Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:31:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2080.72 | 417.63 | 417.63 |
Net Site Energy | 2080.72 | 417.63 | 417.63 |
Total Source Energy | 6351.34 | 1274.81 | 1274.81 |
Net Source Energy | 6351.34 | 1274.81 | 1274.81 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 6.76 | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 739.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1966.32 | 114.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 6.76 | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 739.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 6.76 | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 739.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.18 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 394.67 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.18 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 394.67 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1966.317 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1966.317 | 100.00 |
Total On-Site and Utility Electric Sources | 1966.317 | 100.00 |
Total Electricity End Uses | 1966.317 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 41.50 |
Time Setpoint Not Met During Occupied Cooling | 523.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1577.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-14:09 | 03-JAN-06:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 15418.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40588.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 839.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27823.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8531.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 206165.76 | 23950.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 15418.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 111226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 6054.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 839.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27823.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8531.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 21.42 | 1.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2341.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 480.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 122.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6227.33 | 124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.30 | 0.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 469.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1249.92 | 24.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.30 | 0.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 469.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1249.92 | 24.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.05 | 0.246107 | 0.265000 | 0.806988 | 0.656286 | 0.500000 | 0.001548 |
CORE_MID VAV BOX COMPONENT | 2.33 | 0.322310 | 0.337000 | 0.783612 | 0.859495 | 0.500000 | 0.001182 |
CORE_TOP VAV BOX COMPONENT | 2.63 | 0.284570 | 0.311000 | 0.819061 | 0.758854 | 0.500000 | 0.001339 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.978740 | 0.161424 | 0.200000 | 0.195748 | 0.430463 | 0.500000 | 0.002360 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.744691 | 0.134313 | 0.200000 | 0.148938 | 0.358169 | 0.500000 | 0.002837 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.994037 | 0.158939 | 0.200000 | 0.198807 | 0.423838 | 0.500000 | 0.002397 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.830633 | 0.120408 | 0.200000 | 0.166127 | 0.321089 | 0.500000 | 0.003164 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.804250 | 0.196446 | 0.211000 | 0.169697 | 0.523856 | 0.500000 | 0.001939 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.650160 | 0.153842 | 0.200000 | 0.130032 | 0.410245 | 0.500000 | 0.002477 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.818241 | 0.193087 | 0.208000 | 0.170194 | 0.514898 | 0.500000 | 0.001973 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.680888 | 0.146889 | 0.200000 | 0.136178 | 0.391705 | 0.500000 | 0.002594 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.838995 | 0.188311 | 0.200000 | 0.167799 | 0.502161 | 0.500000 | 0.002023 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.690218 | 0.144913 | 0.200000 | 0.138044 | 0.386435 | 0.500000 | 0.002629 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.855763 | 0.184621 | 0.200000 | 0.171153 | 0.492322 | 0.500000 | 0.002064 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.734732 | 0.136125 | 0.200000 | 0.146946 | 0.362999 | 0.500000 | 0.002799 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26272.54 |
CORE_MID VAV BOX REHEAT COIL | 25511.50 |
CORE_TOP VAV BOX REHEAT COIL | 27967.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11157.39 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7261.30 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11150.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7271.13 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7398.80 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4904.59 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7398.78 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4921.75 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8718.65 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5744.33 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8707.54 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5761.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.00 | 1.41 | 6.00 | 1.41 | 5.65 | 5.65 | 0.300000 | 0.250040 | 5.65 |
PACU_VAV_MID | 2.72 | 1.41 | 5.44 | 1.41 | 5.06 | 5.06 | 0.300000 | 0.278124 | 5.06 |
PACU_VAV_TOP | 3.09 | 1.53 | 6.18 | 2.06 | 6.07 | 6.07 | 0.300000 | 0.339755 | 6.07 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.65 |
PACU_VAV_MID_OA_CONTROLLER | 5.06 |
PACU_VAV_TOP_OA_CONTROLLER | 6.07 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.65 | 125116.14 | 0.738903 | 1.88 | 41701.21 | 0.738903 |
PACU_VAV_MID COOLING COIL | 5.06 | 114771.22 | 0.730365 | 1.69 | 38253.25 | 0.730365 |
PACU_VAV_TOP COOLING COIL | 6.07 | 132213.88 | 0.744267 | 2.02 | 44066.89 | 0.744267 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 4404.51 |
PACU_VAV_MID HEATING COIL | 6038.08 |
PACU_VAV_TOP HEATING COIL | 4827.68 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.65 |
PACU_VAV_MID FAN | 5.06 |
PACU_VAV_TOP FAN | 6.07 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5025E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5418E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8753E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9078E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2046E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2299E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3474E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0012E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1027 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2188E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4379E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8652E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5041E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5520E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8771E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9190E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2065E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2385E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9200E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7695E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6402E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5486E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7284E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3340E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4528E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4680E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2313E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2423E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0279E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0321E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8585E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8950E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4223E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4516E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1182E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1393E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6192E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4748E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0408E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1355E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8543E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.8625E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8580E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8944E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4215E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4495E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1166E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1333E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9347E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3253E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4589E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0159E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7619E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9014E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8125E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8431E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4570E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4874E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4284E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4451E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7620E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0283E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1062 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3039E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0174E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7143E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7665E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6801E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5042E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4690E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6208E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2689E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0138E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9558E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3951E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5544E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2047E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1699E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8102E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2561E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3581E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9609E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6817E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8553E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7616E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0278E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1062 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3033E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0167E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7138E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7663E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6799E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5041E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4688E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6204E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2687E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0138E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9557E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3952E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5543E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2045E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1698E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8101E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2560E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3581E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9607E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6815E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8551E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 41190.78697 | 41190.78697 | 3.04524 | 3.04524 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3809.72332 | 3809.72332 | 0.16532 | 0.42469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31482.97697 | 31482.97697 | 2.32526 | 2.32526 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10439.86146 | 10439.86146 | 0.45132 | 0.45132 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 35333.56369 | 35333.56369 | 2.63364 | 2.63364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19735.44235 | 19735.44235 | 0.85906 | 0.85906 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 13131.17580 | 13131.17580 | 0.97874 | 0.97874 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8523.30854 | 8523.30854 | 0.34271 | 0.34271 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9991.09221 | 9991.09221 | 0.74469 | 0.74469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5542.46042 | 5542.46042 | 0.22304 | 0.22304 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13336.41521 | 13336.41521 | 0.99404 | 0.99404 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8518.39117 | 8518.39117 | 0.34251 | 0.34251 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11144.14895 | 11144.14895 | 0.83063 | 0.83063 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5549.70141 | 5549.70141 | 0.22334 | 0.22334 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10790.14742 | 10790.14742 | 0.80425 | 0.80425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5211.52580 | 5211.52580 | 0.22726 | 0.22726 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8722.83003 | 8722.83003 | 0.65016 | 0.65016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3453.73079 | 3453.73079 | 0.15065 | 0.15065 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10977.85357 | 10977.85357 | 0.81824 | 0.81824 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5211.51315 | 5211.51315 | 0.22726 | 0.22726 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9135.10342 | 9135.10342 | 0.68089 | 0.68089 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3465.74185 | 3465.74185 | 0.15118 | 0.15118 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 11256.29013 | 11256.29013 | 0.83900 | 0.83900 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6136.57867 | 6136.57867 | 0.26780 | 0.26780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9260.26993 | 9260.26993 | 0.69022 | 0.69022 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4042.46487 | 4042.46487 | 0.17644 | 0.17644 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11481.25762 | 11481.25762 | 0.85576 | 0.85576 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6128.79206 | 6128.79206 | 0.26746 | 0.26746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9857.48761 | 9857.48761 | 0.73473 | 0.73473 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4054.80028 | 4054.80028 | 0.17698 | 0.17698 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 99959.77 | 5.65145 | 5.65145 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9054.65 | 1.18104 | 1.18104 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 92031.68 | 5.06089 | 5.06089 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9146.52 | 1.34001 | 1.34001 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 105203.66 | 6.06688 | 6.06688 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 8800.45 | 2.06125 | 2.06125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.04524 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24611 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80699 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65629 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54811E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26272.53733 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32526 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32231 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78361 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85949 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18209E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25511.49769 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63364 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28457 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81906 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75885 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33886E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27967.67294 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97874 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16142 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19575 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43046 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36025E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11157.38786 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74469 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13431 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14894 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35817 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83665E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7261.30092 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99404 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15894 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19881 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42384 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39714E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11150.71375 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83063 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12041 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16613 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32109 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16423E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7271.12673 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80425 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19645 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16970 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52386 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93947E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7398.80114 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65016 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15384 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13003 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41025 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47657E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4904.59095 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81824 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19309 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17019 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51490 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97320E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7398.78307 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68089 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14689 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13618 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39170 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59379E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4921.74852 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18831 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16780 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50216 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02325E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8718.65329 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69022 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14491 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13804 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38644 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62916E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5744.32521 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85576 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18462 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17115 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49232 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06369E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8707.54285 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73473 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13612 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14695 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36300 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79890E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5761.93053 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99939 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41309 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.99878 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41309 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.65145 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.65145 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25004 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72248 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40755 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.44497 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40755 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06089 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.06089 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.27812 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.09087 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52868 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.18174 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06125 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.06688 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.06688 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.33976 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.65145 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.06089 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.06688 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.65145 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.65145 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 125116.14401 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73890 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.88363 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41701.21080 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73890 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 4404.51417 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.65145 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06089 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06089 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 114771.22338 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73036 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68679 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38253.24875 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73036 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 6038.07973 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.06089 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.06688 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.06688 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 132213.87745 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74427 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.02209 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 44066.88535 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74427 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 4827.68206 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.06688 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 124437.74 | 424599.21 | 11.47 | 2.93 | 3.29 | 3.46 | 3.61 | 9.99 | 11.21 | 11.82 | 12.32 | 6.3716 | 5.0770 | 3.4184 | 1.4176 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 114244.26 | 389817.58 | 11.52 | 2.94 | 3.30 | 3.48 | 3.62 | 10.02 | 11.26 | 11.87 | 12.35 | 5.7058 | 4.5423 | 3.0576 | 1.2789 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 131423.67 | 448436.17 | 11.44 | 2.92 | 3.28 | 3.45 | 3.60 | 9.97 | 11.18 | 11.78 | 12.29 | 6.8400 | 5.4522 | 3.6714 | 1.5149 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.3910545045E-003 | 4.9619608216E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.2786874390E-002 | 6.4084099297E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4785541343E-002 | 6.4448075234E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3171937360E-002 | 6.1254109662E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.7721642901E-003 | 5.5302075759E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.9425938820E-002 | 1.5670782783E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9059820089E-002 | 2.7952100530E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.6470126634E-002 | 3.7466811892E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.7269760690E-002 | 5.7392970296E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.9393864979E-002 | 4.7279462121E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8562028952E-002 | 1.8351191919E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.4680270842E-002 | 3.2614970439E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.5261928976E-002 | 4.0191150644E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.1753087981E-002 | 3.3423045591E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3705452557E-002 | 1.9320798557E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.1933504844E-002 | 3.8770986544E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.0884671335E-002 | 4.9532937402E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.2461131769E-002 | 3.8491513702E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2478.51 | -56.2 | 0.00 | -700.3 | 3423.04 | 5145.10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 8.75 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 5.50 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 8.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 5.50 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 8.73 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.60 | 0.0000 | Y | 5.49 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.33 | 0.0000 | Y | 8.58 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.61 | 0.0000 | Y | 5.49 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 8.75 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 5.50 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 8.59 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 5.50 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.75 | 41.75 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.75 | 62.75 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.75 | 46.80 | 41.42 | |
Exterior Lighting Total | 5686.19 | 50.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 125116.14 | 92448.64 | 32667.50 | 0.74 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 114771.22 | 83824.87 | 30946.35 | 0.73 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 132213.88 | 98402.47 | 33811.40 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 124437.7 | 2.93 | 9.99 | N/A | N/A | 11.47 | |
PACU_VAV_MID COOLING COIL | 114244.3 | 2.94 | 10.02 | N/A | N/A | 11.52 | |
PACU_VAV_TOP COOLING COIL | 131423.7 | 2.92 | 9.97 | N/A | N/A | 11.44 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26272.54 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25511.50 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27967.67 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11157.39 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7261.30 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11150.71 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7271.13 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7398.80 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4904.59 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7398.78 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4921.75 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8718.65 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5744.33 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8707.54 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5761.93 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 4404.51 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 6038.08 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 4827.68 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.65 | 12291.28 | 2174.89 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.06 | 11006.87 | 2174.89 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.07 | 13194.78 | 2174.89 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 124437.74 | 2.93 | 9.99 | 11.47 | 6.3716 | 3.29 | 11.21 | 5.0770 | 3.46 | 11.82 | 3.4184 | 3.61 | 12.32 | 1.4176 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 114244.26 | 2.94 | 10.02 | 11.52 | 5.7058 | 3.30 | 11.26 | 4.5423 | 3.48 | 11.87 | 3.0576 | 3.62 | 12.35 | 1.2789 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 131423.67 | 2.92 | 9.97 | 11.44 | 6.8400 | 3.28 | 11.18 | 5.4522 | 3.45 | 11.78 | 3.6714 | 3.60 | 12.29 | 1.5149 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 41190.79 | 41190.79 | 41.88 | 3.045 | 3.045 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 31482.98 | 31482.98 | 32.01 | 2.325 | 2.325 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 35333.56 | 35333.56 | 35.93 | 2.634 | 2.634 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00884 | 41.81 | 0.00916 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13131.18 | 13131.18 | 63.33 | 0.979 | 0.979 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00870 | 41.61 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9991.09 | 9991.09 | 76.12 | 0.745 | 0.745 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00867 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13336.42 | 13336.42 | 64.32 | 0.994 | 0.994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00870 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11144.15 | 11144.15 | 84.91 | 0.831 | 0.831 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00865 | 41.16 | 0.00916 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10790.15 | 10790.15 | 52.04 | 0.804 | 0.804 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00874 | 41.71 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8722.83 | 8722.83 | 66.45 | 0.650 | 0.650 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00869 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10977.85 | 10977.85 | 52.95 | 0.818 | 0.818 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00874 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9135.10 | 9135.10 | 69.60 | 0.681 | 0.681 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00868 | 41.03 | 0.00916 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11256.29 | 11256.29 | 54.29 | 0.839 | 0.839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00873 | 41.71 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9260.27 | 9260.27 | 70.55 | 0.690 | 0.690 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00868 | 39.28 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11481.26 | 11481.26 | 55.37 | 0.856 | 0.856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00873 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9857.49 | 9857.49 | 75.10 | 0.735 | 0.735 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00867 | 41.16 | 0.00916 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3809.72 | 3809.72 | 3.87 | 0.165 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_MID | 10439.86 | 10439.86 | 10.61 | 0.451 | 0.451 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_TOP | 19735.44 | 19735.44 | 20.07 | 0.859 | 0.859 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8523.31 | 8523.31 | 41.11 | 0.343 | 0.343 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00790 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5542.46 | 5542.46 | 42.22 | 0.223 | 0.223 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00791 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8518.39 | 8518.39 | 41.08 | 0.343 | 0.343 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00790 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5549.70 | 5549.70 | 42.28 | 0.223 | 0.223 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00791 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5211.53 | 5211.53 | 25.14 | 0.227 | 0.227 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3453.73 | 3453.73 | 26.31 | 0.151 | 0.151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5211.51 | 5211.51 | 25.14 | 0.227 | 0.227 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3465.74 | 3465.74 | 26.40 | 0.151 | 0.151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6136.58 | 6136.58 | 29.60 | 0.268 | 0.268 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4042.46 | 4042.46 | 30.80 | 0.176 | 0.176 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6128.79 | 6128.79 | 29.56 | 0.267 | 0.267 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4054.80 | 4054.80 | 30.89 | 0.177 | 0.177 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.65 | 5.65 | 1.18 | 1.18 | 5.6515 | 1.4131 | 5.6515 | 0.2500 | 0.3000 |
PACU_VAV_MID | 5.06 | 5.06 | 1.34 | 1.34 | 5.0609 | 1.4076 | 5.0609 | 0.2781 | 0.3000 |
PACU_VAV_TOP | 6.07 | 6.07 | 2.06 | 2.06 | 6.0669 | 2.0613 | 6.0669 | 0.3398 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26272.537 | 26272.537 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26272.54 | 13826.37 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00799998 | 50.4124 | 3809.72 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25511.498 | 25511.498 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25511.50 | 14693.18 | 0.451316 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 10439.86 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27967.673 | 27967.673 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27967.67 | 27967.67 | 0.859056 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 19735.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11157.388 | 11157.388 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11157.39 | 11157.39 | 0.342711 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00790328 | 50.7518 | 8523.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7261.301 | 7261.301 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7261.30 | 7261.30 | 0.223038 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00790640 | 50.7722 | 5542.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11150.714 | 11150.714 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11150.71 | 11150.71 | 0.342506 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00790303 | 50.7502 | 8518.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7271.127 | 7271.127 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7271.13 | 7271.13 | 0.223340 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00790697 | 50.7759 | 5549.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7398.801 | 7398.801 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7398.80 | 7398.80 | 0.227262 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794590 | 50.0764 | 5211.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4904.591 | 4904.591 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4904.59 | 4904.59 | 0.150650 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794707 | 50.0837 | 3453.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7398.783 | 7398.783 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7398.78 | 7398.78 | 0.227261 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794590 | 50.0764 | 5211.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4921.749 | 4921.749 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4921.75 | 4921.75 | 0.151177 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794737 | 50.0855 | 3465.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8718.653 | 8718.653 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8718.65 | 8718.65 | 0.267802 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793962 | 50.0375 | 6136.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5744.325 | 5744.325 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5744.33 | 5744.33 | 0.176443 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794085 | 50.0451 | 4042.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8707.543 | 8707.543 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8707.54 | 8707.54 | 0.267461 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793949 | 50.0366 | 6128.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5761.931 | 5761.931 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5761.93 | 5761.93 | 0.176984 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794116 | 50.0470 | 4054.80 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 125116.144 | 92448.644 | 5.651455 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 115615.38 | 109786.90 | 5.651455 | 27.81 | 17.72 | 0.00885229 | 10.99 | 10.99 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 21.1480 | 24.00 | 0.00877023 | 46.0033 | 75755.11 | 0.00 | 129011.54 | 92843.72 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 4404.514 | 4404.514 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4404.51 | 4404.51 | 1.695436 | 10.60 | 8.97 | 0.00663100 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 70.4934 | 21.00 | 0.00795604 | 50.1394 | 21152.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 114771.223 | 83824.869 | 5.060888 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 106545.43 | 100805.91 | 5.060888 | 28.26 | 17.90 | 0.00888801 | 10.99 | 10.99 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 23.6158 | 24.00 | 0.00880425 | 46.1793 | 67702.50 | 0.00 | 118344.54 | 84246.31 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 6038.080 | 6038.080 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6038.08 | 6038.08 | 1.518266 | 9.43 | 8.26 | 0.00647814 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 78.7194 | 21.00 | 0.00797856 | 50.2793 | 26281.41 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 132213.877 | 98402.475 | 6.066878 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 121980.30 | 116035.03 | 6.066878 | 27.53 | 17.62 | 0.00883442 | 10.99 | 10.99 | 0.00850000 | 41.90 | 0.00915774 | 22.24 | 19.6999 | 24.00 | 0.00875489 | 45.9239 | 81220.28 | 0.00 | 136330.25 | 98797.39 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 4827.682 | 4827.682 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4827.68 | 4827.68 | 1.820064 | 10.55 | 9.02 | 0.00669844 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 65.6664 | 19.60 | 0.00789591 | 54.2636 | 31735.04 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26272.537 | 26272.537 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26272.54 | 13826.37 | 1.0000 | 0.49849623 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26272.54 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.78 | 0.00799998 | 21.00 | 0.00799998 | 50.4124 | 3809.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25511.498 | 25511.498 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25511.50 | 14693.18 | 1.0000 | 0.52974829 | 0.451316 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25511.50 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 10439.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27967.673 | 27967.673 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27967.67 | 27967.67 | 1.0000 | 1.00834713 | 0.859056 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27967.67 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 19735.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11157.388 | 11157.388 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11157.39 | 11157.39 | 1.0000 | 0.40226872 | 0.342711 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11157.39 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00790328 | 20.70 | 0.00790328 | 50.7518 | 8523.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7261.301 | 7261.301 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7261.30 | 7261.30 | 1.0000 | 0.26179911 | 0.223038 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7261.30 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00790640 | 20.70 | 0.00790640 | 50.7722 | 5542.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11150.714 | 11150.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11150.71 | 11150.71 | 1.0000 | 0.40202809 | 0.342506 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11150.71 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00790303 | 20.70 | 0.00790303 | 50.7502 | 8518.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7271.127 | 7271.127 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7271.13 | 7271.13 | 1.0000 | 0.26215337 | 0.223340 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7271.13 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00790697 | 20.70 | 0.00790697 | 50.7759 | 5549.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7398.801 | 7398.801 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7398.80 | 7398.80 | 1.0000 | 0.26675655 | 0.227262 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7398.80 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794590 | 21.00 | 0.00794590 | 50.0764 | 5211.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4904.591 | 4904.591 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4904.59 | 4904.59 | 1.0000 | 0.17683024 | 0.150650 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4904.59 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794707 | 21.00 | 0.00794707 | 50.0837 | 3453.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7398.783 | 7398.783 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7398.78 | 7398.78 | 1.0000 | 0.26675590 | 0.227261 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7398.78 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794590 | 21.00 | 0.00794590 | 50.0764 | 5211.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4921.749 | 4921.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4921.75 | 4921.75 | 1.0000 | 0.17744884 | 0.151177 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4921.75 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794737 | 21.00 | 0.00794737 | 50.0855 | 3465.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8718.653 | 8718.653 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8718.65 | 8718.65 | 1.0000 | 0.31434253 | 0.267802 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8718.65 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00793962 | 21.00 | 0.00793962 | 50.0375 | 6136.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5744.325 | 5744.325 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5744.33 | 5744.33 | 1.0000 | 0.20710604 | 0.176443 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5744.33 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794085 | 21.00 | 0.00794085 | 50.0451 | 4042.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8707.543 | 8707.543 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8707.54 | 8707.54 | 1.0000 | 0.31394195 | 0.267461 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8707.54 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00793949 | 21.00 | 0.00793949 | 50.0366 | 6128.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5761.931 | 5761.931 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5761.93 | 5761.93 | 1.0000 | 0.20774078 | 0.176984 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5761.93 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794116 | 21.00 | 0.00794116 | 50.0470 | 4054.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 125116.144 | 92448.644 | 5.651455 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2960 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.651455 | 6.63359528 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 115615.38 | 109786.90 | 0.9241 | 6.63359528 | 5.651455 | 27.81 | 17.72 | 0.00885229 | 50540.3 | 10.99 | 10.99 | 0.00850000 | 32470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12291.283 | 103324.09 | 42.00 | 0.00915790 | 22.26 | 1.19517000 | 21.1480 | 24.00 | 0.00877023 | 24.00 | 0.00877023 | 46.0033 | 75755.11 | 0.00 | 129011.54 | 92843.72 | 6.37161841 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.40 | 12.39 | 0.00895907 | 35074.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4404.514 | 4404.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.651455 | 6.63359528 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4404.51 | 4404.51 | 1.0000 | 1.99007858 | 1.695436 | 10.60 | 8.97 | 0.00663100 | 27363.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4404.51 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 70.4934 | 20.86 | 0.00796569 | 21.00 | 0.00795604 | 50.1394 | 21152.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 114771.223 | 83824.869 | 5.060888 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3624 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.060888 | 5.94039660 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 106545.43 | 100805.91 | 0.9283 | 5.94039660 | 5.060888 | 28.26 | 17.90 | 0.00888801 | 51094.4 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11006.866 | 95538.57 | 42.00 | 0.00915790 | 22.26 | 1.19517000 | 23.6158 | 24.00 | 0.00880425 | 24.00 | 0.00880425 | 46.1793 | 67702.50 | 0.00 | 118344.54 | 84246.31 | 5.70579584 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.21 | 12.20 | 0.00884158 | 34581.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6038.080 | 6038.080 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.060888 | 5.94039660 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6038.08 | 6038.08 | 1.0000 | 1.78211898 | 1.518266 | 9.43 | 8.26 | 0.00647814 | 25788.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6038.08 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 78.7194 | 21.00 | 0.00797923 | 21.00 | 0.00797856 | 50.2793 | 26281.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 132213.877 | 98402.475 | 6.066878 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2627 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.066878 | 7.12121361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 121980.30 | 116035.03 | 0.9226 | 7.12121361 | 6.066878 | 27.53 | 17.62 | 0.00883442 | 50213.3 | 10.99 | 10.99 | 0.00850000 | 32470.4 | -999.0 | -999.00 | -999.00 | -999.00 | 13194.783 | 108785.51 | 41.90 | 0.00915774 | 22.24 | 1.19517000 | 19.6999 | 24.00 | 0.00875489 | 24.00 | 0.00875489 | 45.9239 | 81220.28 | 0.00 | 136330.25 | 98797.39 | 6.83997951 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.53 | 12.52 | 0.00903322 | 35391.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4827.682 | 4827.682 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.066878 | 7.12121361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4827.68 | 4827.68 | 1.0000 | 2.13636408 | 1.820064 | 10.55 | 9.02 | 0.00669844 | 27486.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4827.68 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 65.6664 | 18.68 | 0.00789591 | 19.60 | 0.00789591 | 54.2636 | 31735.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4667.50 | 191.33 | 12.33 |
CORE_MID | 3956.67 | 1053.00 | 4.67 |
CORE_TOP | 3729.50 | 1575.50 | 31.00 |
PERIMETER_TOP_ZN_3 | 3842.33 | 2246.33 | 528.83 |
PERIMETER_TOP_ZN_2 | 4058.17 | 2026.50 | 546.83 |
PERIMETER_TOP_ZN_1 | 4403.50 | 1621.17 | 556.67 |
PERIMETER_TOP_ZN_4 | 3998.83 | 2133.67 | 569.83 |
PERIMETER_BOT_ZN_3 | 3812.17 | 1827.50 | 241.50 |
PERIMETER_BOT_ZN_2 | 4216.50 | 1466.67 | 351.00 |
PERIMETER_BOT_ZN_1 | 4623.83 | 2013.67 | 1202.00 |
PERIMETER_BOT_ZN_4 | 4168.17 | 1622.00 | 349.17 |
PERIMETER_MID_ZN_3 | 3857.67 | 1922.67 | 375.00 |
PERIMETER_MID_ZN_2 | 3410.50 | 1626.17 | 437.83 |
PERIMETER_MID_ZN_1 | 4532.17 | 1333.33 | 462.17 |
PERIMETER_MID_ZN_4 | 4072.00 | 1844.00 | 433.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5215.83 | 3348.33 | 1577.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 61.50 | 0.17 | 39.17 |
PERIMETER_TOP_ZN_2 | 0.17 | 86.67 | 0.17 | 65.17 |
PERIMETER_TOP_ZN_1 | 0.17 | 95.50 | 0.17 | 70.33 |
PERIMETER_TOP_ZN_4 | 0.17 | 80.83 | 0.17 | 48.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 35.17 | 0.00 | 23.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 69.67 | 0.00 | 53.33 |
PERIMETER_BOT_ZN_1 | 41.33 | 423.67 | 41.33 | 405.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 71.83 | 0.00 | 40.17 |
PERIMETER_MID_ZN_3 | 0.00 | 45.00 | 0.00 | 30.50 |
PERIMETER_MID_ZN_2 | 0.00 | 70.00 | 0.00 | 59.00 |
PERIMETER_MID_ZN_1 | 0.00 | 85.17 | 0.00 | 69.83 |
PERIMETER_MID_ZN_4 | 0.00 | 66.33 | 0.00 | 40.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 41.50 | 588.83 | 41.50 | 523.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.507 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.432 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.423 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.579 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.743 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.760 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.765 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.480 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.631 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.721 | 1.245 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.634 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.567 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.704 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.772 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.762 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.81 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8460062.11 | 0.00 | 8460062.11 | 0.00 | 8460062.11 | 13393058.27 | 6997.33 | 120.34 | 1642.33 | 395.51 |
CORE_MID | 7206910.00 | 0.00 | 7206910.00 | 0.00 | 7206910.00 | 13393058.27 | 8460.27 | 45.25 | 254.47 | 343.01 |
CORE_TOP | 7092778.74 | 0.00 | 7092778.74 | 0.00 | 7092778.74 | 13393058.27 | 8692.79 | 18.79 | 48.42 | 373.00 |
PERIMETER_TOP_ZN_3 | 2028626.25 | 0.00 | 2028626.25 | 173897.85 | 2202524.09 | 2823374.22 | 4116.26 | 105.55 | 4538.19 | 373.00 |
PERIMETER_TOP_ZN_2 | 1638297.99 | 0.00 | 1638297.99 | 115931.20 | 1754229.19 | 1787429.43 | 3389.09 | 19.19 | 5351.72 | 373.00 |
PERIMETER_TOP_ZN_1 | 2625887.44 | 0.00 | 2625887.44 | 173897.85 | 2799785.28 | 2823374.22 | 3412.68 | 14.12 | 5333.20 | 373.00 |
PERIMETER_TOP_ZN_4 | 1703682.97 | 0.00 | 1703682.97 | 115931.20 | 1819614.17 | 1787312.18 | 3490.15 | 25.73 | 5244.12 | 373.00 |
PERIMETER_BOT_ZN_3 | 1693543.44 | 0.00 | 1693543.44 | 92461.45 | 1786004.89 | 2823374.22 | 6952.98 | 108.13 | 1698.89 | 395.51 |
PERIMETER_BOT_ZN_2 | 1402292.11 | 0.00 | 1402292.11 | 61640.59 | 1463932.70 | 1787429.43 | 3994.96 | 105.33 | 4659.71 | 395.51 |
PERIMETER_BOT_ZN_1 | 2483262.73 | 0.00 | 2483262.73 | 4106049.28 | 6589312.01 | 2823374.22 | 4970.36 | 50.35 | 3739.28 | 395.51 |
PERIMETER_BOT_ZN_4 | 1420772.98 | 0.00 | 1420772.98 | 61640.59 | 1482413.57 | 1787312.18 | 4261.49 | 112.94 | 4385.58 | 395.51 |
PERIMETER_MID_ZN_3 | 1966686.42 | 0.00 | 1966686.42 | 144757.29 | 2111443.71 | 2823374.22 | 5662.05 | 427.11 | 2670.84 | 343.01 |
PERIMETER_MID_ZN_2 | 1622465.89 | 0.00 | 1622465.89 | 96504.28 | 1718970.17 | 1787429.43 | 3467.16 | 33.10 | 5259.74 | 1252.01 |
PERIMETER_MID_ZN_1 | 2641786.47 | 0.00 | 2641786.47 | 144757.29 | 2786543.76 | 2823374.22 | 3569.39 | 973.43 | 4217.18 | 343.01 |
PERIMETER_MID_ZN_4 | 1680404.53 | 0.00 | 1680404.53 | 96504.28 | 1776908.81 | 1787312.18 | 3597.50 | 29.31 | 5133.18 | 343.01 |
Total Facility | 45667460.04 | 0.00 | 45667460.04 | 5383973.17 | 51051433.21 | 67843644.98 | 8760.00 | 1942.21 | 5695.30 | 1451.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3681 | 0.0000 | 0.3681 | 0.0000 | 0.3681 | 0.4247 | 4188.35 | 120.01 | 1634.64 |
CORE_MID | 0.3136 | 0.0000 | 0.3136 | 0.0000 | 0.3136 | 0.4247 | 5645.39 | 45.09 | 252.52 |
CORE_TOP | 0.3069 | 0.0000 | 0.3069 | 0.0000 | 0.3069 | 0.4247 | 5877.11 | 18.75 | 47.14 |
PERIMETER_TOP_ZN_3 | 0.0885 | 0.0000 | 0.0885 | 0.0050 | 0.0934 | 0.0895 | 1668.98 | 103.48 | 4170.54 |
PERIMETER_TOP_ZN_2 | 0.0719 | 0.0000 | 0.0719 | 0.0033 | 0.0752 | 0.0567 | 943.91 | 19.10 | 4980.00 |
PERIMETER_TOP_ZN_1 | 0.1163 | 0.0000 | 0.1163 | 0.0050 | 0.1212 | 0.0895 | 967.30 | 13.48 | 4962.22 |
PERIMETER_TOP_ZN_4 | 0.0740 | 0.0000 | 0.0740 | 0.0033 | 0.0774 | 0.0567 | 1045.63 | 25.57 | 4871.81 |
PERIMETER_BOT_ZN_3 | 0.0732 | 0.0000 | 0.0732 | 0.0026 | 0.0759 | 0.0895 | 4167.12 | 107.13 | 1668.75 |
PERIMETER_BOT_ZN_2 | 0.0610 | 0.0000 | 0.0610 | 0.0018 | 0.0628 | 0.0567 | 1569.81 | 103.76 | 4269.43 |
PERIMETER_BOT_ZN_1 | 0.1100 | 0.0000 | 0.1100 | 0.1902 | 0.3002 | 0.0895 | 2206.18 | 47.94 | 3688.88 |
PERIMETER_BOT_ZN_4 | 0.0613 | 0.0000 | 0.0613 | 0.0018 | 0.0630 | 0.0567 | 1838.17 | 112.73 | 3992.10 |
PERIMETER_MID_ZN_3 | 0.0866 | 0.0000 | 0.0866 | 0.0041 | 0.0907 | 0.0895 | 2891.41 | 425.45 | 2626.14 |
PERIMETER_MID_ZN_2 | 0.0681 | 0.0000 | 0.0681 | 0.0028 | 0.0710 | 0.0567 | 953.25 | 25.22 | 4055.52 |
PERIMETER_MID_ZN_1 | 0.1180 | 0.0000 | 0.1180 | 0.0041 | 0.1222 | 0.0895 | 1077.39 | 696.71 | 4168.90 |
PERIMETER_MID_ZN_4 | 0.0737 | 0.0000 | 0.0737 | 0.0028 | 0.0764 | 0.0567 | 1122.69 | 29.14 | 4791.17 |
Total Facility | 1.9911 | 0.0000 | 1.9911 | 0.2268 | 2.2179 | 2.1513 | 5943.00 | 1658.83 | 5152.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21300236.60 | 0.00 | 21300236.60 | 22614548.33 | 3331.28 | 0.00 | 5428.72 | 395.51 |
PACU_VAV_MID | 20829531.12 | 0.00 | 20829531.12 | 22614548.33 | 3391.78 | 0.00 | 5368.22 | 343.01 |
PACU_VAV_TOP | 20789568.81 | 0.00 | 20789568.81 | 22614548.33 | 3367.09 | 0.00 | 5392.91 | 373.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9280 | 0.0000 | 0.9280 | 0.7171 | 909.79 | 0.00 | 5033.21 |
PACU_VAV_MID | 0.9142 | 0.0000 | 0.9142 | 0.7171 | 917.79 | 0.00 | 5025.21 |
PACU_VAV_TOP | 0.9059 | 0.0000 | 0.9059 | 0.7171 | 923.09 | 0.00 | 5019.91 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5428.72 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5368.22 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5392.91 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0958 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0812 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0727 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
Electricity:Building | 1006.20 | 12233.70 | 16-JUL-17:20 | 78507.21 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1006.20 | 12233.70 | 16-JUL-17:20 | 78507.21 | 11-OCT-07:10 |
InteriorLights:Electricity | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.09 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.90 | 267.21 | 02-JUL-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.93 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.06 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.89 | 267.21 | 29-MAY-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.91 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.58 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.58 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:40 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:40 | 859.95 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.09 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.90 | 267.21 | 02-JUL-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.93 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 909.33 | 168.34 | 01-JAN-00:10 | 139889.36 | 12-JUN-14:10 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
ElectricityPurchased:Plant | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
Cogeneration:ElectricityPurchased | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
General:Cogeneration:ElectricityPurchased | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
ElectricityNet:Plant | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
Cogeneration:ElectricityNet | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
General:Cogeneration:ElectricityNet | 1966.32 | 12404.51 | 04-JUN-17:30 | 206165.76 | 12-JUN-14:10 |
Heating:Electricity | 6.76 | 0.00 | 01-JAN-00:10 | 95048.95 | 02-JAN-07:10 |
General:Heating:Electricity | 6.76 | 0.00 | 01-JAN-00:10 | 95048.95 | 02-JAN-07:10 |
Fans:Electricity | 151.60 | 0.00 | 01-JAN-00:10 | 27823.66 | 12-JUN-14:10 |
General:Fans:Electricity | 151.60 | 0.00 | 01-JAN-00:10 | 27823.66 | 12-JUN-14:10 |
ExteriorLights:Electricity | 50.64 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.64 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 739.21 | 0.00 | 01-JAN-00:10 | 116350.40 | 12-JUN-15:30 |
General:Cooling:Electricity | 739.21 | 0.00 | 01-JAN-00:10 | 116350.40 | 12-JUN-15:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 8.45 | 0.00 | 01-JAN-00:10 | 917.25 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 114.40 | 1886.44 | 16-APR-15:20 | 23950.10 | 03-JAN-06:50 |
NaturalGas:HVAC | 1.72 | 0.00 | 01-JAN-00:10 | 15545.43 | 03-JAN-07:00 |
Heating:NaturalGas | 1.72 | 0.00 | 01-JAN-00:10 | 15545.43 | 03-JAN-07:00 |
General:Heating:NaturalGas | 1.72 | 0.00 | 01-JAN-00:10 | 15545.43 | 03-JAN-07:00 |
NaturalGas:Plant | 112.69 | 1886.44 | 03-JAN-06:20 | 9695.02 | 18-JAN-12:10 |
WaterSystems:NaturalGas | 112.69 | 1886.44 | 03-JAN-06:20 | 9695.02 | 18-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 112.69 | 1886.44 | 03-JAN-06:20 | 9695.02 | 18-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4522.47 | 0.00 | 01-JAN-00:10 | 523924.31 | 22-JUN-15:40 |
EnergyTransfer:Building | 1796.00 | 0.00 | 01-JAN-00:10 | 205061.90 | 12-JUN-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 315.74 | 0.00 | 01-JAN-00:10 | 28436.54 | 05-SEP-08:00 |
Heating:EnergyTransfer | 9.05 | 0.00 | 01-JAN-00:10 | 78877.17 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.05 | 0.00 | 01-JAN-00:10 | 78877.17 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1786.95 | 0.00 | 01-JAN-00:10 | 205061.90 | 12-JUN-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 315.74 | 0.00 | 01-JAN-00:10 | 28436.54 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1786.95 | 0.00 | 01-JAN-00:10 | 205061.90 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 315.74 | 0.00 | 01-JAN-00:10 | 28436.54 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 90.50 | 0.00 | 01-JAN-00:10 | 17342.07 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.15 | 0.00 | 01-JAN-00:10 | 8940.52 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.15 | 0.00 | 01-JAN-00:10 | 8940.52 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 86.35 | 0.00 | 01-JAN-00:10 | 17342.07 | 12-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 86.35 | 0.00 | 01-JAN-00:10 | 17342.07 | 12-JUN-14:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 47.89 | 0.00 | 01-JAN-00:10 | 7461.84 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.19 | 0.00 | 01-JAN-00:10 | 2423.65 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.19 | 0.00 | 01-JAN-00:10 | 2423.65 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.69 | 0.00 | 01-JAN-00:10 | 7461.84 | 12-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.69 | 0.00 | 01-JAN-00:10 | 7461.84 | 12-JUN-14:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.45 | 0.00 | 01-JAN-00:10 | 7274.47 | 05-JUL-07:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.54 | 0.00 | 01-JAN-00:10 | 2380.09 | 02-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.54 | 0.00 | 01-JAN-00:10 | 2380.09 | 02-JAN-09:00 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 52.91 | 0.00 | 01-JAN-00:10 | 7274.47 | 05-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 52.91 | 0.00 | 01-JAN-00:10 | 7274.47 | 05-JUL-07:20 |
EnergyTransfer:Zone:CORE_MID | 224.01 | 0.00 | 01-JAN-00:10 | 21054.81 | 30-MAY-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 5518.55 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 5518.55 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 224.01 | 0.00 | 01-JAN-00:10 | 21054.81 | 30-MAY-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 224.01 | 0.00 | 01-JAN-00:10 | 21054.81 | 30-MAY-07:50 |
EnergyTransfer:Zone:CORE_TOP | 232.05 | 0.00 | 01-JAN-00:10 | 24310.86 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.13 | 0.00 | 01-JAN-00:10 | 15287.20 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.13 | 0.00 | 01-JAN-00:10 | 15287.20 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 231.92 | 0.00 | 01-JAN-00:10 | 24310.86 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 231.92 | 0.00 | 01-JAN-00:10 | 24310.86 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 71.01 | 0.00 | 01-JAN-00:10 | 10063.25 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 7945.36 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 7945.36 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.46 | 0.00 | 01-JAN-00:10 | 10063.25 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.46 | 0.00 | 01-JAN-00:10 | 10063.25 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.08 | 0.00 | 01-JAN-00:10 | 9895.88 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.23 | 0.00 | 01-JAN-00:10 | 5097.50 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.23 | 0.00 | 01-JAN-00:10 | 5097.50 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.85 | 0.00 | 01-JAN-00:10 | 9895.88 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.85 | 0.00 | 01-JAN-00:10 | 9895.88 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.21 | 0.00 | 01-JAN-00:10 | 13679.54 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.30 | 0.00 | 01-JAN-00:10 | 7408.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.30 | 0.00 | 01-JAN-00:10 | 7408.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.91 | 0.00 | 01-JAN-00:10 | 13679.54 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.91 | 0.00 | 01-JAN-00:10 | 13679.54 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.82 | 0.00 | 01-JAN-00:10 | 10811.27 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.34 | 0.00 | 01-JAN-00:10 | 5017.68 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.34 | 0.00 | 01-JAN-00:10 | 5017.68 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.47 | 0.00 | 01-JAN-00:10 | 10811.27 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.47 | 0.00 | 01-JAN-00:10 | 10811.27 | 08-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.28 | 0.00 | 01-JAN-00:10 | 8966.72 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2448.45 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2448.45 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.26 | 0.00 | 01-JAN-00:10 | 8966.72 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.26 | 0.00 | 01-JAN-00:10 | 8966.72 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.45 | 0.00 | 01-JAN-00:10 | 8736.35 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1400.08 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1400.08 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.44 | 0.00 | 01-JAN-00:10 | 8736.35 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.44 | 0.00 | 01-JAN-00:10 | 8736.35 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.41 | 0.00 | 01-JAN-00:10 | 16260.92 | 12-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 6785.89 | 03-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 6785.89 | 03-JAN-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.06 | 0.00 | 01-JAN-00:10 | 16260.92 | 12-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.06 | 0.00 | 01-JAN-00:10 | 16260.92 | 12-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.12 | 0.00 | 01-JAN-00:10 | 9147.29 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1325.81 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1325.81 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.11 | 0.00 | 01-JAN-00:10 | 9147.29 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.11 | 0.00 | 01-JAN-00:10 | 9147.29 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.16 | 0.00 | 01-JAN-00:10 | 8994.46 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3999.81 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3999.81 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.08 | 0.00 | 01-JAN-00:10 | 8994.46 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.08 | 0.00 | 01-JAN-00:10 | 8994.46 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.52 | 0.00 | 01-JAN-00:10 | 9161.18 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2587.03 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2587.03 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.48 | 0.00 | 01-JAN-00:10 | 9161.18 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.48 | 0.00 | 01-JAN-00:10 | 9161.18 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.91 | 0.00 | 01-JAN-00:10 | 12138.67 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3471.88 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3471.88 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.87 | 0.00 | 01-JAN-00:10 | 12138.67 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.87 | 0.00 | 01-JAN-00:10 | 12138.67 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.40 | 0.00 | 01-JAN-00:10 | 9874.14 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2525.14 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2525.14 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.35 | 0.00 | 01-JAN-00:10 | 9874.14 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.35 | 0.00 | 01-JAN-00:10 | 9874.14 | 08-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 2691.63 | 0.00 | 01-JAN-00:10 | 340186.91 | 22-JUN-15:40 |
HeatingCoils:EnergyTransfer | 8.14 | 0.00 | 01-JAN-00:10 | 102864.03 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2683.49 | 0.00 | 01-JAN-00:10 | 340186.91 | 22-JUN-15:40 |
EnergyTransfer:Plant | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
WaterSystems:EnergyTransfer | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 34.85 | 0.00 | 01-JAN-00:10 | 4901.53 | 17-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -315.737 | 0.000 | 0.000 | 32.682 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.041 |
CORE_MID | 0.000 | 0.000 | 0.005 | -224.010 | 0.000 | 0.000 | 32.891 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 3.761 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_TOP | 0.000 | 0.000 | 0.128 | -231.919 | 0.000 | 0.000 | 33.234 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 11.204 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.547 | -70.459 | 0.000 | 0.000 | 7.101 | 8.754 | 24.333 | 33.130 | 0.000 | 0.765 | 10.556 | 0.000 | -14.369 | 0.000 | -0.357 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.229 | -57.849 | 0.000 | 0.000 | 4.445 | 5.499 | 15.404 | 38.374 | 0.000 | 0.502 | 2.752 | 0.000 | -9.103 | 0.000 | -0.254 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.303 | -92.906 | 0.000 | 0.000 | 6.983 | 8.595 | 24.332 | 68.960 | 0.000 | 0.749 | 0.001 | 0.000 | -14.374 | 0.000 | -0.422 | -2.219 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.344 | -58.472 | 0.000 | 0.000 | 4.499 | 5.504 | 15.403 | 38.882 | 0.000 | 0.506 | 3.307 | 0.000 | -9.723 | 0.000 | -0.251 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.026 | -67.259 | 0.000 | 0.000 | 7.007 | 8.726 | 24.333 | 33.049 | 0.000 | 0.415 | 9.806 | 0.000 | -15.887 | 0.000 | -0.216 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.008 | -56.438 | 0.000 | 0.000 | 4.396 | 5.487 | 15.404 | 38.217 | 0.000 | 0.269 | 3.034 | 0.000 | -10.221 | 0.000 | -0.155 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.347 | -105.058 | 0.000 | 0.000 | 6.905 | 8.578 | 24.332 | 68.736 | 0.000 | 20.561 | 0.002 | 0.000 | -16.295 | 0.000 | -8.888 | -0.217 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.011 | -56.113 | 0.000 | 0.000 | 4.426 | 5.490 | 15.403 | 38.783 | 0.000 | 0.268 | 2.858 | 0.000 | -10.973 | 0.000 | -0.154 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.080 | -66.083 | 0.000 | 0.000 | 7.018 | 8.754 | 24.333 | 33.096 | 0.000 | 0.639 | 8.115 | 0.000 | -15.618 | 0.000 | -0.334 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.039 | -54.478 | 0.000 | 0.000 | 3.261 | 5.499 | 15.404 | 38.335 | 0.000 | 0.421 | 1.525 | 0.000 | -9.774 | 0.000 | -0.233 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.039 | -88.870 | 0.000 | 0.000 | 6.934 | 8.595 | 24.332 | 68.970 | 0.000 | 0.626 | 0.003 | 0.000 | -15.443 | 0.000 | -0.382 | -4.801 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.055 | -55.347 | 0.000 | 0.000 | 4.451 | 5.504 | 15.403 | 38.884 | 0.000 | 0.421 | 1.374 | 0.000 | -10.514 | 0.000 | -0.232 | -0.001 |
TOPFLOOR_PLENUM | 4.154 | -86.350 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.004 | 81.762 | 0.000 | 0.000 | 0.000 | -0.570 | -0.001 |
MIDFLOOR_PLENUM | 1.194 | -46.693 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.998 | 45.102 | 0.000 | 0.000 | 0.000 | -0.600 | -0.000 |
FIRSTFLOOR_PLENUM | 0.539 | -52.907 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.772 | 52.100 | 0.000 | 0.000 | 0.000 | -0.503 | -0.000 |
Total Facility | 5.886 | -185.951 | 3.160 | -1600.996 | 0.000 | 0.000 | 166.234 | 300.769 | 705.434 | 537.415 | 0.000 | 28.916 | 237.260 | 0.000 | -152.295 | 0.000 | -13.550 | -32.286 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-APR-04:03 | 0.00 | 0.00 | 0.00 | -45928.02 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 41310.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-APR-04:03 | 0.00 | 0.00 | 0.00 | -34959.18 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 32305.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 15-MAY-04:03 | 0.00 | 0.00 | 0.00 | -39711.89 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 37058.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -17016.64 | 0.00 | 0.00 | 22.84 | 36.00 | 478.42 | 4516.59 | 0.00 | 131.93 | 11830.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:51 | 0.00 | 0.00 | 0.00 | -13935.44 | 0.00 | 0.00 | 13.17 | 22.79 | 302.86 | 7077.84 | 0.00 | 56.60 | 6462.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:01 | 0.00 | 0.00 | 0.00 | -18969.89 | 0.00 | 0.00 | 20.76 | 36.00 | 478.41 | 10444.40 | 0.00 | 15.69 | 7974.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -15609.64 | 0.00 | 0.00 | 9.89 | 22.79 | 302.86 | 7867.05 | 0.00 | 81.32 | 7325.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 29-MAY-18:21 | 0.00 | 0.00 | 0.00 | -13629.50 | 0.00 | 0.00 | 0.00 | 52.66 | 386.10 | 2384.42 | 0.00 | 56.58 | 10749.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:01 | 0.00 | 0.00 | 0.00 | -11644.58 | 0.00 | 0.00 | 13.92 | 22.79 | 302.86 | 8462.56 | 0.00 | 181.40 | 2661.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 12-JUN-17:00 | 0.00 | 0.00 | 0.00 | -16261.99 | 0.00 | 0.00 | 138.48 | 359.99 | 797.35 | 3714.03 | 0.00 | 16260.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5008.83 |
PERIMETER_BOT_ZN_4 | 11-JUN-16:21 | 0.00 | 0.00 | 0.00 | -12384.29 | 0.00 | 0.00 | 12.57 | 22.79 | 302.86 | 8423.69 | 0.00 | 45.87 | 3576.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-18:21 | 0.00 | 0.00 | 0.00 | -14387.14 | 0.00 | 0.00 | 0.00 | 52.66 | 386.10 | 2327.43 | 0.00 | 86.03 | 11534.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-07:42 | 0.00 | 0.00 | 0.00 | -12503.71 | 0.00 | 0.00 | 14.56 | 22.79 | 302.86 | 7979.82 | 0.00 | 144.24 | 4039.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:51 | 0.00 | 0.00 | 0.00 | -15549.78 | 0.00 | 0.00 | 21.04 | 36.00 | 478.41 | 11336.20 | 0.00 | 76.28 | 3601.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 29-MAY-16:21 | 0.00 | 0.00 | 0.00 | -13627.22 | 0.00 | 0.00 | 11.08 | 22.79 | 302.86 | 8496.87 | 0.00 | 114.02 | 4679.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-14:10 | 0.00 | -17342.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 17177.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUN-06:15 | 0.00 | -8983.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 | 8903.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:09 | 0.00 | -9073.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 | 8985.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-MAY-04:02 | 0.00 | 10103.77 | 0.00 | -236766.19 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 417.08 | 0.00 | 995.78 | 209848.69 | 0.00 | -5.60 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:01 | 0.00 | 0.00 | 19149.89 | 0.00 | 0.00 | 0.00 | 913.83 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25237.66 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 22814.16 | 0.00 | 0.00 | 0.00 | 498.29 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27054.34 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 10253.44 | 0.00 | 0.00 | 0.00 | 111.78 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1847.80 | 0.00 | 0.00 | -9306.24 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 6582.18 | 0.00 | 0.00 | 0.00 | 70.85 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1233.64 | 0.00 | 0.00 | -5918.76 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 10022.37 | 0.00 | 0.00 | 0.00 | 110.61 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1910.34 | 0.00 | 0.00 | -9011.45 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 6487.66 | 0.00 | 0.00 | 0.00 | 70.78 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1239.87 | 0.00 | 0.00 | -5817.93 |
PERIMETER_BOT_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 5885.92 | 0.00 | 0.00 | 0.00 | 98.61 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2610.31 | 0.00 | -5.53 | -4157.53 |
PERIMETER_BOT_ZN_2 | 04-JAN-07:03 | 0.00 | 0.00 | 3815.81 | 0.00 | 0.00 | 0.00 | 122.37 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1767.88 | 0.00 | 0.00 | -2860.79 |
PERIMETER_BOT_ZN_1 | 03-JAN-07:10 | 0.00 | 0.00 | 6989.54 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 8726.36 | 0.00 | -2710.66 | 0.00 | -14289.24 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JAN-07:03 | 0.00 | 0.00 | 3783.60 | 0.00 | 0.00 | 0.00 | 122.37 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1771.48 | 0.00 | 0.00 | -2824.95 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7326.54 | 0.00 | 0.00 | 0.00 | 104.36 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2174.04 | 0.00 | 0.00 | -6045.68 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 4620.76 | 0.00 | 0.00 | 0.00 | 66.28 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1448.28 | 0.00 | 0.00 | -3738.12 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 7108.12 | 0.00 | 0.00 | 0.00 | 103.03 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2236.75 | 0.00 | 0.00 | -5763.22 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 4542.54 | 0.00 | 0.00 | 0.00 | 66.18 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1454.61 | 0.00 | 0.00 | -3653.46 |
TOPFLOOR_PLENUM | 02-JAN-06:16 | 12207.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12207.45 |
MIDFLOOR_PLENUM | 24-DEC-13:53 | 4556.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4616.88 |
FIRSTFLOOR_PLENUM | 30-AUG-04:02 | 4663.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4663.13 |
Total Facility | 02-JAN-07:01 | 6683.63 | 6260.33 | 104863.71 | -6260.33 | 0.00 | 0.00 | 4552.86 | 10880.98 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22665.17 | 0.00 | -16413.32 | -109001.49 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9988 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6515 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4450 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0609 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.1817 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9994 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4131 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7225 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4076 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0909 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5287 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0452 | 3.0452 | 0.8070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3253 | 2.3253 | 0.7836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6336 | 2.6336 | 0.8191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9787 | 0.9787 | 0.1957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7447 | 0.7447 | 0.1489 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9940 | 0.9940 | 0.1988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8306 | 0.8306 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8043 | 0.8043 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6502 | 0.6502 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8182 | 0.8182 | 0.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6809 | 0.6809 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8390 | 0.8390 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6902 | 0.6902 | 0.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8558 | 0.8558 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7347 | 0.7347 | 0.1469 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9988 | 5.6515 | 5.9988 | 1.4131 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4450 | 5.0609 | 5.4450 | 1.4076 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.1817 | 6.0669 | 6.1817 | 1.5287 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5226 | 1.5226 | 0.8070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1626 | 1.1626 | 0.7836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3168 | 1.3168 | 0.8191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4894 | 0.4894 | 0.1957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3723 | 0.3723 | 0.1489 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4970 | 0.4970 | 0.1988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4153 | 0.4153 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4021 | 0.4021 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3251 | 0.3251 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4091 | 0.4091 | 0.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3404 | 0.3404 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4195 | 0.4195 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3451 | 0.3451 | 0.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4279 | 0.4279 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3674 | 0.3674 | 0.1469 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9994 | 1.4131 | 1.4131 | 1.4131 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7225 | 1.4076 | 1.4076 | 1.4076 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0909 | 1.5287 | 1.5287 | 1.5287 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 41.50 |
Number of hours cooling loads not met | 523.17 |
Number of hours not met | 564.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 6.76 | 95048.95 | 1.72 | 15545.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 739.21 | 116350.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.77 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.64 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 151.60 | 27823.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.69 | 9695.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1966.32 |
Natural Gas | 0.00 | 114.40 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2080.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.37 |
Space Heating | 1.36 |
Space Cooling | 148.37 |
Fans (All) | 30.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 394.67 |
Subtotal | 394.67 |
Natural Gas [MJ/m2] | |
Space Heating | 0.34 |
Service Water Heating | 22.62 |
Miscellaneous (All) | 22.96 |
Subtotal | 22.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.46 |
Space Heating | 0.41 |
Space Cooling | 35.53 |
Fans (All) | 7.29 |
Service Water Heating | 5.42 |
Receptacle Equipment | 33.90 |
Miscellaneous | 3.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8302.17 | 457.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8718.33 | 41.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8151.17 | 608.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8088.33 | 671.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8060.17 | 699.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8010.33 | 749.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8246.83 | 513.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8028.67 | 731.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7899.50 | 860.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7903.83 | 856.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8124.00 | 636.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8073.50 | 686.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8019.17 | 740.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7935.33 | 824.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8132.33 | 627.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8542.50 | 217.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8628.17 | 131.83 | 0.00 | 0.00 | 0.00 |
Min | 7899.50 | 41.67 | 0.00 | 0.00 | 0.00 |
Max | 8718.33 | 860.50 | 0.00 | 0.00 | 0.00 |
Average | 8198.62 | 561.38 | 0.00 | 0.00 | 0.00 |
Sum | 147575.17 | 10104.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128187.33 | 116.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128292.33 | 11.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128283.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24656.67 | 252.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128292.33 | 252.33 | 0.00 | 0.00 | 0.00 |
Average | 34121.02 | 22.31 | 0.00 | 0.00 | 0.00 |
Sum | 614178.33 | 401.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7365.33 | 1394.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7484.17 | 1275.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7469.00 | 1291.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7083.33 | 1676.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7069.83 | 1690.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7032.00 | 1728.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7082.83 | 1677.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7105.00 | 1655.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7037.50 | 1722.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6239.67 | 2520.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7001.33 | 1758.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6989.83 | 1770.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6990.83 | 1769.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6927.17 | 1832.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6977.17 | 1782.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 5209.83 | 3550.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5979.50 | 2780.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6346.33 | 2413.67 | 0.00 | 0.00 | 0.00 |
Min | 5209.83 | 1275.83 | 0.00 | 0.00 | 0.00 |
Max | 7484.17 | 3550.17 | 0.00 | 0.00 | 0.00 |
Average | 6855.04 | 1904.96 | 0.00 | 0.00 | 0.00 |
Sum | 123390.67 | 34289.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127540.00 | 764.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127662.83 | 641.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127581.50 | 722.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24848.00 | 61.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14015.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24849.33 | 59.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24844.33 | 64.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20614.00 | 4295.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24829.67 | 79.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24830.50 | 78.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127662.83 | 4295.00 | 0.00 | 0.00 | 0.00 |
Average | 33767.41 | 375.93 | 0.00 | 0.00 | 0.00 |
Sum | 607813.33 | 6766.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172501E+11 | 19828.46 | 27-JAN-09:00 | 12.50 | 10.62 | 0.198448E+10 | 2606.63 | 13-JAN-14:09 | 12.50 | 10.62 |
February | 0.189328E+11 | 31275.75 | 23-FEB-07:02 | 15.45 | 14.06 | 0.180659E+10 | 2606.65 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.264015E+11 | 43887.14 | 13-MAR-05:12 | 20.73 | 15.50 | 0.216003E+10 | 2606.67 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.276017E+11 | 45938.27 | 18-APR-04:03 | 24.53 | 18.88 | 0.191879E+10 | 2606.66 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.315756E+11 | 45270.33 | 03-MAY-04:03 | 25.78 | 20.40 | 0.207730E+10 | 2606.71 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.312252E+11 | 44252.15 | 20-JUN-04:03 | 28.05 | 23.71 | 0.207032E+10 | 2606.67 | 01-JUN-13:09 | 28.05 | 23.71 |
July | 0.304561E+11 | 42665.57 | 13-JUL-04:03 | 27.87 | 26.38 | 0.192428E+10 | 2606.64 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.316416E+11 | 44637.94 | 22-AUG-04:03 | 25.78 | 25.00 | 0.216054E+10 | 2606.65 | 21-AUG-13:30 | 25.78 | 25.00 |
September | 0.286029E+11 | 44760.49 | 29-SEP-04:03 | 24.00 | 21.14 | 0.191931E+10 | 2606.62 | 11-SEP-13:09 | 24.00 | 21.14 |
October | 0.282207E+11 | 44880.89 | 11-OCT-04:03 | 24.15 | 20.56 | 0.199607E+10 | 2606.68 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.242840E+11 | 41334.23 | 13-NOV-07:02 | 16.07 | 12.01 | 0.197439E+10 | 2606.69 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.195429E+11 | 22394.43 | 01-DEC-07:03 | 12.92 | 9.54 | 0.192032E+10 | 2606.65 | 18-DEC-10:39 | 21.03 | 14.24 |
Annual Sum or Average | 0.315735E+12 | 0.239124E+11 | ||||||||
Minimum of Months | 0.172501E+11 | 19828.46 | 12.50 | 9.54 | 0.180659E+10 | 2606.62 | 12.50 | 10.62 | ||
Maximum of Months | 0.316416E+11 | 45938.27 | 28.05 | 26.38 | 0.216054E+10 | 2606.71 | 39.90 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134698E+10 | 4167.23 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.247712E+10 | 8305.25 | 22-FEB-14:30 | 27.05 | 16.26 | 0.00 | 0.00 | 01-FEB-00:10 | 27.05 | 16.26 |
March | 0.604451E+10 | 13011.12 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.101932E+11 | 15313.40 | 26-APR-14:50 | 39.22 | 22.03 | 0.00 | 0.00 | 01-APR-00:10 | 39.22 | 22.03 |
May | 0.130346E+11 | 17108.15 | 01-MAY-14:20 | 43.93 | 22.01 | 0.00 | 0.00 | 01-MAY-00:10 | 43.93 | 22.01 |
June | 0.128969E+11 | 17342.07 | 12-JUN-14:10 | 43.95 | 22.32 | 0.00 | 0.00 | 01-JUN-00:10 | 43.95 | 22.32 |
July | 0.104265E+11 | 15619.73 | 10-JUL-13:50 | 39.20 | 26.60 | 0.00 | 0.00 | 01-JUL-00:10 | 39.20 | 26.60 |
August | 0.960139E+10 | 14227.30 | 07-AUG-14:20 | 37.23 | 26.37 | 0.00 | 0.00 | 01-AUG-00:10 | 37.23 | 26.37 |
September | 0.777702E+10 | 12951.62 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.697301E+10 | 13043.37 | 02-OCT-14:20 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.397961E+10 | 9059.07 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.159972E+10 | 5510.37 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.863506E+11 | 0.00 | ||||||||
Minimum of Months | 0.134698E+10 | 4167.23 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.130346E+11 | 17342.07 | 43.95 | 26.60 | 0.00 | 0.00 | 43.95 | 26.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370041E+09 | 2482.37 | 06-JAN-07:01 | 5.62 | 5.52 | 0.00 | 0.00 | 01-JAN-00:10 | 5.62 | 5.52 |
February | 0.966492E+09 | 2706.75 | 22-FEB-16:00 | 26.50 | 15.96 | 0.00 | 0.00 | 01-FEB-00:10 | 26.50 | 15.96 |
March | 0.307033E+10 | 5372.39 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.529966E+10 | 6574.43 | 17-APR-15:10 | 34.65 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 34.65 | 21.60 |
May | 0.695469E+10 | 7316.57 | 30-MAY-12:03 | 37.90 | 23.62 | 0.00 | 0.00 | 01-MAY-00:10 | 37.90 | 23.62 |
June | 0.674210E+10 | 8983.63 | 12-JUN-06:15 | 35.03 | 19.50 | 0.00 | 0.00 | 01-JUN-00:10 | 35.03 | 19.50 |
July | 0.606951E+10 | 7257.42 | 05-JUL-12:03 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.582982E+10 | 6683.23 | 07-AUG-15:20 | 37.23 | 26.61 | 0.00 | 0.00 | 01-AUG-00:10 | 37.23 | 26.61 |
September | 0.487279E+10 | 6307.57 | 25-SEP-15:50 | 34.68 | 23.97 | 0.00 | 0.00 | 01-SEP-00:10 | 34.68 | 23.97 |
October | 0.400388E+10 | 6283.63 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.196535E+10 | 3610.30 | 13-NOV-15:50 | 27.70 | 16.51 | 0.00 | 0.00 | 01-NOV-00:10 | 27.70 | 16.51 |
December | 0.548925E+09 | 2688.99 | 21-DEC-07:01 | 5.68 | 4.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.68 | 4.75 |
Annual Sum or Average | 0.466936E+11 | 0.00 | ||||||||
Minimum of Months | 0.370041E+09 | 2482.37 | 5.62 | 4.75 | 0.00 | 0.00 | 5.62 | 4.75 | ||
Maximum of Months | 0.695469E+10 | 8983.63 | 37.90 | 26.61 | 0.00 | 0.00 | 37.90 | 26.61 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770554E+09 | 2753.18 | 05-JAN-07:01 | 4.93 | 4.82 | 0.00 | 0.00 | 01-JAN-00:10 | 4.93 | 4.82 |
February | 0.162452E+10 | 3551.70 | 22-FEB-16:10 | 26.37 | 15.92 | 0.00 | 0.00 | 01-FEB-00:10 | 26.37 | 15.92 |
March | 0.371631E+10 | 5447.48 | 28-MAR-17:08 | 34.60 | 18.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.60 | 18.91 |
April | 0.542255E+10 | 7483.64 | 27-APR-12:10 | 38.00 | 21.24 | 0.00 | 0.00 | 01-APR-00:10 | 38.00 | 21.24 |
May | 0.687567E+10 | 9074.21 | 30-MAY-12:09 | 37.90 | 23.62 | 0.00 | 0.00 | 01-MAY-00:10 | 37.90 | 23.62 |
June | 0.681736E+10 | 8489.28 | 13-JUN-12:08 | 37.92 | 26.46 | 0.00 | 0.00 | 01-JUN-00:10 | 37.92 | 26.46 |
July | 0.643524E+10 | 8779.70 | 05-JUL-12:10 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.648820E+10 | 7689.84 | 28-AUG-12:08 | 33.58 | 28.63 | 0.00 | 0.00 | 01-AUG-00:10 | 33.58 | 28.63 |
September | 0.558989E+10 | 6738.61 | 25-SEP-17:07 | 33.63 | 24.23 | 0.00 | 0.00 | 01-SEP-00:10 | 33.63 | 24.23 |
October | 0.490864E+10 | 6173.37 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.304094E+10 | 4602.88 | 13-NOV-16:30 | 27.00 | 16.63 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 16.63 |
December | 0.121714E+10 | 2824.08 | 01-DEC-16:10 | 22.12 | 13.82 | 0.00 | 0.00 | 01-DEC-00:10 | 22.12 | 13.82 |
Annual Sum or Average | 0.529070E+11 | 0.00 | ||||||||
Minimum of Months | 0.770554E+09 | 2753.18 | 4.93 | 4.82 | 0.00 | 0.00 | 4.93 | 4.82 | ||
Maximum of Months | 0.687567E+10 | 9074.21 | 38.00 | 28.63 | 0.00 | 0.00 | 38.00 | 28.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102799E+11 | 12017.03 | 26-JAN-17:00 | 18.60 | 12.70 | 0.188481E+10 | 2606.60 | 13-JAN-14:09 | 18.60 | 12.70 |
February | 0.118422E+11 | 14901.73 | 23-FEB-17:00 | 23.60 | 14.87 | 0.177879E+10 | 2606.64 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.181129E+11 | 33781.87 | 13-MAR-05:12 | 20.73 | 15.50 | 0.215212E+10 | 2606.67 | 30-MAR-09:09 | 24.92 | 18.16 |
April | 0.208547E+11 | 34965.99 | 18-APR-04:03 | 24.53 | 18.88 | 0.191594E+10 | 2606.66 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.247711E+11 | 34777.49 | 15-MAY-04:03 | 24.27 | 18.74 | 0.207525E+10 | 2606.60 | 01-MAY-09:20 | 24.27 | 18.74 |
June | 0.242419E+11 | 33883.09 | 20-JUN-04:03 | 28.05 | 23.71 | 0.206834E+10 | 2606.62 | 05-JUN-13:09 | 28.05 | 23.71 |
July | 0.233249E+11 | 34208.73 | 11-JUL-04:03 | 26.73 | 24.05 | 0.192259E+10 | 2606.57 | 05-JUL-09:20 | 26.73 | 24.05 |
August | 0.233479E+11 | 33081.41 | 26-AUG-05:03 | 26.08 | 25.65 | 0.215855E+10 | 2606.57 | 21-AUG-13:39 | 26.08 | 25.65 |
September | 0.206691E+11 | 34777.96 | 26-SEP-04:03 | 25.35 | 21.31 | 0.191714E+10 | 2606.57 | 11-SEP-13:09 | 25.35 | 21.31 |
October | 0.196477E+11 | 33767.58 | 03-OCT-05:12 | 23.03 | 17.52 | 0.199170E+10 | 2606.67 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.154442E+11 | 18473.38 | 13-NOV-07:02 | 16.07 | 12.01 | 0.196220E+10 | 2606.68 | 06-NOV-10:09 | 16.07 | 12.01 |
December | 0.114729E+11 | 13609.88 | 01-DEC-17:00 | 21.20 | 14.26 | 0.187604E+10 | 2606.61 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.224010E+12 | 0.237035E+11 | ||||||||
Minimum of Months | 0.102799E+11 | 12017.03 | 16.07 | 12.01 | 0.177879E+10 | 2606.57 | 16.07 | 12.01 | ||
Maximum of Months | 0.247711E+11 | 34965.99 | 28.05 | 25.65 | 0.215855E+10 | 2606.68 | 28.05 | 25.65 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.920918E+10 | 11516.02 | 26-JAN-16:30 | 19.40 | 12.94 | 0.176396E+10 | 2606.59 | 12-JAN-14:20 | 19.40 | 12.94 |
February | 0.110253E+11 | 15729.25 | 23-FEB-15:00 | 25.80 | 14.10 | 0.171742E+10 | 2606.63 | 15-FEB-14:09 | 25.80 | 14.10 |
March | 0.180238E+11 | 20635.13 | 13-MAR-15:00 | 32.90 | 18.68 | 0.213665E+10 | 2606.69 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.225077E+11 | 39601.77 | 17-APR-04:02 | 24.68 | 19.16 | 0.191500E+10 | 2606.70 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.275684E+11 | 39709.44 | 15-MAY-04:03 | 24.27 | 18.74 | 0.207630E+10 | 2606.67 | 01-MAY-09:09 | 24.27 | 18.74 |
June | 0.272664E+11 | 38699.91 | 19-JUN-04:03 | 27.82 | 23.26 | 0.206936E+10 | 2606.62 | 05-JUN-13:09 | 27.82 | 23.26 |
July | 0.257469E+11 | 34775.76 | 03-JUL-06:03 | 29.28 | 24.42 | 0.192376E+10 | 2606.57 | 07-JUL-13:09 | 39.88 | 24.75 |
August | 0.251837E+11 | 39563.64 | 21-AUG-04:02 | 25.67 | 25.19 | 0.215911E+10 | 2606.57 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.215436E+11 | 38950.13 | 25-SEP-04:02 | 26.32 | 23.72 | 0.191675E+10 | 2606.67 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.194536E+11 | 37424.87 | 04-OCT-05:03 | 25.07 | 21.35 | 0.198416E+10 | 2606.70 | 10-OCT-09:30 | 26.65 | 20.45 |
November | 0.142094E+11 | 17158.26 | 09-NOV-15:00 | 29.20 | 17.71 | 0.192780E+10 | 2606.66 | 09-NOV-10:50 | 29.20 | 17.71 |
December | 0.101802E+11 | 12998.38 | 01-DEC-16:20 | 21.93 | 13.92 | 0.176965E+10 | 2606.62 | 28-DEC-14:09 | 24.58 | 15.31 |
Annual Sum or Average | 0.231918E+12 | 0.233599E+11 | ||||||||
Minimum of Months | 0.920918E+10 | 11516.02 | 19.40 | 12.94 | 0.171742E+10 | 2606.57 | 19.40 | 12.94 | ||
Maximum of Months | 0.275684E+11 | 39709.44 | 32.90 | 25.19 | 0.215911E+10 | 2606.70 | 39.88 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160628E+10 | 2422.45 | 26-JAN-15:00 | 21.60 | 13.66 | 0.344830E+09 | 549.48 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.230463E+10 | 4341.71 | 23-FEB-14:40 | 26.00 | 14.03 | 0.342486E+09 | 549.49 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.463360E+10 | 6689.86 | 29-MAR-15:20 | 33.03 | 18.92 | 0.441922E+09 | 549.51 | 30-MAR-09:39 | 26.17 | 18.43 |
April | 0.721661E+10 | 16165.68 | 16-APR-15:22 | 39.50 | 22.49 | 0.403650E+09 | 549.51 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.990156E+10 | 16664.75 | 28-MAY-16:31 | 41.90 | 19.53 | 0.438852E+09 | 549.51 | 01-MAY-09:09 | 41.90 | 19.53 |
June | 0.100876E+11 | 17019.05 | 11-JUN-16:31 | 43.20 | 23.09 | 0.437396E+09 | 549.49 | 05-JUN-13:09 | 43.20 | 23.09 |
July | 0.913575E+10 | 16324.40 | 04-JUL-16:32 | 39.83 | 24.41 | 0.406941E+09 | 549.48 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.851406E+10 | 15593.99 | 06-AUG-16:02 | 36.25 | 26.27 | 0.456033E+09 | 549.48 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.670885E+10 | 13447.30 | 18-SEP-04:02 | 27.28 | 24.67 | 0.404592E+09 | 549.50 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.530126E+10 | 15193.89 | 09-OCT-14:21 | 32.75 | 19.69 | 0.415068E+09 | 549.51 | 10-OCT-09:30 | 26.65 | 20.45 |
November | 0.316706E+10 | 4781.64 | 09-NOV-14:30 | 29.30 | 17.79 | 0.392013E+09 | 549.50 | 09-NOV-10:50 | 29.30 | 17.79 |
December | 0.188250E+10 | 2450.68 | 01-DEC-15:20 | 23.03 | 13.49 | 0.345317E+09 | 549.49 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.704597E+11 | 0.482910E+10 | ||||||||
Minimum of Months | 0.160628E+10 | 2422.45 | 21.60 | 13.49 | 0.342486E+09 | 549.48 | 21.60 | 13.66 | ||
Maximum of Months | 0.100876E+11 | 17019.05 | 43.20 | 26.27 | 0.456033E+09 | 549.51 | 43.20 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144007E+10 | 2068.53 | 26-JAN-14:10 | 22.35 | 13.84 | 0.231254E+09 | 347.87 | 12-JAN-14:00 | 22.35 | 13.84 |
February | 0.210962E+10 | 4124.55 | 23-FEB-10:40 | 22.80 | 14.32 | 0.227198E+09 | 347.88 | 24-FEB-10:00 | 22.30 | 15.46 |
March | 0.432576E+10 | 11484.81 | 12-MAR-10:32 | 27.43 | 17.74 | 0.284085E+09 | 347.89 | 28-MAR-09:20 | 26.40 | 17.57 |
April | 0.659789E+10 | 13215.17 | 16-APR-10:02 | 35.32 | 21.70 | 0.256021E+09 | 348.07 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.827627E+10 | 13384.16 | 29-MAY-09:12 | 34.40 | 21.35 | 0.277963E+09 | 348.03 | 03-MAY-09:00 | 34.40 | 21.35 |
June | 0.775682E+10 | 13944.37 | 11-JUN-09:51 | 36.60 | 25.06 | 0.276920E+09 | 347.97 | 12-JUN-09:00 | 40.00 | 22.14 |
July | 0.670853E+10 | 12800.33 | 04-JUL-09:52 | 35.20 | 25.12 | 0.257653E+09 | 347.94 | 10-JUL-09:00 | 34.40 | 26.59 |
August | 0.621885E+10 | 11904.99 | 06-AUG-08:43 | 30.82 | 24.34 | 0.288683E+09 | 347.87 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.528736E+10 | 8550.09 | 18-SEP-04:02 | 27.28 | 24.67 | 0.256096E+09 | 347.88 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.465231E+10 | 12573.79 | 09-OCT-11:42 | 31.15 | 20.28 | 0.263920E+09 | 347.89 | 17-OCT-09:30 | 27.00 | 18.48 |
November | 0.286562E+10 | 4255.23 | 09-NOV-10:30 | 25.75 | 18.10 | 0.255804E+09 | 347.88 | 09-NOV-10:50 | 26.58 | 18.19 |
December | 0.160964E+10 | 2397.08 | 01-DEC-10:40 | 19.57 | 11.89 | 0.231940E+09 | 347.87 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.578487E+11 | 0.310754E+10 | ||||||||
Minimum of Months | 0.144007E+10 | 2068.53 | 19.57 | 11.89 | 0.227198E+09 | 347.87 | 22.30 | 13.84 | ||
Maximum of Months | 0.827627E+10 | 13944.37 | 36.60 | 25.12 | 0.288683E+09 | 348.07 | 40.00 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370701E+10 | 8467.09 | 12-JAN-14:10 | 23.35 | 14.02 | 0.385978E+09 | 549.50 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.465782E+10 | 17677.72 | 20-FEB-14:22 | 26.35 | 13.75 | 0.360315E+09 | 549.69 | 22-FEB-14:20 | 27.03 | 16.28 |
March | 0.756966E+10 | 17539.22 | 26-MAR-14:12 | 30.27 | 16.70 | 0.446890E+09 | 549.80 | 09-MAR-14:50 | 30.27 | 16.70 |
April | 0.904779E+10 | 17147.19 | 16-APR-14:42 | 39.67 | 22.23 | 0.404025E+09 | 549.71 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.103165E+11 | 17030.45 | 28-MAY-15:11 | 42.23 | 19.17 | 0.438856E+09 | 549.72 | 03-MAY-13:00 | 42.23 | 19.17 |
June | 0.100291E+11 | 17201.95 | 11-JUN-15:51 | 43.40 | 23.22 | 0.437361E+09 | 549.63 | 12-JUN-13:50 | 43.80 | 22.37 |
July | 0.920921E+10 | 16528.09 | 04-JUL-16:32 | 39.83 | 24.41 | 0.406925E+09 | 549.48 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.900667E+10 | 16503.72 | 06-AUG-14:02 | 35.97 | 26.35 | 0.456089E+09 | 549.63 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.831256E+10 | 16952.78 | 24-SEP-13:22 | 34.85 | 24.63 | 0.404860E+09 | 549.65 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.924725E+10 | 18971.93 | 09-OCT-13:01 | 32.37 | 19.90 | 0.417994E+09 | 564.08 | 02-OCT-13:39 | 32.37 | 19.90 |
November | 0.745840E+10 | 18508.38 | 05-NOV-13:22 | 29.15 | 17.16 | 0.406524E+09 | 549.79 | 06-NOV-14:00 | 28.40 | 18.16 |
December | 0.434511E+10 | 16681.46 | 03-DEC-13:23 | 24.25 | 14.17 | 0.381368E+09 | 549.51 | 01-DEC-14:09 | 24.25 | 14.17 |
Annual Sum or Average | 0.929070E+11 | 0.494718E+10 | ||||||||
Minimum of Months | 0.370701E+10 | 8467.09 | 23.35 | 13.75 | 0.360315E+09 | 549.48 | 23.00 | 13.41 | ||
Maximum of Months | 0.103165E+11 | 18971.93 | 43.40 | 26.35 | 0.456089E+09 | 564.08 | 43.80 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153887E+10 | 3497.26 | 31-JAN-16:10 | 20.95 | 11.21 | 0.222520E+09 | 347.84 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.220844E+10 | 6719.04 | 20-FEB-17:03 | 24.33 | 14.52 | 0.214837E+09 | 347.85 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.436563E+10 | 14307.02 | 26-MAR-16:52 | 29.20 | 15.98 | 0.277402E+09 | 347.86 | 30-MAR-09:39 | 26.17 | 18.43 |
April | 0.653160E+10 | 14805.22 | 23-APR-15:22 | 31.80 | 19.70 | 0.255183E+09 | 347.86 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.811563E+10 | 15469.77 | 28-MAY-16:31 | 41.90 | 19.53 | 0.277760E+09 | 347.86 | 01-MAY-09:09 | 41.90 | 19.53 |
June | 0.799885E+10 | 15612.49 | 11-JUN-16:31 | 43.20 | 23.09 | 0.276835E+09 | 347.85 | 07-JUN-09:09 | 43.20 | 23.09 |
July | 0.667680E+10 | 14651.24 | 09-JUL-15:11 | 36.33 | 27.38 | 0.257480E+09 | 347.84 | 05-JUL-13:00 | 36.33 | 27.38 |
August | 0.620313E+10 | 14063.12 | 06-AUG-16:42 | 36.05 | 26.41 | 0.288524E+09 | 347.84 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.532266E+10 | 14012.28 | 24-SEP-15:22 | 34.95 | 25.05 | 0.255810E+09 | 347.85 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.464235E+10 | 14637.66 | 09-OCT-14:21 | 32.75 | 19.69 | 0.261394E+09 | 347.86 | 10-OCT-09:30 | 26.65 | 20.45 |
November | 0.309187E+10 | 12375.37 | 05-NOV-15:22 | 28.45 | 17.59 | 0.245735E+09 | 347.85 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.177660E+10 | 3941.54 | 01-DEC-15:30 | 22.85 | 13.56 | 0.220401E+09 | 347.85 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.584724E+11 | 0.305388E+10 | ||||||||
Minimum of Months | 0.153887E+10 | 3497.26 | 20.95 | 11.21 | 0.214837E+09 | 347.84 | 20.95 | 11.21 | ||
Maximum of Months | 0.811563E+10 | 15612.49 | 43.20 | 27.38 | 0.288524E+09 | 347.86 | 43.20 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185047E+10 | 2141.00 | 26-JAN-14:10 | 22.35 | 13.84 | 0.366626E+09 | 549.48 | 13-JAN-14:00 | 22.35 | 13.84 |
February | 0.214283E+10 | 3467.65 | 24-FEB-15:00 | 26.40 | 17.38 | 0.355577E+09 | 549.49 | 24-FEB-10:30 | 26.40 | 17.38 |
March | 0.367854E+10 | 5089.59 | 29-MAR-15:20 | 33.03 | 18.92 | 0.447257E+09 | 549.50 | 30-MAR-09:09 | 24.92 | 18.16 |
April | 0.564851E+10 | 7641.66 | 17-APR-04:02 | 24.68 | 19.16 | 0.403618E+09 | 549.50 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.828754E+10 | 13629.20 | 29-MAY-18:21 | 39.50 | 21.15 | 0.438594E+09 | 549.52 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.899755E+10 | 13609.55 | 11-JUN-16:21 | 43.25 | 23.12 | 0.437282E+09 | 549.50 | 01-JUN-13:09 | 43.25 | 23.12 |
July | 0.895479E+10 | 13553.30 | 04-JUL-17:01 | 39.95 | 24.24 | 0.406988E+09 | 549.49 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.895396E+10 | 13243.54 | 27-AUG-16:52 | 34.30 | 29.01 | 0.456279E+09 | 549.50 | 21-AUG-13:30 | 34.30 | 29.01 |
September | 0.736195E+10 | 11118.19 | 24-SEP-15:11 | 35.00 | 24.98 | 0.405149E+09 | 549.49 | 11-SEP-13:09 | 35.00 | 24.98 |
October | 0.579808E+10 | 13105.58 | 01-OCT-14:41 | 35.98 | 19.91 | 0.419920E+09 | 549.50 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.342599E+10 | 4517.63 | 09-NOV-14:10 | 29.37 | 17.83 | 0.409935E+09 | 549.50 | 06-NOV-10:09 | 29.37 | 17.83 |
December | 0.215851E+10 | 2645.79 | 01-DEC-15:00 | 23.40 | 13.35 | 0.376449E+09 | 549.49 | 29-DEC-14:09 | 19.75 | 14.80 |
Annual Sum or Average | 0.672587E+11 | 0.492368E+10 | ||||||||
Minimum of Months | 0.185047E+10 | 2141.00 | 22.35 | 13.35 | 0.355577E+09 | 549.48 | 19.75 | 13.84 | ||
Maximum of Months | 0.899755E+10 | 13629.20 | 43.25 | 29.01 | 0.456279E+09 | 549.52 | 43.25 | 29.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160986E+10 | 2220.65 | 26-JAN-11:00 | 19.70 | 13.19 | 0.247048E+09 | 347.87 | 13-JAN-14:09 | 19.70 | 13.19 |
February | 0.204935E+10 | 3783.86 | 22-FEB-10:50 | 23.10 | 14.47 | 0.233752E+09 | 347.88 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.370694E+10 | 8070.40 | 12-MAR-10:32 | 27.43 | 17.74 | 0.286065E+09 | 347.88 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.553049E+10 | 10704.89 | 30-APR-10:12 | 32.30 | 16.64 | 0.256132E+09 | 348.03 | 28-APR-09:50 | 32.30 | 16.64 |
May | 0.727231E+10 | 11643.46 | 29-MAY-09:01 | 34.05 | 21.14 | 0.277943E+09 | 347.99 | 12-MAY-09:30 | 34.05 | 21.14 |
June | 0.706854E+10 | 11360.49 | 11-JUN-10:21 | 37.75 | 25.19 | 0.276935E+09 | 348.03 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.663290E+10 | 11244.64 | 04-JUL-09:41 | 34.98 | 25.17 | 0.257738E+09 | 347.87 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.654456E+10 | 10793.57 | 06-AUG-12:23 | 34.90 | 26.29 | 0.288916E+09 | 347.87 | 21-AUG-13:30 | 29.30 | 27.60 |
September | 0.577503E+10 | 10956.39 | 24-SEP-11:52 | 33.80 | 25.08 | 0.256565E+09 | 347.87 | 11-SEP-13:09 | 33.80 | 25.08 |
October | 0.509680E+10 | 11330.50 | 01-OCT-10:02 | 30.08 | 19.42 | 0.266346E+09 | 347.88 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.323787E+10 | 4415.26 | 13-NOV-10:30 | 23.45 | 14.94 | 0.261660E+09 | 347.88 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.191299E+10 | 2977.77 | 01-DEC-10:30 | 19.25 | 11.77 | 0.247993E+09 | 347.87 | 27-DEC-10:09 | 16.98 | 12.25 |
Annual Sum or Average | 0.564376E+11 | 0.315709E+10 | ||||||||
Minimum of Months | 0.160986E+10 | 2220.65 | 19.25 | 11.77 | 0.233752E+09 | 347.87 | 16.98 | 12.25 | ||
Maximum of Months | 0.727231E+10 | 11643.46 | 37.75 | 26.29 | 0.288916E+09 | 348.03 | 39.75 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305450E+10 | 7965.35 | 08-JAN-13:43 | 21.93 | 12.93 | 0.384260E+09 | 549.51 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.398652E+10 | 13977.49 | 20-FEB-12:32 | 25.43 | 13.32 | 0.361314E+09 | 549.65 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.706032E+10 | 14079.28 | 26-MAR-14:12 | 30.27 | 16.70 | 0.448710E+09 | 638.39 | 28-MAR-12:09 | 33.22 | 18.26 |
April | 0.946268E+10 | 14565.73 | 27-APR-16:50 | 39.30 | 18.95 | 0.410538E+09 | 725.58 | 27-APR-12:09 | 39.30 | 18.95 |
May | 0.120571E+11 | 15925.15 | 01-MAY-16:50 | 43.07 | 22.15 | 0.451570E+09 | 793.17 | 01-MAY-12:09 | 43.07 | 22.15 |
June | 0.123431E+11 | 16260.92 | 12-JUN-17:00 | 43.90 | 22.35 | 0.449569E+09 | 811.96 | 12-JUN-12:09 | 43.90 | 22.35 |
July | 0.114137E+11 | 14824.46 | 03-JUL-17:00 | 39.50 | 25.70 | 0.413311E+09 | 740.00 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.118710E+11 | 13978.79 | 07-AUG-16:50 | 36.68 | 26.89 | 0.461835E+09 | 684.83 | 07-AUG-12:09 | 36.68 | 26.89 |
September | 0.107348E+11 | 14387.78 | 24-SEP-11:52 | 33.80 | 25.08 | 0.412641E+09 | 703.53 | 29-SEP-12:09 | 35.52 | 22.70 |
October | 0.108884E+11 | 15600.17 | 01-OCT-13:21 | 35.55 | 19.91 | 0.431520E+09 | 731.24 | 02-OCT-12:09 | 35.70 | 21.30 |
November | 0.815975E+10 | 15251.13 | 12-NOV-13:12 | 27.87 | 16.14 | 0.413679E+09 | 608.50 | 09-NOV-13:09 | 27.87 | 16.14 |
December | 0.402730E+10 | 11411.71 | 03-DEC-11:43 | 22.38 | 14.19 | 0.386936E+09 | 549.70 | 01-DEC-14:00 | 22.38 | 14.19 |
Annual Sum or Average | 0.105059E+12 | 0.502588E+10 | ||||||||
Minimum of Months | 0.305450E+10 | 7965.35 | 21.93 | 12.93 | 0.361314E+09 | 549.51 | 22.38 | 13.41 | ||
Maximum of Months | 0.123431E+11 | 16260.92 | 43.90 | 26.89 | 0.461835E+09 | 811.96 | 43.90 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169774E+10 | 2895.59 | 31-JAN-16:30 | 20.65 | 11.16 | 0.236878E+09 | 347.84 | 13-JAN-14:09 | 20.65 | 11.16 |
February | 0.201831E+10 | 4465.31 | 20-FEB-16:33 | 24.93 | 14.44 | 0.225945E+09 | 347.85 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.361535E+10 | 11388.88 | 26-MAR-16:52 | 29.20 | 15.98 | 0.283592E+09 | 347.85 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.540803E+10 | 11789.13 | 30-APR-16:12 | 37.57 | 18.06 | 0.255977E+09 | 347.85 | 21-APR-09:09 | 37.57 | 18.06 |
May | 0.705429E+10 | 12377.16 | 29-MAY-18:21 | 39.50 | 21.15 | 0.277862E+09 | 347.87 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.726896E+10 | 12385.86 | 11-JUN-16:21 | 43.25 | 23.12 | 0.276956E+09 | 347.85 | 01-JUN-13:09 | 43.25 | 23.12 |
July | 0.655731E+10 | 12071.24 | 04-JUL-16:21 | 39.80 | 24.49 | 0.257678E+09 | 347.85 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.649840E+10 | 11555.88 | 06-AUG-16:22 | 36.15 | 26.34 | 0.288885E+09 | 347.85 | 21-AUG-13:30 | 29.30 | 27.60 |
September | 0.576996E+10 | 11715.32 | 24-SEP-15:51 | 34.80 | 25.26 | 0.256580E+09 | 347.85 | 11-SEP-13:09 | 34.80 | 25.26 |
October | 0.498311E+10 | 12260.03 | 01-OCT-14:41 | 35.98 | 19.91 | 0.266200E+09 | 347.86 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.324349E+10 | 10278.11 | 05-NOV-15:22 | 28.45 | 17.59 | 0.260070E+09 | 347.86 | 06-NOV-10:09 | 23.13 | 17.24 |
December | 0.199796E+10 | 3667.56 | 01-DEC-15:40 | 22.67 | 13.61 | 0.239705E+09 | 347.84 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.561129E+11 | 0.312633E+10 | ||||||||
Minimum of Months | 0.169774E+10 | 2895.59 | 20.65 | 11.16 | 0.225945E+09 | 347.84 | 20.65 | 11.16 | ||
Maximum of Months | 0.726896E+10 | 12385.86 | 43.25 | 26.34 | 0.288885E+09 | 347.87 | 43.25 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176502E+10 | 2497.61 | 26-JAN-14:40 | 21.90 | 13.73 | 0.363568E+09 | 549.48 | 25-JAN-14:00 | 21.90 | 13.73 |
February | 0.230619E+10 | 4110.46 | 23-FEB-14:30 | 26.10 | 14.00 | 0.358222E+09 | 549.49 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.444206E+10 | 6047.74 | 13-MAR-15:20 | 32.77 | 18.67 | 0.449707E+09 | 549.50 | 30-MAR-09:09 | 24.92 | 18.16 |
April | 0.662221E+10 | 13212.91 | 02-APR-16:41 | 33.57 | 20.57 | 0.404425E+09 | 549.50 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.896474E+10 | 14387.05 | 29-MAY-18:21 | 39.50 | 21.15 | 0.438938E+09 | 549.49 | 05-MAY-09:20 | 39.50 | 21.15 |
June | 0.909168E+10 | 13953.39 | 04-JUN-16:51 | 41.80 | 22.62 | 0.437406E+09 | 549.49 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.830225E+10 | 13779.13 | 02-JUL-09:12 | 34.77 | 25.77 | 0.406970E+09 | 549.49 | 05-JUL-09:20 | 35.67 | 25.11 |
August | 0.789156E+10 | 12299.50 | 06-AUG-16:02 | 36.25 | 26.27 | 0.456103E+09 | 549.48 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.636797E+10 | 10882.55 | 18-SEP-04:02 | 27.28 | 24.67 | 0.404853E+09 | 549.48 | 08-SEP-13:00 | 27.28 | 24.67 |
October | 0.514090E+10 | 9560.05 | 01-OCT-15:31 | 35.67 | 20.08 | 0.418764E+09 | 549.50 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.317381E+10 | 4454.30 | 09-NOV-14:10 | 29.37 | 17.83 | 0.405443E+09 | 549.50 | 06-NOV-10:09 | 29.37 | 17.83 |
December | 0.201479E+10 | 2559.66 | 01-DEC-15:00 | 23.40 | 13.35 | 0.367857E+09 | 549.49 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.660832E+11 | 0.491226E+10 | ||||||||
Minimum of Months | 0.176502E+10 | 2497.61 | 21.90 | 13.35 | 0.358222E+09 | 549.48 | 20.63 | 13.73 | ||
Maximum of Months | 0.909168E+10 | 14387.05 | 41.80 | 26.27 | 0.456103E+09 | 549.50 | 42.20 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157455E+10 | 2378.34 | 26-JAN-11:10 | 19.98 | 13.28 | 0.176243E+09 | 338.72 | 12-JAN-15:09 | 19.98 | 13.28 |
February | 0.217436E+10 | 4340.80 | 22-FEB-10:00 | 20.60 | 13.92 | 0.170593E+09 | 338.73 | 24-FEB-11:20 | 22.80 | 15.66 |
March | 0.416462E+10 | 6663.98 | 28-MAR-10:10 | 28.87 | 18.06 | 0.210710E+09 | 338.73 | 16-MAR-10:20 | 28.87 | 18.06 |
April | 0.608743E+10 | 12172.25 | 16-APR-10:02 | 35.32 | 21.70 | 0.189696E+09 | 339.20 | 14-APR-10:00 | 35.32 | 21.70 |
May | 0.755013E+10 | 12506.06 | 29-MAY-07:42 | 31.52 | 19.34 | 0.205741E+09 | 339.16 | 26-MAY-10:00 | 31.52 | 19.34 |
June | 0.700196E+10 | 11871.88 | 11-JUN-10:02 | 36.98 | 25.11 | 0.204669E+09 | 339.14 | 12-JUN-10:00 | 41.40 | 22.35 |
July | 0.608982E+10 | 12275.84 | 02-JUL-09:12 | 34.77 | 25.77 | 0.191073E+09 | 339.15 | 05-JUL-10:30 | 36.60 | 25.30 |
August | 0.571306E+10 | 11305.38 | 06-AUG-08:43 | 30.82 | 24.34 | 0.213304E+09 | 338.93 | 07-AUG-10:39 | 34.00 | 26.19 |
September | 0.496874E+10 | 8106.92 | 05-SEP-04:02 | 26.28 | 25.12 | 0.189679E+09 | 338.74 | 26-SEP-07:19 | 26.03 | 19.88 |
October | 0.447120E+10 | 12103.79 | 01-OCT-10:12 | 30.47 | 19.50 | 0.196293E+09 | 338.74 | 10-OCT-07:19 | 21.97 | 18.94 |
November | 0.291738E+10 | 4399.21 | 09-NOV-10:00 | 24.50 | 17.90 | 0.191039E+09 | 338.73 | 16-NOV-11:20 | 24.93 | 17.27 |
December | 0.176471E+10 | 2956.13 | 01-DEC-10:00 | 18.30 | 11.37 | 0.176692E+09 | 338.72 | 18-DEC-11:20 | 22.00 | 14.81 |
Annual Sum or Average | 0.544780E+11 | 0.231573E+10 | ||||||||
Minimum of Months | 0.157455E+10 | 2378.34 | 18.30 | 11.37 | 0.170593E+09 | 338.72 | 19.98 | 13.28 | ||
Maximum of Months | 0.755013E+10 | 12506.06 | 36.98 | 25.77 | 0.213304E+09 | 339.20 | 41.40 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407858E+10 | 8473.87 | 08-JAN-13:43 | 21.93 | 12.93 | 0.398243E+09 | 549.50 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.478846E+10 | 14720.60 | 20-FEB-12:32 | 25.43 | 13.32 | 0.370197E+09 | 549.72 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.733305E+10 | 14766.00 | 26-MAR-13:02 | 29.87 | 16.43 | 0.452160E+09 | 549.78 | 08-MAR-14:50 | 29.87 | 16.43 |
April | 0.834763E+10 | 14532.74 | 16-APR-13:22 | 39.30 | 21.89 | 0.404821E+09 | 549.70 | 06-APR-13:00 | 39.30 | 21.89 |
May | 0.935084E+10 | 14678.74 | 29-MAY-15:01 | 41.30 | 21.88 | 0.438948E+09 | 549.67 | 03-MAY-13:50 | 41.30 | 21.88 |
June | 0.903216E+10 | 14144.77 | 04-JUN-16:11 | 42.13 | 22.34 | 0.437375E+09 | 549.66 | 12-JUN-13:30 | 43.60 | 22.38 |
July | 0.837020E+10 | 14013.79 | 04-JUL-15:52 | 39.70 | 24.71 | 0.406954E+09 | 549.59 | 05-JUL-13:50 | 37.90 | 25.56 |
August | 0.835484E+10 | 13991.69 | 06-AUG-16:02 | 36.25 | 26.27 | 0.456162E+09 | 549.62 | 07-AUG-13:50 | 37.08 | 26.29 |
September | 0.790070E+10 | 14572.64 | 24-SEP-13:22 | 34.85 | 24.63 | 0.405127E+09 | 554.46 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.896704E+10 | 15549.91 | 01-OCT-12:51 | 35.20 | 19.96 | 0.421088E+09 | 582.51 | 02-OCT-13:39 | 36.33 | 21.10 |
November | 0.756317E+10 | 14886.55 | 11-NOV-11:23 | 26.50 | 17.20 | 0.412726E+09 | 554.22 | 01-NOV-13:39 | 26.50 | 17.20 |
December | 0.478393E+10 | 14680.72 | 03-DEC-12:53 | 24.00 | 14.17 | 0.392245E+09 | 549.69 | 01-DEC-14:00 | 24.00 | 14.17 |
Annual Sum or Average | 0.888706E+11 | 0.499605E+10 | ||||||||
Minimum of Months | 0.407858E+10 | 8473.87 | 21.93 | 12.93 | 0.370197E+09 | 549.50 | 23.00 | 13.41 | ||
Maximum of Months | 0.935084E+10 | 15549.91 | 42.13 | 26.27 | 0.456162E+09 | 582.51 | 43.60 | 26.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172122E+10 | 3495.26 | 31-JAN-16:10 | 20.95 | 11.21 | 0.231207E+09 | 347.84 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.224388E+10 | 7132.08 | 20-FEB-16:33 | 24.93 | 14.44 | 0.223661E+09 | 347.85 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.418015E+10 | 11176.89 | 26-MAR-15:02 | 30.33 | 16.74 | 0.283187E+09 | 347.86 | 30-MAR-09:09 | 24.92 | 18.16 |
April | 0.605226E+10 | 13392.08 | 02-APR-16:41 | 33.57 | 20.57 | 0.256004E+09 | 347.86 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.744053E+10 | 13627.88 | 29-MAY-16:21 | 41.10 | 21.45 | 0.277850E+09 | 347.85 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.728796E+10 | 13227.21 | 04-JUN-16:11 | 42.13 | 22.34 | 0.276878E+09 | 347.85 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.609787E+10 | 13273.32 | 02-JUL-16:32 | 40.33 | 26.50 | 0.257546E+09 | 347.84 | 05-JUL-09:20 | 35.67 | 25.11 |
August | 0.576183E+10 | 12531.60 | 06-AUG-16:02 | 36.25 | 26.27 | 0.288640E+09 | 347.84 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.504403E+10 | 12365.02 | 24-SEP-15:22 | 34.95 | 25.05 | 0.256201E+09 | 347.84 | 08-SEP-13:00 | 34.95 | 25.05 |
October | 0.446830E+10 | 12837.60 | 01-OCT-15:31 | 35.67 | 20.08 | 0.264585E+09 | 347.85 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.308533E+10 | 5733.74 | 08-NOV-15:30 | 29.55 | 18.29 | 0.254462E+09 | 347.85 | 06-NOV-10:30 | 29.55 | 18.29 |
December | 0.196413E+10 | 3947.60 | 01-DEC-15:30 | 22.85 | 13.56 | 0.231063E+09 | 347.85 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.553475E+11 | 0.310128E+10 | ||||||||
Minimum of Months | 0.172122E+10 | 3495.26 | 20.95 | 11.21 | 0.223661E+09 | 347.84 | 20.95 | 11.21 | ||
Maximum of Months | 0.744053E+10 | 13627.88 | 42.13 | 26.50 | 0.288640E+09 | 347.86 | 42.20 | 27.65 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127731E+10 | 12204.53 | 02-JAN-06:16 | 6.50 |
February | 0.669687E+09 | 4813.78 | 02-FEB-06:03 | 6.92 |
March | 0.318574E+09 | 3830.64 | 01-MAR-06:03 | 13.67 |
April | 65918982.55 | 6598.69 | 17-APR-04:02 | 24.68 |
May | 25092297.65 | 5442.60 | 22-MAY-04:02 | 27.75 |
June | 12751557.22 | 4316.87 | 28-JUN-05:03 | 26.50 |
July | 10775124.50 | 3501.73 | 19-JUL-05:03 | 26.00 |
August | 13161177.84 | 4973.53 | 21-AUG-04:02 | 25.67 |
September | 22609185.85 | 5695.68 | 25-SEP-04:02 | 26.32 |
October | 0.192885E+09 | 4934.00 | 04-OCT-05:03 | 25.07 |
November | 0.529255E+09 | 4439.88 | 24-NOV-06:03 | 10.50 |
December | 0.101586E+10 | 5806.23 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.415388E+10 | |||
Minimum of Months | 10775124.50 | 3501.73 | 6.25 | |
Maximum of Months | 0.127731E+10 | 12204.53 | 27.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.605321E+09 | 3385.48 | 08-JAN-13:43 | 21.93 |
February | 0.125182E+09 | 3756.37 | 05-FEB-13:33 | 23.07 |
March | 15337033.08 | 2865.32 | 26-MAR-15:02 | 30.33 |
April | 15924260.02 | 2592.46 | 28-APR-04:02 | 27.93 |
May | 18697330.47 | 2696.44 | 18-MAY-04:02 | 30.20 |
June | 19910474.97 | 2992.76 | 15-JUN-04:02 | 29.38 |
July | 22105608.13 | 3374.04 | 14-JUL-04:02 | 29.58 |
August | 16435426.53 | 3252.85 | 09-AUG-04:02 | 30.32 |
September | 16877055.60 | 2458.81 | 01-SEP-04:02 | 26.77 |
October | 22223901.61 | 2797.15 | 01-OCT-14:11 | 35.93 |
November | 35398103.68 | 3643.65 | 26-NOV-11:23 | 24.50 |
December | 0.280093E+09 | 4556.19 | 24-DEC-13:53 | 24.30 |
Annual Sum or Average | 0.119350E+10 | |||
Minimum of Months | 15337033.08 | 2458.81 | 21.93 | |
Maximum of Months | 0.605321E+09 | 4556.19 | 35.93 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231539E+09 | 2735.24 | 04-JAN-08:08 | 6.42 |
February | 24396436.71 | 2439.17 | 05-FEB-11:50 | 20.35 |
March | 12666337.35 | 1815.90 | 19-MAR-12:13 | 23.43 |
April | 13913824.04 | 2781.82 | 28-APR-04:02 | 27.93 |
May | 19802995.27 | 3456.06 | 18-MAY-04:02 | 30.20 |
June | 26251615.98 | 3951.27 | 22-JUN-04:02 | 30.28 |
July | 34679142.18 | 4388.91 | 12-JUL-04:02 | 29.25 |
August | 29927394.29 | 4663.06 | 30-AUG-04:02 | 27.93 |
September | 28606657.08 | 4337.04 | 01-SEP-04:02 | 26.77 |
October | 29380500.93 | 3713.38 | 11-OCT-04:03 | 24.15 |
November | 32726430.94 | 2623.34 | 26-NOV-11:03 | 24.17 |
December | 54755632.81 | 3478.91 | 24-DEC-13:43 | 24.00 |
Annual Sum or Average | 0.538646E+09 | |||
Minimum of Months | 12666337.35 | 1815.90 | 6.42 | |
Maximum of Months | 0.231539E+09 | 4663.06 | 30.28 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5054602.83 | 19149.82 | 02-JAN-07:01 | 6.78 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 5054602.83 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 5054602.83 | 19149.82 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121569E+09 | 22815.59 | 02-JAN-06:11 | 6.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 6059371.73 | 19834.57 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.127628E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 0.121569E+09 | 22815.59 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354651E+09 | 10254.36 | 02-JAN-06:11 | 6.50 |
February | 55794532.34 | 8709.17 | 13-FEB-07:03 | 10.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 5296255.58 | 8397.44 | 27-NOV-07:02 | 10.02 |
December | 0.130779E+09 | 9068.70 | 20-DEC-06:12 | 6.60 |
Annual Sum or Average | 0.546521E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.354651E+09 | 10254.36 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149377E+09 | 6583.08 | 02-JAN-06:11 | 6.50 |
February | 21496285.62 | 5661.49 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 2802679.76 | 5531.39 | 27-NOV-07:02 | 10.02 |
December | 55427764.38 | 5866.59 | 20-DEC-06:12 | 6.60 |
Annual Sum or Average | 0.229104E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.149377E+09 | 6583.08 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203970E+09 | 10023.39 | 02-JAN-06:11 | 6.50 |
February | 30134169.17 | 8639.24 | 04-FEB-07:03 | 8.40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1726137.14 | 5806.37 | 27-NOV-07:02 | 10.02 |
December | 67198186.30 | 8709.12 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.303029E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.203970E+09 | 10023.39 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219178E+09 | 6488.63 | 02-JAN-06:11 | 6.50 |
February | 37528543.29 | 5635.17 | 04-FEB-07:03 | 8.40 |
March | 96665.16 | 483.33 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 3993256.48 | 5524.29 | 27-NOV-07:02 | 10.02 |
December | 83471199.48 | 5853.10 | 20-DEC-06:12 | 6.60 |
Annual Sum or Average | 0.344267E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.219178E+09 | 6488.63 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25744028.34 | 5886.01 | 03-JAN-06:11 | 5.53 |
February | 296820.23 | 1282.46 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 216810.58 | 1445.40 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 26257659.15 | |||
Minimum of Months | 0.00 | 0.00 | 5.53 | |
Maximum of Months | 25744028.34 | 5886.01 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7510707.47 | 3815.93 | 04-JAN-07:03 | 5.50 |
February | 154488.39 | 1029.92 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 11914.69 | 79.43 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 7677110.56 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 7510707.47 | 3815.93 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498916E+09 | 6990.02 | 03-JAN-07:10 | 5.50 |
February | 0.326238E+09 | 6311.48 | 02-FEB-07:10 | 7.12 |
March | 68608583.16 | 5743.76 | 01-MAR-07:10 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 84811036.49 | 5762.35 | 20-NOV-07:06 | 13.85 |
December | 0.368780E+09 | 6383.28 | 21-DEC-07:10 | 5.68 |
Annual Sum or Average | 0.134735E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 0.498916E+09 | 6990.02 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10667607.66 | 3783.72 | 04-JAN-07:03 | 5.50 |
February | 334127.41 | 1431.18 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 116341.26 | 775.61 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 11118076.33 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 10667607.66 | 3783.72 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69776980.44 | 7327.37 | 02-JAN-06:11 | 6.50 |
February | 3115655.11 | 5168.85 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 6909539.97 | 6690.34 | 20-DEC-07:02 | 7.70 |
Annual Sum or Average | 79802175.52 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 69776980.44 | 7327.37 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31845791.23 | 4621.58 | 02-JAN-06:11 | 6.50 |
February | 2823586.53 | 4422.66 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 4372203.55 | 4265.30 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 39041581.31 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 31845791.23 | 4621.58 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35105153.75 | 7109.03 | 02-JAN-06:11 | 6.50 |
February | 1234274.08 | 4158.94 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 2458989.39 | 6780.27 | 21-DEC-07:01 | 5.68 |
Annual Sum or Average | 38798417.21 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 35105153.75 | 7109.03 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44880429.71 | 4543.39 | 02-JAN-06:11 | 6.50 |
February | 3338758.46 | 4492.60 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 6367244.65 | 4281.40 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 54586432.81 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 44880429.71 | 4543.39 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.783470E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.687680E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773316E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.669866E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708885E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.708060E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.680015E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.766573E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.695482E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.743205E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.766480E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771400E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.875443E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.669866E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.783470E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484724E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.429787E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485628E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423888E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451637E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450864E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430719E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.484528E+09 | 750.07 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438298E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463349E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479239E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.476547E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549921E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423888E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485628E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738184E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664162E+09 | 1184.79 | 09-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764877E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671962E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.716769E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.715935E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.686041E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.769109E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.691699E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.725575E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.729400E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720873E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.859459E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664162E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.769109E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.480572E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425690E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489316E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426774E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453912E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.453132E+09 | 600.10 | 19-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.435553E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.490544E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.442410E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.469748E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.469596E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466855E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550410E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.425690E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490544E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779795E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.684667E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.771302E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668943E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707953E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.706913E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.678033E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.764651E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.693547E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740540E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.762787E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.766472E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.872560E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.668943E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.779795E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.482516E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.428590E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.484757E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423282E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451166E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450398E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429605E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.483349E+09 | 750.07 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437574E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.462264E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477851E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475378E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548673E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423282E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.484757E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737320E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.662861E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763282E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671005E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.715590E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.714437E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.684406E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.767023E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.690078E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.724688E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.727700E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.719206E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.857759E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.662861E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.767023E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478392E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424406E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488324E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425602E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453193E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452267E+09 | 600.10 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.434503E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.489238E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.441325E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468945E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468281E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.465251E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548973E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424406E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.489238E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.783470E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.687680E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773316E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.669866E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708885E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.708060E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.679994E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.766573E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.695378E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.743205E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.766480E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771400E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.875431E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.669866E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.783470E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484724E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.429787E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485628E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423888E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451637E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450864E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430697E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.484528E+09 | 750.07 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438298E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463349E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479239E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.476547E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549919E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423888E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485628E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738184E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664162E+09 | 1184.79 | 09-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764877E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671962E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.716767E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.715935E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.686041E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.769088E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.691699E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.725575E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.729400E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720873E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.859456E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664162E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.769088E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.480572E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425690E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489316E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426774E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453912E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.453132E+09 | 600.10 | 19-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.435553E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.490544E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.442410E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.469748E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.469596E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466855E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550410E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.425690E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490544E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.783470E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104265.68 | 85129061.93 |
February | 0.901968E+09 | 0.687680E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2987515.49 | 94581801.62 |
March | 0.107774E+10 | 0.773316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23181919.56 | 63080937.02 |
April | 0.956342E+09 | 0.669866E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88554892.76 | 5606865.76 |
May | 0.103597E+10 | 0.708885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187424E+09 | 2258641.57 |
June | 0.103308E+10 | 0.708060E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126681E+09 | 1191278.84 |
July | 0.959235E+09 | 0.680015E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157233E+09 | 477984.28 |
August | 0.107774E+10 | 0.766573E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88468431.85 | 924925.22 |
September | 0.956342E+09 | 0.695482E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52796577.96 | 1680585.26 |
October | 0.994195E+09 | 0.743205E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29375159.92 | 5179436.57 |
November | 0.984487E+09 | 0.766480E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7561578.15 | 19451750.98 |
December | 0.959235E+09 | 0.771400E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982116.58 | 77676276.37 |
Annual Sum or Average | 0.119305E+11 | 0.875443E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765350E+09 | 0.357240E+09 |
Minimum of Months | 0.901968E+09 | 0.669866E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104265.68 | 477984.28 |
Maximum of Months | 0.107774E+10 | 0.783470E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187424E+09 | 94581801.62 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.484724E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17676.08 | 60153592.26 |
February | 0.571020E+09 | 0.429787E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199645.03 | 67750356.52 |
March | 0.682301E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13949788.02 | 44128008.55 |
April | 0.605444E+09 | 0.423888E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57219553.22 | 4188257.22 |
May | 0.655854E+09 | 0.451637E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123830E+09 | 1550085.90 |
June | 0.654023E+09 | 0.450864E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84427338.83 | 808909.87 |
July | 0.607275E+09 | 0.430719E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104819E+09 | 317089.41 |
August | 0.682301E+09 | 0.484528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58695640.20 | 616187.09 |
September | 0.605444E+09 | 0.438298E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35014339.56 | 1095129.96 |
October | 0.629407E+09 | 0.463349E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18329976.55 | 3756487.99 |
November | 0.623262E+09 | 0.479239E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4126973.19 | 14334344.23 |
December | 0.607275E+09 | 0.476547E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 334209.32 | 55528955.16 |
Annual Sum or Average | 0.755301E+10 | 0.549921E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501965E+09 | 0.254227E+09 |
Minimum of Months | 0.571020E+09 | 0.423888E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17676.08 | 317089.41 |
Maximum of Months | 0.682301E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123830E+09 | 67750356.52 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101750E+09 |
February | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1069936.71 | 0.112018E+09 |
March | 0.107774E+10 | 0.764877E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19528430.95 | 69434681.40 |
April | 0.956342E+09 | 0.671962E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86337871.83 | 5985340.73 |
May | 0.103597E+10 | 0.716769E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187433E+09 | 2295957.75 |
June | 0.103308E+10 | 0.715935E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126864E+09 | 1168576.21 |
July | 0.959235E+09 | 0.686041E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157381E+09 | 476673.20 |
August | 0.107774E+10 | 0.769109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88066381.75 | 937038.34 |
September | 0.956342E+09 | 0.691699E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51636630.19 | 1743856.57 |
October | 0.994195E+09 | 0.725575E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26104492.65 | 5818334.16 |
November | 0.984487E+09 | 0.729400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4711513.23 | 24316175.03 |
December | 0.959235E+09 | 0.720873E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19204.57 | 95943044.01 |
Annual Sum or Average | 0.119305E+11 | 0.859459E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749153E+09 | 0.421888E+09 |
Minimum of Months | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476673.20 |
Maximum of Months | 0.107774E+10 | 0.769109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187433E+09 | 0.112018E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.480572E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.52 | 59859994.42 |
February | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1161627.90 | 66182823.04 |
March | 0.682256E+09 | 0.489316E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14228354.35 | 44909134.62 |
April | 0.605404E+09 | 0.426774E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58232231.70 | 4127742.81 |
May | 0.655811E+09 | 0.453912E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124732E+09 | 1645012.90 |
June | 0.653980E+09 | 0.453132E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84358617.07 | 853536.74 |
July | 0.607235E+09 | 0.435553E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105324E+09 | 312936.52 |
August | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58980240.43 | 618234.06 |
September | 0.605404E+09 | 0.442410E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35035805.78 | 1101349.17 |
October | 0.629366E+09 | 0.469748E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18960603.73 | 3463832.34 |
November | 0.623221E+09 | 0.469596E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4368708.81 | 13354424.19 |
December | 0.607235E+09 | 0.466855E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345238.38 | 54157383.57 |
Annual Sum or Average | 0.755252E+10 | 0.550410E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505730E+09 | 0.250586E+09 |
Minimum of Months | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.52 | 312936.52 |
Maximum of Months | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124732E+09 | 66182823.04 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.779795E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22914.99 | 53380573.64 |
February | 0.901968E+09 | 0.684667E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1639756.74 | 55776781.38 |
March | 0.107774E+10 | 0.771302E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13407894.13 | 34279914.28 |
April | 0.956342E+09 | 0.668943E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49818803.15 | 2757493.91 |
May | 0.103597E+10 | 0.707953E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102421E+09 | 970842.37 |
June | 0.103308E+10 | 0.706913E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68437067.68 | 606681.08 |
July | 0.959235E+09 | 0.678033E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84307405.87 | 309179.48 |
August | 0.107774E+10 | 0.764651E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47149736.57 | 573681.94 |
September | 0.956342E+09 | 0.693547E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28029873.60 | 1246853.15 |
October | 0.994195E+09 | 0.740540E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15642838.43 | 3414869.04 |
November | 0.984487E+09 | 0.762787E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3654339.53 | 12597584.23 |
December | 0.959235E+09 | 0.766472E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 296476.76 | 50048141.02 |
Annual Sum or Average | 0.119305E+11 | 0.872560E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414828E+09 | 0.215963E+09 |
Minimum of Months | 0.901968E+09 | 0.668943E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22914.99 | 309179.48 |
Maximum of Months | 0.107774E+10 | 0.779795E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102421E+09 | 55776781.38 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.482516E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.43 | 37968456.67 |
February | 0.571020E+09 | 0.428590E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 634665.30 | 40300947.30 |
March | 0.682301E+09 | 0.484757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7866187.10 | 24850196.21 |
April | 0.605444E+09 | 0.423282E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31260110.68 | 2237984.29 |
May | 0.655854E+09 | 0.451166E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66619778.63 | 764950.73 |
June | 0.654023E+09 | 0.450398E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45205700.15 | 441771.20 |
July | 0.607275E+09 | 0.429605E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55803088.52 | 217448.11 |
August | 0.682301E+09 | 0.483349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31087736.44 | 399043.48 |
September | 0.605444E+09 | 0.437574E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18491655.14 | 849545.19 |
October | 0.629407E+09 | 0.462264E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9836557.10 | 2494287.89 |
November | 0.623262E+09 | 0.477851E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2055648.13 | 9121820.17 |
December | 0.607275E+09 | 0.475378E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75843.83 | 35461985.12 |
Annual Sum or Average | 0.755301E+10 | 0.548673E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268937E+09 | 0.155108E+09 |
Minimum of Months | 0.571020E+09 | 0.423282E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.43 | 217448.11 |
Maximum of Months | 0.682301E+09 | 0.484757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66619778.63 | 40300947.30 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737320E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276066E+10 |
February | 0.901968E+09 | 0.662861E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64125473.84 | 0.159586E+10 |
March | 0.107774E+10 | 0.763282E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905458E+09 | 0.729417E+09 |
April | 0.956342E+09 | 0.671005E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242702E+10 | 95520051.74 |
May | 0.103597E+10 | 0.715590E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393372E+10 | 1374473.65 |
June | 0.103308E+10 | 0.714437E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397608E+10 | 682092.65 |
July | 0.959235E+09 | 0.684406E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274421E+10 | 325583.33 |
August | 0.107774E+10 | 0.767023E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269217E+10 | 935347.87 |
September | 0.956342E+09 | 0.690078E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198352E+10 | 4441985.78 |
October | 0.994195E+09 | 0.724688E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138995E+10 | 0.319007E+09 |
November | 0.984487E+09 | 0.727700E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443885E+09 | 0.100501E+10 |
December | 0.959235E+09 | 0.719206E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 659702.79 | 0.237487E+10 |
Annual Sum or Average | 0.119305E+11 | 0.857759E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205608E+11 | 0.888810E+10 |
Minimum of Months | 0.901968E+09 | 0.662861E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325583.33 |
Maximum of Months | 0.107774E+10 | 0.767023E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397608E+10 | 0.276066E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.478392E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37678751.44 |
February | 0.570983E+09 | 0.424406E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 568813.34 | 39628304.95 |
March | 0.682256E+09 | 0.488324E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7777629.40 | 25581227.72 |
April | 0.605404E+09 | 0.425602E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31457011.16 | 2294644.03 |
May | 0.655811E+09 | 0.453193E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66488388.88 | 823167.94 |
June | 0.653980E+09 | 0.452267E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44774184.15 | 499092.35 |
July | 0.607235E+09 | 0.434503E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55695597.93 | 218572.15 |
August | 0.682256E+09 | 0.489238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31016410.02 | 401223.94 |
September | 0.605404E+09 | 0.441325E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18335379.56 | 892996.12 |
October | 0.629366E+09 | 0.468945E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9917345.61 | 2409909.08 |
November | 0.623221E+09 | 0.468281E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2072816.26 | 8872751.38 |
December | 0.607235E+09 | 0.465251E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60268.12 | 34933331.08 |
Annual Sum or Average | 0.755252E+10 | 0.548973E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268164E+09 | 0.154234E+09 |
Minimum of Months | 0.570983E+09 | 0.424406E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218572.15 |
Maximum of Months | 0.682256E+09 | 0.489238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66488388.88 | 39628304.95 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.783470E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45067.23 | 80477477.20 |
February | 0.901968E+09 | 0.687680E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2207628.33 | 87941933.85 |
March | 0.107774E+10 | 0.773316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19681208.12 | 57465560.96 |
April | 0.956342E+09 | 0.669866E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74503027.41 | 5249023.02 |
May | 0.103597E+10 | 0.708885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156541E+09 | 1881633.34 |
June | 0.103308E+10 | 0.708060E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105864E+09 | 962310.29 |
July | 0.959235E+09 | 0.679994E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131022E+09 | 404604.35 |
August | 0.107774E+10 | 0.766573E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74008358.65 | 770462.68 |
September | 0.956342E+09 | 0.695378E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44097662.52 | 1531178.06 |
October | 0.994195E+09 | 0.743205E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24621603.10 | 4891275.12 |
November | 0.984487E+09 | 0.766480E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6008708.48 | 18593718.51 |
December | 0.959235E+09 | 0.771400E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 593279.67 | 73619144.20 |
Annual Sum or Average | 0.119305E+11 | 0.875431E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639193E+09 | 0.333788E+09 |
Minimum of Months | 0.901968E+09 | 0.669866E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45067.23 | 404604.35 |
Maximum of Months | 0.107774E+10 | 0.783470E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156541E+09 | 87941933.85 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.484724E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4501.23 | 55779273.62 |
February | 0.421807E+09 | 0.429787E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966851.75 | 61597167.53 |
March | 0.502994E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11979014.91 | 39586590.97 |
April | 0.447140E+09 | 0.423888E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48251457.84 | 3830140.09 |
May | 0.484071E+09 | 0.451637E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103801E+09 | 1276584.18 |
June | 0.482240E+09 | 0.450864E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70733085.33 | 648088.78 |
July | 0.448971E+09 | 0.430697E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87565026.23 | 268101.20 |
August | 0.502994E+09 | 0.484528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49209486.60 | 510485.96 |
September | 0.447140E+09 | 0.438298E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29348041.65 | 989335.07 |
October | 0.465148E+09 | 0.463349E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15460531.64 | 3478003.70 |
November | 0.460569E+09 | 0.479239E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3432974.72 | 13254116.98 |
December | 0.448971E+09 | 0.476547E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 203894.01 | 51480940.70 |
Annual Sum or Average | 0.557719E+10 | 0.549919E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420956E+09 | 0.232699E+09 |
Minimum of Months | 0.421807E+09 | 0.423888E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4501.23 | 268101.20 |
Maximum of Months | 0.502994E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103801E+09 | 61597167.53 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92563840.20 |
February | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 910801.71 | 0.101102E+09 |
March | 0.107774E+10 | 0.764877E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16416267.59 | 62470118.75 |
April | 0.956342E+09 | 0.671962E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72253548.57 | 5558316.96 |
May | 0.103597E+10 | 0.716767E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156535E+09 | 1907434.12 |
June | 0.103308E+10 | 0.715935E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106067E+09 | 940434.56 |
July | 0.959235E+09 | 0.686041E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131171E+09 | 403620.14 |
August | 0.107774E+10 | 0.769088E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73660815.65 | 780360.97 |
September | 0.956342E+09 | 0.691699E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43096540.35 | 1583526.16 |
October | 0.994195E+09 | 0.725575E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21796265.96 | 5388467.59 |
November | 0.984487E+09 | 0.729400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3960581.21 | 22181434.14 |
December | 0.959235E+09 | 0.720873E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17141.41 | 87280871.32 |
Annual Sum or Average | 0.119305E+11 | 0.859456E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625886E+09 | 0.382161E+09 |
Minimum of Months | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403620.14 |
Maximum of Months | 0.107774E+10 | 0.769088E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156535E+09 | 0.101102E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.480572E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55652550.11 |
February | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 844342.41 | 60864447.06 |
March | 0.682256E+09 | 0.489316E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11881790.40 | 40762629.81 |
April | 0.605404E+09 | 0.426774E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48740684.16 | 3835441.66 |
May | 0.655811E+09 | 0.453912E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103937E+09 | 1362040.42 |
June | 0.653980E+09 | 0.453132E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70341840.31 | 692455.43 |
July | 0.607235E+09 | 0.435553E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87451478.82 | 266838.19 |
August | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49225614.10 | 516344.98 |
September | 0.605404E+09 | 0.442410E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29148857.48 | 1012241.13 |
October | 0.629366E+09 | 0.469748E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15781153.01 | 3282522.23 |
November | 0.623221E+09 | 0.469596E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3471111.53 | 12680364.44 |
December | 0.607235E+09 | 0.466855E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170965.47 | 50575378.16 |
Annual Sum or Average | 0.755252E+10 | 0.550410E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420995E+09 | 0.231503E+09 |
Minimum of Months | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266838.19 |
Maximum of Months | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103937E+09 | 60864447.06 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123103E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897470.84 | 0.132567E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19982130.15 | 83914696.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87724564.28 | 7141907.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193822E+09 | 2289430.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131209E+09 | 1156315.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164782E+09 | 513360.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90709527.06 | 852089.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51470833.37 | 1588168.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26441117.72 | 7351918.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4607172.57 | 28941198.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68553.23 | 0.113546E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771715E+09 | 0.502964E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513360.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193822E+09 | 0.132567E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3472.60 | 0.142738E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1801099.61 | 0.158980E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26655236.82 | 0.104559E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113045E+09 | 9121006.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248074E+09 | 3097379.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169117E+09 | 1575698.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211652E+09 | 608564.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117212E+09 | 1050663.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67144926.67 | 1766896.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35422722.64 | 8905037.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7137253.88 | 34369210.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567712.78 | 0.132987E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997832E+09 | 0.599758E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3472.60 | 608564.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248074E+09 | 0.158980E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141079E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184214.74 | 0.156729E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19186370.40 | 93863501.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109101E+09 | 6575889.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259691E+09 | 2327552.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176829E+09 | 1385508.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217598E+09 | 484726.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119761E+09 | 1352370.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67197017.79 | 1269320.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30891608.24 | 6814685.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3767648.72 | 31248573.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7459.05 | 0.126688E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100421E+10 | 0.569818E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484726.45 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259691E+09 | 0.156729E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 08-JAN-14:53 | 224.71 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.07 | 19-FEB-14:55 | 320.38 | 09-FEB-22:20 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.39 | 26-MAR-15:00 | 651.74 | 24-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.01 | 15-APR-17:08 | 95.18 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 766.74 | 28-MAY-14:55 | 72.64 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 17-JUN-20:50 | 59.09 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.98 | 02-JUL-11:26 | 47.78 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.80 | 06-AUG-14:06 | 60.23 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 | 24-SEP-14:46 | 23.81 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.95 | 15-OCT-12:00 | 94.90 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.98 | 12-NOV-14:10 | 152.10 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.66 | 24-DEC-14:00 | 352.87 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 23.81 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 766.74 | 651.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 08-JAN-15:00 | 148.23 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 19-FEB-14:53 | 209.93 | 09-FEB-22:10 |
March | 827.22 | 01-MAR-10:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.92 | 26-MAR-15:40 | 442.88 | 24-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.59 | 15-APR-17:08 | 69.19 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.68 | 28-MAY-13:54 | 50.12 | 15-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.01 | 17-JUN-20:50 | 39.00 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.75 | 02-JUL-11:24 | 31.54 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.78 | 06-AUG-14:06 | 40.44 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.96 | 24-SEP-14:46 | 15.32 | 19-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.03 | 15-OCT-12:35 | 62.56 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 12-NOV-14:10 | 101.82 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 | 24-DEC-14:20 | 232.71 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 15.32 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 511.68 | 442.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 306.41 | 22-JAN-14:30 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 21-FEB-15:00 | 321.64 | 09-FEB-22:20 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.56 | 26-MAR-14:55 | 699.46 | 24-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.45 | 15-APR-17:08 | 101.90 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 766.74 | 28-MAY-15:00 | 74.30 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.95 | 17-JUN-20:50 | 58.66 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.09 | 02-JUL-11:26 | 47.67 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.37 | 06-AUG-14:04 | 60.64 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.55 | 24-SEP-14:44 | 24.04 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.69 | 15-OCT-13:00 | 95.76 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 12-NOV-14:45 | 163.21 | 29-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 28-DEC-14:00 | 506.15 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 766.74 | 699.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 08-JAN-14:13 | 149.89 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 | 19-FEB-13:43 | 209.66 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.67 | 26-MAR-13:02 | 464.84 | 24-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.27 | 15-APR-17:07 | 64.85 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.16 | 28-MAY-15:00 | 52.61 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 19-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.29 | 17-JUN-20:50 | 40.90 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.00 | 02-JUL-11:26 | 31.34 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.54 | 06-AUG-09:30 | 40.76 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.03 | 24-SEP-14:04 | 15.83 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.54 | 15-OCT-12:00 | 62.58 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.91 | 12-NOV-12:50 | 102.30 | 29-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 24-DEC-13:33 | 237.10 | 31-DEC-15:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 15.83 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 511.16 | 464.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 08-JAN-14:50 | 139.84 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | 19-FEB-15:10 | 190.47 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 26-MAR-15:00 | 369.74 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.72 | 15-APR-17:02 | 53.69 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.44 | 28-MAY-14:50 | 31.82 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.46 | 17-JUN-21:00 | 31.93 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.74 | 02-JUL-11:40 | 29.66 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.31 | 06-AUG-13:48 | 34.55 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.91 | 24-SEP-14:34 | 18.86 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.24 | 15-OCT-12:10 | 60.96 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 12-NOV-14:00 | 98.40 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.74 | 24-DEC-14:10 | 224.85 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 18.86 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 416.44 | 369.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 08-JAN-14:50 | 94.25 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 19-FEB-15:10 | 126.99 | 09-FEB-22:20 |
March | 827.22 | 01-MAR-10:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.79 | 26-MAR-15:00 | 262.22 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 | 15-APR-17:02 | 41.80 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.27 | 28-MAY-14:35 | 25.26 | 15-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.72 | 17-JUN-20:50 | 22.18 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 | 02-JUL-11:24 | 19.76 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.69 | 06-AUG-13:48 | 23.59 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 | 24-SEP-14:34 | 12.59 | 08-SEP-22:10 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 | 15-OCT-12:45 | 41.16 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 12-NOV-14:00 | 68.12 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 24-DEC-14:10 | 150.61 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 12.59 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 278.27 | 262.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18866.50 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3043.69 | 22-FEB-13:00 | 15927.81 | 02-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12522.97 | 28-MAR-16:02 | 8743.18 | 01-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17092.80 | 27-APR-16:01 | 4978.83 | 10-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21479.02 | 03-MAY-16:01 | 112.47 | 15-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21730.88 | 07-JUN-16:01 | 97.63 | 27-JUN-11:10 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17177.85 | 07-JUL-16:01 | 29.79 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14119.83 | 07-AUG-16:01 | 102.04 | 16-AUG-05:03 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12539.93 | 26-SEP-16:02 | 558.28 | 27-SEP-05:03 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11754.16 | 02-OCT-16:02 | 8972.78 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4895.04 | 09-NOV-12:03 | 14302.37 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.80 | 28-DEC-14:00 | 18401.56 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21730.88 | 18866.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 94.96 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 19-FEB-14:03 | 126.91 | 09-FEB-22:20 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.12 | 26-MAR-13:02 | 274.09 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 | 15-APR-17:08 | 38.48 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 28-MAY-14:55 | 27.49 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.68 | 17-JUN-20:47 | 24.28 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.00 | 02-JUL-11:40 | 19.84 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.52 | 06-AUG-13:48 | 23.77 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.73 | 24-SEP-13:53 | 12.65 | 08-SEP-22:10 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.94 | 15-OCT-12:10 | 41.11 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 12-NOV-12:40 | 68.18 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 24-DEC-14:10 | 150.33 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 274.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 08-JAN-14:45 | 208.26 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 | 19-FEB-15:10 | 293.54 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 215.93 | 26-MAR-14:50 | 597.72 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.45 | 15-APR-17:02 | 91.15 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.08 | 28-MAY-14:33 | 61.07 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.16 | 17-JUN-20:47 | 49.37 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.98 | 02-JUL-11:55 | 42.35 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.52 | 06-AUG-14:06 | 49.16 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.04 | 24-SEP-15:00 | 23.20 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.86 | 15-OCT-12:00 | 86.29 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.78 | 12-NOV-14:10 | 144.74 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 24-DEC-14:20 | 327.33 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 23.20 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 641.08 | 597.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 08-JAN-14:50 | 137.37 | 15-JAN-17:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.32 | 19-FEB-15:10 | 190.15 | 09-FEB-22:20 |
March | 805.43 | 01-MAR-08:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.00 | 26-MAR-14:50 | 402.80 | 24-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.63 | 15-APR-17:02 | 65.14 | 22-APR-18:10 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.65 | 28-MAY-14:33 | 41.80 | 15-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.50 | 17-JUN-20:43 | 32.44 | 18-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.48 | 02-JUL-11:53 | 27.95 | 19-JUL-03:00 |
August | 805.43 | 01-AUG-07:10 | 750.07 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.13 | 06-AUG-14:06 | 32.99 | 15-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.99 | 24-SEP-14:48 | 14.86 | 08-SEP-22:20 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.48 | 15-OCT-13:00 | 56.83 | 12-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 12-NOV-14:10 | 96.41 | 28-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 24-DEC-14:40 | 215.19 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 14.86 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 431.65 | 402.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 258.28 | 22-JAN-14:07 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 21-FEB-15:00 | 294.32 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.70 | 26-MAR-15:05 | 630.81 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.72 | 15-APR-17:08 | 96.87 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.33 | 28-MAY-14:55 | 62.47 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.45 | 17-JUN-20:47 | 48.90 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.28 | 02-JUL-11:55 | 42.26 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.69 | 06-AUG-14:04 | 49.51 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.02 | 24-SEP-14:44 | 23.39 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.31 | 15-OCT-13:00 | 87.01 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 12-NOV-14:45 | 151.38 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 28-DEC-14:00 | 421.08 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 639.33 | 630.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 138.74 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 19-FEB-13:23 | 190.33 | 09-FEB-22:20 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.57 | 26-MAR-12:42 | 418.98 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.62 | 15-APR-17:07 | 62.15 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 28-MAY-14:55 | 44.13 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 19-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 | 17-JUN-20:43 | 34.31 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.39 | 02-JUL-11:55 | 27.89 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.39 | 06-AUG-09:30 | 33.30 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 | 24-SEP-14:04 | 15.05 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.41 | 15-OCT-12:20 | 56.97 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 | 12-NOV-12:50 | 97.01 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 24-DEC-13:33 | 214.85 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 418.98 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 301.76 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.63 | 19-FEB-14:53 | 444.76 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.46 | 26-MAR-15:10 | 907.67 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.89 | 15-APR-17:02 | 124.51 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.11 | 28-MAY-15:00 | 70.57 | 15-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.66 | 17-JUN-21:00 | 66.14 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.55 | 02-JUL-11:48 | 53.76 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.46 | 06-AUG-14:00 | 56.89 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.62 | 24-SEP-14:20 | 28.08 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.66 | 15-OCT-12:30 | 118.44 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 12-NOV-14:10 | 216.28 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 | 24-DEC-14:10 | 485.06 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.11 | 907.67 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 08-JAN-15:00 | 354.04 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.52 | 19-FEB-14:53 | 546.37 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.62 | 26-MAR-14:53 | 1135.16 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.70 | 15-APR-17:02 | 154.95 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.86 | 28-MAY-15:00 | 98.15 | 15-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.05 | 03-JUN-17:02 | 87.67 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.56 | 02-JUL-12:00 | 65.93 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.34 | 06-AUG-13:52 | 71.41 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.08 | 24-SEP-13:52 | 35.91 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.72 | 15-OCT-12:00 | 143.77 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.95 | 12-NOV-13:52 | 259.07 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.57 | 24-DEC-13:53 | 585.84 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 35.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.86 | 1135.16 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 350.37 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 | 24-FEB-16:00 | 517.02 | 09-FEB-22:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.91 | 26-MAR-15:10 | 916.89 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.57 | 15-APR-17:02 | 112.15 | 22-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.84 | 28-MAY-15:00 | 76.95 | 15-MAY-04:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.66 | 17-JUN-20:50 | 78.17 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.35 | 02-JUL-11:02 | 57.85 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.54 | 06-AUG-09:03 | 82.57 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.96 | 24-SEP-14:30 | 22.52 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.43 | 15-OCT-12:00 | 132.79 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 12-NOV-13:50 | 212.48 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 24-DEC-14:20 | 592.43 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.84 | 916.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19828.46 | 27-JAN-09:00 | 6035.01 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31275.75 | 23-FEB-07:02 | 6352.64 | 10740.11 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43887.14 | 13-MAR-05:12 | 2541.06 | 2863.91 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45938.27 | 18-APR-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45270.33 | 03-MAY-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44252.15 | 20-JUN-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42665.57 | 13-JUL-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44637.94 | 22-AUG-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44760.49 | 29-SEP-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44880.89 | 11-OCT-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41334.23 | 13-NOV-07:02 | 7623.17 | 12888.13 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22394.43 | 01-DEC-07:03 | 5082.11 | 8592.08 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19828.46 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45938.27 | 7623.17 | 12888.13 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4167.23 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
February | 8305.25 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
March | 13011.12 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15313.40 | 26-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 | 0.00 |
May | 17108.15 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.71 | 0.00 |
June | 17342.07 | 12-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 0.00 |
July | 15619.73 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 | 0.00 |
August | 14227.30 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.32 | 0.00 |
September | 12951.62 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.49 | 0.00 |
October | 13043.37 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 | 0.00 |
November | 9059.07 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 0.00 |
December | 5510.37 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17342.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 24.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2482.37 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2706.75 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
March | 5372.39 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 0.00 |
April | 6574.43 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 | 0.00 |
May | 7316.57 | 30-MAY-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 | 0.00 |
June | 8983.63 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 | 0.00 |
July | 7257.42 | 05-JUL-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.60 | 0.00 |
August | 6683.23 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.25 | 0.00 |
September | 6307.57 | 25-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.46 | 0.00 |
October | 6283.63 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 0.00 |
November | 3610.30 | 13-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 0.00 |
December | 2688.99 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2482.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8983.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 | 23.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2753.18 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3551.70 | 22-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 0.00 |
March | 5447.48 | 28-MAR-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7483.64 | 27-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.94 | 0.00 |
May | 9074.21 | 30-MAY-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 | 0.00 |
June | 8489.28 | 13-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.74 | 0.00 |
July | 8779.70 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.06 | 0.00 |
August | 7689.84 | 28-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.80 | 0.00 |
September | 6738.61 | 25-SEP-17:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 0.00 |
October | 6173.37 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.03 | 0.00 |
November | 4602.88 | 13-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 | 0.00 |
December | 2824.08 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2753.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9074.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.94 | 6.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12017.03 | 26-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14901.73 | 23-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33781.87 | 13-MAR-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34965.99 | 18-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34777.49 | 15-MAY-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33883.09 | 20-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34208.73 | 11-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33081.41 | 26-AUG-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34777.96 | 26-SEP-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33767.58 | 03-OCT-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18473.38 | 13-NOV-07:02 | 7623.17 | 12888.13 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13609.88 | 01-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12017.03 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34965.99 | 7623.17 | 12888.13 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11516.02 | 26-JAN-16:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15729.25 | 23-FEB-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20635.13 | 13-MAR-15:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39601.77 | 17-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39709.44 | 15-MAY-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38699.91 | 19-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34775.76 | 03-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39563.64 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38950.13 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37424.87 | 04-OCT-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17158.26 | 09-NOV-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12998.38 | 01-DEC-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11516.02 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39709.44 | 6198.29 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2422.45 | 26-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
February | 4341.71 | 23-FEB-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
March | 6689.86 | 29-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 81.73 | 0.00 |
April | 16165.68 | 16-APR-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.32 | 0.00 |
May | 16664.75 | 28-MAY-16:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 650.43 | 0.00 |
June | 17019.05 | 11-JUN-16:31 | 602.64 | 323.98 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 131.93 | 0.00 |
July | 16324.40 | 04-JUL-16:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 158.76 | 0.00 |
August | 15593.99 | 06-AUG-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 202.18 | 0.00 |
September | 13447.30 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
October | 15193.89 | 09-OCT-14:21 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 43.90 | 0.00 |
November | 4781.64 | 09-NOV-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
December | 2450.68 | 01-DEC-15:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2422.45 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17019.05 | 1306.65 | 711.15 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 650.43 | 15.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2068.53 | 26-JAN-14:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
February | 4124.55 | 23-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
March | 11484.81 | 12-MAR-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
April | 13215.17 | 16-APR-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
May | 13384.16 | 29-MAY-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 339.16 | 0.00 |
June | 13944.37 | 11-JUN-09:51 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 | 0.00 |
July | 12800.33 | 04-JUL-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 90.66 | 0.00 |
August | 11904.99 | 06-AUG-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 118.58 | 0.00 |
September | 8550.09 | 18-SEP-04:02 | 0.00 | 141.29 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 | 0.00 |
October | 12573.79 | 09-OCT-11:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
November | 4255.23 | 09-NOV-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
December | 2397.08 | 01-DEC-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2068.53 | 0.00 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13944.37 | 827.22 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.16 | 7.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8467.09 | 12-JAN-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 |
February | 17677.72 | 20-FEB-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
March | 17539.22 | 26-MAR-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 123.09 | 0.00 |
April | 17147.19 | 16-APR-14:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 84.46 | 0.00 |
May | 17030.45 | 28-MAY-15:11 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 718.17 | 0.00 |
June | 17201.95 | 11-JUN-15:51 | 602.64 | 323.98 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 142.89 | 0.00 |
July | 16528.09 | 04-JUL-16:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 159.30 | 0.00 |
August | 16503.72 | 06-AUG-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 235.10 | 0.00 |
September | 16952.78 | 24-SEP-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 166.96 | 0.00 |
October | 18971.93 | 09-OCT-13:01 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 0.00 |
November | 18508.38 | 05-NOV-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 | 0.00 |
December | 16681.46 | 03-DEC-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8467.09 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18971.93 | 1306.65 | 647.98 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 718.17 | 9.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3497.26 | 31-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 |
February | 6719.04 | 20-FEB-17:03 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
March | 14307.02 | 26-MAR-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 58.94 | 0.00 |
April | 14805.22 | 23-APR-15:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.00 |
May | 15469.77 | 28-MAY-16:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 393.45 | 0.00 |
June | 15612.49 | 11-JUN-16:31 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 0.00 |
July | 14651.24 | 09-JUL-15:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 95.75 | 0.00 |
August | 14063.12 | 06-AUG-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 112.83 | 0.00 |
September | 14012.28 | 24-SEP-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 113.64 | 0.00 |
October | 14637.66 | 09-OCT-14:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 | 0.00 |
November | 12375.37 | 05-NOV-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
December | 3941.54 | 01-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3497.26 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15612.49 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 393.45 | 19.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2141.00 | 26-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
February | 3467.65 | 24-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 0.00 |
March | 5089.59 | 29-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 | 0.00 |
April | 7641.66 | 17-APR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13629.20 | 29-MAY-18:21 | 0.00 | 368.65 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 0.00 |
June | 13609.55 | 11-JUN-16:21 | 669.60 | 359.98 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 | 0.00 |
July | 13553.30 | 04-JUL-17:01 | 0.00 | 323.98 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 85.01 | 0.00 |
August | 13243.54 | 27-AUG-16:52 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 0.00 |
September | 11118.19 | 24-SEP-15:11 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 0.00 |
October | 13105.58 | 01-OCT-14:41 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 55.95 | 0.00 |
November | 4517.63 | 09-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
December | 2645.79 | 01-DEC-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2141.00 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13629.20 | 1306.65 | 647.98 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 6.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2220.65 | 26-JAN-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
February | 3783.86 | 22-FEB-10:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
March | 8070.40 | 12-MAR-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
April | 10704.89 | 30-APR-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 | 0.00 |
May | 11643.46 | 29-MAY-09:01 | 381.52 | 205.11 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 181.40 | 0.00 |
June | 11360.49 | 11-JUN-10:21 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 | 0.00 |
July | 11244.64 | 04-JUL-09:41 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 | 0.00 |
August | 10793.57 | 06-AUG-12:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 | 0.00 |
September | 10956.39 | 24-SEP-11:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 0.00 |
October | 11330.50 | 01-OCT-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 0.00 |
November | 4415.26 | 13-NOV-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
December | 2977.77 | 01-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2220.65 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11643.46 | 827.22 | 410.22 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 181.40 | 10.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7965.35 | 08-JAN-13:43 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 |
February | 13977.49 | 20-FEB-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 |
March | 14079.28 | 26-MAR-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 78.26 | 0.00 |
April | 14565.73 | 27-APR-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13291.04 | 0.00 |
May | 15925.15 | 01-MAY-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15856.82 | 0.00 |
June | 16260.92 | 12-JUN-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 16260.98 | 0.00 |
July | 14824.46 | 03-JUL-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13327.34 | 0.00 |
August | 13978.79 | 07-AUG-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11311.78 | 0.00 |
September | 14387.78 | 24-SEP-11:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 | 0.00 |
October | 15600.17 | 01-OCT-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.54 | 0.00 |
November | 15251.13 | 12-NOV-13:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
December | 11411.71 | 03-DEC-11:43 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7965.35 | 200.88 | 107.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16260.92 | 468.72 | 359.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16260.98 | 31.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2895.59 | 31-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
February | 4465.31 | 20-FEB-16:33 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
March | 11388.88 | 26-MAR-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 0.00 |
April | 11789.13 | 30-APR-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 116.96 | 0.00 |
May | 12377.16 | 29-MAY-18:21 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 34.53 | 0.00 |
June | 12385.86 | 11-JUN-16:21 | 423.88 | 227.88 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 45.87 | 0.00 |
July | 12071.24 | 04-JUL-16:21 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 0.00 |
August | 11555.88 | 06-AUG-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 66.71 | 0.00 |
September | 11715.32 | 24-SEP-15:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 | 0.00 |
October | 12260.03 | 01-OCT-14:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 31.54 | 0.00 |
November | 10278.11 | 05-NOV-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
December | 3667.56 | 01-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2895.59 | 0.00 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12385.86 | 805.38 | 410.20 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 116.96 | 6.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2497.61 | 26-JAN-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
February | 4110.46 | 23-FEB-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 0.00 |
March | 6047.74 | 13-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 0.00 |
April | 13212.91 | 02-APR-16:41 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 241.45 | 0.00 |
May | 14387.05 | 29-MAY-18:21 | 0.00 | 368.65 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 86.03 | 0.00 |
June | 13953.39 | 04-JUN-16:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 223.08 | 0.00 |
July | 13779.13 | 02-JUL-09:12 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 233.93 | 0.00 |
August | 12299.50 | 06-AUG-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 | 0.00 |
September | 10882.55 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
October | 9560.05 | 01-OCT-15:31 | 535.68 | 287.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 | 0.00 |
November | 4454.30 | 09-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | 0.00 |
December | 2559.66 | 01-DEC-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2497.61 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14387.05 | 1306.65 | 647.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 241.45 | 11.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2378.34 | 26-JAN-11:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
February | 4340.80 | 22-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
March | 6663.98 | 28-MAR-10:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 0.00 |
April | 12172.25 | 16-APR-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 0.00 |
May | 12506.06 | 29-MAY-07:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 144.24 | 0.00 |
June | 11871.88 | 11-JUN-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 0.00 |
July | 12275.84 | 02-JUL-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 0.00 |
August | 11305.38 | 06-AUG-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 99.79 | 0.00 |
September | 8106.92 | 05-SEP-04:02 | 0.00 | 141.29 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
October | 12103.79 | 01-OCT-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 |
November | 4399.21 | 09-NOV-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
December | 2956.13 | 01-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2378.34 | 0.00 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12506.06 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 144.24 | 15.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8473.87 | 08-JAN-13:43 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 |
February | 14720.60 | 20-FEB-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 |
March | 14766.00 | 26-MAR-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 96.80 | 0.00 |
April | 14532.74 | 16-APR-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 0.00 |
May | 14678.74 | 29-MAY-15:01 | 669.60 | 359.98 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 325.24 | 0.00 |
June | 14144.77 | 04-JUN-16:11 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 243.25 | 0.00 |
July | 14013.79 | 04-JUL-15:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 133.23 | 0.00 |
August | 13991.69 | 06-AUG-16:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 169.47 | 0.00 |
September | 14572.64 | 24-SEP-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 140.49 | 0.00 |
October | 15549.91 | 01-OCT-12:51 | 535.68 | 287.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 76.28 | 0.00 |
November | 14886.55 | 11-NOV-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
December | 14680.72 | 03-DEC-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8473.87 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15549.91 | 669.60 | 359.98 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 325.24 | 49.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3495.26 | 31-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
February | 7132.08 | 20-FEB-16:33 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
March | 11176.89 | 26-MAR-15:02 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 96.13 | 0.00 |
April | 13392.08 | 02-APR-16:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 117.67 | 0.00 |
May | 13627.88 | 29-MAY-16:21 | 423.88 | 227.88 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 114.02 | 0.00 |
June | 13227.21 | 04-JUN-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 148.97 | 0.00 |
July | 13273.32 | 02-JUL-16:32 | 423.88 | 227.88 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 125.22 | 0.00 |
August | 12531.60 | 06-AUG-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 105.91 | 0.00 |
September | 12365.02 | 24-SEP-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 | 0.00 |
October | 12837.60 | 01-OCT-15:31 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 0.00 |
November | 5733.74 | 08-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 0.00 |
December | 3947.60 | 01-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3495.26 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13627.88 | 805.38 | 410.20 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 148.97 | 11.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.112749E+12 | 137293.01 | 02-JAN-07:10 | 0.116200E+11 | 23950.10 | 03-JAN-06:49 |
February | 0.108461E+12 | 114382.26 | 22-FEB-16:10 | 0.943518E+10 | 16061.45 | 02-FEB-06:10 |
March | 0.144917E+12 | 152830.85 | 28-MAR-15:00 | 0.102760E+11 | 9609.35 | 01-MAR-12:00 |
April | 0.167751E+12 | 176154.78 | 26-APR-15:20 | 0.924157E+10 | 9473.12 | 03-APR-11:20 |
May | 0.211935E+12 | 202758.48 | 01-MAY-15:09 | 0.925532E+10 | 9343.13 | 01-MAY-11:09 |
June | 0.219110E+12 | 206165.76 | 12-JUN-14:09 | 0.869453E+10 | 9214.18 | 02-JUN-11:20 |
July | 0.210233E+12 | 197285.97 | 10-JUL-13:00 | 0.858581E+10 | 9143.33 | 05-JUL-11:20 |
August | 0.212059E+12 | 193936.76 | 07-AUG-15:20 | 0.897116E+10 | 9198.05 | 30-AUG-11:20 |
September | 0.180479E+12 | 174470.42 | 14-SEP-15:20 | 0.876707E+10 | 9315.41 | 29-SEP-11:20 |
October | 0.157169E+12 | 165013.16 | 02-OCT-15:09 | 0.947622E+10 | 9458.07 | 31-OCT-11:00 |
November | 0.128891E+12 | 123646.03 | 09-NOV-13:50 | 0.964724E+10 | 9587.43 | 30-NOV-12:50 |
December | 0.112563E+12 | 102693.94 | 01-DEC-15:20 | 0.104339E+11 | 20221.98 | 21-DEC-06:40 |
Annual Sum or Average | 0.196632E+13 | 0.114404E+12 | ||||
Minimum of Months | 0.108461E+12 | 102693.94 | 0.858581E+10 | 9143.33 | ||
Maximum of Months | 0.219110E+12 | 206165.76 | 0.116200E+11 | 23950.10 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.254457E+11 | 0.518279E+10 | 0.593559E+11 | 0.988767E+09 | 0.476336E+10 | 12379742.02 | 0.384142E+10 | 0.131588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229394E+11 | 0.435602E+10 | 0.537310E+11 | 0.894783E+09 | 0.573143E+10 | 11196021.66 | 0.979720E+09 | 0.198173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269764E+11 | 0.436364E+10 | 0.617796E+11 | 0.103569E+10 | 0.104419E+11 | 12675672.10 | 0.102057E+09 | 0.402049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238945E+11 | 0.379987E+10 | 0.572952E+11 | 0.952009E+09 | 0.153356E+11 | 11960507.72 | 0.00 | 0.664620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257084E+11 | 0.355162E+10 | 0.605677E+11 | 0.101190E+10 | 0.197315E+11 | 12527707.06 | 0.00 | 0.101352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256243E+11 | 0.325331E+10 | 0.594895E+11 | 0.996267E+09 | 0.199110E+11 | 12231776.97 | 0.00 | 0.109823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.240857E+11 | 0.349586E+10 | 0.583622E+11 | 0.967663E+09 | 0.176798E+11 | 12256437.81 | 0.00 | 0.105630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.269680E+11 | 0.377888E+10 | 0.617796E+11 | 0.103573E+10 | 0.177874E+11 | 12675672.10 | 0.00 | 0.100697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241189E+11 | 0.401124E+10 | 0.572729E+11 | 0.951966E+09 | 0.146876E+11 | 11960507.72 | 0.00 | 0.794247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251942E+11 | 0.460280E+10 | 0.593671E+11 | 0.988722E+09 | 0.120594E+11 | 12379742.02 | 0.00 | 0.549443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251213E+11 | 0.490037E+10 | 0.580818E+11 | 0.970502E+09 | 0.813195E+10 | 12059151.09 | 0.185919E+09 | 0.314874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246925E+11 | 0.534314E+10 | 0.583511E+11 | 0.967930E+09 | 0.533492E+10 | 12256437.81 | 0.165496E+10 | 0.162061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300769E+12 | 0.506395E+11 | 0.705434E+12 | 0.117619E+11 | 0.151596E+12 | 0.146559E+09 | 0.676408E+10 | 0.739207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229394E+11 | 0.325331E+10 | 0.537310E+11 | 0.894783E+09 | 0.476336E+10 | 11196021.66 | 0.00 | 0.131588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.269764E+11 | 0.534314E+10 | 0.617796E+11 | 0.103573E+10 | 0.199110E+11 | 12675672.10 | 0.384142E+10 | 0.109823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.125640E+10 | 0.00 | 0.103636E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.138376E+09 | 0.00 | 0.929681E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.102760E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.924157E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.925532E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.869453E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.858581E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.897116E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.876707E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.947622E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2623160.69 | 0.00 | 0.964462E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.318487E+09 | 0.00 | 0.101154E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171589E+10 | 0.00 | 0.112688E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.858581E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.125640E+10 | 0.00 | 0.103636E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30940.97 | 18-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 848.10 | 18-JAN-08:20 | 6552.44 | 12-JAN-15:20 | 6.85 | 03-JAN-07:10 | 95048.95 | 02-JAN-07:10 |
February | 30940.97 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 848.10 | 10-FEB-08:20 | 12136.14 | 22-FEB-15:39 | 6.85 | 03-FEB-08:09 | 28971.78 | 02-FEB-07:10 |
March | 30821.00 | 14-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 847.94 | 14-MAR-07:19 | 19029.09 | 13-MAR-15:00 | 6.85 | 01-MAR-06:10 | 6531.70 | 01-MAR-07:19 |
April | 26819.30 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 842.58 | 03-APR-07:19 | 23475.24 | 17-APR-15:09 | 6.85 | 02-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 28290.68 | 24-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 844.55 | 24-MAY-07:19 | 26302.75 | 30-MAY-14:20 | 6.85 | 02-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 28290.68 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 844.55 | 23-JUN-07:19 | 27823.66 | 12-JUN-14:09 | 6.85 | 02-JUN-12:09 | 0.00 | 01-JUN-00:10 |
July | 30940.97 | 18-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 848.10 | 18-JUL-07:19 | 26173.98 | 05-JUL-14:30 | 6.85 | 02-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 30940.97 | 16-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 848.10 | 16-AUG-07:19 | 25041.30 | 07-AUG-15:20 | 6.85 | 06-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 30940.97 | 05-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 848.10 | 05-SEP-07:19 | 21915.32 | 25-SEP-15:50 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 11-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 850.39 | 11-OCT-07:19 | 18703.43 | 03-OCT-15:00 | 6.85 | 01-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 31751.76 | 27-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 845.57 | 03-NOV-07:19 | 13229.71 | 01-NOV-15:50 | 6.85 | 01-NOV-05:10 | 14866.54 | 27-NOV-07:10 |
December | 31791.75 | 29-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 846.68 | 29-DEC-16:00 | 9280.62 | 01-DEC-15:20 | 6.85 | 21-DEC-17:10 | 37160.04 | 23-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26819.30 | 5686.19 | 45864.70 | 842.58 | 6552.44 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 45864.70 | 850.39 | 27823.66 | 6.85 | 95048.95 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 22217.50 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35438.38 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66682.78 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89318.29 | 26-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113198.90 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116350.40 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106877.57 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100295.42 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86547.19 | 14-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80642.94 | 02-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45401.60 | 09-NOV-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26226.74 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22217.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 116350.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 137293.01 | 02-JAN-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 4010.46 | 6.85 | 95048.95 | 316.71 | 0.00 |
February | 114382.26 | 22-FEB-16:10 | 25761.06 | 42072.41 | 0.00 | 839.70 | 11977.54 | 6.85 | 0.00 | 33724.70 | 0.00 |
March | 152830.85 | 28-MAR-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 17548.03 | 6.85 | 0.00 | 66682.78 | 0.00 |
April | 176154.78 | 26-APR-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 18788.24 | 6.85 | 0.00 | 88766.50 | 0.00 |
May | 202758.48 | 01-MAY-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 20959.55 | 6.85 | 0.00 | 113198.90 | 0.00 |
June | 206165.76 | 12-JUN-14:09 | 25681.07 | 40588.47 | 0.00 | 839.16 | 27823.66 | 6.85 | 0.00 | 111226.54 | 0.00 |
July | 197285.97 | 10-JUL-13:00 | 25681.07 | 40588.47 | 0.00 | 839.16 | 24505.90 | 6.85 | 0.00 | 105664.51 | 0.00 |
August | 193936.76 | 07-AUG-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 25041.30 | 6.85 | 0.00 | 100295.42 | 0.00 |
September | 174470.42 | 14-SEP-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 19323.19 | 6.85 | 0.00 | 86547.19 | 0.00 |
October | 165013.16 | 02-OCT-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 16376.47 | 6.85 | 0.00 | 80036.65 | 0.00 |
November | 123646.03 | 09-NOV-13:50 | 25681.07 | 42402.18 | 0.00 | 839.81 | 9500.16 | 6.85 | 0.00 | 45215.95 | 0.00 |
December | 102693.94 | 01-DEC-15:20 | 25990.55 | 40588.47 | 0.00 | 839.44 | 9280.62 | 6.85 | 0.00 | 25988.01 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 102693.94 | 10880.98 | 21098.80 | 0.00 | 244.07 | 4010.46 | 6.85 | 0.00 | 316.71 | 0.00 | |
Maximum of Months | 206165.76 | 25990.55 | 42402.18 | 5686.19 | 839.81 | 27823.66 | 6.85 | 95048.95 | 113198.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 15545.43 | 03-JAN-06:00 | 0.00 | 9695.02 | 18-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 7530.41 | 02-FEB-06:10 | 0.00 | 9686.12 | 02-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9609.35 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9473.12 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9343.13 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9214.18 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9143.33 | 05-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9198.05 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9315.41 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9458.07 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 976.47 | 27-NOV-06:10 | 0.00 | 9587.43 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 12279.17 | 23-DEC-06:10 | 0.00 | 9676.80 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9143.33 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 15545.43 | 0.00 | 9695.02 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.20 | 0.00 | 26.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.90 | 0.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.73 | 3.83 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.80 | 9.00 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.74 | 6.17 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.74 | 9.83 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.67 | 6.00 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.46 | 3.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.90 | 0.17 | 18.90 | 61.50 | 27.68 | 39.17 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.90 | 0.17 | 18.90 | 16.50 | 27.80 | 9.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.88 | 0.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.33 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.95 | 10.33 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.20 | 12.17 | 28.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.93 | 8.67 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.93 | 12.00 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.91 | 7.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.77 | 5.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.70 | 7.33 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.88 | 0.17 | 18.88 | 86.67 | 27.91 | 65.17 | 27.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.88 | 0.17 | 18.88 | 18.67 | 28.20 | 12.17 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.10 | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 3.33 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.88 | 4.83 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.98 | 7.33 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.89 | 9.00 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.73 | 6.33 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.77 | 9.50 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.82 | 6.17 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.90 | 4.33 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.30 | 10.33 | 28.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.99 | 8.17 | 27.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
Annual Sum or Average | 0.17 | 19.10 | 0.17 | 19.10 | 95.50 | 27.87 | 70.33 | 27.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 | 0.00 | 19.10 |
Maximum of Months | 0.17 | 19.10 | 0.17 | 19.10 | 16.00 | 28.30 | 10.33 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.88 | 0.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.97 | 2.33 | 27.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.27 | 6.17 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.34 | 9.00 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.25 | 6.00 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.06 | 9.17 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.02 | 5.50 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.10 | 2.83 | 28.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.17 | 5.50 | 28.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.88 | 0.17 | 18.88 | 80.83 | 28.13 | 48.17 | 28.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.88 | 0.17 | 18.88 | 17.17 | 28.34 | 9.17 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.47 | 5.50 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.40 | 3.00 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.39 | 8.17 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.35 | 4.67 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.25 | 2.17 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.17 | 27.39 | 23.50 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.47 | 8.17 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.76 | 6.00 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.83 | 11.50 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.61 | 5.83 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.59 | 11.50 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.62 | 7.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.58 | 4.50 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.60 | 6.67 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.67 | 27.66 | 53.33 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.83 | 11.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.83 | 18.72 | 18.83 | 18.72 | 0.17 | 18.76 | 0.17 | 18.80 |
February | 9.33 | 19.49 | 9.33 | 19.49 | 3.00 | 20.62 | 3.00 | 21.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.77 | 14.33 | 25.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 26.04 | 42.67 | 26.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 26.63 | 58.67 | 26.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 26.39 | 59.17 | 26.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 26.23 | 44.00 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 25.92 | 41.17 | 25.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 25.68 | 48.00 | 25.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 25.66 | 73.67 | 25.63 |
November | 0.17 | 20.36 | 0.17 | 20.36 | 18.33 | 26.31 | 18.17 | 26.35 |
December | 13.00 | 19.78 | 13.00 | 19.78 | 2.67 | 20.50 | 2.67 | 21.10 |
Annual Sum or Average | 41.33 | 19.24 | 41.33 | 19.24 | 423.67 | 24.98 | 405.67 | 25.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 18.76 | 0.17 | 18.80 |
Maximum of Months | 18.83 | 20.36 | 18.83 | 20.36 | 76.33 | 26.63 | 73.67 | 26.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.63 | 1.00 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.91 | 4.33 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.02 | 7.17 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.72 | 5.33 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.68 | 8.33 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.66 | 5.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.78 | 3.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.89 | 5.00 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 71.83 | 27.79 | 40.17 | 27.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28.02 | 8.33 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.52 | 2.50 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.58 | 8.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.57 | 4.83 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.50 | 8.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.50 | 4.67 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.34 | 1.50 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.00 | 27.53 | 30.50 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.58 | 8.83 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.86 | 9.17 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.97 | 12.33 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.78 | 8.00 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.78 | 11.50 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.75 | 6.50 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.65 | 4.33 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.69 | 5.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 70.00 | 27.81 | 59.00 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.97 | 12.33 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 3.33 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.76 | 4.83 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.78 | 6.67 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.63 | 8.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.59 | 5.00 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.54 | 8.83 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.67 | 5.67 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.83 | 3.83 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.74 | 12.33 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.95 | 8.67 | 27.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 85.17 | 27.70 | 69.83 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.95 | 12.33 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.49 | 0.33 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 2.33 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.12 | 5.33 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.15 | 7.67 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.08 | 5.00 | 28.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.93 | 7.67 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.94 | 4.17 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.04 | 2.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.07 | 4.83 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 66.33 | 28.03 | 40.67 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.15 | 7.67 | 28.25 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.50 | 23.69 | 96.00 | 24.15 | 12.33 | 24.11 |
February | 21.67 | 23.81 | 201.17 | 24.54 | 0.00 | 24.54 |
March | 0.00 | 0.00 | 402.50 | 24.44 | 0.00 | 24.44 |
April | 0.00 | 0.00 | 440.17 | 24.45 | 0.00 | 24.45 |
May | 0.00 | 0.00 | 503.00 | 24.39 | 0.00 | 24.39 |
June | 0.00 | 0.00 | 496.00 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 497.00 | 24.40 | 0.00 | 24.40 |
August | 0.00 | 0.00 | 514.00 | 24.38 | 0.00 | 24.38 |
September | 0.00 | 0.00 | 485.00 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 502.00 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 395.50 | 24.48 | 0.00 | 24.48 |
December | 41.17 | 23.87 | 135.17 | 24.56 | 0.00 | 24.56 |
Annual Sum or Average | 191.33 | 23.75 | 4667.50 | 24.42 | 12.33 | 24.42 |
Minimum of Months | 0.00 | 0.00 | 96.00 | 24.15 | 0.00 | 24.11 |
Maximum of Months | 128.50 | 23.87 | 514.00 | 24.56 | 12.33 | 24.56 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.50 | 23.06 | 2.83 | 23.06 | 1.83 | 23.05 |
February | 190.50 | 23.31 | 75.67 | 23.62 | 0.00 | 23.62 |
March | 42.17 | 23.62 | 302.67 | 24.22 | 0.00 | 24.22 |
April | 0.00 | 0.00 | 411.17 | 24.35 | 0.00 | 24.35 |
May | 0.00 | 0.00 | 496.67 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 496.00 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.31 | 0.00 | 24.31 |
September | 2.83 | 27.15 | 485.00 | 24.38 | 2.83 | 24.39 |
October | 0.00 | 0.00 | 459.67 | 24.35 | 0.00 | 24.35 |
November | 71.50 | 23.53 | 213.00 | 24.16 | 0.00 | 24.16 |
December | 326.50 | 23.30 | 3.00 | 23.31 | 0.00 | 23.31 |
Annual Sum or Average | 1053.00 | 23.25 | 3956.67 | 24.10 | 4.67 | 24.10 |
Minimum of Months | 0.00 | 0.00 | 2.83 | 23.06 | 0.00 | 23.05 |
Maximum of Months | 419.50 | 27.15 | 514.00 | 24.38 | 2.83 | 24.39 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.17 | 22.28 | 18.50 | 22.18 | 18.50 | 22.09 |
February | 303.17 | 22.89 | 45.50 | 23.05 | 0.00 | 23.05 |
March | 117.83 | 23.40 | 244.00 | 23.95 | 0.00 | 23.95 |
April | 5.50 | 23.87 | 395.83 | 24.38 | 0.50 | 24.38 |
May | 1.33 | 26.58 | 505.33 | 24.37 | 1.33 | 24.38 |
June | 1.33 | 26.48 | 496.00 | 24.33 | 1.33 | 24.34 |
July | 0.17 | 26.49 | 497.00 | 24.40 | 0.17 | 24.40 |
August | 0.00 | 0.00 | 514.00 | 24.34 | 0.00 | 24.34 |
September | 1.83 | 27.15 | 481.83 | 24.38 | 1.83 | 24.39 |
October | 24.67 | 23.33 | 398.17 | 24.26 | 0.00 | 24.26 |
November | 212.67 | 23.22 | 126.00 | 23.55 | 0.00 | 23.55 |
December | 433.83 | 22.58 | 7.33 | 22.55 | 7.33 | 22.52 |
Annual Sum or Average | 1575.50 | 22.73 | 3729.50 | 23.84 | 31.00 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 7.33 | 22.18 | 0.00 | 22.09 |
Maximum of Months | 473.17 | 27.15 | 514.00 | 24.40 | 18.50 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.67 | 21.44 | 86.33 | 21.20 | 86.33 | 21.02 |
February | 357.67 | 22.23 | 64.50 | 22.33 | 20.00 | 22.23 |
March | 169.17 | 22.92 | 237.50 | 23.67 | 0.33 | 23.67 |
April | 38.50 | 24.77 | 413.33 | 24.53 | 14.83 | 24.61 |
May | 45.50 | 26.81 | 508.00 | 24.75 | 45.50 | 24.91 |
June | 53.83 | 26.52 | 496.00 | 24.72 | 53.83 | 24.88 |
July | 104.67 | 26.38 | 497.00 | 24.95 | 104.67 | 25.16 |
August | 73.83 | 26.24 | 514.00 | 24.71 | 73.83 | 24.88 |
September | 57.50 | 26.16 | 482.17 | 24.67 | 57.50 | 24.81 |
October | 76.83 | 23.33 | 362.33 | 24.17 | 6.67 | 24.21 |
November | 294.50 | 22.62 | 120.17 | 23.01 | 4.33 | 22.98 |
December | 481.67 | 21.78 | 61.00 | 21.58 | 61.00 | 21.41 |
Annual Sum or Average | 2246.33 | 22.77 | 3842.33 | 23.72 | 528.83 | 23.77 |
Minimum of Months | 38.50 | 21.44 | 61.00 | 21.20 | 0.33 | 21.02 |
Maximum of Months | 492.67 | 26.81 | 514.00 | 24.95 | 104.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.33 | 21.82 | 54.83 | 21.60 | 54.83 | 21.43 |
February | 276.17 | 22.34 | 110.83 | 22.74 | 13.33 | 22.65 |
March | 128.17 | 23.13 | 316.83 | 23.98 | 8.17 | 24.03 |
April | 54.67 | 25.84 | 439.00 | 24.72 | 37.50 | 24.88 |
May | 57.83 | 26.98 | 507.17 | 24.85 | 57.83 | 25.04 |
June | 57.17 | 26.69 | 496.00 | 24.76 | 57.17 | 24.94 |
July | 105.67 | 26.48 | 497.00 | 24.97 | 105.67 | 25.20 |
August | 73.83 | 26.38 | 514.00 | 24.74 | 73.83 | 24.92 |
September | 63.67 | 26.27 | 481.50 | 24.70 | 63.67 | 24.87 |
October | 87.50 | 24.27 | 393.67 | 24.44 | 31.00 | 24.58 |
November | 208.67 | 22.59 | 204.83 | 23.39 | 3.33 | 23.37 |
December | 432.83 | 22.08 | 42.50 | 21.91 | 40.50 | 21.75 |
Annual Sum or Average | 2026.50 | 23.16 | 4058.17 | 23.97 | 546.83 | 24.08 |
Minimum of Months | 54.67 | 21.82 | 42.50 | 21.60 | 3.33 | 21.43 |
Maximum of Months | 480.33 | 26.98 | 514.00 | 24.97 | 105.67 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.83 | 21.73 | 145.50 | 22.09 | 49.50 | 21.87 |
February | 229.17 | 22.45 | 178.83 | 23.23 | 20.17 | 23.21 |
March | 133.83 | 23.44 | 311.50 | 24.10 | 18.00 | 24.21 |
April | 50.67 | 25.46 | 421.67 | 24.66 | 28.50 | 24.80 |
May | 44.83 | 26.87 | 507.67 | 24.75 | 44.83 | 24.91 |
June | 52.17 | 26.51 | 496.00 | 24.71 | 52.17 | 24.87 |
July | 102.67 | 26.38 | 497.00 | 24.94 | 102.67 | 25.15 |
August | 74.00 | 26.30 | 514.00 | 24.73 | 74.00 | 24.90 |
September | 63.00 | 26.33 | 483.50 | 24.73 | 63.00 | 24.90 |
October | 89.17 | 24.92 | 411.00 | 24.63 | 41.33 | 24.81 |
November | 187.00 | 23.33 | 260.33 | 24.05 | 28.00 | 24.22 |
December | 273.83 | 21.98 | 176.50 | 22.67 | 34.50 | 22.49 |
Annual Sum or Average | 1621.17 | 23.47 | 4403.50 | 24.18 | 556.67 | 24.29 |
Minimum of Months | 44.83 | 21.73 | 145.50 | 22.09 | 18.00 | 21.87 |
Maximum of Months | 320.83 | 26.87 | 514.00 | 24.94 | 102.67 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 438.50 | 21.42 | 90.33 | 21.25 | 77.83 | 21.07 |
February | 318.83 | 22.07 | 113.33 | 22.48 | 19.83 | 22.39 |
March | 175.83 | 22.94 | 269.33 | 23.77 | 8.83 | 23.83 |
April | 58.00 | 25.11 | 420.17 | 24.62 | 28.50 | 24.76 |
May | 51.83 | 26.98 | 506.17 | 24.79 | 51.83 | 24.98 |
June | 60.50 | 26.67 | 496.00 | 24.76 | 60.50 | 24.95 |
July | 101.00 | 26.41 | 497.00 | 24.93 | 101.00 | 25.14 |
August | 74.00 | 26.33 | 514.00 | 24.71 | 74.00 | 24.89 |
September | 59.67 | 26.22 | 475.00 | 24.68 | 59.67 | 24.83 |
October | 102.67 | 23.75 | 359.67 | 24.28 | 22.50 | 24.41 |
November | 276.17 | 22.52 | 167.67 | 23.16 | 7.67 | 23.16 |
December | 416.67 | 21.67 | 90.17 | 21.63 | 57.67 | 21.46 |
Annual Sum or Average | 2133.67 | 22.87 | 3998.83 | 23.81 | 569.83 | 23.89 |
Minimum of Months | 51.83 | 21.42 | 90.17 | 21.25 | 7.67 | 21.07 |
Maximum of Months | 438.50 | 26.98 | 514.00 | 24.93 | 101.00 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.83 | 22.24 | 7.00 | 22.21 | 7.00 | 22.17 |
February | 350.67 | 22.76 | 32.17 | 22.88 | 0.00 | 22.88 |
March | 156.50 | 23.26 | 214.00 | 23.78 | 0.00 | 23.78 |
April | 15.50 | 23.82 | 400.50 | 24.40 | 1.00 | 24.41 |
May | 22.33 | 26.75 | 508.00 | 24.62 | 22.33 | 24.71 |
June | 36.33 | 26.42 | 496.00 | 24.63 | 36.33 | 24.75 |
July | 77.33 | 26.49 | 497.00 | 24.90 | 77.33 | 25.09 |
August | 51.33 | 26.48 | 514.00 | 24.70 | 51.33 | 24.85 |
September | 45.33 | 26.51 | 485.00 | 24.72 | 45.33 | 24.86 |
October | 5.00 | 24.11 | 467.50 | 24.40 | 0.83 | 24.41 |
November | 149.00 | 23.34 | 191.00 | 23.80 | 0.00 | 23.80 |
December | 428.33 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Annual Sum or Average | 1827.50 | 23.19 | 3812.17 | 24.05 | 241.50 | 24.15 |
Minimum of Months | 5.00 | 22.24 | 0.00 | 22.21 | 0.00 | 22.17 |
Maximum of Months | 489.83 | 26.75 | 514.00 | 24.90 | 77.33 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.83 | 22.61 | 19.67 | 22.58 | 14.50 | 22.54 |
February | 223.33 | 22.86 | 110.67 | 23.33 | 0.00 | 23.33 |
March | 89.17 | 23.28 | 323.83 | 24.10 | 0.67 | 24.10 |
April | 24.83 | 26.26 | 443.67 | 24.64 | 19.50 | 24.73 |
May | 49.67 | 26.91 | 508.00 | 24.80 | 49.67 | 24.98 |
June | 46.83 | 26.68 | 496.00 | 24.72 | 46.83 | 24.87 |
July | 87.00 | 26.63 | 497.00 | 24.96 | 87.00 | 25.18 |
August | 60.50 | 26.62 | 514.00 | 24.76 | 60.50 | 24.94 |
September | 48.17 | 26.64 | 485.00 | 24.77 | 48.17 | 24.92 |
October | 26.17 | 26.65 | 484.67 | 24.64 | 24.17 | 24.74 |
November | 79.00 | 23.32 | 307.67 | 24.14 | 0.00 | 24.14 |
December | 305.17 | 22.88 | 26.33 | 23.00 | 0.00 | 23.00 |
Annual Sum or Average | 1466.67 | 23.73 | 4216.50 | 24.31 | 351.00 | 24.44 |
Minimum of Months | 24.83 | 22.61 | 19.67 | 22.58 | 0.00 | 22.54 |
Maximum of Months | 426.83 | 26.91 | 514.00 | 24.96 | 87.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 313.50 | 22.30 | 122.00 | 22.68 | 27.00 | 22.55 |
February | 169.00 | 22.45 | 190.67 | 23.53 | 6.17 | 23.53 |
March | 89.67 | 23.06 | 331.17 | 24.15 | 7.00 | 24.20 |
April | 35.67 | 25.47 | 433.17 | 24.76 | 25.67 | 24.85 |
May | 99.50 | 25.81 | 508.00 | 24.99 | 99.50 | 25.11 |
June | 163.50 | 25.28 | 496.00 | 24.92 | 163.50 | 24.99 |
July | 264.83 | 25.04 | 497.00 | 24.88 | 264.83 | 24.92 |
August | 280.17 | 24.80 | 514.00 | 24.71 | 280.17 | 24.73 |
September | 209.50 | 25.00 | 485.00 | 24.83 | 209.50 | 24.87 |
October | 90.83 | 25.73 | 487.33 | 24.96 | 85.33 | 25.09 |
November | 79.33 | 24.11 | 379.83 | 24.56 | 29.67 | 24.71 |
December | 218.17 | 22.69 | 179.67 | 23.58 | 3.67 | 23.57 |
Annual Sum or Average | 2013.67 | 24.07 | 4623.83 | 24.50 | 1202.00 | 24.60 |
Minimum of Months | 35.67 | 22.30 | 122.00 | 22.68 | 3.67 | 22.55 |
Maximum of Months | 313.50 | 25.81 | 514.00 | 24.99 | 280.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.33 | 22.33 | 28.67 | 22.35 | 14.17 | 22.31 |
February | 282.17 | 22.74 | 97.33 | 23.15 | 0.00 | 23.15 |
March | 115.67 | 23.29 | 292.83 | 24.01 | 2.50 | 24.03 |
April | 22.33 | 26.27 | 440.83 | 24.60 | 17.50 | 24.69 |
May | 41.33 | 26.94 | 508.00 | 24.76 | 41.33 | 24.92 |
June | 52.00 | 26.75 | 496.00 | 24.76 | 52.00 | 24.93 |
July | 86.33 | 26.60 | 497.00 | 24.95 | 86.33 | 25.16 |
August | 62.00 | 26.63 | 514.00 | 24.76 | 62.00 | 24.95 |
September | 52.33 | 26.65 | 485.00 | 24.79 | 52.33 | 24.96 |
October | 22.00 | 26.67 | 479.67 | 24.60 | 19.83 | 24.70 |
November | 103.50 | 23.33 | 271.83 | 24.06 | 1.17 | 24.07 |
December | 361.00 | 22.77 | 57.00 | 22.97 | 0.00 | 22.97 |
Annual Sum or Average | 1622.00 | 23.53 | 4168.17 | 24.24 | 349.17 | 24.36 |
Minimum of Months | 22.00 | 22.33 | 28.67 | 22.35 | 0.00 | 22.31 |
Maximum of Months | 421.33 | 26.94 | 514.00 | 24.95 | 86.33 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.33 | 22.04 | 31.00 | 21.92 | 31.00 | 21.81 |
February | 311.17 | 22.71 | 54.17 | 22.92 | 0.00 | 22.92 |
March | 112.17 | 23.30 | 268.50 | 23.95 | 0.00 | 23.95 |
April | 10.67 | 26.07 | 428.67 | 24.54 | 7.83 | 24.59 |
May | 40.00 | 26.76 | 508.00 | 24.73 | 40.00 | 24.87 |
June | 50.67 | 26.44 | 496.00 | 24.70 | 50.67 | 24.85 |
July | 103.83 | 26.37 | 497.00 | 24.95 | 103.83 | 25.16 |
August | 73.50 | 26.19 | 514.00 | 24.71 | 73.50 | 24.88 |
September | 57.50 | 26.20 | 485.00 | 24.69 | 57.50 | 24.83 |
October | 25.33 | 23.55 | 427.17 | 24.32 | 1.83 | 24.33 |
November | 213.83 | 23.11 | 139.33 | 23.50 | 0.00 | 23.50 |
December | 439.67 | 22.36 | 8.83 | 22.32 | 8.83 | 22.28 |
Annual Sum or Average | 1922.67 | 23.19 | 3857.67 | 24.02 | 375.00 | 24.12 |
Minimum of Months | 10.67 | 22.04 | 8.83 | 21.92 | 0.00 | 21.81 |
Maximum of Months | 484.33 | 26.76 | 514.00 | 24.95 | 103.83 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.17 | 22.19 | 22.17 | 22.07 | 22.17 | 21.96 |
February | 219.67 | 22.66 | 85.17 | 23.16 | 0.17 | 23.15 |
March | 88.83 | 23.43 | 268.17 | 24.18 | 5.83 | 24.22 |
April | 38.83 | 26.48 | 372.50 | 24.86 | 33.50 | 25.02 |
May | 55.33 | 26.92 | 430.00 | 24.96 | 55.33 | 25.16 |
June | 52.83 | 26.61 | 418.00 | 24.85 | 52.83 | 25.03 |
July | 101.83 | 26.45 | 422.00 | 25.10 | 101.83 | 25.32 |
August | 72.33 | 26.32 | 433.00 | 24.84 | 72.33 | 25.02 |
September | 62.00 | 26.32 | 410.00 | 24.83 | 62.00 | 25.00 |
October | 48.17 | 25.09 | 363.33 | 24.65 | 25.33 | 24.77 |
November | 155.50 | 22.99 | 174.50 | 23.74 | 0.00 | 23.74 |
December | 335.67 | 22.42 | 11.67 | 22.42 | 6.50 | 22.38 |
Annual Sum or Average | 1626.17 | 23.55 | 3410.50 | 24.25 | 437.83 | 24.40 |
Minimum of Months | 38.83 | 22.19 | 11.67 | 22.07 | 0.00 | 21.96 |
Maximum of Months | 395.17 | 26.92 | 433.00 | 25.10 | 101.83 | 25.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 289.00 | 22.33 | 130.50 | 22.88 | 9.50 | 22.81 |
February | 184.50 | 22.96 | 189.50 | 23.76 | 7.67 | 23.83 |
March | 84.83 | 23.93 | 347.83 | 24.30 | 15.50 | 24.39 |
April | 26.17 | 26.77 | 439.67 | 24.69 | 24.33 | 24.80 |
May | 42.17 | 26.79 | 508.00 | 24.75 | 42.17 | 24.89 |
June | 49.00 | 26.43 | 496.00 | 24.69 | 49.00 | 24.83 |
July | 101.50 | 26.36 | 497.00 | 24.94 | 101.50 | 25.14 |
August | 73.50 | 26.25 | 514.00 | 24.73 | 73.50 | 24.90 |
September | 61.17 | 26.37 | 485.00 | 24.75 | 61.17 | 24.92 |
October | 58.17 | 26.12 | 453.33 | 24.76 | 43.50 | 24.94 |
November | 127.83 | 24.03 | 301.17 | 24.41 | 28.33 | 24.58 |
December | 235.50 | 22.64 | 170.17 | 23.45 | 6.00 | 23.46 |
Annual Sum or Average | 1333.33 | 23.99 | 4532.17 | 24.41 | 462.17 | 24.56 |
Minimum of Months | 26.17 | 22.33 | 130.50 | 22.88 | 6.00 | 22.81 |
Maximum of Months | 289.00 | 26.79 | 514.00 | 24.94 | 101.50 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.67 | 21.94 | 46.67 | 21.90 | 29.17 | 21.79 |
February | 284.83 | 22.54 | 104.67 | 23.04 | 0.67 | 23.04 |
March | 119.33 | 23.32 | 305.83 | 24.03 | 7.17 | 24.08 |
April | 32.50 | 26.14 | 444.33 | 24.65 | 24.33 | 24.76 |
May | 49.50 | 26.95 | 508.00 | 24.79 | 49.50 | 24.97 |
June | 56.17 | 26.62 | 496.00 | 24.74 | 56.17 | 24.91 |
July | 103.67 | 26.38 | 497.00 | 24.94 | 103.67 | 25.15 |
August | 72.17 | 26.27 | 514.00 | 24.71 | 72.17 | 24.88 |
September | 57.33 | 26.29 | 485.00 | 24.69 | 57.33 | 24.85 |
October | 52.50 | 24.69 | 423.50 | 24.47 | 21.17 | 24.58 |
November | 201.83 | 22.98 | 191.00 | 23.62 | 2.17 | 23.64 |
December | 391.50 | 22.26 | 56.00 | 22.41 | 9.67 | 22.37 |
Annual Sum or Average | 1844.00 | 23.29 | 4072.00 | 24.09 | 433.17 | 24.22 |
Minimum of Months | 32.50 | 21.94 | 46.67 | 21.90 | 0.67 | 21.79 |
Maximum of Months | 422.67 | 26.95 | 514.00 | 24.94 | 103.67 | 25.15 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16873 | 36.90427 | 0.35113 | 7.79743 |
February | 454.00000 | 24.32419 | 38.78723 | 0.43242 | 9.13116 |
March | 514.00000 | 24.35290 | 43.00275 | 0.50259 | 10.50605 |
April | 485.00000 | 24.40772 | 44.21951 | 0.54343 | 11.43081 |
May | 508.00000 | 24.38894 | 50.08787 | -0.2510 | 6.75202 |
June | 496.00000 | 24.34827 | 52.65713 | -0.2456 | 6.66838 |
July | 497.00000 | 24.40301 | 54.01955 | -0.2250 | 6.53290 |
August | 514.00000 | 24.38028 | 54.06153 | -0.2284 | 6.59497 |
September | 485.00000 | 24.44761 | 53.64085 | -0.2156 | 6.59452 |
October | 502.00000 | 24.46446 | 48.53207 | 0.58370 | 12.40787 |
November | 489.00000 | 24.40016 | 42.04096 | 0.50248 | 10.49876 |
December | 497.00000 | 24.27972 | 36.06912 | 0.39511 | 8.42256 |
Annual Sum or Average | 5943.00000 | 24.36380 | 46.23026 | 0.17608 | 8.60258 |
Minimum of Months | 454.00000 | 24.16873 | 36.06912 | -0.2510 | 6.53290 |
Maximum of Months | 514.00000 | 24.46446 | 54.06153 | 0.58370 | 12.40787 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.22668 | 39.83739 | 0.12284 | 5.94490 |
February | 454.00000 | 23.80050 | 40.49743 | 0.29511 | 7.26565 |
March | 514.00000 | 24.14936 | 44.06663 | 0.44019 | 9.27588 |
April | 485.00000 | 24.30356 | 45.82363 | 0.51546 | 10.77361 |
May | 508.00000 | 24.31463 | 52.19519 | -0.2772 | 6.95190 |
June | 496.00000 | 24.27879 | 55.06996 | -0.2700 | 6.81908 |
July | 497.00000 | 24.34627 | 56.31091 | -0.2465 | 6.67220 |
August | 514.00000 | 24.31307 | 56.61814 | -0.2576 | 6.77701 |
September | 485.00000 | 24.36231 | 56.03608 | -0.2542 | 6.88441 |
October | 502.00000 | 24.31413 | 49.66447 | 0.53402 | 11.16622 |
November | 489.00000 | 24.08742 | 42.79373 | 0.40364 | 8.63912 |
December | 497.00000 | 23.56508 | 37.93789 | 0.20832 | 6.34261 |
Annual Sum or Average | 5943.00000 | 24.09025 | 48.13518 | 0.09894 | 7.79243 |
Minimum of Months | 454.00000 | 23.22668 | 37.93789 | -0.2772 | 5.94490 |
Maximum of Months | 514.00000 | 24.36231 | 56.61814 | 0.53402 | 11.16622 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.37913 | 41.07535 | -0.0862 | 6.50846 |
February | 454.00000 | 23.27779 | 40.97949 | 0.16413 | 6.59258 |
March | 514.00000 | 23.98143 | 43.29648 | 0.39393 | 8.66952 |
April | 485.00000 | 24.31405 | 45.23686 | 0.52579 | 11.07781 |
May | 508.00000 | 24.36237 | 51.83158 | -0.2355 | 6.65171 |
June | 496.00000 | 24.32640 | 54.82290 | -0.2264 | 6.50965 |
July | 497.00000 | 24.39646 | 56.23677 | -0.2074 | 6.46573 |
August | 514.00000 | 24.34264 | 56.65412 | -0.2300 | 6.59126 |
September | 485.00000 | 24.36407 | 55.93453 | -0.2437 | 6.81324 |
October | 502.00000 | 24.20298 | 49.18645 | 0.50291 | 10.56740 |
November | 489.00000 | 23.69473 | 42.85370 | 0.29913 | 7.45560 |
December | 497.00000 | 22.75877 | 39.05133 | 0.00850 | 6.13517 |
Annual Sum or Average | 5943.00000 | 23.87088 | 48.15667 | 0.05389 | 7.50507 |
Minimum of Months | 454.00000 | 22.37913 | 39.05133 | -0.2437 | 6.13517 |
Maximum of Months | 514.00000 | 24.39646 | 56.65412 | 0.52579 | 11.07781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49048 | 44.42096 | -0.3013 | 8.84278 |
February | 454.00000 | 22.60960 | 43.82626 | 0.01046 | 7.06275 |
March | 514.00000 | 23.74108 | 44.49130 | 0.34849 | 8.70237 |
April | 485.00000 | 24.40502 | 45.14797 | 0.58320 | 12.86493 |
May | 508.00000 | 24.56507 | 51.62879 | -0.0808 | 6.51010 |
June | 496.00000 | 24.52621 | 54.89153 | -0.0599 | 6.34022 |
July | 497.00000 | 24.64515 | 57.01701 | -0.0334 | 6.82421 |
August | 514.00000 | 24.49461 | 57.42228 | -0.1029 | 6.52380 |
September | 485.00000 | 24.48242 | 57.16367 | -0.1477 | 6.74683 |
October | 502.00000 | 24.11139 | 49.73575 | 0.49492 | 10.95784 |
November | 489.00000 | 23.17707 | 44.74362 | 0.17801 | 7.21585 |
December | 497.00000 | 21.84607 | 41.94901 | -0.2105 | 7.83647 |
Annual Sum or Average | 5943.00000 | 23.68235 | 49.41744 | 0.05627 | 8.03486 |
Minimum of Months | 454.00000 | 21.49048 | 41.94901 | -0.3013 | 6.34022 |
Maximum of Months | 514.00000 | 24.64515 | 57.42228 | 0.58320 | 12.86493 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.91037 | 43.66388 | -0.1812 | 7.79067 |
February | 454.00000 | 23.03864 | 42.63439 | 0.13689 | 7.56036 |
March | 514.00000 | 23.94157 | 43.70572 | 0.43999 | 10.42515 |
April | 485.00000 | 24.49644 | 44.78274 | 0.66820 | 15.41406 |
May | 508.00000 | 24.60048 | 51.41817 | 0.01107 | 6.86107 |
June | 496.00000 | 24.53433 | 54.77124 | -0.0050 | 6.50528 |
July | 497.00000 | 24.65584 | 56.90410 | 0.00511 | 7.09658 |
August | 514.00000 | 24.49986 | 57.34601 | -0.0701 | 6.59902 |
September | 485.00000 | 24.48863 | 57.02234 | -0.1002 | 6.69813 |
October | 502.00000 | 24.24628 | 49.20627 | 0.56814 | 12.97559 |
November | 489.00000 | 23.50906 | 43.67385 | 0.28547 | 8.41773 |
December | 497.00000 | 22.32094 | 40.97735 | -0.0817 | 7.24900 |
Annual Sum or Average | 5943.00000 | 23.85938 | 48.89508 | 0.13910 | 8.63031 |
Minimum of Months | 454.00000 | 21.91037 | 40.97735 | -0.1812 | 6.50528 |
Maximum of Months | 514.00000 | 24.65584 | 57.34601 | 0.66820 | 15.41406 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.63626 | 40.95422 | 0.01306 | 8.73032 |
February | 454.00000 | 23.36726 | 41.25500 | 0.24003 | 9.37868 |
March | 514.00000 | 23.98517 | 43.34608 | 0.46337 | 11.19070 |
April | 485.00000 | 24.46254 | 44.82266 | 0.63366 | 14.42224 |
May | 508.00000 | 24.56498 | 51.58985 | -0.0698 | 6.57691 |
June | 496.00000 | 24.52039 | 54.90482 | -0.0637 | 6.35882 |
July | 497.00000 | 24.64170 | 57.00847 | -0.0325 | 6.84921 |
August | 514.00000 | 24.50351 | 57.30921 | -0.0867 | 6.58282 |
September | 485.00000 | 24.52502 | 56.79347 | -0.0873 | 6.78878 |
October | 502.00000 | 24.36249 | 48.56831 | 0.63184 | 14.99967 |
November | 489.00000 | 23.87821 | 42.05834 | 0.42875 | 11.61341 |
December | 497.00000 | 23.07072 | 38.36441 | 0.12596 | 8.95256 |
Annual Sum or Average | 5943.00000 | 24.04760 | 48.14033 | 0.18179 | 9.35904 |
Minimum of Months | 454.00000 | 22.63626 | 38.36441 | -0.0873 | 6.35882 |
Maximum of Months | 514.00000 | 24.64170 | 57.30921 | 0.63366 | 14.99967 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.75323 | 43.64871 | -0.2196 | 8.80917 |
February | 454.00000 | 22.70994 | 43.23128 | 0.06219 | 7.92540 |
March | 514.00000 | 23.73836 | 44.19164 | 0.39215 | 10.03484 |
April | 485.00000 | 24.42288 | 44.99333 | 0.64403 | 14.91203 |
May | 508.00000 | 24.56602 | 51.55402 | -0.0153 | 7.03890 |
June | 496.00000 | 24.52524 | 54.84417 | -0.0028 | 6.74119 |
July | 497.00000 | 24.62517 | 57.03625 | -0.0115 | 7.08324 |
August | 514.00000 | 24.48156 | 57.44295 | -0.0795 | 6.66635 |
September | 485.00000 | 24.46428 | 57.11998 | -0.1092 | 6.89535 |
October | 502.00000 | 24.11197 | 49.57208 | 0.53496 | 12.43079 |
November | 489.00000 | 23.23441 | 44.21639 | 0.22815 | 8.41229 |
December | 497.00000 | 22.06297 | 41.12640 | -0.1385 | 8.06126 |
Annual Sum or Average | 5943.00000 | 23.73206 | 49.13171 | 0.10678 | 8.74666 |
Minimum of Months | 454.00000 | 21.75323 | 41.12640 | -0.2196 | 6.66635 |
Maximum of Months | 514.00000 | 24.62517 | 57.44295 | 0.64403 | 14.91203 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.28096 | 43.45183 | -0.0947 | 6.23333 |
February | 454.00000 | 23.04534 | 43.98529 | 0.11475 | 6.35190 |
March | 514.00000 | 23.84110 | 45.71786 | 0.35589 | 8.17700 |
April | 485.00000 | 24.33600 | 44.96850 | 0.52719 | 11.15789 |
May | 508.00000 | 24.52558 | 50.31927 | -0.1538 | 6.40035 |
June | 496.00000 | 24.50403 | 52.90727 | -0.1137 | 6.18280 |
July | 497.00000 | 24.64729 | 54.39621 | -0.0575 | 6.51305 |
August | 514.00000 | 24.52293 | 54.47833 | -0.1026 | 6.32769 |
September | 485.00000 | 24.55541 | 54.41036 | -0.1245 | 6.45672 |
October | 502.00000 | 24.37259 | 49.35938 | 0.56726 | 12.04511 |
November | 489.00000 | 23.86599 | 44.62815 | 0.35561 | 8.06249 |
December | 497.00000 | 22.89390 | 41.00450 | 0.05468 | 5.91627 |
Annual Sum or Average | 5943.00000 | 23.95516 | 48.34287 | 0.10984 | 7.48713 |
Minimum of Months | 454.00000 | 22.28096 | 41.00450 | -0.1538 | 5.91627 |
Maximum of Months | 514.00000 | 24.64729 | 54.47833 | 0.56726 | 12.04511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.81813 | 42.38429 | 0.04966 | 6.14722 |
February | 454.00000 | 23.51975 | 42.52280 | 0.25331 | 7.41327 |
March | 514.00000 | 24.07611 | 44.61670 | 0.45659 | 10.05421 |
April | 485.00000 | 24.49230 | 44.29039 | 0.62762 | 13.92132 |
May | 508.00000 | 24.59798 | 49.92829 | -0.0464 | 6.39969 |
June | 496.00000 | 24.53350 | 52.69668 | -0.0501 | 6.18686 |
July | 497.00000 | 24.66928 | 54.26746 | -0.0137 | 6.70634 |
August | 514.00000 | 24.53979 | 54.39267 | -0.0646 | 6.35086 |
September | 485.00000 | 24.58026 | 54.21992 | -0.0696 | 6.35521 |
October | 502.00000 | 24.50598 | 48.78682 | 0.64260 | 14.25347 |
November | 489.00000 | 24.11357 | 43.61528 | 0.44910 | 9.76469 |
December | 497.00000 | 23.34546 | 39.76361 | 0.18005 | 6.55137 |
Annual Sum or Average | 5943.00000 | 24.15323 | 47.67020 | 0.19998 | 8.33869 |
Minimum of Months | 454.00000 | 22.81813 | 39.76361 | -0.0696 | 6.14722 |
Maximum of Months | 514.00000 | 24.66928 | 54.39267 | 0.64260 | 14.25347 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.03740 | 39.95600 | 0.15466 | 7.70719 |
February | 454.00000 | 23.64328 | 41.32545 | 0.32432 | 9.23172 |
March | 514.00000 | 24.09220 | 43.83960 | 0.47662 | 10.83654 |
April | 485.00000 | 24.60247 | 43.91930 | 0.61959 | 13.81216 |
May | 508.00000 | 24.83001 | 51.59883 | -0.0471 | 6.54313 |
June | 496.00000 | 24.79649 | 56.27749 | -0.0102 | 6.40526 |
July | 497.00000 | 24.79809 | 60.32915 | 0.03016 | 6.51287 |
August | 514.00000 | 24.66109 | 61.72778 | 0.00390 | 6.25446 |
September | 485.00000 | 24.75476 | 59.23394 | 0.02094 | 6.41470 |
October | 502.00000 | 24.76381 | 49.17419 | 0.74811 | 17.79557 |
November | 489.00000 | 24.33489 | 42.05613 | 0.57090 | 13.20236 |
December | 497.00000 | 23.66239 | 37.56069 | 0.31157 | 8.90976 |
Annual Sum or Average | 5943.00000 | 24.33536 | 48.98849 | 0.26554 | 9.45823 |
Minimum of Months | 454.00000 | 23.03740 | 37.56069 | -0.0471 | 6.25446 |
Maximum of Months | 514.00000 | 24.83001 | 61.72778 | 0.74811 | 17.79557 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60763 | 42.56329 | 0.00259 | 6.36040 |
February | 454.00000 | 23.28772 | 43.04652 | 0.19707 | 7.19989 |
March | 514.00000 | 23.99134 | 44.92150 | 0.43248 | 9.68457 |
April | 485.00000 | 24.46036 | 44.47485 | 0.61391 | 13.55645 |
May | 508.00000 | 24.58724 | 50.06643 | -0.0643 | 6.50152 |
June | 496.00000 | 24.54675 | 52.71898 | -0.0400 | 6.32926 |
July | 497.00000 | 24.66218 | 54.35993 | -0.0228 | 6.70609 |
August | 514.00000 | 24.53995 | 54.45812 | -0.0682 | 6.39024 |
September | 485.00000 | 24.59251 | 54.26756 | -0.0675 | 6.44959 |
October | 502.00000 | 24.47831 | 48.95006 | 0.63108 | 13.93902 |
November | 489.00000 | 24.03898 | 43.82473 | 0.43073 | 9.52905 |
December | 497.00000 | 23.13492 | 40.04014 | 0.13350 | 6.43334 |
Annual Sum or Average | 5943.00000 | 24.08232 | 47.85184 | 0.18055 | 8.25451 |
Minimum of Months | 454.00000 | 22.60763 | 40.04014 | -0.0682 | 6.32926 |
Maximum of Months | 514.00000 | 24.66218 | 54.45812 | 0.63108 | 13.93902 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11168 | 43.82865 | -0.1372 | 6.76723 |
February | 454.00000 | 23.12791 | 43.45371 | 0.13853 | 6.67419 |
March | 514.00000 | 23.97464 | 45.05873 | 0.40541 | 8.98555 |
April | 485.00000 | 24.44463 | 45.50486 | 0.58145 | 12.58592 |
May | 508.00000 | 24.57474 | 51.74067 | -0.1066 | 6.42300 |
June | 496.00000 | 24.52471 | 54.87089 | -0.0906 | 6.26751 |
July | 497.00000 | 24.64901 | 56.85335 | -0.0579 | 6.71047 |
August | 514.00000 | 24.49764 | 57.17885 | -0.1224 | 6.47775 |
September | 485.00000 | 24.50648 | 57.05486 | -0.1527 | 6.66511 |
October | 502.00000 | 24.27464 | 50.07911 | 0.53416 | 11.37657 |
November | 489.00000 | 23.64415 | 44.66368 | 0.29414 | 7.50978 |
December | 497.00000 | 22.54982 | 41.38026 | -0.0319 | 6.27438 |
Annual Sum or Average | 5943.00000 | 23.91218 | 49.35624 | 0.10360 | 7.72682 |
Minimum of Months | 454.00000 | 22.11168 | 41.38026 | -0.1527 | 6.26751 |
Maximum of Months | 514.00000 | 24.64901 | 57.17885 | 0.58145 | 12.58592 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.31874 | 42.86562 | -0.0738 | 6.56434 |
February | 385.00000 | 23.33797 | 42.04951 | 0.20628 | 7.39620 |
March | 433.00000 | 24.10962 | 43.65527 | 0.46195 | 10.42803 |
April | 410.00000 | 24.61681 | 44.21979 | 0.65719 | 15.01854 |
May | 430.00000 | 24.71157 | 51.05652 | -0.0132 | 6.89188 |
June | 418.00000 | 24.62579 | 54.47705 | -0.0325 | 6.51422 |
July | 422.00000 | 24.76909 | 56.62096 | -0.0048 | 7.14272 |
August | 433.00000 | 24.59118 | 57.00472 | -0.0825 | 6.68330 |
September | 410.00000 | 24.59938 | 56.87531 | -0.1009 | 6.73267 |
October | 427.00000 | 24.43466 | 48.98942 | 0.59138 | 13.25553 |
November | 417.00000 | 23.79801 | 43.24544 | 0.34851 | 8.58814 |
December | 422.00000 | 22.75999 | 40.18737 | 0.03046 | 6.42164 |
Annual Sum or Average | 5034.00000 | 24.05950 | 48.48194 | 0.16481 | 8.46835 |
Minimum of Months | 385.00000 | 22.31874 | 40.18737 | -0.1009 | 6.42164 |
Maximum of Months | 433.00000 | 24.76909 | 57.00472 | 0.65719 | 15.01854 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.14391 | 40.21147 | 0.15104 | 7.86941 |
February | 454.00000 | 23.76076 | 40.94905 | 0.34134 | 9.42159 |
March | 514.00000 | 24.17777 | 43.90936 | 0.51010 | 11.45923 |
April | 485.00000 | 24.51009 | 45.12450 | 0.63212 | 14.10737 |
May | 508.00000 | 24.57528 | 51.69137 | -0.0959 | 6.44397 |
June | 496.00000 | 24.51867 | 54.88491 | -0.0944 | 6.28091 |
July | 497.00000 | 24.64566 | 56.84072 | -0.0571 | 6.72212 |
August | 514.00000 | 24.50690 | 57.05374 | -0.1066 | 6.50399 |
September | 485.00000 | 24.54869 | 56.64558 | -0.0940 | 6.62650 |
October | 502.00000 | 24.50175 | 48.87728 | 0.66369 | 15.34790 |
November | 489.00000 | 24.19392 | 42.15004 | 0.51197 | 12.14197 |
December | 497.00000 | 23.56607 | 37.85965 | 0.26066 | 8.66493 |
Annual Sum or Average | 5943.00000 | 24.22354 | 48.07783 | 0.21678 | 9.28743 |
Minimum of Months | 454.00000 | 23.14391 | 37.85965 | -0.1066 | 6.28091 |
Maximum of Months | 514.00000 | 24.64566 | 57.05374 | 0.66369 | 15.34790 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.27900 | 43.00102 | -0.0756 | 7.03937 |
February | 454.00000 | 23.16965 | 42.86805 | 0.17776 | 7.53333 |
March | 514.00000 | 23.98385 | 44.71725 | 0.45022 | 10.27767 |
April | 485.00000 | 24.47752 | 45.30960 | 0.64446 | 14.58219 |
May | 508.00000 | 24.58284 | 51.65197 | -0.0397 | 6.75597 |
June | 496.00000 | 24.52943 | 54.80166 | -0.0323 | 6.50042 |
July | 497.00000 | 24.63781 | 56.84056 | -0.0337 | 6.88263 |
August | 514.00000 | 24.49116 | 57.18651 | -0.0974 | 6.53290 |
September | 485.00000 | 24.50665 | 56.96587 | -0.1104 | 6.65353 |
October | 502.00000 | 24.29691 | 49.87276 | 0.57731 | 12.82763 |
November | 489.00000 | 23.67720 | 44.13866 | 0.33804 | 8.64896 |
December | 497.00000 | 22.64624 | 40.55458 | 0.01511 | 6.72107 |
Annual Sum or Average | 5943.00000 | 23.94525 | 49.04541 | 0.15023 | 8.40988 |
Minimum of Months | 454.00000 | 22.27900 | 40.55458 | -0.1104 | 6.50042 |
Maximum of Months | 514.00000 | 24.63781 | 57.18651 | 0.64446 | 14.58219 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198790E+11 | 0.521299E+10 | 365.10 | 0.171235E+11 | 0.275551E+10 | 0.00 | 0.84 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 34709.43 | 12-JAN-15:00 | 34709.43 | 12-JAN-15:00 | 7145.60 | 17-JAN-17:06 | 8294.87 | 12-JAN-15:00 | 0.00 |
February | 0.295295E+11 | 0.744992E+10 | 365.69 | 0.263027E+11 | 0.322681E+10 | 0.00 | 1.00 | 21-FEB-12:50 | 0.00 | 01-FEB-00:10 | 49364.58 | 22-FEB-16:10 | 49364.58 | 22-FEB-16:10 | 8642.06 | 25-FEB-17:00 | 12212.24 | 22-FEB-15:00 | 0.00 |
March | 0.549381E+11 | 0.141604E+11 | 441.13 | 0.511326E+11 | 0.380554E+10 | 0.00 | 1.00 | 01-MAR-14:40 | 0.00 | 01-MAR-00:10 | 77800.68 | 29-MAR-11:10 | 68851.86 | 28-MAR-16:00 | 22384.73 | 29-MAR-11:10 | 21512.09 | 28-MAR-15:50 | 0.00 |
April | 0.775092E+11 | 0.224782E+11 | 444.83 | 0.726919E+11 | 0.481727E+10 | 0.00 | 1.00 | 01-APR-15:10 | 0.00 | 01-APR-00:10 | 97737.05 | 27-APR-06:03 | 92726.90 | 17-APR-04:02 | 26968.77 | 18-APR-11:05 | 29051.41 | 26-APR-15:30 | 0.00 |
May | 0.112886E+12 | 0.346557E+11 | 515.57 | 0.949574E+11 | 0.179288E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:13 | 136058.39 | 19-MAY-04:02 | 100559.84 | 30-MAY-06:03 | 55751.49 | 24-MAY-04:03 | 36338.06 | 01-MAY-15:20 | 0.00 |
June | 0.127956E+12 | 0.382635E+11 | 514.73 | 0.964164E+11 | 0.315391E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 140578.13 | 27-JUN-04:02 | 103082.64 | 12-JUN-06:03 | 59923.83 | 29-JUN-04:03 | 38079.46 | 12-JUN-16:00 | 0.00 |
July | 0.139081E+12 | 0.378131E+11 | 524.24 | 0.888650E+11 | 0.502156E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:05 | 143677.67 | 20-JUL-04:03 | 94954.23 | 05-JUL-06:03 | 67596.04 | 20-JUL-04:03 | 39682.19 | 02-JUL-16:02 | 0.00 |
August | 0.141496E+12 | 0.371714E+11 | 507.84 | 0.880409E+11 | 0.534553E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 140959.57 | 27-AUG-16:52 | 93107.83 | 03-AUG-06:03 | 65367.93 | 27-AUG-16:52 | 37876.89 | 27-AUG-16:52 | 0.00 |
September | 0.113938E+12 | 0.297019E+11 | 462.17 | 0.764203E+11 | 0.375179E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 139886.13 | 06-SEP-04:03 | 93894.48 | 25-SEP-06:03 | 59846.80 | 06-SEP-04:03 | 33256.10 | 01-SEP-04:02 | 0.00 |
October | 0.785203E+11 | 0.205795E+11 | 452.42 | 0.675639E+11 | 0.109564E+11 | 0.00 | 1.00 | 01-OCT-10:02 | 0.00 | 01-OCT-00:10 | 113424.09 | 04-OCT-04:03 | 85135.36 | 02-OCT-06:03 | 36721.23 | 04-OCT-04:03 | 27316.41 | 02-OCT-15:20 | 0.00 |
November | 0.485337E+11 | 0.121269E+11 | 411.33 | 0.449908E+11 | 0.354291E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 63469.58 | 06-NOV-11:40 | 59176.51 | 13-NOV-14:00 | 11302.82 | 06-NOV-11:40 | 16415.04 | 06-NOV-14:00 | 0.00 |
December | 0.253903E+11 | 0.653209E+10 | 392.00 | 0.227857E+11 | 0.260459E+10 | 0.00 | 1.00 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 42917.34 | 01-DEC-14:00 | 42917.34 | 01-DEC-14:00 | 6856.12 | 29-DEC-18:07 | 9808.36 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.969657E+12 | 0.266146E+12 | 5397.04 | 0.747291E+12 | 0.222366E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.198790E+11 | 0.521299E+10 | 365.10 | 0.171235E+11 | 0.260459E+10 | 0.00 | 0.84 | 0.00 | 34709.43 | 34709.43 | 6856.12 | 8294.87 | 0.00 | ||||||
Maximum of Months | 0.141496E+12 | 0.382635E+11 | 524.24 | 0.964164E+11 | 0.534553E+11 | 0.00 | 1.00 | 0.00 | 143677.67 | 103082.64 | 67596.04 | 39682.19 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144592E+11 | 0.386670E+10 | 345.39 | 0.117693E+11 | 0.268988E+10 | 0.00 | 0.74 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 27315.85 | 12-JAN-15:20 | 27315.85 | 12-JAN-15:20 | 6374.51 | 17-JAN-15:00 | 6712.16 | 12-JAN-15:20 | 0.00 |
February | 0.235616E+11 | 0.603585E+10 | 361.42 | 0.202001E+11 | 0.336151E+10 | 0.00 | 1.00 | 21-FEB-14:20 | 0.00 | 01-FEB-00:10 | 43811.68 | 22-FEB-15:30 | 43811.68 | 22-FEB-15:30 | 8209.04 | 25-FEB-17:00 | 10793.82 | 22-FEB-15:10 | 0.00 |
March | 0.480524E+11 | 0.124670E+11 | 446.00 | 0.442741E+11 | 0.377838E+10 | 0.00 | 1.00 | 03-MAR-14:10 | 0.00 | 01-MAR-00:10 | 66000.08 | 28-MAR-16:00 | 66000.08 | 28-MAR-16:00 | 10985.63 | 10-MAR-20:50 | 20558.73 | 28-MAR-16:00 | 0.00 |
April | 0.714395E+11 | 0.206885E+11 | 451.41 | 0.676346E+11 | 0.380498E+10 | 0.00 | 1.00 | 01-APR-12:50 | 0.00 | 01-APR-00:10 | 96604.05 | 16-APR-16:02 | 87447.12 | 17-APR-04:02 | 22303.17 | 19-APR-05:03 | 31916.62 | 16-APR-15:22 | 0.00 |
May | 0.103061E+12 | 0.314665E+11 | 520.74 | 0.877146E+11 | 0.153468E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:03 | 125291.57 | 19-MAY-04:02 | 91409.06 | 07-MAY-15:51 | 52180.80 | 24-MAY-05:03 | 35575.03 | 29-MAY-14:21 | 0.00 |
June | 0.113988E+12 | 0.338343E+11 | 512.68 | 0.864233E+11 | 0.275645E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 130628.26 | 27-JUN-04:02 | 97139.52 | 12-JUN-06:03 | 58276.42 | 27-JUN-04:02 | 40769.23 | 11-JUN-15:22 | 0.00 |
July | 0.120406E+12 | 0.325019E+11 | 508.36 | 0.761029E+11 | 0.443034E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:05 | 133104.83 | 20-JUL-04:03 | 86130.61 | 05-JUL-06:03 | 67657.89 | 20-JUL-04:03 | 39167.46 | 02-JUL-15:51 | 0.00 |
August | 0.117938E+12 | 0.307388E+11 | 490.06 | 0.719373E+11 | 0.460007E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 130964.96 | 10-AUG-04:02 | 83769.62 | 07-AUG-06:03 | 59595.77 | 19-AUG-05:03 | 35825.89 | 06-AUG-16:02 | 0.00 |
September | 0.934569E+11 | 0.242043E+11 | 442.67 | 0.615569E+11 | 0.319000E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 129351.79 | 11-SEP-04:02 | 83743.00 | 25-SEP-04:02 | 58124.62 | 11-SEP-04:02 | 30629.21 | 01-SEP-04:02 | 0.00 |
October | 0.630847E+11 | 0.166611E+11 | 437.28 | 0.539084E+11 | 0.917624E+10 | 0.00 | 1.00 | 01-OCT-08:53 | 0.00 | 01-OCT-00:10 | 86324.97 | 04-OCT-05:03 | 74322.59 | 01-OCT-14:51 | 27471.17 | 04-OCT-05:03 | 25124.01 | 02-OCT-15:00 | 0.00 |
November | 0.373486E+11 | 0.950996E+10 | 406.36 | 0.336589E+11 | 0.368961E+10 | 0.00 | 1.00 | 01-NOV-11:00 | 0.00 | 01-NOV-00:10 | 54062.56 | 06-NOV-13:30 | 49966.49 | 08-NOV-15:10 | 8717.56 | 08-NOV-19:00 | 13945.29 | 09-NOV-13:40 | 0.00 |
December | 0.182557E+11 | 0.481089E+10 | 382.03 | 0.152911E+11 | 0.296465E+10 | 0.00 | 0.88 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 33444.82 | 01-DEC-15:10 | 33444.82 | 01-DEC-15:10 | 5815.84 | 29-DEC-18:00 | 7915.56 | 01-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.825052E+12 | 0.226786E+12 | 5304.39 | 0.630471E+12 | 0.194581E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.144592E+11 | 0.386670E+10 | 345.39 | 0.117693E+11 | 0.268988E+10 | 0.00 | 0.74 | 0.00 | 27315.85 | 27315.85 | 5815.84 | 6712.16 | 0.00 | ||||||
Maximum of Months | 0.120406E+12 | 0.338343E+11 | 520.74 | 0.877146E+11 | 0.460007E+11 | 0.00 | 1.00 | 0.00 | 133104.83 | 97139.52 | 67657.89 | 40769.23 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.152128E+11 | 0.407910E+10 | 328.78 | 0.121615E+11 | 0.305135E+10 | 0.00 | 0.70 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 29113.76 | 12-JAN-15:20 | 29113.76 | 12-JAN-15:20 | 7091.80 | 17-JAN-15:00 | 7246.30 | 12-JAN-15:20 | 0.00 |
February | 0.245460E+11 | 0.633153E+10 | 348.88 | 0.207245E+11 | 0.382153E+10 | 0.00 | 1.00 | 21-FEB-14:20 | 0.00 | 01-FEB-00:10 | 50532.18 | 22-FEB-15:00 | 50532.18 | 22-FEB-15:00 | 8885.43 | 25-FEB-17:00 | 12515.61 | 22-FEB-15:00 | 0.00 |
March | 0.518458E+11 | 0.135775E+11 | 445.81 | 0.471629E+11 | 0.468286E+10 | 0.00 | 1.00 | 03-MAR-14:10 | 0.00 | 01-MAR-00:10 | 79420.29 | 28-MAR-16:00 | 79420.29 | 28-MAR-16:00 | 12295.89 | 10-MAR-20:20 | 24616.92 | 28-MAR-16:00 | 0.00 |
April | 0.797703E+11 | 0.232953E+11 | 454.88 | 0.754185E+11 | 0.435179E+10 | 0.00 | 1.00 | 01-APR-12:30 | 0.00 | 01-APR-00:10 | 120505.76 | 16-APR-16:42 | 109203.66 | 16-APR-14:42 | 15468.98 | 16-APR-16:42 | 39190.33 | 16-APR-15:22 | 0.00 |
May | 0.114629E+12 | 0.352295E+11 | 526.02 | 0.987220E+11 | 0.159071E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:23 | 143902.87 | 17-MAY-04:02 | 113126.93 | 29-MAY-16:31 | 49932.07 | 24-MAY-04:03 | 43073.17 | 28-MAY-15:51 | 0.00 |
June | 0.126276E+12 | 0.377255E+11 | 521.16 | 0.979847E+11 | 0.282916E+11 | 0.00 | 1.00 | 01-JUN-08:20 | 0.00 | 01-JUN-00:10 | 150825.75 | 27-JUN-04:02 | 114693.11 | 11-JUN-15:51 | 66147.79 | 27-JUN-04:02 | 48186.24 | 11-JUN-15:51 | 0.00 |
July | 0.130369E+12 | 0.353146E+11 | 522.16 | 0.848039E+11 | 0.455647E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:05 | 153333.79 | 20-JUL-04:03 | 107386.49 | 04-JUL-16:32 | 78223.11 | 20-JUL-04:03 | 45088.35 | 02-JUL-16:02 | 0.00 |
August | 0.125391E+12 | 0.327864E+11 | 497.07 | 0.787007E+11 | 0.466898E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 151529.60 | 10-AUG-04:02 | 98522.76 | 06-AUG-16:02 | 66648.39 | 10-AUG-04:02 | 41587.92 | 06-AUG-16:02 | 0.00 |
September | 0.978990E+11 | 0.255185E+11 | 442.79 | 0.658134E+11 | 0.320856E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 149287.88 | 01-SEP-04:02 | 95999.53 | 18-SEP-04:02 | 69990.30 | 01-SEP-04:02 | 35393.53 | 17-SEP-15:12 | 0.00 |
October | 0.663013E+11 | 0.177037E+11 | 436.25 | 0.566626E+11 | 0.963872E+10 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 94267.18 | 09-OCT-14:21 | 94267.18 | 09-OCT-14:21 | 23589.44 | 04-OCT-05:03 | 28698.79 | 02-OCT-14:50 | 0.00 |
November | 0.382012E+11 | 0.985055E+10 | 402.13 | 0.338788E+11 | 0.432241E+10 | 0.00 | 1.00 | 01-NOV-12:05 | 0.00 | 01-NOV-00:10 | 59270.41 | 09-NOV-13:40 | 58203.12 | 09-NOV-14:50 | 9854.51 | 08-NOV-18:30 | 15424.30 | 09-NOV-13:40 | 0.00 |
December | 0.183389E+11 | 0.486309E+10 | 360.26 | 0.149172E+11 | 0.342170E+10 | 0.00 | 0.83 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 35857.46 | 01-DEC-14:50 | 35857.46 | 01-DEC-14:50 | 6361.01 | 29-DEC-17:00 | 8635.92 | 03-DEC-14:02 | 0.00 |
Annual Sum or Average | 0.888780E+12 | 0.246275E+12 | 5286.19 | 0.686951E+12 | 0.201829E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.152128E+11 | 0.407910E+10 | 328.78 | 0.121615E+11 | 0.305135E+10 | 0.00 | 0.70 | 0.00 | 29113.76 | 29113.76 | 6361.01 | 7246.30 | 0.00 | ||||||
Maximum of Months | 0.130369E+12 | 0.377255E+11 | 526.02 | 0.987220E+11 | 0.466898E+11 | 0.00 | 1.00 | 0.00 | 153333.79 | 114693.11 | 78223.11 | 48186.24 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.18 | 0.00 | 342.18 | 237.32 | 1169.01 | 18.50 | 0.00 | 0.00 |
February | 405.77 | 0.00 | 405.77 | 418.37 | 933.46 | 0.00 | 0.00 | 0.00 |
March | 488.95 | 0.00 | 488.95 | 762.60 | 568.72 | 0.00 | 0.00 | 0.00 |
April | 530.55 | 1.80 | 528.75 | 1319.40 | 206.59 | 0.00 | 0.00 | 0.00 |
May | 587.82 | 16.50 | 571.32 | 1836.22 | 39.40 | 0.00 | 0.00 | 0.00 |
June | 608.48 | 22.54 | 585.94 | 1995.73 | 29.56 | 0.00 | 0.00 | 0.00 |
July | 600.10 | 9.50 | 590.60 | 1767.52 | 6.43 | 0.00 | 0.00 | 0.00 |
August | 550.91 | 1.72 | 549.20 | 1486.97 | 21.25 | 0.00 | 0.00 | 0.00 |
September | 490.88 | 0.03 | 490.84 | 1156.82 | 86.30 | 0.00 | 0.00 | 0.00 |
October | 425.26 | 0.00 | 425.26 | 847.68 | 445.47 | 0.00 | 0.00 | 0.00 |
November | 360.20 | 0.00 | 360.20 | 478.43 | 838.43 | 0.00 | 0.00 | 0.00 |
December | 333.80 | 0.00 | 333.80 | 262.29 | 1148.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 477.44 | 4.36 | 473.08 | 1050.53 | 455.65 | 18.50 | 0.00 | 0.00 |
Minimum of Months | 333.80 | 0.00 | 333.80 | 237.32 | 6.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.48 | 22.54 | 590.60 | 1995.73 | 1169.01 | 18.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.68 | 196.15 | 292.53 | 534.99 | 719.27 | 19.00 | 0.00 | 0.00 |
February | 593.69 | 245.10 | 348.58 | 784.57 | 586.96 | 0.00 | 0.00 | 0.00 |
March | 724.23 | 298.94 | 425.30 | 1182.99 | 365.16 | 0.00 | 0.00 | 0.00 |
April | 861.65 | 401.75 | 459.90 | 1769.44 | 139.15 | 0.00 | 0.00 | 0.00 |
May | 848.10 | 376.00 | 472.10 | 2021.95 | 25.88 | 0.00 | 0.00 | 0.00 |
June | 690.24 | 229.02 | 461.22 | 1833.05 | 19.79 | 0.00 | 0.00 | 0.00 |
July | 580.13 | 122.51 | 457.62 | 1499.65 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 522.72 | 90.97 | 431.76 | 1265.88 | 14.33 | 0.00 | 0.00 | 0.00 |
September | 558.47 | 155.74 | 402.73 | 1178.04 | 57.78 | 0.00 | 0.00 | 0.00 |
October | 610.90 | 246.76 | 364.14 | 1139.32 | 291.44 | 0.00 | 0.00 | 0.00 |
November | 541.65 | 232.50 | 309.15 | 818.09 | 533.24 | 0.00 | 0.00 | 0.00 |
December | 472.30 | 187.13 | 285.17 | 555.74 | 722.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 624.23 | 231.52 | 392.70 | 1216.83 | 288.64 | 19.00 | 0.00 | 0.00 |
Minimum of Months | 472.30 | 90.97 | 285.17 | 534.99 | 3.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.65 | 401.75 | 472.10 | 2021.95 | 722.69 | 19.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1556.24 | 945.61 | 610.63 | 2165.93 | 1122.11 | 16.50 | 0.00 | 0.00 |
February | 1479.75 | 821.90 | 657.86 | 2227.92 | 930.95 | 0.00 | 0.00 | 0.00 |
March | 1265.23 | 558.84 | 706.39 | 2226.84 | 586.26 | 0.00 | 0.00 | 0.00 |
April | 888.70 | 250.82 | 637.88 | 2100.33 | 219.45 | 0.00 | 0.00 | 0.00 |
May | 639.09 | 47.31 | 591.78 | 1966.20 | 38.14 | 0.00 | 0.00 | 0.00 |
June | 584.60 | 9.98 | 574.63 | 1950.11 | 29.39 | 0.00 | 0.00 | 0.00 |
July | 609.80 | 8.39 | 601.41 | 1796.48 | 5.71 | 0.00 | 0.00 | 0.00 |
August | 646.87 | 34.55 | 612.32 | 1685.02 | 21.76 | 0.00 | 0.00 | 0.00 |
September | 867.18 | 225.08 | 642.10 | 1885.60 | 92.19 | 0.00 | 0.00 | 0.00 |
October | 1491.89 | 833.06 | 658.82 | 2794.34 | 468.08 | 0.00 | 0.00 | 0.00 |
November | 1863.45 | 1231.70 | 631.75 | 3050.65 | 856.23 | 0.00 | 0.00 | 0.00 |
December | 1663.08 | 1042.13 | 620.95 | 2402.67 | 1125.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1127.64 | 498.92 | 628.72 | 2186.70 | 455.81 | 16.50 | 0.00 | 0.00 |
Minimum of Months | 584.60 | 8.39 | 574.63 | 1685.02 | 5.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1863.45 | 1231.70 | 706.39 | 3050.65 | 1125.19 | 16.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.10 | 186.06 | 292.04 | 577.23 | 778.62 | 20.67 | 0.00 | 0.00 |
February | 546.72 | 201.48 | 345.24 | 759.46 | 629.24 | 0.00 | 0.00 | 0.00 |
March | 708.95 | 283.39 | 425.56 | 1185.51 | 391.84 | 0.00 | 0.00 | 0.00 |
April | 861.72 | 404.11 | 457.61 | 1778.65 | 149.00 | 0.00 | 0.00 | 0.00 |
May | 815.97 | 346.12 | 469.85 | 1973.35 | 29.43 | 0.00 | 0.00 | 0.00 |
June | 766.41 | 297.70 | 468.72 | 1969.23 | 21.28 | 0.00 | 0.00 | 0.00 |
July | 568.72 | 110.62 | 458.10 | 1473.18 | 4.53 | 0.00 | 0.00 | 0.00 |
August | 522.31 | 92.83 | 429.48 | 1267.49 | 14.77 | 0.00 | 0.00 | 0.00 |
September | 574.15 | 168.56 | 405.60 | 1209.45 | 61.57 | 0.00 | 0.00 | 0.00 |
October | 597.61 | 237.97 | 359.64 | 1137.85 | 307.60 | 0.00 | 0.00 | 0.00 |
November | 540.63 | 230.41 | 310.22 | 865.92 | 568.81 | 0.00 | 0.00 | 0.00 |
December | 462.62 | 176.41 | 286.21 | 581.00 | 760.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.21 | 227.67 | 392.54 | 1232.95 | 308.33 | 20.67 | 0.00 | 0.00 |
Minimum of Months | 462.62 | 92.83 | 286.21 | 577.23 | 4.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.72 | 404.11 | 469.85 | 1973.35 | 778.62 | 20.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 70.32 | 440.35 | 20.67 | 0.00 | 0.00 |
February | 135.25 | 0.00 | 135.25 | 137.13 | 335.16 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 260.40 | 192.52 | 0.00 | 0.00 | 0.00 |
April | 176.84 | 0.60 | 176.24 | 451.85 | 64.31 | 0.00 | 0.00 | 0.00 |
May | 195.93 | 5.50 | 190.43 | 622.82 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 202.82 | 7.51 | 195.31 | 671.55 | 9.25 | 0.00 | 0.00 | 0.00 |
July | 200.02 | 3.17 | 196.86 | 589.56 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 183.63 | 0.57 | 183.06 | 492.01 | 9.53 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 381.23 | 35.88 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.46 | 165.58 | 0.00 | 0.00 | 0.00 |
November | 120.06 | 0.00 | 120.06 | 150.20 | 316.78 | 0.00 | 0.00 | 0.00 |
December | 111.26 | 0.00 | 111.26 | 74.03 | 440.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 349.32 | 167.92 | 20.67 | 0.00 | 0.00 |
Minimum of Months | 111.26 | 0.00 | 111.26 | 70.32 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.82 | 7.51 | 196.86 | 671.55 | 440.35 | 20.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 70.33 | 440.37 | 20.67 | 0.00 | 0.00 |
February | 135.26 | 0.00 | 135.26 | 137.14 | 335.18 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 260.42 | 192.53 | 0.00 | 0.00 | 0.00 |
April | 176.85 | 0.60 | 176.25 | 451.88 | 64.31 | 0.00 | 0.00 | 0.00 |
May | 195.94 | 5.50 | 190.44 | 622.85 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 202.83 | 7.51 | 195.31 | 671.59 | 9.25 | 0.00 | 0.00 | 0.00 |
July | 200.03 | 3.17 | 196.86 | 589.60 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 183.64 | 0.57 | 183.06 | 492.03 | 9.53 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 381.25 | 35.88 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.47 | 165.59 | 0.00 | 0.00 | 0.00 |
November | 120.07 | 0.00 | 120.07 | 150.20 | 316.79 | 0.00 | 0.00 | 0.00 |
December | 111.27 | 0.00 | 111.27 | 74.03 | 440.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 349.33 | 167.93 | 20.67 | 0.00 | 0.00 |
Minimum of Months | 111.27 | 0.00 | 111.27 | 70.33 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.83 | 7.51 | 196.86 | 671.59 | 440.37 | 20.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 70.33 | 440.37 | 20.67 | 0.00 | 0.00 |
February | 135.26 | 0.00 | 135.26 | 137.14 | 335.18 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 260.42 | 192.53 | 0.00 | 0.00 | 0.00 |
April | 176.85 | 0.60 | 176.25 | 451.88 | 64.31 | 0.00 | 0.00 | 0.00 |
May | 195.94 | 5.50 | 190.44 | 622.85 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 202.83 | 7.51 | 195.31 | 671.59 | 9.25 | 0.00 | 0.00 | 0.00 |
July | 200.03 | 3.17 | 196.86 | 589.60 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 183.64 | 0.57 | 183.06 | 492.03 | 9.53 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 381.25 | 35.88 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.47 | 165.59 | 0.00 | 0.00 | 0.00 |
November | 120.07 | 0.00 | 120.07 | 150.20 | 316.79 | 0.00 | 0.00 | 0.00 |
December | 111.27 | 0.00 | 111.27 | 74.03 | 440.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 349.33 | 167.93 | 20.67 | 0.00 | 0.00 |
Minimum of Months | 111.27 | 0.00 | 111.27 | 70.33 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.83 | 7.51 | 196.86 | 671.59 | 440.37 | 20.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 470.09 | 188.69 | 281.40 | 485.05 | 791.77 | 21.33 | 0.00 | 0.00 |
February | 571.10 | 235.77 | 335.32 | 746.22 | 618.68 | 0.00 | 0.00 | 0.00 |
March | 696.68 | 287.56 | 409.11 | 1149.92 | 365.75 | 0.00 | 0.00 | 0.00 |
April | 828.86 | 386.46 | 442.41 | 1724.29 | 132.92 | 0.00 | 0.00 | 0.00 |
May | 815.83 | 361.69 | 454.14 | 1962.88 | 23.57 | 0.00 | 0.00 | 0.00 |
June | 663.98 | 220.31 | 443.67 | 1773.75 | 19.05 | 0.00 | 0.00 | 0.00 |
July | 558.06 | 117.85 | 440.21 | 1440.50 | 5.19 | 0.00 | 0.00 | 0.00 |
August | 502.83 | 87.50 | 415.33 | 1210.10 | 19.45 | 0.00 | 0.00 | 0.00 |
September | 537.22 | 149.82 | 387.40 | 1125.86 | 72.65 | 0.00 | 0.00 | 0.00 |
October | 587.65 | 237.37 | 350.28 | 1088.58 | 318.53 | 0.00 | 0.00 | 0.00 |
November | 521.04 | 223.65 | 297.39 | 766.53 | 585.22 | 0.00 | 0.00 | 0.00 |
December | 454.33 | 180.01 | 274.32 | 498.27 | 804.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.47 | 222.71 | 377.76 | 1165.76 | 311.76 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 454.33 | 87.50 | 274.32 | 485.05 | 5.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 828.86 | 386.46 | 454.14 | 1962.88 | 804.00 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.59 | 7.46 | 11.13 | 19.18 | 31.31 | 21.33 | 0.00 | 0.00 |
February | 22.58 | 9.32 | 13.26 | 29.50 | 24.46 | 0.00 | 0.00 | 0.00 |
March | 27.55 | 11.37 | 16.18 | 45.47 | 14.46 | 0.00 | 0.00 | 0.00 |
April | 32.77 | 15.28 | 17.49 | 68.18 | 5.26 | 0.00 | 0.00 | 0.00 |
May | 32.26 | 14.30 | 17.96 | 77.61 | 0.93 | 0.00 | 0.00 | 0.00 |
June | 26.25 | 8.71 | 17.54 | 70.13 | 0.75 | 0.00 | 0.00 | 0.00 |
July | 22.07 | 4.66 | 17.41 | 56.96 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 19.88 | 3.46 | 16.42 | 47.85 | 0.77 | 0.00 | 0.00 | 0.00 |
September | 21.24 | 5.92 | 15.32 | 44.52 | 2.87 | 0.00 | 0.00 | 0.00 |
October | 23.24 | 9.39 | 13.85 | 43.04 | 12.59 | 0.00 | 0.00 | 0.00 |
November | 20.60 | 8.84 | 11.76 | 30.31 | 23.14 | 0.00 | 0.00 | 0.00 |
December | 17.96 | 7.12 | 10.85 | 19.70 | 31.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.74 | 8.81 | 14.94 | 46.09 | 12.33 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 17.96 | 3.46 | 10.85 | 19.18 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.77 | 15.28 | 17.96 | 77.61 | 31.79 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.74 | 315.20 | 203.54 | 717.79 | 430.27 | 17.67 | 0.00 | 0.00 |
February | 493.24 | 273.96 | 219.28 | 744.58 | 343.90 | 0.00 | 0.00 | 0.00 |
March | 421.74 | 186.28 | 235.46 | 749.81 | 205.90 | 0.00 | 0.00 | 0.00 |
April | 296.23 | 83.60 | 212.63 | 707.51 | 72.29 | 0.00 | 0.00 | 0.00 |
May | 213.03 | 15.77 | 197.26 | 656.98 | 11.42 | 0.00 | 0.00 | 0.00 |
June | 194.87 | 3.33 | 191.54 | 647.31 | 9.42 | 0.00 | 0.00 | 0.00 |
July | 203.26 | 2.80 | 200.47 | 593.77 | 2.68 | 0.00 | 0.00 | 0.00 |
August | 215.62 | 11.52 | 204.10 | 554.02 | 10.16 | 0.00 | 0.00 | 0.00 |
September | 289.05 | 75.02 | 214.03 | 621.89 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 497.29 | 277.68 | 219.61 | 925.78 | 181.99 | 0.00 | 0.00 | 0.00 |
November | 621.14 | 410.56 | 210.58 | 1012.54 | 331.41 | 0.00 | 0.00 | 0.00 |
December | 554.35 | 347.37 | 206.98 | 791.01 | 435.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.87 | 166.30 | 209.57 | 726.55 | 172.24 | 17.67 | 0.00 | 0.00 |
Minimum of Months | 194.87 | 2.80 | 191.54 | 554.02 | 2.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.14 | 410.56 | 235.46 | 1012.54 | 435.40 | 17.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.74 | 315.20 | 203.54 | 717.79 | 430.27 | 17.67 | 0.00 | 0.00 |
February | 493.24 | 273.96 | 219.28 | 744.58 | 343.90 | 0.00 | 0.00 | 0.00 |
March | 421.74 | 186.28 | 235.46 | 749.81 | 205.90 | 0.00 | 0.00 | 0.00 |
April | 296.23 | 83.60 | 212.63 | 707.51 | 72.29 | 0.00 | 0.00 | 0.00 |
May | 213.03 | 15.77 | 197.26 | 656.98 | 11.42 | 0.00 | 0.00 | 0.00 |
June | 194.87 | 3.33 | 191.54 | 647.31 | 9.42 | 0.00 | 0.00 | 0.00 |
July | 203.26 | 2.80 | 200.47 | 593.77 | 2.68 | 0.00 | 0.00 | 0.00 |
August | 215.62 | 11.52 | 204.10 | 554.02 | 10.16 | 0.00 | 0.00 | 0.00 |
September | 289.05 | 75.02 | 214.03 | 621.89 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 497.29 | 277.68 | 219.61 | 925.78 | 181.99 | 0.00 | 0.00 | 0.00 |
November | 621.14 | 410.56 | 210.58 | 1012.54 | 331.41 | 0.00 | 0.00 | 0.00 |
December | 554.35 | 347.37 | 206.98 | 791.01 | 435.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.87 | 166.30 | 209.57 | 726.55 | 172.24 | 17.67 | 0.00 | 0.00 |
Minimum of Months | 194.87 | 2.80 | 191.54 | 554.02 | 2.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.14 | 410.56 | 235.46 | 1012.54 | 435.40 | 17.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.70 | 315.18 | 203.53 | 717.75 | 430.24 | 17.67 | 0.00 | 0.00 |
February | 493.21 | 273.94 | 219.27 | 744.53 | 343.88 | 0.00 | 0.00 | 0.00 |
March | 421.71 | 186.26 | 235.44 | 749.76 | 205.88 | 0.00 | 0.00 | 0.00 |
April | 296.21 | 83.60 | 212.61 | 707.47 | 72.28 | 0.00 | 0.00 | 0.00 |
May | 213.02 | 15.77 | 197.25 | 656.94 | 11.42 | 0.00 | 0.00 | 0.00 |
June | 194.85 | 3.33 | 191.53 | 647.27 | 9.42 | 0.00 | 0.00 | 0.00 |
July | 203.25 | 2.80 | 200.46 | 593.74 | 2.68 | 0.00 | 0.00 | 0.00 |
August | 215.61 | 11.51 | 204.09 | 553.99 | 10.16 | 0.00 | 0.00 | 0.00 |
September | 289.04 | 75.02 | 214.02 | 621.85 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 497.26 | 277.66 | 219.59 | 925.72 | 181.97 | 0.00 | 0.00 | 0.00 |
November | 621.10 | 410.53 | 210.57 | 1012.48 | 331.39 | 0.00 | 0.00 | 0.00 |
December | 554.31 | 347.35 | 206.97 | 790.96 | 435.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.85 | 166.29 | 209.56 | 726.50 | 172.23 | 17.67 | 0.00 | 0.00 |
Minimum of Months | 194.85 | 2.80 | 191.53 | 553.99 | 2.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.10 | 410.53 | 235.44 | 1012.48 | 435.37 | 17.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.91 | 178.98 | 280.93 | 540.32 | 856.72 | 23.33 | 0.00 | 0.00 |
February | 525.91 | 193.81 | 332.10 | 727.79 | 665.05 | 0.00 | 0.00 | 0.00 |
March | 681.98 | 272.61 | 409.37 | 1153.15 | 395.70 | 0.00 | 0.00 | 0.00 |
April | 828.94 | 388.74 | 440.20 | 1731.72 | 144.42 | 0.00 | 0.00 | 0.00 |
May | 784.92 | 332.95 | 451.98 | 1911.53 | 27.62 | 0.00 | 0.00 | 0.00 |
June | 737.25 | 286.37 | 450.89 | 1900.38 | 21.35 | 0.00 | 0.00 | 0.00 |
July | 547.08 | 106.41 | 440.67 | 1413.92 | 6.00 | 0.00 | 0.00 | 0.00 |
August | 502.44 | 89.30 | 413.14 | 1209.85 | 20.02 | 0.00 | 0.00 | 0.00 |
September | 552.31 | 162.14 | 390.17 | 1155.48 | 78.15 | 0.00 | 0.00 | 0.00 |
October | 574.87 | 228.91 | 345.96 | 1087.27 | 338.91 | 0.00 | 0.00 | 0.00 |
November | 520.06 | 221.65 | 298.42 | 815.98 | 630.51 | 0.00 | 0.00 | 0.00 |
December | 445.02 | 169.70 | 275.33 | 533.09 | 849.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 596.62 | 219.01 | 377.61 | 1183.03 | 334.73 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 445.02 | 89.30 | 275.33 | 533.09 | 6.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 828.94 | 388.74 | 451.98 | 1911.53 | 856.72 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.18 | 7.08 | 11.11 | 21.36 | 33.87 | 23.33 | 0.00 | 0.00 |
February | 20.79 | 7.66 | 13.13 | 28.78 | 26.30 | 0.00 | 0.00 | 0.00 |
March | 26.96 | 10.78 | 16.19 | 45.59 | 15.65 | 0.00 | 0.00 | 0.00 |
April | 32.78 | 15.37 | 17.40 | 68.47 | 5.71 | 0.00 | 0.00 | 0.00 |
May | 31.04 | 13.16 | 17.87 | 75.58 | 1.09 | 0.00 | 0.00 | 0.00 |
June | 29.15 | 11.32 | 17.83 | 75.14 | 0.84 | 0.00 | 0.00 | 0.00 |
July | 21.63 | 4.21 | 17.42 | 55.91 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 19.87 | 3.53 | 16.34 | 47.84 | 0.79 | 0.00 | 0.00 | 0.00 |
September | 21.84 | 6.41 | 15.43 | 45.69 | 3.09 | 0.00 | 0.00 | 0.00 |
October | 22.73 | 9.05 | 13.68 | 42.99 | 13.40 | 0.00 | 0.00 | 0.00 |
November | 20.56 | 8.76 | 11.80 | 32.26 | 24.93 | 0.00 | 0.00 | 0.00 |
December | 17.60 | 6.71 | 10.89 | 21.08 | 33.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.59 | 8.66 | 14.93 | 46.78 | 13.23 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 17.60 | 3.53 | 10.89 | 21.08 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.78 | 15.37 | 17.87 | 75.58 | 33.87 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.18 | 0.00 | 342.18 | 212.56 | 1287.11 | 17.17 | 0.00 | 0.00 |
February | 405.77 | 0.00 | 405.77 | 398.46 | 1016.77 | 0.00 | 0.00 | 0.00 |
March | 488.95 | 0.00 | 488.95 | 758.94 | 607.85 | 0.00 | 0.00 | 0.00 |
April | 530.55 | 1.80 | 528.75 | 1330.13 | 216.54 | 0.00 | 0.00 | 0.00 |
May | 587.82 | 16.50 | 571.32 | 1852.75 | 39.58 | 0.00 | 0.00 | 0.00 |
June | 608.48 | 22.54 | 585.94 | 2013.67 | 29.05 | 0.00 | 0.00 | 0.00 |
July | 600.10 | 9.50 | 590.60 | 1783.61 | 6.53 | 0.00 | 0.00 | 0.00 |
August | 550.91 | 1.72 | 549.20 | 1500.12 | 22.03 | 0.00 | 0.00 | 0.00 |
September | 490.88 | 0.03 | 490.84 | 1164.33 | 91.13 | 0.00 | 0.00 | 0.00 |
October | 425.26 | 0.00 | 425.26 | 847.19 | 475.25 | 0.00 | 0.00 | 0.00 |
November | 360.20 | 0.00 | 360.20 | 460.74 | 912.63 | 0.00 | 0.00 | 0.00 |
December | 333.80 | 0.00 | 333.80 | 232.82 | 1265.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 477.44 | 4.36 | 473.08 | 1049.45 | 495.25 | 17.17 | 0.00 | 0.00 |
Minimum of Months | 333.80 | 0.00 | 333.80 | 212.56 | 6.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.48 | 22.54 | 590.60 | 2013.67 | 1287.11 | 17.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.68 | 196.15 | 292.53 | 510.30 | 784.77 | 19.00 | 0.00 | 0.00 |
February | 593.69 | 245.10 | 348.58 | 769.18 | 630.83 | 0.00 | 0.00 | 0.00 |
March | 724.23 | 298.94 | 425.30 | 1181.12 | 385.18 | 0.00 | 0.00 | 0.00 |
April | 861.65 | 401.75 | 459.90 | 1778.78 | 144.54 | 0.00 | 0.00 | 0.00 |
May | 848.10 | 376.00 | 472.10 | 2035.81 | 25.85 | 0.00 | 0.00 | 0.00 |
June | 690.24 | 229.02 | 461.22 | 1846.92 | 19.22 | 0.00 | 0.00 | 0.00 |
July | 580.13 | 122.51 | 457.62 | 1511.66 | 3.88 | 0.00 | 0.00 | 0.00 |
August | 522.72 | 90.97 | 431.76 | 1275.71 | 14.74 | 0.00 | 0.00 | 0.00 |
September | 558.47 | 155.74 | 402.73 | 1184.33 | 60.43 | 0.00 | 0.00 | 0.00 |
October | 610.90 | 246.76 | 364.14 | 1139.49 | 307.88 | 0.00 | 0.00 | 0.00 |
November | 541.65 | 232.50 | 309.15 | 805.08 | 572.26 | 0.00 | 0.00 | 0.00 |
December | 472.30 | 187.13 | 285.17 | 530.03 | 786.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 624.23 | 231.52 | 392.70 | 1215.61 | 309.94 | 19.00 | 0.00 | 0.00 |
Minimum of Months | 472.30 | 90.97 | 285.17 | 510.30 | 3.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.65 | 401.75 | 472.10 | 2035.81 | 786.50 | 19.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1556.24 | 945.61 | 610.63 | 2137.60 | 1223.63 | 15.67 | 0.00 | 0.00 |
February | 1479.75 | 821.90 | 657.86 | 2211.54 | 1002.47 | 0.00 | 0.00 | 0.00 |
March | 1265.23 | 558.84 | 706.39 | 2226.85 | 621.28 | 0.00 | 0.00 | 0.00 |
April | 888.70 | 250.82 | 637.88 | 2113.33 | 229.43 | 0.00 | 0.00 | 0.00 |
May | 639.09 | 47.31 | 591.78 | 1983.23 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 584.60 | 9.98 | 574.63 | 1968.18 | 28.73 | 0.00 | 0.00 | 0.00 |
July | 609.80 | 8.39 | 601.41 | 1812.54 | 5.86 | 0.00 | 0.00 | 0.00 |
August | 646.87 | 34.55 | 612.32 | 1698.70 | 22.50 | 0.00 | 0.00 | 0.00 |
September | 867.18 | 225.08 | 642.10 | 1895.35 | 96.80 | 0.00 | 0.00 | 0.00 |
October | 1491.89 | 833.06 | 658.82 | 2796.64 | 494.69 | 0.00 | 0.00 | 0.00 |
November | 1863.45 | 1231.70 | 631.75 | 3038.79 | 918.32 | 0.00 | 0.00 | 0.00 |
December | 1663.08 | 1042.13 | 620.95 | 2372.54 | 1221.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1127.64 | 498.92 | 628.72 | 2187.02 | 489.69 | 15.67 | 0.00 | 0.00 |
Minimum of Months | 584.60 | 8.39 | 574.63 | 1698.70 | 5.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1863.45 | 1231.70 | 706.39 | 3038.79 | 1223.63 | 15.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.10 | 186.06 | 292.04 | 562.64 | 852.53 | 20.33 | 0.00 | 0.00 |
February | 546.72 | 201.48 | 345.24 | 748.39 | 681.61 | 0.00 | 0.00 | 0.00 |
March | 708.95 | 283.39 | 425.56 | 1184.08 | 417.38 | 0.00 | 0.00 | 0.00 |
April | 861.72 | 404.11 | 457.61 | 1786.93 | 155.96 | 0.00 | 0.00 | 0.00 |
May | 815.97 | 346.12 | 469.85 | 1984.78 | 29.73 | 0.00 | 0.00 | 0.00 |
June | 766.41 | 297.70 | 468.72 | 1981.31 | 21.06 | 0.00 | 0.00 | 0.00 |
July | 568.72 | 110.62 | 458.10 | 1483.23 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 522.31 | 92.83 | 429.48 | 1276.07 | 15.30 | 0.00 | 0.00 | 0.00 |
September | 574.15 | 168.56 | 405.60 | 1214.52 | 64.86 | 0.00 | 0.00 | 0.00 |
October | 597.61 | 237.97 | 359.64 | 1137.84 | 327.33 | 0.00 | 0.00 | 0.00 |
November | 540.63 | 230.41 | 310.22 | 855.51 | 616.20 | 0.00 | 0.00 | 0.00 |
December | 462.62 | 176.41 | 286.21 | 562.95 | 832.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.21 | 227.67 | 392.54 | 1232.99 | 333.38 | 20.33 | 0.00 | 0.00 |
Minimum of Months | 462.62 | 92.83 | 286.21 | 562.64 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.72 | 404.11 | 469.85 | 1984.78 | 852.53 | 20.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.635644E+09 | 0.313107E+10 |
February | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.101211E+10 | 0.225823E+10 |
March | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.204256E+10 | 0.152325E+10 |
April | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.341990E+10 | 0.535490E+09 |
May | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.491814E+10 | 0.105542E+09 |
June | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.517294E+10 | 76607382.23 |
July | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.473414E+10 | 17225785.60 |
August | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.398270E+10 | 56918568.18 |
September | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.299848E+10 | 0.223691E+09 |
October | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.227042E+10 | 0.119315E+10 |
November | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.124009E+10 | 0.217320E+10 |
December | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.702511E+09 | 0.307505E+10 |
Annual Sum or Average | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.331296E+11 | 0.143694E+11 |
Minimum of Months | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.635644E+09 | 17225785.60 |
Maximum of Months | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.517294E+10 | 0.313107E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.143291E+10 | 0.192650E+10 |
February | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.189803E+10 | 0.141998E+10 |
March | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.316851E+10 | 0.978053E+09 |
April | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.458640E+10 | 0.360668E+09 |
May | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.541560E+10 | 69313489.81 |
June | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.475128E+10 | 51290306.75 |
July | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.401667E+10 | 10220489.06 |
August | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.339053E+10 | 38389050.74 |
September | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.305347E+10 | 0.149771E+09 |
October | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.305157E+10 | 0.780596E+09 |
November | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.212048E+10 | 0.138215E+10 |
December | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.148851E+10 | 0.193566E+10 |
Annual Sum or Average | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.383740E+11 | 0.910260E+10 |
Minimum of Months | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.143291E+10 | 10220489.06 |
Maximum of Months | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.541560E+10 | 0.193566E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.580123E+10 | 0.300546E+10 |
February | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.538980E+10 | 0.225215E+10 |
March | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.596438E+10 | 0.157024E+10 |
April | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.544405E+10 | 0.568804E+09 |
May | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.526627E+10 | 0.102157E+09 |
June | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.505467E+10 | 76190101.49 |
July | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.481170E+10 | 15292347.92 |
August | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.451316E+10 | 58283141.99 |
September | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.488747E+10 | 0.238957E+09 |
October | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.748436E+10 | 0.125370E+10 |
November | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.790729E+10 | 0.221935E+10 |
December | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.643531E+10 | 0.301372E+10 |
Annual Sum or Average | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.689597E+11 | 0.143743E+11 |
Minimum of Months | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.451316E+10 | 15292347.92 |
Maximum of Months | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.790729E+10 | 0.301372E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.154605E+10 | 0.208546E+10 |
February | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.183729E+10 | 0.152227E+10 |
March | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.317528E+10 | 0.104950E+10 |
April | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.461026E+10 | 0.386208E+09 |
May | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.528542E+10 | 78823380.72 |
June | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.510425E+10 | 55154767.83 |
July | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.394575E+10 | 12134349.41 |
August | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.339485E+10 | 39565099.65 |
September | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.313490E+10 | 0.159595E+09 |
October | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.304762E+10 | 0.823889E+09 |
November | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.224445E+10 | 0.147436E+10 |
December | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.155614E+10 | 0.203646E+10 |
Annual Sum or Average | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.388823E+11 | 0.972342E+10 |
Minimum of Months | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.154605E+10 | 12134349.41 |
Maximum of Months | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.528542E+10 | 0.208546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305485E+09 | 0.00 | 0.305485E+09 | 0.188353E+09 | 0.117942E+10 |
February | 0.327197E+09 | 0.00 | 0.327197E+09 | 0.331752E+09 | 0.810820E+09 |
March | 0.436517E+09 | 0.00 | 0.436517E+09 | 0.697463E+09 | 0.515657E+09 |
April | 0.458376E+09 | 1554509.24 | 0.456822E+09 | 0.117121E+10 | 0.166687E+09 |
May | 0.524777E+09 | 14726215.66 | 0.510051E+09 | 0.166815E+10 | 28999565.93 |
June | 0.525704E+09 | 19472185.50 | 0.506232E+09 | 0.174065E+10 | 23967952.09 |
July | 0.535747E+09 | 8483873.51 | 0.527263E+09 | 0.157909E+10 | 7411741.73 |
August | 0.491831E+09 | 1532816.68 | 0.490298E+09 | 0.131779E+10 | 25536158.38 |
September | 0.424099E+09 | 29779.32 | 0.424069E+09 | 0.988151E+09 | 92997537.35 |
October | 0.379654E+09 | 0.00 | 0.379654E+09 | 0.745825E+09 | 0.443497E+09 |
November | 0.311197E+09 | 0.00 | 0.311197E+09 | 0.389311E+09 | 0.821085E+09 |
December | 0.298006E+09 | 0.00 | 0.298006E+09 | 0.198271E+09 | 0.117940E+10 |
Annual Sum or Average | 0.501859E+10 | 45799379.90 | 0.497279E+10 | 0.110160E+11 | 0.529548E+10 |
Minimum of Months | 0.298006E+09 | 0.00 | 0.298006E+09 | 0.188353E+09 | 7411741.73 |
Maximum of Months | 0.535747E+09 | 19472185.50 | 0.527263E+09 | 0.174065E+10 | 0.117942E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305497E+09 | 0.00 | 0.305497E+09 | 0.188359E+09 | 0.117949E+10 |
February | 0.327210E+09 | 0.00 | 0.327210E+09 | 0.331765E+09 | 0.810866E+09 |
March | 0.436535E+09 | 0.00 | 0.436535E+09 | 0.697496E+09 | 0.515683E+09 |
April | 0.458396E+09 | 1554551.03 | 0.456842E+09 | 0.117127E+10 | 0.166693E+09 |
May | 0.524799E+09 | 14726611.51 | 0.510072E+09 | 0.166825E+10 | 28999672.64 |
June | 0.525726E+09 | 19472708.91 | 0.506253E+09 | 0.174075E+10 | 23968770.76 |
July | 0.535767E+09 | 8484101.56 | 0.527283E+09 | 0.157917E+10 | 7411713.59 |
August | 0.491849E+09 | 1532857.88 | 0.490316E+09 | 0.131785E+10 | 25536597.05 |
September | 0.424115E+09 | 29780.12 | 0.424085E+09 | 0.988201E+09 | 93000053.05 |
October | 0.379669E+09 | 0.00 | 0.379669E+09 | 0.745863E+09 | 0.443518E+09 |
November | 0.311210E+09 | 0.00 | 0.311210E+09 | 0.389330E+09 | 0.821129E+09 |
December | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.198277E+09 | 0.117946E+10 |
Annual Sum or Average | 0.501879E+10 | 45800611.00 | 0.497299E+10 | 0.110166E+11 | 0.529576E+10 |
Minimum of Months | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.188359E+09 | 7411713.59 |
Maximum of Months | 0.535767E+09 | 19472708.91 | 0.527283E+09 | 0.174075E+10 | 0.117949E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305497E+09 | 0.00 | 0.305497E+09 | 0.188359E+09 | 0.117949E+10 |
February | 0.327210E+09 | 0.00 | 0.327210E+09 | 0.331765E+09 | 0.810866E+09 |
March | 0.436535E+09 | 0.00 | 0.436535E+09 | 0.697496E+09 | 0.515683E+09 |
April | 0.458396E+09 | 1554551.03 | 0.456842E+09 | 0.117127E+10 | 0.166693E+09 |
May | 0.524799E+09 | 14726611.51 | 0.510072E+09 | 0.166825E+10 | 28999672.64 |
June | 0.525726E+09 | 19472708.91 | 0.506253E+09 | 0.174075E+10 | 23968770.76 |
July | 0.535767E+09 | 8484101.56 | 0.527283E+09 | 0.157917E+10 | 7411713.59 |
August | 0.491849E+09 | 1532857.88 | 0.490316E+09 | 0.131785E+10 | 25536597.05 |
September | 0.424115E+09 | 29780.12 | 0.424085E+09 | 0.988201E+09 | 93000053.05 |
October | 0.379669E+09 | 0.00 | 0.379669E+09 | 0.745863E+09 | 0.443518E+09 |
November | 0.311210E+09 | 0.00 | 0.311210E+09 | 0.389330E+09 | 0.821129E+09 |
December | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.198277E+09 | 0.117946E+10 |
Annual Sum or Average | 0.501879E+10 | 45800611.00 | 0.497299E+10 | 0.110166E+11 | 0.529576E+10 |
Minimum of Months | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.188359E+09 | 7411713.59 |
Maximum of Months | 0.535767E+09 | 19472708.91 | 0.527283E+09 | 0.174075E+10 | 0.117949E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125908E+10 | 0.505375E+09 | 0.753705E+09 | 0.129915E+10 | 0.212067E+10 |
February | 0.138159E+10 | 0.570384E+09 | 0.811210E+09 | 0.180525E+10 | 0.149672E+10 |
March | 0.186598E+10 | 0.770207E+09 | 0.109577E+10 | 0.307994E+10 | 0.979621E+09 |
April | 0.214842E+10 | 0.100170E+10 | 0.114672E+10 | 0.446937E+10 | 0.344529E+09 |
May | 0.218512E+10 | 0.968759E+09 | 0.121636E+10 | 0.525737E+10 | 63132054.65 |
June | 0.172103E+10 | 0.571035E+09 | 0.115000E+10 | 0.459755E+10 | 49370629.65 |
July | 0.149470E+10 | 0.315639E+09 | 0.117906E+10 | 0.385823E+10 | 13908334.22 |
August | 0.134679E+10 | 0.234371E+09 | 0.111242E+10 | 0.324114E+10 | 52102588.16 |
September | 0.139247E+10 | 0.388324E+09 | 0.100415E+10 | 0.291822E+10 | 0.188308E+09 |
October | 0.157397E+10 | 0.635779E+09 | 0.938195E+09 | 0.291566E+10 | 0.853143E+09 |
November | 0.135054E+10 | 0.579710E+09 | 0.770828E+09 | 0.198683E+10 | 0.151689E+10 |
December | 0.121687E+10 | 0.482127E+09 | 0.734739E+09 | 0.133457E+10 | 0.215342E+10 |
Annual Sum or Average | 0.189366E+11 | 0.702341E+10 | 0.119132E+11 | 0.367633E+11 | 0.983181E+10 |
Minimum of Months | 0.121687E+10 | 0.234371E+09 | 0.734739E+09 | 0.129915E+10 | 13908334.22 |
Maximum of Months | 0.218512E+10 | 0.100170E+10 | 0.121636E+10 | 0.525737E+10 | 0.215342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49782875.71 | 19982077.15 | 29800798.56 | 51367402.44 | 83849307.76 |
February | 54626992.37 | 22552487.90 | 32074504.48 | 71377938.95 | 59178835.88 |
March | 73779083.82 | 30453304.59 | 43325779.23 | 0.121778E+09 | 38733350.22 |
April | 84946476.03 | 39606217.43 | 45340258.60 | 0.176715E+09 | 13622370.38 |
May | 86397680.08 | 38303848.58 | 48093831.50 | 0.207872E+09 | 2496184.60 |
June | 68048135.35 | 22578193.78 | 45469941.58 | 0.181783E+09 | 1952070.25 |
July | 59099080.80 | 12480090.13 | 46618990.67 | 0.152551E+09 | 549923.01 |
August | 53250721.51 | 9266833.39 | 43983888.12 | 0.128152E+09 | 2060089.43 |
September | 55057092.91 | 15353990.10 | 39703102.81 | 0.115384E+09 | 7445530.31 |
October | 62233497.71 | 25138116.68 | 37095381.03 | 0.115283E+09 | 33732506.19 |
November | 53399050.41 | 22921191.96 | 30477858.45 | 78557626.64 | 59976393.53 |
December | 48113780.19 | 19062880.35 | 29050899.84 | 52767698.94 | 85144323.63 |
Annual Sum or Average | 0.748734E+09 | 0.277699E+09 | 0.471035E+09 | 0.145359E+10 | 0.388741E+09 |
Minimum of Months | 48113780.19 | 9266833.39 | 29050899.84 | 51367402.44 | 549923.01 |
Maximum of Months | 86397680.08 | 39606217.43 | 48093831.50 | 0.207872E+09 | 85144323.63 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138938E+10 | 0.844223E+09 | 0.545161E+09 | 0.192253E+10 | 0.115243E+10 |
February | 0.119325E+10 | 0.662765E+09 | 0.530489E+09 | 0.180129E+10 | 0.831971E+09 |
March | 0.112958E+10 | 0.498922E+09 | 0.630655E+09 | 0.200829E+10 | 0.551470E+09 |
April | 0.767828E+09 | 0.216703E+09 | 0.551125E+09 | 0.183387E+10 | 0.187365E+09 |
May | 0.570578E+09 | 42237652.62 | 0.528340E+09 | 0.175966E+10 | 30589012.15 |
June | 0.505095E+09 | 8619186.74 | 0.496476E+09 | 0.167783E+10 | 24416421.70 |
July | 0.544422E+09 | 7488005.76 | 0.536934E+09 | 0.159037E+10 | 7181364.38 |
August | 0.577516E+09 | 30843432.88 | 0.546672E+09 | 0.148389E+10 | 27222930.84 |
September | 0.749231E+09 | 0.194463E+09 | 0.554767E+09 | 0.161193E+10 | 0.106481E+09 |
October | 0.133194E+10 | 0.743745E+09 | 0.588192E+09 | 0.247960E+10 | 0.487429E+09 |
November | 0.160999E+10 | 0.106417E+10 | 0.545824E+09 | 0.262450E+10 | 0.859016E+09 |
December | 0.148477E+10 | 0.930396E+09 | 0.554375E+09 | 0.211865E+10 | 0.116617E+10 |
Annual Sum or Average | 0.118536E+11 | 0.524457E+10 | 0.660901E+10 | 0.229124E+11 | 0.543174E+10 |
Minimum of Months | 0.505095E+09 | 7488005.76 | 0.496476E+09 | 0.148389E+10 | 7181364.38 |
Maximum of Months | 0.160999E+10 | 0.106417E+10 | 0.630655E+09 | 0.262450E+10 | 0.116617E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138938E+10 | 0.844223E+09 | 0.545161E+09 | 0.192253E+10 | 0.115243E+10 |
February | 0.119325E+10 | 0.662765E+09 | 0.530489E+09 | 0.180129E+10 | 0.831971E+09 |
March | 0.112958E+10 | 0.498922E+09 | 0.630655E+09 | 0.200829E+10 | 0.551470E+09 |
April | 0.767828E+09 | 0.216703E+09 | 0.551125E+09 | 0.183387E+10 | 0.187365E+09 |
May | 0.570578E+09 | 42237652.62 | 0.528340E+09 | 0.175966E+10 | 30589012.15 |
June | 0.505095E+09 | 8619186.74 | 0.496476E+09 | 0.167783E+10 | 24416421.70 |
July | 0.544422E+09 | 7488005.76 | 0.536934E+09 | 0.159037E+10 | 7181364.38 |
August | 0.577516E+09 | 30843432.88 | 0.546672E+09 | 0.148389E+10 | 27222930.84 |
September | 0.749231E+09 | 0.194463E+09 | 0.554767E+09 | 0.161193E+10 | 0.106481E+09 |
October | 0.133194E+10 | 0.743745E+09 | 0.588192E+09 | 0.247960E+10 | 0.487429E+09 |
November | 0.160999E+10 | 0.106417E+10 | 0.545824E+09 | 0.262450E+10 | 0.859016E+09 |
December | 0.148477E+10 | 0.930396E+09 | 0.554375E+09 | 0.211865E+10 | 0.116617E+10 |
Annual Sum or Average | 0.118536E+11 | 0.524457E+10 | 0.660901E+10 | 0.229124E+11 | 0.543174E+10 |
Minimum of Months | 0.505095E+09 | 7488005.76 | 0.496476E+09 | 0.148389E+10 | 7181364.38 |
Maximum of Months | 0.160999E+10 | 0.106417E+10 | 0.630655E+09 | 0.262450E+10 | 0.116617E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138930E+10 | 0.844169E+09 | 0.545126E+09 | 0.192241E+10 | 0.115236E+10 |
February | 0.119318E+10 | 0.662723E+09 | 0.530456E+09 | 0.180117E+10 | 0.831919E+09 |
March | 0.112951E+10 | 0.498891E+09 | 0.630615E+09 | 0.200816E+10 | 0.551435E+09 |
April | 0.767779E+09 | 0.216689E+09 | 0.551090E+09 | 0.183375E+10 | 0.187354E+09 |
May | 0.570542E+09 | 42234983.44 | 0.528307E+09 | 0.175955E+10 | 30587079.10 |
June | 0.505064E+09 | 8618642.05 | 0.496445E+09 | 0.167772E+10 | 24414878.72 |
July | 0.544388E+09 | 7487532.56 | 0.536900E+09 | 0.159026E+10 | 7180910.55 |
August | 0.577479E+09 | 30841483.75 | 0.546638E+09 | 0.148380E+10 | 27221210.51 |
September | 0.749183E+09 | 0.194451E+09 | 0.554732E+09 | 0.161182E+10 | 0.106474E+09 |
October | 0.133185E+10 | 0.743698E+09 | 0.588154E+09 | 0.247945E+10 | 0.487398E+09 |
November | 0.160989E+10 | 0.106410E+10 | 0.545789E+09 | 0.262434E+10 | 0.858962E+09 |
December | 0.148468E+10 | 0.930338E+09 | 0.554340E+09 | 0.211852E+10 | 0.116609E+10 |
Annual Sum or Average | 0.118528E+11 | 0.524424E+10 | 0.660859E+10 | 0.229110E+11 | 0.543140E+10 |
Minimum of Months | 0.505064E+09 | 7487532.56 | 0.496445E+09 | 0.148380E+10 | 7180910.55 |
Maximum of Months | 0.160989E+10 | 0.106410E+10 | 0.630615E+09 | 0.262434E+10 | 0.116609E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123181E+10 | 0.479372E+09 | 0.752438E+09 | 0.144719E+10 | 0.229465E+10 |
February | 0.127229E+10 | 0.468872E+09 | 0.803419E+09 | 0.176068E+10 | 0.160888E+10 |
March | 0.182661E+10 | 0.730156E+09 | 0.109645E+10 | 0.308859E+10 | 0.105984E+10 |
April | 0.214860E+10 | 0.100761E+10 | 0.114099E+10 | 0.448861E+10 | 0.374329E+09 |
May | 0.210234E+10 | 0.891767E+09 | 0.121058E+10 | 0.511983E+10 | 73982596.52 |
June | 0.191096E+10 | 0.742266E+09 | 0.116870E+10 | 0.492578E+10 | 55340042.20 |
July | 0.146530E+10 | 0.285000E+09 | 0.118030E+10 | 0.378706E+10 | 16068876.75 |
August | 0.134572E+10 | 0.239175E+09 | 0.110655E+10 | 0.324045E+10 | 53628062.57 |
September | 0.143158E+10 | 0.420271E+09 | 0.101131E+10 | 0.299501E+10 | 0.202577E+09 |
October | 0.153973E+10 | 0.613114E+09 | 0.926613E+09 | 0.291215E+10 | 0.907743E+09 |
November | 0.134800E+10 | 0.574509E+09 | 0.773495E+09 | 0.211501E+10 | 0.163429E+10 |
December | 0.119194E+10 | 0.454514E+09 | 0.737431E+09 | 0.142783E+10 | 0.227470E+10 |
Annual Sum or Average | 0.188149E+11 | 0.690662E+10 | 0.119083E+11 | 0.373082E+11 | 0.105560E+11 |
Minimum of Months | 0.119194E+10 | 0.239175E+09 | 0.737431E+09 | 0.142783E+10 | 16068876.75 |
Maximum of Months | 0.214860E+10 | 0.100761E+10 | 0.121058E+10 | 0.511983E+10 | 0.229465E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48704544.42 | 18953876.96 | 29750667.45 | 57220346.32 | 90728346.70 |
February | 50305114.38 | 18538715.82 | 31766398.56 | 69615424.66 | 63613577.13 |
March | 72222168.57 | 28869617.75 | 43352550.82 | 0.122120E+09 | 41905254.27 |
April | 84953547.95 | 39839791.47 | 45113756.47 | 0.177475E+09 | 14800596.20 |
May | 83124525.94 | 35259549.00 | 47864976.95 | 0.202433E+09 | 2925190.90 |
June | 75557532.32 | 29348432.76 | 46209099.55 | 0.194761E+09 | 2188090.18 |
July | 57936481.56 | 11268615.00 | 46667866.56 | 0.149737E+09 | 635345.12 |
August | 53208563.17 | 9456740.43 | 43751822.74 | 0.128124E+09 | 2120396.68 |
September | 56603380.70 | 16617070.77 | 39986309.93 | 0.118420E+09 | 8009702.47 |
October | 60879265.82 | 24241916.18 | 36637349.64 | 0.115143E+09 | 35891293.80 |
November | 53298707.56 | 22715483.29 | 30583224.27 | 83625475.64 | 64618142.17 |
December | 47128295.36 | 17971013.27 | 29157282.09 | 56454983.18 | 89939351.78 |
Annual Sum or Average | 0.743922E+09 | 0.273081E+09 | 0.470841E+09 | 0.147513E+10 | 0.417375E+09 |
Minimum of Months | 47128295.36 | 9456740.43 | 29157282.09 | 56454983.18 | 635345.12 |
Maximum of Months | 84953547.95 | 39839791.47 | 47864976.95 | 0.202433E+09 | 90728346.70 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.569324E+09 | 0.344739E+10 |
February | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.963959E+09 | 0.245977E+10 |
March | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.203274E+10 | 0.162806E+10 |
April | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.344769E+10 | 0.561272E+09 |
May | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.496239E+10 | 0.106024E+09 |
June | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.521942E+10 | 75292673.99 |
July | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.477722E+10 | 17496281.05 |
August | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.401792E+10 | 58994504.40 |
September | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.301795E+10 | 0.236198E+09 |
October | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.226911E+10 | 0.127291E+10 |
November | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.119424E+10 | 0.236553E+10 |
December | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.623587E+09 | 0.338937E+10 |
Annual Sum or Average | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.330956E+11 | 0.156183E+11 |
Minimum of Months | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.569324E+09 | 17496281.05 |
Maximum of Months | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.521942E+10 | 0.344739E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.136679E+10 | 0.210194E+10 |
February | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.186081E+10 | 0.152610E+10 |
March | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.316351E+10 | 0.103166E+10 |
April | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.461060E+10 | 0.374657E+09 |
May | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.545270E+10 | 69227553.00 |
June | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.478720E+10 | 49811900.15 |
July | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.404882E+10 | 10392480.45 |
August | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.341686E+10 | 39482141.91 |
September | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.306978E+10 | 0.156639E+09 |
October | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.305202E+10 | 0.824620E+09 |
November | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.208676E+10 | 0.148330E+10 |
December | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.141963E+10 | 0.210655E+10 |
Annual Sum or Average | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.383355E+11 | 0.977438E+10 |
Minimum of Months | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.136679E+10 | 10392480.45 |
Maximum of Months | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.545270E+10 | 0.210655E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.572536E+10 | 0.327736E+10 |
February | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.535017E+10 | 0.242519E+10 |
March | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.596439E+10 | 0.166403E+10 |
April | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.547776E+10 | 0.594685E+09 |
May | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.531187E+10 | 0.103069E+09 |
June | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.510152E+10 | 74480158.07 |
July | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.485471E+10 | 15704470.39 |
August | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.454980E+10 | 60257740.30 |
September | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.491274E+10 | 0.250895E+09 |
October | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.749053E+10 | 0.132499E+10 |
November | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.787654E+10 | 0.238027E+10 |
December | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.635462E+10 | 0.327181E+10 |
Annual Sum or Average | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.689700E+11 | 0.154427E+11 |
Minimum of Months | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.454980E+10 | 15704470.39 |
Maximum of Months | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.787654E+10 | 0.327736E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.150698E+10 | 0.228342E+10 |
February | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.181050E+10 | 0.164894E+10 |
March | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.317145E+10 | 0.111791E+10 |
April | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.463172E+10 | 0.404247E+09 |
May | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.531604E+10 | 79617702.26 |
June | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.513556E+10 | 54581514.82 |
July | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.397269E+10 | 12233892.34 |
August | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.341782E+10 | 40970040.63 |
September | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.314804E+10 | 0.168113E+09 |
October | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.304758E+10 | 0.876727E+09 |
November | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.221749E+10 | 0.159720E+10 |
December | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.150781E+10 | 0.222961E+10 |
Annual Sum or Average | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.388837E+11 | 0.105136E+11 |
Minimum of Months | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.150698E+10 | 12233892.34 |
Maximum of Months | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.531604E+10 | 0.228342E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.32 | 1169.01 | 342.18 | 0.00 | 342.18 | 0.00 | 0.00 |
February | 418.37 | 933.46 | 405.77 | 0.00 | 405.77 | 0.00 | 0.00 |
March | 762.60 | 568.72 | 488.95 | 0.00 | 488.95 | 0.00 | 0.00 |
April | 1319.40 | 206.59 | 530.55 | 1.80 | 528.75 | 0.00 | 0.00 |
May | 1836.22 | 39.40 | 587.82 | 16.50 | 571.32 | 0.00 | 0.00 |
June | 1995.73 | 29.56 | 608.48 | 22.54 | 585.94 | 0.00 | 0.00 |
July | 1767.52 | 6.43 | 600.10 | 9.50 | 590.60 | 0.00 | 0.00 |
August | 1486.97 | 21.25 | 550.91 | 1.72 | 549.20 | 0.00 | 0.00 |
September | 1156.82 | 86.30 | 490.88 | 0.03 | 490.84 | 0.00 | 0.00 |
October | 847.68 | 445.47 | 425.26 | 0.00 | 425.26 | 0.00 | 0.00 |
November | 478.43 | 838.43 | 360.20 | 0.00 | 360.20 | 0.00 | 0.00 |
December | 262.29 | 1148.09 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1050.53 | 455.65 | 477.44 | 4.36 | 473.08 | 0.00 | 0.00 |
Minimum of Months | 237.32 | 6.43 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 1995.73 | 1169.01 | 608.48 | 22.54 | 590.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 534.99 | 719.27 | 488.68 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 784.57 | 586.96 | 593.69 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1182.99 | 365.16 | 724.23 | 298.94 | 425.30 | 0.00 | 0.00 |
April | 1769.44 | 139.15 | 861.65 | 401.75 | 459.90 | 0.00 | 0.00 |
May | 2021.95 | 25.88 | 848.10 | 376.00 | 472.10 | 0.00 | 0.00 |
June | 1833.05 | 19.79 | 690.24 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1499.65 | 3.82 | 580.13 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1265.88 | 14.33 | 522.72 | 90.97 | 431.76 | 0.00 | 0.00 |
September | 1178.04 | 57.78 | 558.47 | 155.74 | 402.73 | 0.00 | 0.00 |
October | 1139.32 | 291.44 | 610.90 | 246.76 | 364.14 | 0.00 | 0.00 |
November | 818.09 | 533.24 | 541.65 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 555.74 | 722.69 | 472.30 | 187.13 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1216.83 | 288.64 | 624.23 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 534.99 | 3.82 | 472.30 | 90.97 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2021.95 | 722.69 | 861.65 | 401.75 | 472.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2165.93 | 1122.11 | 1556.24 | 945.61 | 610.63 | 0.00 | 0.00 |
February | 2227.92 | 930.95 | 1479.75 | 821.90 | 657.86 | 0.00 | 0.00 |
March | 2226.84 | 586.26 | 1265.23 | 558.84 | 706.39 | 0.00 | 0.00 |
April | 2100.33 | 219.45 | 888.70 | 250.82 | 637.88 | 0.00 | 0.00 |
May | 1966.20 | 38.14 | 639.09 | 47.31 | 591.78 | 0.00 | 0.00 |
June | 1950.11 | 29.39 | 584.60 | 9.98 | 574.63 | 0.00 | 0.00 |
July | 1796.48 | 5.71 | 609.80 | 8.39 | 601.41 | 0.00 | 0.00 |
August | 1685.02 | 21.76 | 646.87 | 34.55 | 612.32 | 0.00 | 0.00 |
September | 1885.60 | 92.19 | 867.18 | 225.08 | 642.10 | 0.00 | 0.00 |
October | 2794.34 | 468.08 | 1491.89 | 833.06 | 658.82 | 0.00 | 0.00 |
November | 3050.65 | 856.23 | 1863.45 | 1231.70 | 631.75 | 0.00 | 0.00 |
December | 2402.67 | 1125.19 | 1663.08 | 1042.13 | 620.95 | 0.00 | 0.00 |
Annual Sum or Average | 2186.70 | 455.81 | 1127.64 | 498.92 | 628.72 | 0.00 | 0.00 |
Minimum of Months | 1685.02 | 5.71 | 584.60 | 8.39 | 574.63 | 0.00 | 0.00 |
Maximum of Months | 3050.65 | 1125.19 | 1863.45 | 1231.70 | 706.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 577.23 | 778.62 | 478.10 | 186.06 | 292.04 | 0.00 | 0.00 |
February | 759.46 | 629.24 | 546.72 | 201.48 | 345.24 | 0.00 | 0.00 |
March | 1185.51 | 391.84 | 708.95 | 283.39 | 425.56 | 0.00 | 0.00 |
April | 1778.65 | 149.00 | 861.72 | 404.11 | 457.61 | 0.00 | 0.00 |
May | 1973.35 | 29.43 | 815.97 | 346.12 | 469.85 | 0.00 | 0.00 |
June | 1969.23 | 21.28 | 766.41 | 297.70 | 468.72 | 0.00 | 0.00 |
July | 1473.18 | 4.53 | 568.72 | 110.62 | 458.10 | 0.00 | 0.00 |
August | 1267.49 | 14.77 | 522.31 | 92.83 | 429.48 | 0.00 | 0.00 |
September | 1209.45 | 61.57 | 574.15 | 168.56 | 405.60 | 0.00 | 0.00 |
October | 1137.85 | 307.60 | 597.61 | 237.97 | 359.64 | 0.00 | 0.00 |
November | 865.92 | 568.81 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 581.00 | 760.33 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1232.95 | 308.33 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 577.23 | 4.53 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1973.35 | 778.62 | 861.72 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.97 | 1321.09 | 342.17 | 0.00 | 342.17 | 0.00 | 0.00 |
February | 411.41 | 1005.52 | 405.76 | 0.00 | 405.76 | 0.00 | 0.00 |
March | 781.23 | 577.59 | 488.94 | 0.00 | 488.94 | 0.00 | 0.00 |
April | 1355.61 | 192.93 | 530.54 | 1.80 | 528.74 | 0.00 | 0.00 |
May | 1868.52 | 32.48 | 587.80 | 16.49 | 571.31 | 0.00 | 0.00 |
June | 2014.72 | 27.74 | 608.47 | 22.54 | 585.93 | 0.00 | 0.00 |
July | 1768.76 | 8.30 | 600.09 | 9.50 | 590.59 | 0.00 | 0.00 |
August | 1476.07 | 28.60 | 550.90 | 1.72 | 549.18 | 0.00 | 0.00 |
September | 1143.73 | 107.64 | 490.87 | 0.03 | 490.83 | 0.00 | 0.00 |
October | 835.41 | 496.76 | 425.25 | 0.00 | 425.25 | 0.00 | 0.00 |
November | 450.61 | 950.36 | 360.19 | 0.00 | 360.19 | 0.00 | 0.00 |
December | 222.08 | 1321.06 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1047.98 | 503.77 | 477.43 | 4.36 | 473.07 | 0.00 | 0.00 |
Minimum of Months | 210.97 | 8.30 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 2014.72 | 1321.09 | 608.47 | 22.54 | 590.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 504.23 | 823.07 | 488.67 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 775.72 | 643.14 | 593.68 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1195.38 | 380.21 | 724.22 | 298.93 | 425.29 | 0.00 | 0.00 |
April | 1792.47 | 138.18 | 861.64 | 401.74 | 459.90 | 0.00 | 0.00 |
May | 2040.49 | 24.50 | 848.09 | 375.99 | 472.09 | 0.00 | 0.00 |
June | 1843.88 | 19.80 | 690.23 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1497.45 | 5.40 | 580.12 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1257.95 | 20.22 | 522.71 | 90.96 | 431.75 | 0.00 | 0.00 |
September | 1170.37 | 75.52 | 558.46 | 155.74 | 402.72 | 0.00 | 0.00 |
October | 1131.62 | 331.12 | 610.89 | 246.76 | 364.13 | 0.00 | 0.00 |
November | 796.83 | 608.36 | 541.64 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 517.97 | 835.78 | 472.29 | 187.12 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1211.85 | 324.09 | 624.22 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 504.23 | 5.40 | 472.29 | 90.96 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2040.49 | 835.78 | 861.64 | 401.74 | 472.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2153.33 | 1290.78 | 1556.18 | 945.57 | 610.61 | 0.00 | 0.00 |
February | 2233.69 | 1031.69 | 1479.70 | 821.86 | 657.83 | 0.00 | 0.00 |
March | 2249.38 | 617.67 | 1265.18 | 558.82 | 706.36 | 0.00 | 0.00 |
April | 2122.49 | 216.85 | 888.67 | 250.81 | 637.86 | 0.00 | 0.00 |
May | 1970.90 | 34.26 | 639.07 | 47.31 | 591.77 | 0.00 | 0.00 |
June | 1941.89 | 28.26 | 584.59 | 9.98 | 574.61 | 0.00 | 0.00 |
July | 1781.29 | 8.04 | 609.78 | 8.39 | 601.39 | 0.00 | 0.00 |
August | 1662.03 | 30.49 | 646.85 | 34.55 | 612.30 | 0.00 | 0.00 |
September | 1865.62 | 123.24 | 867.15 | 225.07 | 642.08 | 0.00 | 0.00 |
October | 2777.28 | 545.94 | 1491.83 | 833.03 | 658.80 | 0.00 | 0.00 |
November | 3037.56 | 994.21 | 1863.38 | 1231.65 | 631.73 | 0.00 | 0.00 |
December | 2372.99 | 1306.16 | 1663.01 | 1042.09 | 620.93 | 0.00 | 0.00 |
Annual Sum or Average | 2179.60 | 516.71 | 1127.60 | 498.90 | 628.70 | 0.00 | 0.00 |
Minimum of Months | 1662.03 | 8.04 | 584.59 | 8.39 | 574.61 | 0.00 | 0.00 |
Maximum of Months | 3037.56 | 1306.16 | 1863.38 | 1231.65 | 706.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 561.68 | 890.60 | 478.09 | 186.05 | 292.04 | 0.00 | 0.00 |
February | 756.57 | 691.34 | 546.71 | 201.48 | 345.23 | 0.00 | 0.00 |
March | 1198.74 | 411.35 | 708.94 | 283.39 | 425.55 | 0.00 | 0.00 |
April | 1800.19 | 150.13 | 861.71 | 404.11 | 457.60 | 0.00 | 0.00 |
May | 1987.10 | 28.71 | 815.96 | 346.11 | 469.85 | 0.00 | 0.00 |
June | 1975.52 | 22.19 | 766.40 | 297.69 | 468.71 | 0.00 | 0.00 |
July | 1469.83 | 6.24 | 568.71 | 110.61 | 458.10 | 0.00 | 0.00 |
August | 1257.68 | 20.81 | 522.30 | 92.83 | 429.47 | 0.00 | 0.00 |
September | 1201.17 | 81.25 | 574.15 | 168.55 | 405.59 | 0.00 | 0.00 |
October | 1130.26 | 352.31 | 597.60 | 237.96 | 359.64 | 0.00 | 0.00 |
November | 848.24 | 655.44 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 554.17 | 882.85 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1229.81 | 347.96 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 554.17 | 6.24 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1987.10 | 890.60 | 861.71 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.56 | 1287.11 | 342.18 | 0.00 | 342.18 | 0.00 | 0.00 |
February | 398.46 | 1016.77 | 405.77 | 0.00 | 405.77 | 0.00 | 0.00 |
March | 758.94 | 607.85 | 488.95 | 0.00 | 488.95 | 0.00 | 0.00 |
April | 1330.13 | 216.54 | 530.55 | 1.80 | 528.75 | 0.00 | 0.00 |
May | 1852.75 | 39.58 | 587.82 | 16.50 | 571.32 | 0.00 | 0.00 |
June | 2013.67 | 29.05 | 608.48 | 22.54 | 585.94 | 0.00 | 0.00 |
July | 1783.61 | 6.53 | 600.10 | 9.50 | 590.60 | 0.00 | 0.00 |
August | 1500.12 | 22.03 | 550.91 | 1.72 | 549.20 | 0.00 | 0.00 |
September | 1164.33 | 91.13 | 490.88 | 0.03 | 490.84 | 0.00 | 0.00 |
October | 847.19 | 475.25 | 425.26 | 0.00 | 425.26 | 0.00 | 0.00 |
November | 460.74 | 912.63 | 360.20 | 0.00 | 360.20 | 0.00 | 0.00 |
December | 232.82 | 1265.44 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1049.45 | 495.25 | 477.44 | 4.36 | 473.08 | 0.00 | 0.00 |
Minimum of Months | 212.56 | 6.53 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 2013.67 | 1287.11 | 608.48 | 22.54 | 590.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.30 | 784.77 | 488.68 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 769.18 | 630.83 | 593.69 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1181.12 | 385.18 | 724.23 | 298.94 | 425.30 | 0.00 | 0.00 |
April | 1778.78 | 144.54 | 861.65 | 401.75 | 459.90 | 0.00 | 0.00 |
May | 2035.81 | 25.85 | 848.10 | 376.00 | 472.10 | 0.00 | 0.00 |
June | 1846.92 | 19.22 | 690.24 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1511.66 | 3.88 | 580.13 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1275.71 | 14.74 | 522.72 | 90.97 | 431.76 | 0.00 | 0.00 |
September | 1184.33 | 60.43 | 558.47 | 155.74 | 402.73 | 0.00 | 0.00 |
October | 1139.49 | 307.88 | 610.90 | 246.76 | 364.14 | 0.00 | 0.00 |
November | 805.08 | 572.26 | 541.65 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 530.03 | 786.50 | 472.30 | 187.13 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1215.61 | 309.94 | 624.23 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 510.30 | 3.88 | 472.30 | 90.97 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2035.81 | 786.50 | 861.65 | 401.75 | 472.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2137.60 | 1223.63 | 1556.24 | 945.61 | 610.63 | 0.00 | 0.00 |
February | 2211.54 | 1002.47 | 1479.75 | 821.90 | 657.86 | 0.00 | 0.00 |
March | 2226.85 | 621.28 | 1265.23 | 558.84 | 706.39 | 0.00 | 0.00 |
April | 2113.33 | 229.43 | 888.70 | 250.82 | 637.88 | 0.00 | 0.00 |
May | 1983.23 | 38.48 | 639.09 | 47.31 | 591.78 | 0.00 | 0.00 |
June | 1968.18 | 28.73 | 584.60 | 9.98 | 574.63 | 0.00 | 0.00 |
July | 1812.54 | 5.86 | 609.80 | 8.39 | 601.41 | 0.00 | 0.00 |
August | 1698.70 | 22.50 | 646.87 | 34.55 | 612.32 | 0.00 | 0.00 |
September | 1895.35 | 96.80 | 867.18 | 225.08 | 642.10 | 0.00 | 0.00 |
October | 2796.64 | 494.69 | 1491.89 | 833.06 | 658.82 | 0.00 | 0.00 |
November | 3038.79 | 918.32 | 1863.45 | 1231.70 | 631.75 | 0.00 | 0.00 |
December | 2372.54 | 1221.55 | 1663.08 | 1042.13 | 620.95 | 0.00 | 0.00 |
Annual Sum or Average | 2187.02 | 489.69 | 1127.64 | 498.92 | 628.72 | 0.00 | 0.00 |
Minimum of Months | 1698.70 | 5.86 | 584.60 | 8.39 | 574.63 | 0.00 | 0.00 |
Maximum of Months | 3038.79 | 1223.63 | 1863.45 | 1231.70 | 706.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 562.64 | 852.53 | 478.10 | 186.06 | 292.04 | 0.00 | 0.00 |
February | 748.39 | 681.61 | 546.72 | 201.48 | 345.24 | 0.00 | 0.00 |
March | 1184.08 | 417.38 | 708.95 | 283.39 | 425.56 | 0.00 | 0.00 |
April | 1786.93 | 155.96 | 861.72 | 404.11 | 457.61 | 0.00 | 0.00 |
May | 1984.78 | 29.73 | 815.97 | 346.12 | 469.85 | 0.00 | 0.00 |
June | 1981.31 | 21.06 | 766.41 | 297.70 | 468.72 | 0.00 | 0.00 |
July | 1483.23 | 4.57 | 568.72 | 110.62 | 458.10 | 0.00 | 0.00 |
August | 1276.07 | 15.30 | 522.31 | 92.83 | 429.48 | 0.00 | 0.00 |
September | 1214.52 | 64.86 | 574.15 | 168.56 | 405.60 | 0.00 | 0.00 |
October | 1137.84 | 327.33 | 597.61 | 237.97 | 359.64 | 0.00 | 0.00 |
November | 855.51 | 616.20 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 562.95 | 832.44 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1232.99 | 333.38 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 562.64 | 4.57 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1984.78 | 852.53 | 861.72 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.635644E+09 | 0.313107E+10 | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.00 | 0.00 |
February | 0.101211E+10 | 0.225823E+10 | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.00 | 0.00 |
March | 0.204256E+10 | 0.152325E+10 | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.00 | 0.00 |
April | 0.341990E+10 | 0.535490E+09 | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.00 | 0.00 |
May | 0.491814E+10 | 0.105542E+09 | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.00 | 0.00 |
June | 0.517294E+10 | 76607382.23 | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.00 | 0.00 |
July | 0.473414E+10 | 17225785.60 | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.00 | 0.00 |
August | 0.398270E+10 | 56918568.18 | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.00 | 0.00 |
September | 0.299848E+10 | 0.223691E+09 | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.00 | 0.00 |
October | 0.227042E+10 | 0.119315E+10 | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.00 | 0.00 |
November | 0.124009E+10 | 0.217320E+10 | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.00 | 0.00 |
December | 0.702511E+09 | 0.307505E+10 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331296E+11 | 0.143694E+11 | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.635644E+09 | 17225785.60 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517294E+10 | 0.313107E+10 | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143291E+10 | 0.192650E+10 | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.00 | 0.00 |
February | 0.189803E+10 | 0.141998E+10 | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.00 | 0.00 |
March | 0.316851E+10 | 0.978053E+09 | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.00 | 0.00 |
April | 0.458640E+10 | 0.360668E+09 | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.00 | 0.00 |
May | 0.541560E+10 | 69313489.81 | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.00 | 0.00 |
June | 0.475128E+10 | 51290306.75 | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.00 | 0.00 |
July | 0.401667E+10 | 10220489.06 | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.00 | 0.00 |
August | 0.339053E+10 | 38389050.74 | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.00 | 0.00 |
September | 0.305347E+10 | 0.149771E+09 | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.00 | 0.00 |
October | 0.305157E+10 | 0.780596E+09 | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.00 | 0.00 |
November | 0.212048E+10 | 0.138215E+10 | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.00 | 0.00 |
December | 0.148851E+10 | 0.193566E+10 | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383740E+11 | 0.910260E+10 | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143291E+10 | 10220489.06 | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.541560E+10 | 0.193566E+10 | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.580123E+10 | 0.300546E+10 | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.00 | 0.00 |
February | 0.538980E+10 | 0.225215E+10 | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.00 | 0.00 |
March | 0.596438E+10 | 0.157024E+10 | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.00 | 0.00 |
April | 0.544405E+10 | 0.568804E+09 | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.00 | 0.00 |
May | 0.526627E+10 | 0.102157E+09 | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.00 | 0.00 |
June | 0.505467E+10 | 76190101.49 | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.00 | 0.00 |
July | 0.481170E+10 | 15292347.92 | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.00 | 0.00 |
August | 0.451316E+10 | 58283141.99 | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.00 | 0.00 |
September | 0.488747E+10 | 0.238957E+09 | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.00 | 0.00 |
October | 0.748436E+10 | 0.125370E+10 | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.00 | 0.00 |
November | 0.790729E+10 | 0.221935E+10 | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.00 | 0.00 |
December | 0.643531E+10 | 0.301372E+10 | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.689597E+11 | 0.143743E+11 | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.451316E+10 | 15292347.92 | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.790729E+10 | 0.301372E+10 | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154605E+10 | 0.208546E+10 | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.00 | 0.00 |
February | 0.183729E+10 | 0.152227E+10 | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.00 | 0.00 |
March | 0.317528E+10 | 0.104950E+10 | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.00 | 0.00 |
April | 0.461026E+10 | 0.386208E+09 | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.00 | 0.00 |
May | 0.528542E+10 | 78823380.72 | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.00 | 0.00 |
June | 0.510425E+10 | 55154767.83 | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.00 | 0.00 |
July | 0.394575E+10 | 12134349.41 | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.00 | 0.00 |
August | 0.339485E+10 | 39565099.65 | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.00 | 0.00 |
September | 0.313490E+10 | 0.159595E+09 | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.00 | 0.00 |
October | 0.304762E+10 | 0.823889E+09 | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.00 | 0.00 |
November | 0.224445E+10 | 0.147436E+10 | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.00 | 0.00 |
December | 0.155614E+10 | 0.203646E+10 | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388823E+11 | 0.972342E+10 | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154605E+10 | 12134349.41 | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528542E+10 | 0.208546E+10 | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565071E+09 | 0.353840E+10 | 0.916479E+09 | 0.00 | 0.916479E+09 | 0.00 | 0.00 |
February | 0.995283E+09 | 0.243255E+10 | 0.981616E+09 | 0.00 | 0.981616E+09 | 0.00 | 0.00 |
March | 0.209246E+10 | 0.154702E+10 | 0.130959E+10 | 0.00 | 0.130959E+10 | 0.00 | 0.00 |
April | 0.351375E+10 | 0.500072E+09 | 0.137517E+10 | 4663611.29 | 0.137051E+10 | 0.00 | 0.00 |
May | 0.500465E+10 | 86998911.21 | 0.157437E+10 | 44179438.68 | 0.153020E+10 | 0.00 | 0.00 |
June | 0.522216E+10 | 71905493.62 | 0.157716E+10 | 58417603.32 | 0.151874E+10 | 0.00 | 0.00 |
July | 0.473743E+10 | 22235168.91 | 0.160728E+10 | 25452076.62 | 0.158183E+10 | 0.00 | 0.00 |
August | 0.395350E+10 | 76609352.49 | 0.147553E+10 | 4598532.45 | 0.147093E+10 | 0.00 | 0.00 |
September | 0.296455E+10 | 0.278998E+09 | 0.127233E+10 | 89339.55 | 0.127224E+10 | 0.00 | 0.00 |
October | 0.223755E+10 | 0.133053E+10 | 0.113899E+10 | 0.00 | 0.113899E+10 | 0.00 | 0.00 |
November | 0.116797E+10 | 0.246334E+10 | 0.933617E+09 | 0.00 | 0.933617E+09 | 0.00 | 0.00 |
December | 0.594825E+09 | 0.353833E+10 | 0.894042E+09 | 0.00 | 0.894042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330492E+11 | 0.158870E+11 | 0.150562E+11 | 0.137401E+09 | 0.149188E+11 | 0.00 | 0.00 |
Minimum of Months | 0.565071E+09 | 22235168.91 | 0.894042E+09 | 0.00 | 0.894042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.522216E+10 | 0.353840E+10 | 0.160728E+10 | 58417603.32 | 0.158183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135052E+10 | 0.220452E+10 | 0.130886E+10 | 0.525357E+09 | 0.783505E+09 | 0.00 | 0.00 |
February | 0.187663E+10 | 0.155590E+10 | 0.143622E+10 | 0.592937E+09 | 0.843284E+09 | 0.00 | 0.00 |
March | 0.320171E+10 | 0.101835E+10 | 0.193976E+10 | 0.800661E+09 | 0.113910E+10 | 0.00 | 0.00 |
April | 0.464608E+10 | 0.358151E+09 | 0.223336E+10 | 0.104130E+10 | 0.119206E+10 | 0.00 | 0.00 |
May | 0.546525E+10 | 65628239.26 | 0.227152E+10 | 0.100706E+10 | 0.126446E+10 | 0.00 | 0.00 |
June | 0.477934E+10 | 51322699.90 | 0.178908E+10 | 0.593613E+09 | 0.119547E+10 | 0.00 | 0.00 |
July | 0.401078E+10 | 14458257.23 | 0.155380E+10 | 0.328119E+09 | 0.122568E+10 | 0.00 | 0.00 |
August | 0.336930E+10 | 54162677.58 | 0.140004E+10 | 0.243638E+09 | 0.115640E+10 | 0.00 | 0.00 |
September | 0.303361E+10 | 0.195754E+09 | 0.144753E+10 | 0.403678E+09 | 0.104385E+10 | 0.00 | 0.00 |
October | 0.303094E+10 | 0.886876E+09 | 0.163621E+10 | 0.660917E+09 | 0.975290E+09 | 0.00 | 0.00 |
November | 0.206539E+10 | 0.157686E+10 | 0.140394E+10 | 0.602631E+09 | 0.801306E+09 | 0.00 | 0.00 |
December | 0.138734E+10 | 0.223857E+10 | 0.126498E+10 | 0.501190E+09 | 0.763789E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.382169E+11 | 0.102206E+11 | 0.196853E+11 | 0.730111E+10 | 0.123842E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135052E+10 | 14458257.23 | 0.126498E+10 | 0.243638E+09 | 0.763789E+09 | 0.00 | 0.00 |
Maximum of Months | 0.546525E+10 | 0.223857E+10 | 0.227152E+10 | 0.104130E+10 | 0.126446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.576747E+10 | 0.345722E+10 | 0.416806E+10 | 0.253261E+10 | 0.163545E+10 | 0.00 | 0.00 |
February | 0.540375E+10 | 0.249586E+10 | 0.357969E+10 | 0.198825E+10 | 0.159143E+10 | 0.00 | 0.00 |
March | 0.602474E+10 | 0.165438E+10 | 0.338866E+10 | 0.149673E+10 | 0.189192E+10 | 0.00 | 0.00 |
April | 0.550148E+10 | 0.562085E+09 | 0.230343E+10 | 0.650094E+09 | 0.165334E+10 | 0.00 | 0.00 |
May | 0.527886E+10 | 91765103.41 | 0.171170E+10 | 0.126710E+09 | 0.158499E+10 | 0.00 | 0.00 |
June | 0.503338E+10 | 73247722.11 | 0.151525E+10 | 25857015.52 | 0.148940E+10 | 0.00 | 0.00 |
July | 0.477100E+10 | 21543639.31 | 0.163323E+10 | 22463544.07 | 0.161077E+10 | 0.00 | 0.00 |
August | 0.445158E+10 | 81667072.19 | 0.173251E+10 | 92528349.50 | 0.163998E+10 | 0.00 | 0.00 |
September | 0.483568E+10 | 0.319437E+09 | 0.224764E+10 | 0.583377E+09 | 0.166427E+10 | 0.00 | 0.00 |
October | 0.743866E+10 | 0.146226E+10 | 0.399572E+10 | 0.223119E+10 | 0.176454E+10 | 0.00 | 0.00 |
November | 0.787334E+10 | 0.257699E+10 | 0.482987E+10 | 0.319243E+10 | 0.163744E+10 | 0.00 | 0.00 |
December | 0.635583E+10 | 0.349843E+10 | 0.445422E+10 | 0.279113E+10 | 0.166309E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.687358E+11 | 0.162949E+11 | 0.355600E+11 | 0.157334E+11 | 0.198266E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445158E+10 | 21543639.31 | 0.151525E+10 | 22463544.07 | 0.148940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.787334E+10 | 0.349843E+10 | 0.482987E+10 | 0.319243E+10 | 0.189192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150441E+10 | 0.238538E+10 | 0.128051E+10 | 0.498326E+09 | 0.782189E+09 | 0.00 | 0.00 |
February | 0.183029E+10 | 0.167249E+10 | 0.132260E+10 | 0.487411E+09 | 0.835186E+09 | 0.00 | 0.00 |
March | 0.321071E+10 | 0.110175E+10 | 0.189883E+10 | 0.759026E+09 | 0.113980E+10 | 0.00 | 0.00 |
April | 0.466609E+10 | 0.389130E+09 | 0.223356E+10 | 0.104745E+10 | 0.118611E+10 | 0.00 | 0.00 |
May | 0.532226E+10 | 76907787.42 | 0.218547E+10 | 0.927027E+09 | 0.125844E+10 | 0.00 | 0.00 |
June | 0.512054E+10 | 57528132.38 | 0.198652E+10 | 0.771614E+09 | 0.121491E+10 | 0.00 | 0.00 |
July | 0.393679E+10 | 16704221.87 | 0.152324E+10 | 0.296269E+09 | 0.122697E+10 | 0.00 | 0.00 |
August | 0.336858E+10 | 55748459.25 | 0.139893E+10 | 0.248632E+09 | 0.115030E+10 | 0.00 | 0.00 |
September | 0.311343E+10 | 0.210587E+09 | 0.148819E+10 | 0.436888E+09 | 0.105130E+10 | 0.00 | 0.00 |
October | 0.302729E+10 | 0.943634E+09 | 0.160061E+10 | 0.637356E+09 | 0.963250E+09 | 0.00 | 0.00 |
November | 0.219864E+10 | 0.169890E+10 | 0.140130E+10 | 0.597224E+09 | 0.804078E+09 | 0.00 | 0.00 |
December | 0.148429E+10 | 0.236463E+10 | 0.123907E+10 | 0.472485E+09 | 0.766588E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387833E+11 | 0.109734E+11 | 0.195588E+11 | 0.717971E+10 | 0.123791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148429E+10 | 16704221.87 | 0.123907E+10 | 0.248632E+09 | 0.766588E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532226E+10 | 0.238538E+10 | 0.223356E+10 | 0.104745E+10 | 0.125844E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569324E+09 | 0.344739E+10 | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.00 | 0.00 |
February | 0.963959E+09 | 0.245977E+10 | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.00 | 0.00 |
March | 0.203274E+10 | 0.162806E+10 | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.00 | 0.00 |
April | 0.344769E+10 | 0.561272E+09 | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.00 | 0.00 |
May | 0.496239E+10 | 0.106024E+09 | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.00 | 0.00 |
June | 0.521942E+10 | 75292673.99 | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.00 | 0.00 |
July | 0.477722E+10 | 17496281.05 | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.00 | 0.00 |
August | 0.401792E+10 | 58994504.40 | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.00 | 0.00 |
September | 0.301795E+10 | 0.236198E+09 | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.00 | 0.00 |
October | 0.226911E+10 | 0.127291E+10 | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.00 | 0.00 |
November | 0.119424E+10 | 0.236553E+10 | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.00 | 0.00 |
December | 0.623587E+09 | 0.338937E+10 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330956E+11 | 0.156183E+11 | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.569324E+09 | 17496281.05 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521942E+10 | 0.344739E+10 | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136679E+10 | 0.210194E+10 | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.00 | 0.00 |
February | 0.186081E+10 | 0.152610E+10 | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.00 | 0.00 |
March | 0.316351E+10 | 0.103166E+10 | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.00 | 0.00 |
April | 0.461060E+10 | 0.374657E+09 | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.00 | 0.00 |
May | 0.545270E+10 | 69227553.00 | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.00 | 0.00 |
June | 0.478720E+10 | 49811900.15 | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.00 | 0.00 |
July | 0.404882E+10 | 10392480.45 | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.00 | 0.00 |
August | 0.341686E+10 | 39482141.91 | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.00 | 0.00 |
September | 0.306978E+10 | 0.156639E+09 | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.00 | 0.00 |
October | 0.305202E+10 | 0.824620E+09 | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.00 | 0.00 |
November | 0.208676E+10 | 0.148330E+10 | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.00 | 0.00 |
December | 0.141963E+10 | 0.210655E+10 | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383355E+11 | 0.977438E+10 | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136679E+10 | 10392480.45 | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545270E+10 | 0.210655E+10 | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.572536E+10 | 0.327736E+10 | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.00 | 0.00 |
February | 0.535017E+10 | 0.242519E+10 | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.00 | 0.00 |
March | 0.596439E+10 | 0.166403E+10 | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.00 | 0.00 |
April | 0.547776E+10 | 0.594685E+09 | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.00 | 0.00 |
May | 0.531187E+10 | 0.103069E+09 | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.00 | 0.00 |
June | 0.510152E+10 | 74480158.07 | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.00 | 0.00 |
July | 0.485471E+10 | 15704470.39 | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.00 | 0.00 |
August | 0.454980E+10 | 60257740.30 | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.00 | 0.00 |
September | 0.491274E+10 | 0.250895E+09 | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.00 | 0.00 |
October | 0.749053E+10 | 0.132499E+10 | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.00 | 0.00 |
November | 0.787654E+10 | 0.238027E+10 | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.00 | 0.00 |
December | 0.635462E+10 | 0.327181E+10 | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.689700E+11 | 0.154427E+11 | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454980E+10 | 15704470.39 | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.787654E+10 | 0.327736E+10 | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150698E+10 | 0.228342E+10 | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.00 | 0.00 |
February | 0.181050E+10 | 0.164894E+10 | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.00 | 0.00 |
March | 0.317145E+10 | 0.111791E+10 | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.00 | 0.00 |
April | 0.463172E+10 | 0.404247E+09 | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.00 | 0.00 |
May | 0.531604E+10 | 79617702.26 | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.00 | 0.00 |
June | 0.513556E+10 | 54581514.82 | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.00 | 0.00 |
July | 0.397269E+10 | 12233892.34 | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.00 | 0.00 |
August | 0.341782E+10 | 40970040.63 | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.00 | 0.00 |
September | 0.314804E+10 | 0.168113E+09 | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.00 | 0.00 |
October | 0.304758E+10 | 0.876727E+09 | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.00 | 0.00 |
November | 0.221749E+10 | 0.159720E+10 | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.00 | 0.00 |
December | 0.150781E+10 | 0.222961E+10 | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388837E+11 | 0.105136E+11 | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.150698E+10 | 12233892.34 | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.531604E+10 | 0.228342E+10 | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.429304E+10 | -0.359422E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698813895.7 | 58.98 | 0.00 | 0.00 |
February | 0.382344E+10 | -0.319772E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -625722977.2 | 58.98 | 0.00 | 0.00 |
March | 0.422005E+10 | -0.353028E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689764600.2 | 58.98 | 0.00 | 0.00 |
April | 0.351638E+10 | -0.285119E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665195425.1 | 58.98 | 0.00 | 0.00 |
May | 0.339284E+10 | -0.270305E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689785755.1 | 58.98 | 0.00 | 0.00 |
June | 0.307535E+10 | -0.240613E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669221761.0 | 58.98 | 0.00 | 0.00 |
July | 0.285224E+10 | -0.216163E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690618261.5 | 58.98 | 0.00 | 0.00 |
August | 0.316583E+10 | -0.247611E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689710891.4 | 58.98 | 0.00 | 0.00 |
September | 0.313340E+10 | -0.246815E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665246977.0 | 58.98 | 0.00 | 0.00 |
October | 0.357343E+10 | -0.288675E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686672940.5 | 58.98 | 0.00 | 0.00 |
November | 0.384276E+10 | -0.317621E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666556199.6 | 58.98 | 0.00 | 0.00 |
December | 0.408870E+10 | -0.339441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694287918.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.429775E+11 | -0.348459E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.813160E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.285224E+10 | -0.359422E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -698813895.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.429304E+10 | -0.216163E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -625722977.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 6081.91 | 35.36 | 298.33 | 288.50 | 1375.40 | 25.15 | 252.83 | 270.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:09 | 3645.73 | 28.75 | 198.00 | 272.83 | 1214.39 | 21.04 | 174.33 | 247.83 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:49 | 1873.39 | 19.10 | 7.50 | 326.67 | 1034.98 | 20.97 | 185.17 | 296.17 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:30 | 1254.11 | 17.59 | 0.00 | 331.33 | 750.66 | 19.71 | 117.17 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1054.85 | 17.39 | 0.00 | 352.33 | 623.52 | 19.60 | 71.17 | 315.83 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1044.49 | 17.05 | 0.00 | 337.00 | 602.40 | 19.22 | 69.50 | 297.00 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1179.81 | 17.50 | 0.00 | 336.17 | 618.67 | 19.57 | 72.00 | 289.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1331.84 | 17.49 | 0.00 | 324.83 | 675.58 | 19.53 | 116.67 | 278.50 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:30 | 1629.65 | 18.20 | 0.00 | 304.67 | 856.21 | 20.33 | 177.00 | 269.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2791.57 | 20.26 | 42.67 | 308.17 | 1172.04 | 20.77 | 170.17 | 283.17 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 8233.82 | 36.60 | 310.50 | 288.67 | 1450.08 | 24.47 | 217.00 | 274.83 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 6423.88 | 36.70 | 308.83 | 288.33 | 1617.05 | 27.38 | 277.33 | 280.83 |
Annual Sum or Average | 4237.50 | 0.53 | 2869.59 | 22.89 | 1165.83 | 3759.50 | 971.39 | 21.31 | 1900.33 | 3404.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1044.49 | 17.05 | 0.00 | 272.83 | 602.40 | 19.22 | 69.50 | 247.83 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8233.82 | 36.70 | 310.50 | 352.33 | 1617.05 | 27.38 | 277.33 | 315.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1770.82 | 22.21 | 107.00 | 271.00 | 944.84 | 22.94 | 81.50 | 228.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2200.28 | 22.21 | 100.50 | 259.67 | 1171.01 | 23.00 | 74.33 | 227.17 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 2085.66 | 20.16 | 88.33 | 320.50 | 1101.78 | 22.38 | 70.83 | 291.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2567.71 | 20.92 | 110.67 | 330.83 | 1358.50 | 21.89 | 81.33 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:10 | 2652.55 | 20.27 | 116.50 | 358.50 | 1039.38 | 20.87 | 66.67 | 328.33 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2108.36 | 19.28 | 101.00 | 339.33 | 890.43 | 19.96 | 52.00 | 304.17 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:10 | 1744.74 | 19.37 | 96.50 | 341.50 | 785.76 | 19.96 | 46.17 | 295.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:40 | 1601.25 | 19.33 | 98.17 | 326.00 | 744.40 | 19.53 | 42.33 | 275.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1787.14 | 20.41 | 90.17 | 301.00 | 914.62 | 21.52 | 65.17 | 263.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1969.21 | 21.16 | 100.83 | 299.33 | 1004.89 | 21.92 | 70.33 | 268.67 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1772.01 | 20.93 | 88.00 | 271.00 | 906.96 | 21.69 | 59.83 | 241.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1853.80 | 22.89 | 112.50 | 264.83 | 995.96 | 23.57 | 91.67 | 232.33 |
Annual Sum or Average | 4237.50 | 0.53 | 2022.02 | 20.68 | 1210.17 | 3683.50 | 987.28 | 21.52 | 802.17 | 3259.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1601.25 | 19.28 | 88.00 | 259.67 | 744.40 | 19.53 | 42.33 | 227.17 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2652.55 | 22.89 | 116.50 | 358.50 | 1358.50 | 23.57 | 91.67 | 328.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.57 | 0.48 | 01-JAN-09:39 | 577.30 | 15.20 | 0.00 | 252.17 | 358.43 | 17.55 | 0.00 | 179.33 |
February | 303.83 | 0.55 | 0.48 | 01-FEB-09:09 | 665.98 | 16.09 | 0.00 | 252.67 | 411.81 | 18.37 | 0.00 | 194.00 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:30 | 787.65 | 17.24 | 0.00 | 317.67 | 486.03 | 19.44 | 0.00 | 271.33 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 849.38 | 17.31 | 0.00 | 333.83 | 532.13 | 19.42 | 11.83 | 306.33 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 1015.59 | 17.91 | 1.17 | 368.00 | 600.96 | 20.13 | 110.33 | 342.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1127.21 | 18.54 | 18.50 | 350.00 | 638.44 | 21.77 | 162.67 | 319.17 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1150.86 | 19.24 | 29.33 | 347.67 | 607.47 | 21.24 | 109.50 | 305.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 1029.30 | 17.24 | 0.00 | 329.00 | 542.25 | 19.24 | 41.83 | 281.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 892.80 | 17.15 | 0.00 | 302.00 | 500.51 | 19.21 | 1.67 | 253.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 696.69 | 16.06 | 0.00 | 291.33 | 440.31 | 18.35 | 0.00 | 243.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 591.40 | 15.58 | 0.00 | 256.17 | 388.54 | 18.08 | 0.00 | 202.83 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:09 | 568.53 | 15.28 | 0.00 | 248.00 | 356.48 | 17.70 | 0.00 | 177.33 |
Annual Sum or Average | 4237.50 | 0.54 | 845.28 | 17.00 | 49.00 | 3648.50 | 496.44 | 19.30 | 437.83 | 3076.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 568.53 | 15.20 | 0.00 | 248.00 | 356.48 | 17.55 | 0.00 | 177.33 | |
Maximum of Months | 406.00 | 0.57 | 0.48 | 1150.86 | 19.24 | 29.33 | 368.00 | 638.44 | 21.77 | 162.67 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1773.99 | 21.91 | 104.50 | 269.83 | 930.56 | 22.54 | 74.67 | 227.17 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2104.43 | 21.85 | 103.50 | 264.83 | 850.02 | 21.02 | 48.17 | 228.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:50 | 2034.70 | 20.04 | 87.83 | 321.00 | 1069.54 | 22.21 | 69.33 | 292.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2343.62 | 18.89 | 84.50 | 333.67 | 1233.89 | 20.04 | 54.67 | 306.17 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:40 | 2253.63 | 14.18 | 0.00 | 354.17 | 1174.39 | 17.53 | 0.00 | 326.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:20 | 2237.26 | 14.25 | 0.00 | 339.83 | 928.18 | 17.41 | 0.00 | 306.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1691.82 | 15.00 | 3.50 | 339.00 | 775.05 | 17.77 | 0.00 | 293.50 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:00 | 1577.68 | 16.81 | 53.17 | 324.67 | 793.36 | 17.69 | 4.83 | 279.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:30 | 1747.06 | 19.43 | 80.83 | 303.83 | 892.75 | 20.50 | 52.50 | 264.33 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2091.28 | 21.21 | 103.00 | 295.67 | 1065.30 | 22.15 | 74.50 | 267.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:30 | 1817.51 | 20.52 | 85.00 | 271.33 | 931.51 | 22.54 | 67.17 | 244.33 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:09 | 1595.36 | 20.69 | 87.67 | 269.83 | 844.25 | 22.66 | 70.17 | 236.83 |
Annual Sum or Average | 4237.50 | 0.53 | 1948.56 | 18.51 | 793.50 | 3687.67 | 962.69 | 20.19 | 516.00 | 3273.17 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1577.68 | 14.18 | 0.00 | 264.83 | 775.05 | 17.41 | 0.00 | 227.17 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2343.62 | 21.91 | 104.50 | 354.17 | 1233.89 | 22.66 | 74.67 | 326.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 5953.75 | 35.08 | 297.50 | 287.50 | 1279.97 | 22.68 | 85.50 | 267.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:20 | 3529.86 | 27.16 | 196.83 | 271.83 | 1129.27 | 18.12 | 0.00 | 246.00 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1783.68 | 15.41 | 7.50 | 323.67 | 970.49 | 18.57 | 0.00 | 292.83 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:40 | 1199.63 | 14.18 | 0.00 | 329.50 | 714.40 | 17.61 | 0.00 | 298.50 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1016.04 | 13.80 | 0.00 | 350.67 | 600.71 | 17.30 | 0.00 | 313.17 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1007.40 | 13.37 | 0.00 | 335.33 | 581.02 | 16.80 | 0.00 | 294.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:19 | 1136.78 | 13.51 | 0.00 | 334.33 | 592.45 | 16.88 | 0.00 | 284.50 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1281.50 | 13.49 | 0.00 | 322.67 | 644.11 | 16.77 | 0.00 | 275.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 1560.05 | 14.26 | 0.00 | 303.00 | 809.84 | 17.67 | 0.00 | 265.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2683.20 | 16.59 | 41.33 | 307.83 | 1090.43 | 18.11 | 10.00 | 281.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:30 | 8091.22 | 35.52 | 301.67 | 286.50 | 1340.60 | 21.93 | 74.33 | 272.67 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:40 | 6275.40 | 35.55 | 298.83 | 285.50 | 1513.28 | 25.19 | 123.67 | 279.67 |
Annual Sum or Average | 4237.50 | 0.53 | 2787.35 | 19.96 | 1143.67 | 3738.33 | 913.65 | 18.80 | 293.50 | 3371.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1007.40 | 13.37 | 0.00 | 271.83 | 581.02 | 16.77 | 0.00 | 246.00 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8091.22 | 35.55 | 301.67 | 350.67 | 1513.28 | 25.19 | 123.67 | 313.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1676.92 | 19.65 | 85.67 | 265.50 | 907.75 | 22.72 | 77.33 | 225.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2142.64 | 21.76 | 100.50 | 258.17 | 1128.70 | 22.80 | 74.33 | 223.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-07:30 | 2026.42 | 19.67 | 88.33 | 318.33 | 1052.38 | 22.19 | 70.83 | 288.50 |
April | 379.83 | 0.54 | 0.48 | 01-APR-06:49 | 2492.62 | 20.48 | 110.67 | 328.33 | 1306.38 | 21.73 | 81.33 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:19 | 2582.68 | 19.82 | 116.50 | 357.67 | 990.02 | 20.71 | 66.67 | 324.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2056.84 | 18.83 | 101.00 | 338.33 | 850.41 | 19.80 | 52.00 | 302.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-06:19 | 1695.94 | 18.93 | 96.33 | 340.00 | 750.27 | 19.79 | 46.17 | 290.33 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-06:40 | 1552.06 | 18.89 | 97.83 | 324.67 | 711.13 | 19.34 | 42.50 | 271.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1735.46 | 19.77 | 88.17 | 299.00 | 876.70 | 21.34 | 65.33 | 260.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1892.73 | 19.35 | 87.00 | 297.00 | 962.02 | 21.73 | 70.33 | 265.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1718.87 | 20.44 | 88.00 | 268.17 | 866.26 | 21.47 | 58.33 | 238.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1806.74 | 22.43 | 112.50 | 263.33 | 959.95 | 23.35 | 81.67 | 228.67 |
Annual Sum or Average | 4237.50 | 0.54 | 1960.93 | 19.94 | 1172.50 | 3658.50 | 945.71 | 21.33 | 786.83 | 3219.17 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1552.06 | 18.83 | 85.67 | 258.17 | 711.13 | 19.34 | 42.50 | 223.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2582.68 | 22.43 | 116.50 | 357.67 | 1306.38 | 23.35 | 81.67 | 324.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.58 | 0.48 | 01-JAN-09:00 | 555.40 | 11.71 | 0.00 | 249.17 | 346.69 | 15.30 | 0.00 | 171.50 |
February | 303.83 | 0.56 | 0.48 | 01-FEB-09:20 | 641.44 | 12.62 | 0.00 | 249.50 | 398.64 | 16.18 | 0.00 | 188.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:39 | 759.14 | 13.95 | 0.00 | 315.17 | 470.72 | 17.47 | 0.00 | 266.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:40 | 819.56 | 14.14 | 0.00 | 333.00 | 516.36 | 17.59 | 0.00 | 301.83 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 980.17 | 14.31 | 1.17 | 367.00 | 581.15 | 17.90 | 1.17 | 338.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1087.30 | 15.02 | 17.50 | 348.67 | 615.15 | 19.73 | 41.50 | 315.67 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1109.08 | 14.69 | 14.50 | 345.67 | 582.57 | 18.85 | 30.00 | 301.67 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 992.88 | 13.32 | 0.00 | 327.17 | 520.35 | 16.62 | 0.00 | 277.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:49 | 860.73 | 13.51 | 0.00 | 300.50 | 482.05 | 16.87 | 0.00 | 249.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 671.17 | 12.70 | 0.00 | 289.67 | 426.84 | 16.21 | 0.00 | 238.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 568.76 | 12.10 | 0.00 | 253.67 | 376.91 | 15.85 | 0.00 | 196.17 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:20 | 546.63 | 11.76 | 0.00 | 244.50 | 344.80 | 15.43 | 0.00 | 168.67 |
Annual Sum or Average | 4237.50 | 0.54 | 814.74 | 13.41 | 33.17 | 3623.67 | 479.36 | 17.10 | 72.67 | 3014.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 546.63 | 11.71 | 0.00 | 244.50 | 344.80 | 15.30 | 0.00 | 168.67 | |
Maximum of Months | 406.00 | 0.58 | 0.48 | 1109.08 | 15.02 | 17.50 | 367.00 | 615.15 | 19.73 | 41.50 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:50 | 1682.22 | 19.63 | 84.17 | 265.50 | 893.94 | 22.44 | 74.83 | 224.33 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2050.02 | 21.46 | 103.50 | 262.17 | 810.86 | 20.90 | 48.17 | 225.50 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:50 | 1975.03 | 19.60 | 87.83 | 319.83 | 1021.42 | 22.08 | 69.33 | 289.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2231.14 | 18.45 | 84.50 | 331.67 | 1180.80 | 19.89 | 54.67 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:49 | 2182.57 | 13.63 | 0.00 | 352.83 | 1127.61 | 17.33 | 0.00 | 323.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:30 | 2177.70 | 13.72 | 0.00 | 338.33 | 882.88 | 17.21 | 0.00 | 303.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1641.27 | 14.44 | 3.50 | 337.50 | 740.14 | 17.56 | 0.00 | 290.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-08:09 | 1528.92 | 16.32 | 53.00 | 322.83 | 759.83 | 17.49 | 4.83 | 275.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:39 | 1698.00 | 19.00 | 80.67 | 301.50 | 853.54 | 20.36 | 52.50 | 260.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2034.76 | 20.82 | 103.00 | 294.67 | 1023.30 | 22.04 | 74.67 | 265.00 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:39 | 1764.51 | 20.10 | 85.00 | 269.17 | 890.16 | 22.29 | 66.00 | 240.83 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:20 | 1547.18 | 20.29 | 87.67 | 268.17 | 793.94 | 21.57 | 59.33 | 231.50 |
Annual Sum or Average | 4237.50 | 0.54 | 1885.28 | 17.91 | 772.83 | 3664.17 | 920.06 | 19.95 | 504.33 | 3233.50 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1528.92 | 13.63 | 0.00 | 262.17 | 740.14 | 17.21 | 0.00 | 224.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2231.14 | 21.46 | 103.50 | 352.83 | 1180.80 | 22.44 | 74.83 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 5953.68 | 35.08 | 297.50 | 287.50 | 1279.87 | 22.68 | 85.50 | 267.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:20 | 3529.76 | 27.17 | 196.83 | 271.83 | 1129.18 | 18.12 | 0.00 | 246.00 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1783.58 | 15.41 | 7.50 | 323.67 | 970.42 | 18.58 | 0.00 | 292.83 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:40 | 1199.58 | 14.18 | 0.00 | 329.50 | 714.36 | 17.61 | 0.00 | 298.50 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1016.00 | 13.80 | 0.00 | 350.67 | 600.67 | 17.30 | 0.00 | 313.17 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1007.35 | 13.37 | 0.00 | 335.33 | 580.98 | 16.80 | 0.00 | 294.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:19 | 1136.69 | 13.52 | 0.00 | 334.33 | 592.40 | 16.88 | 0.00 | 284.50 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1281.40 | 13.49 | 0.00 | 322.67 | 644.05 | 16.78 | 0.00 | 274.83 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 1559.94 | 14.27 | 0.00 | 303.00 | 809.76 | 17.68 | 0.00 | 265.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2683.11 | 16.59 | 41.33 | 307.83 | 1090.36 | 18.11 | 10.00 | 281.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:30 | 8091.14 | 35.53 | 301.67 | 286.50 | 1340.51 | 21.93 | 74.33 | 272.67 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:40 | 6275.34 | 35.55 | 298.83 | 285.50 | 1513.18 | 25.19 | 123.67 | 279.67 |
Annual Sum or Average | 4237.50 | 0.53 | 2787.27 | 19.96 | 1143.67 | 3738.33 | 913.58 | 18.80 | 293.50 | 3371.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1007.35 | 13.37 | 0.00 | 271.83 | 580.98 | 16.78 | 0.00 | 246.00 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8091.14 | 35.55 | 301.67 | 350.67 | 1513.18 | 25.19 | 123.67 | 313.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1676.89 | 19.65 | 85.67 | 265.50 | 907.70 | 22.72 | 77.33 | 225.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2142.60 | 21.76 | 100.50 | 258.17 | 1128.65 | 22.80 | 74.33 | 223.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-07:30 | 2026.37 | 19.68 | 88.33 | 318.33 | 1052.32 | 22.19 | 70.83 | 288.50 |
April | 379.83 | 0.54 | 0.48 | 01-APR-06:49 | 2492.59 | 20.48 | 110.67 | 328.33 | 1306.32 | 21.73 | 81.33 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:19 | 2582.63 | 19.82 | 116.50 | 357.67 | 989.97 | 20.71 | 66.67 | 324.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2056.78 | 18.84 | 101.00 | 338.33 | 850.35 | 19.80 | 52.00 | 302.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-06:19 | 1695.85 | 18.93 | 96.33 | 339.83 | 750.21 | 19.79 | 46.17 | 290.33 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-06:40 | 1551.97 | 18.89 | 97.83 | 324.67 | 711.06 | 19.34 | 42.50 | 271.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1735.38 | 19.77 | 88.17 | 299.00 | 876.63 | 21.34 | 65.33 | 260.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1892.70 | 19.35 | 87.00 | 297.00 | 961.97 | 21.73 | 70.33 | 265.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1718.86 | 20.44 | 88.00 | 268.17 | 866.22 | 21.47 | 58.33 | 238.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1806.71 | 22.43 | 112.50 | 263.33 | 959.91 | 23.35 | 81.67 | 228.67 |
Annual Sum or Average | 4237.50 | 0.54 | 1960.88 | 19.94 | 1172.50 | 3658.33 | 945.66 | 21.33 | 786.83 | 3219.17 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1551.97 | 18.84 | 85.67 | 258.17 | 711.06 | 19.34 | 42.50 | 223.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2582.63 | 22.43 | 116.50 | 357.67 | 1306.32 | 23.35 | 81.67 | 324.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.58 | 0.48 | 01-JAN-09:00 | 555.39 | 11.71 | 0.00 | 249.17 | 346.67 | 15.30 | 0.00 | 171.50 |
February | 303.83 | 0.56 | 0.48 | 01-FEB-09:20 | 641.42 | 12.62 | 0.00 | 249.50 | 398.62 | 16.18 | 0.00 | 188.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:39 | 759.12 | 13.95 | 0.00 | 315.17 | 470.69 | 17.47 | 0.00 | 266.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:40 | 819.54 | 14.15 | 0.00 | 333.00 | 516.34 | 17.59 | 0.00 | 301.83 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 980.13 | 14.32 | 1.17 | 367.00 | 581.11 | 17.90 | 1.17 | 338.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1087.25 | 15.03 | 17.50 | 348.67 | 615.10 | 19.73 | 41.50 | 315.67 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1109.01 | 14.69 | 14.50 | 345.67 | 582.52 | 18.85 | 30.00 | 301.50 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 992.81 | 13.32 | 0.00 | 327.17 | 520.30 | 16.63 | 0.00 | 277.00 |
September | 344.33 | 0.54 | 0.48 | 01-SEP-07:49 | 860.68 | 13.51 | 0.00 | 300.50 | 482.02 | 16.87 | 0.00 | 249.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 671.16 | 12.71 | 0.00 | 289.67 | 426.82 | 16.21 | 0.00 | 238.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 568.76 | 12.11 | 0.00 | 253.67 | 376.89 | 15.85 | 0.00 | 196.17 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:20 | 546.62 | 11.76 | 0.00 | 244.50 | 344.78 | 15.44 | 0.00 | 168.67 |
Annual Sum or Average | 4237.50 | 0.54 | 814.71 | 13.41 | 33.17 | 3623.67 | 479.33 | 17.10 | 72.67 | 3014.17 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 546.62 | 11.71 | 0.00 | 244.50 | 344.78 | 15.30 | 0.00 | 168.67 | |
Maximum of Months | 406.00 | 0.58 | 0.48 | 1109.01 | 15.03 | 17.50 | 367.00 | 615.10 | 19.73 | 41.50 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:50 | 1682.19 | 19.63 | 84.17 | 265.50 | 893.89 | 22.44 | 74.83 | 224.33 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2049.99 | 21.46 | 103.50 | 262.17 | 810.81 | 20.90 | 48.17 | 225.50 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:50 | 1974.99 | 19.60 | 87.83 | 319.83 | 1021.37 | 22.08 | 69.33 | 289.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2231.10 | 18.45 | 84.50 | 331.67 | 1180.75 | 19.89 | 54.67 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:49 | 2182.52 | 13.64 | 0.00 | 352.83 | 1127.55 | 17.34 | 0.00 | 323.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:30 | 2177.63 | 13.72 | 0.00 | 338.33 | 882.82 | 17.21 | 0.00 | 303.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1641.17 | 14.44 | 3.50 | 337.50 | 740.08 | 17.56 | 0.00 | 290.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-08:09 | 1528.82 | 16.32 | 53.00 | 322.83 | 759.76 | 17.49 | 4.83 | 275.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:39 | 1697.92 | 19.00 | 80.67 | 301.50 | 853.47 | 20.36 | 52.50 | 260.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2034.73 | 20.82 | 103.00 | 294.67 | 1023.25 | 22.04 | 74.67 | 265.00 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:39 | 1764.49 | 20.10 | 85.00 | 269.17 | 890.11 | 22.29 | 66.00 | 240.83 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:20 | 1547.15 | 20.29 | 87.67 | 268.17 | 793.89 | 21.57 | 59.33 | 231.50 |
Annual Sum or Average | 4237.50 | 0.54 | 1885.23 | 17.92 | 772.83 | 3664.17 | 920.00 | 19.95 | 504.33 | 3233.50 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1528.82 | 13.64 | 0.00 | 262.17 | 740.08 | 17.21 | 0.00 | 224.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2231.10 | 21.46 | 103.50 | 352.83 | 1180.75 | 22.44 | 74.83 | 323.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.664995E+09 | 7398.78 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.445623E+09 | 7398.78 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100379E+09 | 7398.78 | 01-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129544E+09 | 7398.78 | 20-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508655E+09 | 7398.78 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.664995E+09 | 7398.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28940005.35 | 4904.59 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 398078.76 | 1867.08 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 191316.56 | 915.79 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29529400.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28940005.35 | 4904.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 94394889.55 | 7398.80 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3769866.58 | 2374.81 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1726945.60 | 2535.73 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99891701.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94394889.55 | 7398.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48405632.70 | 4921.75 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3036182.56 | 2307.60 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1259939.55 | 1650.61 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52701754.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48405632.70 | 4921.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21183532.01 | 25511.50 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21183532.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21183532.01 | 25511.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 83573553.68 | 8707.54 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4296444.09 | 5334.17 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6727720.75 | 8707.54 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94597718.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83573553.68 | 8707.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 91914311.20 | 5744.33 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6141279.51 | 5744.33 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15018138.21 | 5744.33 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91914311.20 | 5744.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186449E+09 | 8718.65 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16548639.45 | 6631.68 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29170537.47 | 8718.65 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186449E+09 | 8718.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157652E+09 | 5761.93 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20140226.76 | 5761.93 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38478289.33 | 5761.93 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157652E+09 | 5761.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382630E+09 | 27967.67 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3030062.00 | 3592.91 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32860237.56 | 25408.73 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382630E+09 | 27967.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.410165E+09 | 11150.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95293463.88 | 11150.71 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5939110.81 | 7449.07 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182299E+09 | 11150.71 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410165E+09 | 11150.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.347606E+09 | 7261.30 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72503150.87 | 7261.30 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 167321.31 | 836.61 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8117006.48 | 7261.30 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175198E+09 | 7261.30 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347606E+09 | 7261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.762516E+09 | 11157.39 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164111E+09 | 11157.39 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 255474.50 | 934.20 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20396344.11 | 11157.39 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364550E+09 | 11157.39 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.762516E+09 | 11157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.560997E+09 | 7271.13 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144828E+09 | 7271.13 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1255304.86 | 1551.07 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21922454.73 | 7271.13 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298829E+09 | 7271.13 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.560997E+09 | 7271.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123292E+09 | 3220.15 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1609882.46 | 560.73 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18187767.45 | 1943.05 | 23-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123292E+09 | 3220.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292219E+09 | 4509.17 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13580680.16 | 1506.31 | 02-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57266571.44 | 3076.45 | 23-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292219E+09 | 4509.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.589609E+09 | 4827.68 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95510204.33 | 4530.67 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2098528.55 | 982.63 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179335E+09 | 4827.68 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.589609E+09 | 4827.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198790E+11 | 0.171235E+11 | 34709.43 | 12-JAN-15:00 | 34709.43 | 0.00 |
February | 0.00 | 0.00 | 0.295295E+11 | 0.263027E+11 | 49364.58 | 22-FEB-16:10 | 49364.58 | 0.00 |
March | 0.00 | 0.00 | 0.549381E+11 | 0.511326E+11 | 77800.68 | 29-MAR-11:10 | 55415.94 | 0.00 |
April | 0.00 | 0.00 | 0.775092E+11 | 0.726919E+11 | 97737.05 | 27-APR-06:03 | 82361.89 | 0.00 |
May | 0.00 | 0.00 | 0.112886E+12 | 0.949574E+11 | 136058.39 | 19-MAY-04:02 | 91306.61 | 0.00 |
June | 0.00 | 0.00 | 0.127956E+12 | 0.964164E+11 | 140578.13 | 27-JUN-04:02 | 82419.84 | 0.00 |
July | 0.00 | 0.00 | 0.139081E+12 | 0.888650E+11 | 143677.67 | 20-JUL-04:03 | 76081.63 | 0.00 |
August | 0.00 | 0.00 | 0.141496E+12 | 0.880409E+11 | 140959.57 | 27-AUG-16:52 | 75591.64 | 0.00 |
September | 0.00 | 0.00 | 0.113938E+12 | 0.764203E+11 | 139886.13 | 06-SEP-04:03 | 80039.32 | 0.00 |
October | 0.00 | 0.00 | 0.785203E+11 | 0.675639E+11 | 113424.09 | 04-OCT-04:03 | 76702.85 | 0.00 |
November | 0.00 | 0.00 | 0.485337E+11 | 0.449908E+11 | 63469.58 | 06-NOV-11:40 | 52166.76 | 0.00 |
December | 0.00 | 0.00 | 0.253903E+11 | 0.227857E+11 | 42917.34 | 01-DEC-14:00 | 42917.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.969657E+12 | 0.747291E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.198790E+11 | 0.171235E+11 | 34709.43 | 34709.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141496E+12 | 0.964164E+11 | 143677.67 | 91306.61 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144592E+11 | 0.117693E+11 | 27315.85 | 12-JAN-15:20 | 27315.85 | 0.00 |
February | 0.00 | 0.00 | 0.235616E+11 | 0.202001E+11 | 43811.68 | 22-FEB-15:30 | 43811.68 | 0.00 |
March | 0.00 | 0.00 | 0.480524E+11 | 0.442741E+11 | 66000.08 | 28-MAR-16:00 | 66000.08 | 0.00 |
April | 0.00 | 0.00 | 0.714395E+11 | 0.676346E+11 | 96604.05 | 16-APR-16:02 | 84286.44 | 0.00 |
May | 0.00 | 0.00 | 0.103061E+12 | 0.877146E+11 | 125291.57 | 19-MAY-04:02 | 82219.45 | 0.00 |
June | 0.00 | 0.00 | 0.113988E+12 | 0.864233E+11 | 130628.26 | 27-JUN-04:02 | 72351.83 | 0.00 |
July | 0.00 | 0.00 | 0.120406E+12 | 0.761029E+11 | 133104.83 | 20-JUL-04:03 | 65446.95 | 0.00 |
August | 0.00 | 0.00 | 0.117938E+12 | 0.719373E+11 | 130964.96 | 10-AUG-04:02 | 71926.24 | 0.00 |
September | 0.00 | 0.00 | 0.934569E+11 | 0.615569E+11 | 129351.79 | 11-SEP-04:02 | 71227.17 | 0.00 |
October | 0.00 | 0.00 | 0.630847E+11 | 0.539084E+11 | 86324.97 | 04-OCT-05:03 | 58853.80 | 0.00 |
November | 0.00 | 0.00 | 0.373486E+11 | 0.336589E+11 | 54062.56 | 06-NOV-13:30 | 47781.02 | 0.00 |
December | 0.00 | 0.00 | 0.182557E+11 | 0.152911E+11 | 33444.82 | 01-DEC-15:10 | 33444.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.825052E+12 | 0.630471E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.144592E+11 | 0.117693E+11 | 27315.85 | 27315.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120406E+12 | 0.877146E+11 | 133104.83 | 84286.44 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152128E+11 | 0.121615E+11 | 29113.76 | 12-JAN-15:20 | 29113.76 | 0.00 |
February | 0.00 | 0.00 | 0.245460E+11 | 0.207245E+11 | 50532.18 | 22-FEB-15:00 | 50532.18 | 0.00 |
March | 0.00 | 0.00 | 0.518458E+11 | 0.471629E+11 | 79420.29 | 28-MAR-16:00 | 79420.29 | 0.00 |
April | 0.00 | 0.00 | 0.797703E+11 | 0.754185E+11 | 120505.76 | 16-APR-16:42 | 105036.78 | 0.00 |
May | 0.00 | 0.00 | 0.114629E+12 | 0.987220E+11 | 143902.87 | 17-MAY-04:02 | 95140.01 | 0.00 |
June | 0.00 | 0.00 | 0.126276E+12 | 0.979847E+11 | 150825.75 | 27-JUN-04:02 | 84677.96 | 0.00 |
July | 0.00 | 0.00 | 0.130369E+12 | 0.848039E+11 | 153333.79 | 20-JUL-04:03 | 75110.68 | 0.00 |
August | 0.00 | 0.00 | 0.125391E+12 | 0.787007E+11 | 151529.60 | 10-AUG-04:02 | 84881.21 | 0.00 |
September | 0.00 | 0.00 | 0.978990E+11 | 0.658134E+11 | 149287.88 | 01-SEP-04:02 | 79297.58 | 0.00 |
October | 0.00 | 0.00 | 0.663013E+11 | 0.566626E+11 | 94267.18 | 09-OCT-14:21 | 94267.18 | 0.00 |
November | 0.00 | 0.00 | 0.382012E+11 | 0.338788E+11 | 59270.41 | 09-NOV-13:40 | 56406.62 | 0.00 |
December | 0.00 | 0.00 | 0.183389E+11 | 0.149172E+11 | 35857.46 | 01-DEC-14:50 | 35857.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.888780E+12 | 0.686951E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.152128E+11 | 0.121615E+11 | 29113.76 | 29113.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130369E+12 | 0.987220E+11 | 153333.79 | 105036.78 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1495.47 | 5142.09 | 18-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1476.01 | 5107.59 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1475.44 | 4875.19 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1254.10 | 4446.00 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1165.50 | 4020.81 | 01-MAY-11:18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1086.78 | 3570.81 | 02-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 961.03 | 3310.87 | 06-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1083.81 | 3511.69 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1107.00 | 3903.98 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1231.62 | 4389.60 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1380.63 | 4811.86 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1419.64 | 5071.58 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1260.25 | ||||
Minimum of Months | 0.00 | 0.00 | 961.03 | 3310.87 | ||
Maximum of Months | 0.00 | 0.00 | 1495.47 | 5142.09 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186444E+10 | 0.29 | 2850.17 | 12-JAN-14:00 | 0.76 |
February | 0.229318E+10 | 0.33 | 4777.86 | 23-FEB-14:00 | 1.01 |
March | 0.383544E+10 | 0.41 | 6532.34 | 14-MAR-16:00 | 1.22 |
April | 0.502256E+10 | 0.49 | 11223.89 | 17-APR-04:02 | 1.71 |
May | 0.647963E+10 | 0.58 | 12286.37 | 01-MAY-04:02 | 1.82 |
June | 0.673617E+10 | 0.61 | 12286.37 | 03-JUN-06:03 | 1.81 |
July | 0.637325E+10 | 0.58 | 12286.37 | 01-JUL-04:02 | 1.81 |
August | 0.676174E+10 | 0.59 | 12286.37 | 01-AUG-04:02 | 1.81 |
September | 0.569837E+10 | 0.53 | 12286.37 | 01-SEP-04:02 | 1.81 |
October | 0.472889E+10 | 0.46 | 9758.16 | 02-OCT-06:03 | 1.57 |
November | 0.339056E+10 | 0.39 | 6003.77 | 13-NOV-17:00 | 1.16 |
December | 0.223242E+10 | 0.32 | 4063.62 | 01-DEC-15:20 | 0.92 |
Annual Sum or Average | 0.554166E+11 | 0.47 | |||
Minimum of Months | 0.186444E+10 | 0.29 | 2850.17 | 0.76 | |
Maximum of Months | 0.676174E+10 | 0.61 | 12286.37 | 1.82 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143477E+10 | 0.28 | 2354.94 | 02-JAN-07:01 | 0.72 |
February | 0.176116E+10 | 0.32 | 4114.91 | 22-FEB-15:30 | 0.99 |
March | 0.339034E+10 | 0.41 | 7061.34 | 13-MAR-16:00 | 1.37 |
April | 0.513664E+10 | 0.52 | 11002.46 | 17-APR-04:02 | 1.81 |
May | 0.655891E+10 | 0.62 | 11002.46 | 02-MAY-04:02 | 1.81 |
June | 0.651801E+10 | 0.63 | 11002.46 | 06-JUN-06:03 | 1.81 |
July | 0.572773E+10 | 0.56 | 11002.46 | 01-JUL-04:02 | 1.81 |
August | 0.566664E+10 | 0.55 | 11002.46 | 02-AUG-04:02 | 1.81 |
September | 0.462147E+10 | 0.49 | 11002.46 | 05-SEP-04:02 | 1.81 |
October | 0.375870E+10 | 0.43 | 7217.66 | 02-OCT-09:30 | 1.39 |
November | 0.245078E+10 | 0.35 | 4875.65 | 13-NOV-15:50 | 1.09 |
December | 0.157442E+10 | 0.29 | 2934.84 | 01-DEC-15:10 | 0.82 |
Annual Sum or Average | 0.485996E+11 | 0.46 | |||
Minimum of Months | 0.143477E+10 | 0.28 | 2354.94 | 0.72 | |
Maximum of Months | 0.655891E+10 | 0.63 | 11002.46 | 1.81 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146414E+10 | 0.28 | 2526.82 | 02-JAN-06:11 | 0.68 |
February | 0.167709E+10 | 0.30 | 3740.64 | 22-FEB-15:00 | 0.84 |
March | 0.321611E+10 | 0.38 | 7203.23 | 13-MAR-15:40 | 1.24 |
April | 0.517638E+10 | 0.48 | 9432.05 | 17-APR-04:02 | 1.47 |
May | 0.669291E+10 | 0.57 | 12896.52 | 06-MAY-04:02 | 1.79 |
June | 0.665681E+10 | 0.59 | 13189.51 | 15-JUN-04:02 | 1.81 |
July | 0.557882E+10 | 0.52 | 13189.51 | 14-JUL-04:02 | 1.81 |
August | 0.535905E+10 | 0.50 | 13189.51 | 10-AUG-04:02 | 1.81 |
September | 0.436781E+10 | 0.44 | 12162.39 | 18-SEP-04:02 | 1.72 |
October | 0.357177E+10 | 0.39 | 7320.99 | 03-OCT-16:00 | 1.25 |
November | 0.229060E+10 | 0.33 | 4572.13 | 09-NOV-15:20 | 0.94 |
December | 0.152807E+10 | 0.28 | 2380.91 | 01-DEC-15:00 | 0.66 |
Annual Sum or Average | 0.475796E+11 | 0.42 | |||
Minimum of Months | 0.146414E+10 | 0.28 | 2380.91 | 0.66 | |
Maximum of Months | 0.669291E+10 | 0.59 | 13189.51 | 1.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.94 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.35 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.67 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.94 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.82 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.81 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 57.14 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.82 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.86 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.01 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.16 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.16 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.86 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.90 | 57.90 | 1495.47 | 5142.09 | 18-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.71 | 56.71 | 1476.01 | 5107.59 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.00 | 57.00 | 1475.44 | 4875.19 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.55 | 57.55 | 1254.10 | 4446.00 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.07 | 57.07 | 1165.50 | 4020.81 | 01-MAY-11:18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.96 | 56.96 | 1086.78 | 3570.81 | 02-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.92 | 57.92 | 961.03 | 3310.87 | 06-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.25 | 57.25 | 1083.81 | 3511.69 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.97 | 56.97 | 1107.00 | 3903.98 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.42 | 56.42 | 1231.62 | 4389.60 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.01 | 58.01 | 1380.63 | 4811.86 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.47 | 56.47 | 1419.64 | 5071.58 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1260.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.42 | 56.42 | 961.03 | 3310.87 | ||
Maximum of Months | 0.00 | 0.00 | 58.01 | 58.01 | 1495.47 | 5142.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.791417E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.101959E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180962E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.275008E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.411353E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.449997E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.441864E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.439332E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.354003E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.253084E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156470E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.927635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.323594E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.791417E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.449997E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.584224E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.784414E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158574E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258251E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.380254E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.403523E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.382296E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364054E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.288257E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.204198E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119607E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.647471E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.276063E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.584224E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403523E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.800716E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.848839E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167953E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.284717E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.419224E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.443823E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.408935E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.381454E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.298863E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212755E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.121975E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.744490E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297910E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.744490E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.443823E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.186444E+10 | 0.198790E+11 | 0.960028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229318E+10 | 0.295295E+11 | 0.454437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.383544E+10 | 0.549381E+11 | 0.100379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.502256E+10 | 0.775092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.647963E+10 | 0.112886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673617E+10 | 0.127956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.637325E+10 | 0.139081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.676174E+10 | 0.141496E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569837E+10 | 0.113938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472889E+10 | 0.785203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339056E+10 | 0.485337E+11 | 0.129544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223242E+10 | 0.253903E+11 | 0.530021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554166E+11 | 0.969657E+12 | 0.217441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186444E+10 | 0.198790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676174E+10 | 0.141496E+12 | 0.960028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143477E+10 | 0.144592E+11 | 0.832992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176116E+10 | 0.235616E+11 | 60707269.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339034E+10 | 0.480524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513664E+10 | 0.714395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.655891E+10 | 0.103061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.651801E+10 | 0.113988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.572773E+10 | 0.120406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566664E+10 | 0.117938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.462147E+10 | 0.934569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375870E+10 | 0.630847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245078E+10 | 0.373486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157442E+10 | 0.182557E+11 | 0.146661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485996E+11 | 0.825052E+12 | 0.104036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143477E+10 | 0.144592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.655891E+10 | 0.120406E+12 | 0.832992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146414E+10 | 0.152128E+11 | 0.305352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167709E+10 | 0.245460E+11 | 0.575276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321611E+10 | 0.518458E+11 | 1678100.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517638E+10 | 0.797703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669291E+10 | 0.114629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665681E+10 | 0.126276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.557882E+10 | 0.130369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.535905E+10 | 0.125391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.436781E+10 | 0.978990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357177E+10 | 0.663013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229060E+10 | 0.382012E+11 | 58473444.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152807E+10 | 0.183389E+11 | 0.123307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475796E+11 | 0.888780E+12 | 0.492202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146414E+10 | 0.152128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669291E+10 | 0.130369E+12 | 0.305352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.186444E+10 | 0.00 | 0.00 | 0.00 | 0.521299E+10 | 0.836736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229318E+10 | 0.00 | 0.00 | 0.00 | 0.744992E+10 | 0.452827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.383544E+10 | 0.00 | 0.00 | 0.00 | 0.141604E+11 | 0.100379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.502256E+10 | 0.00 | 0.00 | 0.00 | 0.224782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.647963E+10 | 0.00 | 0.00 | 0.00 | 0.346557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673617E+10 | 0.00 | 0.00 | 0.00 | 0.382635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.637325E+10 | 0.00 | 0.00 | 0.00 | 0.378131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.676174E+10 | 0.00 | 0.00 | 0.00 | 0.371714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569837E+10 | 0.00 | 0.00 | 0.00 | 0.297019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472889E+10 | 0.00 | 0.00 | 0.00 | 0.205795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339056E+10 | 0.00 | 0.00 | 0.00 | 0.121269E+11 | 0.129544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223242E+10 | 0.00 | 0.00 | 0.00 | 0.653209E+10 | 0.511833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554166E+11 | 0.00 | 0.00 | 0.00 | 0.266146E+12 | 0.203132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186444E+10 | 0.00 | 0.00 | 0.00 | 0.521299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676174E+10 | 0.00 | 0.00 | 0.00 | 0.382635E+11 | 0.836736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143477E+10 | 0.00 | 0.00 | 0.00 | 0.386670E+10 | 0.540773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176116E+10 | 0.00 | 0.00 | 0.00 | 0.603585E+10 | 47126589.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339034E+10 | 0.00 | 0.00 | 0.00 | 0.124670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513664E+10 | 0.00 | 0.00 | 0.00 | 0.206885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.655891E+10 | 0.00 | 0.00 | 0.00 | 0.314665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.651801E+10 | 0.00 | 0.00 | 0.00 | 0.338343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.572773E+10 | 0.00 | 0.00 | 0.00 | 0.325019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566664E+10 | 0.00 | 0.00 | 0.00 | 0.307388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.462147E+10 | 0.00 | 0.00 | 0.00 | 0.242043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375870E+10 | 0.00 | 0.00 | 0.00 | 0.166611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245078E+10 | 0.00 | 0.00 | 0.00 | 0.950996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157442E+10 | 0.00 | 0.00 | 0.00 | 0.481089E+10 | 89394685.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485996E+11 | 0.00 | 0.00 | 0.00 | 0.226786E+12 | 0.677295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143477E+10 | 0.00 | 0.00 | 0.00 | 0.386670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.655891E+10 | 0.00 | 0.00 | 0.00 | 0.338343E+11 | 0.540773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146414E+10 | 0.00 | 0.00 | 0.00 | 0.407910E+10 | 0.246391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167709E+10 | 0.00 | 0.00 | 0.00 | 0.633153E+10 | 0.479766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321611E+10 | 0.00 | 0.00 | 0.00 | 0.135775E+11 | 1678100.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517638E+10 | 0.00 | 0.00 | 0.00 | 0.232953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669291E+10 | 0.00 | 0.00 | 0.00 | 0.352295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665681E+10 | 0.00 | 0.00 | 0.00 | 0.377255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.557882E+10 | 0.00 | 0.00 | 0.00 | 0.353146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.535905E+10 | 0.00 | 0.00 | 0.00 | 0.327864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.436781E+10 | 0.00 | 0.00 | 0.00 | 0.255185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357177E+10 | 0.00 | 0.00 | 0.00 | 0.177037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229060E+10 | 0.00 | 0.00 | 0.00 | 0.985055E+10 | 56374916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152807E+10 | 0.00 | 0.00 | 0.00 | 0.486309E+10 | 0.105374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475796E+11 | 0.00 | 0.00 | 0.00 | 0.246275E+12 | 0.405547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146414E+10 | 0.00 | 0.00 | 0.00 | 0.407910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.669291E+10 | 0.00 | 0.00 | 0.00 | 0.377255E+11 | 0.246391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114108E+10 | 2740836.90 | 0.00 | 31758942.40 | 821805.30 | 0.00 | 0.663118E+10 | 0.00 | 0.38 |
February | 0.399648E+09 | 39272968.60 | 0.00 | 33313897.78 | 18223946.24 | 0.00 | 0.424415E+10 | 0.00 | 0.40 |
March | 0.111439E+09 | 0.921798E+09 | 0.00 | 29850770.04 | 0.224078E+09 | 0.00 | 0.216523E+10 | 0.00 | 0.41 |
April | 21634088.15 | 0.362598E+10 | 0.00 | 5599546.73 | 0.102742E+10 | 0.00 | 0.105761E+09 | 0.00 | 0.35 |
May | 1117497.28 | 0.102265E+11 | 0.00 | 95170.69 | 0.259941E+10 | 0.00 | 1969473.75 | 0.00 | 0.36 |
June | 0.00 | 0.145613E+11 | 0.00 | 0.00 | 0.403849E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.176509E+11 | 0.00 | 0.00 | 0.717809E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.197925E+11 | 0.00 | 0.00 | 0.469669E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.140964E+11 | 0.00 | 0.00 | 0.336495E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 35919286.61 | 0.372089E+10 | 0.00 | 9106266.43 | 0.872496E+09 | 0.00 | 0.304793E+09 | 0.00 | 0.34 |
November | 0.182037E+09 | 0.158253E+09 | 0.00 | 38350624.19 | 0.135204E+09 | 0.00 | 0.282213E+10 | 0.00 | 0.38 |
December | 0.684812E+09 | 4405282.58 | 0.00 | 37016237.54 | 9517178.68 | 0.00 | 0.675625E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.257769E+10 | 0.848009E+11 | 0.00 | 0.185091E+09 | 0.241654E+11 | 0.00 | 0.230315E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 2740836.90 | 0.00 | 0.00 | 821805.30 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.114108E+10 | 0.197925E+11 | 0.00 | 38350624.19 | 0.717809E+10 | 0.00 | 0.675625E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400700E+10 | 0.00 | 0.00 | 5896682.83 | 6778373.50 | 7155898.47 | 0.174385E+10 | 0.00 | 0.29 |
February | 0.142988E+10 | 9525002.66 | 0.00 | 13101880.29 | 50681151.13 | 0.00 | 0.186043E+10 | 0.00 | 0.30 |
March | 0.270426E+09 | 0.618948E+09 | 0.00 | 17521671.75 | 0.278416E+09 | 0.00 | 0.136157E+10 | 0.00 | 0.32 |
April | 32735808.05 | 0.283688E+10 | 0.00 | 4634219.42 | 0.102946E+10 | 0.00 | 95150033.25 | 0.00 | 0.31 |
May | 1156254.12 | 0.889895E+10 | 0.00 | 73732.55 | 0.260509E+10 | 0.00 | 1238558.92 | 0.00 | 0.34 |
June | 0.00 | 0.130671E+11 | 0.00 | 0.00 | 0.398665E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.163814E+11 | 0.00 | 0.00 | 0.643592E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.185702E+11 | 0.00 | 0.00 | 0.403339E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.128891E+11 | 0.00 | 0.00 | 0.290437E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 65388901.06 | 0.327762E+10 | 0.00 | 4630374.22 | 0.700340E+09 | 0.00 | 0.140182E+09 | 0.00 | 0.30 |
November | 0.552640E+09 | 0.121607E+09 | 0.00 | 18960279.20 | 0.160451E+09 | 0.00 | 0.151819E+10 | 0.00 | 0.30 |
December | 0.283059E+10 | 0.00 | 0.00 | 10432064.75 | 28407280.68 | 0.00 | 0.229432E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.918982E+10 | 0.766713E+11 | 0.00 | 75250905.00 | 0.222199E+11 | 7155898.47 | 0.901493E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6778373.50 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.400700E+10 | 0.185702E+11 | 0.00 | 18960279.20 | 0.643592E+10 | 7155898.47 | 0.229432E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.404812E+10 | 0.00 | 0.00 | 2548270.27 | 6451346.18 | 0.134290E+09 | 0.783923E+09 | 0.00 | 0.28 |
February | 0.161909E+10 | 9438355.17 | 0.00 | 8459005.84 | 66676178.57 | 0.00 | 0.109107E+10 | 0.00 | 0.29 |
March | 0.280453E+09 | 0.638823E+09 | 0.00 | 13896419.75 | 0.296825E+09 | 0.00 | 0.984479E+09 | 0.00 | 0.31 |
April | 17909532.94 | 0.268875E+10 | 0.00 | 5737744.90 | 0.101984E+10 | 0.00 | 0.103008E+09 | 0.00 | 0.31 |
May | 674025.09 | 0.859311E+10 | 0.00 | 7093.20 | 0.263722E+10 | 0.00 | 333646.47 | 0.00 | 0.34 |
June | 0.00 | 0.127362E+11 | 0.00 | 0.00 | 0.415765E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.160672E+11 | 0.00 | 0.00 | 0.676538E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.181261E+11 | 0.00 | 0.00 | 0.427047E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.124626E+11 | 0.00 | 0.00 | 0.303035E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 42841948.92 | 0.319979E+10 | 0.00 | 2175446.61 | 0.744293E+09 | 0.00 | 35738255.36 | 0.00 | 0.29 |
November | 0.682823E+09 | 0.142964E+09 | 0.00 | 12883742.09 | 0.157405E+09 | 0.00 | 0.826792E+09 | 0.00 | 0.29 |
December | 0.316999E+10 | 0.00 | 0.00 | 4562425.92 | 18318216.58 | 2603272.49 | 0.101145E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.986191E+10 | 0.746650E+11 | 0.00 | 50270148.59 | 0.231709E+11 | 0.136893E+09 | 0.483680E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6451346.18 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.404812E+10 | 0.181261E+11 | 0.00 | 13896419.75 | 0.676538E+10 | 0.134290E+09 | 0.109107E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.849502E+09 | 0.00 | 0.00 | 142616.18 | 1541811.62 | 0.304763E+09 | 36201279.32 | 0.00 | 0.31 |
February | 0.420787E+09 | 4184145.61 | 0.00 | 1384970.01 | 14006518.63 | 61309520.33 | 0.154500E+09 | 0.00 | 0.32 |
March | 98987640.58 | 0.178121E+09 | 0.00 | 3203612.13 | 70564337.03 | 0.00 | 0.211247E+09 | 0.00 | 0.37 |
April | 4534339.85 | 0.974705E+09 | 0.00 | 1815408.56 | 0.185995E+09 | 0.00 | 31505331.91 | 0.00 | 0.44 |
May | 121854.04 | 0.347998E+10 | 0.00 | 8532.15 | 0.354006E+09 | 0.00 | 112607.57 | 0.00 | 0.54 |
June | 0.00 | 0.525549E+10 | 0.00 | 0.00 | 0.615616E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.675626E+10 | 0.00 | 0.00 | 0.919587E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.670587E+10 | 0.00 | 0.00 | 0.637400E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.407530E+10 | 0.00 | 0.00 | 0.576006E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 10922044.33 | 0.837092E+09 | 0.00 | 551851.42 | 0.221704E+09 | 0.00 | 9302158.50 | 0.00 | 0.37 |
November | 0.212445E+09 | 24694007.99 | 0.00 | 2490623.55 | 46445241.76 | 3867963.40 | 0.132060E+09 | 0.00 | 0.32 |
December | 0.769319E+09 | 0.00 | 0.00 | 312535.07 | 4377883.05 | 0.132158E+09 | 85226825.31 | 0.00 | 0.31 |
Annual Sum or Average | 0.236662E+10 | 0.282917E+11 | 0.00 | 9910149.07 | 0.364725E+10 | 0.502099E+09 | 0.660154E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1541811.62 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.849502E+09 | 0.675626E+10 | 0.00 | 3203612.13 | 0.919587E+09 | 0.304763E+09 | 0.211247E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.613668E+09 | 0.00 | 0.00 | 362384.97 | 1173113.20 | 0.151470E+09 | 0.140579E+09 | 0.00 | 0.38 |
February | 0.261537E+09 | 4958539.11 | 0.00 | 1978646.92 | 8882132.52 | 27402870.02 | 0.239330E+09 | 0.00 | 0.42 |
March | 54573807.70 | 0.178213E+09 | 0.00 | 3244512.93 | 41163734.07 | 0.00 | 0.220707E+09 | 0.00 | 0.53 |
April | 1974052.84 | 0.948306E+09 | 0.00 | 1575880.37 | 0.115988E+09 | 0.00 | 29865200.62 | 0.00 | 0.64 |
May | 92714.69 | 0.285940E+10 | 0.00 | 4395.39 | 0.260388E+09 | 0.00 | 87613.35 | 0.00 | 0.71 |
June | 0.00 | 0.396333E+10 | 0.00 | 0.00 | 0.465851E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.488863E+10 | 0.00 | 0.00 | 0.725641E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.481846E+10 | 0.00 | 0.00 | 0.488134E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.315483E+10 | 0.00 | 0.00 | 0.422999E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 7777573.24 | 0.768483E+09 | 0.00 | 470918.57 | 0.134101E+09 | 0.00 | 7634042.37 | 0.00 | 0.50 |
November | 0.130632E+09 | 36345448.25 | 0.00 | 2697771.41 | 27297289.01 | 1193939.04 | 0.158646E+09 | 0.00 | 0.43 |
December | 0.518266E+09 | 551263.21 | 0.00 | 684240.17 | 2779722.45 | 64328261.62 | 0.171322E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.158852E+10 | 0.216215E+11 | 0.00 | 11018750.74 | 0.269440E+10 | 0.244396E+09 | 0.968171E+09 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1173113.20 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.613668E+09 | 0.488863E+10 | 0.00 | 3244512.93 | 0.725641E+09 | 0.151470E+09 | 0.239330E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.564313E+09 | 2008220.34 | 0.00 | 5028309.59 | 168920.51 | 0.188528E+09 | 0.971008E+09 | 0.00 | 0.47 |
February | 0.312869E+09 | 14129735.80 | 0.00 | 6720747.46 | 9006615.62 | 34445178.31 | 0.650650E+09 | 0.00 | 0.52 |
March | 78079395.88 | 0.313696E+09 | 0.00 | 6406426.87 | 38927743.64 | 0.00 | 0.410160E+09 | 0.00 | 0.55 |
April | 4605211.29 | 0.124711E+10 | 0.00 | 2512131.32 | 0.149200E+09 | 0.00 | 43583817.59 | 0.00 | 0.53 |
May | 123758.61 | 0.359609E+10 | 0.00 | 8491.72 | 0.362888E+09 | 0.00 | 114528.31 | 0.00 | 0.56 |
June | 0.00 | 0.519325E+10 | 0.00 | 0.00 | 0.640345E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.677169E+10 | 0.00 | 0.00 | 0.958546E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.709614E+10 | 0.00 | 0.00 | 0.615484E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.498862E+10 | 0.00 | 0.00 | 0.487685E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 10843001.21 | 0.148870E+10 | 0.00 | 1182285.34 | 0.136275E+09 | 0.00 | 18071791.81 | 0.00 | 0.59 |
November | 0.143167E+09 | 0.124762E+09 | 0.00 | 9510748.67 | 15186128.81 | 511069.59 | 0.519300E+09 | 0.00 | 0.62 |
December | 0.511386E+09 | 6821581.49 | 0.00 | 5942314.28 | 902555.62 | 70960572.62 | 0.933963E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.162539E+10 | 0.308430E+11 | 0.00 | 37311455.26 | 0.341462E+10 | 0.294445E+09 | 0.354685E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 2008220.34 | 0.00 | 0.00 | 168920.51 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.564313E+09 | 0.709614E+10 | 0.00 | 9510748.67 | 0.958546E+09 | 0.188528E+09 | 0.971008E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605818E+09 | 411932.84 | 0.00 | 856155.24 | 896565.48 | 0.243403E+09 | 0.195360E+09 | 0.00 | 0.43 |
February | 0.340623E+09 | 7140868.72 | 0.00 | 1824663.63 | 9389677.76 | 51702714.99 | 0.194418E+09 | 0.00 | 0.46 |
March | 83927128.23 | 0.174080E+09 | 0.00 | 3299644.16 | 49769263.00 | 149490.57 | 0.223846E+09 | 0.00 | 0.54 |
April | 3859038.19 | 0.896838E+09 | 0.00 | 1803911.08 | 0.136489E+09 | 0.00 | 28128091.57 | 0.00 | 0.63 |
May | 103414.58 | 0.283707E+10 | 0.00 | 4975.63 | 0.308582E+09 | 0.00 | 97633.62 | 0.00 | 0.71 |
June | 0.00 | 0.410177E+10 | 0.00 | 0.00 | 0.533991E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.485331E+10 | 0.00 | 0.00 | 0.849095E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.486707E+10 | 0.00 | 0.00 | 0.561031E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.321186E+10 | 0.00 | 0.00 | 0.480615E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 9346497.48 | 0.720154E+09 | 0.00 | 583323.28 | 0.177300E+09 | 0.00 | 10302477.53 | 0.00 | 0.51 |
November | 0.173945E+09 | 31236039.84 | 0.00 | 2772294.46 | 34734084.01 | 3454489.34 | 0.150877E+09 | 0.00 | 0.47 |
December | 0.585619E+09 | 969764.85 | 0.00 | 1002271.01 | 2745638.86 | 0.107683E+09 | 0.179632E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.180324E+10 | 0.217019E+11 | 0.00 | 12147238.49 | 0.314464E+10 | 0.406393E+09 | 0.982661E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 411932.84 | 0.00 | 0.00 | 896565.48 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.605818E+09 | 0.486707E+10 | 0.00 | 3299644.16 | 0.849095E+09 | 0.243403E+09 | 0.223846E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104913E+10 | 0.00 | 0.00 | 228416.76 | 749167.45 | 57685663.59 | 67005330.79 | 0.00 | 0.26 |
February | 0.486591E+09 | 4873851.87 | 0.00 | 1195264.67 | 6161961.36 | 744874.11 | 0.131097E+09 | 0.00 | 0.25 |
March | 0.128569E+09 | 0.152264E+09 | 0.00 | 2256825.55 | 54788623.78 | 0.00 | 0.160380E+09 | 0.00 | 0.28 |
April | 11268986.44 | 0.806991E+09 | 0.00 | 570888.29 | 0.223937E+09 | 0.00 | 8783120.92 | 0.00 | 0.33 |
May | 268330.23 | 0.290514E+10 | 0.00 | 16861.96 | 0.408488E+09 | 0.00 | 382511.15 | 0.00 | 0.43 |
June | 0.00 | 0.453445E+10 | 0.00 | 0.00 | 0.628065E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.607661E+10 | 0.00 | 0.00 | 0.955364E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.620370E+10 | 0.00 | 0.00 | 0.642272E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.389937E+10 | 0.00 | 0.00 | 0.557798E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 24704886.93 | 0.818779E+09 | 0.00 | 959868.61 | 0.193439E+09 | 0.00 | 26368717.90 | 0.00 | 0.33 |
November | 0.219882E+09 | 28147191.33 | 0.00 | 3185381.56 | 28493400.41 | 0.00 | 0.181184E+09 | 0.00 | 0.26 |
December | 0.850650E+09 | 0.00 | 0.00 | 877717.06 | 2916581.94 | 293270.80 | 0.163145E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.277106E+10 | 0.254303E+11 | 0.00 | 9291224.46 | 0.370247E+10 | 58723808.49 | 0.738346E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 749167.45 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.104913E+10 | 0.620370E+10 | 0.00 | 3185381.56 | 0.955364E+09 | 57685663.59 | 0.181184E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.669277E+09 | 305771.52 | 0.00 | 863468.59 | 268285.73 | 18420361.39 | 0.225574E+09 | 0.00 | 0.32 |
February | 0.285956E+09 | 4304649.38 | 0.00 | 2170461.30 | 4151655.81 | 164064.16 | 0.249278E+09 | 0.00 | 0.35 |
March | 71076359.77 | 0.145824E+09 | 0.00 | 3027254.28 | 35699218.42 | 0.00 | 0.210683E+09 | 0.00 | 0.42 |
April | 6487256.13 | 0.837478E+09 | 0.00 | 785416.76 | 0.116712E+09 | 0.00 | 14222619.41 | 0.00 | 0.50 |
May | 199699.34 | 0.256807E+10 | 0.00 | 14152.15 | 0.243591E+09 | 0.00 | 297766.66 | 0.00 | 0.59 |
June | 0.00 | 0.353936E+10 | 0.00 | 0.00 | 0.439864E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.453934E+10 | 0.00 | 0.00 | 0.682136E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.453448E+10 | 0.00 | 0.00 | 0.449579E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.303361E+10 | 0.00 | 0.00 | 0.389709E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 15992001.22 | 0.720670E+09 | 0.00 | 1091193.86 | 0.116227E+09 | 0.00 | 30337593.43 | 0.00 | 0.44 |
November | 0.124825E+09 | 25968959.08 | 0.00 | 3854992.52 | 21606819.76 | 0.00 | 0.242347E+09 | 0.00 | 0.38 |
December | 0.521173E+09 | 633386.53 | 0.00 | 1699461.02 | 1605177.37 | 224721.76 | 0.300220E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.169499E+10 | 0.199500E+11 | 0.00 | 13506400.48 | 0.250115E+10 | 18809147.31 | 0.127296E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 305771.52 | 0.00 | 0.00 | 268285.73 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.669277E+09 | 0.453934E+10 | 0.00 | 3854992.52 | 0.682136E+09 | 18420361.39 | 0.300220E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.732781E+09 | 1233963.46 | 0.00 | 3219322.81 | 136707.62 | 0.305914E+09 | 0.586766E+09 | 0.00 | 0.38 |
February | 0.318608E+09 | 14182073.01 | 0.00 | 5401507.96 | 2578181.40 | 0.124878E+09 | 0.479059E+09 | 0.00 | 0.42 |
March | 90477906.30 | 0.356015E+09 | 0.00 | 5245315.79 | 24250701.25 | 19504025.87 | 0.319945E+09 | 0.00 | 0.47 |
April | 12151357.19 | 0.142342E+10 | 0.00 | 992903.44 | 0.146170E+09 | 0.00 | 12309700.86 | 0.00 | 0.50 |
May | 186375.39 | 0.410246E+10 | 0.00 | 27493.77 | 0.379900E+09 | 0.00 | 615440.74 | 0.00 | 0.57 |
June | 0.00 | 0.595013E+10 | 0.00 | 0.00 | 0.615808E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.745540E+10 | 0.00 | 0.00 | 0.953279E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.800594E+10 | 0.00 | 0.00 | 0.578483E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.563103E+10 | 0.00 | 0.00 | 0.430344E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 27557723.76 | 0.166939E+10 | 0.00 | 1623522.06 | 82399898.15 | 0.00 | 34784515.16 | 0.00 | 0.56 |
November | 0.125678E+09 | 0.120264E+09 | 0.00 | 10504970.82 | 8143334.99 | 30476840.11 | 0.544282E+09 | 0.00 | 0.55 |
December | 0.537532E+09 | 4259229.90 | 0.00 | 5147688.67 | 859928.28 | 0.180695E+09 | 0.781312E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.184497E+10 | 0.347337E+11 | 0.00 | 32162725.31 | 0.322235E+10 | 0.661468E+09 | 0.275907E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 1233963.46 | 0.00 | 0.00 | 136707.62 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.732781E+09 | 0.800594E+10 | 0.00 | 10504970.82 | 0.953279E+09 | 0.305914E+09 | 0.781312E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.772194E+09 | 415575.89 | 0.00 | 934253.77 | 185613.11 | 26926539.82 | 0.178932E+09 | 0.00 | 0.34 |
February | 0.361999E+09 | 6445993.25 | 0.00 | 1670584.90 | 3606473.25 | 319529.32 | 0.167988E+09 | 0.00 | 0.36 |
March | 88902885.51 | 0.171031E+09 | 0.00 | 2508131.91 | 30997777.63 | 0.00 | 0.175903E+09 | 0.00 | 0.41 |
April | 8286547.36 | 0.887606E+09 | 0.00 | 492527.29 | 0.103991E+09 | 0.00 | 7575549.73 | 0.00 | 0.50 |
May | 164270.82 | 0.263407E+10 | 0.00 | 17314.08 | 0.236139E+09 | 0.00 | 358906.68 | 0.00 | 0.59 |
June | 0.00 | 0.379250E+10 | 0.00 | 0.00 | 0.409549E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.456971E+10 | 0.00 | 0.00 | 0.695449E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.461439E+10 | 0.00 | 0.00 | 0.451460E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.313825E+10 | 0.00 | 0.00 | 0.381683E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 17121851.92 | 0.754434E+09 | 0.00 | 785228.70 | 0.113187E+09 | 0.00 | 23205687.88 | 0.00 | 0.44 |
November | 0.147797E+09 | 35460730.36 | 0.00 | 3264136.75 | 18951371.41 | 0.00 | 0.194657E+09 | 0.00 | 0.38 |
December | 0.623076E+09 | 779748.04 | 0.00 | 1417986.93 | 1655964.23 | 235342.82 | 0.240343E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.201954E+10 | 0.206051E+11 | 0.00 | 11090164.33 | 0.244686E+10 | 27481411.96 | 0.988963E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 415575.89 | 0.00 | 0.00 | 185613.11 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.772194E+09 | 0.461439E+10 | 0.00 | 3264136.75 | 0.695449E+09 | 26926539.82 | 0.240343E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100111E+10 | 0.00 | 0.00 | 302842.91 | 1451489.95 | 0.122270E+09 | 93018306.00 | 0.00 | 0.28 |
February | 0.486515E+09 | 6352368.46 | 0.00 | 1742670.80 | 6539902.40 | 3476780.63 | 0.182662E+09 | 0.00 | 0.29 |
March | 0.113206E+09 | 0.193902E+09 | 0.00 | 3368508.87 | 51569969.83 | 0.00 | 0.240935E+09 | 0.00 | 0.35 |
April | 11041356.67 | 0.105994E+10 | 0.00 | 1131261.15 | 0.176564E+09 | 0.00 | 19063000.38 | 0.00 | 0.44 |
May | 142703.29 | 0.368165E+10 | 0.00 | 31185.61 | 0.316742E+09 | 0.00 | 389045.25 | 0.00 | 0.54 |
June | 0.00 | 0.551920E+10 | 0.00 | 0.00 | 0.508025E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.692490E+10 | 0.00 | 0.00 | 0.763843E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.691130E+10 | 0.00 | 0.00 | 0.516590E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.423079E+10 | 0.00 | 0.00 | 0.504885E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 29390074.88 | 0.912200E+09 | 0.00 | 601749.46 | 0.158314E+09 | 0.00 | 10980383.97 | 0.00 | 0.36 |
November | 0.248788E+09 | 32800789.56 | 0.00 | 2762989.15 | 30223654.47 | 0.00 | 0.162140E+09 | 0.00 | 0.30 |
December | 0.893591E+09 | 0.00 | 0.00 | 739215.96 | 6083005.37 | 15732881.16 | 0.137049E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.278379E+10 | 0.294730E+11 | 0.00 | 10680423.90 | 0.304083E+10 | 0.141480E+09 | 0.846237E+09 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1451489.95 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.100111E+10 | 0.692490E+10 | 0.00 | 3368508.87 | 0.763843E+09 | 0.122270E+09 | 0.240935E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.754065E+09 | 0.00 | 0.00 | 618820.06 | 1194100.86 | 55075023.31 | 0.197984E+09 | 0.00 | 0.37 |
February | 0.321866E+09 | 4979779.15 | 0.00 | 2280662.78 | 5627273.50 | 1849501.38 | 0.288201E+09 | 0.00 | 0.42 |
March | 76851943.03 | 0.169196E+09 | 0.00 | 3545097.01 | 35315535.77 | 0.00 | 0.256397E+09 | 0.00 | 0.52 |
April | 7135592.88 | 0.997751E+09 | 0.00 | 1138288.36 | 0.113443E+09 | 0.00 | 22525268.10 | 0.00 | 0.63 |
May | 175063.61 | 0.300888E+10 | 0.00 | 17186.54 | 0.257647E+09 | 0.00 | 242717.42 | 0.00 | 0.71 |
June | 0.00 | 0.411894E+10 | 0.00 | 0.00 | 0.446437E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.497621E+10 | 0.00 | 0.00 | 0.681650E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.489553E+10 | 0.00 | 0.00 | 0.454602E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.319417E+10 | 0.00 | 0.00 | 0.420919E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 22918273.08 | 0.775455E+09 | 0.00 | 717617.07 | 0.107518E+09 | 0.00 | 12829152.50 | 0.00 | 0.49 |
November | 0.177627E+09 | 31926449.86 | 0.00 | 2963116.49 | 24315463.09 | 0.00 | 0.197225E+09 | 0.00 | 0.43 |
December | 0.625665E+09 | 872682.40 | 0.00 | 1133555.12 | 4137845.80 | 5200414.49 | 0.242596E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.198630E+10 | 0.221739E+11 | 0.00 | 12414343.43 | 0.255281E+10 | 62124939.18 | 0.121800E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1194100.86 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.754065E+09 | 0.497621E+10 | 0.00 | 3545097.01 | 0.681650E+09 | 55075023.31 | 0.288201E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.706636E+09 | 2195352.96 | 0.00 | 5970706.88 | 289422.79 | 46489621.05 | 0.113654E+10 | 0.00 | 0.50 |
February | 0.357509E+09 | 17808945.07 | 0.00 | 6867602.14 | 2895811.04 | 1198140.58 | 0.704103E+09 | 0.00 | 0.52 |
March | 96213679.33 | 0.354012E+09 | 0.00 | 6392517.97 | 20555607.93 | 0.00 | 0.441690E+09 | 0.00 | 0.55 |
April | 10849379.81 | 0.140667E+10 | 0.00 | 1518853.44 | 0.128782E+09 | 0.00 | 25164748.58 | 0.00 | 0.54 |
May | 145555.34 | 0.383587E+10 | 0.00 | 30782.82 | 0.319265E+09 | 0.00 | 391947.43 | 0.00 | 0.56 |
June | 0.00 | 0.544508E+10 | 0.00 | 0.00 | 0.546293E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.693845E+10 | 0.00 | 0.00 | 0.814737E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.734201E+10 | 0.00 | 0.00 | 0.489560E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.525328E+10 | 0.00 | 0.00 | 0.403497E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 27338870.10 | 0.167051E+10 | 0.00 | 1187035.41 | 69200810.55 | 0.00 | 19610217.89 | 0.00 | 0.59 |
November | 0.174014E+09 | 0.139523E+09 | 0.00 | 9312176.05 | 8911810.71 | 0.00 | 0.567855E+09 | 0.00 | 0.62 |
December | 0.584491E+09 | 9469433.51 | 0.00 | 6803580.07 | 1726525.05 | 2855702.02 | 0.115511E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.195720E+10 | 0.324149E+11 | 0.00 | 38083254.77 | 0.280571E+10 | 50543463.65 | 0.405045E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 2195352.96 | 0.00 | 0.00 | 289422.79 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.706636E+09 | 0.734201E+10 | 0.00 | 9312176.05 | 0.814737E+09 | 46489621.05 | 0.115511E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.800043E+09 | 570518.81 | 0.00 | 1034211.18 | 700592.06 | 0.103049E+09 | 0.212459E+09 | 0.00 | 0.42 |
February | 0.418681E+09 | 9078333.99 | 0.00 | 1958391.86 | 4170873.60 | 4073351.93 | 0.205022E+09 | 0.00 | 0.44 |
March | 0.102936E+09 | 0.202830E+09 | 0.00 | 3191175.34 | 29332394.09 | 0.00 | 0.236611E+09 | 0.00 | 0.53 |
April | 10627231.98 | 0.104613E+10 | 0.00 | 966474.19 | 0.108460E+09 | 0.00 | 14171854.64 | 0.00 | 0.64 |
May | 186353.82 | 0.311339E+10 | 0.00 | 19471.00 | 0.263227E+09 | 0.00 | 257639.62 | 0.00 | 0.72 |
June | 0.00 | 0.440052E+10 | 0.00 | 0.00 | 0.457094E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.505269E+10 | 0.00 | 0.00 | 0.706321E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.505001E+10 | 0.00 | 0.00 | 0.476864E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.335418E+10 | 0.00 | 0.00 | 0.422728E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 26686233.90 | 0.820741E+09 | 0.00 | 458970.61 | 0.109904E+09 | 0.00 | 8506776.83 | 0.00 | 0.50 |
November | 0.214663E+09 | 41019972.41 | 0.00 | 2769681.51 | 22917656.79 | 0.00 | 0.163472E+09 | 0.00 | 0.45 |
December | 0.740728E+09 | 1165794.96 | 0.00 | 1244015.69 | 4233057.59 | 15578629.48 | 0.210112E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.231455E+10 | 0.230923E+11 | 0.00 | 11642391.39 | 0.260595E+10 | 0.122701E+09 | 0.105061E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 570518.81 | 0.00 | 0.00 | 700592.06 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.800043E+09 | 0.505269E+10 | 0.00 | 3191175.34 | 0.706321E+09 | 0.103049E+09 | 0.236611E+09 | 0.00 | 0.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:31:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.166287E+12 | 0.415668E+10 | 0.00 | 0.656005E+11 | 0.629611E+11 |
February | 0.184452E+12 | 0.283558E+10 | 0.00 | 0.365340E+11 | 0.974821E+11 |
March | 0.243607E+12 | 0.519185E+09 | 0.00 | 0.724321E+10 | 0.195041E+12 |
April | 0.260505E+12 | -0.333834E+10 | 0.00 | -0.379135E+11 | 0.295181E+12 |
May | 0.270251E+12 | -0.966505E+10 | 0.00 | -0.101642E+12 | 0.431928E+12 |
June | 0.249207E+12 | -0.116532E+11 | 0.00 | -0.151877E+12 | 0.478043E+12 |
July | 0.207786E+12 | -0.165353E+11 | 0.00 | -0.203805E+12 | 0.495485E+12 |
August | 0.178585E+12 | -0.151754E+11 | 0.00 | -0.206415E+12 | 0.485521E+12 |
September | 0.195865E+12 | -0.974063E+10 | 0.00 | -0.153549E+12 | 0.384719E+12 |
October | 0.195792E+12 | -0.238663E+10 | 0.00 | -0.357024E+11 | 0.262851E+12 |
November | 0.174667E+12 | 0.105919E+10 | 0.00 | 0.219867E+11 | 0.155571E+12 |
December | 0.151509E+12 | 0.372393E+10 | 0.00 | 0.592537E+11 | 0.782547E+11 |
Annual Sum or Average | 0.247851E+13 | -0.562000E+11 | 0.00 | -0.700285E+12 | 0.342304E+13 |
Minimum of Months | 0.151509E+12 | -0.165353E+11 | 0.00 | -0.206415E+12 | 0.629611E+11 |
Maximum of Months | 0.270251E+12 | 0.415668E+10 | 0.00 | 0.656005E+11 | 0.495485E+12 |