Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2023-10-16 08:27:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 155.31 303.83 303.83
Net Site Energy 155.31 303.83 303.83
Total Source Energy 490.67 959.93 959.93
Net Source Energy 490.67 959.93 959.93


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 6.82 0.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 36.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 20.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 154.74 0.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 6.82 0.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 36.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 20.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 24.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 6.82 0.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 8.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 36.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 10.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 20.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 24.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 90.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 118.10 1.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 302.72 1.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 90.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 118.10 1.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 302.72 1.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 154.739 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 154.739 100.00
     
Total On-Site and Utility Electric Sources 154.739 100.00
Total Electricity End Uses 154.739 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 14.33
Time Setpoint Not Met During Occupied Cooling 2.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 1433.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 9.3958 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 9.3958 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 9.3958 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 9.3958 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 9.3958 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 9.3958 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 9.3958 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 9.3958 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 9.3958 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 9.3958 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 9.3958 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 9.3958 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             9.3958 9.29 6.7800  
Conditioned Total 511.16             9.3958 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 9.3958 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-DEC-08:20 26-DEC-06:19 - - - - - - - - - - 02-JAN-12:09
Heating 7854.86 18423.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3419.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1739.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2738.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 19077.52 18423.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 7854.86 18423.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3419.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1739.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2738.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 21.60 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 25.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 114.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 65.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 78.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 490.06 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 42.25 1.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 50.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 223.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 127.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 153.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 958.73 1.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 42.25 1.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 50.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 223.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 127.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 153.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 958.73 1.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.311360
PERIMETER_ZN_1 DIRECT AIR 0.430875
PERIMETER_ZN_2 DIRECT AIR 0.250883
PERIMETER_ZN_3 DIRECT AIR 0.261791
PERIMETER_ZN_4 DIRECT AIR 0.298093
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.311360 0.311360 0.311360 0.311360 0.311360 0.311360 1.00 1.00 0.311360
PSZ-AC:2 0.430875 0.430875 0.430875 0.430875 0.430875 0.430875 1.00 1.00 0.430875
PSZ-AC:3 0.250883 0.250883 0.250883 0.250883 0.250883 0.250883 1.00 1.00 0.250883
PSZ-AC:4 0.261791 0.261791 0.261791 0.261791 0.261791 0.261791 1.00 1.00 0.261791
PSZ-AC:5 0.298093 0.298093 0.298093 0.298093 0.298093 0.298093 1.00 1.00 0.298093
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.311360 0.064622
PSZ-AC:2_OA_CONTROLLER 0.430875 0.048988
PSZ-AC:3_OA_CONTROLLER 0.250883 0.029060
PSZ-AC:4_OA_CONTROLLER 0.261791 0.048988
PSZ-AC:5_OA_CONTROLLER 0.298093 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.311360 5256.48 0.800496
PSZ-AC:2 HP COOLING COIL 0.430875 7132.51 0.800655
PSZ-AC:3 HP COOLING COIL 0.250883 4153.01 0.800655
PSZ-AC:4 HP COOLING COIL 0.261791 4372.31 0.800398
PSZ-AC:5 HP COOLING COIL 0.298093 4934.50 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.311360 0.311360 0.311360 0.311360 5256.48 5256.48 40.00 3406.87 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.430875 0.430875 0.430875 0.430875 7132.51 7132.51 40.00 4501.02 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.250883 0.250883 0.250883 0.250883 4153.01 4153.01 40.00 2788.28 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.261791 0.261791 0.261791 0.261791 4372.31 4372.31 40.00 4478.66 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.298093 0.298093 0.298093 0.298093 4934.50 4934.50 40.00 2779.65 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.311360
PSZ-AC:2 FAN 0.430875
PSZ-AC:3 FAN 0.250883
PSZ-AC:4 FAN 0.261791
PSZ-AC:5 FAN 0.298093
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.311360 5256.48
PSZ-AC:2 HEATING COIL 0.430875 7132.51
PSZ-AC:3 HEATING COIL 0.250883 4153.01
PSZ-AC:4 HEATING COIL 0.261791 4372.31
PSZ-AC:5 HEATING COIL 0.298093 4934.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 3406.87
PSZ-AC:2_SUPPHEATCOIL 4501.02
PSZ-AC:3_SUPPHEATCOIL 2788.28
PSZ-AC:4_SUPPHEATCOIL 4478.66
PSZ-AC:5_SUPPHEATCOIL 2779.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 9.396 6.780 0.000 0.000 0.000 0.000 16.176 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 9.396 6.780 0.000 0.000 0.000 0.000 16.176 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 9.396 6.780 0.000 0.000 0.000 0.000 16.176 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 9.396 6.780 0.000 0.000 0.000 0.000 16.176 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 9.396 6.780 0.000 0.000 0.000 0.000 16.176 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1406.157 9.396 174.581 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1406.157
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 1065.958 9.396 174.581 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1065.958
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 632.340 9.396 174.581 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 632.340
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 1065.958 9.396 174.581 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1065.958
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 632.340 9.396 174.581 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 632.340


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 7.646E-002 6.739E-004 9.053E-004 0.795 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.1604E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.3949E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.4394E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.6586E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2704E-003
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.4378E-003
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 6.1769E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 6.9004E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.2077E-002
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.2533E-002
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.2409E-002
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.3857E-002
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0660E-002
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.4604E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.2685E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 2.8551E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.0592E-002
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.2036E-002
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.0947E-002
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.3379E-002
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 9.0407E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.9707E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.3739E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.6377E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.1529E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.3799E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.4336E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.6483E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2638E-003
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.4214E-003
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 6.1268E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 6.7888E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.0702E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.0940E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.3601E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.3815E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1983E-003
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.2146E-003
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 5.7821E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 5.8578E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.0641E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.0687E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.3549E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.3589E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1941E-003
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1971E-003
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 5.7597E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 5.7743E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.2171E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.8786E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.5655E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 4.2428E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.9803E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.3594E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 9.7824E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.0987E-003
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.4473E-003
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.6230E-003
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.3444E-003
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.4748E-003
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.2059E-003
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.2658E-003
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.6923E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0358E-003
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.9906E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 4.5998E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.8243E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.8256E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.1770E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.3265E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.7355E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.0307E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.5264E-002
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.2483E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.6227E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.0135E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2005E-002
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 6.1214E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.6490E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.2549E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.8345E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.2968E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.8521E-003
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.3489E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.3300E-003
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.5591E-003
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.7407E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0469E-003
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 7.5450E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 8.9729E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.0570E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.1777E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.9451E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.6925E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.1140E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.7467E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.6938E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 4.0420E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.7020E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.0854E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.5433E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1021E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.9914E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.5353E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 6.5543E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 4.7846E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.1025E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.6165E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.7221E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.3348E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.7858E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.9695E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 7.7284E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 9.4518E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.2006E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.5378E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.0557E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.8959E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.2147E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.9704E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.9053E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 7.1167E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.5317E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.7009E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.4972E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.6127E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.7947E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.8788E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.8444E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.8866E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.4816E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.5158E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.4588E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.4826E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.7693E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.7851E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.7513E-003
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 2.1560E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.7406E-003
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 2.1638E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.2979E-003
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.5158E-003
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.7565E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0480E-003
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.3807E-002
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.6925E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.4370E-002
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.3622E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1493E-002
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.8143E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.6265E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2130E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 6.0202E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.5514E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.8041E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.7452E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.0783E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.1961E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.7319E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.9957E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.4023E-003
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.5799E-003
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.2833E-003
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.4147E-003
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1736E-003
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.2316E-003
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 9.7064E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.0368E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3485.84520 4183.01423 0.25947 0.31136 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 28.77600 8.82049E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 781.80480 938.16576 3.41934E-002 6.46221E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4823.70481 5788.44578 0.35906 0.43087 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 29.40000 8.82150E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 2555.72856 3066.87428 0.11177 0.13413 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2808.84340 3370.61208 0.20907 0.25088 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 25.44800 8.81519E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1616.06834 1939.28201 7.06767E-002 8.48120E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 2930.89439 3517.07327 0.21816 0.26179 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 28.88000 8.82066E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 2536.82535 3044.19042 0.11095 0.13313 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3337.38661 4004.86393 0.24841 0.29809 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 26.90400 8.81750E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1608.76975 1930.52371 7.03575E-002 8.44290E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4494.99 0.31136 0.31136 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC:1 Heating Sensible 3406.87 6.46221E-002 6.46221E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 6020.95 0.43087 0.43087 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC:2 Heating Sensible 4501.02 0.13413 0.13413 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3372.51 0.25088 0.25088 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2788.28 8.48120E-002 8.48120E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 3754.29 0.26179 0.26179 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 PSZ-AC:4 Heating Sensible 4478.66 0.13313 0.13313 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4047.42 0.29809 0.29809 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2779.65 8.44290E-002 8.44290E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.31136
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.43087
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.25088
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.26179
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29809
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.31136
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.31136
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.31136
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.31136
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.31136
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.31136
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.43087
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.43087
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.43087
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.43087
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.43087
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.43087
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.25088
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.25088
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.25088
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.25088
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.25088
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.25088
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.26179
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.26179
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.26179
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.26179
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.26179
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.26179
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29809
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29809
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29809
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.29809
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29809
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.29809
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.31136
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.43087
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.25088
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.26179
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.29809
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.31136
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.31136
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5256.47949
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80050
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.31136
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.31136
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.31136
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.31136
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5256.47949
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5256.47949
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3406.86872
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.31136
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.31136
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5256.47949
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 3406.86872
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.43087
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.43087
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7132.50909
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.43087
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.43087
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.43087
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.43087
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7132.50909
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7132.50909
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4501.01535
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.43087
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.43087
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7132.50909
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 4501.01535
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.25088
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.25088
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4153.00540
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.25088
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.25088
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.25088
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.25088
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4153.00540
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4153.00540
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2788.28204
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.25088
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.25088
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4153.00540
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2788.28204
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.26179
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26179
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4372.30943
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80040
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.26179
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.26179
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.26179
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.26179
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4372.30943
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4372.30943
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4478.66193
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.26179
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.26179
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4372.30943
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 4478.66193
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29809
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29809
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4934.49592
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29809
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29809
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29809
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29809
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4934.49592
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4934.49592
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2779.65131
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.29809
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29809
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4934.49592
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2779.65131
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5012.4 3.30 11.27 11.79 11.15 11.03
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6794.8 3.29 11.22 11.74 11.10 10.96
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 3956.4 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 4167.1 3.29 11.24 11.76 11.12 10.99
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4700.9 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5503.6 3063.1 7.33 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 7474.4 4162.8 7.33 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4352.0 2423.8 7.33 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 4580.1 2550.0 7.34 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5171.0 2879.9 7.32 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.8720078963E-003 1.5679352201E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 0.2152228416 0.1990379999 Pass Pass 1.0871304486 2.1745437757 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.2285092544 0.2132378374 Pass Pass 0.7344524371 1.6473734118 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.2179157339 0.2012300596 Pass Pass 0.8956383389 1.9640874276 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.2297376765 0.2144675011 Pass Pass 0.6731762641 1.5425120048 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.1133563772 0.1129116225 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 777.57 34.10 0.00 38.07 36.59 886.33



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.547 0.596 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.547 0.596 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.118 0.122 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.118 0.122 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.38_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.38_SHGC_SOUTH_0.36   3.91 0.00 0.00 3.91 3.91 2.159 0.361 0.397             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.38_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.38_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.38_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.38_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.38_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.38_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.38_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.38_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.38_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.159 0.361 0.397             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.159 0.361 0.397                      
North Total or Average             16.72 2.159 0.361 0.397                      
Non-North Total or Average             42.93 2.159 0.361 0.397                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 1.00 1.00 1.00 0.00 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 1.00 1.00 1.00 0.00 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 1.00 1.00 1.00 0.00 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 1.00 1.00 1.00 0.00 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 1.00 1.00 1.00 0.00 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 1.00 1.00 1.00 0.02 0.54 0.28 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.18 0.81 0.62 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.04 0.00 1.00 0.00 0.00 1.00 0.73 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.86 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.86 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.86 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.86 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 9.3958 149.66 1406.16 LightsWired LTG_SCH_OFFICE 55.32 168.00 43.88 0.0000 Y 11.58
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 9.3958 113.45 1065.96 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.83 0.0000 Y 7.37
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 9.3958 67.30 632.34 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.33 0.0000 Y 4.55
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 9.3958 113.45 1065.96 LightsWired LTG_SCH_OFFICE 55.32 168.00 40.00 0.0000 Y 8.00
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 9.3958 67.30 632.34 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.39 0.0000 Y 4.56
Interior Lighting Total       9.3958 511.16 4802.75               36.06


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Stepped 0.24 1065.96 255.72
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Stepped 0.03 1065.96 32.19
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Stepped 0.24 632.34 151.70
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Stepped 0.03 632.34 19.10
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Stepped 0.24 1065.96 255.72
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Stepped 0.03 1065.96 32.19
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Stepped 0.24 632.34 151.70
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Stepped 0.03 632.34 19.10


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   42.59 42.59 0.70
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.55 63.07 2.37
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.55 47.80 6.94
Exterior Lighting Total 1061.67           10.01



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5256.48 4207.79 1048.69 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7132.51 5710.68 1421.83 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4153.01 3325.13 827.88 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4372.31 3499.59 872.72 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4934.50 3950.83 983.67 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5012.4 3.30 11.27 11.79 11.15 11.03
PSZ-AC:2 HP COOLING COIL   6794.8 3.29 11.22 11.74 11.10 10.96
PSZ-AC:3 HP COOLING COIL   3956.4 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   4167.1 3.29 11.24 11.76 11.12 10.99
PSZ-AC:5 HP COOLING COIL   4700.9 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5503.6 3063.1 7.33 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 7474.4 4162.8 7.33 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4352.0 2423.8 7.33 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 4580.1 2550.0 7.34 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5171.0 2879.9 7.32 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5256.48 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   3406.87 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   7132.51 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   4501.02 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4153.01 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2788.28 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   4372.31 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   4478.66 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   4934.50 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2779.65 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.31 348.76 1120.11 1.00 1.87 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.43 482.63 1120.11 1.00 1.68 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.25 281.02 1120.11 1.00 2.03 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.26 293.23 1120.11 1.00 2.00 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.30 333.90 1120.11 1.00 1.90 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3485.85 4183.01 27.95 0.259 0.311 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 23.89 23.89 0.00901 28.78 0.00882 0.065 0.00
PERIMETER_ZN_1 4823.70 5788.45 51.02 0.359 0.431 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 23.89 23.89 0.00878 29.40 0.00882 0.049 0.00
PERIMETER_ZN_2 2808.84 3370.61 50.08 0.209 0.251 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 23.89 23.89 0.00879 25.45 0.00882 0.029 0.00
PERIMETER_ZN_3 2930.89 3517.07 31.00 0.218 0.262 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 23.89 23.89 0.00896 28.88 0.00882 0.049 0.00
PERIMETER_ZN_4 3337.39 4004.86 59.51 0.248 0.298 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 23.89 23.89 0.00874 26.90 0.00882 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 781.80 938.17 6.27 0.034 0.065 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 -4.20 0.00269 0.065 0.00
PERIMETER_ZN_1 2555.73 3066.87 27.03 0.112 0.134 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 -4.20 0.00269 0.049 0.00
PERIMETER_ZN_2 1616.07 1939.28 28.82 0.071 0.085 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00746 -4.20 0.00269 0.029 0.00
PERIMETER_ZN_3 2536.83 3044.19 26.83 0.111 0.133 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 -4.20 0.00269 0.049 0.00
PERIMETER_ZN_4 1608.77 1930.52 28.69 0.070 0.084 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00745 -4.20 0.00269 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.31 0.31 0.06 0.06 0.3114 0.3114 0.3114 1.0000 1.0000
PSZ-AC:2 0.43 0.43 0.13 0.13 0.4309 0.4309 0.4309 1.0000 1.0000
PSZ-AC:3 0.25 0.25 0.08 0.08 0.2509 0.2509 0.2509 1.0000 1.0000
PSZ-AC:4 0.26 0.26 0.13 0.13 0.2618 0.2618 0.2618 1.0000 1.0000
PSZ-AC:5 0.30 0.30 0.08 0.08 0.2981 0.2981 0.2981 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5256.479 4207.788 0.311360 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 5207.70 4813.60 0.311360 25.83 17.27 0.00897357 12.80 11.97 0.00850000 28.78 0.00882049 18.14 20.7548 23.89 0.00901626 48.1231 3473.07 0.00 5255.58 4172.35
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5256.479 5256.479 0.311360 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 5256.48 5256.48 0.311360 15.86 11.63 0.00689799 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 20.7548 21.11 0.00800000 50.6363 781.02 0.00 5263.39 5263.39
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 3406.869 3406.869 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 3406.87 3406.87 0.311360 15.86 11.63 0.00689799 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 20.7548 21.11 0.00800000 50.6363 781.02 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7132.509 5710.681 0.430875 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 6993.09 6654.39 0.430875 25.44 16.99 0.00878659 12.80 11.97 0.00850000 29.40 0.00882150 18.34 11.3694 23.89 0.00878211 46.8916 4823.70 0.00 7131.29 5661.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7132.509 7132.509 0.430875 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7132.51 7132.51 0.430875 18.23 12.63 0.00693585 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 11.3694 21.11 0.00748046 47.3900 2555.73 0.00 7141.88 7141.88
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 4501.015 4501.015 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4501.02 4501.02 0.430875 18.23 12.63 0.00693585 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 11.3694 21.11 0.00748046 47.3900 2555.73 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4153.005 3325.126 0.250883 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 4144.16 3933.94 0.250883 24.99 16.84 0.00879145 12.80 11.97 0.00850000 25.45 0.00881519 17.01 11.5831 23.89 0.00878834 46.9224 2808.84 0.00 4152.29 3296.67
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4153.005 4153.005 0.250883 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4153.01 4153.01 0.250883 18.18 12.58 0.00690323 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 11.5831 21.11 0.00745514 47.2318 1616.07 0.00 4158.46 4158.46
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2788.282 2788.282 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2788.28 2788.28 0.250883 18.18 12.58 0.00690323 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 11.5831 21.11 0.00745514 47.2318 1616.07 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4372.309 3499.589 0.261791 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 4322.97 4021.33 0.261791 25.75 17.21 0.00893150 12.80 11.97 0.00850000 28.88 0.00882066 18.17 18.7125 23.89 0.00895851 47.8191 2922.37 0.00 4371.56 3469.97
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4372.309 4372.309 0.261791 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4372.31 4372.31 0.261791 16.37 11.52 0.00658127 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 18.7125 21.11 0.00747697 47.3682 2536.83 0.00 4378.06 4378.06
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 4478.662 4478.662 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4478.66 4478.66 0.261791 16.37 11.52 0.00658127 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 18.7125 21.11 0.00747697 47.3682 2536.83 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4934.496 3950.830 0.298093 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 4891.29 4678.48 0.298093 25.11 16.84 0.00875013 12.80 11.97 0.00850000 26.90 0.00881750 17.51 9.7487 23.89 0.00874286 46.6831 3337.39 0.00 4933.65 3917.02
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4934.496 4934.496 0.298093 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4934.50 4934.50 0.298093 18.64 12.85 0.00698863 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 9.7487 21.11 0.00745293 47.2180 1608.77 0.00 4940.98 4940.98
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2779.651 2779.651 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2779.65 2779.65 0.298093 18.64 12.85 0.00698863 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 9.7487 21.11 0.00745293 47.2180 1608.77 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5256.479 4207.788 0.311360 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.5214 1004.8586 1.1870 PSZ-AC:1 FAN Fan:OnOff 0.311360 0.36958156   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 Sensible 5207.70 4813.60 0.9907 0.36958156 0.311360 25.83 17.27 0.00897357 48825.5 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 348.757 4858.94 28.78 0.00882049 18.14 0.06462207 20.7548 23.89 0.00901366 23.89 0.00901626 48.1231 3473.07 0.00 5255.58 4172.35 0.35498588 26.67 19.44 0.01118466 55322.4 15.18 14.47 0.00998825 40517.4
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5256.479 5256.479 0.311360 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:1 FAN Fan:OnOff 0.311360 0.36958156   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 5256.48 5256.48 1.0000 0.36958156 0.311360 15.86 11.63 0.00689799 33388.5 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5256.48 -4.20 0.00269032 -4.20 0.06462207 20.7548 21.11 0.00800000 21.11 0.00800000 50.6363 781.02 0.00 5263.39 5263.39 0.36305094 21.11 15.56 0.00875166 43444.1 35.31 20.32 0.00875166 57941.8
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3406.869 3406.869 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:1 FAN Fan:OnOff 0.311360 0.36958156   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 3406.87 3406.87 1.0000 0.36958156 0.311360 15.86 11.63 0.00689799 33388.5 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3406.87 -4.20 0.00269032 -4.20 0.06462207 20.7548 21.11 0.00800000 21.11 0.00800000 50.6363 781.02 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7132.509 5710.681 0.430875 -999.0 -999.000 -999.0000 1.03081 1.00000 1021.1738 1004.8586 1.1870 PSZ-AC:2 FAN Fan:OnOff 0.430875 0.51144450   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 Sensible 6993.09 6654.39 0.9805 0.51144450 0.430875 25.44 16.99 0.00878659 47953.0 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 482.626 6510.46 29.40 0.00882150 18.34 0.04898771 11.3694 23.89 0.00878211 23.89 0.00878211 46.8916 4823.70 0.00 7131.29 5661.80 0.49124631 26.67 19.44 0.01118466 55322.4 15.41 14.58 0.01001183 40805.7
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7132.509 7132.509 0.430875 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:2 FAN Fan:OnOff 0.430875 0.51144450   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7132.51 7132.51 1.0000 0.51144450 0.430875 18.23 12.63 0.00693585 35900.9 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7132.51 -4.20 0.00269032 -4.20 0.04898771 11.3694 21.11 0.00748046 21.11 0.00748046 47.3900 2555.73 0.00 7141.88 7141.88 0.50240712 21.11 15.56 0.00875166 43444.1 35.03 20.23 0.00875166 57659.4
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4501.015 4501.015 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:2 FAN Fan:OnOff 0.430875 0.51144450   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4501.02 4501.02 1.0000 0.51144450 0.430875 18.23 12.63 0.00693585 35900.9 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4501.02 -4.20 0.00269032 -4.20 0.04898771 11.3694 21.11 0.00748046 21.11 0.00748046 47.3900 2555.73 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4153.005 3325.126 0.250883 -999.0 -999.000 -999.0000 1.08275 1.00000 1021.1829 1004.8586 1.1870 PSZ-AC:3 FAN Fan:OnOff 0.250883 0.29779588   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 Sensible 4144.16 3933.94 0.9979 0.29779588 0.250883 24.99 16.84 0.00879145 47510.6 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 281.016 3863.14 25.45 0.00881519 17.01 0.02906014 11.5831 23.89 0.00878834 23.89 0.00878834 46.9224 2808.84 0.00 4152.29 3296.67 0.28603519 26.67 19.44 0.01118466 55322.4 15.41 14.58 0.01001183 40805.7
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4153.005 4153.005 0.250883 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:3 FAN Fan:OnOff 0.250883 0.29779588   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4153.01 4153.01 1.0000 0.29779588 0.250883 18.18 12.58 0.00690323 35763.1 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4153.01 -4.20 0.00269032 -4.20 0.02906014 11.5831 21.11 0.00745514 21.11 0.00745514 47.2318 1616.07 0.00 4158.46 4158.46 0.29253373 21.11 15.56 0.00875166 43444.1 35.03 20.23 0.00875166 57659.4
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2788.282 2788.282 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:3 FAN Fan:OnOff 0.250883 0.29779588   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2788.28 2788.28 1.0000 0.29779588 0.250883 18.18 12.58 0.00690323 35763.1 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2788.28 -4.20 0.00269032 -4.20 0.02906014 11.5831 21.11 0.00745514 21.11 0.00745514 47.2318 1616.07 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4372.309 3499.589 0.261791 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.4432 1004.8586 1.1870 PSZ-AC:4 FAN Fan:OnOff 0.261791 0.31074389   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:50:00 Sensible 4322.97 4021.33 0.9887 0.31074389 0.261791 25.75 17.21 0.00893150 48636.3 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 293.235 4029.74 28.88 0.00882066 18.17 0.04898771 18.7125 23.89 0.00895702 23.89 0.00895851 47.8191 2922.37 0.00 4371.56 3469.97 0.29847185 26.67 19.44 0.01118466 55322.4 15.31 14.53 0.01000032 40675.9
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4372.309 4372.309 0.261791 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:4 FAN Fan:OnOff 0.261791 0.31074389   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4372.31 4372.31 1.0000 0.31074389 0.261791 16.37 11.52 0.00658127 33111.9 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4372.31 -4.20 0.00269032 -4.20 0.04898771 18.7125 21.11 0.00747697 21.11 0.00747697 47.3682 2536.83 0.00 4378.06 4378.06 0.30525295 21.11 15.56 0.00875166 43444.1 35.16 20.27 0.00875166 57786.5
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4478.662 4478.662 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:4 FAN Fan:OnOff 0.261791 0.31074389   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4478.66 4478.66 1.0000 0.31074389 0.261791 16.37 11.52 0.00658127 33111.9 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4478.66 -4.20 0.00269032 -4.20 0.04898771 18.7125 21.11 0.00747697 21.11 0.00747697 47.3682 2536.83 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4934.496 3950.830 0.298093 -999.0 -999.000 -999.0000 1.07502 1.00000 1021.1061 1004.8586 1.1870 PSZ-AC:5 FAN Fan:OnOff 0.298093 0.35383352   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 4891.29 4678.48 0.9912 0.35383352 0.298093 25.11 16.84 0.00875013 47521.1 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 333.896 4557.39 26.90 0.00881750 17.51 0.02906014 9.7487 23.89 0.00874286 23.89 0.00874286 46.6831 3337.39 0.00 4933.65 3917.02 0.33985977 26.67 19.44 0.01118466 55322.4 15.41 14.58 0.01001183 40805.7
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4934.496 4934.496 0.298093 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:5 FAN Fan:OnOff 0.298093 0.35383352   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4934.50 4934.50 1.0000 0.35383352 0.298093 18.64 12.85 0.00698863 36452.1 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4934.50 -4.20 0.00269032 -4.20 0.02906014 9.7487 21.11 0.00745293 21.11 0.00745293 47.2180 1608.77 0.00 4940.98 4940.98 0.34758118 21.11 15.56 0.00875166 43444.1 35.03 20.23 0.00875166 57659.4
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2779.651 2779.651 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC:5 FAN Fan:OnOff 0.298093 0.35383352   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2779.65 2779.65 1.0000 0.35383352 0.298093 18.64 12.85 0.00698863 36452.1 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2779.65 -4.20 0.00269032 -4.20 0.02906014 9.7487 21.11 0.00745293 21.11 0.00745293 47.2180 1608.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 1086.83 2391.17 129.33
PERIMETER_ZN_1 1501.17 3058.83 893.83
PERIMETER_ZN_2 1479.33 2628.33 1073.83
PERIMETER_ZN_3 1617.33 3423.83 1340.17
PERIMETER_ZN_4 1766.33 3150.17 1231.50
ATTIC 0.00 0.00 0.00
Facility 2421.83 3490.50 1433.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 2.50 2.67 2.50 2.67
PERIMETER_ZN_1 3.50 0.00 3.50 0.00
PERIMETER_ZN_2 7.00 0.00 5.17 0.00
PERIMETER_ZN_3 16.00 0.00 14.33 0.00
PERIMETER_ZN_4 6.17 0.00 4.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 18.67 2.67 14.33 2.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.367 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.366 0.260 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.333 0.063 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.365 0.051 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.366 0.057 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 703501.65 0.00 703501.65 0.00 703501.65 2037921.45 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_1 533299.81 0.00 533299.81 516414.74 1049714.55 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_2 316360.31 0.00 316360.31 140974.35 457334.66 916440.58 5736.00 3024.00 0.00 756.00
PERIMETER_ZN_3 533299.81 0.00 533299.81 211461.52 744761.33 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_4 316360.31 0.00 316360.31 140974.35 457334.66 916440.58 5736.00 3024.00 0.00 0.00
Total Facility 2402821.88 0.00 2402821.88 1009824.96 3412646.84 6960555.45 5736.00 3024.00 0.00 756.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0456 0.0000 0.0456 0.0000 0.0456 0.0646 1260.00 3024.00 0.00
PERIMETER_ZN_1 0.0346 0.0000 0.0346 0.0246 0.0592 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_2 0.0187 0.0000 0.0187 0.0035 0.0222 0.0291 1260.00 2268.00 0.00
PERIMETER_ZN_3 0.0346 0.0000 0.0346 0.0048 0.0394 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_4 0.0205 0.0000 0.0205 0.0032 0.0237 0.0291 1260.00 3024.00 0.00
Total Facility 0.1540 0.0000 0.1540 0.0361 0.1901 0.2207 1260.00 3024.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 991196.63 0.00 991196.63 2037921.45 5736.00 0.00 3024.00 0.00
PSZ-AC:2 751391.23 0.00 751391.23 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:3 445734.94 0.00 445734.94 916440.58 5736.00 0.00 3024.00 756.00
PSZ-AC:4 751391.23 0.00 751391.23 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:5 445734.94 0.00 445734.94 916440.58 5736.00 0.00 3024.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0643 0.0000 0.0643 0.0646 1260.00 0.00 3024.00
PSZ-AC:2 0.0487 0.0000 0.0487 0.0490 1260.00 0.00 3024.00
PSZ-AC:3 0.0263 0.0000 0.0263 0.0291 1260.00 0.00 2268.00
PSZ-AC:4 0.0487 0.0000 0.0487 0.0490 1260.00 0.00 3024.00
PSZ-AC:5 0.0289 0.0000 0.0289 0.0291 1260.00 0.00 3024.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0910 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0690 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0409 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0690 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0409 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 154.74 1248.68 01-JAN-08:10 19077.52 26-DEC-08:20
Electricity:Building 84.36 677.68 01-JAN-00:10 6744.96 02-JAN-08:10
Electricity:Zone:CORE_ZN 25.72 198.41 01-JAN-00:10 1974.80 02-JAN-08:10
Electricity:SpaceType:GENERAL 84.36 677.68 01-JAN-00:10 6744.96 02-JAN-08:10
InteriorLights:Electricity 36.06 110.04 01-JAN-00:10 3419.66 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_ZN 11.58 32.22 01-JAN-00:10 1001.21 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 36.06 110.04 01-JAN-00:10 3419.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity 36.06 110.04 01-JAN-00:10 3419.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 11.58 32.22 01-JAN-00:10 1001.21 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 36.06 110.04 01-JAN-00:10 3419.66 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_1 18.09 150.41 01-JAN-00:10 1497.03 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.37 24.42 01-JAN-00:10 758.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.37 24.42 01-JAN-00:10 758.98 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_2 10.91 89.23 01-JAN-00:10 888.06 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.55 14.49 01-JAN-00:10 450.24 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.55 14.49 01-JAN-00:10 450.24 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_3 18.72 150.41 01-JAN-00:10 1497.03 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 8.00 24.42 01-JAN-00:10 758.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 8.00 24.42 01-JAN-00:10 758.98 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_4 10.92 89.23 01-JAN-00:10 888.06 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.56 14.49 01-JAN-00:10 450.24 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.56 14.49 01-JAN-00:10 450.24 02-JAN-08:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
ElectricityPurchased:Plant 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
Cogeneration:ElectricityPurchased 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
General:Cogeneration:ElectricityPurchased 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
ElectricityNet:Plant 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
Cogeneration:ElectricityNet 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
General:Cogeneration:ElectricityNet 154.74 1248.68 11-JUN-09:30 19077.52 26-DEC-08:20
ExteriorLights:Electricity 10.01 0.00 01-JAN-08:10 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 10.01 0.00 01-JAN-08:10 1061.67 01-JAN-06:10
Electricity:HVAC 35.57 0.00 01-JAN-00:10 9942.63 21-FEB-08:00
Fans:Electricity 20.57 0.00 01-JAN-00:10 1739.53 02-JAN-06:20
General:Fans:Electricity 20.57 0.00 01-JAN-00:10 1739.53 02-JAN-06:20
Cooling:Electricity 8.19 0.00 01-JAN-00:10 4727.53 10-AUG-16:00
General:Cooling:Electricity 8.19 0.00 01-JAN-00:10 4727.53 10-AUG-16:00
Heating:Electricity 6.82 0.00 01-JAN-00:10 8203.10 21-FEB-08:00
General:Heating:Electricity 6.82 0.00 01-JAN-00:10 8203.10 21-FEB-08:00
Electricity:Plant 24.79 571.00 01-JAN-00:10 2813.12 13-FEB-12:50
WaterSystems:Electricity 24.79 571.00 01-JAN-00:10 2813.12 13-FEB-12:50
Water Heater:WaterSystems:Electricity 24.79 571.00 01-JAN-00:10 2813.12 13-FEB-12:50
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.57 0.00 01-JAN-00:10 18423.30 26-DEC-06:20
NaturalGas:HVAC 0.57 0.00 01-JAN-00:10 18423.30 26-DEC-06:20
Heating:NaturalGas 0.57 0.00 01-JAN-00:10 18423.30 26-DEC-06:20
General:Heating:NaturalGas 0.57 0.00 01-JAN-00:10 18423.30 26-DEC-06:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 10-MAR-12:40
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 10-MAR-12:40
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 13-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 13-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 105.51 0.00 01-JAN-00:10 62261.32 17-JAN-06:20
EnergyTransfer:Building 51.80 0.00 01-JAN-00:10 31788.89 17-JAN-06:20
EnergyTransfer:Zone:CORE_ZN 15.64 0.00 01-JAN-00:10 5839.01 17-JAN-06:20
Heating:EnergyTransfer 12.97 0.00 01-JAN-00:10 31788.89 17-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.65 0.00 01-JAN-00:10 5839.01 17-JAN-06:20
General:Heating:EnergyTransfer 12.97 0.00 01-JAN-00:10 31788.89 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.65 0.00 01-JAN-00:10 5839.01 17-JAN-06:20
Cooling:EnergyTransfer 38.83 0.00 01-JAN-00:10 15250.84 14-AUG-15:30
Cooling:EnergyTransfer:Zone:CORE_ZN 14.99 0.00 01-JAN-00:10 4143.90 14-AUG-05:10
General:Cooling:EnergyTransfer 38.83 0.00 01-JAN-00:10 15250.84 14-AUG-15:30
General:Cooling:EnergyTransfer:Zone:CORE_ZN 14.99 0.00 01-JAN-00:10 4143.90 14-AUG-05:10
EnergyTransfer:Zone:PERIMETER_ZN_1 12.58 0.00 01-JAN-00:10 8611.81 17-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.89 0.00 01-JAN-00:10 8611.81 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.89 0.00 01-JAN-00:10 8611.81 17-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 8.69 0.00 01-JAN-00:10 5183.16 11-SEP-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 8.69 0.00 01-JAN-00:10 5183.16 11-SEP-14:00
EnergyTransfer:Zone:PERIMETER_ZN_2 7.06 0.00 01-JAN-00:10 5418.07 17-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 2.37 0.00 01-JAN-00:10 5418.07 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 2.37 0.00 01-JAN-00:10 5418.07 17-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 4.69 0.00 01-JAN-00:10 2835.90 24-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 4.69 0.00 01-JAN-00:10 2835.90 24-JUL-09:00
EnergyTransfer:Zone:PERIMETER_ZN_3 9.71 0.00 01-JAN-00:10 6655.92 21-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.77 0.00 01-JAN-00:10 6655.92 21-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.77 0.00 01-JAN-00:10 6655.92 21-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 5.94 0.00 01-JAN-00:10 2680.46 24-JUL-15:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 5.94 0.00 01-JAN-00:10 2680.46 24-JUL-15:10
EnergyTransfer:Zone:PERIMETER_ZN_4 6.82 0.00 01-JAN-00:10 5465.72 17-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 2.29 0.00 01-JAN-00:10 5465.72 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 2.29 0.00 01-JAN-00:10 5465.72 17-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 4.53 0.00 01-JAN-00:10 2871.47 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 4.53 0.00 01-JAN-00:10 2871.47 10-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
EnergyTransfer:HVAC 53.71 0.00 01-JAN-00:10 30472.43 17-JAN-06:20
CoolingCoils:EnergyTransfer 37.36 0.00 01-JAN-00:10 19794.69 10-AUG-15:30
HeatingCoils:EnergyTransfer 16.35 0.00 01-JAN-00:10 30472.43 17-JAN-06:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 110.28 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.650 -14.988 0.000 0.000 5.199 11.582 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.583
PERIMETER_ZN_1 0.000 0.000 3.892 -8.685 0.000 0.000 4.019 7.370 10.719 16.340 0.000 0.048 0.000 0.000 -9.085 0.000 -6.764 -17.855
PERIMETER_ZN_2 0.000 0.000 2.368 -4.689 0.000 0.000 1.763 4.549 6.359 6.367 0.000 0.004 0.000 0.000 -4.688 0.000 -1.818 -10.215
PERIMETER_ZN_3 0.000 0.000 3.773 -5.936 0.000 0.000 4.094 8.004 10.719 3.466 0.000 0.007 0.000 0.000 -7.187 0.000 -2.671 -14.269
PERIMETER_ZN_4 0.000 0.000 2.287 -4.531 0.000 0.000 2.400 4.556 6.359 6.904 0.000 0.003 0.000 0.000 -4.892 0.000 -1.855 -11.231
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9.254 21.934 0.000 0.000 0.000 -31.188 -0.000
Total Facility 0.000 0.000 12.971 -38.829 0.000 0.000 17.475 36.062 48.296 33.077 0.000 9.315 21.935 0.000 -25.851 0.000 -44.296 -70.153


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 05-OCT-05:03 0.00 0.00 0.00 -4671.96 0.00 0.00 57.16 32.22 486.79 0.00 0.00 0.00 4095.79 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 24-JUL-05:01 0.00 0.00 0.00 -6385.51 0.00 0.00 41.63 24.42 369.02 0.00 0.00 0.00 6361.62 0.00 -289.71 0.00 -121.48 0.00
PERIMETER_ZN_2 24-JUL-05:01 0.00 0.00 0.00 -3742.41 0.00 0.00 23.93 14.49 218.91 679.58 0.00 0.00 2814.06 0.00 -0.00 0.00 -8.55 0.00
PERIMETER_ZN_3 24-JUL-05:01 0.00 0.00 0.00 -3991.92 0.00 0.00 42.99 24.42 369.02 317.90 0.00 0.00 3249.68 0.00 -0.00 0.00 -12.10 0.00
PERIMETER_ZN_4 24-JUL-05:01 0.00 0.00 0.00 -4420.90 0.00 0.00 22.98 14.49 218.91 0.00 0.00 0.00 4347.68 0.00 -174.31 0.00 -8.85 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-JUL-05:01 0.00 0.00 0.00 -22908.60 0.00 0.00 182.09 110.04 1662.65 997.48 0.00 544.56 20026.78 0.00 -464.03 0.00 -150.97 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 23-JAN-06:01 0.00 0.00 7908.88 0.00 0.00 0.00 81.55 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8509.45
PERIMETER_ZN_1 23-JAN-06:01 0.00 0.00 10799.42 0.00 0.00 0.00 66.41 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -469.35 0.00 -239.35 -10550.58
PERIMETER_ZN_2 23-JAN-06:01 0.00 0.00 6450.60 0.00 0.00 0.00 40.30 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -238.80 0.00 -45.78 -6439.71
PERIMETER_ZN_3 13-FEB-06:01 0.00 0.00 7566.54 0.00 0.00 0.00 68.69 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -431.99 0.00 -218.62 -7378.07
PERIMETER_ZN_4 27-MAR-05:01 0.00 0.00 7147.67 0.00 0.00 0.00 37.68 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -278.68 0.00 -162.74 -6977.34
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 23-JAN-06:01 0.00 0.00 39713.92 0.00 0.00 0.00 296.44 110.04 1662.65 0.00 0.00 441.90 0.00 0.00 -1295.62 0.00 -398.67 -40530.67



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3114 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3114 0.2075 1.0000 Not calculated 0.0646 0.2075    
PSZ-AC:2 0.4309 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4309 0.1137 1.0000 Not calculated 0.0490 0.1137    
PSZ-AC:3 0.2509 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2509 0.1158 1.0000 Not calculated 0.0291 0.1158    
PSZ-AC:4 0.2618 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2618 0.1871 1.0000 Not calculated 0.0490 0.1871    
PSZ-AC:5 0.2981 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2981 0.0975 1.0000 Not calculated 0.0291 0.0975    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3114 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3114 1.0000 1.0000 Not calculated 0.0646 0.2075    
PSZ-AC:2 0.4309 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4309 1.0000 1.0000 Not calculated 0.0490 0.1137    
PSZ-AC:3 0.2509 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2509 1.0000 1.0000 Not calculated 0.0291 0.1158    
PSZ-AC:4 0.2618 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2618 1.0000 1.0000 Not calculated 0.0490 0.1871    
PSZ-AC:5 0.2981 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2981 1.0000 1.0000 Not calculated 0.0291 0.0975    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3114 0.3114 0.3114 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4309 0.4309 0.4309 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2509 0.2509 0.2509 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2618 0.2618 0.2618 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2981 0.2981 0.2981 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3114 0.3114 0.3114 0.3114 0.0646 1.0000
PSZ-AC:2 0.4309 0.4309 0.4309 0.4309 0.0490 1.0000
PSZ-AC:3 0.2509 0.2509 0.2509 0.2509 0.0291 1.0000
PSZ-AC:4 0.2618 0.2618 0.2618 0.2618 0.0490 1.0000
PSZ-AC:5 0.2981 0.2981 0.2981 0.2981 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3114 0.3114 0.3114 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4309 0.4309 0.4309 No 0.0490 0.3652 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2509 0.2509 0.2509 No 0.0291 0.3426 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2618 0.2618 0.2618 No 0.0490 0.3680 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2981 0.2981 0.2981 No 0.0291 0.3442 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3114 0.3114 0.3114 0.3114 0.0646 1.0000
PSZ-AC:2 0.4309 0.4309 0.4309 0.4309 0.0490 1.0000
PSZ-AC:3 0.2509 0.2509 0.2509 0.2509 0.0291 1.0000
PSZ-AC:4 0.2618 0.2618 0.2618 0.2618 0.0490 1.0000
PSZ-AC:5 0.2981 0.2981 0.2981 0.2981 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 14.33
Number of hours cooling loads not met 2.67
Number of hours not met 17.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 6.82 8203.10 0.57 18423.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 8.19 4727.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 36.06 3419.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 10.01 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 20.57 1739.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 24.79 2813.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 154.74
Natural Gas 0.00 0.57
Additional 0.00 0.00
Total 48.30 155.31


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 70.55
Space Heating 13.34
Space Cooling 16.02
Fans (All) 40.23
Service Water Heating 48.50
Receptacle Equipment 94.48
Miscellaneous (All) 302.72
Subtotal 302.72


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.11
Service Water Heating 0.00
Miscellaneous (All) 1.11
Subtotal 1.11


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 23.22
Space Heating 4.76
Space Cooling 5.27
Fans (All) 13.24
Service Water Heating 15.96
Receptacle Equipment 31.10
Miscellaneous 6.45


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8743.33 16.67 0.00 0.00 0.00
PERIMETER_ZN_1 8665.33 94.67 0.00 0.00 0.00
PERIMETER_ZN_2 8704.33 55.67 0.00 0.00 0.00
PERIMETER_ZN_3 8759.67 0.33 0.00 0.00 0.00
PERIMETER_ZN_4 8587.00 173.00 0.00 0.00 0.00
ATTIC 7442.67 521.00 402.50 390.33 3.50
Min 7442.67 0.33 0.00 0.00 0.00
Max 8759.67 521.00 402.50 390.33 3.50
Average 8483.72 143.56 67.08 65.06 0.58
Sum 50902.33 861.33 402.50 390.33 3.50


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 8000.67 759.33 0.00 0.00 0.00
PERIMETER_ZN_1 8649.33 110.67 0.00 0.00 0.00
PERIMETER_ZN_2 8703.67 56.33 0.00 0.00 0.00
PERIMETER_ZN_3 8754.50 5.50 0.00 0.00 0.00
PERIMETER_ZN_4 8586.83 173.17 0.00 0.00 0.00
ATTIC 7524.00 727.67 249.33 176.00 83.00
Min 7524.00 5.50 0.00 0.00 0.00
Max 8754.50 759.33 249.33 176.00 83.00
Average 8369.83 305.44 41.56 29.33 13.83
Sum 50219.00 1832.67 249.33 176.00 83.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:03

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.516065E+09 1323.58 06-JAN-11:10 -0.4 -0.4 0.233182E+09 371.05 11-JAN-16:19 13.67 10.10
February 0.523518E+09 1354.74 09-FEB-08:70 -0.6 -1.1 0.222468E+09 402.33 28-FEB-16:49 14.32 10.79
March 0.729680E+09 1313.71 01-MAR-07:13 0.33 -1.4 0.299969E+09 402.34 17-MAR-15:09 12.80 8.51
April 0.838538E+09 3899.84 28-APR-05:03 11.10 9.92 0.273070E+09 402.36 28-APR-14:20 18.13 12.83
May 0.147482E+10 4529.31 16-MAY-05:03 11.70 10.43 0.311128E+09 402.36 08-MAY-15:20 11.70 10.43
June 0.188544E+10 4668.96 12-JUN-05:02 14.40 13.42 0.312415E+09 402.36 23-JUN-10:00 15.00 12.45
July 0.209657E+10 4466.93 19-JUL-05:02 11.57 9.58 0.284762E+09 402.36 11-JUL-12:39 11.57 9.58
August 0.254838E+10 4420.07 14-AUG-05:01 15.37 13.48 0.327631E+09 402.36 31-AUG-07:49 14.42 13.93
September 0.179355E+10 4464.61 11-SEP-05:02 12.12 10.60 0.284025E+09 402.36 01-SEP-10:50 12.12 10.60
October 0.116531E+10 4671.96 05-OCT-05:03 8.30 5.23 0.294482E+09 402.36 25-OCT-12:00 13.30 10.26
November 0.807511E+09 1512.13 08-NOV-16:05 9.90 8.67 0.268016E+09 402.35 08-NOV-14:39 9.90 8.67
December 0.608555E+09 1309.70 06-DEC-16:57 1.10 0.98 0.230796E+09 370.99 05-DEC-15:09 1.10 0.98
                     
Annual Sum or Average 0.149879E+11         0.334195E+10        
Minimum of Months 0.516065E+09 1309.70   -0.6 -1.4 0.222468E+09 370.99   1.10 0.98
Maximum of Months 0.254838E+10 4671.96   15.37 13.48 0.327631E+09 402.36   18.13 13.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 78088522.29 759.92 06-JAN-11:43 0.40 0.40 0.171386E+09 296.09 20-JAN-14:30 6.95 4.83
February 0.150102E+09 1349.16 27-FEB-15:10 19.90 12.22 0.165152E+09 305.00 28-FEB-14:50 13.98 10.93
March 0.317142E+09 1943.92 02-MAR-14:30 13.30 8.35 0.211471E+09 304.99 10-MAR-14:50 16.20 11.59
April 0.429732E+09 3328.99 27-APR-14:20 26.47 16.98 0.194526E+09 305.01 28-APR-14:20 18.13 12.83
May 0.630858E+09 2662.58 15-MAY-14:00 23.30 13.50 0.228263E+09 305.01 05-MAY-15:00 23.30 13.50
June 0.898470E+09 2698.59 28-JUN-14:00 25.00 15.65 0.233666E+09 305.01 29-JUN-15:39 17.60 13.26
July 0.137798E+10 6385.48 24-JUL-05:01 15.87 13.15 0.215017E+09 305.02 14-JUL-13:50 15.87 13.15
August 0.208584E+10 6313.00 09-AUG-05:02 14.97 12.17 0.247952E+09 305.02 04-AUG-13:00 14.97 12.17
September 0.151076E+10 6360.83 11-SEP-05:02 12.12 10.60 0.213911E+09 305.02 22-SEP-13:20 21.67 16.70
October 0.828807E+09 4704.25 04-OCT-13:50 21.02 11.37 0.215481E+09 305.02 26-OCT-09:00 10.60 9.91
November 0.229073E+09 1259.35 02-NOV-13:30 14.40 11.48 0.189796E+09 305.01 02-NOV-13:39 14.40 11.44
December 0.148315E+09 1397.07 05-DEC-13:10 10.60 6.22 0.168366E+09 304.99 05-DEC-16:10 6.10 4.53
                     
Annual Sum or Average 0.868516E+10         0.245499E+10        
Minimum of Months 78088522.29 759.92   0.40 0.40 0.165152E+09 296.09   6.10 4.53
Maximum of Months 0.208584E+10 6385.48   26.47 16.98 0.247952E+09 305.02   23.30 16.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8472364.65 314.57 13-JAN-16:25 2.75 2.31 72989227.13 148.24 11-JAN-16:19 2.75 2.31
February 32507609.71 317.03 08-FEB-11:06 4.08 2.58 67474115.82 168.12 27-FEB-16:00 18.90 12.17
March 94249487.45 403.16 02-MAR-08:07 2.15 1.10 86853189.34 176.39 14-MAR-15:00 17.20 10.94
April 0.195033E+09 1363.93 27-APR-10:02 19.27 13.13 83878436.41 180.93 28-APR-14:39 17.97 12.77
May 0.401938E+09 1584.09 15-MAY-08:52 17.20 11.71 99510268.77 180.94 05-MAY-15:00 17.20 11.71
June 0.744992E+09 1967.50 28-JUN-08:52 18.90 13.39 0.102299E+09 180.94 12-JUN-10:30 18.90 13.39
July 0.937172E+09 3742.40 24-JUL-05:01 15.87 13.15 93723190.48 180.94 26-JUL-15:00 22.80 17.11
August 0.123556E+10 3656.15 15-AUG-05:02 13.05 11.44 0.107934E+09 180.94 16-AUG-14:39 19.70 15.90
September 0.665155E+09 3563.47 11-SEP-05:02 12.12 10.60 92897746.11 180.94 13-SEP-12:00 21.10 16.89
October 0.256478E+09 1253.61 04-OCT-10:02 17.48 10.97 91395187.35 180.93 06-OCT-12:00 16.70 12.03
November 85803364.09 324.27 10-NOV-08:15 5.37 4.77 79346435.85 180.92 02-NOV-14:00 5.37 4.77
December 31297606.81 368.41 06-DEC-08:55 0.90 0.78 69746148.79 146.26 05-DEC-13:00 0.90 0.78
                     
Annual Sum or Average 0.468866E+10         0.104805E+10        
Minimum of Months 8472364.65 314.57   0.90 0.78 67474115.82 146.26   0.90 0.78
Maximum of Months 0.123556E+10 3742.40   19.27 13.39 0.107934E+09 180.94   22.80 17.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 25169217.42 634.15 05-JAN-16:33 4.63 3.66 0.168479E+09 244.87 11-JAN-16:10 14.03 10.30
February 54025773.03 661.05 17-FEB-16:05 3.80 0.98 0.154542E+09 270.59 28-FEB-16:00 14.40 10.82
March 0.199964E+09 631.34 29-MAR-13:51 5.60 4.80 0.192834E+09 290.85 10-MAR-15:30 5.60 4.80
April 0.249048E+09 1240.71 27-APR-15:53 27.20 16.90 0.182175E+09 305.00 27-APR-14:39 27.20 16.90
May 0.524773E+09 1559.30 05-MAY-15:30 24.70 17.20 0.226618E+09 305.01 05-MAY-15:00 25.00 17.36
June 0.871670E+09 2047.01 28-JUN-15:53 26.10 16.29 0.234356E+09 305.01 23-JUN-10:00 26.10 16.29
July 0.114503E+10 3991.91 24-JUL-05:01 15.87 13.15 0.215071E+09 305.01 14-JUL-13:30 15.87 13.15
August 0.142890E+10 3832.25 09-AUG-05:02 14.97 12.17 0.247428E+09 305.01 16-AUG-15:50 18.98 15.94
September 0.774543E+09 2532.08 14-SEP-05:02 12.62 12.25 0.212674E+09 305.01 14-SEP-13:09 22.98 17.61
October 0.383827E+09 1224.02 04-OCT-15:57 21.10 11.40 0.204952E+09 305.00 06-OCT-13:30 16.95 12.00
November 0.219103E+09 692.13 22-NOV-09:05 3.30 3.04 0.180732E+09 299.22 03-NOV-15:00 3.30 3.04
December 60325937.46 569.25 22-DEC-14:00 5.00 2.63 0.160721E+09 239.97 29-DEC-16:10 10.40 8.63
                     
Annual Sum or Average 0.593639E+10         0.238058E+10        
Minimum of Months 25169217.42 569.25   3.30 0.98 0.154542E+09 239.97   3.30 3.04
Maximum of Months 0.142890E+10 3991.91   27.20 17.20 0.247428E+09 305.01   27.20 17.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 16177829.61 270.16 06-JAN-15:45 3.30 2.55 0.100329E+09 152.28 11-JAN-16:10 14.03 10.30
February 25488333.97 266.94 09-FEB-16:43 5.10 2.79 93717670.77 181.10 27-FEB-15:39 19.60 12.34
March 73279395.67 612.95 02-MAR-16:35 12.97 8.50 0.119502E+09 180.92 14-MAR-15:50 17.02 10.84
April 0.154363E+09 1765.07 27-APR-15:55 27.20 16.90 0.113203E+09 181.36 13-APR-12:30 27.20 16.90
May 0.419201E+09 2113.78 15-MAY-15:57 23.90 12.85 0.137336E+09 180.94 08-MAY-15:30 23.90 12.85
June 0.666801E+09 2971.23 23-JUN-05:02 13.80 11.92 0.140133E+09 180.94 23-JUN-10:00 15.00 12.45
July 0.961065E+09 4420.88 24-JUL-05:01 15.87 13.15 0.128642E+09 180.94 11-JUL-15:00 15.87 13.15
August 0.117076E+10 4355.96 15-AUG-05:02 13.05 11.44 0.147766E+09 180.95 22-AUG-07:10 14.88 12.71
September 0.685545E+09 4313.72 11-SEP-05:02 12.12 10.60 0.127436E+09 180.94 13-SEP-14:20 22.97 17.25
October 0.248634E+09 1973.48 04-OCT-15:57 21.10 11.40 0.126231E+09 180.93 06-OCT-13:30 16.95 12.00
November 72763032.57 281.15 08-NOV-15:45 9.90 8.81 0.110381E+09 180.93 08-NOV-15:00 10.00 8.81
December 36816359.81 369.06 06-DEC-17:00 1.10 0.98 96273695.73 158.45 01-DEC-15:00 1.10 0.98
                     
Annual Sum or Average 0.453089E+10         0.144095E+10        
Minimum of Months 16177829.61 266.94   1.10 0.98 93717670.77 152.28   1.10 0.98
Maximum of Months 0.117076E+10 4420.88   27.20 16.90 0.147766E+09 181.36   27.20 17.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92 4.99 0.00 0.00 01-JAN-00:10 5.92 4.99
February 0.00 0.00 01-FEB-00:10 7.00 6.66 0.00 0.00 01-FEB-00:10 7.00 6.66
March 0.00 0.00 01-MAR-00:10 5.92 4.69 0.00 0.00 01-MAR-00:10 5.92 4.69
April 0.00 0.00 01-APR-00:10 7.93 7.13 0.00 0.00 01-APR-00:10 7.93 7.13
May 0.00 0.00 01-MAY-00:10 10.38 9.30 0.00 0.00 01-MAY-00:10 10.38 9.30
June 0.00 0.00 01-JUN-00:10 12.83 10.29 0.00 0.00 01-JUN-00:10 12.83 10.29
July 0.00 0.00 01-JUL-00:10 15.43 12.22 0.00 0.00 01-JUL-00:10 15.43 12.22
August 0.00 0.00 01-AUG-00:10 17.17 13.75 0.00 0.00 01-AUG-00:10 17.17 13.75
September 0.00 0.00 01-SEP-00:10 16.38 13.40 0.00 0.00 01-SEP-00:10 16.38 13.40
October 0.00 0.00 01-OCT-00:10 14.35 12.42 0.00 0.00 01-OCT-00:10 14.35 12.42
November 0.00 0.00 01-NOV-00:10 9.22 8.04 0.00 0.00 01-NOV-00:10 9.22 8.04
December 0.00 0.00 01-DEC-00:10 4.40 3.48 0.00 0.00 01-DEC-00:10 4.40 3.48
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   4.40 3.48 0.00 0.00   4.40 3.48
Maximum of Months 0.00 0.00   17.17 13.75 0.00 0.00   17.17 13.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294507E+09 7908.88 23-JAN-06:01 3.98
February 0.104924E+09 7835.48 21-FEB-06:01 1.70
March 30538062.57 5249.71 06-MAR-06:01 6.70
April 23061019.37 461.08 27-APR-17:12 26.10
May 5229297.77 425.06 17-MAY-05:07 8.90
June 5997943.82 471.19 28-JUN-17:02 26.52
July 10287803.80 619.50 24-JUL-17:12 28.50
August 19345415.66 856.79 10-AUG-17:02 31.62
September 3074908.42 426.95 29-SEP-05:07 11.52
October 9739530.09 432.87 04-OCT-05:07 11.52
November 32683826.37 7228.50 28-NOV-06:01 4.32
December 0.110573E+09 7703.19 18-DEC-06:01 3.72
         
Annual Sum or Average 0.649962E+09      
Minimum of Months 3074908.42 425.06   1.70
Maximum of Months 0.294507E+09 7908.88   31.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128760E+10 10799.40 23-JAN-06:01 3.98
February 0.677476E+09 10768.43 06-FEB-06:01 3.80
March 0.330831E+09 10361.68 27-MAR-05:01 4.32
April 0.174093E+09 10471.73 18-APR-05:01 3.30
May 57077975.04 1720.36 30-MAY-05:03 10.60
June 35731022.17 517.19 28-JUN-17:23 26.15
July 25636642.14 648.44 24-JUL-17:12 28.50
August 30714797.84 806.16 10-AUG-17:11 31.43
September 18781774.50 666.33 11-SEP-05:05 12.12
October 52634859.72 3607.77 23-OCT-05:03 10.60
November 0.359368E+09 10745.90 28-NOV-06:01 4.32
December 0.842596E+09 10753.04 18-DEC-06:01 3.72
         
Annual Sum or Average 0.389254E+10      
Minimum of Months 18781774.50 517.19   3.30
Maximum of Months 0.128760E+10 10799.40   31.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.818067E+09 6450.59 23-JAN-06:01 3.98
February 0.487078E+09 6431.58 06-FEB-06:01 3.80
March 0.192545E+09 6400.63 27-MAR-05:01 4.32
April 69153940.64 6208.06 18-APR-05:01 3.30
May 22905109.89 2136.20 30-MAY-05:03 10.60
June 15650691.18 299.85 28-JUN-17:23 26.15
July 14474126.85 380.48 24-JUL-17:12 28.50
August 17970498.60 482.09 10-AUG-17:11 31.43
September 15504075.81 373.26 11-SEP-05:03 12.12
October 27760763.81 4011.08 30-OCT-05:02 7.20
November 0.184597E+09 6344.98 28-NOV-06:01 4.32
December 0.502052E+09 6423.32 18-DEC-06:01 3.72
         
Annual Sum or Average 0.236776E+10      
Minimum of Months 14474126.85 299.85   3.30
Maximum of Months 0.818067E+09 6450.59   31.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.125537E+10 7453.36 23-JAN-06:01 3.98
February 0.835370E+09 7566.54 13-FEB-06:01 2.30
March 0.350756E+09 6936.56 27-MAR-05:01 4.32
April 0.135370E+09 6549.09 18-APR-05:01 3.30
May 24642134.88 2612.82 30-MAY-05:03 10.60
June 19758043.19 384.34 28-JUN-17:02 26.52
July 14587821.92 492.40 24-JUL-17:12 28.50
August 20961885.48 665.08 10-AUG-17:02 31.62
September 17377140.80 332.71 14-SEP-05:04 12.62
October 39026043.12 4726.51 23-OCT-05:03 10.60
November 0.287133E+09 6884.08 13-NOV-06:01 1.70
December 0.773118E+09 7269.09 18-DEC-06:01 3.72
         
Annual Sum or Average 0.377347E+10      
Minimum of Months 14587821.92 332.71   1.70
Maximum of Months 0.125537E+10 7566.54   31.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.785139E+09 7101.63 23-JAN-06:01 3.98
February 0.474385E+09 7080.11 06-FEB-06:01 3.80
March 0.195215E+09 7147.67 27-MAR-05:01 4.32
April 73563169.06 6958.05 12-APR-05:01 3.80
May 23946675.50 337.39 24-MAY-05:35 7.80
June 20068663.64 421.61 23-JUN-05:04 13.80
July 11775437.06 469.32 28-JUL-05:04 14.50
August 17235130.71 488.12 29-AUG-17:12 30.73
September 13403129.81 464.76 14-SEP-05:04 12.62
October 28674468.96 4706.14 30-OCT-05:02 7.20
November 0.174425E+09 7115.45 28-NOV-06:01 4.32
December 0.469446E+09 7069.91 18-DEC-06:01 3.72
         
Annual Sum or Average 0.228728E+10      
Minimum of Months 11775437.06 337.39   3.72
Maximum of Months 0.785139E+09 7147.67   30.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.966778E+09 1001.21 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.874572E+09 1001.21 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.105063E+10 1001.21 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.922067E+09 1001.21 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.100871E+10 1001.21 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.100592E+10 1001.21 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.924851E+09 1001.21 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.105063E+10 1001.21 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.922067E+09 1001.21 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.966778E+09 1001.21 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.963995E+09 1001.21 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.924851E+09 1001.21 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.115819E+11     0.141401E+11    
Minimum of Months 0.874572E+09 1001.21   0.107295E+10 973.59  
Maximum of Months 0.105063E+10 1001.21   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.658140E+09 758.98 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.564928E+09 758.98 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.661956E+09 758.98 03-MAR-08:09 0.953087E+09 738.04 01-MAR-08:09
April 0.567813E+09 758.98 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.615231E+09 698.29 01-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.609145E+09 698.29 16-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.567915E+09 758.98 12-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.642395E+09 758.98 02-AUG-07:19 0.953087E+09 738.04 01-AUG-07:10
September 0.574634E+09 758.98 05-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.620208E+09 758.98 10-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.651093E+09 758.98 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.636604E+09 758.98 01-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.737006E+10     0.107191E+11    
Minimum of Months 0.564928E+09 698.29   0.813362E+09 738.04  
Maximum of Months 0.661956E+09 758.98   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.406541E+09 450.24 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.353840E+09 450.24 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.410738E+09 450.24 01-MAR-16:30 0.565383E+09 437.82 01-MAR-08:09
April 0.348905E+09 450.24 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.374778E+09 414.23 01-MAY-14:30 0.549505E+09 437.82 01-MAY-07:10
June 0.374453E+09 414.23 08-JUN-15:20 0.542644E+09 437.82 01-JUN-07:10
July 0.346505E+09 450.24 12-JUL-08:30 0.518151E+09 437.82 03-JUL-07:10
August 0.396832E+09 450.24 02-AUG-07:30 0.565383E+09 437.82 01-AUG-07:10
September 0.355941E+09 450.24 05-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.387089E+09 450.24 03-OCT-15:39 0.534030E+09 437.82 02-OCT-07:10
November 0.402183E+09 450.24 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.391529E+09 450.24 01-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.454933E+10     0.635872E+10    
Minimum of Months 0.346505E+09 414.23   0.482497E+09 437.82  
Maximum of Months 0.410738E+09 450.24   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.714587E+09 758.98 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.634109E+09 758.98 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.732849E+09 758.98 01-MAR-16:49 0.953087E+09 738.04 01-MAR-08:09
April 0.618023E+09 758.98 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.642754E+09 698.29 01-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.638976E+09 698.29 16-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.596219E+09 758.98 12-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.701970E+09 758.98 02-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.633188E+09 758.98 01-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.693056E+09 758.98 02-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.709230E+09 758.98 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.688934E+09 758.98 01-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.800389E+10     0.107191E+11    
Minimum of Months 0.596219E+09 698.29   0.813362E+09 738.04  
Maximum of Months 0.732849E+09 758.98   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.406194E+09 450.24 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.353501E+09 450.24 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.412641E+09 450.24 01-MAR-08:09 0.565383E+09 437.82 01-MAR-08:09
April 0.351156E+09 450.24 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.374542E+09 450.24 01-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.374427E+09 450.24 16-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.346605E+09 450.24 11-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.398190E+09 450.24 02-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.355956E+09 450.24 01-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.387603E+09 450.24 02-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.403505E+09 450.24 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.392089E+09 450.24 01-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.455641E+10     0.635872E+10    
Minimum of Months 0.346605E+09 450.24   0.482497E+09 437.82  
Maximum of Months 0.412641E+09 450.24   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.966778E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.874572E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.105063E+10 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.922067E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.100871E+10 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.100592E+10 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.924851E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.105063E+10 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.922067E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.966778E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.963995E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.924851E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.115819E+11 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.874572E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.105063E+10 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.658140E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.811326E+09
February 0.488155E+09 0.564928E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.704956E+09
March 0.590925E+09 0.661956E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.727469E+09
April 0.513848E+09 0.567813E+09 0.862580E+09 0.00 0.00 0.00 0.00 2133400.76 0.594366E+09
May 0.565233E+09 0.615231E+09 0.926320E+09 0.00 0.00 0.00 0.00 268505.64 0.524068E+09
June 0.565233E+09 0.609145E+09 0.914754E+09 0.00 0.00 0.00 0.00 2001933.31 0.419329E+09
July 0.513848E+09 0.567915E+09 0.873466E+09 0.00 0.00 0.00 0.00 11604374.16 0.307344E+09
August 0.590925E+09 0.642395E+09 0.953087E+09 0.00 0.00 0.00 0.00 31365042.05 0.290863E+09
September 0.513848E+09 0.574634E+09 0.861220E+09 0.00 0.00 0.00 0.00 497494.72 0.339454E+09
October 0.539540E+09 0.620208E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.599220E+09
November 0.539540E+09 0.651093E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.696065E+09
December 0.513848E+09 0.636604E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.749244E+09
                   
Annual Sum or Average 0.647448E+10 0.737006E+10 0.107191E+11 0.00 0.00 0.00 0.00 47870750.63 0.676371E+10
Minimum of Months 0.488155E+09 0.564928E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.290863E+09
Maximum of Months 0.590925E+09 0.661956E+09 0.953087E+09 0.00 0.00 0.00 0.00 31365042.05 0.811326E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.406541E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.206358E+09
February 0.211974E+09 0.353840E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.182375E+09
March 0.256600E+09 0.410738E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.180712E+09
April 0.223130E+09 0.348905E+09 0.511694E+09 0.00 0.00 0.00 0.00 587238.23 0.174140E+09
May 0.245443E+09 0.374778E+09 0.549505E+09 0.00 0.00 0.00 0.00 14971.15 0.151819E+09
June 0.245443E+09 0.374453E+09 0.542644E+09 0.00 0.00 0.00 0.00 99378.53 0.130278E+09
July 0.223130E+09 0.346505E+09 0.518151E+09 0.00 0.00 0.00 0.00 767077.04 0.107596E+09
August 0.256600E+09 0.396832E+09 0.565383E+09 0.00 0.00 0.00 0.00 2041000.96 95806790.72
September 0.223130E+09 0.355941E+09 0.510887E+09 0.00 0.00 0.00 0.00 13849.95 73344540.20
October 0.234287E+09 0.387089E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.163659E+09
November 0.234287E+09 0.402183E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.173998E+09
December 0.223130E+09 0.391529E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.177917E+09
                   
Annual Sum or Average 0.281144E+10 0.454933E+10 0.635872E+10 0.00 0.00 0.00 0.00 3523515.86 0.181800E+10
Minimum of Months 0.211974E+09 0.346505E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 73344540.20
Maximum of Months 0.256600E+09 0.410738E+09 0.565383E+09 0.00 0.00 0.00 0.00 2041000.96 0.206358E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.714587E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.310172E+09
February 0.488155E+09 0.634109E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.271876E+09
March 0.590925E+09 0.732849E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.265105E+09
April 0.513848E+09 0.618023E+09 0.862580E+09 0.00 0.00 0.00 0.00 1143451.36 0.251008E+09
May 0.565233E+09 0.642754E+09 0.926320E+09 0.00 0.00 0.00 0.00 22455.60 0.221066E+09
June 0.565233E+09 0.638976E+09 0.914754E+09 0.00 0.00 0.00 0.00 151375.24 0.187796E+09
July 0.513848E+09 0.596219E+09 0.873466E+09 0.00 0.00 0.00 0.00 2097671.97 0.156940E+09
August 0.590925E+09 0.701970E+09 0.953087E+09 0.00 0.00 0.00 0.00 3497218.42 0.136646E+09
September 0.513848E+09 0.633188E+09 0.861220E+09 0.00 0.00 0.00 0.00 20821.08 0.105599E+09
October 0.539540E+09 0.693056E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.238422E+09
November 0.539540E+09 0.709230E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.259843E+09
December 0.513848E+09 0.688934E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.266912E+09
                   
Annual Sum or Average 0.647448E+10 0.800389E+10 0.107191E+11 0.00 0.00 0.00 0.00 6932993.68 0.267139E+10
Minimum of Months 0.488155E+09 0.596219E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.105599E+09
Maximum of Months 0.590925E+09 0.732849E+09 0.953087E+09 0.00 0.00 0.00 0.00 3497218.42 0.310172E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.406194E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.207084E+09
February 0.289580E+09 0.353501E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.183561E+09
March 0.350544E+09 0.412641E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.183275E+09
April 0.304821E+09 0.351156E+09 0.511694E+09 0.00 0.00 0.00 0.00 412695.20 0.175429E+09
May 0.335303E+09 0.374542E+09 0.549505E+09 0.00 0.00 0.00 0.00 14965.93 0.157524E+09
June 0.335303E+09 0.374427E+09 0.542644E+09 0.00 0.00 0.00 0.00 97767.21 0.132501E+09
July 0.304821E+09 0.346605E+09 0.518151E+09 0.00 0.00 0.00 0.00 718790.89 0.117296E+09
August 0.350544E+09 0.398190E+09 0.565383E+09 0.00 0.00 0.00 0.00 1860903.78 0.101113E+09
September 0.304821E+09 0.355956E+09 0.510887E+09 0.00 0.00 0.00 0.00 13804.80 76611045.15
October 0.320062E+09 0.387603E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.166314E+09
November 0.320062E+09 0.403505E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.175713E+09
December 0.304821E+09 0.392089E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.178722E+09
                   
Annual Sum or Average 0.384075E+10 0.455641E+10 0.635872E+10 0.00 0.00 0.00 0.00 3118927.81 0.185514E+10
Minimum of Months 0.289580E+09 0.346605E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 76611045.15
Maximum of Months 0.350544E+09 0.412641E+09 0.565383E+09 0.00 0.00 0.00 0.00 1860903.78 0.207084E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.932193E+09 0.706261E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.823905E+09 0.126272E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.789940E+09 0.219233E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.630735E+09 0.337422E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.586801E+09 0.449699E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.533832E+09 0.455193E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.581786E+09 0.483628E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.677894E+09 0.376084E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.889933E+09 0.291337E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.866567E+09 0.165824E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.831493E+09 0.860796E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110886E+10 0.573736E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.925394E+10 0.311877E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.533832E+09 0.573736E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110886E+10 0.483628E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 1001.21 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 1001.21 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 1001.21 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 1001.21 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 1001.21 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 1001.21 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 1001.21 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 1001.21 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 1001.21 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 1001.21 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 1001.21 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 1001.21 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   1001.21   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   1001.21   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 758.98 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2383.38 06-JAN-08:00
February 732.70 01-FEB-08:09 758.98 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2234.98 09-FEB-08:00
March 732.70 01-MAR-08:09 758.98 03-MAR-08:09 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2136.47 01-MAR-07:05
April 732.70 03-APR-07:10 758.98 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 287.56 27-APR-16:10 1881.00 19-APR-06:10
May 732.70 01-MAY-07:10 698.29 01-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 68.42 05-MAY-16:10 1558.68 11-MAY-06:03
June 732.70 01-JUN-07:10 698.29 16-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 258.44 28-JUN-16:57 1256.34 15-JUN-06:03
July 732.70 03-JUL-07:10 758.98 12-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 453.74 31-JUL-16:05 1109.48 03-JUL-06:05
August 732.70 01-AUG-07:10 758.98 02-AUG-07:19 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 706.09 10-AUG-17:00 1212.35 01-AUG-06:03
September 732.70 01-SEP-07:10 758.98 05-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 102.66 14-SEP-17:00 1378.65 27-SEP-06:03
October 732.70 02-OCT-07:10 758.98 10-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1618.53 13-OCT-06:03
November 732.70 01-NOV-07:10 758.98 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2027.56 13-NOV-08:00
December 732.70 01-DEC-08:09 758.98 01-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2314.83 26-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   698.29   738.04   0.00 0.00 0.00 0.00 0.00   1109.48  
Maximum of Months 732.70   758.98   738.04   0.00 0.00 0.00 0.00 706.09   2383.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 450.24 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 299.54 12-JAN-24:00
February 434.65 01-FEB-08:09 450.24 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 285.79 16-FEB-06:04
March 434.65 01-MAR-08:09 450.24 01-MAR-16:30 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 286.04 29-MAR-05:04
April 434.65 03-APR-07:10 450.24 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 63.96 01-APR-17:03 290.37 07-APR-24:00
May 434.65 01-MAY-07:10 414.23 01-MAY-14:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 1.47 05-MAY-16:00 287.58 17-MAY-18:55
June 434.65 01-JUN-07:10 414.23 08-JUN-15:20 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 5.17 28-JUN-15:57 300.89 13-JUN-03:00
July 434.65 03-JUL-07:10 450.24 12-JUL-08:30 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 15.74 24-JUL-18:10 147.30 02-JUL-04:00
August 434.65 01-AUG-07:10 450.24 02-AUG-07:30 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 33.47 29-AUG-18:10 228.40 11-AUG-04:00
September 434.65 01-SEP-07:10 450.24 05-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 1.76 14-SEP-17:00 139.76 18-SEP-23:00
October 434.65 02-OCT-07:10 450.24 03-OCT-15:39 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 275.09 31-OCT-20:00
November 434.65 01-NOV-07:10 450.24 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 322.23 29-NOV-21:00
December 434.65 01-DEC-08:09 450.24 01-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 290.91 26-DEC-19:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   414.23   437.82   0.00 0.00 0.00 0.00 0.00   139.76  
Maximum of Months 434.65   450.24   437.82   0.00 0.00 0.00 0.00 63.96   322.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 758.98 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 453.73 12-JAN-24:00
February 732.70 01-FEB-08:09 758.98 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 424.93 16-FEB-07:00
March 732.70 01-MAR-08:09 758.98 01-MAR-16:49 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 422.70 29-MAR-05:05
April 732.70 03-APR-07:10 758.98 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 111.96 01-APR-17:03 418.12 07-APR-24:00
May 732.70 01-MAY-07:10 698.29 01-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 2.20 05-MAY-16:00 430.86 17-MAY-18:55
June 732.70 01-JUN-07:10 698.29 16-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 7.75 28-JUN-15:57 443.66 13-JUN-03:00
July 732.70 03-JUL-07:10 758.98 12-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 48.53 23-JUL-14:00 221.48 02-JUL-04:00
August 732.70 01-AUG-07:10 758.98 02-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 55.88 29-AUG-18:10 335.53 11-AUG-04:00
September 732.70 01-SEP-07:10 758.98 01-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 2.63 14-SEP-17:00 209.67 18-SEP-23:00
October 732.70 02-OCT-07:10 758.98 02-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 411.70 31-OCT-20:00
November 732.70 01-NOV-07:10 758.98 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 487.51 29-NOV-21:00
December 732.70 01-DEC-08:09 758.98 01-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 437.01 26-DEC-19:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   698.29   738.04   0.00 0.00 0.00 0.00 0.00   209.67  
Maximum of Months 732.70   758.98   738.04   0.00 0.00 0.00 0.00 111.96   487.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 450.24 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 300.38 12-JAN-24:00
February 434.65 01-FEB-08:09 450.24 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 287.37 16-FEB-06:04
March 434.65 01-MAR-08:09 450.24 01-MAR-08:09 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 285.07 29-MAR-05:04
April 434.65 03-APR-07:10 450.24 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 42.33 01-APR-17:03 280.82 07-APR-24:00
May 434.65 01-MAY-07:10 450.24 01-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 1.47 05-MAY-16:00 291.76 17-MAY-18:55
June 434.65 01-JUN-07:10 450.24 16-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 5.17 28-JUN-15:57 292.92 13-JUN-03:00
July 434.65 03-JUL-07:10 450.24 11-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 16.06 23-JUL-14:00 152.75 02-JUL-04:00
August 434.65 01-AUG-07:10 450.24 02-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 26.67 29-AUG-18:10 240.49 11-AUG-04:00
September 434.65 01-SEP-07:10 450.24 01-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 1.76 14-SEP-17:00 144.17 30-SEP-06:00
October 434.65 02-OCT-07:10 450.24 02-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 278.67 31-OCT-20:00
November 434.65 01-NOV-07:10 450.24 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 322.48 29-NOV-21:00
December 434.65 01-DEC-08:09 450.24 01-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 290.93 26-DEC-19:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   450.24   437.82   0.00 0.00 0.00 0.00 0.00   144.17  
Maximum of Months 434.65   450.24   437.82   0.00 0.00 0.00 0.00 42.33   322.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1271.92 09-JAN-03:00 2729.45 20-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1585.78 27-FEB-03:55 3638.28 08-FEB-13:30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1443.42 01-MAR-21:00 5370.29 14-MAR-13:20
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1259.16 27-APR-05:45 6114.58 18-APR-12:50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1250.58 15-MAY-03:00 7255.87 31-MAY-13:30
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1229.83 10-JUN-02:00 6461.30 22-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1333.90 08-JUL-03:00 6568.46 13-JUL-13:30
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1314.98 09-AUG-05:35 6007.93 06-AUG-12:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1512.47 10-SEP-05:00 5580.49 07-SEP-13:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1313.42 04-OCT-22:00 4068.89 11-OCT-12:20
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1406.78 11-NOV-24:00 2942.38 04-NOV-13:20
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1738.47 06-DEC-04:00 2241.71 06-DEC-12:20
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1229.83   2241.71  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1738.47   7255.87  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1323.58 06-JAN-11:10 2899.62 3003.64 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
February 1354.74 09-FEB-08:70 966.54 1001.21 973.59 0.00 0.00 0.00 0.00 0.00 0.00
March 1313.71 01-MAR-07:13 608.92 1401.67 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
April 3899.84 28-APR-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
May 4529.31 16-MAY-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
June 4668.96 12-JUN-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
July 4466.93 19-JUL-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
August 4420.07 14-AUG-05:01 744.23 225.53 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
September 4464.61 11-SEP-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
October 4671.96 05-OCT-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
November 1512.13 08-NOV-16:05 1933.08 2002.42 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
December 1309.70 06-DEC-16:57 2899.62 3003.64 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1309.70   318.96 96.65 973.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4671.96   2899.62 3003.64 3407.56 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 759.92 06-JAN-11:43 2198.10 1661.95 2214.13 0.00 0.00 0.00 0.00 0.00 312.44
February 1349.16 27-FEB-15:10 732.70 553.98 738.04 0.00 0.00 0.00 0.00 0.00 55.93
March 1943.92 02-MAR-14:30 1465.40 1107.96 1476.09 0.00 0.00 0.00 0.00 0.00 158.22
April 3328.99 27-APR-14:20 732.70 553.98 738.04 0.00 0.00 0.00 0.00 36.20 0.00
May 2662.58 15-MAY-14:00 732.70 553.98 738.04 0.00 0.00 0.00 0.00 0.00 8.84
June 2698.59 28-JUN-14:00 732.70 553.98 738.04 0.00 0.00 0.00 0.00 16.17 0.00
July 6385.48 24-JUL-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 121.48
August 6313.00 09-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 172.38
September 6360.83 11-SEP-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 250.83
October 4704.25 04-OCT-13:50 732.70 553.98 738.04 0.00 0.00 0.00 0.00 0.00 43.20
November 1259.35 02-NOV-13:30 732.70 553.98 738.04 0.00 0.00 0.00 0.00 0.00 140.15
December 1397.07 05-DEC-13:10 1465.40 1107.96 1476.09 0.00 0.00 0.00 0.00 0.00 184.31
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 759.92   483.58 146.54 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6385.48   2198.10 1661.95 2583.15 0.00 0.00 0.00 0.00 36.20 312.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 314.57 13-JAN-16:25 869.29 900.48 875.63 0.00 0.00 0.00 0.00 0.00 55.05
February 317.03 08-FEB-11:06 2173.23 1665.81 2189.08 0.00 0.00 0.00 0.00 0.00 19.73
March 403.16 02-MAR-08:07 1738.59 1314.52 1751.27 0.00 0.00 0.00 0.00 0.00 26.68
April 1363.93 27-APR-10:02 1738.59 1314.52 1751.27 0.00 0.00 0.00 0.00 0.00 5.80
May 1584.09 15-MAY-08:52 2173.23 1643.15 2189.08 0.00 0.00 0.00 0.00 0.00 9.10
June 1967.50 28-JUN-08:52 2173.23 1643.15 2189.08 0.00 0.00 0.00 0.00 0.00 6.77
July 3742.40 24-JUL-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 8.55
August 3656.15 15-AUG-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 41.18
September 3563.47 11-SEP-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 52.96
October 1253.61 04-OCT-10:02 1738.59 1314.52 1751.27 0.00 0.00 0.00 0.00 0.00 11.49
November 324.27 10-NOV-08:15 869.29 657.26 875.63 0.00 0.00 0.00 0.00 0.00 7.57
December 368.41 06-DEC-08:55 869.29 657.26 875.63 0.00 0.00 0.00 0.00 0.00 16.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 314.57   286.87 86.93 875.63 0.00 0.00 0.00 0.00 0.00 5.80
Maximum of Months 3742.40   2173.23 1665.81 2189.08 0.00 0.00 0.00 0.00 0.00 55.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 634.15 05-JAN-16:33 2198.10 2276.95 2214.13 0.00 0.00 0.00 0.00 0.00 41.49
February 661.05 17-FEB-16:05 1465.40 1396.58 1476.09 0.00 0.00 0.00 0.00 0.00 78.76
March 631.34 29-MAR-13:51 5861.59 5525.20 5904.34 0.00 0.00 0.00 0.00 0.00 79.19
April 1240.71 27-APR-15:53 2930.79 2519.83 2952.17 0.00 0.00 0.00 0.00 10.26 0.00
May 1559.30 05-MAY-15:30 1465.40 1123.24 1476.09 0.00 0.00 0.00 0.00 1.76 0.00
June 2047.01 28-JUN-15:53 2198.10 1889.87 2214.13 0.00 0.00 0.00 0.00 7.75 0.00
July 3991.91 24-JUL-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 12.10
August 3832.25 09-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 52.19
September 2532.08 14-SEP-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 0.00
October 1224.02 04-OCT-15:57 2198.10 2094.87 2214.13 0.00 0.00 0.00 0.00 0.00 11.16
November 692.13 22-NOV-09:05 1465.40 1396.58 1476.09 0.00 0.00 0.00 0.00 0.00 56.09
December 569.25 22-DEC-14:00 732.70 758.98 738.04 0.00 0.00 0.00 0.00 0.00 47.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 569.25   402.98 122.12 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3991.91   5861.59 5525.20 5904.34 0.00 0.00 0.00 0.00 10.26 79.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 270.16 06-JAN-15:45 869.29 657.26 875.63 0.00 0.00 0.00 0.00 0.00 22.31
February 266.94 09-FEB-16:43 1303.94 1201.91 1313.45 0.00 0.00 0.00 0.00 0.00 35.34
March 612.95 02-MAR-16:35 1738.59 1314.52 1751.27 0.00 0.00 0.00 0.00 0.00 8.69
April 1765.07 27-APR-15:55 1738.59 1314.52 1751.27 0.00 0.00 0.00 0.00 6.84 0.00
May 2113.78 15-MAY-15:57 1303.94 985.89 1313.45 0.00 0.00 0.00 0.00 0.01 0.00
June 2971.23 23-JUN-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 108.08
July 4420.88 24-JUL-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 8.85
August 4355.96 15-AUG-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 42.31
September 4313.72 11-SEP-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 53.30
October 1973.48 04-OCT-15:57 1303.94 985.89 1313.45 0.00 0.00 0.00 0.00 0.00 7.44
November 281.15 08-NOV-15:45 869.29 819.40 875.63 0.00 0.00 0.00 0.00 0.00 38.19
December 369.06 06-DEC-17:00 1303.94 1350.72 1313.45 0.00 0.00 0.00 0.00 0.00 28.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 266.94   239.06 72.44 875.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4420.88   1738.59 1350.72 1751.27 0.00 0.00 0.00 0.00 6.84 108.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.20 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 458.19 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 817.56 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 242.53 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581.89 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 868.72 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 424.31 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 732.35 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 658.28 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1109.70 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 415.19 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 923.83 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 242.53 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1109.70 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.146328E+11 17247.49 09-JAN-08:20 0.202757E+09 17169.65 17-JAN-06:19
February 0.124215E+11 18490.46 21-FEB-08:09 0.146776E+09 12114.75 21-FEB-06:10
March 0.130412E+11 12661.77 13-MAR-07:49 19595011.36 3862.95 27-MAR-05:10
April 0.114723E+11 13759.65 27-APR-15:39 8271202.15 3606.33 18-APR-05:10
May 0.123684E+11 13391.24 04-MAY-15:00 0.00 0.00 01-MAY-00:10
June 0.126683E+11 13934.85 28-JUN-15:30 0.00 0.00 01-JUN-00:10
July 0.126746E+11 15272.25 31-JUL-15:30 0.00 0.00 01-JUL-00:10
August 0.144802E+11 15494.16 10-AUG-15:30 0.00 0.00 01-AUG-00:10
September 0.124189E+11 14449.42 14-SEP-15:39 0.00 0.00 01-SEP-00:10
October 0.123433E+11 13369.20 04-OCT-15:09 0.00 0.00 01-OCT-00:10
November 0.126574E+11 14794.67 24-NOV-07:10 17409934.19 4898.13 24-NOV-06:10
December 0.135607E+11 19077.52 26-DEC-08:20 0.171354E+09 18423.30 26-DEC-06:19
             
Annual Sum or Average 0.154739E+12     0.566163E+09    
Minimum of Months 0.114723E+11 12661.77   0.00 0.00  
Maximum of Months 0.146328E+11 19077.52   0.202757E+09 18423.30  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.315224E+10 0.120973E+10 0.405300E+10 0.00 0.174153E+10 0.02 0.233969E+10 0.00 0.00 0.00 0.00 0.213656E+10 0.00
February 0.278095E+10 0.949992E+09 0.366466E+10 0.00 0.156034E+10 0.01 0.152491E+10 8105651.36 0.00 0.00 0.00 0.193251E+10 0.00
March 0.326882E+10 0.861761E+09 0.429420E+10 0.00 0.187243E+10 0.00 0.527037E+09 42206460.70 0.00 0.00 0.00 0.217474E+10 0.00
April 0.280796E+10 0.665175E+09 0.388642E+10 0.00 0.162820E+10 0.00 0.194412E+09 0.253122E+09 0.00 0.00 0.00 0.203703E+10 0.00
May 0.301601E+10 0.568556E+09 0.417360E+10 0.00 0.179102E+10 0.00 9279714.46 0.695801E+09 0.00 0.00 0.00 0.211414E+10 0.00
June 0.300292E+10 0.497288E+09 0.412149E+10 0.00 0.179102E+10 0.00 0.00 0.121375E+10 0.00 0.00 0.00 0.204182E+10 0.00
July 0.278209E+10 0.535596E+09 0.393546E+10 0.00 0.162820E+10 0.00 0.00 0.175355E+10 0.00 0.00 0.00 0.203966E+10 0.00
August 0.319002E+10 0.627856E+09 0.429420E+10 0.00 0.187243E+10 0.00 0.00 0.239990E+10 0.00 0.00 0.00 0.209581E+10 0.00
September 0.284179E+10 0.753744E+09 0.388029E+10 0.00 0.162820E+10 0.00 105922.81 0.132420E+10 0.00 0.00 0.00 0.199054E+10 0.00
October 0.305473E+10 0.970854E+09 0.405607E+10 0.00 0.170961E+10 0.00 28834299.33 0.443897E+09 0.00 0.00 0.00 0.207926E+10 0.00
November 0.313001E+10 0.111763E+10 0.400396E+10 0.00 0.170961E+10 0.00 0.593151E+09 53740145.53 0.00 0.00 0.00 0.204932E+10 0.00
December 0.303401E+10 0.125623E+10 0.393240E+10 0.00 0.163246E+10 0.00 0.160183E+10 2038919.83 0.00 0.00 0.00 0.210170E+10 0.00
                           
Annual Sum or Average 0.360616E+11 0.100144E+11 0.482958E+11 0.00 0.205651E+11 0.03 0.681925E+10 0.819032E+10 0.00 0.00 0.00 0.247931E+11 0.00
Minimum of Months 0.278095E+10 0.497288E+09 0.366466E+10 0.00 0.156034E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.193251E+10 0.00
Maximum of Months 0.326882E+10 0.125623E+10 0.429420E+10 0.00 0.187243E+10 0.02 0.233969E+10 0.239990E+10 0.00 0.00 0.00 0.217474E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.202757E+09 0.00 0.00 0.00 0.00
February 0.00 0.00 0.146776E+09 0.00 0.00 0.00 0.00
March 0.00 0.00 19595011.36 0.00 0.00 0.00 0.00
April 0.00 0.00 8271202.15 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 17409934.19 0.00 0.00 0.00 0.00
December 0.00 0.00 0.171354E+09 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.566163E+09 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.202757E+09 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 3419.66 02-JAN-08:09 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1739.53 02-JAN-06:19 0.00 02-JAN-07:10 7704.01 17-JAN-06:19
February 3419.66 01-FEB-08:09 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1739.53 01-FEB-09:30 0.00 01-FEB-07:10 8203.10 21-FEB-07:00
March 3419.66 03-MAR-08:09 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1739.53 01-MAR-06:10 0.00 01-MAR-00:10 4911.05 06-MAR-06:19
April 3419.66 03-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1739.53 03-APR-16:10 0.00 01-APR-00:10 3125.19 18-APR-06:10
May 3262.27 17-MAY-07:10 675.04 01-MAY-19:19 3325.31 01-MAY-07:10 0.00 1739.53 01-MAY-07:19 0.00 01-MAY-00:10 736.78 18-MAY-06:19
June 3257.73 16-JUN-07:10 675.04 01-JUN-19:00 3325.31 01-JUN-07:10 0.00 1739.53 01-JUN-05:00 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 3419.66 12-JUL-08:30 675.04 01-JUL-20:10 3325.31 03-JUL-07:10 0.00 1739.53 03-JUL-06:19 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 3419.66 02-AUG-07:30 1061.67 16-AUG-05:10 3325.31 01-AUG-07:10 0.00 1739.53 01-AUG-05:19 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 3419.66 05-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1739.53 01-SEP-05:10 0.00 01-SEP-00:10 112.93 28-SEP-06:30
October 3419.66 10-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1739.53 02-OCT-06:10 0.00 01-OCT-00:10 1260.82 30-OCT-06:19
November 3419.66 01-NOV-07:10 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1739.53 01-NOV-05:10 0.00 01-NOV-00:10 6650.80 24-NOV-07:19
December 3419.66 01-DEC-08:09 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1739.53 01-DEC-06:10 0.00 01-DEC-00:10 8143.84 26-DEC-06:19
                           
Annual Sum or Average             0.00            
Minimum of Months 3257.73   675.04   3325.31   0.00 1739.53   0.00   0.00  
Maximum of Months 3419.66   1061.67   3325.31   0.00 1739.53   0.00   8203.10  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 2812.78 30-JAN-12:50 0.00
February 387.11 27-FEB-15:30 0.00 0.00 0.00 2813.12 13-FEB-12:50 0.00
March 626.25 02-MAR-15:00 0.00 0.00 0.00 2811.96 01-MAR-12:09 0.00
April 3019.70 27-APR-15:09 0.00 0.00 0.00 2808.18 03-APR-11:30 0.00
May 2674.87 05-MAY-15:00 0.00 0.00 0.00 2802.89 01-MAY-11:30 0.00
June 3280.46 28-JUN-15:00 0.00 0.00 0.00 2796.67 01-JUN-11:00 0.00
July 4553.62 24-JUL-14:00 0.00 0.00 0.00 2791.08 03-JUL-11:09 0.00
August 4727.53 10-AUG-15:00 0.00 0.00 0.00 2789.24 31-AUG-11:50 0.00
September 3709.60 14-SEP-15:30 0.00 0.00 0.00 2792.25 29-SEP-11:00 0.00
October 2560.11 04-OCT-14:00 0.00 0.00 0.00 2798.00 31-OCT-11:00 0.00
November 641.80 02-NOV-14:20 0.00 0.00 0.00 2804.61 30-NOV-12:20 0.00
December 215.98 05-DEC-13:20 0.00 0.00 0.00 2809.50 29-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 0.00   0.00 0.00 0.00 2789.24   0.00
Maximum of Months 4727.53   0.00 0.00 0.00 2813.12   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17247.49 09-JAN-08:20 3322.96 3325.31 0.00 0.00 1739.53 0.00 6120.52 0.00 0.00
February 18490.46 21-FEB-08:09 3237.92 3325.31 0.00 0.00 1739.53 0.00 7447.61 0.00 0.00
March 12661.77 13-MAR-07:49 3419.66 3325.31 0.00 0.00 1739.53 0.00 1438.01 0.00 0.00
April 13759.65 27-APR-15:39 2923.48 3325.31 0.00 0.00 1739.53 0.00 0.00 3009.67 0.00
May 13391.24 04-MAY-15:00 2999.46 3325.31 0.00 0.00 1739.53 0.00 0.00 2565.96 0.00
June 13934.85 28-JUN-15:30 2887.48 3325.31 0.00 0.00 1739.53 0.00 0.00 3228.76 0.00
July 15272.25 31-JUL-15:30 3064.68 3325.31 0.00 0.00 1739.53 0.00 0.00 4391.14 0.00
August 15494.16 10-AUG-15:30 2991.82 3325.31 0.00 0.00 1739.53 0.00 0.00 4686.10 0.00
September 14449.42 14-SEP-15:39 2923.48 3325.31 0.00 0.00 1739.53 0.00 0.00 3708.43 0.00
October 13369.20 04-OCT-15:09 2996.35 3325.31 0.00 0.00 1739.53 0.00 0.00 2553.58 0.00
November 14794.67 24-NOV-07:10 1595.81 1662.65 1061.67 0.00 1739.53 0.00 6595.07 0.00 0.00
December 19077.52 26-DEC-08:20 3419.66 3325.31 0.00 0.00 1739.53 0.00 7854.86 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 12661.77   1595.81 1662.65 0.00 0.00 1739.53 0.00 0.00 0.00 0.00
Maximum of Months 19077.52   3419.66 3325.31 1061.67 0.00 1739.53 0.00 7854.86 4686.10 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 17169.65 17-JAN-06:19 0.00 0.00 0.00
February 0.00 0.00 12114.75 21-FEB-06:10 0.00 0.00 0.00
March 0.00 0.00 3862.95 27-MAR-05:10 0.00 0.00 0.00
April 0.00 0.00 3606.33 18-APR-05:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 4898.13 24-NOV-06:10 0.00 0.00 0.00
December 0.00 0.00 18423.30 26-DEC-06:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 18423.30   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.83 2.17 19.83 0.00 19.83 0.00 19.83
February 0.17 20.25 0.17 20.25 0.00 20.25 0.00 20.25
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 24.62 0.83 24.62
August 0.00 0.00 0.00 0.00 1.83 24.65 1.83 24.65
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.10 0.17 20.10 0.00 20.10 0.00 20.10
                 
Annual Sum or Average 2.50 19.87 2.50 19.87 2.67 21.53 2.67 22.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 20.25 2.17 20.25 1.83 24.65 1.83 24.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 20.03 2.00 20.03 0.00 20.03 0.00 20.03
February 0.50 20.26 0.50 20.26 0.00 20.26 0.00 20.26
March 0.17 20.37 0.17 20.37 0.00 20.37 0.00 20.37
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.83 20.14 0.83 20.14 0.00 20.14 0.00 20.14
                 
Annual Sum or Average 3.50 20.10 3.50 20.10 0.00 20.10 0.00 20.10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.37 2.00 20.37 0.00 20.37 0.00 20.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 18.79 2.67 19.31 0.00 19.31 0.00 19.31
February 1.50 19.07 1.17 19.58 0.00 19.58 0.00 19.58
March 0.33 20.23 0.33 20.23 0.00 20.23 0.00 20.23
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.40 0.17 20.40 0.00 20.40 0.00 20.40
December 1.50 17.77 0.83 18.57 0.00 18.57 0.00 18.57
                 
Annual Sum or Average 7.00 18.74 5.17 19.31 0.00 19.31 0.00 19.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 20.40 2.67 20.40 0.00 20.40 0.00 20.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.17 19.19 6.50 19.40 0.00 19.40 0.00 19.40
February 3.67 19.35 3.17 19.67 0.00 19.67 0.00 19.67
March 1.00 20.07 1.00 20.07 0.00 20.07 0.00 20.07
April 0.17 20.50 0.17 20.50 0.00 20.50 0.00 20.50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 20.37 0.83 20.37 0.00 20.37 0.00 20.37
December 3.17 19.18 2.67 19.54 0.00 19.54 0.00 19.54
                 
Annual Sum or Average 16.00 19.36 14.33 19.60 0.00 19.60 0.00 19.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.17 20.50 6.50 20.50 0.00 20.50 0.00 20.50



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 18.21 2.00 18.94 0.00 18.94 0.00 18.94
February 1.17 18.73 0.83 19.36 0.00 19.36 0.00 19.36
March 0.33 20.37 0.33 20.37 0.00 20.37 0.00 20.37
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.54 0.17 20.54 0.00 20.54 0.00 20.54
December 1.33 17.53 0.67 18.39 0.00 18.39 0.00 18.39
                 
Annual Sum or Average 6.17 18.34 4.00 19.06 0.00 19.06 0.00 19.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 20.54 2.00 20.54 0.00 20.54 0.00 20.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 21.29 77.00 21.19 77.00 21.13
February 323.00 21.79 28.33 21.71 28.33 21.65
March 391.00 22.87 0.00 22.87 0.00 22.87
April 291.83 23.35 10.67 23.41 0.00 23.41
May 99.67 23.80 60.17 24.23 0.00 24.23
June 20.00 23.88 140.33 24.79 0.00 24.79
July 0.33 23.89 232.00 24.69 0.00 24.69
August 0.00 0.00 327.17 24.58 0.00 24.58
September 8.00 23.84 170.33 24.63 0.00 24.63
October 214.17 23.67 16.83 23.78 0.00 23.78
November 346.17 22.62 1.00 22.62 1.00 22.61
December 340.00 21.64 23.00 21.59 23.00 21.54
             
Annual Sum or Average 2391.17 22.46 1086.83 23.02 129.33 22.94
Minimum of Months 0.00 0.00 0.00 21.19 0.00 21.13
Maximum of Months 391.00 23.89 327.17 24.79 77.00 24.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.75 291.33 20.67 291.33 20.64
February 323.00 21.32 167.00 21.08 167.00 20.97
March 388.83 21.96 77.33 21.78 77.33 21.65
April 307.50 22.43 48.33 22.36 35.33 22.23
May 304.33 23.24 10.83 23.30 0.00 23.30
June 212.67 23.57 35.00 23.80 0.00 23.80
July 66.50 23.70 150.00 24.46 0.00 24.46
August 32.00 23.65 236.00 24.62 0.17 24.62
September 108.67 23.55 133.83 24.19 0.00 24.19
October 261.33 22.96 28.83 23.11 0.00 23.11
November 357.00 21.74 103.17 21.50 103.17 21.34
December 340.00 21.03 219.50 20.87 219.50 20.79
             
Annual Sum or Average 3058.83 22.11 1501.17 22.17 893.83 21.92
Minimum of Months 32.00 20.75 10.83 20.67 0.00 20.64
Maximum of Months 388.83 23.70 291.33 24.62 291.33 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.46 280.83 20.44 280.83 20.44
February 266.00 20.71 203.50 20.60 203.50 20.55
March 322.00 21.35 142.67 21.15 142.67 21.04
April 264.00 22.29 45.50 22.09 42.50 21.92
May 263.50 23.28 6.17 23.32 0.00 23.32
June 145.33 23.69 42.67 24.03 0.00 24.03
July 49.33 23.87 112.00 24.64 0.00 24.64
August 26.33 23.86 174.67 24.70 0.00 24.70
September 140.50 23.68 67.00 24.00 0.00 24.00
October 283.33 22.84 6.83 22.79 6.83 22.74
November 294.00 21.35 144.33 21.10 144.33 20.97
December 280.00 20.57 253.17 20.53 253.17 20.52
             
Annual Sum or Average 2628.33 21.88 1479.33 21.82 1073.83 21.55
Minimum of Months 26.33 20.46 6.17 20.44 0.00 20.44
Maximum of Months 322.00 23.87 280.83 24.70 280.83 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.56 329.67 20.54 329.67 20.53
February 323.00 20.74 249.00 20.66 249.00 20.62
March 391.00 21.13 209.50 20.99 209.50 20.92
April 337.83 21.93 72.83 21.73 72.83 21.59
May 353.67 23.23 1.83 23.24 0.00 23.24
June 242.67 23.68 24.33 23.83 0.00 23.83
July 87.33 23.85 93.00 24.48 0.00 24.48
August 51.83 23.83 131.17 24.57 0.00 24.57
September 225.50 23.66 26.83 23.80 0.00 23.80
October 357.00 22.63 11.33 22.58 11.33 22.52
November 357.00 21.33 163.83 21.12 163.83 21.00
December 340.00 20.65 304.00 20.63 304.00 20.61
             
Annual Sum or Average 3423.83 21.92 1617.33 21.74 1340.17 21.50
Minimum of Months 51.83 20.56 1.83 20.54 0.00 20.53
Maximum of Months 391.00 23.85 329.67 24.57 329.67 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.61 324.17 20.57 324.17 20.56
February 323.00 20.94 218.17 20.79 218.17 20.72
March 391.00 21.59 147.17 21.38 147.17 21.26
April 312.50 22.36 56.67 22.28 45.00 22.12
May 285.50 23.45 35.67 23.67 0.00 23.67
June 182.67 23.88 76.50 24.40 6.33 24.48
July 74.67 25.27 163.67 25.43 25.67 25.67
August 67.00 25.68 210.33 25.31 28.33 25.58
September 133.33 23.78 93.67 24.35 0.50 24.36
October 326.50 23.00 7.67 23.01 3.50 22.99
November 357.00 21.57 154.00 21.29 154.00 21.14
December 340.00 20.73 278.67 20.66 278.67 20.63
             
Annual Sum or Average 3150.17 22.11 1766.33 22.14 1231.50 21.91
Minimum of Months 67.00 20.61 7.67 20.57 0.00 20.56
Maximum of Months 391.00 25.68 324.17 25.43 324.17 25.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 2494964.89 570235.89 3.35 1872067.43 622897.45 0.00 0.09 28-FEB-16:55 0.00 01-FEB-00:10 403.36 28-FEB-16:55 304.47 28-FEB-16:55 98.89 28-FEB-16:55 91.81 28-FEB-16:55 0.00
March 60272213.77 13628479.26 40.53 50258654.47 10013559.30 0.00 0.24 10-MAR-14:25 0.00 01-MAR-00:10 1155.46 10-MAR-14:15 891.32 10-MAR-15:30 283.19 10-MAR-14:15 256.53 10-MAR-14:15 0.00
April 0.435090E+09 96779748.87 112.93 0.375002E+09 60087650.61 0.00 1.00 28-APR-05:03 0.00 01-APR-00:10 5507.59 28-APR-05:03 4492.10 28-APR-05:03 1015.49 28-APR-05:03 1073.16 28-APR-05:03 0.00
May 0.134323E+10 0.293462E+09 242.66 0.112814E+10 0.215089E+09 0.00 1.00 05-MAY-05:03 0.00 01-MAY-00:10 5577.88 08-MAY-05:03 5102.86 16-MAY-05:03 1337.97 08-MAY-05:03 1082.09 08-MAY-05:03 0.00
June 0.201090E+10 0.432137E+09 259.85 0.171253E+10 0.298365E+09 0.00 1.00 09-JUN-05:03 0.00 01-JUN-00:10 5601.88 13-JUN-05:03 5208.41 12-JUN-05:02 1426.06 13-JUN-05:03 1084.88 13-JUN-05:03 0.00
July 0.253484E+10 0.538247E+09 239.74 0.212103E+10 0.413811E+09 0.00 1.00 03-JUL-05:03 0.00 01-JUL-00:10 5622.68 28-JUL-05:02 4994.42 19-JUL-05:02 1390.03 28-JUL-05:15 1105.23 24-JUL-15:00 0.00
August 0.325346E+10 0.693934E+09 275.96 0.267490E+10 0.578558E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5615.62 10-AUG-05:02 4896.10 14-AUG-05:01 1358.55 28-AUG-05:06 1096.11 10-AUG-16:00 0.00
September 0.199090E+10 0.424004E+09 237.18 0.161224E+10 0.378660E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 5601.96 26-SEP-05:03 4963.59 11-SEP-05:02 1456.72 26-SEP-05:03 1084.88 26-SEP-05:03 0.00
October 0.813838E+09 0.179198E+09 199.14 0.694514E+09 0.119325E+09 0.00 1.00 04-OCT-05:03 0.00 01-OCT-00:10 5459.88 06-OCT-05:03 5256.24 05-OCT-05:03 760.96 06-OCT-05:03 1066.47 06-OCT-05:03 0.00
November 0.189199E+09 42410391.76 70.86 0.144202E+09 44997236.77 0.00 0.30 03-NOV-16:00 0.00 01-NOV-00:10 1424.28 03-NOV-16:00 1015.87 02-NOV-14:00 427.52 03-NOV-16:00 313.45 03-NOV-16:00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.126342E+11 0.271437E+10 1682.20 0.105147E+11 0.211953E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.325346E+10 0.693934E+09 275.96 0.267490E+10 0.578558E+09 0.00 1.00   0.00   5622.68   5256.24   1456.72   1105.23   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 32444825.24 7323006.25 17.47 31995067.96 449757.29 0.00 0.26 27-FEB-15:00 0.00 01-FEB-00:10 1598.25 27-FEB-15:00 1598.25 27-FEB-15:00 45.04 28-FEB-14:55 355.17 27-FEB-15:00 0.00
March 0.118088E+09 26494656.56 41.17 0.117374E+09 713519.07 0.00 0.29 02-MAR-14:20 0.00 01-MAR-00:10 1801.87 02-MAR-14:25 1801.87 02-MAR-14:25 101.11 10-MAR-13:20 397.58 02-MAR-14:30 0.00
April 0.348662E+09 78421497.06 77.43 0.335505E+09 13157286.07 0.00 0.63 27-APR-14:30 0.00 01-APR-00:10 4213.17 27-APR-14:30 3973.83 27-APR-14:30 431.33 28-APR-13:02 960.90 27-APR-14:40 0.00
May 0.625393E+09 0.139920E+09 147.11 0.582954E+09 42438322.02 0.00 0.49 04-MAY-14:00 0.00 01-MAY-00:10 3214.54 04-MAY-14:00 3109.50 15-MAY-14:00 373.25 05-MAY-13:15 716.44 04-MAY-14:00 0.00
June 0.104272E+10 0.232764E+09 204.10 0.969221E+09 73500782.81 0.00 0.52 28-JUN-14:10 0.00 01-JUN-00:10 3427.81 28-JUN-14:10 3263.18 28-JUN-14:30 375.30 12-JUN-14:50 778.76 28-JUN-14:30 0.00
July 0.176341E+10 0.391037E+09 216.89 0.158330E+10 0.180114E+09 0.00 1.00 24-JUL-05:01 0.00 01-JUL-00:10 7387.92 31-JUL-05:02 7230.92 24-JUL-05:01 827.03 26-JUL-05:02 1444.06 31-JUL-05:02 0.00
August 0.271164E+10 0.602151E+09 259.81 0.239843E+10 0.313215E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 7452.43 25-AUG-05:02 7209.59 09-AUG-05:02 1058.20 31-AUG-05:02 1453.32 25-AUG-05:02 0.00
September 0.174262E+10 0.373936E+09 201.15 0.156470E+10 0.177915E+09 0.00 1.00 11-SEP-05:02 0.00 01-SEP-00:10 7382.32 15-SEP-05:02 7262.66 11-SEP-05:02 877.87 14-SEP-12:05 1443.23 15-SEP-05:02 0.00
October 0.708023E+09 0.153955E+09 123.25 0.692108E+09 15915184.36 0.00 0.75 04-OCT-14:00 0.00 01-OCT-00:10 5016.91 04-OCT-14:00 5016.91 04-OCT-14:00 233.04 06-OCT-10:43 1029.32 04-OCT-14:10 0.00
November 44224469.48 10044426.43 27.86 40979439.84 3245029.64 0.00 0.21 02-NOV-13:30 0.00 01-NOV-00:10 1311.13 02-NOV-13:30 1179.54 02-NOV-13:30 131.59 02-NOV-13:30 293.50 02-NOV-13:30 0.00
December 9000340.82 2038919.83 5.03 9000340.82 -0.0 0.00 0.18 05-DEC-13:10 0.00 01-DEC-00:10 1043.61 05-DEC-13:10 1043.61 05-DEC-13:10 0.00 05-DEC-15:13 234.23 05-DEC-13:10 0.00
                                       
Annual Sum or Average 0.914622E+10 0.201809E+10 1321.27 0.832556E+10 0.820664E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.271164E+10 0.602151E+09 259.81 0.239843E+10 0.313215E+09 0.00 1.00   0.00   7452.43   7262.66   1058.20   1453.32   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.134720E+09 30697753.72 71.00 0.130065E+09 4655490.57 0.00 0.45 27-APR-15:20 0.00 01-APR-00:10 1670.46 27-APR-15:20 1571.41 27-APR-15:13 140.60 28-APR-13:00 396.10 27-APR-15:20 0.00
May 0.380721E+09 85425596.49 171.45 0.360167E+09 20553705.46 0.00 0.45 15-MAY-10:10 0.00 01-MAY-00:10 1702.62 15-MAY-10:20 1676.76 15-MAY-10:06 175.32 05-MAY-16:00 366.81 15-MAY-10:20 0.00
June 0.827045E+09 0.183181E+09 239.48 0.781282E+09 45762255.61 0.00 0.57 28-JUN-09:00 0.00 01-JUN-00:10 2210.99 28-JUN-09:00 2095.37 28-JUN-10:02 236.85 12-JUN-09:00 467.07 28-JUN-09:00 0.00
July 0.114655E+10 0.253057E+09 232.86 0.105318E+10 93366987.76 0.00 1.00 24-JUL-05:01 0.00 01-JUL-00:10 4295.18 31-JUL-05:02 4226.52 24-JUL-05:01 441.42 31-JUL-05:02 839.85 31-JUL-05:02 0.00
August 0.157247E+10 0.349331E+09 271.34 0.141518E+10 0.157288E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4332.32 25-AUG-05:02 4163.53 15-AUG-05:02 639.90 25-AUG-05:02 845.25 25-AUG-05:02 0.00
September 0.763726E+09 0.167573E+09 210.51 0.686196E+09 77529389.86 0.00 0.98 11-SEP-05:02 0.00 01-SEP-00:10 4106.88 12-SEP-05:02 4068.74 11-SEP-05:02 443.90 14-SEP-05:02 808.83 12-SEP-05:02 0.00
October 0.173575E+09 38852566.35 90.35 0.170319E+09 3256133.65 0.00 0.36 04-OCT-10:02 0.00 01-OCT-00:10 1310.01 04-OCT-10:02 1310.01 04-OCT-10:02 90.59 06-OCT-09:00 286.42 04-OCT-10:10 0.00
November 756706.07 174111.60 2.67 661580.74 95125.33 0.00 0.04 02-NOV-14:20 0.00 01-NOV-00:10 145.08 02-NOV-14:20 131.17 02-NOV-14:20 13.90 02-NOV-14:20 33.33 02-NOV-14:20 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.499956E+10 0.110829E+10 1289.66 0.459705E+10 0.402507E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.157247E+10 0.349331E+09 271.34 0.141518E+10 0.157288E+09 0.00 1.00   0.00   4332.32   4226.52   639.90   845.25   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 65797085.27 15171569.63 21.15 59745217.64 6051867.63 0.00 0.47 27-APR-15:53 0.00 01-APR-00:10 1885.47 27-APR-15:53 1729.15 27-APR-15:53 232.63 28-APR-13:13 443.52 27-APR-15:53 0.00
May 0.331201E+09 74140196.74 128.80 0.297324E+09 33877608.42 0.00 0.54 05-MAY-16:00 0.00 01-MAY-00:10 2206.21 05-MAY-16:00 1907.61 05-MAY-16:00 298.60 05-MAY-16:00 493.60 05-MAY-16:00 0.00
June 0.838926E+09 0.185276E+09 210.29 0.761283E+09 77642419.18 0.00 0.64 28-JUN-16:00 0.00 01-JUN-00:10 2610.32 28-JUN-16:00 2469.91 28-JUN-15:53 357.09 12-JUN-15:00 588.37 28-JUN-16:00 0.00
July 0.134701E+10 0.294796E+09 225.92 0.118516E+10 0.161848E+09 0.00 1.00 24-JUL-05:01 0.00 01-JUL-00:10 4504.77 25-JUL-05:02 4417.94 24-JUL-05:01 548.91 26-JUL-05:02 881.57 25-JUL-05:02 0.00
August 0.180164E+10 0.397598E+09 264.08 0.155110E+10 0.250538E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4555.25 25-AUG-05:02 4270.90 09-AUG-05:02 733.09 25-AUG-05:02 889.06 25-AUG-05:02 0.00
September 0.776050E+09 0.170273E+09 185.81 0.656360E+09 0.119691E+09 0.00 0.79 14-SEP-05:02 0.00 01-SEP-00:10 3417.34 14-SEP-05:02 2936.58 14-SEP-05:02 480.76 14-SEP-05:02 693.91 14-SEP-05:02 0.00
October 0.109094E+09 24400537.68 50.69 0.104779E+09 4314901.44 0.00 0.36 04-OCT-15:27 0.00 01-OCT-00:10 1362.71 04-OCT-15:27 1362.71 04-OCT-15:27 112.15 06-OCT-10:53 300.28 04-OCT-15:00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.526972E+10 0.116165E+10 1086.74 0.461576E+10 0.653963E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.180164E+10 0.397598E+09 264.08 0.155110E+10 0.250538E+09 0.00 1.00   0.00   4555.25   4417.94   733.09   889.06   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 924954.44 212409.21 1.67 913758.06 11196.38 0.00 0.08 27-FEB-15:30 0.00 01-FEB-00:10 315.12 27-FEB-15:30 315.12 27-FEB-15:30 3.13 27-FEB-16:10 72.02 27-FEB-15:30 0.00
March 9139158.79 2083324.87 8.94 9124124.85 15033.94 0.00 0.14 02-MAR-16:35 0.00 01-MAR-00:10 564.48 02-MAR-16:35 564.48 02-MAR-16:35 4.98 14-MAR-15:40 127.75 02-MAR-16:40 0.00
April 0.140242E+09 32051332.19 59.12 0.132406E+09 7836459.27 0.00 0.53 27-APR-15:53 0.00 01-APR-00:10 2374.61 27-APR-15:53 2214.52 27-APR-15:55 184.29 28-APR-13:45 555.60 27-APR-15:53 0.00
May 0.458244E+09 0.102853E+09 179.17 0.424590E+09 33653777.84 0.00 0.55 15-MAY-16:00 0.00 01-MAY-00:10 2447.11 15-MAY-15:57 2447.11 15-MAY-15:57 256.03 08-MAY-15:55 542.49 15-MAY-15:57 0.00
June 0.807601E+09 0.180397E+09 231.30 0.749384E+09 58217361.50 0.00 0.77 23-JUN-05:02 0.00 01-JUN-00:10 3712.06 23-JUN-05:02 3563.67 23-JUN-05:02 238.29 29-JUN-05:02 757.69 23-JUN-05:02 0.00
July 0.124241E+10 0.276414E+09 236.22 0.112412E+10 0.118283E+09 0.00 1.00 20-JUL-05:02 0.00 01-JUL-00:10 5123.07 31-JUL-05:02 5044.41 24-JUL-05:01 624.93 27-JUL-05:02 1000.80 31-JUL-05:02 0.00
August 0.158345E+10 0.356885E+09 272.27 0.140338E+10 0.180073E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5162.03 25-AUG-05:02 5018.68 15-AUG-05:02 657.86 25-AUG-05:02 1006.31 25-AUG-05:02 0.00
September 0.852254E+09 0.188417E+09 214.41 0.754169E+09 98085862.13 0.00 1.00 11-SEP-05:02 0.00 01-SEP-00:10 5074.74 14-SEP-05:02 4969.66 11-SEP-05:02 496.29 15-SEP-05:02 993.48 14-SEP-05:02 0.00
October 0.212295E+09 47490042.55 102.43 0.205317E+09 6977383.74 0.00 0.50 04-OCT-16:00 0.00 01-OCT-00:10 2209.16 04-OCT-15:57 2209.16 04-OCT-15:57 93.18 06-OCT-15:15 472.55 04-OCT-15:57 0.00
November 4843818.58 1111215.74 11.06 4100938.66 742879.92 0.00 0.06 02-NOV-14:40 0.00 01-NOV-00:10 276.98 02-NOV-14:40 237.45 02-NOV-14:35 46.66 03-NOV-16:00 63.34 02-NOV-14:40 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.531140E+10 0.118791E+10 1316.59 0.480750E+10 0.503896E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.158345E+10 0.356885E+09 272.27 0.140338E+10 0.180073E+09 0.00 1.00   0.00   5162.03   5044.41   657.86   1006.31   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.57 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.48 30.11 41.37 81.40 36.48 0.00 0.00 0.00
May 57.76 13.34 44.42 62.00 31.53 0.00 0.00 0.00
June 49.72 8.06 41.67 51.94 25.41 0.00 0.00 0.00
July 54.75 14.72 40.03 65.28 23.96 0.00 0.00 0.00
August 65.95 28.18 37.78 85.41 24.22 0.00 0.00 0.00
September 83.63 46.75 36.88 104.08 34.00 0.00 0.00 0.00
October 77.04 48.27 28.77 88.48 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.66 29.72 31.95 68.89 38.97 0.00 0.00 0.00
Minimum of Months 44.72 8.06 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.63 48.27 44.42 104.08 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.56 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.38 30.08 41.31 81.26 36.51 0.00 0.00 0.00
May 57.68 13.31 44.37 61.84 31.53 0.00 0.00 0.00
June 49.70 8.05 41.65 51.89 25.41 0.00 0.00 0.00
July 54.70 14.69 40.01 65.17 23.96 0.00 0.00 0.00
August 65.84 28.12 37.72 85.16 24.22 0.00 0.00 0.00
September 83.57 46.73 36.84 104.00 34.02 0.00 0.00 0.00
October 77.04 48.27 28.77 88.47 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.63 29.70 31.92 68.82 38.97 0.00 0.00 0.00
Minimum of Months 44.72 8.05 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.57 48.27 44.37 104.00 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.56 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.38 30.08 41.30 81.26 36.52 0.00 0.00 0.00
May 57.68 13.31 44.37 61.84 31.53 0.00 0.00 0.00
June 49.70 8.05 41.65 51.89 25.41 0.00 0.00 0.00
July 54.70 14.69 40.01 65.17 23.96 0.00 0.00 0.00
August 65.84 28.12 37.72 85.16 24.22 0.00 0.00 0.00
September 83.57 46.73 36.84 104.00 34.02 0.00 0.00 0.00
October 77.04 48.27 28.77 88.47 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.63 29.70 31.92 68.82 38.97 0.00 0.00 0.00
Minimum of Months 44.72 8.05 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.57 48.27 44.37 104.00 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.56 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.38 30.08 41.30 81.26 36.52 0.00 0.00 0.00
May 57.68 13.31 44.37 61.84 31.53 0.00 0.00 0.00
June 49.70 8.05 41.65 51.89 25.41 0.00 0.00 0.00
July 54.70 14.69 40.01 65.17 23.96 0.00 0.00 0.00
August 65.84 28.12 37.72 85.16 24.22 0.00 0.00 0.00
September 83.57 46.73 36.84 104.00 34.02 0.00 0.00 0.00
October 77.04 48.27 28.77 88.47 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.63 29.70 31.92 68.82 38.97 0.00 0.00 0.00
Minimum of Months 44.72 8.05 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.57 48.27 44.37 104.00 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.56 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.38 30.08 41.31 81.26 36.51 0.00 0.00 0.00
May 57.68 13.31 44.37 61.84 31.53 0.00 0.00 0.00
June 49.70 8.05 41.65 51.89 25.41 0.00 0.00 0.00
July 54.70 14.69 40.01 65.17 23.96 0.00 0.00 0.00
August 65.84 28.12 37.72 85.16 24.22 0.00 0.00 0.00
September 83.58 46.73 36.85 104.00 34.01 0.00 0.00 0.00
October 77.04 48.27 28.77 88.47 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.63 29.70 31.92 68.82 38.97 0.00 0.00 0.00
Minimum of Months 44.72 8.05 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.58 48.27 44.37 104.00 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.72 27.02 17.70 41.65 53.48 0.00 0.00 0.00
February 68.88 43.32 25.57 73.02 48.54 0.00 0.00 0.00
March 73.74 40.14 33.60 81.18 43.42 0.00 0.00 0.00
April 71.49 30.12 41.37 81.36 36.41 0.00 0.00 0.00
May 57.74 13.33 44.41 61.96 31.52 0.00 0.00 0.00
June 49.73 8.06 41.67 51.94 25.41 0.00 0.00 0.00
July 54.74 14.71 40.03 65.25 23.96 0.00 0.00 0.00
August 65.95 28.17 37.78 85.40 24.22 0.00 0.00 0.00
September 83.62 46.75 36.87 104.03 33.96 0.00 0.00 0.00
October 77.04 48.27 28.77 88.48 42.81 0.00 0.00 0.00
November 45.35 26.49 18.86 44.28 48.12 0.00 0.00 0.00
December 47.74 31.30 16.44 48.52 56.19 0.00 0.00 0.00
                 
Annual Sum or Average 61.66 29.72 31.94 68.87 38.96 0.00 0.00 0.00
Minimum of Months 44.72 8.06 16.44 41.65 23.96 0.00 0.00 0.00
Maximum of Months 83.62 48.27 44.41 104.03 56.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.20 37.86 25.34 58.94 74.37 0.00 0.00 0.00
February 97.26 60.69 36.58 103.17 67.59 0.00 0.00 0.00
March 104.38 56.24 48.13 114.89 60.36 0.00 0.00 0.00
April 109.46 48.08 61.38 127.85 50.68 0.00 0.00 0.00
May 93.42 26.04 67.38 106.35 43.86 0.00 0.00 0.00
June 81.51 18.43 63.08 91.90 35.40 0.00 0.00 0.00
July 90.54 30.25 60.29 113.78 33.48 0.00 0.00 0.00
August 105.05 48.79 56.26 139.17 33.92 0.00 0.00 0.00
September 119.84 66.77 53.07 149.43 47.49 0.00 0.00 0.00
October 108.73 67.63 41.10 124.78 59.67 0.00 0.00 0.00
November 64.14 37.11 27.03 62.68 66.94 0.00 0.00 0.00
December 67.31 43.85 23.47 68.34 78.18 0.00 0.00 0.00
                 
Annual Sum or Average 92.01 45.04 46.96 105.09 54.27 0.00 0.00 0.00
Minimum of Months 63.20 18.43 23.47 58.94 33.48 0.00 0.00 0.00
Maximum of Months 119.84 67.63 67.38 149.43 78.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.60 4.12 11.48 6.05 55.17 0.00 0.00 0.00
February 28.76 10.51 18.25 20.13 47.70 0.00 0.00 0.00
March 42.71 15.75 26.95 37.40 40.03 0.00 0.00 0.00
April 66.12 27.83 38.29 69.26 32.45 0.00 0.00 0.00
May 69.06 23.95 45.11 74.11 29.04 0.00 0.00 0.00
June 83.19 36.06 47.13 94.90 23.74 0.00 0.00 0.00
July 77.47 34.35 43.12 91.94 21.38 0.00 0.00 0.00
August 77.39 38.83 38.56 95.36 21.63 0.00 0.00 0.00
September 57.55 26.87 30.68 62.87 30.78 0.00 0.00 0.00
October 37.58 16.30 21.28 34.28 40.07 0.00 0.00 0.00
November 18.24 5.35 12.90 9.82 47.78 0.00 0.00 0.00
December 15.10 5.04 10.05 7.66 56.79 0.00 0.00 0.00
                 
Annual Sum or Average 49.15 20.46 28.70 50.47 37.17 0.00 0.00 0.00
Minimum of Months 15.10 4.12 10.05 6.05 21.38 0.00 0.00 0.00
Maximum of Months 83.19 38.83 47.13 95.36 56.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.60 4.12 11.48 6.05 55.17 0.00 0.00 0.00
February 28.76 10.51 18.25 20.13 47.70 0.00 0.00 0.00
March 42.70 15.75 26.95 37.40 40.03 0.00 0.00 0.00
April 66.12 27.83 38.29 69.25 32.45 0.00 0.00 0.00
May 69.06 23.95 45.10 74.11 29.04 0.00 0.00 0.00
June 83.18 36.06 47.13 94.90 23.74 0.00 0.00 0.00
July 77.47 34.35 43.12 91.93 21.38 0.00 0.00 0.00
August 77.39 38.83 38.56 95.36 21.63 0.00 0.00 0.00
September 57.55 26.87 30.68 62.87 30.78 0.00 0.00 0.00
October 37.58 16.30 21.28 34.28 40.07 0.00 0.00 0.00
November 18.24 5.35 12.90 9.82 47.78 0.00 0.00 0.00
December 15.10 5.04 10.05 7.66 56.79 0.00 0.00 0.00
                 
Annual Sum or Average 49.15 20.46 28.69 50.47 37.17 0.00 0.00 0.00
Minimum of Months 15.10 4.12 10.05 6.05 21.38 0.00 0.00 0.00
Maximum of Months 83.18 38.83 47.13 95.36 56.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.60 4.12 11.48 6.05 55.17 0.00 0.00 0.00
February 28.76 10.51 18.25 20.13 47.70 0.00 0.00 0.00
March 42.70 15.75 26.95 37.40 40.03 0.00 0.00 0.00
April 66.12 27.83 38.29 69.25 32.45 0.00 0.00 0.00
May 69.06 23.95 45.10 74.11 29.04 0.00 0.00 0.00
June 83.18 36.06 47.13 94.90 23.74 0.00 0.00 0.00
July 77.47 34.35 43.12 91.93 21.38 0.00 0.00 0.00
August 77.39 38.83 38.56 95.36 21.63 0.00 0.00 0.00
September 57.55 26.87 30.68 62.87 30.78 0.00 0.00 0.00
October 37.58 16.30 21.28 34.28 40.07 0.00 0.00 0.00
November 18.24 5.35 12.90 9.82 47.78 0.00 0.00 0.00
December 15.10 5.04 10.05 7.66 56.79 0.00 0.00 0.00
                 
Annual Sum or Average 49.15 20.46 28.69 50.47 37.17 0.00 0.00 0.00
Minimum of Months 15.10 4.12 10.05 6.05 21.38 0.00 0.00 0.00
Maximum of Months 83.18 38.83 47.13 95.36 56.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.66 4.14 11.52 6.10 55.11 0.00 0.00 0.00
February 28.83 10.54 18.29 20.23 47.68 0.00 0.00 0.00
March 42.72 15.76 26.96 37.43 40.03 0.00 0.00 0.00
April 66.12 27.83 38.29 69.26 32.45 0.00 0.00 0.00
May 69.06 23.95 45.11 74.11 29.04 0.00 0.00 0.00
June 83.19 36.06 47.13 94.90 23.74 0.00 0.00 0.00
July 77.47 34.35 43.12 91.94 21.38 0.00 0.00 0.00
August 77.39 38.83 38.56 95.36 21.63 0.00 0.00 0.00
September 57.56 26.88 30.68 62.88 30.78 0.00 0.00 0.00
October 37.63 16.32 21.30 34.37 40.07 0.00 0.00 0.00
November 18.30 5.37 12.93 9.90 47.76 0.00 0.00 0.00
December 15.17 5.07 10.10 7.75 56.74 0.00 0.00 0.00
                 
Annual Sum or Average 49.18 20.47 28.71 50.50 37.15 0.00 0.00 0.00
Minimum of Months 15.17 4.14 10.10 6.10 21.38 0.00 0.00 0.00
Maximum of Months 83.19 38.83 47.13 95.36 56.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.47 0.12 31.35 23.30 32.78 0.00 0.00 0.00
May 40.41 1.20 39.22 34.78 28.33 0.00 0.00 0.00
June 42.68 2.78 39.90 39.38 22.57 0.00 0.00 0.00
July 40.84 3.18 37.66 42.19 20.98 0.00 0.00 0.00
August 33.03 0.90 32.13 34.71 21.06 0.00 0.00 0.00
September 25.54 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.78 0.69 24.09 18.34 37.97 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.98 0.00 0.00 0.00
Maximum of Months 42.68 3.18 39.90 42.19 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.45 0.11 31.34 23.30 32.81 0.00 0.00 0.00
May 40.35 1.18 39.17 34.70 28.36 0.00 0.00 0.00
June 42.58 2.74 39.84 39.18 22.57 0.00 0.00 0.00
July 40.76 3.14 37.62 42.03 20.99 0.00 0.00 0.00
August 32.96 0.88 32.08 34.62 21.11 0.00 0.00 0.00
September 25.54 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.75 0.68 24.08 18.30 37.98 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.99 0.00 0.00 0.00
Maximum of Months 42.58 3.14 39.84 42.03 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.44 0.11 31.33 23.30 32.82 0.00 0.00 0.00
May 40.35 1.18 39.17 34.70 28.36 0.00 0.00 0.00
June 42.58 2.74 39.84 39.18 22.57 0.00 0.00 0.00
July 40.76 3.14 37.62 42.03 20.99 0.00 0.00 0.00
August 32.96 0.88 32.08 34.62 21.11 0.00 0.00 0.00
September 25.53 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.75 0.68 24.08 18.30 37.98 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.99 0.00 0.00 0.00
Maximum of Months 42.58 3.14 39.84 42.03 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.44 0.11 31.33 23.30 32.82 0.00 0.00 0.00
May 40.35 1.18 39.17 34.70 28.36 0.00 0.00 0.00
June 42.58 2.74 39.84 39.18 22.57 0.00 0.00 0.00
July 40.76 3.14 37.62 42.03 20.99 0.00 0.00 0.00
August 32.96 0.88 32.08 34.62 21.11 0.00 0.00 0.00
September 25.54 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.75 0.68 24.08 18.30 37.98 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.99 0.00 0.00 0.00
Maximum of Months 42.58 3.14 39.84 42.03 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.45 0.11 31.34 23.30 32.81 0.00 0.00 0.00
May 40.35 1.18 39.17 34.70 28.36 0.00 0.00 0.00
June 42.58 2.74 39.84 39.18 22.57 0.00 0.00 0.00
July 40.76 3.14 37.62 42.03 20.99 0.00 0.00 0.00
August 32.96 0.88 32.08 34.62 21.11 0.00 0.00 0.00
September 25.54 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.75 0.68 24.08 18.30 37.98 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.99 0.00 0.00 0.00
Maximum of Months 42.58 3.14 39.84 42.03 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 0.41 58.16 0.00 0.00 0.00
February 14.93 0.00 14.93 3.66 50.61 0.00 0.00 0.00
March 22.08 0.00 22.08 10.99 41.31 0.00 0.00 0.00
April 31.47 0.11 31.35 23.32 32.80 0.00 0.00 0.00
May 40.45 1.21 39.23 34.88 28.36 0.00 0.00 0.00
June 42.68 2.77 39.90 39.37 22.57 0.00 0.00 0.00
July 40.87 3.19 37.68 42.26 20.99 0.00 0.00 0.00
August 33.03 0.90 32.12 34.75 21.11 0.00 0.00 0.00
September 25.54 0.01 25.53 19.82 31.17 0.00 0.00 0.00
October 17.37 0.00 17.37 8.02 40.72 0.00 0.00 0.00
November 10.78 0.00 10.78 1.50 49.46 0.00 0.00 0.00
December 8.13 0.00 8.13 0.28 59.22 0.00 0.00 0.00
                 
Annual Sum or Average 24.79 0.69 24.10 18.36 37.98 0.00 0.00 0.00
Minimum of Months 8.13 0.00 8.13 0.28 20.99 0.00 0.00 0.00
Maximum of Months 42.68 3.19 39.90 42.26 59.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.56 5.09 11.47 7.84 55.76 0.00 0.00 0.00
February 29.77 11.50 18.27 22.60 48.84 0.00 0.00 0.00
March 41.26 14.20 27.07 36.37 41.45 0.00 0.00 0.00
April 62.43 24.03 38.40 65.19 34.34 0.00 0.00 0.00
May 79.81 32.65 47.16 88.91 31.00 0.00 0.00 0.00
June 76.57 29.52 47.05 86.32 25.15 0.00 0.00 0.00
July 95.64 50.35 45.28 117.71 24.34 0.00 0.00 0.00
August 79.74 40.91 38.83 99.87 24.14 0.00 0.00 0.00
September 65.41 31.75 33.67 75.29 33.06 0.00 0.00 0.00
October 37.27 15.50 21.77 34.65 41.68 0.00 0.00 0.00
November 18.45 5.42 13.03 10.53 48.51 0.00 0.00 0.00
December 15.67 5.57 10.10 9.31 57.54 0.00 0.00 0.00
                 
Annual Sum or Average 51.68 22.29 29.39 54.76 38.77 0.00 0.00 0.00
Minimum of Months 15.67 5.09 10.10 7.84 24.14 0.00 0.00 0.00
Maximum of Months 95.64 50.35 47.16 117.71 57.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.49 5.07 11.42 7.78 55.81 0.00 0.00 0.00
February 29.72 11.48 18.24 22.51 48.86 0.00 0.00 0.00
March 41.24 14.19 27.06 36.34 41.45 0.00 0.00 0.00
April 62.43 24.03 38.40 65.19 34.34 0.00 0.00 0.00
May 79.81 32.65 47.16 88.90 31.00 0.00 0.00 0.00
June 76.57 29.52 47.05 86.32 25.15 0.00 0.00 0.00
July 95.64 50.35 45.28 117.71 24.34 0.00 0.00 0.00
August 79.74 40.91 38.83 99.86 24.14 0.00 0.00 0.00
September 65.41 31.75 33.66 75.28 33.06 0.00 0.00 0.00
October 37.23 15.49 21.74 34.57 41.68 0.00 0.00 0.00
November 18.39 5.40 12.99 10.45 48.53 0.00 0.00 0.00
December 15.61 5.55 10.06 9.23 57.58 0.00 0.00 0.00
                 
Annual Sum or Average 51.66 22.28 29.38 54.72 38.78 0.00 0.00 0.00
Minimum of Months 15.61 5.07 10.06 7.78 24.14 0.00 0.00 0.00
Maximum of Months 95.64 50.35 47.16 117.71 57.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.49 5.07 11.42 7.78 55.81 0.00 0.00 0.00
February 29.72 11.48 18.24 22.51 48.86 0.00 0.00 0.00
March 41.24 14.19 27.06 36.34 41.45 0.00 0.00 0.00
April 62.43 24.03 38.40 65.19 34.34 0.00 0.00 0.00
May 79.81 32.65 47.16 88.90 31.00 0.00 0.00 0.00
June 76.57 29.52 47.05 86.32 25.15 0.00 0.00 0.00
July 95.64 50.35 45.28 117.71 24.34 0.00 0.00 0.00
August 79.74 40.91 38.83 99.86 24.14 0.00 0.00 0.00
September 65.41 31.75 33.66 75.28 33.06 0.00 0.00 0.00
October 37.23 15.49 21.74 34.57 41.68 0.00 0.00 0.00
November 18.39 5.40 12.99 10.45 48.53 0.00 0.00 0.00
December 15.61 5.55 10.06 9.23 57.58 0.00 0.00 0.00
                 
Annual Sum or Average 51.66 22.28 29.38 54.72 38.78 0.00 0.00 0.00
Minimum of Months 15.61 5.07 10.06 7.78 24.14 0.00 0.00 0.00
Maximum of Months 95.64 50.35 47.16 117.71 57.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.49 5.07 11.42 7.78 55.81 0.00 0.00 0.00
February 29.72 11.48 18.24 22.51 48.86 0.00 0.00 0.00
March 41.24 14.19 27.06 36.34 41.45 0.00 0.00 0.00
April 62.43 24.03 38.40 65.19 34.34 0.00 0.00 0.00
May 79.81 32.65 47.16 88.91 31.00 0.00 0.00 0.00
June 76.57 29.52 47.05 86.32 25.15 0.00 0.00 0.00
July 95.64 50.35 45.28 117.71 24.34 0.00 0.00 0.00
August 79.74 40.91 38.83 99.87 24.14 0.00 0.00 0.00
September 65.41 31.75 33.66 75.28 33.06 0.00 0.00 0.00
October 37.23 15.49 21.75 34.57 41.68 0.00 0.00 0.00
November 18.40 5.40 13.00 10.45 48.53 0.00 0.00 0.00
December 15.61 5.55 10.06 9.23 57.58 0.00 0.00 0.00
                 
Annual Sum or Average 51.66 22.28 29.38 54.72 38.78 0.00 0.00 0.00
Minimum of Months 15.61 5.07 10.06 7.78 24.14 0.00 0.00 0.00
Maximum of Months 95.64 50.35 47.16 117.71 57.58 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119788E+09 72370997.34 47416673.17 0.111558E+09 0.143253E+09
February 0.166642E+09 0.104793E+09 61849569.90 0.176651E+09 0.117438E+09
March 0.197515E+09 0.107521E+09 89994539.33 0.217430E+09 0.116294E+09
April 0.185276E+09 78053649.93 0.107222E+09 0.211000E+09 94557174.17
May 0.154700E+09 35727770.54 0.118972E+09 0.166057E+09 84438497.94
June 0.128879E+09 20880528.17 0.107999E+09 0.134620E+09 65868141.07
July 0.146645E+09 39420510.69 0.107225E+09 0.174858E+09 64185335.49
August 0.176653E+09 75472448.38 0.101180E+09 0.228760E+09 64880637.79
September 0.216758E+09 0.121174E+09 95584256.83 0.269783E+09 88135515.08
October 0.206357E+09 0.129291E+09 77066260.07 0.236972E+09 0.114665E+09
November 0.117543E+09 68662429.69 48881038.34 0.114782E+09 0.124736E+09
December 0.127864E+09 83828109.31 44035673.18 0.129960E+09 0.150511E+09
           
Annual Sum or Average 0.194462E+10 0.937194E+09 0.100743E+10 0.217243E+10 0.122896E+10
Minimum of Months 0.117543E+09 20880528.17 44035673.18 0.111558E+09 64185335.49
Maximum of Months 0.216758E+09 0.129291E+09 0.118972E+09 0.269783E+09 0.150511E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119785E+09 72370997.34 47414368.75 0.111556E+09 0.143253E+09
February 0.166639E+09 0.104793E+09 61846649.61 0.176649E+09 0.117437E+09
March 0.197511E+09 0.107521E+09 89990013.70 0.217425E+09 0.116293E+09
April 0.185030E+09 77966582.65 0.107063E+09 0.210625E+09 94646429.86
May 0.154480E+09 35643507.91 0.118837E+09 0.165637E+09 84439653.00
June 0.128819E+09 20862940.02 0.107956E+09 0.134511E+09 65867809.35
July 0.146497E+09 39344404.45 0.107152E+09 0.174546E+09 64184763.28
August 0.176338E+09 75312378.36 0.101025E+09 0.228102E+09 64879815.52
September 0.216625E+09 0.121124E+09 95500311.12 0.269573E+09 88176101.98
October 0.206354E+09 0.129291E+09 77062900.50 0.236968E+09 0.114664E+09
November 0.117541E+09 68662429.69 48878535.93 0.114780E+09 0.124735E+09
December 0.127862E+09 83828109.31 44033828.24 0.129959E+09 0.150510E+09
           
Annual Sum or Average 0.194348E+10 0.936720E+09 0.100676E+10 0.217033E+10 0.122909E+10
Minimum of Months 0.117541E+09 20862940.02 44033828.24 0.111556E+09 64184763.28
Maximum of Months 0.216625E+09 0.129291E+09 0.118837E+09 0.269573E+09 0.150510E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119785E+09 72370997.34 47414368.75 0.111556E+09 0.143253E+09
February 0.166639E+09 0.104793E+09 61846649.61 0.176649E+09 0.117437E+09
March 0.197511E+09 0.107521E+09 89990013.70 0.217425E+09 0.116293E+09
April 0.185025E+09 77966041.33 0.107059E+09 0.210620E+09 94649948.23
May 0.154480E+09 35643507.91 0.118837E+09 0.165637E+09 84439653.00
June 0.128819E+09 20862940.02 0.107956E+09 0.134511E+09 65867809.35
July 0.146497E+09 39344404.45 0.107152E+09 0.174546E+09 64184763.28
August 0.176337E+09 75312040.13 0.101025E+09 0.228101E+09 64879795.36
September 0.216614E+09 0.121123E+09 95491036.92 0.269562E+09 88184631.64
October 0.206354E+09 0.129291E+09 77062900.50 0.236968E+09 0.114664E+09
November 0.117541E+09 68662429.69 48878535.93 0.114780E+09 0.124735E+09
December 0.127862E+09 83828109.31 44033828.24 0.129959E+09 0.150510E+09
           
Annual Sum or Average 0.194346E+10 0.936717E+09 0.100675E+10 0.217031E+10 0.122910E+10
Minimum of Months 0.117541E+09 20862940.02 44033828.24 0.111556E+09 64184763.28
Maximum of Months 0.216614E+09 0.129291E+09 0.118837E+09 0.269562E+09 0.150510E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119785E+09 72370997.34 47414368.75 0.111556E+09 0.143253E+09
February 0.166639E+09 0.104793E+09 61846649.61 0.176649E+09 0.117437E+09
March 0.197511E+09 0.107521E+09 89990013.70 0.217425E+09 0.116293E+09
April 0.185025E+09 77966041.33 0.107059E+09 0.210620E+09 94649948.23
May 0.154480E+09 35643507.91 0.118837E+09 0.165637E+09 84439653.00
June 0.128819E+09 20862940.02 0.107956E+09 0.134511E+09 65867809.35
July 0.146497E+09 39344404.45 0.107152E+09 0.174546E+09 64184763.28
August 0.176337E+09 75312010.14 0.101025E+09 0.228101E+09 64879526.37
September 0.216615E+09 0.121123E+09 95492026.70 0.269561E+09 88181283.23
October 0.206354E+09 0.129291E+09 77062900.50 0.236968E+09 0.114664E+09
November 0.117541E+09 68662429.69 48878535.93 0.114780E+09 0.124735E+09
December 0.127862E+09 83828109.31 44033828.24 0.129959E+09 0.150510E+09
           
Annual Sum or Average 0.194347E+10 0.936717E+09 0.100675E+10 0.217031E+10 0.122910E+10
Minimum of Months 0.117541E+09 20862940.02 44033828.24 0.111556E+09 64184763.28
Maximum of Months 0.216615E+09 0.129291E+09 0.118837E+09 0.269561E+09 0.150510E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119785E+09 72370997.34 47414368.75 0.111556E+09 0.143253E+09
February 0.166639E+09 0.104793E+09 61846649.61 0.176649E+09 0.117437E+09
March 0.197511E+09 0.107521E+09 89990013.70 0.217425E+09 0.116293E+09
April 0.185029E+09 77966688.82 0.107063E+09 0.210620E+09 94642262.66
May 0.154480E+09 35643507.91 0.118837E+09 0.165637E+09 84439653.00
June 0.128819E+09 20862940.02 0.107956E+09 0.134511E+09 65867809.35
July 0.146497E+09 39344404.45 0.107152E+09 0.174546E+09 64184763.28
August 0.176338E+09 75312312.65 0.101025E+09 0.228101E+09 64878503.62
September 0.216629E+09 0.121126E+09 95503174.60 0.269561E+09 88155388.74
October 0.206354E+09 0.129291E+09 77062900.50 0.236968E+09 0.114664E+09
November 0.117541E+09 68662429.69 48878535.93 0.114780E+09 0.124735E+09
December 0.127862E+09 83828109.31 44033828.24 0.129959E+09 0.150510E+09
           
Annual Sum or Average 0.194348E+10 0.936721E+09 0.100676E+10 0.217031E+10 0.122906E+10
Minimum of Months 0.117541E+09 20862940.02 44033828.24 0.111556E+09 64184763.28
Maximum of Months 0.216629E+09 0.129291E+09 0.118837E+09 0.269561E+09 0.150510E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119788E+09 72370997.34 47416673.05 0.111558E+09 0.143253E+09
February 0.166642E+09 0.104793E+09 61849569.75 0.176651E+09 0.117438E+09
March 0.197515E+09 0.107521E+09 89994539.10 0.217430E+09 0.116294E+09
April 0.185300E+09 78074276.51 0.107226E+09 0.210882E+09 94377831.57
May 0.154644E+09 35705161.36 0.118939E+09 0.165946E+09 84436127.14
June 0.128888E+09 20885859.45 0.108002E+09 0.134640E+09 65868103.68
July 0.146607E+09 39398055.58 0.107209E+09 0.174773E+09 64184664.12
August 0.176651E+09 75462182.67 0.101189E+09 0.228731E+09 64866842.18
September 0.216739E+09 0.121177E+09 95561664.36 0.269650E+09 88024386.89
October 0.206357E+09 0.129291E+09 77066259.90 0.236972E+09 0.114665E+09
November 0.117543E+09 68662429.69 48881038.21 0.114782E+09 0.124736E+09
December 0.127864E+09 83828109.31 44035673.08 0.129960E+09 0.150511E+09
           
Annual Sum or Average 0.194454E+10 0.937168E+09 0.100737E+10 0.217197E+10 0.122865E+10
Minimum of Months 0.117543E+09 20885859.45 44035673.08 0.111558E+09 64184664.12
Maximum of Months 0.216739E+09 0.129291E+09 0.118939E+09 0.269650E+09 0.150511E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.169270E+09 0.101393E+09 67877366.16 0.157866E+09 0.199183E+09
February 0.235300E+09 0.146816E+09 88484491.94 0.249594E+09 0.163525E+09
March 0.279561E+09 0.150638E+09 0.128923E+09 0.307717E+09 0.161679E+09
April 0.283709E+09 0.124616E+09 0.159093E+09 0.331395E+09 0.131365E+09
May 0.250209E+09 69743382.14 0.180466E+09 0.284861E+09 0.117466E+09
June 0.211286E+09 47779390.64 0.163507E+09 0.238203E+09 91763448.70
July 0.242501E+09 81023657.77 0.161477E+09 0.304754E+09 89668360.55
August 0.281368E+09 0.130674E+09 0.150694E+09 0.372755E+09 90861685.53
September 0.310623E+09 0.173058E+09 0.137565E+09 0.387333E+09 0.123087E+09
October 0.291217E+09 0.181138E+09 0.110079E+09 0.334207E+09 0.159822E+09
November 0.166250E+09 96196955.48 70053200.45 0.162464E+09 0.173496E+09
December 0.180296E+09 0.117444E+09 62852223.96 0.183031E+09 0.209401E+09
           
Annual Sum or Average 0.290159E+10 0.142052E+10 0.148107E+10 0.331418E+10 0.171132E+10
Minimum of Months 0.166250E+09 47779390.64 62852223.96 0.157866E+09 89668360.55
Maximum of Months 0.310623E+09 0.181138E+09 0.180466E+09 0.387333E+09 0.209401E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41776763.45 11038209.27 30738554.18 16204677.59 0.147772E+09
February 69585133.53 25430454.28 44154679.25 48703580.58 0.115395E+09
March 0.114382E+09 42187093.05 72194600.64 0.100182E+09 0.107206E+09
April 0.171381E+09 72124814.25 99255845.82 0.179514E+09 84110904.48
May 0.184969E+09 64157972.33 0.120811E+09 0.198505E+09 77780697.32
June 0.215619E+09 93461979.33 0.122157E+09 0.245990E+09 61531988.42
July 0.207496E+09 92009061.40 0.115487E+09 0.246241E+09 57274248.69
August 0.207294E+09 0.104009E+09 0.103284E+09 0.255423E+09 57935046.19
September 0.149179E+09 69657962.12 79521499.71 0.162971E+09 79775770.13
October 0.100663E+09 43668239.27 56994454.26 91828885.57 0.107334E+09
November 47290454.60 13856606.89 33433847.71 25449956.98 0.123856E+09
December 40436360.13 13506560.44 26929799.69 20523779.70 0.152115E+09
           
Annual Sum or Average 0.155007E+10 0.645108E+09 0.904962E+09 0.159154E+10 0.117209E+10
Minimum of Months 40436360.13 11038209.27 26929799.69 16204677.59 57274248.69
Maximum of Months 0.215619E+09 0.104009E+09 0.122157E+09 0.255423E+09 0.152115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41774459.15 11038209.27 30736249.88 16203772.53 0.147772E+09
February 69582213.39 25430454.28 44151759.11 48701142.47 0.115394E+09
March 0.114377E+09 42187093.05 72190075.25 0.100178E+09 0.107206E+09
April 0.171375E+09 72124814.25 99250366.61 0.179508E+09 84110382.46
May 0.184962E+09 64157972.33 0.120804E+09 0.198497E+09 77780195.73
June 0.215613E+09 93461979.33 0.122151E+09 0.245983E+09 61531445.68
July 0.207491E+09 92009061.40 0.115481E+09 0.246235E+09 57273337.58
August 0.207289E+09 0.104009E+09 0.103280E+09 0.255418E+09 57933997.32
September 0.149175E+09 69657962.12 79517280.49 0.162966E+09 79774810.80
October 0.100659E+09 43668239.27 56991094.86 91825750.41 0.107334E+09
November 47287952.32 13856606.89 33431345.43 25448406.56 0.123857E+09
December 40434515.29 13506560.44 26927954.85 20523187.20 0.152115E+09
           
Annual Sum or Average 0.155002E+10 0.645108E+09 0.904912E+09 0.159149E+10 0.117208E+10
Minimum of Months 40434515.29 11038209.27 26927954.85 16203772.53 57273337.58
Maximum of Months 0.215613E+09 0.104009E+09 0.122151E+09 0.255418E+09 0.152115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41774459.15 11038209.27 30736249.88 16203772.53 0.147772E+09
February 69582213.39 25430454.28 44151759.11 48701142.47 0.115394E+09
March 0.114377E+09 42187093.05 72190075.25 0.100178E+09 0.107206E+09
April 0.171375E+09 72124814.25 99250366.61 0.179508E+09 84110382.46
May 0.184962E+09 64157972.33 0.120804E+09 0.198497E+09 77780195.73
June 0.215613E+09 93461979.33 0.122151E+09 0.245983E+09 61531445.68
July 0.207491E+09 92009061.40 0.115481E+09 0.246235E+09 57273337.58
August 0.207289E+09 0.104009E+09 0.103280E+09 0.255418E+09 57933997.32
September 0.149175E+09 69657962.12 79517280.49 0.162966E+09 79774810.80
October 0.100659E+09 43668239.27 56991094.86 91825750.41 0.107334E+09
November 47287952.32 13856606.89 33431345.43 25448406.56 0.123857E+09
December 40434515.29 13506560.44 26927954.85 20523187.20 0.152115E+09
           
Annual Sum or Average 0.155002E+10 0.645108E+09 0.904912E+09 0.159149E+10 0.117208E+10
Minimum of Months 40434515.29 11038209.27 26927954.85 16203772.53 57273337.58
Maximum of Months 0.215613E+09 0.104009E+09 0.122151E+09 0.255418E+09 0.152115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41939202.09 11096497.14 30842704.95 16345927.32 0.147602E+09
February 69734082.89 25489069.80 44245013.10 48938854.18 0.115343E+09
March 0.114422E+09 42206170.85 72215828.14 0.100263E+09 0.107206E+09
April 0.171381E+09 72124814.25 99255846.11 0.179514E+09 84110904.51
May 0.184969E+09 64157972.33 0.120811E+09 0.198505E+09 77780697.35
June 0.215619E+09 93461979.33 0.122157E+09 0.245990E+09 61531988.45
July 0.207496E+09 92009061.40 0.115487E+09 0.246241E+09 57274248.74
August 0.207294E+09 0.104009E+09 0.103284E+09 0.255424E+09 57935046.25
September 0.149191E+09 69661171.57 79529636.32 0.162991E+09 79775770.10
October 0.100777E+09 43719439.86 57058056.96 92055296.87 0.107334E+09
November 47434571.46 13910761.51 33523809.96 25667180.46 0.123796E+09
December 40628240.67 13577259.17 27050981.50 20763769.67 0.151985E+09
           
Annual Sum or Average 0.155088E+10 0.645424E+09 0.905461E+09 0.159270E+10 0.117167E+10
Minimum of Months 40628240.67 11096497.14 27050981.50 16345927.32 57274248.74
Maximum of Months 0.215619E+09 0.104009E+09 0.122157E+09 0.255424E+09 0.151985E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25495335.90 0.00 25495335.90 1107475.33 0.155784E+09
February 36120934.40 0.00 36120934.40 8859165.57 0.122432E+09
March 59136236.43 0.00 59136236.43 29444720.73 0.110654E+09
April 81564127.84 298263.68 81265864.16 60387481.20 84955204.99
May 0.108245E+09 3210726.61 0.105034E+09 93156491.66 75890709.77
June 0.110628E+09 7209339.01 0.103419E+09 0.102075E+09 58496710.71
July 0.109385E+09 8504000.17 0.100881E+09 0.112991E+09 56187148.36
August 88468520.12 2422690.40 86045829.71 92962102.43 56408588.82
September 66191832.27 20245.10 66171587.17 51383202.25 80801749.16
October 46533401.82 0.00 46533401.82 21482962.82 0.109060E+09
November 27953922.68 0.00 27953922.68 3884957.19 0.128204E+09
December 21767100.38 0.00 21767100.38 761719.30 0.158621E+09
           
Annual Sum or Average 0.781490E+09 21665264.97 0.759825E+09 0.578496E+09 0.119750E+10
Minimum of Months 21767100.38 0.00 21767100.38 761719.30 56187148.36
Maximum of Months 0.110628E+09 8504000.17 0.105034E+09 0.112991E+09 0.158621E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25493031.48 0.00 25493031.48 1106923.22 0.155785E+09
February 36118014.11 0.00 36118014.11 8857117.90 0.122432E+09
March 59131710.80 0.00 59131710.80 29440573.62 0.110654E+09
April 81513940.73 291142.96 81222797.77 60381608.62 85033419.27
May 0.108084E+09 3161443.64 0.104922E+09 92935255.65 75970473.19
June 0.110362E+09 7099182.32 0.103263E+09 0.101565E+09 58509635.30
July 0.109164E+09 8400708.26 0.100764E+09 0.112564E+09 56212674.24
August 88285874.45 2355629.15 85930245.30 92732327.84 56540703.23
September 66187337.41 20243.65 66167093.76 51378821.93 80801293.46
October 46530042.25 0.00 46530042.25 21480058.29 0.109059E+09
November 27951420.27 0.00 27951420.27 3883749.94 0.128204E+09
December 21765255.44 0.00 21765255.44 761461.69 0.158622E+09
           
Annual Sum or Average 0.780587E+09 21328349.98 0.759258E+09 0.577086E+09 0.119782E+10
Minimum of Months 21765255.44 0.00 21765255.44 761461.69 56212674.24
Maximum of Months 0.110362E+09 8400708.26 0.104922E+09 0.112564E+09 0.158622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25493031.48 0.00 25493031.48 1106923.22 0.155785E+09
February 36118014.11 0.00 36118014.11 8857117.90 0.122432E+09
March 59131710.80 0.00 59131710.80 29440573.62 0.110654E+09
April 81492066.12 288389.07 81203677.05 60381607.83 85070770.61
May 0.108084E+09 3161443.64 0.104922E+09 92935255.65 75970473.19
June 0.110362E+09 7099182.32 0.103263E+09 0.101565E+09 58509635.30
July 0.109164E+09 8400671.21 0.100764E+09 0.112563E+09 56212771.06
August 88284405.77 2355398.91 85929006.86 92732105.95 56543007.97
September 66186623.18 20099.93 66166523.26 51378821.93 80802718.45
October 46530042.25 0.00 46530042.25 21480058.29 0.109059E+09
November 27951420.27 0.00 27951420.27 3883749.94 0.128204E+09
December 21765255.44 0.00 21765255.44 761461.69 0.158622E+09
           
Annual Sum or Average 0.780563E+09 21325185.07 0.759238E+09 0.577086E+09 0.119787E+10
Minimum of Months 21765255.44 0.00 21765255.44 761461.69 56212771.06
Maximum of Months 0.110362E+09 8400671.21 0.104922E+09 0.112563E+09 0.158622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25493031.48 0.00 25493031.48 1106923.22 0.155785E+09
February 36118014.11 0.00 36118014.11 8857117.90 0.122432E+09
March 59131710.80 0.00 59131710.80 29440573.62 0.110654E+09
April 81492220.85 288407.46 81203813.38 60381836.04 85070739.12
May 0.108084E+09 3161443.64 0.104922E+09 92935255.65 75970473.19
June 0.110362E+09 7099182.32 0.103263E+09 0.101565E+09 58509635.30
July 0.109164E+09 8400671.21 0.100764E+09 0.112563E+09 56212771.06
August 88284078.22 2355409.41 85928668.80 92732835.53 56544165.67
September 66187425.76 19933.68 66167492.07 51378821.93 80801956.38
October 46530042.25 0.00 46530042.25 21480058.29 0.109059E+09
November 27951420.27 0.00 27951420.27 3883749.94 0.128204E+09
December 21765255.44 0.00 21765255.44 761461.69 0.158622E+09
           
Annual Sum or Average 0.780563E+09 21325047.72 0.759238E+09 0.577087E+09 0.119787E+10
Minimum of Months 21765255.44 0.00 21765255.44 761461.69 56212771.06
Maximum of Months 0.110362E+09 8400671.21 0.104922E+09 0.112563E+09 0.158622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25493031.48 0.00 25493031.48 1106923.22 0.155785E+09
February 36118014.11 0.00 36118014.11 8857117.90 0.122432E+09
March 59131710.80 0.00 59131710.80 29440573.62 0.110654E+09
April 81516650.73 291065.87 81225584.86 60399686.84 85047764.22
May 0.108084E+09 3161443.64 0.104922E+09 92935255.65 75970473.19
June 0.110362E+09 7099182.32 0.103263E+09 0.101565E+09 58509635.30
July 0.109164E+09 8400759.42 0.100764E+09 0.112564E+09 56212771.06
August 88285571.37 2355964.54 85929606.83 92736291.71 56544575.29
September 66189205.30 20041.39 66169163.91 51378821.93 80799204.32
October 46530042.25 0.00 46530042.25 21480058.29 0.109059E+09
November 27951420.27 0.00 27951420.27 3883749.94 0.128204E+09
December 21765255.44 0.00 21765255.44 761461.69 0.158622E+09
           
Annual Sum or Average 0.780591E+09 21328457.18 0.759263E+09 0.577108E+09 0.119784E+10
Minimum of Months 21765255.44 0.00 21765255.44 761461.69 56212771.06
Maximum of Months 0.110362E+09 8400759.42 0.104922E+09 0.112564E+09 0.158622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25495335.78 0.00 25495335.78 1107475.30 0.155784E+09
February 36120934.24 0.00 36120934.24 8859165.46 0.122432E+09
March 59136236.19 0.00 59136236.19 29444720.52 0.110654E+09
April 81567152.83 297213.38 81269939.45 60441197.52 85007311.60
May 0.108339E+09 3252690.79 0.105087E+09 93410830.35 75957358.25
June 0.110616E+09 7192591.26 0.103423E+09 0.102044E+09 58508755.65
July 0.109474E+09 8552600.66 0.100922E+09 0.113196E+09 56207348.26
August 88462151.19 2422450.97 86039700.21 93071837.17 56534940.60
September 66193215.54 20040.29 66173175.25 51383202.02 80800370.27
October 46533401.65 0.00 46533401.65 21482962.66 0.109060E+09
November 27953922.55 0.00 27953922.55 3884957.13 0.128204E+09
December 21767100.29 0.00 21767100.29 761719.29 0.158621E+09
           
Annual Sum or Average 0.781659E+09 21737587.35 0.759921E+09 0.579088E+09 0.119777E+10
Minimum of Months 21767100.29 0.00 21767100.29 761719.29 56207348.26
Maximum of Months 0.110616E+09 8552600.66 0.105087E+09 0.113196E+09 0.158621E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44348139.18 13636255.24 30711883.95 21011536.13 0.149341E+09
February 72027062.57 27829525.18 44197537.39 54684172.85 0.118161E+09
March 0.110514E+09 38020195.59 72493924.57 97419709.90 0.111026E+09
April 0.161813E+09 62283665.44 99529219.37 0.168971E+09 89013964.02
May 0.213757E+09 87440219.31 0.126317E+09 0.238129E+09 83028322.18
June 0.198481E+09 76520589.89 0.121960E+09 0.223749E+09 65183276.99
July 0.256161E+09 0.134870E+09 0.121291E+09 0.315274E+09 65186398.96
August 0.213576E+09 0.109568E+09 0.104008E+09 0.267481E+09 64650429.02
September 0.169555E+09 82294799.16 87260512.38 0.195150E+09 85699651.91
October 99835222.26 41526742.05 58308480.21 92798526.09 0.111638E+09
November 47812231.77 14040544.03 33771687.74 27281716.14 0.125747E+09
December 41981638.42 14929467.12 27052171.30 24940231.87 0.154114E+09
           
Annual Sum or Average 0.162986E+10 0.702960E+09 0.926901E+09 0.172689E+10 0.122279E+10
Minimum of Months 41981638.42 13636255.24 27052171.30 21011536.13 64650429.02
Maximum of Months 0.256161E+09 0.134870E+09 0.126317E+09 0.315274E+09 0.154114E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44174056.67 13577970.70 30596085.97 20838279.97 0.149493E+09
February 71895250.92 27772431.73 44122819.19 54455342.68 0.118190E+09
March 0.110465E+09 38000391.21 72464787.88 97328901.94 0.111026E+09
April 0.161807E+09 62283665.44 99523740.16 0.168965E+09 89013592.01
May 0.213750E+09 87440219.31 0.126310E+09 0.238121E+09 83028022.49
June 0.198475E+09 76520589.89 0.121954E+09 0.223742E+09 65182867.19
July 0.256156E+09 0.134870E+09 0.121286E+09 0.315269E+09 65185767.24
August 0.213571E+09 0.109568E+09 0.104003E+09 0.267475E+09 64649487.91
September 0.169537E+09 82288788.99 87248636.15 0.195119E+09 85698746.01
October 99720527.86 41479788.30 58240739.56 92580739.38 0.111638E+09
November 47679025.46 13998032.55 33680992.91 27080498.37 0.125793E+09
December 41817099.95 14871076.61 26946023.33 24722738.19 0.154210E+09
           
Annual Sum or Average 0.162905E+10 0.702671E+09 0.926377E+09 0.172570E+10 0.122311E+10
Minimum of Months 41817099.95 13577970.70 26946023.33 20838279.97 64649487.91
Maximum of Months 0.256156E+09 0.134870E+09 0.126310E+09 0.315269E+09 0.154210E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44174056.67 13577970.70 30596085.97 20838279.97 0.149493E+09
February 71895250.92 27772431.73 44122819.19 54455342.68 0.118190E+09
March 0.110465E+09 38000391.21 72464787.88 97328901.94 0.111026E+09
April 0.161807E+09 62283665.44 99523740.16 0.168965E+09 89013592.01
May 0.213750E+09 87440219.31 0.126310E+09 0.238121E+09 83028022.49
June 0.198475E+09 76520589.89 0.121954E+09 0.223742E+09 65182867.19
July 0.256156E+09 0.134870E+09 0.121286E+09 0.315269E+09 65185767.24
August 0.213571E+09 0.109568E+09 0.104003E+09 0.267475E+09 64649487.91
September 0.169537E+09 82288788.99 87248636.15 0.195119E+09 85698746.01
October 99720527.86 41479788.30 58240739.56 92580739.38 0.111638E+09
November 47679025.46 13998032.55 33680992.91 27080498.37 0.125793E+09
December 41817099.95 14871076.61 26946023.33 24722738.19 0.154210E+09
           
Annual Sum or Average 0.162905E+10 0.702671E+09 0.926377E+09 0.172570E+10 0.122311E+10
Minimum of Months 41817099.95 13577970.70 26946023.33 20838279.97 64649487.91
Maximum of Months 0.256156E+09 0.134870E+09 0.126310E+09 0.315269E+09 0.154210E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44176361.09 13577970.70 30598390.39 20839155.66 0.149493E+09
February 71898171.21 27772431.73 44125739.48 54457604.49 0.118191E+09
March 0.110470E+09 38000391.21 72469313.51 97333265.17 0.111026E+09
April 0.161813E+09 62283665.44 99529219.66 0.168971E+09 89013964.04
May 0.213757E+09 87440219.31 0.126317E+09 0.238129E+09 83028322.19
June 0.198481E+09 76520589.89 0.121960E+09 0.223749E+09 65183277.01
July 0.256161E+09 0.134870E+09 0.121291E+09 0.315274E+09 65186398.99
August 0.213576E+09 0.109568E+09 0.104008E+09 0.267481E+09 64650429.07
September 0.169542E+09 82288788.99 87252855.59 0.195124E+09 85699651.96
October 99723887.43 41479788.30 58244099.13 92583759.67 0.111639E+09
November 47681527.88 13998032.55 33683495.33 27082005.75 0.125793E+09
December 41818944.89 14871076.61 26947868.27 24723196.65 0.154210E+09
           
Annual Sum or Average 0.162910E+10 0.702671E+09 0.926427E+09 0.172575E+10 0.122311E+10
Minimum of Months 41818944.89 13577970.70 26947868.27 20839155.66 64650429.07
Maximum of Months 0.256161E+09 0.134870E+09 0.126317E+09 0.315274E+09 0.154210E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 308.84 395.27 331.54 199.98 131.56 0.00 0.00
February 541.29 358.85 510.56 320.59 189.97 0.00 0.00
March 601.95 320.87 546.83 297.10 249.73 0.00 0.00
April 615.61 269.59 537.96 228.63 309.33 0.00 0.00
May 477.67 233.00 439.62 105.94 333.68 0.00 0.00
June 403.35 187.87 379.76 66.74 313.01 0.00 0.00
July 504.99 177.26 418.81 118.44 300.37 0.00 0.00
August 650.63 179.25 500.31 217.61 282.69 0.00 0.00
September 773.53 251.51 621.37 347.19 274.19 0.00 0.00
October 655.62 316.53 570.99 357.26 213.73 0.00 0.00
November 328.37 355.67 336.23 196.05 140.17 0.00 0.00
December 359.46 415.34 353.75 231.64 122.11 0.00 0.00
               
Annual Sum or Average 518.12 288.08 461.84 223.29 238.55 0.00 0.00
Minimum of Months 308.84 177.26 331.54 66.74 122.11 0.00 0.00
Maximum of Months 773.53 415.34 621.37 357.26 333.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 24.24 220.62 62.45 16.51 45.94 0.00 0.00
February 80.62 190.77 115.11 42.07 73.04 0.00 0.00
March 149.64 160.10 170.83 63.01 107.82 0.00 0.00
April 277.02 129.80 264.47 111.30 153.17 0.00 0.00
May 296.45 116.16 276.23 95.82 180.42 0.00 0.00
June 379.61 94.96 332.74 144.23 188.51 0.00 0.00
July 367.74 85.53 309.88 137.41 172.47 0.00 0.00
August 381.45 86.52 309.58 155.33 154.24 0.00 0.00
September 251.50 123.11 230.22 107.50 122.72 0.00 0.00
October 137.22 160.30 150.37 65.23 85.14 0.00 0.00
November 39.35 191.11 73.03 21.40 51.63 0.00 0.00
December 30.73 227.11 60.46 20.20 40.26 0.00 0.00
               
Annual Sum or Average 201.90 148.65 196.63 81.84 114.80 0.00 0.00
Minimum of Months 24.24 85.53 60.46 16.51 40.26 0.00 0.00
Maximum of Months 381.45 227.11 332.74 155.33 188.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2.48 348.98 57.11 0.00 57.11 0.00 0.00
February 21.97 303.65 89.58 0.00 89.58 0.00 0.00
March 65.95 247.88 132.47 0.00 132.47 0.00 0.00
April 139.80 196.83 188.71 0.68 188.04 0.00 0.00
May 208.44 170.14 242.28 7.13 235.14 0.00 0.00
June 235.49 135.43 255.67 16.51 239.16 0.00 0.00
July 252.55 125.91 244.74 18.91 225.83 0.00 0.00
August 207.93 126.59 197.91 5.33 192.58 0.00 0.00
September 118.94 187.04 153.22 0.05 153.17 0.00 0.00
October 48.12 244.31 104.24 0.00 104.24 0.00 0.00
November 8.99 296.77 64.70 0.00 64.70 0.00 0.00
December 1.71 355.33 48.76 0.00 48.76 0.00 0.00
               
Annual Sum or Average 109.90 227.88 148.57 4.08 144.49 0.00 0.00
Minimum of Months 1.71 125.91 48.76 0.00 48.76 0.00 0.00
Maximum of Months 252.55 355.33 255.67 18.91 239.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 31.18 223.19 66.04 20.30 45.74 0.00 0.00
February 90.13 195.40 118.93 45.94 72.99 0.00 0.00
March 145.39 165.81 164.99 56.76 108.23 0.00 0.00
April 260.75 137.37 249.71 96.12 153.59 0.00 0.00
May 355.62 124.00 319.23 130.59 188.64 0.00 0.00
June 345.29 100.59 306.29 118.09 188.21 0.00 0.00
July 470.84 97.35 382.55 201.42 181.14 0.00 0.00
August 399.46 96.55 318.96 163.63 155.32 0.00 0.00
September 301.12 132.25 261.64 126.99 134.65 0.00 0.00
October 138.35 166.72 148.97 61.96 87.00 0.00 0.00
November 41.86 194.10 73.63 21.62 52.01 0.00 0.00
December 37.00 230.26 62.51 22.23 40.28 0.00 0.00
               
Annual Sum or Average 218.92 155.13 206.65 89.14 117.52 0.00 0.00
Minimum of Months 31.18 96.55 62.51 20.30 40.28 0.00 0.00
Maximum of Months 470.84 230.26 382.55 201.42 188.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.827190E+09 0.105869E+10 0.887987E+09 0.535619E+09 0.352368E+09 0.00 0.00
February 0.130948E+10 0.868136E+09 0.123514E+10 0.775571E+09 0.459570E+09 0.00 0.00
March 0.161226E+10 0.859421E+09 0.146463E+10 0.795763E+09 0.668872E+09 0.00 0.00
April 0.159566E+10 0.698789E+09 0.139439E+10 0.592610E+09 0.801784E+09 0.00 0.00
May 0.127938E+10 0.624065E+09 0.117748E+10 0.283750E+09 0.893725E+09 0.00 0.00
June 0.104550E+10 0.486960E+09 0.984331E+09 0.172998E+09 0.811333E+09 0.00 0.00
July 0.135256E+10 0.474768E+09 0.112174E+10 0.317220E+09 0.804520E+09 0.00 0.00
August 0.174264E+10 0.480116E+09 0.134002E+10 0.582857E+09 0.757164E+09 0.00 0.00
September 0.200499E+10 0.651914E+09 0.161060E+10 0.899904E+09 0.710697E+09 0.00 0.00
October 0.175601E+10 0.847791E+09 0.152935E+10 0.956882E+09 0.572463E+09 0.00 0.00
November 0.851126E+09 0.921888E+09 0.871501E+09 0.508172E+09 0.363329E+09 0.00 0.00
December 0.962782E+09 0.111246E+10 0.947472E+09 0.620413E+09 0.327059E+09 0.00 0.00
               
Annual Sum or Average 0.163396E+11 0.908499E+10 0.145646E+11 0.704176E+10 0.752289E+10 0.00 0.00
Minimum of Months 0.827190E+09 0.474768E+09 0.871501E+09 0.172998E+09 0.327059E+09 0.00 0.00
Maximum of Months 0.200499E+10 0.111246E+10 0.161060E+10 0.956882E+09 0.893725E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 64937335.26 0.590897E+09 0.167265E+09 44211124.96 0.123054E+09 0.00 0.00
February 0.195030E+09 0.461512E+09 0.278484E+09 0.101780E+09 0.176703E+09 0.00 0.00
March 0.400801E+09 0.428824E+09 0.457558E+09 0.168767E+09 0.288791E+09 0.00 0.00
April 0.718044E+09 0.336443E+09 0.685512E+09 0.288499E+09 0.397012E+09 0.00 0.00
May 0.794003E+09 0.311122E+09 0.739860E+09 0.256632E+09 0.483228E+09 0.00 0.00
June 0.983945E+09 0.246127E+09 0.862465E+09 0.373848E+09 0.488617E+09 0.00 0.00
July 0.984953E+09 0.229095E+09 0.829973E+09 0.368036E+09 0.461936E+09 0.00 0.00
August 0.102168E+10 0.231738E+09 0.829166E+09 0.416038E+09 0.413128E+09 0.00 0.00
September 0.651895E+09 0.319101E+09 0.596721E+09 0.278635E+09 0.318086E+09 0.00 0.00
October 0.367536E+09 0.429336E+09 0.402759E+09 0.174724E+09 0.228035E+09 0.00 0.00
November 0.101996E+09 0.495348E+09 0.189301E+09 55480582.17 0.133820E+09 0.00 0.00
December 82305167.74 0.608301E+09 0.161934E+09 54096940.49 0.107837E+09 0.00 0.00
               
Annual Sum or Average 0.636713E+10 0.468784E+10 0.620100E+10 0.258075E+10 0.362025E+10 0.00 0.00
Minimum of Months 64937335.26 0.229095E+09 0.161934E+09 44211124.96 0.107837E+09 0.00 0.00
Maximum of Months 0.102168E+10 0.608301E+09 0.862465E+09 0.416038E+09 0.488617E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 6642643.49 0.934708E+09 0.152963E+09 0.00 0.152963E+09 0.00 0.00
February 53146802.63 0.734593E+09 0.216714E+09 0.00 0.216714E+09 0.00 0.00
March 0.176652E+09 0.663923E+09 0.354799E+09 0.00 0.354799E+09 0.00 0.00
April 0.362370E+09 0.510182E+09 0.489146E+09 1754482.43 0.487392E+09 0.00 0.00
May 0.558280E+09 0.455701E+09 0.648919E+09 19109191.94 0.629809E+09 0.00 0.00
June 0.610378E+09 0.351044E+09 0.662694E+09 42798659.54 0.619895E+09 0.00 0.00
July 0.676431E+09 0.337235E+09 0.655517E+09 50659410.92 0.604857E+09 0.00 0.00
August 0.556920E+09 0.339068E+09 0.530071E+09 14267543.40 0.515803E+09 0.00 0.00
September 0.308282E+09 0.484807E+09 0.397136E+09 120604.04 0.397015E+09 0.00 0.00
October 0.128886E+09 0.654357E+09 0.279187E+09 0.00 0.279187E+09 0.00 0.00
November 23304914.10 0.769223E+09 0.167714E+09 0.00 0.167714E+09 0.00 0.00
December 4569285.36 0.951729E+09 0.130595E+09 0.00 0.130595E+09 0.00 0.00
               
Annual Sum or Average 0.346586E+10 0.718657E+10 0.468545E+10 0.128710E+09 0.455674E+10 0.00 0.00
Minimum of Months 4569285.36 0.337235E+09 0.130595E+09 0.00 0.130595E+09 0.00 0.00
Maximum of Months 0.676431E+09 0.951729E+09 0.662694E+09 50659410.92 0.629809E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 83500166.16 0.597793E+09 0.176873E+09 54370167.33 0.122502E+09 0.00 0.00
February 0.218042E+09 0.472722E+09 0.287716E+09 0.111147E+09 0.176569E+09 0.00 0.00
March 0.389411E+09 0.444102E+09 0.441914E+09 0.152021E+09 0.289893E+09 0.00 0.00
April 0.675873E+09 0.356055E+09 0.647241E+09 0.249135E+09 0.398106E+09 0.00 0.00
May 0.952499E+09 0.332113E+09 0.855015E+09 0.349761E+09 0.505254E+09 0.00 0.00
June 0.894983E+09 0.260732E+09 0.793911E+09 0.306082E+09 0.487829E+09 0.00 0.00
July 0.126109E+10 0.260744E+09 0.102463E+10 0.539480E+09 0.485155E+09 0.00 0.00
August 0.106991E+10 0.258600E+09 0.854294E+09 0.438274E+09 0.416021E+09 0.00 0.00
September 0.780512E+09 0.342797E+09 0.678172E+09 0.329161E+09 0.349011E+09 0.00 0.00
October 0.370544E+09 0.446554E+09 0.399000E+09 0.165966E+09 0.233034E+09 0.00 0.00
November 0.108506E+09 0.503107E+09 0.190852E+09 56034641.69 0.134817E+09 0.00 0.00
December 99096272.20 0.616731E+09 0.167435E+09 59542696.96 0.107892E+09 0.00 0.00
               
Annual Sum or Average 0.690396E+10 0.489205E+10 0.651706E+10 0.281097E+10 0.370608E+10 0.00 0.00
Minimum of Months 83500166.16 0.258600E+09 0.167435E+09 54370167.33 0.107892E+09 0.00 0.00
Maximum of Months 0.126109E+10 0.616731E+09 0.102463E+10 0.539480E+09 0.505254E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.608048E+09 -483092088.6 0.00 0.00 744.00 0.00 -124956214.9 58.99 0.00 0.00
February 0.550892E+09 -440150269.2 0.00 0.00 672.00 0.00 -110742040.3 58.99 0.00 0.00
March 0.644657E+09 -526623451.1 0.00 0.00 744.00 0.00 -118033312.4 58.99 0.00 0.00
April 0.557277E+09 -445443961.8 0.00 0.00 720.00 0.00 -111832751.6 58.99 0.00 0.00
May 0.584675E+09 -472131914.9 0.00 0.00 744.00 0.00 -112542960.9 59.00 0.00 0.00
June 0.560749E+09 -453337575.8 0.00 0.00 720.00 0.00 -107411763.9 58.99 0.00 0.00
July 0.510351E+09 -400668553.5 0.00 0.00 744.00 0.00 -109682539.5 58.99 0.00 0.00
August 0.566702E+09 -457065910.8 0.00 0.00 744.00 0.00 -109636306.5 58.99 0.00 0.00
September 0.510106E+09 -403101995.1 0.00 0.00 720.00 0.00 -107004132.2 58.99 0.00 0.00
October 0.550331E+09 -436661987.2 0.00 0.00 744.00 0.00 -113668588.0 58.99 0.00 0.00
November 0.568822E+09 -454052008.7 0.00 0.00 720.00 0.00 -114770014.2 58.99 0.00 0.00
December 0.571354E+09 -448407312.0 0.00 0.00 744.00 0.00 -122946809.9 58.99 0.00 0.00
                     
Annual Sum or Average 0.678396E+10 -0.542074E+10 0.00 0.00 8760.00 0.00 -0.136323E+10 58.99 0.00 0.00
Minimum of Months 0.510106E+09 -526623451.1 0.00 0.00 672.00 0.00 -124956214.9 58.99 0.00 0.00
Maximum of Months 0.644657E+09 -400668553.5 0.00 0.00 744.00 0.00 -107004132.2 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.82 0.73 03-JAN-09:50 449.67 21.17 68.00 112.00 787.09 28.04 180.33 99.83
February 259.50 0.79 0.73 01-FEB-08:50 1073.04 25.08 122.67 176.67 1209.28 30.43 234.50 160.50
March 247.00 0.78 0.73 01-MAR-07:40 1760.64 25.58 117.83 216.00 717.49 23.16 207.67 155.83
April 379.50 0.80 0.73 01-APR-08:30 587.56 17.72 0.00 249.00 452.05 22.04 253.50 202.00
May 427.83 0.80 0.73 01-MAY-09:20 516.34 17.55 1.00 260.67 386.62 21.82 272.17 197.50
June 375.17 0.80 0.73 01-JUN-09:39 458.84 17.17 0.00 262.67 344.17 21.44 279.67 171.67
July 471.00 0.83 0.73 01-JUL-11:50 407.88 15.92 0.00 234.33 310.39 20.16 207.83 184.00
August 366.67 0.80 0.73 01-AUG-07:00 511.04 17.03 0.17 255.00 398.29 21.34 242.83 194.67
September 301.17 0.78 0.73 01-SEP-11:50 823.99 19.06 11.83 229.67 568.58 22.88 238.67 190.67
October 245.33 0.77 0.73 01-OCT-11:39 1628.21 25.10 106.67 207.83 769.97 23.35 191.83 171.33
November 242.67 0.82 0.73 01-NOV-12:09 624.59 23.41 99.00 122.33 903.15 28.84 193.67 106.00
December 160.33 0.80 0.73 01-DEC-09:00 607.94 20.54 35.83 95.67 1182.03 32.71 144.17 105.17
                         
Annual Sum or Average 3714.00 0.80     730.33 19.70 563.00 2421.83 593.80 23.75 2646.83 1939.17
Minimum of Months 160.33 0.77 0.73   407.88 15.92 0.00 95.67 310.39 20.16 144.17 99.83
Maximum of Months 471.00 0.83 0.73   1760.64 25.58 122.67 262.67 1209.28 32.71 279.67 202.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.89 0.73 03-JAN-10:30 352.92 18.93 65.33 45.33 189.95 20.66 65.33 17.67
February 259.50 0.86 0.73 01-FEB-09:09 572.79 17.91 45.33 89.67 378.43 22.97 117.67 50.17
March 247.00 0.83 0.73 01-MAR-07:49 996.00 18.73 39.17 121.00 362.73 20.90 118.83 79.00
April 379.50 0.83 0.73 01-APR-07:10 434.44 16.01 0.00 178.50 342.47 20.60 167.00 124.33
May 427.83 0.82 0.73 01-MAY-09:09 428.95 16.16 0.00 205.50 338.84 20.84 206.17 143.33
June 375.17 0.82 0.73 01-JUN-05:49 447.46 15.81 0.00 191.50 397.07 22.04 212.67 141.33
July 471.00 0.85 0.73 01-JUL-12:20 366.56 14.56 0.00 174.83 312.17 20.99 184.00 125.33
August 366.67 0.83 0.73 01-AUG-06:10 414.87 15.17 0.00 173.33 350.60 20.24 143.50 121.67
September 301.17 0.83 0.73 02-SEP-06:49 471.49 16.55 7.00 131.00 353.92 21.21 131.17 82.33
October 245.33 0.84 0.73 01-OCT-08:20 1327.59 20.00 62.83 106.00 487.06 22.48 112.33 71.00
November 242.67 0.88 0.73 02-NOV-07:00 503.85 19.12 70.17 50.17 188.72 20.51 61.50 23.00
December 160.33 0.87 0.73 01-DEC-10:30 512.07 21.22 56.83 44.50 171.71 18.99 30.67 13.00
                         
Annual Sum or Average 3714.00 0.84     536.26 16.98 346.67 1511.33 331.68 21.08 1550.83 992.17
Minimum of Months 160.33 0.82 0.73   352.92 14.56 0.00 44.50 171.71 18.99 30.67 13.00
Maximum of Months 471.00 0.89 0.73   1327.59 21.22 70.17 205.50 487.06 22.97 212.67 143.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.96 0.91 06-JAN-11:20 122.23 12.23 0.00 0.00 85.00 15.99 0.00 0.00
February 259.50 0.94 0.83 14-FEB-13:50 155.77 13.47 0.00 0.00 109.95 17.36 0.00 0.00
March 247.00 0.90 0.74 15-MAR-14:20 213.59 15.04 0.00 5.67 152.49 19.00 10.33 0.00
April 379.50 0.87 0.74 10-APR-15:30 251.29 15.88 0.00 15.17 175.50 19.70 44.33 0.00
May 427.83 0.83 0.73 13-MAY-05:30 326.39 16.82 1.33 134.00 217.72 21.27 184.33 5.17
June 375.17 0.82 0.73 04-JUN-08:20 332.52 18.25 25.17 128.33 246.74 22.35 209.00 14.83
July 471.00 0.86 0.74 01-JUL-12:30 276.13 17.20 33.83 117.50 186.37 19.42 141.50 0.00
August 366.67 0.87 0.74 01-AUG-07:49 264.56 15.79 0.00 35.83 173.15 19.64 42.33 0.00
September 301.17 0.88 0.74 02-SEP-13:30 236.16 15.84 0.00 6.33 169.23 19.80 16.50 0.00
October 245.33 0.92 0.74 02-OCT-09:30 172.94 13.94 0.00 0.17 126.28 17.95 0.83 0.00
November 242.67 0.95 0.91 01-NOV-11:50 131.52 12.61 0.00 0.00 91.11 16.31 0.00 0.00
December 160.33 0.96 0.91 01-DEC-10:20 115.88 12.05 0.00 0.00 85.01 16.18 0.00 0.00
                         
Annual Sum or Average 3714.00 0.88     235.09 15.42 60.33 443.00 163.62 19.18 649.17 20.00
Minimum of Months 160.33 0.82 0.73   115.88 12.05 0.00 0.00 85.00 15.99 0.00 0.00
Maximum of Months 471.00 0.96 0.91   332.52 18.25 33.83 134.00 246.74 22.35 209.00 14.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.89 0.73 05-JAN-14:39 339.56 19.12 58.50 43.50 174.81 20.66 56.83 16.50
February 259.50 0.86 0.73 01-FEB-13:30 583.77 18.28 45.17 82.83 350.94 22.92 112.83 50.67
March 247.00 0.83 0.73 01-MAR-13:20 898.77 18.96 39.33 114.83 573.46 23.11 121.50 84.00
April 379.50 0.83 0.73 01-APR-13:09 427.59 16.23 0.00 176.00 331.96 20.68 177.83 119.17
May 427.83 0.82 0.73 01-MAY-11:00 462.04 16.44 0.33 219.00 372.71 21.01 224.00 152.50
June 375.17 0.82 0.73 01-JUN-13:30 434.43 16.07 0.00 194.67 399.15 20.85 202.33 140.00
July 471.00 0.84 0.73 01-JUL-12:20 414.93 14.75 0.00 202.83 352.12 19.53 170.83 161.00
August 366.67 0.83 0.73 02-AUG-11:30 434.73 15.43 0.00 181.00 367.85 20.34 158.83 132.83
September 301.17 0.82 0.73 01-SEP-12:20 665.18 17.26 8.67 155.33 458.70 21.78 160.83 117.83
October 245.33 0.84 0.73 01-OCT-12:20 1243.31 20.56 66.83 113.00 462.46 23.18 128.83 75.33
November 242.67 0.88 0.73 02-NOV-13:09 480.84 19.17 67.50 52.17 181.24 20.00 56.50 19.17
December 160.33 0.88 0.73 01-DEC-13:20 539.36 20.14 47.50 41.17 169.00 18.83 34.67 13.17
                         
Annual Sum or Average 3714.00 0.84     549.41 17.21 333.83 1576.33 358.88 21.00 1605.83 1082.17
Minimum of Months 160.33 0.82 0.73   339.56 14.75 0.00 41.17 169.00 18.83 34.67 13.17
Maximum of Months 471.00 0.89 0.73   1243.31 20.56 67.50 219.00 573.46 23.18 224.00 161.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.533209E+09 5319.13 11-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.210100E+09 5162.69 22-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 14268245.52 5016.30 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 41221528.33 5840.58 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.229013E+09 5453.36 28-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102781E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.533209E+09 5840.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152248E+10 7512.22 11-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.816999E+09 8446.87 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.355746E+09 7576.41 08-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.176977E+09 7265.74 10-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 23294992.11 2101.57 11-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 305782.43 326.33 28-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 31204056.27 3453.68 23-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.430041E+09 7925.08 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.101098E+10 7512.22 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.436802E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152248E+10 8446.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.996282E+09 4374.10 11-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.595152E+09 4918.31 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.220230E+09 4411.47 08-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 67062040.58 4230.58 10-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 1267893.29 2109.58 30-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 11572765.63 4026.13 30-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.249987E+09 4614.49 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.649766E+09 4374.10 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.279132E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.996282E+09 4918.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.167107E+10 4605.08 11-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.113110E+10 5178.03 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.527956E+09 4714.30 09-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.187831E+09 4702.62 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 2612648.26 2514.98 30-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 34183509.60 4702.62 23-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.486966E+09 4858.17 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.114682E+10 4605.08 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.518854E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.167107E+10 5178.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.912258E+09 5197.19 11-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.553073E+09 5843.81 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.202550E+09 5241.60 08-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 64580742.90 5026.67 10-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 7968350.84 4783.75 30-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.210125E+09 5482.82 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.570132E+09 5197.19 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.252069E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.912258E+09 5843.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8072314.63 3406.87 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 6320473.99 3406.87 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 320855.08 2670.32 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 9340222.63 3406.87 12-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 24053866.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 9340222.63 3406.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 37427919.28 4501.02 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 21016053.68 4501.02 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 2776736.34 4498.86 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 1575126.06 4473.46 19-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2588014.47 4501.02 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 32854835.41 4501.02 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 98238685.24     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 37427919.28 4501.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 19847641.90 2788.28 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 14243374.47 2788.28 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 3251360.66 2788.28 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 1418692.15 2788.28 19-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2068466.37 2788.28 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 17683606.61 2788.28 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 58513142.17     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 19847641.90 2788.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 84614235.85 4478.66 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 67152170.06 4428.55 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 7094063.53 3680.76 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 2386479.57 2875.48 19-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 7345991.98 3219.12 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 65246603.89 4478.66 26-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.233840E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 84614235.85 4478.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 12243427.80 2779.65 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 8688984.84 2779.65 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 2553848.56 2779.65 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 1236663.94 2779.65 12-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1604619.44 2779.65 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 11957980.97 2779.65 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 38285525.55     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 12243427.80 2779.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 2494964.89 1872067.43 403.36 28-FEB-16:55 304.47 0.00
March 0.00 0.00 60272213.77 50258654.47 1155.46 10-MAR-14:15 872.27 0.00
April 0.00 0.00 0.435090E+09 0.375002E+09 5507.59 28-APR-05:03 4492.10 0.00
May 0.00 0.00 0.134323E+10 0.112814E+10 5577.88 08-MAY-05:03 4239.91 0.00
June 0.00 0.00 0.201090E+10 0.171253E+10 5601.88 13-JUN-05:03 4175.81 0.00
July 0.00 0.00 0.253484E+10 0.212103E+10 5622.68 28-JUL-05:02 4407.87 0.00
August 0.00 0.00 0.325346E+10 0.267490E+10 5615.62 10-AUG-05:02 4540.76 0.00
September 0.00 0.00 0.199090E+10 0.161224E+10 5601.96 26-SEP-05:03 4145.24 0.00
October 0.00 0.00 0.813838E+09 0.694514E+09 5459.88 06-OCT-05:03 4698.92 0.00
November 0.00 0.00 0.189199E+09 0.144202E+09 1424.28 03-NOV-16:00 996.77 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.126342E+11 0.105147E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.325346E+10 0.267490E+10 5622.68   4698.92 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 32444825.24 31995067.96 1598.25 27-FEB-15:00 1598.25 0.00
March 0.00 0.00 0.118088E+09 0.117374E+09 1801.87 02-MAR-14:25 1801.87 0.00
April 0.00 0.00 0.348662E+09 0.335505E+09 4213.17 27-APR-14:30 3973.83 0.00
May 0.00 0.00 0.625393E+09 0.582954E+09 3214.54 04-MAY-14:00 3014.40 0.00
June 0.00 0.00 0.104272E+10 0.969221E+09 3427.81 28-JUN-14:10 3254.80 0.00
July 0.00 0.00 0.176341E+10 0.158330E+10 7387.92 31-JUL-05:02 6719.23 0.00
August 0.00 0.00 0.271164E+10 0.239843E+10 7452.43 25-AUG-05:02 6440.98 0.00
September 0.00 0.00 0.174262E+10 0.156470E+10 7382.32 15-SEP-05:02 6651.28 0.00
October 0.00 0.00 0.708023E+09 0.692108E+09 5016.91 04-OCT-14:00 5016.91 0.00
November 0.00 0.00 44224469.48 40979439.84 1311.13 02-NOV-13:30 1179.54 0.00
December 0.00 0.00 9000340.82 9000340.82 1043.61 05-DEC-13:10 1043.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.914622E+10 0.832556E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.271164E+10 0.239843E+10 7452.43   6719.23 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.134720E+09 0.130065E+09 1670.46 27-APR-15:20 1571.31 0.00
May 0.00 0.00 0.380721E+09 0.360167E+09 1702.62 15-MAY-10:20 1667.91 0.00
June 0.00 0.00 0.827045E+09 0.781282E+09 2210.99 28-JUN-09:00 2072.30 0.00
July 0.00 0.00 0.114655E+10 0.105318E+10 4295.18 31-JUL-05:02 3853.76 0.00
August 0.00 0.00 0.157247E+10 0.141518E+10 4332.32 25-AUG-05:02 3692.43 0.00
September 0.00 0.00 0.763726E+09 0.686196E+09 4106.88 12-SEP-05:02 3743.64 0.00
October 0.00 0.00 0.173575E+09 0.170319E+09 1310.01 04-OCT-10:02 1310.01 0.00
November 0.00 0.00 756706.07 661580.74 145.08 02-NOV-14:20 131.17 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.499956E+10 0.459705E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.157247E+10 0.141518E+10 4332.32   3853.76 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 65797085.27 59745217.64 1885.47 27-APR-15:53 1729.15 0.00
May 0.00 0.00 0.331201E+09 0.297324E+09 2206.21 05-MAY-16:00 1907.61 0.00
June 0.00 0.00 0.838926E+09 0.761283E+09 2610.32 28-JUN-16:00 2469.81 0.00
July 0.00 0.00 0.134701E+10 0.118516E+10 4504.77 25-JUL-05:02 3962.07 0.00
August 0.00 0.00 0.180164E+10 0.155110E+10 4555.25 25-AUG-05:02 3822.16 0.00
September 0.00 0.00 0.776050E+09 0.656360E+09 3417.34 14-SEP-05:02 2936.58 0.00
October 0.00 0.00 0.109094E+09 0.104779E+09 1362.71 04-OCT-15:27 1362.71 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.526972E+10 0.461576E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.180164E+10 0.155110E+10 4555.25   3962.07 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 924954.44 913758.06 315.12 27-FEB-15:30 315.12 0.00
March 0.00 0.00 9139158.79 9124124.85 564.48 02-MAR-16:35 564.48 0.00
April 0.00 0.00 0.140242E+09 0.132406E+09 2374.61 27-APR-15:53 2214.43 0.00
May 0.00 0.00 0.458244E+09 0.424590E+09 2447.11 15-MAY-15:57 2447.11 0.00
June 0.00 0.00 0.807601E+09 0.749384E+09 3712.06 23-JUN-05:02 3563.67 0.00
July 0.00 0.00 0.124241E+10 0.112412E+10 5123.07 31-JUL-05:02 4701.35 0.00
August 0.00 0.00 0.158345E+10 0.140338E+10 5162.03 25-AUG-05:02 4504.18 0.00
September 0.00 0.00 0.852254E+09 0.754169E+09 5074.74 14-SEP-05:02 4618.59 0.00
October 0.00 0.00 0.212295E+09 0.205317E+09 2209.16 04-OCT-15:57 2209.16 0.00
November 0.00 0.00 4843818.58 4100938.66 276.98 02-NOV-14:40 237.44 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.531140E+10 0.480750E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.158345E+10 0.140338E+10 5162.03   4701.35 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 268.44 639.75 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 114.37 640.76 10-FEB-12:13
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     31.57    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   268.44 640.76  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.342758E+09 0.34 348.76 02-JAN-06:01 0.93
February 0.310115E+09 0.34 348.76 01-FEB-06:01 0.92
March 0.375402E+09 0.37 348.76 01-MAR-06:02 0.92
April 0.326436E+09 0.33 348.76 03-APR-05:03 0.92
May 0.359080E+09 0.36 348.76 01-MAY-05:10 0.92
June 0.359080E+09 0.37 348.76 01-JUN-05:10 0.92
July 0.326436E+09 0.32 348.76 03-JUL-05:03 0.92
August 0.375402E+09 0.37 348.76 01-AUG-05:02 0.92
September 0.326436E+09 0.33 348.76 01-SEP-05:02 0.92
October 0.342758E+09 0.34 348.76 02-OCT-05:10 0.92
November 0.342758E+09 0.35 348.76 01-NOV-05:03 0.92
December 0.326436E+09 0.32 348.76 01-DEC-06:01 0.93
           
Annual Sum or Average 0.411310E+10 0.35      
Minimum of Months 0.310115E+09 0.32 348.76   0.92
Maximum of Months 0.375402E+09 0.37 348.76   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.480285E+09 0.37 482.63 02-JAN-06:01 0.93
February 0.429151E+09 0.34 482.63 01-FEB-06:01 0.93
March 0.519499E+09 0.37 482.63 01-MAR-06:02 0.93
April 0.451738E+09 0.34 482.63 03-APR-05:03 0.93
May 0.496912E+09 0.36 482.63 01-MAY-05:10 0.93
June 0.496912E+09 0.37 482.63 01-JUN-05:10 0.93
July 0.451738E+09 0.32 482.63 03-JUL-05:03 0.93
August 0.519499E+09 0.37 482.63 01-AUG-05:02 0.92
September 0.451738E+09 0.33 482.63 01-SEP-05:02 0.92
October 0.474325E+09 0.34 482.63 02-OCT-05:10 0.93
November 0.474325E+09 0.35 482.63 01-NOV-05:03 0.93
December 0.451951E+09 0.33 482.63 01-DEC-06:01 0.93
           
Annual Sum or Average 0.569808E+10 0.35      
Minimum of Months 0.429151E+09 0.32 482.63   0.92
Maximum of Months 0.519499E+09 0.37 482.63   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.283567E+09 0.39 281.02 02-JAN-06:01 0.93
February 0.253000E+09 0.36 281.02 01-FEB-06:01 0.93
March 0.302486E+09 0.37 281.02 01-MAR-06:02 0.93
April 0.263031E+09 0.34 281.02 03-APR-05:03 0.93
May 0.289334E+09 0.36 281.02 01-MAY-05:10 0.93
June 0.289334E+09 0.37 281.02 01-JUN-05:10 0.93
July 0.263031E+09 0.32 281.02 03-JUL-05:03 0.93
August 0.302486E+09 0.37 281.02 01-AUG-05:02 0.92
September 0.263031E+09 0.33 281.02 01-SEP-05:02 0.92
October 0.276183E+09 0.34 281.02 02-OCT-05:10 0.93
November 0.276183E+09 0.35 281.02 01-NOV-05:03 0.93
December 0.264240E+09 0.33 281.02 01-DEC-06:01 0.93
           
Annual Sum or Average 0.332591E+10 0.35      
Minimum of Months 0.253000E+09 0.32 281.02   0.92
Maximum of Months 0.302486E+09 0.39 281.02   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.299498E+09 0.39 293.23 02-JAN-06:01 0.93
February 0.267520E+09 0.37 293.23 01-FEB-06:01 0.93
March 0.315638E+09 0.37 293.23 01-MAR-06:02 0.93
April 0.274468E+09 0.34 293.23 03-APR-05:03 0.93
May 0.301914E+09 0.36 293.23 01-MAY-05:10 0.93
June 0.301914E+09 0.37 293.23 01-JUN-05:10 0.93
July 0.274468E+09 0.32 293.23 03-JUL-05:03 0.93
August 0.315638E+09 0.37 293.23 01-AUG-05:02 0.92
September 0.274468E+09 0.33 293.23 01-SEP-05:02 0.92
October 0.288191E+09 0.34 293.23 02-OCT-05:10 0.93
November 0.288191E+09 0.35 293.23 01-NOV-05:03 0.93
December 0.276050E+09 0.33 293.23 01-DEC-06:01 0.93
           
Annual Sum or Average 0.347796E+10 0.35      
Minimum of Months 0.267520E+09 0.32 293.23   0.92
Maximum of Months 0.315638E+09 0.39 293.23   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.335419E+09 0.39 333.90 02-JAN-06:01 0.93
February 0.300557E+09 0.37 333.90 01-FEB-06:01 0.93
March 0.359406E+09 0.37 333.90 01-MAR-06:02 0.93
April 0.312527E+09 0.34 333.90 03-APR-05:03 0.93
May 0.343780E+09 0.36 333.90 01-MAY-05:10 0.93
June 0.343780E+09 0.37 333.90 01-JUN-05:10 0.93
July 0.312527E+09 0.32 333.90 03-JUL-05:03 0.93
August 0.359406E+09 0.37 333.90 01-AUG-05:02 0.92
September 0.312527E+09 0.33 333.90 01-SEP-05:02 0.92
October 0.328153E+09 0.34 333.90 02-OCT-05:10 0.93
November 0.328153E+09 0.35 333.90 01-NOV-05:03 0.93
December 0.313784E+09 0.33 333.90 01-DEC-06:01 0.93
           
Annual Sum or Average 0.395002E+10 0.35      
Minimum of Months 0.300557E+09 0.32 333.90   0.92
Maximum of Months 0.359406E+09 0.39 333.90   0.93



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:10 0.00 0.00 31.44 0.00
February 0.01 0.00 0.00 01-FEB-07:10 0.00 0.00 11.16 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 11.10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 11.10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 11.10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 11.10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 11.10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 11.10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 11.10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 11.10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 11.10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 11.10 0.00
                 
Annual Sum or Average 0.03 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 11.10 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 31.44 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.89 48.89 268.44 639.75 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 11.16 11.16 114.37 640.76 10-FEB-12:13
March 0.00 0.00 01-MAR-00:10 11.10 11.10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 11.10 11.10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 11.10 11.10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 11.10 11.10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 11.10 11.10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 11.10 11.10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 11.10 11.10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 11.10 11.10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 11.10 11.10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 11.10 11.10 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         31.57    
Minimum of Months 0.00 0.00   11.10 11.10 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 268.44 640.76  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.552073E+09 0.00 0.00
February 0.00 0.00 0.00 0.409569E+09 0.00 0.00
March 0.00 0.00 0.00 0.398046E+09 0.00 0.00
April 0.00 0.00 0.00 0.424746E+09 0.00 0.00
May 0.00 0.00 0.00 0.652542E+09 0.00 0.00
June 0.00 0.00 0.00 0.791217E+09 0.00 0.00
July 0.00 0.00 0.00 0.864683E+09 0.00 0.00
August 0.00 0.00 0.00 0.106934E+10 0.00 0.00
September 0.00 0.00 0.00 0.750441E+09 0.00 0.00
October 0.00 0.00 0.00 0.521956E+09 0.00 0.00
November 0.00 0.00 0.00 0.405165E+09 0.00 0.00
December 0.00 0.00 0.00 0.434608E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.727438E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.398046E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.106934E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.105396E+10 0.00 0.00
February 0.00 0.00 0.00 0.768321E+09 0.00 0.00
March 0.00 0.00 0.00 0.674719E+09 0.00 0.00
April 0.00 0.00 0.00 0.592931E+09 0.00 0.00
May 0.00 0.00 0.00 0.644819E+09 0.00 0.00
June 0.00 0.00 0.00 0.729676E+09 0.00 0.00
July 0.00 0.00 0.00 0.842775E+09 0.00 0.00
August 0.00 0.00 0.00 0.112165E+10 0.00 0.00
September 0.00 0.00 0.00 0.825780E+09 0.00 0.00
October 0.00 0.00 0.00 0.638945E+09 0.00 0.00
November 0.00 0.00 0.00 0.644079E+09 0.00 0.00
December 0.00 0.00 0.00 0.852498E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.939015E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.592931E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.112165E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.668049E+09 0.00 0.00
February 0.00 0.00 0.00 0.500607E+09 0.00 0.00
March 0.00 0.00 0.00 0.383763E+09 0.00 0.00
April 0.00 0.00 0.00 0.318601E+09 0.00 0.00
May 0.00 0.00 0.00 0.375176E+09 0.00 0.00
June 0.00 0.00 0.00 0.472515E+09 0.00 0.00
July 0.00 0.00 0.00 0.516088E+09 0.00 0.00
August 0.00 0.00 0.00 0.651817E+09 0.00 0.00
September 0.00 0.00 0.00 0.430605E+09 0.00 0.00
October 0.00 0.00 0.00 0.318954E+09 0.00 0.00
November 0.00 0.00 0.00 0.371239E+09 0.00 0.00
December 0.00 0.00 0.00 0.526095E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.553351E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.318601E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.668049E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.913686E+09 0.00 0.00
February 0.00 0.00 0.00 0.705930E+09 0.00 0.00
March 0.00 0.00 0.00 0.500737E+09 0.00 0.00
April 0.00 0.00 0.00 0.355288E+09 0.00 0.00
May 0.00 0.00 0.00 0.376931E+09 0.00 0.00
June 0.00 0.00 0.00 0.487190E+09 0.00 0.00
July 0.00 0.00 0.00 0.569263E+09 0.00 0.00
August 0.00 0.00 0.00 0.713236E+09 0.00 0.00
September 0.00 0.00 0.00 0.444740E+09 0.00 0.00
October 0.00 0.00 0.00 0.324131E+09 0.00 0.00
November 0.00 0.00 0.00 0.464195E+09 0.00 0.00
December 0.00 0.00 0.00 0.709962E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.656529E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.324131E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.913686E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.695966E+09 0.00 0.00
February 0.00 0.00 0.00 0.537850E+09 0.00 0.00
March 0.00 0.00 0.00 0.437308E+09 0.00 0.00
April 0.00 0.00 0.00 0.368868E+09 0.00 0.00
May 0.00 0.00 0.00 0.446633E+09 0.00 0.00
June 0.00 0.00 0.00 0.524176E+09 0.00 0.00
July 0.00 0.00 0.00 0.588941E+09 0.00 0.00
August 0.00 0.00 0.00 0.716291E+09 0.00 0.00
September 0.00 0.00 0.00 0.500944E+09 0.00 0.00
October 0.00 0.00 0.00 0.378355E+09 0.00 0.00
November 0.00 0.00 0.00 0.410772E+09 0.00 0.00
December 0.00 0.00 0.00 0.551283E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.615739E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.368868E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.716291E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.342758E+09 0.00 0.541282E+09 0.00 0.00 0.00 0.00 0.00
February 0.310115E+09 2494964.89 0.216420E+09 0.00 0.00 0.00 0.00 0.00
March 0.375402E+09 60272213.77 14268245.52 0.00 0.00 0.00 0.00 0.00
April 0.326436E+09 0.435090E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.359080E+09 0.134323E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.359080E+09 0.201090E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.326436E+09 0.253484E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.375402E+09 0.325346E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.326436E+09 0.199090E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.342758E+09 0.813838E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.342758E+09 0.189199E+09 41542383.42 0.00 0.00 0.00 0.00 0.00
December 0.326436E+09 0.00 0.238353E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.411310E+10 0.126342E+11 0.105187E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.310115E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.375402E+09 0.325346E+10 0.541282E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.480285E+09 0.00 0.155990E+10 0.00 0.00 0.00 0.00 0.00
February 0.429151E+09 32444825.24 0.838015E+09 0.00 0.00 0.00 0.00 0.00
March 0.519499E+09 0.118088E+09 0.358523E+09 0.00 0.00 0.00 0.00 0.00
April 0.451738E+09 0.348662E+09 0.178552E+09 0.00 0.00 0.00 0.00 0.00
May 0.496912E+09 0.625393E+09 23294992.11 0.00 0.00 0.00 0.00 0.00
June 0.496912E+09 0.104272E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.451738E+09 0.176341E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.519499E+09 0.271164E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.451738E+09 0.174262E+10 305782.43 0.00 0.00 0.00 0.00 0.00
October 0.474325E+09 0.708023E+09 31204056.27 0.00 0.00 0.00 0.00 0.00
November 0.474325E+09 44224469.48 0.432629E+09 0.00 0.00 0.00 0.00 0.00
December 0.451951E+09 9000340.82 0.104384E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.569808E+10 0.914622E+10 0.446626E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.429151E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.519499E+09 0.271164E+10 0.155990E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.283567E+09 0.00 0.101613E+10 0.00 0.00 0.00 0.00 0.00
February 0.253000E+09 0.00 0.609395E+09 0.00 0.00 0.00 0.00 0.00
March 0.302486E+09 0.00 0.223481E+09 0.00 0.00 0.00 0.00 0.00
April 0.263031E+09 0.134720E+09 68480732.74 0.00 0.00 0.00 0.00 0.00
May 0.289334E+09 0.380721E+09 1267893.29 0.00 0.00 0.00 0.00 0.00
June 0.289334E+09 0.827045E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.263031E+09 0.114655E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.302486E+09 0.157247E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.263031E+09 0.763726E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.276183E+09 0.173575E+09 11572765.63 0.00 0.00 0.00 0.00 0.00
November 0.276183E+09 756706.07 0.252056E+09 0.00 0.00 0.00 0.00 0.00
December 0.264240E+09 0.00 0.667449E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.332591E+10 0.499956E+10 0.284983E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.253000E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.302486E+09 0.157247E+10 0.101613E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.299498E+09 0.00 0.175569E+10 0.00 0.00 0.00 0.00 0.00
February 0.267520E+09 0.00 0.119825E+10 0.00 0.00 0.00 0.00 0.00
March 0.315638E+09 0.00 0.535050E+09 0.00 0.00 0.00 0.00 0.00
April 0.274468E+09 65797085.27 0.190217E+09 0.00 0.00 0.00 0.00 0.00
May 0.301914E+09 0.331201E+09 2612648.26 0.00 0.00 0.00 0.00 0.00
June 0.301914E+09 0.838926E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.274468E+09 0.134701E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.315638E+09 0.180164E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.274468E+09 0.776050E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288191E+09 0.109094E+09 34183509.60 0.00 0.00 0.00 0.00 0.00
November 0.288191E+09 0.00 0.494312E+09 0.00 0.00 0.00 0.00 0.00
December 0.276050E+09 0.00 0.121207E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.347796E+10 0.526972E+10 0.542238E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.267520E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.315638E+09 0.180164E+10 0.175569E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.335419E+09 0.00 0.924502E+09 0.00 0.00 0.00 0.00 0.00
February 0.300557E+09 924954.44 0.561762E+09 0.00 0.00 0.00 0.00 0.00
March 0.359406E+09 9139158.79 0.205104E+09 0.00 0.00 0.00 0.00 0.00
April 0.312527E+09 0.140242E+09 65817406.84 0.00 0.00 0.00 0.00 0.00
May 0.343780E+09 0.458244E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.343780E+09 0.807601E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.312527E+09 0.124241E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.359406E+09 0.158345E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.312527E+09 0.852254E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.328153E+09 0.212295E+09 7968350.84 0.00 0.00 0.00 0.00 0.00
November 0.328153E+09 4843818.58 0.211729E+09 0.00 0.00 0.00 0.00 0.00
December 0.313784E+09 0.00 0.582090E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.395002E+10 0.531140E+10 0.255897E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.300557E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.359406E+09 0.158345E+10 0.924502E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.342758E+09 0.00 0.00 0.209315E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.310115E+09 0.00 0.00 98884001.34 570235.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.375402E+09 0.00 0.00 9016033.95 13628479.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.326436E+09 0.00 0.00 1530000.00 96779748.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.359080E+09 0.00 0.00 0.00 0.293462E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.359080E+09 0.00 0.00 0.00 0.432137E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.326436E+09 0.00 0.00 0.00 0.538247E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.375402E+09 0.00 0.00 0.00 0.693934E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.326436E+09 0.00 0.00 0.00 0.424004E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.342758E+09 0.00 0.00 0.00 0.179198E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.342758E+09 0.00 0.00 19996465.93 42410391.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.326436E+09 0.00 0.00 0.108172E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.411310E+10 0.00 0.00 0.446913E+09 0.271437E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.310115E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.375402E+09 0.00 0.00 0.209315E+09 0.693934E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.480285E+09 0.00 0.00 0.573672E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.429151E+09 0.00 0.00 0.331847E+09 7323006.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.519499E+09 0.00 0.00 0.128725E+09 26494656.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.451738E+09 0.00 0.00 62771013.62 78421497.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.496912E+09 0.00 0.00 7986452.53 0.139920E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.496912E+09 0.00 0.00 0.00 0.232764E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.451738E+09 0.00 0.00 0.00 0.391037E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.519499E+09 0.00 0.00 0.00 0.602151E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.451738E+09 0.00 0.00 105922.81 0.373936E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.474325E+09 0.00 0.00 10664431.68 0.153955E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.474325E+09 0.00 0.00 0.159710E+09 10044426.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.451951E+09 0.00 0.00 0.398508E+09 2038919.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.569808E+10 0.00 0.00 0.167399E+10 0.201809E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.429151E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.519499E+09 0.00 0.00 0.573672E+09 0.602151E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.283567E+09 0.00 0.00 0.384482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.253000E+09 0.00 0.00 0.247607E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.302486E+09 0.00 0.00 81276984.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.263031E+09 0.00 0.00 24871895.52 30697753.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.289334E+09 0.00 0.00 416693.36 85425596.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.289334E+09 0.00 0.00 0.00 0.183181E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.263031E+09 0.00 0.00 0.00 0.253057E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.302486E+09 0.00 0.00 0.00 0.349331E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.263031E+09 0.00 0.00 0.00 0.167573E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.276183E+09 0.00 0.00 3919011.03 38852566.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.276183E+09 0.00 0.00 94881900.24 174111.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.264240E+09 0.00 0.00 0.261854E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.332591E+10 0.00 0.00 0.109931E+10 0.110829E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.253000E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.302486E+09 0.00 0.00 0.384482E+09 0.349331E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.299498E+09 0.00 0.00 0.614187E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.267520E+09 0.00 0.00 0.438411E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.315638E+09 0.00 0.00 0.185100E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.274468E+09 0.00 0.00 65649309.70 15171569.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.301914E+09 0.00 0.00 876568.58 74140196.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.301914E+09 0.00 0.00 0.00 0.185276E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.274468E+09 0.00 0.00 0.00 0.294796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.315638E+09 0.00 0.00 0.00 0.397598E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.274468E+09 0.00 0.00 0.00 0.170273E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288191E+09 0.00 0.00 11539317.31 24400537.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.288191E+09 0.00 0.00 0.176004E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.276050E+09 0.00 0.00 0.433912E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.347796E+10 0.00 0.00 0.192568E+10 0.116165E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.267520E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.315638E+09 0.00 0.00 0.614187E+09 0.397598E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.335419E+09 0.00 0.00 0.360547E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.300557E+09 0.00 0.00 0.237081E+09 212409.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.359406E+09 0.00 0.00 75818731.51 2083324.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.312527E+09 0.00 0.00 24290271.32 32051332.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.343780E+09 0.00 0.00 0.00 0.102853E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.343780E+09 0.00 0.00 0.00 0.180397E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.312527E+09 0.00 0.00 0.00 0.276414E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.359406E+09 0.00 0.00 0.00 0.356885E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.312527E+09 0.00 0.00 0.00 0.188417E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.328153E+09 0.00 0.00 2711539.31 47490042.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.328153E+09 0.00 0.00 81507994.49 1111215.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.313784E+09 0.00 0.00 0.237499E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.395002E+10 0.00 0.00 0.101946E+10 0.118791E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.300557E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.359406E+09 0.00 0.00 0.360547E+09 0.356885E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130887E+10 0.00 0.00 0.00 0.00 0.330459E+09 0.00 0.00 0.18
February 0.129549E+10 0.00 0.00 20694.33 0.00 0.125934E+09 21581896.84 0.00 0.18
March 0.132231E+10 0.00 0.00 502710.09 0.00 6820701.17 0.335814E+09 0.00 0.19
April 0.695285E+09 12339.91 0.00 2211728.87 0.00 0.00 0.572142E+09 0.00 0.17
May 0.164099E+09 0.00 0.00 6393827.48 0.00 0.00 0.945056E+09 0.00 0.18
June 63539268.83 23336.31 0.00 7646720.51 5894.92 0.00 0.788088E+09 0.00 0.19
July 30017841.00 17094807.90 0.00 8605347.14 1540587.68 0.00 0.428593E+09 0.00 0.17
August 26691334.59 49698898.70 0.00 8063365.97 4122341.74 0.00 0.334842E+09 0.00 0.19
September 54531475.47 201340.64 0.00 6948321.02 0.00 0.00 0.637846E+09 0.00 0.17
October 0.312581E+09 0.00 0.00 3633489.02 0.00 0.00 0.970774E+09 0.00 0.18
November 0.112696E+10 0.00 0.00 818721.42 0.00 15852700.53 0.409503E+09 0.00 0.18
December 0.143910E+10 0.00 0.00 0.00 0.00 0.146188E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.783948E+10 67030723.47 0.00 44844925.85 5668824.34 0.625255E+09 0.544424E+10 0.00 0.18
Minimum of Months 26691334.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.143910E+10 49698898.70 0.00 8605347.14 4122341.74 0.330459E+09 0.970774E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.257161E+09 0.00 0.00 0.00 0.00 0.660314E+09 0.00 0.00 0.17
February 0.344854E+09 0.00 0.00 159433.39 0.00 0.387064E+09 63609159.93 0.00 0.18
March 0.566781E+09 0.00 0.00 504720.84 0.00 0.159891E+09 0.134766E+09 0.00 0.19
April 0.392766E+09 2451320.80 0.00 1096424.12 69800.04 86347331.63 0.172002E+09 0.00 0.17
May 0.276101E+09 1045402.76 0.00 2274725.30 35818.71 22855404.28 0.310930E+09 0.00 0.18
June 0.141719E+09 801942.85 0.00 3353527.84 179894.33 0.00 0.342837E+09 0.00 0.19
July 56277446.92 27095056.41 0.00 4643345.65 2401462.01 0.00 0.199246E+09 0.00 0.17
August 41993110.37 78840648.85 0.00 4431558.32 5598737.89 0.00 0.168590E+09 0.00 0.19
September 0.107706E+09 11127398.97 0.00 4708997.45 111494.23 496806.57 0.294867E+09 0.00 0.17
October 0.339839E+09 0.00 0.00 2725300.00 0.00 24221240.74 0.333955E+09 0.00 0.18
November 0.509176E+09 0.00 0.00 198649.31 0.00 0.225581E+09 0.101552E+09 0.00 0.18
December 0.384862E+09 0.00 0.00 62054.24 0.00 0.470637E+09 24960985.02 0.00 0.17
                   
Annual Sum or Average 0.341924E+10 0.121362E+09 0.00 24158736.45 8397207.22 0.203741E+10 0.214731E+10 0.00 0.18
Minimum of Months 41993110.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.566781E+09 78840648.85 0.00 4708997.45 5598737.89 0.660314E+09 0.342837E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 41992437.08 0.00 0.00 0.00 0.00 0.493792E+09 0.00 0.00 0.17
February 0.149034E+09 0.00 0.00 0.00 0.00 0.303791E+09 0.00 0.00 0.18
March 0.371370E+09 0.00 0.00 0.00 0.00 0.119504E+09 0.00 0.00 0.19
April 0.257368E+09 1576189.21 0.00 550158.82 37022.41 38163591.33 89506012.99 0.00 0.17
May 0.141016E+09 842250.98 0.00 1665067.16 84647.79 1303344.53 0.219292E+09 0.00 0.18
June 41211967.62 513603.79 0.00 3261494.62 95864.87 0.00 0.236457E+09 0.00 0.19
July 13730340.47 20568164.82 0.00 3374324.81 1753771.22 0.00 0.126125E+09 0.00 0.17
August 11667066.31 55293976.46 0.00 2958501.82 3702958.62 0.00 99474977.77 0.00 0.19
September 47581158.26 6345996.55 0.00 2475553.41 73184.42 0.00 0.190214E+09 0.00 0.17
October 0.260187E+09 0.00 0.00 773518.33 0.00 8023482.24 0.141751E+09 0.00 0.18
November 0.308017E+09 0.00 0.00 5355.26 0.00 0.169546E+09 5701724.80 0.00 0.18
December 0.126420E+09 0.00 0.00 0.00 0.00 0.380791E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.176959E+10 85140181.81 0.00 15063974.22 5747449.33 0.151491E+10 0.110852E+10 0.00 0.18
Minimum of Months 11667066.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.371370E+09 55293976.46 0.00 3374324.81 3702958.62 0.493792E+09 0.236457E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121970E+09 0.00 0.00 0.00 0.00 0.826658E+09 0.00 0.00 0.17
February 0.205771E+09 0.00 0.00 0.00 0.00 0.595136E+09 0.00 0.00 0.18
March 0.575989E+09 0.00 0.00 0.00 0.00 0.276535E+09 0.00 0.00 0.19
April 0.527573E+09 1095855.18 0.00 176036.58 23327.29 96370678.01 32911511.88 0.00 0.17
May 0.337175E+09 621389.68 0.00 1450856.35 64710.12 1649725.04 0.316206E+09 0.00 0.18
June 0.120658E+09 388666.18 0.00 3256807.20 125190.25 0.00 0.400483E+09 0.00 0.19
July 35722666.21 22365866.99 0.00 4279229.03 2665276.57 0.00 0.235771E+09 0.00 0.17
August 27593335.01 62303091.13 0.00 3785887.23 5681802.66 0.00 0.198251E+09 0.00 0.19
September 0.123772E+09 2639787.23 0.00 2549416.93 23401.35 0.00 0.328855E+09 0.00 0.17
October 0.558408E+09 0.00 0.00 495393.49 0.00 14937155.50 0.149851E+09 0.00 0.18
November 0.567078E+09 0.00 0.00 0.00 0.00 0.287119E+09 0.00 0.00 0.18
December 0.252160E+09 0.00 0.00 0.00 0.00 0.645388E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.345387E+10 89414656.39 0.00 15993626.81 8583708.24 0.274379E+10 0.166233E+10 0.00 0.18
Minimum of Months 27593335.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.575989E+09 62303091.13 0.00 4279229.03 5681802.66 0.826658E+09 0.400483E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 84283505.77 0.00 0.00 0.00 0.00 0.474236E+09 0.00 0.00 0.17
February 0.166481E+09 0.00 0.00 429.64 0.00 0.310149E+09 620355.26 0.00 0.18
March 0.375250E+09 0.00 0.00 52672.48 0.00 0.128381E+09 16280618.99 0.00 0.19
April 0.288182E+09 1177415.22 0.00 400038.48 31212.81 40886837.51 73445273.10 0.00 0.17
May 0.144737E+09 659377.58 0.00 1600451.91 68744.80 0.00 0.241458E+09 0.00 0.18
June 53566088.39 533054.49 0.00 2556623.58 64944.08 0.00 0.249401E+09 0.00 0.19
July 13893283.90 17698873.93 0.00 3195853.95 1439980.73 0.00 0.137258E+09 0.00 0.17
August 11677843.83 45482090.37 0.00 2680016.02 3094123.32 0.00 0.110673E+09 0.00 0.19
September 47481661.97 4402069.71 0.00 2200274.32 121436.72 0.00 0.206471E+09 0.00 0.17
October 0.263459E+09 0.00 0.00 773762.84 0.00 6700233.41 0.168633E+09 0.00 0.18
November 0.320138E+09 0.00 0.00 25021.48 0.00 0.159836E+09 31501412.94 0.00 0.18
December 0.174010E+09 0.00 0.00 0.00 0.00 0.356335E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.194316E+10 69952881.30 0.00 13485144.70 4820442.46 0.147652E+10 0.123574E+10 0.00 0.18
Minimum of Months 11677843.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.375250E+09 45482090.37 0.00 3195853.95 3094123.32 0.474236E+09 0.249401E+09 0.00 0.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:03

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.595195E+10 0.126118E+10 0.00 0.459974E+10 -0.325505E+10
February 0.238415E+11 0.179868E+10 0.00 0.396969E+10 -0.170819E+10
March 0.513217E+11 0.278954E+10 0.00 0.439076E+10 -560088876.5
April 0.895845E+11 0.394598E+10 0.00 0.336091E+10 0.107725E+10
May 0.123410E+12 0.494129E+10 0.00 0.313184E+10 0.381670E+10
June 0.126754E+12 0.489716E+10 0.00 0.245530E+10 0.674095E+10
July 0.135358E+12 0.485602E+10 0.00 0.118611E+10 0.978776E+10
August 0.103377E+12 0.353804E+10 0.00 0.739556E+09 0.133226E+11
September 0.684091E+11 0.220243E+10 0.00 0.203366E+10 0.744955E+10
October 0.372731E+11 0.193086E+10 0.00 0.356172E+10 0.240463E+10
November 0.103574E+11 0.130772E+10 0.00 0.423861E+10 -528943472.1
December 0.193009E+10 0.634469E+09 0.00 0.440092E+10 -0.195958E+10
           
Annual Sum or Average 0.777569E+12 0.341034E+11 0.00 0.380688E+11 0.365875E+11
Minimum of Months 0.193009E+10 0.634469E+09 0.00 0.739556E+09 -0.325505E+10
Maximum of Months 0.135358E+12 0.494129E+10 0.00 0.459974E+10 0.133226E+11