Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:31:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2237.84 | 449.17 | 449.17 |
Net Site Energy | 2237.84 | 449.17 | 449.17 |
Total Source Energy | 6861.04 | 1377.12 | 1377.12 |
Net Source Energy | 6861.04 | 1377.12 | 1377.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 892.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 108.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2129.25 | 108.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 892.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 108.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 892.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 108.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 212.97 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 427.37 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 212.97 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 427.37 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2129.250 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2129.250 | 100.00 |
Total On-Site and Utility Electric Sources | 2129.250 | 100.00 |
Total Electricity End Uses | 2129.250 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 510.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1306.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | 18-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 26-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127164.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23651.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9527.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 219416.41 | 9527.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 127164.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 839.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 23651.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9527.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2827.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 951.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 531.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6743.33 | 117.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 567.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1353.49 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 567.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1353.49 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.99 | 0.250733 | 0.270000 | 0.807045 | 0.668621 | 0.500000 | 0.001520 |
CORE_MID VAV BOX COMPONENT | 2.29 | 0.327594 | 0.342000 | 0.782412 | 0.873584 | 0.500000 | 0.001163 |
CORE_TOP VAV BOX COMPONENT | 2.54 | 0.295474 | 0.322000 | 0.816738 | 0.787930 | 0.500000 | 0.001289 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.945358 | 0.167124 | 0.200000 | 0.189072 | 0.445663 | 0.500000 | 0.002280 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.741198 | 0.134946 | 0.200000 | 0.148240 | 0.359856 | 0.500000 | 0.002823 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.05 | 0.150936 | 0.200000 | 0.209349 | 0.402496 | 0.500000 | 0.002524 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.839524 | 0.119133 | 0.200000 | 0.167905 | 0.317689 | 0.500000 | 0.003198 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.811060 | 0.194796 | 0.210000 | 0.170323 | 0.519457 | 0.500000 | 0.001956 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.672250 | 0.148786 | 0.200000 | 0.134450 | 0.396764 | 0.500000 | 0.002561 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.904603 | 0.174653 | 0.200000 | 0.180921 | 0.465742 | 0.500000 | 0.002181 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.711147 | 0.140639 | 0.200000 | 0.142229 | 0.375038 | 0.500000 | 0.002709 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.817301 | 0.193309 | 0.202000 | 0.165095 | 0.515491 | 0.500000 | 0.001971 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.693439 | 0.144240 | 0.200000 | 0.138688 | 0.384640 | 0.500000 | 0.002641 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.916965 | 0.172299 | 0.200000 | 0.183393 | 0.459463 | 0.500000 | 0.002211 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.748101 | 0.133692 | 0.200000 | 0.149620 | 0.356512 | 0.500000 | 0.002850 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26941.66 |
CORE_MID VAV BOX REHEAT COIL | 26119.35 |
CORE_TOP VAV BOX REHEAT COIL | 27265.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7237.87 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4948.70 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7201.59 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5605.18 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5685.90 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4488.36 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6039.69 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4748.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5511.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4629.83 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 6122.22 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4994.78 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.04 | 1.43 | 6.09 | 1.43 | 5.71 | 5.71 | 0.300000 | 0.251298 | 5.71 |
PACU_VAV_MID | 2.73 | 1.42 | 5.46 | 1.42 | 5.04 | 5.04 | 0.300000 | 0.281686 | 5.04 |
PACU_VAV_TOP | 3.05 | 1.53 | 6.11 | 1.53 | 5.95 | 5.95 | 0.300000 | 0.257364 | 5.95 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.71 |
PACU_VAV_MID_OA_CONTROLLER | 5.04 |
PACU_VAV_TOP_OA_CONTROLLER | 5.95 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.71 | 135503.03 | 0.715470 | 1.90 | 45163.16 | 0.715470 |
PACU_VAV_MID COOLING COIL | 5.04 | 123376.29 | 0.705531 | 1.68 | 41121.32 | 0.705531 |
PACU_VAV_TOP COOLING COIL | 5.95 | 140165.58 | 0.717348 | 1.98 | 46717.19 | 0.717348 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.71 |
PACU_VAV_MID FAN | 5.04 |
PACU_VAV_TOP FAN | 5.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4542E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4882E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7144E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7426E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4687E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4900E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5694E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5839E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6568E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2174E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3085E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3336E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2899E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3868E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8227E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0568E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4554E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4962E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7159E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7512E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4702E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4970E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5692E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5837E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2028E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3634E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9332E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1584E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0136E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9772E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3172E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5628E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8407E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8536E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6327E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6422E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4643E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4678E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9989E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0039E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4834E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5151E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1127E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1381E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8415E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8592E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5692E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5837E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2596E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2649E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7679E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7780E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5867E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.7310E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8227E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0568E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4829E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5144E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1120E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1363E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8401E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8543E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5694E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5839E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4226E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0155E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0068E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7455E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2202E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6254E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3172E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5628E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3293E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3538E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0194E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0433E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9682E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9821E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9990E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0040E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0467E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0831E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.6505E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2402E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7949E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1176E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2209E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5024E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0727E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2876E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8193E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0917E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9235E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9227E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2554E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5255E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6048E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6840E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0789E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3440E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8923E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0071E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2209E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5024E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3153E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9558E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9202E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6981E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1525E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5865E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2554E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5255E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0463E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6499E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2397E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7944E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1172E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2206E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5023E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0726E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2875E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8191E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0915E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9233E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9225E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2551E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5253E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6049E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6839E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0789E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3439E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8922E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0070E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2206E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5023E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3153E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9557E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9201E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6980E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1523E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5863E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2551E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5253E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 41459.86308 | 41459.86308 | 2.98906 | 2.98906 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 1064.70502 | 1064.70502 | 4.54583E-002 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31763.90156 | 31763.90156 | 2.28776 | 2.28776 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6794.12316 | 6794.12316 | 0.28414 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34893.98085 | 34893.98085 | 2.53645 | 2.53645 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11770.50348 | 11770.50348 | 0.49690 | 0.49690 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 13005.02309 | 13005.02309 | 0.94536 | 0.94536 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 5100.13268 | 5100.13268 | 0.21681 | 0.21681 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10196.46177 | 10196.46177 | 0.74120 | 0.74120 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3330.47423 | 3330.47423 | 0.14161 | 0.14161 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14399.81921 | 14399.81921 | 1.04675 | 1.04675 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 5074.73263 | 5074.73263 | 0.21573 | 0.21573 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11549.12898 | 11549.12898 | 0.83952 | 0.83952 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3344.77705 | 3344.77705 | 0.14222 | 0.14222 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 11157.68843 | 11157.68843 | 0.81106 | 0.81106 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2575.00534 | 2575.00534 | 0.10877 | 0.10877 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9248.11959 | 9248.11959 | 0.67225 | 0.67225 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1708.22630 | 1708.22630 | 7.22082E-002 | 7.22082E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12444.55673 | 12444.55673 | 0.90460 | 0.90460 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2563.79560 | 2563.79560 | 0.10829 | 0.10829 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9783.22375 | 9783.22375 | 0.71115 | 0.71115 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1715.60342 | 1715.60342 | 7.25245E-002 | 7.25245E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 11243.41704 | 11243.41704 | 0.81730 | 0.81730 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3671.73503 | 3671.73503 | 0.15569 | 0.15569 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9539.50523 | 9539.50523 | 0.69344 | 0.69344 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2421.42499 | 2421.42499 | 0.10270 | 0.10270 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12614.48975 | 12614.48975 | 0.91696 | 0.91696 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3652.86346 | 3652.86346 | 0.15488 | 0.15488 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10291.48485 | 10291.48485 | 0.74810 | 0.74810 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2431.86235 | 2431.86235 | 0.10314 | 0.10314 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 104502.00 | 5.71023 | 5.71023 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 95.62 | 0.79059 | 0.79059 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 95331.27 | 5.03827 | 5.03827 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 113.82 | 0.94110 | 0.94110 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 107561.99 | 5.94996 | 5.94996 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 141.03 | 1.21327 | 1.21327 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.98906 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25073 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80704 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66862 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51954E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26941.65734 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28776 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32759 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78241 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87358 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16303E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26119.34775 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53645 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29547 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81674 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78793 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28946E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27265.23629 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94536 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16712 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18907 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44566 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27975E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7237.87109 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74120 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13495 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14824 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35986 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82335E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4948.69517 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04675 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15094 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20935 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40250 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52425E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7201.59492 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83952 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11913 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16790 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31769 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19810E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5605.18092 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81106 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19480 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17032 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51946 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95589E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5685.89749 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67225 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14879 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39676 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56072E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4488.36078 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90460 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17465 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18092 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46574 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18147E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6039.68704 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71115 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14064 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14223 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37504 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70906E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4748.05831 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81730 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19331 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16509 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51549 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97094E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5511.37325 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69344 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14424 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13869 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38464 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64143E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4629.82993 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91696 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17230 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18339 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45946 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21128E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6122.22416 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74810 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13369 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14962 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35651 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84983E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4994.78473 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.04406 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43497 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.08812 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43497 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.71023 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.71023 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25130 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.73178 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41921 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.46356 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41921 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.03827 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.03827 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.28169 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.05464 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53130 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.10928 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53130 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.94996 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.94996 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.25736 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.71023 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.03827 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.94996 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.71023 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.71023 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 135503.03191 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71547 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90322 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 45163.16054 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71547 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.71023 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.03827 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.03827 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 123376.29431 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70553 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67925 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41121.31889 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70553 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.03827 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.94996 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.94996 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 140165.57680 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71735 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.98312 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 46717.18675 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71735 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.94996 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 135085.67 | 460931.44 | 11.56 | 2.96 | 3.31 | 3.49 | 3.62 | 10.08 | 11.30 | 11.92 | 12.37 | 6.6014 | 5.2460 | 3.5285 | 1.4965 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 123120.73 | 420105.38 | 11.62 | 2.97 | 3.33 | 3.51 | 3.64 | 10.12 | 11.36 | 11.99 | 12.41 | 5.8245 | 4.6165 | 3.1090 | 1.3318 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 139700.42 | 476677.61 | 11.54 | 2.95 | 3.31 | 3.49 | 3.62 | 10.07 | 11.29 | 11.91 | 12.36 | 6.8785 | 5.4674 | 3.6773 | 1.5565 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.8652614552E-002 | 0.1924522355 | Pass | Pass | 6.4682751000E-002 | 0.2432253206 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3548857526E-002 | 4.8431352796E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.7418339772E-002 | 2.3465495244E-002 | Pass | Pass | 0.7048958099 | 7.6067818977 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6916975462E-002 | 2.5275652676E-002 | Pass | Pass | 0.2902440099 | 1.9511902449 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.2865912617E-002 | 0.1331701617 | Pass | Pass | 1.5078325917E-002 | 0.1220969537 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.3747242689E-002 | 1.3276426260E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.3675526077E-002 | 2.7872482345E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.6675185859E-002 | 2.6362065567E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.2515586127E-002 | 5.5714723508E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.4957212616E-002 | 4.5035527135E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.0248454728E-002 | 0.1493466150 | Pass | Pass | 6.4078923209E-002 | 0.2426643914 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.3692535881E-002 | 0.1801713567 | Pass | Pass | 6.4394589640E-002 | 0.2429966555 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1015019692 | 0.1817100524 | Pass | Pass | 7.3845012228E-002 | 0.2845881817 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1086758056 | 0.2031931770 | Pass | Pass | 6.3847506032E-002 | 0.2410391580 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.8644145813E-002 | 0.1127550241 | Pass | Pass | 1.4776990490E-002 | 0.1208090121 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9903966655E-002 | 0.1437427112 | Pass | Pass | 1.5154765190E-002 | 0.1225520894 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.1228320671E-002 | 0.1481632305 | Pass | Pass | 2.5828900518E-002 | 0.1868378121 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4353944095E-002 | 0.1617330685 | Pass | Pass | 1.5191066876E-002 | 0.1227572902 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2118.42 | -123.7 | 0.00 | -1076.1 | 4080.01 | 4998.66 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 8.71 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 5.48 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.26 | 0.0000 | Y | 8.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 5.49 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.64 | 0.0000 | Y | 8.68 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 5.48 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 8.71 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 5.48 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.26 | 0.0000 | Y | 8.55 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 5.49 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.85 | 41.85 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.85 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.85 | 46.68 | 41.32 | |
Exterior Lighting Total | 5686.19 | 50.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 135503.03 | 96948.37 | 38554.66 | 0.72 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 123376.29 | 87045.86 | 36330.44 | 0.71 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 140165.58 | 100547.44 | 39618.14 | 0.72 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 135085.7 | 2.96 | 10.08 | N/A | N/A | 11.56 | |
PACU_VAV_MID COOLING COIL | 123120.7 | 2.97 | 10.12 | N/A | N/A | 11.62 | |
PACU_VAV_TOP COOLING COIL | 139700.4 | 2.95 | 10.07 | N/A | N/A | 11.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26941.66 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 26119.35 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27265.24 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7237.87 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4948.70 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7201.59 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5605.18 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5685.90 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4488.36 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6039.69 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4748.06 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5511.37 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4629.83 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6122.22 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4994.78 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.71 | 12419.12 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.04 | 10957.67 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.95 | 12940.49 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 135085.67 | 2.96 | 10.08 | 11.56 | 6.6014 | 3.31 | 11.30 | 5.2460 | 3.49 | 11.92 | 3.5285 | 3.62 | 12.37 | 1.4965 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 123120.73 | 2.97 | 10.12 | 11.62 | 5.8245 | 3.33 | 11.36 | 4.6165 | 3.51 | 11.99 | 3.1090 | 3.64 | 12.41 | 1.3318 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 139700.42 | 2.95 | 10.07 | 11.54 | 6.8785 | 3.31 | 11.29 | 5.4674 | 3.49 | 11.91 | 3.6773 | 3.62 | 12.36 | 1.5565 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 41459.86 | 41459.86 | 42.15 | 2.989 | 2.989 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 31763.90 | 31763.90 | 32.30 | 2.288 | 2.288 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 34893.98 | 34893.98 | 35.48 | 2.536 | 2.536 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00884 | 42.61 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13005.02 | 13005.02 | 62.72 | 0.945 | 0.945 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00877 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10196.46 | 10196.46 | 77.68 | 0.741 | 0.741 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00872 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14399.82 | 14399.82 | 69.45 | 1.047 | 1.047 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00874 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11549.13 | 11549.13 | 87.99 | 0.840 | 0.840 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00870 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11157.69 | 11157.69 | 53.81 | 0.811 | 0.811 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00877 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9248.12 | 9248.12 | 70.46 | 0.672 | 0.672 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00871 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12444.56 | 12444.56 | 60.02 | 0.905 | 0.905 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00874 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9783.22 | 9783.22 | 74.54 | 0.711 | 0.711 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00870 | 41.83 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11243.42 | 11243.42 | 54.23 | 0.817 | 0.817 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00880 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9539.51 | 9539.51 | 72.68 | 0.693 | 0.693 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00873 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12614.49 | 12614.49 | 60.84 | 0.917 | 0.917 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00876 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10291.48 | 10291.48 | 78.41 | 0.748 | 0.748 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00871 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 1064.71 | 1064.71 | 1.08 | 0.045 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6794.12 | 6794.12 | 6.91 | 0.284 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11770.50 | 11770.50 | 11.97 | 0.497 | 0.497 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 5100.13 | 5100.13 | 24.60 | 0.217 | 0.217 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3330.47 | 3330.47 | 25.37 | 0.142 | 0.142 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 5074.73 | 5074.73 | 24.48 | 0.216 | 0.216 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3344.78 | 3344.78 | 25.48 | 0.142 | 0.142 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2575.01 | 2575.01 | 12.42 | 0.109 | 0.109 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1708.23 | 1708.23 | 13.01 | 0.072 | 0.072 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2563.80 | 2563.80 | 12.37 | 0.108 | 0.108 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1715.60 | 1715.60 | 13.07 | 0.073 | 0.073 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3671.74 | 3671.74 | 17.71 | 0.156 | 0.156 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2421.42 | 2421.42 | 18.45 | 0.103 | 0.103 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3652.86 | 3652.86 | 17.62 | 0.155 | 0.155 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2431.86 | 2431.86 | 18.53 | 0.103 | 0.103 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.71 | 5.71 | 0.79 | 0.79 | 5.7102 | 1.4350 | 5.7102 | 0.2513 | 0.3000 |
PACU_VAV_MID | 5.04 | 5.04 | 0.94 | 0.94 | 5.0383 | 1.4192 | 5.0383 | 0.2817 | 0.3000 |
PACU_VAV_TOP | 5.95 | 5.95 | 1.21 | 1.21 | 5.9500 | 1.5313 | 5.9500 | 0.2574 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26941.657 | 26941.657 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26941.66 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811181 | 52.4060 | 1064.71 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26119.348 | 26119.348 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26119.35 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6794.12 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27265.236 | 27265.236 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27265.24 | 16588.11 | 0.496902 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11770.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7237.871 | 7237.871 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7237.87 | 7237.87 | 0.216812 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823093 | 53.1636 | 5100.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4948.695 | 4948.695 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4948.70 | 4727.40 | 0.141611 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823098 | 53.1639 | 3330.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7201.595 | 7201.595 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7201.59 | 7201.59 | 0.215726 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823241 | 53.1730 | 5074.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5605.181 | 5605.181 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5605.18 | 4747.82 | 0.142222 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822966 | 53.1555 | 3344.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5685.897 | 5685.897 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5685.90 | 3631.17 | 0.108773 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828986 | 53.5398 | 2575.01 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4488.361 | 4488.361 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4488.36 | 2410.53 | 0.072208 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829244 | 53.5562 | 1708.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6039.687 | 6039.687 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6039.69 | 3615.12 | 0.108292 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829084 | 53.5461 | 2563.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4748.058 | 4748.058 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4748.06 | 2421.09 | 0.072524 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829142 | 53.5497 | 1715.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5511.373 | 5511.373 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5511.37 | 5197.30 | 0.155687 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829205 | 53.5533 | 3671.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4629.830 | 4629.830 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4629.83 | 3428.41 | 0.102699 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829194 | 53.5525 | 2421.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 6122.224 | 6122.224 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6122.22 | 5170.43 | 0.154882 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829359 | 53.5631 | 3652.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4994.785 | 4994.785 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4994.78 | 3443.26 | 0.103144 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829059 | 53.5440 | 2431.86 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 135503.032 | 96948.375 | 5.710234 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 126045.89 | 113867.49 | 5.710234 | 27.93 | 18.31 | 0.00919884 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.9303 | 24.00 | 0.00877971 | 47.2221 | 78539.45 | 0.00 | 139721.81 | 98538.71 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.713070 | 15.21 | 13.42 | 0.00885680 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 69.7677 | 21.00 | 0.00823119 | 53.1662 | 9465.28 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 123376.294 | 87045.858 | 5.038267 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 115579.88 | 103400.46 | 5.038267 | 28.46 | 18.56 | 0.00929428 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 23.7218 | 24.00 | 0.00883091 | 47.4939 | 69224.55 | 0.00 | 127217.52 | 88527.69 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.511480 | 14.38 | 13.17 | 0.00894562 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 79.0728 | 21.00 | 0.00818849 | 52.8938 | 18972.01 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 140165.577 | 100547.440 | 5.949957 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 130175.52 | 117652.60 | 5.949957 | 27.78 | 18.25 | 0.00918919 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.0870 | 24.00 | 0.00878760 | 47.2642 | 81647.36 | 0.00 | 144529.52 | 102216.54 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.784987 | 15.44 | 13.46 | 0.00880610 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 66.9568 | 21.00 | 0.00810225 | 52.3442 | 27191.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26941.657 | 26941.657 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26941.66 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26941.66 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.93 | 0.00811181 | 21.00 | 0.00811181 | 52.4060 | 1064.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 26119.348 | 26119.348 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26119.35 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26119.35 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6794.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27265.236 | 27265.236 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27265.24 | 16588.11 | 1.0000 | 0.59806823 | 0.496902 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27265.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11770.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7237.871 | 7237.871 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7237.87 | 7237.87 | 1.0000 | 0.26095437 | 0.216812 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7237.87 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823093 | 21.00 | 0.00823093 | 53.1636 | 5100.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4948.695 | 4948.695 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4948.70 | 4727.40 | 1.0000 | 0.17044181 | 0.141611 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4948.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823098 | 21.00 | 0.00823098 | 53.1639 | 3330.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7201.595 | 7201.595 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7201.59 | 7201.59 | 1.0000 | 0.25964647 | 0.215726 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7201.59 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823241 | 21.00 | 0.00823241 | 53.1730 | 5074.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5605.181 | 5605.181 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5605.18 | 4747.82 | 1.0000 | 0.17117818 | 0.142222 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5605.18 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822966 | 21.00 | 0.00822966 | 53.1555 | 3344.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5685.897 | 5685.897 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5685.90 | 3631.17 | 1.0000 | 0.13091821 | 0.108773 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5685.90 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828986 | 21.00 | 0.00828986 | 53.5398 | 2575.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4488.361 | 4488.361 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4488.36 | 2410.53 | 1.0000 | 0.08690945 | 0.072208 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4488.36 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00829244 | 21.00 | 0.00829244 | 53.5562 | 1708.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6039.687 | 6039.687 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6039.69 | 3615.12 | 1.0000 | 0.13033956 | 0.108292 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6039.69 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00829084 | 21.00 | 0.00829084 | 53.5461 | 2563.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4748.058 | 4748.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4748.06 | 2421.09 | 1.0000 | 0.08729010 | 0.072524 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4748.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00829142 | 21.00 | 0.00829142 | 53.5497 | 1715.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5511.373 | 5511.373 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5511.37 | 5197.30 | 1.0000 | 0.18738372 | 0.155687 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5511.37 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829205 | 21.00 | 0.00829205 | 53.5533 | 3671.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4629.830 | 4629.830 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4629.83 | 3428.41 | 1.0000 | 0.12360785 | 0.102699 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4629.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829194 | 21.00 | 0.00829194 | 53.5525 | 2421.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6122.224 | 6122.224 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6122.22 | 5170.43 | 1.0000 | 0.18641491 | 0.154882 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6122.22 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829359 | 21.00 | 0.00829359 | 53.5631 | 3652.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4994.785 | 4994.785 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4994.78 | 3443.26 | 1.0000 | 0.12414332 | 0.103144 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4994.78 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829059 | 21.00 | 0.00829059 | 53.5440 | 2431.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 135503.032 | 96948.375 | 5.710234 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9402 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.710234 | 6.87280879 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 126045.89 | 113867.49 | 0.9302 | 6.87280879 | 5.710234 | 27.93 | 18.31 | 0.00919884 | 51553.3 | 11.03 | 11.03 | 0.00850000 | 32517.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12419.121 | 113626.77 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 20.9303 | 24.00 | 0.00877971 | 24.00 | 0.00877971 | 47.2221 | 78539.45 | 0.00 | 139721.81 | 98538.71 | 6.60138480 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.05 | 12.03 | 0.00873866 | 34156.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.710234 | 6.87280879 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.06184264 | 1.713070 | 15.21 | 13.42 | 0.00885680 | 37685.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 69.7677 | 21.01 | 0.00817222 | 21.00 | 0.00823119 | 53.1662 | 9465.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 123376.294 | 87045.858 | 5.038267 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1176 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.038267 | 6.06403252 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 115579.88 | 103400.46 | 0.9368 | 6.06403252 | 5.038267 | 28.46 | 18.56 | 0.00929428 | 52338.2 | 11.03 | 11.03 | 0.00850000 | 32517.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10957.667 | 104622.21 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 23.7218 | 24.00 | 0.00883091 | 24.00 | 0.00883091 | 47.4939 | 69224.55 | 0.00 | 127217.52 | 88527.69 | 5.82454907 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.78 | 11.76 | 0.00858027 | 33480.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.038267 | 6.06403252 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.81920975 | 1.511480 | 14.38 | 13.17 | 0.00894562 | 37062.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 79.0728 | 20.73 | 0.00816034 | 21.00 | 0.00818849 | 52.8938 | 18972.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 140165.577 | 100547.440 | 5.949957 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9222 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.949957 | 7.16133885 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 130175.52 | 117652.60 | 0.9287 | 7.16133885 | 5.949957 | 27.78 | 18.25 | 0.00918919 | 51375.5 | 11.03 | 11.03 | 0.00850000 | 32517.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12940.493 | 117235.03 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 20.0870 | 24.00 | 0.00878760 | 24.00 | 0.00878760 | 47.2642 | 81647.36 | 0.00 | 144529.52 | 102216.54 | 6.87852010 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.11 | 12.09 | 0.00877281 | 34310.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.949957 | 7.16133885 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.14840166 | 1.784987 | 15.44 | 13.46 | 0.00880610 | 37793.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 66.9568 | 21.00 | 0.00810225 | 21.00 | 0.00810225 | 52.3442 | 27191.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5486.83 | 0.67 | 0.00 |
CORE_MID | 4823.00 | 251.67 | 0.00 |
CORE_TOP | 4404.17 | 690.17 | 13.83 |
PERIMETER_TOP_ZN_3 | 4411.50 | 1415.00 | 436.00 |
PERIMETER_TOP_ZN_2 | 4656.17 | 1299.33 | 498.83 |
PERIMETER_TOP_ZN_1 | 4814.00 | 1182.33 | 503.17 |
PERIMETER_TOP_ZN_4 | 4474.67 | 1478.50 | 460.83 |
PERIMETER_BOT_ZN_3 | 4898.00 | 648.83 | 264.50 |
PERIMETER_BOT_ZN_2 | 5142.00 | 653.67 | 369.33 |
PERIMETER_BOT_ZN_1 | 5286.00 | 1259.00 | 1016.00 |
PERIMETER_BOT_ZN_4 | 5075.33 | 696.33 | 348.17 |
PERIMETER_MID_ZN_3 | 4694.67 | 1026.33 | 403.00 |
PERIMETER_MID_ZN_2 | 4040.00 | 1006.33 | 459.67 |
PERIMETER_MID_ZN_1 | 5072.50 | 847.00 | 471.17 |
PERIMETER_MID_ZN_4 | 4761.00 | 1109.50 | 434.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5653.83 | 2431.17 | 1306.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 79.00 | 0.00 | 53.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 99.67 | 0.00 | 78.50 |
PERIMETER_TOP_ZN_1 | 0.00 | 96.83 | 0.00 | 74.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 93.17 | 0.00 | 61.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 52.33 | 0.00 | 38.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 87.33 | 0.00 | 70.67 |
PERIMETER_BOT_ZN_1 | 0.67 | 405.00 | 0.67 | 384.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 83.50 | 0.00 | 52.33 |
PERIMETER_MID_ZN_3 | 0.00 | 64.33 | 0.00 | 47.00 |
PERIMETER_MID_ZN_2 | 0.00 | 85.33 | 0.00 | 72.83 |
PERIMETER_MID_ZN_1 | 0.00 | 83.83 | 0.00 | 69.50 |
PERIMETER_MID_ZN_4 | 0.00 | 75.00 | 0.00 | 51.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 576.50 | 0.67 | 510.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.485 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.433 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.426 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.606 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.759 | 0.076 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.737 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.774 | 0.076 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.513 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.648 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.725 | 1.257 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.647 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.600 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.718 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.736 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.767 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8297874.36 | 0.00 | 8297874.36 | 0.00 | 8297874.36 | 13393058.27 | 7269.51 | 92.69 | 1397.79 | 521.50 |
CORE_MID | 7351377.67 | 0.00 | 7351377.67 | 0.00 | 7351377.67 | 13393058.27 | 8446.83 | 44.35 | 268.82 | 436.26 |
CORE_TOP | 7293727.85 | 0.00 | 7293727.85 | 0.00 | 7293727.85 | 13393058.27 | 8641.58 | 26.62 | 91.80 | 482.01 |
PERIMETER_TOP_ZN_3 | 2150185.61 | 0.00 | 2150185.61 | 413457.77 | 2563643.38 | 2823374.22 | 3794.35 | 120.71 | 4844.93 | 482.01 |
PERIMETER_TOP_ZN_2 | 1700565.84 | 0.00 | 1700565.84 | 275636.86 | 1976202.70 | 1787429.43 | 3221.66 | 16.60 | 5521.74 | 482.01 |
PERIMETER_TOP_ZN_1 | 2595615.68 | 0.00 | 2595615.68 | 413457.77 | 3009073.46 | 2823374.22 | 3241.17 | 14.43 | 5504.40 | 482.01 |
PERIMETER_TOP_ZN_4 | 1751559.42 | 0.00 | 1751559.42 | 275636.86 | 2027196.28 | 1787312.18 | 3301.81 | 28.51 | 5429.68 | 482.01 |
PERIMETER_BOT_ZN_3 | 1842088.08 | 0.00 | 1842088.08 | 219835.62 | 2061923.70 | 2823374.22 | 6479.09 | 114.40 | 2166.51 | 521.50 |
PERIMETER_BOT_ZN_2 | 1472163.71 | 0.00 | 1472163.71 | 146556.20 | 1618719.90 | 1787429.43 | 3607.81 | 104.17 | 5048.02 | 521.50 |
PERIMETER_BOT_ZN_1 | 2547742.77 | 0.00 | 2547742.77 | 4198137.27 | 6745880.03 | 2823374.22 | 3769.94 | 73.44 | 4916.62 | 521.50 |
PERIMETER_BOT_ZN_4 | 1481744.00 | 0.00 | 1481744.00 | 146556.20 | 1628300.20 | 1787312.18 | 3901.52 | 88.96 | 4769.52 | 521.50 |
PERIMETER_MID_ZN_3 | 2103633.58 | 0.00 | 2103633.58 | 344173.66 | 2447807.24 | 2823374.22 | 5400.15 | 85.87 | 3273.97 | 436.26 |
PERIMETER_MID_ZN_2 | 1670065.05 | 0.00 | 1670065.05 | 229447.73 | 1899512.77 | 1787429.43 | 3334.91 | 33.88 | 5391.22 | 1345.26 |
PERIMETER_MID_ZN_1 | 2562268.83 | 0.00 | 2562268.83 | 344173.66 | 2906442.49 | 2823374.22 | 3338.11 | 29.22 | 5392.67 | 436.26 |
PERIMETER_MID_ZN_4 | 1715435.61 | 0.00 | 1715435.61 | 229447.73 | 1944883.33 | 1787312.18 | 3471.92 | 38.80 | 5249.28 | 436.26 |
Total Facility | 46536048.05 | 0.00 | 46536048.05 | 7236517.31 | 53772565.36 | 67843644.98 | 8760.00 | 753.24 | 5936.58 | 1620.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3521 | 0.0000 | 0.3521 | 0.0000 | 0.3521 | 0.4247 | 4459.27 | 92.31 | 1391.42 |
CORE_MID | 0.3141 | 0.0000 | 0.3141 | 0.0000 | 0.3141 | 0.4247 | 5631.81 | 44.11 | 267.08 |
CORE_TOP | 0.3090 | 0.0000 | 0.3090 | 0.0000 | 0.3090 | 0.4247 | 5825.68 | 26.42 | 90.90 |
PERIMETER_TOP_ZN_3 | 0.0925 | 0.0000 | 0.0925 | 0.0110 | 0.1035 | 0.0895 | 1456.55 | 118.36 | 4368.08 |
PERIMETER_TOP_ZN_2 | 0.0734 | 0.0000 | 0.0734 | 0.0073 | 0.0808 | 0.0567 | 886.01 | 16.35 | 5040.63 |
PERIMETER_TOP_ZN_1 | 0.1127 | 0.0000 | 0.1127 | 0.0110 | 0.1236 | 0.0895 | 905.44 | 14.35 | 5023.21 |
PERIMETER_TOP_ZN_4 | 0.0748 | 0.0000 | 0.0748 | 0.0073 | 0.0822 | 0.0567 | 966.53 | 28.35 | 4948.13 |
PERIMETER_BOT_ZN_3 | 0.0783 | 0.0000 | 0.0783 | 0.0058 | 0.0841 | 0.0895 | 3705.47 | 112.41 | 2125.13 |
PERIMETER_BOT_ZN_2 | 0.0627 | 0.0000 | 0.0627 | 0.0039 | 0.0666 | 0.0567 | 1310.52 | 103.45 | 4529.03 |
PERIMETER_BOT_ZN_1 | 0.1106 | 0.0000 | 0.1106 | 0.1918 | 0.3024 | 0.0895 | 1465.27 | 64.78 | 4412.95 |
PERIMETER_BOT_ZN_4 | 0.0625 | 0.0000 | 0.0625 | 0.0039 | 0.0664 | 0.0567 | 1604.79 | 88.71 | 4249.50 |
PERIMETER_MID_ZN_3 | 0.0916 | 0.0000 | 0.0916 | 0.0091 | 0.1007 | 0.0895 | 2642.45 | 84.63 | 3215.92 |
PERIMETER_MID_ZN_2 | 0.0694 | 0.0000 | 0.0694 | 0.0064 | 0.0758 | 0.0567 | 906.89 | 22.94 | 4104.17 |
PERIMETER_MID_ZN_1 | 0.1125 | 0.0000 | 0.1125 | 0.0091 | 0.1216 | 0.0895 | 955.93 | 26.93 | 4960.15 |
PERIMETER_MID_ZN_4 | 0.0741 | 0.0000 | 0.0741 | 0.0061 | 0.0802 | 0.0567 | 1090.43 | 38.71 | 4813.85 |
Total Facility | 1.9903 | 0.0000 | 1.9903 | 0.2728 | 2.2632 | 2.1513 | 5943.00 | 736.52 | 5224.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 22659070.04 | 0.00 | 22659070.04 | 22614548.33 | 3144.37 | 0.00 | 5615.63 | 521.50 |
PACU_VAV_MID | 22313113.06 | 0.00 | 22313113.06 | 22614548.33 | 3255.16 | 0.00 | 5504.84 | 436.26 |
PACU_VAV_TOP | 22441833.51 | 0.00 | 22441833.51 | 22614548.33 | 3206.64 | 0.00 | 5553.36 | 482.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9651 | 0.0000 | 0.9651 | 0.7171 | 848.87 | 0.00 | 5094.13 |
PACU_VAV_MID | 0.9633 | 0.0000 | 0.9633 | 0.7171 | 874.42 | 0.00 | 5068.58 |
PACU_VAV_TOP | 0.9596 | 0.0000 | 0.9596 | 0.7171 | 871.65 | 0.00 | 5071.35 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5615.63 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5504.84 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5553.36 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1259 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1296 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1247 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
Electricity:Building | 1005.87 | 12242.94 | 29-MAY-17:20 | 78507.21 | 14-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1005.87 | 12242.94 | 29-MAY-17:20 | 78507.21 | 14-MAR-07:10 |
InteriorLights:Electricity | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.04 | 422.10 | 30-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.89 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.89 | 422.10 | 30-APR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.02 | 422.10 | 23-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-10:40 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-10:40 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.87 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.87 | 422.10 | 26-MAR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.88 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.48 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.48 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.04 | 422.10 | 30-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.89 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.89 | 422.10 | 30-APR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1072.68 | 168.34 | 01-JAN-00:10 | 151656.07 | 10-AUG-15:40 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 14-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 14-MAR-07:20 |
ElectricityPurchased:Facility | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
ElectricityNet:Plant | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 2129.25 | 12411.64 | 29-MAY-17:20 | 219416.41 | 10-AUG-15:40 |
Heating:Electricity | 0.49 | 0.00 | 01-JAN-00:10 | 7286.17 | 20-JAN-07:10 |
General:Heating:Electricity | 0.49 | 0.00 | 01-JAN-00:10 | 7286.17 | 20-JAN-07:10 |
Fans:Electricity | 167.67 | 0.00 | 01-JAN-00:10 | 25606.93 | 05-SEP-15:10 |
General:Fans:Electricity | 167.67 | 0.00 | 01-JAN-00:10 | 25606.93 | 05-SEP-15:10 |
ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 892.77 | 0.00 | 01-JAN-00:10 | 127167.23 | 10-AUG-15:50 |
General:Cooling:Electricity | 892.77 | 0.00 | 01-JAN-00:10 | 127167.23 | 10-AUG-15:50 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
WIRED_LTG_ELECTRICITY | 8.44 | 0.00 | 01-JAN-00:10 | 917.25 | 14-MAR-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 108.59 | 1886.44 | 03-JUL-16:10 | 9527.76 | 18-JAN-12:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 108.59 | 1886.44 | 03-JUL-16:10 | 9527.76 | 18-JAN-12:10 |
WaterSystems:NaturalGas | 108.59 | 1886.44 | 03-JUL-16:10 | 9527.76 | 18-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 108.59 | 1886.44 | 03-JUL-16:10 | 9527.76 | 18-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5179.85 | 0.00 | 01-JAN-00:10 | 557476.04 | 10-AUG-16:00 |
EnergyTransfer:Building | 1960.56 | 0.00 | 01-JAN-00:10 | 194752.38 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 337.44 | 0.00 | 01-JAN-00:10 | 27659.86 | 13-NOV-09:00 |
Heating:EnergyTransfer | 1.95 | 0.00 | 01-JAN-00:10 | 6123.95 | 03-JAN-07:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 1.95 | 0.00 | 01-JAN-00:10 | 6123.95 | 03-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1958.61 | 0.00 | 01-JAN-00:10 | 194752.38 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 337.44 | 0.00 | 01-JAN-00:10 | 27659.86 | 13-NOV-09:00 |
General:Cooling:EnergyTransfer | 1958.61 | 0.00 | 01-JAN-00:10 | 194752.38 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 337.44 | 0.00 | 01-JAN-00:10 | 27659.86 | 13-NOV-09:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 90.69 | 0.00 | 01-JAN-00:10 | 14521.84 | 16-AUG-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.11 | 0.00 | 01-JAN-00:10 | 2737.96 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.11 | 0.00 | 01-JAN-00:10 | 2737.96 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.58 | 0.00 | 01-JAN-00:10 | 14521.84 | 16-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.58 | 0.00 | 01-JAN-00:10 | 14521.84 | 16-AUG-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.46 | 0.00 | 01-JAN-00:10 | 7422.27 | 05-SEP-15:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.21 | 0.00 | 01-JAN-00:10 | 1355.61 | 31-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.21 | 0.00 | 01-JAN-00:10 | 1355.61 | 31-DEC-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.25 | 0.00 | 01-JAN-00:10 | 7422.27 | 05-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.25 | 0.00 | 01-JAN-00:10 | 7422.27 | 05-SEP-15:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.82 | 0.00 | 01-JAN-00:10 | 7433.56 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.32 | 0.00 | 01-JAN-00:10 | 1468.74 | 01-JAN-12:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.32 | 0.00 | 01-JAN-00:10 | 1468.74 | 01-JAN-12:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.51 | 0.00 | 01-JAN-00:10 | 7433.56 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.51 | 0.00 | 01-JAN-00:10 | 7433.56 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 243.71 | 0.00 | 01-JAN-00:10 | 20601.22 | 05-SEP-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 243.71 | 0.00 | 01-JAN-00:10 | 20601.22 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 243.71 | 0.00 | 01-JAN-00:10 | 20601.22 | 05-SEP-07:50 |
EnergyTransfer:Zone:CORE_TOP | 253.01 | 0.00 | 01-JAN-00:10 | 22812.71 | 05-SEP-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 253.01 | 0.00 | 01-JAN-00:10 | 22812.71 | 05-SEP-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 253.01 | 0.00 | 01-JAN-00:10 | 22812.71 | 05-SEP-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.68 | 0.00 | 01-JAN-00:10 | 9423.56 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 97.47 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 97.47 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.68 | 0.00 | 01-JAN-00:10 | 9423.56 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.68 | 0.00 | 01-JAN-00:10 | 9423.56 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.60 | 0.00 | 01-JAN-00:10 | 8006.88 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 252.82 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 252.82 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.60 | 0.00 | 01-JAN-00:10 | 8006.88 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.60 | 0.00 | 01-JAN-00:10 | 8006.88 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.93 | 0.00 | 01-JAN-00:10 | 11232.30 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.93 | 0.00 | 01-JAN-00:10 | 11232.30 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.93 | 0.00 | 01-JAN-00:10 | 11232.30 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.86 | 0.00 | 01-JAN-00:10 | 8240.88 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 441.32 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 441.32 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.86 | 0.00 | 01-JAN-00:10 | 8240.88 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.86 | 0.00 | 01-JAN-00:10 | 8240.88 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 79.92 | 0.00 | 01-JAN-00:10 | 8931.28 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 79.92 | 0.00 | 01-JAN-00:10 | 8931.28 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 79.92 | 0.00 | 01-JAN-00:10 | 8931.28 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.74 | 0.00 | 01-JAN-00:10 | 7491.43 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.74 | 0.00 | 01-JAN-00:10 | 7491.43 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.74 | 0.00 | 01-JAN-00:10 | 7491.43 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.78 | 0.00 | 01-JAN-00:10 | 18871.46 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.30 | 0.00 | 01-JAN-00:10 | 4701.34 | 04-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.30 | 0.00 | 01-JAN-00:10 | 4701.34 | 04-JAN-07:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.48 | 0.00 | 01-JAN-00:10 | 18871.46 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.48 | 0.00 | 01-JAN-00:10 | 18871.46 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.06 | 0.00 | 01-JAN-00:10 | 7530.18 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.06 | 0.00 | 01-JAN-00:10 | 7530.18 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.06 | 0.00 | 01-JAN-00:10 | 7530.18 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.67 | 0.00 | 01-JAN-00:10 | 8502.35 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.67 | 0.00 | 01-JAN-00:10 | 8502.35 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.67 | 0.00 | 01-JAN-00:10 | 8502.35 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.43 | 0.00 | 01-JAN-00:10 | 7540.90 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.43 | 0.00 | 01-JAN-00:10 | 7540.90 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.43 | 0.00 | 01-JAN-00:10 | 7540.90 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.74 | 0.00 | 01-JAN-00:10 | 10445.27 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.74 | 0.00 | 01-JAN-00:10 | 10445.27 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.74 | 0.00 | 01-JAN-00:10 | 10445.27 | 02-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 60.02 | 0.00 | 01-JAN-00:10 | 7606.33 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 60.02 | 0.00 | 01-JAN-00:10 | 7606.33 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 60.02 | 0.00 | 01-JAN-00:10 | 7606.33 | 09-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
EnergyTransfer:HVAC | 3187.73 | 0.00 | 01-JAN-00:10 | 370694.59 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.49 | 0.00 | 01-JAN-00:10 | 7286.17 | 20-JAN-07:10 |
CoolingCoils:EnergyTransfer | 3187.24 | 0.00 | 01-JAN-00:10 | 370694.59 | 10-AUG-16:00 |
EnergyTransfer:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4392.47 | 13-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -337.438 | 0.000 | 0.000 | 32.667 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -3.324 |
CORE_MID | 0.000 | 0.000 | 0.000 | -243.708 | 0.000 | 0.000 | 32.732 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 23.622 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -253.012 | 0.000 | 0.000 | 32.821 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 32.838 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -80.675 | 0.000 | 0.000 | 6.949 | 8.712 | 24.333 | 36.688 | 0.000 | 2.207 | 10.169 | 0.000 | -7.790 | 0.000 | -0.592 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -63.600 | 0.000 | 0.000 | 4.385 | 5.484 | 15.404 | 37.080 | 0.000 | 1.464 | 5.112 | 0.000 | -4.921 | 0.000 | -0.408 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -96.928 | 0.000 | 0.000 | 6.924 | 8.553 | 24.332 | 57.984 | 0.000 | 2.182 | 5.407 | 0.000 | -7.791 | 0.000 | -0.663 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.001 | -63.856 | 0.000 | 0.000 | 4.417 | 5.491 | 15.403 | 37.719 | 0.000 | 1.467 | 5.039 | 0.000 | -5.272 | 0.000 | -0.409 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -79.919 | 0.000 | 0.000 | 6.899 | 8.683 | 24.333 | 36.416 | 0.000 | 1.190 | 11.522 | 0.000 | -8.752 | 0.000 | -0.371 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -63.738 | 0.000 | 0.000 | 4.363 | 5.471 | 15.404 | 36.889 | 0.000 | 0.784 | 6.680 | 0.000 | -5.594 | 0.000 | -0.258 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.301 | -118.476 | 0.000 | 0.000 | 6.846 | 8.538 | 24.332 | 57.575 | 0.000 | 27.077 | 7.201 | 0.000 | -8.900 | 0.000 | -4.494 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -63.064 | 0.000 | 0.000 | 4.369 | 5.476 | 15.403 | 37.531 | 0.000 | 0.780 | 5.816 | 0.000 | -6.050 | 0.000 | -0.262 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -75.669 | 0.000 | 0.000 | 6.910 | 8.712 | 24.333 | 36.734 | 0.000 | 1.840 | 6.063 | 0.000 | -8.375 | 0.000 | -0.548 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -59.434 | 0.000 | 0.000 | 3.226 | 5.484 | 15.404 | 37.130 | 0.000 | 1.224 | 2.576 | 0.000 | -5.237 | 0.000 | -0.373 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -91.740 | 0.000 | 0.000 | 6.897 | 8.553 | 24.332 | 58.081 | 0.000 | 1.820 | 0.965 | 0.000 | -8.305 | 0.000 | -0.603 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -60.022 | 0.000 | 0.000 | 4.386 | 5.491 | 15.403 | 37.764 | 0.000 | 1.220 | 1.792 | 0.000 | -5.657 | 0.000 | -0.377 | -0.000 |
TOPFLOOR_PLENUM | 1.113 | -89.579 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.020 | 86.344 | 0.000 | 0.000 | 0.000 | -0.899 | 0.000 |
MIDFLOOR_PLENUM | 0.215 | -55.246 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.901 | 53.097 | 0.000 | 0.000 | 0.000 | -0.966 | 0.000 |
FIRSTFLOOR_PLENUM | 0.318 | -62.505 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.247 | 60.750 | 0.000 | 0.000 | 0.000 | -0.810 | 0.000 |
Total Facility | 1.645 | -207.330 | 0.302 | -1751.282 | 0.000 | 0.000 | 164.789 | 300.433 | 705.434 | 507.592 | 0.000 | 51.424 | 324.995 | 0.000 | -82.644 | 0.000 | -12.032 | -3.331 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | -46147.23 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 41529.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 23-OCT-04:03 | 0.00 | 0.00 | 0.00 | -34919.27 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 32265.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-SEP-04:02 | 0.00 | 0.00 | 0.00 | -39089.98 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 36436.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-15:01 | 0.00 | 0.00 | 0.00 | -16412.48 | 0.00 | 0.00 | 23.70 | 36.00 | 478.42 | 3687.18 | 0.00 | 579.30 | 11607.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-10:22 | 0.00 | 0.00 | 0.00 | -13585.04 | 0.00 | 0.00 | 14.21 | 22.79 | 302.86 | 4685.27 | 0.00 | 204.05 | 8355.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-11:42 | 0.00 | 0.00 | 0.00 | -19323.77 | 0.00 | 0.00 | 22.73 | 36.00 | 478.41 | 8167.64 | 0.00 | 122.33 | 10496.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-15:41 | 0.00 | 0.00 | 0.00 | -14998.65 | 0.00 | 0.00 | 12.33 | 22.79 | 302.86 | 5776.96 | 0.00 | 332.39 | 8551.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 | -14670.58 | 0.00 | 0.00 | 25.46 | 36.00 | 478.42 | 3661.63 | 0.00 | 305.37 | 10163.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-10:22 | 0.00 | 0.00 | 0.00 | -12283.21 | 0.00 | 0.00 | 14.76 | 22.79 | 302.86 | 4529.42 | 0.00 | 140.69 | 7272.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18871.13 | 0.00 | 0.00 | 227.84 | 647.98 | 1275.77 | 5945.00 | 0.00 | 18776.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8002.13 |
PERIMETER_BOT_ZN_4 | 04-SEP-15:41 | 0.00 | 0.00 | 0.00 | -13587.33 | 0.00 | 0.00 | 13.68 | 22.79 | 302.86 | 5771.79 | 0.00 | 187.67 | 7288.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -14134.47 | 0.00 | 0.00 | 26.54 | 36.00 | 478.42 | 2992.80 | 0.00 | 444.54 | 10156.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-09:52 | 0.00 | 0.00 | 0.00 | -12635.12 | 0.00 | 0.00 | 14.56 | 22.79 | 302.86 | 5089.52 | 0.00 | 218.00 | 6987.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-13:12 | 0.00 | 0.00 | 0.00 | -17136.70 | 0.00 | 0.00 | 22.45 | 36.00 | 478.41 | 7640.53 | 0.00 | 319.03 | 8640.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 09-OCT-15:12 | 0.00 | 0.00 | 0.00 | -13571.53 | 0.00 | 0.00 | 14.49 | 22.79 | 302.86 | 4976.94 | 0.00 | 286.89 | 7967.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:30 | 0.00 | -14521.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.99 | 14248.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-15:10 | 0.00 | -7422.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.28 | 7154.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 05-SEP-12:10 | 0.00 | -9371.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.63 | 9236.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUN-04:02 | 0.00 | 9612.07 | 0.00 | -239749.26 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 225.89 | 215602.38 | 0.00 | -1097.55 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 20-JAN-07:03 | 0.00 | 0.00 | 292.41 | 0.00 | 0.00 | 0.00 | 186.47 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1391.80 | 0.00 | -31.89 | -145.89 |
PERIMETER_TOP_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 758.48 | 0.00 | 0.00 | 0.00 | 119.20 | 286.67 | 403.81 | 93.30 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.24 | -1640.22 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 03-JAN-07:03 | 0.00 | 0.00 | 1454.51 | 0.00 | 0.00 | 0.00 | 119.17 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -942.73 | 0.00 | -1.11 | -1320.30 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-JAN-07:20 | 0.00 | 0.00 | 4702.09 | 0.00 | 0.00 | 0.00 | 184.50 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 4140.72 | 0.00 | -761.35 | 0.00 | -9356.67 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 08-MAY-04:02 | 5211.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5217.46 |
MIDFLOOR_PLENUM | 25-AUG-04:02 | 3415.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3508.53 |
FIRSTFLOOR_PLENUM | 28-SEP-04:02 | 4594.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4651.12 |
Total Facility | 15-SEP-04:02 | -201889.34 | 212468.93 | 0.00 | -212468.93 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 59.40 | 0.00 | 693.95 | 185929.03 | 0.00 | -199.53 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0881 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7102 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4636 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0383 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.1093 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9500 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0441 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4350 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7318 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4192 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0546 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5313 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9891 | 2.9891 | 0.8070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2878 | 2.2878 | 0.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5365 | 2.5365 | 0.8167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9454 | 0.9454 | 0.1891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7412 | 0.7412 | 0.1482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0467 | 1.0467 | 0.2093 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8395 | 0.8395 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8111 | 0.8111 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6723 | 0.6723 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9046 | 0.9046 | 0.1809 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7111 | 0.7111 | 0.1422 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8173 | 0.8173 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6934 | 0.6934 | 0.1387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9170 | 0.9170 | 0.1834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7481 | 0.7481 | 0.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0881 | 5.7102 | 6.0881 | 1.4350 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4636 | 5.0383 | 5.4636 | 1.4192 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.1093 | 5.9500 | 6.1093 | 1.5313 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4945 | 1.4945 | 0.8070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1439 | 1.1439 | 0.7824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2682 | 1.2682 | 0.8167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4727 | 0.4727 | 0.1891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3706 | 0.3706 | 0.1482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5234 | 0.5234 | 0.2093 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4198 | 0.4198 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4055 | 0.4055 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3361 | 0.3361 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4523 | 0.4523 | 0.1809 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3556 | 0.3556 | 0.1422 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4087 | 0.4087 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3467 | 0.3467 | 0.1387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4585 | 0.4585 | 0.1834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3741 | 0.3741 | 0.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0441 | 1.4350 | 1.4350 | 1.4350 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7318 | 1.4192 | 1.4192 | 1.4192 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0546 | 1.5313 | 1.5313 | 1.5313 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 510.00 |
Number of hours not met | 510.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.49 | 7286.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 892.77 | 127167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.43 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.55 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 167.67 | 25606.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 108.59 | 9527.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 2129.25 |
Natural Gas | 0.00 | 108.59 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2237.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.30 |
Space Heating | 0.10 |
Space Cooling | 179.19 |
Fans (All) | 33.65 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 427.37 |
Subtotal | 427.37 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 21.80 |
Miscellaneous (All) | 21.80 |
Subtotal | 21.80 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.43 |
Space Heating | 0.02 |
Space Cooling | 39.89 |
Fans (All) | 7.49 |
Service Water Heating | 4.85 |
Receptacle Equipment | 31.52 |
Miscellaneous | 2.79 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8346.50 | 413.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8727.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7846.33 | 913.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7793.00 | 967.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7773.50 | 986.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7779.00 | 981.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8031.17 | 728.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7813.67 | 946.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7667.17 | 1092.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7735.50 | 1024.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7801.50 | 958.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7740.83 | 1019.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7695.50 | 1064.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7682.00 | 1078.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8014.50 | 745.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8395.67 | 364.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8551.17 | 208.83 | 0.00 | 0.00 | 0.00 |
Min | 7667.17 | 26.00 | 0.00 | 0.00 | 0.00 |
Max | 8734.00 | 1092.83 | 0.00 | 0.00 | 0.00 |
Average | 8007.15 | 752.85 | 0.00 | 0.00 | 0.00 |
Sum | 144128.67 | 13551.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128207.33 | 96.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128296.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24528.17 | 380.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128299.00 | 380.83 | 0.00 | 0.00 | 0.00 |
Average | 34116.12 | 27.21 | 0.00 | 0.00 | 0.00 |
Sum | 614090.17 | 489.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7225.33 | 1534.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7391.00 | 1369.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7397.33 | 1362.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6437.83 | 2322.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6404.00 | 2356.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6341.00 | 2419.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6441.17 | 2318.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6450.17 | 2309.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6344.83 | 2415.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5566.67 | 3193.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6354.17 | 2405.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6309.33 | 2450.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6294.67 | 2465.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6190.83 | 2569.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6290.67 | 2469.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4590.83 | 4169.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5435.33 | 3324.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 5875.00 | 2885.00 | 0.00 | 0.00 | 0.00 |
Min | 4590.83 | 1362.67 | 0.00 | 0.00 | 0.00 |
Max | 7397.33 | 4169.17 | 0.00 | 0.00 | 0.00 |
Average | 6296.68 | 2463.32 | 0.00 | 0.00 | 0.00 |
Sum | 113340.17 | 44339.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127581.17 | 722.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127682.17 | 621.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127568.67 | 735.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24809.83 | 99.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24818.33 | 90.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24821.67 | 87.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21279.00 | 3630.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24795.33 | 113.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24802.17 | 106.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127682.17 | 3630.00 | 0.00 | 0.00 | 0.00 |
Average | 33798.44 | 344.89 | 0.00 | 0.00 | 0.00 |
Sum | 608372.00 | 6208.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:31:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235595E+11 | 42308.69 | 02-JAN-07:02 | 13.00 | 10.98 | 0.199478E+10 | 2606.69 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.217807E+11 | 41019.83 | 21-FEB-07:02 | 13.92 | 13.01 | 0.180986E+10 | 2606.76 | 15-FEB-14:09 | 13.92 | 13.01 |
March | 0.266624E+11 | 45108.51 | 28-MAR-04:03 | 26.08 | 14.62 | 0.216112E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.259644E+11 | 46147.17 | 17-APR-04:03 | 24.33 | 19.27 | 0.191868E+10 | 2606.86 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.306221E+11 | 46074.18 | 16-MAY-04:03 | 25.00 | 22.44 | 0.207774E+10 | 2606.77 | 04-MAY-13:00 | 25.00 | 22.44 |
June | 0.309543E+11 | 45595.27 | 07-JUN-04:03 | 24.83 | 21.13 | 0.207078E+10 | 2606.74 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.316527E+11 | 40065.54 | 13-JUL-04:02 | 30.58 | 20.96 | 0.192276E+10 | 2606.85 | 03-JUL-09:20 | 30.58 | 20.96 |
August | 0.340679E+11 | 40044.01 | 15-AUG-04:02 | 29.75 | 23.27 | 0.215778E+10 | 2606.66 | 04-AUG-13:00 | 29.75 | 23.27 |
September | 0.304671E+11 | 43440.32 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191761E+10 | 2606.64 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.302514E+11 | 45214.06 | 31-OCT-04:03 | 24.33 | 22.73 | 0.199503E+10 | 2606.64 | 27-OCT-13:09 | 24.33 | 22.73 |
November | 0.273005E+11 | 45391.94 | 01-NOV-04:42 | 23.95 | 21.86 | 0.197617E+10 | 2606.67 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.241520E+11 | 44131.42 | 11-DEC-06:12 | 21.80 | 19.16 | 0.192495E+10 | 2606.68 | 13-DEC-10:09 | 21.50 | 16.06 |
Annual Sum or Average | 0.337435E+12 | 0.239273E+11 | ||||||||
Minimum of Months | 0.217807E+11 | 40044.01 | 13.00 | 10.98 | 0.180986E+10 | 2606.64 | 13.92 | 13.01 | ||
Maximum of Months | 0.340679E+11 | 46147.17 | 30.58 | 23.27 | 0.216112E+10 | 2606.86 | 36.42 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226410E+10 | 5333.78 | 31-JAN-14:10 | 23.00 | 16.33 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 16.33 |
February | 0.297761E+10 | 8212.83 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.485021E+10 | 11160.70 | 27-MAR-13:30 | 35.50 | 19.59 | 0.00 | 0.00 | 01-MAR-00:10 | 35.50 | 19.59 |
April | 0.648478E+10 | 12359.22 | 28-APR-12:40 | 38.47 | 22.15 | 0.00 | 0.00 | 01-APR-00:10 | 38.47 | 22.15 |
May | 0.102764E+11 | 12782.14 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.111715E+11 | 13404.20 | 12-JUN-13:10 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.123996E+11 | 14433.65 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.130347E+11 | 14521.84 | 16-AUG-13:30 | 44.10 | 25.63 | 0.00 | 0.00 | 01-AUG-00:10 | 44.10 | 25.63 |
September | 0.100951E+11 | 13593.98 | 05-SEP-14:00 | 40.00 | 25.05 | 0.00 | 0.00 | 01-SEP-00:10 | 40.00 | 25.05 |
October | 0.799555E+10 | 11527.68 | 04-OCT-14:00 | 36.00 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 20.88 |
November | 0.516577E+10 | 9459.18 | 06-NOV-13:02 | 32.42 | 19.73 | 0.00 | 0.00 | 01-NOV-00:10 | 32.42 | 19.73 |
December | 0.286314E+10 | 6868.97 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.895783E+11 | 0.00 | ||||||||
Minimum of Months | 0.226410E+10 | 5333.78 | 23.00 | 16.33 | 0.00 | 0.00 | 23.00 | 16.33 | ||
Maximum of Months | 0.130347E+11 | 14521.84 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144205E+10 | 2197.77 | 31-JAN-15:40 | 22.73 | 16.59 | 0.00 | 0.00 | 01-JAN-00:10 | 22.73 | 16.59 |
February | 0.181930E+10 | 4031.53 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.298589E+10 | 5399.40 | 27-MAR-15:20 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.388228E+10 | 5515.87 | 24-APR-14:30 | 35.00 | 18.42 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 18.42 |
May | 0.619666E+10 | 6540.71 | 22-MAY-12:03 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.666161E+10 | 6749.88 | 12-JUN-12:02 | 42.65 | 25.06 | 0.00 | 0.00 | 01-JUN-00:10 | 42.65 | 25.06 |
July | 0.715871E+10 | 7188.60 | 31-JUL-06:15 | 30.30 | 26.25 | 0.00 | 0.00 | 01-JUL-00:10 | 30.30 | 26.25 |
August | 0.766357E+10 | 6834.70 | 07-AUG-12:03 | 36.98 | 28.67 | 0.00 | 0.00 | 01-AUG-00:10 | 36.98 | 28.67 |
September | 0.631908E+10 | 7422.27 | 05-SEP-15:10 | 39.02 | 25.23 | 0.00 | 0.00 | 01-SEP-00:10 | 39.02 | 25.23 |
October | 0.542519E+10 | 6420.35 | 10-OCT-14:50 | 34.92 | 19.75 | 0.00 | 0.00 | 01-OCT-00:10 | 34.92 | 19.75 |
November | 0.370122E+10 | 5349.53 | 06-NOV-14:50 | 32.17 | 21.60 | 0.00 | 0.00 | 01-NOV-00:10 | 32.17 | 21.60 |
December | 0.199094E+10 | 3358.69 | 04-DEC-15:10 | 26.87 | 21.39 | 0.00 | 0.00 | 01-DEC-00:10 | 26.87 | 21.39 |
Annual Sum or Average | 0.552465E+11 | 0.00 | ||||||||
Minimum of Months | 0.144205E+10 | 2197.77 | 22.73 | 16.59 | 0.00 | 0.00 | 22.73 | 16.59 | ||
Maximum of Months | 0.766357E+10 | 7422.27 | 42.65 | 28.67 | 0.00 | 0.00 | 42.65 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239136E+10 | 3556.78 | 02-JAN-07:07 | 13.00 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.98 |
February | 0.260509E+10 | 4745.98 | 06-FEB-15:40 | 31.77 | 17.48 | 0.00 | 0.00 | 01-FEB-00:10 | 31.77 | 17.48 |
March | 0.375547E+10 | 7724.44 | 27-MAR-12:08 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.440556E+10 | 7463.40 | 24-APR-12:06 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.650849E+10 | 8742.80 | 22-MAY-12:06 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.694760E+10 | 9024.26 | 12-JUN-12:10 | 42.65 | 25.06 | 0.00 | 0.00 | 01-JUN-00:10 | 42.65 | 25.06 |
July | 0.730053E+10 | 9317.37 | 31-JUL-12:08 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.789519E+10 | 9064.53 | 14-AUG-12:08 | 37.95 | 26.72 | 0.00 | 0.00 | 01-AUG-00:10 | 37.95 | 26.72 |
September | 0.675672E+10 | 9372.12 | 05-SEP-12:10 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.615291E+10 | 6836.91 | 04-OCT-12:10 | 37.77 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 37.77 | 20.04 |
November | 0.477987E+10 | 5972.66 | 01-NOV-12:08 | 32.48 | 26.16 | 0.00 | 0.00 | 01-NOV-00:10 | 32.48 | 26.16 |
December | 0.300659E+10 | 4496.57 | 04-DEC-15:00 | 27.00 | 21.53 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.53 |
Annual Sum or Average | 0.625054E+11 | 0.00 | ||||||||
Minimum of Months | 0.239136E+10 | 3556.78 | 13.00 | 10.98 | 0.00 | 0.00 | 13.00 | 10.98 | ||
Maximum of Months | 0.789519E+10 | 9372.12 | 42.65 | 26.72 | 0.00 | 0.00 | 42.65 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146118E+11 | 15116.12 | 30-JAN-15:00 | 22.00 | 20.56 | 0.197841E+10 | 2606.67 | 17-JAN-10:09 | 22.00 | 20.56 |
February | 0.141335E+11 | 17924.64 | 06-FEB-07:03 | 21.25 | 17.86 | 0.179861E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.180946E+11 | 33845.23 | 27-MAR-05:12 | 21.93 | 13.41 | 0.215353E+10 | 2606.79 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.187091E+11 | 34631.10 | 03-APR-04:03 | 24.50 | 18.54 | 0.191452E+10 | 2606.82 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.234044E+11 | 34749.93 | 09-MAY-04:03 | 26.08 | 19.67 | 0.207557E+10 | 2606.76 | 08-MAY-13:30 | 26.08 | 19.67 |
June | 0.238397E+11 | 34692.99 | 06-JUN-04:03 | 25.92 | 21.78 | 0.206881E+10 | 2606.73 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.250908E+11 | 30770.59 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192132E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.263888E+11 | 31319.76 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215675E+10 | 2606.58 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.230097E+11 | 34491.73 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191641E+10 | 2606.64 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.220587E+11 | 34923.09 | 23-OCT-04:03 | 25.42 | 23.19 | 0.199304E+10 | 2606.62 | 20-OCT-09:39 | 25.42 | 23.19 |
November | 0.187539E+11 | 34667.86 | 20-NOV-05:02 | 26.00 | 18.81 | 0.197206E+10 | 2606.68 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.156113E+11 | 23852.28 | 11-DEC-06:12 | 21.80 | 19.16 | 0.191307E+10 | 2606.65 | 08-DEC-10:09 | 21.80 | 19.16 |
Annual Sum or Average | 0.243706E+12 | 0.238621E+11 | ||||||||
Minimum of Months | 0.141335E+11 | 15116.12 | 21.25 | 13.41 | 0.179861E+10 | 2606.58 | 21.80 | 18.27 | ||
Maximum of Months | 0.263888E+11 | 34923.09 | 31.98 | 23.19 | 0.215675E+10 | 2606.83 | 36.90 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133228E+11 | 14993.29 | 31-JAN-15:50 | 22.67 | 16.56 | 0.194610E+10 | 2606.65 | 24-JAN-10:00 | 22.67 | 16.56 |
February | 0.134708E+11 | 17930.11 | 06-FEB-15:50 | 31.58 | 17.52 | 0.177900E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.178858E+11 | 37134.21 | 28-MAR-05:03 | 25.67 | 14.74 | 0.214217E+10 | 2606.80 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.193097E+11 | 37322.72 | 25-APR-05:03 | 23.83 | 13.00 | 0.191085E+10 | 2606.82 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.252306E+11 | 38231.66 | 08-MAY-04:02 | 26.67 | 16.98 | 0.207627E+10 | 2606.76 | 08-MAY-13:39 | 35.50 | 23.99 |
June | 0.261276E+11 | 38202.29 | 21-JUN-04:03 | 27.33 | 24.05 | 0.206954E+10 | 2606.78 | 02-JUN-13:09 | 27.33 | 24.05 |
July | 0.280532E+11 | 34665.42 | 24-JUL-06:03 | 32.02 | 26.74 | 0.192252E+10 | 2606.84 | 03-JUL-09:09 | 32.02 | 26.74 |
August | 0.293791E+11 | 34773.57 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215766E+10 | 2606.57 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.247224E+11 | 39096.89 | 25-SEP-04:02 | 24.17 | 23.10 | 0.191717E+10 | 2606.65 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.226178E+11 | 38860.28 | 23-OCT-04:03 | 25.42 | 23.19 | 0.199278E+10 | 2606.68 | 30-OCT-09:39 | 29.67 | 20.60 |
November | 0.183103E+11 | 37597.19 | 03-NOV-05:03 | 23.83 | 22.46 | 0.196701E+10 | 2606.68 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.145809E+11 | 16709.75 | 12-DEC-15:00 | 24.00 | 16.60 | 0.189223E+10 | 2606.66 | 01-DEC-14:09 | 24.00 | 16.60 |
Annual Sum or Average | 0.253011E+12 | 0.237733E+11 | ||||||||
Minimum of Months | 0.133228E+11 | 14993.29 | 22.67 | 13.00 | 0.177900E+10 | 2606.57 | 22.67 | 16.56 | ||
Maximum of Months | 0.293791E+11 | 39096.89 | 32.02 | 26.74 | 0.215766E+10 | 2606.84 | 36.90 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283795E+10 | 4054.83 | 23-JAN-14:10 | 27.50 | 16.66 | 0.396019E+09 | 549.50 | 23-JAN-14:00 | 25.00 | 16.89 |
February | 0.313837E+10 | 5871.48 | 06-FEB-15:00 | 32.50 | 17.28 | 0.367008E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.469108E+10 | 7258.45 | 27-MAR-13:40 | 35.33 | 19.53 | 0.446779E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.582984E+10 | 14638.46 | 30-APR-13:32 | 35.03 | 22.43 | 0.402061E+09 | 549.54 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.891557E+10 | 16339.34 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438720E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.975213E+10 | 14998.89 | 11-JUN-15:32 | 36.60 | 27.14 | 0.437510E+09 | 549.53 | 02-JUN-13:09 | 36.60 | 27.14 |
July | 0.106804E+11 | 16318.45 | 30-JUL-14:22 | 42.50 | 25.87 | 0.407204E+09 | 549.55 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.110594E+11 | 16417.26 | 06-AUG-15:01 | 40.85 | 24.99 | 0.456471E+09 | 549.48 | 04-AUG-13:00 | 40.85 | 24.99 |
September | 0.859973E+10 | 16294.05 | 04-SEP-15:22 | 40.85 | 24.13 | 0.405308E+09 | 549.50 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.699962E+10 | 15975.03 | 09-OCT-11:42 | 37.67 | 19.71 | 0.420696E+09 | 549.51 | 30-OCT-09:39 | 29.67 | 20.60 |
November | 0.489192E+10 | 10090.77 | 05-NOV-15:12 | 31.80 | 21.10 | 0.413233E+09 | 549.50 | 09-NOV-10:30 | 30.45 | 21.13 |
December | 0.328034E+10 | 4615.76 | 11-DEC-14:40 | 26.97 | 18.21 | 0.390805E+09 | 549.50 | 01-DEC-14:09 | 26.97 | 18.21 |
Annual Sum or Average | 0.806763E+11 | 0.498181E+10 | ||||||||
Minimum of Months | 0.283795E+10 | 4054.83 | 26.97 | 16.66 | 0.367008E+09 | 549.48 | 25.00 | 16.89 | ||
Maximum of Months | 0.110594E+11 | 16417.26 | 42.50 | 27.14 | 0.456471E+09 | 549.55 | 42.50 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233030E+10 | 3000.23 | 24-JAN-11:00 | 24.00 | 17.69 | 0.256075E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.257002E+10 | 4133.00 | 05-FEB-10:58 | 29.00 | 18.72 | 0.235512E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.379040E+10 | 8080.27 | 26-MAR-12:53 | 35.00 | 18.29 | 0.284039E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.480706E+10 | 12646.12 | 23-APR-10:13 | 32.80 | 16.75 | 0.254916E+09 | 347.91 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.706872E+10 | 13328.37 | 07-MAY-09:52 | 36.50 | 17.98 | 0.277832E+09 | 347.90 | 04-MAY-13:00 | 36.50 | 17.98 |
June | 0.743239E+10 | 13304.99 | 18-JUN-09:22 | 35.80 | 24.87 | 0.276980E+09 | 347.89 | 02-JUN-13:09 | 35.80 | 24.87 |
July | 0.807617E+10 | 13118.15 | 30-JUL-10:22 | 43.70 | 22.01 | 0.257827E+09 | 348.01 | 31-JUL-09:39 | 39.27 | 24.03 |
August | 0.853590E+10 | 13594.04 | 06-AUG-10:22 | 38.85 | 24.36 | 0.288990E+09 | 347.97 | 02-AUG-09:50 | 38.85 | 24.36 |
September | 0.679883E+10 | 13275.80 | 03-SEP-09:42 | 36.55 | 23.50 | 0.256648E+09 | 347.88 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.562260E+10 | 13111.91 | 09-OCT-10:22 | 34.65 | 23.19 | 0.266530E+09 | 347.88 | 30-OCT-09:39 | 29.67 | 20.60 |
November | 0.394725E+10 | 8508.21 | 05-NOV-15:12 | 31.80 | 21.10 | 0.262335E+09 | 347.88 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.262111E+10 | 3431.20 | 04-DEC-11:00 | 26.00 | 20.51 | 0.250081E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.636007E+11 | 0.316777E+10 | ||||||||
Minimum of Months | 0.233030E+10 | 3000.23 | 24.00 | 16.75 | 0.235512E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.853590E+10 | 13594.04 | 43.70 | 24.87 | 0.288990E+09 | 348.01 | 39.27 | 24.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483073E+10 | 8390.45 | 22-JAN-14:33 | 26.00 | 16.51 | 0.406630E+09 | 549.51 | 23-JAN-14:50 | 25.50 | 16.89 |
February | 0.498428E+10 | 18243.41 | 05-FEB-13:32 | 31.43 | 19.44 | 0.371924E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.634699E+10 | 18029.46 | 26-MAR-12:53 | 35.00 | 18.29 | 0.447902E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.667097E+10 | 17852.51 | 30-APR-12:53 | 37.10 | 21.04 | 0.401840E+09 | 549.55 | 28-APR-13:09 | 37.10 | 21.04 |
May | 0.901523E+10 | 18034.83 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438521E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.945107E+10 | 14581.31 | 11-JUN-14:52 | 37.00 | 27.77 | 0.437319E+09 | 549.53 | 02-JUN-13:09 | 37.00 | 27.77 |
July | 0.106638E+11 | 18080.60 | 30-JUL-14:22 | 42.50 | 25.87 | 0.407044E+09 | 549.54 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.117241E+11 | 18204.52 | 06-AUG-15:01 | 40.85 | 24.99 | 0.456419E+09 | 549.48 | 04-AUG-13:00 | 40.85 | 24.99 |
September | 0.102790E+11 | 18346.20 | 04-SEP-15:22 | 40.85 | 24.13 | 0.405421E+09 | 549.67 | 05-SEP-13:00 | 40.00 | 25.05 |
October | 0.972435E+10 | 19322.99 | 09-OCT-11:42 | 37.67 | 19.71 | 0.421206E+09 | 549.81 | 02-OCT-13:00 | 37.67 | 19.71 |
November | 0.772707E+10 | 18893.48 | 05-NOV-11:52 | 34.00 | 17.15 | 0.415115E+09 | 549.51 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.551156E+10 | 18231.23 | 03-DEC-13:13 | 28.87 | 18.94 | 0.397528E+09 | 549.51 | 01-DEC-14:09 | 28.87 | 18.94 |
Annual Sum or Average | 0.969291E+11 | 0.500687E+10 | ||||||||
Minimum of Months | 0.483073E+10 | 8390.45 | 26.00 | 16.51 | 0.371924E+09 | 549.48 | 25.50 | 16.89 | ||
Maximum of Months | 0.117241E+11 | 19322.99 | 42.50 | 27.77 | 0.456419E+09 | 549.81 | 42.50 | 27.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249229E+10 | 3711.00 | 31-JAN-16:20 | 22.73 | 16.79 | 0.246219E+09 | 347.85 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.273867E+10 | 8558.86 | 05-FEB-15:32 | 32.00 | 19.08 | 0.229066E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.398378E+10 | 11791.66 | 26-MAR-16:53 | 31.20 | 18.81 | 0.280171E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.471515E+10 | 11655.83 | 30-APR-13:32 | 35.03 | 22.43 | 0.253314E+09 | 347.88 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.688163E+10 | 14477.16 | 21-MAY-15:52 | 37.50 | 23.27 | 0.277487E+09 | 347.88 | 04-MAY-13:00 | 37.50 | 23.27 |
June | 0.737727E+10 | 14081.86 | 18-JUN-16:02 | 35.98 | 27.42 | 0.276837E+09 | 347.87 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.804838E+10 | 14570.66 | 30-JUL-14:22 | 42.50 | 25.87 | 0.257624E+09 | 347.88 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.846635E+10 | 15004.26 | 06-AUG-15:41 | 40.25 | 25.55 | 0.288847E+09 | 347.84 | 04-AUG-13:00 | 40.25 | 25.55 |
September | 0.674368E+10 | 14926.69 | 04-SEP-16:02 | 40.58 | 23.84 | 0.256473E+09 | 347.86 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.557563E+10 | 14387.08 | 09-OCT-15:42 | 36.83 | 19.09 | 0.265921E+09 | 347.86 | 30-OCT-09:39 | 29.67 | 20.60 |
November | 0.401078E+10 | 14245.42 | 05-NOV-15:12 | 31.80 | 21.10 | 0.260247E+09 | 347.85 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.282358E+10 | 4433.60 | 06-DEC-15:30 | 26.85 | 20.67 | 0.243613E+09 | 347.85 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.638572E+11 | 0.313582E+10 | ||||||||
Minimum of Months | 0.249229E+10 | 3711.00 | 22.73 | 16.79 | 0.229066E+09 | 347.84 | 22.73 | 16.79 | ||
Maximum of Months | 0.846635E+10 | 15004.26 | 42.50 | 27.42 | 0.288847E+09 | 347.88 | 42.50 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320072E+10 | 4108.57 | 23-JAN-14:10 | 27.50 | 16.66 | 0.414240E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.319904E+10 | 5273.79 | 06-FEB-15:00 | 32.50 | 17.28 | 0.376947E+09 | 549.51 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.434048E+10 | 6159.13 | 27-MAR-13:10 | 35.83 | 19.71 | 0.452033E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.511967E+10 | 6561.71 | 28-APR-12:50 | 37.58 | 22.61 | 0.403262E+09 | 549.54 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.789678E+10 | 11403.76 | 08-MAY-04:02 | 26.67 | 16.98 | 0.438560E+09 | 549.53 | 04-MAY-13:00 | 26.67 | 16.98 |
June | 0.886776E+10 | 11447.13 | 16-JUN-04:02 | 28.83 | 20.58 | 0.437426E+09 | 549.51 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.994316E+10 | 14163.35 | 16-JUL-15:32 | 37.20 | 27.78 | 0.407069E+09 | 549.55 | 03-JUL-09:20 | 37.20 | 27.78 |
August | 0.109127E+11 | 13856.86 | 06-AUG-10:22 | 38.85 | 24.36 | 0.456397E+09 | 549.51 | 04-AUG-13:00 | 38.85 | 24.36 |
September | 0.888516E+10 | 14676.05 | 04-SEP-15:01 | 40.95 | 24.20 | 0.405419E+09 | 549.50 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.782136E+10 | 11378.65 | 03-OCT-04:02 | 27.42 | 23.02 | 0.421299E+09 | 549.50 | 27-OCT-13:09 | 32.00 | 22.23 |
November | 0.583769E+10 | 9471.69 | 20-NOV-05:02 | 26.00 | 18.81 | 0.416200E+09 | 549.50 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.389500E+10 | 5057.68 | 11-DEC-14:10 | 26.77 | 18.23 | 0.403086E+09 | 549.50 | 08-DEC-10:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.799196E+11 | 0.503194E+10 | ||||||||
Minimum of Months | 0.319904E+10 | 4108.57 | 26.00 | 16.66 | 0.376947E+09 | 549.50 | 25.67 | 16.66 | ||
Maximum of Months | 0.109127E+11 | 14676.05 | 40.95 | 27.78 | 0.456397E+09 | 549.55 | 38.85 | 27.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269773E+10 | 3315.40 | 24-JAN-11:00 | 24.00 | 17.69 | 0.263617E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.267926E+10 | 3834.53 | 06-FEB-14:10 | 32.08 | 17.23 | 0.239536E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.358034E+10 | 5717.33 | 27-MAR-10:50 | 37.50 | 18.71 | 0.286579E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.433204E+10 | 9633.78 | 23-APR-10:13 | 32.80 | 16.75 | 0.255645E+09 | 347.91 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.639974E+10 | 9756.80 | 29-MAY-10:42 | 37.35 | 22.00 | 0.277832E+09 | 347.90 | 04-MAY-13:00 | 37.35 | 22.00 |
June | 0.685601E+10 | 11649.41 | 04-JUN-10:43 | 36.03 | 26.08 | 0.276994E+09 | 347.89 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.762021E+10 | 11888.31 | 30-JUL-10:11 | 43.27 | 21.89 | 0.257802E+09 | 347.91 | 03-JUL-09:09 | 43.27 | 21.89 |
August | 0.849902E+10 | 12100.76 | 06-AUG-10:22 | 38.85 | 24.36 | 0.289012E+09 | 347.88 | 04-AUG-13:00 | 38.85 | 24.36 |
September | 0.705286E+10 | 12289.56 | 04-SEP-10:22 | 38.00 | 23.07 | 0.256798E+09 | 347.88 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.626215E+10 | 11596.10 | 09-OCT-10:43 | 35.55 | 20.67 | 0.266922E+09 | 347.88 | 27-OCT-13:09 | 32.00 | 22.23 |
November | 0.464853E+10 | 7569.09 | 05-NOV-11:23 | 33.15 | 17.98 | 0.263783E+09 | 347.88 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.311031E+10 | 3977.80 | 04-DEC-10:50 | 25.73 | 20.56 | 0.255574E+09 | 347.88 | 13-DEC-10:09 | 21.50 | 16.06 |
Annual Sum or Average | 0.637382E+11 | 0.319009E+10 | ||||||||
Minimum of Months | 0.267926E+10 | 3315.40 | 24.00 | 16.75 | 0.239536E+09 | 347.88 | 21.50 | 16.06 | ||
Maximum of Months | 0.849902E+10 | 12289.56 | 43.27 | 26.08 | 0.289012E+09 | 347.91 | 43.27 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478611E+10 | 10967.45 | 23-JAN-13:00 | 27.40 | 16.52 | 0.411546E+09 | 549.52 | 23-JAN-14:30 | 26.50 | 16.81 |
February | 0.496666E+10 | 13445.22 | 07-FEB-13:00 | 31.00 | 20.84 | 0.375449E+09 | 579.21 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.656043E+10 | 15733.80 | 27-MAR-12:00 | 37.30 | 19.38 | 0.450123E+09 | 694.82 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.735191E+10 | 17132.71 | 28-APR-12:00 | 42.00 | 19.18 | 0.404140E+09 | 770.61 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.109533E+11 | 16714.09 | 09-MAY-12:00 | 41.00 | 19.42 | 0.445347E+09 | 746.20 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.120294E+11 | 17603.93 | 12-JUN-12:00 | 43.00 | 24.56 | 0.446420E+09 | 786.67 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.135094E+11 | 18547.52 | 21-JUL-12:00 | 46.00 | 22.01 | 0.417218E+09 | 844.00 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.157495E+11 | 18871.46 | 16-AUG-12:00 | 46.00 | 25.38 | 0.470349E+09 | 857.03 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.135136E+11 | 17430.35 | 05-SEP-12:00 | 41.00 | 24.24 | 0.415578E+09 | 777.64 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.128508E+11 | 16622.01 | 29-OCT-13:52 | 34.00 | 19.56 | 0.428685E+09 | 719.09 | 04-OCT-12:09 | 34.00 | 19.56 |
November | 0.999334E+10 | 15938.96 | 05-NOV-11:23 | 33.15 | 17.98 | 0.418688E+09 | 635.56 | 06-NOV-13:09 | 32.42 | 19.73 |
December | 0.621276E+10 | 15860.81 | 03-DEC-13:13 | 28.87 | 18.94 | 0.401474E+09 | 554.02 | 04-DEC-13:09 | 27.83 | 21.18 |
Annual Sum or Average | 0.118477E+12 | 0.508502E+10 | ||||||||
Minimum of Months | 0.478611E+10 | 10967.45 | 27.40 | 16.52 | 0.375449E+09 | 549.52 | 26.50 | 16.81 | ||
Maximum of Months | 0.157495E+11 | 18871.46 | 46.00 | 25.38 | 0.470349E+09 | 857.03 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267967E+10 | 3638.38 | 31-JAN-16:30 | 22.80 | 16.92 | 0.261301E+09 | 347.86 | 17-JAN-10:09 | 22.80 | 16.92 |
February | 0.270468E+10 | 4917.54 | 06-FEB-15:30 | 31.95 | 17.43 | 0.238029E+09 | 347.86 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.368315E+10 | 8778.37 | 26-MAR-16:53 | 31.20 | 18.81 | 0.285872E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.418920E+10 | 8532.19 | 30-APR-17:33 | 30.33 | 25.57 | 0.255294E+09 | 347.88 | 28-APR-13:09 | 30.33 | 25.57 |
May | 0.618480E+10 | 10578.97 | 29-MAY-16:42 | 35.85 | 24.03 | 0.277699E+09 | 347.87 | 04-MAY-13:00 | 35.85 | 24.03 |
June | 0.677890E+10 | 10651.05 | 11-JUN-16:12 | 36.60 | 26.54 | 0.276958E+09 | 347.86 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.753689E+10 | 12925.25 | 16-JUL-16:12 | 36.53 | 28.17 | 0.257730E+09 | 347.88 | 03-JUL-09:20 | 36.53 | 28.17 |
August | 0.838763E+10 | 12530.57 | 06-AUG-16:21 | 40.05 | 25.93 | 0.288983E+09 | 347.86 | 04-AUG-13:00 | 40.05 | 25.93 |
September | 0.697296E+10 | 13594.21 | 04-SEP-15:41 | 40.75 | 24.06 | 0.256756E+09 | 347.85 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.616689E+10 | 12156.64 | 29-OCT-15:12 | 32.00 | 19.85 | 0.266825E+09 | 347.85 | 27-OCT-13:09 | 32.00 | 19.85 |
November | 0.462371E+10 | 10382.62 | 05-NOV-16:03 | 31.33 | 21.72 | 0.263634E+09 | 347.85 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.315571E+10 | 4390.89 | 04-DEC-15:30 | 26.60 | 21.10 | 0.254818E+09 | 347.85 | 08-DEC-10:09 | 22.75 | 18.50 |
Annual Sum or Average | 0.630642E+11 | 0.318390E+10 | ||||||||
Minimum of Months | 0.267967E+10 | 3638.38 | 22.80 | 16.92 | 0.238029E+09 | 347.85 | 22.75 | 16.92 | ||
Maximum of Months | 0.838763E+10 | 13594.21 | 40.75 | 28.17 | 0.288983E+09 | 347.88 | 40.05 | 28.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288828E+10 | 3979.30 | 23-JAN-14:10 | 27.50 | 16.66 | 0.409073E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.311929E+10 | 5499.47 | 06-FEB-15:00 | 32.50 | 17.28 | 0.374857E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.458381E+10 | 6696.32 | 27-MAR-13:10 | 35.83 | 19.71 | 0.451800E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.553085E+10 | 11292.19 | 30-APR-13:32 | 35.03 | 22.43 | 0.403549E+09 | 549.54 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.821869E+10 | 13907.45 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438823E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.892424E+10 | 12491.71 | 18-JUN-09:22 | 35.80 | 24.87 | 0.437549E+09 | 549.51 | 02-JUN-13:09 | 35.80 | 24.87 |
July | 0.960796E+10 | 13905.89 | 30-JUL-14:22 | 42.50 | 25.87 | 0.407204E+09 | 549.55 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.100016E+11 | 13744.11 | 13-AUG-16:02 | 38.67 | 26.10 | 0.456462E+09 | 549.57 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.792809E+10 | 14123.66 | 04-SEP-14:31 | 41.00 | 24.55 | 0.405363E+09 | 549.50 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.668923E+10 | 14134.45 | 09-OCT-14:32 | 37.00 | 20.60 | 0.421005E+09 | 549.49 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.485370E+10 | 7014.19 | 20-NOV-06:03 | 25.85 | 18.49 | 0.415251E+09 | 549.50 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.332421E+10 | 4543.07 | 11-DEC-14:10 | 26.77 | 18.23 | 0.399235E+09 | 549.50 | 01-DEC-14:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.756700E+11 | 0.502017E+10 | ||||||||
Minimum of Months | 0.288828E+10 | 3979.30 | 25.85 | 16.66 | 0.374857E+09 | 549.49 | 25.67 | 16.66 | ||
Maximum of Months | 0.100016E+11 | 14134.45 | 42.50 | 26.10 | 0.456462E+09 | 549.57 | 44.00 | 25.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238537E+10 | 3123.28 | 24-JAN-11:10 | 24.00 | 18.08 | 0.191845E+09 | 338.73 | 24-JAN-11:20 | 24.00 | 18.46 |
February | 0.255007E+10 | 3759.21 | 06-FEB-14:00 | 32.00 | 17.22 | 0.175517E+09 | 338.73 | 06-FEB-16:49 | 26.90 | 20.82 |
March | 0.365628E+10 | 6579.97 | 26-MAR-12:43 | 34.83 | 18.09 | 0.210645E+09 | 338.75 | 28-MAR-10:20 | 27.33 | 20.93 |
April | 0.451978E+10 | 11779.38 | 23-APR-10:43 | 32.95 | 16.56 | 0.188996E+09 | 338.74 | 28-APR-12:00 | 36.70 | 22.98 |
May | 0.649693E+10 | 12408.85 | 07-MAY-09:52 | 36.50 | 17.98 | 0.205616E+09 | 338.75 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.678195E+10 | 12335.72 | 18-JUN-09:22 | 35.80 | 24.87 | 0.204736E+09 | 338.74 | 15-JUN-07:19 | 35.80 | 24.87 |
July | 0.727052E+10 | 12172.12 | 30-JUL-09:42 | 41.80 | 21.60 | 0.191245E+09 | 339.06 | 31-JUL-10:50 | 40.82 | 24.66 |
August | 0.771565E+10 | 12310.40 | 27-AUG-09:32 | 36.00 | 26.58 | 0.213577E+09 | 339.10 | 04-AUG-10:30 | 36.00 | 26.58 |
September | 0.625114E+10 | 12643.39 | 04-SEP-09:52 | 38.00 | 23.07 | 0.190083E+09 | 338.73 | 26-SEP-07:19 | 27.40 | 17.98 |
October | 0.532659E+10 | 11996.03 | 09-OCT-11:12 | 36.67 | 19.41 | 0.197564E+09 | 338.73 | 04-OCT-07:19 | 36.67 | 19.41 |
November | 0.384286E+10 | 7311.44 | 05-NOV-11:42 | 33.72 | 17.44 | 0.194643E+09 | 338.74 | 06-NOV-08:20 | 24.33 | 20.27 |
December | 0.263768E+10 | 3526.14 | 04-DEC-10:00 | 24.40 | 20.71 | 0.186827E+09 | 338.73 | 20-DEC-13:20 | 24.30 | 20.76 |
Annual Sum or Average | 0.594348E+11 | 0.235129E+10 | ||||||||
Minimum of Months | 0.238537E+10 | 3123.28 | 24.00 | 16.56 | 0.175517E+09 | 338.73 | 24.00 | 17.98 | ||
Maximum of Months | 0.771565E+10 | 12643.39 | 41.80 | 26.58 | 0.213577E+09 | 339.10 | 40.82 | 26.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499667E+10 | 7666.35 | 23-JAN-13:30 | 27.70 | 16.54 | 0.414507E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.499410E+10 | 16035.77 | 05-FEB-13:43 | 31.52 | 19.39 | 0.377288E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.620164E+10 | 15752.27 | 26-MAR-12:43 | 34.83 | 18.09 | 0.452367E+09 | 549.68 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.631850E+10 | 15544.50 | 30-APR-12:53 | 37.10 | 21.04 | 0.403581E+09 | 549.55 | 28-APR-13:09 | 37.10 | 21.04 |
May | 0.830453E+10 | 15554.01 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438677E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.863206E+10 | 13333.68 | 09-JUN-04:02 | 32.50 | 27.09 | 0.437363E+09 | 549.51 | 02-JUN-13:09 | 32.50 | 27.09 |
July | 0.957325E+10 | 15611.29 | 30-JUL-14:22 | 42.50 | 25.87 | 0.407071E+09 | 549.54 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.106130E+11 | 15471.99 | 13-AUG-14:02 | 40.00 | 25.61 | 0.456442E+09 | 549.62 | 30-AUG-13:30 | 39.80 | 28.02 |
September | 0.952521E+10 | 16364.62 | 04-SEP-11:12 | 39.00 | 23.19 | 0.405501E+09 | 549.75 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.932056E+10 | 17137.05 | 09-OCT-13:12 | 37.40 | 20.06 | 0.421510E+09 | 549.82 | 20-OCT-13:00 | 34.00 | 18.77 |
November | 0.762894E+10 | 16506.84 | 12-NOV-13:32 | 29.77 | 18.86 | 0.416410E+09 | 549.88 | 13-NOV-14:50 | 33.00 | 18.21 |
December | 0.563210E+10 | 15976.71 | 25-DEC-13:13 | 27.33 | 17.20 | 0.402589E+09 | 549.51 | 01-DEC-14:09 | 27.33 | 17.20 |
Annual Sum or Average | 0.917406E+11 | 0.503330E+10 | ||||||||
Minimum of Months | 0.499410E+10 | 7666.35 | 27.33 | 16.54 | 0.377288E+09 | 549.51 | 24.00 | 17.20 | ||
Maximum of Months | 0.106130E+11 | 17137.05 | 42.50 | 27.09 | 0.456442E+09 | 549.88 | 42.50 | 28.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251251E+10 | 3661.25 | 31-JAN-16:20 | 22.73 | 16.79 | 0.255255E+09 | 347.85 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.269543E+10 | 5684.95 | 05-FEB-16:23 | 31.50 | 18.69 | 0.235013E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.386000E+10 | 10935.54 | 26-MAR-16:42 | 31.30 | 18.77 | 0.284514E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.446165E+10 | 12969.78 | 23-APR-16:42 | 31.25 | 19.17 | 0.254958E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.638344E+10 | 12823.34 | 21-MAY-15:52 | 37.50 | 23.27 | 0.277669E+09 | 347.88 | 04-MAY-13:00 | 37.50 | 23.27 |
June | 0.679307E+10 | 12455.88 | 18-JUN-16:02 | 35.98 | 27.42 | 0.276891E+09 | 347.86 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.728683E+10 | 12870.82 | 23-JUL-16:02 | 38.50 | 26.05 | 0.257685E+09 | 347.88 | 03-JUL-09:09 | 38.50 | 26.05 |
August | 0.770416E+10 | 12977.12 | 13-AUG-16:02 | 38.67 | 26.10 | 0.288902E+09 | 347.84 | 04-AUG-13:00 | 38.67 | 26.10 |
September | 0.625525E+10 | 13411.26 | 04-SEP-15:51 | 40.70 | 24.03 | 0.256557E+09 | 347.85 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.533156E+10 | 13569.84 | 09-OCT-15:12 | 36.93 | 20.06 | 0.266372E+09 | 347.85 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.392685E+10 | 12640.29 | 05-NOV-15:02 | 31.90 | 20.93 | 0.262343E+09 | 347.86 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.281237E+10 | 4298.04 | 06-DEC-15:30 | 26.85 | 20.67 | 0.250303E+09 | 347.85 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.600231E+11 | 0.316646E+10 | ||||||||
Minimum of Months | 0.251251E+10 | 3661.25 | 22.73 | 16.79 | 0.235013E+09 | 347.84 | 22.73 | 16.79 | ||
Maximum of Months | 0.770416E+10 | 13569.84 | 40.70 | 27.42 | 0.288902E+09 | 347.88 | 38.67 | 27.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342103E+09 | 3583.52 | 03-JAN-06:03 | 12.93 |
February | 0.203617E+09 | 3386.10 | 13-FEB-06:03 | 13.03 |
March | 0.155689E+09 | 4765.33 | 28-MAR-05:03 | 25.67 |
April | 53555210.65 | 4887.68 | 25-APR-05:03 | 23.83 |
May | 21080381.69 | 5212.17 | 08-MAY-04:02 | 26.67 |
June | 15682293.10 | 3558.01 | 02-JUN-04:03 | 28.33 |
July | 7186172.09 | 2656.44 | 06-JUL-04:02 | 29.17 |
August | 4980953.72 | 3120.16 | 31-AUG-04:02 | 28.83 |
September | 16340675.07 | 4784.40 | 25-SEP-04:02 | 24.17 |
October | 25366087.77 | 4873.95 | 02-OCT-04:02 | 27.05 |
November | 49795215.78 | 4038.43 | 01-NOV-05:03 | 23.83 |
December | 0.217152E+09 | 3357.15 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.111255E+10 | |||
Minimum of Months | 4980953.72 | 2656.44 | 12.93 | |
Maximum of Months | 0.342103E+09 | 5212.17 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20415131.81 | 2603.11 | 01-JAN-13:30 | 22.65 |
February | 13738301.83 | 2365.26 | 19-FEB-11:13 | 24.93 |
March | 9888822.59 | 2075.71 | 02-MAR-05:03 | 29.08 |
April | 10981898.09 | 1862.92 | 17-APR-04:03 | 24.33 |
May | 15491607.22 | 3051.75 | 12-MAY-04:02 | 28.67 |
June | 17044268.30 | 2940.77 | 16-JUN-04:02 | 28.83 |
July | 27748271.79 | 3233.29 | 27-JUL-04:02 | 30.33 |
August | 24772886.41 | 3415.08 | 25-AUG-04:02 | 31.17 |
September | 19543684.55 | 3079.65 | 07-SEP-04:02 | 30.08 |
October | 18576488.27 | 2566.06 | 05-OCT-04:02 | 27.83 |
November | 16678795.91 | 2201.74 | 20-NOV-05:02 | 26.00 |
December | 19954448.95 | 2602.96 | 25-DEC-12:32 | 26.67 |
Annual Sum or Average | 0.214835E+09 | |||
Minimum of Months | 9888822.59 | 1862.92 | 22.65 | |
Maximum of Months | 27748271.79 | 3415.08 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32087819.11 | 2530.64 | 01-JAN-12:43 | 22.08 |
February | 19235863.27 | 2233.91 | 19-FEB-11:13 | 24.93 |
March | 14232550.08 | 3299.36 | 02-MAR-05:03 | 29.08 |
April | 12732514.98 | 3050.95 | 25-APR-04:53 | 24.00 |
May | 17277974.91 | 3932.54 | 23-MAY-04:02 | 31.17 |
June | 19799210.21 | 3764.91 | 16-JUN-04:02 | 28.83 |
July | 37456141.13 | 4090.54 | 13-JUL-04:02 | 30.58 |
August | 42863735.71 | 4082.92 | 31-AUG-04:02 | 28.83 |
September | 33514205.38 | 4594.87 | 28-SEP-04:02 | 27.75 |
October | 32619618.78 | 4532.97 | 05-OCT-04:02 | 27.83 |
November | 27227768.64 | 4202.88 | 20-NOV-05:02 | 26.00 |
December | 28585066.68 | 2494.94 | 31-DEC-10:53 | 24.00 |
Annual Sum or Average | 0.317632E+09 | |||
Minimum of Months | 12732514.98 | 2233.91 | 22.08 | |
Maximum of Months | 42863735.71 | 4594.87 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58480.81 | 292.40 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 58480.81 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 58480.81 | 292.40 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 274962.21 | 758.47 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 274962.21 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 274962.21 | 758.47 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 664438.37 | 1454.50 | 03-JAN-07:03 | 12.67 |
February | 35773.06 | 298.11 | 13-FEB-07:02 | 13.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 700211.42 | |||
Minimum of Months | 0.00 | 0.00 | 12.67 | |
Maximum of Months | 664438.37 | 1454.50 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154671E+09 | 4701.34 | 04-JAN-07:20 | 13.80 |
February | 96162353.11 | 4691.58 | 02-FEB-07:08 | 14.42 |
March | 26869419.99 | 4494.97 | 16-MAR-06:06 | 15.00 |
April | 6201.28 | 51.68 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 23067617.74 | 4061.17 | 18-DEC-07:05 | 14.00 |
Annual Sum or Average | 0.300776E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.80 | |
Maximum of Months | 0.154671E+09 | 4701.34 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787026E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.682380E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.788076E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.678723E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708602E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.698713E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.665518E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747497E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682664E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.734146E+09 | 947.97 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.763127E+09 | 1184.79 | 08-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.775536E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.871201E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.665518E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788076E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485772E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427823E+09 | 750.07 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495128E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429520E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452909E+09 | 450.21 | 18-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447766E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.424337E+09 | 490.21 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474582E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431992E+09 | 450.21 | 19-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458896E+09 | 450.21 | 02-OCT-15:50 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477595E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.477629E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548395E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.424337E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.495128E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738511E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.659399E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.778373E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679878E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719844E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.711281E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.674661E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751641E+09 | 774.31 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680242E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716166E+09 | 774.31 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.722577E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720436E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855301E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.659399E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.778373E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481316E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424537E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500668E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.435037E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.456658E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450024E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.428707E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479795E+09 | 600.10 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435543E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464360E+09 | 750.02 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.465858E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.468468E+09 | 750.02 | 11-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549097E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424537E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500668E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.781088E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.679681E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.785391E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.677181E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707980E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.697534E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.664648E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.746365E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.681454E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.731860E+09 | 947.97 | 10-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.759199E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.770176E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.868256E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664648E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.785391E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484147E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.426697E+09 | 750.07 | 09-FEB-16:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.493820E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.428823E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452169E+09 | 450.21 | 18-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447039E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.423447E+09 | 490.21 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474000E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431316E+09 | 450.21 | 25-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.457901E+09 | 450.21 | 02-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.475929E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475933E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547122E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423447E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.493820E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737862E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.658042E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.776386E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679100E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.718416E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.710191E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.673002E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.750477E+09 | 711.15 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.679205E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.715173E+09 | 774.31 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721622E+09 | 1121.62 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.718992E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853847E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.658042E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.776386E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479519E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.423402E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.499474E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.433580E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455736E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.448938E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.427582E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478537E+09 | 600.10 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434668E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463011E+09 | 750.02 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.464801E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466829E+09 | 750.02 | 14-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547608E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.423402E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.499474E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787026E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.682380E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.788076E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.678723E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708602E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.698713E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.665518E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747497E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682664E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.734146E+09 | 947.97 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.763127E+09 | 1184.79 | 08-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.775536E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.871201E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.665518E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788076E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485772E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427823E+09 | 750.07 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495128E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429520E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452909E+09 | 450.21 | 18-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447763E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.424329E+09 | 490.21 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474582E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431992E+09 | 450.21 | 19-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458896E+09 | 450.21 | 02-OCT-15:50 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477595E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.477629E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548394E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.424329E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.495128E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738511E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.659399E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.778367E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679878E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719844E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.711277E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.674661E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751641E+09 | 774.31 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680242E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716166E+09 | 774.31 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.722577E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720436E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855300E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.659399E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.778367E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481316E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424537E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500668E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.435037E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.456658E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450024E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.428707E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479795E+09 | 600.10 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435543E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464360E+09 | 750.02 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.465858E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.468468E+09 | 750.02 | 11-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549097E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424537E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500668E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787026E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952004.51 | 0.151193E+09 |
February | 0.901968E+09 | 0.682380E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18275283.30 | 0.152844E+09 |
March | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43920565.81 | 85110284.97 |
April | 0.956342E+09 | 0.678723E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105250E+09 | 39713085.94 |
May | 0.103597E+10 | 0.708602E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255166E+09 | 4633510.32 |
June | 0.103308E+10 | 0.698713E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317918E+09 | 433809.98 |
July | 0.959235E+09 | 0.665518E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456238E+09 | 0.00 |
August | 0.107774E+10 | 0.747497E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436699E+09 | 0.00 |
September | 0.956342E+09 | 0.682664E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306214E+09 | 674782.02 |
October | 0.994195E+09 | 0.734146E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175549E+09 | 6489787.71 |
November | 0.984487E+09 | 0.763127E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75437488.46 | 40597412.35 |
December | 0.959235E+09 | 0.775536E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13021790.62 | 0.110027E+09 |
Annual Sum or Average | 0.119305E+11 | 0.871201E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220664E+10 | 0.591717E+09 |
Minimum of Months | 0.901968E+09 | 0.665518E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952004.51 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456238E+09 | 0.152844E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.485772E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339206.20 | 0.105361E+09 |
February | 0.571020E+09 | 0.427823E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10999130.30 | 0.105012E+09 |
March | 0.682301E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28682769.72 | 58292818.31 |
April | 0.605444E+09 | 0.429520E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68142087.98 | 27055703.56 |
May | 0.655854E+09 | 0.452909E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169714E+09 | 3186068.33 |
June | 0.654023E+09 | 0.447766E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212520E+09 | 303509.44 |
July | 0.607275E+09 | 0.424337E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305356E+09 | 0.00 |
August | 0.682301E+09 | 0.474582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291920E+09 | 0.00 |
September | 0.605444E+09 | 0.431992E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203575E+09 | 464102.04 |
October | 0.629407E+09 | 0.458896E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115620E+09 | 4669490.61 |
November | 0.623262E+09 | 0.477595E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48284331.05 | 28583583.21 |
December | 0.607275E+09 | 0.477629E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8031833.81 | 75181553.82 |
Annual Sum or Average | 0.755301E+10 | 0.548395E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146418E+10 | 0.408110E+09 |
Minimum of Months | 0.571020E+09 | 0.424337E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339206.20 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305356E+09 | 0.105361E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738511E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009110.05 | 0.175253E+09 |
February | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14936309.94 | 0.168688E+09 |
March | 0.107774E+10 | 0.778373E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41760238.46 | 91817730.92 |
April | 0.956342E+09 | 0.679878E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102728E+09 | 40523764.14 |
May | 0.103597E+10 | 0.719844E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256787E+09 | 4607338.96 |
June | 0.103308E+10 | 0.711281E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320583E+09 | 412025.51 |
July | 0.959235E+09 | 0.674661E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459721E+09 | 0.00 |
August | 0.107774E+10 | 0.751641E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438148E+09 | 0.00 |
September | 0.956342E+09 | 0.680242E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304020E+09 | 718959.05 |
October | 0.994195E+09 | 0.716166E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169178E+09 | 7618409.79 |
November | 0.984487E+09 | 0.722577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64444185.54 | 46047495.42 |
December | 0.959235E+09 | 0.720436E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8782844.50 | 0.127027E+09 |
Annual Sum or Average | 0.119305E+11 | 0.855301E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218210E+10 | 0.662714E+09 |
Minimum of Months | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009110.05 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.778373E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459721E+09 | 0.175253E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481316E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727835.51 | 0.104396E+09 |
February | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11891156.26 | 0.104797E+09 |
March | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28771978.03 | 59818119.11 |
April | 0.605404E+09 | 0.435037E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68539079.71 | 27792032.66 |
May | 0.655811E+09 | 0.456658E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169813E+09 | 3260630.80 |
June | 0.653980E+09 | 0.450024E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212062E+09 | 308603.44 |
July | 0.607235E+09 | 0.428707E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306618E+09 | 0.00 |
August | 0.682256E+09 | 0.479795E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292814E+09 | 0.00 |
September | 0.605404E+09 | 0.435543E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203270E+09 | 465114.59 |
October | 0.629366E+09 | 0.464360E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115428E+09 | 4683633.97 |
November | 0.623221E+09 | 0.465858E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48247283.89 | 28007267.10 |
December | 0.607235E+09 | 0.468468E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8172892.08 | 75311445.46 |
Annual Sum or Average | 0.755252E+10 | 0.549097E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146736E+10 | 0.408840E+09 |
Minimum of Months | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727835.51 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306618E+09 | 0.104797E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.781088E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339367.66 | 97406519.18 |
February | 0.901968E+09 | 0.679681E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9929395.60 | 93678943.68 |
March | 0.107774E+10 | 0.785391E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24081217.59 | 49351621.70 |
April | 0.956342E+09 | 0.677181E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58741557.96 | 21682123.94 |
May | 0.103597E+10 | 0.707980E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139150E+09 | 2319615.06 |
June | 0.103308E+10 | 0.697534E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172059E+09 | 197162.53 |
July | 0.959235E+09 | 0.664648E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245351E+09 | 0.00 |
August | 0.107774E+10 | 0.746365E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234787E+09 | 0.00 |
September | 0.956342E+09 | 0.681454E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164926E+09 | 387104.10 |
October | 0.994195E+09 | 0.731860E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93766743.26 | 4339012.94 |
November | 0.984487E+09 | 0.759199E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39619959.50 | 27841067.89 |
December | 0.959235E+09 | 0.770176E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6366694.47 | 73735545.12 |
Annual Sum or Average | 0.119305E+11 | 0.868256E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119012E+10 | 0.370939E+09 |
Minimum of Months | 0.901968E+09 | 0.664648E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339367.66 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.785391E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245351E+09 | 97406519.18 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.484147E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604132.70 | 67814280.48 |
February | 0.571020E+09 | 0.426697E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5983385.62 | 64867062.47 |
March | 0.682301E+09 | 0.493820E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15544470.57 | 34241565.14 |
April | 0.605444E+09 | 0.428823E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37293031.86 | 15334713.66 |
May | 0.655854E+09 | 0.452169E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91520767.78 | 1749179.00 |
June | 0.654023E+09 | 0.447039E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114193E+09 | 155332.96 |
July | 0.607275E+09 | 0.423447E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163322E+09 | 0.00 |
August | 0.682301E+09 | 0.474000E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156208E+09 | 0.00 |
September | 0.605444E+09 | 0.431316E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108908E+09 | 290220.24 |
October | 0.629407E+09 | 0.457901E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61351754.94 | 3268190.31 |
November | 0.623262E+09 | 0.475929E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25157465.62 | 19914096.50 |
December | 0.607275E+09 | 0.475933E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992582.78 | 50591376.29 |
Annual Sum or Average | 0.755301E+10 | 0.547122E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784079E+09 | 0.258226E+09 |
Minimum of Months | 0.571020E+09 | 0.423447E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604132.70 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.493820E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163322E+09 | 67814280.48 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737862E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21721369.96 | 0.150846E+10 |
February | 0.901968E+09 | 0.658042E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258664E+09 | 0.932858E+09 |
March | 0.107774E+10 | 0.776386E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893373E+09 | 0.590213E+09 |
April | 0.956342E+09 | 0.679100E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166186E+10 | 0.208513E+09 |
May | 0.103597E+10 | 0.718416E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344508E+10 | 34598638.96 |
June | 0.103308E+10 | 0.710191E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405437E+10 | 1262484.85 |
July | 0.959235E+09 | 0.673002E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430908E+10 | 0.00 |
August | 0.107774E+10 | 0.750477E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495629E+10 | 0.00 |
September | 0.956342E+09 | 0.679205E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344757E+10 | 3054190.15 |
October | 0.994195E+09 | 0.715173E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249205E+10 | 27252819.32 |
November | 0.984487E+09 | 0.721622E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133236E+10 | 0.310444E+09 |
December | 0.959235E+09 | 0.718992E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204902E+09 | 0.877418E+09 |
Annual Sum or Average | 0.119305E+11 | 0.853847E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270773E+11 | 0.449408E+10 |
Minimum of Months | 0.901968E+09 | 0.658042E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21721369.96 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.776386E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495629E+10 | 0.150846E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.479519E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774454.49 | 67890859.27 |
February | 0.570983E+09 | 0.423402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6252759.60 | 65439713.71 |
March | 0.682256E+09 | 0.499474E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15320649.78 | 35706541.00 |
April | 0.605404E+09 | 0.433580E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37016549.66 | 15865218.68 |
May | 0.655811E+09 | 0.455736E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91155594.49 | 1835245.88 |
June | 0.653980E+09 | 0.448938E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113163E+09 | 169137.77 |
July | 0.607235E+09 | 0.427582E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162894E+09 | 0.00 |
August | 0.682256E+09 | 0.478537E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155820E+09 | 0.00 |
September | 0.605404E+09 | 0.434668E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108198E+09 | 303169.63 |
October | 0.629366E+09 | 0.463011E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60828979.73 | 3363662.74 |
November | 0.623221E+09 | 0.464801E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24880201.60 | 19970308.18 |
December | 0.607235E+09 | 0.466829E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3940048.53 | 51171212.43 |
Annual Sum or Average | 0.755252E+10 | 0.547608E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780244E+09 | 0.261715E+09 |
Minimum of Months | 0.570983E+09 | 0.423402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774454.49 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.499474E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162894E+09 | 67890859.27 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787026E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2238170.72 | 0.141615E+09 |
February | 0.901968E+09 | 0.682380E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15136148.58 | 0.140544E+09 |
March | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36561304.12 | 77663654.57 |
April | 0.956342E+09 | 0.678723E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88494987.07 | 35674179.34 |
May | 0.103597E+10 | 0.708602E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213712E+09 | 4040641.01 |
June | 0.103308E+10 | 0.698713E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265588E+09 | 364497.75 |
July | 0.959235E+09 | 0.665518E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379660E+09 | 0.00 |
August | 0.107774E+10 | 0.747497E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363578E+09 | 0.00 |
September | 0.956342E+09 | 0.682664E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255726E+09 | 592143.60 |
October | 0.994195E+09 | 0.734146E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146587E+09 | 5886224.48 |
November | 0.984487E+09 | 0.763127E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62529424.74 | 38321210.78 |
December | 0.959235E+09 | 0.775536E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10276961.99 | 0.103393E+09 |
Annual Sum or Average | 0.119305E+11 | 0.871201E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184009E+10 | 0.548094E+09 |
Minimum of Months | 0.901968E+09 | 0.665518E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2238170.72 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379660E+09 | 0.141615E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.485772E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111911.68 | 97000976.30 |
February | 0.421807E+09 | 0.427823E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9228489.21 | 95343154.30 |
March | 0.502994E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23946143.10 | 52486747.92 |
April | 0.447140E+09 | 0.429520E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57524270.74 | 24151548.99 |
May | 0.484071E+09 | 0.452909E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142468E+09 | 2749059.13 |
June | 0.482240E+09 | 0.447763E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177920E+09 | 248627.40 |
July | 0.448971E+09 | 0.424329E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254546E+09 | 0.00 |
August | 0.502994E+09 | 0.474582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243422E+09 | 0.00 |
September | 0.447140E+09 | 0.431992E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170357E+09 | 399540.55 |
October | 0.465148E+09 | 0.458896E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96936944.38 | 4130458.36 |
November | 0.460569E+09 | 0.477595E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40272574.47 | 26548617.18 |
December | 0.448971E+09 | 0.477629E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6526639.27 | 69712793.03 |
Annual Sum or Average | 0.557719E+10 | 0.548394E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122426E+10 | 0.372772E+09 |
Minimum of Months | 0.421807E+09 | 0.424329E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111911.68 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254546E+09 | 97000976.30 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738511E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 815107.89 | 0.159800E+09 |
February | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12394380.48 | 0.152697E+09 |
March | 0.107774E+10 | 0.778367E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34752332.95 | 83076041.08 |
April | 0.956342E+09 | 0.679878E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86058642.06 | 36382879.93 |
May | 0.103597E+10 | 0.719844E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215084E+09 | 4021882.98 |
June | 0.103308E+10 | 0.711277E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267851E+09 | 343385.78 |
July | 0.959235E+09 | 0.674661E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382347E+09 | 0.00 |
August | 0.107774E+10 | 0.751641E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364515E+09 | 0.00 |
September | 0.956342E+09 | 0.680242E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253657E+09 | 629154.51 |
October | 0.994195E+09 | 0.716166E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141114E+09 | 6796578.85 |
November | 0.984487E+09 | 0.722577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53660836.50 | 42740080.05 |
December | 0.959235E+09 | 0.720436E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7273041.44 | 0.116413E+09 |
Annual Sum or Average | 0.119305E+11 | 0.855300E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181952E+10 | 0.602899E+09 |
Minimum of Months | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 815107.89 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.778367E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382347E+09 | 0.159800E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481316E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1352065.11 | 97038804.90 |
February | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9751460.96 | 95966640.28 |
March | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23748701.05 | 54340329.51 |
April | 0.605404E+09 | 0.435037E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57180750.36 | 24985875.98 |
May | 0.655811E+09 | 0.456658E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141986E+09 | 2848128.90 |
June | 0.653980E+09 | 0.450024E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176771E+09 | 255196.75 |
July | 0.607235E+09 | 0.428707E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254286E+09 | 0.00 |
August | 0.682256E+09 | 0.479795E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243067E+09 | 0.00 |
September | 0.605404E+09 | 0.435543E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169332E+09 | 408387.66 |
October | 0.629366E+09 | 0.464360E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96176536.35 | 4193004.48 |
November | 0.623221E+09 | 0.465858E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39792390.59 | 26440735.87 |
December | 0.607235E+09 | 0.468468E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6431594.34 | 70545593.77 |
Annual Sum or Average | 0.755252E+10 | 0.549097E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121988E+10 | 0.377023E+09 |
Minimum of Months | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1352065.11 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254286E+09 | 97038804.90 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350170.28 | 0.214662E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16314578.59 | 0.207417E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39915578.35 | 0.112723E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103257E+09 | 48470802.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263808E+09 | 4757416.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330682E+09 | 443782.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475598E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451365E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315325E+09 | 705505.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174248E+09 | 8253851.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66342124.48 | 55275460.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8970680.55 | 0.157095E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224718E+10 | 0.809803E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350170.28 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475598E+09 | 0.214662E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2950902.93 | 0.251165E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22653883.05 | 0.249475E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52775807.31 | 0.136841E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134165E+09 | 60825955.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337624E+09 | 6170839.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424114E+09 | 572826.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610428E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580764E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405817E+09 | 921060.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226212E+09 | 9833612.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89450357.96 | 66025345.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13572678.70 | 0.184233E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290053E+10 | 0.966064E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2950902.93 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610428E+09 | 0.251165E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960405.75 | 0.244082E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19037501.34 | 0.239620E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51335986.84 | 0.132268E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122605E+09 | 50741777.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347210E+09 | 4341114.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449658E+09 | 431839.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645883E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620411E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428415E+09 | 609000.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238394E+09 | 5922654.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87285644.74 | 50125955.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9284237.46 | 0.170573E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302048E+10 | 0.898715E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960405.75 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645883E+09 | 0.244082E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.49 | 29-JAN-12:00 | 387.40 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 401.87 | 05-FEB-14:40 | 333.81 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 338.22 | 26-MAR-14:00 | 340.73 | 05-MAR-15:10 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.34 | 30-APR-12:58 | 230.49 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.70 | 21-MAY-13:00 | 82.92 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 658.15 | 11-JUN-14:54 | 59.92 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.68 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.19 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.00 | 03-SEP-15:58 | 60.46 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 621.83 | 09-OCT-15:05 | 113.10 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 08-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.59 | 19-NOV-13:53 | 185.63 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.15 | 10-DEC-12:00 | 262.43 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 179.49 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.70 | 387.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 | 29-JAN-12:00 | 257.63 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.28 | 05-FEB-15:00 | 223.66 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.78 | 26-MAR-14:20 | 233.55 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.33 | 30-APR-12:58 | 153.66 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 18-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.47 | 21-MAY-13:00 | 55.56 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.55 | 11-JUN-14:56 | 39.59 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 671.63 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.07 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 19-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.32 | 03-SEP-15:44 | 40.11 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 450.21 | 02-OCT-15:50 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.87 | 09-OCT-15:05 | 75.59 | 20-OCT-04:50 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.74 | 19-NOV-14:00 | 122.75 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 | 10-DEC-12:40 | 172.28 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 | 0.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.47 | 257.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.33 | 29-JAN-12:00 | 403.48 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 379.83 | 05-FEB-14:58 | 347.04 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.22 | 26-MAR-13:53 | 389.91 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.72 | 30-APR-12:58 | 233.19 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.70 | 21-MAY-13:00 | 83.55 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.44 | 11-JUN-14:56 | 59.50 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.68 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 935.56 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.00 | 03-SEP-15:58 | 61.30 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.44 | 09-OCT-15:05 | 116.66 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.26 | 19-NOV-13:53 | 188.95 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.46 | 10-DEC-12:00 | 262.47 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 67.33 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.70 | 403.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 29-JAN-12:00 | 258.69 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 259.79 | 05-FEB-15:00 | 224.92 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.21 | 26-MAR-13:53 | 249.96 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.87 | 30-APR-12:58 | 157.14 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.46 | 21-MAY-13:00 | 56.21 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.81 | 11-JUN-12:58 | 40.17 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.78 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.25 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 03-SEP-15:58 | 40.00 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.17 | 09-OCT-15:03 | 76.86 | 20-OCT-04:40 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.34 | 19-NOV-13:53 | 123.61 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 11-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.76 | 10-DEC-12:20 | 171.42 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.46 | 258.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 29-JAN-12:00 | 256.38 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 235.36 | 05-FEB-15:00 | 207.57 | 10-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.35 | 26-MAR-14:00 | 181.65 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.18 | 30-APR-13:00 | 131.01 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.22 | 21-MAY-13:00 | 43.03 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.86 | 11-JUN-13:10 | 26.99 | 07-JUN-04:45 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.72 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.94 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.78 | 03-SEP-15:44 | 36.74 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 10-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.65 | 09-OCT-15:28 | 76.97 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.42 | 19-NOV-14:00 | 122.25 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.02 | 10-DEC-12:20 | 169.72 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.22 | 256.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.66 | 29-JAN-12:00 | 175.76 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 09-FEB-16:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.93 | 05-FEB-15:00 | 140.78 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.40 | 26-MAR-14:00 | 120.77 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.72 | 30-APR-12:58 | 89.17 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 18-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 947.81 | 21-MAY-13:00 | 30.09 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.04 | 11-JUN-14:56 | 18.63 | 07-JUN-04:45 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.20 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.66 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 25-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.99 | 03-SEP-15:44 | 25.68 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 450.21 | 02-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.03 | 09-OCT-15:28 | 53.66 | 20-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.15 | 19-NOV-14:00 | 81.97 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 | 10-DEC-13:00 | 112.24 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.66 | 0.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 947.81 | 175.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.29 | 23-JAN-13:00 | 12127.17 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7533.07 | 07-FEB-13:00 | 10696.07 | 13-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15827.25 | 27-MAR-11:01 | 8766.20 | 07-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18470.75 | 28-APR-11:01 | 6646.23 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18232.62 | 09-MAY-11:01 | 4113.56 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20315.54 | 12-JUN-11:01 | 541.51 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23338.71 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22679.88 | 16-AUG-11:01 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17809.88 | 12-SEP-11:01 | 1054.92 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14198.87 | 04-OCT-11:01 | 2698.85 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1121.62 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9279.49 | 01-NOV-11:02 | 7636.90 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5000.78 | 01-DEC-12:10 | 11395.08 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.29 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23338.71 | 12127.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.36 | 29-JAN-12:00 | 175.92 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 | 05-FEB-15:00 | 142.59 | 10-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.13 | 26-MAR-13:53 | 130.10 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.66 | 30-APR-13:00 | 91.43 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 958.82 | 21-MAY-13:00 | 30.59 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.42 | 11-JUN-13:10 | 19.48 | 07-JUN-04:45 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.68 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.59 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.88 | 03-SEP-16:00 | 25.96 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.73 | 09-OCT-15:25 | 54.72 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.60 | 19-NOV-14:00 | 82.93 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.19 | 10-DEC-12:20 | 112.14 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 58.36 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 958.82 | 175.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.18 | 29-JAN-12:00 | 365.87 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.52 | 05-FEB-14:50 | 307.66 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 | 26-MAR-13:53 | 284.27 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.55 | 30-APR-12:58 | 204.63 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.23 | 21-MAY-13:00 | 71.28 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 548.47 | 11-JUN-14:54 | 51.70 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.58 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 785.05 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.58 | 03-SEP-15:54 | 52.96 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.13 | 09-OCT-15:15 | 103.38 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 08-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.10 | 19-NOV-14:00 | 172.06 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.31 | 10-DEC-13:00 | 240.33 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 138.18 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.23 | 365.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 29-JAN-12:00 | 242.58 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.11 | 05-FEB-15:17 | 205.73 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.56 | 26-MAR-14:10 | 194.45 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.74 | 30-APR-12:58 | 136.21 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 18-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.82 | 21-MAY-13:00 | 47.76 | 01-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.31 | 11-JUN-14:56 | 33.93 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 490.21 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 564.12 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 526.05 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 805.43 | 01-SEP-07:10 | 450.21 | 19-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.09 | 03-SEP-15:56 | 34.96 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 450.21 | 02-OCT-15:50 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.14 | 09-OCT-15:15 | 68.85 | 20-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.61 | 19-NOV-14:00 | 113.63 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.92 | 10-DEC-13:00 | 157.72 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 0.00 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.82 | 242.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 23-JAN-13:00 | 378.34 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.97 | 05-FEB-14:25 | 318.46 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.33 | 26-MAR-14:04 | 322.50 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.84 | 30-APR-12:55 | 206.88 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.22 | 21-MAY-13:00 | 71.91 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.79 | 11-JUN-14:56 | 51.31 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 832.38 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.60 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.37 | 03-SEP-15:54 | 53.69 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.92 | 09-OCT-15:15 | 106.37 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.42 | 19-NOV-13:53 | 174.60 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.86 | 10-DEC-12:10 | 240.33 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.22 | 378.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.26 | 29-JAN-12:00 | 244.04 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 214.25 | 05-FEB-12:43 | 206.92 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 | 26-MAR-13:53 | 208.10 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.05 | 30-APR-12:58 | 139.32 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.81 | 21-MAY-13:00 | 48.53 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.69 | 11-JUN-12:58 | 34.64 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.96 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.59 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.92 | 03-SEP-15:54 | 35.15 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.33 | 09-OCT-15:15 | 69.91 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.09 | 19-NOV-13:53 | 114.51 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 11-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 | 10-DEC-12:20 | 157.61 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 108.26 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.81 | 244.04 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.46 | 29-JAN-12:00 | 547.47 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.35 | 05-FEB-15:00 | 452.62 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.08 | 26-MAR-14:00 | 403.65 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.86 | 30-APR-13:00 | 286.31 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2745.91 | 21-MAY-13:00 | 90.97 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.94 | 11-JUN-13:20 | 65.71 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.07 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.50 | 13-AUG-13:51 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.20 | 03-SEP-16:00 | 68.54 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.97 | 09-OCT-15:00 | 141.87 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.44 | 19-NOV-14:00 | 250.99 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 10-DEC-12:00 | 351.00 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2745.91 | 547.47 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.35 | 29-JAN-11:55 | 648.18 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.95 | 05-FEB-14:53 | 551.27 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.63 | 26-MAR-13:53 | 493.70 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.63 | 30-APR-13:00 | 361.37 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.22 | 21-MAY-13:00 | 119.04 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.76 | 11-JUN-13:20 | 83.74 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1328.34 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255.07 | 13-AUG-13:51 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.51 | 03-SEP-16:00 | 89.08 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.51 | 09-OCT-15:00 | 170.79 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.38 | 19-NOV-13:55 | 308.47 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.16 | 10-DEC-13:00 | 427.39 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.35 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.22 | 648.18 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.31 | 29-JAN-12:00 | 566.86 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.52 | 05-FEB-15:20 | 513.76 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.11 | 02-MAR-04:00 | 615.23 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.40 | 30-APR-13:00 | 323.06 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3261.80 | 21-MAY-13:00 | 114.44 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.94 | 11-JUN-14:40 | 69.23 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.48 | 30-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.86 | 13-AUG-13:51 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.99 | 04-SEP-17:00 | 76.06 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741.62 | 09-OCT-15:20 | 142.52 | 20-OCT-04:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.28 | 19-NOV-13:53 | 257.32 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.05 | 10-DEC-12:00 | 389.59 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.31 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3261.80 | 615.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 42308.69 | 02-JAN-07:02 | 7623.17 | 12888.13 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41019.83 | 21-FEB-07:02 | 6352.64 | 10740.11 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45108.51 | 28-MAR-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46147.17 | 17-APR-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46074.18 | 16-MAY-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45595.27 | 07-JUN-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40065.54 | 13-JUL-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40044.01 | 15-AUG-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43440.32 | 26-SEP-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45214.06 | 31-OCT-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45391.94 | 01-NOV-04:42 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44131.42 | 11-DEC-06:12 | 2541.06 | 2863.91 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 40044.01 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46147.17 | 7623.17 | 12888.13 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5333.78 | 31-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 |
February | 8212.83 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.70 | 0.00 |
March | 11160.70 | 27-MAR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.76 | 0.00 |
April | 12359.22 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.12 | 0.00 |
May | 12782.14 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.93 | 0.00 |
June | 13404.20 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.24 | 0.00 |
July | 14433.65 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.19 | 0.00 |
August | 14521.84 | 16-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.99 | 0.00 |
September | 13593.98 | 05-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.67 | 0.00 |
October | 11527.68 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.11 | 0.00 |
November | 9459.18 | 06-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.32 | 0.00 |
December | 6868.97 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5333.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14521.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.12 | 31.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2197.77 | 31-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 |
February | 4031.53 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.99 | 0.00 |
March | 5399.40 | 27-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.15 | 0.00 |
April | 5515.87 | 24-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.08 | 0.00 |
May | 6540.71 | 22-MAY-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.41 | 0.00 |
June | 6749.88 | 12-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 | 0.00 |
July | 7188.60 | 31-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
August | 6834.70 | 07-AUG-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.36 | 0.00 |
September | 7422.27 | 05-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.28 | 0.00 |
October | 6420.35 | 10-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.13 | 0.00 |
November | 5349.53 | 06-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 0.00 |
December | 3358.69 | 04-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2197.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7422.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.28 | 33.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3556.78 | 02-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 |
February | 4745.98 | 06-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 | 0.00 |
March | 7724.44 | 27-MAR-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.96 | 0.00 |
April | 7463.40 | 24-APR-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.03 | 0.00 |
May | 8742.80 | 22-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.81 | 0.00 |
June | 9024.26 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 | 0.00 |
July | 9317.37 | 31-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.68 | 0.00 |
August | 9064.53 | 14-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.09 | 0.00 |
September | 9372.12 | 05-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.63 | 0.00 |
October | 6836.91 | 04-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 0.00 |
November | 5972.66 | 01-NOV-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 | 0.00 |
December | 4496.57 | 04-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3556.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9372.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.96 | 31.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15116.12 | 30-JAN-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17924.64 | 06-FEB-07:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33845.23 | 27-MAR-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34631.10 | 03-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34749.93 | 09-MAY-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34692.99 | 06-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30770.59 | 03-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31319.76 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34491.73 | 26-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34923.09 | 23-OCT-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34667.86 | 20-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23852.28 | 11-DEC-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15116.12 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34923.09 | 6198.29 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14993.29 | 31-JAN-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17930.11 | 06-FEB-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37134.21 | 28-MAR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37322.72 | 25-APR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38231.66 | 08-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38202.29 | 21-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34665.42 | 24-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34773.57 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39096.89 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38860.28 | 23-OCT-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37597.19 | 03-NOV-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16709.75 | 12-DEC-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14993.29 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39096.89 | 6198.29 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4054.83 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 | 0.00 |
February | 5871.48 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 0.00 |
March | 7258.45 | 27-MAR-13:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 0.00 |
April | 14638.46 | 30-APR-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 394.12 | 0.00 |
May | 16339.34 | 21-MAY-13:12 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.38 | 0.00 |
June | 14998.89 | 11-JUN-15:32 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 577.39 | 0.00 |
July | 16318.45 | 30-JUL-14:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 964.42 | 0.00 |
August | 16417.26 | 06-AUG-15:01 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 579.30 | 0.00 |
September | 16294.05 | 04-SEP-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 595.94 | 0.00 |
October | 15975.03 | 09-OCT-11:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 139.10 | 0.00 |
November | 10090.77 | 05-NOV-15:12 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 300.74 | 0.00 |
December | 4615.76 | 11-DEC-14:40 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4054.83 | 267.84 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 0.00 | |
Maximum of Months | 16417.26 | 1306.65 | 711.15 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.38 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3000.23 | 24-JAN-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
February | 4133.00 | 05-FEB-10:58 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 82.73 | 0.00 |
March | 8080.27 | 26-MAR-12:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 100.74 | 0.00 |
April | 12646.12 | 23-APR-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 0.00 |
May | 13328.37 | 07-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 109.37 | 0.00 |
June | 13304.99 | 18-JUN-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 205.23 | 0.00 |
July | 13118.15 | 30-JUL-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 374.99 | 0.00 |
August | 13594.04 | 06-AUG-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 204.05 | 0.00 |
September | 13275.80 | 03-SEP-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 234.44 | 0.00 |
October | 13111.91 | 09-OCT-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 42.52 | 0.00 |
November | 8508.21 | 05-NOV-15:12 | 211.95 | 125.06 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 199.46 | 0.00 |
December | 3431.20 | 04-DEC-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3000.23 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13594.04 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 374.99 | 0.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8390.45 | 22-JAN-14:33 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 |
February | 18243.41 | 05-FEB-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 267.37 | 0.00 |
March | 18029.46 | 26-MAR-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 147.52 | 0.00 |
April | 17852.51 | 30-APR-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 444.26 | 0.00 |
May | 18034.83 | 21-MAY-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1918.21 | 0.00 |
June | 14581.31 | 11-JUN-14:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 629.72 | 0.00 |
July | 18080.60 | 30-JUL-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 963.87 | 0.00 |
August | 18204.52 | 06-AUG-15:01 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 578.39 | 0.00 |
September | 18346.20 | 04-SEP-15:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 585.64 | 0.00 |
October | 19322.99 | 09-OCT-11:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 122.33 | 0.00 |
November | 18893.48 | 05-NOV-11:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 118.05 | 0.00 |
December | 18231.23 | 03-DEC-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 41.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8390.45 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19322.99 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1918.21 | 15.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3711.00 | 31-JAN-16:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
February | 8558.86 | 05-FEB-15:32 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 211.22 | 0.00 |
March | 11791.66 | 26-MAR-16:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 112.63 | 0.00 |
April | 11655.83 | 30-APR-13:32 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 261.12 | 0.00 |
May | 14477.16 | 21-MAY-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 430.92 | 0.00 |
June | 14081.86 | 18-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 312.97 | 0.00 |
July | 14570.66 | 30-JUL-14:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 639.79 | 0.00 |
August | 15004.26 | 06-AUG-15:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 332.39 | 0.00 |
September | 14926.69 | 04-SEP-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 390.07 | 0.00 |
October | 14387.08 | 09-OCT-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 373.98 | 0.00 |
November | 14245.42 | 05-NOV-15:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 191.52 | 0.00 |
December | 4433.60 | 06-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3711.00 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15004.26 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 639.79 | 11.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4108.57 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
February | 5273.79 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 | 0.00 |
March | 6159.13 | 27-MAR-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 | 0.00 |
April | 6561.71 | 28-APR-12:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 0.00 |
May | 11403.76 | 08-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
June | 11447.13 | 16-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 0.00 |
July | 14163.35 | 16-JUL-15:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 280.71 | 0.00 |
August | 13856.86 | 06-AUG-10:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 180.32 | 0.00 |
September | 14676.05 | 04-SEP-15:01 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 305.37 | 0.00 |
October | 11378.65 | 03-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 0.00 |
November | 9471.69 | 20-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 0.00 |
December | 5057.68 | 11-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4108.57 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 | |
Maximum of Months | 14676.05 | 1306.65 | 647.98 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 305.37 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3315.40 | 24-JAN-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3834.53 | 06-FEB-14:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
March | 5717.33 | 27-MAR-10:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
April | 9633.78 | 23-APR-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 | 0.00 |
May | 9756.80 | 29-MAY-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 93.98 | 0.00 |
June | 11649.41 | 04-JUN-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 0.00 |
July | 11888.31 | 30-JUL-10:11 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 185.68 | 0.00 |
August | 12100.76 | 06-AUG-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 112.66 | 0.00 |
September | 12289.56 | 04-SEP-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 140.69 | 0.00 |
October | 11596.10 | 09-OCT-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 35.41 | 0.00 |
November | 7569.09 | 05-NOV-11:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 45.39 | 0.00 |
December | 3977.80 | 04-DEC-10:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3315.40 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12289.56 | 827.22 | 410.22 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 185.68 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10967.45 | 23-JAN-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.29 | 0.00 |
February | 13445.22 | 07-FEB-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7533.07 | 0.00 |
March | 15733.80 | 27-MAR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12327.81 | 0.00 |
April | 17132.71 | 28-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16068.12 | 0.00 |
May | 16714.09 | 09-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15407.53 | 0.00 |
June | 17603.93 | 12-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16735.18 | 0.00 |
July | 18547.52 | 21-JUL-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18851.70 | 0.00 |
August | 18871.46 | 16-AUG-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18776.69 | 0.00 |
September | 17430.35 | 05-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14756.60 | 0.00 |
October | 16622.01 | 29-OCT-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 170.31 | 0.00 |
November | 15938.96 | 05-NOV-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 | 0.00 |
December | 15860.81 | 03-DEC-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10967.45 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 | |
Maximum of Months | 18871.46 | 687.71 | 647.98 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18851.70 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3638.38 | 31-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
February | 4917.54 | 06-FEB-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
March | 8778.37 | 26-MAR-16:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 62.50 | 0.00 |
April | 8532.19 | 30-APR-17:33 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 0.00 |
May | 10578.97 | 29-MAY-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 103.93 | 0.00 |
June | 10651.05 | 11-JUN-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 | 0.00 |
July | 12925.25 | 16-JUL-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 176.94 | 0.00 |
August | 12530.57 | 06-AUG-16:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 175.80 | 0.00 |
September | 13594.21 | 04-SEP-15:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 187.67 | 0.00 |
October | 12156.64 | 29-OCT-15:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 0.00 |
November | 10382.62 | 05-NOV-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 | 0.00 |
December | 4390.89 | 04-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3638.38 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13594.21 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 | 5.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3979.30 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
February | 5499.47 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 | 0.00 |
March | 6696.32 | 27-MAR-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 178.33 | 0.00 |
April | 11292.19 | 30-APR-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 330.76 | 0.00 |
May | 13907.45 | 21-MAY-13:12 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.11 | 0.00 |
June | 12491.71 | 18-JUN-09:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 284.42 | 0.00 |
July | 13905.89 | 30-JUL-14:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 812.28 | 0.00 |
August | 13744.11 | 13-AUG-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 605.80 | 0.00 |
September | 14123.66 | 04-SEP-14:31 | 535.68 | 287.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 519.30 | 0.00 |
October | 14134.45 | 09-OCT-14:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 444.54 | 0.00 |
November | 7014.19 | 20-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 0.00 |
December | 4543.07 | 11-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3979.30 | 267.84 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 0.00 | |
Maximum of Months | 14134.45 | 1306.65 | 647.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3123.28 | 24-JAN-11:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
February | 3759.21 | 06-FEB-14:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 | 0.00 |
March | 6579.97 | 26-MAR-12:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 78.78 | 0.00 |
April | 11779.38 | 23-APR-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 0.00 |
May | 12408.85 | 07-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 91.92 | 0.00 |
June | 12335.72 | 18-JUN-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 173.54 | 0.00 |
July | 12172.12 | 30-JUL-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 245.45 | 0.00 |
August | 12310.40 | 27-AUG-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 148.75 | 0.00 |
September | 12643.39 | 04-SEP-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 218.00 | 0.00 |
October | 11996.03 | 09-OCT-11:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 68.38 | 0.00 |
November | 7311.44 | 05-NOV-11:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 | 0.00 |
December | 3526.14 | 04-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3123.28 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12643.39 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 245.45 | 0.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7666.35 | 23-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 |
February | 16035.77 | 05-FEB-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 226.76 | 0.00 |
March | 15752.27 | 26-MAR-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 115.36 | 0.00 |
April | 15544.50 | 30-APR-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 374.91 | 0.00 |
May | 15554.01 | 21-MAY-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.57 | 0.00 |
June | 13333.68 | 09-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.91 | 0.00 |
July | 15611.29 | 30-JUL-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 811.86 | 0.00 |
August | 15471.99 | 13-AUG-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 758.04 | 0.00 |
September | 16364.62 | 04-SEP-11:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 315.64 | 0.00 |
October | 17137.05 | 09-OCT-13:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 319.03 | 0.00 |
November | 16506.84 | 12-NOV-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.93 | 0.00 |
December | 15976.71 | 25-DEC-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7666.35 | 0.00 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 | |
Maximum of Months | 17137.05 | 1272.23 | 647.98 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.57 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3661.25 | 31-JAN-16:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 5684.95 | 05-FEB-16:23 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 144.82 | 0.00 |
March | 10935.54 | 26-MAR-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 | 0.00 |
April | 12969.78 | 23-APR-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 115.72 | 0.00 |
May | 12823.34 | 21-MAY-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 362.91 | 0.00 |
June | 12455.88 | 18-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 263.36 | 0.00 |
July | 12870.82 | 23-JUL-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 220.37 | 0.00 |
August | 12977.12 | 13-AUG-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 388.99 | 0.00 |
September | 13411.26 | 04-SEP-15:51 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 312.63 | 0.00 |
October | 13569.84 | 09-OCT-15:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 286.89 | 0.00 |
November | 12640.29 | 05-NOV-15:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 166.22 | 0.00 |
December | 4298.04 | 06-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3661.25 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13569.84 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 388.99 | 9.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124657E+12 | 112799.44 | 23-JAN-13:00 | 0.988561E+10 | 9527.76 | 18-JAN-12:09 |
February | 0.118590E+12 | 133666.54 | 06-FEB-14:00 | 0.885252E+10 | 9512.06 | 01-FEB-12:50 |
March | 0.146064E+12 | 158545.39 | 27-MAR-12:09 | 0.977399E+10 | 9449.88 | 01-MAR-12:09 |
April | 0.151090E+12 | 173245.11 | 28-APR-12:09 | 0.884389E+10 | 9324.90 | 04-APR-11:39 |
May | 0.196092E+12 | 191647.62 | 30-MAY-15:09 | 0.889329E+10 | 9218.94 | 02-MAY-11:20 |
June | 0.215020E+12 | 201268.39 | 12-JUN-12:00 | 0.841902E+10 | 9126.62 | 01-JUN-11:20 |
July | 0.237476E+12 | 206698.82 | 21-JUL-13:00 | 0.837452E+10 | 9083.01 | 31-JUL-11:20 |
August | 0.257786E+12 | 219416.41 | 10-AUG-15:39 | 0.876750E+10 | 9144.07 | 30-AUG-11:09 |
September | 0.210997E+12 | 196452.13 | 05-SEP-15:20 | 0.855993E+10 | 9238.17 | 28-SEP-11:09 |
October | 0.186215E+12 | 172147.65 | 06-OCT-15:20 | 0.920823E+10 | 9360.18 | 31-OCT-11:09 |
November | 0.154415E+12 | 159707.46 | 01-NOV-13:00 | 0.930543E+10 | 9463.17 | 30-NOV-12:50 |
December | 0.130849E+12 | 127717.55 | 04-DEC-13:09 | 0.970401E+10 | 9516.72 | 29-DEC-12:00 |
Annual Sum or Average | 0.212925E+13 | 0.108588E+12 | ||||
Minimum of Months | 0.118590E+12 | 112799.44 | 0.837452E+10 | 9083.01 | ||
Maximum of Months | 0.257786E+12 | 219416.41 | 0.988561E+10 | 9527.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.254616E+11 | 0.507020E+10 | 0.593559E+11 | 0.988799E+09 | 0.665474E+10 | 12379742.02 | 0.238453E+09 | 0.268751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229004E+11 | 0.427755E+10 | 0.537310E+11 | 0.894750E+09 | 0.699136E+10 | 11196021.66 | 0.139825E+09 | 0.296437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271220E+11 | 0.435515E+10 | 0.617796E+11 | 0.103584E+10 | 0.985439E+10 | 12675672.10 | 54432255.69 | 0.418498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239857E+11 | 0.382924E+10 | 0.572952E+11 | 0.952087E+09 | 0.114754E+11 | 11960507.72 | 1348143.35 | 0.535392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257284E+11 | 0.363967E+10 | 0.605677E+11 | 0.101191E+10 | 0.178564E+11 | 12527707.06 | 0.00 | 0.872748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.255635E+11 | 0.340476E+10 | 0.594895E+11 | 0.996228E+09 | 0.194156E+11 | 12231776.97 | 0.00 | 0.106138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239697E+11 | 0.358307E+10 | 0.583622E+11 | 0.967544E+09 | 0.201197E+11 | 12256437.81 | 0.00 | 0.130461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267986E+11 | 0.383930E+10 | 0.617796E+11 | 0.103557E+10 | 0.220410E+11 | 12675672.10 | 0.00 | 0.142279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240082E+11 | 0.401557E+10 | 0.572729E+11 | 0.951849E+09 | 0.179104E+11 | 11960507.72 | 0.00 | 0.106826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251091E+11 | 0.454821E+10 | 0.593671E+11 | 0.988643E+09 | 0.156289E+11 | 12379742.02 | 0.00 | 0.805610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250751E+11 | 0.480143E+10 | 0.580818E+11 | 0.970476E+09 | 0.118869E+11 | 12059151.09 | 0.00 | 0.535876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247109E+11 | 0.518961E+10 | 0.583511E+11 | 0.967979E+09 | 0.783393E+10 | 12256437.81 | 52856884.38 | 0.337302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300433E+12 | 0.505538E+11 | 0.705434E+12 | 0.117617E+11 | 0.167669E+12 | 0.146559E+09 | 0.486915E+09 | 0.892765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229004E+11 | 0.340476E+10 | 0.537310E+11 | 0.894750E+09 | 0.665474E+10 | 11196021.66 | 0.00 | 0.268751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271220E+11 | 0.518961E+10 | 0.617796E+11 | 0.103584E+10 | 0.220410E+11 | 12675672.10 | 0.238453E+09 | 0.142279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.988561E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.885252E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.977399E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.884389E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.889329E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.841902E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.837452E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.876750E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.855993E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.920823E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.930543E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.970401E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.108588E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.837452E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.988561E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29780.74 | 23-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 846.55 | 09-JAN-08:20 | 10022.51 | 23-JAN-13:00 | 6.85 | 01-JAN-06:10 | 7286.17 | 20-JAN-07:10 |
February | 30491.21 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 845.17 | 09-FEB-16:00 | 15622.43 | 06-FEB-15:39 | 6.85 | 01-FEB-06:10 | 6039.69 | 01-FEB-07:19 |
March | 32642.50 | 14-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 850.39 | 14-MAR-07:19 | 20113.04 | 27-MAR-15:30 | 6.85 | 27-MAR-12:09 | 4954.69 | 07-MAR-07:19 |
April | 30491.18 | 18-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 847.50 | 18-APR-07:19 | 21417.63 | 24-APR-14:39 | 6.85 | 26-APR-12:09 | 657.21 | 05-APR-06:00 |
May | 26300.01 | 23-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 841.89 | 23-MAY-07:19 | 24987.74 | 30-MAY-15:30 | 6.85 | 04-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 26426.34 | 08-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 842.06 | 08-JUN-07:19 | 24797.45 | 12-JUN-15:09 | 6.85 | 01-JUN-11:09 | 0.00 | 01-JUN-00:10 |
July | 28740.43 | 20-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 845.15 | 20-JUL-07:19 | 25218.72 | 31-JUL-15:20 | 6.85 | 03-JUL-12:09 | 0.00 | 01-JUL-00:10 |
August | 26945.64 | 29-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 842.75 | 29-AUG-07:19 | 23843.79 | 16-AUG-14:09 | 6.85 | 01-AUG-11:09 | 0.00 | 01-AUG-00:10 |
September | 27008.81 | 06-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 842.83 | 06-SEP-07:19 | 25606.93 | 05-SEP-15:09 | 6.85 | 03-SEP-15:39 | 0.00 | 01-SEP-00:10 |
October | 27939.54 | 25-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 844.08 | 25-OCT-07:19 | 20705.95 | 10-OCT-15:09 | 6.85 | 04-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 31087.65 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 845.17 | 29-NOV-16:00 | 17326.11 | 06-NOV-14:00 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 31791.75 | 14-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 848.10 | 15-DEC-08:20 | 13431.44 | 04-DEC-14:00 | 6.85 | 01-DEC-06:10 | 4499.34 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26300.01 | 5686.19 | 45864.70 | 841.89 | 10022.51 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 45864.70 | 850.39 | 25606.93 | 6.85 | 7286.17 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 33866.49 | 30-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51264.57 | 06-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71254.53 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86310.55 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98496.98 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 109765.42 | 12-JUN-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116567.93 | 21-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 127167.23 | 10-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 107468.78 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84665.84 | 05-OCT-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76575.97 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47288.03 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 33866.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 112799.44 | 23-JAN-13:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 10022.51 | 6.85 | 0.00 | 33847.01 | 0.00 |
February | 133666.54 | 06-FEB-14:00 | 25681.07 | 40588.47 | 0.00 | 839.16 | 15286.41 | 6.85 | 0.00 | 51264.57 | 0.00 |
March | 158545.39 | 27-MAR-12:09 | 25681.07 | 42402.18 | 0.00 | 839.81 | 18360.94 | 6.85 | 0.00 | 71254.53 | 0.00 |
April | 173245.11 | 28-APR-12:09 | 25681.07 | 42402.18 | 0.00 | 839.81 | 18004.64 | 6.85 | 0.00 | 86310.55 | 0.00 |
May | 191647.62 | 30-MAY-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 24717.92 | 6.85 | 0.00 | 98329.67 | 0.00 |
June | 201268.39 | 12-JUN-12:00 | 25681.07 | 42402.18 | 0.00 | 839.81 | 23022.65 | 6.85 | 0.00 | 109315.82 | 0.00 |
July | 206698.82 | 21-JUL-13:00 | 25681.07 | 40588.47 | 0.00 | 839.16 | 23015.33 | 6.85 | 0.00 | 116567.93 | 0.00 |
August | 219416.41 | 10-AUG-15:39 | 25681.07 | 42072.41 | 0.00 | 839.70 | 23651.54 | 6.85 | 0.00 | 127164.84 | 0.00 |
September | 196452.13 | 05-SEP-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 25516.90 | 6.85 | 0.00 | 102335.19 | 0.00 |
October | 172147.65 | 06-OCT-15:20 | 25681.07 | 42072.41 | 0.00 | 839.70 | 19137.48 | 6.85 | 0.00 | 84410.13 | 0.00 |
November | 159707.46 | 01-NOV-13:00 | 25681.07 | 40588.47 | 0.00 | 839.16 | 16015.92 | 6.85 | 0.00 | 76575.97 | 0.00 |
December | 127717.55 | 04-DEC-13:09 | 25681.07 | 42402.18 | 0.00 | 839.81 | 12673.32 | 6.85 | 0.00 | 46114.31 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112799.44 | 25681.07 | 40588.47 | 0.00 | 839.16 | 10022.51 | 6.85 | 0.00 | 33847.01 | 0.00 | |
Maximum of Months | 219416.41 | 25681.07 | 42402.18 | 0.00 | 839.81 | 25516.90 | 6.85 | 0.00 | 127164.84 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9527.76 | 18-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 9512.06 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9449.88 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9324.90 | 04-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9218.94 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9126.62 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9083.01 | 31-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9144.07 | 30-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9238.17 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9360.18 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9463.17 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9516.72 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9083.01 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9527.76 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.20 | 0.00 | 26.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.20 | 0.00 | 26.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.46 | 2.17 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.74 | 8.50 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.71 | 8.17 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.72 | 12.33 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.69 | 8.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.72 | 8.67 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.59 | 5.50 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 79.00 | 27.70 | 53.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.74 | 12.33 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 1.33 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.68 | 6.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.99 | 12.00 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.02 | 9.50 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.00 | 15.00 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.00 | 9.67 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.01 | 11.67 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.74 | 12.00 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 99.67 | 27.94 | 78.50 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.02 | 15.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.73 | 1.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.81 | 1.50 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.60 | 5.33 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.77 | 8.17 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.77 | 6.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.75 | 11.50 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.81 | 8.33 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.04 | 9.50 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.06 | 11.00 | 28.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.83 | 8.33 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.66 | 2.33 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 96.83 | 27.84 | 74.33 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 28.06 | 11.50 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.85 | 0.83 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.80 | 4.33 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.08 | 8.00 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.04 | 8.00 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28.02 | 12.50 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.04 | 8.50 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.09 | 8.83 | 28.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 6.67 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 2.83 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 93.17 | 28.01 | 61.00 | 28.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28.09 | 12.50 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.43 | 3.17 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.37 | 5.83 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.41 | 10.50 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.36 | 7.50 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.45 | 7.50 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.33 | 3.67 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 52.33 | 27.39 | 38.17 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.45 | 10.50 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.46 | 2.33 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.67 | 10.83 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.68 | 9.00 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.67 | 13.67 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.55 | 9.50 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.75 | 11.17 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.56 | 12.33 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.30 | 1.83 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 87.33 | 27.63 | 70.67 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.75 | 13.67 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.34 | 0.67 | 20.34 | 0.67 | 22.65 | 0.67 | 23.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.63 | 2.00 | 26.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.77 | 7.33 | 25.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 25.63 | 13.17 | 25.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.89 | 45.67 | 25.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 26.13 | 52.50 | 26.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 26.54 | 58.33 | 26.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 | 26.54 | 67.50 | 26.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 26.44 | 55.67 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 26.11 | 53.83 | 26.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 26.21 | 24.33 | 26.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 3.67 | 27.54 |
Annual Sum or Average | 0.67 | 20.34 | 0.67 | 20.34 | 405.00 | 26.26 | 384.67 | 26.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.65 | 0.67 | 23.81 |
Maximum of Months | 0.67 | 20.34 | 0.67 | 20.34 | 74.00 | 27.54 | 67.50 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.55 | 2.33 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.84 | 6.00 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.69 | 6.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.64 | 11.17 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.55 | 8.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.74 | 8.00 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.75 | 6.50 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 2.83 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 83.50 | 27.66 | 52.33 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.84 | 11.17 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.54 | 7.83 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.57 | 7.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.53 | 11.50 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.47 | 7.67 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.54 | 7.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.44 | 4.17 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 64.33 | 27.52 | 47.00 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.57 | 11.50 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 1.00 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.56 | 5.50 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.80 | 12.17 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.82 | 9.50 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.86 | 14.17 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.85 | 9.33 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.88 | 11.00 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.63 | 10.17 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 85.33 | 27.79 | 72.83 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.88 | 14.17 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.69 | 1.33 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.50 | 3.33 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.57 | 7.67 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.54 | 6.33 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.59 | 10.67 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.60 | 7.50 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.83 | 9.17 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.91 | 11.00 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.74 | 8.50 | 27.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.63 | 2.50 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 83.83 | 27.68 | 69.50 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.91 | 11.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.70 | 0.67 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.72 | 3.50 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.94 | 7.17 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.89 | 6.67 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.88 | 10.83 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.93 | 7.50 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.97 | 7.33 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.87 | 6.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 75.00 | 27.89 | 51.67 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.97 | 10.83 | 28.00 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 23.89 | 344.50 | 24.61 | 0.00 | 24.61 |
February | 0.00 | 0.00 | 371.00 | 24.53 | 0.00 | 24.53 |
March | 0.00 | 0.00 | 412.83 | 24.49 | 0.00 | 24.49 |
April | 0.00 | 0.00 | 461.50 | 24.43 | 0.00 | 24.43 |
May | 0.00 | 0.00 | 499.17 | 24.41 | 0.00 | 24.41 |
June | 0.00 | 0.00 | 496.00 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 496.67 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 514.00 | 24.27 | 0.00 | 24.27 |
September | 0.00 | 0.00 | 485.00 | 24.37 | 0.00 | 24.37 |
October | 0.00 | 0.00 | 492.17 | 24.45 | 0.00 | 24.45 |
November | 0.00 | 0.00 | 482.00 | 24.46 | 0.00 | 24.46 |
December | 0.00 | 0.00 | 432.00 | 24.48 | 0.00 | 24.48 |
Annual Sum or Average | 0.67 | 23.89 | 5486.83 | 24.43 | 0.00 | 24.43 |
Minimum of Months | 0.00 | 0.00 | 344.50 | 24.27 | 0.00 | 24.27 |
Maximum of Months | 0.67 | 23.89 | 514.00 | 24.61 | 0.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.50 | 23.48 | 167.50 | 24.02 | 0.00 | 24.02 |
February | 59.00 | 23.52 | 246.17 | 24.21 | 0.00 | 24.21 |
March | 24.50 | 23.57 | 317.83 | 24.30 | 0.00 | 24.30 |
April | 4.83 | 23.71 | 400.17 | 24.32 | 0.00 | 24.32 |
May | 0.00 | 0.00 | 488.00 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 496.00 | 24.30 | 0.00 | 24.30 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 485.00 | 24.34 | 0.00 | 24.34 |
October | 0.00 | 0.00 | 483.33 | 24.38 | 0.00 | 24.38 |
November | 0.67 | 23.75 | 452.00 | 24.34 | 0.00 | 24.34 |
December | 56.17 | 23.50 | 276.00 | 24.19 | 0.00 | 24.19 |
Annual Sum or Average | 251.67 | 23.51 | 4823.00 | 24.29 | 0.00 | 24.29 |
Minimum of Months | 0.00 | 0.00 | 167.50 | 24.02 | 0.00 | 24.02 |
Maximum of Months | 106.50 | 23.75 | 514.00 | 24.38 | 0.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.17 | 23.31 | 92.83 | 23.51 | 13.33 | 23.54 |
February | 154.00 | 23.32 | 159.17 | 23.76 | 0.00 | 23.76 |
March | 86.50 | 23.40 | 255.17 | 24.05 | 0.00 | 24.05 |
April | 14.50 | 23.43 | 377.50 | 24.29 | 0.00 | 24.29 |
May | 0.00 | 0.00 | 485.17 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 496.17 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.28 | 0.00 | 24.28 |
September | 0.50 | 26.60 | 485.00 | 24.38 | 0.50 | 24.38 |
October | 0.00 | 0.00 | 478.50 | 24.39 | 0.00 | 24.39 |
November | 10.67 | 23.49 | 387.17 | 24.27 | 0.00 | 24.27 |
December | 165.83 | 23.28 | 177.50 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 690.17 | 23.32 | 4404.17 | 24.19 | 13.83 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 92.83 | 23.51 | 0.00 | 23.54 |
Maximum of Months | 258.17 | 26.60 | 514.00 | 24.39 | 13.33 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.17 | 22.75 | 80.50 | 23.01 | 0.00 | 23.01 |
February | 211.00 | 22.91 | 157.17 | 23.45 | 0.33 | 23.45 |
March | 132.83 | 23.09 | 265.17 | 23.86 | 0.17 | 23.86 |
April | 54.50 | 24.00 | 390.00 | 24.38 | 19.83 | 24.42 |
May | 45.83 | 26.66 | 501.17 | 24.74 | 45.83 | 24.89 |
June | 68.50 | 26.50 | 496.00 | 24.79 | 68.50 | 24.98 |
July | 93.83 | 26.59 | 497.00 | 24.98 | 93.83 | 25.20 |
August | 68.50 | 26.57 | 514.00 | 24.79 | 68.50 | 24.97 |
September | 75.33 | 26.40 | 485.00 | 24.83 | 75.33 | 25.01 |
October | 60.67 | 26.03 | 484.83 | 24.70 | 58.00 | 24.84 |
November | 45.50 | 23.34 | 374.33 | 24.23 | 3.17 | 24.24 |
December | 230.33 | 22.90 | 166.33 | 23.43 | 2.50 | 23.43 |
Annual Sum or Average | 1415.00 | 23.98 | 4411.50 | 24.36 | 436.00 | 24.51 |
Minimum of Months | 45.50 | 22.75 | 80.50 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 328.17 | 26.66 | 514.00 | 24.98 | 93.83 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 261.00 | 22.71 | 131.83 | 23.24 | 0.00 | 23.24 |
February | 169.33 | 22.83 | 207.50 | 23.64 | 0.33 | 23.64 |
March | 117.17 | 23.06 | 306.83 | 23.97 | 2.33 | 23.99 |
April | 73.67 | 25.07 | 413.17 | 24.59 | 44.67 | 24.74 |
May | 57.67 | 26.82 | 504.17 | 24.82 | 57.67 | 25.00 |
June | 70.50 | 26.65 | 496.00 | 24.82 | 70.50 | 25.02 |
July | 95.67 | 26.70 | 497.00 | 25.01 | 95.67 | 25.25 |
August | 70.50 | 26.71 | 514.00 | 24.81 | 70.50 | 25.02 |
September | 78.33 | 26.63 | 485.00 | 24.89 | 78.33 | 25.10 |
October | 70.83 | 26.47 | 492.17 | 24.82 | 69.67 | 25.01 |
November | 37.67 | 23.55 | 399.67 | 24.35 | 5.67 | 24.37 |
December | 197.00 | 22.91 | 208.83 | 23.58 | 3.50 | 23.59 |
Annual Sum or Average | 1299.33 | 24.29 | 4656.17 | 24.47 | 498.83 | 24.63 |
Minimum of Months | 37.67 | 22.71 | 131.83 | 23.24 | 0.00 | 23.24 |
Maximum of Months | 261.00 | 26.82 | 514.00 | 25.01 | 95.67 | 25.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 219.00 | 22.82 | 209.83 | 23.66 | 0.83 | 23.66 |
February | 149.67 | 23.03 | 234.83 | 23.87 | 6.50 | 23.92 |
March | 116.33 | 23.22 | 308.50 | 24.04 | 6.17 | 24.08 |
April | 72.00 | 24.52 | 396.83 | 24.47 | 34.33 | 24.58 |
May | 42.83 | 26.68 | 496.00 | 24.72 | 42.83 | 24.86 |
June | 62.00 | 26.44 | 496.00 | 24.74 | 62.00 | 24.91 |
July | 86.33 | 26.55 | 497.00 | 24.93 | 86.33 | 25.14 |
August | 66.33 | 26.58 | 514.00 | 24.78 | 66.33 | 24.96 |
September | 76.33 | 26.54 | 485.00 | 24.87 | 76.33 | 25.07 |
October | 73.17 | 26.48 | 492.17 | 24.85 | 71.33 | 25.04 |
November | 61.33 | 25.34 | 415.67 | 24.63 | 36.33 | 24.79 |
December | 157.00 | 23.24 | 268.17 | 24.03 | 13.83 | 24.11 |
Annual Sum or Average | 1182.33 | 24.46 | 4814.00 | 24.52 | 503.17 | 24.68 |
Minimum of Months | 42.83 | 22.82 | 209.83 | 23.66 | 0.83 | 23.66 |
Maximum of Months | 219.00 | 26.68 | 514.00 | 24.93 | 86.33 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.50 | 22.52 | 116.50 | 23.01 | 0.00 | 23.01 |
February | 206.83 | 22.68 | 175.33 | 23.41 | 1.00 | 23.42 |
March | 146.50 | 22.95 | 284.17 | 23.85 | 3.33 | 23.87 |
April | 82.67 | 24.23 | 385.33 | 24.42 | 34.00 | 24.53 |
May | 47.00 | 26.76 | 492.33 | 24.75 | 46.50 | 24.92 |
June | 69.17 | 26.68 | 496.00 | 24.80 | 69.17 | 25.01 |
July | 86.83 | 26.68 | 497.00 | 24.95 | 86.83 | 25.18 |
August | 69.50 | 26.68 | 514.00 | 24.79 | 69.50 | 24.99 |
September | 78.50 | 26.54 | 484.50 | 24.86 | 78.50 | 25.06 |
October | 62.33 | 26.07 | 475.67 | 24.72 | 57.50 | 24.87 |
November | 71.83 | 23.56 | 368.33 | 24.25 | 11.50 | 24.31 |
December | 240.83 | 22.71 | 185.50 | 23.39 | 3.00 | 23.39 |
Annual Sum or Average | 1478.50 | 23.89 | 4474.67 | 24.35 | 460.83 | 24.51 |
Minimum of Months | 47.00 | 22.52 | 116.50 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 316.50 | 26.76 | 514.00 | 24.95 | 86.83 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.17 | 23.44 | 158.17 | 23.80 | 0.00 | 23.80 |
February | 91.83 | 23.36 | 230.00 | 23.99 | 0.00 | 23.99 |
March | 73.00 | 23.44 | 305.50 | 24.10 | 0.00 | 24.10 |
April | 17.67 | 24.15 | 411.17 | 24.37 | 6.50 | 24.38 |
May | 19.83 | 26.68 | 506.17 | 24.61 | 19.83 | 24.68 |
June | 44.67 | 26.48 | 496.00 | 24.70 | 44.67 | 24.83 |
July | 61.50 | 26.69 | 497.00 | 24.88 | 61.50 | 25.06 |
August | 45.50 | 26.67 | 514.00 | 24.71 | 45.50 | 24.85 |
September | 52.83 | 26.57 | 485.00 | 24.79 | 52.83 | 24.95 |
October | 33.00 | 26.54 | 498.17 | 24.71 | 33.00 | 24.81 |
November | 0.67 | 25.02 | 474.00 | 24.43 | 0.67 | 24.43 |
December | 49.17 | 23.49 | 322.83 | 24.16 | 0.00 | 24.16 |
Annual Sum or Average | 648.83 | 24.71 | 4898.00 | 24.50 | 264.50 | 24.59 |
Minimum of Months | 0.67 | 23.36 | 158.17 | 23.80 | 0.00 | 23.80 |
Maximum of Months | 159.17 | 26.69 | 514.00 | 24.88 | 61.50 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 110.50 | 23.36 | 235.50 | 24.02 | 0.17 | 24.02 |
February | 67.50 | 23.26 | 272.83 | 24.14 | 0.00 | 24.14 |
March | 58.00 | 23.31 | 350.33 | 24.19 | 0.00 | 24.19 |
April | 25.17 | 25.29 | 439.33 | 24.52 | 15.33 | 24.58 |
May | 47.50 | 26.83 | 508.00 | 24.77 | 47.50 | 24.93 |
June | 53.33 | 26.68 | 496.00 | 24.76 | 53.33 | 24.93 |
July | 73.67 | 26.84 | 497.00 | 24.96 | 73.67 | 25.17 |
August | 57.33 | 26.85 | 514.00 | 24.78 | 57.33 | 24.97 |
September | 64.50 | 26.81 | 485.00 | 24.88 | 64.50 | 25.09 |
October | 52.83 | 26.83 | 502.00 | 24.85 | 52.83 | 25.02 |
November | 4.67 | 26.92 | 482.17 | 24.54 | 4.67 | 24.56 |
December | 38.67 | 23.40 | 359.83 | 24.24 | 0.00 | 24.24 |
Annual Sum or Average | 653.67 | 25.29 | 5142.00 | 24.61 | 369.33 | 24.74 |
Minimum of Months | 4.67 | 23.26 | 235.50 | 24.02 | 0.00 | 24.02 |
Maximum of Months | 110.50 | 26.92 | 514.00 | 24.96 | 73.67 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.17 | 22.64 | 304.67 | 24.15 | 1.83 | 24.15 |
February | 61.17 | 22.88 | 325.17 | 24.20 | 9.33 | 24.21 |
March | 69.50 | 22.97 | 359.50 | 24.17 | 13.67 | 24.17 |
April | 47.83 | 23.92 | 418.50 | 24.42 | 28.67 | 24.44 |
May | 57.67 | 25.32 | 504.17 | 24.73 | 57.67 | 24.79 |
June | 134.50 | 25.29 | 496.00 | 24.84 | 134.50 | 24.92 |
July | 195.67 | 25.42 | 497.00 | 25.03 | 195.67 | 25.12 |
August | 188.83 | 25.60 | 514.00 | 25.04 | 188.83 | 25.16 |
September | 165.17 | 25.77 | 485.00 | 25.08 | 165.17 | 25.22 |
October | 128.00 | 25.75 | 502.00 | 25.02 | 128.00 | 25.14 |
November | 71.17 | 25.58 | 482.67 | 24.77 | 69.33 | 24.87 |
December | 57.33 | 23.68 | 397.33 | 24.43 | 23.33 | 24.49 |
Annual Sum or Average | 1259.00 | 24.94 | 5286.00 | 24.73 | 1016.00 | 24.83 |
Minimum of Months | 47.83 | 22.64 | 304.67 | 24.15 | 1.83 | 24.15 |
Maximum of Months | 195.67 | 25.77 | 514.00 | 25.08 | 195.67 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 141.33 | 23.29 | 218.67 | 23.91 | 0.00 | 23.91 |
February | 81.33 | 23.21 | 268.00 | 24.06 | 0.00 | 24.06 |
March | 60.67 | 23.31 | 343.83 | 24.19 | 0.67 | 24.19 |
April | 27.83 | 24.85 | 422.33 | 24.47 | 14.00 | 24.53 |
May | 29.83 | 26.89 | 505.83 | 24.68 | 29.83 | 24.80 |
June | 55.50 | 26.73 | 496.00 | 24.78 | 55.50 | 24.96 |
July | 70.33 | 26.83 | 497.00 | 24.94 | 70.33 | 25.15 |
August | 60.67 | 26.83 | 514.00 | 24.79 | 60.67 | 24.99 |
September | 66.17 | 26.79 | 485.00 | 24.89 | 66.17 | 25.09 |
October | 42.50 | 26.73 | 501.17 | 24.79 | 42.50 | 24.93 |
November | 8.50 | 26.84 | 481.17 | 24.53 | 8.50 | 24.57 |
December | 51.67 | 23.35 | 342.33 | 24.21 | 0.00 | 24.21 |
Annual Sum or Average | 696.33 | 25.03 | 5075.33 | 24.58 | 348.17 | 24.70 |
Minimum of Months | 8.50 | 23.21 | 218.67 | 23.91 | 0.00 | 23.91 |
Maximum of Months | 141.33 | 26.89 | 514.00 | 24.94 | 70.33 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.67 | 23.22 | 114.50 | 23.51 | 0.00 | 23.51 |
February | 132.17 | 23.25 | 205.83 | 23.84 | 0.33 | 23.84 |
March | 75.17 | 23.38 | 306.00 | 24.10 | 0.00 | 24.10 |
April | 28.17 | 24.63 | 419.33 | 24.44 | 16.33 | 24.48 |
May | 41.50 | 26.63 | 506.17 | 24.72 | 41.50 | 24.85 |
June | 66.00 | 26.45 | 496.00 | 24.78 | 66.00 | 24.95 |
July | 90.00 | 26.57 | 497.00 | 24.97 | 90.00 | 25.18 |
August | 63.50 | 26.52 | 514.00 | 24.76 | 63.50 | 24.94 |
September | 72.00 | 26.39 | 485.00 | 24.82 | 72.00 | 25.00 |
October | 50.00 | 26.22 | 490.33 | 24.70 | 50.00 | 24.83 |
November | 8.33 | 23.79 | 430.50 | 24.35 | 2.17 | 24.35 |
December | 148.83 | 23.31 | 230.00 | 23.85 | 1.17 | 23.85 |
Annual Sum or Average | 1026.33 | 24.50 | 4694.67 | 24.49 | 403.00 | 24.61 |
Minimum of Months | 8.33 | 23.22 | 114.50 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 250.67 | 26.63 | 514.00 | 24.97 | 90.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 202.50 | 23.09 | 122.83 | 23.59 | 0.33 | 23.59 |
February | 119.50 | 23.12 | 184.17 | 23.91 | 0.33 | 23.91 |
March | 76.67 | 23.29 | 265.17 | 24.17 | 1.50 | 24.18 |
April | 46.00 | 25.53 | 360.50 | 24.70 | 32.83 | 24.83 |
May | 57.00 | 26.77 | 430.00 | 24.93 | 57.00 | 25.12 |
June | 67.50 | 26.58 | 418.00 | 24.93 | 67.50 | 25.13 |
July | 92.67 | 26.68 | 422.00 | 25.15 | 92.67 | 25.38 |
August | 65.00 | 26.64 | 433.00 | 24.91 | 65.00 | 25.11 |
September | 72.83 | 26.63 | 410.00 | 25.01 | 72.83 | 25.22 |
October | 63.50 | 26.57 | 423.17 | 24.94 | 63.50 | 25.13 |
November | 13.17 | 24.25 | 368.33 | 24.51 | 4.33 | 24.53 |
December | 130.00 | 23.20 | 202.83 | 23.90 | 1.83 | 23.91 |
Annual Sum or Average | 1006.33 | 24.73 | 4040.00 | 24.64 | 459.67 | 24.81 |
Minimum of Months | 13.17 | 23.09 | 122.83 | 23.59 | 0.33 | 23.59 |
Maximum of Months | 202.50 | 26.77 | 433.00 | 25.15 | 92.67 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.33 | 23.22 | 246.00 | 24.04 | 0.83 | 24.05 |
February | 86.17 | 23.39 | 279.67 | 24.18 | 5.67 | 24.22 |
March | 64.83 | 23.54 | 346.33 | 24.24 | 4.33 | 24.27 |
April | 37.83 | 25.07 | 423.33 | 24.52 | 24.33 | 24.59 |
May | 40.50 | 26.63 | 505.67 | 24.70 | 40.50 | 24.83 |
June | 59.67 | 26.37 | 496.00 | 24.73 | 59.67 | 24.89 |
July | 84.67 | 26.51 | 497.00 | 24.93 | 84.67 | 25.13 |
August | 60.50 | 26.53 | 514.00 | 24.75 | 60.50 | 24.92 |
September | 72.17 | 26.53 | 485.00 | 24.86 | 72.17 | 25.05 |
October | 69.50 | 26.64 | 497.83 | 24.87 | 69.50 | 25.07 |
November | 39.33 | 26.57 | 458.17 | 24.70 | 36.33 | 24.85 |
December | 88.50 | 23.74 | 323.50 | 24.33 | 12.67 | 24.41 |
Annual Sum or Average | 847.00 | 25.07 | 5072.50 | 24.61 | 471.17 | 24.76 |
Minimum of Months | 37.83 | 23.22 | 246.00 | 24.04 | 0.83 | 24.05 |
Maximum of Months | 143.33 | 26.64 | 514.00 | 24.93 | 84.67 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.83 | 22.98 | 152.00 | 23.48 | 0.00 | 23.48 |
February | 142.17 | 23.03 | 220.00 | 23.80 | 0.67 | 23.80 |
March | 89.83 | 23.25 | 323.83 | 24.09 | 2.67 | 24.11 |
April | 50.67 | 24.86 | 414.83 | 24.51 | 28.67 | 24.60 |
May | 41.67 | 26.75 | 502.83 | 24.72 | 41.67 | 24.87 |
June | 67.67 | 26.60 | 496.00 | 24.79 | 67.67 | 24.99 |
July | 88.33 | 26.63 | 497.00 | 24.96 | 88.33 | 25.18 |
August | 68.00 | 26.64 | 514.00 | 24.79 | 68.00 | 24.98 |
September | 72.33 | 26.51 | 485.00 | 24.84 | 72.33 | 25.03 |
October | 53.50 | 26.33 | 490.17 | 24.72 | 52.67 | 24.87 |
November | 25.17 | 24.47 | 422.50 | 24.41 | 9.67 | 24.45 |
December | 160.33 | 23.07 | 242.83 | 23.80 | 1.67 | 23.80 |
Annual Sum or Average | 1109.50 | 24.41 | 4761.00 | 24.48 | 434.00 | 24.62 |
Minimum of Months | 25.17 | 22.98 | 152.00 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 249.83 | 26.75 | 514.00 | 24.96 | 88.33 | 25.18 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43553 | 42.04691 | 0.50122 | 10.51638 |
February | 454.00000 | 24.43613 | 45.08278 | 0.52678 | 11.05552 |
March | 514.00000 | 24.39522 | 44.60784 | 0.52466 | 11.00131 |
April | 485.00000 | 24.40637 | 47.52654 | 0.55741 | 11.76867 |
May | 508.00000 | 24.40126 | 50.15717 | -0.2501 | 6.79990 |
June | 496.00000 | 24.36842 | 53.37688 | -0.2335 | 6.60663 |
July | 497.00000 | 24.34357 | 53.05047 | -0.2466 | 6.57757 |
August | 514.00000 | 24.27360 | 53.17955 | -0.2626 | 6.69141 |
September | 485.00000 | 24.37497 | 52.81839 | -0.2366 | 6.60095 |
October | 502.00000 | 24.44261 | 50.71065 | 0.60184 | 12.89202 |
November | 489.00000 | 24.45544 | 49.57642 | 0.58898 | 12.50231 |
December | 497.00000 | 24.42636 | 46.37295 | 0.53799 | 11.30577 |
Annual Sum or Average | 5943.00000 | 24.39601 | 49.06158 | 0.21423 | 9.50806 |
Minimum of Months | 454.00000 | 24.27360 | 42.04691 | -0.2626 | 6.57757 |
Maximum of Months | 514.00000 | 24.45544 | 53.37688 | 0.60184 | 12.89202 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04858 | 42.65471 | 0.38305 | 8.29487 |
February | 454.00000 | 24.12988 | 45.65990 | 0.43171 | 9.11459 |
March | 514.00000 | 24.19270 | 45.13191 | 0.45716 | 9.56517 |
April | 485.00000 | 24.26491 | 48.66241 | 0.51306 | 10.70966 |
May | 508.00000 | 24.32594 | 51.80189 | -0.2847 | 7.10086 |
June | 496.00000 | 24.30186 | 55.11831 | -0.2632 | 6.81931 |
July | 497.00000 | 24.29461 | 55.34702 | -0.2610 | 6.70117 |
August | 514.00000 | 24.24422 | 56.08297 | -0.2683 | 6.73620 |
September | 485.00000 | 24.33547 | 55.53194 | -0.2512 | 6.72921 |
October | 502.00000 | 24.36621 | 52.79915 | 0.58131 | 12.34279 |
November | 489.00000 | 24.31378 | 50.63960 | 0.53832 | 11.22869 |
December | 497.00000 | 24.12260 | 46.62186 | 0.43885 | 9.26062 |
Annual Sum or Average | 5943.00000 | 24.24551 | 50.53028 | 0.16500 | 8.70744 |
Minimum of Months | 454.00000 | 24.04858 | 42.65471 | -0.2847 | 6.70117 |
Maximum of Months | 514.00000 | 24.36621 | 56.08297 | 0.58131 | 12.34279 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67882 | 43.93362 | 0.29197 | 7.33834 |
February | 454.00000 | 23.86204 | 45.23153 | 0.35822 | 8.08153 |
March | 514.00000 | 24.04489 | 44.42326 | 0.41531 | 8.91391 |
April | 485.00000 | 24.22358 | 47.78375 | 0.50193 | 10.50296 |
May | 508.00000 | 24.36496 | 51.20381 | -0.2576 | 6.91502 |
June | 496.00000 | 24.33816 | 54.87972 | -0.2309 | 6.59591 |
July | 497.00000 | 24.34710 | 55.13006 | -0.2181 | 6.42435 |
August | 514.00000 | 24.28269 | 56.01877 | -0.2306 | 6.45229 |
September | 485.00000 | 24.37513 | 55.42679 | -0.2218 | 6.58139 |
October | 502.00000 | 24.36888 | 52.35225 | 0.58429 | 12.43582 |
November | 489.00000 | 24.21430 | 49.91017 | 0.50665 | 10.55256 |
December | 497.00000 | 23.82548 | 46.08395 | 0.35521 | 8.05769 |
Annual Sum or Average | 5943.00000 | 24.16217 | 50.22652 | 0.15208 | 8.23186 |
Minimum of Months | 454.00000 | 23.67882 | 43.93362 | -0.2576 | 6.42435 |
Maximum of Months | 514.00000 | 24.37513 | 56.01877 | 0.58429 | 12.43582 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19748 | 45.48985 | 0.17682 | 6.80320 |
February | 454.00000 | 23.54678 | 48.35916 | 0.30022 | 7.89746 |
March | 514.00000 | 23.89457 | 46.20703 | 0.39805 | 9.07100 |
April | 485.00000 | 24.27415 | 49.36530 | 0.54882 | 11.97600 |
May | 508.00000 | 24.55619 | 51.57586 | -0.1140 | 6.73886 |
June | 496.00000 | 24.55455 | 55.67970 | -0.0567 | 6.55947 |
July | 497.00000 | 24.67934 | 55.39029 | 0.00042 | 6.77417 |
August | 514.00000 | 24.54874 | 56.47423 | -0.0357 | 6.43326 |
September | 485.00000 | 24.58492 | 56.84334 | -0.0671 | 6.74246 |
October | 502.00000 | 24.50904 | 54.01822 | 0.66031 | 14.88785 |
November | 489.00000 | 24.18181 | 51.82292 | 0.51995 | 11.11850 |
December | 497.00000 | 23.52373 | 49.18983 | 0.29628 | 7.80346 |
Annual Sum or Average | 5943.00000 | 24.17480 | 51.71342 | 0.21743 | 8.56148 |
Minimum of Months | 454.00000 | 23.19748 | 45.48985 | -0.1140 | 6.43326 |
Maximum of Months | 514.00000 | 24.67934 | 56.84334 | 0.66031 | 14.88785 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39566 | 44.76525 | 0.24230 | 7.47575 |
February | 454.00000 | 23.67878 | 47.75250 | 0.35324 | 8.74198 |
March | 514.00000 | 23.95393 | 45.82896 | 0.43806 | 9.96512 |
April | 485.00000 | 24.35033 | 48.87585 | 0.60171 | 13.54823 |
May | 508.00000 | 24.58214 | 51.31616 | -0.0489 | 6.79757 |
June | 496.00000 | 24.56138 | 55.46656 | -0.0066 | 6.65719 |
July | 497.00000 | 24.68945 | 55.19539 | 0.05219 | 7.08486 |
August | 514.00000 | 24.55386 | 56.26040 | 0.02090 | 6.55323 |
September | 485.00000 | 24.60865 | 56.44377 | -0.0049 | 6.92196 |
October | 502.00000 | 24.56772 | 53.50494 | 0.70851 | 16.47621 |
November | 489.00000 | 24.26813 | 51.37349 | 0.56830 | 12.40536 |
December | 497.00000 | 23.63090 | 48.68693 | 0.34068 | 8.43572 |
Annual Sum or Average | 5943.00000 | 24.24001 | 51.30345 | 0.27059 | 9.24555 |
Minimum of Months | 454.00000 | 23.39566 | 44.76525 | -0.0489 | 6.55323 |
Maximum of Months | 514.00000 | 24.68945 | 56.44377 | 0.70851 | 16.47621 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69466 | 43.32082 | 0.33262 | 9.13985 |
February | 454.00000 | 23.84362 | 46.81579 | 0.41067 | 10.02960 |
March | 514.00000 | 24.00112 | 45.44521 | 0.45570 | 10.41355 |
April | 485.00000 | 24.29629 | 49.05967 | 0.57130 | 12.69532 |
May | 508.00000 | 24.53379 | 51.57892 | -0.1200 | 6.76123 |
June | 496.00000 | 24.52752 | 55.75921 | -0.0759 | 6.53973 |
July | 497.00000 | 24.65305 | 55.42517 | -0.0107 | 6.70711 |
August | 514.00000 | 24.54221 | 56.36498 | -0.0223 | 6.44956 |
September | 485.00000 | 24.60790 | 56.42909 | -0.0136 | 6.91128 |
October | 502.00000 | 24.59452 | 53.24184 | 0.73294 | 17.31428 |
November | 489.00000 | 24.39778 | 50.57665 | 0.62890 | 14.29026 |
December | 497.00000 | 23.93701 | 47.20755 | 0.43764 | 10.59285 |
Annual Sum or Average | 5943.00000 | 24.30499 | 50.95413 | 0.27524 | 9.80560 |
Minimum of Months | 454.00000 | 23.69466 | 43.32082 | -0.1200 | 6.44956 |
Maximum of Months | 514.00000 | 24.65305 | 56.42909 | 0.73294 | 17.31428 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13188 | 45.16628 | 0.18571 | 7.37236 |
February | 454.00000 | 23.47673 | 48.09096 | 0.31177 | 8.49590 |
March | 514.00000 | 23.84019 | 45.97581 | 0.41699 | 9.82267 |
April | 485.00000 | 24.23911 | 49.15023 | 0.57165 | 12.87966 |
May | 508.00000 | 24.53865 | 51.46272 | -0.0763 | 6.94265 |
June | 496.00000 | 24.54276 | 55.54668 | -0.0199 | 6.75096 |
July | 497.00000 | 24.65144 | 55.28637 | 0.03190 | 6.99555 |
August | 514.00000 | 24.53471 | 56.34189 | 0.00660 | 6.59901 |
September | 485.00000 | 24.58457 | 56.53404 | -0.0203 | 6.97713 |
October | 502.00000 | 24.49268 | 53.78394 | 0.68779 | 15.84479 |
November | 489.00000 | 24.14229 | 51.61820 | 0.54039 | 11.92597 |
December | 497.00000 | 23.43915 | 48.94792 | 0.30203 | 8.30277 |
Annual Sum or Average | 5943.00000 | 24.13858 | 51.50504 | 0.24344 | 9.06846 |
Minimum of Months | 454.00000 | 23.13188 | 45.16628 | -0.0763 | 6.59901 |
Maximum of Months | 514.00000 | 24.65144 | 56.53404 | 0.68779 | 15.84479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90166 | 45.36075 | 0.36085 | 8.06381 |
February | 454.00000 | 23.99062 | 48.60894 | 0.41401 | 8.93442 |
March | 514.00000 | 24.08303 | 47.10840 | 0.44232 | 9.40630 |
April | 485.00000 | 24.29923 | 49.59047 | 0.53947 | 11.40590 |
May | 508.00000 | 24.52383 | 50.86727 | -0.1587 | 6.50883 |
June | 496.00000 | 24.53562 | 54.13326 | -0.0976 | 6.30816 |
July | 497.00000 | 24.65773 | 53.12917 | -0.0419 | 6.40611 |
August | 514.00000 | 24.53316 | 53.24412 | -0.0660 | 6.21639 |
September | 485.00000 | 24.59085 | 53.49025 | -0.0804 | 6.43938 |
October | 502.00000 | 24.58127 | 51.64465 | 0.67658 | 15.22345 |
November | 489.00000 | 24.41684 | 50.88600 | 0.59452 | 12.64004 |
December | 497.00000 | 24.12757 | 49.05415 | 0.46248 | 9.75782 |
Annual Sum or Average | 5943.00000 | 24.35546 | 50.59727 | 0.25165 | 8.93172 |
Minimum of Months | 454.00000 | 23.90166 | 45.36075 | -0.1587 | 6.21639 |
Maximum of Months | 514.00000 | 24.65773 | 54.13326 | 0.67658 | 15.22345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.02731 | 44.78316 | 0.41362 | 9.02815 |
February | 454.00000 | 24.09168 | 48.07891 | 0.46229 | 9.94653 |
March | 514.00000 | 24.14587 | 46.71974 | 0.48376 | 10.37588 |
April | 485.00000 | 24.40230 | 49.02509 | 0.59830 | 13.06580 |
May | 508.00000 | 24.57792 | 50.50038 | -0.0835 | 6.43379 |
June | 496.00000 | 24.55840 | 53.86961 | -0.0412 | 6.31118 |
July | 497.00000 | 24.67982 | 52.89066 | 0.01488 | 6.59226 |
August | 514.00000 | 24.55171 | 53.01195 | -0.0028 | 6.25498 |
September | 485.00000 | 24.62914 | 53.11642 | -0.0111 | 6.55180 |
October | 502.00000 | 24.64232 | 51.19718 | 0.72768 | 16.88952 |
November | 489.00000 | 24.50901 | 50.52133 | 0.64606 | 14.15206 |
December | 497.00000 | 24.19408 | 48.72074 | 0.50014 | 10.61550 |
Annual Sum or Average | 5943.00000 | 24.41904 | 50.20865 | 0.30689 | 9.66860 |
Minimum of Months | 454.00000 | 24.02731 | 44.78316 | -0.0835 | 6.25498 |
Maximum of Months | 514.00000 | 24.67982 | 53.86961 | 0.72768 | 16.88952 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11546 | 44.33039 | 0.47270 | 10.75909 |
February | 454.00000 | 24.15250 | 48.23426 | 0.50956 | 11.32395 |
March | 514.00000 | 24.14121 | 46.91445 | 0.49730 | 10.92050 |
April | 485.00000 | 24.35709 | 50.12177 | 0.57592 | 12.51870 |
May | 508.00000 | 24.66006 | 52.19739 | -0.1100 | 6.39078 |
June | 496.00000 | 24.71995 | 57.20477 | -0.0364 | 6.27211 |
July | 497.00000 | 24.88050 | 57.67928 | 0.04921 | 6.63351 |
August | 514.00000 | 24.83719 | 58.57263 | 0.07557 | 6.80324 |
September | 485.00000 | 24.85047 | 57.24322 | 0.07408 | 6.85196 |
October | 502.00000 | 24.83340 | 53.65990 | 0.80774 | 19.55266 |
November | 489.00000 | 24.63213 | 52.15255 | 0.72575 | 16.73873 |
December | 497.00000 | 24.30652 | 48.83269 | 0.57162 | 12.79813 |
Annual Sum or Average | 5943.00000 | 24.54276 | 52.28180 | 0.34887 | 10.61124 |
Minimum of Months | 454.00000 | 24.11546 | 44.33039 | -0.1100 | 6.27211 |
Maximum of Months | 514.00000 | 24.88050 | 58.57263 | 0.80774 | 19.55266 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94416 | 44.94986 | 0.39278 | 8.76556 |
February | 454.00000 | 24.03840 | 48.17522 | 0.44994 | 9.75650 |
March | 514.00000 | 24.13768 | 46.67005 | 0.48437 | 10.40774 |
April | 485.00000 | 24.35519 | 49.21590 | 0.58261 | 12.64055 |
May | 508.00000 | 24.55208 | 50.65206 | -0.1038 | 6.46892 |
June | 496.00000 | 24.55855 | 53.93284 | -0.0469 | 6.36849 |
July | 497.00000 | 24.66964 | 52.95066 | 0.00419 | 6.53820 |
August | 514.00000 | 24.55312 | 53.07771 | -0.0100 | 6.30491 |
September | 485.00000 | 24.62734 | 53.18863 | -0.0184 | 6.55887 |
October | 502.00000 | 24.62291 | 51.37344 | 0.71899 | 16.58167 |
November | 489.00000 | 24.47712 | 50.60243 | 0.63717 | 13.89875 |
December | 497.00000 | 24.15972 | 48.73204 | 0.49273 | 10.52404 |
Annual Sum or Average | 5943.00000 | 24.39319 | 50.29871 | 0.29655 | 9.55362 |
Minimum of Months | 454.00000 | 23.94416 | 44.94986 | -0.1038 | 6.30491 |
Maximum of Months | 514.00000 | 24.66964 | 53.93284 | 0.71899 | 16.58167 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65086 | 45.38242 | 0.29019 | 7.32646 |
February | 454.00000 | 23.87512 | 48.44713 | 0.38187 | 8.55596 |
March | 514.00000 | 24.08053 | 46.65641 | 0.44467 | 9.52479 |
April | 485.00000 | 24.34977 | 49.91926 | 0.56398 | 12.11627 |
May | 508.00000 | 24.56116 | 51.95092 | -0.1307 | 6.63563 |
June | 496.00000 | 24.55555 | 55.67254 | -0.0805 | 6.48862 |
July | 497.00000 | 24.68227 | 55.36076 | -0.0286 | 6.64265 |
August | 514.00000 | 24.54726 | 56.29803 | -0.0645 | 6.36919 |
September | 485.00000 | 24.58825 | 56.65236 | -0.0872 | 6.64695 |
October | 502.00000 | 24.53705 | 54.15749 | 0.66029 | 14.81661 |
November | 489.00000 | 24.30783 | 52.14853 | 0.55257 | 11.66433 |
December | 497.00000 | 23.87596 | 49.34066 | 0.38634 | 8.61685 |
Annual Sum or Average | 5943.00000 | 24.30352 | 51.84448 | 0.23874 | 8.77452 |
Minimum of Months | 454.00000 | 23.65086 | 45.38242 | -0.1307 | 6.36919 |
Maximum of Months | 514.00000 | 24.68227 | 56.65236 | 0.66029 | 14.81661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.69052 | 44.42988 | 0.31099 | 7.82661 |
February | 385.00000 | 23.91100 | 47.71771 | 0.40210 | 9.16954 |
March | 433.00000 | 24.11111 | 45.91864 | 0.46204 | 10.15425 |
April | 410.00000 | 24.47837 | 49.29620 | 0.61109 | 13.68114 |
May | 430.00000 | 24.68587 | 51.53286 | -0.0603 | 6.87071 |
June | 418.00000 | 24.66026 | 55.46554 | -0.0245 | 6.76176 |
July | 422.00000 | 24.81088 | 54.90019 | 0.03541 | 7.15380 |
August | 433.00000 | 24.65272 | 56.00117 | -0.0025 | 6.63050 |
September | 410.00000 | 24.71674 | 56.23017 | -0.0167 | 7.03446 |
October | 427.00000 | 24.68448 | 53.51907 | 0.71163 | 16.59814 |
November | 417.00000 | 24.43162 | 51.06472 | 0.59103 | 12.85608 |
December | 422.00000 | 23.89068 | 48.59777 | 0.39950 | 9.03385 |
Annual Sum or Average | 5034.00000 | 24.39602 | 51.23291 | 0.28366 | 9.47434 |
Minimum of Months | 385.00000 | 23.69052 | 44.42988 | -0.0603 | 6.63050 |
Maximum of Months | 433.00000 | 24.81088 | 56.23017 | 0.71163 | 16.59814 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.03761 | 43.41761 | 0.42298 | 9.85981 |
February | 454.00000 | 24.11017 | 47.01601 | 0.47888 | 10.71666 |
March | 514.00000 | 24.17232 | 45.91119 | 0.49816 | 10.83573 |
April | 485.00000 | 24.37953 | 49.59631 | 0.58715 | 12.82612 |
May | 508.00000 | 24.54089 | 51.95061 | -0.1362 | 6.63410 |
June | 496.00000 | 24.52850 | 55.76383 | -0.0993 | 6.47421 |
July | 497.00000 | 24.65875 | 55.40001 | -0.0389 | 6.57875 |
August | 514.00000 | 24.54360 | 56.17717 | -0.0509 | 6.35176 |
September | 485.00000 | 24.61315 | 56.21579 | -0.0345 | 6.71857 |
October | 502.00000 | 24.62218 | 53.34937 | 0.73120 | 17.14676 |
November | 489.00000 | 24.50010 | 50.97993 | 0.65509 | 14.75901 |
December | 497.00000 | 24.20029 | 47.54874 | 0.50883 | 11.46425 |
Annual Sum or Average | 5943.00000 | 24.41041 | 51.12890 | 0.29114 | 10.01213 |
Minimum of Months | 454.00000 | 24.03761 | 43.41761 | -0.1362 | 6.35176 |
Maximum of Months | 514.00000 | 24.65875 | 56.21579 | 0.73120 | 17.14676 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57979 | 45.07611 | 0.29730 | 7.81332 |
February | 454.00000 | 23.81660 | 48.17447 | 0.39494 | 9.10316 |
March | 514.00000 | 24.04940 | 46.39622 | 0.46731 | 10.26272 |
April | 485.00000 | 24.33936 | 49.67401 | 0.59109 | 13.03596 |
May | 508.00000 | 24.55056 | 51.82511 | -0.0914 | 6.69772 |
June | 496.00000 | 24.54850 | 55.53193 | -0.0425 | 6.57257 |
July | 497.00000 | 24.66647 | 55.22658 | 0.00611 | 6.77098 |
August | 514.00000 | 24.54361 | 56.13634 | -0.0197 | 6.44086 |
September | 485.00000 | 24.59245 | 56.33225 | -0.0396 | 6.74438 |
October | 502.00000 | 24.53360 | 53.90264 | 0.68979 | 15.76387 |
November | 489.00000 | 24.29857 | 51.91799 | 0.57801 | 12.51869 |
December | 497.00000 | 23.80947 | 49.09091 | 0.39482 | 9.08191 |
Annual Sum or Average | 5943.00000 | 24.28011 | 51.62006 | 0.26699 | 9.22273 |
Minimum of Months | 454.00000 | 23.57979 | 45.07611 | -0.0914 | 6.44086 |
Maximum of Months | 514.00000 | 24.66647 | 56.33225 | 0.68979 | 15.76387 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.422534E+11 | 0.104681E+11 | 405.72 | 0.361600E+11 | 0.609339E+10 | 0.00 | 1.00 | 09-JAN-14:00 | 0.00 | 01-JAN-00:10 | 57648.81 | 30-JAN-14:00 | 50999.61 | 23-JAN-14:00 | 14495.42 | 30-JAN-14:50 | 13258.39 | 30-JAN-14:00 | 0.00 |
February | 0.446837E+11 | 0.111096E+11 | 367.99 | 0.375949E+11 | 0.708874E+10 | 0.00 | 1.00 | 02-FEB-13:50 | 0.00 | 01-FEB-00:10 | 77635.41 | 07-FEB-12:10 | 63252.03 | 06-FEB-15:00 | 21258.30 | 06-FEB-12:10 | 20483.89 | 07-FEB-13:03 | 0.00 |
March | 0.595291E+11 | 0.152403E+11 | 434.22 | 0.519562E+11 | 0.757296E+10 | 0.00 | 1.00 | 01-MAR-09:50 | 0.00 | 01-MAR-00:10 | 85905.51 | 28-MAR-11:40 | 76583.27 | 27-MAR-12:08 | 27316.28 | 28-MAR-11:40 | 25361.48 | 27-MAR-12:08 | 0.00 |
April | 0.705254E+11 | 0.189471E+11 | 424.64 | 0.601550E+11 | 0.103703E+11 | 0.00 | 1.00 | 03-APR-04:03 | 0.00 | 01-APR-00:10 | 92479.86 | 10-APR-12:00 | 79541.74 | 28-APR-12:02 | 33431.45 | 10-APR-12:00 | 30209.07 | 28-APR-12:00 | 0.00 |
May | 0.105410E+12 | 0.306447E+11 | 488.50 | 0.874233E+11 | 0.179864E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 150538.93 | 31-MAY-04:02 | 100489.09 | 12-MAY-04:02 | 68586.23 | 24-MAY-04:03 | 38518.33 | 23-MAY-04:02 | 0.00 |
June | 0.127529E+12 | 0.372863E+11 | 496.29 | 0.942523E+11 | 0.332772E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 155675.09 | 14-JUN-04:03 | 100630.49 | 01-JUN-04:02 | 74761.07 | 14-JUN-04:03 | 40273.58 | 09-JUN-12:01 | 0.00 |
July | 0.154075E+12 | 0.458043E+11 | 560.93 | 0.104263E+12 | 0.498119E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 153878.44 | 06-JUL-04:02 | 103449.77 | 11-JUL-04:02 | 70753.57 | 16-JUL-17:32 | 44477.29 | 30-JUL-15:31 | 0.00 |
August | 0.171716E+12 | 0.512113E+11 | 589.80 | 0.114092E+12 | 0.576242E+11 | 0.00 | 1.00 | 01-AUG-00:27 | 0.00 | 01-AUG-00:03 | 153236.05 | 26-AUG-04:02 | 101649.91 | 07-AUG-06:03 | 68416.39 | 22-AUG-17:00 | 44301.01 | 10-AUG-12:02 | 0.00 |
September | 0.137379E+12 | 0.390191E+11 | 513.66 | 0.939971E+11 | 0.433821E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:25 | 154332.71 | 28-SEP-04:02 | 103073.28 | 05-SEP-05:03 | 71030.55 | 10-SEP-14:52 | 39918.37 | 03-SEP-14:22 | 0.00 |
October | 0.111498E+12 | 0.302713E+11 | 495.72 | 0.843557E+11 | 0.271419E+11 | 0.00 | 1.00 | 01-OCT-06:53 | 0.00 | 01-OCT-00:10 | 150818.04 | 06-OCT-04:02 | 99124.85 | 03-OCT-04:02 | 66924.58 | 18-OCT-04:03 | 36506.84 | 05-OCT-04:02 | 0.00 |
November | 0.805355E+11 | 0.206396E+11 | 429.82 | 0.651271E+11 | 0.154084E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 127451.10 | 03-NOV-04:03 | 95531.35 | 20-NOV-05:02 | 53533.66 | 03-NOV-04:03 | 29938.78 | 01-NOV-12:04 | 0.00 |
December | 0.529354E+11 | 0.129990E+11 | 408.35 | 0.438204E+11 | 0.911500E+10 | 0.00 | 1.00 | 01-DEC-10:20 | 0.00 | 01-DEC-00:10 | 83492.38 | 11-DEC-06:12 | 58739.43 | 04-DEC-13:20 | 27308.33 | 11-DEC-06:12 | 20358.86 | 04-DEC-12:10 | 0.00 |
Annual Sum or Average | 0.115807E+13 | 0.323641E+12 | 5615.63 | 0.873198E+12 | 0.284873E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.422534E+11 | 0.104681E+11 | 367.99 | 0.361600E+11 | 0.609339E+10 | 0.00 | 1.00 | 0.00 | 57648.81 | 50999.61 | 14495.42 | 13258.39 | 0.00 | ||||||
Maximum of Months | 0.171716E+12 | 0.512113E+11 | 589.80 | 0.114092E+12 | 0.576242E+11 | 0.00 | 1.00 | 0.00 | 155675.09 | 103449.77 | 74761.07 | 44477.29 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.320764E+11 | 0.814137E+10 | 400.89 | 0.255984E+11 | 0.647804E+10 | 0.00 | 0.98 | 30-JAN-14:00 | 0.00 | 01-JAN-00:10 | 43480.50 | 30-JAN-14:00 | 39129.58 | 23-JAN-14:00 | 13365.25 | 30-JAN-15:00 | 10071.15 | 23-JAN-14:00 | 0.00 |
February | 0.358419E+11 | 0.907164E+10 | 367.57 | 0.287070E+11 | 0.713486E+10 | 0.00 | 1.00 | 05-FEB-14:23 | 0.00 | 01-FEB-00:10 | 64071.86 | 07-FEB-15:50 | 55450.30 | 06-FEB-15:10 | 17289.95 | 07-FEB-16:00 | 15899.79 | 07-FEB-15:50 | 0.00 |
March | 0.498711E+11 | 0.129087E+11 | 436.10 | 0.423478E+11 | 0.752338E+10 | 0.00 | 1.00 | 01-MAR-10:40 | 0.00 | 01-MAR-00:10 | 66836.96 | 27-MAR-12:03 | 66836.96 | 27-MAR-12:03 | 15882.33 | 31-MAR-18:00 | 22630.61 | 27-MAR-11:00 | 0.00 |
April | 0.616890E+11 | 0.166043E+11 | 429.07 | 0.519209E+11 | 0.976810E+10 | 0.00 | 1.00 | 02-APR-13:33 | 0.00 | 01-APR-00:10 | 89136.76 | 30-APR-13:32 | 73365.94 | 30-APR-13:32 | 27640.81 | 30-APR-17:33 | 26367.57 | 28-APR-12:02 | 0.00 |
May | 0.937379E+11 | 0.270691E+11 | 492.13 | 0.776780E+11 | 0.160599E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 139729.94 | 24-MAY-05:03 | 91106.44 | 22-MAY-04:02 | 68750.91 | 24-MAY-05:03 | 33440.92 | 31-MAY-04:02 | 0.00 |
June | 0.113788E+12 | 0.329380E+11 | 496.05 | 0.832016E+11 | 0.305867E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 143635.01 | 14-JUN-04:03 | 88980.08 | 01-JUN-04:02 | 73379.37 | 14-JUN-04:03 | 37160.76 | 04-JUN-15:52 | 0.00 |
July | 0.136906E+12 | 0.403442E+11 | 549.59 | 0.925910E+11 | 0.443152E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 142700.72 | 06-JUL-04:02 | 96598.34 | 30-JUL-13:42 | 69201.11 | 06-JUL-04:02 | 42796.10 | 30-JUL-14:22 | 0.00 |
August | 0.147022E+12 | 0.435259E+11 | 560.80 | 0.984061E+11 | 0.486161E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:13 | 142025.08 | 08-AUG-04:02 | 90473.50 | 07-AUG-06:03 | 69638.97 | 08-AUG-04:02 | 41069.23 | 13-AUG-14:42 | 0.00 |
September | 0.116152E+12 | 0.327150E+11 | 486.41 | 0.792889E+11 | 0.368635E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:25 | 142632.57 | 28-SEP-04:02 | 93979.04 | 04-SEP-14:31 | 70414.00 | 23-SEP-05:03 | 42057.28 | 04-SEP-13:51 | 0.00 |
October | 0.906044E+11 | 0.245199E+11 | 466.96 | 0.684071E+11 | 0.221973E+11 | 0.00 | 1.00 | 01-OCT-07:12 | 0.00 | 01-OCT-00:10 | 139792.92 | 02-OCT-04:02 | 90408.81 | 10-OCT-04:02 | 62906.69 | 06-OCT-04:02 | 33915.08 | 08-OCT-11:52 | 0.00 |
November | 0.628880E+11 | 0.162022E+11 | 415.44 | 0.495477E+11 | 0.133403E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 93029.20 | 03-NOV-05:03 | 67335.45 | 20-NOV-05:02 | 41191.49 | 03-NOV-05:03 | 23483.49 | 01-NOV-14:00 | 0.00 |
December | 0.408201E+11 | 0.102345E+11 | 403.83 | 0.316842E+11 | 0.913590E+10 | 0.00 | 1.00 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 | 61058.00 | 05-DEC-15:10 | 46633.95 | 04-DEC-13:10 | 19081.27 | 05-DEC-15:00 | 14550.39 | 05-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.981398E+12 | 0.274275E+12 | 5504.84 | 0.729379E+12 | 0.252019E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.320764E+11 | 0.814137E+10 | 367.57 | 0.255984E+11 | 0.647804E+10 | 0.00 | 0.98 | 0.00 | 43480.50 | 39129.58 | 13365.25 | 10071.15 | 0.00 | ||||||
Maximum of Months | 0.147022E+12 | 0.435259E+11 | 560.80 | 0.984061E+11 | 0.486161E+11 | 0.00 | 1.00 | 0.00 | 143635.01 | 96598.34 | 73379.37 | 42796.10 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.321268E+11 | 0.826561E+10 | 398.17 | 0.247435E+11 | 0.738332E+10 | 0.00 | 0.91 | 30-JAN-14:30 | 0.00 | 01-JAN-00:10 | 44968.36 | 30-JAN-14:30 | 41577.60 | 23-JAN-14:00 | 14066.52 | 30-JAN-15:00 | 10853.52 | 23-JAN-14:00 | 0.00 |
February | 0.369270E+11 | 0.946244E+10 | 366.99 | 0.290016E+11 | 0.792538E+10 | 0.00 | 1.00 | 05-FEB-12:53 | 0.00 | 01-FEB-00:10 | 69225.98 | 07-FEB-15:30 | 61400.05 | 06-FEB-15:00 | 17249.18 | 07-FEB-16:00 | 17423.72 | 06-FEB-15:00 | 0.00 |
March | 0.523678E+11 | 0.137008E+11 | 435.54 | 0.439650E+11 | 0.840286E+10 | 0.00 | 1.00 | 01-MAR-11:10 | 0.00 | 01-MAR-00:10 | 75145.36 | 27-MAR-13:10 | 75145.36 | 27-MAR-13:10 | 16928.37 | 31-MAR-18:00 | 24458.53 | 27-MAR-12:03 | 0.00 |
April | 0.662228E+11 | 0.179877E+11 | 431.47 | 0.555239E+11 | 0.106989E+11 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 110325.56 | 30-APR-13:32 | 94689.98 | 30-APR-13:32 | 31299.34 | 30-APR-17:33 | 32303.34 | 30-APR-13:32 | 0.00 |
May | 0.101815E+12 | 0.295610E+11 | 495.52 | 0.849937E+11 | 0.168209E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:05 | 157675.81 | 31-MAY-04:02 | 107357.96 | 21-MAY-13:12 | 72474.08 | 24-MAY-05:03 | 38533.67 | 21-MAY-13:12 | 0.00 |
June | 0.123639E+12 | 0.359134E+11 | 504.47 | 0.918767E+11 | 0.317625E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 163181.14 | 14-JUN-04:03 | 100160.96 | 12-JUN-04:02 | 87637.71 | 20-JUN-04:03 | 43746.60 | 04-JUN-15:52 | 0.00 |
July | 0.150057E+12 | 0.443126E+11 | 568.62 | 0.103657E+12 | 0.463999E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 162119.71 | 06-JUL-04:02 | 116691.80 | 30-JUL-13:42 | 77454.99 | 06-JUL-04:02 | 49249.87 | 30-JUL-14:22 | 0.00 |
August | 0.160348E+12 | 0.475416E+11 | 579.80 | 0.109646E+12 | 0.507026E+11 | 0.00 | 1.00 | 01-AUG-00:27 | 0.00 | 01-AUG-00:03 | 161352.13 | 08-AUG-04:02 | 110718.07 | 06-AUG-15:01 | 75407.14 | 08-AUG-04:02 | 48104.24 | 06-AUG-15:01 | 0.00 |
September | 0.124163E+12 | 0.350922E+11 | 492.77 | 0.862856E+11 | 0.378770E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:03 | 162785.60 | 28-SEP-04:02 | 111552.23 | 04-SEP-14:02 | 82127.59 | 28-SEP-04:02 | 47693.28 | 04-SEP-14:02 | 0.00 |
October | 0.945398E+11 | 0.257698E+11 | 464.32 | 0.718520E+11 | 0.226878E+11 | 0.00 | 1.00 | 01-OCT-07:17 | 0.00 | 01-OCT-00:10 | 158619.84 | 02-OCT-04:02 | 103235.48 | 09-OCT-14:22 | 69417.08 | 02-OCT-04:02 | 37636.34 | 02-OCT-04:02 | 0.00 |
November | 0.643210E+11 | 0.167458E+11 | 413.58 | 0.502177E+11 | 0.141033E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 108693.81 | 03-NOV-05:03 | 80334.97 | 05-NOV-15:12 | 50440.92 | 03-NOV-05:03 | 25535.10 | 01-NOV-14:00 | 0.00 |
December | 0.412476E+11 | 0.104967E+11 | 402.13 | 0.311294E+11 | 0.101182E+11 | 0.00 | 1.00 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 64361.96 | 05-DEC-15:00 | 49393.25 | 04-DEC-14:10 | 19279.42 | 05-DEC-15:00 | 15292.18 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.104777E+13 | 0.294850E+12 | 5553.36 | 0.782892E+12 | 0.264883E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.321268E+11 | 0.826561E+10 | 366.99 | 0.247435E+11 | 0.738332E+10 | 0.00 | 0.91 | 0.00 | 44968.36 | 41577.60 | 14066.52 | 10853.52 | 0.00 | ||||||
Maximum of Months | 0.160348E+12 | 0.475416E+11 | 579.80 | 0.109646E+12 | 0.507026E+11 | 0.00 | 1.00 | 0.00 | 163181.14 | 116691.80 | 87637.71 | 49249.87 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.97 | 0.00 | 317.97 | 377.03 | 659.18 | 0.00 | 0.00 | 0.00 |
February | 364.49 | 0.00 | 364.49 | 513.24 | 553.11 | 0.00 | 0.00 | 0.00 |
March | 418.66 | 0.00 | 418.66 | 728.89 | 425.23 | 0.00 | 0.00 | 0.00 |
April | 471.70 | 0.97 | 470.73 | 1050.72 | 270.74 | 0.00 | 0.00 | 0.00 |
May | 530.94 | 15.57 | 515.37 | 1589.82 | 70.02 | 0.00 | 0.00 | 0.00 |
June | 568.47 | 31.56 | 536.91 | 1838.97 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 15.03 | 506.60 | 2056.04 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 485.59 | 4.02 | 481.57 | 2026.78 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 442.33 | 0.05 | 442.28 | 1523.11 | 25.68 | 0.00 | 0.00 | 0.00 |
October | 392.11 | 0.00 | 392.11 | 1091.61 | 113.40 | 0.00 | 0.00 | 0.00 |
November | 336.62 | 0.00 | 336.62 | 696.17 | 307.44 | 0.00 | 0.00 | 0.00 |
December | 296.79 | 0.00 | 296.79 | 420.00 | 538.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 429.19 | 5.62 | 423.57 | 1163.38 | 247.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.79 | 0.00 | 296.79 | 377.03 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.47 | 31.56 | 536.91 | 2056.04 | 659.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 383.47 | 116.02 | 267.45 | 538.26 | 413.88 | 0.00 | 0.00 | 0.00 |
February | 417.90 | 113.25 | 304.65 | 646.81 | 350.22 | 0.00 | 0.00 | 0.00 |
March | 461.61 | 113.77 | 347.84 | 817.51 | 270.96 | 0.00 | 0.00 | 0.00 |
April | 562.03 | 163.76 | 398.27 | 1163.01 | 174.32 | 0.00 | 0.00 | 0.00 |
May | 628.09 | 200.11 | 427.97 | 1570.50 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 188.11 | 427.00 | 1660.24 | 10.36 | 0.00 | 0.00 | 0.00 |
July | 574.11 | 165.52 | 408.60 | 1797.11 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 587.88 | 180.43 | 407.45 | 1856.35 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 552.68 | 170.83 | 381.85 | 1502.86 | 15.08 | 0.00 | 0.00 | 0.00 |
October | 501.50 | 163.84 | 337.66 | 1175.36 | 69.19 | 0.00 | 0.00 | 0.00 |
November | 420.26 | 133.12 | 287.14 | 819.11 | 194.17 | 0.00 | 0.00 | 0.00 |
December | 340.16 | 93.33 | 246.83 | 525.41 | 341.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 504.07 | 150.33 | 353.74 | 1175.79 | 156.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.16 | 93.33 | 246.83 | 525.41 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 628.09 | 200.11 | 427.97 | 1856.35 | 413.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1027.66 | 483.15 | 544.51 | 1638.21 | 646.66 | 0.00 | 0.00 | 0.00 |
February | 965.01 | 394.73 | 570.28 | 1633.62 | 553.61 | 0.00 | 0.00 | 0.00 |
March | 794.25 | 215.63 | 578.62 | 1501.51 | 434.22 | 0.00 | 0.00 | 0.00 |
April | 624.34 | 66.19 | 558.15 | 1399.31 | 276.10 | 0.00 | 0.00 | 0.00 |
May | 528.87 | 8.10 | 520.77 | 1586.83 | 69.79 | 0.00 | 0.00 | 0.00 |
June | 498.07 | 0.62 | 497.46 | 1688.58 | 14.05 | 0.00 | 0.00 | 0.00 |
July | 498.06 | 4.23 | 493.83 | 1997.68 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 577.71 | 40.93 | 536.78 | 2237.79 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 761.72 | 174.57 | 587.15 | 2207.87 | 25.36 | 0.00 | 0.00 | 0.00 |
October | 997.24 | 396.46 | 600.78 | 2290.98 | 113.19 | 0.00 | 0.00 | 0.00 |
November | 1100.16 | 530.36 | 569.80 | 2130.65 | 310.17 | 0.00 | 0.00 | 0.00 |
December | 1021.28 | 504.48 | 516.80 | 1733.42 | 539.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 781.77 | 234.10 | 547.67 | 1838.66 | 247.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 498.06 | 0.62 | 493.83 | 1399.31 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1100.16 | 530.36 | 600.78 | 2290.98 | 646.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.07 | 108.01 | 268.06 | 554.11 | 438.52 | 0.00 | 0.00 | 0.00 |
February | 429.43 | 122.46 | 306.97 | 691.46 | 368.90 | 0.00 | 0.00 | 0.00 |
March | 508.67 | 150.59 | 358.08 | 918.21 | 288.40 | 0.00 | 0.00 | 0.00 |
April | 555.89 | 156.18 | 399.72 | 1157.63 | 189.02 | 0.00 | 0.00 | 0.00 |
May | 605.08 | 181.13 | 423.96 | 1534.66 | 51.15 | 0.00 | 0.00 | 0.00 |
June | 625.30 | 197.11 | 428.19 | 1686.50 | 11.76 | 0.00 | 0.00 | 0.00 |
July | 573.65 | 164.11 | 409.54 | 1795.27 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 588.50 | 178.93 | 409.57 | 1848.90 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 559.82 | 175.88 | 383.94 | 1515.94 | 18.56 | 0.00 | 0.00 | 0.00 |
October | 497.51 | 160.71 | 336.80 | 1176.13 | 80.06 | 0.00 | 0.00 | 0.00 |
November | 427.55 | 139.82 | 287.73 | 853.85 | 210.21 | 0.00 | 0.00 | 0.00 |
December | 357.93 | 108.19 | 249.73 | 585.15 | 361.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 509.07 | 153.70 | 355.37 | 1196.07 | 167.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.93 | 108.01 | 249.73 | 554.11 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 625.30 | 197.11 | 428.19 | 1848.90 | 438.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.65 | 253.61 | 0.00 | 0.00 | 0.00 |
February | 121.49 | 0.00 | 121.49 | 167.09 | 205.80 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.95 | 150.81 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.90 | 354.62 | 91.24 | 0.00 | 0.00 | 0.00 |
May | 176.97 | 5.19 | 171.78 | 534.45 | 22.36 | 0.00 | 0.00 | 0.00 |
June | 189.48 | 10.52 | 178.96 | 614.83 | 5.63 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 685.09 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 670.49 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.71 | 10.23 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.80 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 112.20 | 0.00 | 112.20 | 224.64 | 120.61 | 0.00 | 0.00 | 0.00 |
December | 98.92 | 0.00 | 98.92 | 131.50 | 211.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.18 | 384.91 | 92.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.92 | 0.00 | 98.92 | 117.65 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.48 | 10.52 | 178.96 | 685.09 | 253.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.66 | 253.62 | 0.00 | 0.00 | 0.00 |
February | 121.50 | 0.00 | 121.50 | 167.09 | 205.81 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.96 | 150.81 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.91 | 354.64 | 91.25 | 0.00 | 0.00 | 0.00 |
May | 176.98 | 5.19 | 171.79 | 534.47 | 22.36 | 0.00 | 0.00 | 0.00 |
June | 189.49 | 10.52 | 178.97 | 614.86 | 5.63 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 685.13 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 670.53 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.74 | 10.23 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.82 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 112.21 | 0.00 | 112.21 | 224.65 | 120.62 | 0.00 | 0.00 | 0.00 |
December | 98.93 | 0.00 | 98.93 | 131.50 | 211.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.19 | 384.93 | 92.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.93 | 0.00 | 98.93 | 117.66 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.49 | 10.52 | 178.97 | 685.13 | 253.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.66 | 253.62 | 0.00 | 0.00 | 0.00 |
February | 121.50 | 0.00 | 121.50 | 167.09 | 205.81 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.96 | 150.81 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.91 | 354.64 | 91.25 | 0.00 | 0.00 | 0.00 |
May | 176.98 | 5.19 | 171.79 | 534.47 | 22.36 | 0.00 | 0.00 | 0.00 |
June | 189.49 | 10.52 | 178.97 | 614.86 | 5.63 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 685.13 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 670.53 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.74 | 10.23 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.82 | 44.57 | 0.00 | 0.00 | 0.00 |
November | 112.21 | 0.00 | 112.21 | 224.65 | 120.62 | 0.00 | 0.00 | 0.00 |
December | 98.93 | 0.00 | 98.93 | 131.50 | 211.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.19 | 384.93 | 92.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.93 | 0.00 | 98.93 | 117.66 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.49 | 10.52 | 178.97 | 685.13 | 253.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 368.88 | 111.60 | 257.28 | 498.85 | 459.52 | 0.00 | 0.00 | 0.00 |
February | 402.00 | 108.94 | 293.05 | 613.82 | 378.16 | 0.00 | 0.00 | 0.00 |
March | 444.05 | 109.44 | 334.61 | 788.73 | 280.45 | 0.00 | 0.00 | 0.00 |
April | 540.65 | 157.53 | 383.12 | 1128.51 | 174.37 | 0.00 | 0.00 | 0.00 |
May | 604.19 | 192.50 | 411.69 | 1519.60 | 43.65 | 0.00 | 0.00 | 0.00 |
June | 591.71 | 180.95 | 410.76 | 1600.79 | 10.59 | 0.00 | 0.00 | 0.00 |
July | 552.27 | 159.22 | 393.05 | 1727.35 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 565.51 | 173.56 | 391.95 | 1774.99 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 531.65 | 164.33 | 367.32 | 1434.57 | 19.02 | 0.00 | 0.00 | 0.00 |
October | 482.42 | 157.61 | 324.81 | 1119.68 | 83.07 | 0.00 | 0.00 | 0.00 |
November | 404.27 | 128.05 | 276.22 | 774.19 | 223.75 | 0.00 | 0.00 | 0.00 |
December | 327.22 | 89.77 | 237.44 | 486.53 | 386.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.89 | 144.60 | 340.28 | 1125.25 | 170.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.22 | 89.77 | 237.44 | 486.53 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 604.19 | 192.50 | 411.69 | 1774.99 | 459.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.59 | 4.41 | 10.17 | 19.72 | 18.17 | 0.00 | 0.00 | 0.00 |
February | 15.89 | 4.31 | 11.59 | 24.27 | 14.95 | 0.00 | 0.00 | 0.00 |
March | 17.56 | 4.33 | 13.23 | 31.19 | 11.09 | 0.00 | 0.00 | 0.00 |
April | 21.38 | 6.23 | 15.15 | 44.62 | 6.89 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 7.61 | 16.28 | 60.08 | 1.73 | 0.00 | 0.00 | 0.00 |
June | 23.40 | 7.15 | 16.24 | 63.29 | 0.42 | 0.00 | 0.00 | 0.00 |
July | 21.84 | 6.30 | 15.54 | 68.30 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.36 | 6.86 | 15.50 | 70.18 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21.02 | 6.50 | 14.52 | 56.72 | 0.75 | 0.00 | 0.00 | 0.00 |
October | 19.07 | 6.23 | 12.84 | 44.27 | 3.28 | 0.00 | 0.00 | 0.00 |
November | 15.98 | 5.06 | 10.92 | 30.61 | 8.85 | 0.00 | 0.00 | 0.00 |
December | 12.94 | 3.55 | 9.39 | 19.24 | 15.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.17 | 5.72 | 13.45 | 44.49 | 6.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.94 | 3.55 | 9.39 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.89 | 7.61 | 16.28 | 70.18 | 18.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.55 | 161.05 | 181.50 | 541.83 | 249.65 | 0.00 | 0.00 | 0.00 |
February | 321.67 | 131.57 | 190.09 | 544.43 | 208.78 | 0.00 | 0.00 | 0.00 |
March | 264.75 | 71.88 | 192.87 | 503.28 | 156.04 | 0.00 | 0.00 | 0.00 |
April | 208.11 | 22.06 | 186.05 | 470.71 | 94.61 | 0.00 | 0.00 | 0.00 |
May | 176.29 | 2.70 | 173.59 | 529.51 | 23.26 | 0.00 | 0.00 | 0.00 |
June | 166.02 | 0.21 | 165.82 | 558.40 | 4.95 | 0.00 | 0.00 | 0.00 |
July | 166.02 | 1.41 | 164.61 | 658.95 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 192.57 | 13.64 | 178.92 | 731.83 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 253.90 | 58.19 | 195.71 | 724.42 | 11.44 | 0.00 | 0.00 | 0.00 |
October | 332.41 | 132.15 | 200.26 | 755.47 | 48.92 | 0.00 | 0.00 | 0.00 |
November | 366.71 | 176.78 | 189.93 | 705.43 | 125.95 | 0.00 | 0.00 | 0.00 |
December | 340.42 | 168.16 | 172.26 | 573.19 | 211.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.59 | 78.03 | 182.55 | 608.57 | 94.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.02 | 0.21 | 164.61 | 470.71 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.71 | 176.78 | 200.26 | 755.47 | 249.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.55 | 161.05 | 181.50 | 541.83 | 249.65 | 0.00 | 0.00 | 0.00 |
February | 321.67 | 131.57 | 190.09 | 544.43 | 208.78 | 0.00 | 0.00 | 0.00 |
March | 264.75 | 71.88 | 192.87 | 503.28 | 156.04 | 0.00 | 0.00 | 0.00 |
April | 208.11 | 22.06 | 186.05 | 470.71 | 94.61 | 0.00 | 0.00 | 0.00 |
May | 176.29 | 2.70 | 173.59 | 529.51 | 23.26 | 0.00 | 0.00 | 0.00 |
June | 166.02 | 0.21 | 165.82 | 558.40 | 4.95 | 0.00 | 0.00 | 0.00 |
July | 166.02 | 1.41 | 164.61 | 658.95 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 192.57 | 13.64 | 178.92 | 731.83 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 253.90 | 58.19 | 195.71 | 724.42 | 11.44 | 0.00 | 0.00 | 0.00 |
October | 332.41 | 132.15 | 200.26 | 755.47 | 48.92 | 0.00 | 0.00 | 0.00 |
November | 366.71 | 176.78 | 189.93 | 705.43 | 125.95 | 0.00 | 0.00 | 0.00 |
December | 340.42 | 168.16 | 172.26 | 573.19 | 211.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.59 | 78.03 | 182.55 | 608.57 | 94.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.02 | 0.21 | 164.61 | 470.71 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.71 | 176.78 | 200.26 | 755.47 | 249.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.52 | 161.04 | 181.49 | 541.79 | 249.63 | 0.00 | 0.00 | 0.00 |
February | 321.65 | 131.57 | 190.08 | 544.40 | 208.77 | 0.00 | 0.00 | 0.00 |
March | 264.73 | 71.87 | 192.86 | 503.25 | 156.03 | 0.00 | 0.00 | 0.00 |
April | 208.10 | 22.06 | 186.04 | 470.68 | 94.60 | 0.00 | 0.00 | 0.00 |
May | 176.28 | 2.70 | 173.58 | 529.48 | 23.26 | 0.00 | 0.00 | 0.00 |
June | 166.01 | 0.21 | 165.81 | 558.36 | 4.95 | 0.00 | 0.00 | 0.00 |
July | 166.01 | 1.41 | 164.60 | 658.90 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 192.56 | 13.64 | 178.91 | 731.79 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 253.89 | 58.19 | 195.70 | 724.38 | 11.44 | 0.00 | 0.00 | 0.00 |
October | 332.39 | 132.14 | 200.24 | 755.42 | 48.92 | 0.00 | 0.00 | 0.00 |
November | 366.69 | 176.77 | 189.92 | 705.39 | 125.95 | 0.00 | 0.00 | 0.00 |
December | 340.40 | 168.15 | 172.25 | 573.16 | 211.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.57 | 78.03 | 182.54 | 608.53 | 94.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.01 | 0.21 | 164.60 | 470.68 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.69 | 176.77 | 200.24 | 755.42 | 249.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 361.76 | 103.90 | 257.86 | 518.01 | 492.66 | 0.00 | 0.00 | 0.00 |
February | 413.09 | 117.80 | 295.29 | 658.58 | 402.67 | 0.00 | 0.00 | 0.00 |
March | 489.32 | 144.86 | 344.45 | 887.05 | 302.00 | 0.00 | 0.00 | 0.00 |
April | 534.74 | 150.23 | 384.51 | 1123.52 | 190.15 | 0.00 | 0.00 | 0.00 |
May | 582.06 | 174.23 | 407.83 | 1484.03 | 50.98 | 0.00 | 0.00 | 0.00 |
June | 601.51 | 189.61 | 411.90 | 1622.68 | 12.59 | 0.00 | 0.00 | 0.00 |
July | 551.82 | 157.87 | 393.96 | 1722.50 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 566.11 | 172.12 | 393.99 | 1766.24 | 0.12 | 0.00 | 0.00 | 0.00 |
September | 538.52 | 169.19 | 369.33 | 1446.46 | 23.15 | 0.00 | 0.00 | 0.00 |
October | 478.58 | 154.59 | 323.99 | 1119.74 | 94.84 | 0.00 | 0.00 | 0.00 |
November | 411.28 | 134.50 | 276.78 | 809.00 | 243.99 | 0.00 | 0.00 | 0.00 |
December | 344.31 | 104.08 | 240.23 | 546.88 | 413.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.70 | 147.85 | 341.85 | 1144.84 | 184.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.31 | 103.90 | 240.23 | 518.01 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.51 | 189.61 | 411.90 | 1766.24 | 492.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.30 | 4.11 | 10.20 | 20.48 | 19.48 | 0.00 | 0.00 | 0.00 |
February | 16.33 | 4.66 | 11.68 | 26.04 | 15.92 | 0.00 | 0.00 | 0.00 |
March | 19.35 | 5.73 | 13.62 | 35.07 | 11.94 | 0.00 | 0.00 | 0.00 |
April | 21.14 | 5.94 | 15.20 | 44.42 | 7.52 | 0.00 | 0.00 | 0.00 |
May | 23.01 | 6.89 | 16.13 | 58.68 | 2.02 | 0.00 | 0.00 | 0.00 |
June | 23.78 | 7.50 | 16.29 | 64.16 | 0.50 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 6.24 | 15.58 | 68.11 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.38 | 6.81 | 15.58 | 69.84 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21.29 | 6.69 | 14.60 | 57.19 | 0.92 | 0.00 | 0.00 | 0.00 |
October | 18.92 | 6.11 | 12.81 | 44.27 | 3.75 | 0.00 | 0.00 | 0.00 |
November | 16.26 | 5.32 | 10.94 | 31.99 | 9.65 | 0.00 | 0.00 | 0.00 |
December | 13.61 | 4.12 | 9.50 | 21.62 | 16.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.36 | 5.85 | 13.52 | 45.27 | 7.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.61 | 4.11 | 9.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.78 | 7.50 | 16.29 | 69.84 | 19.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.97 | 0.00 | 317.97 | 361.18 | 719.69 | 0.00 | 0.00 | 0.00 |
February | 364.49 | 0.00 | 364.49 | 502.61 | 597.91 | 0.00 | 0.00 | 0.00 |
March | 418.66 | 0.00 | 418.66 | 725.76 | 453.62 | 0.00 | 0.00 | 0.00 |
April | 471.70 | 0.97 | 470.73 | 1054.68 | 282.99 | 0.00 | 0.00 | 0.00 |
May | 530.94 | 15.57 | 515.37 | 1600.28 | 70.98 | 0.00 | 0.00 | 0.00 |
June | 568.47 | 31.56 | 536.91 | 1849.76 | 17.67 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 15.03 | 506.60 | 2069.49 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 485.59 | 4.02 | 481.57 | 2037.91 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 442.33 | 0.05 | 442.28 | 1531.50 | 26.37 | 0.00 | 0.00 | 0.00 |
October | 392.11 | 0.00 | 392.11 | 1095.44 | 119.01 | 0.00 | 0.00 | 0.00 |
November | 336.62 | 0.00 | 336.62 | 692.83 | 330.07 | 0.00 | 0.00 | 0.00 |
December | 296.79 | 0.00 | 296.79 | 407.47 | 587.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 429.19 | 5.62 | 423.57 | 1164.82 | 265.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.79 | 0.00 | 296.79 | 361.18 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.47 | 31.56 | 536.91 | 2069.49 | 719.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 383.47 | 116.02 | 267.45 | 525.55 | 445.73 | 0.00 | 0.00 | 0.00 |
February | 417.90 | 113.25 | 304.65 | 639.15 | 374.34 | 0.00 | 0.00 | 0.00 |
March | 461.61 | 113.77 | 347.84 | 815.38 | 286.61 | 0.00 | 0.00 | 0.00 |
April | 562.03 | 163.76 | 398.27 | 1166.55 | 181.15 | 0.00 | 0.00 | 0.00 |
May | 628.09 | 200.11 | 427.97 | 1579.23 | 44.71 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 188.11 | 427.00 | 1669.13 | 10.19 | 0.00 | 0.00 | 0.00 |
July | 574.11 | 165.52 | 408.60 | 1807.73 | 0.17 | 0.00 | 0.00 | 0.00 |
August | 587.88 | 180.43 | 407.45 | 1865.43 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 552.68 | 170.83 | 381.85 | 1510.43 | 15.45 | 0.00 | 0.00 | 0.00 |
October | 501.50 | 163.84 | 337.66 | 1179.78 | 72.28 | 0.00 | 0.00 | 0.00 |
November | 420.26 | 133.12 | 287.14 | 817.22 | 206.88 | 0.00 | 0.00 | 0.00 |
December | 340.16 | 93.33 | 246.83 | 515.71 | 367.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 504.07 | 150.33 | 353.74 | 1177.39 | 166.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.16 | 93.33 | 246.83 | 515.71 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 628.09 | 200.11 | 427.97 | 1865.43 | 445.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1027.66 | 483.15 | 544.51 | 1624.20 | 696.72 | 0.00 | 0.00 | 0.00 |
February | 965.01 | 394.73 | 570.28 | 1626.43 | 593.27 | 0.00 | 0.00 | 0.00 |
March | 794.25 | 215.63 | 578.62 | 1500.76 | 461.31 | 0.00 | 0.00 | 0.00 |
April | 624.34 | 66.19 | 558.15 | 1404.34 | 288.92 | 0.00 | 0.00 | 0.00 |
May | 528.87 | 8.10 | 520.77 | 1597.62 | 71.43 | 0.00 | 0.00 | 0.00 |
June | 498.07 | 0.62 | 497.46 | 1698.57 | 14.18 | 0.00 | 0.00 | 0.00 |
July | 498.06 | 4.23 | 493.83 | 2010.73 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 577.71 | 40.93 | 536.78 | 2249.06 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 761.72 | 174.57 | 587.15 | 2218.39 | 26.15 | 0.00 | 0.00 | 0.00 |
October | 997.24 | 396.46 | 600.78 | 2298.49 | 118.48 | 0.00 | 0.00 | 0.00 |
November | 1100.16 | 530.36 | 569.80 | 2130.70 | 329.54 | 0.00 | 0.00 | 0.00 |
December | 1021.28 | 504.48 | 516.80 | 1723.48 | 579.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 781.77 | 234.10 | 547.67 | 1841.74 | 263.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 498.06 | 0.62 | 493.83 | 1404.34 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1100.16 | 530.36 | 600.78 | 2298.49 | 696.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.07 | 108.01 | 268.06 | 543.96 | 477.21 | 0.00 | 0.00 | 0.00 |
February | 429.43 | 122.46 | 306.97 | 684.96 | 398.02 | 0.00 | 0.00 | 0.00 |
March | 508.67 | 150.59 | 358.08 | 916.88 | 307.30 | 0.00 | 0.00 | 0.00 |
April | 555.89 | 156.18 | 399.72 | 1161.01 | 197.69 | 0.00 | 0.00 | 0.00 |
May | 605.08 | 181.13 | 423.96 | 1542.53 | 52.15 | 0.00 | 0.00 | 0.00 |
June | 625.30 | 197.11 | 428.19 | 1693.83 | 11.82 | 0.00 | 0.00 | 0.00 |
July | 573.65 | 164.11 | 409.54 | 1803.69 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 588.50 | 178.93 | 409.57 | 1856.28 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 559.82 | 175.88 | 383.94 | 1522.36 | 19.02 | 0.00 | 0.00 | 0.00 |
October | 497.51 | 160.71 | 336.80 | 1179.75 | 83.82 | 0.00 | 0.00 | 0.00 |
November | 427.55 | 139.82 | 287.73 | 852.32 | 225.61 | 0.00 | 0.00 | 0.00 |
December | 357.93 | 108.19 | 249.73 | 577.01 | 392.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 509.07 | 153.70 | 355.37 | 1197.50 | 179.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.93 | 108.01 | 249.73 | 543.96 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 625.30 | 197.11 | 428.19 | 1856.28 | 477.21 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.100983E+10 | 0.176554E+10 |
February | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.124163E+10 | 0.133808E+10 |
March | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.195226E+10 | 0.113892E+10 |
April | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.272346E+10 | 0.701757E+09 |
May | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.425817E+10 | 0.187546E+09 |
June | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.476660E+10 | 46379329.09 |
July | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.550691E+10 | 962966.09 |
August | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.542853E+10 | 222902.24 |
September | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.394791E+10 | 66559831.19 |
October | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.292376E+10 | 0.303739E+09 |
November | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.180448E+10 | 0.796894E+09 |
December | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.112492E+10 | 0.144351E+10 |
Annual Sum or Average | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.366885E+11 | 0.779012E+10 |
Minimum of Months | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.100983E+10 | 222902.24 |
Maximum of Months | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.550691E+10 | 0.176554E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.144168E+10 | 0.110853E+10 |
February | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.156477E+10 | 0.847262E+09 |
March | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.218962E+10 | 0.725748E+09 |
April | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.301453E+10 | 0.451827E+09 |
May | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.420643E+10 | 0.118365E+09 |
June | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.430334E+10 | 26845945.36 |
July | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.481337E+10 | 396672.51 |
August | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.497205E+10 | 85019.01 |
September | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.389542E+10 | 39099864.68 |
October | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.314809E+10 | 0.185312E+09 |
November | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.212314E+10 | 0.503280E+09 |
December | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.140727E+10 | 0.913779E+09 |
Annual Sum or Average | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.370797E+11 | 0.492053E+10 |
Minimum of Months | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.140727E+10 | 85019.01 |
Maximum of Months | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.497205E+10 | 0.110853E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.438779E+10 | 0.173200E+10 |
February | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.395206E+10 | 0.133928E+10 |
March | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.402163E+10 | 0.116302E+10 |
April | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.362702E+10 | 0.715652E+09 |
May | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.425016E+10 | 0.186912E+09 |
June | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.437681E+10 | 36418289.61 |
July | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.535058E+10 | 394777.35 |
August | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.599368E+10 | 123274.44 |
September | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.572279E+10 | 65724752.66 |
October | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.613617E+10 | 0.303168E+09 |
November | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.552265E+10 | 0.803970E+09 |
December | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.464279E+10 | 0.144472E+10 |
Annual Sum or Average | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.579841E+11 | 0.779139E+10 |
Minimum of Months | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.362702E+10 | 123274.44 |
Maximum of Months | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.613617E+10 | 0.173200E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.148412E+10 | 0.117453E+10 |
February | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.167279E+10 | 0.892435E+09 |
March | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.245933E+10 | 0.772452E+09 |
April | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.300057E+10 | 0.489941E+09 |
May | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.411043E+10 | 0.136991E+09 |
June | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.437141E+10 | 30485345.74 |
July | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.480844E+10 | 399341.04 |
August | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.495210E+10 | 231590.05 |
September | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.392933E+10 | 48102826.90 |
October | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.315014E+10 | 0.214424E+09 |
November | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.221318E+10 | 0.544852E+09 |
December | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.156726E+10 | 0.967434E+09 |
Annual Sum or Average | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.377191E+11 | 0.527227E+10 |
Minimum of Months | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.148412E+10 | 231590.05 |
Maximum of Months | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.495210E+10 | 0.117453E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283873E+09 | 0.00 | 0.283873E+09 | 0.315117E+09 | 0.679268E+09 |
February | 0.293910E+09 | 0.00 | 0.293910E+09 | 0.404213E+09 | 0.497878E+09 |
March | 0.373766E+09 | 0.00 | 0.373766E+09 | 0.653392E+09 | 0.403918E+09 |
April | 0.407528E+09 | 839690.24 | 0.406688E+09 | 0.919179E+09 | 0.236506E+09 |
May | 0.473999E+09 | 13902104.80 | 0.460097E+09 | 0.143146E+10 | 59891708.37 |
June | 0.491135E+09 | 27266316.28 | 0.463868E+09 | 0.159364E+10 | 14602730.55 |
July | 0.465686E+09 | 13417543.97 | 0.452269E+09 | 0.183496E+10 | 372092.27 |
August | 0.433514E+09 | 3585590.35 | 0.429928E+09 | 0.179584E+10 | 83069.27 |
September | 0.382153E+09 | 43791.23 | 0.382109E+09 | 0.130043E+10 | 26517146.30 |
October | 0.350063E+09 | 0.00 | 0.350063E+09 | 0.955665E+09 | 0.119383E+09 |
November | 0.290827E+09 | 0.00 | 0.290827E+09 | 0.582277E+09 | 0.312628E+09 |
December | 0.264959E+09 | 0.00 | 0.264959E+09 | 0.352203E+09 | 0.566079E+09 |
Annual Sum or Average | 0.451141E+10 | 59055036.89 | 0.445236E+10 | 0.121384E+11 | 0.291713E+10 |
Minimum of Months | 0.264959E+09 | 0.00 | 0.264959E+09 | 0.315117E+09 | 83069.27 |
Maximum of Months | 0.491135E+09 | 27266316.28 | 0.463868E+09 | 0.183496E+10 | 0.679268E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283884E+09 | 0.00 | 0.283884E+09 | 0.315128E+09 | 0.679305E+09 |
February | 0.293921E+09 | 0.00 | 0.293921E+09 | 0.404229E+09 | 0.497905E+09 |
March | 0.373780E+09 | 0.00 | 0.373780E+09 | 0.653421E+09 | 0.403938E+09 |
April | 0.407544E+09 | 839712.81 | 0.406704E+09 | 0.919224E+09 | 0.236516E+09 |
May | 0.474018E+09 | 13902478.50 | 0.460115E+09 | 0.143154E+10 | 59892971.23 |
June | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.159373E+10 | 14602376.77 |
July | 0.465704E+09 | 13417904.64 | 0.452287E+09 | 0.183506E+10 | 372034.71 |
August | 0.433531E+09 | 3585686.74 | 0.429946E+09 | 0.179594E+10 | 83046.32 |
September | 0.382168E+09 | 43792.41 | 0.382124E+09 | 0.130050E+10 | 26517352.07 |
October | 0.350076E+09 | 0.00 | 0.350076E+09 | 0.955717E+09 | 0.119387E+09 |
November | 0.290838E+09 | 0.00 | 0.290838E+09 | 0.582305E+09 | 0.312642E+09 |
December | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.352216E+09 | 0.566109E+09 |
Annual Sum or Average | 0.451159E+10 | 59056624.30 | 0.445253E+10 | 0.121390E+11 | 0.291727E+10 |
Minimum of Months | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.315128E+09 | 83046.32 |
Maximum of Months | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.183506E+10 | 0.679305E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283884E+09 | 0.00 | 0.283884E+09 | 0.315128E+09 | 0.679305E+09 |
February | 0.293921E+09 | 0.00 | 0.293921E+09 | 0.404229E+09 | 0.497905E+09 |
March | 0.373780E+09 | 0.00 | 0.373780E+09 | 0.653421E+09 | 0.403938E+09 |
April | 0.407544E+09 | 839712.81 | 0.406704E+09 | 0.919224E+09 | 0.236516E+09 |
May | 0.474018E+09 | 13902478.50 | 0.460115E+09 | 0.143154E+10 | 59892971.23 |
June | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.159373E+10 | 14602376.77 |
July | 0.465704E+09 | 13417904.64 | 0.452287E+09 | 0.183506E+10 | 372034.71 |
August | 0.433531E+09 | 3585686.74 | 0.429946E+09 | 0.179594E+10 | 83046.32 |
September | 0.382168E+09 | 43792.41 | 0.382124E+09 | 0.130050E+10 | 26517352.07 |
October | 0.350076E+09 | 0.00 | 0.350076E+09 | 0.955717E+09 | 0.119387E+09 |
November | 0.290838E+09 | 0.00 | 0.290838E+09 | 0.582305E+09 | 0.312642E+09 |
December | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.352216E+09 | 0.566109E+09 |
Annual Sum or Average | 0.451159E+10 | 59056624.30 | 0.445253E+10 | 0.121390E+11 | 0.291727E+10 |
Minimum of Months | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.315128E+09 | 83046.32 |
Maximum of Months | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.183506E+10 | 0.679305E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.988016E+09 | 0.298922E+09 | 0.689094E+09 | 0.133612E+10 | 0.123078E+10 |
February | 0.972513E+09 | 0.263555E+09 | 0.708958E+09 | 0.148495E+10 | 0.914851E+09 |
March | 0.118934E+10 | 0.293127E+09 | 0.896211E+09 | 0.211253E+10 | 0.751149E+09 |
April | 0.140136E+10 | 0.408307E+09 | 0.993048E+09 | 0.292511E+10 | 0.451978E+09 |
May | 0.161825E+10 | 0.515582E+09 | 0.110267E+10 | 0.407009E+10 | 0.116924E+09 |
June | 0.153371E+10 | 0.469023E+09 | 0.106469E+10 | 0.414926E+10 | 27440794.31 |
July | 0.147920E+10 | 0.426447E+09 | 0.105275E+10 | 0.462654E+10 | 676171.76 |
August | 0.151467E+10 | 0.464871E+09 | 0.104980E+10 | 0.475415E+10 | 170476.65 |
September | 0.137803E+10 | 0.425931E+09 | 0.952101E+09 | 0.371840E+10 | 49290130.63 |
October | 0.129211E+10 | 0.422130E+09 | 0.869977E+09 | 0.299895E+10 | 0.222494E+09 |
November | 0.104786E+10 | 0.331908E+09 | 0.715954E+09 | 0.200669E+10 | 0.579970E+09 |
December | 0.876414E+09 | 0.240452E+09 | 0.635962E+09 | 0.130312E+10 | 0.103555E+10 |
Annual Sum or Average | 0.152915E+11 | 0.456025E+10 | 0.107312E+11 | 0.354859E+11 | 0.538127E+10 |
Minimum of Months | 0.876414E+09 | 0.240452E+09 | 0.635962E+09 | 0.130312E+10 | 170476.65 |
Maximum of Months | 0.161825E+10 | 0.515582E+09 | 0.110267E+10 | 0.475415E+10 | 0.123078E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39065258.48 | 11819103.90 | 27246154.59 | 52828820.73 | 48663928.76 |
February | 38452275.37 | 10420713.04 | 28031562.33 | 58713747.40 | 36172376.73 |
March | 47025345.96 | 11589972.09 | 35435373.87 | 83527713.36 | 29699758.57 |
April | 55408338.03 | 16144095.39 | 39264242.64 | 0.115656E+09 | 17870814.32 |
May | 63984314.02 | 20385644.58 | 43598669.44 | 0.160928E+09 | 4623081.68 |
June | 60641450.18 | 18544738.24 | 42096711.94 | 0.164058E+09 | 1084984.30 |
July | 58486056.92 | 16861338.40 | 41624718.52 | 0.182929E+09 | 26735.22 |
August | 59888712.98 | 18380572.30 | 41508140.68 | 0.187975E+09 | 6740.49 |
September | 54486149.10 | 16840947.48 | 37645201.62 | 0.147022E+09 | 1948887.39 |
October | 51088757.59 | 16690654.48 | 34398103.11 | 0.118576E+09 | 8797223.30 |
November | 41431482.81 | 13123324.59 | 28308158.22 | 79342791.76 | 22931476.83 |
December | 34652617.29 | 9507238.85 | 25145378.45 | 51524017.25 | 40944727.51 |
Annual Sum or Average | 0.604611E+09 | 0.180308E+09 | 0.424302E+09 | 0.140308E+10 | 0.212771E+09 |
Minimum of Months | 34652617.29 | 9507238.85 | 25145378.45 | 51524017.25 | 6740.49 |
Maximum of Months | 63984314.02 | 20385644.58 | 43598669.44 | 0.187975E+09 | 48663928.76 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917476E+09 | 0.431346E+09 | 0.486131E+09 | 0.145123E+10 | 0.668653E+09 |
February | 0.778174E+09 | 0.318306E+09 | 0.459868E+09 | 0.131709E+10 | 0.505090E+09 |
March | 0.709096E+09 | 0.192515E+09 | 0.516581E+09 | 0.134798E+10 | 0.417949E+09 |
April | 0.539423E+09 | 57188570.39 | 0.482235E+09 | 0.122008E+10 | 0.245220E+09 |
May | 0.472171E+09 | 7230741.31 | 0.464940E+09 | 0.141824E+10 | 62301854.03 |
June | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.144736E+10 | 12821079.33 |
July | 0.444665E+09 | 3778245.47 | 0.440887E+09 | 0.176492E+10 | 190556.89 |
August | 0.515775E+09 | 36544326.84 | 0.479230E+09 | 0.196015E+10 | 112639.88 |
September | 0.658116E+09 | 0.150825E+09 | 0.507290E+09 | 0.187770E+10 | 29656675.93 |
October | 0.890320E+09 | 0.353951E+09 | 0.536369E+09 | 0.202344E+10 | 0.131034E+09 |
November | 0.950519E+09 | 0.458219E+09 | 0.492300E+09 | 0.182848E+10 | 0.326472E+09 |
December | 0.911781E+09 | 0.450391E+09 | 0.461390E+09 | 0.153524E+10 | 0.567086E+09 |
Annual Sum or Average | 0.821785E+10 | 0.246083E+10 | 0.575702E+10 | 0.191919E+11 | 0.296659E+10 |
Minimum of Months | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.122008E+10 | 112639.88 |
Maximum of Months | 0.950519E+09 | 0.458219E+09 | 0.536369E+09 | 0.202344E+10 | 0.668653E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917476E+09 | 0.431346E+09 | 0.486131E+09 | 0.145123E+10 | 0.668653E+09 |
February | 0.778174E+09 | 0.318306E+09 | 0.459868E+09 | 0.131709E+10 | 0.505090E+09 |
March | 0.709096E+09 | 0.192515E+09 | 0.516581E+09 | 0.134798E+10 | 0.417949E+09 |
April | 0.539423E+09 | 57188570.39 | 0.482235E+09 | 0.122008E+10 | 0.245220E+09 |
May | 0.472171E+09 | 7230741.31 | 0.464940E+09 | 0.141824E+10 | 62301854.03 |
June | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.144736E+10 | 12821079.33 |
July | 0.444665E+09 | 3778245.47 | 0.440887E+09 | 0.176492E+10 | 190556.89 |
August | 0.515775E+09 | 36544326.84 | 0.479230E+09 | 0.196015E+10 | 112639.88 |
September | 0.658116E+09 | 0.150825E+09 | 0.507290E+09 | 0.187770E+10 | 29656675.93 |
October | 0.890320E+09 | 0.353951E+09 | 0.536369E+09 | 0.202344E+10 | 0.131034E+09 |
November | 0.950519E+09 | 0.458219E+09 | 0.492300E+09 | 0.182848E+10 | 0.326472E+09 |
December | 0.911781E+09 | 0.450391E+09 | 0.461390E+09 | 0.153524E+10 | 0.567086E+09 |
Annual Sum or Average | 0.821785E+10 | 0.246083E+10 | 0.575702E+10 | 0.191919E+11 | 0.296659E+10 |
Minimum of Months | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.122008E+10 | 112639.88 |
Maximum of Months | 0.950519E+09 | 0.458219E+09 | 0.536369E+09 | 0.202344E+10 | 0.668653E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917418E+09 | 0.431318E+09 | 0.486100E+09 | 0.145114E+10 | 0.668611E+09 |
February | 0.778125E+09 | 0.318286E+09 | 0.459839E+09 | 0.131700E+10 | 0.505059E+09 |
March | 0.709051E+09 | 0.192502E+09 | 0.516549E+09 | 0.134790E+10 | 0.417922E+09 |
April | 0.539389E+09 | 57184956.40 | 0.482204E+09 | 0.122000E+10 | 0.245205E+09 |
May | 0.472141E+09 | 7230284.37 | 0.464911E+09 | 0.141815E+10 | 62297916.90 |
June | 0.430305E+09 | 532512.00 | 0.429773E+09 | 0.144727E+10 | 12820269.11 |
July | 0.444637E+09 | 3778006.70 | 0.440859E+09 | 0.176481E+10 | 190544.84 |
August | 0.515742E+09 | 36542017.44 | 0.479200E+09 | 0.196002E+10 | 112632.76 |
September | 0.658074E+09 | 0.150816E+09 | 0.507258E+09 | 0.187758E+10 | 29654801.80 |
October | 0.890264E+09 | 0.353928E+09 | 0.536335E+09 | 0.202331E+10 | 0.131026E+09 |
November | 0.950458E+09 | 0.458190E+09 | 0.492268E+09 | 0.182836E+10 | 0.326452E+09 |
December | 0.911724E+09 | 0.450362E+09 | 0.461361E+09 | 0.153514E+10 | 0.567050E+09 |
Annual Sum or Average | 0.821733E+10 | 0.246067E+10 | 0.575666E+10 | 0.191907E+11 | 0.296640E+10 |
Minimum of Months | 0.430305E+09 | 532512.00 | 0.429773E+09 | 0.122000E+10 | 112632.76 |
Maximum of Months | 0.950458E+09 | 0.458190E+09 | 0.536335E+09 | 0.202331E+10 | 0.668611E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.968932E+09 | 0.278284E+09 | 0.690647E+09 | 0.138744E+10 | 0.131955E+10 |
February | 0.999348E+09 | 0.284973E+09 | 0.714375E+09 | 0.159325E+10 | 0.974131E+09 |
March | 0.131059E+10 | 0.388002E+09 | 0.922587E+09 | 0.237588E+10 | 0.808871E+09 |
April | 0.138605E+10 | 0.389404E+09 | 0.996644E+09 | 0.291216E+10 | 0.492872E+09 |
May | 0.155900E+10 | 0.466668E+09 | 0.109233E+10 | 0.397483E+10 | 0.136540E+09 |
June | 0.155912E+10 | 0.491475E+09 | 0.106765E+10 | 0.420599E+10 | 32623964.88 |
July | 0.147800E+10 | 0.422826E+09 | 0.105518E+10 | 0.461355E+10 | 856007.86 |
August | 0.151627E+10 | 0.461009E+09 | 0.105526E+10 | 0.473070E+10 | 331186.52 |
September | 0.139583E+10 | 0.438529E+09 | 0.957304E+09 | 0.374922E+10 | 59995509.78 |
October | 0.128184E+10 | 0.414067E+09 | 0.867769E+09 | 0.299910E+10 | 0.254018E+09 |
November | 0.106604E+10 | 0.348630E+09 | 0.717415E+09 | 0.209693E+10 | 0.632415E+09 |
December | 0.922194E+09 | 0.278762E+09 | 0.643432E+09 | 0.146476E+10 | 0.110786E+10 |
Annual Sum or Average | 0.154432E+11 | 0.466263E+10 | 0.107806E+11 | 0.361038E+11 | 0.582006E+10 |
Minimum of Months | 0.922194E+09 | 0.278284E+09 | 0.643432E+09 | 0.138744E+10 | 331186.52 |
Maximum of Months | 0.155912E+10 | 0.491475E+09 | 0.109233E+10 | 0.473070E+10 | 0.131955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38310577.77 | 11003077.04 | 27307500.73 | 54858056.65 | 52173660.52 |
February | 39513211.75 | 11267528.36 | 28245683.39 | 62995365.12 | 38516241.67 |
March | 51819367.10 | 15341183.56 | 36478183.54 | 93940094.40 | 31981978.72 |
April | 54802937.33 | 15396622.59 | 39406314.74 | 0.115144E+09 | 19487670.79 |
May | 61641163.83 | 18451589.80 | 43189574.02 | 0.157161E+09 | 5398661.59 |
June | 61646131.46 | 19432416.19 | 42213715.27 | 0.166301E+09 | 1289912.95 |
July | 58438824.35 | 16718109.48 | 41720714.87 | 0.182416E+09 | 33844.82 |
August | 59951733.09 | 18227802.62 | 41723930.47 | 0.187047E+09 | 13094.49 |
September | 55189856.52 | 17338991.81 | 37850864.72 | 0.148241E+09 | 2372157.08 |
October | 50682477.21 | 16371773.25 | 34310703.96 | 0.118582E+09 | 10043608.87 |
November | 42150315.10 | 13784453.03 | 28365862.07 | 82910460.14 | 25005091.98 |
December | 36462607.41 | 11021956.80 | 25440650.61 | 57915041.55 | 43803772.81 |
Annual Sum or Average | 0.610609E+09 | 0.184356E+09 | 0.426254E+09 | 0.142751E+10 | 0.230120E+09 |
Minimum of Months | 36462607.41 | 11003077.04 | 25440650.61 | 54858056.65 | 13094.49 |
Maximum of Months | 61646131.46 | 19432416.19 | 43189574.02 | 0.187047E+09 | 52173660.52 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.967377E+09 | 0.192762E+10 |
February | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.121590E+10 | 0.144647E+10 |
March | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.194388E+10 | 0.121497E+10 |
April | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.273373E+10 | 0.733515E+09 |
May | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.428618E+10 | 0.190108E+09 |
June | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.479458E+10 | 45795580.33 |
July | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.554292E+10 | 1063799.02 |
August | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.545835E+10 | 194672.70 |
September | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.396966E+10 | 68363363.09 |
October | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.293402E+10 | 0.318751E+09 |
November | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.179582E+10 | 0.855541E+09 |
December | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.109137E+10 | 0.157247E+10 |
Annual Sum or Average | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.367338E+11 | 0.837486E+10 |
Minimum of Months | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.967377E+09 | 194672.70 |
Maximum of Months | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.554292E+10 | 0.192762E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.140764E+10 | 0.119383E+10 |
February | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.154623E+10 | 0.905604E+09 |
March | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.218392E+10 | 0.767650E+09 |
April | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.302370E+10 | 0.469533E+09 |
May | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.422980E+10 | 0.119740E+09 |
June | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.432639E+10 | 26422923.26 |
July | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.484183E+10 | 462858.86 |
August | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.499635E+10 | 76110.84 |
September | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.391503E+10 | 40056068.19 |
October | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.315993E+10 | 0.193594E+09 |
November | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.211824E+10 | 0.536225E+09 |
December | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.138127E+10 | 0.983909E+09 |
Annual Sum or Average | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.371303E+11 | 0.523711E+10 |
Minimum of Months | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.138127E+10 | 76110.84 |
Maximum of Months | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.499635E+10 | 0.119383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.435025E+10 | 0.186609E+10 |
February | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.393465E+10 | 0.143523E+10 |
March | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.401962E+10 | 0.123557E+10 |
April | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.364004E+10 | 0.748870E+09 |
May | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.427907E+10 | 0.191327E+09 |
June | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.440268E+10 | 36751429.17 |
July | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.538553E+10 | 478634.01 |
August | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.602387E+10 | 109307.17 |
September | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.575006E+10 | 67782339.32 |
October | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.615628E+10 | 0.317345E+09 |
November | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.552278E+10 | 0.854174E+09 |
December | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.461616E+10 | 0.155166E+10 |
Annual Sum or Average | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.580810E+11 | 0.830539E+10 |
Minimum of Months | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.364004E+10 | 109307.17 |
Maximum of Months | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.615628E+10 | 0.186609E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.145693E+10 | 0.127815E+10 |
February | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.165705E+10 | 0.962884E+09 |
March | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.245578E+10 | 0.823082E+09 |
April | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.300934E+10 | 0.512407E+09 |
May | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.413153E+10 | 0.139668E+09 |
June | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.439040E+10 | 30634504.33 |
July | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.483101E+10 | 484542.58 |
August | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.497186E+10 | 218307.54 |
September | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.394595E+10 | 49300608.50 |
October | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.315984E+10 | 0.224496E+09 |
November | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.220921E+10 | 0.584770E+09 |
December | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.154545E+10 | 0.105087E+10 |
Annual Sum or Average | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.377644E+11 | 0.565696E+10 |
Minimum of Months | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.145693E+10 | 218307.54 |
Maximum of Months | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.497186E+10 | 0.127815E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 377.03 | 659.18 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 513.24 | 553.11 | 364.49 | 0.00 | 364.49 | 0.00 | 0.00 |
March | 728.89 | 425.23 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1050.72 | 270.74 | 471.70 | 0.97 | 470.73 | 0.00 | 0.00 |
May | 1589.82 | 70.02 | 530.94 | 15.57 | 515.37 | 0.00 | 0.00 |
June | 1838.97 | 17.89 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
July | 2056.04 | 0.36 | 521.63 | 15.03 | 506.60 | 0.00 | 0.00 |
August | 2026.78 | 0.08 | 485.59 | 4.02 | 481.57 | 0.00 | 0.00 |
September | 1523.11 | 25.68 | 442.33 | 0.05 | 442.28 | 0.00 | 0.00 |
October | 1091.61 | 113.40 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 696.17 | 307.44 | 336.62 | 0.00 | 336.62 | 0.00 | 0.00 |
December | 420.00 | 538.95 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Annual Sum or Average | 1163.38 | 247.02 | 429.19 | 5.62 | 423.57 | 0.00 | 0.00 |
Minimum of Months | 377.03 | 0.08 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Maximum of Months | 2056.04 | 659.18 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 538.26 | 413.88 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 646.81 | 350.22 | 417.90 | 113.25 | 304.65 | 0.00 | 0.00 |
March | 817.51 | 270.96 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1163.01 | 174.32 | 562.03 | 163.76 | 398.27 | 0.00 | 0.00 |
May | 1570.50 | 44.19 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1660.24 | 10.36 | 615.11 | 188.11 | 427.00 | 0.00 | 0.00 |
July | 1797.11 | 0.15 | 574.11 | 165.52 | 408.60 | 0.00 | 0.00 |
August | 1856.35 | 0.03 | 587.88 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1502.86 | 15.08 | 552.68 | 170.83 | 381.85 | 0.00 | 0.00 |
October | 1175.36 | 69.19 | 501.50 | 163.84 | 337.66 | 0.00 | 0.00 |
November | 819.11 | 194.17 | 420.26 | 133.12 | 287.14 | 0.00 | 0.00 |
December | 525.41 | 341.17 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1175.79 | 156.03 | 504.07 | 150.33 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 525.41 | 0.03 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1856.35 | 413.88 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1638.21 | 646.66 | 1027.66 | 483.15 | 544.51 | 0.00 | 0.00 |
February | 1633.62 | 553.61 | 965.01 | 394.73 | 570.28 | 0.00 | 0.00 |
March | 1501.51 | 434.22 | 794.25 | 215.63 | 578.62 | 0.00 | 0.00 |
April | 1399.31 | 276.10 | 624.34 | 66.19 | 558.15 | 0.00 | 0.00 |
May | 1586.83 | 69.79 | 528.87 | 8.10 | 520.77 | 0.00 | 0.00 |
June | 1688.58 | 14.05 | 498.07 | 0.62 | 497.46 | 0.00 | 0.00 |
July | 1997.68 | 0.15 | 498.06 | 4.23 | 493.83 | 0.00 | 0.00 |
August | 2237.79 | 0.05 | 577.71 | 40.93 | 536.78 | 0.00 | 0.00 |
September | 2207.87 | 25.36 | 761.72 | 174.57 | 587.15 | 0.00 | 0.00 |
October | 2290.98 | 113.19 | 997.24 | 396.46 | 600.78 | 0.00 | 0.00 |
November | 2130.65 | 310.17 | 1100.16 | 530.36 | 569.80 | 0.00 | 0.00 |
December | 1733.42 | 539.40 | 1021.28 | 504.48 | 516.80 | 0.00 | 0.00 |
Annual Sum or Average | 1838.66 | 247.06 | 781.77 | 234.10 | 547.67 | 0.00 | 0.00 |
Minimum of Months | 1399.31 | 0.05 | 498.06 | 0.62 | 493.83 | 0.00 | 0.00 |
Maximum of Months | 2290.98 | 646.66 | 1100.16 | 530.36 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 554.11 | 438.52 | 376.07 | 108.01 | 268.06 | 0.00 | 0.00 |
February | 691.46 | 368.90 | 429.43 | 122.46 | 306.97 | 0.00 | 0.00 |
March | 918.21 | 288.40 | 508.67 | 150.59 | 358.08 | 0.00 | 0.00 |
April | 1157.63 | 189.02 | 555.89 | 156.18 | 399.72 | 0.00 | 0.00 |
May | 1534.66 | 51.15 | 605.08 | 181.13 | 423.96 | 0.00 | 0.00 |
June | 1686.50 | 11.76 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1795.27 | 0.15 | 573.65 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1848.90 | 0.09 | 588.50 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1515.94 | 18.56 | 559.82 | 175.88 | 383.94 | 0.00 | 0.00 |
October | 1176.13 | 80.06 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 853.85 | 210.21 | 427.55 | 139.82 | 287.73 | 0.00 | 0.00 |
December | 585.15 | 361.20 | 357.93 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1196.07 | 167.18 | 509.07 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 554.11 | 0.09 | 357.93 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1848.90 | 438.52 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.96 | 760.86 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 501.27 | 617.43 | 364.48 | 0.00 | 364.48 | 0.00 | 0.00 |
March | 731.87 | 452.43 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1063.90 | 273.74 | 471.69 | 0.97 | 470.72 | 0.00 | 0.00 |
May | 1603.40 | 67.08 | 530.93 | 15.57 | 515.36 | 0.00 | 0.00 |
June | 1844.56 | 16.90 | 568.46 | 31.56 | 536.90 | 0.00 | 0.00 |
July | 2055.36 | 0.42 | 521.62 | 15.03 | 506.59 | 0.00 | 0.00 |
August | 2011.54 | 0.09 | 485.58 | 4.02 | 481.56 | 0.00 | 0.00 |
September | 1505.18 | 30.69 | 442.32 | 0.05 | 442.27 | 0.00 | 0.00 |
October | 1070.45 | 133.72 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 673.95 | 361.85 | 336.61 | 0.00 | 336.61 | 0.00 | 0.00 |
December | 394.50 | 634.07 | 296.78 | 0.00 | 296.78 | 0.00 | 0.00 |
Annual Sum or Average | 1154.76 | 277.51 | 429.18 | 5.62 | 423.56 | 0.00 | 0.00 |
Minimum of Months | 352.96 | 0.09 | 296.78 | 0.00 | 296.78 | 0.00 | 0.00 |
Maximum of Months | 2055.36 | 760.86 | 568.46 | 31.56 | 536.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 518.57 | 477.69 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 638.09 | 393.11 | 417.89 | 113.25 | 304.64 | 0.00 | 0.00 |
March | 819.92 | 291.54 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1173.13 | 181.27 | 562.02 | 163.75 | 398.27 | 0.00 | 0.00 |
May | 1579.68 | 45.38 | 628.08 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1664.09 | 11.01 | 615.10 | 188.10 | 427.00 | 0.00 | 0.00 |
July | 1795.65 | 0.26 | 574.10 | 165.51 | 408.59 | 0.00 | 0.00 |
August | 1845.18 | 0.07 | 587.87 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1491.29 | 19.77 | 552.67 | 170.82 | 381.85 | 0.00 | 0.00 |
October | 1163.95 | 86.35 | 501.49 | 163.84 | 337.65 | 0.00 | 0.00 |
November | 804.80 | 232.60 | 420.25 | 133.11 | 287.14 | 0.00 | 0.00 |
December | 505.76 | 401.92 | 340.15 | 93.32 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1169.74 | 177.39 | 504.06 | 150.32 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 505.76 | 0.07 | 340.15 | 93.32 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1845.18 | 477.69 | 628.08 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1625.45 | 748.92 | 1027.62 | 483.13 | 544.49 | 0.00 | 0.00 |
February | 1633.26 | 626.34 | 964.98 | 394.72 | 570.26 | 0.00 | 0.00 |
March | 1509.80 | 468.12 | 794.22 | 215.63 | 578.60 | 0.00 | 0.00 |
April | 1412.10 | 283.81 | 624.32 | 66.19 | 558.13 | 0.00 | 0.00 |
May | 1588.50 | 69.78 | 528.85 | 8.10 | 520.76 | 0.00 | 0.00 |
June | 1675.15 | 14.84 | 498.06 | 0.62 | 497.44 | 0.00 | 0.00 |
July | 1976.79 | 0.21 | 498.05 | 4.23 | 493.81 | 0.00 | 0.00 |
August | 2195.46 | 0.13 | 577.69 | 40.93 | 536.76 | 0.00 | 0.00 |
September | 2173.22 | 34.32 | 761.69 | 174.56 | 587.13 | 0.00 | 0.00 |
October | 2266.35 | 146.76 | 997.20 | 396.44 | 600.76 | 0.00 | 0.00 |
November | 2116.25 | 377.85 | 1100.11 | 530.33 | 569.78 | 0.00 | 0.00 |
December | 1719.54 | 635.16 | 1021.24 | 504.46 | 516.78 | 0.00 | 0.00 |
Annual Sum or Average | 1825.68 | 282.20 | 781.74 | 234.09 | 547.65 | 0.00 | 0.00 |
Minimum of Months | 1412.10 | 0.13 | 498.05 | 0.62 | 493.81 | 0.00 | 0.00 |
Maximum of Months | 2266.35 | 748.92 | 1100.11 | 530.33 | 600.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 538.49 | 512.14 | 376.06 | 108.01 | 268.05 | 0.00 | 0.00 |
February | 684.62 | 418.59 | 429.42 | 122.45 | 306.97 | 0.00 | 0.00 |
March | 922.13 | 313.94 | 508.66 | 150.59 | 358.07 | 0.00 | 0.00 |
April | 1167.94 | 197.67 | 555.88 | 156.17 | 399.71 | 0.00 | 0.00 |
May | 1542.71 | 52.99 | 605.08 | 181.12 | 423.95 | 0.00 | 0.00 |
June | 1686.84 | 13.08 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1790.61 | 0.33 | 573.64 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1836.08 | 0.13 | 588.49 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1503.65 | 24.06 | 559.81 | 175.88 | 383.93 | 0.00 | 0.00 |
October | 1164.01 | 98.59 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 840.99 | 253.63 | 427.54 | 139.82 | 287.72 | 0.00 | 0.00 |
December | 568.50 | 429.98 | 357.92 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1190.11 | 191.85 | 509.06 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 538.49 | 0.13 | 357.92 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1836.08 | 512.14 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 361.18 | 719.69 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 502.61 | 597.91 | 364.49 | 0.00 | 364.49 | 0.00 | 0.00 |
March | 725.76 | 453.62 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1054.68 | 282.99 | 471.70 | 0.97 | 470.73 | 0.00 | 0.00 |
May | 1600.28 | 70.98 | 530.94 | 15.57 | 515.37 | 0.00 | 0.00 |
June | 1849.76 | 17.67 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
July | 2069.49 | 0.40 | 521.63 | 15.03 | 506.60 | 0.00 | 0.00 |
August | 2037.91 | 0.07 | 485.59 | 4.02 | 481.57 | 0.00 | 0.00 |
September | 1531.50 | 26.37 | 442.33 | 0.05 | 442.28 | 0.00 | 0.00 |
October | 1095.44 | 119.01 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 692.83 | 330.07 | 336.62 | 0.00 | 336.62 | 0.00 | 0.00 |
December | 407.47 | 587.09 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Annual Sum or Average | 1164.82 | 265.56 | 429.19 | 5.62 | 423.57 | 0.00 | 0.00 |
Minimum of Months | 361.18 | 0.07 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Maximum of Months | 2069.49 | 719.69 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 525.55 | 445.73 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 639.15 | 374.34 | 417.90 | 113.25 | 304.65 | 0.00 | 0.00 |
March | 815.38 | 286.61 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1166.55 | 181.15 | 562.03 | 163.76 | 398.27 | 0.00 | 0.00 |
May | 1579.23 | 44.71 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1669.13 | 10.19 | 615.11 | 188.11 | 427.00 | 0.00 | 0.00 |
July | 1807.73 | 0.17 | 574.11 | 165.52 | 408.60 | 0.00 | 0.00 |
August | 1865.43 | 0.03 | 587.88 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1510.43 | 15.45 | 552.68 | 170.83 | 381.85 | 0.00 | 0.00 |
October | 1179.78 | 72.28 | 501.50 | 163.84 | 337.66 | 0.00 | 0.00 |
November | 817.22 | 206.88 | 420.26 | 133.12 | 287.14 | 0.00 | 0.00 |
December | 515.71 | 367.35 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1177.39 | 166.07 | 504.07 | 150.33 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 515.71 | 0.03 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1865.43 | 445.73 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1624.20 | 696.72 | 1027.66 | 483.15 | 544.51 | 0.00 | 0.00 |
February | 1626.43 | 593.27 | 965.01 | 394.73 | 570.28 | 0.00 | 0.00 |
March | 1500.76 | 461.31 | 794.25 | 215.63 | 578.62 | 0.00 | 0.00 |
April | 1404.34 | 288.92 | 624.34 | 66.19 | 558.15 | 0.00 | 0.00 |
May | 1597.62 | 71.43 | 528.87 | 8.10 | 520.77 | 0.00 | 0.00 |
June | 1698.57 | 14.18 | 498.07 | 0.62 | 497.46 | 0.00 | 0.00 |
July | 2010.73 | 0.18 | 498.06 | 4.23 | 493.83 | 0.00 | 0.00 |
August | 2249.06 | 0.04 | 577.71 | 40.93 | 536.78 | 0.00 | 0.00 |
September | 2218.39 | 26.15 | 761.72 | 174.57 | 587.15 | 0.00 | 0.00 |
October | 2298.49 | 118.48 | 997.24 | 396.46 | 600.78 | 0.00 | 0.00 |
November | 2130.70 | 329.54 | 1100.16 | 530.36 | 569.80 | 0.00 | 0.00 |
December | 1723.48 | 579.32 | 1021.28 | 504.48 | 516.80 | 0.00 | 0.00 |
Annual Sum or Average | 1841.74 | 263.36 | 781.77 | 234.10 | 547.67 | 0.00 | 0.00 |
Minimum of Months | 1404.34 | 0.04 | 498.06 | 0.62 | 493.83 | 0.00 | 0.00 |
Maximum of Months | 2298.49 | 696.72 | 1100.16 | 530.36 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 543.96 | 477.21 | 376.07 | 108.01 | 268.06 | 0.00 | 0.00 |
February | 684.96 | 398.02 | 429.43 | 122.46 | 306.97 | 0.00 | 0.00 |
March | 916.88 | 307.30 | 508.67 | 150.59 | 358.08 | 0.00 | 0.00 |
April | 1161.01 | 197.69 | 555.89 | 156.18 | 399.72 | 0.00 | 0.00 |
May | 1542.53 | 52.15 | 605.08 | 181.13 | 423.96 | 0.00 | 0.00 |
June | 1693.83 | 11.82 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1803.69 | 0.18 | 573.65 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1856.28 | 0.08 | 588.50 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1522.36 | 19.02 | 559.82 | 175.88 | 383.94 | 0.00 | 0.00 |
October | 1179.75 | 83.82 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 852.32 | 225.61 | 427.55 | 139.82 | 287.73 | 0.00 | 0.00 |
December | 577.01 | 392.35 | 357.93 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1197.50 | 179.38 | 509.07 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 543.96 | 0.08 | 357.93 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1856.28 | 477.21 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100983E+10 | 0.176554E+10 | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.00 | 0.00 |
February | 0.124163E+10 | 0.133808E+10 | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.00 | 0.00 |
March | 0.195226E+10 | 0.113892E+10 | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.00 | 0.00 |
April | 0.272346E+10 | 0.701757E+09 | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.00 | 0.00 |
May | 0.425817E+10 | 0.187546E+09 | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.00 | 0.00 |
June | 0.476660E+10 | 46379329.09 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
July | 0.550691E+10 | 962966.09 | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.00 | 0.00 |
August | 0.542853E+10 | 222902.24 | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.00 | 0.00 |
September | 0.394791E+10 | 66559831.19 | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.00 | 0.00 |
October | 0.292376E+10 | 0.303739E+09 | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.00 | 0.00 |
November | 0.180448E+10 | 0.796894E+09 | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.00 | 0.00 |
December | 0.112492E+10 | 0.144351E+10 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366885E+11 | 0.779012E+10 | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100983E+10 | 222902.24 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550691E+10 | 0.176554E+10 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144168E+10 | 0.110853E+10 | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.00 | 0.00 |
February | 0.156477E+10 | 0.847262E+09 | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.00 | 0.00 |
March | 0.218962E+10 | 0.725748E+09 | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.00 | 0.00 |
April | 0.301453E+10 | 0.451827E+09 | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.00 | 0.00 |
May | 0.420643E+10 | 0.118365E+09 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
June | 0.430334E+10 | 26845945.36 | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.00 | 0.00 |
July | 0.481337E+10 | 396672.51 | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.00 | 0.00 |
August | 0.497205E+10 | 85019.01 | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.00 | 0.00 |
September | 0.389542E+10 | 39099864.68 | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.00 | 0.00 |
October | 0.314809E+10 | 0.185312E+09 | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.00 | 0.00 |
November | 0.212314E+10 | 0.503280E+09 | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.00 | 0.00 |
December | 0.140727E+10 | 0.913779E+09 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.370797E+11 | 0.492053E+10 | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140727E+10 | 85019.01 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497205E+10 | 0.110853E+10 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438779E+10 | 0.173200E+10 | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.00 | 0.00 |
February | 0.395206E+10 | 0.133928E+10 | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.00 | 0.00 |
March | 0.402163E+10 | 0.116302E+10 | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.00 | 0.00 |
April | 0.362702E+10 | 0.715652E+09 | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.00 | 0.00 |
May | 0.425016E+10 | 0.186912E+09 | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.00 | 0.00 |
June | 0.437681E+10 | 36418289.61 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
July | 0.535058E+10 | 394777.35 | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.00 | 0.00 |
August | 0.599368E+10 | 123274.44 | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.00 | 0.00 |
September | 0.572279E+10 | 65724752.66 | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.00 | 0.00 |
October | 0.613617E+10 | 0.303168E+09 | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.00 | 0.00 |
November | 0.552265E+10 | 0.803970E+09 | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.00 | 0.00 |
December | 0.464279E+10 | 0.144472E+10 | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579841E+11 | 0.779139E+10 | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362702E+10 | 123274.44 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.613617E+10 | 0.173200E+10 | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148412E+10 | 0.117453E+10 | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.00 | 0.00 |
February | 0.167279E+10 | 0.892435E+09 | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.00 | 0.00 |
March | 0.245933E+10 | 0.772452E+09 | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.00 | 0.00 |
April | 0.300057E+10 | 0.489941E+09 | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.00 | 0.00 |
May | 0.411043E+10 | 0.136991E+09 | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.00 | 0.00 |
June | 0.437141E+10 | 30485345.74 | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.00 | 0.00 |
July | 0.480844E+10 | 399341.04 | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.00 | 0.00 |
August | 0.495210E+10 | 231590.05 | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.00 | 0.00 |
September | 0.392933E+10 | 48102826.90 | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.00 | 0.00 |
October | 0.315014E+10 | 0.214424E+09 | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.00 | 0.00 |
November | 0.221318E+10 | 0.544852E+09 | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.00 | 0.00 |
December | 0.156726E+10 | 0.967434E+09 | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377191E+11 | 0.527227E+10 | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148412E+10 | 231590.05 | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495210E+10 | 0.117453E+10 | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.945373E+09 | 0.203788E+10 | 0.851641E+09 | 0.00 | 0.851641E+09 | 0.00 | 0.00 |
February | 0.121267E+10 | 0.149369E+10 | 0.881752E+09 | 0.00 | 0.881752E+09 | 0.00 | 0.00 |
March | 0.196023E+10 | 0.121179E+10 | 0.112133E+10 | 0.00 | 0.112133E+10 | 0.00 | 0.00 |
April | 0.275763E+10 | 0.709538E+09 | 0.122262E+10 | 2519115.86 | 0.122010E+10 | 0.00 | 0.00 |
May | 0.429453E+10 | 0.179678E+09 | 0.142203E+10 | 41707061.80 | 0.138033E+10 | 0.00 | 0.00 |
June | 0.478109E+10 | 43807484.08 | 0.147344E+10 | 81800414.70 | 0.139164E+10 | 0.00 | 0.00 |
July | 0.550508E+10 | 1116161.69 | 0.139709E+10 | 40253353.26 | 0.135684E+10 | 0.00 | 0.00 |
August | 0.538772E+10 | 249161.91 | 0.130058E+10 | 10756963.82 | 0.128982E+10 | 0.00 | 0.00 |
September | 0.390143E+10 | 79551850.43 | 0.114649E+10 | 131376.06 | 0.114636E+10 | 0.00 | 0.00 |
October | 0.286710E+10 | 0.358157E+09 | 0.105022E+10 | 0.00 | 0.105022E+10 | 0.00 | 0.00 |
November | 0.174689E+10 | 0.937912E+09 | 0.872504E+09 | 0.00 | 0.872504E+09 | 0.00 | 0.00 |
December | 0.105664E+10 | 0.169830E+10 | 0.794897E+09 | 0.00 | 0.794897E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364164E+11 | 0.875166E+10 | 0.135346E+11 | 0.177168E+09 | 0.133574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.945373E+09 | 249161.91 | 0.794897E+09 | 0.00 | 0.794897E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550508E+10 | 0.203788E+10 | 0.147344E+10 | 81800414.70 | 0.139164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138894E+10 | 0.127944E+10 | 0.102708E+10 | 0.310741E+09 | 0.716340E+09 | 0.00 | 0.00 |
February | 0.154367E+10 | 0.951023E+09 | 0.101096E+10 | 0.273975E+09 | 0.736990E+09 | 0.00 | 0.00 |
March | 0.219606E+10 | 0.780849E+09 | 0.123636E+10 | 0.304717E+09 | 0.931646E+09 | 0.00 | 0.00 |
April | 0.304076E+10 | 0.469849E+09 | 0.145676E+10 | 0.424451E+09 | 0.103231E+10 | 0.00 | 0.00 |
May | 0.423102E+10 | 0.121547E+09 | 0.168224E+10 | 0.535968E+09 | 0.114627E+10 | 0.00 | 0.00 |
June | 0.431332E+10 | 28525778.61 | 0.159435E+10 | 0.487568E+09 | 0.110678E+10 | 0.00 | 0.00 |
July | 0.480947E+10 | 702906.98 | 0.153768E+10 | 0.443309E+09 | 0.109437E+10 | 0.00 | 0.00 |
August | 0.494212E+10 | 177217.15 | 0.157456E+10 | 0.483251E+09 | 0.109131E+10 | 0.00 | 0.00 |
September | 0.386543E+10 | 51239018.02 | 0.143252E+10 | 0.442772E+09 | 0.989746E+09 | 0.00 | 0.00 |
October | 0.311752E+10 | 0.231291E+09 | 0.134320E+10 | 0.438821E+09 | 0.904375E+09 | 0.00 | 0.00 |
November | 0.208603E+10 | 0.602901E+09 | 0.108929E+10 | 0.345031E+09 | 0.744262E+09 | 0.00 | 0.00 |
December | 0.135464E+10 | 0.107650E+10 | 0.911067E+09 | 0.249959E+09 | 0.661108E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368890E+11 | 0.559404E+10 | 0.158961E+11 | 0.474056E+10 | 0.111555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135464E+10 | 177217.15 | 0.911067E+09 | 0.249959E+09 | 0.661108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494212E+10 | 0.127944E+10 | 0.168224E+10 | 0.535968E+09 | 0.114627E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435360E+10 | 0.200592E+10 | 0.275237E+10 | 0.129401E+10 | 0.145836E+10 | 0.00 | 0.00 |
February | 0.395118E+10 | 0.151524E+10 | 0.233447E+10 | 0.954898E+09 | 0.137958E+10 | 0.00 | 0.00 |
March | 0.404386E+10 | 0.125382E+10 | 0.212724E+10 | 0.577531E+09 | 0.154971E+10 | 0.00 | 0.00 |
April | 0.366016E+10 | 0.735646E+09 | 0.161824E+10 | 0.171562E+09 | 0.144667E+10 | 0.00 | 0.00 |
May | 0.425464E+10 | 0.186902E+09 | 0.141648E+10 | 21691766.98 | 0.139479E+10 | 0.00 | 0.00 |
June | 0.434200E+10 | 38462427.77 | 0.129097E+10 | 1597603.30 | 0.128937E+10 | 0.00 | 0.00 |
July | 0.529464E+10 | 571658.62 | 0.133397E+10 | 11334497.64 | 0.132263E+10 | 0.00 | 0.00 |
August | 0.588032E+10 | 337912.51 | 0.154729E+10 | 0.109631E+09 | 0.143766E+10 | 0.00 | 0.00 |
September | 0.563299E+10 | 88968153.66 | 0.197431E+10 | 0.452466E+09 | 0.152184E+10 | 0.00 | 0.00 |
October | 0.607019E+10 | 0.393095E+09 | 0.267090E+10 | 0.106183E+10 | 0.160907E+10 | 0.00 | 0.00 |
November | 0.548532E+10 | 0.979396E+09 | 0.285150E+10 | 0.137463E+10 | 0.147687E+10 | 0.00 | 0.00 |
December | 0.460562E+10 | 0.170122E+10 | 0.273529E+10 | 0.135114E+10 | 0.138414E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575745E+11 | 0.889958E+10 | 0.246530E+11 | 0.738232E+10 | 0.172707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366016E+10 | 337912.51 | 0.129097E+10 | 1597603.30 | 0.128937E+10 | 0.00 | 0.00 |
Maximum of Months | 0.607019E+10 | 0.200592E+10 | 0.285150E+10 | 0.137463E+10 | 0.160907E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144230E+10 | 0.137172E+10 | 0.100724E+10 | 0.289287E+09 | 0.717955E+09 | 0.00 | 0.00 |
February | 0.165624E+10 | 0.101265E+10 | 0.103886E+10 | 0.296240E+09 | 0.742621E+09 | 0.00 | 0.00 |
March | 0.246982E+10 | 0.840853E+09 | 0.136241E+10 | 0.403343E+09 | 0.959066E+09 | 0.00 | 0.00 |
April | 0.302730E+10 | 0.512359E+09 | 0.144085E+10 | 0.404800E+09 | 0.103605E+10 | 0.00 | 0.00 |
May | 0.413199E+10 | 0.141939E+09 | 0.162064E+10 | 0.485120E+09 | 0.113552E+10 | 0.00 | 0.00 |
June | 0.437229E+10 | 33913877.83 | 0.162077E+10 | 0.510907E+09 | 0.110986E+10 | 0.00 | 0.00 |
July | 0.479597E+10 | 889852.68 | 0.153644E+10 | 0.439544E+09 | 0.109690E+10 | 0.00 | 0.00 |
August | 0.491775E+10 | 344281.00 | 0.157622E+10 | 0.479236E+09 | 0.109698E+10 | 0.00 | 0.00 |
September | 0.389746E+10 | 62367666.86 | 0.145102E+10 | 0.455868E+09 | 0.995155E+09 | 0.00 | 0.00 |
October | 0.311768E+10 | 0.264062E+09 | 0.133252E+10 | 0.430439E+09 | 0.902079E+09 | 0.00 | 0.00 |
November | 0.217984E+10 | 0.657420E+09 | 0.110819E+10 | 0.362414E+09 | 0.745781E+09 | 0.00 | 0.00 |
December | 0.152267E+10 | 0.115166E+10 | 0.958656E+09 | 0.289784E+09 | 0.668872E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375313E+11 | 0.605018E+10 | 0.160538E+11 | 0.484698E+10 | 0.112068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144230E+10 | 344281.00 | 0.958656E+09 | 0.289287E+09 | 0.668872E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491775E+10 | 0.137172E+10 | 0.162077E+10 | 0.510907E+09 | 0.113552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.967377E+09 | 0.192762E+10 | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.00 | 0.00 |
February | 0.121590E+10 | 0.144647E+10 | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.00 | 0.00 |
March | 0.194388E+10 | 0.121497E+10 | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.00 | 0.00 |
April | 0.273373E+10 | 0.733515E+09 | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.00 | 0.00 |
May | 0.428618E+10 | 0.190108E+09 | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.00 | 0.00 |
June | 0.479458E+10 | 45795580.33 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
July | 0.554292E+10 | 1063799.02 | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.00 | 0.00 |
August | 0.545835E+10 | 194672.70 | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.00 | 0.00 |
September | 0.396966E+10 | 68363363.09 | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.00 | 0.00 |
October | 0.293402E+10 | 0.318751E+09 | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.00 | 0.00 |
November | 0.179582E+10 | 0.855541E+09 | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.00 | 0.00 |
December | 0.109137E+10 | 0.157247E+10 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367338E+11 | 0.837486E+10 | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.00 | 0.00 |
Minimum of Months | 0.967377E+09 | 194672.70 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554292E+10 | 0.192762E+10 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140764E+10 | 0.119383E+10 | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.00 | 0.00 |
February | 0.154623E+10 | 0.905604E+09 | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.00 | 0.00 |
March | 0.218392E+10 | 0.767650E+09 | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.00 | 0.00 |
April | 0.302370E+10 | 0.469533E+09 | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.00 | 0.00 |
May | 0.422980E+10 | 0.119740E+09 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
June | 0.432639E+10 | 26422923.26 | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.00 | 0.00 |
July | 0.484183E+10 | 462858.86 | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.00 | 0.00 |
August | 0.499635E+10 | 76110.84 | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.00 | 0.00 |
September | 0.391503E+10 | 40056068.19 | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.00 | 0.00 |
October | 0.315993E+10 | 0.193594E+09 | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.00 | 0.00 |
November | 0.211824E+10 | 0.536225E+09 | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.00 | 0.00 |
December | 0.138127E+10 | 0.983909E+09 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.371303E+11 | 0.523711E+10 | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138127E+10 | 76110.84 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499635E+10 | 0.119383E+10 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435025E+10 | 0.186609E+10 | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.00 | 0.00 |
February | 0.393465E+10 | 0.143523E+10 | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.00 | 0.00 |
March | 0.401962E+10 | 0.123557E+10 | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.00 | 0.00 |
April | 0.364004E+10 | 0.748870E+09 | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.00 | 0.00 |
May | 0.427907E+10 | 0.191327E+09 | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.00 | 0.00 |
June | 0.440268E+10 | 36751429.17 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
July | 0.538553E+10 | 478634.01 | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.00 | 0.00 |
August | 0.602387E+10 | 109307.17 | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.00 | 0.00 |
September | 0.575006E+10 | 67782339.32 | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.00 | 0.00 |
October | 0.615628E+10 | 0.317345E+09 | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.00 | 0.00 |
November | 0.552278E+10 | 0.854174E+09 | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.00 | 0.00 |
December | 0.461616E+10 | 0.155166E+10 | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580810E+11 | 0.830539E+10 | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.364004E+10 | 109307.17 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.615628E+10 | 0.186609E+10 | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145693E+10 | 0.127815E+10 | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.00 | 0.00 |
February | 0.165705E+10 | 0.962884E+09 | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.00 | 0.00 |
March | 0.245578E+10 | 0.823082E+09 | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.00 | 0.00 |
April | 0.300934E+10 | 0.512407E+09 | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.00 | 0.00 |
May | 0.413153E+10 | 0.139668E+09 | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.00 | 0.00 |
June | 0.439040E+10 | 30634504.33 | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.00 | 0.00 |
July | 0.483101E+10 | 484542.58 | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.00 | 0.00 |
August | 0.497186E+10 | 218307.54 | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.00 | 0.00 |
September | 0.394595E+10 | 49300608.50 | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.00 | 0.00 |
October | 0.315984E+10 | 0.224496E+09 | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.00 | 0.00 |
November | 0.220921E+10 | 0.584770E+09 | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.00 | 0.00 |
December | 0.154545E+10 | 0.105087E+10 | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377644E+11 | 0.565696E+10 | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145693E+10 | 218307.54 | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497186E+10 | 0.127815E+10 | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390627E+10 | -0.321808E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688186433.2 | 58.98 | 0.00 | 0.00 |
February | 0.346436E+10 | -0.284291E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -621448922.9 | 58.98 | 0.00 | 0.00 |
March | 0.381558E+10 | -0.312692E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688665279.0 | 58.98 | 0.00 | 0.00 |
April | 0.319353E+10 | -0.252848E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665042941.3 | 58.98 | 0.00 | 0.00 |
May | 0.310367E+10 | -0.241539E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688280185.2 | 58.98 | 0.00 | 0.00 |
June | 0.284964E+10 | -0.218187E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667765551.4 | 58.98 | 0.00 | 0.00 |
July | 0.268489E+10 | -0.199154E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693357185.0 | 58.98 | 0.00 | 0.00 |
August | 0.299987E+10 | -0.230409E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695771901.1 | 58.98 | 0.00 | 0.00 |
September | 0.296594E+10 | -0.229725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668687792.4 | 58.98 | 0.00 | 0.00 |
October | 0.335588E+10 | -0.266744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688432290.6 | 58.98 | 0.00 | 0.00 |
November | 0.356874E+10 | -0.290456E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664181608.3 | 58.98 | 0.00 | 0.00 |
December | 0.375776E+10 | -0.307026E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687500260.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.396661E+11 | -0.315488E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.811732E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.268489E+10 | -0.321808E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -695771901.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.390627E+10 | -0.199154E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -621448922.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4184.40 | 34.11 | 310.83 | 292.67 | 1096.35 | 25.00 | 290.00 | 280.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2152.07 | 24.99 | 142.00 | 274.00 | 976.29 | 20.81 | 177.67 | 244.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:30 | 1580.47 | 18.41 | 5.00 | 313.33 | 828.66 | 20.38 | 146.83 | 277.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 1229.88 | 17.41 | 0.00 | 321.83 | 656.40 | 19.47 | 86.17 | 284.00 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1042.30 | 17.35 | 0.00 | 348.50 | 574.90 | 19.47 | 19.17 | 303.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 996.87 | 17.25 | 0.00 | 343.50 | 558.78 | 19.41 | 9.83 | 296.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-07:30 | 1048.58 | 17.17 | 0.00 | 344.00 | 580.68 | 19.32 | 42.50 | 303.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1233.60 | 17.67 | 0.00 | 342.67 | 666.59 | 19.79 | 135.67 | 303.33 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1549.25 | 18.40 | 0.00 | 318.17 | 824.33 | 20.55 | 188.67 | 284.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 2081.82 | 20.37 | 34.50 | 317.17 | 1000.65 | 21.45 | 232.50 | 288.00 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3519.92 | 31.75 | 256.33 | 297.67 | 1136.11 | 24.84 | 301.33 | 282.00 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4173.11 | 34.49 | 307.00 | 288.83 | 1170.91 | 26.19 | 288.00 | 275.50 |
Annual Sum or Average | 4323.33 | 0.53 | 1972.52 | 21.91 | 1055.67 | 3802.33 | 818.86 | 21.21 | 1918.33 | 3422.50 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 996.87 | 17.17 | 0.00 | 274.00 | 558.78 | 19.32 | 9.83 | 244.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 4184.40 | 34.49 | 310.83 | 348.50 | 1170.91 | 26.19 | 301.33 | 303.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1519.85 | 21.79 | 111.83 | 272.83 | 801.99 | 22.51 | 80.83 | 234.00 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1642.20 | 21.37 | 102.50 | 261.33 | 710.00 | 20.78 | 47.17 | 224.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1529.48 | 19.19 | 83.83 | 306.67 | 790.84 | 21.38 | 66.00 | 268.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1800.14 | 20.38 | 109.33 | 318.83 | 923.09 | 21.38 | 79.83 | 281.33 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 2033.08 | 20.26 | 118.83 | 355.50 | 869.57 | 20.94 | 67.83 | 319.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:10 | 1953.33 | 20.00 | 114.33 | 349.17 | 857.28 | 21.00 | 66.67 | 316.33 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1843.92 | 19.92 | 114.17 | 347.33 | 818.68 | 20.66 | 61.83 | 309.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1898.99 | 20.51 | 113.83 | 340.00 | 852.05 | 20.40 | 56.00 | 305.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1892.81 | 21.36 | 107.00 | 310.17 | 979.72 | 22.35 | 77.33 | 283.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:49 | 1760.11 | 21.27 | 104.67 | 303.83 | 915.95 | 22.32 | 76.00 | 272.83 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1511.99 | 20.50 | 84.33 | 275.33 | 789.22 | 22.27 | 63.00 | 241.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-07:19 | 1251.77 | 20.34 | 85.50 | 267.50 | 630.87 | 20.92 | 50.67 | 223.00 |
Annual Sum or Average | 4323.33 | 0.54 | 1737.44 | 20.54 | 1250.17 | 3708.50 | 833.10 | 21.38 | 793.17 | 3279.67 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1251.77 | 19.19 | 83.83 | 261.33 | 630.87 | 20.40 | 47.17 | 223.00 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 2033.08 | 21.79 | 118.83 | 355.50 | 979.72 | 22.51 | 80.83 | 319.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.57 | 0.48 | 01-JAN-10:39 | 583.95 | 15.21 | 0.00 | 258.67 | 337.79 | 17.35 | 0.00 | 173.83 |
February | 308.33 | 0.55 | 0.48 | 01-FEB-09:09 | 664.12 | 16.06 | 0.00 | 251.83 | 383.06 | 18.19 | 0.00 | 189.33 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:09 | 774.93 | 16.72 | 0.00 | 305.17 | 440.69 | 18.80 | 0.00 | 253.50 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 888.56 | 17.04 | 0.00 | 325.83 | 498.75 | 19.06 | 0.00 | 285.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1048.69 | 18.06 | 2.83 | 367.83 | 580.84 | 20.13 | 58.67 | 334.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1161.11 | 21.19 | 77.67 | 366.00 | 634.77 | 21.74 | 159.67 | 337.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:00 | 1122.40 | 19.02 | 27.00 | 357.67 | 614.73 | 21.15 | 131.83 | 327.17 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:10 | 1015.31 | 17.71 | 0.00 | 349.17 | 569.21 | 19.83 | 57.67 | 315.17 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 884.63 | 17.40 | 0.00 | 316.67 | 507.78 | 19.51 | 0.00 | 274.33 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 731.07 | 16.51 | 0.00 | 298.33 | 429.39 | 18.65 | 0.00 | 246.00 |
November | 318.83 | 0.55 | 0.48 | 01-NOV-08:20 | 632.93 | 16.13 | 0.00 | 260.50 | 373.18 | 18.35 | 0.00 | 194.83 |
December | 319.00 | 0.57 | 0.48 | 01-DEC-09:20 | 566.22 | 15.30 | 0.00 | 247.67 | 328.20 | 17.48 | 0.00 | 151.67 |
Annual Sum or Average | 4323.33 | 0.54 | 858.46 | 17.33 | 107.50 | 3705.33 | 484.58 | 19.30 | 407.83 | 3082.67 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 566.22 | 15.21 | 0.00 | 247.67 | 328.20 | 17.35 | 0.00 | 151.67 | |
Maximum of Months | 405.33 | 0.57 | 0.48 | 1161.11 | 21.19 | 77.67 | 367.83 | 634.77 | 21.74 | 159.67 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:20 | 1472.49 | 21.41 | 108.17 | 273.67 | 770.48 | 22.12 | 77.17 | 234.00 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:30 | 1441.48 | 19.80 | 76.33 | 260.33 | 731.40 | 20.69 | 48.33 | 222.67 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1643.78 | 19.44 | 85.83 | 307.67 | 844.33 | 21.41 | 65.67 | 270.50 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:39 | 1670.50 | 16.78 | 55.00 | 323.00 | 871.46 | 17.27 | 0.00 | 285.83 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-08:09 | 1755.31 | 14.44 | 0.00 | 348.83 | 908.83 | 17.58 | 0.00 | 312.50 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:00 | 1864.70 | 14.62 | 0.00 | 345.33 | 831.45 | 17.79 | 0.00 | 310.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:09 | 1785.81 | 14.65 | 3.67 | 347.00 | 813.31 | 17.57 | 0.00 | 308.17 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:09 | 1824.05 | 17.26 | 59.83 | 342.17 | 945.36 | 17.97 | 5.50 | 307.50 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1753.99 | 19.77 | 86.83 | 316.33 | 913.00 | 20.84 | 57.33 | 284.00 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1823.51 | 21.44 | 107.83 | 301.83 | 949.35 | 22.47 | 79.33 | 271.50 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1569.76 | 20.46 | 85.00 | 275.67 | 823.99 | 22.59 | 69.00 | 243.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1371.99 | 20.01 | 87.33 | 267.17 | 719.82 | 22.18 | 71.17 | 225.50 |
Annual Sum or Average | 4323.33 | 0.54 | 1677.91 | 18.12 | 755.83 | 3709.00 | 847.81 | 19.86 | 473.50 | 3275.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1371.99 | 14.44 | 0.00 | 260.33 | 719.82 | 17.27 | 0.00 | 222.67 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1864.70 | 21.44 | 108.17 | 348.83 | 949.35 | 22.59 | 79.33 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4086.59 | 33.82 | 310.17 | 292.17 | 1028.59 | 22.68 | 91.67 | 279.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2064.32 | 22.71 | 141.00 | 272.67 | 915.48 | 17.90 | 0.00 | 241.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:39 | 1512.04 | 14.51 | 5.00 | 311.67 | 782.61 | 17.73 | 0.00 | 274.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 1181.64 | 13.73 | 0.00 | 320.50 | 625.95 | 17.06 | 0.00 | 280.50 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1003.72 | 13.75 | 0.00 | 345.67 | 551.91 | 17.15 | 0.00 | 299.67 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 960.15 | 13.58 | 0.00 | 342.33 | 537.26 | 17.05 | 0.00 | 294.33 |
July | 405.00 | 0.55 | 0.48 | 01-JUL-07:30 | 1009.76 | 13.44 | 0.00 | 342.83 | 557.67 | 16.85 | 0.00 | 298.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1185.81 | 14.02 | 0.00 | 341.83 | 637.18 | 17.40 | 0.00 | 299.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1483.91 | 14.69 | 0.00 | 317.17 | 781.48 | 18.11 | 0.00 | 282.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1994.96 | 16.79 | 34.50 | 316.17 | 940.22 | 18.93 | 10.67 | 285.17 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3419.48 | 30.75 | 255.67 | 296.17 | 1064.51 | 22.45 | 76.67 | 280.50 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4073.66 | 34.24 | 306.00 | 287.50 | 1101.75 | 24.02 | 113.17 | 274.67 |
Annual Sum or Average | 4323.33 | 0.53 | 1906.79 | 19.03 | 1052.33 | 3786.67 | 775.12 | 18.77 | 292.17 | 3390.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 960.15 | 13.44 | 0.00 | 272.67 | 537.26 | 16.85 | 0.00 | 241.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 4086.59 | 34.24 | 310.17 | 345.67 | 1101.75 | 24.02 | 113.17 | 299.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-07:00 | 1477.44 | 21.34 | 111.83 | 271.17 | 770.93 | 22.29 | 80.83 | 230.17 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1598.28 | 20.91 | 102.33 | 259.50 | 677.76 | 20.56 | 47.17 | 222.17 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-07:00 | 1486.55 | 18.70 | 83.83 | 304.00 | 756.64 | 21.18 | 66.00 | 264.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:10 | 1745.70 | 19.95 | 109.33 | 316.33 | 885.84 | 21.22 | 79.83 | 278.00 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 1978.19 | 19.83 | 118.83 | 354.50 | 822.55 | 19.95 | 57.33 | 312.00 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-06:10 | 1906.78 | 19.55 | 114.33 | 347.33 | 818.23 | 20.81 | 66.33 | 312.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1794.64 | 19.48 | 114.17 | 345.50 | 778.78 | 19.69 | 52.50 | 306.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1837.56 | 20.08 | 113.83 | 338.67 | 812.55 | 20.23 | 56.17 | 303.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1838.98 | 20.74 | 105.17 | 309.00 | 939.81 | 22.18 | 77.33 | 280.50 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-06:00 | 1687.40 | 19.31 | 87.83 | 302.33 | 877.59 | 22.12 | 76.00 | 269.17 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1465.58 | 19.99 | 84.33 | 273.50 | 754.40 | 22.05 | 63.00 | 237.67 |
December | 319.00 | 0.55 | 0.48 | 01-DEC-07:19 | 1213.13 | 19.85 | 85.33 | 264.83 | 602.64 | 20.68 | 50.67 | 218.33 |
Annual Sum or Average | 4323.33 | 0.54 | 1686.47 | 19.95 | 1231.17 | 3686.67 | 795.92 | 21.03 | 773.17 | 3235.33 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1213.13 | 18.70 | 83.83 | 259.50 | 602.64 | 19.69 | 47.17 | 218.33 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1978.19 | 21.34 | 118.83 | 354.50 | 939.81 | 22.29 | 80.83 | 312.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.58 | 0.48 | 01-JAN-11:09 | 563.02 | 11.56 | 0.00 | 254.17 | 326.01 | 15.02 | 0.00 | 161.83 |
February | 308.33 | 0.56 | 0.48 | 01-FEB-09:20 | 640.55 | 12.32 | 0.00 | 250.17 | 369.77 | 15.82 | 0.00 | 183.00 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:20 | 747.66 | 13.05 | 0.00 | 303.00 | 425.11 | 16.48 | 0.00 | 246.17 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 856.88 | 13.49 | 0.00 | 324.00 | 480.37 | 16.84 | 0.00 | 281.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1010.38 | 14.42 | 2.83 | 366.50 | 558.12 | 17.86 | 1.17 | 328.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1117.74 | 18.33 | 77.33 | 363.17 | 608.57 | 19.55 | 34.17 | 333.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1080.87 | 15.56 | 26.83 | 356.33 | 589.86 | 18.88 | 27.33 | 324.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 977.84 | 14.13 | 0.00 | 347.50 | 547.30 | 17.57 | 0.00 | 310.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 852.42 | 13.96 | 0.00 | 315.33 | 489.39 | 17.37 | 0.00 | 270.83 |
October | 351.17 | 0.55 | 0.48 | 01-OCT-07:00 | 704.50 | 13.07 | 0.00 | 295.83 | 414.52 | 16.53 | 0.00 | 240.67 |
November | 318.83 | 0.56 | 0.48 | 01-NOV-08:30 | 609.74 | 12.53 | 0.00 | 257.17 | 360.27 | 16.11 | 0.00 | 185.67 |
December | 319.00 | 0.58 | 0.48 | 01-DEC-09:30 | 545.66 | 11.53 | 0.00 | 243.83 | 316.64 | 15.08 | 0.00 | 137.17 |
Annual Sum or Average | 4323.33 | 0.54 | 827.19 | 13.81 | 107.00 | 3677.00 | 466.41 | 17.04 | 62.67 | 3004.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 545.66 | 11.53 | 0.00 | 243.83 | 316.64 | 15.02 | 0.00 | 137.17 | |
Maximum of Months | 405.33 | 0.58 | 0.48 | 1117.74 | 18.33 | 77.33 | 366.50 | 608.57 | 19.55 | 34.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-10:20 | 1431.04 | 21.03 | 108.17 | 271.33 | 739.89 | 22.02 | 77.17 | 228.83 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:39 | 1395.63 | 19.38 | 76.33 | 258.83 | 697.96 | 20.57 | 48.33 | 218.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1596.77 | 19.01 | 85.83 | 306.83 | 806.38 | 21.29 | 65.83 | 266.83 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:50 | 1600.12 | 16.31 | 55.00 | 320.17 | 833.79 | 17.10 | 0.00 | 282.83 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-08:09 | 1699.56 | 13.89 | 0.00 | 347.83 | 870.84 | 17.38 | 0.00 | 309.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-08:09 | 1816.32 | 14.07 | 0.00 | 344.17 | 792.02 | 17.58 | 0.00 | 306.83 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:20 | 1734.07 | 14.10 | 3.67 | 345.33 | 775.79 | 17.36 | 0.00 | 304.83 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:20 | 1762.23 | 16.77 | 59.83 | 340.17 | 905.81 | 17.79 | 5.50 | 304.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1703.72 | 19.34 | 86.83 | 314.50 | 872.46 | 20.70 | 57.33 | 281.17 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-08:20 | 1772.59 | 21.04 | 107.83 | 300.00 | 911.28 | 22.36 | 79.33 | 269.00 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1522.63 | 20.02 | 85.00 | 273.17 | 788.90 | 22.49 | 69.00 | 240.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1330.39 | 19.58 | 87.33 | 265.00 | 689.13 | 22.07 | 71.33 | 222.67 |
Annual Sum or Average | 4323.33 | 0.54 | 1626.43 | 17.66 | 755.83 | 3687.33 | 811.03 | 19.71 | 473.83 | 3235.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1330.39 | 13.89 | 0.00 | 258.83 | 689.13 | 17.10 | 0.00 | 218.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1816.32 | 21.04 | 108.17 | 347.83 | 911.28 | 22.49 | 79.33 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4086.49 | 33.82 | 310.17 | 292.17 | 1028.50 | 22.68 | 91.67 | 279.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2064.21 | 22.71 | 141.00 | 272.67 | 915.40 | 17.90 | 0.00 | 241.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:39 | 1511.93 | 14.51 | 5.00 | 311.50 | 782.54 | 17.73 | 0.00 | 274.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 1181.56 | 13.73 | 0.00 | 320.50 | 625.90 | 17.06 | 0.00 | 280.50 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1003.67 | 13.75 | 0.00 | 345.67 | 551.86 | 17.15 | 0.00 | 299.67 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 960.10 | 13.58 | 0.00 | 342.33 | 537.22 | 17.05 | 0.00 | 294.33 |
July | 405.00 | 0.55 | 0.48 | 01-JUL-07:30 | 1009.71 | 13.44 | 0.00 | 342.83 | 557.63 | 16.85 | 0.00 | 298.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1185.73 | 14.02 | 0.00 | 341.83 | 637.13 | 17.40 | 0.00 | 299.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1483.81 | 14.69 | 0.00 | 317.17 | 781.41 | 18.11 | 0.00 | 282.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1994.84 | 16.79 | 34.50 | 316.17 | 940.13 | 18.94 | 10.67 | 285.17 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3419.37 | 30.75 | 255.67 | 296.17 | 1064.41 | 22.45 | 76.67 | 280.50 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4073.58 | 34.24 | 306.00 | 287.50 | 1101.66 | 24.02 | 113.33 | 274.67 |
Annual Sum or Average | 4323.33 | 0.53 | 1906.71 | 19.03 | 1052.33 | 3786.50 | 775.05 | 18.77 | 292.33 | 3390.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 960.10 | 13.44 | 0.00 | 272.67 | 537.22 | 16.85 | 0.00 | 241.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 4086.49 | 34.24 | 310.17 | 345.67 | 1101.66 | 24.02 | 113.33 | 299.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-07:00 | 1477.39 | 21.34 | 111.83 | 271.17 | 770.88 | 22.29 | 80.83 | 230.17 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1598.23 | 20.92 | 102.33 | 259.50 | 677.71 | 20.56 | 47.17 | 222.17 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-07:00 | 1486.48 | 18.70 | 83.83 | 304.00 | 756.59 | 21.18 | 66.00 | 264.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:10 | 1745.63 | 19.95 | 109.33 | 316.33 | 885.79 | 21.22 | 79.83 | 278.00 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 1978.13 | 19.83 | 118.83 | 354.50 | 822.49 | 19.95 | 57.33 | 312.00 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-06:10 | 1906.71 | 19.55 | 114.33 | 347.33 | 818.17 | 20.81 | 66.33 | 312.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1794.57 | 19.49 | 114.17 | 345.50 | 778.72 | 19.69 | 52.50 | 306.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1837.49 | 20.08 | 113.83 | 338.67 | 812.49 | 20.23 | 56.17 | 303.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1838.91 | 20.74 | 105.17 | 309.00 | 939.74 | 22.18 | 77.33 | 280.50 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-06:00 | 1687.34 | 19.31 | 87.83 | 302.33 | 877.53 | 22.12 | 76.00 | 269.17 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1465.54 | 20.00 | 84.33 | 273.50 | 754.35 | 22.05 | 63.00 | 237.67 |
December | 319.00 | 0.55 | 0.48 | 01-DEC-07:19 | 1213.09 | 19.85 | 85.33 | 264.83 | 602.60 | 20.68 | 50.67 | 218.33 |
Annual Sum or Average | 4323.33 | 0.54 | 1686.41 | 19.95 | 1231.17 | 3686.67 | 795.86 | 21.03 | 773.17 | 3235.33 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1213.09 | 18.70 | 83.83 | 259.50 | 602.60 | 19.69 | 47.17 | 218.33 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1978.13 | 21.34 | 118.83 | 354.50 | 939.74 | 22.29 | 80.83 | 312.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.58 | 0.48 | 01-JAN-11:09 | 563.00 | 11.56 | 0.00 | 254.17 | 325.99 | 15.02 | 0.00 | 161.83 |
February | 308.33 | 0.56 | 0.48 | 01-FEB-09:20 | 640.53 | 12.32 | 0.00 | 250.17 | 369.74 | 15.82 | 0.00 | 183.00 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:20 | 747.62 | 13.05 | 0.00 | 303.00 | 425.08 | 16.48 | 0.00 | 246.17 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 856.84 | 13.49 | 0.00 | 324.00 | 480.33 | 16.84 | 0.00 | 281.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1010.32 | 14.42 | 2.83 | 366.50 | 558.07 | 17.86 | 1.17 | 328.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1117.68 | 18.33 | 77.33 | 363.17 | 608.53 | 19.55 | 34.17 | 333.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1080.81 | 15.56 | 26.83 | 356.33 | 589.82 | 18.88 | 27.33 | 324.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 977.79 | 14.13 | 0.00 | 347.50 | 547.26 | 17.57 | 0.00 | 310.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 852.38 | 13.96 | 0.00 | 315.33 | 489.35 | 17.37 | 0.00 | 270.83 |
October | 351.17 | 0.55 | 0.48 | 01-OCT-07:00 | 704.48 | 13.07 | 0.00 | 295.83 | 414.49 | 16.54 | 0.00 | 240.67 |
November | 318.83 | 0.56 | 0.48 | 01-NOV-08:30 | 609.72 | 12.54 | 0.00 | 257.17 | 360.24 | 16.12 | 0.00 | 185.67 |
December | 319.00 | 0.58 | 0.48 | 01-DEC-09:30 | 545.64 | 11.53 | 0.00 | 243.83 | 316.62 | 15.08 | 0.00 | 137.17 |
Annual Sum or Average | 4323.33 | 0.54 | 827.15 | 13.81 | 107.00 | 3677.00 | 466.38 | 17.04 | 62.67 | 3004.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 545.64 | 11.53 | 0.00 | 243.83 | 316.62 | 15.02 | 0.00 | 137.17 | |
Maximum of Months | 405.33 | 0.58 | 0.48 | 1117.68 | 18.33 | 77.33 | 366.50 | 608.53 | 19.55 | 34.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-10:20 | 1431.00 | 21.03 | 108.17 | 271.33 | 739.84 | 22.02 | 77.17 | 228.83 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:39 | 1395.57 | 19.38 | 76.33 | 258.83 | 697.91 | 20.57 | 48.33 | 218.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1596.71 | 19.01 | 85.83 | 306.83 | 806.32 | 21.29 | 65.83 | 266.83 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:50 | 1600.05 | 16.31 | 55.00 | 320.17 | 833.73 | 17.10 | 0.00 | 282.83 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-08:09 | 1699.49 | 13.89 | 0.00 | 347.83 | 870.78 | 17.38 | 0.00 | 309.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-08:09 | 1816.25 | 14.07 | 0.00 | 344.17 | 791.96 | 17.58 | 0.00 | 306.83 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:20 | 1733.99 | 14.10 | 3.67 | 345.33 | 775.73 | 17.36 | 0.00 | 304.83 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:20 | 1762.15 | 16.77 | 59.83 | 340.17 | 905.74 | 17.79 | 5.50 | 304.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1703.65 | 19.34 | 86.83 | 314.50 | 872.40 | 20.70 | 57.33 | 281.17 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-08:20 | 1772.54 | 21.04 | 107.83 | 300.00 | 911.22 | 22.36 | 79.33 | 269.00 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1522.58 | 20.03 | 85.00 | 273.17 | 788.85 | 22.49 | 69.00 | 240.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1330.35 | 19.58 | 87.33 | 265.00 | 689.08 | 22.07 | 71.33 | 222.67 |
Annual Sum or Average | 4323.33 | 0.54 | 1626.37 | 17.66 | 755.83 | 3687.33 | 810.97 | 19.71 | 473.83 | 3235.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1330.35 | 13.89 | 0.00 | 258.83 | 689.08 | 17.10 | 0.00 | 218.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1816.25 | 21.04 | 108.17 | 347.83 | 911.22 | 22.49 | 79.33 | 309.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225356E+09 | 6039.69 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139185E+09 | 6039.69 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54432255.69 | 6039.69 | 16-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1348143.35 | 1256.82 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52052836.94 | 5252.85 | 18-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225356E+09 | 6039.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 256015.24 | 996.78 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256015.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 256015.24 | 996.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1112798.76 | 1734.76 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19110.35 | 191.10 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1131909.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1112798.76 | 1734.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2101973.87 | 1539.86 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2101973.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2101973.87 | 1539.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9625755.42 | 2560.00 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 639493.32 | 1407.08 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 784937.09 | 655.90 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11050185.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9625755.42 | 2560.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.422534E+11 | 0.361600E+11 | 57648.81 | 30-JAN-14:00 | 43193.24 | 0.00 |
February | 0.00 | 0.00 | 0.446837E+11 | 0.375949E+11 | 77635.41 | 07-FEB-12:10 | 56628.99 | 0.00 |
March | 0.00 | 0.00 | 0.595291E+11 | 0.519562E+11 | 85905.51 | 28-MAR-11:40 | 58589.24 | 0.00 |
April | 0.00 | 0.00 | 0.705254E+11 | 0.601550E+11 | 92479.86 | 10-APR-12:00 | 59048.41 | 0.00 |
May | 0.00 | 0.00 | 0.105410E+12 | 0.874233E+11 | 150538.93 | 31-MAY-04:02 | 92606.74 | 0.00 |
June | 0.00 | 0.00 | 0.127529E+12 | 0.942523E+11 | 155675.09 | 14-JUN-04:03 | 80914.02 | 0.00 |
July | 0.00 | 0.00 | 0.154075E+12 | 0.104263E+12 | 153878.44 | 06-JUL-04:02 | 86375.09 | 0.00 |
August | 0.00 | 0.00 | 0.171716E+12 | 0.114092E+12 | 153236.05 | 26-AUG-04:02 | 86524.33 | 0.00 |
September | 0.00 | 0.00 | 0.137379E+12 | 0.939971E+11 | 154332.71 | 28-SEP-04:02 | 84831.09 | 0.00 |
October | 0.00 | 0.00 | 0.111498E+12 | 0.843557E+11 | 150818.04 | 06-OCT-04:02 | 91414.57 | 0.00 |
November | 0.00 | 0.00 | 0.805355E+11 | 0.651271E+11 | 127451.10 | 03-NOV-04:03 | 73917.45 | 0.00 |
December | 0.00 | 0.00 | 0.529354E+11 | 0.438204E+11 | 83492.38 | 11-DEC-06:12 | 56184.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115807E+13 | 0.873198E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.422534E+11 | 0.361600E+11 | 57648.81 | 43193.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171716E+12 | 0.114092E+12 | 155675.09 | 92606.74 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.320764E+11 | 0.255984E+11 | 43480.50 | 30-JAN-14:00 | 31691.92 | 0.00 |
February | 0.00 | 0.00 | 0.358419E+11 | 0.287070E+11 | 64071.86 | 07-FEB-15:50 | 47175.15 | 0.00 |
March | 0.00 | 0.00 | 0.498711E+11 | 0.423478E+11 | 66836.96 | 27-MAR-12:03 | 66836.96 | 0.00 |
April | 0.00 | 0.00 | 0.616890E+11 | 0.519209E+11 | 89136.76 | 30-APR-13:32 | 73365.94 | 0.00 |
May | 0.00 | 0.00 | 0.937379E+11 | 0.776780E+11 | 139729.94 | 24-MAY-05:03 | 70979.03 | 0.00 |
June | 0.00 | 0.00 | 0.113788E+12 | 0.832016E+11 | 143635.01 | 14-JUN-04:03 | 70255.64 | 0.00 |
July | 0.00 | 0.00 | 0.136906E+12 | 0.925910E+11 | 142700.72 | 06-JUL-04:02 | 73499.61 | 0.00 |
August | 0.00 | 0.00 | 0.147022E+12 | 0.984061E+11 | 142025.08 | 08-AUG-04:02 | 72386.11 | 0.00 |
September | 0.00 | 0.00 | 0.116152E+12 | 0.792889E+11 | 142632.57 | 28-SEP-04:02 | 72778.35 | 0.00 |
October | 0.00 | 0.00 | 0.906044E+11 | 0.684071E+11 | 139792.92 | 02-OCT-04:02 | 80378.28 | 0.00 |
November | 0.00 | 0.00 | 0.628880E+11 | 0.495477E+11 | 93029.20 | 03-NOV-05:03 | 51837.71 | 0.00 |
December | 0.00 | 0.00 | 0.408201E+11 | 0.316842E+11 | 61058.00 | 05-DEC-15:10 | 42102.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.981398E+12 | 0.729379E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.320764E+11 | 0.255984E+11 | 43480.50 | 31691.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.147022E+12 | 0.984061E+11 | 143635.01 | 80378.28 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321268E+11 | 0.247435E+11 | 44968.36 | 30-JAN-14:30 | 31676.14 | 0.00 |
February | 0.00 | 0.00 | 0.369270E+11 | 0.290016E+11 | 69225.98 | 07-FEB-15:30 | 53249.07 | 0.00 |
March | 0.00 | 0.00 | 0.523678E+11 | 0.439650E+11 | 75145.36 | 27-MAR-13:10 | 75145.36 | 0.00 |
April | 0.00 | 0.00 | 0.662228E+11 | 0.555239E+11 | 110325.56 | 30-APR-13:32 | 94689.98 | 0.00 |
May | 0.00 | 0.00 | 0.101815E+12 | 0.849937E+11 | 157675.81 | 31-MAY-04:02 | 91883.36 | 0.00 |
June | 0.00 | 0.00 | 0.123639E+12 | 0.918767E+11 | 163181.14 | 14-JUN-04:03 | 76041.20 | 0.00 |
July | 0.00 | 0.00 | 0.150057E+12 | 0.103657E+12 | 162119.71 | 06-JUL-04:02 | 84664.72 | 0.00 |
August | 0.00 | 0.00 | 0.160348E+12 | 0.109646E+12 | 161352.13 | 08-AUG-04:02 | 85944.99 | 0.00 |
September | 0.00 | 0.00 | 0.124163E+12 | 0.862856E+11 | 162785.60 | 28-SEP-04:02 | 80658.01 | 0.00 |
October | 0.00 | 0.00 | 0.945398E+11 | 0.718520E+11 | 158619.84 | 02-OCT-04:02 | 89202.76 | 0.00 |
November | 0.00 | 0.00 | 0.643210E+11 | 0.502177E+11 | 108693.81 | 03-NOV-05:03 | 58252.89 | 0.00 |
December | 0.00 | 0.00 | 0.412476E+11 | 0.311294E+11 | 64361.96 | 05-DEC-15:00 | 45082.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104777E+13 | 0.782892E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.321268E+11 | 0.247435E+11 | 44968.36 | 31676.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160348E+12 | 0.109646E+12 | 163181.14 | 94689.98 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1355.55 | 4611.80 | 12-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1329.91 | 4561.41 | 02-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1325.10 | 4363.93 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1129.61 | 3955.79 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1058.57 | 3571.83 | 04-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 999.90 | 3259.50 | 01-JUN-11:12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 897.90 | 3091.17 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 1018.74 | 3309.90 | 30-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 1041.37 | 3648.38 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1150.82 | 4075.45 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1275.64 | 4400.75 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1298.77 | 4588.59 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1155.90 | ||||
Minimum of Months | 0.00 | 0.00 | 897.90 | 3091.17 | ||
Maximum of Months | 0.00 | 0.00 | 1355.55 | 4611.80 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294155E+10 | 0.34 | 4623.85 | 02-JAN-14:00 | 0.96 |
February | 0.294168E+10 | 0.36 | 6305.43 | 08-FEB-13:10 | 1.15 |
March | 0.392120E+10 | 0.40 | 8849.67 | 27-MAR-12:08 | 1.43 |
April | 0.437969E+10 | 0.43 | 8869.13 | 24-APR-12:20 | 1.43 |
May | 0.656989E+10 | 0.55 | 12414.15 | 31-MAY-04:02 | 1.77 |
June | 0.708108E+10 | 0.60 | 12414.15 | 10-JUN-04:02 | 1.77 |
July | 0.701819E+10 | 0.61 | 12414.15 | 01-JUL-04:02 | 1.76 |
August | 0.746227E+10 | 0.65 | 12414.15 | 01-AUG-04:02 | 1.76 |
September | 0.627811E+10 | 0.57 | 12414.15 | 01-SEP-04:02 | 1.77 |
October | 0.585846E+10 | 0.52 | 12414.15 | 02-OCT-06:03 | 1.77 |
November | 0.504116E+10 | 0.47 | 11763.02 | 20-NOV-05:02 | 1.71 |
December | 0.351250E+10 | 0.37 | 6145.21 | 01-DEC-13:10 | 1.14 |
Annual Sum or Average | 0.630058E+11 | 0.49 | |||
Minimum of Months | 0.294155E+10 | 0.34 | 4623.85 | 0.96 | |
Maximum of Months | 0.746227E+10 | 0.65 | 12414.15 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195565E+10 | 0.30 | 2954.04 | 23-JAN-13:30 | 0.80 |
February | 0.212259E+10 | 0.33 | 5165.26 | 06-FEB-15:10 | 1.10 |
March | 0.309119E+10 | 0.38 | 7226.42 | 27-MAR-14:30 | 1.36 |
April | 0.365162E+10 | 0.42 | 7029.59 | 24-APR-14:10 | 1.34 |
May | 0.573718E+10 | 0.55 | 10953.28 | 12-MAY-04:02 | 1.77 |
June | 0.623529E+10 | 0.59 | 10953.28 | 01-JUN-04:02 | 1.77 |
July | 0.656301E+10 | 0.62 | 10953.28 | 01-JUL-04:02 | 1.76 |
August | 0.733843E+10 | 0.66 | 10953.28 | 03-AUG-06:03 | 1.76 |
September | 0.593835E+10 | 0.57 | 10953.28 | 06-SEP-04:03 | 1.76 |
October | 0.508104E+10 | 0.50 | 10953.28 | 02-OCT-04:02 | 1.77 |
November | 0.365729E+10 | 0.41 | 6625.07 | 13-NOV-14:50 | 1.29 |
December | 0.229511E+10 | 0.32 | 4329.99 | 04-DEC-13:10 | 0.99 |
Annual Sum or Average | 0.536667E+11 | 0.47 | |||
Minimum of Months | 0.195565E+10 | 0.30 | 2954.04 | 0.80 | |
Maximum of Months | 0.733843E+10 | 0.66 | 10953.28 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175755E+10 | 0.28 | 2509.97 | 23-JAN-14:00 | 0.67 |
February | 0.192709E+10 | 0.30 | 4761.40 | 06-FEB-15:00 | 0.95 |
March | 0.284201E+10 | 0.35 | 6875.93 | 27-MAR-14:40 | 1.19 |
April | 0.344413E+10 | 0.39 | 6974.24 | 28-APR-13:10 | 1.20 |
May | 0.554931E+10 | 0.50 | 12935.32 | 30-MAY-04:02 | 1.77 |
June | 0.609920E+10 | 0.54 | 12935.32 | 05-JUN-04:02 | 1.77 |
July | 0.653853E+10 | 0.58 | 12935.32 | 01-JUL-04:02 | 1.76 |
August | 0.724028E+10 | 0.61 | 12935.32 | 01-AUG-04:02 | 1.76 |
September | 0.569395E+10 | 0.52 | 12935.32 | 01-SEP-04:02 | 1.77 |
October | 0.468942E+10 | 0.44 | 12536.95 | 02-OCT-04:02 | 1.73 |
November | 0.318840E+10 | 0.37 | 6148.09 | 06-NOV-14:10 | 1.11 |
December | 0.202633E+10 | 0.30 | 3629.82 | 04-DEC-14:10 | 0.81 |
Annual Sum or Average | 0.509962E+11 | 0.43 | |||
Minimum of Months | 0.175755E+10 | 0.28 | 2509.97 | 0.67 | |
Maximum of Months | 0.724028E+10 | 0.61 | 12935.32 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.20 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.98 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.33 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.22 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.69 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 57.48 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.73 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:10 | 2.06 | 2.06 | 57.55 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:10 | 2.06 | 2.06 | 58.12 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.24 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.19 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.37 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.37 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.24 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.25 | 57.25 | 1355.55 | 4611.80 | 12-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.26 | 57.26 | 1329.91 | 4561.41 | 02-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.60 | 57.60 | 1325.10 | 4363.93 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.43 | 57.43 | 1129.61 | 3955.79 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.78 | 57.78 | 1058.57 | 3571.83 | 04-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.55 | 57.55 | 999.90 | 3259.50 | 01-JUN-11:12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.59 | 58.59 | 897.90 | 3091.17 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.66 | 57.66 | 1018.74 | 3309.90 | 30-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.25 | 58.25 | 1041.37 | 3648.38 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.85 | 57.85 | 1150.82 | 4075.45 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.15 | 58.15 | 1275.64 | 4400.75 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.62 | 56.62 | 1298.77 | 4588.59 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1155.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.62 | 56.62 | 897.90 | 3091.17 | ||
Maximum of Months | 0.00 | 0.00 | 58.59 | 58.59 | 1355.55 | 4611.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.136350E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141905E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192160E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.233282E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.372146E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.443674E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.528225E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.586735E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.452972E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.361298E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256808E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165636E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.387119E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136350E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.586735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100970E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111942E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159999E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202559E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.328063E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.391733E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.469072E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.508643E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.386533E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.296009E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.198595E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125296E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.327942E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100970E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508643E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100362E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113902E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165428E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214318E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.351103E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.420126E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.508511E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.547819E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.407862E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.304592E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.199342E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125238E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.345860E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100362E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.547819E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.294155E+10 | 0.422534E+11 | 0.225356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294168E+10 | 0.446837E+11 | 0.139185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392120E+10 | 0.595291E+11 | 54432255.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437969E+10 | 0.705254E+11 | 1348143.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.656989E+10 | 0.105410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.708108E+10 | 0.127529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.701819E+10 | 0.154075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746227E+10 | 0.171716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.627811E+10 | 0.137379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.585846E+10 | 0.111498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504116E+10 | 0.805355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351250E+10 | 0.529354E+11 | 52052836.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630058E+11 | 0.115807E+13 | 0.472375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294155E+10 | 0.422534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746227E+10 | 0.171716E+12 | 0.225356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.195565E+10 | 0.320764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212259E+10 | 0.358419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309119E+10 | 0.498711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365162E+10 | 0.616890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573718E+10 | 0.937379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623529E+10 | 0.113788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656301E+10 | 0.136906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733843E+10 | 0.147022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.593835E+10 | 0.116152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.508104E+10 | 0.906044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365729E+10 | 0.628880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229511E+10 | 0.408201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536667E+11 | 0.981398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.195565E+10 | 0.320764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733843E+10 | 0.147022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175755E+10 | 0.321268E+11 | 13096543.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192709E+10 | 0.369270E+11 | 639493.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284201E+10 | 0.523678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344413E+10 | 0.662228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.554931E+10 | 0.101815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609920E+10 | 0.123639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.653853E+10 | 0.150057E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724028E+10 | 0.160348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569395E+10 | 0.124163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468942E+10 | 0.945398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318840E+10 | 0.643210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202633E+10 | 0.412476E+11 | 804047.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509962E+11 | 0.104777E+13 | 14540084.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175755E+10 | 0.321268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724028E+10 | 0.160348E+12 | 13096543.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.294155E+10 | 0.00 | 0.00 | 0.00 | 0.104681E+11 | 0.225356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294168E+10 | 0.00 | 0.00 | 0.00 | 0.111096E+11 | 0.139185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392120E+10 | 0.00 | 0.00 | 0.00 | 0.152403E+11 | 54432255.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437969E+10 | 0.00 | 0.00 | 0.00 | 0.189471E+11 | 1348143.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.656989E+10 | 0.00 | 0.00 | 0.00 | 0.306447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.708108E+10 | 0.00 | 0.00 | 0.00 | 0.372863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.701819E+10 | 0.00 | 0.00 | 0.00 | 0.458043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746227E+10 | 0.00 | 0.00 | 0.00 | 0.512113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.627811E+10 | 0.00 | 0.00 | 0.00 | 0.390191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.585846E+10 | 0.00 | 0.00 | 0.00 | 0.302713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504116E+10 | 0.00 | 0.00 | 0.00 | 0.206396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351250E+10 | 0.00 | 0.00 | 0.00 | 0.129990E+11 | 52052836.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630058E+11 | 0.00 | 0.00 | 0.00 | 0.323641E+12 | 0.472375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294155E+10 | 0.00 | 0.00 | 0.00 | 0.104681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746227E+10 | 0.00 | 0.00 | 0.00 | 0.512113E+11 | 0.225356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.195565E+10 | 0.00 | 0.00 | 0.00 | 0.814137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212259E+10 | 0.00 | 0.00 | 0.00 | 0.907164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309119E+10 | 0.00 | 0.00 | 0.00 | 0.129087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365162E+10 | 0.00 | 0.00 | 0.00 | 0.166043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573718E+10 | 0.00 | 0.00 | 0.00 | 0.270691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623529E+10 | 0.00 | 0.00 | 0.00 | 0.329380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656301E+10 | 0.00 | 0.00 | 0.00 | 0.403442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733843E+10 | 0.00 | 0.00 | 0.00 | 0.435259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.593835E+10 | 0.00 | 0.00 | 0.00 | 0.327150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.508104E+10 | 0.00 | 0.00 | 0.00 | 0.245199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365729E+10 | 0.00 | 0.00 | 0.00 | 0.162022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229511E+10 | 0.00 | 0.00 | 0.00 | 0.102345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536667E+11 | 0.00 | 0.00 | 0.00 | 0.274275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.195565E+10 | 0.00 | 0.00 | 0.00 | 0.814137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733843E+10 | 0.00 | 0.00 | 0.00 | 0.435259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175755E+10 | 0.00 | 0.00 | 0.00 | 0.826561E+10 | 13096543.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192709E+10 | 0.00 | 0.00 | 0.00 | 0.946244E+10 | 639493.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284201E+10 | 0.00 | 0.00 | 0.00 | 0.137008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344413E+10 | 0.00 | 0.00 | 0.00 | 0.179877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.554931E+10 | 0.00 | 0.00 | 0.00 | 0.295610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609920E+10 | 0.00 | 0.00 | 0.00 | 0.359134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.653853E+10 | 0.00 | 0.00 | 0.00 | 0.443126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724028E+10 | 0.00 | 0.00 | 0.00 | 0.475416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569395E+10 | 0.00 | 0.00 | 0.00 | 0.350922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468942E+10 | 0.00 | 0.00 | 0.00 | 0.257698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318840E+10 | 0.00 | 0.00 | 0.00 | 0.167458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202633E+10 | 0.00 | 0.00 | 0.00 | 0.104967E+11 | 804047.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509962E+11 | 0.00 | 0.00 | 0.00 | 0.294850E+12 | 14540084.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175755E+10 | 0.00 | 0.00 | 0.00 | 0.826561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724028E+10 | 0.00 | 0.00 | 0.00 | 0.475416E+11 | 13096543.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243958E+09 | 0.364266E+09 | 0.00 | 34515431.61 | 0.138541E+09 | 0.00 | 0.324171E+10 | 0.00 | 0.39 |
February | 0.131108E+09 | 0.110861E+10 | 0.00 | 23337244.84 | 0.141872E+09 | 0.00 | 0.163676E+10 | 0.00 | 0.37 |
March | 98397628.67 | 0.217912E+10 | 0.00 | 20938346.23 | 0.182544E+09 | 0.00 | 0.132724E+10 | 0.00 | 0.38 |
April | 47304968.30 | 0.447934E+10 | 0.00 | 6780556.11 | 0.970564E+09 | 0.00 | 0.406725E+09 | 0.00 | 0.35 |
May | 18805662.81 | 0.884431E+10 | 0.00 | 1752432.31 | 0.260010E+10 | 0.00 | 67380788.19 | 0.00 | 0.35 |
June | 3366354.19 | 0.140614E+11 | 0.00 | 348779.92 | 0.426565E+10 | 0.00 | 11847112.85 | 0.00 | 0.35 |
July | 2133221.49 | 0.178197E+11 | 0.00 | 7485.67 | 0.913888E+10 | 0.00 | 193162.00 | 0.00 | 0.38 |
August | 0.00 | 0.204785E+11 | 0.00 | 0.00 | 0.913640E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 62521.71 | 0.155372E+11 | 0.00 | 54951.08 | 0.609051E+10 | 0.00 | 119014.01 | 0.00 | 0.36 |
October | 30786366.52 | 0.982548E+10 | 0.00 | 1276929.70 | 0.362223E+10 | 0.00 | 55766600.67 | 0.00 | 0.34 |
November | 14485958.30 | 0.529525E+10 | 0.00 | 3830125.15 | 0.815194E+09 | 0.00 | 0.107017E+09 | 0.00 | 0.33 |
December | 0.105841E+09 | 0.157729E+10 | 0.00 | 25102370.28 | 0.363892E+09 | 0.00 | 0.148615E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.696249E+09 | 0.101570E+12 | 0.00 | 0.117945E+09 | 0.374664E+11 | 0.00 | 0.834091E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.364266E+09 | 0.00 | 0.00 | 0.138541E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.243958E+09 | 0.204785E+11 | 0.00 | 34515431.61 | 0.913888E+10 | 0.00 | 0.324171E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.766442E+09 | 0.366952E+09 | 0.00 | 13652472.70 | 0.204309E+09 | 0.00 | 0.157824E+10 | 0.00 | 0.30 |
February | 0.357243E+09 | 0.948029E+09 | 0.00 | 10120730.66 | 0.243679E+09 | 0.00 | 0.840082E+09 | 0.00 | 0.30 |
March | 0.268352E+09 | 0.185968E+10 | 0.00 | 10820713.84 | 0.247645E+09 | 0.00 | 0.759646E+09 | 0.00 | 0.31 |
April | 0.139342E+09 | 0.381245E+10 | 0.00 | 4161090.46 | 0.101852E+10 | 0.00 | 0.260337E+09 | 0.00 | 0.31 |
May | 38608565.76 | 0.783305E+10 | 0.00 | 1210881.37 | 0.255037E+10 | 0.00 | 57504693.60 | 0.00 | 0.33 |
June | 7290453.88 | 0.127826E+11 | 0.00 | 257295.96 | 0.422842E+10 | 0.00 | 11771326.24 | 0.00 | 0.34 |
July | 4299517.28 | 0.165778E+11 | 0.00 | 3742.18 | 0.841862E+10 | 0.00 | 62834.38 | 0.00 | 0.36 |
August | 0.00 | 0.192162E+11 | 0.00 | 0.00 | 0.749907E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 325543.00 | 0.145284E+11 | 0.00 | 108793.22 | 0.473108E+10 | 0.00 | 2592216.59 | 0.00 | 0.33 |
October | 38844738.47 | 0.895133E+10 | 0.00 | 1026027.93 | 0.268593E+10 | 0.00 | 41693888.04 | 0.00 | 0.31 |
November | 30297111.88 | 0.491350E+10 | 0.00 | 2289480.28 | 0.643272E+09 | 0.00 | 67416237.23 | 0.00 | 0.30 |
December | 0.324506E+09 | 0.146904E+10 | 0.00 | 10641976.44 | 0.421139E+09 | 0.00 | 0.710916E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.197555E+10 | 0.932590E+11 | 0.00 | 54293205.04 | 0.328921E+11 | 0.00 | 0.433026E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.366952E+09 | 0.00 | 0.00 | 0.204309E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.766442E+09 | 0.192162E+11 | 0.00 | 13652472.70 | 0.841862E+10 | 0.00 | 0.157824E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.863600E+09 | 0.352916E+09 | 0.00 | 8959563.46 | 0.332291E+09 | 0.00 | 0.922073E+09 | 0.00 | 0.29 |
February | 0.397562E+09 | 0.916939E+09 | 0.00 | 7357000.15 | 0.403754E+09 | 0.00 | 0.499247E+09 | 0.00 | 0.29 |
March | 0.326067E+09 | 0.187473E+10 | 0.00 | 7130742.89 | 0.315629E+09 | 0.00 | 0.421424E+09 | 0.00 | 0.31 |
April | 0.136816E+09 | 0.380592E+10 | 0.00 | 2480943.24 | 0.100828E+10 | 0.00 | 0.121806E+09 | 0.00 | 0.31 |
May | 37276478.23 | 0.766496E+10 | 0.00 | 1074374.33 | 0.252646E+10 | 0.00 | 32200210.73 | 0.00 | 0.32 |
June | 9984996.37 | 0.124395E+11 | 0.00 | 307761.64 | 0.445483E+10 | 0.00 | 6730276.63 | 0.00 | 0.34 |
July | 1819678.67 | 0.163050E+11 | 0.00 | 0.00 | 0.896649E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.188923E+11 | 0.00 | 0.00 | 0.819772E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 586002.17 | 0.140643E+11 | 0.00 | 49644.81 | 0.498949E+10 | 0.00 | 1159228.62 | 0.00 | 0.33 |
October | 41266737.54 | 0.870980E+10 | 0.00 | 896687.80 | 0.268172E+10 | 0.00 | 19138766.65 | 0.00 | 0.31 |
November | 20340725.56 | 0.498901E+10 | 0.00 | 1498009.90 | 0.657521E+09 | 0.00 | 36991606.37 | 0.00 | 0.29 |
December | 0.343306E+09 | 0.137569E+10 | 0.00 | 6388853.71 | 0.715001E+09 | 0.00 | 0.335737E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.217862E+10 | 0.913911E+11 | 0.00 | 36143581.93 | 0.352492E+11 | 0.00 | 0.239651E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.352916E+09 | 0.00 | 0.00 | 0.315629E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.863600E+09 | 0.188923E+11 | 0.00 | 8959563.46 | 0.896649E+10 | 0.00 | 0.922073E+09 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264050E+09 | 69290268.47 | 0.00 | 1430789.57 | 87085446.54 | 332428.14 | 0.134051E+09 | 0.00 | 0.31 |
February | 0.111811E+09 | 0.194274E+09 | 0.00 | 1546987.02 | 0.122554E+09 | 0.00 | 95338224.90 | 0.00 | 0.32 |
March | 85525641.14 | 0.513376E+09 | 0.00 | 1592237.07 | 74356345.33 | 0.00 | 91414851.34 | 0.00 | 0.37 |
April | 39799228.39 | 0.124240E+10 | 0.00 | 560782.23 | 0.202118E+09 | 0.00 | 21053671.15 | 0.00 | 0.42 |
May | 7313794.09 | 0.314085E+10 | 0.00 | 296947.61 | 0.353035E+09 | 0.00 | 9515874.64 | 0.00 | 0.52 |
June | 1479568.11 | 0.550001E+10 | 0.00 | 104291.66 | 0.540084E+09 | 0.00 | 2613703.08 | 0.00 | 0.57 |
July | 286443.91 | 0.769785E+10 | 0.00 | 12186.43 | 0.118283E+10 | 0.00 | 130747.28 | 0.00 | 0.62 |
August | 0.00 | 0.841866E+10 | 0.00 | 0.00 | 0.111580E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 184180.64 | 0.564779E+10 | 0.00 | 10352.51 | 0.710818E+09 | 0.00 | 219629.36 | 0.00 | 0.51 |
October | 10613389.28 | 0.285737E+10 | 0.00 | 256860.18 | 0.503203E+09 | 0.00 | 4093626.72 | 0.00 | 0.43 |
November | 5013674.68 | 0.129885E+10 | 0.00 | 389074.43 | 0.192234E+09 | 0.00 | 9549580.55 | 0.00 | 0.36 |
December | 92642862.93 | 0.308959E+09 | 0.00 | 1211403.23 | 0.178011E+09 | 0.00 | 61300558.02 | 0.00 | 0.31 |
Annual Sum or Average | 0.618719E+09 | 0.368897E+11 | 0.00 | 7411911.95 | 0.526213E+10 | 332428.14 | 0.429282E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 69290268.47 | 0.00 | 0.00 | 74356345.33 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.264050E+09 | 0.841866E+10 | 0.00 | 1592237.07 | 0.118283E+10 | 332428.14 | 0.134051E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179372E+09 | 70420186.42 | 0.00 | 1416573.37 | 55672163.74 | 422487.71 | 0.135792E+09 | 0.00 | 0.39 |
February | 80639982.28 | 0.159353E+09 | 0.00 | 1380967.39 | 92177779.88 | 0.00 | 85141246.91 | 0.00 | 0.42 |
March | 64098928.62 | 0.430082E+09 | 0.00 | 1335944.13 | 49154207.18 | 0.00 | 74748518.29 | 0.00 | 0.47 |
April | 31239845.30 | 0.104176E+10 | 0.00 | 530205.89 | 0.122998E+09 | 0.00 | 17833838.34 | 0.00 | 0.54 |
May | 5680391.67 | 0.240919E+10 | 0.00 | 246452.58 | 0.269504E+09 | 0.00 | 7534695.54 | 0.00 | 0.65 |
June | 1354376.14 | 0.410370E+10 | 0.00 | 83497.85 | 0.436358E+09 | 0.00 | 1882265.88 | 0.00 | 0.68 |
July | 224583.34 | 0.565438E+10 | 0.00 | 10624.16 | 0.972699E+09 | 0.00 | 99656.71 | 0.00 | 0.74 |
August | 0.00 | 0.633207E+10 | 0.00 | 0.00 | 0.899901E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 186984.76 | 0.435178E+10 | 0.00 | 5925.40 | 0.567283E+09 | 0.00 | 127776.53 | 0.00 | 0.64 |
October | 5662555.94 | 0.234030E+10 | 0.00 | 327151.23 | 0.344017E+09 | 0.00 | 6992145.50 | 0.00 | 0.55 |
November | 3677211.89 | 0.107079E+10 | 0.00 | 300041.35 | 0.133593E+09 | 0.00 | 7047614.62 | 0.00 | 0.46 |
December | 65180488.02 | 0.262563E+09 | 0.00 | 1006827.37 | 0.128595E+09 | 0.00 | 55120965.09 | 0.00 | 0.39 |
Annual Sum or Average | 0.437317E+09 | 0.282264E+11 | 0.00 | 6644210.72 | 0.407195E+10 | 422487.71 | 0.392321E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 70420186.42 | 0.00 | 0.00 | 49154207.18 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.179372E+09 | 0.633207E+10 | 0.00 | 1416573.37 | 0.972699E+09 | 422487.71 | 0.135792E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234923E+09 | 0.181150E+09 | 0.00 | 3911866.05 | 58096476.68 | 0.00 | 0.341826E+09 | 0.00 | 0.47 |
February | 0.109888E+09 | 0.352934E+09 | 0.00 | 3184904.74 | 80371695.14 | 0.00 | 0.189728E+09 | 0.00 | 0.47 |
March | 91612932.76 | 0.699511E+09 | 0.00 | 2481427.90 | 62842911.81 | 0.00 | 0.138044E+09 | 0.00 | 0.48 |
April | 45069573.17 | 0.145082E+10 | 0.00 | 620268.33 | 0.193856E+09 | 0.00 | 22409860.56 | 0.00 | 0.47 |
May | 8798223.00 | 0.310224E+10 | 0.00 | 276499.49 | 0.430698E+09 | 0.00 | 9288990.79 | 0.00 | 0.52 |
June | 1921420.70 | 0.521236E+10 | 0.00 | 96499.20 | 0.680535E+09 | 0.00 | 2471592.24 | 0.00 | 0.55 |
July | 317164.87 | 0.750055E+10 | 0.00 | 9573.16 | 0.144003E+10 | 0.00 | 144935.83 | 0.00 | 0.62 |
August | 0.00 | 0.880523E+10 | 0.00 | 0.00 | 0.128641E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 264066.76 | 0.672804E+10 | 0.00 | 10155.04 | 0.726833E+09 | 0.00 | 181855.96 | 0.00 | 0.61 |
October | 8590593.05 | 0.403305E+10 | 0.00 | 775562.79 | 0.405836E+09 | 0.00 | 11162132.73 | 0.00 | 0.58 |
November | 5376903.69 | 0.208464E+10 | 0.00 | 708360.24 | 0.108096E+09 | 0.00 | 16161702.78 | 0.00 | 0.54 |
December | 83185854.17 | 0.653110E+09 | 0.00 | 2893021.04 | 0.107013E+09 | 0.00 | 0.143612E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.589948E+09 | 0.408036E+11 | 0.00 | 14968137.98 | 0.558062E+10 | 0.00 | 0.875031E+09 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.181150E+09 | 0.00 | 0.00 | 58096476.68 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.234923E+09 | 0.880523E+10 | 0.00 | 3911866.05 | 0.144003E+10 | 0.00 | 0.341826E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240569E+09 | 59704916.43 | 0.00 | 1274367.69 | 75133660.71 | 932206.45 | 0.119195E+09 | 0.00 | 0.43 |
February | 98947102.34 | 0.164284E+09 | 0.00 | 1400055.69 | 0.107222E+09 | 94827.02 | 91103887.49 | 0.00 | 0.45 |
March | 77745905.14 | 0.431578E+09 | 0.00 | 1387865.86 | 67719940.94 | 0.00 | 86274301.39 | 0.00 | 0.51 |
April | 37874252.51 | 0.105047E+10 | 0.00 | 377451.71 | 0.155223E+09 | 0.00 | 14439626.30 | 0.00 | 0.54 |
May | 8105045.98 | 0.247434E+10 | 0.00 | 179641.49 | 0.311041E+09 | 0.00 | 6079494.73 | 0.00 | 0.64 |
June | 2032282.44 | 0.418305E+10 | 0.00 | 64066.24 | 0.501681E+09 | 0.00 | 1374620.16 | 0.00 | 0.69 |
July | 254376.20 | 0.569118E+10 | 0.00 | 7098.95 | 0.114911E+10 | 0.00 | 114278.37 | 0.00 | 0.75 |
August | 0.00 | 0.642208E+10 | 0.00 | 0.00 | 0.106384E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 276912.80 | 0.450175E+10 | 0.00 | 5642.38 | 0.622717E+09 | 0.00 | 78524.75 | 0.00 | 0.65 |
October | 10169560.16 | 0.229077E+10 | 0.00 | 154164.70 | 0.420611E+09 | 0.00 | 2414816.02 | 0.00 | 0.55 |
November | 4455485.62 | 0.103764E+10 | 0.00 | 345956.36 | 0.181424E+09 | 0.00 | 8844873.30 | 0.00 | 0.48 |
December | 80583534.54 | 0.252320E+09 | 0.00 | 1032089.45 | 0.176273E+09 | 0.00 | 59640172.58 | 0.00 | 0.43 |
Annual Sum or Average | 0.561013E+09 | 0.285592E+11 | 0.00 | 6228400.52 | 0.483200E+10 | 1027033.47 | 0.389560E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 59704916.43 | 0.00 | 0.00 | 67719940.94 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.240569E+09 | 0.642208E+10 | 0.00 | 1400055.69 | 0.114911E+10 | 932206.45 | 0.119195E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214022E+09 | 54696889.03 | 0.00 | 2820779.82 | 32934263.58 | 0.00 | 0.256360E+09 | 0.00 | 0.26 |
February | 0.115093E+09 | 0.174303E+09 | 0.00 | 2144864.35 | 43278495.60 | 0.00 | 0.135625E+09 | 0.00 | 0.27 |
March | 98720609.63 | 0.395031E+09 | 0.00 | 1910628.13 | 42281683.92 | 0.00 | 0.107829E+09 | 0.00 | 0.29 |
April | 44549065.28 | 0.944856E+09 | 0.00 | 582269.44 | 0.209051E+09 | 0.00 | 28077626.70 | 0.00 | 0.32 |
May | 6489351.96 | 0.258144E+10 | 0.00 | 262129.34 | 0.395032E+09 | 0.00 | 10880124.41 | 0.00 | 0.41 |
June | 900146.53 | 0.460373E+10 | 0.00 | 59800.83 | 0.557075E+09 | 0.00 | 2234833.66 | 0.00 | 0.46 |
July | 444257.48 | 0.674883E+10 | 0.00 | 4789.12 | 0.121798E+10 | 0.00 | 50397.86 | 0.00 | 0.53 |
August | 0.00 | 0.771269E+10 | 0.00 | 0.00 | 0.126697E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 13194.88 | 0.521980E+10 | 0.00 | 15443.26 | 0.918217E+09 | 0.00 | 22548.13 | 0.00 | 0.47 |
October | 6692764.35 | 0.276919E+10 | 0.00 | 247763.67 | 0.636754E+09 | 0.00 | 11050433.72 | 0.00 | 0.41 |
November | 8643475.18 | 0.117922E+10 | 0.00 | 531726.07 | 0.174351E+09 | 0.00 | 12407778.74 | 0.00 | 0.33 |
December | 88128936.67 | 0.282807E+09 | 0.00 | 2788159.60 | 78397381.99 | 0.00 | 0.152854E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.583697E+09 | 0.326666E+11 | 0.00 | 11368353.61 | 0.557232E+10 | 0.00 | 0.717391E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 54696889.03 | 0.00 | 0.00 | 32934263.58 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.214022E+09 | 0.771269E+10 | 0.00 | 2820779.82 | 0.126697E+10 | 0.00 | 0.256360E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144457E+09 | 46936992.09 | 0.00 | 2705436.93 | 24771713.21 | 0.00 | 0.244170E+09 | 0.00 | 0.34 |
February | 83185992.35 | 0.139015E+09 | 0.00 | 2049650.78 | 30890506.60 | 0.00 | 0.125853E+09 | 0.00 | 0.35 |
March | 73237743.67 | 0.325549E+09 | 0.00 | 1673754.62 | 31864452.03 | 0.00 | 94267178.16 | 0.00 | 0.38 |
April | 33250758.37 | 0.815693E+09 | 0.00 | 587811.94 | 0.127384E+09 | 0.00 | 27571360.81 | 0.00 | 0.43 |
May | 4411159.76 | 0.208193E+10 | 0.00 | 241363.86 | 0.253823E+09 | 0.00 | 9524344.98 | 0.00 | 0.52 |
June | 710561.95 | 0.353152E+10 | 0.00 | 40914.49 | 0.420165E+09 | 0.00 | 1746010.12 | 0.00 | 0.56 |
July | 350690.08 | 0.512582E+10 | 0.00 | 5347.52 | 0.929781E+09 | 0.00 | 45556.44 | 0.00 | 0.64 |
August | 0.00 | 0.593635E+10 | 0.00 | 0.00 | 0.965478E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 10415.84 | 0.412756E+10 | 0.00 | 10026.38 | 0.667667E+09 | 0.00 | 18997.45 | 0.00 | 0.59 |
October | 3351329.69 | 0.230094E+10 | 0.00 | 295045.95 | 0.407306E+09 | 0.00 | 12356994.83 | 0.00 | 0.51 |
November | 6284611.16 | 0.930785E+09 | 0.00 | 450192.87 | 0.124530E+09 | 0.00 | 11094604.87 | 0.00 | 0.41 |
December | 59509848.08 | 0.220351E+09 | 0.00 | 2373604.29 | 62157627.03 | 0.00 | 0.134968E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.408760E+09 | 0.255825E+11 | 0.00 | 10433149.61 | 0.404582E+10 | 0.00 | 0.661616E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 46936992.09 | 0.00 | 0.00 | 24771713.21 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.144457E+09 | 0.593635E+10 | 0.00 | 2705436.93 | 0.965478E+09 | 0.00 | 0.244170E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190331E+09 | 0.112495E+09 | 0.00 | 4904787.80 | 26312871.48 | 53344548.15 | 0.369344E+09 | 0.00 | 0.37 |
February | 97848088.96 | 0.306711E+09 | 0.00 | 3730516.56 | 23054067.50 | 26953017.42 | 0.207573E+09 | 0.00 | 0.39 |
March | 97024306.13 | 0.645378E+09 | 0.00 | 2753265.55 | 36360547.64 | 11138424.02 | 0.143229E+09 | 0.00 | 0.41 |
April | 53319431.58 | 0.137018E+10 | 0.00 | 708830.98 | 0.196802E+09 | 47177.02 | 26499242.09 | 0.00 | 0.43 |
May | 6888573.95 | 0.337710E+10 | 0.00 | 341575.48 | 0.442614E+09 | 0.00 | 12386216.88 | 0.00 | 0.53 |
June | 865719.87 | 0.570598E+10 | 0.00 | 68054.16 | 0.683569E+09 | 0.00 | 2471699.74 | 0.00 | 0.58 |
July | 471900.19 | 0.863638E+10 | 0.00 | 4950.55 | 0.137486E+10 | 0.00 | 60527.26 | 0.00 | 0.66 |
August | 0.00 | 0.106859E+11 | 0.00 | 0.00 | 0.129882E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 14015.90 | 0.784887E+10 | 0.00 | 20549.02 | 0.797163E+09 | 0.00 | 29815.91 | 0.00 | 0.67 |
October | 4465224.43 | 0.476897E+10 | 0.00 | 669905.19 | 0.403069E+09 | 0.00 | 17397459.07 | 0.00 | 0.62 |
November | 11076497.13 | 0.214710E+10 | 0.00 | 763318.28 | 87653963.90 | 0.00 | 16506517.95 | 0.00 | 0.53 |
December | 87108858.74 | 0.543152E+09 | 0.00 | 4516933.75 | 52382612.93 | 12990131.11 | 0.228638E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.549413E+09 | 0.461482E+11 | 0.00 | 18482687.33 | 0.542266E+10 | 0.104473E+09 | 0.102414E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.112495E+09 | 0.00 | 0.00 | 23054067.50 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.190331E+09 | 0.106859E+11 | 0.00 | 4904787.80 | 0.137486E+10 | 53344548.15 | 0.369344E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174926E+09 | 48978470.14 | 0.00 | 2385120.37 | 25710987.58 | 0.00 | 0.221540E+09 | 0.00 | 0.35 |
February | 95619665.05 | 0.149184E+09 | 0.00 | 1880775.22 | 31599895.17 | 0.00 | 0.120710E+09 | 0.00 | 0.36 |
March | 80617034.38 | 0.349793E+09 | 0.00 | 1645234.27 | 27612124.31 | 0.00 | 98283782.84 | 0.00 | 0.40 |
April | 38636966.27 | 0.853395E+09 | 0.00 | 411138.97 | 0.126516E+09 | 0.00 | 19488348.69 | 0.00 | 0.42 |
May | 5629894.49 | 0.215880E+10 | 0.00 | 190679.70 | 0.266589E+09 | 0.00 | 8456730.57 | 0.00 | 0.52 |
June | 610863.82 | 0.366884E+10 | 0.00 | 44028.64 | 0.399668E+09 | 0.00 | 1978401.18 | 0.00 | 0.57 |
July | 370981.08 | 0.521116E+10 | 0.00 | 4338.54 | 0.970904E+09 | 0.00 | 51297.32 | 0.00 | 0.65 |
August | 0.00 | 0.608677E+10 | 0.00 | 0.00 | 0.983311E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 11018.50 | 0.431422E+10 | 0.00 | 9967.64 | 0.648364E+09 | 0.00 | 20732.88 | 0.00 | 0.59 |
October | 5461938.57 | 0.231615E+10 | 0.00 | 176523.66 | 0.427531E+09 | 0.00 | 8395253.66 | 0.00 | 0.51 |
November | 7075648.93 | 0.956608E+09 | 0.00 | 418126.43 | 0.119010E+09 | 0.00 | 10178361.50 | 0.00 | 0.41 |
December | 76551489.37 | 0.235084E+09 | 0.00 | 2160678.98 | 65897288.67 | 0.00 | 0.124387E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.485511E+09 | 0.263490E+11 | 0.00 | 9326612.42 | 0.409271E+10 | 0.00 | 0.613490E+09 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 48978470.14 | 0.00 | 0.00 | 25710987.58 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.174926E+09 | 0.608677E+10 | 0.00 | 2385120.37 | 0.983311E+09 | 0.00 | 0.221540E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273009E+09 | 74357577.06 | 0.00 | 1940970.64 | 47014591.10 | 0.00 | 0.189847E+09 | 0.00 | 0.29 |
February | 0.133022E+09 | 0.218287E+09 | 0.00 | 1776867.79 | 57963850.77 | 0.00 | 0.117506E+09 | 0.00 | 0.31 |
March | 0.102858E+09 | 0.526469E+09 | 0.00 | 1943593.75 | 45341614.71 | 0.00 | 0.116033E+09 | 0.00 | 0.36 |
April | 47311223.45 | 0.126827E+10 | 0.00 | 729009.74 | 0.184108E+09 | 0.00 | 36876819.54 | 0.00 | 0.41 |
May | 7056787.77 | 0.324824E+10 | 0.00 | 337810.27 | 0.315717E+09 | 0.00 | 14492211.78 | 0.00 | 0.51 |
June | 1390955.86 | 0.566747E+10 | 0.00 | 83442.55 | 0.438924E+09 | 0.00 | 2878600.49 | 0.00 | 0.56 |
July | 674349.91 | 0.791318E+10 | 0.00 | 23243.11 | 0.939715E+09 | 0.00 | 294805.29 | 0.00 | 0.60 |
August | 0.00 | 0.864732E+10 | 0.00 | 0.00 | 0.868982E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 68691.95 | 0.575458E+10 | 0.00 | 24177.95 | 0.630821E+09 | 0.00 | 549091.69 | 0.00 | 0.51 |
October | 9712181.83 | 0.291759E+10 | 0.00 | 247146.31 | 0.471960E+09 | 0.00 | 7292789.07 | 0.00 | 0.43 |
November | 10670577.21 | 0.130971E+10 | 0.00 | 394739.60 | 0.144470E+09 | 0.00 | 10892807.49 | 0.00 | 0.36 |
December | 0.116844E+09 | 0.333383E+09 | 0.00 | 1688515.53 | 89062571.81 | 0.00 | 95829068.54 | 0.00 | 0.30 |
Annual Sum or Average | 0.702618E+09 | 0.378788E+11 | 0.00 | 9189517.24 | 0.423408E+10 | 0.00 | 0.592493E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 74357577.06 | 0.00 | 0.00 | 45341614.71 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.273009E+09 | 0.864732E+10 | 0.00 | 1943593.75 | 0.939715E+09 | 0.00 | 0.189847E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207004E+09 | 62151273.76 | 0.00 | 1744606.44 | 37191229.00 | 0.00 | 0.179153E+09 | 0.00 | 0.38 |
February | 0.104715E+09 | 0.159032E+09 | 0.00 | 1578848.21 | 59330690.22 | 0.00 | 0.105033E+09 | 0.00 | 0.41 |
March | 86245132.98 | 0.417631E+09 | 0.00 | 1565644.12 | 36385372.93 | 0.00 | 92779148.44 | 0.00 | 0.46 |
April | 40895312.83 | 0.102746E+10 | 0.00 | 671822.17 | 0.125723E+09 | 0.00 | 31646297.41 | 0.00 | 0.53 |
May | 5834252.01 | 0.245912E+10 | 0.00 | 255052.13 | 0.263634E+09 | 0.00 | 11843988.16 | 0.00 | 0.64 |
June | 1281546.00 | 0.416806E+10 | 0.00 | 58002.75 | 0.420329E+09 | 0.00 | 2203585.46 | 0.00 | 0.67 |
July | 566650.06 | 0.576625E+10 | 0.00 | 15579.16 | 0.862147E+09 | 0.00 | 225459.16 | 0.00 | 0.72 |
August | 0.00 | 0.642927E+10 | 0.00 | 0.00 | 0.797499E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 165347.90 | 0.440037E+10 | 0.00 | 12638.19 | 0.539943E+09 | 0.00 | 339824.34 | 0.00 | 0.63 |
October | 5838191.85 | 0.234127E+10 | 0.00 | 310847.08 | 0.353777E+09 | 0.00 | 9891746.16 | 0.00 | 0.54 |
November | 8202694.32 | 0.101607E+10 | 0.00 | 325351.69 | 0.119202E+09 | 0.00 | 9050777.83 | 0.00 | 0.45 |
December | 90552166.52 | 0.260844E+09 | 0.00 | 1351789.82 | 78357180.52 | 0.00 | 83538238.13 | 0.00 | 0.39 |
Annual Sum or Average | 0.551300E+09 | 0.285075E+11 | 0.00 | 7890181.75 | 0.369352E+10 | 0.00 | 0.525705E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 62151273.76 | 0.00 | 0.00 | 36385372.93 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.207004E+09 | 0.642927E+10 | 0.00 | 1744606.44 | 0.862147E+09 | 0.00 | 0.179153E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239570E+09 | 0.175450E+09 | 0.00 | 4646256.49 | 25313542.79 | 0.00 | 0.436664E+09 | 0.00 | 0.46 |
February | 0.130149E+09 | 0.370627E+09 | 0.00 | 3468143.00 | 26986452.15 | 0.00 | 0.224189E+09 | 0.00 | 0.47 |
March | 0.112345E+09 | 0.723047E+09 | 0.00 | 2811536.17 | 35543948.87 | 0.00 | 0.164376E+09 | 0.00 | 0.48 |
April | 54509204.41 | 0.149487E+10 | 0.00 | 765928.34 | 0.170457E+09 | 0.00 | 37197689.54 | 0.00 | 0.47 |
May | 9029848.15 | 0.321797E+10 | 0.00 | 319062.88 | 0.389147E+09 | 0.00 | 13892187.84 | 0.00 | 0.52 |
June | 1623637.05 | 0.533678E+10 | 0.00 | 74844.45 | 0.603377E+09 | 0.00 | 2962775.40 | 0.00 | 0.55 |
July | 749091.21 | 0.770199E+10 | 0.00 | 19216.04 | 0.117635E+10 | 0.00 | 304231.49 | 0.00 | 0.60 |
August | 0.00 | 0.905909E+10 | 0.00 | 0.00 | 0.102232E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 76305.40 | 0.693408E+10 | 0.00 | 23464.46 | 0.635455E+09 | 0.00 | 604235.14 | 0.00 | 0.60 |
October | 7265605.47 | 0.419070E+10 | 0.00 | 628233.47 | 0.365192E+09 | 0.00 | 13450935.29 | 0.00 | 0.58 |
November | 10645861.37 | 0.208590E+10 | 0.00 | 705779.52 | 77367094.89 | 0.00 | 18526691.66 | 0.00 | 0.54 |
December | 0.107394E+09 | 0.641069E+09 | 0.00 | 3682281.02 | 52193466.10 | 0.00 | 0.202245E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.673357E+09 | 0.419316E+11 | 0.00 | 17144745.84 | 0.457971E+10 | 0.00 | 0.111441E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.175450E+09 | 0.00 | 0.00 | 25313542.79 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.239570E+09 | 0.905909E+10 | 0.00 | 4646256.49 | 0.117635E+10 | 0.00 | 0.436664E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254862E+09 | 62708497.39 | 0.00 | 1598188.45 | 43127114.03 | 0.00 | 0.163862E+09 | 0.00 | 0.41 |
February | 0.123710E+09 | 0.178905E+09 | 0.00 | 1529474.54 | 57122358.10 | 0.00 | 0.104844E+09 | 0.00 | 0.43 |
March | 98699339.84 | 0.450128E+09 | 0.00 | 1567968.94 | 37483712.60 | 0.00 | 0.100685E+09 | 0.00 | 0.49 |
April | 48822724.09 | 0.109559E+10 | 0.00 | 453392.12 | 0.131341E+09 | 0.00 | 21509159.62 | 0.00 | 0.54 |
May | 8416654.81 | 0.261399E+10 | 0.00 | 200448.34 | 0.276311E+09 | 0.00 | 9473573.55 | 0.00 | 0.64 |
June | 1382566.20 | 0.438211E+10 | 0.00 | 48851.32 | 0.412167E+09 | 0.00 | 2236880.20 | 0.00 | 0.69 |
July | 616683.57 | 0.594193E+10 | 0.00 | 12311.91 | 0.927918E+09 | 0.00 | 226625.85 | 0.00 | 0.73 |
August | 0.00 | 0.669104E+10 | 0.00 | 0.00 | 0.834696E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 260009.05 | 0.467679E+10 | 0.00 | 12310.80 | 0.533078E+09 | 0.00 | 283508.95 | 0.00 | 0.64 |
October | 9413483.50 | 0.237054E+10 | 0.00 | 148348.17 | 0.388617E+09 | 0.00 | 4929458.83 | 0.00 | 0.55 |
November | 11115582.07 | 0.105770E+10 | 0.00 | 327892.30 | 0.115859E+09 | 0.00 | 8523382.74 | 0.00 | 0.46 |
December | 0.110477E+09 | 0.276067E+09 | 0.00 | 1355259.00 | 94487077.80 | 0.00 | 81219114.86 | 0.00 | 0.41 |
Annual Sum or Average | 0.667776E+09 | 0.297975E+11 | 0.00 | 7254445.89 | 0.385221E+10 | 0.00 | 0.497792E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 62708497.39 | 0.00 | 0.00 | 37483712.60 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.254862E+09 | 0.669104E+10 | 0.00 | 1598188.45 | 0.927918E+09 | 0.00 | 0.163862E+09 | 0.00 | 0.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:31:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147603E+12 | 0.257694E+10 | 0.00 | 0.207085E+11 | 0.133332E+12 |
February | 0.162031E+12 | 0.892308E+09 | 0.00 | 0.470557E+10 | 0.147096E+12 |
March | 0.198226E+12 | -963386714.0 | 0.00 | -0.689428E+10 | 0.203618E+12 |
April | 0.207959E+12 | -0.503055E+10 | 0.00 | -0.408468E+11 | 0.251976E+12 |
May | 0.215418E+12 | -0.115215E+11 | 0.00 | -0.961636E+11 | 0.388237E+12 |
June | 0.204987E+12 | -0.189804E+11 | 0.00 | -0.157858E+12 | 0.471095E+12 |
July | 0.201745E+12 | -0.256875E+11 | 0.00 | -0.218727E+12 | 0.571499E+12 |
August | 0.196318E+12 | -0.275271E+11 | 0.00 | -0.234689E+12 | 0.621366E+12 |
September | 0.176251E+12 | -0.202426E+11 | 0.00 | -0.181440E+12 | 0.484521E+12 |
October | 0.153857E+12 | -0.118898E+11 | 0.00 | -0.112257E+12 | 0.377203E+12 |
November | 0.126832E+12 | -0.535197E+10 | 0.00 | -0.478758E+11 | 0.261332E+12 |
December | 0.127195E+12 | 67124196.95 | 0.00 | -0.480563E+10 | 0.168733E+12 |
Annual Sum or Average | 0.211842E+13 | -0.123658E+12 | 0.00 | -0.107614E+13 | 0.408001E+13 |
Minimum of Months | 0.126832E+12 | -0.275271E+11 | 0.00 | -0.234689E+12 | 0.133332E+12 |
Maximum of Months | 0.215418E+12 | 0.257694E+10 | 0.00 | 0.207085E+11 | 0.621366E+12 |