286.71 | 24-NOV-05:01 | -3.0 |
December | 0.574671E+10 | 11266.94 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.224392E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.650556E+10 | 11400.77 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382228E+10 | 12423.95 | 09-JAN-01:52 | -8.3 |
February | 0.331212E+10 | 13036.60 | 13-FEB-05:11 | -9.1 |
March | 0.109083E+10 | 12143.51 | 06-MAR-05:11 | -11.1 |
April | 0.197477E+09 | 11620.00 | 17-APR-04:01 | -3.4 |
May | 3669217.09 | 5185.42 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 3431110.04 | 5657.74 | 30-SEP-06:03 | 7.30 |
October | 0.187728E+09 | 11432.98 | 30-OCT-04:01 | -0.5 |
November | 0.782348E+09 | 11703.24 | 24-NOV-05:01 | -3.0 |
December | 0.360036E+10 | 12770.68 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.130002E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.382228E+10 | 13036.60 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477248E+10 | 15513.49 | 09-JAN-01:52 | -8.3 |
February | 0.429433E+10 | 16267.86 | 13-FEB-05:11 | -9.1 |
March | 0.139966E+10 | 15079.46 | 06-MAR-05:11 | -11.1 |
April | 0.387533E+09 | 14497.19 | 17-APR-04:01 | -3.4 |
May | 15136315.93 | 8994.44 | 01-MAY-06:03 | 2.35 |
June | 68308.30 | 227.69 | 14-JUN-06:05 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4283960.57 | 8579.32 | 30-SEP-06:03 | 7.30 |
October | 0.238763E+09 | 14121.42 | 30-OCT-04:01 | -0.5 |
November | 0.100120E+10 | 14628.89 | 24-NOV-05:01 | -3.0 |
December | 0.442790E+10 | 15982.11 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.165413E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.477248E+10 | 16267.86 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412115E+10 | 13523.68 | 09-JAN-01:52 | -8.3 |
February | 0.356315E+10 | 14212.79 | 13-FEB-05:11 | -9.1 |
March | 0.127283E+10 | 13203.20 | 06-MAR-05:11 | -11.1 |
April | 0.285374E+09 | 12572.61 | 17-APR-04:01 | -3.4 |
May | 10126263.48 | 5624.87 | 01-MAY-06:03 | 2.35 |
June | 156704.42 | 522.35 | 14-JUN-06:05 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4407072.29 | 5549.62 | 30-SEP-06:03 | 7.30 |
October | 0.219632E+09 | 12329.37 | 30-OCT-04:01 | -0.5 |
November | 0.860536E+09 | 12719.72 | 24-NOV-05:01 | -3.0 |
December | 0.366857E+10 | 13899.64 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.140059E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.412115E+10 | 14212.79 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423594E+10 | 8339.29 | 02-JAN-02:62 | -1.7 |
February | 0.355432E+10 | 8454.83 | 13-FEB-05:11 | -9.1 |
March | 0.154159E+10 | 8160.84 | 06-MAR-05:01 | -11.1 |
April | 0.223679E+09 | 7310.47 | 17-APR-05:01 | -4.0 |
May | 2670636.32 | 6451.10 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 22404526.79 | 6808.64 | 30-OCT-05:01 | -0.1 |
November | 0.238409E+09 | 7230.89 | 24-NOV-06:01 | -3.8 |
December | 0.281300E+10 | 8206.74 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.126320E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.423594E+10 | 8454.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240429E+10 | 9709.70 | 09-JAN-05:11 | -9.4 |
February | 0.192810E+10 | 10070.18 | 13-FEB-05:11 | -9.1 |
March | 0.525146E+09 | 9544.28 | 06-MAR-05:01 | -11.1 |
April | 58240910.48 | 8618.32 | 17-APR-05:01 | -4.0 |
May | 425191.60 | 1808.58 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 12079761.08 | 7769.93 | 17-OCT-06:01 | -2.8 |
November | 0.135696E+09 | 8599.14 | 24-NOV-06:01 | -3.8 |
December | 0.171216E+10 | 9701.38 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.677614E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.240429E+10 | 10070.18 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709071E+10 | 13885.69 | 04-JAN-08:00 | -13.3 |
February | 0.613566E+10 | 14395.19 | 07-FEB-08:00 | -15.6 |
March | 0.321573E+10 | 13356.50 | 07-MAR-07:10 | -12.9 |
April | 0.168586E+10 | 12021.41 | 17-APR-06:50 | -3.5 |
May | 0.593370E+09 | 10513.65 | 01-MAY-06:10 | 2.35 |
June | 0.116979E+09 | 8650.26 | 06-JUN-06:10 | 7.67 |
July | 3723995.42 | 2701.96 | 06-JUL-06:08 | 13.07 |
August | 18230661.64 | 4471.08 | 01-AUG-06:07 | 11.57 |
September | 0.149968E+09 | 9472.40 | 06-SEP-06:05 | 6.28 |
October | 0.898055E+09 | 11233.54 | 17-OCT-06:10 | -2.8 |
November | 0.222555E+10 | 11795.99 | 24-NOV-07:10 | -3.2 |
December | 0.589339E+10 | 14139.62 | 11-DEC-08:00 | -15.0 |
Annual Sum or Average | 0.280272E+11 | |||
Minimum of Months | 3723995.42 | 2701.96 | -15.6 | |
Maximum of Months | 0.709071E+10 | 14395.19 | 13.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265430E+10 | 10163.48 | 09-JAN-05:11 | -9.4 |
February | 0.213206E+10 | 10529.97 | 13-FEB-05:11 | -9.1 |
March | 0.597635E+09 | 9956.61 | 06-MAR-05:01 | -11.1 |
April | 86351631.29 | 8967.65 | 17-APR-05:01 | -4.0 |
May | 1369129.19 | 3923.93 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 12901295.42 | 8096.04 | 17-OCT-06:01 | -2.8 |
November | 0.145785E+09 | 8886.51 | 24-NOV-06:01 | -3.8 |
December | 0.176073E+10 | 10102.96 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.739113E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.265430E+10 | 10529.97 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401810E+10 | 9333.95 | 29-JAN-22:42 | -9.0 |
February | 0.336807E+10 | 9553.25 | 05-FEB-22:22 | -12.8 |
March | 0.108549E+10 | 9104.49 | 06-MAR-05:01 | -11.1 |
April | 0.130355E+09 | 8410.14 | 17-APR-04:01 | -3.4 |
May | 127298.08 | 848.65 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 70298583.72 | 8070.76 | 30-OCT-05:01 | -0.1 |
November | 0.431071E+09 | 8471.87 | 24-NOV-05:01 | -3.0 |
December | 0.327198E+10 | 9377.34 | 11-DEC-04:42 | -17.2 |
Annual Sum or Average | 0.123755E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.401810E+10 | 9553.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236440E+10 | 10770.28 | 29-JAN-22:42 | -9.0 |
February | 0.196409E+10 | 11197.27 | 05-FEB-22:22 | -12.8 |
March | 0.463247E+09 | 10623.71 | 06-MAR-05:01 | -11.1 |
April | 53865848.91 | 9350.78 | 17-APR-05:01 | -4.0 |
May | 149212.83 | 994.75 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 377840.05 | 2407.59 | 30-SEP-06:03 | 7.30 |
October | 44339470.43 | 9352.87 | 30-OCT-05:01 | -0.1 |
November | 0.269379E+09 | 9906.37 | 24-NOV-05:01 | -3.0 |
December | 0.208218E+10 | 10974.21 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.724203E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.236440E+10 | 11197.27 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274793E+10 | 13664.06 | 30-JAN-04:42 | -9.5 |
February | 0.236214E+10 | 13958.47 | 05-FEB-22:22 | -12.8 |
March | 0.524061E+09 | 13313.77 | 06-MAR-05:01 | -11.1 |
April | 0.104649E+09 | 11970.08 | 17-APR-05:01 | -4.0 |
May | 661927.90 | 4412.85 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 48024726.49 | 11807.90 | 30-OCT-05:01 | -0.1 |
November | 0.307742E+09 | 12475.57 | 24-NOV-05:01 | -3.0 |
December | 0.229422E+10 | 13838.10 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.838943E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.274793E+10 | 13958.47 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253322E+10 | 10970.87 | 29-JAN-22:42 | -9.0 |
February | 0.208536E+10 | 11329.35 | 05-FEB-22:22 | -12.8 |
March | 0.541886E+09 | 10694.82 | 06-MAR-05:01 | -11.1 |
April | 79537352.81 | 9386.13 | 17-APR-05:01 | -4.0 |
May | 670987.84 | 3035.08 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 242966.84 | 1619.78 | 30-SEP-06:03 | 7.30 |
October | 47889872.57 | 9313.75 | 30-OCT-05:01 | -0.1 |
November | 0.287286E+09 | 9937.94 | 24-NOV-05:01 | -3.0 |
December | 0.207032E+10 | 11091.80 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.764642E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.253322E+10 | 11329.35 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838871E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.702291E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.775995E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.660517E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.694200E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.679334E+09 | 711.15 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638323E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.724654E+09 | 774.31 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.680801E+09 | 947.97 | 14-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.755649E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841564E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.843643E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883584E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638323E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.843643E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515874E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.439151E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487360E+09 | 600.14 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418354E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442742E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433737E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407032E+09 | 450.21 | 11-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461307E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428862E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468762E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.518058E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515679E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553692E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407032E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.518058E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790656E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.682144E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764945E+09 | 1011.14 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.661965E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.700517E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.685468E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.644308E+09 | 774.31 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.728907E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676824E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.732804E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.797400E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.794634E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866057E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.644308E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.797400E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513904E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437043E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488336E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419395E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440951E+09 | 490.17 | 10-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431460E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405988E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460047E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430711E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.473677E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516635E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.517000E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553515E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405988E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.517000E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.833996E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.699502E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773634E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.659386E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.693316E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.678838E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.637855E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.723545E+09 | 711.15 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.678831E+09 | 947.97 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.752389E+09 | 1358.45 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.837027E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.838649E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.880697E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.637855E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.838649E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513619E+09 | 860.01 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437731E+09 | 860.01 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.486368E+09 | 600.14 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.417853E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442073E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433292E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.406666E+09 | 450.21 | 17-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460826E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428024E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467774E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516103E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.514168E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552450E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.406666E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.516103E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788494E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.680470E+09 | 1184.79 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763857E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.660924E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.699030E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.684654E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.643297E+09 | 711.15 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.727559E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.675263E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.731188E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.794840E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.791833E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.864141E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.643297E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.794840E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.511425E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.435830E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487068E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418538E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440165E+09 | 490.17 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.430945E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405451E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.459138E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.429897E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.472617E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.514477E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515447E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552100E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405451E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.515447E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838729E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.702291E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.775995E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.660517E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.694200E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.679334E+09 | 711.15 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638323E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.724654E+09 | 774.31 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.680801E+09 | 947.97 | 14-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.755590E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841526E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.843539E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883550E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638323E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.843539E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515808E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.439151E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487360E+09 | 600.14 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418353E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442742E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433737E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407032E+09 | 450.21 | 11-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461293E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428862E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468762E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.518058E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515679E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553684E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407032E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.518058E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790656E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.682144E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764945E+09 | 1011.14 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.661952E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.700517E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.685468E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.644295E+09 | 774.31 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.728907E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676824E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.732804E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.797400E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.794634E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866055E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.644295E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.797400E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513904E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437043E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488336E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419395E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440951E+09 | 490.17 | 10-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431460E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405988E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460047E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430711E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.473677E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516635E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.516976E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553512E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405988E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.516976E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838871E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187910E+10 |
February | 0.901968E+09 | 0.702291E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200160E+10 |
March | 0.107774E+10 | 0.775995E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471518.85 | 0.122067E+10 |
April | 0.956342E+09 | 0.660517E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983457E+09 |
May | 0.103597E+10 | 0.694200E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 475388.72 | 0.606799E+09 |
June | 0.103308E+10 | 0.679334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11248886.99 | 0.357581E+09 |
July | 0.959235E+09 | 0.638323E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26799010.88 | 0.212716E+09 |
August | 0.107774E+10 | 0.724654E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21959892.32 | 0.243426E+09 |
September | 0.956342E+09 | 0.680801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1577951.40 | 0.353271E+09 |
October | 0.994195E+09 | 0.755649E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744409E+09 |
November | 0.984487E+09 | 0.841564E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999246E+09 |
December | 0.959235E+09 | 0.843643E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198076E+10 |
Annual Sum or Average | 0.119305E+11 | 0.883584E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62532649.15 | 0.115830E+11 |
Minimum of Months | 0.901968E+09 | 0.638323E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212716E+09 |
Maximum of Months | 0.107774E+10 | 0.843643E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26799010.88 | 0.200160E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.515874E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125430E+10 |
February | 0.571020E+09 | 0.439151E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133696E+10 |
March | 0.682301E+09 | 0.487360E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 294781.91 | 0.820387E+09 |
April | 0.605444E+09 | 0.418354E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667780E+09 |
May | 0.655854E+09 | 0.442742E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368191.57 | 0.417148E+09 |
June | 0.654023E+09 | 0.433737E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7474741.67 | 0.242184E+09 |
July | 0.607275E+09 | 0.407032E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17700704.56 | 0.143824E+09 |
August | 0.682301E+09 | 0.461307E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14425700.18 | 0.165071E+09 |
September | 0.605444E+09 | 0.428862E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111785.43 | 0.240084E+09 |
October | 0.629407E+09 | 0.468762E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507957E+09 |
November | 0.623262E+09 | 0.518058E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670248E+09 |
December | 0.607275E+09 | 0.515679E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132208E+10 |
Annual Sum or Average | 0.755301E+10 | 0.553692E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41375905.32 | 0.778803E+10 |
Minimum of Months | 0.571020E+09 | 0.407032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143824E+09 |
Maximum of Months | 0.682301E+09 | 0.518058E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17700704.56 | 0.133696E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790656E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191236E+10 |
February | 0.901968E+09 | 0.682144E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202497E+10 |
March | 0.107774E+10 | 0.764945E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 437534.27 | 0.128121E+10 |
April | 0.956342E+09 | 0.661965E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102156E+10 |
May | 0.103597E+10 | 0.700517E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201887.74 | 0.625826E+09 |
June | 0.103308E+10 | 0.685468E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10870358.29 | 0.359363E+09 |
July | 0.959235E+09 | 0.644308E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26206850.33 | 0.216973E+09 |
August | 0.107774E+10 | 0.728907E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20089413.87 | 0.253427E+09 |
September | 0.956342E+09 | 0.676824E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432976.45 | 0.376072E+09 |
October | 0.994195E+09 | 0.732804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801695E+09 |
November | 0.984487E+09 | 0.797400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104009E+10 |
December | 0.959235E+09 | 0.794634E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201549E+10 |
Annual Sum or Average | 0.119305E+11 | 0.866057E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59239020.95 | 0.119290E+11 |
Minimum of Months | 0.901968E+09 | 0.644308E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216973E+09 |
Maximum of Months | 0.107774E+10 | 0.797400E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26206850.33 | 0.202497E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.513904E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125452E+10 |
February | 0.570983E+09 | 0.437043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133885E+10 |
March | 0.682256E+09 | 0.488336E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397666.45 | 0.833698E+09 |
April | 0.605404E+09 | 0.419395E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675376E+09 |
May | 0.655811E+09 | 0.440951E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134606.84 | 0.420571E+09 |
June | 0.653980E+09 | 0.431460E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7897679.23 | 0.247520E+09 |
July | 0.607235E+09 | 0.405988E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18084373.35 | 0.149397E+09 |
August | 0.682256E+09 | 0.460047E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14883000.26 | 0.170929E+09 |
September | 0.605404E+09 | 0.430711E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 945351.41 | 0.241260E+09 |
October | 0.629366E+09 | 0.473677E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502989E+09 |
November | 0.623221E+09 | 0.516635E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667129E+09 |
December | 0.607235E+09 | 0.517000E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132123E+10 |
Annual Sum or Average | 0.755252E+10 | 0.553515E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42342677.55 | 0.782348E+10 |
Minimum of Months | 0.570983E+09 | 0.405988E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149397E+09 |
Maximum of Months | 0.682256E+09 | 0.517000E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18084373.35 | 0.133885E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.833996E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104090E+10 |
February | 0.901968E+09 | 0.699502E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110206E+10 |
March | 0.107774E+10 | 0.773634E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 534944.96 | 0.674103E+09 |
April | 0.956342E+09 | 0.659386E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535578E+09 |
May | 0.103597E+10 | 0.693316E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 492905.57 | 0.311921E+09 |
June | 0.103308E+10 | 0.678838E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8443451.74 | 0.186178E+09 |
July | 0.959235E+09 | 0.637855E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16714938.06 | 0.107338E+09 |
August | 0.107774E+10 | 0.723545E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14060855.01 | 0.130739E+09 |
September | 0.956342E+09 | 0.678831E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 931726.72 | 0.200944E+09 |
October | 0.994195E+09 | 0.752389E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447057E+09 |
November | 0.984487E+09 | 0.837027E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594359E+09 |
December | 0.959235E+09 | 0.838649E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112221E+10 |
Annual Sum or Average | 0.119305E+11 | 0.880697E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41178822.06 | 0.645339E+10 |
Minimum of Months | 0.901968E+09 | 0.637855E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107338E+09 |
Maximum of Months | 0.107774E+10 | 0.838649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16714938.06 | 0.112221E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.513619E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696973E+09 |
February | 0.571020E+09 | 0.437731E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737076E+09 |
March | 0.682301E+09 | 0.486368E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235264.58 | 0.457206E+09 |
April | 0.605444E+09 | 0.417853E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373582E+09 |
May | 0.655854E+09 | 0.442073E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 195164.93 | 0.225921E+09 |
June | 0.654023E+09 | 0.433292E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4314592.75 | 0.132243E+09 |
July | 0.607275E+09 | 0.406666E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9978071.78 | 77837908.91 |
August | 0.682301E+09 | 0.460826E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8137838.73 | 93351070.05 |
September | 0.605444E+09 | 0.428024E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 608316.67 | 0.140673E+09 |
October | 0.629407E+09 | 0.467774E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309663E+09 |
November | 0.623262E+09 | 0.516103E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400918E+09 |
December | 0.607275E+09 | 0.514168E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749118E+09 |
Annual Sum or Average | 0.755301E+10 | 0.552450E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23469249.44 | 0.439456E+10 |
Minimum of Months | 0.571020E+09 | 0.406666E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77837908.91 |
Maximum of Months | 0.682301E+09 | 0.516103E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9978071.78 | 0.749118E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.788494E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727723E+10 |
February | 0.901968E+09 | 0.680470E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676311E+10 |
March | 0.107774E+10 | 0.763857E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7787542.37 | 0.561692E+10 |
April | 0.956342E+09 | 0.660924E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383545E+10 |
May | 0.103597E+10 | 0.699030E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2390688.16 | 0.242357E+10 |
June | 0.103308E+10 | 0.684654E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129401E+09 | 0.129329E+10 |
July | 0.959235E+09 | 0.643297E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359384E+09 | 0.539670E+09 |
August | 0.107774E+10 | 0.727559E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278649E+09 | 0.919193E+09 |
September | 0.956342E+09 | 0.675263E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13768146.46 | 0.158225E+10 |
October | 0.994195E+09 | 0.731188E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347441E+10 |
November | 0.984487E+09 | 0.794840E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454722E+10 |
December | 0.959235E+09 | 0.791833E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674571E+10 |
Annual Sum or Average | 0.119305E+11 | 0.864141E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791381E+09 | 0.450180E+11 |
Minimum of Months | 0.901968E+09 | 0.643297E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539670E+09 |
Maximum of Months | 0.107774E+10 | 0.794840E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359384E+09 | 0.727723E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.511425E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694794E+09 |
February | 0.570983E+09 | 0.435830E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737554E+09 |
March | 0.682256E+09 | 0.487068E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 330822.17 | 0.463705E+09 |
April | 0.605404E+09 | 0.418538E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374277E+09 |
May | 0.655811E+09 | 0.440165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84961.12 | 0.229142E+09 |
June | 0.653980E+09 | 0.430945E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4243640.17 | 0.137578E+09 |
July | 0.607235E+09 | 0.405451E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10203161.00 | 82569654.89 |
August | 0.682256E+09 | 0.459138E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8029255.88 | 97584364.25 |
September | 0.605404E+09 | 0.429897E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 507347.15 | 0.142199E+09 |
October | 0.629366E+09 | 0.472617E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305243E+09 |
November | 0.623221E+09 | 0.514477E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398735E+09 |
December | 0.607235E+09 | 0.515447E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748442E+09 |
Annual Sum or Average | 0.755252E+10 | 0.552100E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23399187.50 | 0.441182E+10 |
Minimum of Months | 0.570983E+09 | 0.405451E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82569654.89 |
Maximum of Months | 0.682256E+09 | 0.515447E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10203161.00 | 0.748442E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838729E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160782E+10 |
February | 0.901968E+09 | 0.702291E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170853E+10 |
March | 0.107774E+10 | 0.775995E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407783.52 | 0.106770E+10 |
April | 0.956342E+09 | 0.660517E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869123E+09 |
May | 0.103597E+10 | 0.694200E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570392.38 | 0.529592E+09 |
June | 0.103308E+10 | 0.679334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10409237.25 | 0.307279E+09 |
July | 0.959235E+09 | 0.638323E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23231665.90 | 0.180920E+09 |
August | 0.107774E+10 | 0.724654E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19120015.92 | 0.210511E+09 |
September | 0.956342E+09 | 0.680801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1365265.42 | 0.313472E+09 |
October | 0.994195E+09 | 0.755590E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677289E+09 |
November | 0.984487E+09 | 0.841526E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900746E+09 |
December | 0.959235E+09 | 0.843539E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171204E+10 |
Annual Sum or Average | 0.119305E+11 | 0.883550E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55104360.38 | 0.100850E+11 |
Minimum of Months | 0.901968E+09 | 0.638323E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180920E+09 |
Maximum of Months | 0.107774E+10 | 0.843539E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23231665.90 | 0.171204E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.515808E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107392E+10 |
February | 0.421807E+09 | 0.439151E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114037E+10 |
March | 0.502994E+09 | 0.487360E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261290.20 | 0.718084E+09 |
April | 0.447140E+09 | 0.418353E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587193E+09 |
May | 0.484071E+09 | 0.442742E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 422084.38 | 0.361884E+09 |
June | 0.482240E+09 | 0.433737E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6737720.01 | 0.207505E+09 |
July | 0.448971E+09 | 0.407032E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15257119.71 | 0.122027E+09 |
August | 0.502994E+09 | 0.461293E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12584600.51 | 0.142296E+09 |
September | 0.447140E+09 | 0.428862E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 965088.29 | 0.211315E+09 |
October | 0.465148E+09 | 0.468762E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458811E+09 |
November | 0.460569E+09 | 0.518058E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602092E+09 |
December | 0.448971E+09 | 0.515679E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114135E+10 |
Annual Sum or Average | 0.557719E+10 | 0.553684E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36227903.11 | 0.676684E+10 |
Minimum of Months | 0.421807E+09 | 0.407032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122027E+09 |
Maximum of Months | 0.502994E+09 | 0.518058E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15257119.71 | 0.114135E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790656E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164765E+10 |
February | 0.901968E+09 | 0.682144E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173582E+10 |
March | 0.107774E+10 | 0.764945E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374513.80 | 0.112394E+10 |
April | 0.956342E+09 | 0.661952E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900748E+09 |
May | 0.103597E+10 | 0.700517E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171673.47 | 0.545952E+09 |
June | 0.103308E+10 | 0.685468E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9284112.13 | 0.310403E+09 |
July | 0.959235E+09 | 0.644295E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22275751.91 | 0.185904E+09 |
August | 0.107774E+10 | 0.728907E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17009798.52 | 0.219542E+09 |
September | 0.956342E+09 | 0.676824E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1221346.47 | 0.331708E+09 |
October | 0.994195E+09 | 0.732804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723712E+09 |
November | 0.984487E+09 | 0.797400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936186E+09 |
December | 0.959235E+09 | 0.794634E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175107E+10 |
Annual Sum or Average | 0.119305E+11 | 0.866055E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50337196.31 | 0.104126E+11 |
Minimum of Months | 0.901968E+09 | 0.644295E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185904E+09 |
Maximum of Months | 0.107774E+10 | 0.797400E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22275751.91 | 0.175107E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.513904E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107245E+10 |
February | 0.570983E+09 | 0.437043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114132E+10 |
March | 0.682256E+09 | 0.488336E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 325074.62 | 0.729624E+09 |
April | 0.605404E+09 | 0.419395E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594743E+09 |
May | 0.655811E+09 | 0.440951E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114462.09 | 0.367027E+09 |
June | 0.653980E+09 | 0.431460E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810260.94 | 0.214113E+09 |
July | 0.607235E+09 | 0.405988E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15419931.08 | 0.128468E+09 |
August | 0.682256E+09 | 0.460047E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12471567.20 | 0.148286E+09 |
September | 0.605404E+09 | 0.430711E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 779932.40 | 0.214142E+09 |
October | 0.629366E+09 | 0.473677E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455572E+09 |
November | 0.623221E+09 | 0.516635E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599849E+09 |
December | 0.607235E+09 | 0.516976E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114082E+10 |
Annual Sum or Average | 0.755252E+10 | 0.553512E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35921228.33 | 0.680641E+10 |
Minimum of Months | 0.570983E+09 | 0.405988E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128468E+09 |
Maximum of Months | 0.682256E+09 | 0.516976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15419931.08 | 0.114132E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222062E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234680E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585180.30 | 0.150043E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122152E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540077.74 | 0.723426E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10047741.56 | 0.419135E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24574611.22 | 0.243398E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20671135.28 | 0.290724E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064304.53 | 0.444650E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979640E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130078E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239585E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57483050.63 | 0.140870E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243398E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24574611.22 | 0.239585E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273611E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289086E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871646.49 | 0.185008E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151196E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936554.71 | 0.911828E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13435102.18 | 0.533002E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31250498.01 | 0.310610E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27065990.44 | 0.367043E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1465212.36 | 0.549707E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117277E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154997E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292062E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75025004.19 | 0.173046E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310610E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31250498.01 | 0.292062E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280074E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298089E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38030.40 | 0.188428E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154589E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28967.17 | 0.971247E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7666064.87 | 0.574071E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23279849.63 | 0.341543E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16858964.32 | 0.385762E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735894.08 | 0.566239E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116507E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152488E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296179E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48607770.48 | 0.177024E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341543E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23279849.63 | 0.298089E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.33 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3614.84 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2009.69 | 01-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1819.38 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 | 14-MAY-14:43 | 1159.90 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 | 17-JUN-17:03 | 1031.84 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 741.34 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.86 | 13-AUG-13:00 | 485.05 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 14-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.61 | 16-SEP-17:03 | 812.54 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 978.93 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1770.14 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3368.23 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.05 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 367.86 | 3614.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.91 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1340.44 | 01-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1211.83 | 04-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.40 | 14-MAY-15:10 | 846.34 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.73 | 17-JUN-17:20 | 689.84 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 11-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 491.12 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.42 | 13-AUG-12:40 | 313.47 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 16-SEP-17:03 | 533.85 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 684.05 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1169.49 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2231.65 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.47 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 246.42 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.40 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3754.71 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1011.14 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2139.78 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1819.09 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 10-MAY-14:00 | 1267.08 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.83 | 17-JUN-17:03 | 1039.83 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 744.10 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.98 | 13-AUG-12:38 | 481.98 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 815.36 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1029.73 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1793.35 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3387.96 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.98 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 340.98 | 3754.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.92 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1463.96 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1211.34 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 10-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 903.51 | 29-MAY-15:20 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.42 | 17-JUN-17:50 | 693.88 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.74 | 16-JUL-10:20 | 500.49 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.54 | 13-AUG-13:00 | 384.74 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 531.61 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 652.83 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1165.70 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2233.38 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.74 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 273.54 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.55 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.56 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 14-MAR-14:00 | 1110.27 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1066.22 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.86 | 14-MAY-14:53 | 567.00 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.45 | 17-JUN-17:03 | 568.35 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.92 | 21-JUL-03:00 | 414.31 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.44 | 13-AUG-13:00 | 270.92 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 | 16-SEP-17:03 | 505.58 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 637.39 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1081.30 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1880.84 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.92 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 240.44 | 1992.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.73 | 12-JAN-05:55 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1329.55 | 13-FEB-05:54 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 762.07 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 715.13 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.46 | 14-MAY-14:43 | 427.04 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 | 17-JUN-17:03 | 394.72 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 17-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 | 21-JUL-03:00 | 284.84 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.31 | 13-AUG-13:00 | 179.29 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 16-SEP-17:20 | 334.74 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 441.03 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 724.79 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1248.89 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.29 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 139.31 | 1329.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29210.44 | 04-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32394.14 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 800.33 | 15-MAR-12:00 | 29859.03 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20973.89 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.05 | 10-MAY-16:10 | 14787.08 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4721.30 | 27-JUN-12:00 | 11356.71 | 14-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4518.87 | 21-JUL-12:00 | 7998.56 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.04 | 10-AUG-12:00 | 8986.36 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.80 | 15-SEP-12:00 | 13232.28 | 05-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19734.97 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19921.16 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32599.45 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7998.56 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4721.30 | 32599.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.73 | 12-JAN-05:55 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.85 | 13-FEB-05:54 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 15-MAR-12:00 | 771.94 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 706.81 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 14-MAY-14:43 | 440.71 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 | 17-JUN-17:03 | 399.26 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 | 16-JUL-11:20 | 291.57 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.13 | 13-AUG-13:00 | 179.24 | 19-AUG-17:40 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 333.72 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 428.39 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 724.62 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1249.18 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 144.13 | 1328.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.81 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.54 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1745.92 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1625.60 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.55 | 14-MAY-14:53 | 984.60 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.71 | 17-JUN-17:03 | 896.78 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 651.88 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.94 | 13-AUG-13:00 | 419.61 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 14-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 | 16-SEP-17:03 | 753.08 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 933.86 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1619.33 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.18 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.61 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 323.94 | 3122.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.87 | 12-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-05:56 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1171.33 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1089.46 | 16-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.06 | 14-MAY-15:10 | 718.11 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.83 | 17-JUN-17:20 | 599.45 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 11-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 15-JUL-15:00 | 432.12 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.37 | 13-AUG-13:00 | 271.12 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 16-SEP-17:03 | 494.36 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 648.37 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1067.83 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1916.70 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.12 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 208.37 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.82 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.54 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1011.14 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1903.55 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1629.44 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 10-MAY-14:00 | 1075.73 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.51 | 17-JUN-17:03 | 903.52 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 654.65 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.77 | 13-AUG-12:38 | 418.32 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 16-SEP-13:00 | 755.05 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 976.27 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1639.86 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2915.10 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.32 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 276.77 | 3122.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.86 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-05:56 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1248.81 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1073.22 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 10-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 10-MAY-14:00 | 754.08 | 29-MAY-15:10 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 12-JUN-13:00 | 603.30 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.86 | 16-JUL-11:40 | 440.25 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.00 | 13-AUG-13:00 | 309.87 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 493.17 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.97 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1066.05 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1919.19 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.87 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 233.00 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3998.71 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3905.20 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.40 | 15-MAR-14:00 | 2592.21 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2408.81 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 | 14-MAY-15:00 | 1202.53 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.24 | 17-JUN-17:03 | 1241.08 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.51 | 21-JUL-03:00 | 904.88 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.04 | 13-AUG-13:00 | 577.02 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 16-SEP-13:00 | 1096.39 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1357.95 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2398.06 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4050.21 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.04 | 4050.21 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4953.91 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4758.00 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 14-MAR-14:00 | 3212.07 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2927.93 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.24 | 14-MAY-14:53 | 1494.26 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.57 | 17-JUN-17:03 | 1587.20 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.63 | 21-JUL-03:00 | 1146.81 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.03 | 13-AUG-13:00 | 734.14 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.51 | 16-SEP-17:03 | 1336.67 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1607.74 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2911.72 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5041.03 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.03 | 5041.03 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4954.80 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.81 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 15-MAR-14:00 | 2992.62 | 25-MAR-17:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2780.81 | 16-APR-07:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | 10-MAY-15:00 | 1988.26 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.99 | 17-JUN-17:03 | 1585.45 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.63 | 21-JUL-02:00 | 1121.44 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.60 | 13-AUG-13:00 | 749.65 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.69 | 16-SEP-13:00 | 1241.97 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1483.85 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2721.29 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5417.67 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.60 | 5417.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9468.55 | 20-JAN-17:00 | 6035.01 | 6443.98 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9882.35 | 17-FEB-17:00 | 6035.01 | 6443.98 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18090.88 | 17-MAR-08:00 | 6035.01 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18560.47 | 21-APR-07:03 | 36210.05 | 38663.87 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24483.15 | 24-MAY-06:03 | 3811.58 | 6444.06 | 26390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42105.42 | 19-JUN-05:12 | 2541.06 | 2863.91 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43314.76 | 05-JUL-05:12 | 2541.06 | 2863.91 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43180.47 | 21-AUG-05:12 | 2541.06 | 2863.91 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41842.17 | 18-SEP-06:01 | 8893.70 | 15036.15 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22303.56 | 13-OCT-06:02 | 6352.64 | 10740.11 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17710.22 | 07-NOV-08:06 | 42245.05 | 45107.84 | 127296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14231.02 | 01-DEC-08:15 | 12070.02 | 12887.96 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9468.55 | 2541.06 | 2863.91 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43314.76 | 42245.05 | 45107.84 | 127296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.07 |
February | 275.02 | 22-FEB-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.24 |
March | 5347.05 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
April | 4484.30 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.49 |
May | 7038.66 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.87 |
June | 11052.29 | 27-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
July | 10343.11 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.05 | 0.00 |
August | 10254.23 | 09-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 0.00 |
September | 8077.32 | 21-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 0.00 |
October | 4186.34 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 |
November | 999.48 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 |
December | 57.48 | 16-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11052.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.05 | 974.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2692.79 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.07 |
February | 2472.55 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.69 |
March | 2183.08 | 07-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.97 |
April | 1385.34 | 14-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.41 |
May | 2268.52 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 |
June | 4351.88 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 0.00 |
July | 5295.81 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.96 | 0.00 |
August | 4563.51 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.60 | 0.00 |
September | 3218.63 | 18-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 |
October | 1675.30 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.01 |
November | 1383.37 | 18-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.11 |
December | 2410.86 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1862.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1383.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5295.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 1862.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2100.85 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.31 |
February | 1807.47 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.33 |
March | 2866.26 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.37 |
April | 2194.50 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.07 |
May | 2560.08 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 |
June | 4546.48 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.61 | 0.00 |
July | 5713.65 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 0.00 |
August | 4944.43 | 09-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 | 0.00 |
September | 4238.94 | 18-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 |
October | 2012.87 | 13-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.83 |
November | 1695.28 | 17-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.48 |
December | 1770.70 | 15-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1695.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5713.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.61 | 1179.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6248.54 | 12-JAN-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6373.75 | 17-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12041.52 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11178.54 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14515.55 | 31-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31272.32 | 19-JUN-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32327.32 | 05-JUL-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30198.06 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30025.93 | 18-SEP-06:01 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12723.50 | 12-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8117.87 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6679.24 | 01-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6248.54 | 2541.06 | 2863.91 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32327.32 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5904.09 | 12-JAN-16:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6168.69 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12174.60 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11899.34 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16045.83 | 31-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27263.03 | 27-JUN-15:05 | 12070.02 | 12887.96 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25902.43 | 20-JUL-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30318.96 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17146.30 | 18-SEP-13:30 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12349.09 | 12-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7464.08 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6331.43 | 01-DEC-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5904.09 | 2541.06 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30318.96 | 12070.02 | 12887.96 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1003.47 | 14-JAN-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.66 |
February | 1010.68 | 18-FEB-17:03 | 267.84 | 249.24 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.26 |
March | 3667.56 | 15-MAR-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 | 0.00 |
April | 2418.44 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
May | 4731.40 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 8463.60 | 27-JUN-15:05 | 2544.47 | 1295.96 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 0.00 |
July | 11647.59 | 16-JUL-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 58.69 | 0.00 |
August | 7261.68 | 06-AUG-14:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 0.00 |
September | 4785.80 | 15-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
October | 2446.42 | 12-OCT-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 |
November | 1410.47 | 16-NOV-16:50 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.46 |
December | 1100.02 | 01-DEC-13:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1003.47 | 267.84 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11647.59 | 2544.47 | 1358.45 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 58.69 | 313.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 984.42 | 14-JAN-17:03 | 169.56 | 191.11 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.60 |
February | 1312.84 | 28-FEB-10:00 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
March | 2836.92 | 15-MAR-14:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 5185.76 | 24-APR-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
May | 7494.13 | 31-MAY-08:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 |
June | 14262.38 | 11-JUN-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.96 |
July | 14045.88 | 04-JUL-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.54 |
August | 8227.47 | 17-AUG-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
September | 8735.02 | 04-SEP-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 |
October | 3987.79 | 11-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
November | 1486.16 | 03-NOV-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.74 |
December | 992.49 | 16-DEC-17:03 | 169.56 | 191.11 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 984.42 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14262.38 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 205.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3559.38 | 12-JAN-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.38 |
February | 6047.62 | 28-FEB-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
March | 10089.06 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
April | 8068.73 | 21-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.16 |
May | 8097.00 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
June | 11598.38 | 11-JUN-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.03 |
July | 17152.40 | 30-JUL-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.32 |
August | 17257.85 | 13-AUG-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 248.65 | 0.00 |
September | 18132.71 | 10-SEP-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.64 |
October | 11969.81 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 |
November | 7455.37 | 03-NOV-12:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 |
December | 3761.09 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3559.38 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18132.71 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 248.65 | 906.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1230.36 | 06-JAN-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.58 |
February | 1767.27 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.68 |
March | 3689.84 | 15-MAR-14:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 6299.65 | 24-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 12452.13 | 27-MAY-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.86 |
June | 16979.07 | 11-JUN-16:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.40 |
July | 16062.54 | 02-JUL-17:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 |
August | 13757.15 | 06-AUG-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 0.00 |
September | 15422.88 | 04-SEP-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.33 |
October | 6009.42 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 1743.45 | 03-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.73 |
December | 1249.74 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1230.36 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16979.07 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 258.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1009.29 | 14-JAN-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 |
February | 1010.35 | 18-FEB-17:03 | 267.84 | 210.65 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.27 |
March | 1630.02 | 15-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
April | 1498.00 | 21-APR-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.53 |
May | 2791.44 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4818.10 | 27-JUN-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 0.00 |
July | 5552.23 | 21-JUL-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.35 | 0.00 |
August | 5433.35 | 14-AUG-12:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 0.00 |
September | 4120.45 | 15-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
October | 2199.08 | 05-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
November | 1420.58 | 16-NOV-16:40 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.24 |
December | 1212.68 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1009.29 | 267.84 | 210.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5552.23 | 1306.65 | 1358.45 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 166.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 884.91 | 14-JAN-07:05 | 339.13 | 382.22 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 |
February | 980.16 | 28-FEB-09:45 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.16 |
March | 1501.59 | 15-MAR-14:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
April | 3714.80 | 24-APR-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 |
May | 4983.08 | 31-MAY-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
June | 10660.27 | 11-JUN-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.65 |
July | 11491.89 | 16-JUL-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 0.00 |
August | 6750.45 | 10-AUG-10:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
September | 7176.61 | 04-SEP-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.49 |
October | 3564.05 | 11-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
November | 1346.22 | 03-NOV-08:50 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.87 |
December | 950.66 | 01-DEC-13:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 884.91 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11491.89 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 121.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1253.87 | 21-JAN-12:30 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.48 |
February | 1475.86 | 18-FEB-14:40 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.62 |
March | 6198.16 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 173.51 | 0.00 |
April | 3771.71 | 24-APR-14:00 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.29 |
May | 5021.06 | 26-MAY-12:10 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.99 |
June | 11004.54 | 27-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4721.30 | 0.00 |
July | 11405.32 | 21-JUL-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4518.87 | 0.00 |
August | 13704.52 | 13-AUG-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 141.33 | 0.00 |
September | 13990.03 | 04-SEP-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.17 |
October | 10050.14 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.08 |
November | 4243.49 | 01-NOV-12:20 | 3816.70 | 1943.94 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1453.34 |
December | 1995.71 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1253.87 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13990.03 | 3816.70 | 1943.94 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4721.30 | 1453.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1017.07 | 12-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.49 |
February | 1275.83 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.91 |
March | 1767.03 | 15-MAR-14:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
April | 3794.37 | 24-APR-17:30 | 84.78 | 136.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 6500.60 | 27-MAY-17:07 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.52 |
June | 11939.39 | 11-JUN-17:51 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
July | 11986.40 | 02-JUL-18:02 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
August | 12182.13 | 27-AUG-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 |
September | 12207.68 | 04-SEP-17:22 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.67 |
October | 4975.11 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 1412.16 | 03-NOV-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 |
December | 1047.47 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1017.07 | 0.00 | 113.94 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12207.68 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 263.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 986.16 | 14-JAN-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 |
February | 988.94 | 18-FEB-17:03 | 267.84 | 249.24 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.17 |
March | 3238.00 | 15-MAR-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
April | 2297.82 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 |
May | 4491.65 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 6079.22 | 12-JUN-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 0.00 |
July | 7621.73 | 16-JUL-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 | 0.00 |
August | 8120.04 | 06-AUG-16:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 52.66 | 0.00 |
September | 4556.05 | 15-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
October | 2581.28 | 12-OCT-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.93 |
November | 1442.46 | 16-NOV-16:50 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 |
December | 1168.30 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 986.16 | 267.84 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8120.04 | 1306.65 | 1358.45 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 261.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1097.61 | 18-JAN-07:04 | 847.82 | 1433.37 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.36 |
February | 1412.25 | 28-FEB-09:50 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.29 |
March | 2793.56 | 14-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
April | 6038.91 | 24-APR-08:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.39 |
May | 7730.71 | 31-MAY-08:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
June | 11565.78 | 11-JUN-08:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.47 |
July | 13972.58 | 09-JUL-08:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
August | 13967.73 | 06-AUG-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.28 |
September | 7221.00 | 04-SEP-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.26 |
October | 4663.59 | 11-OCT-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
November | 1625.87 | 03-NOV-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.25 |
December | 1114.98 | 15-DEC-07:04 | 847.82 | 1433.37 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1097.61 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | |
Maximum of Months | 13972.58 | 1610.86 | 1433.37 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4599.33 | 12-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.87 |
February | 6323.44 | 28-FEB-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 9592.34 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 0.00 |
April | 7982.28 | 24-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.72 |
May | 7611.38 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
June | 9181.90 | 12-JUN-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 113.72 | 0.00 |
July | 16535.22 | 30-JUL-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.81 |
August | 15859.57 | 06-AUG-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 0.00 |
September | 16097.58 | 04-SEP-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.61 |
October | 12070.12 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
November | 8398.06 | 03-NOV-12:25 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 4359.48 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4359.48 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16535.22 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 113.72 | 775.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1253.06 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.49 |
February | 1812.06 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.46 |
March | 3400.44 | 15-MAR-14:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
April | 6246.25 | 24-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 11608.63 | 27-MAY-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.59 |
June | 14041.71 | 11-JUN-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.84 |
July | 14881.79 | 30-JUL-17:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.38 |
August | 15174.22 | 06-AUG-16:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
September | 11005.85 | 10-SEP-17:12 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.07 |
October | 5949.03 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 1918.99 | 03-NOV-14:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 |
December | 1252.02 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1252.02 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15174.22 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 421.49 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.175159E+12 | 250011.58 | 02-JAN-07:10 | 0.752859E+11 | 100096.75 | 04-JAN-07:19 |
February | 0.152914E+12 | 237779.53 | 06-FEB-07:10 | 0.694914E+11 | 115520.39 | 07-FEB-07:30 |
March | 0.128327E+12 | 189485.93 | 06-MAR-07:10 | 0.437509E+11 | 96897.66 | 07-MAR-07:19 |
April | 0.989426E+11 | 151402.75 | 17-APR-06:10 | 0.187752E+11 | 60529.46 | 17-APR-06:19 |
May | 0.104063E+12 | 107297.26 | 23-MAY-14:30 | 0.118106E+11 | 27612.42 | 01-MAY-06:30 |
June | 0.127765E+12 | 159696.27 | 27-JUN-15:20 | 0.110230E+11 | 9986.80 | 01-JUN-11:39 |
July | 0.147448E+12 | 167304.03 | 17-JUL-07:10 | 0.106516E+11 | 9869.00 | 03-JUL-11:39 |
August | 0.146165E+12 | 173801.10 | 15-AUG-14:30 | 0.110592E+11 | 9811.07 | 29-AUG-11:09 |
September | 0.112209E+12 | 135821.83 | 15-SEP-10:00 | 0.104921E+11 | 13897.89 | 06-SEP-06:10 |
October | 0.102436E+12 | 135945.86 | 30-OCT-06:10 | 0.147970E+11 | 54096.42 | 17-OCT-06:40 |
November | 0.114094E+12 | 164951.80 | 24-NOV-07:10 | 0.260531E+11 | 58065.41 | 24-NOV-07:40 |
December | 0.161586E+12 | 234949.47 | 11-DEC-07:10 | 0.660225E+11 | 111340.93 | 11-DEC-07:19 |
Annual Sum or Average | 0.157111E+13 | 0.369213E+12 | ||||
Minimum of Months | 0.989426E+11 | 107297.26 | 0.104921E+11 | 9811.07 | ||
Maximum of Months | 0.175159E+12 | 250011.58 | 0.752859E+11 | 115520.39 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.259597E+11 | 0.597089E+10 | 0.593559E+11 | 0.989337E+09 | 0.520506E+10 | 12379742.02 | 0.776660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230990E+11 | 0.474836E+10 | 0.537310E+11 | 0.894911E+09 | 0.468767E+10 | 11196021.66 | 0.657415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269867E+11 | 0.441831E+10 | 0.617796E+11 | 0.103569E+10 | 0.494964E+10 | 12675672.10 | 0.276323E+11 | 0.151180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237978E+11 | 0.352418E+10 | 0.572952E+11 | 0.951963E+09 | 0.471000E+10 | 11960507.72 | 0.808565E+10 | 0.565847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255495E+11 | 0.304929E+10 | 0.605677E+11 | 0.101183E+10 | 0.689516E+10 | 12527707.06 | 0.987744E+09 | 0.598947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253320E+11 | 0.273786E+10 | 0.594895E+11 | 0.996112E+09 | 0.120649E+11 | 12231776.97 | 0.171248E+09 | 0.269610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.236791E+11 | 0.290320E+10 | 0.583622E+11 | 0.967390E+09 | 0.152215E+11 | 12256437.81 | 13207419.38 | 0.462890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.265631E+11 | 0.337878E+10 | 0.617796E+11 | 0.103544E+10 | 0.148490E+11 | 12675672.10 | 36800993.85 | 0.385101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239671E+11 | 0.391430E+10 | 0.572729E+11 | 0.951836E+09 | 0.911340E+10 | 11960507.72 | 0.303108E+09 | 0.166745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252797E+11 | 0.488938E+10 | 0.593671E+11 | 0.988801E+09 | 0.512300E+10 | 12379742.02 | 0.483717E+10 | 0.193888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258050E+11 | 0.553154E+10 | 0.580818E+11 | 0.971290E+09 | 0.421689E+10 | 12059151.09 | 0.191256E+11 | 0.350183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253967E+11 | 0.618583E+10 | 0.583511E+11 | 0.968772E+09 | 0.485266E+10 | 12256437.81 | 0.658185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301415E+12 | 0.512519E+11 | 0.705434E+12 | 0.117634E+11 | 0.918889E+11 | 0.146559E+09 | 0.270419E+12 | 0.138791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.230990E+11 | 0.273786E+10 | 0.537310E+11 | 0.894911E+09 | 0.421689E+10 | 11196021.66 | 13207419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269867E+11 | 0.618583E+10 | 0.617796E+11 | 0.103569E+10 | 0.152215E+11 | 12675672.10 | 0.776660E+11 | 0.462890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.632692E+11 | 0.00 | 0.120167E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.585282E+11 | 0.00 | 0.109632E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.313077E+11 | 0.00 | 0.124432E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.741929E+10 | 0.00 | 0.113559E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.213411E+09 | 0.00 | 0.115972E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3484496.01 | 0.00 | 0.110195E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.106516E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.110592E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 50884009.07 | 0.00 | 0.104412E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.375582E+10 | 0.00 | 0.110412E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149488E+11 | 0.00 | 0.111043E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.544271E+11 | 0.00 | 0.115954E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233924E+12 | 0.00 | 0.135289E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.104412E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.632692E+11 | 0.00 | 0.124432E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 850.39 | 11-JAN-08:20 | 7275.48 | 02-JAN-07:10 | 6.85 | 03-JAN-07:19 | 205141.51 | 02-JAN-06:19 |
February | 32139.06 | 01-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 849.71 | 01-FEB-08:20 | 6709.41 | 06-FEB-07:10 | 6.85 | 01-FEB-13:09 | 193153.22 | 06-FEB-07:10 |
March | 29907.05 | 17-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 846.71 | 17-MAR-07:19 | 7905.15 | 15-MAR-13:50 | 6.85 | 02-MAR-06:10 | 156838.38 | 06-MAR-06:10 |
April | 28290.68 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 844.55 | 12-APR-07:19 | 7636.45 | 21-APR-15:20 | 6.85 | 03-APR-05:10 | 117023.90 | 17-APR-06:10 |
May | 26798.99 | 11-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 842.55 | 11-MAY-07:19 | 13555.93 | 31-MAY-15:00 | 6.85 | 01-MAY-05:10 | 31518.27 | 01-MAY-06:10 |
June | 26116.88 | 19-JUN-07:10 | 3328.83 | 01-JUN-19:49 | 45864.70 | 01-JUN-07:10 | 841.64 | 19-JUN-07:19 | 26829.32 | 27-JUN-15:20 | 6.85 | 13-JUN-11:09 | 12534.08 | 14-JUN-06:10 |
July | 26506.32 | 11-JUL-07:30 | 3328.83 | 01-JUL-19:00 | 45864.70 | 03-JUL-07:10 | 842.16 | 11-JUL-07:40 | 28989.26 | 17-JUL-12:09 | 6.85 | 02-JUL-15:50 | 2585.40 | 13-JUL-06:19 |
August | 26735.82 | 24-AUG-07:10 | 5686.19 | 02-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 842.47 | 24-AUG-07:19 | 27947.06 | 15-AUG-14:30 | 6.85 | 01-AUG-05:10 | 4210.33 | 31-AUG-06:40 |
September | 29070.25 | 26-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 845.59 | 26-SEP-07:19 | 19948.51 | 21-SEP-15:00 | 6.85 | 01-SEP-05:10 | 16768.40 | 29-SEP-06:10 |
October | 32272.70 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 849.89 | 30-OCT-07:19 | 10314.69 | 11-OCT-15:50 | 6.85 | 13-OCT-16:10 | 94074.60 | 30-OCT-06:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 850.39 | 01-NOV-07:19 | 4890.67 | 03-NOV-12:50 | 6.85 | 03-NOV-07:10 | 122798.69 | 24-NOV-07:10 |
December | 32642.50 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 850.39 | 18-DEC-08:20 | 6622.48 | 11-DEC-07:10 | 6.85 | 04-DEC-17:10 | 190410.10 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26116.88 | 3328.83 | 45864.70 | 841.64 | 4890.67 | 6.85 | 2585.40 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 45864.70 | 850.39 | 28989.26 | 6.85 | 205141.51 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24852.84 | 15-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10891.71 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28718.36 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64266.91 | 27-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71493.19 | 17-JUL-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78738.48 | 15-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51993.35 | 15-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20013.66 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8245.44 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78738.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 250011.58 | 02-JAN-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 7275.48 | 6.85 | 204819.20 | 0.00 | 0.00 |
February | 237779.53 | 06-FEB-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 6709.41 | 6.85 | 193153.22 | 0.00 | 0.00 |
March | 189485.93 | 06-MAR-07:10 | 9486.96 | 21098.80 | 0.00 | 243.93 | 4998.95 | 6.85 | 153650.44 | 0.00 | 0.00 |
April | 151402.75 | 17-APR-06:10 | 8918.83 | 21098.80 | 0.00 | 243.83 | 4110.54 | 6.85 | 117023.90 | 0.00 | 0.00 |
May | 107297.26 | 23-MAY-14:30 | 25681.07 | 40588.47 | 0.00 | 839.16 | 13447.64 | 6.85 | 0.00 | 26734.06 | 0.00 |
June | 159696.27 | 27-JUN-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 26829.32 | 6.85 | 0.00 | 64266.91 | 0.00 |
July | 167304.03 | 17-JUL-07:10 | 25681.07 | 45864.70 | 0.00 | 818.45 | 24696.88 | 6.85 | 0.00 | 70236.06 | 0.00 |
August | 173801.10 | 15-AUG-14:30 | 25681.07 | 40588.47 | 0.00 | 839.16 | 27947.06 | 6.85 | 0.00 | 78738.48 | 0.00 |
September | 135821.83 | 15-SEP-10:00 | 25681.07 | 41577.77 | 0.00 | 839.52 | 15723.26 | 6.85 | 0.00 | 51993.35 | 0.00 |
October | 135945.86 | 30-OCT-06:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 3954.37 | 6.85 | 94074.60 | 0.00 | 0.00 |
November | 164951.80 | 24-NOV-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 4236.21 | 6.85 | 122798.69 | 0.00 | 0.00 |
December | 234949.47 | 11-DEC-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 6622.48 | 6.85 | 190410.10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 107297.26 | 8918.83 | 21098.80 | 0.00 | 243.83 | 3954.37 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 250011.58 | 25681.07 | 45864.70 | 5686.19 | 839.70 | 27947.06 | 6.85 | 204819.20 | 78738.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 91159.76 | 04-JAN-07:19 | 0.00 | 11111.60 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 108110.08 | 07-FEB-07:19 | 0.00 | 11188.10 | 06-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 88082.23 | 07-MAR-07:19 | 0.00 | 11021.17 | 07-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 53237.90 | 17-APR-06:19 | 0.00 | 10236.69 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 23105.26 | 01-MAY-06:10 | 0.00 | 10133.06 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 1884.09 | 14-JUN-06:10 | 0.00 | 9986.80 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9869.00 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9811.07 | 29-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 5319.25 | 30-SEP-06:19 | 0.00 | 9879.04 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 45558.99 | 17-OCT-06:19 | 0.00 | 9988.53 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 49883.01 | 24-NOV-07:30 | 0.00 | 10121.30 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 103129.95 | 11-DEC-07:19 | 0.00 | 10250.86 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9811.07 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 108110.08 | 0.00 | 11188.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.55 | 0.50 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.55 | 0.50 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.55 | 0.50 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.23 | 1.83 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 0.67 | 19.33 | 0.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.27 | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 3.17 | 19.25 | 2.83 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.33 | 1.83 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.20 | 1.50 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 1.83 | 18.00 | 1.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
March | 0.33 | 17.78 | 0.17 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 18.46 | 1.17 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 6.50 | 18.20 | 3.83 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 18.46 | 1.50 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.00 | 16.11 | 20.33 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
February | 47.67 | 16.13 | 18.67 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
March | 10.33 | 16.58 | 3.83 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
April | 0.83 | 17.07 | 0.33 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
November | 1.17 | 18.49 | 0.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
December | 36.33 | 16.01 | 15.50 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
Annual Sum or Average | 143.50 | 16.15 | 59.50 | 16.60 | 2.00 | 16.71 | 1.67 | 16.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.67 | 18.49 | 20.33 | 18.77 | 1.67 | 27.43 | 1.33 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 14.98 | 6.83 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
February | 30.67 | 14.80 | 3.67 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
March | 6.67 | 15.32 | 0.17 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
April | 0.33 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.83 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.83 | 6.83 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.54 | 3.17 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
October | 0.17 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
November | 1.50 | 16.62 | 0.17 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
December | 28.00 | 14.96 | 6.83 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
Annual Sum or Average | 101.33 | 14.97 | 17.67 | 15.01 | 13.67 | 16.32 | 13.50 | 17.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.00 | 16.84 | 6.83 | 16.90 | 7.00 | 27.83 | 6.83 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.33 | 15.16 | 4.83 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 27.33 | 15.10 | 4.00 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
March | 4.33 | 16.07 | 0.67 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
April | 0.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 2.33 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.66 | 6.50 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.77 | 4.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.83 | 2.83 | 27.83 |
October | 0.17 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
November | 0.50 | 17.68 | 0.17 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
December | 21.50 | 15.28 | 4.17 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
Annual Sum or Average | 81.33 | 15.24 | 13.83 | 15.41 | 16.83 | 17.26 | 16.33 | 18.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 | 15.27 |
Maximum of Months | 27.33 | 17.68 | 4.83 | 18.09 | 6.67 | 27.83 | 6.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 14.93 | 8.83 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 31.17 | 14.80 | 5.17 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
March | 6.33 | 15.39 | 0.83 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
April | 0.50 | 15.61 | 0.33 | 15.37 | 0.17 | 17.36 | 0.00 | 17.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.73 | 1.17 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.05 | 3.17 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.21 | 4.17 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.03 | 2.83 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 1.83 | 27.74 |
October | 0.17 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
November | 0.67 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
December | 27.83 | 14.92 | 6.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Annual Sum or Average | 101.83 | 14.94 | 21.33 | 14.96 | 22.17 | 16.95 | 13.17 | 17.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 | 14.83 |
Maximum of Months | 35.17 | 16.99 | 8.83 | 16.99 | 7.67 | 28.21 | 4.17 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 17.83 | 8.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
February | 14.50 | 18.11 | 9.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
March | 2.83 | 19.25 | 2.33 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 18.58 | 4.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Annual Sum or Average | 38.50 | 18.17 | 24.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.67 | 19.25 | 9.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 15.63 | 0.33 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
February | 4.83 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 0.33 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.50 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.62 | 0.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 16.30 | 0.17 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
Annual Sum or Average | 14.17 | 15.71 | 0.50 | 15.78 | 4.00 | 18.32 | 4.00 | 19.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 16.93 | 0.33 | 16.93 | 2.33 | 27.73 | 2.33 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.67 | 16.84 | 76.83 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
February | 73.83 | 16.98 | 71.33 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
March | 42.83 | 18.18 | 42.83 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
April | 21.33 | 19.10 | 21.33 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
May | 3.83 | 19.85 | 3.83 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 1.17 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.52 | 2.83 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.60 | 2.83 | 27.60 |
October | 9.17 | 19.31 | 9.17 | 19.31 | 0.17 | 19.38 | 0.17 | 19.45 |
November | 33.83 | 19.32 | 33.83 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 70.17 | 17.26 | 69.17 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
Annual Sum or Average | 336.67 | 17.62 | 328.33 | 17.64 | 7.00 | 17.75 | 7.00 | 17.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.67 | 19.85 | 76.83 | 19.85 | 2.83 | 27.60 | 2.83 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 15.63 | 0.67 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
February | 4.50 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
March | 0.33 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.47 | 0.17 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.75 | 1.67 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.91 | 2.17 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.72 | 2.00 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 0.67 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 16.19 | 0.17 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 14.50 | 15.73 | 0.83 | 15.78 | 13.17 | 21.33 | 6.67 | 22.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 16.98 | 0.67 | 16.98 | 4.67 | 27.91 | 2.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 16.70 | 5.83 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
February | 19.17 | 16.84 | 7.00 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 1.17 | 18.39 | 0.67 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.17 | 16.95 | 5.17 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
Annual Sum or Average | 51.17 | 16.86 | 18.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.17 | 18.39 | 7.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 15.45 | 0.83 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
February | 11.67 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 0.50 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.65 | 2.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.83 | 6.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.66 | 1.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.67 | 15.45 | 0.33 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Annual Sum or Average | 33.33 | 15.37 | 1.17 | 15.44 | 13.33 | 18.86 | 13.33 | 20.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 16.88 | 0.83 | 16.88 | 6.00 | 27.83 | 6.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 15.64 | 0.67 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 9.83 | 15.44 | 0.33 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
March | 0.33 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.44 | 1.33 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.54 | 5.33 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 4.00 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.80 | 3.50 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.83 | 15.64 | 0.33 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
Annual Sum or Average | 26.00 | 15.58 | 1.33 | 15.74 | 15.00 | 19.95 | 15.00 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 16.95 | 0.67 | 16.95 | 5.33 | 27.80 | 5.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 15.40 | 1.00 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
February | 10.67 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 0.50 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.73 | 1.00 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.10 | 2.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.15 | 3.17 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.89 | 2.67 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.85 | 1.50 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.17 | 15.46 | 0.83 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
Annual Sum or Average | 34.00 | 15.36 | 1.83 | 15.42 | 20.50 | 20.00 | 11.33 | 21.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 16.94 | 1.00 | 16.94 | 6.50 | 28.15 | 3.17 | 28.16 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.23 | 73.33 | 21.98 | 73.33 | 21.79 |
February | 454.00 | 22.49 | 29.33 | 22.39 | 29.33 | 22.31 |
March | 448.67 | 23.40 | 14.67 | 23.42 | 2.50 | 23.41 |
April | 314.67 | 23.70 | 12.83 | 23.77 | 0.00 | 23.77 |
May | 96.17 | 23.95 | 157.50 | 24.55 | 0.00 | 24.55 |
June | 0.00 | 0.00 | 354.50 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 487.33 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 483.83 | 24.42 | 0.00 | 24.42 |
September | 4.83 | 23.86 | 344.17 | 24.52 | 0.00 | 24.52 |
October | 173.67 | 23.87 | 74.33 | 24.13 | 0.00 | 24.13 |
November | 433.67 | 23.68 | 1.50 | 23.68 | 0.00 | 23.68 |
December | 491.00 | 22.76 | 17.33 | 22.70 | 17.33 | 22.64 |
Annual Sum or Average | 2918.67 | 23.07 | 2050.67 | 23.57 | 122.50 | 23.50 |
Minimum of Months | 0.00 | 0.00 | 1.50 | 21.98 | 0.00 | 21.79 |
Maximum of Months | 502.00 | 23.95 | 487.33 | 24.55 | 73.33 | 24.55 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.84 | 345.33 | 20.70 | 345.33 | 20.64 |
February | 454.00 | 21.01 | 270.17 | 20.86 | 270.17 | 20.79 |
March | 482.33 | 21.97 | 83.33 | 21.83 | 78.17 | 21.71 |
April | 463.00 | 22.88 | 4.33 | 22.86 | 4.33 | 22.85 |
May | 247.83 | 23.54 | 58.83 | 23.71 | 0.00 | 23.71 |
June | 45.83 | 23.76 | 276.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 470.00 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 418.17 | 24.31 | 0.00 | 24.31 |
September | 72.83 | 23.43 | 217.17 | 24.14 | 0.00 | 24.14 |
October | 398.67 | 22.96 | 8.83 | 22.99 | 0.17 | 22.99 |
November | 489.00 | 22.19 | 13.17 | 22.15 | 13.17 | 22.11 |
December | 497.00 | 21.06 | 267.17 | 20.90 | 267.17 | 20.82 |
Annual Sum or Average | 3652.50 | 21.98 | 2432.50 | 22.32 | 978.50 | 22.08 |
Minimum of Months | 0.00 | 0.00 | 4.33 | 20.70 | 0.00 | 20.64 |
Maximum of Months | 502.00 | 23.76 | 470.00 | 24.31 | 345.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 446.50 | 20.31 | 446.50 | 20.29 |
February | 454.00 | 20.49 | 372.00 | 20.40 | 372.00 | 20.36 |
March | 490.17 | 21.36 | 202.33 | 21.14 | 197.67 | 20.99 |
April | 474.83 | 22.27 | 45.67 | 22.10 | 45.67 | 21.95 |
May | 310.17 | 23.26 | 46.83 | 23.39 | 0.00 | 23.39 |
June | 79.00 | 23.51 | 256.17 | 24.06 | 0.00 | 24.06 |
July | 6.67 | 23.49 | 449.33 | 24.29 | 0.00 | 24.29 |
August | 22.00 | 23.39 | 385.67 | 24.21 | 0.00 | 24.21 |
September | 164.83 | 23.14 | 156.17 | 23.70 | 0.00 | 23.70 |
October | 457.50 | 22.19 | 42.00 | 22.06 | 38.83 | 21.94 |
November | 489.00 | 21.30 | 149.83 | 21.08 | 149.83 | 20.95 |
December | 497.00 | 20.46 | 402.67 | 20.37 | 402.67 | 20.34 |
Annual Sum or Average | 3947.17 | 21.50 | 2955.17 | 21.74 | 1653.17 | 21.46 |
Minimum of Months | 6.67 | 20.37 | 42.00 | 20.31 | 0.00 | 20.29 |
Maximum of Months | 502.00 | 23.51 | 449.33 | 24.29 | 446.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 494.17 | 19.77 | 494.17 | 19.77 |
February | 454.00 | 19.83 | 452.33 | 19.83 | 452.33 | 19.83 |
March | 495.67 | 20.58 | 337.50 | 20.41 | 328.33 | 20.31 |
April | 477.50 | 21.40 | 143.67 | 21.08 | 143.67 | 20.88 |
May | 345.33 | 22.69 | 58.33 | 22.81 | 10.67 | 22.75 |
June | 104.17 | 23.43 | 268.17 | 24.03 | 13.83 | 24.08 |
July | 50.83 | 24.90 | 446.17 | 24.43 | 38.67 | 24.50 |
August | 78.17 | 23.48 | 370.67 | 24.12 | 13.83 | 24.15 |
September | 251.67 | 22.78 | 140.33 | 23.28 | 13.67 | 23.34 |
October | 481.00 | 21.30 | 135.33 | 21.01 | 132.50 | 20.81 |
November | 489.00 | 20.42 | 321.17 | 20.26 | 321.17 | 20.19 |
December | 497.00 | 19.78 | 479.83 | 19.76 | 479.83 | 19.75 |
Annual Sum or Average | 4226.33 | 20.95 | 3647.67 | 21.17 | 2442.67 | 20.90 |
Minimum of Months | 50.83 | 19.78 | 58.33 | 19.76 | 10.67 | 19.75 |
Maximum of Months | 502.00 | 24.90 | 494.17 | 24.43 | 494.17 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 494.50 | 19.82 | 494.50 | 19.82 |
February | 454.00 | 19.90 | 437.50 | 19.88 | 437.50 | 19.87 |
March | 490.83 | 20.72 | 290.50 | 20.54 | 273.33 | 20.40 |
April | 402.83 | 21.38 | 116.83 | 21.17 | 100.67 | 20.94 |
May | 265.17 | 22.52 | 140.67 | 23.11 | 9.00 | 23.08 |
June | 98.17 | 23.68 | 336.00 | 24.20 | 22.00 | 24.30 |
July | 68.50 | 25.73 | 461.33 | 24.61 | 58.50 | 24.77 |
August | 79.33 | 23.72 | 398.83 | 24.20 | 21.67 | 24.28 |
September | 205.00 | 22.64 | 229.00 | 23.50 | 15.67 | 23.56 |
October | 451.83 | 21.39 | 107.33 | 21.16 | 98.33 | 20.97 |
November | 489.00 | 20.52 | 306.67 | 20.34 | 306.67 | 20.26 |
December | 497.00 | 19.84 | 480.50 | 19.82 | 480.50 | 19.81 |
Annual Sum or Average | 4003.67 | 20.96 | 3799.67 | 21.35 | 2318.33 | 21.09 |
Minimum of Months | 68.50 | 19.83 | 107.33 | 19.82 | 9.00 | 19.81 |
Maximum of Months | 502.00 | 25.73 | 494.50 | 24.61 | 494.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 436.17 | 20.00 | 436.17 | 19.94 |
February | 449.50 | 20.16 | 375.33 | 19.98 | 375.33 | 19.91 |
March | 460.33 | 21.13 | 240.50 | 20.87 | 222.83 | 20.67 |
April | 388.83 | 21.43 | 140.17 | 21.32 | 110.67 | 21.09 |
May | 289.17 | 22.51 | 118.67 | 22.96 | 15.67 | 22.91 |
June | 129.67 | 23.39 | 294.67 | 24.03 | 22.17 | 24.12 |
July | 85.67 | 25.05 | 438.17 | 24.53 | 59.17 | 24.68 |
August | 93.83 | 23.79 | 391.50 | 24.22 | 24.67 | 24.32 |
September | 192.33 | 22.96 | 246.83 | 23.77 | 23.33 | 23.88 |
October | 387.67 | 21.58 | 147.00 | 21.63 | 85.50 | 21.39 |
November | 465.67 | 20.87 | 243.00 | 20.61 | 240.00 | 20.47 |
December | 495.00 | 20.08 | 440.83 | 19.98 | 440.83 | 19.95 |
Annual Sum or Average | 3939.67 | 21.22 | 3512.83 | 21.55 | 2056.33 | 21.28 |
Minimum of Months | 85.67 | 20.08 | 118.67 | 19.98 | 15.67 | 19.91 |
Maximum of Months | 502.00 | 25.05 | 440.83 | 24.53 | 440.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 491.17 | 19.82 | 491.17 | 19.82 |
February | 454.00 | 19.93 | 431.83 | 19.89 | 431.83 | 19.87 |
March | 491.67 | 20.77 | 290.00 | 20.56 | 281.17 | 20.43 |
April | 419.50 | 21.21 | 161.17 | 21.14 | 128.83 | 20.94 |
May | 322.83 | 22.37 | 122.00 | 22.83 | 18.17 | 22.82 |
June | 141.50 | 23.32 | 305.83 | 24.01 | 24.00 | 24.13 |
July | 83.33 | 24.68 | 431.00 | 24.45 | 50.50 | 24.59 |
August | 108.17 | 23.34 | 374.17 | 24.10 | 20.17 | 24.18 |
September | 263.67 | 22.60 | 179.17 | 23.30 | 21.17 | 23.40 |
October | 464.00 | 21.22 | 141.67 | 21.04 | 122.17 | 20.85 |
November | 489.00 | 20.48 | 305.17 | 20.30 | 305.17 | 20.22 |
December | 497.00 | 19.82 | 475.50 | 19.80 | 475.50 | 19.79 |
Annual Sum or Average | 4236.67 | 20.98 | 3708.67 | 21.29 | 2369.83 | 21.04 |
Minimum of Months | 83.33 | 19.82 | 122.00 | 19.80 | 18.17 | 19.79 |
Maximum of Months | 502.00 | 24.68 | 491.17 | 24.45 | 491.17 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 494.33 | 20.03 | 494.33 | 20.03 |
February | 454.00 | 20.12 | 454.00 | 20.12 | 454.00 | 20.12 |
March | 514.00 | 20.76 | 345.00 | 20.60 | 345.00 | 20.54 |
April | 485.00 | 21.29 | 132.33 | 21.09 | 132.33 | 20.96 |
May | 452.50 | 22.64 | 14.50 | 22.65 | 5.50 | 22.62 |
June | 136.67 | 23.53 | 220.83 | 23.92 | 9.00 | 23.94 |
July | 27.17 | 24.70 | 448.67 | 24.30 | 23.00 | 24.33 |
August | 42.33 | 23.67 | 378.00 | 24.17 | 9.17 | 24.18 |
September | 209.67 | 23.30 | 147.67 | 23.69 | 10.50 | 23.75 |
October | 477.00 | 22.12 | 26.83 | 22.05 | 25.17 | 21.98 |
November | 489.00 | 21.02 | 186.33 | 20.86 | 186.33 | 20.77 |
December | 497.00 | 20.22 | 464.50 | 20.19 | 464.50 | 20.18 |
Annual Sum or Average | 4286.33 | 21.25 | 3313.00 | 21.43 | 2158.83 | 21.19 |
Minimum of Months | 27.17 | 20.04 | 14.50 | 20.03 | 5.50 | 20.03 |
Maximum of Months | 514.00 | 24.70 | 494.33 | 24.30 | 494.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 494.17 | 20.12 | 494.17 | 20.11 |
February | 454.00 | 20.21 | 444.33 | 20.20 | 444.33 | 20.19 |
March | 505.83 | 20.97 | 272.50 | 20.76 | 272.50 | 20.67 |
April | 443.50 | 21.82 | 68.33 | 21.64 | 63.83 | 21.47 |
May | 305.83 | 22.82 | 86.33 | 23.21 | 1.17 | 23.20 |
June | 68.33 | 23.71 | 328.50 | 24.26 | 9.50 | 24.30 |
July | 37.17 | 26.03 | 484.33 | 24.56 | 37.17 | 24.66 |
August | 32.33 | 24.33 | 438.83 | 24.35 | 13.50 | 24.39 |
September | 120.83 | 23.32 | 287.33 | 24.06 | 11.17 | 24.11 |
October | 405.67 | 22.29 | 34.67 | 22.34 | 13.33 | 22.29 |
November | 489.00 | 21.17 | 150.33 | 21.00 | 150.33 | 20.89 |
December | 497.00 | 20.26 | 465.17 | 20.24 | 465.17 | 20.23 |
Annual Sum or Average | 3861.50 | 21.28 | 3554.83 | 21.71 | 1976.17 | 21.44 |
Minimum of Months | 32.33 | 20.12 | 34.67 | 20.12 | 1.17 | 20.11 |
Maximum of Months | 505.83 | 26.03 | 494.17 | 24.56 | 494.17 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 462.33 | 19.64 | 462.33 | 19.61 |
February | 454.00 | 19.75 | 414.33 | 19.67 | 414.33 | 19.65 |
March | 497.83 | 20.89 | 220.50 | 20.66 | 212.00 | 20.50 |
April | 446.17 | 21.40 | 97.50 | 21.26 | 87.33 | 21.08 |
May | 388.50 | 22.37 | 51.83 | 22.57 | 9.50 | 22.52 |
June | 173.17 | 23.06 | 237.67 | 23.76 | 33.33 | 23.79 |
July | 93.17 | 24.17 | 447.00 | 24.37 | 70.00 | 24.41 |
August | 95.50 | 23.63 | 417.83 | 24.24 | 48.17 | 24.29 |
September | 129.50 | 23.21 | 305.83 | 24.09 | 28.50 | 24.18 |
October | 362.33 | 22.11 | 88.33 | 22.44 | 14.17 | 22.35 |
November | 470.00 | 21.31 | 128.17 | 21.07 | 128.17 | 20.92 |
December | 496.83 | 20.00 | 433.33 | 19.89 | 433.33 | 19.85 |
Annual Sum or Average | 4109.00 | 21.17 | 3304.67 | 21.50 | 1941.17 | 21.24 |
Minimum of Months | 93.17 | 19.71 | 51.83 | 19.64 | 9.50 | 19.61 |
Maximum of Months | 502.00 | 24.17 | 462.33 | 24.37 | 462.33 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.09 | 490.67 | 20.08 | 490.67 | 20.08 |
February | 454.00 | 20.20 | 438.83 | 20.18 | 438.83 | 20.17 |
March | 509.67 | 21.00 | 270.33 | 20.79 | 270.33 | 20.69 |
April | 446.33 | 21.58 | 89.83 | 21.42 | 83.33 | 21.27 |
May | 334.83 | 22.67 | 78.17 | 23.04 | 0.83 | 23.04 |
June | 85.83 | 23.69 | 321.83 | 24.22 | 15.00 | 24.28 |
July | 40.00 | 25.44 | 466.00 | 24.52 | 34.50 | 24.60 |
August | 41.17 | 24.54 | 439.33 | 24.39 | 19.17 | 24.45 |
September | 140.17 | 23.33 | 241.33 | 23.99 | 13.00 | 24.07 |
October | 440.00 | 22.15 | 38.67 | 22.16 | 19.33 | 22.10 |
November | 489.00 | 21.10 | 167.17 | 20.94 | 167.17 | 20.84 |
December | 497.00 | 20.25 | 462.83 | 20.22 | 462.83 | 20.21 |
Annual Sum or Average | 3980.00 | 21.27 | 3505.00 | 21.65 | 2015.00 | 21.40 |
Minimum of Months | 40.00 | 20.09 | 38.67 | 20.08 | 0.83 | 20.08 |
Maximum of Months | 509.67 | 25.44 | 490.67 | 24.52 | 490.67 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 491.17 | 19.96 | 491.17 | 19.96 |
February | 454.00 | 20.05 | 439.50 | 20.04 | 439.50 | 20.03 |
March | 493.50 | 20.88 | 290.83 | 20.70 | 281.83 | 20.59 |
April | 477.67 | 21.84 | 73.17 | 21.61 | 73.17 | 21.43 |
May | 313.33 | 23.08 | 54.83 | 23.25 | 0.00 | 23.25 |
June | 71.17 | 23.76 | 274.50 | 24.16 | 8.67 | 24.19 |
July | 33.83 | 25.36 | 464.83 | 24.45 | 32.67 | 24.51 |
August | 35.83 | 23.63 | 402.67 | 24.23 | 7.00 | 24.23 |
September | 193.50 | 23.21 | 162.00 | 23.68 | 12.00 | 23.75 |
October | 464.33 | 21.87 | 66.83 | 21.71 | 61.50 | 21.57 |
November | 489.00 | 20.86 | 221.17 | 20.67 | 221.17 | 20.57 |
December | 497.00 | 20.05 | 460.50 | 20.01 | 460.50 | 20.00 |
Annual Sum or Average | 4025.17 | 21.19 | 3402.00 | 21.46 | 2089.17 | 21.19 |
Minimum of Months | 33.83 | 19.97 | 54.83 | 19.96 | 0.00 | 19.96 |
Maximum of Months | 502.00 | 25.36 | 491.17 | 24.45 | 491.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.86 | 419.67 | 19.85 | 419.67 | 19.85 |
February | 385.00 | 19.98 | 366.00 | 19.94 | 366.00 | 19.93 |
March | 416.00 | 20.95 | 218.33 | 20.76 | 207.33 | 20.63 |
April | 346.83 | 21.66 | 74.83 | 21.58 | 55.67 | 21.39 |
May | 231.67 | 22.83 | 99.00 | 23.38 | 3.33 | 23.42 |
June | 77.67 | 23.90 | 278.00 | 24.32 | 16.33 | 24.41 |
July | 51.17 | 26.11 | 400.50 | 24.71 | 49.50 | 24.85 |
August | 51.83 | 24.00 | 339.17 | 24.34 | 15.83 | 24.41 |
September | 163.83 | 23.08 | 186.83 | 23.81 | 16.00 | 23.92 |
October | 374.17 | 21.76 | 59.00 | 21.67 | 47.00 | 21.53 |
November | 417.00 | 20.83 | 193.17 | 20.64 | 193.17 | 20.54 |
December | 422.00 | 19.92 | 398.83 | 19.89 | 398.83 | 19.88 |
Annual Sum or Average | 3364.17 | 21.15 | 3033.33 | 21.54 | 1788.67 | 21.27 |
Minimum of Months | 51.17 | 19.86 | 59.00 | 19.85 | 3.33 | 19.85 |
Maximum of Months | 427.00 | 26.11 | 419.67 | 24.71 | 419.67 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.33 | 20.40 | 409.67 | 20.23 | 408.50 | 20.17 |
February | 447.50 | 20.47 | 346.00 | 20.26 | 346.00 | 20.18 |
March | 443.50 | 21.48 | 178.83 | 21.25 | 159.83 | 21.06 |
April | 375.50 | 21.89 | 81.50 | 21.89 | 52.33 | 21.71 |
May | 255.67 | 22.92 | 115.00 | 23.40 | 1.83 | 23.42 |
June | 90.00 | 23.69 | 312.17 | 24.17 | 14.83 | 24.23 |
July | 63.67 | 25.58 | 459.17 | 24.58 | 53.50 | 24.72 |
August | 54.17 | 24.55 | 420.00 | 24.38 | 23.50 | 24.47 |
September | 144.50 | 23.53 | 281.00 | 24.12 | 23.17 | 24.25 |
October | 344.17 | 22.10 | 108.50 | 22.37 | 32.17 | 22.23 |
November | 450.67 | 21.31 | 155.17 | 21.08 | 149.50 | 20.93 |
December | 492.67 | 20.41 | 394.83 | 20.27 | 394.83 | 20.21 |
Annual Sum or Average | 3658.33 | 21.50 | 3261.83 | 21.91 | 1660.00 | 21.64 |
Minimum of Months | 54.17 | 20.40 | 81.50 | 20.23 | 1.83 | 20.17 |
Maximum of Months | 496.33 | 25.58 | 459.17 | 24.58 | 408.50 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 484.83 | 20.00 | 484.83 | 19.99 |
February | 454.00 | 20.14 | 418.00 | 20.08 | 418.00 | 20.06 |
March | 488.50 | 21.09 | 239.83 | 20.88 | 229.50 | 20.74 |
April | 413.50 | 21.62 | 98.33 | 21.62 | 65.50 | 21.45 |
May | 284.50 | 22.73 | 125.00 | 23.27 | 5.17 | 23.32 |
June | 103.33 | 23.74 | 325.67 | 24.20 | 22.17 | 24.31 |
July | 61.33 | 25.21 | 457.67 | 24.51 | 45.33 | 24.63 |
August | 72.83 | 23.88 | 409.50 | 24.27 | 19.17 | 24.34 |
September | 206.17 | 23.04 | 207.67 | 23.71 | 18.33 | 23.82 |
October | 449.83 | 21.73 | 77.67 | 21.68 | 54.17 | 21.55 |
November | 487.67 | 20.87 | 210.67 | 20.68 | 210.67 | 20.58 |
December | 497.00 | 20.08 | 458.67 | 20.04 | 458.67 | 20.02 |
Annual Sum or Average | 4020.67 | 21.22 | 3513.50 | 21.59 | 2031.50 | 21.34 |
Minimum of Months | 61.33 | 20.02 | 77.67 | 20.00 | 5.17 | 19.99 |
Maximum of Months | 502.00 | 25.21 | 484.83 | 24.51 | 484.83 | 24.63 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22870 | 19.09002 | -0.3197 | 8.77154 |
February | 454.00000 | 22.48940 | 18.43189 | -0.2538 | 7.14550 |
March | 514.00000 | 23.49729 | 24.95695 | 0.06308 | 5.95010 |
April | 485.00000 | 23.95034 | 28.44493 | 0.22252 | 6.39814 |
May | 508.00000 | 24.34555 | 32.19332 | -0.4908 | 10.58280 |
June | 496.00000 | 24.35260 | 43.20354 | -0.3540 | 8.10391 |
July | 497.00000 | 24.44236 | 51.28248 | -0.2549 | 6.85264 |
August | 514.00000 | 24.39254 | 47.90328 | -0.2925 | 7.25954 |
September | 485.00000 | 24.39187 | 43.46061 | -0.3530 | 8.19876 |
October | 502.00000 | 24.18474 | 33.60594 | 0.33215 | 7.56309 |
November | 489.00000 | 23.75169 | 28.27913 | 0.15401 | 5.87768 |
December | 497.00000 | 22.77268 | 21.88597 | -0.1577 | 6.43886 |
Annual Sum or Average | 5943.00000 | 23.74187 | 32.83227 | -0.1422 | 7.43546 |
Minimum of Months | 454.00000 | 22.22870 | 18.43189 | -0.4908 | 5.87768 |
Maximum of Months | 514.00000 | 24.44236 | 51.28248 | 0.33215 | 10.58280 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.83765 | 20.13306 | -0.6405 | 14.84611 |
February | 454.00000 | 21.01032 | 19.57356 | -0.5971 | 13.33920 |
March | 514.00000 | 22.10001 | 27.11124 | -0.2502 | 8.05302 |
April | 485.00000 | 22.93724 | 31.00977 | -0.0093 | 6.04516 |
May | 508.00000 | 23.89176 | 34.01481 | -0.6495 | 14.58466 |
June | 496.00000 | 24.15068 | 44.34286 | -0.4398 | 9.48556 |
July | 497.00000 | 24.28819 | 52.34857 | -0.3234 | 7.50818 |
August | 514.00000 | 24.24926 | 48.94712 | -0.3652 | 8.09141 |
September | 485.00000 | 24.08207 | 44.87828 | -0.4838 | 10.57460 |
October | 502.00000 | 23.18434 | 36.67397 | 0.09161 | 6.04674 |
November | 489.00000 | 22.18742 | 31.55507 | -0.2055 | 6.75585 |
December | 497.00000 | 21.05525 | 23.58479 | -0.5558 | 12.43164 |
Annual Sum or Average | 5943.00000 | 22.84481 | 34.61991 | -0.3681 | 9.79818 |
Minimum of Months | 454.00000 | 20.83765 | 19.57356 | -0.6495 | 6.04516 |
Maximum of Months | 514.00000 | 24.28819 | 52.34857 | 0.09161 | 14.84611 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36959 | 20.16742 | -0.7862 | 19.82175 |
February | 454.00000 | 20.49337 | 19.98161 | -0.7499 | 18.57600 |
March | 514.00000 | 21.48645 | 27.72276 | -0.4135 | 11.18310 |
April | 485.00000 | 22.31207 | 31.85744 | -0.1624 | 7.26586 |
May | 508.00000 | 23.60249 | 34.54835 | -0.7475 | 18.06065 |
June | 496.00000 | 24.05020 | 44.55932 | -0.4696 | 10.28868 |
July | 497.00000 | 24.25488 | 52.17849 | -0.3288 | 7.63872 |
August | 514.00000 | 24.15546 | 48.97212 | -0.3966 | 8.65991 |
September | 485.00000 | 23.79031 | 45.53564 | -0.5899 | 13.58005 |
October | 502.00000 | 22.35037 | 38.29375 | -0.1120 | 7.03652 |
November | 489.00000 | 21.30157 | 32.87641 | -0.4334 | 10.16989 |
December | 497.00000 | 20.46240 | 24.12756 | -0.7318 | 17.94712 |
Annual Sum or Average | 5943.00000 | 22.40096 | 35.17224 | -0.4921 | 12.48412 |
Minimum of Months | 454.00000 | 20.36959 | 19.98161 | -0.7862 | 7.03652 |
Maximum of Months | 514.00000 | 24.25488 | 52.17849 | -0.1120 | 19.82175 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78031 | 20.97308 | -1.0003 | 28.47289 |
February | 454.00000 | 19.83456 | 21.05306 | -0.9699 | 27.28975 |
March | 514.00000 | 20.69691 | 29.43171 | -0.6326 | 17.34657 |
April | 485.00000 | 21.43792 | 33.54913 | -0.3722 | 10.67734 |
May | 508.00000 | 23.13471 | 36.84120 | -0.8871 | 24.22052 |
June | 496.00000 | 23.99301 | 45.71033 | -0.4595 | 11.02676 |
July | 497.00000 | 24.31499 | 53.70421 | -0.2629 | 7.43582 |
August | 514.00000 | 24.06731 | 50.26407 | -0.3986 | 9.52245 |
September | 485.00000 | 23.37478 | 47.78176 | -0.7212 | 18.85167 |
October | 502.00000 | 21.41339 | 40.36186 | -0.3389 | 10.26829 |
November | 489.00000 | 20.42385 | 34.08064 | -0.6735 | 16.52377 |
December | 497.00000 | 19.78355 | 25.08273 | -0.9590 | 27.03670 |
Annual Sum or Average | 5943.00000 | 21.87183 | 36.67635 | -0.6374 | 17.32393 |
Minimum of Months | 454.00000 | 19.78031 | 20.97308 | -1.0003 | 7.43582 |
Maximum of Months | 514.00000 | 24.31499 | 53.70421 | -0.2629 | 28.47289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83227 | 20.51101 | -0.9749 | 27.41407 |
February | 454.00000 | 19.90261 | 20.61694 | -0.9330 | 25.92705 |
March | 514.00000 | 20.86093 | 28.75551 | -0.5579 | 15.40434 |
April | 485.00000 | 21.85759 | 32.28613 | -0.2348 | 10.05701 |
May | 508.00000 | 23.32914 | 35.69991 | -0.7471 | 20.64091 |
June | 496.00000 | 24.05777 | 45.06399 | -0.3520 | 10.01681 |
July | 497.00000 | 24.38291 | 52.96997 | -0.1526 | 7.31863 |
August | 514.00000 | 24.08504 | 49.75701 | -0.3088 | 8.91076 |
September | 485.00000 | 23.49655 | 46.82969 | -0.6076 | 16.55080 |
October | 502.00000 | 21.64898 | 39.32351 | -0.2585 | 9.46708 |
November | 489.00000 | 20.51676 | 33.42797 | -0.6412 | 15.63495 |
December | 497.00000 | 19.83700 | 24.66204 | -0.9422 | 26.24781 |
Annual Sum or Average | 5943.00000 | 22.00104 | 35.93140 | -0.5567 | 16.06426 |
Minimum of Months | 454.00000 | 19.83227 | 20.51101 | -0.9749 | 7.31863 |
Maximum of Months | 514.00000 | 24.38291 | 52.96997 | -0.1526 | 27.41407 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14955 | 20.17445 | -0.8640 | 24.26148 |
February | 454.00000 | 20.19662 | 20.25101 | -0.8312 | 23.63233 |
March | 514.00000 | 21.42463 | 27.89276 | -0.4103 | 13.40080 |
April | 485.00000 | 21.99564 | 31.79852 | -0.2111 | 10.20440 |
May | 508.00000 | 23.23622 | 35.86666 | -0.8067 | 22.80565 |
June | 496.00000 | 23.92830 | 45.50591 | -0.4427 | 11.78726 |
July | 497.00000 | 24.31139 | 53.35717 | -0.2206 | 7.95822 |
August | 514.00000 | 24.10024 | 49.65477 | -0.3212 | 9.30833 |
September | 485.00000 | 23.67554 | 46.11518 | -0.5340 | 15.41426 |
October | 502.00000 | 22.17305 | 37.84149 | -0.1201 | 9.54311 |
November | 489.00000 | 21.02111 | 32.43712 | -0.5048 | 13.74484 |
December | 497.00000 | 20.10050 | 24.30563 | -0.8485 | 23.26515 |
Annual Sum or Average | 5943.00000 | 22.20932 | 35.54045 | -0.5075 | 15.39080 |
Minimum of Months | 454.00000 | 20.10050 | 20.17445 | -0.8640 | 7.95822 |
Maximum of Months | 514.00000 | 24.31139 | 53.35717 | -0.1201 | 24.26148 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83599 | 20.31726 | -0.9836 | 27.78461 |
February | 454.00000 | 19.92982 | 20.38856 | -0.9367 | 26.20511 |
March | 514.00000 | 20.90900 | 28.56361 | -0.5563 | 15.53016 |
April | 485.00000 | 21.63044 | 32.43784 | -0.2950 | 10.80906 |
May | 508.00000 | 23.02926 | 36.36399 | -0.8435 | 24.92648 |
June | 496.00000 | 23.87877 | 45.63126 | -0.4054 | 12.02395 |
July | 497.00000 | 24.24016 | 53.58469 | -0.2093 | 8.23817 |
August | 514.00000 | 23.97218 | 50.22509 | -0.3483 | 10.17545 |
September | 485.00000 | 23.25397 | 47.59391 | -0.6909 | 19.67466 |
October | 502.00000 | 21.42932 | 39.55992 | -0.3115 | 10.20763 |
November | 489.00000 | 20.48183 | 33.30897 | -0.6523 | 16.09004 |
December | 497.00000 | 19.82404 | 24.50930 | -0.9467 | 26.48827 |
Annual Sum or Average | 5943.00000 | 21.88448 | 36.14914 | -0.5959 | 17.28422 |
Minimum of Months | 454.00000 | 19.82404 | 20.31726 | -0.9836 | 8.23817 |
Maximum of Months | 514.00000 | 24.24016 | 53.58469 | -0.2093 | 27.78461 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04070 | 20.99105 | -0.9203 | 24.55336 |
February | 454.00000 | 20.12112 | 21.10380 | -0.8902 | 23.25697 |
March | 514.00000 | 20.76483 | 29.80079 | -0.6229 | 15.37225 |
April | 485.00000 | 21.29024 | 34.04192 | -0.4169 | 9.81533 |
May | 508.00000 | 22.79226 | 38.06014 | -1.0356 | 29.26507 |
June | 496.00000 | 23.93431 | 46.18055 | -0.5244 | 11.61123 |
July | 497.00000 | 24.24182 | 53.89325 | -0.3280 | 7.65553 |
August | 514.00000 | 24.12705 | 50.15288 | -0.4011 | 8.84348 |
September | 485.00000 | 23.71631 | 47.12160 | -0.6118 | 14.21731 |
October | 502.00000 | 22.21164 | 38.74020 | -0.1347 | 6.82062 |
November | 489.00000 | 21.01691 | 33.29852 | -0.4895 | 10.85262 |
December | 497.00000 | 20.21579 | 24.94986 | -0.8183 | 20.64681 |
Annual Sum or Average | 5943.00000 | 22.05466 | 36.63719 | -0.5981 | 15.21288 |
Minimum of Months | 454.00000 | 20.04070 | 20.99105 | -1.0356 | 6.82062 |
Maximum of Months | 514.00000 | 24.24182 | 53.89325 | -0.1347 | 29.26507 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12195 | 20.91082 | -0.8889 | 23.24587 |
February | 454.00000 | 20.20689 | 21.04651 | -0.8501 | 21.71080 |
March | 514.00000 | 21.01217 | 29.39156 | -0.5259 | 12.97218 |
April | 485.00000 | 22.04173 | 32.61846 | -0.2065 | 8.30167 |
May | 508.00000 | 23.40493 | 36.18118 | -0.7748 | 20.37978 |
June | 496.00000 | 24.16424 | 44.92318 | -0.3651 | 9.14042 |
July | 497.00000 | 24.43280 | 52.74898 | -0.1768 | 6.72048 |
August | 514.00000 | 24.25977 | 49.30675 | -0.2732 | 7.57531 |
September | 485.00000 | 23.98583 | 45.82931 | -0.4531 | 11.09631 |
October | 502.00000 | 22.63977 | 37.62433 | -0.0132 | 6.74509 |
November | 489.00000 | 21.16620 | 32.98160 | -0.4422 | 10.18114 |
December | 497.00000 | 20.26253 | 24.88825 | -0.8029 | 19.96518 |
Annual Sum or Average | 5943.00000 | 22.32416 | 35.80910 | -0.4791 | 13.12629 |
Minimum of Months | 454.00000 | 20.12195 | 20.91082 | -0.8889 | 6.72048 |
Maximum of Months | 514.00000 | 24.43280 | 52.74898 | -0.0132 | 23.24587 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71254 | 18.94367 | -0.9167 | 25.15288 |
February | 454.00000 | 19.74761 | 19.25879 | -0.8927 | 24.00690 |
March | 514.00000 | 20.98515 | 27.23722 | -0.4799 | 12.60935 |
April | 485.00000 | 21.65576 | 31.66082 | -0.2809 | 9.10968 |
May | 508.00000 | 22.83008 | 36.53547 | -0.9644 | 27.64867 |
June | 496.00000 | 23.78361 | 46.51736 | -0.5240 | 12.82196 |
July | 497.00000 | 24.28168 | 54.51772 | -0.2608 | 7.77828 |
August | 514.00000 | 24.15277 | 50.09038 | -0.3114 | 8.66327 |
September | 485.00000 | 23.97569 | 45.64236 | -0.4210 | 11.49127 |
October | 502.00000 | 22.71569 | 35.78761 | 0.04307 | 7.46649 |
November | 489.00000 | 21.42163 | 30.44791 | -0.3505 | 9.61127 |
December | 497.00000 | 19.99945 | 23.08999 | -0.8110 | 21.04262 |
Annual Sum or Average | 5943.00000 | 22.12246 | 35.09166 | -0.5124 | 14.74487 |
Minimum of Months | 454.00000 | 19.71254 | 18.94367 | -0.9644 | 7.46649 |
Maximum of Months | 514.00000 | 24.28168 | 54.51772 | 0.04307 | 27.64867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.09136 | 20.81475 | -0.9039 | 23.93781 |
February | 454.00000 | 20.20134 | 20.91275 | -0.8600 | 22.19503 |
March | 514.00000 | 21.02370 | 29.28276 | -0.5284 | 13.01581 |
April | 485.00000 | 21.80097 | 32.84248 | -0.2680 | 8.75754 |
May | 508.00000 | 23.22728 | 36.62579 | -0.8355 | 22.75705 |
June | 496.00000 | 24.12679 | 45.14443 | -0.3733 | 9.50757 |
July | 497.00000 | 24.39218 | 53.06525 | -0.2014 | 6.95567 |
August | 514.00000 | 24.26110 | 49.45403 | -0.2778 | 7.78094 |
September | 485.00000 | 23.90985 | 46.26133 | -0.4889 | 11.97958 |
October | 502.00000 | 22.37882 | 38.00182 | -0.0740 | 6.86910 |
November | 489.00000 | 21.09547 | 32.98214 | -0.4603 | 10.41451 |
December | 497.00000 | 20.24650 | 24.79207 | -0.8078 | 20.18893 |
Annual Sum or Average | 5943.00000 | 22.24550 | 35.95444 | -0.5046 | 13.65447 |
Minimum of Months | 454.00000 | 20.09136 | 20.81475 | -0.9039 | 6.86910 |
Maximum of Months | 514.00000 | 24.39218 | 53.06525 | -0.0740 | 23.93781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97012 | 20.88555 | -0.9149 | 24.71851 |
February | 454.00000 | 20.05400 | 20.94192 | -0.8784 | 23.24983 |
March | 514.00000 | 21.00636 | 29.10188 | -0.5284 | 14.03528 |
April | 485.00000 | 21.87240 | 32.90529 | -0.2538 | 8.43598 |
May | 508.00000 | 23.46451 | 36.16359 | -0.7770 | 19.42697 |
June | 496.00000 | 24.10601 | 45.34323 | -0.4255 | 9.64094 |
July | 497.00000 | 24.35751 | 53.65076 | -0.2555 | 7.03370 |
August | 514.00000 | 24.18018 | 50.03488 | -0.3627 | 8.43278 |
September | 485.00000 | 23.71112 | 46.94929 | -0.6038 | 14.35762 |
October | 502.00000 | 22.02567 | 39.14611 | -0.1769 | 7.69488 |
November | 489.00000 | 20.86385 | 33.45386 | -0.5306 | 12.15149 |
December | 497.00000 | 20.05121 | 24.80150 | -0.8522 | 22.41451 |
Annual Sum or Average | 5943.00000 | 22.15554 | 36.22082 | -0.5446 | 14.24517 |
Minimum of Months | 454.00000 | 19.97012 | 20.88555 | -0.9149 | 7.03370 |
Maximum of Months | 514.00000 | 24.35751 | 53.65076 | -0.1769 | 24.71851 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.86144 | 19.83863 | -0.9315 | 25.37397 |
February | 385.00000 | 19.97709 | 19.95577 | -0.8825 | 23.49015 |
March | 433.00000 | 21.06137 | 27.95873 | -0.4916 | 12.92830 |
April | 410.00000 | 22.06627 | 31.48735 | -0.1763 | 8.62648 |
May | 430.00000 | 23.50921 | 35.01520 | -0.6991 | 18.56469 |
June | 418.00000 | 24.16484 | 44.60500 | -0.3410 | 9.47499 |
July | 422.00000 | 24.48915 | 52.75606 | -0.1497 | 7.22560 |
August | 433.00000 | 24.20658 | 49.34098 | -0.2952 | 8.43634 |
September | 410.00000 | 23.72732 | 46.23426 | -0.5405 | 14.11335 |
October | 427.00000 | 22.05218 | 37.91709 | -0.1518 | 7.75574 |
November | 417.00000 | 20.83377 | 32.16614 | -0.5344 | 12.29816 |
December | 422.00000 | 19.92380 | 23.77184 | -0.8797 | 23.37388 |
Annual Sum or Average | 5034.00000 | 22.17014 | 35.17894 | -0.5040 | 14.25288 |
Minimum of Months | 385.00000 | 19.86144 | 19.83863 | -0.9315 | 7.22560 |
Maximum of Months | 433.00000 | 24.48915 | 52.75606 | -0.1497 | 25.37397 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44934 | 20.00623 | -0.7581 | 20.36048 |
February | 454.00000 | 20.51883 | 20.05147 | -0.7211 | 19.31784 |
March | 514.00000 | 21.82745 | 27.45663 | -0.2904 | 10.64254 |
April | 485.00000 | 22.43492 | 31.12115 | -0.0935 | 8.35146 |
May | 508.00000 | 23.56983 | 35.18328 | -0.6969 | 18.01639 |
June | 496.00000 | 24.08580 | 45.05837 | -0.3978 | 9.92539 |
July | 497.00000 | 24.39288 | 53.21566 | -0.2035 | 7.24699 |
August | 514.00000 | 24.23702 | 49.38887 | -0.2804 | 8.04825 |
September | 485.00000 | 23.98269 | 45.41714 | -0.4269 | 11.64062 |
October | 502.00000 | 22.76770 | 36.66889 | 0.03589 | 8.05366 |
November | 489.00000 | 21.52777 | 31.76014 | -0.3510 | 10.27102 |
December | 497.00000 | 20.43883 | 23.97874 | -0.7285 | 18.70487 |
Annual Sum or Average | 5943.00000 | 22.53553 | 35.04835 | -0.4075 | 12.50771 |
Minimum of Months | 454.00000 | 20.43883 | 20.00623 | -0.7581 | 7.24699 |
Maximum of Months | 514.00000 | 24.39288 | 53.21566 | 0.03589 | 20.36048 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01575 | 20.19557 | -0.9006 | 24.22043 |
February | 454.00000 | 20.13777 | 20.27096 | -0.8482 | 22.40327 |
March | 514.00000 | 21.22915 | 28.24174 | -0.4508 | 12.51287 |
April | 485.00000 | 22.01836 | 31.86667 | -0.1860 | 8.81935 |
May | 508.00000 | 23.38713 | 35.68400 | -0.7270 | 19.77492 |
June | 496.00000 | 24.05331 | 45.17074 | -0.3559 | 9.98784 |
July | 497.00000 | 24.33921 | 53.40186 | -0.1874 | 7.38400 |
August | 514.00000 | 24.13872 | 49.90535 | -0.2991 | 8.61037 |
September | 485.00000 | 23.63172 | 46.78945 | -0.5634 | 14.77499 |
October | 502.00000 | 21.96622 | 38.52909 | -0.1641 | 7.88955 |
November | 489.00000 | 20.87860 | 32.80670 | -0.5181 | 11.98641 |
December | 497.00000 | 20.07610 | 24.19933 | -0.8437 | 22.03437 |
Annual Sum or Average | 5943.00000 | 22.17264 | 35.69595 | -0.5014 | 14.14653 |
Minimum of Months | 454.00000 | 20.01575 | 20.19557 | -0.9006 | 7.38400 |
Maximum of Months | 514.00000 | 24.33921 | 53.40186 | -0.1641 | 24.22043 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.197533E+10 | 0.506315E+09 | 33.50 | 0.161792E+10 | 0.357407E+09 | 0.00 | 0.87 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 30275.48 | 15-MAR-14:00 | 30275.48 | 15-MAR-14:00 | 8709.44 | 14-MAR-11:00 | 7590.74 | 15-MAR-14:00 | 0.00 |
April | 0.672434E+09 | 0.186866E+09 | 34.50 | 0.599278E+09 | 73156051.55 | 0.00 | 0.43 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 13563.52 | 07-APR-13:00 | 13563.52 | 07-APR-13:00 | 2907.50 | 08-APR-14:00 | 3617.91 | 07-APR-13:00 | 0.00 |
May | 0.758819E+10 | 0.197285E+10 | 185.58 | 0.682157E+10 | 0.766621E+09 | 0.00 | 1.00 | 10-MAY-14:50 | 0.00 | 01-MAY-00:10 | 38301.85 | 23-MAY-14:30 | 38301.85 | 23-MAY-14:30 | 7413.63 | 17-MAY-13:00 | 9160.94 | 10-MAY-15:10 | 0.00 |
June | 0.375193E+11 | 0.917452E+10 | 370.06 | 0.283090E+11 | 0.921031E+10 | 0.00 | 1.00 | 01-JUN-14:20 | 0.00 | 01-JUN-00:10 | 100775.23 | 27-JUN-07:40 | 61358.39 | 12-JUN-15:10 | 57219.47 | 27-JUN-07:40 | 22746.98 | 27-JUN-07:40 | 0.00 |
July | 0.662434E+11 | 0.159881E+11 | 422.86 | 0.469698E+11 | 0.192736E+11 | 0.00 | 1.00 | 03-JUL-10:20 | 0.00 | 01-JUL-00:10 | 124283.10 | 20-JUL-04:03 | 65571.84 | 17-JUL-12:10 | 74419.57 | 20-JUL-04:03 | 28354.06 | 21-JUL-04:03 | 0.00 |
August | 0.565934E+11 | 0.137213E+11 | 413.72 | 0.438517E+11 | 0.127417E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 124256.29 | 14-AUG-08:00 | 67060.59 | 09-AUG-15:50 | 75975.89 | 14-AUG-06:03 | 27894.85 | 14-AUG-08:00 | 0.00 |
September | 0.252157E+11 | 0.613292E+10 | 301.84 | 0.189121E+11 | 0.630357E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 81902.67 | 15-SEP-14:50 | 56938.82 | 21-SEP-16:00 | 37508.21 | 15-SEP-14:50 | 18852.07 | 15-SEP-14:50 | 0.00 |
October | 0.267823E+10 | 0.712499E+09 | 83.50 | 0.225572E+10 | 0.422508E+09 | 0.00 | 0.89 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 31647.97 | 11-OCT-15:10 | 31647.97 | 11-OCT-15:10 | 6088.73 | 12-OCT-15:00 | 7453.40 | 11-OCT-15:10 | 0.00 |
November | 0.442975E+09 | 0.123445E+09 | 18.83 | 0.314186E+09 | 0.128790E+09 | 0.00 | 0.36 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 11079.55 | 16-NOV-18:00 | 8991.35 | 16-NOV-13:00 | 2899.44 | 04-NOV-15:00 | 3010.16 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.198929E+12 | 0.485189E+11 | 1864.39 | 0.149651E+12 | 0.492777E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.662434E+11 | 0.159881E+11 | 422.86 | 0.469698E+11 | 0.192736E+11 | 0.00 | 1.00 | 0.00 | 124283.10 | 67060.59 | 75975.89 | 28354.06 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.188361E+10 | 0.479607E+09 | 33.50 | 0.155012E+10 | 0.333488E+09 | 0.00 | 0.97 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 32153.81 | 15-MAR-13:50 | 32153.81 | 15-MAR-13:50 | 8198.10 | 14-MAR-10:40 | 7796.62 | 15-MAR-14:00 | 0.00 |
April | 0.670564E+09 | 0.186141E+09 | 37.78 | 0.604842E+09 | 65721890.91 | 0.00 | 0.47 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 13641.11 | 08-APR-13:30 | 12114.24 | 07-APR-14:00 | 2236.58 | 08-APR-14:10 | 3605.93 | 08-APR-13:30 | 0.00 |
May | 0.757838E+10 | 0.196305E+10 | 194.90 | 0.683235E+10 | 0.746029E+09 | 0.00 | 1.00 | 10-MAY-13:40 | 0.00 | 01-MAY-00:10 | 38476.16 | 23-MAY-14:30 | 38476.16 | 23-MAY-14:30 | 7159.71 | 14-MAY-16:05 | 9102.67 | 10-MAY-15:00 | 0.00 |
June | 0.351491E+11 | 0.859660E+10 | 377.06 | 0.267309E+11 | 0.841821E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 86142.98 | 27-JUN-07:40 | 59575.50 | 12-JUN-15:00 | 48867.96 | 27-JUN-07:40 | 20293.24 | 27-JUN-13:00 | 0.00 |
July | 0.606610E+11 | 0.146435E+11 | 428.33 | 0.429910E+11 | 0.176700E+11 | 0.00 | 1.00 | 02-JUL-13:53 | 0.00 | 01-JUL-00:10 | 114498.32 | 20-JUL-06:03 | 61944.24 | 21-JUL-13:40 | 68835.46 | 20-JUL-05:03 | 26259.17 | 21-JUL-04:03 | 0.00 |
August | 0.495615E+11 | 0.120596E+11 | 414.71 | 0.385107E+11 | 0.110508E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 113103.93 | 14-AUG-06:03 | 62590.56 | 09-AUG-15:20 | 70168.88 | 14-AUG-06:03 | 25584.03 | 15-AUG-14:30 | 0.00 |
September | 0.212570E+11 | 0.521611E+10 | 300.57 | 0.159274E+11 | 0.532959E+10 | 0.00 | 1.00 | 08-SEP-12:20 | 0.00 | 01-SEP-00:10 | 73522.92 | 15-SEP-11:00 | 51842.27 | 21-SEP-15:30 | 32634.64 | 15-SEP-11:00 | 16833.78 | 15-SEP-11:00 | 0.00 |
October | 0.230472E+10 | 0.619425E+09 | 83.94 | 0.190753E+10 | 0.397191E+09 | 0.00 | 0.82 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 26275.79 | 11-OCT-15:00 | 26275.79 | 11-OCT-15:00 | 5501.20 | 12-OCT-15:00 | 6316.65 | 11-OCT-15:00 | 0.00 |
November | 0.394488E+09 | 0.110248E+09 | 18.83 | 0.273606E+09 | 0.120883E+09 | 0.00 | 0.33 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 9258.36 | 16-NOV-18:00 | 7010.76 | 16-NOV-12:40 | 2773.53 | 04-NOV-15:00 | 2534.96 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.179460E+12 | 0.438742E+11 | 1889.63 | 0.135328E+12 | 0.441319E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.606610E+11 | 0.146435E+11 | 428.33 | 0.429910E+11 | 0.176700E+11 | 0.00 | 1.00 | 0.00 | 114498.32 | 62590.56 | 70168.88 | 26259.17 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.206944E+10 | 0.525878E+09 | 33.50 | 0.171990E+10 | 0.349533E+09 | 0.00 | 1.00 | 15-MAR-13:30 | 0.00 | 01-MAR-00:10 | 39210.20 | 15-MAR-14:00 | 39210.20 | 15-MAR-14:00 | 8979.03 | 14-MAR-10:50 | 9465.48 | 15-MAR-14:00 | 0.00 |
April | 0.692355E+09 | 0.192841E+09 | 36.94 | 0.612057E+09 | 80298400.75 | 0.00 | 0.45 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 14440.59 | 08-APR-13:30 | 12472.61 | 07-APR-14:00 | 2687.27 | 08-APR-14:00 | 3835.50 | 08-APR-13:30 | 0.00 |
May | 0.789674E+10 | 0.205357E+10 | 194.71 | 0.702448E+10 | 0.872257E+09 | 0.00 | 1.00 | 10-MAY-13:10 | 0.00 | 01-MAY-00:10 | 44197.95 | 10-MAY-14:30 | 44197.95 | 10-MAY-14:30 | 7962.84 | 14-MAY-16:05 | 10662.32 | 10-MAY-14:30 | 0.00 |
June | 0.374543E+11 | 0.918992E+10 | 375.79 | 0.281826E+11 | 0.927169E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 126626.42 | 27-JUN-15:00 | 80321.62 | 27-JUN-15:05 | 70839.05 | 27-JUN-15:00 | 28883.58 | 27-JUN-15:15 | 0.00 |
July | 0.646352E+11 | 0.156574E+11 | 428.45 | 0.457408E+11 | 0.188945E+11 | 0.00 | 1.00 | 02-JUL-13:53 | 0.00 | 01-JUL-00:10 | 126626.42 | 21-JUL-05:03 | 72851.73 | 21-JUL-13:30 | 73585.50 | 17-JUL-06:03 | 29128.65 | 21-JUL-04:03 | 0.00 |
August | 0.520614E+11 | 0.127292E+11 | 413.94 | 0.401571E+11 | 0.119043E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 125277.48 | 15-AUG-14:20 | 71047.95 | 09-AUG-14:50 | 74472.50 | 14-AUG-06:03 | 28573.47 | 15-AUG-14:20 | 0.00 |
September | 0.215240E+11 | 0.532544E+10 | 298.97 | 0.156709E+11 | 0.585309E+10 | 0.00 | 1.00 | 08-SEP-12:50 | 0.00 | 01-SEP-00:10 | 85228.38 | 15-SEP-12:30 | 57949.32 | 21-SEP-15:20 | 37703.94 | 15-SEP-12:30 | 19805.71 | 15-SEP-12:30 | 0.00 |
October | 0.223683E+10 | 0.606956E+09 | 82.33 | 0.179035E+10 | 0.446481E+09 | 0.00 | 0.74 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25662.07 | 11-OCT-15:00 | 25662.07 | 11-OCT-15:00 | 5934.23 | 12-OCT-15:00 | 6309.63 | 11-OCT-15:00 | 0.00 |
November | 0.415677E+09 | 0.116489E+09 | 18.83 | 0.283584E+09 | 0.132092E+09 | 0.00 | 0.32 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 10046.68 | 27-NOV-07:03 | 8513.55 | 27-NOV-07:03 | 3019.95 | 04-NOV-15:00 | 2755.03 | 27-NOV-07:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.188986E+12 | 0.463977E+11 | 1883.48 | 0.141182E+12 | 0.478042E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.646352E+11 | 0.156574E+11 | 428.45 | 0.457408E+11 | 0.188945E+11 | 0.00 | 1.00 | 0.00 | 126626.42 | 80321.62 | 74472.50 | 29128.65 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.09 | 0.00 | 363.09 | 6.04 | 2145.34 | 0.00 | 0.00 | 0.00 |
February | 553.22 | 0.00 | 553.22 | 37.57 | 2004.99 | 0.00 | 0.00 | 0.00 |
March | 670.90 | 0.00 | 670.90 | 224.69 | 1433.02 | 0.00 | 0.00 | 0.00 |
April | 854.86 | 3.41 | 851.45 | 476.89 | 1008.50 | 0.00 | 0.00 | 0.00 |
May | 993.30 | 42.12 | 951.18 | 783.89 | 662.68 | 0.00 | 0.00 | 0.00 |
June | 1194.74 | 101.70 | 1093.03 | 1282.95 | 439.89 | 0.00 | 0.00 | 0.00 |
July | 1108.28 | 71.54 | 1036.73 | 1376.10 | 311.43 | 0.00 | 0.00 | 0.00 |
August | 958.97 | 14.59 | 944.38 | 1126.40 | 409.08 | 0.00 | 0.00 | 0.00 |
September | 729.79 | 0.15 | 729.64 | 663.45 | 652.04 | 0.00 | 0.00 | 0.00 |
October | 545.55 | 0.00 | 545.55 | 282.54 | 994.20 | 0.00 | 0.00 | 0.00 |
November | 366.60 | 0.00 | 366.60 | 88.56 | 1286.65 | 0.00 | 0.00 | 0.00 |
December | 339.84 | 0.00 | 339.84 | 6.92 | 2029.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 723.97 | 19.54 | 704.42 | 532.63 | 1110.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.84 | 0.00 | 339.84 | 6.04 | 311.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1194.74 | 101.70 | 1093.03 | 1376.10 | 2145.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 442.97 | 142.84 | 300.13 | 175.12 | 1297.86 | 0.00 | 0.00 | 0.00 |
February | 649.98 | 195.04 | 454.94 | 313.86 | 1227.74 | 0.00 | 0.00 | 0.00 |
March | 932.70 | 390.61 | 542.09 | 739.56 | 877.72 | 0.00 | 0.00 | 0.00 |
April | 1234.49 | 545.46 | 689.03 | 1171.43 | 639.07 | 0.00 | 0.00 | 0.00 |
May | 1383.07 | 611.81 | 771.26 | 1501.59 | 447.97 | 0.00 | 0.00 | 0.00 |
June | 1544.66 | 682.66 | 861.99 | 1871.29 | 297.37 | 0.00 | 0.00 | 0.00 |
July | 1483.28 | 653.07 | 830.21 | 1931.08 | 208.89 | 0.00 | 0.00 | 0.00 |
August | 1339.56 | 562.27 | 777.29 | 1707.46 | 270.54 | 0.00 | 0.00 | 0.00 |
September | 1114.75 | 494.46 | 620.29 | 1287.39 | 415.95 | 0.00 | 0.00 | 0.00 |
October | 756.45 | 312.89 | 443.56 | 690.56 | 626.68 | 0.00 | 0.00 | 0.00 |
November | 429.07 | 137.64 | 291.43 | 276.51 | 818.76 | 0.00 | 0.00 | 0.00 |
December | 345.42 | 71.37 | 274.05 | 92.27 | 1270.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 972.81 | 400.98 | 571.83 | 983.44 | 697.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.42 | 71.37 | 274.05 | 92.27 | 208.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1544.66 | 682.66 | 861.99 | 1931.08 | 1297.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1561.30 | 911.38 | 649.92 | 1271.02 | 1826.53 | 0.00 | 0.00 | 0.00 |
February | 1782.62 | 859.56 | 923.05 | 1429.79 | 1794.14 | 0.00 | 0.00 | 0.00 |
March | 2175.80 | 1222.57 | 953.23 | 2145.10 | 1324.25 | 0.00 | 0.00 | 0.00 |
April | 1801.91 | 720.05 | 1081.86 | 1855.54 | 1047.05 | 0.00 | 0.00 | 0.00 |
May | 1576.83 | 457.98 | 1118.85 | 1753.43 | 729.87 | 0.00 | 0.00 | 0.00 |
June | 1532.17 | 324.67 | 1207.49 | 1897.82 | 482.24 | 0.00 | 0.00 | 0.00 |
July | 1564.10 | 379.50 | 1184.59 | 2144.22 | 337.69 | 0.00 | 0.00 | 0.00 |
August | 1755.95 | 569.32 | 1186.63 | 2371.18 | 433.15 | 0.00 | 0.00 | 0.00 |
September | 2041.65 | 994.44 | 1047.22 | 2547.74 | 668.93 | 0.00 | 0.00 | 0.00 |
October | 1953.56 | 1115.91 | 837.65 | 2126.28 | 968.03 | 0.00 | 0.00 | 0.00 |
November | 1399.10 | 789.84 | 609.26 | 1343.00 | 1220.03 | 0.00 | 0.00 | 0.00 |
December | 1305.56 | 675.69 | 629.87 | 1008.85 | 1788.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1703.68 | 751.34 | 952.34 | 1826.79 | 1047.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.56 | 324.67 | 609.26 | 1008.85 | 337.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2175.80 | 1222.57 | 1207.49 | 2547.74 | 1826.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.06 | 89.22 | 290.84 | 108.04 | 1349.30 | 0.00 | 0.00 | 0.00 |
February | 615.98 | 158.31 | 457.67 | 269.74 | 1268.91 | 0.00 | 0.00 | 0.00 |
March | 965.44 | 413.38 | 552.06 | 781.53 | 902.33 | 0.00 | 0.00 | 0.00 |
April | 1182.05 | 484.69 | 697.36 | 1123.33 | 669.24 | 0.00 | 0.00 | 0.00 |
May | 1394.42 | 630.19 | 764.23 | 1531.37 | 474.84 | 0.00 | 0.00 | 0.00 |
June | 1682.40 | 791.33 | 891.07 | 2067.03 | 324.79 | 0.00 | 0.00 | 0.00 |
July | 1504.13 | 659.46 | 844.67 | 1970.07 | 231.60 | 0.00 | 0.00 | 0.00 |
August | 1360.40 | 578.46 | 781.94 | 1755.04 | 290.00 | 0.00 | 0.00 | 0.00 |
September | 1068.34 | 461.37 | 606.97 | 1240.65 | 437.67 | 0.00 | 0.00 | 0.00 |
October | 692.55 | 243.95 | 448.59 | 621.53 | 649.18 | 0.00 | 0.00 | 0.00 |
November | 410.41 | 118.26 | 292.14 | 255.33 | 835.18 | 0.00 | 0.00 | 0.00 |
December | 355.79 | 77.52 | 278.26 | 104.54 | 1290.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 969.26 | 393.32 | 575.94 | 989.53 | 724.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.79 | 77.52 | 278.26 | 104.54 | 231.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1682.40 | 791.33 | 891.07 | 2067.03 | 1349.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 1.16 | 730.40 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 11.72 | 682.64 | 0.00 | 0.00 | 0.00 |
March | 223.62 | 0.00 | 223.62 | 79.40 | 484.86 | 0.00 | 0.00 | 0.00 |
April | 284.94 | 1.14 | 283.80 | 168.17 | 337.68 | 0.00 | 0.00 | 0.00 |
May | 331.09 | 14.04 | 317.05 | 277.23 | 214.10 | 0.00 | 0.00 | 0.00 |
June | 398.23 | 33.90 | 364.33 | 438.92 | 143.92 | 0.00 | 0.00 | 0.00 |
July | 369.41 | 23.85 | 345.56 | 468.53 | 100.99 | 0.00 | 0.00 | 0.00 |
August | 319.64 | 4.86 | 314.78 | 380.10 | 138.40 | 0.00 | 0.00 | 0.00 |
September | 243.25 | 0.05 | 243.20 | 220.77 | 231.31 | 0.00 | 0.00 | 0.00 |
October | 181.84 | 0.00 | 181.84 | 87.24 | 367.63 | 0.00 | 0.00 | 0.00 |
November | 122.19 | 0.00 | 122.19 | 25.57 | 469.50 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.59 | 708.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.31 | 6.51 | 234.80 | 181.05 | 382.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 1.16 | 100.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.23 | 33.90 | 364.33 | 468.53 | 730.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 1.16 | 730.45 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 11.72 | 682.68 | 0.00 | 0.00 | 0.00 |
March | 223.63 | 0.00 | 223.63 | 79.40 | 484.89 | 0.00 | 0.00 | 0.00 |
April | 284.95 | 1.14 | 283.81 | 168.17 | 337.70 | 0.00 | 0.00 | 0.00 |
May | 331.10 | 14.04 | 317.06 | 277.24 | 214.11 | 0.00 | 0.00 | 0.00 |
June | 398.24 | 33.90 | 364.34 | 438.93 | 143.93 | 0.00 | 0.00 | 0.00 |
July | 369.42 | 23.85 | 345.58 | 468.55 | 100.99 | 0.00 | 0.00 | 0.00 |
August | 319.65 | 4.86 | 314.79 | 380.11 | 138.41 | 0.00 | 0.00 | 0.00 |
September | 243.26 | 0.05 | 243.21 | 220.78 | 231.33 | 0.00 | 0.00 | 0.00 |
October | 181.85 | 0.00 | 181.85 | 87.24 | 367.65 | 0.00 | 0.00 | 0.00 |
November | 122.20 | 0.00 | 122.20 | 25.57 | 469.53 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.59 | 708.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.32 | 6.51 | 234.81 | 181.06 | 382.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 1.16 | 100.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.24 | 33.90 | 364.34 | 468.55 | 730.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 1.16 | 730.45 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 11.72 | 682.68 | 0.00 | 0.00 | 0.00 |
March | 223.63 | 0.00 | 223.63 | 79.40 | 484.89 | 0.00 | 0.00 | 0.00 |
April | 284.95 | 1.14 | 283.81 | 168.17 | 337.70 | 0.00 | 0.00 | 0.00 |
May | 331.10 | 14.04 | 317.06 | 277.24 | 214.11 | 0.00 | 0.00 | 0.00 |
June | 398.24 | 33.90 | 364.34 | 438.93 | 143.93 | 0.00 | 0.00 | 0.00 |
July | 369.42 | 23.85 | 345.58 | 468.55 | 100.99 | 0.00 | 0.00 | 0.00 |
August | 319.65 | 4.86 | 314.79 | 380.11 | 138.41 | 0.00 | 0.00 | 0.00 |
September | 243.26 | 0.05 | 243.21 | 220.78 | 231.33 | 0.00 | 0.00 | 0.00 |
October | 181.85 | 0.00 | 181.85 | 87.24 | 367.65 | 0.00 | 0.00 | 0.00 |
November | 122.20 | 0.00 | 122.20 | 25.57 | 469.53 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.59 | 708.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.32 | 6.51 | 234.81 | 181.06 | 382.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 1.16 | 100.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.24 | 33.90 | 364.34 | 468.55 | 730.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.12 | 137.40 | 288.72 | 167.70 | 1282.55 | 0.00 | 0.00 | 0.00 |
February | 625.25 | 187.62 | 437.63 | 302.34 | 1211.98 | 0.00 | 0.00 | 0.00 |
March | 897.21 | 375.75 | 521.47 | 722.74 | 869.72 | 0.00 | 0.00 | 0.00 |
April | 1187.52 | 524.71 | 662.81 | 1139.92 | 636.88 | 0.00 | 0.00 | 0.00 |
May | 1330.45 | 588.52 | 741.92 | 1465.29 | 436.16 | 0.00 | 0.00 | 0.00 |
June | 1485.88 | 656.68 | 829.20 | 1817.36 | 292.87 | 0.00 | 0.00 | 0.00 |
July | 1426.84 | 628.21 | 798.62 | 1873.11 | 205.32 | 0.00 | 0.00 | 0.00 |
August | 1288.59 | 540.88 | 747.71 | 1650.76 | 274.70 | 0.00 | 0.00 | 0.00 |
September | 1072.33 | 475.64 | 596.69 | 1236.00 | 438.65 | 0.00 | 0.00 | 0.00 |
October | 727.67 | 300.98 | 426.68 | 645.93 | 680.90 | 0.00 | 0.00 | 0.00 |
November | 412.74 | 132.40 | 280.34 | 254.80 | 868.36 | 0.00 | 0.00 | 0.00 |
December | 332.28 | 68.66 | 263.62 | 86.00 | 1281.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 935.79 | 385.72 | 550.07 | 950.31 | 704.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.28 | 68.66 | 263.62 | 86.00 | 205.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1485.88 | 656.68 | 829.20 | 1873.11 | 1282.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.85 | 5.43 | 11.42 | 6.63 | 50.71 | 0.00 | 0.00 | 0.00 |
February | 24.72 | 7.42 | 17.30 | 11.95 | 47.92 | 0.00 | 0.00 | 0.00 |
March | 35.47 | 14.86 | 20.62 | 28.58 | 34.39 | 0.00 | 0.00 | 0.00 |
April | 46.95 | 20.75 | 26.21 | 45.07 | 25.18 | 0.00 | 0.00 | 0.00 |
May | 52.60 | 23.27 | 29.33 | 57.94 | 17.25 | 0.00 | 0.00 | 0.00 |
June | 58.75 | 25.96 | 32.79 | 71.86 | 11.58 | 0.00 | 0.00 | 0.00 |
July | 56.42 | 24.84 | 31.58 | 74.06 | 8.12 | 0.00 | 0.00 | 0.00 |
August | 50.95 | 21.39 | 29.56 | 65.27 | 10.86 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 18.81 | 23.59 | 48.87 | 17.34 | 0.00 | 0.00 | 0.00 |
October | 28.77 | 11.90 | 16.87 | 25.54 | 26.92 | 0.00 | 0.00 | 0.00 |
November | 16.32 | 5.24 | 11.08 | 10.07 | 34.33 | 0.00 | 0.00 | 0.00 |
December | 13.14 | 2.71 | 10.42 | 3.40 | 50.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 15.25 | 21.75 | 37.57 | 27.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.14 | 2.71 | 10.42 | 3.40 | 8.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.75 | 25.96 | 32.79 | 74.06 | 50.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.42 | 303.79 | 216.64 | 431.50 | 622.81 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 286.51 | 307.68 | 487.60 | 609.79 | 0.00 | 0.00 | 0.00 |
March | 725.26 | 407.51 | 317.74 | 730.79 | 458.74 | 0.00 | 0.00 | 0.00 |
April | 600.63 | 240.01 | 360.62 | 632.66 | 357.36 | 0.00 | 0.00 | 0.00 |
May | 525.60 | 152.66 | 372.95 | 601.79 | 240.00 | 0.00 | 0.00 | 0.00 |
June | 510.72 | 108.22 | 402.50 | 646.39 | 160.07 | 0.00 | 0.00 | 0.00 |
July | 521.36 | 126.50 | 394.86 | 725.14 | 112.92 | 0.00 | 0.00 | 0.00 |
August | 585.31 | 189.77 | 395.54 | 796.79 | 151.52 | 0.00 | 0.00 | 0.00 |
September | 680.54 | 331.47 | 349.07 | 851.56 | 244.62 | 0.00 | 0.00 | 0.00 |
October | 651.18 | 371.96 | 279.21 | 706.53 | 364.64 | 0.00 | 0.00 | 0.00 |
November | 466.36 | 263.27 | 203.08 | 444.83 | 451.89 | 0.00 | 0.00 | 0.00 |
December | 435.18 | 225.22 | 209.95 | 338.81 | 621.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.89 | 250.44 | 317.44 | 616.95 | 365.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.18 | 108.22 | 203.08 | 338.81 | 112.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.26 | 407.51 | 402.50 | 851.56 | 622.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.42 | 303.79 | 216.64 | 431.50 | 622.81 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 286.51 | 307.68 | 487.60 | 609.79 | 0.00 | 0.00 | 0.00 |
March | 725.26 | 407.51 | 317.74 | 730.79 | 458.74 | 0.00 | 0.00 | 0.00 |
April | 600.63 | 240.01 | 360.62 | 632.66 | 357.36 | 0.00 | 0.00 | 0.00 |
May | 525.60 | 152.66 | 372.95 | 601.79 | 240.00 | 0.00 | 0.00 | 0.00 |
June | 510.72 | 108.22 | 402.50 | 646.39 | 160.07 | 0.00 | 0.00 | 0.00 |
July | 521.36 | 126.50 | 394.86 | 725.14 | 112.92 | 0.00 | 0.00 | 0.00 |
August | 585.31 | 189.77 | 395.54 | 796.79 | 151.52 | 0.00 | 0.00 | 0.00 |
September | 680.54 | 331.47 | 349.07 | 851.56 | 244.62 | 0.00 | 0.00 | 0.00 |
October | 651.18 | 371.96 | 279.21 | 706.53 | 364.64 | 0.00 | 0.00 | 0.00 |
November | 466.36 | 263.27 | 203.08 | 444.83 | 451.89 | 0.00 | 0.00 | 0.00 |
December | 435.18 | 225.22 | 209.95 | 338.81 | 621.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.89 | 250.44 | 317.44 | 616.95 | 365.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.18 | 108.22 | 203.08 | 338.81 | 112.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.26 | 407.51 | 402.50 | 851.56 | 622.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.39 | 303.77 | 216.62 | 431.47 | 622.78 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.50 | 307.66 | 487.57 | 609.75 | 0.00 | 0.00 | 0.00 |
March | 725.21 | 407.49 | 317.72 | 730.75 | 458.71 | 0.00 | 0.00 | 0.00 |
April | 600.59 | 240.00 | 360.59 | 632.62 | 357.34 | 0.00 | 0.00 | 0.00 |
May | 525.57 | 152.65 | 372.92 | 601.76 | 239.98 | 0.00 | 0.00 | 0.00 |
June | 510.69 | 108.22 | 402.47 | 646.35 | 160.06 | 0.00 | 0.00 | 0.00 |
July | 521.33 | 126.49 | 394.84 | 725.09 | 112.91 | 0.00 | 0.00 | 0.00 |
August | 585.27 | 189.76 | 395.51 | 796.74 | 151.51 | 0.00 | 0.00 | 0.00 |
September | 680.50 | 331.45 | 349.05 | 851.51 | 244.60 | 0.00 | 0.00 | 0.00 |
October | 651.13 | 371.94 | 279.19 | 706.49 | 364.62 | 0.00 | 0.00 | 0.00 |
November | 466.33 | 263.26 | 203.07 | 444.80 | 451.86 | 0.00 | 0.00 | 0.00 |
December | 435.15 | 225.21 | 209.94 | 338.79 | 621.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.85 | 250.43 | 317.42 | 616.91 | 365.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.15 | 108.22 | 203.07 | 338.79 | 112.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.21 | 407.49 | 402.47 | 851.51 | 622.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.60 | 85.83 | 279.77 | 104.57 | 1327.72 | 0.00 | 0.00 | 0.00 |
February | 592.54 | 152.29 | 440.26 | 264.48 | 1249.84 | 0.00 | 0.00 | 0.00 |
March | 928.71 | 397.65 | 531.06 | 768.66 | 896.08 | 0.00 | 0.00 | 0.00 |
April | 1137.07 | 466.24 | 670.83 | 1098.95 | 665.15 | 0.00 | 0.00 | 0.00 |
May | 1341.36 | 606.21 | 735.15 | 1495.03 | 465.16 | 0.00 | 0.00 | 0.00 |
June | 1618.39 | 761.22 | 857.17 | 2006.66 | 324.55 | 0.00 | 0.00 | 0.00 |
July | 1446.90 | 634.37 | 812.53 | 1911.26 | 230.22 | 0.00 | 0.00 | 0.00 |
August | 1308.64 | 556.44 | 752.20 | 1695.41 | 297.30 | 0.00 | 0.00 | 0.00 |
September | 1027.69 | 443.81 | 583.88 | 1189.95 | 462.92 | 0.00 | 0.00 | 0.00 |
October | 666.20 | 234.67 | 431.52 | 583.66 | 701.55 | 0.00 | 0.00 | 0.00 |
November | 394.79 | 113.76 | 281.03 | 237.19 | 883.48 | 0.00 | 0.00 | 0.00 |
December | 342.25 | 74.57 | 267.68 | 99.25 | 1299.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 932.38 | 378.35 | 554.03 | 958.30 | 731.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.25 | 74.57 | 267.68 | 99.25 | 230.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1618.39 | 761.22 | 857.17 | 2006.66 | 1327.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.46 | 3.39 | 11.06 | 4.13 | 52.50 | 0.00 | 0.00 | 0.00 |
February | 23.43 | 6.02 | 17.41 | 10.46 | 49.42 | 0.00 | 0.00 | 0.00 |
March | 36.72 | 15.72 | 21.00 | 30.39 | 35.43 | 0.00 | 0.00 | 0.00 |
April | 44.96 | 18.43 | 26.52 | 43.45 | 26.30 | 0.00 | 0.00 | 0.00 |
May | 53.04 | 23.97 | 29.07 | 59.11 | 18.39 | 0.00 | 0.00 | 0.00 |
June | 63.99 | 30.10 | 33.89 | 79.34 | 12.83 | 0.00 | 0.00 | 0.00 |
July | 57.21 | 25.08 | 32.13 | 75.57 | 9.10 | 0.00 | 0.00 | 0.00 |
August | 51.74 | 22.00 | 29.74 | 67.03 | 11.76 | 0.00 | 0.00 | 0.00 |
September | 40.63 | 17.55 | 23.09 | 47.05 | 18.30 | 0.00 | 0.00 | 0.00 |
October | 26.34 | 9.28 | 17.06 | 23.08 | 27.74 | 0.00 | 0.00 | 0.00 |
November | 15.61 | 4.50 | 11.11 | 9.38 | 34.93 | 0.00 | 0.00 | 0.00 |
December | 13.53 | 2.95 | 10.58 | 3.92 | 51.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.87 | 14.96 | 21.91 | 37.89 | 28.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.53 | 2.95 | 10.58 | 3.92 | 9.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.99 | 30.10 | 33.89 | 79.34 | 52.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.09 | 0.00 | 363.09 | 3.66 | 2213.70 | 0.00 | 0.00 | 0.00 |
February | 553.22 | 0.00 | 553.22 | 31.94 | 2073.58 | 0.00 | 0.00 | 0.00 |
March | 670.90 | 0.00 | 670.90 | 214.94 | 1507.45 | 0.00 | 0.00 | 0.00 |
April | 854.86 | 3.41 | 851.45 | 459.12 | 1073.03 | 0.00 | 0.00 | 0.00 |
May | 993.30 | 42.12 | 951.18 | 770.41 | 698.48 | 0.00 | 0.00 | 0.00 |
June | 1194.74 | 101.70 | 1093.03 | 1280.98 | 455.65 | 0.00 | 0.00 | 0.00 |
July | 1108.28 | 71.54 | 1036.73 | 1379.73 | 319.65 | 0.00 | 0.00 | 0.00 |
August | 958.97 | 14.59 | 944.38 | 1125.32 | 425.09 | 0.00 | 0.00 | 0.00 |
September | 729.79 | 0.15 | 729.64 | 653.13 | 694.68 | 0.00 | 0.00 | 0.00 |
October | 545.55 | 0.00 | 545.55 | 261.10 | 1079.92 | 0.00 | 0.00 | 0.00 |
November | 366.60 | 0.00 | 366.60 | 76.76 | 1385.55 | 0.00 | 0.00 | 0.00 |
December | 339.84 | 0.00 | 339.84 | 4.81 | 2114.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 723.97 | 19.54 | 704.42 | 524.80 | 1165.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.84 | 0.00 | 339.84 | 3.66 | 319.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1194.74 | 101.70 | 1093.03 | 1379.73 | 2213.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 442.97 | 142.84 | 300.13 | 170.49 | 1340.78 | 0.00 | 0.00 | 0.00 |
February | 649.98 | 195.04 | 454.94 | 305.89 | 1269.26 | 0.00 | 0.00 | 0.00 |
March | 932.70 | 390.61 | 542.09 | 728.89 | 923.15 | 0.00 | 0.00 | 0.00 |
April | 1234.49 | 545.46 | 689.03 | 1159.19 | 675.70 | 0.00 | 0.00 | 0.00 |
May | 1383.07 | 611.81 | 771.26 | 1495.88 | 469.18 | 0.00 | 0.00 | 0.00 |
June | 1544.66 | 682.66 | 861.99 | 1872.01 | 307.22 | 0.00 | 0.00 | 0.00 |
July | 1483.28 | 653.07 | 830.21 | 1934.73 | 214.04 | 0.00 | 0.00 | 0.00 |
August | 1339.56 | 562.27 | 777.29 | 1708.30 | 280.34 | 0.00 | 0.00 | 0.00 |
September | 1114.75 | 494.46 | 620.29 | 1281.31 | 439.73 | 0.00 | 0.00 | 0.00 |
October | 756.45 | 312.89 | 443.56 | 674.27 | 676.22 | 0.00 | 0.00 | 0.00 |
November | 429.07 | 137.64 | 291.43 | 265.43 | 879.19 | 0.00 | 0.00 | 0.00 |
December | 345.42 | 71.37 | 274.05 | 88.25 | 1322.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 972.81 | 400.98 | 571.83 | 977.34 | 730.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.42 | 71.37 | 274.05 | 88.25 | 214.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1544.66 | 682.66 | 861.99 | 1934.73 | 1340.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1561.30 | 911.38 | 649.92 | 1258.81 | 1893.94 | 0.00 | 0.00 | 0.00 |
February | 1782.62 | 859.56 | 923.05 | 1415.92 | 1860.18 | 0.00 | 0.00 | 0.00 |
March | 2175.80 | 1222.57 | 953.23 | 2128.83 | 1397.09 | 0.00 | 0.00 | 0.00 |
April | 1801.91 | 720.05 | 1081.86 | 1839.59 | 1110.64 | 0.00 | 0.00 | 0.00 |
May | 1576.83 | 457.98 | 1118.85 | 1745.76 | 769.62 | 0.00 | 0.00 | 0.00 |
June | 1532.17 | 324.67 | 1207.49 | 1899.02 | 502.52 | 0.00 | 0.00 | 0.00 |
July | 1564.10 | 379.50 | 1184.59 | 2149.75 | 348.60 | 0.00 | 0.00 | 0.00 |
August | 1755.95 | 569.32 | 1186.63 | 2373.03 | 451.15 | 0.00 | 0.00 | 0.00 |
September | 2041.65 | 994.44 | 1047.22 | 2540.90 | 709.53 | 0.00 | 0.00 | 0.00 |
October | 1953.56 | 1115.91 | 837.65 | 2102.70 | 1046.73 | 0.00 | 0.00 | 0.00 |
November | 1399.10 | 789.84 | 609.26 | 1322.21 | 1312.57 | 0.00 | 0.00 | 0.00 |
December | 1305.56 | 675.69 | 629.87 | 995.68 | 1867.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1703.68 | 751.34 | 952.34 | 1816.68 | 1101.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.56 | 324.67 | 609.26 | 995.68 | 348.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2175.80 | 1222.57 | 1207.49 | 2540.90 | 1893.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.06 | 89.22 | 290.84 | 105.22 | 1392.47 | 0.00 | 0.00 | 0.00 |
February | 615.98 | 158.31 | 457.67 | 265.12 | 1311.61 | 0.00 | 0.00 | 0.00 |
March | 965.44 | 413.38 | 552.06 | 773.76 | 950.67 | 0.00 | 0.00 | 0.00 |
April | 1182.05 | 484.69 | 697.36 | 1113.26 | 710.42 | 0.00 | 0.00 | 0.00 |
May | 1394.42 | 630.19 | 764.23 | 1525.17 | 500.69 | 0.00 | 0.00 | 0.00 |
June | 1682.40 | 791.33 | 891.07 | 2068.16 | 338.15 | 0.00 | 0.00 | 0.00 |
July | 1504.13 | 659.46 | 844.67 | 1973.74 | 239.06 | 0.00 | 0.00 | 0.00 |
August | 1360.40 | 578.46 | 781.94 | 1755.20 | 301.90 | 0.00 | 0.00 | 0.00 |
September | 1068.34 | 461.37 | 606.97 | 1233.65 | 465.76 | 0.00 | 0.00 | 0.00 |
October | 692.55 | 243.95 | 448.59 | 607.45 | 702.62 | 0.00 | 0.00 | 0.00 |
November | 410.41 | 118.26 | 292.14 | 245.94 | 897.35 | 0.00 | 0.00 | 0.00 |
December | 355.79 | 77.52 | 278.26 | 101.19 | 1343.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 969.26 | 393.32 | 575.94 | 984.51 | 760.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.79 | 77.52 | 278.26 | 101.19 | 239.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1682.40 | 791.33 | 891.07 | 2068.16 | 1392.47 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972507E+09 | 0.00 | 0.972507E+09 | 16175137.80 | 0.574607E+10 |
February | 0.133834E+10 | 0.00 | 0.133834E+10 | 90877652.30 | 0.485046E+10 |
March | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.601811E+09 | 0.383820E+10 |
April | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.123609E+10 | 0.261403E+10 |
May | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.209957E+10 | 0.177492E+10 |
June | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.332541E+10 | 0.114020E+10 |
July | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.368573E+10 | 0.834133E+09 |
August | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.301694E+10 | 0.109568E+10 |
September | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.171967E+10 | 0.169010E+10 |
October | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.756752E+09 | 0.266288E+10 |
November | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.229547E+09 | 0.333499E+10 |
December | 0.910238E+09 | 0.00 | 0.910238E+09 | 18538874.78 | 0.543612E+10 |
Annual Sum or Average | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.167971E+11 | 0.350178E+11 |
Minimum of Months | 0.910238E+09 | 0.00 | 0.910238E+09 | 16175137.80 | 0.834133E+09 |
Maximum of Months | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.368573E+10 | 0.574607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.469052E+09 | 0.347619E+10 |
February | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.759283E+09 | 0.297016E+10 |
March | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.198085E+10 | 0.235088E+10 |
April | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.303634E+10 | 0.165646E+10 |
May | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.402185E+10 | 0.119984E+10 |
June | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.485040E+10 | 0.770780E+09 |
July | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.517221E+10 | 0.559494E+09 |
August | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.457327E+10 | 0.724604E+09 |
September | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.333691E+10 | 0.107815E+10 |
October | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.184960E+10 | 0.167849E+10 |
November | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.716708E+09 | 0.212222E+10 |
December | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.247147E+09 | 0.340272E+10 |
Annual Sum or Average | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.310136E+11 | 0.219900E+11 |
Minimum of Months | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.247147E+09 | 0.559494E+09 |
Maximum of Months | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.517221E+10 | 0.347619E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.340431E+10 | 0.489218E+10 |
February | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.345895E+10 | 0.434039E+10 |
March | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.574545E+10 | 0.354688E+10 |
April | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.480955E+10 | 0.271396E+10 |
May | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.469638E+10 | 0.195487E+10 |
June | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.491914E+10 | 0.124997E+10 |
July | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.574307E+10 | 0.904469E+09 |
August | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.635096E+10 | 0.116015E+10 |
September | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.660373E+10 | 0.173387E+10 |
October | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.569502E+10 | 0.259278E+10 |
November | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.348107E+10 | 0.316231E+10 |
December | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.270210E+10 | 0.478997E+10 |
Annual Sum or Average | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.576097E+11 | 0.330418E+11 |
Minimum of Months | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.270210E+10 | 0.904469E+09 |
Maximum of Months | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.660373E+10 | 0.489218E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.289386E+09 | 0.361397E+10 |
February | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.652546E+09 | 0.306975E+10 |
March | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.209325E+10 | 0.241681E+10 |
April | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.291167E+10 | 0.173467E+10 |
May | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.410162E+10 | 0.127182E+10 |
June | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535775E+10 | 0.841850E+09 |
July | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.527665E+10 | 0.620328E+09 |
August | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.470070E+10 | 0.776744E+09 |
September | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.321576E+10 | 0.113444E+10 |
October | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.166470E+10 | 0.173877E+10 |
November | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.661808E+09 | 0.216478E+10 |
December | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.280004E+09 | 0.345745E+10 |
Annual Sum or Average | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.312058E+11 | 0.228414E+11 |
Minimum of Months | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.280004E+09 | 0.620328E+09 |
Maximum of Months | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535775E+10 | 0.361397E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324154E+09 | 0.00 | 0.324154E+09 | 3101420.05 | 0.195631E+10 |
February | 0.446093E+09 | 0.00 | 0.446093E+09 | 28350194.34 | 0.165143E+10 |
March | 0.598947E+09 | 0.00 | 0.598947E+09 | 0.212653E+09 | 0.129865E+10 |
April | 0.738563E+09 | 2947159.07 | 0.735616E+09 | 0.435889E+09 | 0.875256E+09 |
May | 0.886780E+09 | 37604498.19 | 0.849175E+09 | 0.742533E+09 | 0.573438E+09 |
June | 0.103220E+10 | 87866326.22 | 0.944336E+09 | 0.113768E+10 | 0.373042E+09 |
July | 0.989422E+09 | 63869394.40 | 0.925552E+09 | 0.125491E+10 | 0.270489E+09 |
August | 0.856125E+09 | 13024079.41 | 0.843101E+09 | 0.101806E+10 | 0.370689E+09 |
September | 0.630512E+09 | 130993.15 | 0.630381E+09 | 0.572247E+09 | 0.599560E+09 |
October | 0.487046E+09 | 0.00 | 0.487046E+09 | 0.233663E+09 | 0.984660E+09 |
November | 0.316725E+09 | 0.00 | 0.316725E+09 | 66270006.74 | 0.121694E+10 |
December | 0.303398E+09 | 0.00 | 0.303398E+09 | 4259467.80 | 0.189725E+10 |
Annual Sum or Average | 0.760997E+10 | 0.205442E+09 | 0.740452E+10 | 0.570961E+10 | 0.120677E+11 |
Minimum of Months | 0.303398E+09 | 0.00 | 0.303398E+09 | 3101420.05 | 0.270489E+09 |
Maximum of Months | 0.103220E+10 | 87866326.22 | 0.944336E+09 | 0.125491E+10 | 0.195631E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324166E+09 | 0.00 | 0.324166E+09 | 3100701.48 | 0.195643E+10 |
February | 0.446109E+09 | 0.00 | 0.446109E+09 | 28346994.66 | 0.165154E+10 |
March | 0.598971E+09 | 0.00 | 0.598971E+09 | 0.212655E+09 | 0.129873E+10 |
April | 0.738592E+09 | 2947238.29 | 0.735645E+09 | 0.435898E+09 | 0.875312E+09 |
May | 0.886815E+09 | 37605509.01 | 0.849210E+09 | 0.742556E+09 | 0.573473E+09 |
June | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.113772E+10 | 0.373063E+09 |
July | 0.989461E+09 | 63871111.23 | 0.925590E+09 | 0.125496E+10 | 0.270504E+09 |
August | 0.856159E+09 | 13024429.50 | 0.843134E+09 | 0.101810E+10 | 0.370710E+09 |
September | 0.630537E+09 | 130996.67 | 0.630406E+09 | 0.572266E+09 | 0.599596E+09 |
October | 0.487064E+09 | 0.00 | 0.487064E+09 | 0.233666E+09 | 0.984721E+09 |
November | 0.316737E+09 | 0.00 | 0.316737E+09 | 66269452.76 | 0.121701E+10 |
December | 0.303409E+09 | 0.00 | 0.303409E+09 | 4258993.99 | 0.189738E+10 |
Annual Sum or Average | 0.761026E+10 | 0.205448E+09 | 0.740482E+10 | 0.570979E+10 | 0.120685E+11 |
Minimum of Months | 0.303409E+09 | 0.00 | 0.303409E+09 | 3100701.48 | 0.270504E+09 |
Maximum of Months | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.125496E+10 | 0.195643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324166E+09 | 0.00 | 0.324166E+09 | 3100701.48 | 0.195643E+10 |
February | 0.446109E+09 | 0.00 | 0.446109E+09 | 28346994.66 | 0.165154E+10 |
March | 0.598971E+09 | 0.00 | 0.598971E+09 | 0.212655E+09 | 0.129873E+10 |
April | 0.738592E+09 | 2947238.29 | 0.735645E+09 | 0.435898E+09 | 0.875312E+09 |
May | 0.886815E+09 | 37605509.01 | 0.849210E+09 | 0.742556E+09 | 0.573473E+09 |
June | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.113772E+10 | 0.373063E+09 |
July | 0.989461E+09 | 63871111.23 | 0.925590E+09 | 0.125496E+10 | 0.270504E+09 |
August | 0.856159E+09 | 13024429.50 | 0.843134E+09 | 0.101810E+10 | 0.370710E+09 |
September | 0.630537E+09 | 130996.67 | 0.630406E+09 | 0.572266E+09 | 0.599596E+09 |
October | 0.487064E+09 | 0.00 | 0.487064E+09 | 0.233666E+09 | 0.984721E+09 |
November | 0.316737E+09 | 0.00 | 0.316737E+09 | 66269452.76 | 0.121701E+10 |
December | 0.303409E+09 | 0.00 | 0.303409E+09 | 4258993.99 | 0.189738E+10 |
Annual Sum or Average | 0.761026E+10 | 0.205448E+09 | 0.740482E+10 | 0.570979E+10 | 0.120685E+11 |
Minimum of Months | 0.303409E+09 | 0.00 | 0.303409E+09 | 3100701.48 | 0.270504E+09 |
Maximum of Months | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.125496E+10 | 0.195643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114132E+10 | 0.368023E+09 | 0.773295E+09 | 0.449160E+09 | 0.343517E+10 |
February | 0.151260E+10 | 0.453892E+09 | 0.105871E+10 | 0.731430E+09 | 0.293201E+10 |
March | 0.240309E+10 | 0.100640E+10 | 0.139670E+10 | 0.193578E+10 | 0.232945E+10 |
April | 0.307804E+10 | 0.136004E+10 | 0.171800E+10 | 0.295466E+10 | 0.165079E+10 |
May | 0.356346E+10 | 0.157630E+10 | 0.198716E+10 | 0.392463E+10 | 0.116821E+10 |
June | 0.385141E+10 | 0.170213E+10 | 0.214928E+10 | 0.471059E+10 | 0.759110E+09 |
July | 0.382164E+10 | 0.168261E+10 | 0.213903E+10 | 0.501693E+10 | 0.549933E+09 |
August | 0.345136E+10 | 0.144869E+10 | 0.200267E+10 | 0.442141E+10 | 0.735762E+09 |
September | 0.277948E+10 | 0.123287E+10 | 0.154662E+10 | 0.320372E+10 | 0.113698E+10 |
October | 0.194898E+10 | 0.806147E+09 | 0.114283E+10 | 0.173005E+10 | 0.182371E+10 |
November | 0.106983E+10 | 0.343189E+09 | 0.726645E+09 | 0.660430E+09 | 0.225079E+10 |
December | 0.889981E+09 | 0.183888E+09 | 0.706092E+09 | 0.230335E+09 | 0.343125E+10 |
Annual Sum or Average | 0.295112E+11 | 0.121642E+11 | 0.173470E+11 | 0.299691E+11 | 0.222032E+11 |
Minimum of Months | 0.889981E+09 | 0.183888E+09 | 0.706092E+09 | 0.230335E+09 | 0.549933E+09 |
Maximum of Months | 0.385141E+10 | 0.170213E+10 | 0.214928E+10 | 0.501693E+10 | 0.343517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45126691.54 | 14551315.80 | 30575375.73 | 17759382.98 | 0.135824E+09 |
February | 59806742.31 | 17946463.36 | 41860278.95 | 28920090.74 | 0.115929E+09 |
March | 95016148.63 | 39792019.63 | 55224129.00 | 76538933.61 | 92104240.47 |
April | 0.121703E+09 | 53774767.72 | 67928318.11 | 0.116825E+09 | 65270612.63 |
May | 0.140896E+09 | 62325660.64 | 78570500.95 | 0.155176E+09 | 46189921.25 |
June | 0.152281E+09 | 67300549.10 | 84980731.10 | 0.186252E+09 | 30014534.78 |
July | 0.151104E+09 | 66528845.45 | 84575443.71 | 0.198365E+09 | 21743869.99 |
August | 0.136464E+09 | 57279803.41 | 79183956.05 | 0.174818E+09 | 29091376.36 |
September | 0.109898E+09 | 48746454.24 | 61151775.08 | 0.126672E+09 | 44955354.15 |
October | 77060880.03 | 31874343.11 | 45186536.92 | 68404611.93 | 72107992.87 |
November | 42300300.33 | 13569398.48 | 28730901.85 | 26112805.64 | 88994341.96 |
December | 35189031.70 | 7270783.46 | 27918248.24 | 9107231.16 | 0.135669E+09 |
Annual Sum or Average | 0.116685E+10 | 0.480960E+09 | 0.685886E+09 | 0.118495E+10 | 0.877894E+09 |
Minimum of Months | 35189031.70 | 7270783.46 | 27918248.24 | 9107231.16 | 21743869.99 |
Maximum of Months | 0.152281E+09 | 67300549.10 | 84980731.10 | 0.198365E+09 | 0.135824E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139391E+10 | 0.813662E+09 | 0.580244E+09 | 0.115573E+10 | 0.166815E+10 |
February | 0.143748E+10 | 0.693137E+09 | 0.744340E+09 | 0.117960E+10 | 0.147519E+10 |
March | 0.194252E+10 | 0.109149E+10 | 0.851036E+09 | 0.195736E+10 | 0.122869E+10 |
April | 0.155682E+10 | 0.622108E+09 | 0.934716E+09 | 0.163984E+10 | 0.926276E+09 |
May | 0.140778E+10 | 0.408874E+09 | 0.998901E+09 | 0.161185E+10 | 0.642811E+09 |
June | 0.132378E+10 | 0.280513E+09 | 0.104327E+10 | 0.167544E+10 | 0.414905E+09 |
July | 0.139641E+10 | 0.338811E+09 | 0.105760E+10 | 0.194221E+10 | 0.302445E+09 |
August | 0.156770E+10 | 0.508283E+09 | 0.105941E+10 | 0.213413E+10 | 0.405826E+09 |
September | 0.176396E+10 | 0.859176E+09 | 0.904784E+09 | 0.220725E+10 | 0.634050E+09 |
October | 0.174411E+10 | 0.996265E+09 | 0.747843E+09 | 0.189238E+10 | 0.976664E+09 |
November | 0.120880E+10 | 0.682406E+09 | 0.526394E+09 | 0.115299E+10 | 0.117130E+10 |
December | 0.116558E+10 | 0.603240E+09 | 0.562342E+09 | 0.907476E+09 | 0.166573E+10 |
Annual Sum or Average | 0.179088E+11 | 0.789796E+10 | 0.100109E+11 | 0.194563E+11 | 0.115120E+11 |
Minimum of Months | 0.116558E+10 | 0.280513E+09 | 0.526394E+09 | 0.907476E+09 | 0.302445E+09 |
Maximum of Months | 0.194252E+10 | 0.109149E+10 | 0.105941E+10 | 0.220725E+10 | 0.166815E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139391E+10 | 0.813662E+09 | 0.580244E+09 | 0.115573E+10 | 0.166815E+10 |
February | 0.143748E+10 | 0.693137E+09 | 0.744340E+09 | 0.117960E+10 | 0.147519E+10 |
March | 0.194252E+10 | 0.109149E+10 | 0.851036E+09 | 0.195736E+10 | 0.122869E+10 |
April | 0.155682E+10 | 0.622108E+09 | 0.934716E+09 | 0.163984E+10 | 0.926276E+09 |
May | 0.140778E+10 | 0.408874E+09 | 0.998901E+09 | 0.161185E+10 | 0.642811E+09 |
June | 0.132378E+10 | 0.280513E+09 | 0.104327E+10 | 0.167544E+10 | 0.414905E+09 |
July | 0.139641E+10 | 0.338811E+09 | 0.105760E+10 | 0.194221E+10 | 0.302445E+09 |
August | 0.156770E+10 | 0.508283E+09 | 0.105941E+10 | 0.213413E+10 | 0.405826E+09 |
September | 0.176396E+10 | 0.859176E+09 | 0.904784E+09 | 0.220725E+10 | 0.634050E+09 |
October | 0.174411E+10 | 0.996265E+09 | 0.747843E+09 | 0.189238E+10 | 0.976664E+09 |
November | 0.120880E+10 | 0.682406E+09 | 0.526394E+09 | 0.115299E+10 | 0.117130E+10 |
December | 0.116558E+10 | 0.603240E+09 | 0.562342E+09 | 0.907476E+09 | 0.166573E+10 |
Annual Sum or Average | 0.179088E+11 | 0.789796E+10 | 0.100109E+11 | 0.194563E+11 | 0.115120E+11 |
Minimum of Months | 0.116558E+10 | 0.280513E+09 | 0.526394E+09 | 0.907476E+09 | 0.302445E+09 |
Maximum of Months | 0.194252E+10 | 0.109149E+10 | 0.105941E+10 | 0.220725E+10 | 0.166815E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139382E+10 | 0.813611E+09 | 0.580207E+09 | 0.115566E+10 | 0.166804E+10 |
February | 0.143739E+10 | 0.693093E+09 | 0.744293E+09 | 0.117952E+10 | 0.147510E+10 |
March | 0.194240E+10 | 0.109142E+10 | 0.850982E+09 | 0.195723E+10 | 0.122861E+10 |
April | 0.155673E+10 | 0.622069E+09 | 0.934657E+09 | 0.163974E+10 | 0.926217E+09 |
May | 0.140769E+10 | 0.408848E+09 | 0.998838E+09 | 0.161175E+10 | 0.642770E+09 |
June | 0.132370E+10 | 0.280495E+09 | 0.104320E+10 | 0.167534E+10 | 0.414879E+09 |
July | 0.139632E+10 | 0.338790E+09 | 0.105753E+10 | 0.194209E+10 | 0.302426E+09 |
August | 0.156760E+10 | 0.508251E+09 | 0.105935E+10 | 0.213399E+10 | 0.405800E+09 |
September | 0.176385E+10 | 0.859121E+09 | 0.904727E+09 | 0.220711E+10 | 0.634010E+09 |
October | 0.174400E+10 | 0.996202E+09 | 0.747796E+09 | 0.189226E+10 | 0.976602E+09 |
November | 0.120872E+10 | 0.682363E+09 | 0.526360E+09 | 0.115292E+10 | 0.117123E+10 |
December | 0.116551E+10 | 0.603202E+09 | 0.562306E+09 | 0.907419E+09 | 0.166563E+10 |
Annual Sum or Average | 0.179077E+11 | 0.789746E+10 | 0.100102E+11 | 0.194550E+11 | 0.115113E+11 |
Minimum of Months | 0.116551E+10 | 0.280495E+09 | 0.526360E+09 | 0.907419E+09 | 0.302426E+09 |
Maximum of Months | 0.194240E+10 | 0.109142E+10 | 0.105935E+10 | 0.220711E+10 | 0.166804E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.979234E+09 | 0.229885E+09 | 0.749349E+09 | 0.280082E+09 | 0.355617E+10 |
February | 0.143348E+10 | 0.368414E+09 | 0.106507E+10 | 0.639818E+09 | 0.302360E+10 |
March | 0.248745E+10 | 0.106506E+10 | 0.142238E+10 | 0.205878E+10 | 0.240006E+10 |
April | 0.294730E+10 | 0.120851E+10 | 0.173879E+10 | 0.284848E+10 | 0.172407E+10 |
May | 0.359270E+10 | 0.162366E+10 | 0.196904E+10 | 0.400428E+10 | 0.124589E+10 |
June | 0.419487E+10 | 0.197309E+10 | 0.222179E+10 | 0.520126E+10 | 0.841227E+09 |
July | 0.387539E+10 | 0.169910E+10 | 0.217629E+10 | 0.511912E+10 | 0.616634E+09 |
August | 0.350506E+10 | 0.149038E+10 | 0.201468E+10 | 0.454098E+10 | 0.796299E+09 |
September | 0.266377E+10 | 0.115036E+10 | 0.151341E+10 | 0.308435E+10 | 0.119989E+10 |
October | 0.178434E+10 | 0.628545E+09 | 0.115580E+10 | 0.156328E+10 | 0.187902E+10 |
November | 0.102330E+10 | 0.294877E+09 | 0.728420E+09 | 0.614800E+09 | 0.228998E+10 |
December | 0.916678E+09 | 0.199733E+09 | 0.716944E+09 | 0.265824E+09 | 0.348000E+10 |
Annual Sum or Average | 0.294036E+11 | 0.119316E+11 | 0.174720E+11 | 0.302211E+11 | 0.230528E+11 |
Minimum of Months | 0.916678E+09 | 0.199733E+09 | 0.716944E+09 | 0.265824E+09 | 0.616634E+09 |
Maximum of Months | 0.419487E+10 | 0.197309E+10 | 0.222179E+10 | 0.520126E+10 | 0.355617E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38717917.76 | 9089412.29 | 29628505.47 | 11074130.66 | 0.140608E+09 |
February | 56678404.17 | 14566707.70 | 42111696.47 | 25297689.12 | 0.119551E+09 |
March | 98351102.73 | 42111491.08 | 56239611.65 | 81401942.76 | 94896383.96 |
April | 0.116533E+09 | 47783122.10 | 68750079.23 | 0.112626E+09 | 68168347.04 |
May | 0.142052E+09 | 64197993.46 | 77853845.79 | 0.158325E+09 | 49261507.40 |
June | 0.165861E+09 | 78013909.58 | 87847222.32 | 0.205652E+09 | 33261336.18 |
July | 0.153229E+09 | 67180589.64 | 86048435.07 | 0.202405E+09 | 24381156.46 |
August | 0.138587E+09 | 58928107.66 | 79658462.03 | 0.179546E+09 | 31484926.53 |
September | 0.105323E+09 | 45484091.01 | 59838578.33 | 0.121952E+09 | 47442364.77 |
October | 70551039.24 | 24852018.57 | 45699020.67 | 61810532.47 | 74294832.15 |
November | 40460141.23 | 11659124.40 | 28801016.83 | 24308516.21 | 90543817.96 |
December | 36244509.01 | 7897243.42 | 28347265.59 | 10510386.96 | 0.137596E+09 |
Annual Sum or Average | 0.116259E+10 | 0.471764E+09 | 0.690824E+09 | 0.119491E+10 | 0.911489E+09 |
Minimum of Months | 36244509.01 | 7897243.42 | 28347265.59 | 10510386.96 | 24381156.46 |
Maximum of Months | 0.165861E+09 | 78013909.58 | 87847222.32 | 0.205652E+09 | 0.140608E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972507E+09 | 0.00 | 0.972507E+09 | 9800418.15 | 0.592917E+10 |
February | 0.133834E+10 | 0.00 | 0.133834E+10 | 77279815.50 | 0.501640E+10 |
March | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.575685E+09 | 0.403757E+10 |
April | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.119005E+10 | 0.278130E+10 |
May | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.206346E+10 | 0.187080E+10 |
June | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.332031E+10 | 0.118105E+10 |
July | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.369548E+10 | 0.856151E+09 |
August | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.301405E+10 | 0.113856E+10 |
September | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.169292E+10 | 0.180061E+10 |
October | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.699336E+09 | 0.289245E+10 |
November | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.198955E+09 | 0.359133E+10 |
December | 0.910238E+09 | 0.00 | 0.910238E+09 | 12872697.92 | 0.566293E+10 |
Annual Sum or Average | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.165502E+11 | 0.367583E+11 |
Minimum of Months | 0.910238E+09 | 0.00 | 0.910238E+09 | 9800418.15 | 0.856151E+09 |
Maximum of Months | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.369548E+10 | 0.592917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.456628E+09 | 0.359115E+10 |
February | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.740011E+09 | 0.307059E+10 |
March | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.195225E+10 | 0.247257E+10 |
April | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.300461E+10 | 0.175140E+10 |
May | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.400656E+10 | 0.125666E+10 |
June | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.485225E+10 | 0.796325E+09 |
July | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.518197E+10 | 0.573289E+09 |
August | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.457551E+10 | 0.750853E+09 |
September | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.332115E+10 | 0.113977E+10 |
October | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.180598E+10 | 0.181118E+10 |
November | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.687985E+09 | 0.227886E+10 |
December | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.236375E+09 | 0.354312E+10 |
Annual Sum or Average | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.308213E+11 | 0.230358E+11 |
Minimum of Months | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.236375E+09 | 0.573289E+09 |
Maximum of Months | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.518197E+10 | 0.359115E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.337160E+10 | 0.507272E+10 |
February | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.342540E+10 | 0.450015E+10 |
March | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.570186E+10 | 0.374196E+10 |
April | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.476821E+10 | 0.287879E+10 |
May | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.467583E+10 | 0.206136E+10 |
June | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.492227E+10 | 0.130254E+10 |
July | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.575790E+10 | 0.933684E+09 |
August | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.635593E+10 | 0.120836E+10 |
September | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.658601E+10 | 0.183910E+10 |
October | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.563188E+10 | 0.280356E+10 |
November | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.342717E+10 | 0.340218E+10 |
December | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.266683E+10 | 0.500095E+10 |
Annual Sum or Average | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.572909E+11 | 0.347454E+11 |
Minimum of Months | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.266683E+10 | 0.933684E+09 |
Maximum of Months | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.658601E+10 | 0.507272E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.281829E+09 | 0.372958E+10 |
February | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.641372E+09 | 0.317304E+10 |
March | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.207243E+10 | 0.254627E+10 |
April | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.288556E+10 | 0.184141E+10 |
May | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.408503E+10 | 0.134105E+10 |
June | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.536066E+10 | 0.876483E+09 |
July | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.528647E+10 | 0.640298E+09 |
August | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.470112E+10 | 0.808609E+09 |
September | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.319762E+10 | 0.120724E+10 |
October | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.162698E+10 | 0.188190E+10 |
November | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.637476E+09 | 0.232593E+10 |
December | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.271018E+09 | 0.359832E+10 |
Annual Sum or Average | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.310476E+11 | 0.239702E+11 |
Minimum of Months | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.271018E+09 | 0.640298E+09 |
Maximum of Months | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.536066E+10 | 0.372958E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.04 | 2145.34 | 363.09 | 0.00 | 363.09 | 0.00 | 0.00 |
February | 37.57 | 2004.99 | 553.22 | 0.00 | 553.22 | 0.00 | 0.00 |
March | 224.69 | 1433.02 | 670.90 | 0.00 | 670.90 | 0.00 | 0.00 |
April | 476.89 | 1008.50 | 854.86 | 3.41 | 851.45 | 0.00 | 0.00 |
May | 783.89 | 662.68 | 993.30 | 42.12 | 951.18 | 0.00 | 0.00 |
June | 1282.95 | 439.89 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
July | 1376.10 | 311.43 | 1108.28 | 71.54 | 1036.73 | 0.00 | 0.00 |
August | 1126.40 | 409.08 | 958.97 | 14.59 | 944.38 | 0.00 | 0.00 |
September | 663.45 | 652.04 | 729.79 | 0.15 | 729.64 | 0.00 | 0.00 |
October | 282.54 | 994.20 | 545.55 | 0.00 | 545.55 | 0.00 | 0.00 |
November | 88.56 | 1286.65 | 366.60 | 0.00 | 366.60 | 0.00 | 0.00 |
December | 6.92 | 2029.61 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 532.63 | 1110.41 | 723.97 | 19.54 | 704.42 | 0.00 | 0.00 |
Minimum of Months | 6.04 | 311.43 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1376.10 | 2145.34 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.12 | 1297.86 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 313.86 | 1227.74 | 649.98 | 195.04 | 454.94 | 0.00 | 0.00 |
March | 739.56 | 877.72 | 932.70 | 390.61 | 542.09 | 0.00 | 0.00 |
April | 1171.43 | 639.07 | 1234.49 | 545.46 | 689.03 | 0.00 | 0.00 |
May | 1501.59 | 447.97 | 1383.07 | 611.81 | 771.26 | 0.00 | 0.00 |
June | 1871.29 | 297.37 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
July | 1931.08 | 208.89 | 1483.28 | 653.07 | 830.21 | 0.00 | 0.00 |
August | 1707.46 | 270.54 | 1339.56 | 562.27 | 777.29 | 0.00 | 0.00 |
September | 1287.39 | 415.95 | 1114.75 | 494.46 | 620.29 | 0.00 | 0.00 |
October | 690.56 | 626.68 | 756.45 | 312.89 | 443.56 | 0.00 | 0.00 |
November | 276.51 | 818.76 | 429.07 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 92.27 | 1270.43 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 983.44 | 697.30 | 972.81 | 400.98 | 571.83 | 0.00 | 0.00 |
Minimum of Months | 92.27 | 208.89 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1931.08 | 1297.86 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1271.02 | 1826.53 | 1561.30 | 911.38 | 649.92 | 0.00 | 0.00 |
February | 1429.79 | 1794.14 | 1782.62 | 859.56 | 923.05 | 0.00 | 0.00 |
March | 2145.10 | 1324.25 | 2175.80 | 1222.57 | 953.23 | 0.00 | 0.00 |
April | 1855.54 | 1047.05 | 1801.91 | 720.05 | 1081.86 | 0.00 | 0.00 |
May | 1753.43 | 729.87 | 1576.83 | 457.98 | 1118.85 | 0.00 | 0.00 |
June | 1897.82 | 482.24 | 1532.17 | 324.67 | 1207.49 | 0.00 | 0.00 |
July | 2144.22 | 337.69 | 1564.10 | 379.50 | 1184.59 | 0.00 | 0.00 |
August | 2371.18 | 433.15 | 1755.95 | 569.32 | 1186.63 | 0.00 | 0.00 |
September | 2547.74 | 668.93 | 2041.65 | 994.44 | 1047.22 | 0.00 | 0.00 |
October | 2126.28 | 968.03 | 1953.56 | 1115.91 | 837.65 | 0.00 | 0.00 |
November | 1343.00 | 1220.03 | 1399.10 | 789.84 | 609.26 | 0.00 | 0.00 |
December | 1008.85 | 1788.37 | 1305.56 | 675.69 | 629.87 | 0.00 | 0.00 |
Annual Sum or Average | 1826.79 | 1047.75 | 1703.68 | 751.34 | 952.34 | 0.00 | 0.00 |
Minimum of Months | 1008.85 | 337.69 | 1305.56 | 324.67 | 609.26 | 0.00 | 0.00 |
Maximum of Months | 2547.74 | 1826.53 | 2175.80 | 1222.57 | 1207.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.04 | 1349.30 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 269.74 | 1268.91 | 615.98 | 158.31 | 457.67 | 0.00 | 0.00 |
March | 781.53 | 902.33 | 965.44 | 413.38 | 552.06 | 0.00 | 0.00 |
April | 1123.33 | 669.24 | 1182.05 | 484.69 | 697.36 | 0.00 | 0.00 |
May | 1531.37 | 474.84 | 1394.42 | 630.19 | 764.23 | 0.00 | 0.00 |
June | 2067.03 | 324.79 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
July | 1970.07 | 231.60 | 1504.13 | 659.46 | 844.67 | 0.00 | 0.00 |
August | 1755.04 | 290.00 | 1360.40 | 578.46 | 781.94 | 0.00 | 0.00 |
September | 1240.65 | 437.67 | 1068.34 | 461.37 | 606.97 | 0.00 | 0.00 |
October | 621.53 | 649.18 | 692.55 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 255.33 | 835.18 | 410.41 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 104.54 | 1290.86 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 989.53 | 724.30 | 969.26 | 393.32 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 104.54 | 231.60 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2067.03 | 1349.30 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.47 | 2191.30 | 363.08 | 0.00 | 363.08 | 0.00 | 0.00 |
February | 35.15 | 2048.00 | 553.20 | 0.00 | 553.20 | 0.00 | 0.00 |
March | 238.19 | 1454.64 | 670.88 | 0.00 | 670.88 | 0.00 | 0.00 |
April | 504.51 | 1013.07 | 854.84 | 3.41 | 851.43 | 0.00 | 0.00 |
May | 831.71 | 642.32 | 993.28 | 42.12 | 951.16 | 0.00 | 0.00 |
June | 1316.79 | 431.78 | 1194.71 | 101.70 | 1093.01 | 0.00 | 0.00 |
July | 1405.63 | 302.98 | 1108.25 | 71.54 | 1036.71 | 0.00 | 0.00 |
August | 1140.32 | 415.21 | 958.95 | 14.59 | 944.36 | 0.00 | 0.00 |
September | 662.34 | 693.96 | 729.78 | 0.15 | 729.63 | 0.00 | 0.00 |
October | 261.72 | 1102.94 | 545.54 | 0.00 | 545.54 | 0.00 | 0.00 |
November | 76.70 | 1408.55 | 366.59 | 0.00 | 366.59 | 0.00 | 0.00 |
December | 4.77 | 2125.15 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 543.16 | 1148.04 | 723.95 | 19.54 | 704.41 | 0.00 | 0.00 |
Minimum of Months | 3.47 | 302.98 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1405.63 | 2191.30 | 1194.71 | 101.70 | 1093.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.33 | 1333.26 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 314.30 | 1259.90 | 649.97 | 195.04 | 454.93 | 0.00 | 0.00 |
March | 751.31 | 904.10 | 932.69 | 390.60 | 542.09 | 0.00 | 0.00 |
April | 1184.99 | 662.06 | 1234.47 | 545.45 | 689.02 | 0.00 | 0.00 |
May | 1523.22 | 453.40 | 1383.05 | 611.79 | 771.26 | 0.00 | 0.00 |
June | 1889.21 | 304.45 | 1544.63 | 682.65 | 861.98 | 0.00 | 0.00 |
July | 1947.17 | 213.44 | 1483.25 | 653.05 | 830.20 | 0.00 | 0.00 |
August | 1716.03 | 285.56 | 1339.54 | 562.26 | 777.28 | 0.00 | 0.00 |
September | 1284.87 | 456.00 | 1114.73 | 494.45 | 620.28 | 0.00 | 0.00 |
October | 671.47 | 707.82 | 756.44 | 312.88 | 443.56 | 0.00 | 0.00 |
November | 264.87 | 902.70 | 429.06 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 89.40 | 1331.74 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 987.89 | 731.90 | 972.79 | 400.97 | 571.82 | 0.00 | 0.00 |
Minimum of Months | 89.40 | 213.44 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1947.17 | 1333.26 | 1544.63 | 682.65 | 861.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1294.48 | 1868.40 | 1561.24 | 911.34 | 649.90 | 0.00 | 0.00 |
February | 1462.76 | 1829.32 | 1782.55 | 859.53 | 923.02 | 0.00 | 0.00 |
March | 2192.33 | 1376.19 | 2175.72 | 1222.52 | 953.20 | 0.00 | 0.00 |
April | 1897.93 | 1072.06 | 1801.84 | 720.02 | 1081.82 | 0.00 | 0.00 |
May | 1805.35 | 719.98 | 1576.78 | 457.96 | 1118.82 | 0.00 | 0.00 |
June | 1939.13 | 480.20 | 1532.12 | 324.66 | 1207.46 | 0.00 | 0.00 |
July | 2175.37 | 338.75 | 1564.05 | 379.49 | 1184.56 | 0.00 | 0.00 |
August | 2390.32 | 454.54 | 1755.89 | 569.30 | 1186.59 | 0.00 | 0.00 |
September | 2554.64 | 733.84 | 2041.58 | 994.40 | 1047.18 | 0.00 | 0.00 |
October | 2119.56 | 1093.91 | 1953.48 | 1115.86 | 837.62 | 0.00 | 0.00 |
November | 1334.45 | 1355.65 | 1399.04 | 789.81 | 609.24 | 0.00 | 0.00 |
December | 1016.42 | 1865.70 | 1305.51 | 675.66 | 629.85 | 0.00 | 0.00 |
Annual Sum or Average | 1850.82 | 1095.11 | 1703.62 | 751.31 | 952.31 | 0.00 | 0.00 |
Minimum of Months | 1016.42 | 338.75 | 1305.51 | 324.66 | 609.24 | 0.00 | 0.00 |
Maximum of Months | 2554.64 | 1868.40 | 2175.72 | 1222.52 | 1207.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.71 | 1380.22 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 274.93 | 1299.25 | 615.97 | 158.31 | 457.66 | 0.00 | 0.00 |
March | 799.05 | 931.51 | 965.43 | 413.37 | 552.05 | 0.00 | 0.00 |
April | 1142.40 | 691.45 | 1182.03 | 484.68 | 697.35 | 0.00 | 0.00 |
May | 1554.14 | 483.56 | 1394.40 | 630.18 | 764.22 | 0.00 | 0.00 |
June | 2086.00 | 337.38 | 1682.38 | 791.32 | 891.06 | 0.00 | 0.00 |
July | 1986.83 | 239.33 | 1504.11 | 659.45 | 844.66 | 0.00 | 0.00 |
August | 1762.44 | 309.06 | 1360.38 | 578.45 | 781.94 | 0.00 | 0.00 |
September | 1237.00 | 481.22 | 1068.32 | 461.36 | 606.96 | 0.00 | 0.00 |
October | 606.74 | 729.28 | 692.54 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 246.57 | 918.41 | 410.40 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 103.17 | 1350.65 | 355.78 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 996.19 | 759.90 | 969.25 | 393.31 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 103.17 | 239.33 | 355.78 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2086.00 | 1380.22 | 1682.38 | 791.32 | 891.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.66 | 2213.70 | 363.09 | 0.00 | 363.09 | 0.00 | 0.00 |
February | 31.94 | 2073.58 | 553.22 | 0.00 | 553.22 | 0.00 | 0.00 |
March | 214.94 | 1507.45 | 670.90 | 0.00 | 670.90 | 0.00 | 0.00 |
April | 459.12 | 1073.03 | 854.86 | 3.41 | 851.45 | 0.00 | 0.00 |
May | 770.41 | 698.48 | 993.30 | 42.12 | 951.18 | 0.00 | 0.00 |
June | 1280.98 | 455.65 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
July | 1379.73 | 319.65 | 1108.28 | 71.54 | 1036.73 | 0.00 | 0.00 |
August | 1125.32 | 425.09 | 958.97 | 14.59 | 944.38 | 0.00 | 0.00 |
September | 653.13 | 694.68 | 729.79 | 0.15 | 729.64 | 0.00 | 0.00 |
October | 261.10 | 1079.92 | 545.55 | 0.00 | 545.55 | 0.00 | 0.00 |
November | 76.76 | 1385.55 | 366.60 | 0.00 | 366.60 | 0.00 | 0.00 |
December | 4.81 | 2114.30 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 524.80 | 1165.60 | 723.97 | 19.54 | 704.42 | 0.00 | 0.00 |
Minimum of Months | 3.66 | 319.65 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1379.73 | 2213.70 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.49 | 1340.78 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 305.89 | 1269.26 | 649.98 | 195.04 | 454.94 | 0.00 | 0.00 |
March | 728.89 | 923.15 | 932.70 | 390.61 | 542.09 | 0.00 | 0.00 |
April | 1159.19 | 675.70 | 1234.49 | 545.46 | 689.03 | 0.00 | 0.00 |
May | 1495.88 | 469.18 | 1383.07 | 611.81 | 771.26 | 0.00 | 0.00 |
June | 1872.01 | 307.22 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
July | 1934.73 | 214.04 | 1483.28 | 653.07 | 830.21 | 0.00 | 0.00 |
August | 1708.30 | 280.34 | 1339.56 | 562.27 | 777.29 | 0.00 | 0.00 |
September | 1281.31 | 439.73 | 1114.75 | 494.46 | 620.29 | 0.00 | 0.00 |
October | 674.27 | 676.22 | 756.45 | 312.89 | 443.56 | 0.00 | 0.00 |
November | 265.43 | 879.19 | 429.07 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 88.25 | 1322.85 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 977.34 | 730.46 | 972.81 | 400.98 | 571.83 | 0.00 | 0.00 |
Minimum of Months | 88.25 | 214.04 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1934.73 | 1340.78 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1258.81 | 1893.94 | 1561.30 | 911.38 | 649.92 | 0.00 | 0.00 |
February | 1415.92 | 1860.18 | 1782.62 | 859.56 | 923.05 | 0.00 | 0.00 |
March | 2128.83 | 1397.09 | 2175.80 | 1222.57 | 953.23 | 0.00 | 0.00 |
April | 1839.59 | 1110.64 | 1801.91 | 720.05 | 1081.86 | 0.00 | 0.00 |
May | 1745.76 | 769.62 | 1576.83 | 457.98 | 1118.85 | 0.00 | 0.00 |
June | 1899.02 | 502.52 | 1532.17 | 324.67 | 1207.49 | 0.00 | 0.00 |
July | 2149.75 | 348.60 | 1564.10 | 379.50 | 1184.59 | 0.00 | 0.00 |
August | 2373.03 | 451.15 | 1755.95 | 569.32 | 1186.63 | 0.00 | 0.00 |
September | 2540.90 | 709.53 | 2041.65 | 994.44 | 1047.22 | 0.00 | 0.00 |
October | 2102.70 | 1046.73 | 1953.56 | 1115.91 | 837.65 | 0.00 | 0.00 |
November | 1322.21 | 1312.57 | 1399.10 | 789.84 | 609.26 | 0.00 | 0.00 |
December | 995.68 | 1867.14 | 1305.56 | 675.69 | 629.87 | 0.00 | 0.00 |
Annual Sum or Average | 1816.68 | 1101.77 | 1703.68 | 751.34 | 952.34 | 0.00 | 0.00 |
Minimum of Months | 995.68 | 348.60 | 1305.56 | 324.67 | 609.26 | 0.00 | 0.00 |
Maximum of Months | 2540.90 | 1893.94 | 2175.80 | 1222.57 | 1207.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 105.22 | 1392.47 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 265.12 | 1311.61 | 615.98 | 158.31 | 457.67 | 0.00 | 0.00 |
March | 773.76 | 950.67 | 965.44 | 413.38 | 552.06 | 0.00 | 0.00 |
April | 1113.26 | 710.42 | 1182.05 | 484.69 | 697.36 | 0.00 | 0.00 |
May | 1525.17 | 500.69 | 1394.42 | 630.19 | 764.23 | 0.00 | 0.00 |
June | 2068.16 | 338.15 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
July | 1973.74 | 239.06 | 1504.13 | 659.46 | 844.67 | 0.00 | 0.00 |
August | 1755.20 | 301.90 | 1360.40 | 578.46 | 781.94 | 0.00 | 0.00 |
September | 1233.65 | 465.76 | 1068.34 | 461.37 | 606.97 | 0.00 | 0.00 |
October | 607.45 | 702.62 | 692.55 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 245.94 | 897.35 | 410.41 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 101.19 | 1343.46 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 984.51 | 760.09 | 969.26 | 393.32 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 101.19 | 239.06 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2068.16 | 1392.47 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16175137.80 | 0.574607E+10 | 0.972507E+09 | 0.00 | 0.972507E+09 | 0.00 | 0.00 |
February | 90877652.30 | 0.485046E+10 | 0.133834E+10 | 0.00 | 0.133834E+10 | 0.00 | 0.00 |
March | 0.601811E+09 | 0.383820E+10 | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.00 | 0.00 |
April | 0.123609E+10 | 0.261403E+10 | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.00 | 0.00 |
May | 0.209957E+10 | 0.177492E+10 | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.00 | 0.00 |
June | 0.332541E+10 | 0.114020E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
July | 0.368573E+10 | 0.834133E+09 | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.00 | 0.00 |
August | 0.301694E+10 | 0.109568E+10 | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.00 | 0.00 |
September | 0.171967E+10 | 0.169010E+10 | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.00 | 0.00 |
October | 0.756752E+09 | 0.266288E+10 | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.00 | 0.00 |
November | 0.229547E+09 | 0.333499E+10 | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.00 | 0.00 |
December | 18538874.78 | 0.543612E+10 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167971E+11 | 0.350178E+11 | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.00 | 0.00 |
Minimum of Months | 16175137.80 | 0.834133E+09 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368573E+10 | 0.574607E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469052E+09 | 0.347619E+10 | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.00 | 0.00 |
February | 0.759283E+09 | 0.297016E+10 | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.00 | 0.00 |
March | 0.198085E+10 | 0.235088E+10 | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.00 | 0.00 |
April | 0.303634E+10 | 0.165646E+10 | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.00 | 0.00 |
May | 0.402185E+10 | 0.119984E+10 | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.00 | 0.00 |
June | 0.485040E+10 | 0.770780E+09 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
July | 0.517221E+10 | 0.559494E+09 | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.00 | 0.00 |
August | 0.457327E+10 | 0.724604E+09 | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.00 | 0.00 |
September | 0.333691E+10 | 0.107815E+10 | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.00 | 0.00 |
October | 0.184960E+10 | 0.167849E+10 | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.00 | 0.00 |
November | 0.716708E+09 | 0.212222E+10 | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.00 | 0.00 |
December | 0.247147E+09 | 0.340272E+10 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310136E+11 | 0.219900E+11 | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247147E+09 | 0.559494E+09 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517221E+10 | 0.347619E+10 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340431E+10 | 0.489218E+10 | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.00 | 0.00 |
February | 0.345895E+10 | 0.434039E+10 | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.00 | 0.00 |
March | 0.574545E+10 | 0.354688E+10 | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.00 | 0.00 |
April | 0.480955E+10 | 0.271396E+10 | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.00 | 0.00 |
May | 0.469638E+10 | 0.195487E+10 | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.00 | 0.00 |
June | 0.491914E+10 | 0.124997E+10 | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.00 | 0.00 |
July | 0.574307E+10 | 0.904469E+09 | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.00 | 0.00 |
August | 0.635096E+10 | 0.116015E+10 | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.00 | 0.00 |
September | 0.660373E+10 | 0.173387E+10 | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.00 | 0.00 |
October | 0.569502E+10 | 0.259278E+10 | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.00 | 0.00 |
November | 0.348107E+10 | 0.316231E+10 | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.00 | 0.00 |
December | 0.270210E+10 | 0.478997E+10 | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.576097E+11 | 0.330418E+11 | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.00 | 0.00 |
Minimum of Months | 0.270210E+10 | 0.904469E+09 | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660373E+10 | 0.489218E+10 | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289386E+09 | 0.361397E+10 | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.00 | 0.00 |
February | 0.652546E+09 | 0.306975E+10 | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.00 | 0.00 |
March | 0.209325E+10 | 0.241681E+10 | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.00 | 0.00 |
April | 0.291167E+10 | 0.173467E+10 | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.00 | 0.00 |
May | 0.410162E+10 | 0.127182E+10 | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.00 | 0.00 |
June | 0.535775E+10 | 0.841850E+09 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
July | 0.527665E+10 | 0.620328E+09 | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.00 | 0.00 |
August | 0.470070E+10 | 0.776744E+09 | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.00 | 0.00 |
September | 0.321576E+10 | 0.113444E+10 | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.00 | 0.00 |
October | 0.166470E+10 | 0.173877E+10 | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.00 | 0.00 |
November | 0.661808E+09 | 0.216478E+10 | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.00 | 0.00 |
December | 0.280004E+09 | 0.345745E+10 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.312058E+11 | 0.228414E+11 | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280004E+09 | 0.620328E+09 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535775E+10 | 0.361397E+10 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9302823.01 | 0.586918E+10 | 0.972485E+09 | 0.00 | 0.972485E+09 | 0.00 | 0.00 |
February | 85044183.66 | 0.495452E+10 | 0.133831E+10 | 0.00 | 0.133831E+10 | 0.00 | 0.00 |
March | 0.637963E+09 | 0.389612E+10 | 0.179689E+10 | 0.00 | 0.179689E+10 | 0.00 | 0.00 |
April | 0.130768E+10 | 0.262588E+10 | 0.221575E+10 | 8841635.65 | 0.220691E+10 | 0.00 | 0.00 |
May | 0.222765E+10 | 0.172038E+10 | 0.266041E+10 | 0.112816E+09 | 0.254759E+10 | 0.00 | 0.00 |
June | 0.341311E+10 | 0.111917E+10 | 0.309669E+10 | 0.263604E+09 | 0.283309E+10 | 0.00 | 0.00 |
July | 0.376483E+10 | 0.811497E+09 | 0.296834E+10 | 0.191612E+09 | 0.277673E+10 | 0.00 | 0.00 |
August | 0.305425E+10 | 0.111211E+10 | 0.256844E+10 | 39072938.42 | 0.252937E+10 | 0.00 | 0.00 |
September | 0.171678E+10 | 0.179875E+10 | 0.189159E+10 | 392986.49 | 0.189119E+10 | 0.00 | 0.00 |
October | 0.700995E+09 | 0.295410E+10 | 0.146117E+10 | 0.00 | 0.146117E+10 | 0.00 | 0.00 |
November | 0.198809E+09 | 0.365097E+10 | 0.950199E+09 | 0.00 | 0.950199E+09 | 0.00 | 0.00 |
December | 12777455.78 | 0.569200E+10 | 0.910216E+09 | 0.00 | 0.910216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171292E+11 | 0.362047E+11 | 0.228305E+11 | 0.616338E+09 | 0.222142E+11 | 0.00 | 0.00 |
Minimum of Months | 9302823.01 | 0.811497E+09 | 0.910216E+09 | 0.00 | 0.910216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376483E+10 | 0.586918E+10 | 0.309669E+10 | 0.263604E+09 | 0.283309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.466919E+09 | 0.357100E+10 | 0.118644E+10 | 0.382575E+09 | 0.803870E+09 | 0.00 | 0.00 |
February | 0.760350E+09 | 0.304794E+10 | 0.157240E+10 | 0.471838E+09 | 0.110057E+10 | 0.00 | 0.00 |
March | 0.201232E+10 | 0.242155E+10 | 0.249811E+10 | 0.104619E+10 | 0.145192E+10 | 0.00 | 0.00 |
April | 0.307149E+10 | 0.171606E+10 | 0.319975E+10 | 0.141382E+10 | 0.178593E+10 | 0.00 | 0.00 |
May | 0.407980E+10 | 0.121440E+10 | 0.370436E+10 | 0.163863E+10 | 0.206573E+10 | 0.00 | 0.00 |
June | 0.489684E+10 | 0.789125E+09 | 0.400369E+10 | 0.176943E+10 | 0.223426E+10 | 0.00 | 0.00 |
July | 0.521530E+10 | 0.571677E+09 | 0.397275E+10 | 0.174914E+10 | 0.222361E+10 | 0.00 | 0.00 |
August | 0.459623E+10 | 0.764854E+09 | 0.358783E+10 | 0.150597E+10 | 0.208186E+10 | 0.00 | 0.00 |
September | 0.333040E+10 | 0.118194E+10 | 0.288938E+10 | 0.128161E+10 | 0.160777E+10 | 0.00 | 0.00 |
October | 0.179845E+10 | 0.189582E+10 | 0.202604E+10 | 0.838022E+09 | 0.118802E+10 | 0.00 | 0.00 |
November | 0.686543E+09 | 0.233979E+10 | 0.111213E+10 | 0.356759E+09 | 0.755376E+09 | 0.00 | 0.00 |
December | 0.239442E+09 | 0.356692E+10 | 0.925170E+09 | 0.191159E+09 | 0.734010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311541E+11 | 0.230811E+11 | 0.306781E+11 | 0.126451E+11 | 0.180329E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239442E+09 | 0.571677E+09 | 0.925170E+09 | 0.191159E+09 | 0.734010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521530E+10 | 0.357100E+10 | 0.400369E+10 | 0.176943E+10 | 0.223426E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.346713E+10 | 0.500433E+10 | 0.418163E+10 | 0.244094E+10 | 0.174069E+10 | 0.00 | 0.00 |
February | 0.353871E+10 | 0.442549E+10 | 0.431234E+10 | 0.207937E+10 | 0.223297E+10 | 0.00 | 0.00 |
March | 0.587194E+10 | 0.368599E+10 | 0.582745E+10 | 0.327439E+10 | 0.255305E+10 | 0.00 | 0.00 |
April | 0.491943E+10 | 0.277877E+10 | 0.467038E+10 | 0.186628E+10 | 0.280409E+10 | 0.00 | 0.00 |
May | 0.483544E+10 | 0.192839E+10 | 0.422324E+10 | 0.122660E+10 | 0.299664E+10 | 0.00 | 0.00 |
June | 0.502622E+10 | 0.124469E+10 | 0.397126E+10 | 0.841520E+09 | 0.312974E+10 | 0.00 | 0.00 |
July | 0.582650E+10 | 0.907315E+09 | 0.418914E+10 | 0.101641E+10 | 0.317273E+10 | 0.00 | 0.00 |
August | 0.640224E+10 | 0.121745E+10 | 0.470299E+10 | 0.152482E+10 | 0.317817E+10 | 0.00 | 0.00 |
September | 0.662162E+10 | 0.190211E+10 | 0.529177E+10 | 0.257747E+10 | 0.271430E+10 | 0.00 | 0.00 |
October | 0.567703E+10 | 0.292993E+10 | 0.523221E+10 | 0.298873E+10 | 0.224348E+10 | 0.00 | 0.00 |
November | 0.345890E+10 | 0.351384E+10 | 0.362632E+10 | 0.204718E+10 | 0.157915E+10 | 0.00 | 0.00 |
December | 0.272237E+10 | 0.499709E+10 | 0.349667E+10 | 0.180968E+10 | 0.168699E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583675E+11 | 0.345354E+11 | 0.537254E+11 | 0.236934E+11 | 0.300320E+11 | 0.00 | 0.00 |
Minimum of Months | 0.272237E+10 | 0.907315E+09 | 0.349667E+10 | 0.841520E+09 | 0.157915E+10 | 0.00 | 0.00 |
Maximum of Months | 0.662162E+10 | 0.500433E+10 | 0.582745E+10 | 0.327439E+10 | 0.317817E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291156E+09 | 0.369677E+10 | 0.101795E+10 | 0.238974E+09 | 0.778977E+09 | 0.00 | 0.00 |
February | 0.665116E+09 | 0.314315E+10 | 0.149016E+10 | 0.382981E+09 | 0.110718E+10 | 0.00 | 0.00 |
March | 0.214018E+10 | 0.249496E+10 | 0.258580E+10 | 0.110717E+10 | 0.147862E+10 | 0.00 | 0.00 |
April | 0.296111E+10 | 0.179224E+10 | 0.306383E+10 | 0.125629E+10 | 0.180754E+10 | 0.00 | 0.00 |
May | 0.416261E+10 | 0.129516E+10 | 0.373475E+10 | 0.168786E+10 | 0.204689E+10 | 0.00 | 0.00 |
June | 0.540691E+10 | 0.874488E+09 | 0.436074E+10 | 0.205110E+10 | 0.230963E+10 | 0.00 | 0.00 |
July | 0.532153E+10 | 0.641016E+09 | 0.402862E+10 | 0.176628E+10 | 0.226234E+10 | 0.00 | 0.00 |
August | 0.472053E+10 | 0.827784E+09 | 0.364365E+10 | 0.154931E+10 | 0.209434E+10 | 0.00 | 0.00 |
September | 0.320630E+10 | 0.124733E+10 | 0.276909E+10 | 0.119585E+10 | 0.157324E+10 | 0.00 | 0.00 |
October | 0.162509E+10 | 0.195332E+10 | 0.185489E+10 | 0.653397E+09 | 0.120149E+10 | 0.00 | 0.00 |
November | 0.639108E+09 | 0.238053E+10 | 0.106376E+10 | 0.306536E+09 | 0.757221E+09 | 0.00 | 0.00 |
December | 0.276335E+09 | 0.361759E+10 | 0.952922E+09 | 0.207630E+09 | 0.745292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314160E+11 | 0.239643E+11 | 0.305662E+11 | 0.124034E+11 | 0.181628E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276335E+09 | 0.641016E+09 | 0.952922E+09 | 0.207630E+09 | 0.745292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540691E+10 | 0.369677E+10 | 0.436074E+10 | 0.205110E+10 | 0.230963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9800418.15 | 0.592917E+10 | 0.972507E+09 | 0.00 | 0.972507E+09 | 0.00 | 0.00 |
February | 77279815.50 | 0.501640E+10 | 0.133834E+10 | 0.00 | 0.133834E+10 | 0.00 | 0.00 |
March | 0.575685E+09 | 0.403757E+10 | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.00 | 0.00 |
April | 0.119005E+10 | 0.278130E+10 | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.00 | 0.00 |
May | 0.206346E+10 | 0.187080E+10 | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.00 | 0.00 |
June | 0.332031E+10 | 0.118105E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
July | 0.369548E+10 | 0.856151E+09 | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.00 | 0.00 |
August | 0.301405E+10 | 0.113856E+10 | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.00 | 0.00 |
September | 0.169292E+10 | 0.180061E+10 | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.00 | 0.00 |
October | 0.699336E+09 | 0.289245E+10 | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.00 | 0.00 |
November | 0.198955E+09 | 0.359133E+10 | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.00 | 0.00 |
December | 12872697.92 | 0.566293E+10 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165502E+11 | 0.367583E+11 | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.00 | 0.00 |
Minimum of Months | 9800418.15 | 0.856151E+09 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.369548E+10 | 0.592917E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456628E+09 | 0.359115E+10 | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.00 | 0.00 |
February | 0.740011E+09 | 0.307059E+10 | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.00 | 0.00 |
March | 0.195225E+10 | 0.247257E+10 | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.00 | 0.00 |
April | 0.300461E+10 | 0.175140E+10 | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.00 | 0.00 |
May | 0.400656E+10 | 0.125666E+10 | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.00 | 0.00 |
June | 0.485225E+10 | 0.796325E+09 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
July | 0.518197E+10 | 0.573289E+09 | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.00 | 0.00 |
August | 0.457551E+10 | 0.750853E+09 | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.00 | 0.00 |
September | 0.332115E+10 | 0.113977E+10 | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.00 | 0.00 |
October | 0.180598E+10 | 0.181118E+10 | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.00 | 0.00 |
November | 0.687985E+09 | 0.227886E+10 | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.00 | 0.00 |
December | 0.236375E+09 | 0.354312E+10 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308213E+11 | 0.230358E+11 | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236375E+09 | 0.573289E+09 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.518197E+10 | 0.359115E+10 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337160E+10 | 0.507272E+10 | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.00 | 0.00 |
February | 0.342540E+10 | 0.450015E+10 | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.00 | 0.00 |
March | 0.570186E+10 | 0.374196E+10 | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.00 | 0.00 |
April | 0.476821E+10 | 0.287879E+10 | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.00 | 0.00 |
May | 0.467583E+10 | 0.206136E+10 | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.00 | 0.00 |
June | 0.492227E+10 | 0.130254E+10 | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.00 | 0.00 |
July | 0.575790E+10 | 0.933684E+09 | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.00 | 0.00 |
August | 0.635593E+10 | 0.120836E+10 | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.00 | 0.00 |
September | 0.658601E+10 | 0.183910E+10 | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.00 | 0.00 |
October | 0.563188E+10 | 0.280356E+10 | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.00 | 0.00 |
November | 0.342717E+10 | 0.340218E+10 | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.00 | 0.00 |
December | 0.266683E+10 | 0.500095E+10 | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.572909E+11 | 0.347454E+11 | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.00 | 0.00 |
Minimum of Months | 0.266683E+10 | 0.933684E+09 | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.658601E+10 | 0.507272E+10 | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281829E+09 | 0.372958E+10 | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.00 | 0.00 |
February | 0.641372E+09 | 0.317304E+10 | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.00 | 0.00 |
March | 0.207243E+10 | 0.254627E+10 | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.00 | 0.00 |
April | 0.288556E+10 | 0.184141E+10 | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.00 | 0.00 |
May | 0.408503E+10 | 0.134105E+10 | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.00 | 0.00 |
June | 0.536066E+10 | 0.876483E+09 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
July | 0.528647E+10 | 0.640298E+09 | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.00 | 0.00 |
August | 0.470112E+10 | 0.808609E+09 | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.00 | 0.00 |
September | 0.319762E+10 | 0.120724E+10 | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.00 | 0.00 |
October | 0.162698E+10 | 0.188190E+10 | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.00 | 0.00 |
November | 0.637476E+09 | 0.232593E+10 | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.00 | 0.00 |
December | 0.271018E+09 | 0.359832E+10 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310476E+11 | 0.239702E+11 | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271018E+09 | 0.640298E+09 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.536066E+10 | 0.372958E+10 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.562863E+10 | -0.488012E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -748507778.0 | 58.99 | 0.00 | 0.00 |
February | 0.516969E+10 | -0.449946E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -670231742.4 | 58.98 | 0.00 | 0.00 |
March | 0.597142E+10 | -0.525357E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717848270.8 | 58.99 | 0.00 | 0.00 |
April | 0.522337E+10 | -0.454106E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682312433.6 | 58.98 | 0.00 | 0.00 |
May | 0.528878E+10 | -0.459550E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693281443.6 | 58.98 | 0.00 | 0.00 |
June | 0.495004E+10 | -0.428193E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668106514.7 | 58.98 | 0.00 | 0.00 |
July | 0.452436E+10 | -0.383721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687148568.7 | 58.98 | 0.00 | 0.00 |
August | 0.485232E+10 | -0.416398E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688333147.0 | 58.98 | 0.00 | 0.00 |
September | 0.448430E+10 | -0.381723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667075078.7 | 58.98 | 0.00 | 0.00 |
October | 0.483813E+10 | -0.413951E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698628218.3 | 58.98 | 0.00 | 0.00 |
November | 0.502285E+10 | -0.433461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -688243474.1 | 58.98 | 0.00 | 0.00 |
December | 0.528458E+10 | -0.454949E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -735090433.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.612385E+11 | -0.528937E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.834481E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448430E+10 | -0.525357E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -748507778.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.597142E+10 | -0.381723E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667075078.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 4433.29 | 32.59 | 236.17 | 250.83 | 3566.29 | 33.72 | 243.00 | 224.00 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5564.35 | 32.78 | 246.33 | 256.17 | 1866.82 | 27.01 | 241.00 | 237.67 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7947.08 | 29.83 | 255.00 | 326.83 | 1507.88 | 21.82 | 190.67 | 294.33 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 2081.46 | 18.78 | 3.33 | 346.00 | 1170.02 | 20.97 | 201.17 | 311.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1886.02 | 18.85 | 0.50 | 384.00 | 1112.42 | 21.11 | 184.33 | 337.83 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:19 | 1699.30 | 18.65 | 0.00 | 393.17 | 979.10 | 20.87 | 224.50 | 353.83 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1782.64 | 18.68 | 1.00 | 400.00 | 1013.05 | 20.90 | 221.17 | 355.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2114.15 | 19.16 | 4.67 | 377.50 | 1176.23 | 21.37 | 254.00 | 338.17 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3016.72 | 20.65 | 33.33 | 324.33 | 1551.94 | 22.00 | 220.33 | 292.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 6431.02 | 32.23 | 277.67 | 298.33 | 1587.10 | 22.41 | 196.83 | 277.00 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 4171.27 | 32.39 | 240.50 | 240.67 | 1696.42 | 27.89 | 219.17 | 217.33 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3736.40 | 31.21 | 209.17 | 239.17 | 2926.26 | 33.09 | 223.33 | 208.67 |
Annual Sum or Average | 3928.50 | 0.51 | 3536.63 | 24.43 | 1507.67 | 3837.00 | 1557.93 | 23.67 | 2619.50 | 3448.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1699.30 | 18.65 | 0.00 | 239.17 | 979.10 | 20.87 | 184.33 | 208.67 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7947.08 | 32.78 | 277.67 | 400.00 | 3566.29 | 33.72 | 254.00 | 355.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:20 | 1522.75 | 20.83 | 70.83 | 236.17 | 762.65 | 21.58 | 84.00 | 188.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 2105.02 | 21.98 | 83.33 | 248.33 | 1093.83 | 22.84 | 112.00 | 217.17 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2836.87 | 21.68 | 104.50 | 320.00 | 1249.85 | 22.42 | 90.17 | 285.33 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 3080.93 | 21.10 | 104.33 | 350.50 | 1728.75 | 22.37 | 88.17 | 315.17 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4115.81 | 22.59 | 103.50 | 392.17 | 1749.47 | 22.35 | 59.00 | 347.67 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3743.24 | 21.83 | 133.33 | 403.17 | 1649.07 | 22.09 | 79.17 | 372.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3539.47 | 21.98 | 135.17 | 409.83 | 1561.57 | 22.10 | 81.00 | 372.00 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3260.65 | 21.37 | 110.50 | 379.00 | 1456.79 | 22.33 | 77.33 | 345.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3322.93 | 22.82 | 85.83 | 323.83 | 1832.09 | 23.79 | 102.00 | 288.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2106.25 | 20.82 | 81.67 | 288.67 | 1140.59 | 22.66 | 95.00 | 254.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1533.72 | 21.15 | 87.00 | 230.00 | 842.21 | 21.98 | 91.33 | 178.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1312.48 | 20.10 | 60.33 | 226.17 | 659.48 | 21.06 | 69.17 | 173.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2857.60 | 21.57 | 1160.33 | 3807.83 | 1367.90 | 22.31 | 1028.33 | 3340.17 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1312.48 | 20.10 | 60.33 | 226.17 | 659.48 | 21.06 | 59.00 | 173.83 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 4115.81 | 22.82 | 135.17 | 409.83 | 1832.09 | 23.79 | 112.00 | 372.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-11:20 | 655.71 | 15.92 | 0.00 | 220.67 | 368.38 | 18.17 | 0.00 | 136.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 861.52 | 17.01 | 0.00 | 241.83 | 481.01 | 19.15 | 0.67 | 192.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 911.37 | 17.56 | 0.00 | 314.17 | 535.61 | 19.79 | 4.33 | 266.00 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1051.27 | 18.12 | 0.00 | 350.17 | 620.82 | 20.23 | 59.17 | 316.00 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1263.28 | 20.32 | 26.67 | 401.50 | 767.87 | 22.43 | 163.33 | 363.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1414.12 | 21.76 | 81.83 | 413.17 | 830.83 | 22.69 | 236.67 | 389.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1345.47 | 21.42 | 75.83 | 419.17 | 788.69 | 22.43 | 234.83 | 389.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1190.90 | 18.83 | 0.00 | 387.17 | 709.63 | 20.98 | 141.17 | 353.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 995.06 | 18.36 | 0.00 | 321.50 | 617.93 | 20.58 | 42.00 | 272.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 799.85 | 16.77 | 0.00 | 281.17 | 461.99 | 18.99 | 0.33 | 222.33 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:39 | 635.98 | 15.39 | 0.00 | 217.33 | 355.50 | 17.55 | 0.00 | 127.33 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:09 | 660.22 | 15.85 | 0.00 | 207.50 | 362.67 | 18.02 | 0.00 | 118.00 |
Annual Sum or Average | 3928.50 | 0.52 | 1031.30 | 18.48 | 184.33 | 3775.33 | 605.59 | 20.39 | 882.50 | 3147.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 635.98 | 15.39 | 0.00 | 207.50 | 355.50 | 17.55 | 0.00 | 118.00 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1414.12 | 21.76 | 81.83 | 419.17 | 830.83 | 22.69 | 236.67 | 389.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1426.64 | 21.27 | 86.00 | 235.83 | 778.22 | 22.23 | 87.00 | 189.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:50 | 1926.76 | 20.40 | 68.17 | 248.17 | 1043.01 | 22.71 | 97.50 | 217.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2785.35 | 21.52 | 101.67 | 322.00 | 1576.35 | 22.75 | 99.17 | 287.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 3297.10 | 20.86 | 104.67 | 346.17 | 1399.71 | 20.89 | 55.50 | 312.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3530.01 | 18.16 | 43.00 | 390.50 | 1955.61 | 18.89 | 0.17 | 353.83 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3733.17 | 17.92 | 52.83 | 400.83 | 1609.90 | 18.87 | 0.17 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3330.46 | 17.98 | 54.83 | 407.17 | 1516.01 | 19.05 | 6.17 | 371.00 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3117.58 | 19.92 | 85.50 | 382.83 | 1694.12 | 21.29 | 63.17 | 347.17 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3406.68 | 22.40 | 83.50 | 321.83 | 1506.43 | 22.19 | 69.17 | 290.33 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:20 | 1976.09 | 20.50 | 79.67 | 288.00 | 1061.45 | 22.43 | 91.67 | 254.17 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:39 | 1465.77 | 20.77 | 86.83 | 228.50 | 782.14 | 21.55 | 82.33 | 181.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:50 | 1356.11 | 19.74 | 56.33 | 221.67 | 729.02 | 21.71 | 72.17 | 173.67 |
Annual Sum or Average | 3928.50 | 0.51 | 2760.49 | 19.96 | 903.00 | 3793.50 | 1365.03 | 21.01 | 724.17 | 3348.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1356.11 | 17.92 | 43.00 | 221.67 | 729.02 | 18.87 | 0.17 | 173.67 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3733.17 | 22.40 | 104.67 | 407.17 | 1955.61 | 22.75 | 99.17 | 371.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:30 | 4299.04 | 32.13 | 233.33 | 248.83 | 3468.92 | 33.25 | 233.00 | 221.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5417.85 | 32.40 | 242.00 | 254.67 | 1764.78 | 24.98 | 107.00 | 236.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7807.59 | 28.72 | 235.00 | 325.67 | 1405.53 | 19.05 | 19.17 | 291.83 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 1982.02 | 14.93 | 0.00 | 343.83 | 1099.63 | 18.42 | 11.50 | 309.17 |
May | 332.17 | 0.52 | 0.48 | 01-MAY-06:49 | 1801.01 | 15.21 | 0.00 | 381.33 | 1054.42 | 18.78 | 3.83 | 333.17 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:30 | 1628.84 | 15.05 | 0.00 | 390.50 | 933.71 | 18.55 | 0.33 | 350.67 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1707.10 | 15.00 | 0.00 | 397.17 | 963.53 | 18.50 | 7.33 | 351.67 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2018.59 | 15.43 | 0.00 | 374.33 | 1111.23 | 18.91 | 18.83 | 334.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2875.13 | 17.10 | 17.00 | 321.83 | 1448.62 | 19.52 | 28.50 | 289.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:30 | 6296.77 | 31.63 | 270.67 | 297.50 | 1485.84 | 19.52 | 25.33 | 274.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:49 | 4051.33 | 32.05 | 237.67 | 239.50 | 1612.60 | 26.22 | 135.33 | 215.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3592.28 | 29.73 | 195.33 | 236.50 | 2838.77 | 32.70 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.51 | 3425.93 | 21.99 | 1431.00 | 3811.67 | 1480.80 | 21.50 | 807.00 | 3414.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1628.84 | 14.93 | 0.00 | 236.50 | 933.71 | 18.42 | 0.33 | 206.50 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7807.59 | 32.40 | 270.67 | 397.17 | 3468.92 | 33.25 | 233.00 | 351.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:30 | 1477.23 | 20.32 | 70.00 | 234.83 | 728.29 | 21.32 | 78.17 | 183.83 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-09:00 | 2005.24 | 20.24 | 69.33 | 246.50 | 1048.45 | 22.63 | 98.50 | 214.67 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:30 | 2755.43 | 21.12 | 103.17 | 317.50 | 1194.25 | 22.22 | 79.83 | 281.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2997.68 | 20.65 | 104.00 | 349.00 | 1663.95 | 22.18 | 83.00 | 312.33 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4019.07 | 22.14 | 103.50 | 389.83 | 1675.06 | 22.17 | 58.17 | 344.33 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3653.59 | 21.40 | 132.83 | 400.83 | 1582.25 | 21.91 | 76.83 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3450.61 | 21.54 | 135.17 | 406.83 | 1495.10 | 21.92 | 77.50 | 369.83 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3173.41 | 20.91 | 110.17 | 377.00 | 1389.67 | 22.15 | 69.50 | 343.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3229.69 | 22.36 | 85.83 | 322.33 | 1758.60 | 23.59 | 87.83 | 284.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2043.95 | 20.34 | 81.33 | 286.83 | 1091.91 | 22.44 | 84.50 | 249.83 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-07:40 | 1489.96 | 20.70 | 87.00 | 228.00 | 810.18 | 21.75 | 84.67 | 173.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1272.13 | 19.60 | 59.67 | 224.67 | 630.27 | 20.80 | 64.00 | 169.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2779.03 | 21.02 | 1142.00 | 3784.17 | 1310.61 | 22.11 | 942.50 | 3298.50 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1272.13 | 19.60 | 59.67 | 224.67 | 630.27 | 20.80 | 58.17 | 169.83 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 4019.07 | 22.36 | 135.17 | 406.83 | 1758.60 | 23.59 | 98.50 | 369.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.55 | 0.48 | 01-JAN-11:30 | 631.52 | 11.93 | 0.00 | 217.33 | 354.64 | 15.52 | 0.00 | 127.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 830.96 | 13.29 | 0.00 | 240.00 | 463.58 | 16.71 | 0.00 | 187.00 |
March | 339.33 | 0.52 | 0.48 | 01-MAR-08:39 | 879.34 | 14.04 | 0.00 | 311.50 | 518.04 | 17.55 | 0.00 | 259.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1019.92 | 14.67 | 0.00 | 349.50 | 600.63 | 18.11 | 0.17 | 310.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1219.44 | 17.21 | 26.17 | 399.83 | 743.96 | 20.55 | 40.67 | 359.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1364.42 | 18.96 | 74.50 | 411.83 | 802.49 | 20.68 | 71.33 | 386.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1298.16 | 18.57 | 71.00 | 418.17 | 761.88 | 20.41 | 62.50 | 386.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1148.56 | 15.42 | 0.00 | 385.50 | 686.24 | 18.92 | 12.17 | 350.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 958.85 | 15.24 | 0.00 | 319.33 | 598.71 | 18.74 | 0.00 | 267.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 771.20 | 13.09 | 0.00 | 278.67 | 446.03 | 16.59 | 0.00 | 215.50 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:50 | 612.75 | 11.46 | 0.00 | 214.67 | 342.29 | 14.91 | 0.00 | 119.83 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:20 | 636.12 | 11.82 | 0.00 | 205.00 | 348.79 | 15.33 | 0.00 | 109.50 |
Annual Sum or Average | 3928.50 | 0.52 | 995.24 | 15.08 | 171.67 | 3751.33 | 585.19 | 18.18 | 186.83 | 3080.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 612.75 | 11.46 | 0.00 | 205.00 | 342.29 | 14.91 | 0.00 | 109.50 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1364.42 | 18.96 | 74.50 | 418.17 | 802.49 | 20.68 | 71.33 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1387.24 | 20.90 | 85.00 | 233.33 | 749.39 | 22.12 | 85.67 | 183.17 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-11:20 | 1868.53 | 19.99 | 68.17 | 247.00 | 999.73 | 22.61 | 95.33 | 214.33 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2712.40 | 21.11 | 101.67 | 320.50 | 1517.41 | 22.62 | 95.83 | 284.50 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:40 | 3159.57 | 20.43 | 104.50 | 343.83 | 1339.77 | 20.74 | 53.67 | 309.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-07:10 | 3423.89 | 17.67 | 43.00 | 389.00 | 1862.82 | 18.73 | 0.00 | 349.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3586.28 | 17.43 | 52.67 | 399.33 | 1533.94 | 18.69 | 0.00 | 366.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3203.50 | 17.49 | 54.83 | 404.33 | 1447.36 | 18.87 | 3.83 | 369.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3031.18 | 19.47 | 85.50 | 380.17 | 1626.84 | 21.14 | 60.17 | 342.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3320.02 | 21.97 | 83.50 | 320.33 | 1436.48 | 22.05 | 65.67 | 288.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:30 | 1917.47 | 20.08 | 78.67 | 286.33 | 1016.74 | 22.31 | 90.00 | 251.67 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:50 | 1424.53 | 20.40 | 86.50 | 226.17 | 752.13 | 21.44 | 81.83 | 175.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1313.67 | 19.16 | 53.83 | 220.00 | 699.26 | 21.60 | 71.50 | 168.17 |
Annual Sum or Average | 3928.50 | 0.51 | 2670.28 | 19.51 | 897.83 | 3770.33 | 1306.27 | 20.87 | 703.50 | 3302.83 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1313.67 | 17.43 | 43.00 | 220.00 | 699.26 | 18.69 | 0.00 | 168.17 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3586.28 | 21.97 | 104.50 | 404.33 | 1862.82 | 22.62 | 95.83 | 369.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:30 | 4299.02 | 32.13 | 233.33 | 248.83 | 3468.82 | 33.25 | 233.00 | 221.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5417.76 | 32.40 | 242.00 | 254.67 | 1764.65 | 24.99 | 107.00 | 236.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7807.47 | 28.72 | 235.00 | 325.67 | 1405.42 | 19.05 | 19.17 | 291.83 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 1981.89 | 14.94 | 0.00 | 343.83 | 1099.54 | 18.42 | 11.50 | 309.17 |
May | 332.17 | 0.52 | 0.48 | 01-MAY-06:49 | 1800.92 | 15.21 | 0.00 | 381.33 | 1054.34 | 18.78 | 3.83 | 333.17 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:30 | 1628.76 | 15.05 | 0.00 | 390.50 | 933.65 | 18.55 | 0.33 | 350.67 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1707.00 | 15.01 | 0.00 | 397.17 | 963.45 | 18.50 | 7.33 | 351.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2018.46 | 15.43 | 0.00 | 374.33 | 1111.14 | 18.91 | 18.83 | 334.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2875.00 | 17.10 | 17.00 | 321.83 | 1448.51 | 19.52 | 28.50 | 289.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:30 | 6296.67 | 31.64 | 270.67 | 297.50 | 1485.73 | 19.52 | 25.33 | 274.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:49 | 4051.28 | 32.05 | 237.67 | 239.50 | 1612.50 | 26.22 | 135.33 | 215.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3592.24 | 29.73 | 195.33 | 236.50 | 2838.67 | 32.70 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.51 | 3425.84 | 22.00 | 1431.00 | 3811.67 | 1480.71 | 21.50 | 807.00 | 3414.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1628.76 | 14.94 | 0.00 | 236.50 | 933.65 | 18.42 | 0.33 | 206.50 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7807.47 | 32.40 | 270.67 | 397.17 | 3468.82 | 33.25 | 233.00 | 351.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:30 | 1477.19 | 20.32 | 70.00 | 234.83 | 728.24 | 21.32 | 78.17 | 183.83 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-09:00 | 2005.18 | 20.24 | 69.33 | 246.50 | 1048.38 | 22.63 | 98.50 | 214.67 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:30 | 2755.38 | 21.12 | 103.17 | 317.50 | 1194.18 | 22.22 | 79.83 | 281.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2997.62 | 20.65 | 104.00 | 349.00 | 1663.87 | 22.18 | 83.17 | 312.33 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4019.01 | 22.14 | 103.50 | 389.83 | 1674.99 | 22.17 | 58.17 | 344.33 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3653.52 | 21.40 | 132.83 | 400.83 | 1582.18 | 21.92 | 76.83 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3450.54 | 21.54 | 135.17 | 406.83 | 1495.03 | 21.93 | 77.50 | 369.83 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3173.34 | 20.91 | 110.17 | 377.00 | 1389.59 | 22.15 | 69.50 | 343.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3229.64 | 22.36 | 85.83 | 322.33 | 1758.52 | 23.60 | 87.83 | 284.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2043.90 | 20.34 | 81.33 | 286.83 | 1091.85 | 22.44 | 84.50 | 249.83 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-07:40 | 1489.92 | 20.70 | 87.00 | 228.00 | 810.13 | 21.75 | 84.67 | 173.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1272.08 | 19.60 | 59.67 | 224.67 | 630.22 | 20.80 | 64.00 | 169.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2778.97 | 21.02 | 1142.00 | 3784.17 | 1310.54 | 22.11 | 942.67 | 3298.33 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1272.08 | 19.60 | 59.67 | 224.67 | 630.22 | 20.80 | 58.17 | 169.83 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 4019.01 | 22.36 | 135.17 | 406.83 | 1758.52 | 23.60 | 98.50 | 369.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.55 | 0.48 | 01-JAN-11:30 | 631.49 | 11.93 | 0.00 | 217.33 | 354.62 | 15.52 | 0.00 | 127.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 830.92 | 13.29 | 0.00 | 240.00 | 463.54 | 16.71 | 0.00 | 187.00 |
March | 339.33 | 0.52 | 0.48 | 01-MAR-08:39 | 879.31 | 14.05 | 0.00 | 311.50 | 518.00 | 17.56 | 0.00 | 259.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1019.88 | 14.67 | 0.00 | 349.50 | 600.59 | 18.12 | 0.17 | 310.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1219.41 | 17.22 | 26.17 | 399.83 | 743.91 | 20.55 | 40.67 | 359.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1364.38 | 18.96 | 74.50 | 411.83 | 802.44 | 20.68 | 71.33 | 386.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1298.11 | 18.57 | 71.00 | 418.17 | 761.83 | 20.42 | 62.50 | 386.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1148.52 | 15.42 | 0.00 | 385.50 | 686.19 | 18.92 | 12.17 | 350.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 958.83 | 15.24 | 0.00 | 319.33 | 598.67 | 18.74 | 0.00 | 267.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 771.17 | 13.09 | 0.00 | 278.67 | 445.99 | 16.59 | 0.00 | 215.33 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:50 | 612.72 | 11.46 | 0.00 | 214.67 | 342.26 | 14.91 | 0.00 | 119.67 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:20 | 636.09 | 11.82 | 0.00 | 205.00 | 348.76 | 15.33 | 0.00 | 109.50 |
Annual Sum or Average | 3928.50 | 0.52 | 995.21 | 15.08 | 171.67 | 3751.33 | 585.15 | 18.18 | 186.83 | 3080.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 612.72 | 11.46 | 0.00 | 205.00 | 342.26 | 14.91 | 0.00 | 109.50 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1364.38 | 18.96 | 74.50 | 418.17 | 802.44 | 20.68 | 71.33 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1387.20 | 20.90 | 85.00 | 233.33 | 749.34 | 22.12 | 85.67 | 183.17 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-11:20 | 1868.47 | 19.99 | 68.17 | 247.00 | 999.66 | 22.62 | 95.33 | 214.33 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2712.35 | 21.11 | 101.67 | 320.50 | 1517.34 | 22.62 | 95.83 | 284.50 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:40 | 3159.50 | 20.43 | 104.50 | 343.83 | 1339.70 | 20.74 | 53.67 | 309.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-07:10 | 3423.84 | 17.67 | 43.00 | 389.00 | 1862.75 | 18.73 | 0.00 | 349.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3586.21 | 17.43 | 52.67 | 399.33 | 1533.86 | 18.69 | 0.00 | 366.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3203.43 | 17.49 | 54.83 | 404.33 | 1447.29 | 18.88 | 4.00 | 369.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3031.11 | 19.47 | 85.50 | 380.17 | 1626.76 | 21.14 | 60.17 | 342.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3319.98 | 21.97 | 83.50 | 320.33 | 1436.41 | 22.06 | 65.83 | 288.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:30 | 1917.42 | 20.08 | 78.67 | 286.33 | 1016.68 | 22.32 | 90.00 | 251.67 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:50 | 1424.48 | 20.40 | 86.50 | 226.17 | 752.08 | 21.44 | 81.83 | 175.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1313.62 | 19.16 | 53.83 | 220.00 | 699.21 | 21.60 | 71.50 | 168.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2670.22 | 19.51 | 897.83 | 3770.33 | 1306.20 | 20.87 | 703.83 | 3302.67 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1313.62 | 17.43 | 43.00 | 220.00 | 699.21 | 18.69 | 0.00 | 168.00 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3586.21 | 21.97 | 104.50 | 404.33 | 1862.75 | 22.62 | 95.83 | 369.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.722252E+09 | 25645.77 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60851349.63 | 25645.77 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 666670.49 | 11111.17 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27837370.04 | 25645.77 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.722252E+09 | 25645.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.862035E+10 | 12076.17 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748626E+10 | 12063.95 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429036E+10 | 12123.63 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232698E+10 | 12088.64 | 04-APR-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.795438E+09 | 12069.36 | 12-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168870E+09 | 11201.57 | 06-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13207419.38 | 3757.68 | 06-JUL-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36800993.85 | 5708.42 | 01-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217551E+09 | 12313.53 | 06-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116549E+10 | 12082.26 | 26-OCT-16:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311454E+10 | 12071.68 | 20-NOV-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729999E+10 | 12067.33 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13207419.38 | 3757.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.862035E+10 | 12313.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.362720E+10 | 9905.80 | 05-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298411E+10 | 9923.01 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115911E+10 | 9883.56 | 11-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223566E+09 | 9863.04 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2500907.55 | 2679.33 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37592699.69 | 9851.30 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534971E+09 | 9857.72 | 21-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284354E+10 | 9910.97 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362720E+10 | 9923.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579327E+10 | 8268.87 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497869E+10 | 8260.07 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262924E+10 | 8283.28 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.626032E+09 | 8244.79 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10738622.73 | 8247.99 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87939099.55 | 8218.96 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.770791E+09 | 8249.90 | 21-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421737E+10 | 8259.06 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579327E+10 | 8283.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390614E+10 | 10332.22 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324561E+10 | 10354.35 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131422E+10 | 10300.24 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320382E+09 | 10282.07 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7246837.22 | 5020.36 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54700266.54 | 10279.57 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.599028E+09 | 10296.22 | 13-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292728E+10 | 10341.80 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390614E+10 | 10354.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361439E+10 | 24871.02 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281092E+10 | 24871.02 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447291E+09 | 24871.02 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48037157.74 | 24871.02 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9490357.57 | 24871.02 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201697E+09 | 24871.02 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244467E+10 | 24871.02 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.957649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.361439E+10 | 24871.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407359E+10 | 13738.04 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.346428E+10 | 13710.38 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101250E+10 | 13703.20 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260858E+09 | 13705.16 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2766130.28 | 5649.68 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 348186.52 | 615.14 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111147E+09 | 13556.62 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811317E+09 | 13721.50 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362193E+10 | 13727.25 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407359E+10 | 13738.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378688E+10 | 10760.92 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316616E+10 | 10760.92 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111781E+10 | 10760.92 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206197E+09 | 10760.92 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1140709.86 | 2035.07 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1565533.94 | 3450.18 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169694E+09 | 10760.92 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.998823E+09 | 10760.92 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345273E+10 | 10760.92 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378688E+10 | 10760.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551271E+10 | 9236.32 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471575E+10 | 9224.89 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188972E+10 | 9195.58 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320478E+09 | 9201.75 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 294509.30 | 1884.10 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 557118.55 | 734.08 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179457E+09 | 9170.23 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107695E+10 | 9209.30 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466019E+10 | 9245.22 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.551271E+10 | 9245.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396359E+10 | 10864.55 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332723E+10 | 10864.55 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126529E+10 | 10864.55 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303352E+09 | 10864.55 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4732536.57 | 4106.52 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3004538.76 | 2698.40 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201293E+09 | 10864.55 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101836E+10 | 10864.55 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345103E+10 | 10864.55 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396359E+10 | 10864.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.837203E+10 | 33862.14 | 17-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698454E+10 | 33912.37 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258011E+10 | 33833.83 | 03-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504138E+09 | 33927.88 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1757025.85 | 7056.96 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309327E+09 | 33952.59 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182667E+10 | 33887.99 | 25-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.712027E+10 | 33945.66 | 19-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.837203E+10 | 33952.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641404E+10 | 15048.62 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572096E+10 | 15025.58 | 01-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225020E+10 | 14986.38 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792364E+09 | 15006.99 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53525109.14 | 11487.32 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 809279.76 | 1546.97 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15434471.67 | 10974.25 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.550332E+09 | 15032.00 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196811E+10 | 15010.91 | 20-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.609402E+10 | 15023.03 | 18-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.641404E+10 | 15048.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.533055E+10 | 12030.57 | 14-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461244E+10 | 12060.52 | 23-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194355E+10 | 12024.81 | 10-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.505866E+09 | 12070.12 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17713883.31 | 6636.04 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16015637.09 | 7236.25 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.520615E+09 | 12012.14 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180046E+10 | 12066.18 | 21-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506495E+10 | 12082.99 | 18-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.533055E+10 | 12082.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.820670E+10 | 10474.85 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.720043E+10 | 10466.31 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345767E+10 | 10461.64 | 11-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.889793E+09 | 10452.82 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29617622.06 | 10404.01 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19662001.02 | 10389.28 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749209E+09 | 10454.96 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241448E+10 | 10476.67 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.735444E+10 | 10472.10 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.820670E+10 | 10476.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.572238E+10 | 13140.84 | 14-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498322E+10 | 13141.22 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227459E+10 | 13116.88 | 13-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.757606E+09 | 13117.84 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60271857.72 | 7185.16 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1568355.10 | 1678.28 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28969709.89 | 7098.34 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690883E+09 | 13027.47 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198943E+10 | 13170.04 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523826E+10 | 13188.93 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.572238E+10 | 13188.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157782E+11 | 24164.76 | 04-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146034E+11 | 28440.32 | 07-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743017E+10 | 23844.27 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136371E+10 | 13426.35 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19313568.35 | 4795.46 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 563321.09 | 374.97 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.531297E+09 | 10633.47 | 17-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275742E+10 | 12254.37 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132626E+11 | 28919.56 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157782E+11 | 28919.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168126E+11 | 24316.70 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155606E+11 | 28538.94 | 07-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.867030E+10 | 23781.43 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217067E+10 | 14673.33 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48668023.83 | 6092.43 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8312638.37 | 1181.39 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108211E+10 | 11993.44 | 17-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.438153E+10 | 14043.32 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145625E+11 | 28987.30 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168126E+11 | 28987.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180246E+11 | 26564.95 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166586E+11 | 31268.69 | 07-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894568E+10 | 26872.07 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240104E+10 | 16725.64 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102747E+09 | 7879.64 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2787596.81 | 1539.84 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31831247.80 | 2941.66 | 06-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139125E+10 | 14278.69 | 17-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482012E+10 | 15497.69 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157166E+11 | 27512.56 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.680952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180246E+11 | 31268.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197533E+10 | 0.161792E+10 | 30275.48 | 15-MAR-14:00 | 30275.48 | 0.00 |
April | 0.00 | 0.00 | 0.672434E+09 | 0.599278E+09 | 13563.52 | 07-APR-13:00 | 13563.52 | 0.00 |
May | 0.00 | 0.00 | 0.758819E+10 | 0.682157E+10 | 38301.85 | 23-MAY-14:30 | 38301.85 | 0.00 |
June | 0.00 | 0.00 | 0.375193E+11 | 0.283090E+11 | 100775.23 | 27-JUN-07:40 | 43555.76 | 0.00 |
July | 0.00 | 0.00 | 0.662434E+11 | 0.469698E+11 | 124283.10 | 20-JUL-04:03 | 49863.53 | 0.00 |
August | 0.00 | 0.00 | 0.565934E+11 | 0.438517E+11 | 124256.29 | 14-AUG-08:00 | 52633.50 | 0.00 |
September | 0.00 | 0.00 | 0.252157E+11 | 0.189121E+11 | 81902.67 | 15-SEP-14:50 | 44394.46 | 0.00 |
October | 0.00 | 0.00 | 0.267823E+10 | 0.225572E+10 | 31647.97 | 11-OCT-15:10 | 31647.97 | 0.00 |
November | 0.00 | 0.00 | 0.442975E+09 | 0.314186E+09 | 11079.55 | 16-NOV-18:00 | 8334.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198929E+12 | 0.149651E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662434E+11 | 0.469698E+11 | 124283.10 | 52633.50 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188361E+10 | 0.155012E+10 | 32153.81 | 15-MAR-13:50 | 32153.81 | 0.00 |
April | 0.00 | 0.00 | 0.670564E+09 | 0.604842E+09 | 13641.11 | 08-APR-13:30 | 11883.54 | 0.00 |
May | 0.00 | 0.00 | 0.757838E+10 | 0.683235E+10 | 38476.16 | 23-MAY-14:30 | 38476.16 | 0.00 |
June | 0.00 | 0.00 | 0.351491E+11 | 0.267309E+11 | 86142.98 | 27-JUN-07:40 | 37275.01 | 0.00 |
July | 0.00 | 0.00 | 0.606610E+11 | 0.429910E+11 | 114498.32 | 20-JUL-06:03 | 46414.06 | 0.00 |
August | 0.00 | 0.00 | 0.495615E+11 | 0.385107E+11 | 113103.93 | 14-AUG-06:03 | 42935.05 | 0.00 |
September | 0.00 | 0.00 | 0.212570E+11 | 0.159274E+11 | 73522.92 | 15-SEP-11:00 | 40888.27 | 0.00 |
October | 0.00 | 0.00 | 0.230472E+10 | 0.190753E+10 | 26275.79 | 11-OCT-15:00 | 26275.79 | 0.00 |
November | 0.00 | 0.00 | 0.394488E+09 | 0.273606E+09 | 9258.36 | 16-NOV-18:00 | 6657.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179460E+12 | 0.135328E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.606610E+11 | 0.429910E+11 | 114498.32 | 46414.06 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.206944E+10 | 0.171990E+10 | 39210.20 | 15-MAR-14:00 | 39210.20 | 0.00 |
April | 0.00 | 0.00 | 0.692355E+09 | 0.612057E+09 | 14440.59 | 08-APR-13:30 | 12179.88 | 0.00 |
May | 0.00 | 0.00 | 0.789674E+10 | 0.702448E+10 | 44197.95 | 10-MAY-14:30 | 44197.95 | 0.00 |
June | 0.00 | 0.00 | 0.374543E+11 | 0.281826E+11 | 126626.42 | 27-JUN-15:00 | 55787.37 | 0.00 |
July | 0.00 | 0.00 | 0.646352E+11 | 0.457408E+11 | 126626.42 | 21-JUL-05:03 | 53056.11 | 0.00 |
August | 0.00 | 0.00 | 0.520614E+11 | 0.401571E+11 | 125277.48 | 15-AUG-14:20 | 61189.84 | 0.00 |
September | 0.00 | 0.00 | 0.215240E+11 | 0.156709E+11 | 85228.38 | 15-SEP-12:30 | 47524.45 | 0.00 |
October | 0.00 | 0.00 | 0.223683E+10 | 0.179035E+10 | 25662.07 | 11-OCT-15:00 | 25662.07 | 0.00 |
November | 0.00 | 0.00 | 0.415677E+09 | 0.283584E+09 | 10046.68 | 27-NOV-07:03 | 8513.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188986E+12 | 0.141182E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.646352E+11 | 0.457408E+11 | 126626.42 | 61189.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1975.02 | 6956.36 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2012.51 | 6976.67 | 13-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2117.56 | 6946.25 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1904.33 | 6716.02 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1870.74 | 6423.99 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1808.02 | 6009.99 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1584.68 | 5666.44 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1711.58 | 5523.98 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1625.65 | 5696.70 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1698.92 | 6009.25 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1826.45 | 6392.77 | 29-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1849.75 | 6733.96 | 29-DEC-12:12 |
Annual Sum or Average | 0.00 | 1831.07 | ||||
Minimum of Months | 0.00 | 0.00 | 1584.68 | 5523.98 | ||
Maximum of Months | 0.00 | 0.00 | 2117.56 | 6976.67 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154453E+10 | 0.32 | 2804.52 | 02-JAN-05:01 | 0.81 |
February | 0.137569E+10 | 0.32 | 2804.52 | 06-FEB-07:01 | 0.82 |
March | 0.163384E+10 | 0.32 | 2138.45 | 15-MAR-13:50 | 0.70 |
April | 0.168382E+10 | 0.31 | 2445.46 | 24-APR-16:00 | 0.75 |
May | 0.248178E+10 | 0.35 | 4195.56 | 31-MAY-16:00 | 1.01 |
June | 0.426962E+10 | 0.48 | 8679.50 | 12-JUN-12:10 | 1.57 |
July | 0.549619E+10 | 0.52 | 11841.91 | 17-JUL-06:03 | 1.91 |
August | 0.565993E+10 | 0.54 | 11841.91 | 14-AUG-06:03 | 1.91 |
September | 0.370343E+10 | 0.43 | 8158.65 | 18-SEP-12:10 | 1.52 |
October | 0.201896E+10 | 0.32 | 4448.43 | 11-OCT-15:50 | 1.05 |
November | 0.150005E+10 | 0.29 | 2034.13 | 01-NOV-12:20 | 0.69 |
December | 0.141606E+10 | 0.30 | 2804.52 | 11-DEC-07:01 | 0.82 |
Annual Sum or Average | 0.327839E+11 | 0.38 | |||
Minimum of Months | 0.137569E+10 | 0.29 | 2034.13 | 0.69 | |
Maximum of Months | 0.565993E+10 | 0.54 | 11841.91 | 1.91 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163531E+10 | 0.35 | 2829.66 | 02-JAN-05:01 | 0.87 |
February | 0.146075E+10 | 0.34 | 2829.66 | 02-FEB-07:01 | 0.87 |
March | 0.157814E+10 | 0.33 | 2829.66 | 01-MAR-07:01 | 0.87 |
April | 0.150594E+10 | 0.31 | 2829.66 | 17-APR-06:01 | 0.87 |
May | 0.227648E+10 | 0.36 | 4802.71 | 23-MAY-14:30 | 1.18 |
June | 0.404233E+10 | 0.49 | 8252.07 | 12-JUN-15:20 | 1.64 |
July | 0.503542E+10 | 0.53 | 10659.36 | 17-JUL-06:03 | 1.92 |
August | 0.482167E+10 | 0.53 | 10659.36 | 15-AUG-14:30 | 1.92 |
September | 0.289438E+10 | 0.41 | 7104.61 | 21-SEP-15:30 | 1.49 |
October | 0.157598E+10 | 0.30 | 3323.64 | 11-OCT-15:10 | 0.95 |
November | 0.132495E+10 | 0.29 | 2829.66 | 24-NOV-06:01 | 0.87 |
December | 0.153471E+10 | 0.33 | 2829.66 | 04-DEC-06:01 | 0.87 |
Annual Sum or Average | 0.296860E+11 | 0.38 | |||
Minimum of Months | 0.132495E+10 | 0.29 | 2829.66 | 0.87 | |
Maximum of Months | 0.503542E+10 | 0.53 | 10659.36 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202522E+10 | 0.40 | 2724.13 | 02-JAN-05:01 | 0.79 |
February | 0.185123E+10 | 0.40 | 2724.13 | 01-FEB-06:11 | 0.79 |
March | 0.173766E+10 | 0.34 | 3007.67 | 15-MAR-13:50 | 0.83 |
April | 0.152024E+10 | 0.30 | 2724.13 | 03-APR-05:01 | 0.79 |
May | 0.213690E+10 | 0.34 | 4667.54 | 31-MAY-16:00 | 1.07 |
June | 0.375294E+10 | 0.45 | 12076.28 | 27-JUN-14:55 | 1.90 |
July | 0.468987E+10 | 0.48 | 12076.28 | 21-JUL-05:03 | 1.90 |
August | 0.436743E+10 | 0.47 | 12076.28 | 15-AUG-14:20 | 1.91 |
September | 0.251559E+10 | 0.36 | 6735.86 | 21-SEP-15:20 | 1.33 |
October | 0.152807E+10 | 0.29 | 2789.44 | 11-OCT-15:20 | 0.80 |
November | 0.139189E+10 | 0.29 | 2724.13 | 13-NOV-06:11 | 0.79 |
December | 0.190190E+10 | 0.38 | 2724.13 | 02-DEC-06:11 | 0.79 |
Annual Sum or Average | 0.294189E+11 | 0.38 | |||
Minimum of Months | 0.139189E+10 | 0.29 | 2724.13 | 0.79 | |
Maximum of Months | 0.468987E+10 | 0.48 | 12076.28 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.13 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 55.24 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.00 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 56.37 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.82 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.24 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 55.89 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.35 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 55.92 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.07 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 55.79 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.61 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.24 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.13 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.72 | 56.72 | 1975.02 | 6956.36 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.16 | 56.16 | 2012.51 | 6976.67 | 13-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.50 | 56.50 | 2117.56 | 6946.25 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.86 | 56.86 | 1904.33 | 6716.02 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.49 | 57.49 | 1870.74 | 6423.99 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.71 | 56.71 | 1808.02 | 6009.99 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.32 | 56.32 | 1584.68 | 5666.44 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.59 | 57.59 | 1711.58 | 5523.98 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.59 | 56.59 | 1625.65 | 5696.70 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.50 | 56.50 | 1698.92 | 6009.25 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.32 | 56.32 | 1826.45 | 6392.77 | 29-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.33 | 56.33 | 1849.75 | 6733.96 | 29-DEC-12:12 |
Annual Sum or Average | 0.00 | 1831.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.16 | 56.16 | 1584.68 | 5523.98 | ||
Maximum of Months | 0.00 | 0.00 | 57.59 | 57.59 | 2117.56 | 6976.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.242137E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201312E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115337E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.536765E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.527055E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136130E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.214975E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.194181E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.100539E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.407718E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.664282E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187321E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160551E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.407718E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.242137E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.225865E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.189451E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.779036E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.283100E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.424847E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126389E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.196789E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168812E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.811597E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.286648E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.554234E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.191653E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141290E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.283100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.225865E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.360709E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.313528E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147697E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.516285E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.435335E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129452E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.203472E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170966E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.792112E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.495539E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115075E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.327738E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.199257E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.435335E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.360709E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154453E+10 | 0.00 | 0.384474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137569E+10 | 0.00 | 0.333589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163384E+10 | 0.197533E+10 | 0.168238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168382E+10 | 0.672434E+09 | 0.486067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248178E+10 | 0.758819E+10 | 0.835238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.426962E+10 | 0.375193E+11 | 0.168870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.549619E+10 | 0.662434E+11 | 13207419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.565993E+10 | 0.565934E+11 | 36800993.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.370343E+10 | 0.252157E+11 | 0.218114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201896E+10 | 0.267823E+10 | 0.187702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150005E+10 | 0.442975E+09 | 0.777675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141606E+10 | 0.00 | 0.305787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327839E+11 | 0.198929E+12 | 0.134995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137569E+10 | 0.00 | 13207419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.565993E+10 | 0.662434E+11 | 0.384474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163531E+10 | 0.00 | 0.377637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146075E+10 | 0.00 | 0.330450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157814E+10 | 0.188361E+10 | 0.144029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150594E+10 | 0.670564E+09 | 0.330960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227648E+10 | 0.757838E+10 | 57601909.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404233E+10 | 0.351491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503542E+10 | 0.606610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.482167E+10 | 0.495615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289438E+10 | 0.212570E+11 | 13788016.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157598E+10 | 0.230472E+10 | 0.175319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132495E+10 | 0.394488E+09 | 0.848867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153471E+10 | 0.00 | 0.321930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296860E+11 | 0.179460E+12 | 0.131027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.503542E+10 | 0.606610E+11 | 0.377637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.202522E+10 | 0.00 | 0.520703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185123E+10 | 0.00 | 0.461602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173766E+10 | 0.206944E+10 | 0.214518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152024E+10 | 0.692355E+09 | 0.585081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213690E+10 | 0.789674E+10 | 0.265633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375294E+10 | 0.374543E+11 | 5165231.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.468987E+10 | 0.646352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.436743E+10 | 0.520614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251559E+10 | 0.215240E+11 | 0.111913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152807E+10 | 0.223683E+10 | 0.421161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139189E+10 | 0.415677E+09 | 0.148193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190190E+10 | 0.00 | 0.465885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294189E+11 | 0.188986E+12 | 0.191535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468987E+10 | 0.646352E+11 | 0.520703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163384E+10 | 0.00 | 0.00 | 0.00 | 0.506315E+09 | 0.939360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168382E+10 | 0.00 | 0.00 | 0.00 | 0.186866E+09 | 0.349696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248178E+10 | 0.00 | 0.00 | 0.00 | 0.197285E+10 | 0.815924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.426962E+10 | 0.00 | 0.00 | 0.00 | 0.917452E+10 | 0.168870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.549619E+10 | 0.00 | 0.00 | 0.00 | 0.159881E+11 | 13207419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.565993E+10 | 0.00 | 0.00 | 0.00 | 0.137213E+11 | 36800993.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.370343E+10 | 0.00 | 0.00 | 0.00 | 0.613292E+10 | 0.217551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201896E+10 | 0.00 | 0.00 | 0.00 | 0.712499E+09 | 0.134573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150005E+10 | 0.00 | 0.00 | 0.00 | 0.123445E+09 | 0.501933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327839E+11 | 0.00 | 0.00 | 0.00 | 0.485189E+11 | 0.792487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13207419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.565993E+10 | 0.00 | 0.00 | 0.00 | 0.159881E+11 | 0.226692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157814E+10 | 0.00 | 0.00 | 0.00 | 0.479607E+09 | 0.573261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150594E+10 | 0.00 | 0.00 | 0.00 | 0.186141E+09 | 0.113892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227648E+10 | 0.00 | 0.00 | 0.00 | 0.196305E+10 | 8933886.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404233E+10 | 0.00 | 0.00 | 0.00 | 0.859660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503542E+10 | 0.00 | 0.00 | 0.00 | 0.146435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.482167E+10 | 0.00 | 0.00 | 0.00 | 0.120596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289438E+10 | 0.00 | 0.00 | 0.00 | 0.521611E+10 | 5475377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157598E+10 | 0.00 | 0.00 | 0.00 | 0.619425E+09 | 0.671081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132495E+10 | 0.00 | 0.00 | 0.00 | 0.110248E+09 | 0.410714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296860E+11 | 0.00 | 0.00 | 0.00 | 0.438742E+11 | 0.677302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.503542E+10 | 0.00 | 0.00 | 0.00 | 0.146435E+11 | 0.209512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.202522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173766E+10 | 0.00 | 0.00 | 0.00 | 0.525878E+09 | 0.125061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152024E+10 | 0.00 | 0.00 | 0.00 | 0.192841E+09 | 0.344977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213690E+10 | 0.00 | 0.00 | 0.00 | 0.205357E+10 | 0.162885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375294E+10 | 0.00 | 0.00 | 0.00 | 0.918992E+10 | 2377634.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.468987E+10 | 0.00 | 0.00 | 0.00 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.436743E+10 | 0.00 | 0.00 | 0.00 | 0.127292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251559E+10 | 0.00 | 0.00 | 0.00 | 0.532544E+10 | 80081819.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152807E+10 | 0.00 | 0.00 | 0.00 | 0.606956E+09 | 0.282037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139189E+10 | 0.00 | 0.00 | 0.00 | 0.116489E+09 | 0.999915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294189E+11 | 0.00 | 0.00 | 0.00 | 0.463977E+11 | 0.123440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468987E+10 | 0.00 | 0.00 | 0.00 | 0.156574E+11 | 0.340457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139848E+11 | 0.00 | 0.00 | 1664919.08 | 0.00 | 0.414474E+09 | 0.280411E+10 | 0.00 | 0.28 |
February | 0.128994E+11 | 0.00 | 0.00 | 1910145.69 | 0.00 | 17772520.18 | 0.313146E+10 | 0.00 | 0.28 |
March | 0.706336E+10 | 9435884.65 | 0.00 | 16778021.69 | 0.00 | 734621.89 | 0.100221E+11 | 0.00 | 0.39 |
April | 0.276552E+10 | 0.00 | 0.00 | 24441763.98 | 0.00 | 0.00 | 0.140741E+11 | 0.00 | 0.50 |
May | 0.101821E+10 | 2659416.96 | 0.00 | 39448593.07 | 5263744.09 | 0.00 | 0.192231E+11 | 0.00 | 0.91 |
June | 0.414791E+09 | 0.174229E+10 | 0.00 | 34477911.14 | 0.185271E+09 | 0.00 | 0.123441E+11 | 0.00 | 1.12 |
July | 0.181719E+09 | 0.596013E+10 | 0.00 | 18261864.37 | 0.439557E+09 | 0.00 | 0.371369E+10 | 0.00 | 0.88 |
August | 0.300385E+09 | 0.334798E+10 | 0.00 | 34207963.87 | 0.143663E+09 | 0.00 | 0.811438E+10 | 0.00 | 1.06 |
September | 0.986154E+09 | 0.120051E+10 | 0.00 | 36239546.70 | 19215849.14 | 0.00 | 0.146261E+11 | 0.00 | 1.11 |
October | 0.125764E+10 | 0.00 | 0.00 | 33388960.61 | 664106.00 | 0.00 | 0.176244E+11 | 0.00 | 0.64 |
November | 0.400171E+10 | 0.00 | 0.00 | 19215871.64 | 3755310.39 | 0.00 | 0.111540E+11 | 0.00 | 0.39 |
December | 0.112270E+11 | 0.00 | 0.00 | 5313174.81 | 0.00 | 8764324.93 | 0.528600E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.561007E+11 | 0.122630E+11 | 0.00 | 0.265349E+09 | 0.797391E+09 | 0.441746E+09 | 0.122118E+12 | 0.00 | 0.65 |
Minimum of Months | 0.181719E+09 | 0.00 | 0.00 | 1664919.08 | 0.00 | 0.00 | 0.280411E+10 | 0.00 | 0.28 |
Maximum of Months | 0.139848E+11 | 0.596013E+10 | 0.00 | 39448593.07 | 0.439557E+09 | 0.414474E+09 | 0.192231E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262610E+10 | 0.00 | 0.00 | 0.27 |
February | 0.130839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218332E+10 | 0.00 | 0.00 | 0.28 |
March | 0.132387E+11 | 1912372.40 | 0.00 | 1847523.82 | 6028704.68 | 0.209449E+09 | 0.100809E+10 | 0.00 | 0.33 |
April | 0.833370E+10 | 0.00 | 0.00 | 4319009.46 | 0.00 | 42458245.01 | 0.372635E+10 | 0.00 | 0.36 |
May | 0.379721E+10 | 0.00 | 0.00 | 17598016.40 | 18780384.23 | 0.00 | 0.980819E+10 | 0.00 | 0.61 |
June | 0.888590E+09 | 0.126996E+10 | 0.00 | 20586570.70 | 0.148902E+09 | 0.00 | 0.783005E+10 | 0.00 | 0.78 |
July | 0.408495E+09 | 0.438771E+10 | 0.00 | 11888582.68 | 0.442713E+09 | 0.00 | 0.239401E+10 | 0.00 | 0.65 |
August | 0.717050E+09 | 0.239428E+10 | 0.00 | 21243684.49 | 0.136017E+09 | 0.00 | 0.501938E+10 | 0.00 | 0.74 |
September | 0.222648E+10 | 0.773098E+09 | 0.00 | 17882068.43 | 23342209.63 | 0.00 | 0.774282E+10 | 0.00 | 0.72 |
October | 0.693987E+10 | 0.00 | 0.00 | 6762840.83 | 2484753.08 | 910230.13 | 0.485969E+10 | 0.00 | 0.40 |
November | 0.107165E+11 | 0.00 | 154863.46 | 387898.75 | 6831885.82 | 51938075.46 | 0.640661E+09 | 1992.01 | 0.30 |
December | 0.138798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158538E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.881390E+11 | 0.882696E+10 | 154863.46 | 0.102516E+09 | 0.785100E+09 | 0.669956E+10 | 0.430292E+11 | 1992.01 | 0.48 |
Minimum of Months | 0.408495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.139087E+11 | 0.438771E+10 | 154863.46 | 21243684.49 | 0.442713E+09 | 0.262610E+10 | 0.980819E+10 | 1992.01 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.839249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687146E+10 | 0.00 | 0.00 | 0.26 |
February | 0.867177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553420E+10 | 0.00 | 0.00 | 0.26 |
March | 0.114117E+11 | 595808.81 | 0.00 | 1450934.67 | 543120.69 | 0.144527E+10 | 0.773599E+09 | 0.00 | 0.33 |
April | 0.940204E+10 | 0.00 | 0.00 | 1963778.44 | 0.00 | 0.192339E+09 | 0.219032E+10 | 0.00 | 0.36 |
May | 0.479507E+10 | 228587.53 | 0.00 | 14262345.68 | 23715058.76 | 1484274.70 | 0.857473E+10 | 0.00 | 0.60 |
June | 0.152308E+10 | 0.131943E+10 | 0.00 | 18779814.20 | 0.244667E+09 | 0.00 | 0.726083E+10 | 0.00 | 0.82 |
July | 0.556312E+09 | 0.450783E+10 | 0.00 | 10862288.00 | 0.455740E+09 | 0.00 | 0.218339E+10 | 0.00 | 0.70 |
August | 0.108253E+10 | 0.244358E+10 | 0.00 | 18050628.99 | 0.220154E+09 | 0.00 | 0.424232E+10 | 0.00 | 0.76 |
September | 0.328178E+10 | 0.778973E+09 | 0.00 | 12676718.94 | 62798385.74 | 0.00 | 0.573840E+10 | 0.00 | 0.70 |
October | 0.821603E+10 | 0.00 | 0.00 | 2869883.83 | 134153.15 | 0.126469E+09 | 0.253329E+10 | 0.00 | 0.39 |
November | 0.996102E+10 | 0.00 | 556578.29 | 7369.18 | 11029870.91 | 0.595209E+09 | 76204210.79 | 40703.82 | 0.30 |
December | 0.871531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548748E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.760092E+11 | 0.905063E+10 | 556578.29 | 80923761.94 | 0.101878E+10 | 0.202539E+11 | 0.335731E+11 | 40703.82 | 0.48 |
Minimum of Months | 0.556312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.114117E+11 | 0.450783E+10 | 556578.29 | 18779814.20 | 0.455740E+09 | 0.687146E+10 | 0.857473E+10 | 40703.82 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47201285.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363834E+10 | 0.00 | 0.00 | 0.29 |
February | 89486863.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335515E+10 | 0.00 | 0.00 | 0.30 |
March | 0.102400E+10 | 204108.14 | 0.00 | 254471.54 | 35609.66 | 0.189049E+10 | 81045666.05 | 0.00 | 0.34 |
April | 0.179371E+10 | 0.00 | 0.00 | 221176.18 | 0.00 | 0.473554E+09 | 0.218261E+09 | 0.00 | 0.36 |
May | 0.138690E+10 | 0.00 | 0.00 | 2700777.84 | 5039572.97 | 14348172.78 | 0.143165E+10 | 0.00 | 0.63 |
June | 0.386709E+09 | 0.427854E+09 | 0.00 | 4746621.63 | 50061970.66 | 0.00 | 0.164035E+10 | 0.00 | 1.00 |
July | 0.130321E+09 | 0.139379E+10 | 0.00 | 2910108.34 | 88275196.98 | 0.00 | 0.547203E+09 | 0.00 | 0.91 |
August | 0.321288E+09 | 0.715531E+09 | 0.00 | 4395609.56 | 40271574.76 | 0.00 | 0.917817E+09 | 0.00 | 0.92 |
September | 0.953515E+09 | 0.194381E+09 | 0.00 | 2304287.40 | 19068993.15 | 8159615.67 | 0.920867E+09 | 0.00 | 0.73 |
October | 0.173084E+10 | 0.00 | 0.00 | 256039.51 | 28236.08 | 0.351369E+09 | 0.195223E+09 | 0.00 | 0.38 |
November | 0.861502E+09 | 0.00 | 470243.33 | 0.00 | 2002343.92 | 0.140531E+10 | 0.00 | 13146.25 | 0.30 |
December | 0.142613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323117E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.886809E+10 | 0.273176E+10 | 470243.33 | 17789091.99 | 0.204783E+09 | 0.143679E+11 | 0.595242E+10 | 13146.25 | 0.54 |
Minimum of Months | 47201285.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.179371E+10 | 0.139379E+10 | 470243.33 | 4746621.63 | 88275196.98 | 0.363834E+10 | 0.164035E+10 | 13146.25 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70603275.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318057E+10 | 0.00 | 0.00 | 0.41 |
February | 0.501704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253568E+10 | 0.00 | 0.00 | 0.42 |
March | 0.157933E+10 | 289921.97 | 0.00 | 288585.12 | 0.00 | 0.115772E+10 | 0.111303E+09 | 0.00 | 0.52 |
April | 0.152505E+10 | 0.00 | 0.00 | 1409833.02 | 0.00 | 0.255101E+09 | 0.895300E+09 | 0.00 | 0.61 |
May | 0.109002E+10 | 0.00 | 0.00 | 4159892.38 | 5002264.42 | 4716274.13 | 0.228276E+10 | 0.00 | 1.15 |
June | 0.352685E+09 | 0.395000E+09 | 0.00 | 5427662.42 | 34882103.30 | 0.00 | 0.214206E+10 | 0.00 | 1.63 |
July | 94193811.42 | 0.117647E+10 | 0.00 | 4417441.21 | 94537738.65 | 0.00 | 0.850777E+09 | 0.00 | 1.51 |
August | 0.271612E+09 | 0.570528E+09 | 0.00 | 5113898.72 | 48132421.75 | 0.00 | 0.112515E+10 | 0.00 | 1.50 |
September | 0.809686E+09 | 0.167426E+09 | 0.00 | 3293687.62 | 26762628.90 | 3867361.21 | 0.141862E+10 | 0.00 | 1.27 |
October | 0.166600E+10 | 0.00 | 0.00 | 501182.39 | 28027.04 | 0.249303E+09 | 0.357037E+09 | 0.00 | 0.61 |
November | 0.103471E+10 | 0.00 | 426642.35 | 0.00 | 1987520.33 | 0.119227E+10 | 0.00 | 9370.12 | 0.47 |
December | 0.170801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285042E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.916639E+10 | 0.230971E+10 | 426642.35 | 24612182.88 | 0.211333E+09 | 0.114296E+11 | 0.918301E+10 | 9370.12 | 0.88 |
Minimum of Months | 70603275.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.166600E+10 | 0.117647E+10 | 426642.35 | 5427662.42 | 94537738.65 | 0.318057E+10 | 0.228276E+10 | 9370.12 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.888405E+09 | 0.00 | 0.00 | 202501.70 | 0.00 | 0.312206E+10 | 0.154366E+09 | 0.00 | 0.33 |
February | 0.997527E+09 | 0.00 | 0.00 | 408398.40 | 0.00 | 0.269203E+10 | 0.290968E+09 | 0.00 | 0.35 |
March | 0.172085E+10 | 1133265.89 | 0.00 | 2072594.06 | 0.00 | 0.115332E+10 | 0.107066E+10 | 0.00 | 0.47 |
April | 0.169729E+10 | 0.00 | 0.00 | 3123561.65 | 0.00 | 0.408468E+09 | 0.181712E+10 | 0.00 | 0.59 |
May | 0.144793E+10 | 4305143.73 | 0.00 | 5661140.56 | 2180792.40 | 28420054.89 | 0.289220E+10 | 0.00 | 0.97 |
June | 0.576184E+09 | 0.497669E+09 | 0.00 | 6046982.53 | 49106804.62 | 503818.95 | 0.215479E+10 | 0.00 | 1.26 |
July | 0.200424E+09 | 0.167095E+10 | 0.00 | 3847700.45 | 0.109733E+09 | 0.00 | 0.680472E+09 | 0.00 | 1.12 |
August | 0.409421E+09 | 0.902487E+09 | 0.00 | 6795889.37 | 37866426.41 | 0.00 | 0.134831E+10 | 0.00 | 1.29 |
September | 0.869465E+09 | 0.298467E+09 | 0.00 | 7163369.39 | 21167509.78 | 6226509.53 | 0.269663E+10 | 0.00 | 1.36 |
October | 0.166700E+10 | 0.00 | 0.00 | 3780444.98 | 34846.55 | 0.234593E+09 | 0.192793E+10 | 0.00 | 0.71 |
November | 0.135457E+10 | 0.00 | 555360.88 | 1081700.99 | 2471121.72 | 0.110417E+10 | 0.529767E+09 | 10438.87 | 0.40 |
December | 0.710558E+09 | 0.00 | 0.00 | 108290.26 | 0.00 | 0.303691E+10 | 87688763.98 | 0.00 | 0.33 |
Annual Sum or Average | 0.125396E+11 | 0.337501E+10 | 555360.88 | 40292574.34 | 0.222561E+09 | 0.117867E+11 | 0.156509E+11 | 10438.87 | 0.77 |
Minimum of Months | 0.200424E+09 | 0.00 | 0.00 | 108290.26 | 0.00 | 0.00 | 87688763.98 | 0.00 | 0.33 |
Maximum of Months | 0.172085E+10 | 0.167095E+10 | 555360.88 | 7163369.39 | 0.109733E+09 | 0.312206E+10 | 0.289220E+10 | 10438.87 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330511E+10 | 0.00 | 0.00 | 0.45 |
February | 0.400980E+09 | 0.00 | 0.00 | 7761.23 | 0.00 | 0.289430E+10 | 14529979.93 | 0.00 | 0.46 |
March | 0.147126E+10 | 23958.44 | 0.00 | 373318.18 | 235945.95 | 0.146548E+10 | 0.194976E+09 | 0.00 | 0.56 |
April | 0.167867E+10 | 0.00 | 0.00 | 1489983.15 | 0.00 | 0.436164E+09 | 0.908650E+09 | 0.00 | 0.70 |
May | 0.147932E+10 | 1176159.17 | 0.00 | 3936910.02 | 4366771.05 | 19086528.82 | 0.208241E+10 | 0.00 | 1.24 |
June | 0.544791E+09 | 0.392815E+09 | 0.00 | 5616201.68 | 50962140.88 | 442621.35 | 0.178169E+10 | 0.00 | 1.69 |
July | 0.185042E+09 | 0.120328E+10 | 0.00 | 3057592.75 | 99814752.43 | 0.00 | 0.459459E+09 | 0.00 | 1.35 |
August | 0.422549E+09 | 0.607775E+09 | 0.00 | 4353638.83 | 44007756.45 | 0.00 | 0.774032E+09 | 0.00 | 1.41 |
September | 0.105385E+10 | 0.147004E+09 | 0.00 | 2953313.40 | 38935648.61 | 9915406.16 | 0.110965E+10 | 0.00 | 1.27 |
October | 0.184567E+10 | 0.00 | 0.00 | 658377.91 | 30613.83 | 0.331906E+09 | 0.364559E+09 | 0.00 | 0.69 |
November | 0.104310E+10 | 0.00 | 459559.05 | 15453.66 | 2170960.88 | 0.135894E+10 | 28555390.55 | 9545.35 | 0.51 |
December | 0.241807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304513E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.105967E+11 | 0.235207E+10 | 459559.05 | 22462550.81 | 0.240525E+09 | 0.128665E+11 | 0.771851E+10 | 9545.35 | 0.90 |
Minimum of Months | 0.185042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.184567E+10 | 0.120328E+10 | 459559.05 | 5616201.68 | 99814752.43 | 0.330511E+10 | 0.208241E+10 | 9545.35 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 81598207.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381980E+10 | 0.00 | 0.00 | 0.29 |
February | 0.100585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356164E+10 | 0.00 | 0.00 | 0.30 |
March | 0.114643E+10 | 0.00 | 0.00 | 14064.91 | 1367915.89 | 0.205548E+10 | 9127068.41 | 0.00 | 0.33 |
April | 0.209546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460449E+09 | 0.00 | 0.00 | 0.35 |
May | 0.198878E+10 | 0.00 | 0.00 | 668776.10 | 1645288.99 | 3490340.97 | 0.445169E+09 | 0.00 | 0.51 |
June | 0.440903E+09 | 0.290482E+09 | 0.00 | 3116339.23 | 49345852.84 | 0.00 | 0.112186E+10 | 0.00 | 0.73 |
July | 0.114125E+09 | 0.105202E+10 | 0.00 | 2245695.28 | 0.108253E+09 | 0.00 | 0.437216E+09 | 0.00 | 0.68 |
August | 0.300595E+09 | 0.598888E+09 | 0.00 | 3910171.10 | 35800226.04 | 0.00 | 0.841372E+09 | 0.00 | 0.77 |
September | 0.923673E+09 | 0.180724E+09 | 0.00 | 2362045.70 | 7944939.06 | 0.00 | 0.101164E+10 | 0.00 | 0.69 |
October | 0.219886E+10 | 0.00 | 0.00 | 340146.98 | 140057.42 | 48015469.42 | 0.268952E+09 | 0.00 | 0.39 |
November | 0.193167E+10 | 0.00 | 5900.15 | 0.00 | 783128.90 | 0.592275E+09 | 0.00 | 4625.50 | 0.30 |
December | 0.395827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319398E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.117185E+11 | 0.212211E+10 | 5900.15 | 12657239.29 | 0.205281E+09 | 0.137351E+11 | 0.413533E+10 | 4625.50 | 0.47 |
Minimum of Months | 81598207.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.219886E+10 | 0.105202E+10 | 5900.15 | 3910171.10 | 0.108253E+09 | 0.381980E+10 | 0.112186E+10 | 4625.50 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289958E+10 | 0.00 | 0.00 | 0.36 |
February | 0.431862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242101E+10 | 0.00 | 0.00 | 0.37 |
March | 0.155833E+10 | 308129.21 | 0.00 | 67452.49 | 813561.43 | 0.100748E+10 | 18625055.24 | 0.00 | 0.42 |
April | 0.151130E+10 | 0.00 | 0.00 | 794367.32 | 0.00 | 0.145895E+09 | 0.551944E+09 | 0.00 | 0.48 |
May | 0.101887E+10 | 119673.06 | 0.00 | 2707933.55 | 1229463.45 | 400698.63 | 0.148277E+10 | 0.00 | 0.85 |
June | 0.249756E+09 | 0.297377E+09 | 0.00 | 4479542.51 | 29280258.20 | 0.00 | 0.170897E+10 | 0.00 | 1.28 |
July | 63823664.74 | 0.972558E+09 | 0.00 | 3622005.73 | 85504018.22 | 0.00 | 0.729652E+09 | 0.00 | 1.19 |
August | 0.193045E+09 | 0.510354E+09 | 0.00 | 5004124.74 | 25799462.73 | 0.00 | 0.110164E+10 | 0.00 | 1.28 |
September | 0.567118E+09 | 0.162921E+09 | 0.00 | 3792541.28 | 4686144.86 | 0.00 | 0.160141E+10 | 0.00 | 1.18 |
October | 0.154679E+10 | 0.00 | 0.00 | 943828.36 | 114847.05 | 20575509.37 | 0.587159E+09 | 0.00 | 0.54 |
November | 0.164066E+10 | 0.00 | 4902.38 | 14570.88 | 642165.47 | 0.406656E+09 | 22734284.99 | 2356.05 | 0.39 |
December | 0.341603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251814E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.926657E+10 | 0.194364E+10 | 4902.38 | 21426366.87 | 0.148070E+09 | 0.941974E+10 | 0.780491E+10 | 2356.05 | 0.73 |
Minimum of Months | 63823664.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.164066E+10 | 0.972558E+09 | 4902.38 | 5004124.74 | 85504018.22 | 0.289958E+10 | 0.170897E+10 | 2356.05 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499117E+10 | 0.00 | 0.00 | 0.39 |
February | 0.300067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454080E+10 | 0.00 | 0.00 | 0.39 |
March | 0.143273E+10 | 3119263.26 | 0.00 | 225558.78 | 0.00 | 0.244521E+10 | 28886707.20 | 0.00 | 0.40 |
April | 0.162549E+10 | 0.00 | 0.00 | 539114.02 | 0.00 | 0.108000E+10 | 0.359125E+09 | 0.00 | 0.42 |
May | 0.170449E+10 | 148255.43 | 0.00 | 1568598.02 | 1502179.22 | 0.336877E+09 | 0.719259E+09 | 0.00 | 0.60 |
June | 0.713524E+09 | 0.352939E+09 | 0.00 | 2919887.42 | 55672900.80 | 85232371.61 | 0.878743E+09 | 0.00 | 0.82 |
July | 0.182717E+09 | 0.133853E+10 | 0.00 | 2501962.40 | 0.107489E+09 | 10262760.60 | 0.400062E+09 | 0.00 | 0.80 |
August | 0.409141E+09 | 0.824500E+09 | 0.00 | 5405956.22 | 28765612.15 | 23218755.99 | 0.901607E+09 | 0.00 | 1.02 |
September | 0.671217E+09 | 0.270807E+09 | 0.00 | 6014401.64 | 8522785.34 | 0.118136E+09 | 0.210477E+10 | 0.00 | 1.13 |
October | 0.160743E+10 | 142810.33 | 0.00 | 2166894.13 | 21691.86 | 0.516474E+09 | 0.119133E+10 | 0.00 | 0.58 |
November | 0.128757E+10 | 0.00 | 3185.31 | 277131.56 | 789478.51 | 0.160704E+10 | 0.208862E+09 | 813.30 | 0.36 |
December | 0.260903E+09 | 0.00 | 0.00 | 20872.81 | 0.00 | 0.439342E+10 | 20404932.29 | 0.00 | 0.37 |
Annual Sum or Average | 0.104856E+11 | 0.279019E+10 | 3185.31 | 21640376.99 | 0.202764E+09 | 0.201479E+11 | 0.681305E+10 | 813.30 | 0.61 |
Minimum of Months | 0.182717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10262760.60 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.170449E+10 | 0.133853E+10 | 3185.31 | 6014401.64 | 0.107489E+09 | 0.499117E+10 | 0.210477E+10 | 813.30 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293847E+10 | 0.00 | 0.00 | 0.38 |
February | 0.338021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264221E+10 | 0.00 | 0.00 | 0.39 |
March | 0.149461E+10 | 0.00 | 0.00 | 50136.93 | 1170450.81 | 0.117500E+10 | 31159827.89 | 0.00 | 0.44 |
April | 0.167309E+10 | 0.00 | 0.00 | 683314.27 | 0.00 | 0.224152E+09 | 0.396898E+09 | 0.00 | 0.51 |
May | 0.129418E+10 | 254297.83 | 0.00 | 2260662.96 | 1282908.53 | 2618974.96 | 0.118102E+10 | 0.00 | 0.86 |
June | 0.325565E+09 | 0.311657E+09 | 0.00 | 4283468.41 | 33230208.69 | 0.00 | 0.142511E+10 | 0.00 | 1.29 |
July | 0.104928E+09 | 0.991669E+09 | 0.00 | 2627476.54 | 71057365.46 | 0.00 | 0.409092E+09 | 0.00 | 1.03 |
August | 0.239440E+09 | 0.565908E+09 | 0.00 | 4127845.16 | 18096646.28 | 0.00 | 0.790970E+09 | 0.00 | 1.17 |
September | 0.664462E+09 | 0.147696E+09 | 0.00 | 3306349.00 | 6065016.74 | 0.00 | 0.125768E+10 | 0.00 | 1.10 |
October | 0.174856E+10 | 0.00 | 0.00 | 747302.76 | 119839.48 | 29154806.91 | 0.459820E+09 | 0.00 | 0.57 |
November | 0.167609E+10 | 0.00 | 5068.39 | 15551.88 | 670080.57 | 0.460775E+09 | 22715959.22 | 2505.57 | 0.41 |
December | 0.419173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256176E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.102131E+11 | 0.201718E+10 | 5068.39 | 18102107.90 | 0.131693E+09 | 0.100341E+11 | 0.597447E+10 | 2505.57 | 0.71 |
Minimum of Months | 0.104928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.174856E+10 | 0.991669E+09 | 5068.39 | 4283468.41 | 71057365.46 | 0.293847E+10 | 0.142511E+10 | 2505.57 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354327E+10 | 0.00 | 0.00 | 0.29 |
February | 0.375052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310203E+10 | 0.00 | 0.00 | 0.29 |
March | 0.152394E+10 | 923630.91 | 0.00 | 275523.88 | 759210.61 | 0.144747E+10 | 0.107408E+09 | 0.00 | 0.33 |
April | 0.207657E+10 | 0.00 | 0.00 | 252554.99 | 0.00 | 0.225455E+09 | 0.225913E+09 | 0.00 | 0.36 |
May | 0.120499E+10 | 0.00 | 0.00 | 3120933.09 | 3966641.91 | 405215.71 | 0.160230E+10 | 0.00 | 0.62 |
June | 0.307992E+09 | 0.412451E+09 | 0.00 | 4950486.80 | 31367024.66 | 0.00 | 0.167758E+10 | 0.00 | 0.94 |
July | 0.106133E+09 | 0.135330E+10 | 0.00 | 3017313.67 | 91527420.25 | 0.00 | 0.567275E+09 | 0.00 | 0.84 |
August | 0.265653E+09 | 0.697657E+09 | 0.00 | 4678192.37 | 29075602.82 | 0.00 | 0.997771E+09 | 0.00 | 0.88 |
September | 0.840463E+09 | 0.197988E+09 | 0.00 | 2806960.53 | 6168323.07 | 0.00 | 0.113026E+10 | 0.00 | 0.74 |
October | 0.196726E+10 | 0.00 | 0.00 | 483282.71 | 524809.59 | 0.118900E+09 | 0.315784E+09 | 0.00 | 0.39 |
November | 0.161522E+10 | 0.00 | 45099.64 | 0.00 | 1442976.05 | 0.803291E+09 | 0.00 | 5849.52 | 0.30 |
December | 0.374017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307297E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.108242E+11 | 0.266232E+10 | 45099.64 | 19585248.04 | 0.164832E+09 | 0.123138E+11 | 0.662428E+10 | 5849.52 | 0.52 |
Minimum of Months | 0.106133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.207657E+10 | 0.135330E+10 | 45099.64 | 4950486.80 | 91527420.25 | 0.354327E+10 | 0.167758E+10 | 5849.52 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320640E+10 | 0.00 | 0.00 | 0.44 |
February | 0.720923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256647E+10 | 0.00 | 0.00 | 0.44 |
March | 0.197318E+10 | 1975147.75 | 0.00 | 299897.56 | 0.00 | 0.941868E+09 | 0.141318E+09 | 0.00 | 0.52 |
April | 0.173493E+10 | 0.00 | 0.00 | 1658466.75 | 0.00 | 0.114274E+09 | 0.100453E+10 | 0.00 | 0.64 |
May | 0.109969E+10 | 0.00 | 0.00 | 4419616.72 | 3996329.14 | 225036.33 | 0.230939E+10 | 0.00 | 1.16 |
June | 0.320349E+09 | 0.365339E+09 | 0.00 | 5453425.70 | 21165086.64 | 0.00 | 0.213290E+10 | 0.00 | 1.53 |
July | 84913532.75 | 0.111950E+10 | 0.00 | 4366824.91 | 92555724.97 | 0.00 | 0.867247E+09 | 0.00 | 1.38 |
August | 0.264137E+09 | 0.538992E+09 | 0.00 | 5240692.29 | 33086288.98 | 0.00 | 0.118532E+10 | 0.00 | 1.41 |
September | 0.828812E+09 | 0.165412E+09 | 0.00 | 3656398.34 | 11936268.41 | 478995.04 | 0.153216E+10 | 0.00 | 1.27 |
October | 0.186245E+10 | 0.00 | 0.00 | 773823.36 | 528737.38 | 86068595.54 | 0.511218E+09 | 0.00 | 0.63 |
November | 0.165873E+10 | 0.00 | 106780.80 | 16372.33 | 1385309.73 | 0.753186E+09 | 20453146.00 | 5245.48 | 0.48 |
December | 0.320727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300245E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.112121E+11 | 0.219122E+10 | 106780.80 | 25885517.98 | 0.164654E+09 | 0.106714E+11 | 0.970454E+10 | 5245.48 | 0.86 |
Minimum of Months | 84913532.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.197318E+10 | 0.111950E+10 | 106780.80 | 5453425.70 | 92555724.97 | 0.320640E+10 | 0.230939E+10 | 5245.48 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117239E+10 | 0.00 | 0.00 | 382542.07 | 0.00 | 0.281571E+10 | 0.269383E+09 | 0.00 | 0.33 |
February | 0.130794E+10 | 0.00 | 0.00 | 564541.92 | 0.00 | 0.232827E+10 | 0.389670E+09 | 0.00 | 0.34 |
March | 0.201383E+10 | 7373789.91 | 0.00 | 2517243.91 | 0.00 | 0.719615E+09 | 0.134236E+10 | 0.00 | 0.45 |
April | 0.185064E+10 | 0.00 | 0.00 | 3458901.65 | 0.00 | 0.181092E+09 | 0.182315E+10 | 0.00 | 0.58 |
May | 0.127993E+10 | 3131992.82 | 0.00 | 6086981.67 | 1621483.84 | 487564.19 | 0.286200E+10 | 0.00 | 0.95 |
June | 0.465798E+09 | 0.464573E+09 | 0.00 | 6119262.41 | 35752861.99 | 0.00 | 0.206686E+10 | 0.00 | 1.17 |
July | 0.167012E+09 | 0.161588E+10 | 0.00 | 3572791.57 | 94645714.86 | 0.00 | 0.629877E+09 | 0.00 | 0.99 |
August | 0.337478E+09 | 0.871491E+09 | 0.00 | 6862267.48 | 29374698.96 | 0.00 | 0.133316E+10 | 0.00 | 1.19 |
September | 0.745655E+09 | 0.293427E+09 | 0.00 | 7728011.98 | 7459721.73 | 0.00 | 0.279060E+10 | 0.00 | 1.34 |
October | 0.163444E+10 | 376472.04 | 0.00 | 4762129.92 | 328218.75 | 72346468.03 | 0.228347E+10 | 0.00 | 0.74 |
November | 0.179987E+10 | 0.00 | 34887.66 | 1556708.24 | 1684729.57 | 0.624822E+09 | 0.741274E+09 | 3792.59 | 0.40 |
December | 0.111439E+10 | 0.00 | 0.00 | 191769.61 | 0.00 | 0.267741E+10 | 0.142886E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.138894E+11 | 0.325625E+10 | 34887.66 | 43803152.44 | 0.170867E+09 | 0.941975E+10 | 0.166747E+11 | 3792.59 | 0.74 |
Minimum of Months | 0.167012E+09 | 0.00 | 0.00 | 191769.61 | 0.00 | 0.00 | 0.142886E+09 | 0.00 | 0.33 |
Maximum of Months | 0.201383E+10 | 0.161588E+10 | 34887.66 | 7728011.98 | 94645714.86 | 0.281571E+10 | 0.286200E+10 | 3792.59 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325935E+10 | 0.00 | 0.00 | 0.45 |
February | 0.694236E+09 | 0.00 | 0.00 | 11877.34 | 0.00 | 0.269262E+10 | 15250587.80 | 0.00 | 0.46 |
March | 0.189223E+10 | 551434.17 | 0.00 | 412626.18 | 1212657.91 | 0.106336E+10 | 0.228629E+09 | 0.00 | 0.53 |
April | 0.188286E+10 | 0.00 | 0.00 | 1566524.54 | 0.00 | 0.203327E+09 | 0.876861E+09 | 0.00 | 0.68 |
May | 0.134880E+10 | 126475.51 | 0.00 | 4175422.40 | 4004970.68 | 899643.57 | 0.201464E+10 | 0.00 | 1.19 |
June | 0.442183E+09 | 0.374967E+09 | 0.00 | 5276247.48 | 28887027.53 | 0.00 | 0.170634E+10 | 0.00 | 1.55 |
July | 0.171914E+09 | 0.118340E+10 | 0.00 | 2934031.17 | 72528023.40 | 0.00 | 0.418972E+09 | 0.00 | 1.20 |
August | 0.366858E+09 | 0.588989E+09 | 0.00 | 4269524.60 | 24437421.11 | 0.00 | 0.778163E+09 | 0.00 | 1.28 |
September | 0.916471E+09 | 0.157557E+09 | 0.00 | 3321964.12 | 16577284.17 | 247549.88 | 0.120714E+10 | 0.00 | 1.22 |
October | 0.199685E+10 | 0.00 | 0.00 | 804895.20 | 546614.14 | 0.111997E+09 | 0.472585E+09 | 0.00 | 0.68 |
November | 0.171476E+10 | 0.00 | 108992.04 | 38562.07 | 1432147.45 | 0.766623E+09 | 33915603.48 | 5375.81 | 0.50 |
December | 0.512439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292234E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.123475E+11 | 0.230559E+10 | 108992.04 | 22811675.11 | 0.149626E+09 | 0.110208E+11 | 0.775250E+10 | 5375.81 | 0.85 |
Minimum of Months | 0.171914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.199685E+10 | 0.118340E+10 | 108992.04 | 5276247.48 | 72528023.40 | 0.325935E+10 | 0.201464E+10 | 5375.81 | 1.55 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:31:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.138077E+12 | 0.308289E+11 | 0.00 | 0.140197E+12 | 0.126538E+11 |
February | 0.211955E+12 | 0.315557E+11 | 0.00 | 0.130746E+12 | 0.117056E+11 |
March | 0.312020E+12 | 0.215752E+11 | 0.00 | 0.167882E+12 | 0.137017E+11 |
April | 0.368360E+12 | 0.169416E+11 | 0.00 | 0.202543E+12 | 0.408506E+10 |
May | 0.448136E+12 | 0.100108E+11 | 0.00 | 0.226491E+12 | 0.290955E+11 |
June | 0.481664E+12 | 0.381841E+10 | 0.00 | 0.128734E+12 | 0.137084E+12 |
July | 0.447591E+12 | -0.106005E+10 | 0.00 | 0.127489E+11 | 0.237829E+12 |
August | 0.383694E+12 | 0.134643E+10 | 0.00 | 0.884650E+11 | 0.196726E+12 |
September | 0.295728E+12 | 0.562422E+10 | 0.00 | 0.181586E+12 | 0.846813E+11 |
October | 0.203175E+12 | 0.137345E+11 | 0.00 | 0.209953E+12 | 0.990983E+10 |
November | 0.108165E+12 | 0.182810E+11 | 0.00 | 0.164607E+12 | 0.459309E+10 |
December | 0.123723E+12 | 0.317798E+11 | 0.00 | 0.144053E+12 | 0.108854E+11 |
Annual Sum or Average | 0.352229E+13 | 0.184437E+12 | 0.00 | 0.179801E+13 | 0.752951E+12 |
Minimum of Months | 0.108165E+12 | -0.106005E+10 | 0.00 | 0.127489E+11 | 0.408506E+10 |
Maximum of Months | 0.481664E+12 | 0.317798E+11 | 0.00 | 0.226491E+12 | 0.237829E+12 |