Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:28:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1746.01 | 350.45 | 350.45 |
Net Site Energy | 1746.01 | 350.45 | 350.45 |
Total Source Energy | 5228.17 | 1049.37 | 1049.37 |
Net Source Energy | 5228.17 | 1049.37 | 1049.37 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 128.07 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 332.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 124.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1601.29 | 144.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 128.07 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 332.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 69.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 124.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 128.07 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 332.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 69.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 124.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.45 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.40 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.45 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.40 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1601.294 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1601.294 | 100.00 |
Total On-Site and Utility Electric Sources | 1601.294 | 100.00 |
Total Electricity End Uses | 1601.294 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 138.00 |
Time Setpoint Not Met During Occupied Cooling | 105.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1927.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 03-FEB-07:40 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 197096.46 | 50738.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 244.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5772.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8844.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 240785.62 | 59583.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 197096.46 | 50738.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 244.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5772.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8844.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 405.58 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1053.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 957.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 134.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5071.30 | 156.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 81.41 | 4.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1017.89 | 31.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 81.41 | 4.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1017.89 | 31.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.99 | 0.250790 | 0.262000 | 0.782955 | 0.668773 | 0.500000 | 0.001519 |
CORE_MID VAV BOX COMPONENT | 2.21 | 0.338864 | 0.341000 | 0.754180 | 0.903637 | 0.500000 | 0.001124 |
CORE_TOP VAV BOX COMPONENT | 2.35 | 0.319582 | 0.335000 | 0.785611 | 0.852220 | 0.500000 | 0.001192 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.741331 | 0.213119 | 0.224000 | 0.166058 | 0.568318 | 0.500000 | 0.001788 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.702642 | 0.142351 | 0.200000 | 0.140528 | 0.379602 | 0.500000 | 0.002676 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.855804 | 0.184612 | 0.200000 | 0.171161 | 0.492299 | 0.500000 | 0.002064 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.776515 | 0.128800 | 0.200000 | 0.155303 | 0.343467 | 0.500000 | 0.002958 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.598949 | 0.263782 | 0.275000 | 0.164711 | 0.703417 | 0.500000 | 0.001444 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.603346 | 0.165779 | 0.200000 | 0.120669 | 0.442076 | 0.500000 | 0.002298 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.698822 | 0.226083 | 0.236000 | 0.164922 | 0.602887 | 0.500000 | 0.001685 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.624864 | 0.160059 | 0.200000 | 0.124973 | 0.426825 | 0.500000 | 0.002380 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.645491 | 0.244762 | 0.247000 | 0.159436 | 0.652699 | 0.500000 | 0.001557 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.676768 | 0.147793 | 0.200000 | 0.135354 | 0.394116 | 0.500000 | 0.002578 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.759079 | 0.208136 | 0.210000 | 0.159407 | 0.555029 | 0.500000 | 0.001831 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.706090 | 0.141647 | 0.200000 | 0.141218 | 0.377724 | 0.500000 | 0.002690 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25211.95 |
CORE_MID VAV BOX REHEAT COIL | 24285.36 |
CORE_TOP VAV BOX REHEAT COIL | 37048.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17731.59 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11511.70 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17580.38 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11603.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13271.10 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8682.31 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13146.28 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8763.98 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14063.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9171.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13923.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9255.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.76 | 1.36 | 5.51 | 1.79 | 5.02 | 5.02 | 0.300000 | 0.356163 | 5.02 |
PACU_VAV_MID | 2.50 | 1.35 | 5.00 | 2.11 | 4.41 | 4.41 | 0.300000 | 0.479128 | 4.41 |
PACU_VAV_TOP | 2.71 | 1.42 | 5.42 | 2.96 | 5.13 | 5.13 | 0.300000 | 0.578343 | 5.13 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.02 |
PACU_VAV_MID_OA_CONTROLLER | 4.41 |
PACU_VAV_TOP_OA_CONTROLLER | 5.13 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.02 | 113132.19 | 0.731892 | 1.67 | 37706.96 | 0.731892 |
PACU_VAV_MID COOLING COIL | 4.41 | 103511.30 | 0.719356 | 1.47 | 34500.32 | 0.719356 |
PACU_VAV_TOP COOLING COIL | 5.13 | 115017.41 | 0.734273 | 1.71 | 38335.30 | 0.734273 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 24305.96 |
PACU_VAV_MID HEATING COIL | 25712.58 |
PACU_VAV_TOP HEATING COIL | 24777.01 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.02 |
PACU_VAV_MID FAN | 4.41 |
PACU_VAV_TOP FAN | 5.13 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.534 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0154E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0548E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5333E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5658E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3333E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3590E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1011 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6105E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1127 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9971E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6512E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0535E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0182E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0717E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5364E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5846E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3363E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3723E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4712E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0617E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3095E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8955E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1866E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5629E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8084E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8244E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6586E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6702E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2994E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3039E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9419E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9799E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4803E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5112E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1854E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2090E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7332E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5479E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1205E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1871E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9704E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3399E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9411E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9793E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4790E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5082E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1828E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1998E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9026E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3393E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3943E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0120E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7737E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9199E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7990E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8327E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4179E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4521E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4291E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4468E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1093 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7177E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1214 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1854E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3417E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9225E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2977E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9600E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1501E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8013E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0648E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4890E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1345E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0406E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4795E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6142E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3290E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2281E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7764E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2698E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2932E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9575E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6925E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8735E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1093 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7171E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1214 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1847E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3412E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9220E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2976E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9597E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1499E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8011E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0645E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4887E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1346E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0405E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4795E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6142E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3289E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2279E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7763E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2696E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2931E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9574E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6923E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8733E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39982.03299 | 39982.03299 | 2.98838 | 2.98838 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7608.31489 | 7608.31489 | 0.33168 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29623.27473 | 29623.27473 | 2.21167 | 2.21167 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15302.50991 | 15302.50991 | 0.67213 | 0.67213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31119.13912 | 31119.13912 | 2.34511 | 2.34511 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 26089.87512 | 26089.87512 | 1.15053 | 1.15053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9836.66363 | 9836.66363 | 0.74133 | 0.74133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12451.03723 | 12451.03723 | 0.55065 | 0.55065 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9323.34555 | 9323.34555 | 0.70264 | 0.70264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8083.00975 | 8083.00975 | 0.35749 | 0.35749 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11355.62365 | 11355.62365 | 0.85580 | 0.85580 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12345.12250 | 12345.12250 | 0.54596 | 0.54596 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10303.58453 | 10303.58453 | 0.77652 | 0.77652 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8147.48651 | 8147.48651 | 0.36035 | 0.36035 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7947.67395 | 7947.67395 | 0.59895 | 0.59895 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9325.56740 | 9325.56740 | 0.41213 | 0.41213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8006.06245 | 8006.06245 | 0.60335 | 0.60335 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6100.40921 | 6100.40921 | 0.26963 | 0.26963 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9272.94761 | 9272.94761 | 0.69882 | 0.69882 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9238.16245 | 9238.16245 | 0.40826 | 0.40826 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8291.60092 | 8291.60092 | 0.62486 | 0.62486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59500 | 1.44700E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6157.60004 | 6157.60004 | 0.27216 | 0.27216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8565.06373 | 8565.06373 | 0.64549 | 0.64549 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9881.14251 | 9881.14251 | 0.43673 | 0.43673 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8980.12339 | 8980.12339 | 0.67677 | 0.67677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6443.81448 | 6443.81448 | 0.28483 | 0.28483 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10072.29457 | 10072.29457 | 0.75908 | 0.75908 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9782.89559 | 9782.89559 | 0.43238 | 0.43238 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9369.22002 | 9369.22002 | 0.70609 | 0.70609 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6502.49457 | 6502.49457 | 0.28743 | 0.28743 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 79924.51 | 5.01701 | 5.01701 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 26443.30 | 1.78687 | 1.78687 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71760.27 | 4.41115 | 4.41115 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 26478.33 | 2.11351 | 2.11351 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80930.56 | 5.12670 | 5.12670 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 26602.76 | 2.96499 | 2.96499 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.98838 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25079 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78295 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66877 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51920E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25211.94983 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21167 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33886 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75418 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90364 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12435E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24285.35738 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34511 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31958 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78561 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85222 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19218E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 37048.36803 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74133 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21312 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16606 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56832 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78773E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17731.59368 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70264 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14235 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14053 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37960 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67648E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11511.69976 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85580 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18461 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17116 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49230 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06379E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17580.37763 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77652 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12880 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15530 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34347 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.95807E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11603.75600 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59895 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26378 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16471 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70342 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44438E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13271.09695 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60335 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16578 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12067 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44208 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29825E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8682.31112 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69882 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22608 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16492 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60289 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68522E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13146.28008 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62486 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16006 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12497 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42682 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38037E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8763.98104 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64549 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24476 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15944 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65270 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55661E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14063.27700 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67677 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14779 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13535 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39412 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57792E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9171.91106 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75908 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20814 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15941 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55503 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83053E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13922.99640 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70609 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14165 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14122 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37772 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68979E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9255.69791 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75718 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35823 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51436 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78687 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01701 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.01701 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.35616 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.49955 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34959 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.99910 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.11351 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.41115 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.41115 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.47913 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71070 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41866 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.42140 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.96499 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.12670 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.12670 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.57834 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.01701 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.41115 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.12670 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01701 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.01701 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113132.19356 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73189 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67217 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37706.96012 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73189 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 24305.95650 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.01701 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.41115 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.41115 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103511.30290 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71936 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.47024 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34500.31726 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71936 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 25712.57556 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.41115 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.12670 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.12670 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 115017.41225 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73427 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.70873 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38335.30350 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73427 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 24777.01047 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.12670 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 112590.79 | 384175.74 | 11.53 | 2.94 | 3.30 | 3.48 | 3.62 | 10.02 | 11.27 | 11.88 | 12.36 | 5.5946 | 4.4514 | 2.9957 | 1.2550 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 103154.52 | 351977.84 | 11.60 | 2.95 | 3.33 | 3.51 | 3.64 | 10.07 | 11.35 | 11.97 | 12.41 | 4.9190 | 3.9122 | 2.6330 | 1.1146 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 114446.81 | 390508.74 | 11.52 | 2.93 | 3.30 | 3.48 | 3.62 | 10.01 | 11.26 | 11.87 | 12.35 | 5.7169 | 4.5529 | 3.0650 | 1.2786 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.1583348353E-003 | 6.1429553991E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0861151196E-002 | 5.2146779935E-002 | Pass | Pass | 0.1162298337 | 0.3124266270 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8745952742E-003 | 5.6861771216E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4349226082E-003 | 5.0034282806E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.7443494139E-003 | 7.1515441002E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.0963173044E-002 | 7.0357075008E-002 | Pass | Pass | 0.1199706285 | 0.3256137242 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.8579515142E-002 | 0.1226521319 | Pass | Pass | 0.2566718848 | 0.8305491828 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0670809720E-002 | 0.1240354055 | Pass | Pass | 0.2663533514 | 0.8940509838 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.4843235800E-002 | 0.1103060385 | Pass | Pass | 0.2479195058 | 0.8103110064 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.3783363717E-002 | 0.1311416565 | Pass | Pass | 0.2721651288 | 0.9198575505 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4264797712E-002 | 2.3043340194E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.5206852524E-002 | 2.4648850056E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.5544931548E-002 | 2.5639581353E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.5248423436E-002 | 2.3507727291E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9456044491E-002 | 2.6764704129E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.0735903401E-002 | 2.8680612052E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.1072489321E-002 | 3.0091059988E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.0784444434E-002 | 2.7421227801E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2914.39 | 47.13 | 0.00 | 1157.58 | 1644.35 | 5763.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.557 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 9.01 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 5.57 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 8.69 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.29 | 0.0000 | Y | 5.63 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.50 | 0.0000 | Y | 8.97 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.59 | 0.0000 | Y | 8.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.19 | 0.0000 | Y | 5.61 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 9.01 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 5.57 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.65 | 0.0000 | Y | 8.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.29 | 0.0000 | Y | 5.63 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 302.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 47.60 | 42.13 | |
Exterior Lighting Total | 5686.19 | 51.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113132.19 | 82800.58 | 30331.61 | 0.73 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103511.30 | 74461.49 | 29049.81 | 0.72 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 115017.41 | 84454.18 | 30563.23 | 0.73 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 112590.8 | 2.94 | 10.02 | N/A | N/A | 11.53 | |
PACU_VAV_MID COOLING COIL | 103154.5 | 2.95 | 10.07 | N/A | N/A | 11.60 | |
PACU_VAV_TOP COOLING COIL | 114446.8 | 2.93 | 10.01 | N/A | N/A | 11.52 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25211.95 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24285.36 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 37048.37 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17731.59 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11511.70 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17580.38 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11603.76 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13271.10 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8682.31 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13146.28 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8763.98 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14063.28 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9171.91 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13923.00 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9255.70 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 24305.96 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 25712.58 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 24777.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.02 | 10982.28 | 2189.01 | 1.00 | 1.13 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.41 | 9656.07 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.13 | 11150.01 | 2174.89 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112590.79 | 2.94 | 10.02 | 11.53 | 5.5946 | 3.30 | 11.27 | 4.4514 | 3.48 | 11.88 | 2.9957 | 3.62 | 12.36 | 1.2550 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103154.52 | 2.95 | 10.07 | 11.60 | 4.9190 | 3.33 | 11.35 | 3.9122 | 3.51 | 11.97 | 2.6330 | 3.64 | 12.41 | 1.1146 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 114446.81 | 2.93 | 10.01 | 11.52 | 5.7169 | 3.30 | 11.26 | 4.5529 | 3.48 | 11.87 | 3.0650 | 3.62 | 12.35 | 1.2786 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39982.03 | 39982.03 | 40.65 | 2.988 | 2.988 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 29623.27 | 29623.27 | 30.12 | 2.212 | 2.212 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 31119.14 | 31119.14 | 31.64 | 2.345 | 2.345 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00889 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9836.66 | 9836.66 | 47.44 | 0.741 | 0.741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00897 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9323.35 | 9323.35 | 71.03 | 0.703 | 0.703 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00883 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11355.62 | 11355.62 | 54.77 | 0.856 | 0.856 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00891 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10303.58 | 10303.58 | 78.50 | 0.777 | 0.777 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00879 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7947.67 | 7947.67 | 38.33 | 0.599 | 0.599 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00896 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8006.06 | 8006.06 | 60.99 | 0.603 | 0.603 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00880 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9272.95 | 9272.95 | 44.72 | 0.699 | 0.699 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00889 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8291.60 | 8291.60 | 63.17 | 0.625 | 0.625 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00879 | 32.59 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8565.06 | 8565.06 | 41.31 | 0.645 | 0.645 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00900 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8980.12 | 8980.12 | 68.41 | 0.677 | 0.677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00881 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10072.29 | 10072.29 | 48.58 | 0.759 | 0.759 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00892 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9369.22 | 9369.22 | 71.38 | 0.706 | 0.706 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00880 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7608.31 | 7608.31 | 7.74 | 0.332 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 15302.51 | 15302.51 | 15.56 | 0.672 | 0.672 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 26089.88 | 26089.88 | 26.53 | 1.151 | 1.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12451.04 | 12451.04 | 60.05 | 0.551 | 0.551 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8083.01 | 8083.01 | 61.58 | 0.357 | 0.357 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12345.12 | 12345.12 | 59.54 | 0.546 | 0.546 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8147.49 | 8147.49 | 62.07 | 0.360 | 0.360 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9325.57 | 9325.57 | 44.98 | 0.412 | 0.412 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6100.41 | 6100.41 | 46.47 | 0.270 | 0.270 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9238.16 | 9238.16 | 44.56 | 0.408 | 0.408 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6157.60 | 6157.60 | 46.91 | 0.272 | 0.272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9881.14 | 9881.14 | 47.66 | 0.437 | 0.437 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6443.81 | 6443.81 | 49.09 | 0.285 | 0.285 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9782.90 | 9782.90 | 47.18 | 0.432 | 0.432 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6502.49 | 6502.49 | 49.54 | 0.287 | 0.287 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.02 | 5.02 | 1.79 | 1.79 | 5.0170 | 1.7869 | 5.0170 | 0.3562 | 0.3000 |
PACU_VAV_MID | 4.41 | 4.41 | 2.11 | 2.11 | 4.4112 | 2.1135 | 4.4112 | 0.4791 | 0.3000 |
PACU_VAV_TOP | 5.13 | 5.13 | 2.96 | 2.96 | 5.1267 | 2.9650 | 5.1267 | 0.5783 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25211.950 | 25211.950 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25211.95 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 7608.31 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24285.357 | 24285.357 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24285.36 | 21643.29 | 0.672130 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 15302.51 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 37048.368 | 37048.368 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37048.37 | 37048.37 | 1.150534 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 26089.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17731.594 | 17731.594 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17731.59 | 17731.59 | 0.550653 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756570 | 47.1944 | 12451.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11511.700 | 11511.700 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11511.70 | 11511.70 | 0.357495 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755570 | 47.1329 | 8083.01 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17580.378 | 17580.378 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17580.38 | 17580.38 | 0.545957 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756201 | 47.1716 | 12345.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11603.756 | 11603.756 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11603.76 | 11603.76 | 0.360354 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755914 | 47.1541 | 8147.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13271.097 | 13271.097 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13271.10 | 13271.10 | 0.412133 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763809 | 47.6387 | 9325.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8682.311 | 8682.311 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8682.31 | 8682.31 | 0.269628 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00764101 | 47.6567 | 6100.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13146.280 | 13146.280 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13146.28 | 13146.28 | 0.408257 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763155 | 47.5984 | 9238.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8763.981 | 8763.981 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8763.98 | 8763.98 | 0.272165 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00764674 | 47.6919 | 6157.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 14063.277 | 14063.277 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14063.28 | 14063.28 | 0.436734 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00752561 | 46.9468 | 9881.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9171.911 | 9171.911 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9171.91 | 9171.91 | 0.284833 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00752017 | 46.9134 | 6443.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13922.996 | 13922.996 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13923.00 | 13923.00 | 0.432377 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751975 | 46.9107 | 9782.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9255.698 | 9255.698 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9255.70 | 9255.70 | 0.287435 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00752523 | 46.9446 | 6502.49 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 113132.194 | 82800.580 | 5.017007 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 113582.44 | 89066.57 | 5.017007 | 26.48 | 18.24 | 0.01020021 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 23.8224 | 24.00 | 0.00886065 | 45.9645 | 66449.24 | 0.00 | 116654.48 | 82782.24 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 24305.956 | 24305.956 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24305.96 | 24305.96 | 1.505102 | -1.04 | -1.43 | 0.00334037 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 79.4079 | 19.60 | 0.00703622 | 47.8990 | 20153.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 103511.303 | 74461.489 | 4.411155 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 104695.33 | 79959.00 | 4.411155 | 26.83 | 18.55 | 0.01045420 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 27.0943 | 24.00 | 0.00894728 | 46.4081 | 58156.50 | 0.00 | 106734.05 | 74539.46 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 25712.576 | 25712.576 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25712.58 | 25712.58 | 1.323346 | -3.85 | -3.94 | 0.00278435 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 90.3142 | 19.60 | 0.00707990 | 48.1884 | 22585.59 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 115017.412 | 84454.184 | 5.126704 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 115569.02 | 90442.07 | 5.126704 | 26.39 | 18.21 | 0.01020597 | 10.97 | 10.97 | 0.00850000 | 34.21 | 0.01447292 | 23.49 | 23.3126 | 24.00 | 0.00890163 | 46.1748 | 67739.83 | 0.00 | 118598.39 | 84435.23 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 24777.010 | 24777.010 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24777.01 | 24777.01 | 1.538011 | -1.01 | -1.29 | 0.00341759 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 77.7088 | 17.60 | 0.00718977 | 55.4597 | 27434.52 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25211.950 | 25211.950 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25211.95 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25211.95 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 7608.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24285.357 | 24285.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24285.36 | 21643.29 | 1.0000 | 0.78032770 | 0.672130 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24285.36 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 15302.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 37048.368 | 37048.368 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37048.37 | 37048.37 | 1.0000 | 1.33574273 | 1.150534 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37048.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 26089.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17731.594 | 17731.594 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17731.59 | 17731.59 | 1.0000 | 0.63929529 | 0.550653 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17731.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00756570 | 21.00 | 0.00756570 | 47.1944 | 12451.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11511.700 | 11511.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11511.70 | 11511.70 | 1.0000 | 0.41504309 | 0.357495 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11511.70 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755570 | 21.00 | 0.00755570 | 47.1329 | 8083.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17580.378 | 17580.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17580.38 | 17580.38 | 1.0000 | 0.63384335 | 0.545957 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17580.38 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00756201 | 21.00 | 0.00756201 | 47.1716 | 12345.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11603.756 | 11603.756 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11603.76 | 11603.76 | 1.0000 | 0.41836209 | 0.360354 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11603.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755914 | 21.00 | 0.00755914 | 47.1541 | 8147.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13271.097 | 13271.097 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13271.10 | 13271.10 | 1.0000 | 0.47847644 | 0.412133 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13271.10 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763809 | 21.00 | 0.00763809 | 47.6387 | 9325.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8682.311 | 8682.311 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8682.31 | 8682.31 | 1.0000 | 0.31303225 | 0.269628 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8682.31 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764101 | 21.00 | 0.00764101 | 47.6567 | 6100.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13146.280 | 13146.280 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13146.28 | 13146.28 | 1.0000 | 0.47397629 | 0.408257 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13146.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763155 | 21.00 | 0.00763155 | 47.5984 | 9238.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8763.981 | 8763.981 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8763.98 | 8763.98 | 1.0000 | 0.31597678 | 0.272165 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8763.98 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764674 | 21.00 | 0.00764674 | 47.6919 | 6157.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14063.277 | 14063.277 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14063.28 | 14063.28 | 1.0000 | 0.50703772 | 0.436734 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14063.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752561 | 21.00 | 0.00752561 | 46.9468 | 9881.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9171.911 | 9171.911 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9171.91 | 9171.91 | 1.0000 | 0.33068430 | 0.284833 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9171.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752017 | 21.00 | 0.00752017 | 46.9134 | 6443.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13922.996 | 13922.996 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13923.00 | 13923.00 | 1.0000 | 0.50198004 | 0.432377 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13923.00 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751975 | 21.00 | 0.00751975 | 46.9107 | 9782.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9255.698 | 9255.698 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9255.70 | 9255.70 | 1.0000 | 0.33370515 | 0.287435 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9255.70 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752523 | 21.00 | 0.00752523 | 46.9446 | 6502.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113132.194 | 82800.580 | 5.017007 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8017 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.017007 | 5.82462773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 113582.44 | 89066.57 | 1.0040 | 5.82462773 | 5.017007 | 26.48 | 18.24 | 0.01020021 | 52621.5 | 10.96 | 10.96 | 0.00850000 | 32442.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10982.284 | 102600.15 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 23.8224 | 24.00 | 0.00886065 | 24.00 | 0.00886065 | 45.9645 | 66449.24 | 0.00 | 116654.48 | 82782.24 | 5.59459897 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.18 | 12.15 | 0.00881084 | 34471.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24305.956 | 24305.956 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.017007 | 5.82462773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24305.96 | 24305.96 | 1.0000 | 1.74738832 | 1.505102 | -1.04 | -1.43 | 0.00334037 | 7299.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24305.96 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 79.4079 | 19.23 | 0.00736076 | 19.60 | 0.00703622 | 47.8990 | 20153.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103511.303 | 74461.489 | 4.411155 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2738 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.411155 | 5.12124745 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 104695.33 | 79959.00 | 1.0114 | 5.12124745 | 4.411155 | 26.83 | 18.55 | 0.01045420 | 53631.6 | 10.96 | 10.96 | 0.00850000 | 32443.4 | -999.0 | -999.00 | -999.00 | -999.00 | 9656.067 | 95039.26 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 27.0943 | 24.00 | 0.00894728 | 24.00 | 0.00894728 | 46.4081 | 58156.50 | 0.00 | 106734.05 | 74539.46 | 4.91899689 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.82 | 11.81 | 0.00861853 | 33624.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25712.576 | 25712.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.411155 | 5.12124745 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25712.58 | 25712.58 | 1.0000 | 1.53637424 | 1.323346 | -3.85 | -3.94 | 0.00278435 | 3069.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25712.58 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 90.3142 | 18.94 | 0.00732121 | 19.60 | 0.00707990 | 48.1884 | 22585.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 115017.412 | 84454.184 | 5.126704 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8124 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.126704 | 5.95198331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 115569.02 | 90442.07 | 1.0048 | 5.95198331 | 5.126704 | 26.39 | 18.21 | 0.01020597 | 52542.0 | 10.97 | 10.97 | 0.00850000 | 32454.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11150.009 | 104419.01 | 34.21 | 0.01447292 | 23.49 | 1.19517000 | 23.3126 | 24.00 | 0.00890163 | 24.00 | 0.00890163 | 46.1748 | 67739.83 | 0.00 | 118598.39 | 84435.23 | 5.71692497 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.21 | 12.20 | 0.00884169 | 34577.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24777.010 | 24777.010 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.126704 | 5.95198331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24777.01 | 24777.01 | 1.0000 | 1.78559499 | 1.538011 | -1.01 | -1.29 | 0.00341759 | 7526.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24777.01 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 77.7088 | 17.44 | 0.00732126 | 17.60 | 0.00718977 | 55.4597 | 27434.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.02 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.41 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.13 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2728.67 | 2135.33 | 33.83 |
CORE_MID | 2337.50 | 3182.83 | 341.33 |
CORE_TOP | 2596.67 | 3464.33 | 764.83 |
PERIMETER_TOP_ZN_3 | 3408.33 | 3645.67 | 1504.50 |
PERIMETER_TOP_ZN_2 | 3399.33 | 3501.83 | 1365.67 |
PERIMETER_TOP_ZN_1 | 3238.33 | 3152.00 | 1078.67 |
PERIMETER_TOP_ZN_4 | 3270.50 | 3625.00 | 1392.17 |
PERIMETER_BOT_ZN_3 | 2974.83 | 3688.33 | 1138.33 |
PERIMETER_BOT_ZN_2 | 3109.83 | 3311.00 | 938.17 |
PERIMETER_BOT_ZN_1 | 2939.33 | 3383.33 | 911.67 |
PERIMETER_BOT_ZN_4 | 3063.33 | 3367.50 | 958.83 |
PERIMETER_MID_ZN_3 | 3213.17 | 3436.50 | 1165.00 |
PERIMETER_MID_ZN_2 | 2698.00 | 2904.50 | 968.50 |
PERIMETER_MID_ZN_1 | 3123.00 | 2831.83 | 754.50 |
PERIMETER_MID_ZN_4 | 3169.67 | 3377.83 | 1073.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4525.83 | 4372.17 | 1927.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.83 | 0.00 | 0.83 | 0.00 |
CORE_TOP | 2.17 | 0.00 | 1.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 31.33 | 4.33 | 13.33 | 2.67 |
PERIMETER_TOP_ZN_2 | 21.17 | 23.50 | 4.17 | 22.50 |
PERIMETER_TOP_ZN_1 | 16.17 | 17.83 | 4.67 | 16.33 |
PERIMETER_TOP_ZN_4 | 20.83 | 26.17 | 5.67 | 14.83 |
PERIMETER_BOT_ZN_3 | 3.33 | 0.00 | 3.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.50 | 9.33 | 0.17 | 9.33 |
PERIMETER_BOT_ZN_1 | 127.83 | 42.17 | 127.50 | 42.17 |
PERIMETER_BOT_ZN_4 | 0.50 | 13.83 | 0.17 | 7.67 |
PERIMETER_MID_ZN_3 | 6.33 | 0.33 | 3.50 | 0.33 |
PERIMETER_MID_ZN_2 | 4.17 | 16.33 | 1.33 | 16.33 |
PERIMETER_MID_ZN_1 | 2.00 | 13.00 | 1.17 | 13.00 |
PERIMETER_MID_ZN_4 | 4.50 | 21.33 | 1.50 | 11.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 158.50 | 123.50 | 138.00 | 105.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.702 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.562 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.567 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.631 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.879 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.774 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.940 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.579 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.751 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.706 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.753 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.618 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.800 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.765 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.892 | 0.074 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.56 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11061715.96 | 0.00 | 11061715.96 | 0.00 | 11061715.96 | 13393058.27 | 5131.46 | 422.60 | 3205.94 | 9.08 |
CORE_MID | 8898853.15 | 0.00 | 8898853.15 | 0.00 | 8898853.15 | 13393058.27 | 6389.66 | 178.47 | 2191.87 | 34.89 |
CORE_TOP | 9022494.51 | 0.00 | 9022494.51 | 0.00 | 9022494.51 | 13393058.27 | 6572.68 | 47.58 | 2139.74 | 116.64 |
PERIMETER_TOP_ZN_3 | 2113125.66 | 0.00 | 2113125.66 | 563886.35 | 2677012.01 | 2823374.22 | 5230.08 | 72.16 | 3457.76 | 116.64 |
PERIMETER_TOP_ZN_2 | 1863125.58 | 0.00 | 1863125.58 | 375921.98 | 2239047.56 | 1787429.43 | 4240.62 | 5.65 | 4513.73 | 116.64 |
PERIMETER_TOP_ZN_1 | 2584480.84 | 0.00 | 2584480.84 | 563886.35 | 3148367.20 | 2823374.22 | 4403.16 | 463.79 | 3893.05 | 116.64 |
PERIMETER_TOP_ZN_4 | 1993324.05 | 0.00 | 1993324.05 | 375921.98 | 2369246.02 | 1787312.18 | 4261.32 | 15.53 | 4483.15 | 116.64 |
PERIMETER_BOT_ZN_3 | 1931523.36 | 0.00 | 1931523.36 | 299816.06 | 2231339.42 | 2823374.22 | 5741.49 | 429.77 | 2588.74 | 9.08 |
PERIMETER_BOT_ZN_2 | 1582252.86 | 0.00 | 1582252.86 | 199876.17 | 1782129.04 | 1787429.43 | 4391.59 | 47.16 | 4321.25 | 9.08 |
PERIMETER_BOT_ZN_1 | 2352536.70 | 0.00 | 2352536.70 | 2951634.14 | 5304170.85 | 2823374.22 | 4902.00 | 396.02 | 3461.99 | 9.08 |
PERIMETER_BOT_ZN_4 | 1588585.79 | 0.00 | 1588585.79 | 199876.17 | 1788461.97 | 1787312.18 | 4656.07 | 79.72 | 4024.21 | 9.08 |
PERIMETER_MID_ZN_3 | 2061725.53 | 0.00 | 2061725.53 | 469392.62 | 2531118.15 | 2823374.22 | 5008.46 | 255.71 | 3495.83 | 34.89 |
PERIMETER_MID_ZN_2 | 1831967.20 | 0.00 | 1831967.20 | 312926.53 | 2144893.74 | 1787429.43 | 4232.19 | 9.16 | 4518.64 | 943.89 |
PERIMETER_MID_ZN_1 | 2548025.60 | 0.00 | 2548025.60 | 469392.62 | 3017418.22 | 2823374.22 | 4882.18 | 249.36 | 3628.46 | 34.89 |
PERIMETER_MID_ZN_4 | 1884721.21 | 0.00 | 1884721.21 | 312926.53 | 2197647.74 | 1787312.18 | 4276.82 | 26.86 | 4456.32 | 34.89 |
Total Facility | 53318458.02 | 0.00 | 53318458.02 | 7095457.52 | 60413915.53 | 67843644.98 | 6733.09 | 1102.79 | 4563.90 | 1029.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5166 | 0.0000 | 0.5166 | 0.0000 | 0.5166 | 0.4247 | 2315.34 | 422.60 | 3205.06 |
CORE_MID | 0.4146 | 0.0000 | 0.4146 | 0.0000 | 0.4146 | 0.4247 | 3575.16 | 178.47 | 2189.37 |
CORE_TOP | 0.4191 | 0.0000 | 0.4191 | 0.0000 | 0.4191 | 0.4247 | 3759.74 | 47.58 | 2135.68 |
PERIMETER_TOP_ZN_3 | 0.0982 | 0.0000 | 0.0982 | 0.0131 | 0.1113 | 0.0895 | 2417.18 | 72.16 | 3453.66 |
PERIMETER_TOP_ZN_2 | 0.0866 | 0.0000 | 0.0866 | 0.0087 | 0.0953 | 0.0567 | 1428.01 | 5.59 | 4509.40 |
PERIMETER_TOP_ZN_1 | 0.1202 | 0.0000 | 0.1202 | 0.0131 | 0.1333 | 0.0895 | 1590.24 | 463.79 | 3888.96 |
PERIMETER_TOP_ZN_4 | 0.0926 | 0.0000 | 0.0926 | 0.0087 | 0.1013 | 0.0567 | 1448.76 | 15.53 | 4478.70 |
PERIMETER_BOT_ZN_3 | 0.0902 | 0.0000 | 0.0902 | 0.0069 | 0.0971 | 0.0895 | 2925.49 | 429.75 | 2587.76 |
PERIMETER_BOT_ZN_2 | 0.0739 | 0.0000 | 0.0739 | 0.0046 | 0.0785 | 0.0567 | 1575.74 | 47.12 | 4320.14 |
PERIMETER_BOT_ZN_1 | 0.1099 | 0.0000 | 0.1099 | 0.1309 | 0.2408 | 0.0895 | 2085.93 | 396.02 | 3461.05 |
PERIMETER_BOT_ZN_4 | 0.0742 | 0.0000 | 0.0742 | 0.0046 | 0.0788 | 0.0567 | 1840.16 | 79.72 | 4023.12 |
PERIMETER_MID_ZN_3 | 0.0961 | 0.0000 | 0.0961 | 0.0109 | 0.1070 | 0.0895 | 2194.36 | 255.63 | 3493.01 |
PERIMETER_MID_ZN_2 | 0.0788 | 0.0000 | 0.0788 | 0.0077 | 0.0865 | 0.0567 | 1411.39 | 6.27 | 3616.34 |
PERIMETER_MID_ZN_1 | 0.1188 | 0.0000 | 0.1188 | 0.0109 | 0.1297 | 0.0895 | 2067.90 | 249.33 | 3625.77 |
PERIMETER_MID_ZN_4 | 0.0878 | 0.0000 | 0.0878 | 0.0073 | 0.0951 | 0.0567 | 1463.06 | 26.83 | 4453.11 |
Total Facility | 2.4774 | 0.0000 | 2.4774 | 0.2274 | 2.7048 | 2.1513 | 3916.75 | 1102.49 | 4558.16 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 24957934.94 | 0.00 | 24957934.94 | 22614548.33 | 4213.59 | 2.24 | 4544.16 | 9.08 |
PACU_VAV_MID | 23217439.03 | 0.00 | 23217439.03 | 22614548.33 | 4211.63 | 0.53 | 4547.85 | 34.89 |
PACU_VAV_TOP | 23690847.34 | 0.00 | 23690847.34 | 22614548.33 | 4230.97 | 2.04 | 4527.00 | 116.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1655 | 0.0000 | 1.1655 | 0.7171 | 1398.93 | 1.39 | 4542.68 |
PACU_VAV_MID | 1.0819 | 0.0000 | 1.0819 | 0.7171 | 1397.55 | 0.48 | 4544.97 |
PACU_VAV_TOP | 1.1008 | 0.0000 | 1.1008 | 0.7171 | 1418.02 | 2.04 | 4522.94 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2356.29 | 0.00 | 0.00 | 0.00 | 2216.07 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2261.66 | 0.00 | 0.00 | 0.00 | 2347.54 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2362.01 | 0.00 | 0.00 | 0.00 | 2351.41 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 1.9525 | 0.0000 | 0.0000 | 0.0000 | 1.0577 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.7725 | 0.0000 | 0.0000 | 0.0000 | 1.0585 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.8128 | 0.0000 | 0.0000 | 0.0000 | 1.0516 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2218 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
Electricity:Building | 1007.83 | 12229.26 | 29-MAY-17:20 | 78507.21 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 308.10 | 4006.86 | 01-JAN-00:10 | 24629.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1007.83 | 12229.26 | 29-MAY-17:20 | 78507.21 | 03-JAN-08:10 |
InteriorLights:Electricity | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.35 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.97 | 267.21 | 21-MAY-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 33.02 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 21.04 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.30 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.97 | 36.00 | 01-JAN-11:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.97 | 36.00 | 01-JAN-11:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.96 | 267.21 | 23-APR-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.55 | 22.79 | 01-JAN-09:10 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.55 | 22.79 | 01-JAN-09:10 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 33.00 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.02 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.61 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.61 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.35 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.97 | 267.21 | 21-MAY-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 33.02 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 21.04 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 541.97 | 168.59 | 09-JUL-17:40 | 203112.80 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 06-FEB-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.76 | 168.34 | 01-JAN-00:10 | 850.39 | 06-FEB-08:20 |
ElectricityPurchased:Facility | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
ElectricityNet:Plant | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1601.29 | 12402.40 | 06-AUG-17:20 | 240785.62 | 02-JAN-07:10 |
Heating:Electricity | 128.07 | 0.00 | 01-JAN-00:40 | 197096.46 | 02-JAN-07:10 |
General:Heating:Electricity | 128.07 | 0.00 | 01-JAN-00:40 | 197096.46 | 02-JAN-07:10 |
Fans:Electricity | 69.51 | 0.00 | 01-JAN-00:40 | 13909.72 | 02-AUG-16:00 |
General:Fans:Electricity | 69.51 | 0.00 | 01-JAN-00:40 | 13909.72 | 02-AUG-16:00 |
ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 332.63 | 0.00 | 01-JAN-00:10 | 76871.17 | 07-JUL-16:00 |
General:Cooling:Electricity | 332.63 | 0.00 | 01-JAN-00:10 | 76871.17 | 07-JUL-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-18:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-18:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-18:10 |
WIRED_LTG_ELECTRICITY | 8.50 | 0.00 | 01-JAN-00:10 | 917.25 | 03-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 144.72 | 1886.44 | 05-JAN-05:10 | 59583.43 | 03-FEB-07:40 |
NaturalGas:HVAC | 20.26 | 0.00 | 01-JAN-00:10 | 50817.95 | 03-FEB-07:30 |
Heating:NaturalGas | 20.26 | 0.00 | 01-JAN-00:10 | 50817.95 | 03-FEB-07:30 |
General:Heating:NaturalGas | 20.26 | 0.00 | 01-JAN-00:10 | 50817.95 | 03-FEB-07:30 |
NaturalGas:Plant | 124.45 | 1886.44 | 04-JAN-08:10 | 10018.44 | 01-FEB-12:10 |
WaterSystems:NaturalGas | 124.45 | 1886.44 | 04-JAN-08:10 | 10018.44 | 01-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 124.45 | 1886.44 | 04-JAN-08:10 | 10018.44 | 01-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2732.16 | 0.00 | 01-JAN-00:40 | 415017.81 | 07-JUL-16:00 |
EnergyTransfer:Building | 1236.01 | 0.00 | 01-JAN-00:40 | 161820.23 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 249.15 | 0.00 | 01-JAN-00:10 | 26911.78 | 21-AUG-08:00 |
Heating:EnergyTransfer | 74.23 | 0.00 | 01-JAN-00:40 | 159353.59 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 7779.08 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 74.23 | 0.00 | 01-JAN-00:40 | 159353.59 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 7779.08 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1161.77 | 0.00 | 01-JAN-00:40 | 160644.96 | 02-AUG-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 249.11 | 0.00 | 01-JAN-00:10 | 26911.78 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 1161.77 | 0.00 | 01-JAN-00:40 | 160644.96 | 02-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 249.11 | 0.00 | 01-JAN-00:10 | 26911.78 | 21-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.34 | 0.00 | 01-JAN-00:40 | 14211.72 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.75 | 0.00 | 01-JAN-00:40 | 14211.72 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.75 | 0.00 | 01-JAN-00:40 | 14211.72 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.58 | 0.00 | 01-JAN-00:10 | 10449.73 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.58 | 0.00 | 01-JAN-00:10 | 10449.73 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.78 | 0.00 | 01-JAN-00:10 | 7751.28 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.68 | 0.00 | 01-JAN-00:10 | 7751.28 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.68 | 0.00 | 01-JAN-00:10 | 7751.28 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.10 | 0.00 | 01-JAN-00:10 | 4346.49 | 10-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.10 | 0.00 | 01-JAN-00:10 | 4346.49 | 10-JUL-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 26.65 | 0.00 | 01-JAN-00:10 | 4705.40 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.30 | 0.00 | 01-JAN-00:10 | 4647.71 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.30 | 0.00 | 01-JAN-00:10 | 4647.71 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.35 | 0.00 | 01-JAN-00:10 | 4705.40 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.35 | 0.00 | 01-JAN-00:10 | 4705.40 | 18-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 179.54 | 0.00 | 01-JAN-00:10 | 18518.42 | 21-AUG-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.74 | 0.00 | 01-JAN-00:10 | 16825.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.74 | 0.00 | 01-JAN-00:10 | 16825.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 178.81 | 0.00 | 01-JAN-00:10 | 18518.42 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 178.81 | 0.00 | 01-JAN-00:10 | 18518.42 | 21-AUG-08:00 |
EnergyTransfer:Zone:CORE_TOP | 178.64 | 0.00 | 01-JAN-00:40 | 29829.37 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.94 | 0.00 | 01-JAN-00:10 | 29829.37 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.94 | 0.00 | 01-JAN-00:10 | 29829.37 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 174.70 | 0.00 | 01-JAN-00:40 | 20697.11 | 07-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 174.70 | 0.00 | 01-JAN-00:40 | 20697.11 | 07-JUL-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.82 | 0.00 | 01-JAN-00:40 | 9856.53 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.31 | 0.00 | 01-JAN-00:40 | 9856.53 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.31 | 0.00 | 01-JAN-00:40 | 9856.53 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.51 | 0.00 | 01-JAN-00:20 | 7334.05 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.51 | 0.00 | 01-JAN-00:20 | 7334.05 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.49 | 0.00 | 01-JAN-00:40 | 8349.93 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.29 | 0.00 | 01-JAN-00:40 | 8349.93 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.29 | 0.00 | 01-JAN-00:40 | 8349.93 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.20 | 0.00 | 01-JAN-00:20 | 8175.47 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.20 | 0.00 | 01-JAN-00:20 | 8175.47 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.85 | 0.00 | 01-JAN-00:40 | 10950.57 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.21 | 0.00 | 01-JAN-00:40 | 10707.20 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.21 | 0.00 | 01-JAN-00:40 | 10707.20 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 52.64 | 0.00 | 01-JAN-00:20 | 10950.57 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 52.64 | 0.00 | 01-JAN-00:20 | 10950.57 | 10-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.22 | 0.00 | 01-JAN-00:40 | 8284.12 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.94 | 0.00 | 01-JAN-00:40 | 8189.63 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.94 | 0.00 | 01-JAN-00:40 | 8189.63 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.28 | 0.00 | 01-JAN-00:20 | 8284.12 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.28 | 0.00 | 01-JAN-00:20 | 8284.12 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.17 | 0.00 | 01-JAN-00:10 | 7519.54 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.50 | 0.00 | 01-JAN-00:10 | 7519.54 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.50 | 0.00 | 01-JAN-00:10 | 7519.54 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.67 | 0.00 | 01-JAN-00:10 | 5947.05 | 09-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.67 | 0.00 | 01-JAN-00:10 | 5947.05 | 09-AUG-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.96 | 0.00 | 01-JAN-00:10 | 6771.53 | 07-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.63 | 0.00 | 01-JAN-00:10 | 5525.93 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.63 | 0.00 | 01-JAN-00:10 | 5525.93 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.33 | 0.00 | 01-JAN-00:10 | 6771.53 | 07-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.33 | 0.00 | 01-JAN-00:10 | 6771.53 | 07-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.22 | 0.00 | 01-JAN-00:10 | 10753.97 | 13-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.95 | 0.00 | 01-JAN-00:10 | 10753.97 | 13-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.95 | 0.00 | 01-JAN-00:10 | 10753.97 | 13-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 48.27 | 0.00 | 01-JAN-00:10 | 10613.25 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 48.27 | 0.00 | 01-JAN-00:10 | 10613.25 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.06 | 0.00 | 01-JAN-00:10 | 6738.08 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.78 | 0.00 | 01-JAN-00:10 | 5432.93 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.78 | 0.00 | 01-JAN-00:10 | 5432.93 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.28 | 0.00 | 01-JAN-00:10 | 6738.08 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.28 | 0.00 | 01-JAN-00:10 | 6738.08 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.47 | 0.00 | 01-JAN-00:10 | 8164.78 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.80 | 0.00 | 01-JAN-00:10 | 8164.78 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.80 | 0.00 | 01-JAN-00:10 | 8164.78 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.67 | 0.00 | 01-JAN-00:10 | 6541.47 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.67 | 0.00 | 01-JAN-00:10 | 6541.47 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.83 | 0.00 | 01-JAN-00:10 | 7794.43 | 07-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.01 | 0.00 | 01-JAN-00:10 | 6221.96 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.01 | 0.00 | 01-JAN-00:10 | 6221.96 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 35.82 | 0.00 | 01-JAN-00:10 | 7794.43 | 07-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 35.82 | 0.00 | 01-JAN-00:10 | 7794.43 | 07-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.82 | 0.00 | 01-JAN-00:10 | 10203.39 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.14 | 0.00 | 01-JAN-00:10 | 8801.74 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.14 | 0.00 | 01-JAN-00:10 | 8801.74 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.67 | 0.00 | 01-JAN-00:10 | 10203.39 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.67 | 0.00 | 01-JAN-00:10 | 10203.39 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.97 | 0.00 | 01-JAN-00:10 | 7669.48 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.21 | 0.00 | 01-JAN-00:10 | 6066.21 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.21 | 0.00 | 01-JAN-00:10 | 6066.21 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 35.76 | 0.00 | 01-JAN-00:10 | 7669.48 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 35.76 | 0.00 | 01-JAN-00:10 | 7669.48 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
PlantLoopHeatingDemand:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
EnergyTransfer:HVAC | 1451.94 | 0.00 | 01-JAN-00:40 | 253740.77 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 144.27 | 0.00 | 01-JAN-00:40 | 211871.63 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1307.67 | 0.00 | 01-JAN-00:10 | 253740.77 | 07-JUL-16:00 |
EnergyTransfer:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5831.02 | 02-FEB-12:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.043 | -249.111 | 0.000 | 0.000 | 33.127 | 71.928 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -92.156 |
CORE_MID | 0.000 | 0.000 | 0.738 | -178.807 | 0.000 | 0.000 | 34.440 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.725 |
CORE_TOP | 0.000 | 0.000 | 3.936 | -174.702 | 0.000 | 0.000 | 35.083 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -51.670 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.315 | -39.505 | 0.000 | 0.000 | 7.501 | 9.014 | 24.333 | 18.284 | 0.000 | 0.300 | 2.180 | 0.000 | -25.354 | 0.000 | -5.068 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.292 | -36.200 | 0.000 | 0.000 | 4.702 | 5.569 | 15.404 | 29.391 | 0.000 | 0.192 | 0.000 | 0.000 | -15.563 | 0.000 | -3.444 | -4.343 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.212 | -52.641 | 0.000 | 0.000 | 7.305 | 8.686 | 24.332 | 51.597 | 0.000 | 0.278 | 0.001 | 0.000 | -23.722 | 0.000 | -5.402 | -15.645 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.938 | -36.282 | 0.000 | 0.000 | 4.766 | 5.635 | 15.403 | 29.754 | 0.000 | 0.191 | 0.000 | 0.000 | -16.651 | 0.000 | -3.464 | -4.289 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.500 | -36.670 | 0.000 | 0.000 | 7.473 | 8.972 | 24.333 | 18.647 | 0.000 | 0.174 | 2.999 | 0.000 | -26.544 | 0.000 | -2.883 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.629 | -33.327 | 0.000 | 0.000 | 4.652 | 5.553 | 15.404 | 29.517 | 0.000 | 0.104 | 0.002 | 0.000 | -16.633 | 0.000 | -1.995 | -4.903 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 8.950 | -48.269 | 0.000 | 0.000 | 7.366 | 8.665 | 24.332 | 52.146 | 0.000 | 4.051 | 0.001 | 0.000 | -25.354 | 0.000 | -21.871 | -10.016 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.783 | -32.280 | 0.000 | 0.000 | 4.695 | 5.613 | 15.403 | 29.938 | 0.000 | 0.102 | 0.001 | 0.000 | -17.827 | 0.000 | -2.008 | -5.420 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.799 | -39.673 | 0.000 | 0.000 | 7.424 | 9.014 | 24.333 | 18.147 | 0.000 | 0.256 | 8.096 | 0.000 | -26.894 | 0.000 | -4.502 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.008 | -35.823 | 0.000 | 0.000 | 3.453 | 5.569 | 15.404 | 29.244 | 0.000 | 0.164 | 0.002 | 0.000 | -16.444 | 0.000 | -3.053 | -0.521 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.144 | -52.671 | 0.000 | 0.000 | 7.216 | 8.686 | 24.332 | 51.355 | 0.000 | 0.236 | 0.000 | 0.000 | -25.145 | 0.000 | -4.799 | -11.356 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.212 | -35.762 | 0.000 | 0.000 | 4.710 | 5.635 | 15.403 | 29.648 | 0.000 | 0.158 | 0.000 | 0.000 | -17.654 | 0.000 | -3.075 | -1.275 |
TOPFLOOR_PLENUM | 12.755 | -36.582 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.292 | 31.278 | 0.000 | 0.000 | 0.000 | -7.743 | -0.003 |
MIDFLOOR_PLENUM | 4.680 | -20.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.367 | 22.938 | 0.000 | 0.000 | 0.000 | -7.880 | -0.000 |
FIRSTFLOOR_PLENUM | 3.302 | -23.347 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.277 | 26.271 | 0.000 | 0.000 | 0.000 | -6.503 | -0.000 |
Total Facility | 20.736 | -80.033 | 53.498 | -1081.723 | 0.000 | 0.000 | 173.913 | 302.396 | 705.434 | 387.667 | 0.000 | 7.143 | 93.770 | 0.000 | -253.783 | 0.000 | -83.691 | -245.324 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 03-AUG-04:02 | 0.00 | 0.00 | 0.00 | -43862.94 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 39245.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 03-AUG-04:02 | 0.00 | 0.00 | 0.00 | -32353.96 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 29700.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -33817.59 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31163.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:32 | 0.00 | 0.00 | 0.00 | -12052.96 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 1799.80 | 0.00 | 97.58 | 9733.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-10:22 | 0.00 | 0.00 | 0.00 | -11734.80 | 0.00 | 0.00 | 14.55 | 22.79 | 302.86 | 6043.73 | 0.00 | 48.75 | 5302.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:02 | 0.00 | 0.00 | 0.00 | -14589.63 | 0.00 | 0.00 | 25.62 | 36.00 | 478.41 | 9169.27 | 0.00 | 0.19 | 4880.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-17:02 | 0.00 | 0.00 | 0.00 | -13365.12 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 7248.24 | 0.00 | 73.01 | 5776.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5946.98 | 0.00 | 0.00 | 737.23 | 647.98 | 1435.25 | 3959.92 | 0.00 | 15.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -848.49 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:12 | 0.00 | 0.00 | 0.00 | -10286.25 | 0.00 | 0.00 | 16.44 | 22.79 | 302.86 | 8038.41 | 0.00 | 0.00 | 1908.05 | 0.00 | -0.00 | 0.00 | -2.30 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:13 | 0.00 | 0.00 | 0.00 | -12051.30 | 0.00 | 0.00 | 25.85 | 36.00 | 478.41 | 9091.12 | 0.00 | 0.00 | 2420.30 | 0.00 | -0.00 | 0.00 | -0.39 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUN-16:32 | 0.00 | 0.00 | 0.00 | -10601.84 | 0.00 | 0.00 | 16.38 | 22.79 | 302.86 | 7345.51 | 0.00 | 40.96 | 2873.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:53 | 0.00 | 0.00 | 0.00 | -8989.29 | 0.00 | 0.00 | 28.76 | 36.00 | 478.42 | 3534.82 | 0.00 | 107.58 | 4803.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:12 | 0.00 | 0.00 | 0.00 | -11857.93 | 0.00 | 0.00 | 15.24 | 22.79 | 302.86 | 7958.43 | 0.00 | 0.00 | 3563.30 | 0.00 | -0.00 | 0.00 | -4.69 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:02 | 0.00 | 0.00 | 0.00 | -12988.37 | 0.00 | 0.00 | 25.84 | 36.00 | 478.41 | 9194.26 | 0.00 | 0.00 | 3255.08 | 0.00 | -0.00 | 0.00 | -1.22 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:52 | 0.00 | 0.00 | 0.00 | -12563.95 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 5710.23 | 0.00 | 22.66 | 6563.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:00 | 0.00 | -10449.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.76 | 10359.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-JUL-15:40 | 0.00 | -4346.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.61 | 4221.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 18-AUG-16:00 | 0.00 | -4705.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.42 | 4624.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 8387.02 | 0.00 | -182960.21 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 164858.72 | 0.00 | -5177.29 | 0.00 | -514.72 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-JAN-06:01 | 0.00 | 0.00 | 17478.92 | 0.00 | 0.00 | 0.00 | 466.91 | 211.73 | 4989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23147.07 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 18533.73 | 0.00 | 0.00 | 0.00 | 514.04 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22789.67 |
CORE_TOP | 09-JAN-05:01 | 0.00 | 0.00 | 32802.57 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35456.36 |
PERIMETER_TOP_ZN_3 | 12-FEB-05:32 | 0.00 | 0.00 | 11290.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3905.55 | 0.00 | -2051.66 | -5763.95 |
PERIMETER_TOP_ZN_2 | 12-FEB-05:32 | 0.00 | 0.00 | 10554.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2512.85 | 0.00 | -1386.62 | -6927.29 |
PERIMETER_TOP_ZN_1 | 12-FEB-05:32 | 0.00 | 0.00 | 12899.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3794.29 | 0.00 | -2072.85 | -7463.01 |
PERIMETER_TOP_ZN_4 | 12-FEB-05:32 | 0.00 | 0.00 | 10922.75 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2605.02 | 0.00 | -1389.77 | -7200.63 |
PERIMETER_BOT_ZN_3 | 09-JAN-05:01 | 0.00 | 0.00 | 8463.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2626.00 | 0.00 | -526.60 | -5870.12 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 7549.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1702.39 | 0.00 | -353.76 | -5847.09 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 10877.67 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 11834.16 | 0.00 | -4046.25 | 0.00 | -19949.58 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 7596.24 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1747.55 | 0.00 | -353.44 | -5849.40 |
PERIMETER_MID_ZN_3 | 13-FEB-04:02 | 0.00 | 0.00 | 9426.44 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3082.82 | 0.00 | -1495.84 | -5407.22 |
PERIMETER_MID_ZN_2 | 13-FEB-04:02 | 0.00 | 0.00 | 8252.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2059.52 | 0.00 | -1007.79 | -5539.11 |
PERIMETER_MID_ZN_1 | 12-FEB-05:32 | 0.00 | 0.00 | 10892.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3982.13 | 0.00 | -1804.98 | -5535.90 |
PERIMETER_MID_ZN_4 | 13-FEB-04:02 | 0.00 | 0.00 | 8319.93 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2021.33 | 0.00 | -1021.78 | -5630.97 |
TOPFLOOR_PLENUM | 13-FEB-06:06 | 14923.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -573.40 | -14349.87 |
MIDFLOOR_PLENUM | 09-JAN-07:11 | 8208.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.71 | -7841.68 |
FIRSTFLOOR_PLENUM | 02-JAN-07:03 | 5843.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -140.49 | -5702.65 |
Total Facility | 02-JAN-06:11 | 6718.18 | 0.00 | 176575.35 | 0.00 | 0.00 | 0.00 | 2636.41 | 3626.85 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17160.90 | 0.00 | -2614.28 | -187073.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.5144 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0170 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9991 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4214 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1267 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7572 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3582 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4995 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3496 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7107 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9884 | 2.9884 | 0.7830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2117 | 2.2117 | 0.7542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3451 | 2.3451 | 0.7856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7413 | 0.7413 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7026 | 0.7026 | 0.1405 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8558 | 0.8558 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7765 | 0.7765 | 0.1553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5989 | 0.5989 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6033 | 0.6033 | 0.1207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6988 | 0.6988 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6249 | 0.6249 | 0.1250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6455 | 0.6455 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6768 | 0.6768 | 0.1354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7591 | 0.7591 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7061 | 0.7061 | 0.1412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.5144 | 5.0170 | 5.5144 | 1.3582 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9991 | 4.4112 | 4.9991 | 1.3496 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4214 | 5.1267 | 5.4214 | 1.4187 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4942 | 1.4942 | 0.7830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1058 | 1.1058 | 0.7542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1726 | 1.1726 | 0.7856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3707 | 0.3707 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3513 | 0.3513 | 0.1405 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4279 | 0.4279 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3883 | 0.3883 | 0.1553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2995 | 0.2995 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3017 | 0.3017 | 0.1207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3494 | 0.3494 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3124 | 0.3124 | 0.1250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3227 | 0.3227 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3384 | 0.3384 | 0.1354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3795 | 0.3795 | 0.1594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3530 | 0.3530 | 0.1412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7572 | 1.3582 | 1.3582 | 1.3582 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4995 | 1.3496 | 1.3496 | 1.3496 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7107 | 1.4187 | 1.4187 | 1.4187 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 138.00 |
Number of hours cooling loads not met | 105.17 |
Number of hours not met | 243.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 128.07 | 197096.46 | 20.26 | 50817.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 332.63 | 76871.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 302.40 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.35 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.76 | 850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 69.51 | 13909.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 124.45 | 10018.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1601.29 |
Natural Gas | 0.00 | 144.72 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1746.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.70 |
Space Heating | 25.70 |
Space Cooling | 66.76 |
Fans (All) | 13.95 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 321.40 |
Subtotal | 321.40 |
Natural Gas [MJ/m2] | |
Space Heating | 4.07 |
Service Water Heating | 24.98 |
Miscellaneous (All) | 29.05 |
Subtotal | 29.05 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.32 |
Space Heating | 8.50 |
Space Cooling | 19.05 |
Fans (All) | 3.98 |
Service Water Heating | 7.13 |
Receptacle Equipment | 40.40 |
Miscellaneous | 3.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8684.33 | 75.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8640.00 | 120.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8689.67 | 70.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8708.50 | 51.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8641.50 | 118.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8590.33 | 169.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8590.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 169.67 | 0.00 | 0.00 | 0.00 |
Average | 8707.79 | 52.21 | 0.00 | 0.00 | 0.00 |
Sum | 156740.17 | 939.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128302.33 | 1.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1.67 | 0.00 | 0.00 | 0.00 |
Average | 34143.24 | 0.09 | 0.00 | 0.00 | 0.00 |
Sum | 614578.33 | 1.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8462.33 | 297.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7896.00 | 864.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7886.83 | 873.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7867.50 | 892.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7884.00 | 876.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8133.67 | 626.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8003.83 | 756.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7882.33 | 877.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7980.67 | 779.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7881.00 | 879.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7866.33 | 893.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7831.50 | 928.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7842.33 | 917.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8191.33 | 568.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8249.50 | 510.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8332.83 | 427.17 | 0.00 | 0.00 | 0.00 |
Min | 7831.50 | 1.50 | 0.00 | 0.00 | 0.00 |
Max | 8758.50 | 928.50 | 0.00 | 0.00 | 0.00 |
Average | 8094.91 | 665.09 | 0.00 | 0.00 | 0.00 |
Sum | 145708.33 | 11971.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128209.33 | 94.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24880.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24881.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24896.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23898.50 | 1010.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24877.83 | 31.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24877.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1010.50 | 0.00 | 0.00 | 0.00 |
Average | 34074.64 | 68.69 | 0.00 | 0.00 | 0.00 |
Sum | 613343.50 | 1236.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120924E+11 | 11918.22 | 31-JAN-17:00 | 19.40 | 13.37 | 0.177744E+10 | 2606.39 | 31-JAN-14:30 | 19.40 | 13.37 |
February | 0.127880E+11 | 17335.57 | 28-FEB-17:00 | 23.90 | 12.94 | 0.170413E+10 | 2606.64 | 22-FEB-14:09 | 23.90 | 12.94 |
March | 0.189800E+11 | 20971.78 | 31-MAR-08:00 | 18.30 | 16.52 | 0.213860E+10 | 2606.71 | 08-MAR-10:09 | 18.30 | 16.52 |
April | 0.196449E+11 | 21753.74 | 18-APR-08:00 | 19.40 | 14.96 | 0.190910E+10 | 2606.61 | 17-APR-09:09 | 19.40 | 14.96 |
May | 0.239944E+11 | 31597.86 | 30-MAY-05:13 | 19.07 | 17.52 | 0.207576E+10 | 2606.72 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.270285E+11 | 33656.26 | 26-JUN-05:13 | 23.30 | 21.67 | 0.206981E+10 | 2606.67 | 09-JUN-09:00 | 23.30 | 21.67 |
July | 0.271106E+11 | 43801.86 | 07-JUL-04:02 | 25.22 | 21.53 | 0.192396E+10 | 2606.54 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.297032E+11 | 43864.50 | 03-AUG-04:02 | 23.90 | 22.21 | 0.215962E+10 | 2606.54 | 28-AUG-13:30 | 28.30 | 22.11 |
September | 0.250837E+11 | 34556.38 | 06-SEP-05:13 | 21.30 | 20.11 | 0.191760E+10 | 2606.65 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.214061E+11 | 23709.64 | 19-OCT-05:13 | 20.73 | 20.73 | 0.198589E+10 | 2606.60 | 04-OCT-13:09 | 20.73 | 20.73 |
November | 0.172714E+11 | 20894.25 | 03-NOV-07:07 | 13.40 | 12.69 | 0.195439E+10 | 2607.91 | 21-NOV-10:30 | 3.30 | 0.39 |
December | 0.140075E+11 | 18347.94 | 13-DEC-08:10 | 16.78 | 15.73 | 0.185075E+10 | 2606.57 | 22-DEC-14:09 | 9.50 | 7.22 |
Annual Sum or Average | 0.249111E+12 | 0.234670E+11 | ||||||||
Minimum of Months | 0.120924E+11 | 11918.22 | 13.40 | 12.69 | 0.170413E+10 | 2606.39 | 3.30 | 0.39 | ||
Maximum of Months | 0.297032E+11 | 43864.50 | 25.22 | 22.21 | 0.215962E+10 | 2607.91 | 28.30 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144188E+09 | 1609.41 | 28-JAN-17:25 | 11.40 | 4.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.40 | 4.15 |
February | 0.520945E+09 | 3626.04 | 26-FEB-14:17 | 24.60 | 12.61 | 0.00 | 0.00 | 01-FEB-00:10 | 24.60 | 12.61 |
March | 0.159606E+10 | 6773.04 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.280329E+10 | 7717.77 | 17-APR-15:10 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.444188E+10 | 8619.72 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.631979E+10 | 9290.98 | 27-JUN-14:50 | 32.20 | 23.14 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 23.14 |
July | 0.674033E+10 | 10344.56 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.702225E+10 | 10449.73 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.391506E+10 | 8973.35 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.196325E+10 | 6790.74 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.818863E+09 | 3216.01 | 05-NOV-15:10 | 23.98 | 18.38 | 0.00 | 0.00 | 01-NOV-00:10 | 23.98 | 18.38 |
December | 0.296729E+09 | 2083.71 | 12-DEC-14:40 | 22.80 | 16.47 | 0.00 | 0.00 | 01-DEC-00:10 | 22.80 | 16.47 |
Annual Sum or Average | 0.365826E+11 | 0.00 | ||||||||
Minimum of Months | 0.144188E+09 | 1609.41 | 11.40 | 4.15 | 0.00 | 0.00 | 11.40 | 4.15 | ||
Maximum of Months | 0.702225E+10 | 10449.73 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51146806.41 | 1909.19 | 14-JAN-05:01 | -6.2 | -7.4 | 0.00 | 0.00 | 01-JAN-00:10 | -6.2 | -7.4 |
February | 0.196871E+09 | 1913.13 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.747130E+09 | 2118.07 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.131172E+10 | 2715.94 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.225902E+10 | 3518.30 | 30-MAY-15:30 | 29.20 | 21.54 | 0.00 | 0.00 | 01-MAY-00:10 | 29.20 | 21.54 |
June | 0.343884E+10 | 3971.13 | 26-JUN-15:30 | 30.00 | 23.57 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 23.57 |
July | 0.381438E+10 | 4346.49 | 10-JUL-15:40 | 32.60 | 22.27 | 0.00 | 0.00 | 01-JUL-00:10 | 32.60 | 22.27 |
August | 0.414093E+10 | 4298.08 | 18-AUG-16:00 | 35.00 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.11 |
September | 0.251769E+10 | 3936.08 | 07-SEP-16:00 | 31.70 | 23.71 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.71 |
October | 0.109975E+10 | 2623.35 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.386074E+09 | 1900.23 | 07-NOV-07:03 | 5.68 | 2.52 | 0.00 | 0.00 | 01-NOV-00:10 | 5.68 | 2.52 |
December | 0.140903E+09 | 2068.86 | 09-DEC-06:11 | 2.20 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | -1.0 |
Annual Sum or Average | 0.201045E+11 | 0.00 | ||||||||
Minimum of Months | 51146806.41 | 1900.23 | -6.2 | -7.4 | 0.00 | 0.00 | -6.2 | -7.4 | ||
Maximum of Months | 0.414093E+10 | 4346.49 | 35.00 | 23.71 | 0.00 | 0.00 | 35.00 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63230965.19 | 1804.71 | 13-JAN-06:11 | 3.90 | 2.25 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 2.25 |
February | 0.245889E+09 | 2328.49 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.996859E+09 | 2638.83 | 17-MAR-06:03 | 8.30 | 5.61 | 0.00 | 0.00 | 01-MAR-00:10 | 8.30 | 5.61 |
April | 0.160684E+10 | 2950.28 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.252950E+10 | 3716.76 | 30-MAY-15:10 | 30.13 | 21.49 | 0.00 | 0.00 | 01-MAY-00:10 | 30.13 | 21.49 |
June | 0.374634E+10 | 4063.81 | 19-JUN-16:00 | 32.20 | 23.34 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 23.34 |
July | 0.413987E+10 | 4556.71 | 10-JUL-16:00 | 32.80 | 22.35 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 22.35 |
August | 0.463212E+10 | 4705.40 | 18-AUG-16:00 | 35.00 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.11 |
September | 0.310168E+10 | 4515.01 | 07-SEP-16:00 | 31.70 | 23.71 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.71 |
October | 0.154270E+10 | 3415.03 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.547673E+09 | 1933.43 | 14-NOV-07:03 | 3.03 | 0.85 | 0.00 | 0.00 | 01-NOV-00:10 | 3.03 | 0.85 |
December | 0.195028E+09 | 2121.32 | 15-DEC-07:03 | 3.22 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 0.92 |
Annual Sum or Average | 0.233477E+11 | 0.00 | ||||||||
Minimum of Months | 63230965.19 | 1804.71 | 1.20 | -0.4 | 0.00 | 0.00 | 1.20 | -0.4 | ||
Maximum of Months | 0.463212E+10 | 4705.40 | 35.00 | 23.71 | 0.00 | 0.00 | 35.00 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781802E+10 | 8842.11 | 20-JAN-17:00 | 16.70 | 11.48 | 0.152578E+10 | 2262.79 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.914136E+10 | 9973.55 | 28-FEB-17:00 | 23.90 | 12.94 | 0.147461E+10 | 2557.40 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.135897E+11 | 13829.24 | 31-MAR-16:00 | 17.20 | 13.86 | 0.198620E+10 | 2606.55 | 30-MAR-13:09 | 17.20 | 13.86 |
April | 0.142398E+11 | 14839.97 | 18-APR-16:00 | 25.60 | 16.92 | 0.185249E+10 | 2606.60 | 17-APR-09:09 | 25.60 | 16.92 |
May | 0.175875E+11 | 16852.43 | 30-MAY-16:00 | 27.80 | 21.50 | 0.205583E+10 | 2606.68 | 11-MAY-09:00 | 27.80 | 21.50 |
June | 0.200459E+11 | 27634.20 | 26-JUN-05:13 | 23.30 | 21.67 | 0.206127E+10 | 2606.66 | 09-JUN-09:39 | 23.30 | 21.67 |
July | 0.204828E+11 | 31773.80 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191719E+10 | 2606.55 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.220388E+11 | 32354.83 | 03-AUG-04:02 | 23.90 | 22.21 | 0.215485E+10 | 2606.55 | 25-AUG-09:09 | 24.97 | 18.13 |
September | 0.177876E+11 | 19521.90 | 07-SEP-05:13 | 22.20 | 21.11 | 0.190289E+10 | 2606.61 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.144342E+11 | 15420.92 | 11-OCT-16:00 | 26.10 | 17.12 | 0.189901E+10 | 2606.58 | 10-OCT-09:00 | 26.10 | 17.12 |
November | 0.117858E+11 | 11046.78 | 06-NOV-17:00 | 18.90 | 9.61 | 0.176061E+10 | 2601.99 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.985546E+10 | 9689.84 | 13-DEC-17:00 | 16.70 | 16.70 | 0.156303E+10 | 2489.40 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.178807E+12 | 0.221538E+11 | ||||||||
Minimum of Months | 0.781802E+10 | 8842.11 | 16.70 | 9.61 | 0.147461E+10 | 2262.79 | 16.70 | 9.61 | ||
Maximum of Months | 0.220388E+11 | 32354.83 | 27.80 | 22.21 | 0.215485E+10 | 2606.68 | 27.80 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602985E+10 | 9065.42 | 20-JAN-17:00 | 16.70 | 11.48 | 0.148131E+10 | 2204.76 | 20-JAN-16:00 | 16.70 | 11.48 |
February | 0.763758E+10 | 10324.55 | 28-FEB-17:00 | 23.90 | 12.94 | 0.140953E+10 | 2518.26 | 28-FEB-16:00 | 23.90 | 12.94 |
March | 0.130592E+11 | 15831.86 | 30-MAR-16:00 | 27.80 | 17.47 | 0.188429E+10 | 2606.57 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.143120E+11 | 16909.25 | 17-APR-16:00 | 28.90 | 16.41 | 0.179434E+10 | 2606.62 | 11-APR-13:09 | 28.90 | 16.41 |
May | 0.181509E+11 | 19226.43 | 30-MAY-15:30 | 29.20 | 21.54 | 0.203313E+10 | 2606.63 | 15-MAY-13:09 | 29.20 | 21.54 |
June | 0.211785E+11 | 30603.66 | 26-JUN-05:13 | 23.30 | 21.67 | 0.205511E+10 | 2606.66 | 06-JUN-09:09 | 23.30 | 21.67 |
July | 0.218031E+11 | 33189.58 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191445E+10 | 2606.60 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.232488E+11 | 33811.01 | 14-AUG-04:02 | 24.22 | 20.90 | 0.215237E+10 | 2606.62 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.176591E+11 | 19423.09 | 07-SEP-16:00 | 31.70 | 23.71 | 0.188159E+10 | 2606.66 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.135813E+11 | 16401.54 | 11-OCT-16:00 | 26.10 | 17.12 | 0.180551E+10 | 2606.57 | 11-OCT-09:00 | 26.10 | 17.12 |
November | 0.104723E+11 | 10261.91 | 06-NOV-17:00 | 18.90 | 9.61 | 0.162509E+10 | 2522.27 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.756986E+10 | 9740.59 | 13-DEC-17:00 | 16.70 | 16.70 | 0.147485E+10 | 2404.76 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.174703E+12 | 0.215116E+11 | ||||||||
Minimum of Months | 0.602985E+10 | 9065.42 | 16.70 | 9.61 | 0.140953E+10 | 2204.76 | 16.70 | 9.61 | ||
Maximum of Months | 0.232488E+11 | 33811.01 | 31.70 | 23.71 | 0.215237E+10 | 2606.66 | 29.20 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323084E+09 | 1864.07 | 31-JAN-16:50 | 19.50 | 13.40 | 0.307345E+09 | 460.81 | 31-JAN-14:00 | 19.50 | 13.40 |
February | 0.788132E+09 | 2390.65 | 28-FEB-15:40 | 23.87 | 12.92 | 0.288004E+09 | 549.36 | 28-FEB-14:00 | 23.87 | 12.92 |
March | 0.225500E+10 | 4653.93 | 30-MAR-15:50 | 27.80 | 17.41 | 0.377152E+09 | 549.47 | 30-MAR-13:09 | 27.80 | 17.41 |
April | 0.304800E+10 | 5034.23 | 19-APR-14:30 | 26.15 | 17.54 | 0.364576E+09 | 549.49 | 12-APR-13:50 | 26.15 | 17.54 |
May | 0.457273E+10 | 6500.25 | 30-MAY-15:00 | 30.60 | 21.44 | 0.423733E+09 | 549.49 | 15-MAY-13:09 | 30.60 | 21.44 |
June | 0.626028E+10 | 9103.02 | 25-JUN-14:23 | 31.65 | 23.29 | 0.433349E+09 | 549.50 | 09-JUN-13:09 | 31.65 | 23.29 |
July | 0.654427E+10 | 12052.00 | 16-JUL-18:32 | 31.67 | 22.10 | 0.404325E+09 | 549.48 | 03-JUL-09:09 | 31.67 | 22.10 |
August | 0.681505E+10 | 9221.90 | 06-AUG-14:02 | 32.62 | 23.99 | 0.454247E+09 | 549.48 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.426585E+10 | 6360.72 | 06-SEP-14:30 | 30.25 | 23.24 | 0.391933E+09 | 549.49 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.251783E+10 | 4305.19 | 02-OCT-14:40 | 26.70 | 20.10 | 0.361200E+09 | 549.47 | 19-OCT-13:50 | 23.62 | 19.69 |
November | 0.146250E+10 | 2144.14 | 02-NOV-15:40 | 22.40 | 16.14 | 0.323678E+09 | 524.64 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.653839E+09 | 1998.39 | 13-DEC-15:00 | 18.30 | 16.86 | 0.300051E+09 | 496.30 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.395066E+11 | 0.442959E+10 | ||||||||
Minimum of Months | 0.323084E+09 | 1864.07 | 18.30 | 12.92 | 0.288004E+09 | 460.81 | 18.30 | 12.92 | ||
Maximum of Months | 0.681505E+10 | 12052.00 | 32.62 | 23.99 | 0.454247E+09 | 549.50 | 31.67 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391490E+09 | 1542.48 | 31-JAN-15:10 | 20.92 | 13.08 | 0.194613E+09 | 288.24 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.828079E+09 | 2040.58 | 27-FEB-10:40 | 14.27 | 6.32 | 0.187637E+09 | 347.86 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.209735E+10 | 3561.16 | 30-MAR-11:00 | 22.20 | 17.83 | 0.250546E+09 | 347.87 | 08-MAR-10:30 | 22.20 | 17.83 |
April | 0.300596E+10 | 5800.54 | 16-APR-11:13 | 26.47 | 15.53 | 0.241787E+09 | 347.88 | 12-APR-13:50 | 26.47 | 15.53 |
May | 0.430660E+10 | 11654.93 | 07-MAY-09:23 | 24.15 | 19.65 | 0.270948E+09 | 347.89 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.549192E+10 | 11700.53 | 04-JUN-08:23 | 23.30 | 17.57 | 0.275042E+09 | 347.88 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.576801E+10 | 11735.83 | 09-JUL-10:22 | 28.85 | 23.10 | 0.255751E+09 | 347.86 | 03-JUL-09:09 | 28.85 | 23.10 |
August | 0.587887E+10 | 11718.53 | 13-AUG-10:23 | 27.25 | 22.90 | 0.287468E+09 | 347.88 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.399317E+10 | 9891.54 | 04-SEP-09:53 | 26.70 | 22.31 | 0.249144E+09 | 347.88 | 25-SEP-09:30 | 25.55 | 19.33 |
October | 0.234453E+10 | 4415.62 | 11-OCT-10:30 | 24.20 | 19.54 | 0.238089E+09 | 347.87 | 11-OCT-09:00 | 24.20 | 19.54 |
November | 0.138153E+10 | 1843.29 | 06-NOV-10:50 | 16.73 | 12.97 | 0.209277E+09 | 343.55 | 06-NOV-10:00 | 17.20 | 13.02 |
December | 0.712974E+09 | 1642.47 | 12-DEC-15:10 | 22.70 | 16.14 | 0.190725E+09 | 305.41 | 12-DEC-14:00 | 22.70 | 16.14 |
Annual Sum or Average | 0.362005E+11 | 0.285103E+10 | ||||||||
Minimum of Months | 0.391490E+09 | 1542.48 | 14.27 | 6.32 | 0.187637E+09 | 288.24 | 17.20 | 13.02 | ||
Maximum of Months | 0.587887E+10 | 11735.83 | 28.85 | 23.10 | 0.287468E+09 | 347.89 | 28.85 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128961E+10 | 4544.64 | 11-JAN-14:30 | 6.70 | 2.05 | 0.338275E+09 | 549.48 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.181517E+10 | 12539.06 | 26-FEB-14:43 | 24.90 | 12.71 | 0.315306E+09 | 549.49 | 21-FEB-14:00 | 24.90 | 12.71 |
March | 0.353322E+10 | 9546.97 | 30-MAR-13:50 | 27.62 | 17.92 | 0.403754E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.92 |
April | 0.412516E+10 | 8358.08 | 17-APR-14:00 | 28.90 | 16.63 | 0.374677E+09 | 549.52 | 12-APR-13:50 | 28.90 | 16.63 |
May | 0.522196E+10 | 7768.98 | 30-MAY-14:30 | 30.60 | 21.24 | 0.423351E+09 | 549.49 | 15-MAY-13:09 | 30.60 | 21.24 |
June | 0.648554E+10 | 13322.04 | 25-JUN-14:23 | 31.65 | 23.29 | 0.432086E+09 | 549.50 | 09-JUN-13:09 | 31.65 | 23.29 |
July | 0.689019E+10 | 13848.41 | 16-JUL-13:53 | 33.90 | 23.22 | 0.404070E+09 | 549.48 | 03-JUL-09:09 | 33.90 | 23.22 |
August | 0.800176E+10 | 14391.36 | 06-AUG-13:23 | 32.50 | 23.69 | 0.454402E+09 | 549.48 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.594792E+10 | 14556.01 | 24-SEP-14:02 | 28.40 | 19.93 | 0.394439E+09 | 549.50 | 22-SEP-13:00 | 28.40 | 19.93 |
October | 0.455458E+10 | 14587.39 | 09-OCT-14:02 | 27.30 | 19.46 | 0.384239E+09 | 549.49 | 04-OCT-13:00 | 27.30 | 19.46 |
November | 0.289545E+10 | 13847.74 | 11-NOV-14:43 | 21.10 | 11.81 | 0.362071E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.188226E+10 | 6066.58 | 08-DEC-14:10 | 12.80 | 5.52 | 0.339229E+09 | 549.47 | 07-DEC-14:00 | 12.80 | 5.52 |
Annual Sum or Average | 0.526428E+11 | 0.462590E+10 | ||||||||
Minimum of Months | 0.128961E+10 | 4544.64 | 6.70 | 2.05 | 0.315306E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.800176E+10 | 14587.39 | 33.90 | 23.69 | 0.454402E+09 | 549.52 | 33.90 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460577E+09 | 1809.09 | 20-JAN-16:40 | 16.87 | 11.91 | 0.195816E+09 | 299.20 | 11-JAN-16:49 | 16.87 | 11.91 |
February | 0.856653E+09 | 4128.66 | 27-FEB-17:00 | 22.20 | 11.44 | 0.184011E+09 | 345.71 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.229800E+10 | 6344.23 | 30-MAR-16:00 | 27.80 | 17.47 | 0.237591E+09 | 347.83 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.317244E+10 | 11456.27 | 09-APR-17:23 | 21.40 | 11.01 | 0.226378E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.430362E+10 | 11198.43 | 06-MAY-17:42 | 27.30 | 19.67 | 0.262083E+09 | 347.84 | 15-MAY-13:09 | 27.88 | 17.61 |
June | 0.530952E+10 | 13357.66 | 04-JUN-17:42 | 30.78 | 19.44 | 0.271310E+09 | 347.85 | 02-JUN-09:00 | 30.78 | 19.44 |
July | 0.551577E+10 | 13270.41 | 04-JUL-18:42 | 30.10 | 22.17 | 0.254083E+09 | 347.84 | 03-JUL-09:09 | 30.10 | 22.17 |
August | 0.579162E+10 | 13364.95 | 13-AUG-17:02 | 31.10 | 22.35 | 0.286082E+09 | 347.84 | 25-AUG-09:00 | 27.80 | 18.82 |
September | 0.395830E+10 | 11317.25 | 04-SEP-16:33 | 28.13 | 22.40 | 0.243110E+09 | 347.84 | 22-SEP-13:00 | 26.70 | 17.59 |
October | 0.248182E+10 | 8834.74 | 09-OCT-16:42 | 26.88 | 19.41 | 0.226124E+09 | 347.83 | 19-OCT-13:39 | 23.33 | 19.60 |
November | 0.142163E+10 | 3736.84 | 06-NOV-16:00 | 20.60 | 10.48 | 0.207170E+09 | 347.80 | 06-NOV-14:00 | 20.60 | 10.48 |
December | 0.713780E+09 | 1950.66 | 11-DEC-16:00 | 21.10 | 15.91 | 0.192467E+09 | 320.64 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.362837E+11 | 0.278623E+10 | ||||||||
Minimum of Months | 0.460577E+09 | 1809.09 | 16.87 | 10.48 | 0.184011E+09 | 299.20 | 16.87 | 10.48 | ||
Maximum of Months | 0.579162E+10 | 13364.95 | 31.10 | 22.40 | 0.286082E+09 | 347.85 | 30.78 | 22.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346161E+09 | 1777.42 | 31-JAN-15:10 | 20.92 | 13.08 | 0.307979E+09 | 447.76 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.826285E+09 | 2035.14 | 28-FEB-15:20 | 24.43 | 13.32 | 0.286191E+09 | 511.13 | 28-FEB-14:00 | 24.43 | 13.32 |
March | 0.217402E+10 | 2612.25 | 30-MAR-16:00 | 27.80 | 17.47 | 0.367905E+09 | 549.47 | 30-MAR-13:39 | 27.80 | 17.47 |
April | 0.250242E+10 | 2969.20 | 19-APR-14:30 | 26.15 | 17.54 | 0.351685E+09 | 549.47 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.342428E+10 | 4493.47 | 30-MAY-15:00 | 30.60 | 21.44 | 0.419297E+09 | 549.48 | 09-MAY-13:09 | 30.60 | 21.44 |
June | 0.506488E+10 | 5391.50 | 30-JUN-14:30 | 33.05 | 22.98 | 0.433743E+09 | 549.49 | 09-JUN-09:00 | 33.05 | 22.98 |
July | 0.560243E+10 | 5898.49 | 14-JUL-15:00 | 35.00 | 23.85 | 0.404417E+09 | 549.48 | 03-JUL-09:09 | 35.00 | 23.85 |
August | 0.615583E+10 | 5947.05 | 09-AUG-15:00 | 32.80 | 23.20 | 0.454591E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.428991E+10 | 5634.00 | 06-SEP-14:30 | 30.25 | 23.24 | 0.399889E+09 | 549.49 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.301486E+10 | 3892.38 | 02-OCT-14:30 | 26.70 | 20.05 | 0.382821E+09 | 549.47 | 20-OCT-13:09 | 18.22 | 11.22 |
November | 0.217712E+10 | 2163.53 | 05-NOV-13:13 | 22.57 | 18.26 | 0.344015E+09 | 537.38 | 03-NOV-13:00 | 22.57 | 18.26 |
December | 0.109243E+10 | 1999.40 | 13-DEC-13:30 | 19.45 | 17.14 | 0.305435E+09 | 499.21 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.366706E+11 | 0.445797E+10 | ||||||||
Minimum of Months | 0.346161E+09 | 1777.42 | 19.45 | 13.08 | 0.286191E+09 | 447.76 | 18.22 | 11.22 | ||
Maximum of Months | 0.615583E+10 | 5947.05 | 35.00 | 23.85 | 0.454591E+09 | 549.49 | 35.00 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450918E+09 | 1339.89 | 31-JAN-15:00 | 21.10 | 12.97 | 0.196076E+09 | 291.69 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.810091E+09 | 1772.41 | 27-FEB-10:40 | 14.27 | 6.32 | 0.189174E+09 | 347.87 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.188392E+10 | 2508.24 | 14-MAR-11:00 | 20.60 | 15.46 | 0.251113E+09 | 347.87 | 08-MAR-10:50 | 20.60 | 15.46 |
April | 0.229437E+10 | 4222.81 | 17-APR-10:10 | 23.27 | 15.57 | 0.240773E+09 | 347.87 | 17-APR-09:09 | 23.27 | 15.57 |
May | 0.330234E+10 | 5249.15 | 30-MAY-10:00 | 27.80 | 21.16 | 0.271426E+09 | 347.89 | 11-MAY-09:00 | 27.80 | 21.16 |
June | 0.462676E+10 | 7882.86 | 04-JUN-08:23 | 23.30 | 17.57 | 0.275638E+09 | 347.88 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.507077E+10 | 8803.46 | 09-JUL-10:22 | 28.85 | 23.10 | 0.256531E+09 | 347.86 | 17-JUL-09:00 | 27.80 | 22.02 |
August | 0.542277E+10 | 10283.74 | 27-AUG-09:12 | 25.73 | 21.64 | 0.288237E+09 | 347.86 | 18-AUG-13:00 | 25.73 | 21.64 |
September | 0.395647E+10 | 6287.84 | 08-SEP-09:30 | 26.65 | 22.11 | 0.253977E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.266834E+10 | 4356.12 | 11-OCT-10:30 | 24.20 | 19.54 | 0.250412E+09 | 347.87 | 04-OCT-13:00 | 24.20 | 19.54 |
November | 0.177123E+10 | 2292.60 | 06-NOV-10:10 | 14.87 | 12.62 | 0.229675E+09 | 347.87 | 08-NOV-10:09 | 12.25 | 6.43 |
December | 0.106996E+10 | 1473.15 | 13-DEC-12:00 | 20.00 | 17.41 | 0.198480E+09 | 316.82 | 13-DEC-14:09 | 18.30 | 16.86 |
Annual Sum or Average | 0.333279E+11 | 0.290151E+10 | ||||||||
Minimum of Months | 0.450918E+09 | 1339.89 | 14.27 | 6.32 | 0.189174E+09 | 291.69 | 12.25 | 6.43 | ||
Maximum of Months | 0.542277E+10 | 10283.74 | 28.85 | 23.10 | 0.288237E+09 | 347.89 | 27.80 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.828046E+09 | 2510.57 | 28-JAN-14:50 | 11.93 | 4.48 | 0.314096E+09 | 524.42 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.129895E+10 | 6225.57 | 26-FEB-14:13 | 24.60 | 12.61 | 0.299513E+09 | 549.49 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.265941E+10 | 7645.95 | 30-MAR-16:10 | 27.62 | 17.53 | 0.390289E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.299637E+10 | 7757.54 | 17-APR-16:10 | 28.80 | 16.45 | 0.361260E+09 | 549.51 | 12-APR-13:39 | 28.80 | 16.45 |
May | 0.401131E+10 | 8866.47 | 30-MAY-12:00 | 29.40 | 21.24 | 0.414171E+09 | 549.49 | 10-MAY-13:00 | 29.40 | 21.24 |
June | 0.603134E+10 | 9961.24 | 06-JUN-16:20 | 33.90 | 21.85 | 0.431028E+09 | 564.33 | 06-JUN-12:09 | 33.90 | 21.85 |
July | 0.671554E+10 | 10405.73 | 07-JUL-16:10 | 35.50 | 23.98 | 0.404134E+09 | 589.05 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.826760E+10 | 11505.27 | 06-AUG-14:02 | 32.62 | 23.99 | 0.456277E+09 | 614.14 | 18-AUG-12:09 | 33.98 | 23.68 |
September | 0.617761E+10 | 10280.20 | 07-SEP-12:00 | 31.10 | 23.22 | 0.399088E+09 | 592.77 | 07-SEP-12:09 | 31.02 | 23.18 |
October | 0.455342E+10 | 12049.54 | 09-OCT-14:13 | 27.40 | 19.48 | 0.392702E+09 | 578.59 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.293201E+10 | 10661.89 | 12-NOV-14:13 | 19.27 | 10.66 | 0.370316E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.179874E+10 | 5665.57 | 12-DEC-14:00 | 22.80 | 17.07 | 0.331914E+09 | 549.49 | 05-DEC-14:09 | 22.80 | 17.07 |
Annual Sum or Average | 0.482703E+11 | 0.456479E+10 | ||||||||
Minimum of Months | 0.828046E+09 | 2510.57 | 11.93 | 4.48 | 0.299513E+09 | 524.42 | 20.00 | 9.44 | ||
Maximum of Months | 0.826760E+10 | 12049.54 | 35.50 | 23.99 | 0.456277E+09 | 614.14 | 33.98 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445239E+09 | 1442.75 | 20-JAN-16:40 | 16.87 | 11.91 | 0.196807E+09 | 295.16 | 27-JAN-16:00 | 4.40 | -1.6 |
February | 0.792513E+09 | 2946.64 | 27-FEB-17:00 | 22.20 | 11.44 | 0.184924E+09 | 341.60 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.197137E+10 | 4212.46 | 30-MAR-16:00 | 27.80 | 17.47 | 0.241113E+09 | 347.83 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.232490E+10 | 4785.27 | 17-APR-16:00 | 28.90 | 16.41 | 0.228462E+09 | 347.83 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.314522E+10 | 6464.04 | 29-MAY-16:03 | 30.00 | 20.55 | 0.266152E+09 | 347.84 | 09-MAY-13:09 | 30.00 | 20.55 |
June | 0.435168E+10 | 10600.87 | 04-JUN-16:32 | 31.50 | 19.59 | 0.274544E+09 | 347.85 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.472377E+10 | 10518.92 | 04-JUL-18:42 | 30.10 | 22.17 | 0.256137E+09 | 347.84 | 03-JUL-09:09 | 30.10 | 22.17 |
August | 0.526272E+10 | 10539.63 | 13-AUG-17:02 | 31.10 | 22.35 | 0.288138E+09 | 347.83 | 10-AUG-13:00 | 31.10 | 22.35 |
September | 0.378893E+10 | 8442.90 | 04-SEP-16:23 | 28.05 | 22.55 | 0.253391E+09 | 347.84 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.265436E+10 | 5648.36 | 11-OCT-16:00 | 26.10 | 17.12 | 0.245474E+09 | 347.84 | 10-OCT-09:09 | 26.10 | 17.12 |
November | 0.182373E+10 | 3694.82 | 06-NOV-16:30 | 19.75 | 10.05 | 0.224078E+09 | 347.82 | 15-NOV-14:00 | 21.70 | 11.58 |
December | 0.996187E+09 | 1617.65 | 11-DEC-16:20 | 20.93 | 15.86 | 0.197975E+09 | 331.10 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.322806E+11 | 0.285720E+10 | ||||||||
Minimum of Months | 0.445239E+09 | 1442.75 | 16.87 | 10.05 | 0.184924E+09 | 295.16 | 4.40 | -1.6 | ||
Maximum of Months | 0.526272E+10 | 10600.87 | 31.50 | 22.55 | 0.288138E+09 | 347.85 | 31.10 | 22.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425059E+09 | 1820.88 | 31-JAN-17:00 | 19.40 | 13.37 | 0.309059E+09 | 470.30 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.987379E+09 | 2388.96 | 28-FEB-15:30 | 24.15 | 13.12 | 0.292086E+09 | 549.47 | 28-FEB-14:50 | 24.15 | 13.12 |
March | 0.251578E+10 | 4121.30 | 30-MAR-16:00 | 27.80 | 17.47 | 0.389811E+09 | 549.47 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.304567E+10 | 4555.41 | 18-APR-14:00 | 27.20 | 15.86 | 0.374751E+09 | 549.48 | 19-APR-09:09 | 19.78 | 15.80 |
May | 0.436076E+10 | 5844.18 | 30-MAY-15:00 | 30.60 | 21.44 | 0.429799E+09 | 549.49 | 18-MAY-09:09 | 30.60 | 21.44 |
June | 0.589167E+10 | 6235.85 | 30-JUN-14:30 | 33.05 | 22.98 | 0.434929E+09 | 549.50 | 09-JUN-09:39 | 33.05 | 22.98 |
July | 0.612639E+10 | 8988.34 | 16-JUL-13:53 | 33.90 | 23.22 | 0.404945E+09 | 549.47 | 03-JUL-09:09 | 33.90 | 23.22 |
August | 0.643690E+10 | 7467.56 | 14-AUG-04:02 | 24.22 | 20.90 | 0.454819E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.422783E+10 | 5782.94 | 06-SEP-14:30 | 30.25 | 23.24 | 0.397998E+09 | 549.49 | 22-SEP-13:39 | 26.50 | 17.31 |
October | 0.282153E+10 | 3995.60 | 02-OCT-14:40 | 26.70 | 20.10 | 0.375599E+09 | 549.47 | 11-OCT-09:50 | 22.43 | 18.62 |
November | 0.188985E+10 | 2099.50 | 03-NOV-15:20 | 21.50 | 17.22 | 0.337165E+09 | 541.59 | 03-NOV-13:00 | 21.50 | 17.22 |
December | 0.945058E+09 | 1979.09 | 13-DEC-13:30 | 19.45 | 17.14 | 0.305143E+09 | 511.62 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.396739E+11 | 0.450610E+10 | ||||||||
Minimum of Months | 0.425059E+09 | 1820.88 | 19.40 | 13.12 | 0.292086E+09 | 470.30 | 18.30 | 13.12 | ||
Maximum of Months | 0.643690E+10 | 8988.34 | 33.90 | 23.24 | 0.454819E+09 | 549.50 | 33.90 | 23.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487718E+09 | 1498.83 | 31-JAN-15:30 | 20.55 | 13.30 | 0.144206E+09 | 283.75 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.944289E+09 | 2557.14 | 27-FEB-10:00 | 12.80 | 5.65 | 0.139799E+09 | 338.72 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.225337E+10 | 3620.30 | 14-MAR-11:00 | 20.60 | 15.46 | 0.187372E+09 | 338.72 | 30-MAR-12:20 | 25.57 | 18.16 |
April | 0.298900E+10 | 6660.99 | 16-APR-10:53 | 26.10 | 15.47 | 0.179836E+09 | 338.74 | 18-APR-14:30 | 26.40 | 16.44 |
May | 0.409925E+10 | 11270.54 | 07-MAY-09:13 | 23.87 | 19.51 | 0.201017E+09 | 338.74 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.513548E+10 | 11215.56 | 11-JUN-09:53 | 25.00 | 14.66 | 0.203313E+09 | 338.73 | 05-JUN-07:30 | 25.00 | 14.66 |
July | 0.536789E+10 | 11789.36 | 23-JUL-09:12 | 26.87 | 22.77 | 0.189769E+09 | 338.73 | 03-JUL-07:49 | 26.87 | 22.77 |
August | 0.550161E+10 | 11854.91 | 27-AUG-09:12 | 25.73 | 21.64 | 0.212455E+09 | 338.72 | 14-AUG-07:19 | 25.73 | 21.64 |
September | 0.389225E+10 | 10564.40 | 04-SEP-09:23 | 25.85 | 21.92 | 0.185489E+09 | 338.74 | 11-SEP-07:30 | 20.85 | 19.50 |
October | 0.255643E+10 | 4603.99 | 11-OCT-10:20 | 23.73 | 19.29 | 0.178564E+09 | 338.72 | 10-OCT-10:09 | 23.73 | 19.29 |
November | 0.166754E+10 | 2455.21 | 06-NOV-09:50 | 14.03 | 12.24 | 0.159632E+09 | 338.70 | 06-NOV-09:39 | 14.03 | 12.24 |
December | 0.929254E+09 | 1618.52 | 13-DEC-12:00 | 20.00 | 17.41 | 0.142970E+09 | 304.20 | 13-DEC-13:39 | 19.07 | 17.05 |
Annual Sum or Average | 0.358241E+11 | 0.212442E+10 | ||||||||
Minimum of Months | 0.487718E+09 | 1498.83 | 12.80 | 5.65 | 0.139799E+09 | 283.75 | 14.03 | 12.02 | ||
Maximum of Months | 0.550161E+10 | 11854.91 | 26.87 | 22.77 | 0.212455E+09 | 338.74 | 26.87 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146116E+10 | 4638.73 | 11-JAN-14:10 | 6.70 | 2.05 | 0.345179E+09 | 549.48 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.203840E+10 | 9731.83 | 26-FEB-14:13 | 24.60 | 12.61 | 0.322085E+09 | 549.50 | 28-FEB-14:09 | 25.00 | 13.72 |
March | 0.374566E+10 | 8942.13 | 30-MAR-13:40 | 27.43 | 17.97 | 0.416748E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.406265E+10 | 7664.00 | 17-APR-13:50 | 28.72 | 16.68 | 0.384198E+09 | 549.49 | 11-APR-13:09 | 28.72 | 16.68 |
May | 0.494774E+10 | 7210.26 | 29-MAY-13:32 | 28.50 | 20.43 | 0.429893E+09 | 549.49 | 18-MAY-09:09 | 28.50 | 20.43 |
June | 0.606824E+10 | 8533.07 | 25-JUN-14:23 | 31.65 | 23.29 | 0.434333E+09 | 549.50 | 09-JUN-09:39 | 31.65 | 23.29 |
July | 0.641764E+10 | 10983.63 | 16-JUL-13:53 | 33.90 | 23.22 | 0.404999E+09 | 549.47 | 03-JUL-09:09 | 33.90 | 23.22 |
August | 0.753816E+10 | 12671.23 | 06-AUG-13:23 | 32.50 | 23.69 | 0.455165E+09 | 549.47 | 25-AUG-13:00 | 31.10 | 18.60 |
September | 0.583596E+10 | 9569.12 | 17-SEP-14:43 | 28.12 | 22.39 | 0.399696E+09 | 549.51 | 22-SEP-13:39 | 26.50 | 17.31 |
October | 0.489151E+10 | 12986.45 | 09-OCT-14:02 | 27.30 | 19.46 | 0.395284E+09 | 556.47 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.337091E+10 | 12760.93 | 11-NOV-14:43 | 21.10 | 11.81 | 0.376761E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.229445E+10 | 6575.07 | 08-DEC-14:00 | 12.80 | 5.54 | 0.349696E+09 | 549.47 | 07-DEC-14:00 | 12.80 | 5.54 |
Annual Sum or Average | 0.526725E+11 | 0.471404E+10 | ||||||||
Minimum of Months | 0.146116E+10 | 4638.73 | 6.70 | 2.05 | 0.322085E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.753816E+10 | 12986.45 | 33.90 | 23.69 | 0.455165E+09 | 556.47 | 33.90 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538721E+09 | 1683.39 | 11-JAN-16:40 | 6.47 | 1.83 | 0.197571E+09 | 306.09 | 11-JAN-16:49 | 6.28 | 1.74 |
February | 0.991629E+09 | 3989.90 | 27-FEB-17:00 | 22.20 | 11.44 | 0.186527E+09 | 347.81 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.245107E+10 | 5934.31 | 30-MAR-16:00 | 27.80 | 17.47 | 0.245129E+09 | 347.83 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.309383E+10 | 10500.64 | 09-APR-17:12 | 21.50 | 10.93 | 0.233629E+09 | 347.84 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.403690E+10 | 12015.19 | 29-MAY-16:52 | 30.00 | 20.55 | 0.268078E+09 | 347.85 | 17-MAY-09:00 | 30.00 | 20.55 |
June | 0.496056E+10 | 11771.04 | 25-JUN-16:22 | 33.05 | 22.20 | 0.273819E+09 | 347.85 | 02-JUN-09:50 | 33.05 | 22.20 |
July | 0.512124E+10 | 12560.83 | 23-JUL-17:52 | 28.90 | 22.63 | 0.255616E+09 | 347.84 | 03-JUL-09:09 | 28.90 | 22.63 |
August | 0.543241E+10 | 12341.33 | 13-AUG-16:51 | 31.10 | 22.45 | 0.287409E+09 | 347.83 | 25-AUG-09:09 | 24.97 | 18.13 |
September | 0.381264E+10 | 10593.14 | 04-SEP-16:12 | 27.97 | 22.70 | 0.249217E+09 | 347.84 | 22-SEP-13:50 | 26.60 | 17.45 |
October | 0.266823E+10 | 8302.57 | 09-OCT-16:03 | 27.62 | 19.54 | 0.234952E+09 | 347.83 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.173192E+10 | 3864.29 | 06-NOV-16:00 | 20.60 | 10.48 | 0.214388E+09 | 347.82 | 07-NOV-14:00 | 18.90 | 8.70 |
December | 0.924120E+09 | 1832.38 | 11-DEC-15:50 | 21.10 | 15.67 | 0.196081E+09 | 330.98 | 11-DEC-15:00 | 21.10 | 15.91 |
Annual Sum or Average | 0.357633E+11 | 0.284242E+10 | ||||||||
Minimum of Months | 0.538721E+09 | 1683.39 | 6.47 | 1.83 | 0.186527E+09 | 306.09 | 6.28 | 1.74 | ||
Maximum of Months | 0.543241E+10 | 12560.83 | 33.05 | 22.70 | 0.287409E+09 | 347.85 | 33.05 | 22.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39456813.95 | 17478.90 | 09-JAN-06:01 | -2.4 |
February | 3943987.56 | 15660.94 | 14-FEB-07:01 | 1.02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 43400801.51 | |||
Minimum of Months | 0.00 | 0.00 | -2.4 | |
Maximum of Months | 39456813.95 | 17478.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419376E+10 | 12859.62 | 09-JAN-06:13 | -2.6 |
February | 0.264269E+10 | 14923.28 | 13-FEB-06:06 | -5.6 |
March | 0.818069E+09 | 5615.23 | 18-MAR-06:03 | 2.70 |
April | 0.433227E+09 | 6306.11 | 06-APR-06:02 | 1.20 |
May | 0.131891E+09 | 3734.63 | 10-MAY-05:03 | 8.98 |
June | 59440385.59 | 3296.96 | 08-JUN-05:03 | 11.70 |
July | 18979576.91 | 3216.01 | 07-JUL-04:02 | 25.22 |
August | 16944580.90 | 4106.98 | 10-AUG-05:03 | 24.40 |
September | 0.108727E+09 | 3160.98 | 29-SEP-05:03 | 12.30 |
October | 0.628426E+09 | 6191.53 | 26-OCT-06:03 | 2.20 |
November | 0.121128E+10 | 10089.37 | 22-NOV-07:02 | -3.2 |
December | 0.249102E+10 | 13699.64 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.127544E+11 | |||
Minimum of Months | 16944580.90 | 3160.98 | -5.6 | |
Maximum of Months | 0.419376E+10 | 14923.28 | 25.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188443E+10 | 8208.39 | 09-JAN-07:11 | -3.3 |
February | 0.101334E+10 | 7675.91 | 13-FEB-07:11 | -5.6 |
March | 0.181519E+09 | 2576.27 | 26-MAR-16:27 | 20.30 |
April | 44319091.67 | 2185.01 | 09-APR-17:12 | 21.50 |
May | 9563709.57 | 1685.08 | 14-MAY-16:33 | 25.60 |
June | 7581799.77 | 1594.25 | 11-JUN-09:13 | 23.87 |
July | 10460123.53 | 1940.50 | 30-JUL-10:53 | 27.20 |
August | 8813531.75 | 1720.82 | 14-AUG-04:02 | 24.22 |
September | 9167793.95 | 2030.32 | 03-SEP-12:23 | 27.50 |
October | 0.129015E+09 | 3087.98 | 08-OCT-15:43 | 27.20 |
November | 0.383705E+09 | 3352.39 | 11-NOV-14:43 | 21.10 |
December | 0.997671E+09 | 5007.53 | 26-DEC-07:03 | 3.30 |
Annual Sum or Average | 0.467958E+10 | |||
Minimum of Months | 7581799.77 | 1594.25 | -5.6 | |
Maximum of Months | 0.188443E+10 | 8208.39 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140782E+10 | 5842.71 | 02-JAN-07:03 | 3.30 |
February | 0.757999E+09 | 4203.48 | 13-FEB-08:19 | -4.8 |
March | 92243157.34 | 1501.48 | 23-MAR-07:40 | 6.50 |
April | 13510382.26 | 1748.03 | 09-APR-16:35 | 21.70 |
May | 5962128.95 | 1778.97 | 29-MAY-14:10 | 28.48 |
June | 7595530.67 | 1489.04 | 11-JUN-07:30 | 20.85 |
July | 8798523.43 | 2807.25 | 07-JUL-04:02 | 25.22 |
August | 10116216.54 | 3040.08 | 04-AUG-04:02 | 23.90 |
September | 12597633.75 | 2110.47 | 03-SEP-12:28 | 27.50 |
October | 75300973.84 | 2726.17 | 22-OCT-11:32 | 21.67 |
November | 0.209130E+09 | 2651.48 | 12-NOV-11:33 | 15.77 |
December | 0.700325E+09 | 2724.55 | 26-DEC-08:09 | 3.30 |
Annual Sum or Average | 0.330140E+10 | |||
Minimum of Months | 5962128.95 | 1489.04 | -4.8 | |
Maximum of Months | 0.140782E+10 | 5842.71 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481061E+09 | 18534.49 | 02-JAN-06:11 | 3.30 |
February | 0.162017E+09 | 17459.25 | 13-FEB-06:01 | -5.6 |
March | 87863.17 | 585.75 | 23-MAR-06:03 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 4288591.59 | 14174.65 | 22-NOV-07:01 | -3.2 |
December | 90118708.47 | 16812.26 | 18-DEC-07:04 | -5.1 |
Annual Sum or Average | 0.737573E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.481061E+09 | 18534.49 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202337E+10 | 32802.60 | 09-JAN-05:01 | -2.2 |
February | 0.904653E+09 | 32670.90 | 13-FEB-05:01 | -5.1 |
March | 44269035.26 | 26381.78 | 20-MAR-06:03 | 5.00 |
April | 5806304.94 | 26117.38 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 19453833.12 | 26335.54 | 26-OCT-06:03 | 2.20 |
November | 0.137780E+09 | 28766.94 | 22-NOV-06:01 | -3.3 |
December | 0.800788E+09 | 31399.07 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.393612E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.202337E+10 | 32802.60 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358307E+10 | 10911.40 | 09-JAN-04:53 | -2.2 |
February | 0.201216E+10 | 11290.60 | 12-FEB-05:32 | -12.0 |
March | 0.232879E+09 | 9311.71 | 18-MAR-05:11 | 3.13 |
April | 62130033.47 | 9125.67 | 06-APR-05:02 | 0.18 |
May | 882179.52 | 4024.88 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 99332008.54 | 9433.19 | 26-OCT-05:11 | 2.20 |
November | 0.554894E+09 | 10147.46 | 22-NOV-05:02 | -2.9 |
December | 0.176954E+10 | 10706.41 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.831489E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.358307E+10 | 11290.60 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193019E+10 | 10140.79 | 09-JAN-04:53 | -2.2 |
February | 0.103931E+10 | 10554.20 | 12-FEB-05:32 | -12.0 |
March | 0.113100E+09 | 8779.72 | 22-MAR-05:11 | 5.93 |
April | 29679838.38 | 8545.36 | 06-APR-05:02 | 0.18 |
May | 612224.61 | 2164.72 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 274725.79 | 1373.63 | 29-SEP-06:03 | 12.88 |
October | 62947152.52 | 8888.52 | 26-OCT-05:11 | 2.20 |
November | 0.259725E+09 | 9477.06 | 22-NOV-05:02 | -2.9 |
December | 0.855804E+09 | 10040.71 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.429165E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.193019E+10 | 10554.20 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231595E+10 | 12478.82 | 09-JAN-04:53 | -2.2 |
February | 0.129679E+10 | 12899.58 | 12-FEB-05:32 | -12.0 |
March | 0.164969E+09 | 10673.41 | 23-MAR-05:11 | 6.10 |
April | 54131276.15 | 10392.52 | 06-APR-05:02 | 0.18 |
May | 1165638.77 | 5446.86 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 76119483.49 | 10655.22 | 26-OCT-05:11 | 2.20 |
November | 0.316549E+09 | 11432.54 | 21-NOV-05:02 | -2.3 |
December | 0.986252E+09 | 12201.47 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.521193E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.231595E+10 | 12899.58 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211976E+10 | 10458.71 | 09-JAN-04:53 | -2.2 |
February | 0.118298E+10 | 10922.84 | 12-FEB-05:32 | -12.0 |
March | 0.140251E+09 | 8884.12 | 23-MAR-05:11 | 6.10 |
April | 38332947.10 | 8624.57 | 06-APR-05:02 | 0.18 |
May | 1175575.58 | 4522.59 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 399697.70 | 1998.49 | 29-SEP-06:03 | 12.88 |
October | 65262739.58 | 8964.34 | 26-OCT-05:11 | 2.20 |
November | 0.341425E+09 | 9738.68 | 22-NOV-05:02 | -2.9 |
December | 0.104807E+10 | 10373.40 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.493766E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.211976E+10 | 10922.84 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197167E+10 | 8463.38 | 09-JAN-05:01 | -2.2 |
February | 0.991458E+09 | 8394.86 | 13-FEB-05:01 | -5.1 |
March | 67587045.51 | 7126.04 | 20-MAR-05:12 | 5.00 |
April | 18069639.12 | 6850.02 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 3083293.80 | 6734.09 | 26-OCT-06:03 | 2.20 |
November | 40561293.16 | 7197.96 | 22-NOV-06:01 | -3.3 |
December | 0.407200E+09 | 7752.49 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.349963E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.197167E+10 | 8463.38 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.991016E+09 | 7549.25 | 09-JAN-05:01 | -2.2 |
February | 0.431813E+09 | 7473.29 | 13-FEB-05:01 | -5.1 |
March | 27105434.97 | 6395.87 | 23-MAR-05:11 | 6.10 |
April | 5492597.29 | 5905.09 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 2324062.51 | 4902.59 | 26-OCT-06:03 | 2.20 |
November | 11955802.62 | 6180.83 | 22-NOV-06:01 | -3.3 |
December | 0.159480E+09 | 6732.16 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.162919E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.991016E+09 | 7549.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323533E+10 | 10656.42 | 09-JAN-08:00 | -3.3 |
February | 0.195758E+10 | 10877.90 | 03-FEB-07:10 | -8.9 |
March | 0.778220E+09 | 8813.42 | 06-MAR-07:50 | 2.80 |
April | 0.436149E+09 | 9218.26 | 06-APR-06:10 | 1.20 |
May | 0.105189E+09 | 8030.19 | 11-MAY-06:03 | 8.17 |
June | 12190799.40 | 5872.77 | 08-JUN-06:07 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 12086158.13 | 4116.70 | 29-SEP-06:07 | 12.88 |
October | 0.378993E+09 | 8803.34 | 26-OCT-07:00 | 2.20 |
November | 0.764816E+09 | 9716.78 | 22-NOV-07:10 | -3.2 |
December | 0.126928E+10 | 10342.56 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.894983E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.323533E+10 | 10877.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104648E+10 | 7596.41 | 09-JAN-05:01 | -2.2 |
February | 0.489682E+09 | 7499.20 | 13-FEB-05:01 | -5.1 |
March | 26917685.90 | 5976.12 | 23-MAR-05:11 | 6.10 |
April | 6060951.31 | 5995.41 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1742933.66 | 4528.59 | 31-OCT-06:03 | 8.22 |
November | 18740753.10 | 6211.12 | 22-NOV-06:01 | -3.3 |
December | 0.193068E+09 | 6738.42 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.178269E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.104648E+10 | 7596.41 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194530E+10 | 9120.22 | 02-JAN-06:11 | 3.30 |
February | 0.964397E+09 | 9426.45 | 13-FEB-04:02 | -5.0 |
March | 46193274.71 | 7636.83 | 22-MAR-05:11 | 5.93 |
April | 9044473.66 | 7360.63 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 13154429.35 | 7606.74 | 26-OCT-05:11 | 2.20 |
November | 0.140898E+09 | 8254.23 | 22-NOV-06:01 | -3.3 |
December | 0.680399E+09 | 8837.71 | 18-DEC-05:02 | -5.0 |
Annual Sum or Average | 0.379939E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.194530E+10 | 9426.45 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107822E+10 | 7909.29 | 09-JAN-05:01 | -2.2 |
February | 0.498586E+09 | 8252.28 | 13-FEB-04:02 | -5.0 |
March | 28018547.91 | 6757.69 | 23-MAR-05:11 | 6.10 |
April | 5429324.18 | 6357.67 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 11118094.98 | 6728.78 | 26-OCT-05:11 | 2.20 |
November | 65766508.72 | 7021.16 | 22-NOV-06:01 | -3.3 |
December | 0.320763E+09 | 7617.53 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.200790E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.107822E+10 | 8252.28 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115560E+10 | 10691.45 | 02-JAN-06:11 | 3.30 |
February | 0.535221E+09 | 10892.27 | 12-FEB-05:32 | -12.0 |
March | 30177383.45 | 8530.29 | 22-MAR-06:03 | 5.50 |
April | 7353137.38 | 8609.60 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 10687575.32 | 8511.15 | 26-OCT-06:03 | 2.20 |
November | 67489645.87 | 9456.60 | 22-NOV-06:01 | -3.3 |
December | 0.337912E+09 | 10246.83 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.214444E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.115560E+10 | 10892.27 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113159E+10 | 7938.73 | 09-JAN-05:01 | -2.2 |
February | 0.547487E+09 | 8319.93 | 13-FEB-04:02 | -5.0 |
March | 30039511.83 | 6796.42 | 22-MAR-05:11 | 5.93 |
April | 6298266.48 | 6479.04 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 10570173.42 | 5635.37 | 26-OCT-06:03 | 2.20 |
November | 89308482.57 | 7024.47 | 22-NOV-06:01 | -3.3 |
December | 0.396428E+09 | 7637.74 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.221172E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.113159E+10 | 8319.93 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846055E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.762897E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.796776E+09 | 1358.45 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.675359E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699833E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.687181E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651426E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.744765E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.703252E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.808123E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.811693E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.826313E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.901367E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651426E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.846055E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.508129E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.460497E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.492356E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.424791E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.447103E+09 | 450.21 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439946E+09 | 450.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415308E+09 | 600.14 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471842E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436677E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.484045E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.494745E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493985E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556942E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415308E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508129E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765762E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.705338E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.777899E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.677143E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712140E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700772E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663635E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749752E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.692213E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.750902E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.748109E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.742755E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.868642E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.663635E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.777899E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507897E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.468127E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.503400E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.431347E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451973E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.442883E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420627E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477530E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.446712E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.500286E+09 | 859.95 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.490384E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493477E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.563464E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420627E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.507897E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.839329E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.757888E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.793132E+09 | 1358.45 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.673272E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699539E+09 | 774.31 | 02-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.686444E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651107E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.743416E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.700764E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.802629E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.805079E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.819465E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.897207E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651107E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.839329E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505975E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.458253E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491163E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423886E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446374E+09 | 450.21 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439292E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.414667E+09 | 490.21 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471104E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435545E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.481922E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.492680E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.491780E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555264E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.414667E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505975E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.763932E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.704598E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.775420E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.675198E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.710688E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.699319E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.661869E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.747992E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.690150E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.748760E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.746697E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.740187E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866481E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.661869E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.775420E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505576E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.465983E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.501880E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429834E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450170E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.441854E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.419226E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.476238E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.444656E+09 | 859.95 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.498301E+09 | 859.95 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.487915E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.491638E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.561327E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.419226E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505576E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846055E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.762897E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.796776E+09 | 1358.45 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.675359E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699833E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.687181E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651426E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.744765E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.703252E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.808123E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.811693E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.826313E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.901367E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651426E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.846055E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.508129E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.460497E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.492356E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.424791E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.447103E+09 | 450.21 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439946E+09 | 450.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415308E+09 | 600.14 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471842E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436677E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.484045E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.494745E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493961E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556940E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415308E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508129E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765727E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.705338E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.777861E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.677143E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712140E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700772E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663635E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749752E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.692213E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.750900E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.748109E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.742755E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.868634E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.663635E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.777861E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507897E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.468127E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.503400E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.431347E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451973E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.442883E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420627E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477530E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.446712E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.500286E+09 | 859.95 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.490384E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493477E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.563464E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420627E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.507897E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846055E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997667E+09 |
February | 0.901968E+09 | 0.762897E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2447672.85 | 0.849081E+09 |
March | 0.107774E+10 | 0.796776E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3186290.83 | 0.538110E+09 |
April | 0.956342E+09 | 0.675359E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7655481.36 | 0.339936E+09 |
May | 0.103597E+10 | 0.699833E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18909697.04 | 0.226977E+09 |
June | 0.103308E+10 | 0.687181E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74944485.00 | 0.114464E+09 |
July | 0.959235E+09 | 0.651426E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81064549.77 | 75842904.98 |
August | 0.107774E+10 | 0.744765E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78238623.44 | 48306666.44 |
September | 0.956342E+09 | 0.703252E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24197146.39 | 0.111325E+09 |
October | 0.994195E+09 | 0.808123E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8020139.96 | 0.361642E+09 |
November | 0.984487E+09 | 0.811693E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1063730.59 | 0.515394E+09 |
December | 0.959235E+09 | 0.826313E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3741.50 | 0.888889E+09 |
Annual Sum or Average | 0.119305E+11 | 0.901367E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299732E+09 | 0.506763E+10 |
Minimum of Months | 0.901968E+09 | 0.651426E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48306666.44 |
Maximum of Months | 0.107774E+10 | 0.846055E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81064549.77 | 0.997667E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.508129E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672112E+09 |
February | 0.571020E+09 | 0.460497E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 831259.62 | 0.576169E+09 |
March | 0.682301E+09 | 0.492356E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2198680.50 | 0.371368E+09 |
April | 0.605444E+09 | 0.424791E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4340716.40 | 0.234075E+09 |
May | 0.655854E+09 | 0.447103E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11468539.42 | 0.157164E+09 |
June | 0.654023E+09 | 0.439946E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49017354.74 | 77829885.34 |
July | 0.607275E+09 | 0.415308E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52790897.08 | 51688782.63 |
August | 0.682301E+09 | 0.471842E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51296046.89 | 32844655.87 |
September | 0.605444E+09 | 0.436677E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15196314.74 | 74508845.06 |
October | 0.629407E+09 | 0.484045E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4197930.11 | 0.248196E+09 |
November | 0.623262E+09 | 0.494745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 658463.16 | 0.351478E+09 |
December | 0.607275E+09 | 0.493985E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4372.96 | 0.596788E+09 |
Annual Sum or Average | 0.755301E+10 | 0.556942E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192001E+09 | 0.344422E+10 |
Minimum of Months | 0.571020E+09 | 0.415308E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32844655.87 |
Maximum of Months | 0.682301E+09 | 0.508129E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52790897.08 | 0.672112E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.765762E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105535E+10 |
February | 0.901968E+09 | 0.705338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114326.70 | 0.904264E+09 |
March | 0.107774E+10 | 0.777899E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2134872.30 | 0.591595E+09 |
April | 0.956342E+09 | 0.677143E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5375105.61 | 0.354928E+09 |
May | 0.103597E+10 | 0.712140E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17397172.75 | 0.229029E+09 |
June | 0.103308E+10 | 0.700772E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74591703.95 | 0.112930E+09 |
July | 0.959235E+09 | 0.663635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80275337.70 | 75402396.60 |
August | 0.107774E+10 | 0.749752E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75409007.24 | 49913294.94 |
September | 0.956342E+09 | 0.692213E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19834031.59 | 0.116244E+09 |
October | 0.994195E+09 | 0.750902E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3132344.89 | 0.397293E+09 |
November | 0.984487E+09 | 0.748109E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571825E+09 |
December | 0.959235E+09 | 0.742755E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943637E+09 |
Annual Sum or Average | 0.119305E+11 | 0.868642E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278264E+09 | 0.540241E+10 |
Minimum of Months | 0.901968E+09 | 0.663635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49913294.94 |
Maximum of Months | 0.107774E+10 | 0.777899E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80275337.70 | 0.105535E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.507897E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674206E+09 |
February | 0.570983E+09 | 0.468127E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1087526.73 | 0.576997E+09 |
March | 0.682256E+09 | 0.503400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1679734.03 | 0.380387E+09 |
April | 0.605404E+09 | 0.431347E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4392075.35 | 0.235445E+09 |
May | 0.655811E+09 | 0.451973E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11922854.54 | 0.155252E+09 |
June | 0.653980E+09 | 0.442883E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48902397.89 | 78213294.85 |
July | 0.607235E+09 | 0.420627E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53260233.22 | 51225849.98 |
August | 0.682256E+09 | 0.477530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50300589.20 | 34800028.15 |
September | 0.605404E+09 | 0.446712E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15350155.21 | 75485308.31 |
October | 0.629366E+09 | 0.500286E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3932234.91 | 0.249215E+09 |
November | 0.623221E+09 | 0.490384E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116326.77 | 0.353850E+09 |
December | 0.607235E+09 | 0.493477E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.08 | 0.599039E+09 |
Annual Sum or Average | 0.755252E+10 | 0.563464E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190945E+09 | 0.346412E+10 |
Minimum of Months | 0.570983E+09 | 0.420627E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34800028.15 |
Maximum of Months | 0.682256E+09 | 0.507897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53260233.22 | 0.674206E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.839329E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567657E+09 |
February | 0.901968E+09 | 0.757888E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1431366.99 | 0.474048E+09 |
March | 0.107774E+10 | 0.793132E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2621874.45 | 0.288547E+09 |
April | 0.956342E+09 | 0.673272E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5894305.45 | 0.172049E+09 |
May | 0.103597E+10 | 0.699539E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11801366.15 | 0.114804E+09 |
June | 0.103308E+10 | 0.686444E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42754614.37 | 58634426.10 |
July | 0.959235E+09 | 0.651107E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47543037.16 | 39236243.53 |
August | 0.107774E+10 | 0.743416E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44706501.12 | 25105279.06 |
September | 0.956342E+09 | 0.700764E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13261913.01 | 67736510.20 |
October | 0.994195E+09 | 0.802629E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4200914.90 | 0.221349E+09 |
November | 0.984487E+09 | 0.805079E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159144.41 | 0.315708E+09 |
December | 0.959235E+09 | 0.819465E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4132.16 | 0.538128E+09 |
Annual Sum or Average | 0.119305E+11 | 0.897207E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174379E+09 | 0.288300E+10 |
Minimum of Months | 0.901968E+09 | 0.651107E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25105279.06 |
Maximum of Months | 0.107774E+10 | 0.839329E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47543037.16 | 0.567657E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.505975E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384656E+09 |
February | 0.571020E+09 | 0.458253E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374294.98 | 0.325169E+09 |
March | 0.682301E+09 | 0.491163E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1467365.17 | 0.204856E+09 |
April | 0.605444E+09 | 0.423886E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2680069.95 | 0.123210E+09 |
May | 0.655854E+09 | 0.446374E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6411998.26 | 83706021.21 |
June | 0.654023E+09 | 0.439292E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26759885.83 | 41831871.77 |
July | 0.607275E+09 | 0.414667E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29011213.73 | 28340110.13 |
August | 0.682301E+09 | 0.471104E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27787975.97 | 18660241.53 |
September | 0.605444E+09 | 0.435545E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7928726.89 | 46920640.33 |
October | 0.629407E+09 | 0.481922E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1914135.99 | 0.154617E+09 |
November | 0.623262E+09 | 0.492680E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46632.65 | 0.219165E+09 |
December | 0.607275E+09 | 0.491780E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364158E+09 |
Annual Sum or Average | 0.755301E+10 | 0.555264E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104382E+09 | 0.199529E+10 |
Minimum of Months | 0.571020E+09 | 0.414667E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18660241.53 |
Maximum of Months | 0.682301E+09 | 0.505975E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29011213.73 | 0.384656E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.763932E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461596E+10 |
February | 0.901968E+09 | 0.704598E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656385.41 | 0.341204E+10 |
March | 0.107774E+10 | 0.775420E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28290355.06 | 0.241403E+10 |
April | 0.956342E+09 | 0.675198E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143464E+09 | 0.136571E+10 |
May | 0.103597E+10 | 0.710688E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340123E+09 | 0.727176E+09 |
June | 0.103308E+10 | 0.699319E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969149E+09 | 0.276172E+09 |
July | 0.959235E+09 | 0.661869E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100611E+10 | 0.203332E+09 |
August | 0.107774E+10 | 0.747992E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111033E+10 | 0.127753E+09 |
September | 0.956342E+09 | 0.690150E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382527E+09 | 0.487217E+09 |
October | 0.994195E+09 | 0.748760E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70408648.48 | 0.187839E+10 |
November | 0.984487E+09 | 0.746697E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285308E+10 |
December | 0.959235E+09 | 0.740187E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350985E+10 |
Annual Sum or Average | 0.119305E+11 | 0.866481E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405106E+10 | 0.218707E+11 |
Minimum of Months | 0.901968E+09 | 0.661869E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127753E+09 |
Maximum of Months | 0.107774E+10 | 0.775420E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111033E+10 | 0.461596E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.505576E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385586E+09 |
February | 0.570983E+09 | 0.465983E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 476363.83 | 0.324587E+09 |
March | 0.682256E+09 | 0.501880E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021517.98 | 0.210263E+09 |
April | 0.605404E+09 | 0.429834E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2523194.49 | 0.125148E+09 |
May | 0.655811E+09 | 0.450170E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6185976.40 | 83397932.99 |
June | 0.653980E+09 | 0.441854E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26288039.80 | 42591774.41 |
July | 0.607235E+09 | 0.419226E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28848948.14 | 28301537.64 |
August | 0.682256E+09 | 0.476238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26780514.54 | 20071265.32 |
September | 0.605404E+09 | 0.444656E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7767517.00 | 48105601.99 |
October | 0.629366E+09 | 0.498301E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1658732.68 | 0.156062E+09 |
November | 0.623221E+09 | 0.487915E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219915E+09 |
December | 0.607235E+09 | 0.491638E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364260E+09 |
Annual Sum or Average | 0.755252E+10 | 0.561327E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101551E+09 | 0.200829E+10 |
Minimum of Months | 0.570983E+09 | 0.419226E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20071265.32 |
Maximum of Months | 0.682256E+09 | 0.505576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28848948.14 | 0.385586E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846055E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872547E+09 |
February | 0.901968E+09 | 0.762897E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1820632.08 | 0.743002E+09 |
March | 0.107774E+10 | 0.796776E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2625918.72 | 0.479795E+09 |
April | 0.956342E+09 | 0.675359E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6636757.44 | 0.299869E+09 |
May | 0.103597E+10 | 0.699833E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16285457.15 | 0.197981E+09 |
June | 0.103308E+10 | 0.687181E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63987884.84 | 98742055.61 |
July | 0.959235E+09 | 0.651426E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69914622.14 | 65412713.89 |
August | 0.107774E+10 | 0.744765E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67274050.60 | 41556371.50 |
September | 0.956342E+09 | 0.703252E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20471140.93 | 0.101335E+09 |
October | 0.994195E+09 | 0.808123E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6347148.29 | 0.329493E+09 |
November | 0.984487E+09 | 0.811693E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 435808.47 | 0.469640E+09 |
December | 0.959235E+09 | 0.826313E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802909E+09 |
Annual Sum or Average | 0.119305E+11 | 0.901367E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255799E+09 | 0.450228E+10 |
Minimum of Months | 0.901968E+09 | 0.651426E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41556371.50 |
Maximum of Months | 0.107774E+10 | 0.846055E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69914622.14 | 0.872547E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.508129E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588699E+09 |
February | 0.421807E+09 | 0.460497E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 666685.59 | 0.504855E+09 |
March | 0.502994E+09 | 0.492356E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1862130.05 | 0.329243E+09 |
April | 0.447140E+09 | 0.424791E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3858629.79 | 0.204972E+09 |
May | 0.484071E+09 | 0.447103E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9939329.55 | 0.136242E+09 |
June | 0.482240E+09 | 0.439946E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41691910.73 | 66858111.23 |
July | 0.448971E+09 | 0.415308E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45287827.93 | 44584893.77 |
August | 0.502994E+09 | 0.471842E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43883884.78 | 28217576.69 |
September | 0.447140E+09 | 0.436677E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12914673.74 | 67413678.31 |
October | 0.465148E+09 | 0.484045E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3431737.10 | 0.223792E+09 |
November | 0.460569E+09 | 0.494745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265790.61 | 0.318613E+09 |
December | 0.448971E+09 | 0.493961E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8541.18 | 0.539445E+09 |
Annual Sum or Average | 0.557719E+10 | 0.556940E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163811E+09 | 0.305294E+10 |
Minimum of Months | 0.421807E+09 | 0.415308E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28217576.69 |
Maximum of Months | 0.502994E+09 | 0.508129E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45287827.93 | 0.588699E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.765727E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928170E+09 |
February | 0.901968E+09 | 0.705338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98663.61 | 0.794304E+09 |
March | 0.107774E+10 | 0.777861E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1783011.80 | 0.524390E+09 |
April | 0.956342E+09 | 0.677143E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4617769.44 | 0.312253E+09 |
May | 0.103597E+10 | 0.712140E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14901466.97 | 0.200043E+09 |
June | 0.103308E+10 | 0.700772E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63390827.21 | 97736259.42 |
July | 0.959235E+09 | 0.663635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68621004.65 | 65274023.18 |
August | 0.107774E+10 | 0.749752E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63912243.45 | 43041359.34 |
September | 0.956342E+09 | 0.692213E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16514645.50 | 0.105393E+09 |
October | 0.994195E+09 | 0.750900E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2645133.86 | 0.357956E+09 |
November | 0.984487E+09 | 0.748109E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516929E+09 |
December | 0.959235E+09 | 0.742755E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853802E+09 |
Annual Sum or Average | 0.119305E+11 | 0.868634E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236485E+09 | 0.479929E+10 |
Minimum of Months | 0.901968E+09 | 0.663635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43041359.34 |
Maximum of Months | 0.107774E+10 | 0.777861E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68621004.65 | 0.928170E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.507897E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589972E+09 |
February | 0.570983E+09 | 0.468127E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724815.75 | 0.504969E+09 |
March | 0.682256E+09 | 0.503400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1333354.94 | 0.337585E+09 |
April | 0.605404E+09 | 0.431347E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3567642.88 | 0.207500E+09 |
May | 0.655811E+09 | 0.451973E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9701079.75 | 0.136071E+09 |
June | 0.653980E+09 | 0.442883E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40833835.00 | 67877561.38 |
July | 0.607235E+09 | 0.420627E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44627696.31 | 44697917.83 |
August | 0.682256E+09 | 0.477530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42101311.95 | 30183571.50 |
September | 0.605404E+09 | 0.446712E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12580883.43 | 69074658.85 |
October | 0.629366E+09 | 0.500286E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2928629.53 | 0.225792E+09 |
November | 0.623221E+09 | 0.490384E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6680.70 | 0.320881E+09 |
December | 0.607235E+09 | 0.493477E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540500E+09 |
Annual Sum or Average | 0.755252E+10 | 0.563464E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158406E+09 | 0.307510E+10 |
Minimum of Months | 0.570983E+09 | 0.420627E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30183571.50 |
Maximum of Months | 0.682256E+09 | 0.507897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44627696.31 | 0.589972E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124260E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867320.67 | 0.106802E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1953009.87 | 0.698000E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5758402.84 | 0.421263E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16224032.81 | 0.273170E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71911320.81 | 0.131669E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81755816.42 | 86116893.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74760367.91 | 54336009.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19341858.80 | 0.147278E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4089341.80 | 0.491720E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352686.07 | 0.703890E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118451E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277014E+09 | 0.650258E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54336009.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81755816.42 | 0.124260E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151187E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2239381.83 | 0.129805E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3047208.83 | 0.854055E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8858522.92 | 0.526707E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22225295.83 | 0.345538E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93339000.36 | 0.167882E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104838E+09 | 0.109311E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96499926.11 | 68907633.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27099615.47 | 0.176826E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6688115.08 | 0.583491E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1834419.17 | 0.829656E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140812E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366670E+09 | 0.788041E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68907633.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104838E+09 | 0.151187E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149989E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195703.40 | 0.128812E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315998.95 | 0.852812E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2685392.62 | 0.533789E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11894335.29 | 0.351259E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78110331.41 | 0.161145E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89610999.86 | 0.107519E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85051598.68 | 63756645.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19873312.55 | 0.166480E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2908245.83 | 0.567143E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526082.32 | 0.798793E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135232E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292172E+09 | 0.774302E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63756645.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89610999.86 | 0.149989E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1951.19 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.19 | 26-FEB-13:10 | 2420.67 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.45 | 11-MAR-18:03 | 1316.00 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.39 | 16-APR-12:10 | 756.01 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 07-MAY-12:10 | 607.79 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.28 | 11-JUN-15:00 | 452.94 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.02 | 08-JUL-18:53 | 322.10 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.70 | 06-AUG-14:10 | 211.55 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.41 | 17-SEP-15:00 | 403.82 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.75 | 08-OCT-13:57 | 782.63 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.92 | 19-NOV-15:00 | 1384.88 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 12-DEC-14:00 | 1934.44 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.55 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 412.28 | 2420.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1290.01 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.24 | 26-FEB-15:50 | 1613.77 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.55 | 11-MAR-18:03 | 867.60 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.70 | 08-APR-17:20 | 500.93 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 | 29-MAY-17:50 | 402.92 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.43 | 11-JUN-15:00 | 302.62 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 600.14 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.59 | 08-JUL-19:10 | 214.59 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.56 | 06-AUG-14:08 | 139.85 | 23-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.75 | 17-SEP-15:10 | 266.10 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.34 | 08-OCT-14:00 | 518.15 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.51 | 19-NOV-15:00 | 922.14 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 12-DEC-14:00 | 1283.49 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.85 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 279.56 | 1613.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1972.59 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 28-FEB-15:00 | 2420.67 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 30-MAR-16:00 | 1322.38 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 08-APR-17:20 | 758.00 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.42 | 07-MAY-12:13 | 610.80 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.02 | 11-JUN-15:10 | 453.82 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.03 | 08-JUL-18:53 | 322.18 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.57 | 06-AUG-14:08 | 212.82 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.83 | 17-SEP-14:48 | 405.07 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 | 09-OCT-16:08 | 810.90 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1385.22 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1966.59 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.82 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 388.02 | 2420.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1299.36 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.81 | 26-FEB-13:03 | 1635.10 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 30-MAR-16:00 | 872.04 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 16-APR-12:00 | 497.23 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.83 | 07-MAY-12:10 | 410.39 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.20 | 25-JUN-15:53 | 306.22 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.54 | 08-JUL-19:10 | 211.42 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 | 06-AUG-14:08 | 143.47 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.93 | 17-SEP-12:10 | 264.89 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.98 | 08-OCT-13:53 | 522.91 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 | 19-NOV-15:00 | 922.66 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 12-DEC-14:00 | 1280.70 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.47 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 | 1635.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1087.58 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 | 26-FEB-13:10 | 1319.71 | 12-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.42 | 11-MAR-18:03 | 774.06 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.18 | 08-APR-17:03 | 404.06 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 02-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.74 | 07-MAY-12:00 | 345.16 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.25 | 11-JUN-15:00 | 246.34 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.65 | 08-JUL-18:53 | 181.66 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.75 | 06-AUG-13:53 | 121.65 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.68 | 17-SEP-15:00 | 254.47 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.05 | 08-OCT-14:00 | 493.00 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 19-NOV-15:00 | 745.41 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 12-DEC-14:00 | 1249.05 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 252.25 | 1319.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 722.06 | 07-JAN-18:10 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 | 26-FEB-16:00 | 877.10 | 12-FEB-00:53 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 11-MAR-18:03 | 522.28 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 08-APR-17:03 | 268.26 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 | 29-MAY-17:50 | 235.12 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 | 11-JUN-15:10 | 170.03 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.36 | 08-JUL-18:53 | 119.36 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.24 | 06-AUG-14:10 | 81.00 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.12 | 17-SEP-15:00 | 168.73 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.15 | 09-OCT-16:00 | 335.11 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 19-NOV-15:00 | 500.50 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 833.99 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 150.36 | 877.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 23173.22 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.15 | 28-FEB-15:00 | 25123.36 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.79 | 30-MAR-16:10 | 14358.87 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.00 | 17-APR-16:10 | 15725.42 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.21 | 19-MAY-16:10 | 10416.43 | 11-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7236.71 | 06-JUN-16:05 | 7322.24 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8335.35 | 07-JUL-16:03 | 3467.55 | 28-JUL-16:03 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8046.13 | 01-AUG-16:03 | 3623.21 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.28 | 07-SEP-16:03 | 7893.37 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.52 | 10-OCT-16:05 | 14881.97 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19683.58 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21610.84 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3467.55 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8335.35 | 25123.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 726.40 | 07-JAN-18:10 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 | 26-FEB-13:10 | 897.55 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 30-MAR-16:00 | 525.02 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.44 | 16-APR-11:23 | 267.93 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 | 07-MAY-12:00 | 239.32 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 11-JUN-15:00 | 172.24 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.73 | 08-JUL-18:53 | 121.31 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 06-AUG-13:53 | 84.75 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.90 | 24-SEP-13:00 | 168.74 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 | 08-OCT-14:00 | 337.75 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 505.33 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 829.93 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 897.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1679.88 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 26-FEB-13:10 | 2012.99 | 12-FEB-00:58 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 11-MAR-18:03 | 1213.17 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.34 | 16-APR-12:00 | 671.26 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.98 | 07-MAY-12:00 | 547.50 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.99 | 11-JUN-15:00 | 392.63 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.65 | 08-JUL-18:53 | 282.09 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.64 | 06-AUG-13:53 | 189.23 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.91 | 17-SEP-15:10 | 374.30 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.15 | 08-OCT-14:00 | 726.33 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 19-NOV-15:00 | 1160.21 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1802.25 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.23 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 370.99 | 2012.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1110.01 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 | 26-FEB-15:40 | 1341.98 | 12-FEB-00:58 |
March | 805.43 | 01-MAR-08:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.09 | 11-MAR-18:03 | 798.99 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 | 08-APR-17:20 | 444.57 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 | 29-MAY-18:00 | 362.81 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | 11-JUN-15:00 | 262.13 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 600.14 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.44 | 08-JUL-18:53 | 182.92 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.97 | 06-AUG-14:10 | 124.66 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.18 | 17-SEP-15:10 | 246.84 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.24 | 09-OCT-15:30 | 479.64 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 19-NOV-15:00 | 772.66 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 12-DEC-15:00 | 1195.96 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.66 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 236.44 | 1341.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1697.81 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 28-FEB-15:00 | 2056.77 | 11-FEB-18:05 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 30-MAR-16:00 | 1219.12 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 | 08-APR-17:20 | 673.32 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.12 | 07-MAY-12:00 | 550.11 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.56 | 11-JUN-15:00 | 393.38 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.49 | 08-JUL-18:53 | 282.64 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.25 | 06-AUG-14:08 | 190.32 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 17-SEP-14:48 | 375.50 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.93 | 09-OCT-16:08 | 748.79 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1160.40 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1831.17 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.32 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 346.56 | 2056.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1118.28 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.59 | 26-FEB-13:07 | 1403.51 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 | 30-MAR-16:00 | 803.59 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 16-APR-12:00 | 442.45 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.31 | 07-MAY-12:00 | 369.49 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.01 | 11-JUN-15:00 | 265.47 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.85 | 08-JUL-18:53 | 186.36 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.96 | 06-AUG-13:53 | 128.18 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.39 | 17-SEP-12:10 | 246.47 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.44 | 08-OCT-14:00 | 484.47 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 27-NOV-13:00 | 773.04 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1193.23 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.18 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 228.96 | 1403.51 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2373.42 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 | 26-FEB-15:20 | 2927.94 | 12-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.59 | 11-MAR-16:00 | 1807.57 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.52 | 16-APR-12:00 | 944.52 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.22 | 07-MAY-12:00 | 783.45 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.34 | 11-JUN-15:00 | 539.07 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.01 | 08-JUL-18:53 | 384.59 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.58 | 06-AUG-13:53 | 261.82 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.77 | 17-SEP-14:55 | 545.16 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.63 | 09-OCT-16:00 | 1089.37 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 19-NOV-15:00 | 1612.15 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2742.66 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.34 | 2927.94 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2968.81 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 26-FEB-13:20 | 3628.16 | 12-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 11-MAR-16:00 | 2200.72 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.93 | 16-APR-12:00 | 1193.86 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.73 | 07-MAY-12:20 | 991.46 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.72 | 11-JUN-15:00 | 688.42 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.01 | 08-JUL-18:53 | 481.58 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.32 | 06-AUG-13:53 | 329.67 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.26 | 17-SEP-15:00 | 670.91 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.39 | 08-OCT-14:00 | 1297.20 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.01 | 19-NOV-15:00 | 1965.67 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3294.85 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.72 | 3628.16 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3157.39 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 26-FEB-14:30 | 3760.91 | 11-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | 11-MAR-16:00 | 2006.39 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.42 | 16-APR-11:43 | 1135.39 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.36 | 07-MAY-11:53 | 887.45 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.35 | 11-JUN-15:10 | 675.79 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.18 | 08-JUL-18:53 | 513.19 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.57 | 06-AUG-13:53 | 316.34 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.13 | 17-SEP-15:00 | 577.25 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 | 08-OCT-14:00 | 1190.26 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.20 | 19-NOV-15:00 | 2020.80 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2964.08 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.34 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.18 | 3760.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11918.22 | 31-JAN-17:00 | 6035.01 | 6443.98 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17335.57 | 28-FEB-17:00 | 6035.01 | 6443.98 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20971.78 | 31-MAR-08:00 | 6035.01 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21753.74 | 18-APR-08:00 | 6035.01 | 6443.98 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31597.86 | 30-MAY-05:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33656.26 | 26-JUN-05:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43801.86 | 07-JUL-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43864.50 | 03-AUG-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34556.38 | 06-SEP-05:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23709.64 | 19-OCT-05:13 | 1905.79 | 2147.94 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20894.25 | 03-NOV-07:07 | 18105.02 | 19331.93 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18347.94 | 13-DEC-08:10 | 18105.02 | 19331.93 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11918.22 | 0.00 | 1058.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43864.50 | 18105.02 | 19331.93 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1609.41 | 28-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 |
February | 3626.04 | 26-FEB-14:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 0.00 |
March | 6773.04 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 | 0.00 |
April | 7717.77 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | 0.00 |
May | 8619.72 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.47 | 0.00 |
June | 9290.98 | 27-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 | 0.00 |
July | 10344.56 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.66 | 0.00 |
August | 10449.73 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.76 | 0.00 |
September | 8973.35 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 0.00 |
October | 6790.74 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 | 0.00 |
November | 3216.01 | 05-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
December | 2083.71 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1609.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10449.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 | 145.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1909.19 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1594.24 |
February | 1913.13 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.83 |
March | 2118.07 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.91 | 0.00 |
April | 2715.94 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.04 |
May | 3518.30 | 30-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 | 0.00 |
June | 3971.13 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 0.00 |
July | 4346.49 | 10-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.61 | 0.00 |
August | 4298.08 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 | 0.00 |
September | 3936.08 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.05 | 0.00 |
October | 2623.35 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 0.00 |
November | 1900.23 | 07-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.73 |
December | 2068.86 | 09-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1900.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4346.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.61 | 1594.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1804.71 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 |
February | 2328.49 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.29 |
March | 2638.83 | 17-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.63 |
April | 2950.28 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.48 |
May | 3716.76 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 0.00 |
June | 4063.81 | 19-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 | 0.00 |
July | 4556.71 | 10-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.28 | 0.00 |
August | 4705.40 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.42 | 0.00 |
September | 4515.01 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.46 | 0.00 |
October | 3415.03 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 0.00 |
November | 1933.43 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 |
December | 2121.32 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1804.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4705.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.28 | 314.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8842.11 | 20-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9973.55 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13829.24 | 31-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14839.97 | 18-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16852.43 | 30-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27634.20 | 26-JUN-05:13 | 1905.79 | 2147.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31773.80 | 07-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32354.83 | 03-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19521.90 | 07-SEP-05:13 | 1905.79 | 2147.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15420.92 | 11-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11046.78 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9689.84 | 13-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8842.11 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32354.83 | 6035.01 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9065.42 | 20-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10324.55 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15831.86 | 30-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16909.25 | 17-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19226.43 | 30-MAY-15:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30603.66 | 26-JUN-05:13 | 1905.79 | 2147.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33189.58 | 07-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33811.01 | 14-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19423.09 | 07-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16401.54 | 11-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10261.91 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9740.59 | 13-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9065.42 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33811.01 | 6035.01 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1864.07 | 31-JAN-16:50 | 1272.23 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
February | 2390.65 | 28-FEB-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
March | 4653.93 | 30-MAR-15:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 0.00 |
April | 5034.23 | 19-APR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
May | 6500.25 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.98 | 0.00 |
June | 9103.02 | 25-JUN-14:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 140.73 | 0.00 |
July | 12052.00 | 16-JUL-18:32 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 | 0.00 |
August | 9221.90 | 06-AUG-14:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 345.42 | 0.00 |
September | 6360.72 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 0.00 |
October | 4305.19 | 02-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
November | 2144.14 | 02-NOV-15:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
December | 1998.39 | 13-DEC-15:00 | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1864.07 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12052.00 | 1306.65 | 947.97 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 345.42 | 32.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1542.48 | 31-JAN-15:10 | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 |
February | 2040.58 | 27-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 |
March | 3561.16 | 30-MAR-11:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
April | 5800.54 | 16-APR-11:13 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
May | 11654.93 | 07-MAY-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 |
June | 11700.53 | 04-JUN-08:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.90 |
July | 11735.83 | 09-JUL-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 0.00 |
August | 11718.53 | 13-AUG-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 |
September | 9891.54 | 04-SEP-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
October | 4415.62 | 11-OCT-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
November | 1843.29 | 06-NOV-10:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 |
December | 1642.47 | 12-DEC-15:10 | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1542.48 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11735.83 | 827.22 | 450.21 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 84.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4544.64 | 11-JAN-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 |
February | 12539.06 | 26-FEB-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.26 |
March | 9546.97 | 30-MAR-13:50 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 | 0.00 |
April | 8358.08 | 17-APR-14:00 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
May | 7768.98 | 30-MAY-14:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 0.00 |
June | 13322.04 | 25-JUN-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 139.12 | 0.00 |
July | 13848.41 | 16-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 125.88 | 0.00 |
August | 14391.36 | 06-AUG-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 221.62 | 0.00 |
September | 14556.01 | 24-SEP-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 39.71 | 0.00 |
October | 14587.39 | 09-OCT-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
November | 13847.74 | 11-NOV-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.96 |
December | 6066.58 | 08-DEC-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4544.64 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14587.39 | 1306.65 | 647.98 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 221.62 | 240.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1809.09 | 20-JAN-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 |
February | 4128.66 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
March | 6344.23 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
April | 11456.27 | 09-APR-17:23 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 |
May | 11198.43 | 06-MAY-17:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 0.00 |
June | 13357.66 | 04-JUN-17:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 0.00 |
July | 13270.41 | 04-JUL-18:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 | 0.00 |
August | 13364.95 | 13-AUG-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 73.01 | 0.00 |
September | 11317.25 | 04-SEP-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 0.00 |
October | 8834.74 | 09-OCT-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 0.00 |
November | 3736.84 | 06-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
December | 1950.66 | 11-DEC-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1809.09 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13364.95 | 805.38 | 410.20 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 73.01 | 59.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1777.42 | 31-JAN-15:10 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
February | 2035.14 | 28-FEB-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
March | 2612.25 | 30-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
April | 2969.20 | 19-APR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
May | 4493.47 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
June | 5391.50 | 30-JUN-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 0.00 |
July | 5898.49 | 14-JUL-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 0.00 |
August | 5947.05 | 09-AUG-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 0.00 |
September | 5634.00 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 | 0.00 |
October | 3892.38 | 02-OCT-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
November | 2163.53 | 05-NOV-13:13 | 200.88 | 107.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
December | 1999.40 | 13-DEC-13:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1777.42 | 200.88 | 107.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5947.05 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 17.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1339.89 | 31-JAN-15:00 | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
February | 1772.41 | 27-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 |
March | 2508.24 | 14-MAR-11:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
April | 4222.81 | 17-APR-10:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
May | 5249.15 | 30-MAY-10:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
June | 7882.86 | 04-JUN-08:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 |
July | 8803.46 | 09-JUL-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 | 0.00 |
August | 10283.74 | 27-AUG-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
September | 6287.84 | 08-SEP-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
October | 4356.12 | 11-OCT-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
November | 2292.60 | 06-NOV-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 |
December | 1473.15 | 13-DEC-12:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1339.89 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10283.74 | 827.22 | 450.21 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 | 45.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2510.57 | 28-JAN-14:50 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
February | 6225.57 | 26-FEB-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 |
March | 7645.95 | 30-MAR-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.79 | 0.00 |
April | 7757.54 | 17-APR-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.00 | 0.00 |
May | 8866.47 | 30-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4181.57 | 0.00 |
June | 9961.24 | 06-JUN-16:20 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6919.45 | 0.00 |
July | 10405.73 | 07-JUL-16:10 | 1205.27 | 1079.96 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7722.25 | 0.00 |
August | 11505.27 | 06-AUG-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 183.20 | 0.00 |
September | 10280.20 | 07-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4593.34 | 0.00 |
October | 12049.54 | 09-OCT-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
November | 10661.89 | 12-NOV-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 |
December | 5665.57 | 12-DEC-14:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2510.57 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12049.54 | 1272.23 | 1079.96 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7722.25 | 131.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1442.75 | 20-JAN-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
February | 2946.64 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 4212.46 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
April | 4785.27 | 17-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 0.00 |
May | 6464.04 | 29-MAY-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 0.00 |
June | 10600.87 | 04-JUN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 0.00 |
July | 10518.92 | 04-JUL-18:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 0.00 |
August | 10539.63 | 13-AUG-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 0.00 |
September | 8442.90 | 04-SEP-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
October | 5648.36 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
November | 3694.82 | 06-NOV-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 |
December | 1617.65 | 11-DEC-16:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1442.75 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10600.87 | 805.38 | 410.20 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 26.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1820.88 | 31-JAN-17:00 | 1272.23 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
February | 2388.96 | 28-FEB-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
March | 4121.30 | 30-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 0.00 |
April | 4555.41 | 18-APR-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
May | 5844.18 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 0.00 |
June | 6235.85 | 30-JUN-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 112.37 | 0.00 |
July | 8988.34 | 16-JUL-13:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 0.00 |
August | 7467.56 | 14-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 |
September | 5782.94 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 | 0.00 |
October | 3995.60 | 02-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
November | 2099.50 | 03-NOV-15:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 |
December | 1979.09 | 13-DEC-13:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1820.88 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8988.34 | 1306.65 | 947.97 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 112.37 | 34.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1498.83 | 31-JAN-15:30 | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
February | 2557.14 | 27-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 |
March | 3620.30 | 14-MAR-11:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
April | 6660.99 | 16-APR-10:53 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
May | 11270.54 | 07-MAY-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 |
June | 11215.56 | 11-JUN-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
July | 11789.36 | 23-JUL-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.06 |
August | 11854.91 | 27-AUG-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
September | 10564.40 | 04-SEP-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 |
October | 4603.99 | 11-OCT-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 |
November | 2455.21 | 06-NOV-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 |
December | 1618.52 | 13-DEC-12:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1498.83 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | |
Maximum of Months | 11854.91 | 805.43 | 450.21 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4638.73 | 11-JAN-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 |
February | 9731.83 | 26-FEB-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.67 |
March | 8942.13 | 30-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
April | 7664.00 | 17-APR-13:50 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 0.00 |
May | 7210.26 | 29-MAY-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 | 0.00 |
June | 8533.07 | 25-JUN-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 117.89 | 0.00 |
July | 10983.63 | 16-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 107.27 | 0.00 |
August | 12671.23 | 06-AUG-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 191.95 | 0.00 |
September | 9569.12 | 17-SEP-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 60.25 | 0.00 |
October | 12986.45 | 09-OCT-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 12760.93 | 11-NOV-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 |
December | 6575.07 | 08-DEC-14:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4638.73 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12986.45 | 1306.65 | 647.98 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 191.95 | 212.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1683.39 | 11-JAN-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 |
February | 3989.90 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
March | 5934.31 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 | 0.00 |
April | 10500.64 | 09-APR-17:12 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 |
May | 12015.19 | 29-MAY-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 | 0.00 |
June | 11771.04 | 25-JUN-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 | 0.00 |
July | 12560.83 | 23-JUL-17:52 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 0.00 |
August | 12341.33 | 13-AUG-16:51 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 59.16 | 0.00 |
September | 10593.14 | 04-SEP-16:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 | 0.00 |
October | 8302.57 | 09-OCT-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 |
November | 3864.29 | 06-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 |
December | 1832.38 | 11-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1683.39 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12560.83 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 | 48.44 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.150043E+12 | 240785.62 | 02-JAN-07:10 | 0.227591E+11 | 51877.69 | 27-JAN-07:40 |
February | 0.120294E+12 | 234881.51 | 13-FEB-07:10 | 0.155889E+11 | 59583.43 | 03-FEB-07:40 |
March | 0.115683E+12 | 113100.86 | 23-MAR-06:10 | 0.116057E+11 | 17647.76 | 18-MAR-07:19 |
April | 0.111595E+12 | 117695.15 | 17-APR-15:39 | 0.104625E+11 | 19659.37 | 06-APR-06:30 |
May | 0.132624E+12 | 133463.67 | 30-MAY-15:09 | 0.104861E+11 | 9733.68 | 01-MAY-11:09 |
June | 0.152594E+12 | 144724.63 | 27-JUN-15:50 | 0.990213E+10 | 9597.38 | 01-JUN-11:20 |
July | 0.159229E+12 | 158722.02 | 07-JUL-15:00 | 0.964240E+10 | 9494.49 | 03-JUL-11:30 |
August | 0.173989E+12 | 156582.99 | 02-AUG-15:00 | 0.100298E+11 | 9492.90 | 31-AUG-11:39 |
September | 0.135370E+12 | 148973.73 | 07-SEP-15:50 | 0.960877E+10 | 9574.99 | 29-SEP-11:20 |
October | 0.116873E+12 | 126862.07 | 10-OCT-15:00 | 0.103109E+11 | 17411.04 | 26-OCT-06:30 |
November | 0.110046E+12 | 140007.56 | 22-NOV-07:10 | 0.111579E+11 | 37416.94 | 22-NOV-07:30 |
December | 0.122954E+12 | 189023.96 | 18-DEC-07:10 | 0.131609E+11 | 47669.55 | 18-DEC-07:00 |
Annual Sum or Average | 0.160129E+13 | 0.144715E+12 | ||||
Minimum of Months | 0.110046E+12 | 113100.86 | 0.960877E+10 | 9492.90 | ||
Maximum of Months | 0.173989E+12 | 240785.62 | 0.227591E+11 | 59583.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.258642E+11 | 0.544208E+10 | 0.593559E+11 | 0.989278E+09 | 0.402316E+10 | 12379742.02 | 0.527190E+11 | 0.163724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235047E+11 | 0.447543E+10 | 0.537310E+11 | 0.895470E+09 | 0.368163E+10 | 11196021.66 | 0.300455E+11 | 0.394882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271449E+11 | 0.443078E+10 | 0.617796E+11 | 0.103591E+10 | 0.434689E+10 | 12675672.10 | 0.569035E+10 | 0.112419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239402E+11 | 0.378945E+10 | 0.572952E+11 | 0.952096E+09 | 0.459523E+10 | 11960507.72 | 0.163817E+10 | 0.193723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256470E+11 | 0.345949E+10 | 0.605677E+11 | 0.101189E+10 | 0.605227E+10 | 12527707.06 | 0.205704E+09 | 0.356669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.254527E+11 | 0.317507E+10 | 0.594895E+11 | 0.996183E+09 | 0.828881E+10 | 12231776.97 | 27530985.32 | 0.551522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238434E+11 | 0.336986E+10 | 0.583622E+11 | 0.967496E+09 | 0.895859E+10 | 12256437.81 | 0.00 | 0.637151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267688E+11 | 0.373343E+10 | 0.617796E+11 | 0.103560E+10 | 0.100265E+11 | 12675672.10 | 0.00 | 0.706326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241495E+11 | 0.405491E+10 | 0.572729E+11 | 0.952019E+09 | 0.689423E+10 | 11960507.72 | 36243044.33 | 0.419986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256123E+11 | 0.470282E+10 | 0.593671E+11 | 0.989256E+09 | 0.492972E+10 | 12379742.02 | 0.287583E+10 | 0.183837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254175E+11 | 0.511872E+10 | 0.580818E+11 | 0.970844E+09 | 0.392061E+10 | 12059151.09 | 0.862339E+10 | 0.790101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250509E+11 | 0.559902E+10 | 0.583511E+11 | 0.968356E+09 | 0.379340E+10 | 12256437.81 | 0.262035E+11 | 0.297583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302396E+12 | 0.513511E+11 | 0.705434E+12 | 0.117644E+11 | 0.695110E+11 | 0.146559E+09 | 0.128065E+12 | 0.332626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235047E+11 | 0.317507E+10 | 0.537310E+11 | 0.895470E+09 | 0.368163E+10 | 11196021.66 | 0.00 | 0.163724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271449E+11 | 0.559902E+10 | 0.617796E+11 | 0.103591E+10 | 0.100265E+11 | 12675672.10 | 0.527190E+11 | 0.706326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.115012E+11 | 0.00 | 0.112579E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.540204E+10 | 0.00 | 0.101869E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172917E+09 | 0.00 | 0.114328E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 94864472.00 | 0.00 | 0.103676E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.104861E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.990213E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.964240E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.100298E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.960877E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 49572724.80 | 0.00 | 0.102613E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.765677E+09 | 0.00 | 0.103922E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227419E+10 | 0.00 | 0.108868E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202604E+11 | 0.00 | 0.124455E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.960877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.115012E+11 | 0.00 | 0.114328E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 03-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 850.39 | 03-JAN-08:20 | 5898.74 | 09-JAN-07:10 | 6.85 | 03-JAN-18:10 | 197096.46 | 02-JAN-07:10 |
February | 32642.50 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 850.39 | 06-FEB-08:20 | 5813.73 | 13-FEB-07:10 | 6.85 | 01-FEB-06:10 | 191150.88 | 13-FEB-07:10 |
March | 32642.50 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 850.39 | 21-MAR-07:19 | 7324.14 | 30-MAR-15:00 | 6.85 | 06-MAR-08:09 | 71959.84 | 23-MAR-06:10 |
April | 31270.76 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 848.55 | 03-APR-07:19 | 7907.71 | 17-APR-15:00 | 6.85 | 01-APR-05:10 | 61794.37 | 07-APR-06:10 |
May | 28326.84 | 24-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 844.60 | 24-MAY-07:19 | 10356.63 | 30-MAY-15:09 | 6.85 | 01-MAY-05:10 | 18020.44 | 11-MAY-06:10 |
June | 27609.75 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 843.64 | 23-JUN-07:19 | 11332.48 | 27-JUN-15:30 | 6.85 | 01-JUN-05:10 | 5136.80 | 08-JUN-06:19 |
July | 28960.31 | 27-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 845.45 | 27-JUL-07:19 | 13250.82 | 07-JUL-15:00 | 6.85 | 09-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 30940.97 | 24-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 848.10 | 24-AUG-07:19 | 13909.72 | 02-AUG-15:00 | 6.85 | 13-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 32312.69 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 849.95 | 29-SEP-07:19 | 13098.57 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 6434.14 | 29-SEP-06:10 |
October | 32642.50 | 19-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 850.39 | 19-OCT-07:19 | 9327.38 | 11-OCT-15:30 | 6.85 | 26-OCT-05:19 | 67814.62 | 26-OCT-06:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 850.39 | 01-NOV-07:19 | 4664.61 | 06-NOV-15:30 | 6.85 | 13-NOV-12:09 | 98589.24 | 22-NOV-07:10 |
December | 32642.50 | 06-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 850.39 | 06-DEC-08:20 | 4328.91 | 26-DEC-06:19 | 6.85 | 02-DEC-06:10 | 146825.49 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 27609.75 | 5686.19 | 45864.70 | 843.64 | 4328.91 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 45864.70 | 850.39 | 13909.72 | 6.85 | 197096.46 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 16410.07 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20451.70 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37365.11 | 30-MAR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41196.54 | 17-APR-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54808.24 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64885.98 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76871.17 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74646.82 | 01-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67503.64 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49008.83 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22402.94 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21888.21 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16410.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76871.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 240785.62 | 02-JAN-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 5772.27 | 6.85 | 197096.46 | 0.00 | 0.00 |
February | 234881.51 | 13-FEB-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 5813.73 | 6.85 | 191150.88 | 0.00 | 0.00 |
March | 113100.86 | 23-MAR-06:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 3224.13 | 6.85 | 71959.84 | 0.00 | 0.00 |
April | 117695.15 | 17-APR-15:39 | 25681.07 | 42072.41 | 0.00 | 839.70 | 7898.58 | 6.85 | 0.00 | 41196.54 | 0.00 |
May | 133463.67 | 30-MAY-15:09 | 25681.07 | 42072.41 | 0.00 | 839.70 | 10356.63 | 6.85 | 0.00 | 54507.01 | 0.00 |
June | 144724.63 | 27-JUN-15:50 | 25681.07 | 42072.41 | 0.00 | 839.70 | 11271.15 | 6.85 | 0.00 | 64853.44 | 0.00 |
July | 158722.02 | 07-JUL-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13250.82 | 6.85 | 0.00 | 76871.17 | 0.00 |
August | 156582.99 | 02-AUG-15:00 | 25681.07 | 42072.41 | 0.00 | 839.70 | 13909.72 | 6.85 | 0.00 | 74073.24 | 0.00 |
September | 148973.73 | 07-SEP-15:50 | 25681.07 | 42072.41 | 0.00 | 839.70 | 12957.83 | 6.85 | 0.00 | 67415.87 | 0.00 |
October | 126862.07 | 10-OCT-15:00 | 25990.55 | 42072.41 | 0.00 | 839.80 | 8943.62 | 6.85 | 0.00 | 49008.83 | 0.00 |
November | 140007.56 | 22-NOV-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 3501.43 | 6.85 | 98589.24 | 0.00 | 0.00 |
December | 189023.96 | 18-DEC-07:10 | 10880.98 | 21098.80 | 5686.19 | 244.07 | 4281.58 | 6.85 | 146825.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 113100.86 | 10880.98 | 21098.80 | 0.00 | 244.07 | 3224.13 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 240785.62 | 25990.55 | 42072.41 | 5686.19 | 839.80 | 13909.72 | 6.85 | 197096.46 | 76871.17 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 43432.08 | 14-JAN-07:19 | 0.00 | 10016.35 | 26-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 50817.95 | 03-FEB-07:30 | 0.00 | 10018.44 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 9525.44 | 18-MAR-06:00 | 0.00 | 9978.56 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 11233.90 | 06-APR-06:19 | 0.00 | 9871.78 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9733.68 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9597.38 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9494.49 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9492.90 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9574.99 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 8737.15 | 26-OCT-06:19 | 0.00 | 9714.67 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 28814.23 | 22-NOV-07:19 | 0.00 | 9852.28 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 39454.48 | 18-DEC-07:00 | 0.00 | 9958.77 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9492.90 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 50817.95 | 0.00 | 10018.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.29 | 0.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.29 | 0.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.29 | 0.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.40 | 0.67 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
February | 0.67 | 18.10 | 0.33 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 18.63 | 0.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Annual Sum or Average | 2.17 | 18.38 | 1.50 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.63 | 0.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 16.28 | 6.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
February | 11.17 | 16.03 | 5.00 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.52 | 1.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.33 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
December | 5.17 | 17.38 | 2.33 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
Annual Sum or Average | 31.33 | 16.38 | 13.33 | 16.79 | 4.33 | 17.74 | 2.67 | 18.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.67 | 17.38 | 6.00 | 18.00 | 3.00 | 27.52 | 1.83 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 15.54 | 2.33 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 7.00 | 15.04 | 1.33 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.50 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.77 | 4.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.75 | 9.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.73 | 6.33 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
December | 2.83 | 15.97 | 0.50 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
Annual Sum or Average | 21.17 | 15.46 | 4.17 | 15.60 | 23.50 | 21.43 | 22.50 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 16.96 | 2.33 | 16.96 | 9.67 | 27.77 | 9.00 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 15.98 | 2.50 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
February | 5.67 | 15.63 | 1.67 | 15.90 | 0.50 | 16.63 | 0.50 | 17.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.51 | 1.17 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.55 | 3.67 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.66 | 5.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.60 | 1.67 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.62 | 3.00 | 27.62 |
November | 0.33 | 17.10 | 0.00 | 17.10 | 0.67 | 24.05 | 0.67 | 25.44 |
December | 1.50 | 17.41 | 0.50 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
Annual Sum or Average | 16.17 | 16.01 | 4.67 | 16.29 | 17.83 | 21.50 | 16.33 | 23.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 17.41 | 2.50 | 17.83 | 5.50 | 27.66 | 5.00 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.83 | 15.56 | 2.83 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 7.50 | 15.03 | 2.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 0.67 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.84 | 1.50 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.00 | 3.00 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.18 | 4.33 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.10 | 3.50 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 1.50 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
November | 0.33 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
December | 2.17 | 16.29 | 0.33 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
Annual Sum or Average | 20.83 | 15.46 | 5.67 | 15.55 | 26.17 | 21.74 | 14.83 | 23.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.83 | 16.94 | 2.83 | 16.94 | 8.83 | 28.18 | 4.33 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.11 | 1.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
February | 1.33 | 19.43 | 1.17 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.43 | 0.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 3.33 | 19.27 | 3.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.43 | 1.50 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.89 | 0.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
February | 0.17 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.55 | 1.50 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.58 | 3.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 3.33 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 17.48 | 0.17 | 17.85 | 9.33 | 26.90 | 9.33 | 27.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.89 | 0.17 | 18.25 | 3.67 | 27.58 | 3.67 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.67 | 18.12 | 46.50 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 30.50 | 18.35 | 30.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
March | 11.50 | 19.50 | 11.50 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
April | 4.67 | 18.83 | 4.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.72 | 1.00 | 24.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 24.82 | 11.33 | 24.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 25.02 | 18.17 | 25.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.17 | 5.50 | 25.17 |
October | 2.17 | 19.49 | 2.17 | 19.49 | 4.83 | 23.32 | 4.83 | 24.50 |
November | 12.00 | 19.50 | 12.00 | 19.50 | 1.33 | 19.92 | 1.33 | 20.29 |
December | 20.33 | 18.40 | 20.33 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
Annual Sum or Average | 127.83 | 18.52 | 127.50 | 18.53 | 42.17 | 19.48 | 42.17 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.67 | 19.50 | 46.50 | 19.50 | 18.17 | 25.17 | 18.17 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.87 | 0.17 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
February | 0.17 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.00 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 1.33 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.82 | 2.83 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.78 | 2.50 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 0.83 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 17.49 | 0.17 | 17.85 | 13.83 | 27.29 | 7.67 | 27.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.87 | 0.17 | 18.22 | 5.50 | 27.82 | 2.83 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.51 | 1.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 3.33 | 16.65 | 1.83 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.75 | 0.17 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
Annual Sum or Average | 6.33 | 17.47 | 3.50 | 17.79 | 0.33 | 18.11 | 0.33 | 18.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 18.51 | 1.83 | 18.87 | 0.33 | 27.27 | 0.33 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 17.74 | 0.50 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
February | 2.17 | 15.54 | 0.67 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.62 | 1.00 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.83 | 3.17 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.71 | 6.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 4.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.58 | 1.00 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.84 | 0.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
Annual Sum or Average | 4.17 | 16.61 | 1.33 | 16.82 | 16.33 | 24.98 | 16.33 | 26.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 17.84 | 0.67 | 18.19 | 6.50 | 27.83 | 6.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.95 | 0.33 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
February | 1.17 | 15.92 | 0.67 | 15.92 | 0.50 | 18.38 | 0.50 | 19.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.50 | 4.33 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.70 | 0.83 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.62 | 3.33 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.52 | 2.00 | 27.52 |
December | 0.17 | 19.23 | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 2.00 | 16.87 | 1.17 | 17.02 | 13.00 | 25.46 | 13.00 | 26.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.23 | 0.67 | 19.23 | 4.33 | 27.70 | 4.33 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 17.51 | 0.33 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
February | 2.50 | 15.64 | 1.00 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.50 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.76 | 1.17 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.91 | 2.17 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.03 | 3.67 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.95 | 2.83 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.86 | 0.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 4.50 | 16.51 | 1.50 | 16.56 | 21.33 | 25.41 | 11.83 | 26.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.86 | 1.00 | 18.20 | 7.33 | 28.03 | 3.67 | 28.03 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.41 | 28.00 | 22.30 | 28.00 | 22.20 |
February | 430.00 | 23.04 | 7.00 | 23.01 | 5.83 | 22.98 |
March | 289.33 | 23.64 | 59.50 | 23.78 | 0.00 | 23.78 |
April | 103.00 | 23.65 | 167.83 | 24.26 | 0.00 | 24.26 |
May | 10.83 | 23.78 | 360.67 | 24.50 | 0.00 | 24.50 |
June | 1.17 | 23.78 | 428.00 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 489.67 | 24.40 | 0.00 | 24.40 |
August | 0.00 | 0.00 | 513.33 | 24.34 | 0.00 | 24.34 |
September | 0.83 | 23.36 | 430.17 | 24.44 | 0.00 | 24.44 |
October | 67.17 | 23.49 | 196.33 | 24.34 | 0.00 | 24.34 |
November | 287.17 | 23.70 | 42.17 | 23.83 | 0.00 | 23.83 |
December | 443.83 | 23.22 | 6.00 | 23.24 | 0.00 | 23.24 |
Annual Sum or Average | 2135.33 | 23.15 | 2728.67 | 23.85 | 33.83 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 6.00 | 22.30 | 0.00 | 22.20 |
Maximum of Months | 502.00 | 23.78 | 513.33 | 24.50 | 28.00 | 24.50 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.04 | 203.83 | 20.87 | 203.83 | 20.78 |
February | 453.33 | 21.68 | 85.00 | 21.49 | 85.00 | 21.36 |
March | 450.17 | 22.78 | 19.00 | 22.84 | 0.00 | 22.84 |
April | 291.33 | 23.17 | 74.17 | 23.40 | 0.00 | 23.40 |
May | 98.00 | 23.26 | 240.17 | 24.00 | 0.00 | 24.00 |
June | 38.50 | 23.43 | 363.83 | 24.18 | 0.00 | 24.18 |
July | 11.50 | 23.06 | 441.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 470.33 | 24.25 | 0.00 | 24.25 |
September | 61.83 | 23.12 | 307.50 | 24.13 | 0.00 | 24.13 |
October | 300.00 | 22.92 | 80.17 | 23.18 | 0.00 | 23.18 |
November | 479.83 | 22.60 | 0.33 | 22.60 | 0.33 | 22.60 |
December | 496.33 | 21.62 | 52.17 | 21.54 | 52.17 | 21.48 |
Annual Sum or Average | 3182.83 | 22.22 | 2337.50 | 22.86 | 341.33 | 22.72 |
Minimum of Months | 0.00 | 0.00 | 0.33 | 20.87 | 0.00 | 20.78 |
Maximum of Months | 502.00 | 23.43 | 470.33 | 24.25 | 203.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.55 | 326.50 | 20.40 | 326.50 | 20.34 |
February | 453.67 | 21.15 | 153.50 | 20.93 | 153.50 | 20.80 |
March | 470.00 | 22.23 | 39.50 | 22.21 | 23.67 | 22.14 |
April | 332.17 | 22.81 | 58.00 | 23.00 | 1.50 | 22.99 |
May | 145.50 | 23.11 | 212.00 | 23.78 | 0.00 | 23.78 |
June | 46.50 | 23.28 | 352.83 | 24.15 | 0.00 | 24.15 |
July | 16.83 | 22.84 | 430.33 | 24.24 | 0.00 | 24.24 |
August | 3.00 | 23.37 | 460.83 | 24.25 | 0.00 | 24.25 |
September | 120.33 | 22.95 | 250.67 | 23.84 | 0.00 | 23.84 |
October | 389.17 | 22.42 | 54.83 | 22.61 | 2.00 | 22.60 |
November | 488.17 | 21.77 | 56.00 | 21.65 | 56.00 | 21.55 |
December | 497.00 | 20.95 | 201.67 | 20.76 | 201.67 | 20.65 |
Annual Sum or Average | 3464.33 | 21.76 | 2596.67 | 22.32 | 764.83 | 22.09 |
Minimum of Months | 3.00 | 20.55 | 39.50 | 20.40 | 0.00 | 20.34 |
Maximum of Months | 502.00 | 23.37 | 460.83 | 24.25 | 326.50 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 420.00 | 19.94 | 420.00 | 19.90 |
February | 451.50 | 20.63 | 262.33 | 20.41 | 262.33 | 20.31 |
March | 468.50 | 21.57 | 115.83 | 21.46 | 93.33 | 21.30 |
April | 333.00 | 22.30 | 105.83 | 22.55 | 31.33 | 22.47 |
May | 159.17 | 22.87 | 262.17 | 23.72 | 8.67 | 23.72 |
June | 60.17 | 23.87 | 398.17 | 24.26 | 21.67 | 24.31 |
July | 55.50 | 24.70 | 460.17 | 24.46 | 40.50 | 24.53 |
August | 42.50 | 24.98 | 496.67 | 24.38 | 37.83 | 24.44 |
September | 177.00 | 23.16 | 274.00 | 23.86 | 28.33 | 23.93 |
October | 411.67 | 21.83 | 92.33 | 22.03 | 39.67 | 21.99 |
November | 487.67 | 21.11 | 175.83 | 20.89 | 175.83 | 20.76 |
December | 497.00 | 20.30 | 345.00 | 20.13 | 345.00 | 20.06 |
Annual Sum or Average | 3645.67 | 21.37 | 3408.33 | 21.97 | 1504.50 | 21.71 |
Minimum of Months | 42.50 | 20.04 | 92.33 | 19.94 | 8.67 | 19.90 |
Maximum of Months | 502.00 | 24.98 | 496.67 | 24.46 | 420.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 401.00 | 20.06 | 401.00 | 20.02 |
February | 449.83 | 20.89 | 227.50 | 20.61 | 227.50 | 20.46 |
March | 436.17 | 21.85 | 90.83 | 21.81 | 57.67 | 21.66 |
April | 272.17 | 22.41 | 155.50 | 22.97 | 23.33 | 22.92 |
May | 139.00 | 23.04 | 310.00 | 23.98 | 17.83 | 24.04 |
June | 62.67 | 24.49 | 421.17 | 24.40 | 31.67 | 24.51 |
July | 88.33 | 25.28 | 453.67 | 24.65 | 66.17 | 24.81 |
August | 63.50 | 25.56 | 483.50 | 24.54 | 55.00 | 24.67 |
September | 167.50 | 23.08 | 307.67 | 23.92 | 29.67 | 24.01 |
October | 340.00 | 21.82 | 129.67 | 22.26 | 37.00 | 22.20 |
November | 483.67 | 21.31 | 122.67 | 21.10 | 122.67 | 20.96 |
December | 497.00 | 20.40 | 296.17 | 20.19 | 296.17 | 20.10 |
Annual Sum or Average | 3501.83 | 21.55 | 3399.33 | 22.22 | 1365.67 | 22.01 |
Minimum of Months | 62.67 | 20.16 | 90.83 | 20.06 | 17.83 | 20.02 |
Maximum of Months | 502.00 | 25.56 | 483.50 | 24.65 | 401.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.83 | 20.81 | 290.33 | 20.47 | 287.67 | 20.30 |
February | 402.83 | 21.13 | 201.67 | 20.96 | 185.50 | 20.77 |
March | 357.33 | 21.84 | 132.50 | 22.04 | 61.83 | 21.84 |
April | 266.67 | 22.38 | 150.83 | 22.93 | 28.00 | 22.87 |
May | 157.83 | 22.84 | 273.17 | 23.76 | 9.50 | 23.77 |
June | 76.67 | 23.84 | 387.50 | 24.26 | 25.50 | 24.32 |
July | 67.67 | 24.95 | 452.50 | 24.52 | 50.00 | 24.62 |
August | 56.83 | 25.49 | 494.67 | 24.49 | 51.83 | 24.60 |
September | 151.17 | 23.41 | 311.83 | 24.09 | 36.67 | 24.21 |
October | 287.50 | 22.05 | 183.33 | 22.85 | 37.67 | 22.86 |
November | 383.83 | 21.60 | 136.17 | 21.67 | 91.50 | 21.46 |
December | 454.83 | 20.99 | 223.83 | 20.69 | 213.00 | 20.48 |
Annual Sum or Average | 3152.00 | 21.81 | 3238.33 | 22.53 | 1078.67 | 22.31 |
Minimum of Months | 56.83 | 20.81 | 132.50 | 20.47 | 9.50 | 20.30 |
Maximum of Months | 488.83 | 25.49 | 494.67 | 24.52 | 287.67 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.19 | 377.67 | 20.04 | 377.67 | 19.98 |
February | 437.67 | 20.70 | 247.00 | 20.52 | 242.33 | 20.40 |
March | 420.33 | 21.50 | 128.17 | 21.58 | 80.83 | 21.41 |
April | 305.83 | 22.14 | 144.67 | 22.68 | 30.50 | 22.64 |
May | 187.83 | 22.72 | 265.17 | 23.65 | 16.00 | 23.70 |
June | 97.17 | 23.62 | 380.67 | 24.22 | 28.67 | 24.31 |
July | 84.17 | 24.43 | 424.17 | 24.45 | 47.83 | 24.56 |
August | 59.17 | 24.99 | 458.83 | 24.44 | 43.83 | 24.54 |
September | 195.67 | 22.91 | 261.33 | 23.76 | 33.17 | 23.87 |
October | 379.17 | 21.72 | 119.83 | 22.14 | 36.50 | 22.10 |
November | 459.00 | 21.11 | 156.83 | 20.95 | 148.67 | 20.80 |
December | 497.00 | 20.45 | 306.17 | 20.23 | 306.17 | 20.13 |
Annual Sum or Average | 3625.00 | 21.43 | 3270.50 | 22.07 | 1392.17 | 21.85 |
Minimum of Months | 59.17 | 20.19 | 119.83 | 20.04 | 16.00 | 19.98 |
Maximum of Months | 502.00 | 24.99 | 458.83 | 24.45 | 377.67 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 410.17 | 20.27 | 410.17 | 20.24 |
February | 454.00 | 20.77 | 239.33 | 20.60 | 239.33 | 20.51 |
March | 504.67 | 21.56 | 75.67 | 21.44 | 72.33 | 21.34 |
April | 435.50 | 22.24 | 35.33 | 22.25 | 22.00 | 22.21 |
May | 252.00 | 23.04 | 167.33 | 23.51 | 11.50 | 23.55 |
June | 51.17 | 23.79 | 377.17 | 24.19 | 11.00 | 24.23 |
July | 30.83 | 24.58 | 469.00 | 24.36 | 21.67 | 24.39 |
August | 18.33 | 25.38 | 504.83 | 24.33 | 18.33 | 24.37 |
September | 81.33 | 23.69 | 314.50 | 24.19 | 19.33 | 24.25 |
October | 382.50 | 22.57 | 80.00 | 22.83 | 12.50 | 22.86 |
November | 479.00 | 21.83 | 48.00 | 21.73 | 46.67 | 21.63 |
December | 497.00 | 20.83 | 253.50 | 20.69 | 253.50 | 20.62 |
Annual Sum or Average | 3688.33 | 21.64 | 2974.83 | 22.20 | 1138.33 | 21.98 |
Minimum of Months | 18.33 | 20.35 | 35.33 | 20.27 | 11.00 | 20.24 |
Maximum of Months | 504.67 | 25.38 | 504.83 | 24.36 | 410.17 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 368.17 | 20.42 | 368.17 | 20.38 |
February | 451.17 | 21.15 | 192.33 | 20.91 | 192.33 | 20.78 |
March | 476.33 | 22.10 | 39.50 | 22.04 | 28.33 | 21.95 |
April | 315.67 | 22.54 | 85.50 | 22.88 | 10.33 | 22.87 |
May | 161.17 | 23.17 | 274.00 | 23.99 | 13.33 | 24.05 |
June | 31.67 | 24.64 | 432.67 | 24.39 | 15.67 | 24.44 |
July | 51.17 | 25.35 | 472.17 | 24.59 | 38.00 | 24.70 |
August | 31.67 | 26.19 | 509.33 | 24.52 | 31.67 | 24.61 |
September | 68.17 | 23.94 | 375.17 | 24.35 | 22.67 | 24.43 |
October | 273.50 | 22.61 | 146.50 | 23.21 | 12.83 | 23.23 |
November | 451.50 | 22.20 | 31.67 | 22.17 | 22.00 | 22.10 |
December | 497.00 | 21.05 | 182.83 | 20.87 | 182.83 | 20.77 |
Annual Sum or Average | 3311.00 | 21.87 | 3109.83 | 22.60 | 938.17 | 22.42 |
Minimum of Months | 31.67 | 20.52 | 31.67 | 20.42 | 10.33 | 20.38 |
Maximum of Months | 502.00 | 26.19 | 509.33 | 24.59 | 368.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.70 | 269.00 | 20.43 | 265.17 | 20.27 |
February | 414.00 | 21.06 | 164.50 | 20.88 | 152.67 | 20.70 |
March | 419.83 | 21.94 | 75.00 | 22.05 | 33.17 | 21.92 |
April | 353.67 | 22.31 | 83.17 | 22.58 | 17.00 | 22.54 |
May | 238.00 | 22.82 | 198.50 | 23.48 | 19.83 | 23.51 |
June | 111.33 | 23.55 | 387.67 | 24.08 | 57.67 | 24.08 |
July | 95.33 | 24.04 | 470.33 | 24.31 | 84.00 | 24.29 |
August | 101.17 | 24.42 | 508.67 | 24.41 | 100.17 | 24.41 |
September | 98.50 | 23.68 | 387.83 | 24.30 | 44.83 | 24.35 |
October | 236.50 | 22.59 | 213.50 | 23.49 | 35.00 | 23.54 |
November | 359.33 | 22.22 | 75.00 | 22.58 | 13.00 | 22.49 |
December | 459.67 | 21.39 | 106.17 | 21.24 | 89.17 | 21.04 |
Annual Sum or Average | 3383.33 | 21.99 | 2939.33 | 22.71 | 911.67 | 22.57 |
Minimum of Months | 95.33 | 20.70 | 75.00 | 20.43 | 13.00 | 20.27 |
Maximum of Months | 496.00 | 24.42 | 508.67 | 24.41 | 265.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 359.17 | 20.40 | 359.17 | 20.35 |
February | 444.67 | 20.96 | 200.00 | 20.77 | 198.83 | 20.66 |
March | 453.50 | 21.88 | 67.67 | 21.90 | 41.00 | 21.80 |
April | 349.50 | 22.47 | 81.33 | 22.78 | 11.33 | 22.78 |
May | 185.83 | 23.07 | 240.33 | 23.81 | 12.67 | 23.86 |
June | 48.67 | 24.05 | 403.33 | 24.32 | 15.17 | 24.38 |
July | 46.17 | 25.07 | 465.00 | 24.50 | 33.33 | 24.58 |
August | 29.50 | 26.10 | 506.33 | 24.49 | 29.50 | 24.58 |
September | 72.50 | 23.81 | 369.50 | 24.33 | 22.00 | 24.40 |
October | 296.67 | 22.60 | 133.50 | 23.14 | 12.50 | 23.18 |
November | 441.67 | 22.03 | 45.17 | 22.02 | 31.33 | 21.93 |
December | 496.83 | 21.04 | 192.00 | 20.86 | 192.00 | 20.76 |
Annual Sum or Average | 3367.50 | 21.80 | 3063.33 | 22.51 | 958.83 | 22.32 |
Minimum of Months | 29.50 | 20.53 | 45.17 | 20.40 | 11.33 | 20.35 |
Maximum of Months | 502.00 | 26.10 | 506.33 | 24.50 | 359.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 398.67 | 20.17 | 398.67 | 20.13 |
February | 451.17 | 20.87 | 213.67 | 20.64 | 213.67 | 20.52 |
March | 464.33 | 21.93 | 71.50 | 21.89 | 48.00 | 21.77 |
April | 312.83 | 22.62 | 88.00 | 22.92 | 10.83 | 22.91 |
May | 121.00 | 23.16 | 286.50 | 23.94 | 4.67 | 23.96 |
June | 38.17 | 24.17 | 418.50 | 24.29 | 16.33 | 24.33 |
July | 36.83 | 24.83 | 476.33 | 24.44 | 30.00 | 24.49 |
August | 28.83 | 25.13 | 506.33 | 24.37 | 28.83 | 24.41 |
September | 112.67 | 23.54 | 303.33 | 24.11 | 27.17 | 24.19 |
October | 390.17 | 22.27 | 82.67 | 22.54 | 19.17 | 22.55 |
November | 481.50 | 21.57 | 86.00 | 21.39 | 86.00 | 21.27 |
December | 497.00 | 20.66 | 281.67 | 20.48 | 281.67 | 20.40 |
Annual Sum or Average | 3436.50 | 21.60 | 3213.17 | 22.26 | 1165.00 | 22.02 |
Minimum of Months | 28.83 | 20.28 | 71.50 | 20.17 | 4.67 | 20.13 |
Maximum of Months | 502.00 | 25.13 | 506.33 | 24.44 | 398.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.32 | 316.67 | 20.19 | 316.67 | 20.13 |
February | 374.33 | 21.00 | 161.83 | 20.74 | 161.50 | 20.59 |
March | 368.33 | 22.06 | 51.50 | 22.10 | 24.67 | 21.99 |
April | 230.83 | 22.61 | 110.33 | 23.16 | 12.33 | 23.17 |
May | 115.83 | 23.32 | 252.17 | 24.17 | 14.17 | 24.26 |
June | 45.00 | 24.89 | 358.83 | 24.51 | 26.83 | 24.61 |
July | 63.17 | 25.49 | 396.83 | 24.72 | 50.67 | 24.86 |
August | 44.67 | 25.80 | 416.00 | 24.59 | 42.33 | 24.71 |
September | 123.67 | 23.51 | 260.00 | 24.17 | 30.17 | 24.29 |
October | 288.83 | 22.15 | 97.67 | 22.66 | 18.17 | 22.67 |
November | 400.83 | 21.63 | 59.00 | 21.51 | 53.83 | 21.38 |
December | 422.00 | 20.67 | 217.17 | 20.47 | 217.17 | 20.37 |
Annual Sum or Average | 2904.50 | 21.75 | 2698.00 | 22.46 | 968.50 | 22.27 |
Minimum of Months | 44.67 | 20.32 | 51.50 | 20.19 | 12.33 | 20.13 |
Maximum of Months | 427.00 | 25.80 | 416.00 | 24.72 | 316.67 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.83 | 21.06 | 252.17 | 20.75 | 247.83 | 20.57 |
February | 394.00 | 21.43 | 144.83 | 21.30 | 128.17 | 21.10 |
March | 337.33 | 22.25 | 106.17 | 22.57 | 25.83 | 22.45 |
April | 232.83 | 22.71 | 142.00 | 23.32 | 10.83 | 23.31 |
May | 112.17 | 23.11 | 298.33 | 24.00 | 4.67 | 24.01 |
June | 49.67 | 24.11 | 410.67 | 24.30 | 18.83 | 24.35 |
July | 42.50 | 25.13 | 473.50 | 24.50 | 35.67 | 24.57 |
August | 46.00 | 25.79 | 507.33 | 24.51 | 46.00 | 24.61 |
September | 97.83 | 23.93 | 343.50 | 24.32 | 33.17 | 24.43 |
October | 256.00 | 22.52 | 199.17 | 23.33 | 27.00 | 23.39 |
November | 356.50 | 22.08 | 94.33 | 22.33 | 38.50 | 22.19 |
December | 435.17 | 21.38 | 151.00 | 21.15 | 138.00 | 20.94 |
Annual Sum or Average | 2831.83 | 22.07 | 3123.00 | 22.89 | 754.50 | 22.72 |
Minimum of Months | 42.50 | 21.06 | 94.33 | 20.75 | 4.67 | 20.57 |
Maximum of Months | 471.83 | 25.79 | 507.33 | 24.51 | 247.83 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.45 | 348.17 | 20.28 | 348.17 | 20.21 |
February | 435.83 | 20.93 | 193.83 | 20.74 | 189.33 | 20.61 |
March | 406.17 | 21.83 | 93.67 | 22.00 | 40.67 | 21.89 |
April | 278.33 | 22.50 | 139.67 | 23.08 | 14.83 | 23.10 |
May | 142.83 | 23.03 | 296.83 | 23.93 | 10.50 | 23.98 |
June | 66.33 | 24.13 | 406.50 | 24.33 | 25.33 | 24.42 |
July | 59.50 | 25.07 | 454.17 | 24.51 | 44.33 | 24.62 |
August | 42.67 | 25.53 | 492.83 | 24.45 | 38.33 | 24.54 |
September | 142.50 | 23.35 | 303.00 | 24.06 | 30.50 | 24.17 |
October | 354.00 | 22.13 | 116.83 | 22.63 | 18.83 | 22.65 |
November | 452.00 | 21.54 | 86.00 | 21.45 | 74.33 | 21.32 |
December | 495.67 | 20.80 | 238.17 | 20.59 | 238.17 | 20.48 |
Annual Sum or Average | 3377.83 | 21.67 | 3169.67 | 22.40 | 1073.33 | 22.21 |
Minimum of Months | 42.67 | 20.45 | 86.00 | 20.28 | 10.50 | 20.21 |
Maximum of Months | 502.00 | 25.53 | 492.83 | 24.51 | 348.17 | 24.62 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40816 | 27.06425 | -0.1932 | 6.83320 |
February | 454.00000 | 23.10215 | 27.52704 | -0.0005 | 6.04170 |
March | 514.00000 | 23.92322 | 30.83630 | 0.25825 | 6.80826 |
April | 485.00000 | 24.19660 | 35.58080 | 0.37411 | 8.25304 |
May | 508.00000 | 24.36573 | 41.91853 | -0.3792 | 8.50270 |
June | 496.00000 | 24.33190 | 44.10689 | -0.3387 | 7.85330 |
July | 497.00000 | 24.38991 | 46.27351 | -0.3021 | 7.36090 |
August | 514.00000 | 24.33983 | 46.67334 | -0.3040 | 7.34515 |
September | 485.00000 | 24.38194 | 44.68839 | -0.3283 | 7.76700 |
October | 502.00000 | 24.20615 | 38.12832 | 0.40144 | 8.67521 |
November | 489.00000 | 23.95048 | 29.03073 | 0.24744 | 6.66868 |
December | 497.00000 | 23.31629 | 28.74003 | 0.06224 | 5.69802 |
Annual Sum or Average | 5943.00000 | 23.91465 | 36.79015 | -0.0430 | 7.32603 |
Minimum of Months | 454.00000 | 22.40816 | 27.06425 | -0.3792 | 5.69802 |
Maximum of Months | 514.00000 | 24.38991 | 46.67334 | 0.40144 | 8.67521 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04035 | 28.56695 | -0.5076 | 11.37996 |
February | 454.00000 | 21.67889 | 29.47359 | -0.3223 | 8.68620 |
March | 514.00000 | 22.93728 | 33.32482 | 0.03590 | 6.00961 |
April | 485.00000 | 23.56059 | 37.79012 | 0.23013 | 6.75829 |
May | 508.00000 | 23.96129 | 43.89530 | -0.5137 | 11.09243 |
June | 496.00000 | 24.11859 | 45.57810 | -0.4196 | 9.19050 |
July | 497.00000 | 24.19987 | 47.75251 | -0.3735 | 8.33486 |
August | 514.00000 | 24.20473 | 48.00445 | -0.3633 | 8.09350 |
September | 485.00000 | 24.05071 | 46.29454 | -0.4551 | 9.96171 |
October | 502.00000 | 23.38268 | 40.82543 | 0.20349 | 6.69593 |
November | 489.00000 | 22.62407 | 31.88075 | -0.0588 | 5.89094 |
December | 497.00000 | 21.62104 | 31.47388 | -0.3218 | 8.05678 |
Annual Sum or Average | 5943.00000 | 23.12576 | 38.81391 | -0.2389 | 8.34538 |
Minimum of Months | 454.00000 | 21.04035 | 28.56695 | -0.5137 | 5.89094 |
Maximum of Months | 514.00000 | 24.20473 | 48.00445 | 0.23013 | 11.37996 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54991 | 27.48552 | -0.6602 | 16.25198 |
February | 454.00000 | 21.15497 | 29.84950 | -0.4676 | 11.74054 |
March | 514.00000 | 22.37652 | 33.79579 | -0.1001 | 6.80888 |
April | 485.00000 | 23.20787 | 37.85095 | 0.14682 | 6.60692 |
May | 508.00000 | 23.81892 | 43.47141 | -0.5569 | 12.41853 |
June | 496.00000 | 24.08057 | 45.25893 | -0.4219 | 9.37776 |
July | 497.00000 | 24.19191 | 47.47415 | -0.3640 | 8.29066 |
August | 514.00000 | 24.19473 | 47.84674 | -0.3543 | 7.97102 |
September | 485.00000 | 23.85146 | 46.16123 | -0.5246 | 11.80144 |
October | 502.00000 | 22.77788 | 41.82062 | 0.05560 | 6.49234 |
November | 489.00000 | 21.77666 | 32.93153 | -0.2689 | 7.67713 |
December | 497.00000 | 20.95455 | 31.81536 | -0.5095 | 11.88060 |
Annual Sum or Average | 5943.00000 | 22.75734 | 38.88538 | -0.3349 | 9.76140 |
Minimum of Months | 454.00000 | 20.54991 | 27.48552 | -0.6602 | 6.49234 |
Maximum of Months | 514.00000 | 24.19473 | 47.84674 | 0.14682 | 16.25198 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03833 | 29.09922 | -0.8419 | 22.91141 |
February | 454.00000 | 20.64817 | 31.14083 | -0.6350 | 16.49288 |
March | 514.00000 | 21.78397 | 35.99744 | -0.2500 | 9.00447 |
April | 485.00000 | 22.85080 | 40.80779 | 0.07213 | 7.56441 |
May | 508.00000 | 23.76190 | 46.22395 | -0.5494 | 13.35268 |
June | 496.00000 | 24.17466 | 47.48310 | -0.3394 | 8.65534 |
July | 497.00000 | 24.35161 | 50.85976 | -0.2476 | 7.47441 |
August | 514.00000 | 24.30253 | 51.42059 | -0.2585 | 7.21212 |
September | 485.00000 | 23.78278 | 49.98351 | -0.5231 | 12.94817 |
October | 502.00000 | 22.21438 | 46.25610 | -0.0722 | 7.56475 |
November | 489.00000 | 21.11879 | 36.12376 | -0.4431 | 11.10301 |
December | 497.00000 | 20.30494 | 32.88867 | -0.7094 | 18.30235 |
Annual Sum or Average | 5943.00000 | 22.45902 | 41.60421 | -0.3983 | 11.84374 |
Minimum of Months | 454.00000 | 20.03833 | 29.09922 | -0.8419 | 7.21212 |
Maximum of Months | 514.00000 | 24.35161 | 51.42059 | 0.07213 | 22.91141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16453 | 28.83155 | -0.7889 | 20.76293 |
February | 454.00000 | 20.91846 | 30.62035 | -0.5455 | 14.72006 |
March | 514.00000 | 22.16885 | 35.12441 | -0.1346 | 8.04288 |
April | 485.00000 | 23.17880 | 39.70337 | 0.18618 | 8.21776 |
May | 508.00000 | 23.90566 | 45.17059 | -0.4389 | 11.99983 |
June | 496.00000 | 24.24421 | 46.75704 | -0.2505 | 8.01834 |
July | 497.00000 | 24.40084 | 49.98396 | -0.1639 | 7.72310 |
August | 514.00000 | 24.33874 | 50.61562 | -0.1832 | 7.15584 |
September | 485.00000 | 23.79913 | 49.18042 | -0.4567 | 12.58060 |
October | 502.00000 | 22.55035 | 44.96823 | 0.03125 | 7.99023 |
November | 489.00000 | 21.33956 | 35.47041 | -0.3681 | 9.79476 |
December | 497.00000 | 20.40026 | 32.64042 | -0.6610 | 16.67815 |
Annual Sum or Average | 5943.00000 | 22.63157 | 40.83386 | -0.3129 | 11.10658 |
Minimum of Months | 454.00000 | 20.16453 | 28.83155 | -0.7889 | 7.15584 |
Maximum of Months | 514.00000 | 24.40084 | 50.61562 | 0.18618 | 20.76293 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.90557 | 27.92737 | -0.5841 | 17.08038 |
February | 454.00000 | 21.52235 | 29.74893 | -0.3870 | 13.01043 |
March | 514.00000 | 22.59096 | 34.12452 | -0.0355 | 8.72571 |
April | 485.00000 | 23.19443 | 39.61515 | 0.17381 | 8.43781 |
May | 508.00000 | 23.78947 | 45.87781 | -0.5222 | 13.20880 |
June | 496.00000 | 24.14337 | 47.49086 | -0.3442 | 9.08303 |
July | 497.00000 | 24.35463 | 50.74124 | -0.2378 | 7.65567 |
August | 514.00000 | 24.34389 | 50.96423 | -0.2126 | 7.13264 |
September | 485.00000 | 23.94422 | 48.89285 | -0.4202 | 11.74897 |
October | 502.00000 | 22.98642 | 43.57875 | 0.14746 | 9.23345 |
November | 489.00000 | 22.21682 | 33.62378 | -0.1499 | 9.61140 |
December | 497.00000 | 21.27332 | 31.29119 | -0.4326 | 13.62393 |
Annual Sum or Average | 5943.00000 | 22.95019 | 40.40680 | -0.2498 | 10.69313 |
Minimum of Months | 454.00000 | 20.90557 | 27.92737 | -0.5841 | 7.13264 |
Maximum of Months | 514.00000 | 24.35463 | 50.96423 | 0.17381 | 17.08038 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19217 | 28.55239 | -0.7880 | 21.13934 |
February | 454.00000 | 20.83704 | 30.47349 | -0.5717 | 15.38412 |
March | 514.00000 | 21.99674 | 35.07386 | -0.1720 | 9.14370 |
April | 485.00000 | 22.88675 | 40.20351 | 0.12228 | 8.45586 |
May | 508.00000 | 23.62311 | 45.90478 | -0.5333 | 14.39264 |
June | 496.00000 | 24.07479 | 47.32024 | -0.3166 | 9.50287 |
July | 497.00000 | 24.25136 | 50.61196 | -0.2281 | 8.24987 |
August | 514.00000 | 24.25301 | 50.94600 | -0.2175 | 7.58497 |
September | 485.00000 | 23.64097 | 49.64685 | -0.5111 | 14.10647 |
October | 502.00000 | 22.31107 | 45.37214 | -0.0217 | 8.15964 |
November | 489.00000 | 21.30510 | 35.25516 | -0.3812 | 10.70973 |
December | 497.00000 | 20.45188 | 32.37265 | -0.6586 | 16.93166 |
Annual Sum or Average | 5943.00000 | 22.49912 | 41.05844 | -0.3550 | 11.94867 |
Minimum of Months | 454.00000 | 20.19217 | 28.55239 | -0.7880 | 7.58497 |
Maximum of Months | 514.00000 | 24.25301 | 50.94600 | 0.12228 | 21.13934 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34667 | 29.00270 | -0.7492 | 18.51301 |
February | 454.00000 | 20.76544 | 31.35813 | -0.5931 | 14.34921 |
March | 514.00000 | 21.60359 | 36.85554 | -0.2933 | 8.24326 |
April | 485.00000 | 22.41695 | 42.24769 | -0.0463 | 6.63047 |
May | 508.00000 | 23.55608 | 47.43650 | -0.6615 | 15.71167 |
June | 496.00000 | 24.12648 | 47.19015 | -0.4009 | 9.00440 |
July | 497.00000 | 24.29568 | 49.83068 | -0.3067 | 7.52093 |
August | 514.00000 | 24.28404 | 50.01129 | -0.2968 | 7.26372 |
September | 485.00000 | 24.07270 | 48.71142 | -0.4304 | 9.82360 |
October | 502.00000 | 22.90285 | 44.22571 | 0.10317 | 6.62944 |
November | 489.00000 | 21.87639 | 34.75409 | -0.2294 | 7.44533 |
December | 497.00000 | 20.83087 | 32.29725 | -0.5413 | 12.38426 |
Annual Sum or Average | 5943.00000 | 22.60326 | 41.23815 | -0.3696 | 10.27565 |
Minimum of Months | 454.00000 | 20.34667 | 29.00270 | -0.7492 | 6.62944 |
Maximum of Months | 514.00000 | 24.29568 | 50.01129 | 0.10317 | 18.51301 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52221 | 29.12118 | -0.6834 | 16.32867 |
February | 454.00000 | 21.16941 | 31.10464 | -0.4746 | 12.16746 |
March | 514.00000 | 22.22871 | 35.95668 | -0.1255 | 7.01716 |
April | 485.00000 | 23.10035 | 40.69848 | 0.14030 | 7.13935 |
May | 508.00000 | 23.92382 | 45.93859 | -0.4858 | 12.20347 |
June | 496.00000 | 24.28873 | 46.30880 | -0.2828 | 7.63129 |
July | 497.00000 | 24.45313 | 48.93997 | -0.1886 | 7.08113 |
August | 514.00000 | 24.40516 | 49.22492 | -0.1927 | 6.71496 |
September | 485.00000 | 24.19813 | 47.94385 | -0.3306 | 8.76394 |
October | 502.00000 | 23.32420 | 42.96396 | 0.22586 | 7.79119 |
November | 489.00000 | 22.34701 | 34.17565 | -0.1029 | 6.73785 |
December | 497.00000 | 21.04741 | 32.26025 | -0.4653 | 10.76732 |
Annual Sum or Average | 5943.00000 | 22.93006 | 40.46062 | -0.2462 | 9.17947 |
Minimum of Months | 454.00000 | 20.52221 | 29.12118 | -0.6834 | 6.71496 |
Maximum of Months | 514.00000 | 24.45313 | 49.22492 | 0.22586 | 16.32867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76184 | 26.85506 | -0.5680 | 14.92382 |
February | 454.00000 | 21.38399 | 29.04208 | -0.3833 | 11.72311 |
March | 514.00000 | 22.37935 | 34.68576 | -0.0689 | 7.52849 |
April | 485.00000 | 22.82180 | 40.72257 | 0.07368 | 7.25844 |
May | 508.00000 | 23.51920 | 48.91773 | -0.6373 | 15.69697 |
June | 496.00000 | 24.06096 | 50.77446 | -0.3914 | 9.31126 |
July | 497.00000 | 24.30977 | 54.25800 | -0.2621 | 7.22081 |
August | 514.00000 | 24.39398 | 54.69599 | -0.1919 | 6.48519 |
September | 485.00000 | 24.19243 | 50.39640 | -0.3141 | 8.87670 |
October | 502.00000 | 23.51781 | 42.58122 | 0.30669 | 9.34799 |
November | 489.00000 | 22.84711 | 31.97107 | 0.05074 | 7.79080 |
December | 497.00000 | 21.61449 | 30.01499 | -0.2878 | 9.49263 |
Annual Sum or Average | 5943.00000 | 22.99490 | 41.34762 | -0.2225 | 9.63218 |
Minimum of Months | 454.00000 | 20.76184 | 26.85506 | -0.6373 | 6.48519 |
Maximum of Months | 514.00000 | 24.39398 | 54.69599 | 0.30669 | 15.69697 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52571 | 29.00388 | -0.6855 | 16.64168 |
February | 454.00000 | 21.03645 | 31.13064 | -0.5091 | 12.84354 |
March | 514.00000 | 22.15142 | 35.83609 | -0.1419 | 7.52441 |
April | 485.00000 | 22.94475 | 40.94895 | 0.10418 | 7.09505 |
May | 508.00000 | 23.77804 | 46.46488 | -0.5419 | 13.13166 |
June | 496.00000 | 24.21457 | 46.73304 | -0.3209 | 8.24173 |
July | 497.00000 | 24.36977 | 49.42762 | -0.2329 | 7.27871 |
August | 514.00000 | 24.38836 | 49.41361 | -0.2059 | 6.79058 |
September | 485.00000 | 24.18462 | 48.13165 | -0.3437 | 8.94263 |
October | 502.00000 | 23.23862 | 43.27039 | 0.20483 | 7.60077 |
November | 489.00000 | 22.24251 | 34.13294 | -0.1273 | 7.08846 |
December | 497.00000 | 21.04552 | 32.18791 | -0.4724 | 11.06946 |
Annual Sum or Average | 5943.00000 | 22.85665 | 40.63185 | -0.2717 | 9.50377 |
Minimum of Months | 454.00000 | 20.52571 | 29.00388 | -0.6855 | 6.79058 |
Maximum of Months | 514.00000 | 24.38836 | 49.42762 | 0.20483 | 16.64168 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27709 | 28.99350 | -0.7510 | 19.19215 |
February | 454.00000 | 20.88642 | 30.95210 | -0.5478 | 13.97733 |
March | 514.00000 | 22.13013 | 35.74004 | -0.1539 | 7.53831 |
April | 485.00000 | 23.13758 | 40.63943 | 0.14277 | 7.17445 |
May | 508.00000 | 23.92617 | 46.28841 | -0.5017 | 11.47516 |
June | 496.00000 | 24.22841 | 47.44765 | -0.3349 | 8.10032 |
July | 497.00000 | 24.37405 | 50.66201 | -0.2559 | 7.18285 |
August | 514.00000 | 24.32256 | 51.13345 | -0.2673 | 7.10256 |
September | 485.00000 | 23.98695 | 49.72196 | -0.4559 | 10.68070 |
October | 502.00000 | 22.64788 | 45.32889 | 0.04193 | 6.87586 |
November | 489.00000 | 21.60104 | 35.41131 | -0.3031 | 8.51779 |
December | 497.00000 | 20.66055 | 32.39238 | -0.5893 | 14.20448 |
Annual Sum or Average | 5943.00000 | 22.69556 | 41.30625 | -0.3302 | 10.13947 |
Minimum of Months | 454.00000 | 20.27709 | 28.99350 | -0.7510 | 6.87586 |
Maximum of Months | 514.00000 | 24.37405 | 51.13345 | 0.14277 | 19.19215 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.31717 | 28.00688 | -0.7280 | 18.21399 |
February | 385.00000 | 21.09448 | 29.97780 | -0.4835 | 12.96042 |
March | 433.00000 | 22.36128 | 34.36579 | -0.0848 | 7.29365 |
April | 410.00000 | 23.32251 | 39.48109 | 0.21224 | 7.94556 |
May | 430.00000 | 24.03160 | 45.01494 | -0.4247 | 11.33455 |
June | 418.00000 | 24.33591 | 46.61197 | -0.2599 | 7.91281 |
July | 422.00000 | 24.51232 | 49.79801 | -0.1688 | 7.52926 |
August | 433.00000 | 24.42681 | 50.45279 | -0.1951 | 7.23121 |
September | 410.00000 | 23.99211 | 48.97930 | -0.4135 | 11.05796 |
October | 427.00000 | 22.81174 | 44.03908 | 0.09746 | 7.59413 |
November | 417.00000 | 21.72749 | 34.25834 | -0.2607 | 8.13647 |
December | 422.00000 | 20.67058 | 31.59691 | -0.5718 | 13.53325 |
Annual Sum or Average | 5034.00000 | 22.81073 | 40.28107 | -0.2725 | 10.04236 |
Minimum of Months | 385.00000 | 20.31717 | 28.00688 | -0.7280 | 7.23121 |
Maximum of Months | 433.00000 | 24.51232 | 50.45279 | 0.21224 | 18.21399 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27042 | 27.70027 | -0.4717 | 13.99636 |
February | 454.00000 | 21.84522 | 29.46155 | -0.2867 | 10.85387 |
March | 514.00000 | 22.95511 | 33.77384 | 0.06141 | 7.78716 |
April | 485.00000 | 23.48639 | 39.38646 | 0.24381 | 8.15915 |
May | 508.00000 | 23.96957 | 45.92363 | -0.4708 | 11.16916 |
June | 496.00000 | 24.21626 | 47.44492 | -0.3347 | 8.32788 |
July | 497.00000 | 24.39696 | 50.53751 | -0.2410 | 7.24596 |
August | 514.00000 | 24.38027 | 50.67244 | -0.2180 | 6.94640 |
September | 485.00000 | 24.14822 | 48.66191 | -0.3551 | 9.60270 |
October | 502.00000 | 23.36760 | 42.70031 | 0.24847 | 9.00026 |
November | 489.00000 | 22.72912 | 32.77925 | -0.0085 | 8.22307 |
December | 497.00000 | 21.74134 | 30.59946 | -0.2950 | 10.50282 |
Annual Sum or Average | 5943.00000 | 23.21929 | 40.05410 | -0.1771 | 9.30612 |
Minimum of Months | 454.00000 | 21.27042 | 27.70027 | -0.4717 | 6.94640 |
Maximum of Months | 514.00000 | 24.39696 | 50.67244 | 0.24847 | 13.99636 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44534 | 28.56411 | -0.6946 | 17.61905 |
February | 454.00000 | 21.07433 | 30.40271 | -0.4852 | 13.01601 |
March | 514.00000 | 22.33759 | 34.90870 | -0.0777 | 7.87785 |
April | 485.00000 | 23.21091 | 40.00920 | 0.19903 | 8.11420 |
May | 508.00000 | 23.85926 | 45.92656 | -0.4672 | 11.80923 |
June | 496.00000 | 24.18641 | 47.26047 | -0.2967 | 8.40758 |
July | 497.00000 | 24.33453 | 50.39780 | -0.2202 | 7.54720 |
August | 514.00000 | 24.32202 | 50.67670 | -0.2136 | 7.14571 |
September | 485.00000 | 23.91995 | 49.39139 | -0.4248 | 11.12839 |
October | 502.00000 | 22.72933 | 44.58947 | 0.08882 | 7.60583 |
November | 489.00000 | 21.74897 | 34.72546 | -0.2494 | 8.42380 |
December | 497.00000 | 20.80937 | 31.98999 | -0.5390 | 13.10442 |
Annual Sum or Average | 5943.00000 | 22.76151 | 40.81701 | -0.2806 | 10.12608 |
Minimum of Months | 454.00000 | 20.44534 | 28.56411 | -0.6946 | 7.14571 |
Maximum of Months | 514.00000 | 24.33453 | 50.67670 | 0.19903 | 17.61905 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.202934E+10 | 0.542708E+09 | 52.83 | 0.124979E+10 | 0.779547E+09 | 0.00 | 0.61 | 19-JAN-20:00 | 0.00 | 01-JAN-00:05 | 21412.59 | 19-JAN-20:00 | 14381.93 | 31-JAN-15:00 | 10363.03 | 19-JAN-16:00 | 5451.80 | 19-JAN-20:00 | 0.00 |
February | 0.493248E+10 | 0.131874E+10 | 131.50 | 0.401424E+10 | 0.918239E+09 | 0.00 | 0.83 | 28-FEB-14:00 | 0.00 | 01-FEB-00:10 | 30620.35 | 28-FEB-14:00 | 30620.35 | 28-FEB-14:00 | 8922.55 | 18-FEB-16:00 | 7558.12 | 28-FEB-14:00 | 0.00 |
March | 0.151782E+11 | 0.388148E+10 | 267.83 | 0.117250E+11 | 0.345319E+10 | 0.00 | 1.00 | 29-MAR-15:40 | 0.00 | 01-MAR-00:10 | 47886.01 | 30-MAR-15:10 | 47886.01 | 30-MAR-15:10 | 15253.48 | 31-MAR-11:30 | 12066.51 | 30-MAR-15:10 | 0.00 |
April | 0.257912E+11 | 0.650120E+10 | 328.01 | 0.209254E+11 | 0.486577E+10 | 0.00 | 1.00 | 04-APR-13:50 | 0.00 | 01-APR-00:10 | 54143.67 | 17-APR-15:10 | 54143.67 | 17-APR-15:10 | 16950.68 | 04-APR-07:10 | 14065.80 | 17-APR-15:10 | 0.00 |
May | 0.487284E+11 | 0.120547E+11 | 406.99 | 0.366172E+11 | 0.121113E+11 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:10 | 68507.22 | 30-MAY-12:00 | 53785.85 | 30-MAY-15:10 | 19512.45 | 22-MAY-05:13 | 17902.28 | 30-MAY-15:10 | 0.00 |
June | 0.737661E+11 | 0.189384E+11 | 432.09 | 0.551493E+11 | 0.186169E+11 | 0.00 | 1.00 | 01-JUN-07:05 | 0.00 | 01-JUN-00:10 | 83080.54 | 27-JUN-12:00 | 59501.25 | 06-JUN-15:50 | 27599.98 | 27-JUN-12:00 | 22449.51 | 23-JUN-12:00 | 0.00 |
July | 0.846172E+11 | 0.219361E+11 | 438.24 | 0.600465E+11 | 0.245708E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 91434.54 | 07-JUL-12:03 | 66434.11 | 07-JUL-16:00 | 32544.93 | 26-JUL-12:00 | 25869.06 | 07-JUL-12:03 | 0.00 |
August | 0.967485E+11 | 0.247907E+11 | 462.23 | 0.671797E+11 | 0.295688E+11 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:10 | 92379.50 | 21-AUG-06:03 | 77508.28 | 14-AUG-04:02 | 46169.82 | 23-AUG-05:13 | 25143.73 | 18-AUG-12:02 | 0.00 |
September | 0.617830E+11 | 0.152003E+11 | 409.86 | 0.453822E+11 | 0.164008E+11 | 0.00 | 1.00 | 01-SEP-05:13 | 0.00 | 01-SEP-00:10 | 86983.98 | 06-SEP-12:03 | 64434.44 | 07-SEP-15:40 | 26082.82 | 06-SEP-12:03 | 23377.10 | 07-SEP-16:00 | 0.00 |
October | 0.273949E+11 | 0.675248E+10 | 301.76 | 0.201709E+11 | 0.722401E+10 | 0.00 | 1.00 | 02-OCT-08:00 | 0.00 | 01-OCT-00:10 | 66835.83 | 10-OCT-16:00 | 55121.12 | 10-OCT-16:00 | 25027.82 | 18-OCT-17:00 | 17687.79 | 10-OCT-16:00 | 0.00 |
November | 0.109085E+11 | 0.281248E+10 | 218.22 | 0.824653E+10 | 0.266195E+10 | 0.00 | 0.92 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 35159.94 | 02-NOV-13:00 | 27144.79 | 08-NOV-16:10 | 12213.09 | 02-NOV-11:00 | 8262.64 | 02-NOV-13:00 | 0.00 |
December | 0.394800E+10 | 0.102436E+10 | 112.78 | 0.258632E+10 | 0.136168E+10 | 0.00 | 0.87 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 32695.65 | 12-DEC-14:00 | 24784.89 | 12-DEC-14:00 | 15323.17 | 13-DEC-17:00 | 7765.51 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.455826E+12 | 0.115754E+12 | 3562.37 | 0.333293E+12 | 0.122533E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.202934E+10 | 0.542708E+09 | 52.83 | 0.124979E+10 | 0.779547E+09 | 0.00 | 0.61 | 0.00 | 21412.59 | 14381.93 | 8922.55 | 5451.80 | 0.00 | ||||||
Maximum of Months | 0.967485E+11 | 0.247907E+11 | 462.23 | 0.671797E+11 | 0.295688E+11 | 0.00 | 1.00 | 0.00 | 92379.50 | 77508.28 | 46169.82 | 25869.06 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200007E+10 | 0.530770E+09 | 52.83 | 0.126216E+10 | 0.737914E+09 | 0.00 | 0.67 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 21808.56 | 19-JAN-16:00 | 14048.83 | 31-JAN-15:00 | 9779.47 | 19-JAN-15:00 | 5465.78 | 19-JAN-16:00 | 0.00 |
February | 0.479494E+10 | 0.128015E+10 | 133.54 | 0.392227E+10 | 0.872680E+09 | 0.00 | 0.77 | 28-FEB-15:20 | 0.00 | 01-FEB-00:10 | 25585.37 | 28-FEB-15:20 | 25585.37 | 28-FEB-15:20 | 8514.23 | 18-FEB-16:00 | 6373.98 | 28-FEB-15:00 | 0.00 |
March | 0.138683E+11 | 0.355833E+10 | 270.06 | 0.107546E+11 | 0.311371E+10 | 0.00 | 1.00 | 29-MAR-15:30 | 0.00 | 01-MAR-00:10 | 47364.12 | 30-MAR-15:10 | 47364.12 | 30-MAR-15:10 | 11995.29 | 31-MAR-11:30 | 11933.11 | 30-MAR-15:10 | 0.00 |
April | 0.243901E+11 | 0.616118E+10 | 339.43 | 0.198934E+11 | 0.449673E+10 | 0.00 | 1.00 | 04-APR-15:20 | 0.00 | 01-APR-00:10 | 52931.46 | 17-APR-15:40 | 52931.46 | 17-APR-15:40 | 13693.78 | 21-APR-10:40 | 13748.74 | 17-APR-15:40 | 0.00 |
May | 0.455192E+11 | 0.112813E+11 | 421.46 | 0.343655E+11 | 0.111537E+11 | 0.00 | 1.00 | 02-MAY-13:30 | 0.00 | 01-MAY-00:10 | 64850.11 | 30-MAY-15:10 | 51588.92 | 30-MAY-15:00 | 17190.08 | 31-MAY-13:00 | 17344.67 | 30-MAY-15:00 | 0.00 |
June | 0.678750E+11 | 0.173917E+11 | 438.09 | 0.500996E+11 | 0.177754E+11 | 0.00 | 1.00 | 01-JUN-08:20 | 0.00 | 01-JUN-00:10 | 74720.84 | 26-JUN-15:00 | 55238.09 | 06-JUN-16:00 | 24159.67 | 23-JUN-10:50 | 20306.17 | 27-JUN-16:00 | 0.00 |
July | 0.778633E+11 | 0.201076E+11 | 441.52 | 0.540088E+11 | 0.238545E+11 | 0.00 | 1.00 | 01-JUL-07:20 | 0.00 | 01-JUL-00:10 | 82323.04 | 15-JUL-05:03 | 63585.74 | 15-JUL-05:03 | 27314.38 | 26-JUL-10:50 | 23905.78 | 07-JUL-16:00 | 0.00 |
August | 0.870324E+11 | 0.222016E+11 | 463.52 | 0.585261E+11 | 0.285062E+11 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:10 | 85858.76 | 21-AUG-06:03 | 68841.81 | 14-AUG-04:02 | 34561.39 | 21-AUG-06:03 | 23198.55 | 01-AUG-15:20 | 0.00 |
September | 0.530819E+11 | 0.130918E+11 | 410.76 | 0.377183E+11 | 0.153635E+11 | 0.00 | 1.00 | 01-SEP-09:30 | 0.00 | 01-SEP-00:10 | 77102.03 | 07-SEP-16:00 | 56840.11 | 07-SEP-15:30 | 25485.59 | 17-SEP-11:23 | 21034.62 | 07-SEP-16:00 | 0.00 |
October | 0.230304E+11 | 0.571367E+10 | 300.64 | 0.164973E+11 | 0.653311E+10 | 0.00 | 1.00 | 02-OCT-10:10 | 0.00 | 01-OCT-00:10 | 58769.66 | 11-OCT-14:10 | 46395.20 | 11-OCT-16:00 | 22793.63 | 18-OCT-15:00 | 15015.29 | 10-OCT-16:00 | 0.00 |
November | 0.959012E+10 | 0.248725E+10 | 218.11 | 0.711192E+10 | 0.247819E+10 | 0.00 | 0.86 | 05-NOV-13:43 | 0.00 | 01-NOV-00:10 | 29308.50 | 05-NOV-13:43 | 22112.49 | 05-NOV-13:43 | 10663.01 | 27-NOV-18:00 | 6985.12 | 05-NOV-13:43 | 0.00 |
December | 0.366717E+10 | 0.954253E+09 | 112.39 | 0.247936E+10 | 0.118782E+10 | 0.00 | 0.83 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 28239.16 | 12-DEC-14:00 | 20644.96 | 12-DEC-14:00 | 10634.32 | 13-DEC-17:02 | 6771.19 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.412713E+12 | 0.104760E+12 | 3602.34 | 0.296639E+12 | 0.116073E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.200007E+10 | 0.530770E+09 | 52.83 | 0.126216E+10 | 0.737914E+09 | 0.00 | 0.67 | 0.00 | 21808.56 | 14048.83 | 8514.23 | 5465.78 | 0.00 | ||||||
Maximum of Months | 0.870324E+11 | 0.222016E+11 | 463.52 | 0.585261E+11 | 0.285062E+11 | 0.00 | 1.00 | 0.00 | 85858.76 | 68841.81 | 34561.39 | 23905.78 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.211112E+10 | 0.563764E+09 | 53.33 | 0.131046E+10 | 0.800659E+09 | 0.00 | 0.62 | 19-JAN-17:50 | 0.00 | 01-JAN-00:05 | 22128.00 | 19-JAN-17:50 | 14760.46 | 31-JAN-15:00 | 10776.14 | 19-JAN-16:00 | 5620.95 | 19-JAN-17:50 | 0.00 |
February | 0.503262E+10 | 0.134993E+10 | 133.00 | 0.407828E+10 | 0.954344E+09 | 0.00 | 0.77 | 26-FEB-14:43 | 0.00 | 01-FEB-00:10 | 28552.53 | 26-FEB-14:43 | 28552.53 | 26-FEB-14:43 | 8983.02 | 18-FEB-16:00 | 7143.83 | 26-FEB-14:43 | 0.00 |
March | 0.147362E+11 | 0.380210E+10 | 270.43 | 0.113593E+11 | 0.337684E+10 | 0.00 | 1.00 | 29-MAR-15:30 | 0.00 | 01-MAR-00:10 | 53365.05 | 30-MAR-15:30 | 53365.05 | 30-MAR-15:30 | 11949.35 | 31-MAR-11:30 | 13439.21 | 30-MAR-15:30 | 0.00 |
April | 0.264522E+11 | 0.670991E+10 | 340.03 | 0.215405E+11 | 0.491166E+10 | 0.00 | 1.00 | 11-APR-14:20 | 0.00 | 01-APR-00:10 | 59644.93 | 17-APR-15:40 | 59644.93 | 17-APR-15:40 | 15862.14 | 23-APR-13:13 | 15492.05 | 17-APR-15:40 | 0.00 |
May | 0.494681E+11 | 0.123310E+11 | 423.61 | 0.379136E+11 | 0.115545E+11 | 0.00 | 1.00 | 01-MAY-16:00 | 0.00 | 01-MAY-00:10 | 73716.12 | 30-MAY-15:10 | 62973.46 | 16-MAY-15:50 | 17355.64 | 31-MAY-13:00 | 19684.75 | 30-MAY-15:00 | 0.00 |
June | 0.730904E+11 | 0.188221E+11 | 440.02 | 0.548902E+11 | 0.182002E+11 | 0.00 | 1.00 | 01-JUN-09:30 | 0.00 | 01-JUN-00:10 | 83296.61 | 26-JUN-15:00 | 66466.36 | 25-JUN-14:23 | 24465.90 | 23-JUN-10:40 | 22944.27 | 27-JUN-15:50 | 0.00 |
July | 0.834434E+11 | 0.216714E+11 | 444.99 | 0.592381E+11 | 0.242053E+11 | 0.00 | 1.00 | 01-JUL-08:70 | 0.00 | 01-JUL-00:10 | 89797.95 | 07-JUL-16:00 | 71764.95 | 07-JUL-16:00 | 27583.57 | 26-JUL-10:40 | 27133.67 | 07-JUL-16:00 | 0.00 |
August | 0.922019E+11 | 0.236403E+11 | 464.63 | 0.634137E+11 | 0.287882E+11 | 0.00 | 1.00 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 88806.17 | 01-AUG-15:00 | 71820.05 | 02-AUG-16:00 | 29937.84 | 20-AUG-09:32 | 26392.65 | 01-AUG-15:00 | 0.00 |
September | 0.551550E+11 | 0.137064E+11 | 410.64 | 0.392642E+11 | 0.158908E+11 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 85075.93 | 06-SEP-14:00 | 64791.46 | 07-SEP-15:30 | 27382.54 | 17-SEP-11:25 | 23091.92 | 07-SEP-16:00 | 0.00 |
October | 0.236606E+11 | 0.591759E+10 | 298.06 | 0.167635E+11 | 0.689706E+10 | 0.00 | 1.00 | 02-OCT-11:30 | 0.00 | 01-OCT-00:10 | 64076.06 | 11-OCT-14:00 | 51399.35 | 10-OCT-15:40 | 22992.44 | 18-OCT-15:00 | 16330.77 | 10-OCT-14:00 | 0.00 |
November | 0.996680E+10 | 0.260128E+10 | 216.35 | 0.731304E+10 | 0.265376E+10 | 0.00 | 0.84 | 05-NOV-13:55 | 0.00 | 01-NOV-00:10 | 31921.15 | 05-NOV-13:55 | 24459.88 | 05-NOV-13:55 | 11133.73 | 27-NOV-18:00 | 7683.88 | 05-NOV-13:55 | 0.00 |
December | 0.381292E+10 | 0.997217E+09 | 111.00 | 0.253941E+10 | 0.127351E+10 | 0.00 | 0.81 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 30459.00 | 12-DEC-14:00 | 22264.08 | 12-DEC-14:10 | 11017.27 | 13-DEC-16:00 | 7351.52 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.439131E+12 | 0.112113E+12 | 3606.08 | 0.319624E+12 | 0.119507E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.211112E+10 | 0.563764E+09 | 53.33 | 0.131046E+10 | 0.800659E+09 | 0.00 | 0.62 | 0.00 | 22128.00 | 14760.46 | 8983.02 | 5620.95 | 0.00 | ||||||
Maximum of Months | 0.922019E+11 | 0.236403E+11 | 464.63 | 0.634137E+11 | 0.287882E+11 | 0.00 | 1.00 | 0.00 | 89797.95 | 71820.05 | 29937.84 | 27133.67 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 49.89 | 1752.08 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 147.09 | 1431.67 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 326.28 | 891.09 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 601.76 | 718.18 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 893.05 | 473.12 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1266.60 | 303.57 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1263.50 | 219.80 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1152.67 | 183.36 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 670.46 | 396.69 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 317.53 | 815.30 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 185.03 | 1102.74 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 54.78 | 1398.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 579.79 | 803.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 49.89 | 183.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1266.60 | 1752.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 301.15 | 1043.22 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 516.72 | 858.67 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 757.36 | 549.05 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1096.48 | 453.22 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1325.83 | 312.07 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1561.19 | 202.55 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1572.27 | 146.91 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1463.38 | 121.69 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1050.91 | 255.30 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 732.20 | 507.21 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 470.63 | 662.92 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 309.99 | 831.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 931.98 | 493.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 301.15 | 121.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1572.27 | 1043.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1726.77 | 1469.50 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1749.33 | 1264.87 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1706.16 | 875.21 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1417.35 | 743.81 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1204.80 | 501.58 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1324.22 | 322.36 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1405.20 | 228.43 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1706.97 | 191.83 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1604.46 | 408.90 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 2012.50 | 800.52 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1962.40 | 1024.08 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1816.65 | 1228.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1636.12 | 752.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1204.80 | 191.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 2012.50 | 1469.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 345.53 | 1085.42 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 509.43 | 910.45 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 901.78 | 591.66 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1157.20 | 491.38 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1267.33 | 337.11 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1500.31 | 221.54 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1465.53 | 157.04 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1450.46 | 133.50 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1037.20 | 270.00 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 789.75 | 546.63 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 533.94 | 722.80 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 336.07 | 892.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 943.49 | 528.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 336.07 | 133.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1500.31 | 1085.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.87 | 0.00 | 92.87 | 16.12 | 609.12 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 50.82 | 491.69 | 0.00 | 0.00 | 0.00 |
March | 144.52 | 0.00 | 144.52 | 117.56 | 296.51 | 0.00 | 0.00 | 0.00 |
April | 174.81 | 0.78 | 174.04 | 217.14 | 228.38 | 0.00 | 0.00 | 0.00 |
May | 209.07 | 6.67 | 202.40 | 312.12 | 149.06 | 0.00 | 0.00 | 0.00 |
June | 230.09 | 15.19 | 214.90 | 431.52 | 97.56 | 0.00 | 0.00 | 0.00 |
July | 217.09 | 10.55 | 206.54 | 429.82 | 70.42 | 0.00 | 0.00 | 0.00 |
August | 193.07 | 2.10 | 190.97 | 389.67 | 60.30 | 0.00 | 0.00 | 0.00 |
September | 145.94 | 0.02 | 145.92 | 221.55 | 145.09 | 0.00 | 0.00 | 0.00 |
October | 110.96 | 0.00 | 110.96 | 99.64 | 305.48 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 53.14 | 412.02 | 0.00 | 0.00 | 0.00 |
December | 85.85 | 0.00 | 85.85 | 16.17 | 513.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.80 | 2.96 | 147.85 | 197.09 | 280.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.85 | 0.00 | 85.85 | 16.12 | 60.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.09 | 15.19 | 214.90 | 431.52 | 609.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 16.12 | 609.16 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 50.82 | 491.72 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 117.56 | 296.53 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 217.14 | 228.40 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 312.13 | 149.07 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 431.54 | 97.57 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 429.84 | 70.42 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 389.68 | 60.30 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 221.56 | 145.09 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 99.65 | 305.50 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 53.14 | 412.05 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 16.17 | 513.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 197.10 | 280.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 16.12 | 60.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 431.54 | 609.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 16.12 | 609.16 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 50.82 | 491.72 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 117.56 | 296.53 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 217.14 | 228.40 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 312.13 | 149.07 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 431.54 | 97.57 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 429.84 | 70.42 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 389.68 | 60.30 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 221.56 | 145.09 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 99.65 | 305.50 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 53.14 | 412.05 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 16.17 | 513.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 197.10 | 280.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 16.12 | 60.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 431.54 | 609.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 392.41 | 177.00 | 215.42 | 285.89 | 1056.45 | 0.00 | 0.00 | 0.00 |
February | 494.71 | 265.80 | 228.91 | 499.83 | 863.56 | 0.00 | 0.00 | 0.00 |
March | 622.40 | 283.33 | 339.07 | 743.35 | 542.63 | 0.00 | 0.00 | 0.00 |
April | 752.65 | 343.19 | 409.46 | 1080.41 | 431.64 | 0.00 | 0.00 | 0.00 |
May | 826.46 | 349.50 | 476.96 | 1299.69 | 295.65 | 0.00 | 0.00 | 0.00 |
June | 855.67 | 358.63 | 497.04 | 1518.90 | 195.55 | 0.00 | 0.00 | 0.00 |
July | 834.31 | 350.75 | 483.55 | 1527.36 | 143.51 | 0.00 | 0.00 | 0.00 |
August | 763.12 | 302.75 | 460.36 | 1417.87 | 122.99 | 0.00 | 0.00 | 0.00 |
September | 627.18 | 277.89 | 349.29 | 1006.70 | 277.63 | 0.00 | 0.00 | 0.00 |
October | 535.04 | 278.39 | 256.64 | 688.87 | 558.46 | 0.00 | 0.00 | 0.00 |
November | 427.77 | 193.69 | 234.08 | 424.91 | 728.70 | 0.00 | 0.00 | 0.00 |
December | 370.53 | 168.90 | 201.63 | 285.77 | 893.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.81 | 279.11 | 346.71 | 900.37 | 507.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.53 | 168.90 | 201.63 | 285.77 | 122.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 855.67 | 358.63 | 497.04 | 1527.36 | 1056.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.52 | 7.00 | 8.52 | 11.30 | 41.77 | 0.00 | 0.00 | 0.00 |
February | 19.56 | 10.51 | 9.05 | 19.76 | 34.14 | 0.00 | 0.00 | 0.00 |
March | 24.61 | 11.20 | 13.41 | 29.39 | 21.46 | 0.00 | 0.00 | 0.00 |
April | 29.76 | 13.57 | 16.19 | 42.72 | 17.07 | 0.00 | 0.00 | 0.00 |
May | 32.68 | 13.82 | 18.86 | 51.39 | 11.69 | 0.00 | 0.00 | 0.00 |
June | 33.83 | 14.18 | 19.65 | 60.06 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 32.99 | 13.87 | 19.12 | 60.39 | 5.67 | 0.00 | 0.00 | 0.00 |
August | 30.17 | 11.97 | 18.20 | 56.06 | 4.86 | 0.00 | 0.00 | 0.00 |
September | 24.80 | 10.99 | 13.81 | 39.80 | 10.98 | 0.00 | 0.00 | 0.00 |
October | 21.15 | 11.01 | 10.15 | 27.24 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 16.91 | 7.66 | 9.26 | 16.80 | 28.81 | 0.00 | 0.00 | 0.00 |
December | 14.65 | 6.68 | 7.97 | 11.30 | 35.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.74 | 11.04 | 13.71 | 35.60 | 20.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.65 | 6.68 | 7.97 | 11.30 | 4.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.83 | 14.18 | 19.65 | 60.39 | 41.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 581.33 | 521.57 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 591.23 | 445.74 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 581.74 | 302.34 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 489.47 | 242.10 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 416.72 | 159.16 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 451.30 | 103.81 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 476.88 | 73.90 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 573.83 | 65.56 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 534.52 | 151.77 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 668.46 | 306.06 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 646.68 | 393.17 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 603.40 | 462.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 551.19 | 267.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 416.72 | 65.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 668.46 | 521.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 581.33 | 521.57 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 591.23 | 445.74 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 581.74 | 302.34 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 489.47 | 242.10 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 416.72 | 159.16 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 451.30 | 103.81 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 476.88 | 73.90 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 573.83 | 65.56 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 534.52 | 151.77 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 668.46 | 306.06 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 646.68 | 393.17 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 603.40 | 462.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 551.19 | 267.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 416.72 | 65.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 668.46 | 521.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.67 | 346.28 | 150.39 | 581.29 | 521.54 | 0.00 | 0.00 | 0.00 |
February | 463.56 | 310.74 | 152.82 | 591.19 | 445.71 | 0.00 | 0.00 | 0.00 |
March | 416.90 | 217.26 | 199.64 | 581.70 | 302.32 | 0.00 | 0.00 | 0.00 |
April | 312.23 | 101.64 | 210.59 | 489.44 | 242.08 | 0.00 | 0.00 | 0.00 |
May | 252.27 | 29.32 | 222.95 | 416.69 | 159.15 | 0.00 | 0.00 | 0.00 |
June | 233.25 | 12.98 | 220.27 | 451.27 | 103.81 | 0.00 | 0.00 | 0.00 |
July | 235.81 | 17.58 | 218.23 | 476.85 | 73.89 | 0.00 | 0.00 | 0.00 |
August | 281.54 | 52.59 | 228.95 | 573.79 | 65.56 | 0.00 | 0.00 | 0.00 |
September | 309.63 | 115.16 | 194.46 | 534.49 | 151.76 | 0.00 | 0.00 | 0.00 |
October | 448.87 | 290.78 | 158.09 | 668.42 | 306.05 | 0.00 | 0.00 | 0.00 |
November | 482.90 | 320.44 | 162.46 | 646.64 | 393.15 | 0.00 | 0.00 | 0.00 |
December | 489.58 | 344.42 | 145.16 | 603.36 | 462.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.19 | 179.32 | 188.87 | 551.16 | 267.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.25 | 12.98 | 145.16 | 416.69 | 65.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.67 | 346.28 | 228.95 | 668.42 | 521.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.06 | 186.97 | 216.10 | 334.49 | 1100.25 | 0.00 | 0.00 | 0.00 |
February | 462.72 | 216.35 | 246.37 | 497.84 | 914.49 | 0.00 | 0.00 | 0.00 |
March | 682.02 | 329.56 | 352.45 | 885.10 | 588.55 | 0.00 | 0.00 | 0.00 |
April | 767.26 | 351.09 | 416.16 | 1138.76 | 472.28 | 0.00 | 0.00 | 0.00 |
May | 771.11 | 292.14 | 478.97 | 1239.89 | 322.23 | 0.00 | 0.00 | 0.00 |
June | 810.93 | 311.96 | 498.97 | 1459.51 | 215.88 | 0.00 | 0.00 | 0.00 |
July | 764.89 | 283.59 | 481.30 | 1422.62 | 153.96 | 0.00 | 0.00 | 0.00 |
August | 749.48 | 280.28 | 469.21 | 1403.52 | 135.81 | 0.00 | 0.00 | 0.00 |
September | 610.62 | 254.35 | 356.27 | 990.97 | 295.06 | 0.00 | 0.00 | 0.00 |
October | 543.99 | 282.39 | 261.60 | 747.44 | 604.10 | 0.00 | 0.00 | 0.00 |
November | 434.15 | 194.87 | 239.28 | 495.37 | 791.49 | 0.00 | 0.00 | 0.00 |
December | 358.17 | 156.66 | 201.51 | 316.98 | 954.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.97 | 261.88 | 352.09 | 913.23 | 543.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.17 | 156.66 | 201.51 | 316.98 | 135.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.93 | 351.09 | 498.97 | 1459.51 | 1100.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.94 | 7.39 | 8.54 | 13.23 | 43.50 | 0.00 | 0.00 | 0.00 |
February | 18.30 | 8.55 | 9.74 | 19.68 | 36.16 | 0.00 | 0.00 | 0.00 |
March | 26.97 | 13.03 | 13.94 | 35.00 | 23.27 | 0.00 | 0.00 | 0.00 |
April | 30.34 | 13.88 | 16.45 | 45.03 | 18.67 | 0.00 | 0.00 | 0.00 |
May | 30.49 | 11.55 | 18.94 | 49.02 | 12.74 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 12.33 | 19.73 | 57.71 | 8.54 | 0.00 | 0.00 | 0.00 |
July | 30.24 | 11.21 | 19.03 | 56.25 | 6.09 | 0.00 | 0.00 | 0.00 |
August | 29.63 | 11.08 | 18.55 | 55.49 | 5.37 | 0.00 | 0.00 | 0.00 |
September | 24.14 | 10.06 | 14.09 | 39.18 | 11.67 | 0.00 | 0.00 | 0.00 |
October | 21.51 | 11.17 | 10.34 | 29.55 | 23.89 | 0.00 | 0.00 | 0.00 |
November | 17.17 | 7.70 | 9.46 | 19.59 | 31.29 | 0.00 | 0.00 | 0.00 |
December | 14.16 | 6.19 | 7.97 | 12.53 | 37.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.28 | 10.35 | 13.92 | 36.11 | 21.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.16 | 6.19 | 7.97 | 12.53 | 5.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 13.88 | 19.73 | 57.71 | 43.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 45.70 | 1837.24 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 140.69 | 1507.72 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 314.05 | 951.31 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 593.95 | 756.51 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 892.00 | 491.96 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1272.38 | 310.84 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1272.96 | 223.90 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1161.24 | 187.14 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 665.82 | 423.50 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 303.42 | 883.35 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 165.91 | 1194.48 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 47.89 | 1505.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 575.44 | 852.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 45.70 | 187.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1272.96 | 1837.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 292.00 | 1094.72 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 507.35 | 904.34 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 747.03 | 582.22 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1091.81 | 473.59 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1326.87 | 322.14 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1566.49 | 206.61 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1579.66 | 149.61 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1470.26 | 123.99 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1048.88 | 270.42 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 721.60 | 544.01 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 451.89 | 714.18 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 297.82 | 894.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 927.32 | 521.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 292.00 | 123.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1579.66 | 1094.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1706.49 | 1547.38 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1734.36 | 1336.24 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1693.32 | 931.27 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1411.54 | 782.01 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1205.73 | 522.29 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1330.99 | 331.80 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1414.92 | 233.99 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1716.45 | 196.40 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1601.96 | 434.50 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 2000.14 | 860.11 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1936.22 | 1104.62 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1792.10 | 1322.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1628.46 | 797.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1205.73 | 196.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 2000.14 | 1547.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 340.10 | 1139.78 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 504.58 | 959.55 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 894.89 | 630.23 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1152.62 | 517.15 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1266.68 | 351.53 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1504.66 | 228.50 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1470.89 | 161.37 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1455.72 | 136.88 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1033.06 | 288.24 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 781.48 | 589.72 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 521.13 | 780.01 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 328.01 | 959.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 940.12 | 559.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 328.01 | 136.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1504.66 | 1139.78 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.133633E+09 | 0.469277E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.355834E+09 | 0.346350E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.873918E+09 | 0.238668E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.155975E+10 | 0.186152E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.239195E+10 | 0.126721E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.328303E+10 | 0.786860E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.338417E+10 | 0.588711E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.308731E+10 | 0.491119E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.173782E+10 | 0.102823E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.850470E+09 | 0.218371E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.479603E+09 | 0.285831E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.146732E+09 | 0.374503E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.182842E+11 | 0.253537E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.133633E+09 | 0.491119E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.338417E+10 | 0.469277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.806589E+09 | 0.279416E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.125004E+10 | 0.207730E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.202851E+10 | 0.147058E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.284207E+10 | 0.117475E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.355111E+10 | 0.835857E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.404660E+10 | 0.525015E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.421116E+10 | 0.393475E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.391952E+10 | 0.325930E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.272395E+10 | 0.661725E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.196113E+10 | 0.135852E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.121986E+10 | 0.171828E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.830278E+09 | 0.222744E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.293908E+11 | 0.155630E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.806589E+09 | 0.325930E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.421116E+10 | 0.279416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.462497E+10 | 0.393590E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.423197E+10 | 0.305996E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.456978E+10 | 0.234415E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.367377E+10 | 0.192795E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.322693E+10 | 0.134344E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.343238E+10 | 0.835570E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.376368E+10 | 0.611827E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.457195E+10 | 0.513806E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.415875E+10 | 0.105987E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.539029E+10 | 0.214412E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.508653E+10 | 0.265441E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.486572E+10 | 0.329087E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.515967E+11 | 0.237219E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.322693E+10 | 0.513806E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.539029E+10 | 0.393590E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.925477E+09 | 0.290718E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.123241E+10 | 0.220256E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.241533E+10 | 0.158471E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.299946E+10 | 0.127366E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.339442E+10 | 0.902917E+09 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.388881E+10 | 0.574230E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.392526E+10 | 0.420624E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.388491E+10 | 0.357570E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.268841E+10 | 0.699830E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.211527E+10 | 0.146409E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.138397E+10 | 0.187350E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.900122E+09 | 0.239054E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.297539E+11 | 0.166514E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.900122E+09 | 0.357570E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.392526E+10 | 0.290718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248747E+09 | 0.00 | 0.248747E+09 | 43164136.11 | 0.163147E+10 |
February | 0.249030E+09 | 0.00 | 0.249030E+09 | 0.122945E+09 | 0.118950E+10 |
March | 0.387084E+09 | 0.00 | 0.387084E+09 | 0.314867E+09 | 0.794177E+09 |
April | 0.453110E+09 | 2009678.92 | 0.451101E+09 | 0.562815E+09 | 0.591970E+09 |
May | 0.559977E+09 | 17871404.04 | 0.542106E+09 | 0.835983E+09 | 0.399242E+09 |
June | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.111850E+10 | 0.252876E+09 |
July | 0.581461E+09 | 28265234.63 | 0.553196E+09 | 0.115122E+10 | 0.188606E+09 |
August | 0.517114E+09 | 5633145.20 | 0.511481E+09 | 0.104368E+10 | 0.161508E+09 |
September | 0.378280E+09 | 53251.27 | 0.378227E+09 | 0.574259E+09 | 0.376066E+09 |
October | 0.297206E+09 | 0.00 | 0.297206E+09 | 0.266885E+09 | 0.818205E+09 |
November | 0.257408E+09 | 0.00 | 0.257408E+09 | 0.137737E+09 | 0.106796E+10 |
December | 0.229948E+09 | 0.00 | 0.229948E+09 | 43308148.66 | 0.137606E+10 |
Annual Sum or Average | 0.475577E+10 | 93209170.84 | 0.466256E+10 | 0.621537E+10 | 0.884764E+10 |
Minimum of Months | 0.229948E+09 | 0.00 | 0.229948E+09 | 43164136.11 | 0.161508E+09 |
Maximum of Months | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.115122E+10 | 0.163147E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 43164699.48 | 0.163157E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.122948E+09 | 0.118958E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.314877E+09 | 0.794225E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.562838E+09 | 0.592004E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.836017E+09 | 0.399264E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.111855E+10 | 0.252889E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.115127E+10 | 0.188615E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.104373E+10 | 0.161516E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.574284E+09 | 0.376086E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.266895E+09 | 0.818253E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.137740E+09 | 0.106803E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 43308091.03 | 0.137615E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.621563E+10 | 0.884817E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 43164699.48 | 0.161516E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.115127E+10 | 0.163157E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 43164699.48 | 0.163157E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.122948E+09 | 0.118958E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.314877E+09 | 0.794225E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.562838E+09 | 0.592004E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.836017E+09 | 0.399264E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.111855E+10 | 0.252889E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.115127E+10 | 0.188615E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.104373E+10 | 0.161516E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.574284E+09 | 0.376086E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.266895E+09 | 0.818253E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.137740E+09 | 0.106803E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 43308091.03 | 0.137615E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.621563E+10 | 0.884817E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 43164699.48 | 0.161516E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.115127E+10 | 0.163157E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105104E+10 | 0.474071E+09 | 0.576970E+09 | 0.765732E+09 | 0.282959E+10 |
February | 0.119680E+10 | 0.643031E+09 | 0.553772E+09 | 0.120920E+10 | 0.208912E+10 |
March | 0.166704E+10 | 0.758884E+09 | 0.908160E+09 | 0.199098E+10 | 0.145339E+10 |
April | 0.195086E+10 | 0.889537E+09 | 0.106132E+10 | 0.280041E+10 | 0.111881E+10 |
May | 0.221359E+10 | 0.936093E+09 | 0.127750E+10 | 0.348108E+10 | 0.791856E+09 |
June | 0.221789E+10 | 0.929567E+09 | 0.128832E+10 | 0.393698E+10 | 0.506871E+09 |
July | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.409089E+10 | 0.384365E+09 |
August | 0.204393E+10 | 0.810897E+09 | 0.123303E+10 | 0.379762E+10 | 0.329403E+09 |
September | 0.162564E+10 | 0.720278E+09 | 0.905366E+09 | 0.260936E+10 | 0.719628E+09 |
October | 0.143304E+10 | 0.745643E+09 | 0.687397E+09 | 0.184507E+10 | 0.149578E+10 |
November | 0.110877E+10 | 0.502044E+09 | 0.606724E+09 | 0.110136E+10 | 0.188879E+10 |
December | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.765419E+09 | 0.239247E+10 |
Annual Sum or Average | 0.197356E+11 | 0.880189E+10 | 0.109338E+11 | 0.283941E+11 | 0.160001E+11 |
Minimum of Months | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.765419E+09 | 0.329403E+09 |
Maximum of Months | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.409089E+10 | 0.282959E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41557201.42 | 18744328.32 | 22812873.10 | 30276350.32 | 0.111880E+09 |
February | 47320506.07 | 25424863.36 | 21895642.72 | 47810563.69 | 82601999.37 |
March | 65913438.86 | 30005591.80 | 35907847.06 | 78721746.65 | 57465741.88 |
April | 77135194.26 | 35171493.49 | 41963700.77 | 0.110726E+09 | 44236930.68 |
May | 87523548.73 | 37012286.17 | 50511262.56 | 0.137639E+09 | 31309279.20 |
June | 87693210.88 | 36754233.49 | 50938977.38 | 0.155665E+09 | 20041238.17 |
July | 88354573.77 | 37145363.44 | 51209210.33 | 0.161750E+09 | 15197436.83 |
August | 80815226.94 | 32062140.92 | 48753086.02 | 0.150154E+09 | 13024314.86 |
September | 64276518.48 | 28479146.03 | 35797372.45 | 0.103172E+09 | 28453424.41 |
October | 56661118.88 | 29482041.05 | 27179077.83 | 72952406.75 | 59141930.92 |
November | 43839703.36 | 19850374.49 | 23989328.87 | 43546832.04 | 74681163.40 |
December | 39239425.34 | 17886781.13 | 21352644.21 | 30263961.63 | 94595969.79 |
Annual Sum or Average | 0.780330E+09 | 0.348019E+09 | 0.432311E+09 | 0.112268E+10 | 0.632629E+09 |
Minimum of Months | 39239425.34 | 17886781.13 | 21352644.21 | 30263961.63 | 13024314.86 |
Maximum of Months | 88354573.77 | 37145363.44 | 51209210.33 | 0.161750E+09 | 0.111880E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.155704E+10 | 0.139698E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.143029E+10 | 0.107834E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.155813E+10 | 0.809795E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126870E+10 | 0.627514E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111613E+10 | 0.426304E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.116976E+10 | 0.269086E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.127727E+10 | 0.197926E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.153695E+10 | 0.175605E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138548E+10 | 0.393386E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.179040E+10 | 0.819763E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.167619E+10 | 0.101911E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.161615E+10 | 0.123765E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.173825E+11 | 0.845145E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111613E+10 | 0.175605E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.179040E+10 | 0.139698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.155704E+10 | 0.139698E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.143029E+10 | 0.107834E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.155813E+10 | 0.809795E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126870E+10 | 0.627514E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111613E+10 | 0.426304E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.116976E+10 | 0.269086E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.127727E+10 | 0.197926E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.153695E+10 | 0.175605E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138548E+10 | 0.393386E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.179040E+10 | 0.819763E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.167619E+10 | 0.101911E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.161615E+10 | 0.123765E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.173825E+11 | 0.845145E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111613E+10 | 0.175605E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.179040E+10 | 0.139698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133029E+10 | 0.927469E+09 | 0.402817E+09 | 0.155694E+10 | 0.139689E+10 |
February | 0.112145E+10 | 0.751735E+09 | 0.369713E+09 | 0.143020E+10 | 0.107827E+10 |
March | 0.111662E+10 | 0.581915E+09 | 0.534708E+09 | 0.155804E+10 | 0.809744E+09 |
April | 0.809302E+09 | 0.263443E+09 | 0.545859E+09 | 0.126862E+10 | 0.627474E+09 |
May | 0.675681E+09 | 78531585.46 | 0.597149E+09 | 0.111606E+10 | 0.426277E+09 |
June | 0.604586E+09 | 33642425.56 | 0.570944E+09 | 0.116968E+10 | 0.269069E+09 |
July | 0.631599E+09 | 47095045.70 | 0.584504E+09 | 0.127719E+10 | 0.197914E+09 |
August | 0.754082E+09 | 0.140864E+09 | 0.613218E+09 | 0.153685E+10 | 0.175594E+09 |
September | 0.802550E+09 | 0.298505E+09 | 0.504045E+09 | 0.138539E+10 | 0.393361E+09 |
October | 0.120225E+10 | 0.778815E+09 | 0.423434E+09 | 0.179029E+10 | 0.819711E+09 |
November | 0.125168E+10 | 0.830591E+09 | 0.421088E+09 | 0.167609E+10 | 0.101904E+10 |
December | 0.131129E+10 | 0.922503E+09 | 0.388791E+09 | 0.161605E+10 | 0.123758E+10 |
Annual Sum or Average | 0.116114E+11 | 0.565511E+10 | 0.595627E+10 | 0.173814E+11 | 0.845092E+10 |
Minimum of Months | 0.604586E+09 | 33642425.56 | 0.369713E+09 | 0.111606E+10 | 0.175594E+09 |
Maximum of Months | 0.133029E+10 | 0.927469E+09 | 0.613218E+09 | 0.179029E+10 | 0.139689E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107957E+10 | 0.500778E+09 | 0.578790E+09 | 0.895896E+09 | 0.294690E+10 |
February | 0.111940E+10 | 0.523386E+09 | 0.596015E+09 | 0.120438E+10 | 0.221234E+10 |
March | 0.182671E+10 | 0.882705E+09 | 0.944005E+09 | 0.237066E+10 | 0.157636E+10 |
April | 0.198873E+10 | 0.910029E+09 | 0.107870E+10 | 0.295166E+10 | 0.122414E+10 |
May | 0.206535E+10 | 0.782478E+09 | 0.128288E+10 | 0.332092E+10 | 0.863061E+09 |
June | 0.210193E+10 | 0.808598E+09 | 0.129333E+10 | 0.378306E+10 | 0.559559E+09 |
July | 0.204868E+10 | 0.759579E+09 | 0.128910E+10 | 0.381035E+10 | 0.412356E+09 |
August | 0.200742E+10 | 0.750692E+09 | 0.125673E+10 | 0.375920E+10 | 0.363746E+09 |
September | 0.158274E+10 | 0.659277E+09 | 0.923461E+09 | 0.256861E+10 | 0.764802E+09 |
October | 0.145703E+10 | 0.756357E+09 | 0.700675E+09 | 0.200193E+10 | 0.161801E+10 |
November | 0.112531E+10 | 0.505094E+09 | 0.620213E+09 | 0.128399E+10 | 0.205154E+10 |
December | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.848999E+09 | 0.255573E+10 |
Annual Sum or Average | 0.193622E+11 | 0.825858E+10 | 0.111036E+11 | 0.287996E+11 | 0.171485E+11 |
Minimum of Months | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.848999E+09 | 0.363746E+09 |
Maximum of Months | 0.210193E+10 | 0.910029E+09 | 0.129333E+10 | 0.381035E+10 | 0.294690E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42685035.43 | 19800245.05 | 22884790.38 | 35422756.42 | 0.116518E+09 |
February | 44259987.63 | 20694142.70 | 23565844.93 | 47620010.45 | 87473786.09 |
March | 72226267.00 | 34901238.65 | 37325028.36 | 93733617.38 | 62327824.06 |
April | 78632209.33 | 35981626.23 | 42650583.10 | 0.116706E+09 | 48401453.91 |
May | 81662019.58 | 30938378.45 | 50723641.13 | 0.131306E+09 | 34124629.29 |
June | 83108020.92 | 31971121.65 | 51136899.27 | 0.149578E+09 | 22124450.21 |
July | 81002876.45 | 30032981.75 | 50969894.70 | 0.150657E+09 | 16304167.84 |
August | 79371262.08 | 29681575.71 | 49689686.37 | 0.148635E+09 | 14382159.23 |
September | 62579864.35 | 26067143.10 | 36512721.25 | 0.101560E+09 | 30239561.54 |
October | 57609595.62 | 29905591.65 | 27704003.97 | 79154269.44 | 63974594.89 |
November | 44493501.38 | 19970895.60 | 24522605.78 | 50767767.20 | 81115939.53 |
December | 37930402.25 | 16590743.33 | 21339658.92 | 33568497.68 | 0.101051E+09 |
Annual Sum or Average | 0.765561E+09 | 0.326536E+09 | 0.439025E+09 | 0.113871E+10 | 0.678038E+09 |
Minimum of Months | 37930402.25 | 16590743.33 | 21339658.92 | 33568497.68 | 14382159.23 |
Maximum of Months | 83108020.92 | 35981626.23 | 51136899.27 | 0.150657E+09 | 0.116518E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.122397E+09 | 0.492086E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.340357E+09 | 0.364749E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.841143E+09 | 0.254798E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.153951E+10 | 0.196089E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.238914E+10 | 0.131767E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.329801E+10 | 0.805689E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.340949E+10 | 0.599698E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.311026E+10 | 0.501242E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.172581E+10 | 0.109771E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.812687E+09 | 0.236596E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.430047E+09 | 0.309609E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.128268E+09 | 0.403309E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.181471E+11 | 0.268944E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.122397E+09 | 0.501242E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.340949E+10 | 0.492086E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.782104E+09 | 0.293210E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.122738E+10 | 0.218779E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.200085E+10 | 0.155941E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.282996E+10 | 0.122754E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.355389E+10 | 0.862827E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.406034E+10 | 0.535524E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.423097E+10 | 0.400708E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.393795E+10 | 0.332095E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.271869E+10 | 0.700940E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.193273E+10 | 0.145708E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.117129E+10 | 0.185114E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.797694E+09 | 0.239659E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.292438E+11 | 0.164437E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.782104E+09 | 0.332095E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.423097E+10 | 0.293210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.457065E+10 | 0.414450E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.419577E+10 | 0.323264E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.453540E+10 | 0.249432E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.365871E+10 | 0.202697E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.322944E+10 | 0.139890E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.344993E+10 | 0.860023E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.378972E+10 | 0.626710E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.459735E+10 | 0.526029E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.415228E+10 | 0.112624E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.535717E+10 | 0.230373E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.501869E+10 | 0.286317E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.479995E+10 | 0.354138E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.513551E+11 | 0.251446E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.322944E+10 | 0.526029E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.535717E+10 | 0.414450E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.910915E+09 | 0.305279E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.122069E+10 | 0.232135E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.239688E+10 | 0.168802E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.298758E+10 | 0.134046E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.339266E+10 | 0.941530E+09 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.390008E+10 | 0.592271E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.393964E+10 | 0.432216E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.389901E+10 | 0.366613E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.267768E+10 | 0.747122E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.209311E+10 | 0.157951E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.135078E+10 | 0.202179E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.878540E+09 | 0.256986E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.296476E+11 | 0.176535E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.878540E+09 | 0.366613E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.393964E+10 | 0.305279E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.89 | 1752.08 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 147.09 | 1431.67 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 326.28 | 891.09 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 601.76 | 718.18 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 893.05 | 473.12 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1266.60 | 303.57 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1263.50 | 219.80 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1152.67 | 183.36 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 670.46 | 396.69 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 317.53 | 815.30 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 185.03 | 1102.74 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 54.78 | 1398.23 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 579.79 | 803.96 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 49.89 | 183.36 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1266.60 | 1752.08 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.15 | 1043.22 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 516.72 | 858.67 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 757.36 | 549.05 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1096.48 | 453.22 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1325.83 | 312.07 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1561.19 | 202.55 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1572.27 | 146.91 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1463.38 | 121.69 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1050.91 | 255.30 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 732.20 | 507.21 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 470.63 | 662.92 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 309.99 | 831.63 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 931.98 | 493.50 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 301.15 | 121.69 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1572.27 | 1043.22 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1726.77 | 1469.50 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1749.33 | 1264.87 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1706.16 | 875.21 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1417.35 | 743.81 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1204.80 | 501.58 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1324.22 | 322.36 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1405.20 | 228.43 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1706.97 | 191.83 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1604.46 | 408.90 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 2012.50 | 800.52 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1962.40 | 1024.08 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1816.65 | 1228.67 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1636.12 | 752.22 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1204.80 | 191.83 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 2012.50 | 1469.50 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 345.53 | 1085.42 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 509.43 | 910.45 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 901.78 | 591.66 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1157.20 | 491.38 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1267.33 | 337.11 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1500.31 | 221.54 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1465.53 | 157.04 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1450.46 | 133.50 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1037.20 | 270.00 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 789.75 | 546.63 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 533.94 | 722.80 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 336.07 | 892.52 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 943.49 | 528.01 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 336.07 | 133.50 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1500.31 | 1085.42 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 48.35 | 1827.44 | 278.62 | 0.00 | 278.62 | 0.00 | 0.00 |
February | 152.46 | 1475.14 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 352.68 | 889.57 | 433.57 | 0.00 | 433.57 | 0.00 | 0.00 |
April | 651.42 | 685.18 | 524.45 | 2.33 | 522.12 | 0.00 | 0.00 |
May | 936.39 | 447.20 | 627.23 | 20.02 | 607.21 | 0.00 | 0.00 |
June | 1294.60 | 292.69 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
July | 1289.49 | 211.26 | 651.30 | 31.66 | 619.64 | 0.00 | 0.00 |
August | 1169.04 | 180.91 | 579.22 | 6.31 | 572.91 | 0.00 | 0.00 |
September | 664.67 | 435.28 | 437.84 | 0.06 | 437.77 | 0.00 | 0.00 |
October | 298.94 | 916.48 | 332.90 | 0.00 | 332.90 | 0.00 | 0.00 |
November | 159.42 | 1236.12 | 297.93 | 0.00 | 297.93 | 0.00 | 0.00 |
December | 48.51 | 1541.35 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 591.28 | 841.70 | 452.43 | 8.87 | 443.56 | 0.00 | 0.00 |
Minimum of Months | 48.35 | 180.91 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1294.60 | 1827.44 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 297.20 | 1098.22 | 407.93 | 184.00 | 223.93 | 0.00 | 0.00 |
February | 519.60 | 897.70 | 514.27 | 276.31 | 237.96 | 0.00 | 0.00 |
March | 772.74 | 564.09 | 647.01 | 294.54 | 352.47 | 0.00 | 0.00 |
April | 1123.12 | 448.71 | 782.41 | 356.75 | 425.65 | 0.00 | 0.00 |
May | 1351.08 | 307.33 | 859.14 | 363.32 | 495.82 | 0.00 | 0.00 |
June | 1578.95 | 203.28 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
July | 1587.75 | 149.18 | 867.30 | 364.62 | 502.67 | 0.00 | 0.00 |
August | 1473.93 | 127.85 | 793.29 | 314.72 | 478.56 | 0.00 | 0.00 |
September | 1046.50 | 288.61 | 651.98 | 288.87 | 363.10 | 0.00 | 0.00 |
October | 716.11 | 580.54 | 556.19 | 289.40 | 266.79 | 0.00 | 0.00 |
November | 441.71 | 757.51 | 444.68 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 297.07 | 928.56 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 935.97 | 527.42 | 650.56 | 290.14 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 297.07 | 127.85 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1587.75 | 1098.22 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1743.95 | 1564.68 | 1490.08 | 1038.88 | 451.20 | 0.00 | 0.00 |
February | 1773.64 | 1337.20 | 1390.74 | 932.25 | 458.49 | 0.00 | 0.00 |
March | 1745.19 | 907.01 | 1250.75 | 651.81 | 598.94 | 0.00 | 0.00 |
April | 1468.37 | 726.27 | 936.73 | 304.92 | 631.81 | 0.00 | 0.00 |
May | 1250.12 | 477.48 | 756.84 | 87.96 | 668.88 | 0.00 | 0.00 |
June | 1353.86 | 311.44 | 699.78 | 38.94 | 660.84 | 0.00 | 0.00 |
July | 1430.60 | 221.69 | 707.47 | 52.75 | 654.71 | 0.00 | 0.00 |
August | 1721.45 | 196.69 | 844.66 | 157.78 | 686.88 | 0.00 | 0.00 |
September | 1603.53 | 455.30 | 928.92 | 345.51 | 583.41 | 0.00 | 0.00 |
October | 2005.33 | 918.17 | 1346.66 | 872.37 | 474.30 | 0.00 | 0.00 |
November | 1940.00 | 1179.50 | 1448.76 | 961.37 | 487.39 | 0.00 | 0.00 |
December | 1810.16 | 1386.23 | 1468.80 | 1033.31 | 435.49 | 0.00 | 0.00 |
Annual Sum or Average | 1653.55 | 803.96 | 1104.63 | 537.99 | 566.64 | 0.00 | 0.00 |
Minimum of Months | 1250.12 | 196.69 | 699.78 | 38.94 | 435.49 | 0.00 | 0.00 |
Maximum of Months | 2005.33 | 1564.68 | 1490.08 | 1038.88 | 686.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.71 | 1143.75 | 419.00 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 517.53 | 950.65 | 481.01 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 920.10 | 611.82 | 708.98 | 342.59 | 366.39 | 0.00 | 0.00 |
April | 1183.78 | 490.95 | 797.59 | 364.97 | 432.62 | 0.00 | 0.00 |
May | 1288.91 | 334.97 | 801.60 | 303.69 | 497.91 | 0.00 | 0.00 |
June | 1517.22 | 224.42 | 842.99 | 324.29 | 518.70 | 0.00 | 0.00 |
July | 1478.87 | 160.04 | 795.13 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1459.02 | 141.18 | 779.12 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1030.16 | 306.73 | 634.77 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 776.99 | 627.98 | 565.50 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 514.95 | 822.78 | 451.31 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 329.51 | 991.93 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 949.34 | 565.28 | 638.25 | 272.23 | 366.01 | 0.00 | 0.00 |
Minimum of Months | 329.51 | 141.18 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1517.22 | 1143.75 | 842.99 | 364.97 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.70 | 1837.24 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 140.69 | 1507.72 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 314.05 | 951.31 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 593.95 | 756.51 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 892.00 | 491.96 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1272.38 | 310.84 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1272.96 | 223.90 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1161.24 | 187.14 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 665.82 | 423.50 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 303.42 | 883.35 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 165.91 | 1194.48 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 47.89 | 1505.78 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 575.44 | 852.81 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 45.70 | 187.14 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1272.96 | 1837.24 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 292.00 | 1094.72 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 507.35 | 904.34 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 747.03 | 582.22 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1091.81 | 473.59 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1326.87 | 322.14 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1566.49 | 206.61 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1579.66 | 149.61 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1470.26 | 123.99 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1048.88 | 270.42 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 721.60 | 544.01 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 451.89 | 714.18 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 297.82 | 894.78 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 927.32 | 521.43 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 292.00 | 123.99 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1579.66 | 1094.72 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1706.49 | 1547.38 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1734.36 | 1336.24 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1693.32 | 931.27 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1411.54 | 782.01 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1205.73 | 522.29 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1330.99 | 331.80 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1414.92 | 233.99 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1716.45 | 196.40 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1601.96 | 434.50 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 2000.14 | 860.11 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1936.22 | 1104.62 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1792.10 | 1322.20 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1628.46 | 797.33 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1205.73 | 196.40 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 2000.14 | 1547.38 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 340.10 | 1139.78 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 504.58 | 959.55 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 894.89 | 630.23 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1152.62 | 517.15 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1266.68 | 351.53 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1504.66 | 228.50 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1470.89 | 161.37 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1455.72 | 136.88 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1033.06 | 288.24 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 781.48 | 589.72 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 521.13 | 780.01 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 328.01 | 959.48 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 940.12 | 559.79 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 328.01 | 136.88 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1504.66 | 1139.78 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133633E+09 | 0.469277E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.355834E+09 | 0.346350E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.873918E+09 | 0.238668E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.155975E+10 | 0.186152E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.239195E+10 | 0.126721E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.328303E+10 | 0.786860E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.338417E+10 | 0.588711E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.308731E+10 | 0.491119E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.173782E+10 | 0.102823E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.850470E+09 | 0.218371E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.479603E+09 | 0.285831E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.146732E+09 | 0.374503E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182842E+11 | 0.253537E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133633E+09 | 0.491119E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.338417E+10 | 0.469277E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.806589E+09 | 0.279416E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.125004E+10 | 0.207730E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.202851E+10 | 0.147058E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.284207E+10 | 0.117475E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.355111E+10 | 0.835857E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.404660E+10 | 0.525015E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.421116E+10 | 0.393475E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.391952E+10 | 0.325930E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.272395E+10 | 0.661725E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.196113E+10 | 0.135852E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.121986E+10 | 0.171828E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.830278E+09 | 0.222744E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293908E+11 | 0.155630E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.806589E+09 | 0.325930E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421116E+10 | 0.279416E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462497E+10 | 0.393590E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.423197E+10 | 0.305996E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.456978E+10 | 0.234415E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.367377E+10 | 0.192795E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.322693E+10 | 0.134344E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.343238E+10 | 0.835570E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.376368E+10 | 0.611827E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.457195E+10 | 0.513806E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.415875E+10 | 0.105987E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.539029E+10 | 0.214412E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.508653E+10 | 0.265441E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.486572E+10 | 0.329087E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.515967E+11 | 0.237219E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322693E+10 | 0.513806E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.539029E+10 | 0.393590E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.925477E+09 | 0.290718E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.123241E+10 | 0.220256E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.241533E+10 | 0.158471E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.299946E+10 | 0.127366E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.339442E+10 | 0.902917E+09 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.388881E+10 | 0.574230E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.392526E+10 | 0.420624E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.388491E+10 | 0.357570E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.268841E+10 | 0.699830E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.211527E+10 | 0.146409E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.138397E+10 | 0.187350E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.900122E+09 | 0.239054E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.297539E+11 | 0.166514E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.900122E+09 | 0.357570E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.392526E+10 | 0.290718E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129494E+09 | 0.489461E+10 | 0.746261E+09 | 0.00 | 0.746261E+09 | 0.00 | 0.00 |
February | 0.368842E+09 | 0.356865E+10 | 0.747110E+09 | 0.00 | 0.747110E+09 | 0.00 | 0.00 |
March | 0.944621E+09 | 0.238263E+10 | 0.116128E+10 | 0.00 | 0.116128E+10 | 0.00 | 0.00 |
April | 0.168849E+10 | 0.177598E+10 | 0.135937E+10 | 6029144.79 | 0.135334E+10 | 0.00 | 0.00 |
May | 0.250802E+10 | 0.119777E+10 | 0.167998E+10 | 53615172.89 | 0.162636E+10 | 0.00 | 0.00 |
June | 0.335560E+10 | 0.758654E+09 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
July | 0.345376E+10 | 0.565837E+09 | 0.174443E+10 | 84797223.43 | 0.165963E+10 | 0.00 | 0.00 |
August | 0.313115E+10 | 0.484539E+09 | 0.155138E+10 | 16899738.46 | 0.153448E+10 | 0.00 | 0.00 |
September | 0.172283E+10 | 0.112824E+10 | 0.113487E+10 | 159756.68 | 0.113471E+10 | 0.00 | 0.00 |
October | 0.800675E+09 | 0.245471E+10 | 0.891642E+09 | 0.00 | 0.891642E+09 | 0.00 | 0.00 |
November | 0.413218E+09 | 0.320402E+10 | 0.772246E+09 | 0.00 | 0.772246E+09 | 0.00 | 0.00 |
December | 0.129924E+09 | 0.412835E+10 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186466E+11 | 0.265440E+11 | 0.142677E+11 | 0.279633E+09 | 0.139880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129494E+09 | 0.484539E+09 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345376E+10 | 0.489461E+10 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.796008E+09 | 0.294147E+10 | 0.109260E+10 | 0.492815E+09 | 0.599783E+09 | 0.00 | 0.00 |
February | 0.125701E+10 | 0.217172E+10 | 0.124412E+10 | 0.668456E+09 | 0.575668E+09 | 0.00 | 0.00 |
March | 0.206971E+10 | 0.151086E+10 | 0.173296E+10 | 0.788890E+09 | 0.944068E+09 | 0.00 | 0.00 |
April | 0.291114E+10 | 0.116305E+10 | 0.202799E+10 | 0.924709E+09 | 0.110329E+10 | 0.00 | 0.00 |
May | 0.361872E+10 | 0.823165E+09 | 0.230112E+10 | 0.973106E+09 | 0.132801E+10 | 0.00 | 0.00 |
June | 0.409264E+10 | 0.526913E+09 | 0.230558E+10 | 0.966321E+09 | 0.133926E+10 | 0.00 | 0.00 |
July | 0.425264E+10 | 0.399562E+09 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
August | 0.394777E+10 | 0.342428E+09 | 0.212475E+10 | 0.842959E+09 | 0.128179E+10 | 0.00 | 0.00 |
September | 0.271253E+10 | 0.748081E+09 | 0.168992E+10 | 0.748757E+09 | 0.941164E+09 | 0.00 | 0.00 |
October | 0.191802E+10 | 0.155493E+10 | 0.148970E+10 | 0.775125E+09 | 0.714577E+09 | 0.00 | 0.00 |
November | 0.114491E+10 | 0.196347E+10 | 0.115261E+10 | 0.521895E+09 | 0.630714E+09 | 0.00 | 0.00 |
December | 0.795683E+09 | 0.248706E+10 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295168E+11 | 0.166327E+11 | 0.205160E+11 | 0.914990E+10 | 0.113661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.795683E+09 | 0.342428E+09 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Maximum of Months | 0.425264E+10 | 0.294147E+10 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.467101E+10 | 0.419085E+10 | 0.399103E+10 | 0.278252E+10 | 0.120850E+10 | 0.00 | 0.00 |
February | 0.429078E+10 | 0.323495E+10 | 0.336449E+10 | 0.225530E+10 | 0.110919E+10 | 0.00 | 0.00 |
March | 0.467431E+10 | 0.242933E+10 | 0.335001E+10 | 0.174582E+10 | 0.160419E+10 | 0.00 | 0.00 |
April | 0.380601E+10 | 0.188250E+10 | 0.242801E+10 | 0.790362E+09 | 0.163765E+10 | 0.00 | 0.00 |
May | 0.334832E+10 | 0.127889E+10 | 0.202713E+10 | 0.235605E+09 | 0.179152E+10 | 0.00 | 0.00 |
June | 0.350920E+10 | 0.807242E+09 | 0.181384E+10 | 0.100932E+09 | 0.171290E+10 | 0.00 | 0.00 |
July | 0.383172E+10 | 0.593766E+09 | 0.189488E+10 | 0.141291E+09 | 0.175358E+10 | 0.00 | 0.00 |
August | 0.461074E+10 | 0.526804E+09 | 0.226234E+10 | 0.422609E+09 | 0.183973E+10 | 0.00 | 0.00 |
September | 0.415635E+10 | 0.118013E+10 | 0.240775E+10 | 0.895553E+09 | 0.151220E+10 | 0.00 | 0.00 |
October | 0.537109E+10 | 0.245924E+10 | 0.360690E+10 | 0.233654E+10 | 0.127035E+10 | 0.00 | 0.00 |
November | 0.502847E+10 | 0.305725E+10 | 0.375519E+10 | 0.249188E+10 | 0.126332E+10 | 0.00 | 0.00 |
December | 0.484834E+10 | 0.371288E+10 | 0.393405E+10 | 0.276763E+10 | 0.116642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.521463E+11 | 0.253538E+11 | 0.348356E+11 | 0.169660E+11 | 0.178696E+11 | 0.00 | 0.00 |
Minimum of Months | 0.334832E+10 | 0.526804E+09 | 0.181384E+10 | 0.100932E+09 | 0.110919E+10 | 0.00 | 0.00 |
Maximum of Months | 0.537109E+10 | 0.419085E+10 | 0.399103E+10 | 0.278252E+10 | 0.183973E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.931319E+09 | 0.306342E+10 | 0.112225E+10 | 0.520578E+09 | 0.601675E+09 | 0.00 | 0.00 |
February | 0.125200E+10 | 0.229981E+10 | 0.116366E+10 | 0.544080E+09 | 0.619581E+09 | 0.00 | 0.00 |
March | 0.246440E+10 | 0.163869E+10 | 0.189894E+10 | 0.917606E+09 | 0.981330E+09 | 0.00 | 0.00 |
April | 0.306836E+10 | 0.127254E+10 | 0.206736E+10 | 0.946011E+09 | 0.112135E+10 | 0.00 | 0.00 |
May | 0.345222E+10 | 0.897186E+09 | 0.214702E+10 | 0.813416E+09 | 0.133360E+10 | 0.00 | 0.00 |
June | 0.393263E+10 | 0.581684E+09 | 0.218503E+10 | 0.840569E+09 | 0.134446E+10 | 0.00 | 0.00 |
July | 0.396101E+10 | 0.428660E+09 | 0.212969E+10 | 0.789612E+09 | 0.134007E+10 | 0.00 | 0.00 |
August | 0.390783E+10 | 0.378128E+09 | 0.208679E+10 | 0.780373E+09 | 0.130642E+10 | 0.00 | 0.00 |
September | 0.267017E+10 | 0.795042E+09 | 0.164532E+10 | 0.685344E+09 | 0.959973E+09 | 0.00 | 0.00 |
October | 0.208108E+10 | 0.168198E+10 | 0.151464E+10 | 0.786263E+09 | 0.728379E+09 | 0.00 | 0.00 |
November | 0.133476E+10 | 0.213265E+10 | 0.116980E+10 | 0.525065E+09 | 0.644736E+09 | 0.00 | 0.00 |
December | 0.882567E+09 | 0.265678E+10 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299384E+11 | 0.178266E+11 | 0.201277E+11 | 0.858511E+10 | 0.115426E+11 | 0.00 | 0.00 |
Minimum of Months | 0.882567E+09 | 0.378128E+09 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Maximum of Months | 0.396101E+10 | 0.306342E+10 | 0.218503E+10 | 0.946011E+09 | 0.134446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122397E+09 | 0.492086E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.340357E+09 | 0.364749E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.841143E+09 | 0.254798E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.153951E+10 | 0.196089E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.238914E+10 | 0.131767E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.329801E+10 | 0.805689E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.340949E+10 | 0.599698E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.311026E+10 | 0.501242E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.172581E+10 | 0.109771E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.812687E+09 | 0.236596E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.430047E+09 | 0.309609E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.128268E+09 | 0.403309E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181471E+11 | 0.268944E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122397E+09 | 0.501242E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340949E+10 | 0.492086E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.782104E+09 | 0.293210E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.122738E+10 | 0.218779E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.200085E+10 | 0.155941E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.282996E+10 | 0.122754E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.355389E+10 | 0.862827E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.406034E+10 | 0.535524E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.423097E+10 | 0.400708E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.393795E+10 | 0.332095E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.271869E+10 | 0.700940E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.193273E+10 | 0.145708E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.117129E+10 | 0.185114E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.797694E+09 | 0.239659E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292438E+11 | 0.164437E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.782104E+09 | 0.332095E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.423097E+10 | 0.293210E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457065E+10 | 0.414450E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.419577E+10 | 0.323264E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.453540E+10 | 0.249432E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.365871E+10 | 0.202697E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.322944E+10 | 0.139890E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.344993E+10 | 0.860023E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.378972E+10 | 0.626710E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.459735E+10 | 0.526029E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.415228E+10 | 0.112624E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.535717E+10 | 0.230373E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.501869E+10 | 0.286317E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.479995E+10 | 0.354138E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.513551E+11 | 0.251446E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322944E+10 | 0.526029E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535717E+10 | 0.414450E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.910915E+09 | 0.305279E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.122069E+10 | 0.232135E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.239688E+10 | 0.168802E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.298758E+10 | 0.134046E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.339266E+10 | 0.941530E+09 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.390008E+10 | 0.592271E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.393964E+10 | 0.432216E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.389901E+10 | 0.366613E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.267768E+10 | 0.747122E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.209311E+10 | 0.157951E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.135078E+10 | 0.202179E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.878540E+09 | 0.256986E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296476E+11 | 0.176535E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.878540E+09 | 0.366613E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.393964E+10 | 0.305279E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.501349E+10 | -0.427287E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -740616522.0 | 58.98 | 0.00 | 0.00 |
February | 0.454563E+10 | -0.389171E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -653922869.3 | 58.98 | 0.00 | 0.00 |
March | 0.515443E+10 | -0.445088E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703546729.0 | 58.98 | 0.00 | 0.00 |
April | 0.442293E+10 | -0.374958E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673347688.5 | 58.98 | 0.00 | 0.00 |
May | 0.439050E+10 | -0.370002E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690484915.3 | 58.98 | 0.00 | 0.00 |
June | 0.404928E+10 | -0.338185E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667430121.6 | 58.98 | 0.00 | 0.00 |
July | 0.370934E+10 | -0.302129E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688050723.3 | 58.98 | 0.00 | 0.00 |
August | 0.402003E+10 | -0.333089E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689149325.7 | 58.98 | 0.00 | 0.00 |
September | 0.381141E+10 | -0.314526E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666149266.5 | 58.98 | 0.00 | 0.00 |
October | 0.421054E+10 | -0.351556E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694981335.7 | 58.98 | 0.00 | 0.00 |
November | 0.444475E+10 | -0.376449E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -680260658.5 | 58.98 | 0.00 | 0.00 |
December | 0.471167E+10 | -0.399241E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719255243.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.524840E+11 | -0.442168E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826720E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.370934E+10 | -0.445088E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -740616522.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.515443E+10 | -0.302129E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -653922869.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5944.13 | 33.56 | 265.83 | 271.50 | 1657.27 | 25.59 | 178.50 | 250.33 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6962.61 | 33.59 | 230.83 | 246.83 | 1109.82 | 19.25 | 74.67 | 210.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1639.75 | 18.12 | 6.83 | 317.83 | 961.50 | 20.22 | 124.00 | 283.00 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:39 | 1350.13 | 17.76 | 0.00 | 324.17 | 773.30 | 19.91 | 104.50 | 280.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1220.07 | 17.94 | 0.00 | 358.50 | 683.84 | 20.09 | 89.67 | 310.67 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1133.53 | 17.68 | 0.00 | 358.67 | 641.54 | 19.85 | 91.67 | 311.00 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1195.26 | 17.85 | 0.00 | 362.50 | 668.51 | 19.99 | 118.50 | 312.83 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1461.06 | 18.48 | 0.00 | 349.33 | 801.51 | 20.60 | 174.83 | 311.50 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:40 | 1564.17 | 18.59 | 6.50 | 307.83 | 880.51 | 20.47 | 122.67 | 268.33 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2832.02 | 23.85 | 119.33 | 291.83 | 1070.85 | 19.63 | 83.17 | 255.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5850.38 | 34.50 | 285.50 | 272.83 | 1203.10 | 24.25 | 167.17 | 252.83 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5602.08 | 34.35 | 269.83 | 267.67 | 1598.52 | 26.54 | 179.50 | 245.17 |
Annual Sum or Average | 4071.00 | 0.52 | 2776.74 | 22.92 | 1184.67 | 3729.50 | 962.96 | 21.19 | 1508.83 | 3292.00 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1133.53 | 17.68 | 0.00 | 246.83 | 641.54 | 19.25 | 74.67 | 210.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6962.61 | 34.50 | 285.50 | 362.50 | 1657.27 | 26.54 | 179.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:09 | 1403.14 | 19.13 | 71.83 | 240.83 | 715.25 | 19.99 | 55.33 | 179.00 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1863.36 | 18.94 | 60.17 | 222.67 | 1030.30 | 21.08 | 50.00 | 177.17 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2242.56 | 20.56 | 105.50 | 309.83 | 881.09 | 20.10 | 47.50 | 267.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2159.60 | 19.96 | 93.33 | 325.00 | 1163.95 | 21.19 | 67.17 | 287.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:10 | 2462.38 | 20.32 | 108.50 | 366.67 | 1018.16 | 20.21 | 50.17 | 327.67 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2486.06 | 20.25 | 110.67 | 368.50 | 1042.13 | 20.91 | 64.00 | 332.50 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2460.73 | 20.28 | 105.50 | 371.83 | 1042.79 | 20.29 | 51.83 | 330.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2255.62 | 20.63 | 102.17 | 350.83 | 1190.30 | 21.92 | 73.50 | 313.33 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2082.99 | 19.39 | 67.33 | 303.17 | 1122.96 | 21.64 | 55.33 | 259.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-08:20 | 2490.79 | 20.88 | 90.83 | 267.17 | 929.04 | 19.93 | 43.83 | 214.83 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1701.57 | 21.17 | 97.00 | 246.83 | 918.85 | 22.00 | 75.50 | 200.83 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-07:49 | 1440.43 | 19.73 | 73.33 | 236.67 | 771.34 | 21.42 | 60.17 | 177.50 |
Annual Sum or Average | 4071.00 | 0.53 | 2130.75 | 20.15 | 1086.17 | 3610.00 | 996.80 | 20.87 | 694.33 | 3067.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1403.14 | 18.94 | 60.17 | 222.67 | 715.25 | 19.93 | 43.83 | 177.17 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2490.79 | 21.17 | 110.67 | 371.83 | 1190.30 | 22.00 | 75.50 | 332.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.59 | 0.48 | 01-JAN-11:20 | 500.43 | 14.35 | 0.00 | 211.33 | 302.57 | 16.75 | 0.00 | 89.17 |
February | 263.00 | 0.59 | 0.48 | 01-FEB-13:50 | 531.48 | 14.55 | 0.00 | 190.50 | 330.34 | 16.90 | 0.00 | 111.67 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-09:30 | 678.09 | 16.37 | 0.00 | 299.67 | 413.74 | 18.58 | 0.00 | 226.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:30 | 809.95 | 17.28 | 0.00 | 328.17 | 485.58 | 19.39 | 0.67 | 271.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1012.67 | 20.33 | 51.83 | 382.67 | 584.27 | 20.48 | 66.67 | 342.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1101.66 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:10 | 1110.01 | 20.48 | 53.33 | 384.83 | 617.52 | 21.45 | 145.83 | 348.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 990.02 | 18.23 | 0.00 | 359.33 | 578.27 | 20.31 | 54.67 | 324.83 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 752.92 | 17.08 | 0.00 | 302.50 | 456.60 | 19.19 | 0.00 | 219.83 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 556.20 | 15.08 | 0.00 | 237.00 | 355.94 | 17.47 | 0.00 | 143.83 |
November | 299.00 | 0.58 | 0.48 | 01-NOV-09:00 | 517.80 | 14.66 | 0.00 | 224.67 | 315.06 | 17.00 | 0.00 | 121.50 |
December | 285.17 | 0.59 | 0.48 | 01-DEC-10:20 | 483.52 | 14.43 | 0.00 | 203.50 | 293.36 | 16.87 | 0.00 | 82.83 |
Annual Sum or Average | 4071.00 | 0.54 | 789.00 | 17.35 | 172.00 | 3510.00 | 467.36 | 19.24 | 445.83 | 2646.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 483.52 | 14.35 | 0.00 | 190.50 | 293.36 | 16.75 | 0.00 | 82.83 | |
Maximum of Months | 411.67 | 0.59 | 0.48 | 1110.01 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:00 | 1724.54 | 21.14 | 89.83 | 243.83 | 955.65 | 21.84 | 68.00 | 191.33 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1648.22 | 18.89 | 64.00 | 214.33 | 856.95 | 19.72 | 40.33 | 165.33 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2222.20 | 20.89 | 98.17 | 309.33 | 1182.08 | 21.80 | 72.00 | 266.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2368.78 | 18.68 | 78.67 | 330.67 | 1304.67 | 20.04 | 51.83 | 288.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:30 | 2368.37 | 17.04 | 50.83 | 364.67 | 1008.52 | 18.03 | 0.00 | 325.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2490.05 | 14.72 | 1.67 | 367.50 | 1066.09 | 17.98 | 0.00 | 330.83 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-08:09 | 2471.35 | 17.03 | 52.17 | 367.50 | 1043.28 | 18.02 | 0.00 | 328.00 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:00 | 2423.28 | 19.52 | 89.00 | 352.67 | 1057.45 | 18.72 | 7.67 | 319.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2175.17 | 21.47 | 90.83 | 305.00 | 1149.50 | 22.24 | 62.67 | 256.67 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2351.32 | 20.91 | 92.67 | 262.50 | 902.70 | 19.99 | 42.83 | 210.33 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1596.56 | 19.48 | 80.83 | 248.50 | 857.86 | 21.75 | 68.67 | 200.00 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-10:09 | 1393.57 | 19.37 | 74.17 | 236.50 | 757.14 | 21.35 | 63.33 | 177.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2150.89 | 18.88 | 862.83 | 3603.00 | 1024.87 | 19.93 | 477.33 | 3060.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1393.57 | 14.72 | 1.67 | 214.33 | 757.14 | 17.98 | 0.00 | 165.33 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2490.05 | 21.47 | 98.17 | 367.50 | 1304.67 | 22.24 | 72.00 | 330.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.08 | 33.12 | 258.17 | 269.83 | 1561.52 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.73 | 33.22 | 229.67 | 245.83 | 1060.06 | 18.04 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.16 | 14.23 | 6.67 | 314.67 | 896.80 | 17.63 | 0.50 | 278.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.89 | 14.01 | 0.00 | 321.83 | 731.87 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.51 | 14.26 | 0.00 | 355.83 | 654.37 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.09 | 14.07 | 0.00 | 356.33 | 616.22 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.36 | 14.24 | 0.00 | 359.33 | 640.70 | 17.67 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.63 | 14.86 | 0.00 | 347.33 | 762.74 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.14 | 14.98 | 6.50 | 305.00 | 828.73 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.91 | 21.24 | 117.33 | 290.33 | 988.09 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.91 | 34.09 | 281.17 | 271.67 | 1115.61 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.53 | 32.30 | 249.50 | 263.83 | 1501.05 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.29 | 20.12 | 1149.00 | 3701.83 | 908.51 | 18.87 | 330.17 | 3259.00 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.09 | 14.01 | 0.00 | 245.83 | 616.22 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.73 | 34.09 | 281.17 | 359.33 | 1561.52 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.77 | 18.62 | 71.50 | 239.00 | 684.67 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.50 | 18.44 | 60.17 | 219.33 | 989.09 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.30 | 20.09 | 105.33 | 308.00 | 839.46 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.61 | 19.49 | 93.00 | 322.67 | 1115.83 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.36 | 19.87 | 108.33 | 364.00 | 967.49 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.72 | 19.80 | 110.33 | 366.00 | 992.13 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.59 | 19.83 | 105.33 | 369.00 | 991.41 | 20.11 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.22 | 20.17 | 102.17 | 349.17 | 1140.60 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.73 | 18.89 | 67.33 | 301.33 | 1074.78 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.85 | 20.40 | 90.50 | 265.00 | 884.47 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.27 | 20.71 | 97.00 | 244.33 | 885.48 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.26 | 19.22 | 73.00 | 234.17 | 739.07 | 21.18 | 57.50 | 173.33 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.27 | 19.67 | 1084.00 | 3582.00 | 952.46 | 20.68 | 679.50 | 3015.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.77 | 18.44 | 60.17 | 219.33 | 684.67 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.85 | 20.71 | 110.33 | 369.00 | 1140.60 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.96 | 10.47 | 0.00 | 206.50 | 293.15 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.49 | 10.78 | 0.00 | 185.33 | 320.90 | 14.47 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.86 | 12.86 | 0.00 | 296.67 | 401.31 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.39 | 13.81 | 0.00 | 325.67 | 470.58 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.23 | 17.28 | 51.83 | 380.33 | 573.88 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.26 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.85 | 16.16 | 27.33 | 383.17 | 604.40 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.90 | 14.80 | 0.00 | 357.83 | 557.88 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.98 | 13.77 | 0.00 | 299.67 | 441.99 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.67 | 11.52 | 0.00 | 231.00 | 346.46 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.26 | 10.90 | 0.00 | 219.33 | 305.08 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.99 | 10.51 | 0.00 | 198.00 | 283.90 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.54 | 13.79 | 144.83 | 3468.17 | 453.78 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.99 | 10.47 | 0.00 | 185.33 | 283.90 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.85 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.62 | 20.74 | 89.33 | 240.83 | 922.67 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.52 | 18.47 | 64.00 | 211.67 | 817.05 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.20 | 18.82 | 77.50 | 306.83 | 1133.94 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.77 | 18.21 | 78.50 | 327.83 | 1256.61 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.27 | 16.53 | 50.83 | 361.83 | 961.70 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.94 | 14.17 | 1.67 | 364.17 | 1018.49 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.26 | 16.52 | 52.00 | 365.33 | 995.72 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.84 | 18.89 | 86.50 | 351.17 | 1000.66 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.15 | 19.40 | 75.50 | 301.17 | 1102.03 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.89 | 20.49 | 92.50 | 260.67 | 859.80 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.04 | 19.05 | 80.83 | 245.83 | 823.42 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.65 | 18.95 | 73.83 | 233.83 | 726.36 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.55 | 18.14 | 823.00 | 3571.17 | 980.42 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.65 | 14.17 | 1.67 | 211.67 | 726.36 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.94 | 20.74 | 92.50 | 365.33 | 1256.61 | 22.11 | 72.17 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.03 | 33.12 | 258.17 | 269.83 | 1561.45 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.66 | 33.22 | 229.67 | 245.83 | 1059.99 | 18.05 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.07 | 14.23 | 6.67 | 314.67 | 896.74 | 17.63 | 0.50 | 278.67 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.81 | 14.01 | 0.00 | 321.83 | 731.82 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.44 | 14.26 | 0.00 | 355.83 | 654.32 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.03 | 14.07 | 0.00 | 356.33 | 616.17 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.30 | 14.24 | 0.00 | 359.33 | 640.65 | 17.68 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.54 | 14.86 | 0.00 | 347.33 | 762.68 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.05 | 14.99 | 6.50 | 305.00 | 828.67 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.84 | 21.24 | 117.33 | 290.33 | 988.03 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.86 | 34.09 | 281.17 | 271.67 | 1115.53 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.50 | 32.30 | 249.50 | 263.83 | 1500.98 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.22 | 20.12 | 1149.00 | 3701.83 | 908.45 | 18.87 | 330.17 | 3258.83 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.03 | 14.01 | 0.00 | 245.83 | 616.17 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.66 | 34.09 | 281.17 | 359.33 | 1561.45 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.74 | 18.63 | 71.50 | 239.00 | 684.64 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.48 | 18.44 | 60.17 | 219.33 | 989.06 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.27 | 20.09 | 105.33 | 308.00 | 839.42 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.57 | 19.50 | 93.00 | 322.67 | 1115.78 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.30 | 19.87 | 108.33 | 364.00 | 967.43 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.66 | 19.80 | 110.33 | 366.00 | 992.07 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.53 | 19.84 | 105.33 | 369.00 | 991.34 | 20.12 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.16 | 20.18 | 102.17 | 349.17 | 1140.53 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.69 | 18.90 | 67.33 | 301.33 | 1074.73 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.83 | 20.40 | 90.50 | 265.00 | 884.43 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.24 | 20.71 | 97.00 | 244.33 | 885.44 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.23 | 19.22 | 73.00 | 234.17 | 739.04 | 21.18 | 57.50 | 173.17 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.23 | 19.67 | 1084.00 | 3582.00 | 952.41 | 20.68 | 679.50 | 3015.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.74 | 18.44 | 60.17 | 219.33 | 684.64 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.83 | 20.71 | 110.33 | 369.00 | 1140.53 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.94 | 10.47 | 0.00 | 206.50 | 293.13 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.48 | 10.78 | 0.00 | 185.33 | 320.88 | 14.48 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.84 | 12.86 | 0.00 | 296.67 | 401.28 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.36 | 13.81 | 0.00 | 325.67 | 470.55 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.19 | 17.28 | 51.83 | 380.33 | 573.84 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.22 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.80 | 16.16 | 27.33 | 383.17 | 604.36 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.87 | 14.80 | 0.00 | 357.83 | 557.84 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.96 | 13.78 | 0.00 | 299.67 | 441.96 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.66 | 11.52 | 0.00 | 231.00 | 346.44 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.24 | 10.90 | 0.00 | 219.33 | 305.06 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.98 | 10.51 | 0.00 | 198.00 | 283.88 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.51 | 13.79 | 144.83 | 3468.17 | 453.75 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.98 | 10.47 | 0.00 | 185.33 | 283.88 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.80 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.59 | 20.74 | 89.33 | 240.83 | 922.63 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.50 | 18.47 | 64.00 | 211.67 | 817.01 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.16 | 18.82 | 77.50 | 306.83 | 1133.89 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.72 | 18.21 | 78.50 | 327.83 | 1256.56 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.21 | 16.54 | 50.83 | 361.83 | 961.64 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.88 | 14.17 | 1.67 | 364.17 | 1018.43 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.20 | 16.52 | 52.00 | 365.33 | 995.66 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.78 | 18.89 | 86.50 | 351.17 | 1000.60 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.10 | 19.40 | 75.50 | 301.17 | 1101.97 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.87 | 20.49 | 92.50 | 260.67 | 859.76 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.01 | 19.05 | 80.83 | 245.83 | 823.38 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.63 | 18.95 | 73.83 | 233.83 | 726.32 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.50 | 18.14 | 823.00 | 3571.17 | 980.37 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.63 | 14.17 | 1.67 | 211.67 | 726.32 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.88 | 20.74 | 92.50 | 365.33 | 1256.56 | 22.11 | 72.17 | 328.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.333225E+09 | 25211.95 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18308112.83 | 25211.95 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333225E+09 | 25211.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.491780E+10 | 11289.43 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317011E+10 | 11268.46 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126655E+10 | 11248.31 | 24-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689544E+09 | 11227.87 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183521E+09 | 11185.18 | 11-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27530985.32 | 8417.04 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25726120.99 | 5892.04 | 29-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.581928E+09 | 11247.18 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114730E+10 | 11242.71 | 06-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210052E+10 | 11234.32 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491780E+10 | 11289.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217638E+10 | 8682.31 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119408E+10 | 8682.31 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169122E+09 | 8682.31 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27740855.81 | 8682.31 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19613278.56 | 6997.13 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97918392.01 | 8682.31 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.743801E+09 | 8682.31 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217638E+10 | 8682.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.386583E+10 | 9663.61 | 04-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225231E+10 | 9658.03 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466166E+09 | 9627.29 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104395E+09 | 9617.37 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23508388.14 | 9577.40 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278983E+09 | 9605.39 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153369E+10 | 9612.86 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.852488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386583E+10 | 9663.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230171E+10 | 8763.98 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132283E+10 | 8763.98 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218344E+09 | 8106.07 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39138613.47 | 8763.98 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18571922.77 | 6461.59 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153384E+09 | 8763.98 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.911861E+09 | 8763.98 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230171E+10 | 8763.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332317E+10 | 24285.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146308E+10 | 24285.36 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4172764.92 | 7796.67 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1879548.32 | 3892.54 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67157741.27 | 24285.36 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102260E+10 | 24285.36 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332317E+10 | 24285.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226953E+10 | 12238.64 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126042E+10 | 12182.13 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148878E+09 | 12135.64 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32820295.55 | 12079.18 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66473552.75 | 12106.49 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236931E+09 | 12106.54 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.921407E+09 | 12197.39 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226953E+10 | 12238.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245222E+10 | 9171.91 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136859E+10 | 9171.91 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176446E+09 | 9171.91 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24548427.21 | 9171.91 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129142E+09 | 9171.91 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359702E+09 | 9171.91 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122476E+10 | 9171.91 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245222E+10 | 9171.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375204E+10 | 10407.02 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208374E+10 | 10408.69 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255881E+09 | 10320.36 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42278856.90 | 10271.63 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103117E+09 | 10358.00 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.543600E+09 | 10364.83 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190256E+10 | 10373.86 | 26-DEC-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375204E+10 | 10408.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255051E+10 | 9255.70 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147132E+10 | 9255.70 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242149E+09 | 9255.70 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41389980.35 | 9255.70 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129520E+09 | 8020.18 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468523E+09 | 9255.70 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140162E+10 | 9255.70 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255051E+10 | 9255.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.751135E+10 | 37048.37 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397362E+10 | 37048.37 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403269E+09 | 37048.37 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38740147.17 | 37048.37 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229963E+09 | 37048.37 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107103E+10 | 37048.37 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434816E+10 | 37048.37 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.751135E+10 | 37048.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388007E+10 | 13794.34 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237364E+10 | 13786.00 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.502150E+09 | 13746.72 | 22-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152547E+09 | 13624.16 | 07-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6379065.58 | 7790.53 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1037305.74 | 1446.03 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324576E+09 | 13721.93 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800528E+09 | 13770.08 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203313E+10 | 13760.77 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388007E+10 | 13794.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361348E+10 | 11295.16 | 19-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212996E+10 | 11286.75 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.443821E+09 | 11229.65 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94745823.33 | 11185.99 | 07-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1654078.21 | 3518.14 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2892829.95 | 2733.98 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342140E+09 | 11265.98 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.850277E+09 | 11268.81 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209310E+10 | 11292.18 | 07-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.957207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.361348E+10 | 11295.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.583081E+10 | 11949.22 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350414E+10 | 11941.92 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.740979E+09 | 11907.94 | 22-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179985E+09 | 11873.59 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3965467.83 | 5759.33 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 999118.45 | 1424.67 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.458804E+09 | 11911.60 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140790E+10 | 11928.13 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347039E+10 | 11919.98 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583081E+10 | 11949.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394090E+10 | 11603.76 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245930E+10 | 11603.76 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.652417E+09 | 11603.76 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170295E+09 | 11603.76 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10184529.59 | 6462.95 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5587669.21 | 3500.30 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446588E+09 | 11603.76 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114016E+10 | 11603.76 | 08-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249589E+10 | 11603.76 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394090E+10 | 11603.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264227E+10 | 10461.34 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117011E+10 | 12376.31 | 03-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9279883.73 | 1356.44 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3826546.92 | 1282.58 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1398016.18 | 1078.50 | 26-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101656E+09 | 6194.66 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395335E+09 | 9589.22 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264227E+10 | 12376.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328026E+10 | 11697.77 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155372E+10 | 13717.80 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37609784.04 | 2444.82 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21329150.12 | 3074.39 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13510160.69 | 2555.07 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207809E+09 | 8009.47 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654848E+09 | 10771.91 | 18-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.576909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328026E+10 | 13717.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327841E+10 | 13851.42 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159780E+10 | 16233.16 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91443790.76 | 3819.09 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50735880.56 | 5106.19 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24750002.96 | 4286.84 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303076E+09 | 9582.75 | 22-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769168E+09 | 11270.48 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327841E+10 | 16233.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202934E+10 | 0.124979E+10 | 21412.59 | 19-JAN-20:00 | 11876.87 | 0.00 |
February | 0.00 | 0.00 | 0.493248E+10 | 0.401424E+10 | 30620.35 | 28-FEB-14:00 | 30620.35 | 0.00 |
March | 0.00 | 0.00 | 0.151782E+11 | 0.117250E+11 | 47886.01 | 30-MAR-15:10 | 47886.01 | 0.00 |
April | 0.00 | 0.00 | 0.257912E+11 | 0.209254E+11 | 54143.67 | 17-APR-15:10 | 54143.67 | 0.00 |
May | 0.00 | 0.00 | 0.487284E+11 | 0.366172E+11 | 68507.22 | 30-MAY-12:00 | 52668.85 | 0.00 |
June | 0.00 | 0.00 | 0.737661E+11 | 0.551493E+11 | 83080.54 | 27-JUN-12:00 | 55480.56 | 0.00 |
July | 0.00 | 0.00 | 0.846172E+11 | 0.600465E+11 | 91434.54 | 07-JUL-12:03 | 63573.85 | 0.00 |
August | 0.00 | 0.00 | 0.967485E+11 | 0.671797E+11 | 92379.50 | 21-AUG-06:03 | 65090.19 | 0.00 |
September | 0.00 | 0.00 | 0.617830E+11 | 0.453822E+11 | 86983.98 | 06-SEP-12:03 | 60901.16 | 0.00 |
October | 0.00 | 0.00 | 0.273949E+11 | 0.201709E+11 | 66835.83 | 10-OCT-16:00 | 55121.12 | 0.00 |
November | 0.00 | 0.00 | 0.109085E+11 | 0.824653E+10 | 35159.94 | 02-NOV-13:00 | 26817.10 | 0.00 |
December | 0.00 | 0.00 | 0.394800E+10 | 0.258632E+10 | 32695.65 | 12-DEC-14:00 | 24784.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.455826E+12 | 0.333293E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.202934E+10 | 0.124979E+10 | 21412.59 | 11876.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.967485E+11 | 0.671797E+11 | 92379.50 | 65090.19 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200007E+10 | 0.126216E+10 | 21808.56 | 19-JAN-16:00 | 12447.41 | 0.00 |
February | 0.00 | 0.00 | 0.479494E+10 | 0.392227E+10 | 25585.37 | 28-FEB-15:20 | 25585.37 | 0.00 |
March | 0.00 | 0.00 | 0.138683E+11 | 0.107546E+11 | 47364.12 | 30-MAR-15:10 | 47364.12 | 0.00 |
April | 0.00 | 0.00 | 0.243901E+11 | 0.198934E+11 | 52931.46 | 17-APR-15:40 | 52931.46 | 0.00 |
May | 0.00 | 0.00 | 0.455192E+11 | 0.343655E+11 | 64850.11 | 30-MAY-15:10 | 51043.96 | 0.00 |
June | 0.00 | 0.00 | 0.678750E+11 | 0.500996E+11 | 74720.84 | 26-JUN-15:00 | 53232.93 | 0.00 |
July | 0.00 | 0.00 | 0.778633E+11 | 0.540088E+11 | 82323.04 | 15-JUL-05:03 | 63585.74 | 0.00 |
August | 0.00 | 0.00 | 0.870324E+11 | 0.585261E+11 | 85858.76 | 21-AUG-06:03 | 51297.37 | 0.00 |
September | 0.00 | 0.00 | 0.530819E+11 | 0.377183E+11 | 77102.03 | 07-SEP-16:00 | 56323.46 | 0.00 |
October | 0.00 | 0.00 | 0.230304E+11 | 0.164973E+11 | 58769.66 | 11-OCT-14:10 | 44035.40 | 0.00 |
November | 0.00 | 0.00 | 0.959012E+10 | 0.711192E+10 | 29308.50 | 05-NOV-13:43 | 22112.49 | 0.00 |
December | 0.00 | 0.00 | 0.366717E+10 | 0.247936E+10 | 28239.16 | 12-DEC-14:00 | 20644.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.412713E+12 | 0.296639E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200007E+10 | 0.126216E+10 | 21808.56 | 12447.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.870324E+11 | 0.585261E+11 | 85858.76 | 63585.74 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.211112E+10 | 0.131046E+10 | 22128.00 | 19-JAN-17:50 | 12109.31 | 0.00 |
February | 0.00 | 0.00 | 0.503262E+10 | 0.407828E+10 | 28552.53 | 26-FEB-14:43 | 28552.53 | 0.00 |
March | 0.00 | 0.00 | 0.147362E+11 | 0.113593E+11 | 53365.05 | 30-MAR-15:30 | 53365.05 | 0.00 |
April | 0.00 | 0.00 | 0.264522E+11 | 0.215405E+11 | 59644.93 | 17-APR-15:40 | 59644.93 | 0.00 |
May | 0.00 | 0.00 | 0.494681E+11 | 0.379136E+11 | 73716.12 | 30-MAY-15:10 | 59904.56 | 0.00 |
June | 0.00 | 0.00 | 0.730904E+11 | 0.548902E+11 | 83296.61 | 26-JUN-15:00 | 61749.84 | 0.00 |
July | 0.00 | 0.00 | 0.834434E+11 | 0.592381E+11 | 89797.95 | 07-JUL-16:00 | 71764.95 | 0.00 |
August | 0.00 | 0.00 | 0.922019E+11 | 0.634137E+11 | 88806.17 | 01-AUG-15:00 | 70957.08 | 0.00 |
September | 0.00 | 0.00 | 0.551550E+11 | 0.392642E+11 | 85075.93 | 06-SEP-14:00 | 63042.32 | 0.00 |
October | 0.00 | 0.00 | 0.236606E+11 | 0.167635E+11 | 64076.06 | 11-OCT-14:00 | 48623.63 | 0.00 |
November | 0.00 | 0.00 | 0.996680E+10 | 0.731304E+10 | 31921.15 | 05-NOV-13:55 | 24459.88 | 0.00 |
December | 0.00 | 0.00 | 0.381292E+10 | 0.253941E+10 | 30459.00 | 12-DEC-14:00 | 22263.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.439131E+12 | 0.319624E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.211112E+10 | 0.131046E+10 | 22128.00 | 12109.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.922019E+11 | 0.634137E+11 | 89797.95 | 71764.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1748.43 | 6085.52 | 27-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1761.59 | 6096.41 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1818.51 | 5976.52 | 02-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1599.89 | 5662.78 | 03-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1536.85 | 5262.66 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1461.68 | 4836.69 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1280.44 | 4517.52 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1401.91 | 4497.66 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1367.18 | 4787.43 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1466.46 | 5222.98 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1606.76 | 5623.49 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1642.41 | 5925.91 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1556.53 | ||||
Minimum of Months | 0.00 | 0.00 | 1280.44 | 4497.66 | ||
Maximum of Months | 0.00 | 0.00 | 1818.51 | 6096.41 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123711E+10 | 0.28 | 2457.63 | 02-JAN-06:11 | 0.76 |
February | 0.117486E+10 | 0.29 | 2457.63 | 13-FEB-07:01 | 0.76 |
March | 0.153381E+10 | 0.30 | 2222.87 | 30-MAR-16:00 | 0.71 |
April | 0.160785E+10 | 0.30 | 2457.79 | 17-APR-16:00 | 0.75 |
May | 0.211385E+10 | 0.33 | 3369.29 | 30-MAY-15:10 | 0.89 |
June | 0.300348E+10 | 0.41 | 3867.84 | 19-JUN-16:00 | 0.97 |
July | 0.329196E+10 | 0.41 | 6146.90 | 07-JUL-04:02 | 1.28 |
August | 0.381920E+10 | 0.45 | 9518.26 | 14-AUG-04:02 | 1.69 |
September | 0.275932E+10 | 0.38 | 4866.33 | 07-SEP-15:40 | 1.11 |
October | 0.192082E+10 | 0.32 | 3642.47 | 11-OCT-15:40 | 0.94 |
November | 0.141975E+10 | 0.29 | 1995.00 | 06-NOV-16:10 | 0.68 |
December | 0.123759E+10 | 0.28 | 1411.92 | 01-DEC-07:01 | 0.59 |
Annual Sum or Average | 0.251196E+11 | 0.34 | |||
Minimum of Months | 0.117486E+10 | 0.28 | 1411.92 | 0.59 | |
Maximum of Months | 0.381920E+10 | 0.45 | 9518.26 | 1.69 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126400E+10 | 0.29 | 2307.36 | 02-JAN-06:11 | 0.78 |
February | 0.118688E+10 | 0.30 | 2307.36 | 02-FEB-07:01 | 0.78 |
March | 0.138887E+10 | 0.31 | 2473.99 | 30-MAR-16:00 | 0.81 |
April | 0.148123E+10 | 0.31 | 2621.49 | 17-APR-16:00 | 0.84 |
May | 0.195997E+10 | 0.35 | 3413.71 | 30-MAY-15:00 | 0.97 |
June | 0.264328E+10 | 0.41 | 4084.09 | 26-JUN-05:13 | 1.08 |
July | 0.283324E+10 | 0.41 | 7249.12 | 15-JUL-05:03 | 1.54 |
August | 0.312886E+10 | 0.44 | 8489.35 | 14-AUG-04:02 | 1.70 |
September | 0.212695E+10 | 0.36 | 4108.49 | 07-SEP-15:30 | 1.08 |
October | 0.152978E+10 | 0.31 | 2945.02 | 11-OCT-15:30 | 0.89 |
November | 0.123356E+10 | 0.29 | 2307.36 | 22-NOV-07:01 | 0.79 |
December | 0.120644E+10 | 0.28 | 2307.36 | 01-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.219831E+11 | 0.34 | |||
Minimum of Months | 0.118688E+10 | 0.28 | 2307.36 | 0.78 | |
Maximum of Months | 0.312886E+10 | 0.44 | 8489.35 | 1.70 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152205E+10 | 0.33 | 2301.87 | 02-JAN-06:11 | 0.72 |
February | 0.131989E+10 | 0.32 | 2301.87 | 01-FEB-07:02 | 0.72 |
March | 0.142421E+10 | 0.30 | 2627.28 | 30-MAR-16:00 | 0.77 |
April | 0.150615E+10 | 0.30 | 2831.98 | 17-APR-15:40 | 0.80 |
May | 0.197845E+10 | 0.33 | 3608.84 | 30-MAY-15:00 | 0.92 |
June | 0.264204E+10 | 0.38 | 3895.62 | 27-JUN-15:30 | 0.96 |
July | 0.283338E+10 | 0.38 | 4927.34 | 15-JUL-05:03 | 1.10 |
August | 0.307843E+10 | 0.41 | 5695.25 | 14-AUG-04:02 | 1.20 |
September | 0.200797E+10 | 0.33 | 4127.78 | 07-SEP-15:30 | 0.99 |
October | 0.147912E+10 | 0.29 | 2762.24 | 11-OCT-15:30 | 0.79 |
November | 0.126730E+10 | 0.28 | 2301.87 | 21-NOV-06:01 | 0.72 |
December | 0.134937E+10 | 0.29 | 2301.87 | 01-DEC-06:01 | 0.72 |
Annual Sum or Average | 0.224084E+11 | 0.33 | |||
Minimum of Months | 0.126730E+10 | 0.28 | 2301.87 | 0.72 | |
Maximum of Months | 0.307843E+10 | 0.41 | 5695.25 | 1.20 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.66 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.11 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 55.64 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.40 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.21 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.22 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.30 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.38 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.04 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.31 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.44 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.24 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.64 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.66 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.44 | 56.44 | 1748.43 | 6085.52 | 27-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.60 | 56.60 | 1761.59 | 6096.41 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.14 | 56.14 | 1818.51 | 5976.52 | 02-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.85 | 56.85 | 1599.89 | 5662.78 | 03-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.67 | 56.67 | 1536.85 | 5262.66 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.72 | 56.72 | 1461.68 | 4836.69 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.56 | 56.56 | 1280.44 | 4517.52 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.62 | 57.62 | 1401.91 | 4497.66 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.98 | 57.98 | 1367.18 | 4787.43 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.89 | 56.89 | 1466.46 | 5222.98 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.89 | 56.89 | 1606.76 | 5623.49 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.59 | 56.59 | 1642.41 | 5925.91 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1556.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.14 | 56.14 | 1280.44 | 4497.66 | ||
Maximum of Months | 0.00 | 0.00 | 57.98 | 57.98 | 1818.51 | 6096.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153748E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104512E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.753548E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.896987E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143520E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219694E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252280E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.286098E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179854E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.931692E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.590982E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.755181E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173255E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.590982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286098E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.161422E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.101142E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.577472E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.778345E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132413E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200350E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.229408E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253305E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152188E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.767359E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.539672E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.863364E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158285E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.539672E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253305E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.268624E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171105E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.796895E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.885237E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143316E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.214641E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.245048E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.267187E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.157249E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.919878E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.913847E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167873E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.198663E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.796895E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.268624E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123711E+10 | 0.202934E+10 | 0.162372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117486E+10 | 0.493248E+10 | 0.912775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153381E+10 | 0.151782E+11 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160785E+10 | 0.257912E+11 | 0.864645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211385E+10 | 0.487284E+11 | 0.183521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300348E+10 | 0.737661E+11 | 27530985.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329196E+10 | 0.846172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381920E+10 | 0.967485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.275932E+10 | 0.617830E+11 | 25726120.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192082E+10 | 0.273949E+11 | 0.645020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141975E+10 | 0.109085E+11 | 0.177924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123759E+10 | 0.394800E+10 | 0.568520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251196E+11 | 0.455826E+12 | 0.367053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117486E+10 | 0.202934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381920E+10 | 0.967485E+11 | 0.162372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126400E+10 | 0.200007E+10 | 0.176277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118688E+10 | 0.479494E+10 | 0.920088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138887E+10 | 0.138683E+11 | 0.865137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148123E+10 | 0.243901E+11 | 0.162367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195997E+10 | 0.455192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264328E+10 | 0.678750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283324E+10 | 0.778633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312886E+10 | 0.870324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212695E+10 | 0.530819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152978E+10 | 0.230304E+11 | 0.443642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123356E+10 | 0.959012E+10 | 0.188372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120644E+10 | 0.366717E+10 | 0.712780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219831E+11 | 0.412713E+12 | 0.373113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118688E+10 | 0.200007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312886E+10 | 0.870324E+11 | 0.176277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152205E+10 | 0.211112E+10 | 0.280550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131989E+10 | 0.503262E+10 | 0.160385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142421E+10 | 0.147362E+11 | 0.283408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150615E+10 | 0.264522E+11 | 0.687049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197845E+10 | 0.494681E+11 | 22183141.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264204E+10 | 0.730904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283338E+10 | 0.834434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307843E+10 | 0.922019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200797E+10 | 0.551550E+11 | 10516923.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147912E+10 | 0.236606E+11 | 0.182682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126730E+10 | 0.996680E+10 | 0.557296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134937E+10 | 0.381292E+10 | 0.152098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224084E+11 | 0.439131E+12 | 0.702569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126730E+10 | 0.211112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307843E+10 | 0.922019E+11 | 0.280550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123711E+10 | 0.00 | 0.00 | 0.00 | 0.542708E+09 | 0.135949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117486E+10 | 0.00 | 0.00 | 0.00 | 0.131874E+10 | 0.795764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153381E+10 | 0.00 | 0.00 | 0.00 | 0.388148E+10 | 0.212019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160785E+10 | 0.00 | 0.00 | 0.00 | 0.650120E+10 | 0.860819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211385E+10 | 0.00 | 0.00 | 0.00 | 0.120547E+11 | 0.183521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300348E+10 | 0.00 | 0.00 | 0.00 | 0.189384E+11 | 27530985.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329196E+10 | 0.00 | 0.00 | 0.00 | 0.219361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381920E+10 | 0.00 | 0.00 | 0.00 | 0.247907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.275932E+10 | 0.00 | 0.00 | 0.00 | 0.152003E+11 | 25726120.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192082E+10 | 0.00 | 0.00 | 0.00 | 0.675248E+10 | 0.643622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141975E+10 | 0.00 | 0.00 | 0.00 | 0.281248E+10 | 0.167759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123759E+10 | 0.00 | 0.00 | 0.00 | 0.102436E+10 | 0.528987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251196E+11 | 0.00 | 0.00 | 0.00 | 0.115754E+12 | 0.323814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117486E+10 | 0.00 | 0.00 | 0.00 | 0.542708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381920E+10 | 0.00 | 0.00 | 0.00 | 0.247907E+11 | 0.135949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126400E+10 | 0.00 | 0.00 | 0.00 | 0.530770E+09 | 0.143475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118688E+10 | 0.00 | 0.00 | 0.00 | 0.128015E+10 | 0.764716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138887E+10 | 0.00 | 0.00 | 0.00 | 0.355833E+10 | 0.827527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148123E+10 | 0.00 | 0.00 | 0.00 | 0.616118E+10 | 0.141038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195997E+10 | 0.00 | 0.00 | 0.00 | 0.112813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264328E+10 | 0.00 | 0.00 | 0.00 | 0.173917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283324E+10 | 0.00 | 0.00 | 0.00 | 0.201076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312886E+10 | 0.00 | 0.00 | 0.00 | 0.222016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212695E+10 | 0.00 | 0.00 | 0.00 | 0.130918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152978E+10 | 0.00 | 0.00 | 0.00 | 0.571367E+10 | 0.430132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123356E+10 | 0.00 | 0.00 | 0.00 | 0.248725E+10 | 0.167591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120644E+10 | 0.00 | 0.00 | 0.00 | 0.954253E+09 | 0.647295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219831E+11 | 0.00 | 0.00 | 0.00 | 0.104760E+12 | 0.315422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118688E+10 | 0.00 | 0.00 | 0.00 | 0.530770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312886E+10 | 0.00 | 0.00 | 0.00 | 0.222016E+11 | 0.143475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152205E+10 | 0.00 | 0.00 | 0.00 | 0.563764E+09 | 0.247766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131989E+10 | 0.00 | 0.00 | 0.00 | 0.134993E+10 | 0.144407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142421E+10 | 0.00 | 0.00 | 0.00 | 0.380210E+10 | 0.274264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150615E+10 | 0.00 | 0.00 | 0.00 | 0.670991E+10 | 0.636313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197845E+10 | 0.00 | 0.00 | 0.00 | 0.123310E+11 | 22183141.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264204E+10 | 0.00 | 0.00 | 0.00 | 0.188221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283338E+10 | 0.00 | 0.00 | 0.00 | 0.216714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307843E+10 | 0.00 | 0.00 | 0.00 | 0.236403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200797E+10 | 0.00 | 0.00 | 0.00 | 0.137064E+11 | 10516923.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147912E+10 | 0.00 | 0.00 | 0.00 | 0.591759E+10 | 0.180207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126730E+10 | 0.00 | 0.00 | 0.00 | 0.260128E+10 | 0.526989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134937E+10 | 0.00 | 0.00 | 0.00 | 0.997217E+09 | 0.144407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224084E+11 | 0.00 | 0.00 | 0.00 | 0.112113E+12 | 0.641416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126730E+10 | 0.00 | 0.00 | 0.00 | 0.563764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307843E+10 | 0.00 | 0.00 | 0.00 | 0.236403E+11 | 0.247766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104737E+11 | 0.00 | 0.00 | 3292783.82 | 13783997.68 | 78776694.83 | 0.305663E+10 | 0.00 | 0.35 |
February | 0.666032E+10 | 0.00 | 0.00 | 9775592.88 | 2198909.17 | 4123999.08 | 0.509528E+10 | 0.00 | 0.45 |
March | 0.300697E+10 | 0.248964E+09 | 0.00 | 23392812.48 | 87315492.09 | 0.00 | 0.992706E+10 | 0.00 | 0.63 |
April | 0.979519E+09 | 0.500718E+09 | 0.00 | 23666791.78 | 96445871.95 | 0.00 | 0.705154E+10 | 0.00 | 0.65 |
May | 0.346186E+09 | 0.289994E+10 | 0.00 | 12541921.87 | 58153089.93 | 0.00 | 0.247016E+10 | 0.00 | 0.52 |
June | 0.133379E+09 | 0.813202E+10 | 0.00 | 5916351.43 | 77158226.46 | 0.00 | 0.114811E+10 | 0.00 | 0.41 |
July | 0.00 | 0.105029E+11 | 0.00 | 0.00 | 0.194836E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 1729123.48 | 0.126358E+11 | 0.00 | 236693.39 | 0.145979E+09 | 0.00 | 9696632.61 | 0.00 | 0.30 |
September | 0.147725E+09 | 0.512125E+10 | 0.00 | 12689442.64 | 0.104348E+09 | 0.00 | 0.174658E+10 | 0.00 | 0.49 |
October | 0.115961E+10 | 0.155892E+10 | 0.00 | 25795078.80 | 14526381.28 | 0.00 | 0.102769E+11 | 0.00 | 0.62 |
November | 0.284837E+10 | 0.126750E+09 | 0.00 | 23586894.59 | 95367724.27 | 0.00 | 0.107207E+11 | 0.00 | 0.59 |
December | 0.627369E+10 | 21660897.07 | 0.00 | 11966409.88 | 0.00 | 0.00 | 0.689815E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.320312E+11 | 0.417490E+11 | 0.00 | 0.152861E+09 | 0.890112E+09 | 82900693.91 | 0.584008E+11 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.104737E+11 | 0.126358E+11 | 0.00 | 25795078.80 | 0.194836E+09 | 78776694.83 | 0.107207E+11 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117595E+11 | 0.00 | 0.00 | 0.00 | 30311539.82 | 0.102898E+10 | 0.00 | 0.00 | 0.34 |
February | 0.100652E+11 | 31494.12 | 0.00 | 261116.00 | 4796197.14 | 0.229444E+09 | 0.165993E+09 | 0.00 | 0.41 |
March | 0.770004E+10 | 0.105102E+09 | 0.00 | 2790810.45 | 0.179485E+09 | 1155054.53 | 0.214604E+10 | 0.00 | 0.49 |
April | 0.342957E+10 | 0.232511E+09 | 0.00 | 7356723.70 | 0.250959E+09 | 0.00 | 0.254081E+10 | 0.00 | 0.48 |
May | 0.857119E+09 | 0.184867E+10 | 0.00 | 5313541.30 | 0.383311E+09 | 0.00 | 0.122074E+10 | 0.00 | 0.39 |
June | 0.304960E+09 | 0.686420E+10 | 0.00 | 2996099.43 | 0.129928E+09 | 0.00 | 0.658111E+09 | 0.00 | 0.33 |
July | 261610.99 | 0.902372E+10 | 0.00 | 18178.82 | 0.383105E+09 | 0.00 | 63219.66 | 0.00 | 0.24 |
August | 8970030.31 | 0.113333E+11 | 0.00 | 148164.12 | 0.143985E+09 | 0.00 | 7481926.83 | 0.00 | 0.27 |
September | 0.402548E+09 | 0.412818E+10 | 0.00 | 5619419.68 | 0.538147E+09 | 0.00 | 0.833361E+09 | 0.00 | 0.37 |
October | 0.488682E+10 | 0.113976E+10 | 0.00 | 5878058.74 | 0.191402E+09 | 0.00 | 0.290542E+10 | 0.00 | 0.45 |
November | 0.868398E+10 | 29280787.94 | 0.00 | 1077984.44 | 0.255670E+09 | 3406745.41 | 0.102406E+10 | 0.00 | 0.44 |
December | 0.107861E+11 | 8223435.14 | 0.00 | 17230.99 | 59224926.16 | 0.172342E+09 | 75336229.69 | 0.00 | 0.39 |
Annual Sum or Average | 0.588850E+11 | 0.347130E+11 | 0.00 | 31477327.67 | 0.255032E+10 | 0.143533E+10 | 0.115774E+11 | 0.00 | 0.38 |
Minimum of Months | 261610.99 | 0.00 | 0.00 | 0.00 | 4796197.14 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.117595E+11 | 0.113333E+11 | 0.00 | 7356723.70 | 0.538147E+09 | 0.102898E+10 | 0.290542E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.948045E+10 | 0.00 | 0.00 | 0.00 | 24391827.68 | 0.294875E+10 | 0.00 | 0.00 | 0.35 |
February | 0.873210E+10 | 0.00 | 0.00 | 149587.54 | 8352538.11 | 0.120343E+10 | 63416890.59 | 0.00 | 0.42 |
March | 0.862491E+10 | 0.103114E+09 | 0.00 | 1779369.00 | 0.186739E+09 | 42381300.26 | 0.777393E+09 | 0.00 | 0.50 |
April | 0.391535E+10 | 0.168936E+09 | 0.00 | 6454211.54 | 0.281262E+09 | 2682501.36 | 0.174541E+10 | 0.00 | 0.51 |
May | 0.899967E+09 | 0.172182E+10 | 0.00 | 3337157.33 | 0.416114E+09 | 0.00 | 0.941898E+09 | 0.00 | 0.38 |
June | 0.377116E+09 | 0.658399E+10 | 0.00 | 2559622.10 | 0.150128E+09 | 0.00 | 0.500519E+09 | 0.00 | 0.33 |
July | 0.00 | 0.867962E+10 | 0.00 | 0.00 | 0.443696E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 8251433.55 | 0.109893E+11 | 0.00 | 22358.89 | 0.149288E+09 | 0.00 | 2131205.12 | 0.00 | 0.27 |
September | 0.486143E+09 | 0.368724E+10 | 0.00 | 4226700.50 | 0.101241E+10 | 0.00 | 0.501289E+09 | 0.00 | 0.37 |
October | 0.582950E+10 | 0.997884E+09 | 0.00 | 2487757.52 | 0.332272E+09 | 26649555.27 | 0.126878E+10 | 0.00 | 0.45 |
November | 0.863352E+10 | 14392257.63 | 1417686.38 | 209596.84 | 0.306232E+09 | 0.185149E+09 | 0.215659E+09 | 39261.18 | 0.44 |
December | 0.967319E+10 | 0.00 | 0.00 | 0.00 | 74741504.36 | 0.100114E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.566605E+11 | 0.329463E+11 | 1417686.38 | 21226361.26 | 0.338562E+10 | 0.541019E+10 | 0.601650E+10 | 39261.18 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8352538.11 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.967319E+10 | 0.109893E+11 | 1417686.38 | 6454211.54 | 0.101241E+10 | 0.294875E+10 | 0.174541E+10 | 39261.18 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495361E+09 | 0.00 | 0.00 | 0.00 | 5155810.29 | 0.233449E+10 | 0.00 | 0.00 | 0.37 |
February | 0.840180E+09 | 0.00 | 306325.22 | 50526.83 | 1457746.20 | 0.135966E+10 | 14000220.43 | 1442.12 | 0.43 |
March | 0.161856E+10 | 25623530.99 | 0.00 | 291075.03 | 37955107.53 | 0.280548E+09 | 0.102760E+09 | 0.00 | 0.50 |
April | 0.927933E+09 | 61117269.46 | 0.00 | 1402299.46 | 40826968.32 | 62133999.20 | 0.225056E+09 | 0.00 | 0.54 |
May | 0.233942E+09 | 0.509325E+09 | 0.00 | 749639.36 | 56477830.10 | 554986.59 | 0.165282E+09 | 0.00 | 0.44 |
June | 83162226.32 | 0.207472E+10 | 0.00 | 681754.93 | 40779624.55 | 0.00 | 0.115007E+09 | 0.00 | 0.45 |
July | 0.00 | 0.281264E+10 | 0.00 | 0.00 | 79872047.00 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 1990262.22 | 0.333136E+10 | 0.00 | 162.87 | 40032357.16 | 0.00 | 126070.08 | 0.00 | 0.37 |
September | 0.123195E+09 | 0.981789E+09 | 0.00 | 911053.28 | 0.197426E+09 | 0.00 | 95015525.96 | 0.00 | 0.41 |
October | 0.121350E+10 | 0.244366E+09 | 0.00 | 262533.36 | 67965674.69 | 0.160442E+09 | 0.126674E+09 | 0.00 | 0.46 |
November | 0.138397E+10 | 3356048.41 | 2938762.62 | 8602.45 | 61843658.19 | 0.545150E+09 | 962789.83 | 14020.17 | 0.45 |
December | 0.907341E+09 | 0.00 | 70482.55 | 0.00 | 15726615.99 | 0.143683E+10 | 0.00 | 1349.30 | 0.41 |
Annual Sum or Average | 0.782913E+10 | 0.100443E+11 | 3315570.39 | 4357647.56 | 0.645520E+09 | 0.617981E+10 | 0.844883E+09 | 16811.59 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1457746.20 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.161856E+10 | 0.333136E+10 | 2938762.62 | 1402299.46 | 0.197426E+09 | 0.233449E+10 | 0.225056E+09 | 14020.17 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.780277E+09 | 0.00 | 0.00 | 0.00 | 4363162.85 | 0.150326E+10 | 0.00 | 0.00 | 0.48 |
February | 0.867089E+09 | 0.00 | 259189.17 | 155771.07 | 1233634.23 | 0.853316E+09 | 96116599.41 | 1262.42 | 0.57 |
March | 0.126094E+10 | 21381810.29 | 0.00 | 694662.18 | 32483476.68 | 0.155226E+09 | 0.287232E+09 | 0.00 | 0.68 |
April | 0.591608E+09 | 42088172.91 | 0.00 | 2300183.32 | 43984791.93 | 30327869.20 | 0.490922E+09 | 0.00 | 0.81 |
May | 0.148655E+09 | 0.487848E+09 | 0.00 | 1170580.77 | 51466276.70 | 454666.51 | 0.253325E+09 | 0.00 | 0.66 |
June | 53974522.14 | 0.175396E+10 | 0.00 | 889128.47 | 34188135.85 | 0.00 | 0.167116E+09 | 0.00 | 0.64 |
July | 0.00 | 0.244514E+10 | 0.00 | 0.00 | 95990895.43 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 1791108.01 | 0.280986E+10 | 0.00 | 0.00 | 52663370.54 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 94368344.78 | 0.930073E+09 | 0.00 | 1101948.19 | 0.172654E+09 | 285002.99 | 0.116986E+09 | 0.00 | 0.62 |
October | 0.829901E+09 | 0.209456E+09 | 0.00 | 864756.63 | 62552575.24 | 0.119729E+09 | 0.377578E+09 | 0.00 | 0.64 |
November | 0.127489E+10 | 4043804.00 | 2441629.75 | 39069.65 | 51132186.13 | 0.306124E+09 | 41466152.44 | 8116.79 | 0.60 |
December | 0.108365E+10 | 0.00 | 58620.86 | 0.00 | 13308826.90 | 0.851892E+09 | 0.00 | 2167.66 | 0.53 |
Annual Sum or Average | 0.698714E+10 | 0.870386E+10 | 2759439.77 | 7216100.27 | 0.616021E+09 | 0.382062E+10 | 0.183074E+10 | 11546.87 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1233634.23 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.127489E+10 | 0.280986E+10 | 2441629.75 | 2300183.32 | 0.172654E+09 | 0.150326E+10 | 0.490922E+09 | 8116.79 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.981840E+09 | 0.00 | 0.00 | 778107.09 | 5314240.82 | 0.146110E+10 | 0.499961E+09 | 0.00 | 0.39 |
February | 0.964621E+09 | 0.00 | 316558.59 | 1667782.51 | 1502540.62 | 0.868187E+09 | 0.632981E+09 | 665.98 | 0.52 |
March | 0.124098E+10 | 59686076.07 | 0.00 | 3043321.53 | 21953541.20 | 0.193273E+09 | 0.967465E+09 | 0.00 | 0.65 |
April | 0.734900E+09 | 85584618.27 | 0.00 | 3326798.75 | 30048895.89 | 56459993.55 | 0.649681E+09 | 0.00 | 0.69 |
May | 0.231323E+09 | 0.575757E+09 | 0.00 | 1076151.16 | 65065782.81 | 645836.95 | 0.222562E+09 | 0.00 | 0.50 |
June | 96156530.06 | 0.211279E+10 | 0.00 | 697622.01 | 57948182.09 | 0.00 | 0.113036E+09 | 0.00 | 0.46 |
July | 0.00 | 0.292794E+10 | 0.00 | 0.00 | 0.101182E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 2051420.07 | 0.386297E+10 | 0.00 | 281.63 | 44745525.01 | 0.00 | 129830.27 | 0.00 | 0.43 |
September | 0.116512E+09 | 0.138103E+10 | 0.00 | 1807158.09 | 0.180778E+09 | 0.00 | 0.182254E+09 | 0.00 | 0.57 |
October | 0.852927E+09 | 0.429237E+09 | 0.00 | 3574710.80 | 38291614.87 | 0.120126E+09 | 0.117051E+10 | 0.00 | 0.70 |
November | 0.113841E+10 | 8437379.01 | 2372376.94 | 2738880.34 | 60971709.41 | 0.297155E+09 | 0.987568E+09 | 10349.20 | 0.60 |
December | 0.116121E+10 | 5091768.39 | 0.00 | 1653517.76 | 13749679.25 | 0.709090E+09 | 0.750886E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.752094E+10 | 0.114485E+11 | 2688935.53 | 20364331.67 | 0.621551E+09 | 0.370604E+10 | 0.617703E+10 | 11015.19 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1502540.62 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.124098E+10 | 0.386297E+10 | 2372376.94 | 3574710.80 | 0.180778E+09 | 0.146110E+10 | 0.117051E+10 | 10349.20 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.761684E+09 | 0.00 | 0.00 | 0.00 | 4821888.09 | 0.174497E+10 | 0.00 | 0.00 | 0.52 |
February | 0.890804E+09 | 0.00 | 287454.08 | 271396.75 | 1363333.53 | 0.103626E+10 | 96601040.78 | 380.33 | 0.64 |
March | 0.133693E+10 | 31711065.17 | 0.00 | 1068106.74 | 31070464.64 | 0.242201E+09 | 0.361007E+09 | 0.00 | 0.79 |
April | 0.736519E+09 | 42709860.46 | 0.00 | 2274608.35 | 49544827.70 | 52599164.20 | 0.442371E+09 | 0.00 | 0.89 |
May | 0.223691E+09 | 0.414516E+09 | 0.00 | 910155.64 | 81931792.46 | 761625.64 | 0.203300E+09 | 0.00 | 0.68 |
June | 93940268.28 | 0.163197E+10 | 0.00 | 631978.38 | 85563222.84 | 0.00 | 0.100656E+09 | 0.00 | 0.62 |
July | 0.00 | 0.222845E+10 | 0.00 | 0.00 | 0.142380E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 1979417.83 | 0.276104E+10 | 0.00 | 0.00 | 78239212.00 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.120261E+09 | 0.832055E+09 | 0.00 | 946866.67 | 0.237902E+09 | 314967.04 | 93478941.80 | 0.00 | 0.62 |
October | 0.102913E+10 | 0.186713E+09 | 0.00 | 895044.18 | 93720215.20 | 0.139543E+09 | 0.322188E+09 | 0.00 | 0.72 |
November | 0.124824E+10 | 308286.33 | 2684955.84 | 332504.96 | 60668683.49 | 0.440074E+09 | 0.129326E+09 | 8003.60 | 0.67 |
December | 0.102590E+10 | 418440.06 | 64599.95 | 3280.34 | 14289622.89 | 0.109647E+10 | 11649571.57 | 2579.62 | 0.59 |
Annual Sum or Average | 0.746908E+10 | 0.812989E+10 | 3037009.87 | 7333942.02 | 0.881496E+09 | 0.475320E+10 | 0.176058E+10 | 10963.55 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1363333.53 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.133693E+10 | 0.276104E+10 | 2684955.84 | 2274608.35 | 0.237902E+09 | 0.174497E+10 | 0.442371E+09 | 8003.60 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.689001E+09 | 0.00 | 0.00 | 0.00 | 2899752.48 | 0.223933E+10 | 0.00 | 0.00 | 0.35 |
February | 0.112622E+10 | 0.00 | 0.00 | 0.00 | 462586.58 | 0.129164E+10 | 0.00 | 0.00 | 0.42 |
March | 0.201942E+10 | 7822837.12 | 0.00 | 21044.63 | 51923839.85 | 0.178133E+09 | 25675097.98 | 0.00 | 0.50 |
April | 0.118643E+10 | 20323318.76 | 0.00 | 231457.56 | 81785006.65 | 34833559.41 | 43092373.58 | 0.00 | 0.47 |
May | 0.341156E+09 | 0.354927E+09 | 0.00 | 244678.50 | 0.117867E+09 | 0.00 | 71239870.66 | 0.00 | 0.36 |
June | 0.101158E+09 | 0.160348E+10 | 0.00 | 501166.29 | 24862296.68 | 0.00 | 89639223.93 | 0.00 | 0.34 |
July | 0.00 | 0.224091E+10 | 0.00 | 0.00 | 61921170.32 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 1540274.81 | 0.269594E+10 | 0.00 | 2467.13 | 30907075.50 | 0.00 | 365969.19 | 0.00 | 0.30 |
September | 0.147444E+09 | 0.948609E+09 | 0.00 | 1021193.28 | 35997466.21 | 0.00 | 0.131744E+09 | 0.00 | 0.38 |
October | 0.153559E+10 | 0.238674E+09 | 0.00 | 433441.48 | 15838743.49 | 8589752.27 | 0.220613E+09 | 0.00 | 0.45 |
November | 0.216323E+10 | 2541461.89 | 133799.33 | 23372.54 | 39846344.06 | 0.117743E+09 | 28724814.58 | 2699.55 | 0.46 |
December | 0.183393E+10 | 0.00 | 0.00 | 0.00 | 3310457.05 | 0.826700E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.111451E+11 | 0.811323E+10 | 133799.33 | 2478821.41 | 0.467621E+09 | 0.469697E+10 | 0.611094E+09 | 2699.55 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 462586.58 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.216323E+10 | 0.269594E+10 | 133799.33 | 1021193.28 | 0.117867E+09 | 0.223933E+10 | 0.220613E+09 | 2699.55 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.904528E+09 | 0.00 | 0.00 | 0.00 | 2124392.69 | 0.122480E+10 | 0.00 | 0.00 | 0.41 |
February | 0.946952E+09 | 0.00 | 0.00 | 130236.37 | 338896.35 | 0.717104E+09 | 93413668.79 | 0.00 | 0.49 |
March | 0.137826E+10 | 10677619.75 | 0.00 | 352647.89 | 33902275.25 | 59687811.29 | 0.197741E+09 | 0.00 | 0.58 |
April | 0.658295E+09 | 29144029.06 | 0.00 | 1312108.95 | 48914055.88 | 8160053.89 | 0.316908E+09 | 0.00 | 0.61 |
May | 0.161268E+09 | 0.388534E+09 | 0.00 | 963346.88 | 64078608.80 | 0.00 | 0.207883E+09 | 0.00 | 0.53 |
June | 48155440.83 | 0.142471E+10 | 0.00 | 847956.28 | 15663619.50 | 0.00 | 0.161738E+09 | 0.00 | 0.52 |
July | 0.00 | 0.204326E+10 | 0.00 | 0.00 | 54366100.94 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 1128423.40 | 0.235918E+10 | 0.00 | 2198.29 | 22580620.20 | 0.00 | 267722.48 | 0.00 | 0.41 |
September | 99890354.99 | 0.876115E+09 | 0.00 | 1284628.08 | 20174598.53 | 0.00 | 0.161267E+09 | 0.00 | 0.56 |
October | 0.847849E+09 | 0.210380E+09 | 0.00 | 1469051.70 | 4930165.17 | 5680453.85 | 0.614630E+09 | 0.00 | 0.61 |
November | 0.148067E+10 | 2345433.61 | 0.00 | 323858.77 | 28808371.09 | 25058772.42 | 0.194606E+09 | 0.00 | 0.54 |
December | 0.162138E+10 | 0.00 | 0.00 | 0.00 | 2425279.68 | 0.325812E+09 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.814838E+10 | 0.734435E+10 | 0.00 | 6686033.20 | 0.298307E+09 | 0.236630E+10 | 0.194845E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 338896.35 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.162138E+10 | 0.235918E+10 | 0.00 | 1469051.70 | 64078608.80 | 0.122480E+10 | 0.614630E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113301E+10 | 0.00 | 0.00 | 53598.63 | 2903469.21 | 0.229477E+10 | 41141825.28 | 0.00 | 0.41 |
February | 0.107096E+10 | 0.00 | 0.00 | 726225.36 | 463179.50 | 0.152151E+10 | 0.222927E+09 | 0.00 | 0.50 |
March | 0.163310E+10 | 47376369.71 | 0.00 | 820964.80 | 24615002.42 | 0.571832E+09 | 0.248747E+09 | 0.00 | 0.56 |
April | 0.965719E+09 | 48643808.40 | 0.00 | 1081060.51 | 66091560.07 | 0.298184E+09 | 0.110464E+09 | 0.00 | 0.54 |
May | 0.306011E+09 | 0.480582E+09 | 0.00 | 339201.36 | 0.104393E+09 | 67811751.88 | 68190032.60 | 0.00 | 0.41 |
June | 0.112392E+09 | 0.189900E+10 | 0.00 | 381034.82 | 76932041.75 | 19197175.62 | 59602822.28 | 0.00 | 0.39 |
July | 0.00 | 0.263936E+10 | 0.00 | 0.00 | 0.119056E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 1877596.19 | 0.359418E+10 | 0.00 | 412.21 | 46663667.05 | 0.00 | 33149.21 | 0.00 | 0.39 |
September | 0.152164E+09 | 0.138285E+10 | 0.00 | 1683177.31 | 51154506.86 | 14790775.22 | 0.165928E+09 | 0.00 | 0.53 |
October | 0.100741E+10 | 0.405086E+09 | 0.00 | 2906735.54 | 9090344.41 | 0.262672E+09 | 0.980122E+09 | 0.00 | 0.65 |
November | 0.149291E+10 | 11031174.97 | 0.00 | 2112567.62 | 32943974.91 | 0.492326E+09 | 0.823845E+09 | 0.00 | 0.59 |
December | 0.169863E+10 | 3551887.98 | 0.00 | 642168.73 | 1069455.51 | 0.932083E+09 | 0.345021E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.957418E+10 | 0.105117E+11 | 0.00 | 10747146.90 | 0.535376E+09 | 0.647517E+10 | 0.306602E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 463179.50 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.169863E+10 | 0.359418E+10 | 0.00 | 2906735.54 | 0.119056E+09 | 0.229477E+10 | 0.980122E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.771728E+09 | 0.00 | 0.00 | 0.00 | 2200158.13 | 0.142972E+10 | 0.00 | 0.00 | 0.42 |
February | 0.982694E+09 | 0.00 | 0.00 | 160582.49 | 350982.93 | 0.798788E+09 | 44349107.10 | 0.00 | 0.51 |
March | 0.143837E+10 | 25522509.27 | 0.00 | 503274.42 | 25358152.87 | 82111647.65 | 0.188044E+09 | 0.00 | 0.62 |
April | 0.804740E+09 | 32970244.24 | 0.00 | 965159.87 | 50934516.08 | 12010361.61 | 0.174087E+09 | 0.00 | 0.62 |
May | 0.223796E+09 | 0.361908E+09 | 0.00 | 539421.40 | 61292990.41 | 0.00 | 0.128557E+09 | 0.00 | 0.51 |
June | 77337660.04 | 0.136817E+10 | 0.00 | 525889.17 | 20360825.60 | 0.00 | 81731068.21 | 0.00 | 0.48 |
July | 0.00 | 0.190443E+10 | 0.00 | 0.00 | 49848042.02 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 1168668.08 | 0.235450E+10 | 0.00 | 2714.84 | 15698201.45 | 0.00 | 276832.53 | 0.00 | 0.40 |
September | 0.109878E+09 | 0.845767E+09 | 0.00 | 1064558.01 | 24722447.76 | 0.00 | 0.113873E+09 | 0.00 | 0.53 |
October | 0.100509E+10 | 0.207911E+09 | 0.00 | 1138021.12 | 6845456.55 | 2477191.23 | 0.431366E+09 | 0.00 | 0.61 |
November | 0.154369E+10 | 2001833.06 | 0.00 | 470171.04 | 30264592.05 | 47354564.92 | 0.196991E+09 | 0.00 | 0.58 |
December | 0.154685E+10 | 319951.06 | 0.00 | 12107.60 | 2191825.05 | 0.446058E+09 | 23098106.77 | 0.00 | 0.50 |
Annual Sum or Average | 0.850533E+10 | 0.710349E+10 | 0.00 | 5381899.95 | 0.290068E+09 | 0.281852E+10 | 0.138237E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 350982.93 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.154685E+10 | 0.235450E+10 | 0.00 | 1138021.12 | 61292990.41 | 0.142972E+10 | 0.431366E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.676345E+09 | 0.00 | 0.00 | 0.00 | 6407967.82 | 0.210986E+10 | 0.00 | 0.00 | 0.35 |
February | 0.112107E+10 | 6657.97 | 0.00 | 54814.80 | 1013933.21 | 0.112599E+10 | 10416696.94 | 0.00 | 0.42 |
March | 0.187600E+10 | 29572312.69 | 0.00 | 264973.55 | 33583116.84 | 0.105648E+09 | 0.101706E+09 | 0.00 | 0.49 |
April | 0.100596E+10 | 77918915.43 | 0.00 | 1157415.02 | 33009784.79 | 17475350.19 | 0.233776E+09 | 0.00 | 0.50 |
May | 0.260939E+09 | 0.569899E+09 | 0.00 | 887853.34 | 33374479.57 | 0.00 | 0.174965E+09 | 0.00 | 0.43 |
June | 88227341.68 | 0.221833E+10 | 0.00 | 708579.55 | 16399270.74 | 0.00 | 0.118675E+09 | 0.00 | 0.44 |
July | 65828.95 | 0.297651E+10 | 0.00 | 0.00 | 54044580.41 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 2848825.00 | 0.349486E+10 | 0.00 | 2379.96 | 30641839.33 | 0.00 | 522713.69 | 0.00 | 0.38 |
September | 0.154076E+09 | 0.113471E+10 | 0.00 | 915997.67 | 57490424.96 | 0.00 | 0.101084E+09 | 0.00 | 0.40 |
October | 0.141847E+10 | 0.283648E+09 | 0.00 | 377988.27 | 29709838.59 | 25248059.52 | 0.170108E+09 | 0.00 | 0.45 |
November | 0.175369E+10 | 5140838.55 | 251737.67 | 14696.53 | 54963985.26 | 0.290604E+09 | 14182105.67 | 7215.43 | 0.44 |
December | 0.140746E+10 | 0.00 | 0.00 | 0.00 | 14258824.57 | 0.957010E+09 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.976514E+10 | 0.107906E+11 | 251737.67 | 4384698.69 | 0.364898E+09 | 0.463184E+10 | 0.925436E+09 | 7215.43 | 0.42 |
Minimum of Months | 65828.95 | 0.00 | 0.00 | 0.00 | 1013933.21 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.187600E+10 | 0.349486E+10 | 251737.67 | 1157415.02 | 57490424.96 | 0.210986E+10 | 0.233776E+09 | 7215.43 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.952193E+09 | 0.00 | 0.00 | 0.00 | 5440048.43 | 0.136994E+10 | 0.00 | 0.00 | 0.46 |
February | 0.101412E+10 | 6078.40 | 0.00 | 231143.42 | 860779.26 | 0.760183E+09 | 0.124579E+09 | 0.00 | 0.56 |
March | 0.134368E+10 | 22571267.81 | 0.00 | 805389.30 | 30002658.24 | 63261462.57 | 0.394474E+09 | 0.00 | 0.67 |
April | 0.635483E+09 | 59646309.96 | 0.00 | 2193034.21 | 33131705.47 | 8191189.84 | 0.559460E+09 | 0.00 | 0.77 |
May | 0.177771E+09 | 0.508547E+09 | 0.00 | 1342690.48 | 39390106.87 | 0.00 | 0.278288E+09 | 0.00 | 0.66 |
June | 60087264.95 | 0.182139E+10 | 0.00 | 937415.10 | 17308785.84 | 0.00 | 0.181172E+09 | 0.00 | 0.63 |
July | 55885.53 | 0.252895E+10 | 0.00 | 0.00 | 73816460.52 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 2756332.13 | 0.289436E+10 | 0.00 | 1322.38 | 31453418.69 | 0.00 | 106635.91 | 0.00 | 0.50 |
September | 0.125469E+09 | 0.949036E+09 | 0.00 | 1085936.25 | 0.124030E+09 | 0.00 | 0.131614E+09 | 0.00 | 0.60 |
October | 0.981015E+09 | 0.215963E+09 | 0.00 | 1132023.12 | 44336101.68 | 23379247.52 | 0.483672E+09 | 0.00 | 0.64 |
November | 0.146459E+10 | 4449011.01 | 816172.83 | 137844.38 | 45932081.54 | 0.165193E+09 | 0.119154E+09 | 5090.31 | 0.59 |
December | 0.143060E+10 | 0.00 | 0.00 | 0.00 | 12105038.36 | 0.563680E+09 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.818782E+10 | 0.900492E+10 | 816172.83 | 7866798.66 | 0.457807E+09 | 0.295383E+10 | 0.227252E+10 | 5090.31 | 0.59 |
Minimum of Months | 55885.53 | 0.00 | 0.00 | 0.00 | 860779.26 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.146459E+10 | 0.289436E+10 | 816172.83 | 2193034.21 | 0.124030E+09 | 0.136994E+10 | 0.559460E+09 | 5090.31 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111679E+10 | 0.00 | 0.00 | 1144862.74 | 6406777.25 | 0.119717E+10 | 0.627057E+09 | 0.00 | 0.36 |
February | 0.115402E+10 | 17390.68 | 0.00 | 1990288.75 | 1013744.83 | 0.646488E+09 | 0.718874E+09 | 0.00 | 0.51 |
March | 0.138398E+10 | 76603174.77 | 0.00 | 3123552.87 | 12354638.61 | 62444743.68 | 0.101287E+10 | 0.00 | 0.63 |
April | 0.785463E+09 | 0.114370E+09 | 0.00 | 2911778.98 | 17662202.24 | 14488164.00 | 0.634903E+09 | 0.00 | 0.63 |
May | 0.257724E+09 | 0.659463E+09 | 0.00 | 1157911.10 | 33746002.14 | 0.00 | 0.214274E+09 | 0.00 | 0.49 |
June | 0.100347E+09 | 0.228053E+10 | 0.00 | 678267.36 | 19128978.79 | 0.00 | 0.108270E+09 | 0.00 | 0.46 |
July | 65816.71 | 0.313310E+10 | 0.00 | 0.00 | 53673324.80 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 2911789.62 | 0.408708E+10 | 0.00 | 2410.68 | 30535355.02 | 0.00 | 459091.49 | 0.00 | 0.44 |
September | 0.143295E+09 | 0.155953E+10 | 0.00 | 1722462.66 | 44699632.76 | 0.00 | 0.173564E+09 | 0.00 | 0.56 |
October | 0.957214E+09 | 0.465191E+09 | 0.00 | 4042055.74 | 12475080.76 | 20034430.58 | 0.132242E+10 | 0.00 | 0.71 |
November | 0.131398E+10 | 15495112.94 | 132203.71 | 3560438.53 | 48077596.91 | 0.112249E+09 | 0.120922E+10 | 2529.77 | 0.62 |
December | 0.137915E+10 | 14417874.27 | 0.00 | 2218887.71 | 4642484.91 | 0.397583E+09 | 0.940878E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.859494E+10 | 0.124058E+11 | 132203.71 | 22552917.11 | 0.284416E+09 | 0.245046E+10 | 0.696279E+10 | 2529.77 | 0.52 |
Minimum of Months | 65816.71 | 0.00 | 0.00 | 0.00 | 1013744.83 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.138398E+10 | 0.408708E+10 | 132203.71 | 4042055.74 | 53673324.80 | 0.119717E+10 | 0.132242E+10 | 2529.77 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841613E+09 | 0.00 | 0.00 | 0.00 | 5675750.22 | 0.157733E+10 | 0.00 | 0.00 | 0.48 |
February | 0.106452E+10 | 5897.19 | 0.00 | 300613.46 | 898074.37 | 0.841953E+09 | 87489505.09 | 0.00 | 0.59 |
March | 0.149956E+10 | 44840189.94 | 0.00 | 1033353.67 | 18701047.21 | 86710123.30 | 0.330971E+09 | 0.00 | 0.74 |
April | 0.796377E+09 | 67366315.04 | 0.00 | 1879649.48 | 33743331.57 | 15548696.24 | 0.389585E+09 | 0.00 | 0.80 |
May | 0.246649E+09 | 0.492554E+09 | 0.00 | 841316.42 | 41253258.80 | 0.00 | 0.184973E+09 | 0.00 | 0.65 |
June | 96333864.13 | 0.181237E+10 | 0.00 | 588230.29 | 28097126.78 | 0.00 | 90506756.24 | 0.00 | 0.61 |
July | 58306.89 | 0.244334E+10 | 0.00 | 0.00 | 69550658.41 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 2988391.96 | 0.297134E+10 | 0.00 | 0.00 | 24041397.48 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.143736E+09 | 0.930713E+09 | 0.00 | 878290.88 | 0.134328E+09 | 0.00 | 83851827.40 | 0.00 | 0.59 |
October | 0.116951E+10 | 0.225647E+09 | 0.00 | 998022.39 | 44233808.35 | 21576350.91 | 0.332871E+09 | 0.00 | 0.68 |
November | 0.145382E+10 | 3385914.38 | 844244.92 | 430615.80 | 49192585.74 | 0.225839E+09 | 0.177504E+09 | 5262.12 | 0.64 |
December | 0.135216E+10 | 1059570.49 | 0.00 | 20307.27 | 11569944.66 | 0.694874E+09 | 32412029.98 | 0.00 | 0.54 |
Annual Sum or Average | 0.866733E+10 | 0.899262E+10 | 844244.92 | 6970399.66 | 0.461285E+09 | 0.346383E+10 | 0.171016E+10 | 5262.12 | 0.61 |
Minimum of Months | 58306.89 | 0.00 | 0.00 | 0.00 | 898074.37 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.149956E+10 | 0.297134E+10 | 844244.92 | 1879649.48 | 0.134328E+09 | 0.157733E+10 | 0.389585E+09 | 5262.12 | 0.80 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.187391E+12 | 0.175787E+11 | 0.00 | 0.188389E+12 | 0.100780E+11 |
February | 0.185349E+12 | 0.147138E+11 | 0.00 | 0.184799E+12 | 0.197893E+11 |
March | 0.266350E+12 | 0.930029E+10 | 0.00 | 0.204780E+12 | 0.550592E+11 |
April | 0.295769E+12 | 0.439831E+10 | 0.00 | 0.135433E+12 | 0.960248E+11 |
May | 0.324725E+12 | -90459202.7 | 0.00 | 0.456251E+11 | 0.179383E+12 |
June | 0.314975E+12 | -0.585678E+10 | 0.00 | -0.163323E+11 | 0.269884E+12 |
July | 0.305306E+12 | -0.879812E+10 | 0.00 | -0.601406E+11 | 0.309639E+12 |
August | 0.284908E+12 | -0.105477E+11 | 0.00 | -0.729032E+11 | 0.346615E+12 |
September | 0.223293E+12 | -0.292567E+10 | 0.00 | -0.136953E+10 | 0.212018E+12 |
October | 0.215023E+12 | 0.459459E+10 | 0.00 | 0.150831E+12 | 0.924795E+11 |
November | 0.158601E+12 | 0.922443E+10 | 0.00 | 0.186814E+12 | 0.385195E+11 |
December | 0.152702E+12 | 0.155428E+11 | 0.00 | 0.211635E+12 | 0.148588E+11 |
Annual Sum or Average | 0.291439E+13 | 0.471342E+11 | 0.00 | 0.115756E+13 | 0.164435E+13 |
Minimum of Months | 0.152702E+12 | -0.105477E+11 | 0.00 | -0.729032E+11 | 0.100780E+11 |
Maximum of Months | 0.324725E+12 | 0.175787E+11 | 0.00 | 0.211635E+12 | 0.346615E+12 |